Low Voltage

EasyPact CVS
Moulded-case circuit breakers and switch-disconnectors
from 100 to 630 A

Catalogue
2011

Safe
Reliable
Simple

The easy choice for


quality and value
EasyPact CVS

LV circuit breakers from 100 to 630A

Do you strain to find a high


quality circuit breaker that
is simple, flexible, and safe?
Have tight project budgets
restricted you from choosing
the best quality products?
Do you need the reach,
support and accessibility
of a global leader, with the
value of a local supplier?

Buildings

Industry

Gain peace of mind


and optimized cost
for every installation

EasyPact CVS

General contents

Presentation

Functions
and characteristics

A-1

Installation
recommendations

B-1

Dimensions
and connection

C-1

Additional characteristics

D-1

Catalogue numbers

E-1

A-7

Functions and characteristics

A-2

EasyPact CVS

Functions and characteristics

Introduction

General characteristics
Characteristics and performance

Protection of distribution systems

A-2
A-4

TM-D thermal-magnetic trip units


ETS 2.3 electronic trip unit and accessories

A-6
A-7

Earth-leakage protection

A-8

Motor protection

MA instantaneous trip units

Switch-disconnectors
Accessories and auxiliaries

Overview
Device installation
Connection of devices
Selection of auxiliaries
Indication contacts
Remote tripping
Rotary handles
Locks and sealing accessories
Escutcheons and protection collars

Installation recommendations
Dimensions and connection
Additional characteristics
Catalogue numbers

A-9
A-10

A-12
A-13
A-14
A-16
A-17
A-18
A-19
A-20
A-21

B-1
C-1
D-1
E-1

A-1

Introduction

Functions
and characteristics

General characteristics

DB400000

1
2
7
8
3
4
5
6
cat.A

Standardised characteristics indicated on the rating plate:


1 Type of device: frame size and breaking capacity class
2 Ui: rated insulation voltage.
3 Uimp: rated impulse withstand voltage.
4 Ics: service breaking capacity.
5 Icu: ultimate breaking capacity for various values of the
rated operational voltage Ue
6 Ue: operational voltage.
7 Colour label indicating the breaking capacity class.

CVS

CVS

CVS

CVS

CVS

8 Suitable for Isolation symbol.


9 Reference standard.
Note: when the circuit breaker is equipped with an extended
rotary handle, the door must be opened to access the rating
plate.

A-2

Compliance with standards

EasyPact CVS circuit breakers and auxiliaries comply with the following international
recommendations:
bb IEC 60947-1: general rules
bb IEC 60947-2: circuit breakers
bb IEC 60947-3: switch-disconnectors

Pollution degree

EasyPact CVS circuit breakers are certified for operation in pollution-degree III
environments as defined by IEC standards 60947-1 and 60664-1 (industrial
environments).

Climatic withstand

EasyPact CVS circuit breakers have successfully passed the tests defined by the
following standards for extreme atmospheric conditions:
bb IEC 60068-2-1: dry cold (-55C)
bb IEC 60068-2-2: dry heat (+85C)
bb IEC 60068-2-30: damp heat (95 % relative humidity at 55C)
bb IEC 60068-2-52 severity level 2: salt mist.

Environment

EasyPact CVS respects the European environment directive EC/2002/95 concerning


the restriction of hazardous substances (RoHS).
All EasyPact CVS production sites have set up an ISO 14001 certified environmental
management system.

Ambient temperature

bb EasyPact CVS circuit breakers can be used between -25C and +70C. For
temperatures higher than 40C (65C for circuit breakers used to protect motor
feeders), devices must be derated (see page B-2).
bb Circuit breakers should be put into service under normal ambient, operatingtemperature conditions. Exceptionally, the circuit breaker can be put into service
when the ambient temperature is between -35C and -25C.
bb The permissible storage-temperature range for EasyPact CVS circuit breakers in
the original packing is -50C and +85C.

Suitable for isolation with positive contact


indication

All EasyPact CVS circuit breakers are suitable for isolation as defined in IEC
standard 60947-2:
bb The isolation position corresponds to the O (OFF) position.
bb The operating handle cannot indicate the OFF position unless the contacts are
effectively open.
bb Padlocks cannot be installed unless the contacts are open.
Installation of a rotary handle does not alter the reliability of the position-indication
system.
The isolation function is certified by tests guaranteeing:
bb The mechanical reliability of the position-indication system
bb The absence of leakage currents
bb Over voltage withstand capacity between upstream and downstream connections.
The tripped position does not ensure isolation with positive contact indication.
Only the OFF position guarantees isolation.

Installation in class II switchboards

All EasyPact CVS circuit breakers are class II front face devices. They can be
installed through the door of class II switchboards (as per IEC standards 61140
and 60664-1) without downgrading switchboard insulation. Installation requires no
special operations, even when the circuit breaker is equipped with a rotary handle.

Degree of protection

The following indications are in accordance with standards IEC 60529 (IP degree of
protection) and IEC 62262 (IK protection against external mechanical impacts).
Bare circuit breaker:
bb with toggle: IP40, IK07 front face
bb with extended rotary handle: IP 55, IK08
Circuit breaker installed in a switchboard:
bb with toggle: IP40, IK07 front face
bb with extended rotary handle: IP 55, IK08

A-3

Functions
and characteristics

Introduction

Characteristics and performance

PB106447

Common characteristics
Rated voltages
Insulation voltage (V)
Impulse withstand voltage (kV)
Operational voltage (V)
Suitability for isolation
Utilisation category
Pollution degree

Ui
Uimp
Ue

690
8
440
yes
A
3

AC 50/60 Hz
IEC/EN 60947-2
IEC 60664-1

Circuit breakers

Performance
Electrical characteristics as per IEC 60947-2
Rated current (A)

In

40 C

lcu

AC 50/60 Hz 220/240 V
380/415 V
440 V

lcs

AC 50/60 Hz 220/240 V
380/415 V
440 V
Mechanical
Electrical
415V

Number of poles
Breaking capacity levels

PB106448

EasyPact CVS100/160/250

Breaking capacity (kA rms)

Service breaking capacity (kA rms)

Durability (C-O cycles)

Protection

Short-circuit protection
Overload/short-circuit protection

Earth-leakage protection

Installation/connections
Dimensions and weights

EasyPact CVS400/630

A-4

Magnetic only
Thermal magnetic
Electronic
with neutral protection (Off-0.5-1)
By Vigi module

Dimensions (mm)
WxHxD

Fixed, front connections

Weight (kg)

Fixed, front connections

Connections

In/2
In

3P
4P
3P
4P

Connection terminals

Pitch

Without/With spreaders

Large Cu or Al cables

Cross-section

mm

CVS100

CVS160

CVS250

CVS400

CVS630

100

160

250

400

630

3, 4
B
F

3, 4
B
F

3, 4
B
F

3, 4
F
N

3, 4
F
N

40
25
20

40
25
20

40
25
20

40
36
30

40
36
30

70
36
36

70
36
36

70
36
36

70
50
42

70
50
42

40 70
25 36
15 18
30000
30000
12000

40 70
25 36
15 18
25000
25000
12000

40 70
25 36
15 18
20000
20000
10000

40 70
36 50
23 32
15000
12000
6000

40 70
36 50
23 32
15000
8000
4000

b
b
b

b
b
b

b
b
b

b
b
b
b
b

b
b
b
b
b

105 x 161 x 86
140 x 161 x 86
1.8
2.2

105 x 161 x 86
140 x 161 x 86
1.8
2.3

105 x 161 x 86
140 x 161 x 86
2.0
2.6

140 x 255 x 110


185 x 255 x 110
4.7
6.3

140 x 255 x 110


185 x 255 x 110
5.2
7.1

35/45 mm

35/45 mm

35/45 mm

300

300

300

45/52.5 mm
45/70 mm
4 x 240

45/52.5 mm
45/70 mm
4 x 240

A-5

Functions
and characteristics

Protection of distribution systems

TM-D thermal-magnetic trip units can be used on


EasyPact CVS100-630 circuit breakers with
performance levels B/F/N.

