D20 Control Output Module
D20 Control Output Module
Digital Energy
D20 Control
Output Module
Overview
The D20 Control module is composed of two detachable modules, WESTERM D20 K and WESDAC D20 K.
The top module, WESDAC D20 K, processes the data acquired and communicates this to the main D20
processor, see Figure 2.
The bottom module, WESTERM D20 K, is composed of terminal blocks where field wirings are terminated.
The WESTERM D20 K termination board handles all connections to and from the WESDAC D20 K module.
These connections are:
The D.20 network ports
The 9600 baud RS232 maintenance port
The WESDAC D20 K module address
The relay outputs
imagination at work
Ease of Use
To first time users, both the software
configuration setup and hardware
installations are trivial; this makes it simple to
install and maintain the control module
SCADA Masters
The D20 Remote Terminal Unit (RTU) design is based on a distributedprocessing architecture including the real-time data acquisition and control
software. These I/O modules can be located close to the primary equipment
being monitored and controlled as they receive and send data back to the
master D20 main processor.
The I/O modules are intelligent modules that contain on-board
microprocessors and are configured as slave devices to the D20 main
processor. In the figure 1 pictorial setup, specific I/O processing is distributed
throughout the D20 RTU to the appropriate I/O modules.
The I/O modules support two communication protocols: (1) DNP 3 protocol,
and (2) high speed, high-level data link controller (D.20 Link) in the form of
poll and response messages protocol. The peripheral modules have serial
communication ports and various types of field connections.
The hardware construction of each remote I/O module type is similar (see
Figure 2.)
Acrylic Display
Cover
WESDAC
Logic Panel
WESTERM
Terminal Panel
Terminal Blocks
GEDigitalEnergy.com
Control Output
Configurations/Applications
The D20K can have one of the following control output configurations:
32 Trip/Close pairs
24 Trip/Close and 4 Raise/Lower pairs
Interposing Relays
The hardware and software can also be configured to provide a wide range
of control output schemes, including parallel, pulse duration, pulse trains
and latched-output applications.
The control output duration is software-adjustable from 1 to 215 ms in onemillisecond increments, and on a per-point basis (protocol dependent). The
D20K software also supports discrete timed/latch relay functionality.
Termination Panel
Termination Types
D20 Control output module can be ordered with the following field
termination options:
Compression
Field wiring is terminated directly onto board-mounted screw terminal
compression blocks (#12 AWG [2.05mm] max, blade screwdriver - 0.6 x
3.5 x 100 mm) on the D20 I/O Peripheral
DB25
Field wiring is terminated onto the D20 I/O peripheral through DB25
connectors
To Field Equipment
Figure 3: Interposing Relays
Compression Disconnect
Field wiring is terminated onto plug-on terminator blocks (#12 AWG
[2.05mm] max, blade screwdriver - 0.6 x 3.5 x 100 mm), which then mate
with board-mounted headers on the D20 I/O Peripheral.
GEDigitalEnergy.com
Technical Specifications
Table 1: D20K Specifications
ITEM
DESCRIPTION
ITEM
DESCRIPTION
Processor
Every 500 s
Clock
Contact Duration
Memory
32 KB EPROM
24 KB static RAM
512 bytes EEPROM
Programmable 1 to 215 ms in 1 ms
intervals (protocol dependent)
Switches
1500 Vrms
Control Outputs
Dielectric Rating
1000 VDC
Maintenance Port
Power Requirements
Size
Output Types
Momentary (fixed)
Latching
Trip/Close (T/C)
Raise/Lower (R/L)
Pulse duration
Pulse train
32 T/C pairs
24 T/C + 4 R/L pairs
16 R/L pairs
32 isolated Form-C contact outputs
Optional 32 isolated open-drain
outputs, rated 150 mA @ 60VDC
LED Indicators
GEDigitalEnergy.com
Common LEDs
Local (GREEN) LED, which turns on
when the I/O module is set to Local
module using the Local/Remote switch,
or if the modules control software has
been disabled.
Remote (RED), which turns on when the
module is in Remote mode.
Control points (RED), which turn on
when the particular control point is
enabled.
Ordering
D20K System Components
Please note
1. For the rules regarding the combination of various options to build an
order code, visit the online web:
http://store.gedigitalenergy.com/ViewProd.asp?Model=D20K
3. The order defined in the ordering guide may not be final and can only be
accepted once GE has reviewed and accepted the order. This document is
only meant as a guide and by no means will portray the final order.
