50% found this document useful (2 votes)
132 views30 pages

Powerwiz Gep400

The document contains configuration parameters for an engine controller including sensor thresholds, shutdown settings, and input/output configurations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
50% found this document useful (2 votes)
132 views30 pages

Powerwiz Gep400

The document contains configuration parameters for an engine controller including sensor thresholds, shutdown settings, and input/output configurations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 30

1 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

EST-OLYMPIAN 2012B v1.0


Configuration
5/20/2013 12:28 PM

PowerWizard 1.0
Parameter
ECM Part Number
ECM Serial Number
Software Group Part Number
Software Group Release Date
Software Group Description

Value
3007649-03
3131B153UA
3927441-00
MAR2011
L0 9_0 Standard -- English, 2.2.3 Prod, 14December2011

Description
Automatic Start/Stop
Engine Start Fault Protection Activation Delay Time
Crank Duration
Crank Cycle Rest Interval
Purge Cycle Duration
Maximum Number of Crank Cycles
Cooldown Duration
Start Aid Activation Time
Crank Alert Activation Time
Crank Terminate RPM
Engine Fuel Type Configuration
Fuel Shutoff Solenoid Type Configuration
Engine Type Configuration
Engine Controller J1939 Data Link Support Configuration
Engine Cooldown Speed Configuration
Engine Operating State Input Configuration
Fuel Priming Feature Enable Status
Engine Forced Idle Feature Enable Status
AVR Desired Voltage Request
Maximum Generator Voltage Output Bias Percentage
Generator Nominal Output Voltage
Battery Voltage Monitor
High Battery Voltage Warning Event Threshold

Value

TT

30 sec
7 sec
7 sec
0 sec
3
3 min
0 sec
0 sec
400 rpm
Diesel
Energized to Run
Electronic
Basic J1939 Support
Rated Speed
Hardwired Input
Disabled
Disabled
5%
400 Volts
30.0 Volts

5/20/2013 3:04 PM

2 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

High Battery Voltage Warning Event Notification Delay Time


High Battery Voltage Shutdown Event Threshold
High Battery Voltage Shutdown Event Notification Delay Time
Low Battery Voltage Warning Event Threshold
Low Battery Voltage Warning Event Notification Delay Time
Low Battery Charging System Voltage Warning Event
Threshold
Low Battery Charging System Voltage Warning Event
Notification Delay Time
Low Cranking Voltage Warning Event Threshold
Low Cranking Voltage Warning Event Notification Delay Time
Digital Inputs
Digital Input #1 Active State Configuration
Digital Input #2 Active State Configuration
Digital Input #3 Active State Configuration
Digital Input #4 Active State Configuration
Digital Input #5 Active State Configuration
Digital Input #6 Active State Configuration
Digital Selectors
Digital Selector #1 Source Configuration
Digital Selector #2 Source Configuration
Digital Selector #3 Source Configuration
Digital Selector #4 Source Configuration
Digital Selector #5 Source Configuration
Digital Selector #6 Source Configuration
Digital Selector #7 Source Configuration
Digital Selector #8 Source Configuration
Digital Selector #9 Source Configuration
Digital Selector #10 Source Configuration
Engine Coolant Temperature Monitor
Engine Coolant Temperature Sensor Configuration
High Engine Coolant Temperature Warning Event Threshold
High Engine Coolant Temperature Warning Event Notification
Delay Time
High Engine Coolant Temperature Shutdown Event Threshold
High Engine Coolant Temperature Shutdown Event Notification
Delay Time
Low Engine Coolant Temperature Warning Event Threshold
Low Engine Coolant Temperature Warning Event Notification
Delay Time
Engine Coolant Temperature Sensor Configuration Code
Engine Oil Pressure Monitor

30 sec
30.0 Volts
30 sec
23.4 Volts
30 sec
25.0 Volts
30 sec
0.0 Volts
2 sec
Low
Low
Low
Low
Low
Low
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled

or
or
or
or
or
or

Not
Not
Not
Not
Not
Not

Installed
Installed
Installed
Installed
Installed
Installed

Data Link
203 Deg F
15 sec
225 Deg F
5 sec
34 Deg F
10 sec
Map #1

5/20/2013 3:04 PM

3 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Engine Oil Pressure Sensor Configuration


Low Engine Oil Pressure Warning Event Threshold
Low Idle Low Engine Oil Pressure Warning Event Threshold
Low Engine Oil Pressure Warning Event Notification Delay
Time
Low Engine Oil Pressure Shutdown Event Threshold
Low Idle Low Engine Oil Pressure Shutdown Event Threshold
Low Engine Oil Pressure Shutdown Event Notification Delay
Time
Low Engine Oil Pressure Step Speed
Engine Oil Pressure Sensor Configuration Code
Engine Speed Monitor
Flywheel Teeth
Engine Overspeed Setpoint
Engine Underspeed Warning Event Threshold
Engine Underspeed Warning Event Notification Delay Time
Engine Underspeed Shutdown Event Threshold
Engine Underspeed Shutdown Event Notification Delay Time
Engine Speed Sensor Configuration
Event Input Functions
Event Input Function #1 Suspect Parameter Number
Event Input Function #1 Failure Mode Identifier
Event Input Function #1 Event Notification Delay Time
Event Input Function #1 Active State Configuration
Event Input Function #2 Suspect Parameter Number
Event Input Function #2 Failure Mode Identifier
Event Input Function #2 Event Notification Delay Time
Event Input Function #2 Active State Configuration
Event Input Function #3 Suspect Parameter Number
Event Input Function #3 Failure Mode Identifier
Event Input Function #3 Event Notification Delay Time
Event Input Function #3 Active State Configuration
Event Input Function #4 Suspect Parameter Number
Event Input Function #4 Failure Mode Identifier
Event Input Function #4 Event Notification Delay Time
Event Input Function #4 Active State Configuration
Event Input Function #5 Suspect Parameter Number
Event Input Function #5 Failure Mode Identifier
Event Input Function #5 Event Notification Delay Time
Event Input Function #5 Active State Configuration
Event Input Function #6 Suspect Parameter Number
Event Input Function #6 Failure Mode Identifier

Data Link
29 psi
23 psi
10 sec
15 psi
15 psi
10 sec
1350 rpm
Map #1
113
1700 rpm
1350 rpm
2.0 sec
1250 rpm
2.0 sec
Sensor
Custom Event
High Warning
0 sec
High
Custom Event
High Warning
0 sec
High
Custom Event
High Warning
0 sec
High
Custom Event
High Warning
0 sec
High
Disabled or Not
Disabled or Not
Disabled or Not
Disabled or Not
Disabled or Not
Disabled or Not

Installed
Installed
Installed
Installed
Installed
Installed

5/20/2013 3:04 PM

4 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Event Input Function #6 Event Notification Delay Time


Event Input Function #6 Active State Configuration
Event Output Functions
Event Output Function #1 Suspect Parameter Number
Event Output Function #1 Trigger Condition
Event Output Function #2 Suspect Parameter Number
Event Output Function #2 Trigger Condition
Event Output Function #3 Suspect Parameter Number
Event Output Function #3 Trigger Condition
Event Output Function #4 Suspect Parameter Number
Event Output Function #4 Trigger Condition
Event Output Function #5 Suspect Parameter Number
Event Output Function #5 Trigger Condition
Event Output Function #6 Suspect Parameter Number
Event Output Function #6 Trigger Condition
Event Output Function #7 Suspect Parameter Number
Event Output Function #7 Trigger Condition
Event Output Function #8 Suspect Parameter Number
Event Output Function #8 Trigger Condition
Event Response Configuration - Diagnostic Events
Air Filter Differential Pressure Sensor Diagnostic Response
Configuration
Air Filter Differential Pressure Sensor Diagnostic Audible Alert
Air Filter Differential Pressure Sensor Diagnostic Breaker #1
Trip
Air Filter Differential Pressure Sensor Diagnostic Breaker #2
Trip
Ambient Air Temperature Sensor Diagnostic Response
Configuration
Ambient Air Temperature Sensor Diagnostic Audible Alert
Ambient Air Temperature Sensor Diagnostic Breaker #1 Trip
Ambient Air Temperature Sensor Diagnostic Breaker #2 Trip
Engine Coolant Level Sensor Diagnostic Response
Configuration
Engine Coolant Level Sensor Diagnostic Audible Alert
Engine Coolant Level Sensor Diagnostic Breaker #1 Trip
Engine Coolant Level Sensor Diagnostic Breaker #2 Trip
Engine Coolant Temperature Sensor Diagnostic Response
Configuration
Engine Coolant Temperature Sensor Diagnostic Audible Alert
Engine Coolant Temperature Sensor Diagnostic Breaker #1
Trip