TM-D thermal-magnetic trip units


DB400003

TM-D thermal-magnetic trip units

2400

4800
600

540

4200

420
480

600A/40

3000
3600

Protection...............................................................................
TM-D trip units are used mainly in electrical distribution applications for
protection of cables supplied by transformers.
Thermal protection (Ir)
Thermal protection operates according to:
bb Ir that can be adjusted in amps from 0.7 to 1 times the rating of the trip unit (16 A to
250 A), corresponding to settings from 11 to 250 A for the range of trip units
bb a non-adjustable time delay.
Magnetic protection (Im)
Short-circuit protection with a fixed or adjustable pick-up Im that initiates instantaneous
tripping if exceeded.
bb TM-D: fixed pick-up, Im, for 16 to 250 A ratings and adjustable from 5 to 10 x In for
400 A ratings, 4.2 to 8.3 x In for 600 A rating.
Protection versions
bb 3-pole:
vv 3P 3D: 3-pole frame (3P) with detection on all 3 poles (3D)
bb 4-pole:
vv 4P 3D: 4-pole frame (4P) with detection on 3 poles (3D).
vv 4P 4D: 4-pole frame (4P) with detection on all 4 poles (same threshold for phases
and neutral).

Thermal-magnetic trip units

TM16D to 250D

Ratings (A)

In at 40 C (1)

16 25 32 40 50 63 80 100 125 160 200 250 320 400 500 600

Circuit breaker

TM320D to 600D

CVS100

CVS160

CVS250

CVS400
CVS630

Magnetic protection
Pick-up (A)

Im

fixed

accuracy 20 %

CVS100

190 300 400 500 500 500 640 800

adjustable
800 1250 1250 2000 2500

CVS160/250
CVS400

1600 to 3200 (320A), 2000 to 4000 (400A)

CVS630

2500 to 5000

Thermal protection
Ir = In x ...

adjustable in amps from 0.7 to 1 x In

Unprotected neutral

4P 3D

no detection

Fully protected neutral

4P 4D

1 x Ir

Pick-up (A)
tripping between
1.05 and 1.30 Ir

Neutral protection

(1) For temperatures not equal to 40C, the thermal protection characteristics are modified. See the temperature derating table on page B-2.

Note: All the trip units have a transparent lead-sealable cover that protects access to the adjustment dials.

A-6

Protection of distribution systems


ETS 2.3 electronic trip unit and accessories

DB400166

ETS 2.3 electronic trip unit


440

505

565

630

370

315

8
10

Protection...............................................................................
The protection functions can be set using the adjustment dials.

Overload protection

Long-time protection with an adjustable threshold and fixed tripping delay:


bb Ir base setting (6-position dial from 0.5 to 1)

Short-circuit protection

Short-time and instantaneous protection:


bb short-time protection with an adjustable pick-up and fixed tripping delay
bb instantaneous protection with fixed pick-up.

Protection of the fourth pole

On 4-pole circuit breakers, neutral protection is set using a three-position switch to


4P 3D (neutral unprotected), 4P 3D + N/2 (neutral protection at 0.5 In) or 4P 4D
(neutral protection at In).

Trip units
Ratings (A) of circuit breaker
Circuit breaker

ETS 2.3
In 20 to 70 C
CVS400 F/N
CVS630 F/N

400
b
-

Ir = In x

0.5...1
adj., 6 settings
fixed
90...180
5...7.5
3.2...5.0

Overload protection (Long time)

Current setting
Time delay (s)
(min.max.)

at 1.5 x Ir
at 6 x Ir
at 7.2 Ir

Short-circuit protection (Short time)

Pick-up (A)
accuracy 15 %
Time delay (ms)

Isd = Ir x

max. resettable time


max. break time

2...10
adj, 8 settings
fixed
y 40
y 60

Ii = In x

11

Short-circuit protection (instantaneous)

Pick-up (A)

Protection of the fourth pole

Neutral unprotected
Neutral protection at 0.5 In
Neutral protection at In

Thermal memory

630
b

4P 3D
4P 3D + N/2
4P 4D

no protection
0.5 x Ir
1 x Ir

CVS400 F/N
CVS630 F/N

Yes
Yes

Test equipment for ETS electronic trip unit


Mini test kit
The mini test kit is a portable unit requiring no external power supply, used to check
operation of the electronic trip unit and circuit breaker tripping.
It connects to the test connector on the front of the circuit breaker.
Required power source: five 9 V alkaline batteries (not supplied).
Portable test kit
The portable test kit is used to check all aspects of the protection functions:
bb long time protection
bb short time protection
bb instantaneous protection
bb earth-fault protection.
Required power source: 110 or 220 V AC, 50/60 Hz.
Spare test plug and wiring kit
A spare test plug and wiring kit are available for this offer.
A-7

Functions
and characteristics

Earth-leakage protection

A Vigi module can be added to any three or four-pole


CVS100 to 630 circuit breaker to form a Vigi CVS.

Circuit breaker with add-on Vigi module (Vigi CVS)

Add-on protection against insulation faults using


a Vigi module

PB106449

bb For general characteristics of circuit breakers, see pages A-2 and A-3.
bb Add-on Vigi modules: Earth-leakage protection is achieved by installing a Vigi
module (characteristics and selection criteria on next page) directly on the circuit
breaker terminals. It directly actuates the trip unit (magnetic, thermal-magnetic or
ETS).

Vigi CVS100 to 630 circuit breakers with earthleakage protection


Addition of the Vigi module does not alter circuit-breaker characteristics:
bb compliance with standards
bb degree of protection, class II front-face insulation
bb positive contact indication
bb electrical characteristics
bb trip-unit characteristics
bb installation and connection modes
bb indication, measurement and control auxiliaries
bb installation and connection accessories.