2. This ordering guide should ONLY be used with reference to the product
documentation and it is assumed the user has read those documents.
The ordering guide is for the use of experienced users who have extensive
knowledge in the area and the products.
D20K -
D20K Termination
1
F
2
3
G
5
K
H
J
D20 PCommon
D.20 Cable
D.20 Terminator
D.20 Duct Panel
Description
Equivalent Legacy #
517-0164
517-0164-CC
517-0143
517-0218
517-0218-CC
517-0242
517-0242-CC
517-0220
517-0235
U
A
U
1
2
3
4
5
6
7
8
U
1
2
3
4
5
6
7
8
U
1
U
1
2
3
4
5
6
GEDigitalEnergy.com
3. The order defined in the ordering guide may not be final and can only be
accepted once GE has reviewed and accepted the order. This document is
only meant as a guide and by no means will portray the final order.
2. This ordering guide should ONLY be used with reference to the product
documentation and it is assumed the user has read those documents.
The ordering guide is for the use of experienced users who have extensive
knowledge in the area and the products
D20K -
Module Type
T
D
3
Termination Type
Environmental Protection
D.20 Link
PCOMMON
Description
U
A
WESTERM Module
WESDAC Module
DNP 3 I/O Module
None (Need ONLY RNET Voltage Adapter Packs)
High Voltage (40-150VDC)
Low Voltage (20-60 VDC or D.20 Link Power)
None
DB25 Termination Type
Compression Termination Type
Compression/Disconnect Terminatiion Type
None
Conformal Coat
Epoxy-Conformal Coat
None
WESTERM allows for D.20 Link and Dual PS Input
WESTERM allows for Wire Wrap Adaptor Connection
None
WESTERM Redundant D.20 Link & Dual Power Supply Option (540-0313)
WESDAC Redundant D.20 Link & Dual Power Supply Option (540-0207)
Standard D.20 Link [ For Module type T, or D] (540-0162)
None
PCommon 212 (SBA0001/00)
PCommon 213 (SBA0003/00)
PCommon 220 (SBA0004/00)
PCommon 221 (SBA0007/00)
PCommon 300 (SBA0005/00)
PCommon 301 (SBA0006/00)
PCommon 305 (SBA0009/00)
PCOMMON 306 (P010-0 VER.306)
None
Trip/Close Configuration
Raise/Lower Configuration
None
WESTERM D20K Wire Wrap Adapter [517-0228]
U
H
L
U
D
P
X
U
C
E
U
R
W
U
R
L
S
U
1
2
3
4
5
6
7
8
U
A
B
GEDigitalEnergy.com
(D20K-TL-X-CU) - D20KX LV (20-60VDC or D.20 Power), Compression Disconnect Termination, Conformal Coated
(D20K-TH-P-EU) - D20K4Z HV (40-150VDC or D.20 Power), Compression Termination, Epoxy Conformal Coated
(D20K-TL-D-UW) - D20KR TYPE 2 LV (20-60VDC or D.20 Power), DB25 Termination with Wire-Wrap adapter option
(D20K-TL-D-UR) - D20 OKR LV (20-60VDC or D.20 input), Compression Termination, redundant D.20 and PS Input
Note: The cross reference tab attempts to compare the old part numbers to the new smart catalogue numbers. The new smart catalogue numbers represented
are the prefix or base line for the complete catalogue number. For the complete catalogue number, and to determine the selections for the various sub
components, visit: http://store.gedigitalenergy.com/ViewProd.asp?Model=D20K+Spare+Parts+
See figure 9 for examples of sub components specific to a user: D20K Special options, D.20 Link options, D20 PCOMMON options, DNP3 control output
configuration, D20K Wire Wrap Adapter.
GEDigitalEnergy.com
GE Digital Energy
650 Markland St.
Markham, ON
Canada L6C 0M1
+1 877-605-6777 (toll free in North America)
+1 678-844-6777 (direct number)
[email protected]
GEDigitalEnergy.com
imagination at work
GE Digital Energy reserves the right to make changes to specifications of products described at any
time without notice and without obligation to notify any person of such changes.
GEA-12711A(E)
English
140627