Disabled or Not Installed


Disabled or Not Installed
Engine Oil Pressure
**Disabled
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Activate Warning Condition
No
No
No
Activate Warning Condition
No
No
No
Activate Warning Condition
No
No
No
Activate Warning Condition
No
No

5/20/2013 3:04 PM

5 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Engine Coolant Temperature Sensor Diagnostic Breaker #2


Trip
Engine Oil Level Sensor Diagnostic Response Configuration
Engine Oil Level Sensor Diagnostic Audible Alert
Engine Oil Level Sensor Diagnostic Breaker #1 Trip
Engine Oil Level Sensor Diagnostic Breaker #2 Trip
Engine Oil Pressure Sensor Diagnostic Response Configuration
Engine Oil Pressure Sensor Diagnostic Audible Alert
Engine Oil Pressure Sensor Diagnostic Breaker #1 Trip
Engine Oil Pressure Sensor Diagnostic Breaker #2 Trip
Engine Oil Temperature Sensor Diagnostic Response
Configuration
Engine Oil Temperature Sensor Diagnostic Audible Alert
Engine Oil Temperature Sensor Diagnostic Breaker #1 Trip
Engine Oil Temperature Sensor Diagnostic Breaker #2 Trip
Engine Speed Sensor Diagnostic Response Configuration

No
Activate Warning Condition
No
No
No
Activate Warning Condition
No
No
No
Activate Warning Condition
No
No
No
Activate Hard Shutdown
Condition
Yes
No
No

Engine Speed Sensor Diagnostic Audible Alert


Engine Speed Sensor Diagnostic Breaker #1 Trip
Engine Speed Sensor Diagnostic Breaker #2 Trip
Exhaust Temperature Sensor Diagnostic Response
Activate
Configuration
Exhaust Temperature Sensor Diagnostic Audible Alert
No
Exhaust Temperature Sensor Diagnostic Breaker #1 Trip
No
Exhaust Temperature Sensor Diagnostic Breaker #2 Trip
No
Right Exhaust Temperature Sensor Diagnostic Response
Activate
Configuration
Right Exhaust Temperature Sensor Diagnostic Audible Alert
No
Right Exhaust Temperature Sensor Diagnostic Breaker #1 Trip No
Right Exhaust Temperature Sensor Diagnostic Breaker #2 Trip No
Left Exhaust Temperature Sensor Diagnostic Response
Activate
Configuration
Left Exhaust Temperature Sensor Diagnostic Audible Alert
No
Left Exhaust Temperature Sensor Diagnostic Breaker #1 Trip No
Left Exhaust Temperature Sensor Diagnostic Breaker #2 Trip No
Fire Extinguisher Pressure Sensor Diagnostic Response
Activate
Configuration
Fire Extinguisher Pressure Sensor Audible Alert
No
Fire Extinguisher Pressure Sensor Breaker #1 Trip
No
Fire Extinguisher Pressure Sensor Breaker #2 Trip
No
Fuel Filter Differential Pressure Sensor Diagnostic Response
Activate
Configuration
Fuel Filter Differential Pressure Sensor Diagnostic Audible Alert No

Warning Condition

Warning Condition

Warning Condition

Warning Condition

Warning Condition

5/20/2013 3:04 PM

6 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Fuel Filter Differential Pressure Sensor Diagnostic Breaker #1


Trip
Fuel Filter Differential Pressure Sensor Diagnostic Breaker #2
Trip
Fuel Level Sensor Diagnostic Response Configuration
Fuel Level Sensor Diagnostic Audible Alert
Fuel Level Sensor Diagnostic Breaker #1 Trip
Fuel Level Sensor Diagnostic Breaker #2 Trip
External Tank Fuel Level Sensor Diagnostic Response
Configuration
External Tank Fuel Level Sensor Diagnostic Audible Alert
External Tank Fuel Level Sensor Diagnostic Breaker #1 Trip
External Tank Fuel Level Sensor Diagnostic Breaker #2 Trip
Generator Bearing #1 Temperature Sensor Diagnostic
Response Configuration
Generator Bearing #1 Temperature Sensor Diagnostic Audible
Alert
Generator Bearing #1 Temperature Sensor Diagnostic Breaker
#1 Trip
Generator Bearing #1 Temperature Sensor Diagnostic Breaker
#2 Trip
Generator Output Sensing System Diagnostic Response
Configuration
Generator Output Sensing System Diagnostic Audible Alert
Generator Output Sensing System Diagnostic Breaker #1 Trip
Generator Output Sensing System Diagnostic Breaker #2 Trip
Engine Oil Filter Differential Pressure Sensor Diagnostic
Response Config
Engine Oil Filter Differential Pressure Sensor Diagnostic
Audible Alert
Engine Oil Filter Differential Pressure Sensor Diagnostic
Breaker #1 Trip
Engine Oil Filter Differential Pressure Sensor Diagnostic
Breaker #2 Trip
Primary Data Link Diagnostic Response Configuration
Primary Data Link Diagnostic Audible Alert
Primary Data Link Diagnostic Breaker #1 Trip
Primary Data Link Diagnostic Breaker #2 Trip
Starting Air Pressure Sensor Diagnostic Response
Configuration
Starting Air Pressure Sensor Diagnostic Audible Alert
Starting Air Pressure Sensor Diagnostic Breaker #1 Trip
Starting Air Pressure Sensor Diagnostic Breaker #2 Trip

No
No
Activate Warning Condition
No
No
No
Activate Warning Condition
No
No
No
Activate Warning Condition
No
No
No
Activate Warning Condition
Yes
No
No
Activate Warning Condition
No
No
No
Activate Warning Condition
No
No
No
Activate Warning Condition
No
No
No

5/20/2013 3:04 PM

7 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Battery Charger Failure Diagnostic Response Configuration


Battery Charger Failure Diagnostic Audible Alert
Engine Controller Not Responding Diagnostic Response
Configuration
Engine Controller Not Responding Diagnostic Audible Alert
Engine Controller Not Responding Diagnostic Breaker #1 Trip
Engine Controller Not Responding Diagnostic Breaker #2 Trip
Event Response Configuration - Engine Protection
Events
Air Damper Closed Event Response Configuration
Air Damper Closed Event Audible Alert
High Air Filter Differential Pressure Warning Event Response
Configuration
High Air Filter Differential Pressure Warning Event Audible
Alert
High Air Filter Differential Pressure Warning Event Breaker #1
Trip
High Air Filter Differential Pressure Warning Event Breaker #2
Trip
High Air Filter Differential Pressure Shutdown Event Response
Configuration
High Air Filter Differential Pressure Shutdown Event Audible
Alert
High Air Filter Differential Pressure Shutdown Event Breaker
#1 Trip
High Air Filter Differential Pressure Shutdown Event Breaker
#2 Trip
Low Air Filter Differential Pressure Warning Event Response
Configuration
Low Air Filter Differential Pressure Warning Event Audible
Alert
Low Air Filter Differential Pressure Warning Event Breaker #1
Trip
Low Air Filter Differential Pressure Warning Event Breaker #2
Trip
Low Air Filter Differential Pressure Warning Event Fault
Protection Timer
Low Air Filter Differential Pressure Shutdown Event Response
Configuration
Low Air Filter Differential Pressure Shutdown Event Audible
Alert
Low Air Filter Differential Pressure Shutdown Event Breaker
#1 Trip