PB103580-36

Vigi CVS100 to 630

Dimensions and weights

CVS100/160/250

CVS400/630

Dimensions

105 x 236 x 86

135 x 355 x 110

3-pole

W x H x D (mm)

4-pole

140 x 236 x 86

180 x 355 x 110

Weight (kg)

3-pole

2.5

8.8

4-pole

3.2

10.8

Vigi earth-leakage protection modules

Compliance with standards


bb IEC 60947-2, annex B.
bb Decree dated 14 November 1988 (for France).
bb IEC 60755, class A, immunity to DC components up to 6 mA
bb operation down to -25 C as per VDE 664.

DB112147

1 Sensitivity setting
2 Time-delay setting (for selective earth-leakage protection).
3 Lead-seal fixture for controlled access to settings.
4 Test button simulating an earth-fault for regular checks on
the tripping function
5 Reset button (reset required after earth-fault tripping).
6 Rating plate

Vigi module selection


Type

Vigi MH

Number of poles

3, 4 (1)

Vigi MB
3, 4 (1)

CVS100

CVS160

CVS250

CVS400

CVS630

Sensitivity

adjustable

adjustable

In (A)

0.03 - 0.3 - 1 - 3 - 10

0.3 - 1 - 3 - 10 - 30

Time delay

adjustable

adjustable

Intentional delay (ms)

0 - 60 (2) - 150 (2) - 310 (2)

0 - 60 - 150 - 310

Max. break time (ms)

< 40 < 140 < 300 < 800

< 40 < 140 < 300 < 800

Rated voltage
V AC 50/60 Hz

200... 440

200...440

Protection characteristics

(1) Vigi 3P modules may also be used on 3P circuit breakers used for two-phase protection.
(2) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.

Operating safety

The Vigi module is a user safety device. It must be tested at regular intervals (every 6
months) via the test button.

A-8

Motor protection

MA instantaneous trip units


3100

2000

2900

DB400006

2700

2450

MA 220
220A/65

2200

MA magnetic trip units for EasyPact CVS100-630A

Circuit breakers with an MA trip unit are combined with a thermal relay and a
contactor or a starter.

E26988

Protection
Magnetic protection (Im)

Short-circuit protection with an adjustable pick-up Im that initiates instantaneous


tripping if exceeded.
bb Im = In x ... is set on an adjustment dial in multiples of the rating:
vv 6 to 14 x In (2.5 to 100 A ratings)
vv 9 to 14 x In (150 to 220 A ratings)
vv 6 to 13 x In (320 to 500 A ratings)
Protection version
bb 3-pole (3P 3D): 3-pole frame (3P) equipped with detection on all 3 poles (3D).

Motor protection up to 250 kW


Motor protection rating (kW)

CVS 100/160/250
CVS 400/630

1.1...110

Breaking
capacity (kA rms)
380/415 V

B
F
N

18.5...250

25
36
-

25
36
-

CVS100 to 630 circuit breakers, equipped with


an MA magnetic trip unit with adjustable thresholds,
offer:
- short-circuit protection
- suitability for isolation.
CVS100 to 630 circuit breakers with trip unit are
supplied ready-assembled.

MA trip units
Ratings (A)

In at 65 C
CVS100

Circuit breaker

2.5

6.3

12.5

25

50

100

150

220

320

500

CVS160

CVS250

CVS400

CVS630

Short-circuit protection (magnetic)


Pick-up (A)
CVS100
CVS160/250
CVS400/630

Im = In x ...

setting
6...14 x ln
-

setting
9...14 x ln
-

setting
6...13 x ln

A-9

Functions
and characteristics

Switch-disconnectors

Characteristics and performance

Installation standards require upstream protection.


However EasyPact CVS100 to 630 NA switchdisconnectors are self-protected by their high-set
magnetic release.

PB106451

Switch-disconnectors

Electrical characteristics as per IEC 60947-3 and EN 60947-3

Conventional thermal current (A)

Ith 50 C

Number of poles
Operational current (A) depending on le
the utilisation category

AC 50/60 Hz
220/240 V
380/415 V
440 V

Short-circuit making capacity


(kA peak)

lcm

Rated short-time withstand current


(A rms)

lcw

Durability (C-O cycles)

mechanical

min. (switch-disconnector alone)


max. (protection by upstream circuit
breaker)
for

1s
3s
20 s

electrical
EasyPact CVS100 to 250 NA

AC
415 V

Protection
Add-on earth-leakage protection

By Vigi module

Additional indication and control auxiliaries


PB106452

Indication contacts
Voltage releases

MX shunt release
MN undervoltage release

Installation/connections
Dimensions (mm)

fixed, front connections

WxHxD
Weight (kg)

3P
4P

fixed, front connections

3P
4P

EasyPact CVS400 to 630 NA

A-10

In

CVS100NA

CVS160NA

CVS250NA

CVS400NA

CVS630NA

100

160

250

400

630

3, 4

3, 4

3, 4

3, 4

3, 4

AC22A / AC23A

AC22A / AC23A

AC22A / AC23A

AC22A / AC23A

AC22A / AC23A

100

160

250

400

630/500

100

160

250

400

630/500

100

160

250

400

630/500

2.6

3.6

4.9

7.1

8.5

75

75

75

105

105

1800

2500

3500

5000

6000

1800

2500

3500

5000

6000

690

960

1350

1930

2320

30000

25000

20000

15000

15000

AC22A / AC23A

AC22A / AC23A

AC22A / AC23A

AC22A / AC23A

AC22A / AC23A

8000

8000

6500

4000

2500

105 x 161 x 86

140 x 255 x 110

140 x 161 x 86

185 x 255 x 110

1.5 to 1.8

5.2

2.0 to 2.2

6.8

A-11

Accessories and auxiliaries

Functions
and characteristics

E-9, E-19

DB400001

Insulation accessories

Overview

Connection

A-14

Cable connectors

Interphase barriers

Sealable terminal
shields

Rear connectors
Terminal
extensions

Electrical auxiliaries

Cable connectors

A-17

Indication contact

Voltage release

Monitoring

A-8

cat.A

Control accessories

A-19

Earth leakage protection


(VigiCVS)
Direct rotary handle

A-12

Extended rotary handle

Accessories and auxiliaries


Device installation

Fixed circuit breakers

DB400011

DB400010

DB400009

Fixed circuit breakers are designed for standard connection using bars or cables with
lugs. Bare-cable connectors are available for connection to bare copper or aluminium
cables.

Mounting on a backplate.

Mounting on rails.

Mounting on DIN rail (with


adaptor).

DB400012

CVS circuit breakers may be installed horizontally,


vertically or flat on their back, without derating
performance levels.

Mounting on a Prisma
mounting plate.

A-13

Accessories and auxiliaries

Functions
and characteristics

Connection of devices

DB400013

DB112169

Fixed circuit breakers are designed for standard front


connection using bars or cables with lugs.
Cable connectors are available for bare cables. Rear
connection is also possible.

Front connection
Bars or cables with lugs
Standard terminals
EasyPact CVS100 to 630 come with terminals comprising snap-in nuts with screws:
bb EasyPact CVS100: M6 nuts and screws.
bb EasyPact CVS160/250: M8 nuts and screws
bb EasyPact CVS400/630: M10 nuts and screws.
These terminals may be used for:
bb direct connection of insulated bars or cables with lugs
bb terminal extensions.
Interphase barriers or terminal shields are recommended. They are mandatory for
certain connection accessories (in which case the interphase barriers are provided).
Bars
When the switchboard configuration has not been tested, insulated bars are
mandatory.

Insulated bar.
DB112170

Maximum size of bars

EasyPact CVS circuit breaker


Without spreaders
With spreaders
Small lug for copper cables.

DB112171

DB112177

DB112173

DB112172

100/160/250

400/630

35
20 x 2
45
32 x 2

45
32 x 6
52.5
40 x 6

Crimp lugs
There are two modules of lugs, for aluminium and copper cables.
Interphase barriers or long terminal shields must be used with narrow lugs. The lugs
are supplied with interphase barriers.
Small lug for Al cables.

Straight terminal
extensions.

pitch (mm)
maximum bar size (mm)
pitch (mm)
maximum bar size (mm)

Right-angle
terminal extensions

Spreaders.

EasyPact CVS circuit breaker


Copper cables
size (mm)
crimping
Aluminium cables
size (mm)
crimping

100/160/250
400/630
150, 185
240, 300
hexagonal barrels or punching
150, 185
240, 300
hexagonal barrels

Terminal extensions
Extensions with anti-rotation ribs can be attached to the standard terminals to
provide numerous connection possibilities in little space:
bb straight terminal extensions
bb right-angle terminal extensions
Spreaders
Spreaders may be used to increase the pitch:
bb CVS100 to 250: the 35 mm pitch can be increased to 45 mm
bb CVS400/630: the 45 mm pitch can be increased to 52 or 70 mm.
Bars, cable lugs or cable connectors can be attached to the ends.
Pitch (mm) depending on the type of spreader
EasyPact CVS circuit breaker
Without spreaders
With spreaders

A-14

CVS100 to 250
35
45

CVS100 to 630
45
52.5 or 70

Accessories and auxiliaries


Connection of devices

DB400014

DB112314

Bare cables

Bare-cable connectors may be used for both copper and aluminium cables.
1-cable connectors for EasyPact CVS100 to 250
The connectors snap directly on to the device terminals or are secured by clips to
right-angle and straight terminal extensions as well as spreaders.
1-cable connectors for EasyPact CVS400 to 630
The connectors are screwed directly to the device terminals.

Bare cable.

2-cable connectors for EasyPact CVS100 to 250 and 400/630


The connectors are screwed to device terminals or right-angle terminal extensions.
Maximum size of cables depending on the type of connector

Four positions.

DB111330

DB400015

1-cable
2-cable
connector for
connector for
CVS100 to 250 CVS400/630. CVS100 to 250

100/160 250
1.5 to 95 mm

Aluminium connectors

25 to 95 mm

120 to 185 mm

2 cables 50 to 120 mm

DB111326

DB112317

DB112316

DB112315

EasyPact CVS circuit breaker


Steel connectors

400

630

2 cables 35 to 240 mm

35 to 300 mm

CVS400/630.

Two lengths.

Rear connection

Device mounting on a backplate with suitable holes enables rear connection.

Bars or cables with lugs

Rear connections for bars or cables with lugs are available in two lengths. Bars may
be positioned flat, on edge or at 45 angles depending on how the rear connections
are positioned.
The rear connections are simply fitted to the device connection terminals. All
combinations of rear connection lengths and positions are possible on a given
device.

A-15

Accessories and auxiliaries

Functions
and characteristics

Selection of auxiliaries

DB115583

EasyPact CVS100/160/250

Standard

Rotary handle

OF1
MN /
MX

OF2
SDE

SDV

All EasyPact CVS100/160/250 circuit breakers and switch-disconnectors have slots


for the electrical auxiliaries listed below.
5 indication contacts (see page A-17)
bb 2 ON/OFF (OF1 and OF2)
bb 1 trip indication (SD)
bb 1 fault-trip indication (SDE)
bb 1 earth-fault indication (SDV), when the device is equipped with a Vigi module.
1 remote-tripping release (see page A-18)
bb either 1 MN undervoltage release
bb or 1 MX shunt release.

All these auxiliaries can be installed with a rotary handle.


The illustration shown (TMD, MA, NA standard) indicates auxiliary possibilities
depending on the type of trip unit.

DB115590

EasyPact CVS400/630

Standard

Rotary handle

OF1
OF2
OF3
Reserved
MN /
MX

SD
SDE

SDV

A-16

All EasyPact CVS400/630 circuit breakers and switch-disconnectors have slots for
the electrical auxiliaries listed below.
6 indication contacts (see page A-17)
bb 3 ON/OFF (OF3)
bb 1 trip indication (SD)
bb 1 fault-trip indication (SDE)
bb 1 earth-fault indication (SDV), when the device is equipped with a Vigi module.
1 remote-tripping release (see page A-18)
bb either 1 MN undervoltage release
bb or 1 MX shunt release.
All these auxiliaries can be installed with a rotary handle.
The illustration shown (TMD, MA, NA and ETS 2.3 standard) indicates auxiliary
possibilities depending on the type of trip unit.

Accessories and auxiliaries


Indication contacts

One contact model provides circuit-breaker status


indications (OF - SD - SDE - SDV).

These common-point changeover contacts provide remote circuit-breaker status


information.
They can be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.

DB125549

Functions

Indication contacts.

Breaker-status indications, during normal operation or after a fault


A single type of contact provides all the different indication functions:
bb OF (ON/OFF) indicates the position of the circuit breaker contacts
bb SD (trip indication) indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
vv an earth fault (Vigi)
vv operation of a voltage release
vv operation of the push to trip button
vv disconnection when the device is ON.
The SD contact returns to de-energised state when the circuit breaker is reset.
bb SDE (fault-trip indication) indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
vv an earth fault (Vigi)
bb SDV indicates that the circuit breaker has tripped due to an earth fault. It returns
de-energised state when the Vigi module is reset.

Installation

bb OF, SD, SDE and SDV functions: a single type of contact provides all these
different indication functions, depending on where it is inserted in the device. The
contacts clip into slots behind the front cover of the circuit breaker (or the Vigi module
for the SDV function).
The SDE function on a CVS100 - 630 A equipped with a magnetic, thermal-magnetic
or ETS2.3 trip unit requires the SDE adaptor.

Electrical characteristics of auxiliary contacts


Contacts

Standard

Types of contacts

All

OF, SD, SDE, SDV

Rated thermal current (A)

Minimum load

100 mA at 24 V DC

1 mA at 4 V DC

Utilisation cat. (IEC 60947-5-1)

AC12 AC15 DC12 DC14

Operational 24 V
current (A)
48 V
110 V

Low level

AC12 AC15 DC12 DC14

AC/DC 6

AC/DC 6

2.5

0.2

2.5

0.2

AC/DC 6

0.6

0.05

2.5

0.6

0.05

220/240 V AC

250 V

DC

0.3

0.03

0.3

0.03

380/440 V AC

1.5

A-17

Accessories and auxiliaries

Functions
and characteristics

Remote tripping

DB125550

MN undervoltage release

bb This release trips the circuit breaker when the control voltage drops below a
tripping threshold
bb The tripping threshold is between 0.35 and 0.7 times the rated voltage
bb Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated
voltage.
Characteristics

DB115605

MX or MN voltage release.