Activate Warning Condition


Yes
Activate Warning Condition
No
No
No

Hard Shutdown & Active Only


Condition
Yes
Activate Warning Condition
Yes
No
No
Activate Hard Shutdown
Condition
Yes
No
No
Activate Warning Condition
Yes
No
No
Yes
Activate Hard Shutdown
Condition
Yes
No

5/20/2013 3:04 PM

8 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Low Air Filter Differential Pressure Shutdown Event Breaker


#2 Trip
Low Air Filter Differential Pressure Shutdown Event Fault
Protection Timer
Emergency Stop Activated Event Response Configuration
Emergency Stop Activated Event Audible Alert
Emergency Stop Activated Event Breaker #1 Trip
Emergency Stop Activated Event Breaker #2 Trip
High Engine Coolant Level Warning Event Response
Configuration
High Engine Coolant Level Warning Event Audible Alert
High Engine Coolant Level Warning Event Breaker #1 Trip
High Engine Coolant Level Warning Event Breaker #2 Trip
High Engine Coolant Level Shutdown Event Response
Configuration
High Engine Coolant Level Shutdown Event Audible Alert
High Engine Coolant Level Shutdown Event Breaker #1 Trip
High Engine Coolant Level Shutdown Event Breaker #2 Trip
Low Engine Coolant Level Warning Event Response
Configuration
Low Engine Coolant Level Warning Event Audible Alert
Low Engine Coolant Level Warning Event Breaker #1 Trip
Low Engine Coolant Level Warning Event Breaker #2 Trip
Low Engine Coolant Level Shutdown Event Response
Configuration
Low Engine Coolant Level Shutdown Event Audible Alert
Low Engine Coolant Level Shutdown Event Breaker #1 Trip
Low Engine Coolant Level Shutdown Event Breaker #2 Trip
High Engine Coolant Temperature Warning Event Response
Configuration
High Engine Coolant Temperature Warning Event Audible Alert
High Engine Coolant Temperature Warning Event Breaker #1
Trip
High Engine Coolant Temperature Warning Event Breaker #2
Trip
High Engine Coolant Temperature Warning Event Fault
Protection Timer
High Engine Coolant Temperature Shutdown Event Response
Configuration
High Engine Coolant Temperature Shutdown Event Audible
Alert
High Engine Coolant Temperature Shutdown Event Breaker #1
Trip

No
Yes
Activate Hard Shutdown
Condition
Yes
No
No
Activate Warning Condition
Yes
No
No
Activate Hard Shutdown
Condition
Yes
No
No
Activate Warning Condition
Yes
No
No
Activate Hard Shutdown
Condition
Yes
No
No
Activate Warning Condition
Yes
No
No
Yes
Activate Hard Shutdown
Condition
Yes
No

5/20/2013 3:04 PM

9 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

High Engine Coolant Temperature Shutdown Event Breaker #2


Trip
High Engine Coolant Temperature Shutdown Event Fault
Protection Timer
Low Engine Coolant Temperature Warning Event Response
Configuration
Low Engine Coolant Temperature Warning Event Audible Alert
Low Engine Coolant Temperature Warning Event Breaker #1
Trip
Low Engine Coolant Temperature Warning Event Breaker #2
Trip
Low Engine Coolant Temperature Warning Event Fault
Protection Timer
Engine Failure To Start Shutdown Event Response
Configuration
Engine Failure To Start Shutdown Event Audible Alert
Engine Failure To Start Shutdown Event Breaker #1 Trip
Engine Failure To Start Shutdown Event Breaker #2 Trip
High Engine Oil Level Warning Event Response Configuration
High Engine Oil Level Warning Event Audible Alert
High Engine Oil Level Warning Event Breaker #1 Trip
High Engine Oil Level Warning Event Breaker #2 Trip

No
Yes
Disable Condition
No
No
No
No

Activate Hard Shutdown


Condition
Yes
No
No
Activate Warning Condition
Yes
No
No
Activate Hard Shutdown
High Engine Oil Level Shutdown Event Response Configuration
Condition
High Engine Oil Level Shutdown Event Audible Alert
Yes
High Engine Oil Level Shutdown Event Breaker #1 Trip
No
High Engine Oil Level Shutdown Event Breaker #2 Trip
No
Low Engine Oil Level Warning Event Response Configuration Activate Warning Condition
Low Engine Oil Level Warning Event Audible Alert
Yes
Low Engine Oil Level Warning Event Breaker #1 Trip
No
Low Engine Oil Level Warning Event Breaker #2 Trip
No
Activate Hard Shutdown
Low Engine Oil Level Shutdown Event Response Configuration
Condition
Low Engine Oil Level Shutdown Event Audible Alert
Yes
Low Engine Oil Level Shutdown Event Breaker #1 Trip
No
Low Engine Oil Level Shutdown Event Breaker #2 Trip
No
Low Engine Oil Pressure Warning Event Response
Activate Warning Condition
Configuration
Low Engine Oil Pressure Warning Event Audible Alert
Yes
Low Engine Oil Pressure Warning Event Breaker #1 Trip
No
Low Engine Oil Pressure Warning Event Breaker #2 Trip
No
Low Engine Oil Pressure Warning Event Fault Protection Timer Yes

5/20/2013 3:04 PM

10 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Low Engine Oil Pressure Shutdown Event Response


Configuration
Low Engine Oil Pressure Shutdown Event Audible Alert
Low Engine Oil Pressure Shutdown Event Breaker #1 Trip
Low Engine Oil Pressure Shutdown Event Breaker #2 Trip
Low Engine Oil Pressure Shutdown Event Fault Protection
Timer
High Engine Oil Temperature Warning Event Response
Configuration
High Engine Oil Temperature Warning Event Audible Alert
High Engine Oil Temperature Warning Event Breaker #1 Trip
High Engine Oil Temperature Warning Event Breaker #2 Trip
High Engine Oil Temperature Warning Event Fault Protection
Timer
High Engine Oil Temperature Shutdown Event Response
Configuration
High Engine Oil Temperature Shutdown Event Audible Alert
High Engine Oil Temperature Shutdown Event Breaker #1 Trip
High Engine Oil Temperature Shutdown Event Breaker #2 Trip
High Engine Oil Temperature Shutdown Event Fault Protection
Timer
Low Engine Oil Temperature Warning Event Response
Configuration
Low Engine Oil Temperature Warning Event Audible Alert
Low Engine Oil Temperature Warning Event Breaker #1 Trip
Low Engine Oil Temperature Warning Event Breaker #2 Trip
Low Engine Oil Temperature Warning Event Fault Protection
Timer
Low Engine Oil Temperature Shutdown Event Response
Configuration
Low Engine Oil Temperature Shutdown Event Audible Alert
Low Engine Oil Temperature Shutdown Event Breaker #1 Trip
Low Engine Oil Temperature Shutdown Event Breaker #2 Trip
Low Engine Oil Temperature Shutdown Event Fault Protection
Timer
Unexpected Engine Shutdown Event Response Configuration
Unexpected Engine Shutdown Event Audible Alert
Unexpected Engine Shutdown Event Breaker #1 Trip
Unexpected Engine Shutdown Event Breaker #2 Trip
Engine Overspeed Shutdown Event Response Configuration
Engine Overspeed Shutdown Event Audible Alert

Activate Hard Shutdown


Condition
Yes
No
No
Yes
Activate Warning Condition
Yes
No
No
No
Activate Hard Shutdown
Condition
Yes
No
No
No
Activate Warning Condition
Yes
No
No
Yes
Disable Condition
No
No
No
No
Activate Hard Shutdown
Condition
Yes
No
No
Activate Hard Shutdown
Condition
Yes

5/20/2013 3:04 PM

11 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Engine
Engine
Engine
Engine
Engine
Engine
Engine

Overspeed Shutdown Event Breaker #1 Trip


Overspeed Shutdown Event Breaker #2 Trip
Underspeed Warning Event Response Configuration
Underspeed Warning Event Audible Alert
Underspeed Warning Event Breaker #1 Trip
Underspeed Warning Event Breaker #2 Trip
Underspeed Warning Event Fault Protection Timer

Engine Underspeed Shutdown Event Response Configuration


Engine Underspeed Shutdown Event Audible Alert
Engine Underspeed Shutdown Event Breaker #1 Trip
Engine Underspeed Shutdown Event Breaker #2 Trip
Engine Underspeed Shutdown Event Fault Protection Timer
High Exhaust Temperature Warning Event Response
Configuration
High Exhaust Temperature Warning Event Audible Alert
High Exhaust Temperature Warning Event Breaker #1 Trip
High Exhaust Temperature Warning Event Breaker #2 Trip
High Exhaust Temperature Warning Event Fault Protection
Timer
High Exhaust Temperature Shutdown Event Response
Configuration
High Exhaust Temperature Shutdown Event Audible Alert
High Exhaust Temperature Shutdown Event Breaker #1 Trip
High Exhaust Temperature Shutdown Event Breaker #2 Trip
High Exhaust Temperature Shutdown Event Fault Protection
Timer
Low Exhaust Temperature Warning Event Response
Configuration
Low Exhaust Temperature Warning Event Audible Alert
Low Exhaust Temperature Warning Event Breaker #1 Trip
Low Exhaust Temperature Warning Event Breaker #2 Trip
Low Exhaust Temperature Warning Event Fault Protection
Timer
Low Exhaust Temperature Shutdown Event Response
Configuration
Low Exhaust Temperature Shutdown Event Audible Alert
Low Exhaust Temperature Shutdown Event Breaker #1 Trip
Low Exhaust Temperature Shutdown Event Breaker #2 Trip
Low Exhaust Temperature Shutdown Event Fault Protection
Timer
High Right Exhaust Temperature Warning Event Response
Configuration

No
No
Activate Warning Condition
Yes
No
No
Yes
Activate Hard Shutdown
Condition
Yes
No
No
Yes
Activate Warning Condition
Yes
No
No
No
Activate Hard Shutdown
Condition
Yes
No
No
No
Activate Warning Condition
Yes
No
No
Yes
Disable Condition
No
No
No
No
Activate Warning Condition

5/20/2013 3:04 PM

12 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

High Right Exhaust Temperature Warning Event Audible Alert Yes


High Right Exhaust Temperature Warning Event Breaker #1
No
Trip
High Right Exhaust Temperature Warning Event Breaker #2
No
Trip
High Right Exhaust Temperature Warning Event Fault
No
Protection Timer
High Right Exhaust Temperature Shutdown Event Response
Activate Hard Shutdown
Configuration
Condition
High Right Exhaust Temperature Shutdown Event Audible Alert Yes
High Right Exhaust Temperature Shutdown Event Breaker #1
No
Trip
High Right Exhaust Temperature Shutdown Event Breaker #2
No
Trip
High Right Exhaust Temperature Shutdown Event Fault
No
Protection Timer
Low Right Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Right Exhaust Temperature Warning Event Audible Alert Yes
Low Right Exhaust Temperature Warning Event Breaker #1
No
Trip
Low Right Exhaust Temperature Warning Event Breaker #2
No
Trip
Low Right Exhaust Temperature Warning Event Fault
Yes
Protection Timer
Low Right Exhaust Temperature Shutdown Event Response
Disable Condition
Configuration
Low Right Exhaust Temperature Shutdown Event Audible Alert No
Low Right Exhaust Temperature Shutdown Event Breaker #1
No
Trip
Low Right Exhaust Temperature Shutdown Event Breaker #2
No
Trip
Low Right Exhaust Temperature Shutdown Event Fault
No
Protection Timer
High Left Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
High Left Exhaust Temperature Warning Event Audible Alert
Yes
High Left Exhaust Temperature Warning Event Breaker #1
No
Trip
High Left Exhaust Temperature Warning Event Breaker #2
No
Trip
High Left Exhaust Temperature Warning Event Fault Protection
No
Timer

5/20/2013 3:04 PM

13 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

High Left Exhaust Temperature Shutdown Event Response


Activate Hard Shutdown
Configuration
Condition
High Left Exhaust Temperature Shutdown Event Audible Alert Yes
High Left Exhaust Temperature Shutdown Event Breaker #1
No
Trip
High Left Exhaust Temperature Shutdown Event Breaker #2
No
Trip
High Left Exhaust Temperature Shutdown Event Fault
No
Protection Timer
Low Left Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Left Exhaust Temperature Warning Event Audible Alert
Yes
Low Left Exhaust Temperature Warning Event Breaker #1 Trip No
Low Left Exhaust Temperature Warning Event Breaker #2 Trip No
Low Left Exhaust Temperature Warning Event Fault Protection
Yes
Timer
Low Left Exhaust Temperature Shutdown Event Response
Disable Condition
Configuration
Low Left Exhaust Temperature Shutdown Event Audible Alert No
Low Left Exhaust Temperature Shutdown Event Breaker #1
No
Trip
Low Left Exhaust Temperature Shutdown Event Breaker #2
No
Trip
Low Left Exhaust Temperature Shutdown Event Fault
No
Protection Timer
High Fuel Filter Differential Pressure Warning Event Response
Activate Warning Condition
Configuration
High Fuel Filter Differential Pressure Warning Event Audible
Yes
Alert
High Fuel Filter Differential Pressure Warning Event Breaker
No
#1 Trip
High Fuel Filter Differential Pressure Warning Event Breaker
No
#2 Trip
High Fuel Filter Differential Pressure Shutdown Event
Activate Hard Shutdown
Response Config
Condition
High Fuel Filter Differential Pressure Shutdown Event Audible
Yes
Alert
High Fuel Filter Differential Pressure Shutdown Event Breaker
No
#1 Trip
High Fuel Filter Differential Pressure Shutdown Event Breaker
No
#2 Trip
Low Fuel Filter Differential Pressure Warning Event Response
Activate Warning Condition
Configuration

5/20/2013 3:04 PM

14 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Low Fuel Filter Differential Pressure Warning Event Audible


Alert
Low Fuel Filter Differential Pressure Warning Event Breaker
#1 Trip
Low Fuel Filter Differential Pressure Warning Event Breaker
#2 Trip
Low Fuel Filter Differential Pressure Warning Event Fault
Protection Timer
Low Fuel Filter Differential Pressure Shutdown Event
Response Configuration
Low Fuel Filter Differential Pressure Shutdown Event Audible
Alert
Low Fuel Filter Differential Pressure Shutdown Event Breaker
#1 Trip
Low Fuel Filter Differential Pressure Shutdown Event Breaker
#2 Trip
Low Fuel Filter Differential Pressure Shutdown Event Fault
Protection Timer
High Fuel Level Warning Event Response Configuration
High Fuel Level Warning Event Audible Alert
High Fuel Level Warning Event Breaker #1 Trip
High Fuel Level Warning Event Breaker #2 Trip
High Fuel Level Shutdown Event Response Configuration
High Fuel Level Shutdown Event Audible Alert
High Fuel Level Shutdown Event Breaker #1 Trip
High Fuel Level Shutdown Event Breaker #2 Trip
Low Fuel Level Warning Event Response Configuration
Low Fuel Level Warning Event Audible Alert
Low Fuel Level Warning Event Breaker #1 Trip
Low Fuel Level Warning Event Breaker #2 Trip
Low Fuel Level Shutdown Event Response Configuration
Low Fuel Level Shutdown Event Audible Alert
Low Fuel Level Shutdown Event Breaker #1 Trip
Low Fuel Level Shutdown Event Breaker #2 Trip
External Tank High Fuel Level Warning Event Response
Configuration
External Tank High Fuel Level Warning Event Audible Alert
External Tank High Fuel Level Warning Event Breaker #1 Trip
External Tank High Fuel Level Warning Event Breaker #2 Trip
External Tank High Fuel Level Shutdown Event Response
Configuration

Yes
No
No
Yes
Activate Hard Shutdown
Condition
Yes
No
No
Yes
Activate Warning Condition
Yes
No
No
Activate Hard Shutdown
Condition
Yes
No
No
Activate Warning Condition
Yes
No
No
Activate Hard Shutdown
Condition
Yes
No
No
Activate Warning Condition
Yes
No
No
Activate Hard Shutdown
Condition