Failsafe opening Possible opening


0

0.35

0.7

1.1 Un

DB115606

Opening conditions of the MN release.


Failsafe closing
0

0.85

1.1 Un

PB103752-32

DB115607

Closing conditions of the MN release.

Delayed
trip order

Time-delay
unit
Instantaneous
trip order

10

12

V AC

Operating threshold

V DC
Opening
Closing

Operating range
Consumption (VA or W)
Response time (ms)

50/60 Hz: 24 - 48 - 100/130 - 200/240


50 Hz: 380/415
60 Hz: 208/277
12 - 24 - 30 - 48 - 60 - 125 -250
0.35 to 0.7 Un
0.85 Un
0.85 to 1.1 Un
Pick-up: 10 - Hold: 5
50

Time-delay unit for an MN release


A time delay unit for the MN release eliminates the risk of nuisance tripping due to
a transient voltage dip lasting y 200 ms. For shorter micro-outages, a system of
capacitors provides temporary supply to the MN at U > 0.7 to ensure non tripping.
The correspondence between MN releases and time-delay units is shown below.
Power supply
Unit with fixed delay 200 ms
48 V AC
220 / 240 V AC
Unit with adjustable delay y 200 ms
48 - 60 V AC/DC
100 - 130 V AC/DC
220 - 250 V AC/DC

Corresponding MN release
48 V DC
250 V DC
48 V DC
125 V DC
250 V DC

MX shunt release

The MX release opens the circuit breaker via an impulse-type (u 20 ms) or


maintained order.

D2

Opening conditions
When the MX release is supplied, it automatically opens the circuit breaker. Opening
is ensured for a voltage U u 0.7 x Un.

MN

Characteristics

D1
MN release with a time-delay
unit.

Power supply

Power supply

Wiring diagram for


emergency-off function with
MN + time-delay unit.

V AC
V DC

Operating range
Consumption (VA or W)
Response time (ms)

50/60 Hz: 24 - 48 - 100/130 - 200/240


50 Hz: 380/415
60 Hz: 208/277
12 - 24 - 30 - 48 - 60 - 125 -250
0.7 to 1.1 Un
Pick-up: 10
50

DB115608

Circuit breaker control by MN or MX


Possible opening

Failsafe opening

0
0.7
Opening conditions of the MX release.

1.1

Un

Note: circuit breaker opening using an MN or MX release must


be reserved for safety functions. This type of tripping increases
wear on the opening mechanism. Repeated use reduces the
mechanical endurance of the circuit breaker by 50 %.

A-18

When the circuit breaker has been tripped by an MN or MX release, it must be reset
before it can be reclosed.
MN or MX tripping takes priority over manual closing.
In the presence of a standing trip order, closing of the contacts, even temporary, is
not possible.
Connection using wires up to 1.5mm2 to integrated terminal blocks.

Accessories and auxiliaries


Rotary handles

PB106453

There are two types of rotary handle:


b direct rotary handle
b extended rotary handle.

Direct rotary handle


Standard handle

Degree of protection IP40, IK07.


The direct rotary handle maintains:
bb visibility of and access to trip-unit settings
bb suitability for isolation
bb indication of the three positions O (OFF), I (ON) and tripped
bb access to the "push to trip" button.
Device locking
The rotary handle facilitates circuit-breaker locking.
bb Padlocking:
vv standard situation, in the OFF position, using 1 to 3 padlocks, shackle diameter 5 to
8 mm, not supplied

EasyPact CVS with a rotary handle.

PB106454

Extended rotary handle

Degree of protection IP56, IK08.


The extended rotary handle makes it possible to operate circuit breakers installed at
the back of switchboards, from the switchboard front.
It maintains:
bb visibility of and access to trip-unit settings
bb suitability for isolation
bb indication of the three positions O (OFF), I (ON) and tripped.
Device and door padlocking
Padlocking locks the circuit-breaker handle and disables door opening:
bb standard situation, in the OFF position, using 1 to 3 padlocks, shackle diameter 5
to 8 mm, not supplied

PB106455

EasyPact CVS with an extended rotary handle installed at the


back of a switchboard, with the keylock option and key.

Parts of the extended rotary handles


bb A unit that replaces the front cover of the circuit breaker (secured by screws).
bb An assembly (handle and front plate) on the door that is always secured in the
same position, whether the circuit breaker is installed vertically or horizontally.
bb An extension shaft that must be adjusted to the distance. The min/max distance
between the back of circuit breaker and door is:
vv 185600 mm for EasyPact CVS100 to 250
vv 209600 mm for EasyPact CVS 400/630.

Manual source-changeover systems

PB106456

An additional accessory interlocks two devices with rotary handles to create a


source-changeover system. Closing of one device is possible only if the second is
open.
This function is compatible with direct or extended rotary handles.
Up to three padlocks can be used to lock in the OFF or ON position.

A-19

DB400026

DB400025

Functions
and characteristics

Toggle locking using padlocks and an accessory:


Fixed device attached to the
Removable device
case.

Accessories and auxiliaries


Locks and sealing accessories

Locks

Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking
systems can receive up to three padlocks with shackle diameters ranging from 5 to
8 mm (padlocks not supplied). Certain locking systems require an additional
accessory.
Control device

Function

Means Required accessories

Toggle

Lock in OFF position

Padlock Removable device

Lock in OFF or ON
position

Padlock Fixed device

Direct rotary
handle

Standard Lock in
b OFF position
b OFF or ON position (1)

Extended rotary handle

DB400027

Removable device

Padlock Keylock Locking device + keylock

Lock in
b OFF position
b OFF or ON position (1)
with door opening
prevented (2)

Padlock -

Lock in OFF position

Padlock UL508 control accessory

b OFF or ON position (1)

Keylock Locking device + keylock

inside the switchboard

(1) Following a simple modification of the mechanism.


(2) Unless door locking has been voluntarily disabled.

DB400029

Rotary-handle locking using a padlock or a keylock.

Sealing accessories

Rotary handle

DB400018

Sealing accessories.

Access to Vigi-module
settings

DB400019

DB115033

Toggle control

Types of seals
Protected operations

A-20

DB400017

DB400028

Rotary-handle locking using a keylock.

Protection cover for


settings
bb modification of settings.

Accessories and auxiliaries


Escutcheons and protection collars

IP40 escutcheons for fixed devices

Escutcheons are an optional feature mounted on the


switchboard door. They increase the degree of
protection to IP40, IK07. Protection collars maintain the
degree of protection, whatever the position of the
device (connected, disconnected).

DB400030

DB400031

There are three types of escutcheon with a gasket which are screwed to the door
cut-out:
bb three escutcheons for all control types (toggle, handle or motor mechanism)
bb a wide model for Vigi modules that can be combined with the above.

DB400032

Escutcheon for toggle without and with access to the trip unit.

Escutcheon for Vigi module.