5/20/2013 3:04 PM

15 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

External Tank High Fuel Level Shutdown Event Audible Alert


Yes
External Tank High Fuel Level Shutdown Event Breaker #1
No
Trip
External Tank High Fuel Level Shutdown Event Breaker #2
No
Trip
External Tank Low Fuel Level Warning Event Response
Activate Warning Condition
Configuration
External Tank Low Fuel Level Warning Event Audible Alert
Yes
External Tank Low Fuel Level Warning Event Breaker #1 Trip No
External Tank Low Fuel Level Warning Event Breaker #2 Trip No
External Tank Low Fuel Level Shutdown Event Response
Activate Hard Shutdown
Configuration
Condition
External Tank Low Fuel Level Shutdown Event Audible Alert
Yes
External Tank Low Fuel Level Shutdown Event Breaker #1 Trip No
External Tank Low Fuel Level Shutdown Event Breaker #2 Trip No
Fuel Leak Event Response Configuration
Activate Warning Condition
Fuel Leak Event Audible Alert
Yes
Fuel Leak Event Breaker #1 Trip
No
Fuel Leak Event Breaker #2 Trip
No
High Engine Oil Filter Differential Pressure Warning Event
Activate Warning Condition
Response Config
High Engine Oil Filter Differential Pressure Warning Event
Yes
Audible Alert
High Engine Oil Filter Differential Pressure Warning Event
No
Breaker #1 Trip
High Engine Oil Filter Differential Pressure Warning Event
No
Breaker #2 Trip
High Engine Oil Filter Differential Pressure Shutdown Event
Activate Hard Shutdown
Response Config
Condition
High Engine Oil Filter Differential Pressure Shutdown Event
Yes
Audible Alert
High Engine Oil Filter Differential Pressure Shutdown Event
No
Breaker #1 Trip
High Engine Oil Filter Differential Pressure Shutdown Event
No
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Warning Event
Activate Warning Condition
Response Config
Low Engine Oil Filter Differential Pressure Warning Event
Yes
Audible Alert
Low Engine Oil Filter Differential Pressure Warning Event
No
Breaker #1 Trip
Low Engine Oil Filter Differential Pressure Warning Event
No
Breaker #2 Trip

5/20/2013 3:04 PM

16 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Low Engine Oil Filter Differential Pressure Warning Fault


Protection Timer
Low Engine Oil Filter Differential Pressure Shutdown Event
Response Config
Low Engine Oil Filter Differential Pressure Shutdown Event
Audible Alert
Low Engine Oil Filter Differential Pressure Shutdown Event
Breaker #1 Trip
Low Engine Oil Filter Differential Pressure Shutdown Event
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Shutdown Fault
Protection Timer
High Starting Air Pressure Warning Event Response
Configuration
High Starting Air Pressure Warning Event Audible Alert
High Starting Air Pressure Warning Event Breaker #1 Trip
High Starting Air Pressure Warning Event Breaker #2 Trip
High Starting Air Pressure Shutdown Event Response
Configuration
High Starting Air Pressure Shutdown Event Audible Alert
High Starting Air Pressure Shutdown Event Breaker #1 Trip
High Starting Air Pressure Shutdown Event Breaker #2 Trip
Low Starting Air Pressure Warning Event Response
Configuration
Low Starting Air Pressure Warning Event Audible Alert
Low Starting Air Pressure Warning Event Breaker #1 Trip
Low Starting Air Pressure Warning Event Breaker #2 Trip
Low Starting Air Pressure Warning Event Fault Protection
Timer
Low Starting Air Pressure Shutdown Event Response
Configuration
Low Starting Air Pressure Shutdown Event Audible Alert
Low Starting Air Pressure Shutdown Event Breaker #1 Trip
Low Starting Air Pressure Shutdown Event Breaker #2 Trip
Low Starting Air Pressure Shutdown Event Fault Protection
Timer
High Gas Pressure Warning Event Response Configuration
High Gas Pressure Warning Event Audible Alert
High Gas Pressure Warning Event Breaker #1 Trip
High Gas Pressure Warning Event Breaker #2 Trip
High Gas Pressure Shutdown Event Response Configuration
High Gas Pressure Shutdown Event Audible Alert

Yes
Activate Hard Shutdown
Condition
Yes
No
No
Yes
Activate Warning Condition
Yes
No
No
Activate Hard Shutdown
Condition
Yes
No
No
Activate Warning Condition
Yes
No
No
Yes
Activate Hard Shutdown
Condition
Yes
No
No
Yes
Activate Warning Condition
Yes
No
No
Activate Hard Shutdown
Condition
Yes

5/20/2013 3:04 PM

17 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

High Gas Pressure Shutdown Event Breaker #1 Trip


High Gas Pressure Shutdown Event Breaker #2 Trip
Low Gas Pressure Warning Event Response Configuration
Low Gas Pressure Warning Event Audible Alert
Low Gas Pressure Warning Event Breaker #1 Trip
Low Gas Pressure Warning Event Breaker #2 Trip

No
No
Activate Warning Condition
Yes
No
No
Activate Hard Shutdown
Low Gas Pressure Shutdown Event Response Configuration
Condition
Low Gas Pressure Shutdown Event Audible Alert
Yes
Low Gas Pressure Shutdown Event Breaker #1 Trip
No
Low Gas Pressure Shutdown Event Breaker #2 Trip
No
Engine Intake Manifold Charge Combustion Event Response
Activate Hard Shutdown
Configuration
Condition
Engine Intake Manifold Charge Combustion Event Audible Alert Yes
Engine Intake Manifold Charge Combustion Event Loss of
No
Utility
Engine Intake Manifold Charge Combustion Event Breaker #1
No
Trip
Engine Intake Manifold Charge Combustion Event Breaker #2
No
Trip
Engine Intake Manifold Charge Combustion Event Fault
No
Protection Timer
Event Response Configuration - Generator Protection
Events
High Generator Bearing #1 Temperature Warning Event
Activate Warning Condition
Response Configuration
High Generator Bearing #1 Temperature Warning Event
Yes
Audible Alert
High Generator Bearing #1 Temperature Warning Event
No
Breaker #1 Trip
High Generator Bearing #1 Temperature Warning Event
No
Breaker #2 Trip
High Generator Bearing #1 Temperature Warning Event Fault
No
Protection Timer
High Generator Bearing #1 Temperature Shutdown Event
Activate Hard Shutdown
Response Configuration
Condition
High Generator Bearing #1 Temperature Shutdown Event
Yes
Audible Alert
High Generator Bearing #1 Temperature Shutdown Event
No
Breaker #1 Trip
High Generator Bearing #1 Temperature Shutdown Event
No
Breaker #2 Trip
High Generator Bearing #1 Temperature Shutdown Event
No
Fault Protection Timer

5/20/2013 3:04 PM

18 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Low Generator Bearing #1


Response Configuration
Low Generator Bearing #1
Audible Alert
Low Generator Bearing #1
Breaker #1 Trip
Low Generator Bearing #1
Breaker #2 Trip
Low Generator Bearing #1
Protection Timer
Low Generator Bearing #1
Response Configuration
Low Generator Bearing #1
Audible Alert
Low Generator Bearing #1
Breaker #1 Trip
Low Generator Bearing #1
Breaker #2 Trip
Low Generator Bearing #1
Protection Timer

Temperature Warning Event


Temperature Warning Event
Temperature Warning Event
Temperature Warning Event
Temperature Warning Event Fault
Temperature Shutdown Event
Temperature Shutdown Event
Temperature Shutdown Event
Temperature Shutdown Event
Temperature Shutdown Event Fault

Yes
No
No
Yes
Disable Condition
No
No
No
No
Activate Hard Shutdown
Condition
Yes
No
No

Earth Fault Event Response Configuration


Earth Fault Event Audible Alert
Earth Fault Event Breaker #1 Trip
Earth Fault Event Breaker #2 Trip
Generator Winding #1 High Temperature
Response Configuration
Generator Winding #1 High Temperature
Audible Alert
Generator Winding #1 High Temperature
Breaker #1 Trip
Generator Winding #1 High Temperature
Breaker #2 Trip
Generator Winding #1 High Temperature
Protection Timer
Generator Winding #2 High Temperature
Response Configuration
Generator Winding #2 High Temperature
Audible Alert
Generator Winding #2 High Temperature
Breaker #1 Trip
Generator Winding #2 High Temperature
Breaker #2 Trip
Generator Winding #2 High Temperature
Protection Timer