A-21

Installation
recommendations

B-2

EasyPact CVS

Installation recommendations
Contents

Functions and characteristics

A-1

Operating conditions and temperature derating

B-2

Installation in switchboards
Power supply and weights

B-3

Safety clearances and minimum distances

B-4

Installation example

B-5

Dimensions and connection


Additional characteristics
Catalogue numbers

C-1
D-1
E-1

B-1

Operating conditions and temprature


derating

Installation
recommendations

When thermal-magnetic trip units are used at ambient


temperatures other than 40 C, the Ir pick-up is
modified.
DB400035

(m)
2000

Altitude derating

Altitude does not significantly affect the characteristics of EasyPact CVS circuit
breakers up to 2000 m. Above this altitude, it is necessary to take into account the
decrease in the dielectric strength and cooling capacity of air.

Vibrations

CVS devices resist electromagnetic or mechanical vibrations.


Tests are carried out in compliance with standard IEC 60068-2-6 for the levels
required by merchant-marine inspection organisations (Veritas, Lloyds, etc.):
bb 2 to 13.2 Hz: amplitude 1 mm
bb 13.2 to 100 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to
mechanical parts.

Degree of protection

CVS circuit breakers have been tested for degree of protection (IP) and mechanical
impact protection (IK). See page A-3.

DB115053

Electronic trip units are not affected by variations in


temperature. If the trip units are used in hightemperature environments, the ETS setting must
nevertheless take into account the temperature limits
of the circuit breaker.
(A)
110

Settings of CVS100 to 630 equipped with TM-D trip units as a


function of the temperature

100

The table indicates the real Ir (A) value for a given rating and temperature.

90

Rat. Temperature (C)


(A) 10
15
20
25

45

50

55

60

16

18.4

18

18

18

17

16.6

16

15.6

15.2

14.8

14.5

14

13.8

25

28.8

28

27.5

27

26.3

25.6

25

24.5

24

23.5

23

22

21

32

36.8

36

35.2

34.4

33.6

32.8

32

31.3

30.5

30

29.5

29

28.5

40

46

45

44

43

42

41

40

39

38

37

36

35

33.5

50

57.5

56

55

54

53

51

50

49

47

46

44

43

41

63

73

72

70

68

67

65

63

61

59

57

55

53

50

80

92

90

88

86

84

82

80

78

75.5

73

70.7

68

65

100 114

112

110

107

105

102.5 100

97

95

92.0

89

86

83

500

125 144

141

138

134

131

128

125

122

119

116

113

109

106

200

160 184

180

176

172

168

164

160

156

152

148

144

140

136

50

200 230

225

220

215

210

205

200

195

190

185

180

175

170

20

250 288

281

277

269

263

256

250

244

238

231

225

219

213

320 365

358

350.5 343

335.6 328

320

312

303.6 295

286

277

267.7

400 456.6 447.7 438.6 429

419.7 410

400

390

379.3 368.5 357.3 345.8 334

80

10

20

30

40

50

70 (C)

60

10 000
5 000

DB400102

DB400102

Temperature derating curve for CVS100.

2 000
1 000

100

10
5

t(s)

TM80D : Im = 10 x In

1
.5
.2

TM100D : Im = 10 x In

.02
.01

637

35

40

520.3 510.2 500

489.6 479

468

625

587

560.6 547

612.6 600

574

457

65

3 4 5 7 10

20 30

50 70 100

200 300

532.7 518

Thermal-protection curve with minimum and maximum

The table below indicates the maximum long-time (LT) protection setting Ir (A)
depending on the ambient temperature.
Type of
Rating (A) Temperature (C)
device
40
45
50
55
60
65
70
CVS400
Fixed
CVS630
Fixed

70

445.4 433.6

CVS400 and 630 (equipped with ETS2.3 electronic trip unit)


2

I / Ir

values.

539.7 530

660.5 649

30

t < 10 ms

.005
.002
.001
.5 .7 1

500 558.6 549


600 672

.1
.05

B-2

The overload protection is calibrated at 40 C in the lab. This means that when the
ambient temperature is less than or greater than 40 C, the Ir protection pick-up is
slightly modified.
To obtain the tripping time for a given temperature:
bb see the tripping curves for 40 C (see pages D-2 and D-3)
bb determine tripping times corresponding to the Ir value (thermal setting on the
device), corrected for the ambient temperature as indicated in the tables below.

400

400

400

400

390

380

370

360

630

630

615

600

585

570

550

535

Installation in switchboards

DB400038

Power supply and weights

Power supply from the top or bottom

CVS circuit breakers can be supplied from either the top or the bottom, even when
equipped with a Vigi earth-leakage protection module, without any reduction in
performance. This capability facilitates connection when installed in a switchboard.
All connection and insulation accessories can be used on circuit breakers supplied
either from the top or bottom.

Weight

The table below presents the weights (in kg) of the circuit breakers and Vigi module.
Type of device

Circuit breakers
CVS with
TM-D

CVS100

CVS160

CVS250

CVS400

CVS630

Vigi module

CVS with
ETS

3P 3D

1.64

0.87

4P 4D

2.01

1.13

4P 3D

2.01

3P 3D

1.60

0.87

4P 4D

2.08

1.13

4P 3D

2.08

3P 3D

1.79

0.87

4P 4D

2.39

1.13

4P 3D

2.39

3P 3D

4.37

4.71

2.8

4P 4D

5.83

6.32

4P 3D

2.39

3P 3D

4.80

5.24

2.8

4P 4D

6.40

7.14

4P 3D

2.39

B-3

Installation in switchboards

Installation
recommendations

Safety clearances and minimum distances

General rules

When installing a circuit breaker, minimum distances (safety clearances) must


be maintained between the device and panels, bars and other protection devices
installed nearby. These distances, which depend on the ultimate breaking capacity,
are defined by tests carried out in accordance with standard IEC 60947-2.
If installation conformity is not checked by type tests, it is also necessary to:
bb use insulated bars for circuit-breaker connections
bb segregate the busbars using insulating screens.
For CVS100 to 630 devices, terminal shields and interphase barriers are
recommended and may be mandatory depending on the operating voltage of the
device and type of installation (fixed, withdrawable, etc.).

Power connections

The table below indicates the rules to be respected for CVS100 to 630 devices to
ensure insulation of live parts for fixed devices.

CVS100 to 630: rules to be respected to ensure insulation of live parts


Fixed, rear
connection

operating voltage

Long terminal
shields (1)
DB115060

With:

y 440 V

Interphase
barriers
DB115059

Possible, recommended or mandatory accessories: No insulating


accessory

DB400040

Fixed, front connection

DB400039

Type of connection

Short terminal
shields
DB115061

type of conductor

Insulated bars

Extension terminals
Cables + crimp lugs
Bare cables +
connectors

Possible

Possible

Possible

Recommended

No

Mandatory
(supplied)

Possible
(instead of ph.
barriers)

Recommended

Possible for
Possible for
Possible for
CVS100 to 250 CVS100 to 250 CVS100 to 250
No

Mandatory
(supplied)

Possible
(instead of ph.
barriers)

Recommended

(1) Long terminal shields provide a degree of protection of IP40 (ingress) and IK07 (mechanical
impact).