Activate Warning Condition

Warning Event
Warning Event
Warning Event
Warning Event
Warning Event Fault
Warning Event
Warning Event
Warning Event
Warning Event
Warning Event Fault

Activate Warning Condition


Yes
No
No
No
Activate Warning Condition
Yes
No
No
No

5/20/2013 3:04 PM

19 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Generator Winding #3 High Temperature Warning Event


Response Configuration
Generator Winding #3 High Temperature Warning Event
Audible Alert
Generator Winding #3 High Temperature Warning Event
Breaker #1 Trip
Generator Winding #3 High Temperature Warning Event
Breaker #2 Trip
Generator Winding #3 High Temperature Warning Event Fault
Protection Timer
Generator Winding #1 High Temperature Shutdown Event
Response Configuration
Generator Winding #1 High Temperature Shutdown Event
Audible Alert
Generator Winding #1 High Temperature Shutdown Event
Breaker #1 Trip
Generator Winding #1 High Temperature Shutdown Event
Breaker #2 Trip
Generator Winding #1 High Temperature Shutdown Event
Fault Protection Timer
Generator Winding #2 High Temperature Shutdown Event
Response Configuration
Generator Winding #2 High Temperature Shutdown Event
Audible Alert
Generator Winding #2 High Temperature Shutdown Event
Breaker #1 Trip
Generator Winding #2 High Temperature Shutdown Event
Breaker #2 Trip
Generator Winding #2 High Temperature Shutdown Event
Fault Protection Timer
Generator Winding #3 High Temperature Shutdown Event
Response Configuration
Generator Winding #3 High Temperature Shutdown Event
Audible Alert
Generator Winding #3 High Temperature Shutdown Event
Breaker #1 Trip
Generator Winding #3 High Temperature Shutdown Event
Breaker #2 Trip
Generator Winding #3 High Temperature Shutdown Event
Fault Protection Timer
Generator High Power Warning Event Response Configuration
Generator High Power Warning Event Audible Alert
Generator High Power Warning Event Breaker #1 Trip
Generator High Power Warning Event Breaker #2 Trip

Activate Warning Condition


Yes
No
No
No
Activate Hard Shutdown
Condition
Yes
No
No
No
Activate Hard Shutdown
Condition
Yes
No
No
No
Activate Hard Shutdown
Condition
Yes
No
No
No
Activate Warning Condition
Yes
No
No

5/20/2013 3:04 PM

20 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Event Response Configuration - Other System Events


High Ambient Air Temperature Warning Event Response
Configuration
High Ambient Air Temperature Warning Event Audible Alert
High Ambient Air Temperature Warning Event Breaker #1 Trip
High Ambient Air Temperature Warning Event Breaker #2 Trip
High Ambient Air Temperature Warning Event Fault Protection
Timer
High Ambient Air Temperature Shutdown Event Response
Configuration
High Ambient Air Temperature Shutdown Event Audible Alert
High Ambient Air Temperature Shutdown Event Breaker #1
Trip
High Ambient Air Temperature Shutdown Event Breaker #2
Trip
High Ambient Air Temperature Shutdown Event Fault
Protection Timer
Low Ambient Air Temperature Warning Event Response
Configuration
Low Ambient Air Temperature Warning Event Audible Alert
Low Ambient Air Temperature Warning Event Breaker #1 Trip
Low Ambient Air Temperature Warning Event Breaker #2 Trip
Low Ambient Air Temperature Shutdown Event Response
Configuration
Low Ambient Air Temperature Shutdown Event Audible Alert
Low Ambient Air Temperature Shutdown Event Breaker #1
Trip
Low Ambient Air Temperature Shutdown Event Breaker #2
Trip
Automatic Transfer Switch In Normal Position Event Response
Configuration
Automatic Transfer Switch In Normal Position Event Audible
Alert
Automatic Transfer Switch In Emergency Position Event
Response Config
Automatic Transfer Switch In Emergency Position Event
Audible Alert
High Battery Voltage Warning Event Response Configuration
High Battery Voltage Warning Event Audible Alert
High Battery Voltage Warning Event Breaker #1 Trip
High Battery Voltage Warning Event Breaker #2 Trip

Activate Warning Condition


Yes
No
No
No
Activate Hard Shutdown
Condition
Yes
No
No
No
Activate Warning Condition
Yes
No
No
Disable Condition
No
No
No
Active Only Condition
No
Active Only Condition
No

Activate Warning Condition


Yes
No
No
Activate Soft Shutdown
High Battery Voltage Shutdown Event Response Configuration
Condition
High Battery Voltage Shutdown Event Audible Alert
Yes

5/20/2013 3:04 PM

21 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

High Battery Voltage Shutdown Event Breaker #1 Trip


No
High Battery Voltage Shutdown Event Breaker #2 Trip
No
Low Battery Voltage Warning Event Response Configuration
Activate Warning Condition
Low Battery Voltage Warning Event Audible Alert
Yes
Low Battery Voltage Warning Event Breaker #1 Trip
No
Low Battery Voltage Warning Event Breaker #2 Trip
No
Low Battery Voltage Warning Event Fault Protection Timer
No
Low Battery Charging System Voltage Warning Event
Disable Condition
Response Configuration
Low Battery Charging System Voltage Warning Event Audible
Yes
Alert
Low Battery Charging System Voltage Warning Event Breaker
No
#1 Trip
Low Battery Charging System Voltage Warning Event Breaker
No
#2 Trip
Low Battery Charging System Voltage Warning Event Fault
No
Protection Timer
Engine In Cooldown Event Response Configuration
Active Only Condition
Engine In Cooldown Event Audible Alert
No
Engine Speed-Generator Output Freq Mismatch Warning Event
Activate Warning Condition
Response Config
Engine Speed-Generator Output Freq Mismatch Warning Event
Yes
Audible Alert
Engine Speed-Generator Output Freq Mismatch Warning Event
No
Breaker #1 Trip
Engine Speed-Generator Output Freq Mismatch Warning Event
No
Breaker #2 Trip
High Fire Extinguisher Pressure Warning Event Response
Activate Warning Condition
Configuration
High Fire Extinguisher Pressure Warning Event Audible Alert
Yes
High Fire Extinguisher Pressure Warning Event Breaker #1
No
Trip
High Fire Extinguisher Pressure Warning Event Breaker #2
No
Trip
High Fire Extinguisher Pressure Shutdown Event Response
Activate Hard Shutdown
Configuration
Condition
High Fire Extinguisher Pressure Shutdown Event Audible Alert Yes
High Fire Extinguisher Pressure Shutdown Event Breaker #1
No
Trip
High Fire Extinguisher Pressure Shutdown Event Breaker #2
No
Trip
Low Fire Extinguisher Pressure Warning Event Response
Activate Warning Condition
Configuration
Low Fire Extinguisher Pressure Warning Event Audible Alert
Yes

5/20/2013 3:04 PM

22 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Low Fire Extinguisher Pressure Warning Event Breaker #1 Trip No