B-4

Installation in switchboards
Installation example

Safety clearance

DB400047

Minimum distance between circuit


breaker and front or rear panels

DB400046

Minimum distance between two


adjacent circuit breakers

Front
panel

A1

B=0
Bare or painted sheet metal

Note: if F < 8 mm: an insulating screen or long


terminal shield is mandatory.

D1

D2

DB400050

DB400049

DB400048

Minimum distance between circuit breaker and top, bottom or side panels

D1

D1

C1

Devices without accessories.

Devices with interphase barriers or long terminal shields.

Minimum safety clearances for CVS100 to 630


Insulation, insulated bars Bare sheetmetal
Dimensions (mm)
or painted sheet metal
Compact circuit
breaker

CVS100-250 U 440V
CVS400-630 U 440V

DB400051

Spacing y 60 mm

C1

D1

D2

C1

D1

D2

A1

0
0

30
30

30
30

5
5

35
60

35
60

0
0

Spacing > 60 mm
Bars

F1

Clearances with respect to live bare busbars

F1

Minimum clearances for CVS100 to 630


Operating voltage

F2

Clearances with respect to live bare busbars


spacing y 60 mm
spacing > 60 mm

F1
F2
F1
F2
U < 440 V
350
350
80
80
These clearances can be reduced for special installations as long as the configuration is checked
by tests.

F2
Bars

Live busbars.

B-5

Dimensions and connection

C-2

EasyPact CVS

Dimensions and connection


Contents

Functions and characteristics


Installation recommendations

A-1
B-1

Dimensions and mounting

C-2

EasyPact CVS100 to 630

C-2

Vigi CVS100 to 630

C-3

Front-panel accessories
EasyPact CVS100 to 630

Front-panel cutouts

C-4
C-4

C-5

EasyPact CVS100 to 630

C-5

Vigi CVS100 to 630

C-6

Power connections
EasyPact and Vigi CVS100 to 630

C-7
C-7

Connection of insulated bars or cables with lugs to EasyPact and Vigi


CVS100 to 630

C-10

Connection of bare cables to EasyPact and Vigi CVS100 to 630

C-11

Additional characteristics
Catalogue numbers

D-1
E-1

C-1

Dimensions and mounting

Dimensions and
connection

EasyPact CVS100 to 630

A3
A

A1

A4

A2
X

X
A2
A3

B1

C3

Interphase barriers.
Short terminal shields.

A4

C1
C2
Z

DB400058

4P

DB400057

DB400056

3P

DB400055

Dimensions

B
B2

Y
Y
Long terminal shields (also available for CVS400/630 spreaders with 52.5 mm pitch:
B1 = 157.5 mm, B2 = 210 mm).

CVS400/630

CVS100 to 630

3P

3P

4P

F1

F1

F2

F1

F1

E4
E2
E1

F1

DB112066

DB400059

F1

DB112067

CVS100 to 250

On backplate

DB111411

Mounting

F2

F1

F1 F1
F3

F2

E3

2 6

T(1)

4 6

4 6

(1) The T holes are required for rear connection only.

F1

DB400063

4P

F2

F1

DB112070

3P
DB112069

3P
DB111412

On rails

F2

F3

F2

U
X

E2
E1

2 6

DB400169

DB400168

On DIN rail with adaptor plate (CVS100 to 250)


G4

G5

G3

G2
G1
Z

C-2

4 6

4 6

Dimensions and mounting


Vigi CVS100 to 630

3/4P

CVS100 to 250

DB400070

DB400068

DB400069

3/4P

DB400067

Dimensions

CVS400/630

A4
A3
A2

A6
A5

A8
A7

A9

C1
C2
C3

B1
B2

B1
B2
Y

Mounting

CVS100 to 250

CVS400/630

CVS100 to 630

On backplate

3P

3P

4P

E1

F1

F2

F3

X
E6

F1 F1

DB112079

DB112078

DB400071

DB111420

F1 F1
F2
F1

F1 F1
F2
F1

E8

E5

E7

T(1)

6 6

3 6

6 6

(1) The T holes are required for rear connection only.

F1

DB400075

4P

F2

F1

F3

DB112082

3P
DB112081

3P
DB111421

On rails

F2

F2

E6

X
E1

E5

3 6

Y
Type
CVS100/160/250
CVS400/630
Type
CVS100/160/250
CVS400/630

A
80.5
127.5
E2
125
200

A1
161
255
E3
70
113.5

A2
94
142.5
E4
140
227

A3
145
200
E5
137.5
200

A4
178.5
237
E6
200
300

A5
155.5
227.5
E7
145
213.5

A6
236
355
E8
215
327

A7
169
242.5
F1
35
45

A8
220
300
F2
17.5
22.5

A9
253.5
337
F3
70
90

6 6

B
52.5
70
G1
95
-

B1
105
140
G2
75
-

B2
140
185
G3
13.5
-

C1
81
95.5
G4
23
-

C2
86
110
G5
17.5
-

C3
126
168
T
24
32

6 6

E1
62.5
100
U
y 32
y 35

C-3

Front-panel accessories

Dimensions and
connection

EasyPact CVS100 to 630

IP40 front-panel escutcheons


E21643

E21642

DB400041

E21641

For toggle

M3

M2

D1

A1

D2

DB115012

DB400089

DB115010

DB115011

For rotary handle or module and protection collar

A2

B1
Y

A3

3.5

6.5

DB115020

DB115019

DB400097

DB115018

For Vigi

79 X

64

3.5

69
Y

Type
CVS100/160/250
CVS400/630

C-4

A1
91
123

A2
114
164

A3
101
151

B1
157
189

M2
115
155

6.5

M3
102
142

Front-panel cutouts
EasyPact CVS100 to 630

Bare sheet metal

CVS100 to 250

CVS400/630
DB400117

DB400116

DB400034

DB400115

For toggle

76

29

P3

41.5

R1

116

R1

DB400121

DB400120

DB400119

DB400118

For toggle with access to trip unit

P3

175

P3
88
112

90

63.5

47.5

127

95
Y

Type
CVS100/160/250
CVS400/630

102
54.5

R
14.5
31.5

R1
29
63

C-5

Front-panel cutouts

Dimensions and
connection

Vigi CVS100 to 630

Bare sheet metal

CVS100 to 250

CVS400/630
DB400125

DB400124

DB400123

DB400122

For toggle

X
85.5

148

38
38
P3

14.5
29
Y

29
32
Y

DB400129

DB400128

DB400127

DB400126

For toggle with access to trip unit

85.5
148

38

P3
Z

38

14.5
29
Y

29
32
Y

C-6

Power connections

EasyPact and Vigi CVS100 to 630

Connection locations
B1

DB400135

DB400134

C1

B1

B1

A1

A2
A3

C2
Z
Type
CVS100/160
CVS250
CVS400/630

A1
70
70
113.5

A2
140
140
227

B1
35
35
45

C1
19.5
21.5
26

C2
19.5
19.5
26

Type
CVS100/160 + Vigi
CVS250 + Vigi
CVS400/630 + Vigi

A1
70
70
113.5

A3
215
215
327

B1
35
35
45

C1
19.5
21.5
26

C2
21.5
21.5
26

Front connection without accessories


CVS400/630
DB400138

DB400137

DB400136

CVS100 to 250
Z

10.5

14

70

113.5
X

X
Cables with lugs/bars

Bars/cables with lugs

Connection with accessories


Long and short rear connectors
DB116107

CVS100 to 250

10

DB400137

43 for short RC
88 for long RC
8.6

13
18
70

20

DB116108

CVS400/630
50 for short RC
115 for long RC
15
30

13

23.2

14

113.5
8
X

C-7

Power connections

Dimensions and
connection

EasyPact and Vigi CVS100 to 630

Connection with accessories (cont.)