Low Fire Extinguisher Pressure Warning Event Breaker #2 Trip No
Low Fire Extinguisher Pressure Warning Event Fault Protection
No
Timer
Low Fire Extinguisher Pressure Shutdown Event Response
Activate Hard Shutdown
Configuration
Condition
Low Fire Extinguisher Pressure Shutdown Event Audible Alert Yes
Low Fire Extinguisher Pressure Shutdown Event Breaker #1
No
Trip
Low Fire Extinguisher Pressure Shutdown Event Breaker #2
No
Trip
Low Fire Extinguisher Pressure Shutdown Event Fault
No
Protection Timer
Generator Control Not in Automatic Warning Event Response Warning & Active Only
Configuration
Condition
Generator Control Not in Automatic Warning Event Audible
Yes
Alert
Generator Breaker Locked Out Warning Event Response
Warning & Active Only
Configuration
Condition
Generator Breaker Locked Out Warning Event Audible Alert
Yes
Generator Breaker Locked Out Warning Event Breaker #1 Trip No
Generator Breaker Locked Out Warning Event Breaker #2 Trip No
Utility Breaker Locked Out Warning Event Response
Warning & Active Only
Configuration
Condition
Utility Breaker Locked Out Warning Event Audible Alert
Yes
Utility Breaker Locked Out Warning Event Breaker #1 Trip
No
Utility Breaker Locked Out Warning Event Breaker #2 Trip
No
Activate Hard Shutdown
Earth Leakage Event Response Configuration
Condition
Earth Leakage Event Audible Alert
Yes
Earth Leakage Event Breaker #1 Trip
No
Earth Leakage Event Breaker #2 Trip
No
Emergency Power System Supplying Load Event Response
Warning & Active Only
Configuration
Condition
Emergency Power System Supplying Load Event Audible Alert No
Low Cranking Voltage Warning Event Response Configuration Disable Condition
Low Cranking Voltage Warning Event Audible Alert
No
Low Cranking Voltage Warning Event Breaker #1 Trip
No
Low Cranking Voltage Warning Event Breaker #2 Trip
No
Event Response Configuration - Custom Events
Custom Event #1 High Warning Event Response Configuration Activate Warning Condition
Custom Event #1 High Warning Event Audible Alert
Yes
Custom Event #1 High Warning Event Breaker #1 Trip
No

5/20/2013 3:04 PM

23 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event

#1 High Warning Event Breaker #2 Trip


#1 High Warning Event Fault Protection Timer
#1 High Shutdown Event Response
#1
#1
#1
#1
#1
#1
#1
#1
#1
#1
#1
#1
#1
#1
#1
#1
#1
#1
#1
#1
#2
#2
#2
#2
#2
#2
#2
#2
#2
#2
#2
#2
#2
#2
#2

No
No
Activate Hard Shutdown
Condition
High Shutdown Event Audible Alert
Yes
High Shutdown Event Breaker #1 Trip
No
High Shutdown Event Breaker #2 Trip
No
High Shutdown Event Fault Protection Timer No
Low Warning Event Response Configuration Activate Warning Condition
Low Warning Event Audible Alert
Yes
Low Warning Event Breaker #1 Trip
No
Low Warning Event Breaker #2 Trip
No
Low Warning Event Fault Protection Timer No
Low Shutdown Event Response
Activate Hard Shutdown
Condition
Low Shutdown Event Audible Alert
Yes
Low Shutdown Event Breaker #1 Trip
No
Low Shutdown Event Breaker #2 Trip
No
Low Shutdown Event Fault Protection Timer No
Condition Exists Event Response
Active Only Condition
Condition Exists Event Audible Alert
No
Condition Exists Event Loss of Utility
No
Condition Exists Event Breaker #1 Trip
No
Condition Exists Event Breaker #2 Trip
No
Condition Exists Event Fault Protection Timer No
High Warning Event Response Configuration Activate Warning Condition
High Warning Event Audible Alert
Yes
High Warning Event Breaker #1 Trip
No
High Warning Event Breaker #2 Trip
No
High Warning Event Fault Protection Timer No
High Shutdown Event Response
Activate Hard Shutdown
Condition
High Shutdown Audible Alert
Yes
High Shutdown Breaker #1 Trip
No
High Shutdown Breaker #2 Trip
No
High Shutdown Fault Protection Timer
No
Low Warning Event Response Configuration Activate Warning Condition
Low Warning Audible Alert
Yes
Low Warning Breaker #1 Trip
No
Low Warning Breaker #2 Trip
No
Low Warning Fault Protection Timer
No

5/20/2013 3:04 PM

24 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event

#2 Low Shutdown Event Response


#2
#2
#2
#2
#2
#2
#2
#2
#2
#2
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3
#3

Activate Hard Shutdown


Condition
Low Shutdown Event Audible Alert
Yes
Low Shutdown Event Breaker #1 Trip
No
Low Shutdown Event Breaker #2 Trip
No
Low Shutdown Event Fault Protection Timer No
Condition Exists Event Response
Active Only Condition
Condition Exists Event Audible Alert
No
Condition Exists Event Loss of Utility
No
Condition Exists Event Breaker #1 Trip
No
Condition Exists Event Breaker #2 Trip
No
Condition Exists Event Fault Protection Timer No
High Warning Event Response Configuration Activate Warning Condition
High Warning Event Audible Alert
Yes
High Warning Event Breaker #1 Trip
No
High Warning Event Breaker #2 Trip
No
High Warning Event Fault Protection Timer No
High Shutdown Event Response
Activate Hard Shutdown
Condition
High Shutdown Event Audible Alert
Yes
High Shutdown Event Breaker #1 Trip
No
High Shutdown Event Breaker #2 Trip
No
High Shutdown Event Fault Protection Timer No
Low Warning Event Response Configuration Activate Warning Condition
Low Warning Event Audible Alert
Yes
Low Warning Event Breaker #1 Trip
No
Low Warning Event Breaker #2 Trip
No
Low Warning Event Fault Protection Timer No
Low Shutdown Event Response
Activate Hard Shutdown
Condition
Low Shutdown Event Audible Alert
Yes
Low Shutdown Event Breaker #1 Trip
No
Low Shutdown Event Breaker #2 Trip
No
Low Shutdown Event Fault Protection Timer No
Condition Exists Event Response
Active Only Condition
Condition
Condition
Condition
Condition
Condition

Exists
Exists
Exists
Exists
Exists

Event
Event
Event
Event
Event

Audible Alert
No
Loss of Utility
No
Breaker #1 Trip
No
Breaker #2 Trip
No
Fault Protection Timer No

5/20/2013 3:04 PM

25 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event

#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5

High
High
High
High
High
High

Warning Event Response Configuration


Warning Event Audible Alert
Warning Event Breaker #1 Trip
Warning Event Breaker #2 Trip
Warning Event Fault Protection Timer
Shutdown Event Response

Activate Warning Condition


Yes
No
No
No
Activate Hard Shutdown
Condition
High Shutdown Event Audible Alert
Yes
High Shutdown Event Breaker #1 Trip
No
High Shutdown Event Breaker #2 Trip
No
High Shutdown Event Fault Protection Timer No
Low Warning Event Response Configuration Activate Warning Condition
Low Warning Event Audible Alert
Yes
Low Warning Event Breaker #1 Trip
No
Low Warning Event Breaker #2 Trip
No
Low Warning Event Fault Protection Timer No
Low Shutdown Event Response
Activate Hard Shutdown
Condition
Low Shutdown Event Audible Alert
Yes
Low Shutdown Event Breaker #1 Trip
No
Low Shutdown Event Breaker #2 Trip
No
Low Shutdown Event Fault Protection Timer No
Condition Exists Event Response
Active Only Condition
Condition Exists Event Audible Alert
No
Condition Exists Event Loss of Utility
No
Condition Exists Event Breaker #1 Trip
No
Condition Exists Event Breaker #2 Trip
No
Condition Exists Event Fault Protection Timer No
High Warning Event Response Configuration Activate Warning Condition
High Warning Event Audible Alert
Yes
High Warning Event Breaker #1 Trip
No
High Warning Event Breaker #2 Trip
No
High Warning Event Fault Protection Timer No
High Shutdown Event Response
Activate Hard Shutdown
Condition
High Shutdown Event Audible Alert
Yes
High Shutdown Event Breaker #1 Trip
No
High Shutdown Event Breaker #2 Trip
No
High Shutdown Event Fault Protection Timer No
Low Warning Event Response Configuration Activate Warning Condition
Low Warning Event Audible Alert
Yes

5/20/2013 3:04 PM

26 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event

#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6

Low
Low
Low
Low

Warning Event Breaker #1 Trip


Warning Event Breaker #2 Trip
Warning Event Fault Protection Timer
Shutdown Event Response

No
No
No
Activate Hard Shutdown
Condition
Low Shutdown Event Audible Alert
Yes
Low Shutdown Event Breaker #1 Trip
No
Low Shutdown Event Breaker #2 Trip
No
Low Shutdown Event Fault Protection Timer No
Condition Exists Event Response
Active Only Condition
Condition Exists Event Audible Alert
No
Condition Exists Event Loss of Utility
No
Condition Exists Event Breaker #1 Trip
No
Condition Exists Event Breaker #2 Trip
No
Condition Exists Event Fault Protection Timer No
High Warning Event Response Configuration Activate Warning Condition
High Warning Event Audible Alert
Yes
High Warning Event Breaker #1 Trip
No
High Warning Event Breaker #2 Trip
No
High Warning Event Fault Protection Timer No
High Shutdown Event Response
Activate Hard Shutdown
Condition
High Shutdown Event Audible Alert
Yes
High Shutdown Event Breaker #1 Trip
No
High Shutdown Event Breaker #2 Trip
No
High Shutdown Event Fault Protection Timer No
Low Warning Event Response Configuration Activate Warning Condition
Low Warning Event Audible Alert
Yes
Low Warning Event Breaker #1 Trip
No
Low Warning Event Breaker #2 Trip
No
Low Warning Event Fault Protection Timer No
Low Shutdown Event Response
Activate Hard Shutdown
Condition
Low Shutdown Event Audible Alert
Yes
Low Shutdown Event Breaker #1 Trip
No
Low Shutdown Event Breaker #2 Trip
No
Low Shutdown Event Fault Protection Timer No
Condition Exists Event Response
Active Only Condition

#6 Condition Exists Event Audible Alert


#6 Condition Exists Event Loss of Utility

No
No

5/20/2013 3:04 PM

27 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Custom Event
Configuration
Custom Event
Custom Event
Custom Event

#6
#6
#6
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7

Condition Exists Event Breaker #1 Trip


No
Condition Exists Event Breaker #2 Trip
No
Condition Exists Event Fault Protection Timer No
High Warning Event Response Configuration Activate Warning Condition
High Warning Event Audible Alert
Yes
High Warning Event Breaker #1 Trip
No
High Warning Event Breaker #2 Trip
No
High Warning Event Fault Protection Timer No
High Shutdown Event Response
Activate Hard Shutdown
Condition
High Shutdown Event Audible Alert
Yes
High Shutdown Event Breaker #1 Trip
No
High Shutdown Event Breaker #2 Trip
No
High Shutdown Event Fault Protection Timer No
Low Warning Event Response Configuration Activate Warning Condition
Low Warning Event Audible Alert
Yes
Low Warning Event Breaker #1 Trip
No
Low Warning Event Breaker #2 Trip
No
Low Warning Event Fault Protection Timer No
Low Shutdown Event Response
Activate Hard Shutdown
Condition
Low Shutdown Event Audible Alert
Yes
Low Shutdown Event Breaker #1 Trip
No
Low Shutdown Event Breaker #2 Trip
No
Low Shutdown Event Fault Protection Timer No
Condition Exists Event Response
Active Only Condition

#7
#7
#7
#7
#7
#8
#8
#8
#8
#8
#8

Condition Exists Event Audible Alert


No
Condition Exists Event Loss of Utility
No
Condition Exists Event Breaker #1 Trip
No
Condition Exists Event Breaker #2 Trip
No
Condition Exists Event Fault Protection Timer No
High Warning Event Response Configuration Activate Warning Condition
High Warning Event Audible Alert
Yes
High Warning Event Breaker #1 Trip
No
High Warning Event Breaker #2 Trip
No
High Warning Event Fault Protection Timer No
High Shutdown Event Response
Activate Hard Shutdown
Condition
#8 High Shutdown Event Audible Alert
Yes
#8 High Shutdown Event Breaker #1 Trip
No
#8 High Shutdown Event Breaker #2 Trip
No

5/20/2013 3:04 PM

28 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Custom Event #8 High Shutdown Event Fault Protection Timer No


Custom Event #8 Low Warning Event Response Configuration Activate Warning Condition
Custom Event #8 Low Warning Event Audible Alert
Yes
Custom Event #8 Low Warning Event Breaker #1 Trip
No
Custom Event #8 Low Warning Event Breaker #2 Trip
No
Custom Event #8 Low Warning Event Fault Protection Timer No
Custom Event #8 Low Shutdown Event Response
Activate Hard Shutdown
Configuration
Condition
Custom Event #8 Low Shutdown Event Audible Alert
Yes
Custom Event #8 Low Shutdown Event Breaker #1 Trip
No
Custom Event #8 Low Shutdown Event Breaker #2 Trip
No
Custom Event #8 Low Shutdown Event Fault Protection Timer No
Custom Event #8 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #8 Condition Exists Event Audible Alert
No
Custom Event #8 Condition Exists Event Loss of Utility
No
Custom Event #8 Condition Exists Event Breaker #1 Trip
No
Custom Event #8 Condition Exists Event Breaker #2 Trip
No
Custom Event #8 Condition Exists Event Fault Protection Timer No
Event System
Event Warning Condition Response Auto Reset Enable Status Enabled
Event Audible Alert Response Auto Reset Enable Status
Enabled
Event Loss Of Utility Response Auto Reset Enable Status
Enabled
Event Breaker #1 Trip Response Auto Reset Enable Status
Enabled
Event Breaker #2 Trip Response Auto Reset Enable Status
Enabled
Generator AC Monitor
Generator Connection Configuration
Wye (or Star) Connection
Generator Potential Transformer Primary Winding Rating
1 Volts
Generator Potential Transformer Secondary Winding Rating
1 Volts
Generator Current Transformer Primary Winding Rating
800 Amps
Generator Current Transformer Secondary Winding Rating
5 Amps
Number of Generator Poles
4 Poles
Generator Rated Frequency
50 Hz
Generator Rated Voltage
400 Volts
Generator Rated Power
320 kW
Generator Rated Apparent Power
400 kVA
Governor Desired Engine Speed Request
Maximum Engine Speed Bias
400 rpm
Generator Nominal Output Frequency
50.0 Hz
Electronic Control Module Reduced Power Mode
Electronic Control Module Reduced Power Mode Enable Status Enabled
Electronic Control Module Reduced Power Mode Delay Time
10 min

5/20/2013 3:04 PM

29 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...

Relay Outputs
Relay Output #1 Active State Configuration
Relay Output #2 Active State Configuration
Relay Output #3 Active State Configuration
Relay Output #4 Active State Configuration
Relay Output #5 Active State Configuration
Relay Output #6 Active State Configuration
Programmable Trip Point Function
Programmable Trip Point Function #1 Trigger Condition
Programmable Trip Point Function #1 Percentage Threshold
Programmable Trip Point Function #1 Hysteresis Percentage
Programmable Trip Point Function #1 Trip Activation Delay
Time
Programmable Trip Point Function #1 Trip Deactivation Delay
Time
Programmable Trip Point Function #2 Trigger Condition
Programmable Trip Point Function #2 Percentage Threshold
Programmable Trip Point Function #2 Hysteresis Percentage
Programmable Trip Point Function #2 Trip Activation Delay
Time
Programmable Trip Point Function #2 Trip Deactivation Delay
Time
Programmable Trip Point Function #3 Trigger Condition
Programmable Trip Point Function #3 Percentage Threshold
Programmable Trip Point Function #3 Hysteresis Percentage
Programmable Trip Point Function #3 Trip Activation Delay
Time
Programmable Trip Point Function #3 Trip Deactivation Delay
Time
Programmable Trip Point Function #4 Trigger Condition
Programmable Trip Point Function #4 Percentage Threshold
Programmable Trip Point Function #4 Hysteresis Percentage
Programmable Trip Point Function #4 Trip Activation Delay
Time
Programmable Trip Point Function #4 Trip Deactivation Delay
Time
Configuration Data
Engine Serial Number
Display Preferences
Display Pressure Units Configuration
Display Temperature Units Configuration
Display Volume Units Configuration

High
High
High
High
High
High
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Disabled or Not Installed
Not Programmed
kPa
Degrees Centigrade (Celsius)
liters

5/20/2013 3:04 PM

30 of 30

file:///C:/Documents and Settings/All Users/Perkins/Olympian Service To...