CVS100 to 250

DB115452

DB400138

DB115451

Bare-cable connectors

63

22

70

70
DB400139

X
DB115455

DB115454

CVS400/630
Z

Z
46.5

14

113.5

113.5
X

Distribution connectors (for CVS100 to 250 only)


DB115456

DB115457

X
70

41

(a) Vigi module


or CVS250.
Z

64.5
66.5 (a)

Right-angle terminal extensions (upstream only)


Z

CVS400/630

37.5
39.5 (b)

DB115460

DB400140

DB115459

CVS100 to 250
4

DB115462

DB400141

34

70

113.5
X

Straight terminal extensions (for CVS100 to 250 only)


4
Z
41

70
X

C-8

61

20.5

(b) CVS250.

30

Power connections

EasyPact and Vigi CVS100 to 630

Connection with accessories (cont.)


Spreaders

3P

4P

E2

F2

E3
E2

E2

DB400145

E2

DB400144

DB400143

DB400142

CVS100 to 250
E1

E2

C3

F1

X
Z

CVS400/630
Y

C4

Type

C3

C4

E1

E2

E3

F1

F2

CVS100/160

23.5

114

45

159

100

11

CVS250

25.5

114

45

159

100

11

CVS400/630

44

135
170

52.5
70

187.5
240

152.5
166

15
15

X
Z

C-9

Power connections

Dimensions and
connection

Connection of insulated bars or cables with lugs


to EasyPact and Vigi CVS100 to 630

DB400013

DB115653

Direct connection to CVS100 to 630


400
I

Bars

L (mm)
I (mm)
d (mm)
e (mm)
(mm)
L (mm)
(mm)

d
L
e

Lugs

DB115654

Bar.

Dimensions

Torque (Nm) (1)


Torque (Nm) (2)

CVS100

CVS160/250

CVS400/630

y 25
d + 10
y 10
y6
6.5
y 25
6.5
10
5/5

y 25
d + 10
y 10
y6
8.5
y 25
8.5
15
5/5

y 32
d + 15
y 15
3 y e y 10
10.5
y 32
10.5
50
20/11

(1) Tightening torque on the circuit breaker for lugs or bars.


(2) Tightening torque on fixed devices for rear connectors.
L
Lug.

Connection with accessories to CVS100 to 250 (IEC 228)


Pole pitch
Without spreaders
With spreaders
Dimensions

Accessories for CVS100 to 250

Spreaders:
separate parts

L (mm)
l (mm)
d (mm)

e (mm)
(mm)
Lugs
L (mm)
(mm)
Torque (Nm) (1)

CVS100

CVS160/250

y 25
20 y I y 25
y 10
y6
6.5
y 25
6.5
10

y 25
20 y I y 25
y 10
y6
8.5
y 25
8.5
15

DB112177

(1) Tightening torque on the circuit breaker for spreaders or terminal extensions.

Spreaders and straight, right-angle, 45, double-L and edgewise terminal extensions
are supplied with flexible interphase barriers.

Connection with accessories to CVS400 and 630 (IEC 228)

Accessories for CVS400 and 630

Pole pitch

Spreaders made up of separate parts for 52.5 and


70 mm pitch

Without spreaders

45 mm

With spreaders

52.5 or 70 mm

Dimensions
Bars

DB115655

DB115657

d
e

Tinned copper

Tinned copper

400
I

Accessories for CVS100 to 630


Right-angle terminal extensions

d
L
e

Lugs

L (mm)
l (mm)
d (mm)
e (mm)
(mm)

With spreaders

With terminal extensions

y 40
d + 15
y 20
3 y e y 10
12.5

y 32
30 y I y 34
y 15
3 y e y 10
10.5

L (mm)

y 40

y 32

(mm)

12.5

10.5

50

50

Torque (Nm) (1)

(1) Tightening torque on the circuit breaker for spreaders or terminal extensions.
Tinned copper
To be mounted on upstream
side.

Spreaders and right-angle, 45 and edgewise terminal extensions are supplied with
flexible interphase barriers.
DB115658

DB112173

400

Tinned copper

35 mm
45 mm
With spreaders or terminal extensions
Bars

DB115655

DB112172

Straight terminal
extensions

Mounting detail: 2 cables


with lugs.

C-10

Power connections

DB112315

DB112317

Connection for CVS100 to 250

DB115663

1-cable
connector

2-cable
connector
1-cable connector

Steel
y 160 A

Aluminium
y 250 A

L (mm)

25

25

S (mm) Cu/Al

1.5 to 95 (1)

25 to 50

70 to 95

120 to 185
150 max. flex.

Torque (Nm)

12

20

26

26

2-cable connector

L (mm)

25 or 50

S (mm) Cu/Al

2 x 50 to 2 x 120

Torque (Nm)

22

(1) For flexible cables from 1.5 to 4 mm, connection with crimped or self-crimping ferrules.

DB112316

DB111326

Connection to CVS400 and 630

1-cable connector

DB115663

DB400149

Connection of bare cables to EasyPact and


Vigi CVS100 to 630

2-cable connector
1-cable connector

2-cable connector

L (mm)

30

30 or 60

S (mm) Cu/Al

35 to 300 rigid
240 max. flex.

2 x 35 to 2 x 240 rigid
240 max. flex.

Torque (Nm)

31

31

Conductor materials and electrodynamic stresses

EasyPact CVS circuit breakers can be connected indifferently with bare-copper,


tinned-copper and tinned-aluminium conductors (flexible or rigid bars, cables).
In the event of a short-circuit, thermal and electrodynamic stresses will be exerted on
the conductors. They must therefore be correctly sized and held in place by supports.
Electrical connection points on switchgear devices (switch-disconnectors,
contactors, circuit breakers, etc.) should not be used for mechanical support.
Any partition between upstream and downstream connections of the device must be
made of non-magnetic material.

C-11

Additional characteristics

D-2

EasyPact CVS

Additional characteristics
Contents

Functions and characteristics


Installation recommendations
Dimensions and connection

A-1
B-1
C-1

Tripping curves
EasyPact CVS100 to 630 Protection of distribution systems

D-2

EasyPact CVS100 to 250 Motor protection

D-5

Current and energy limiting curves

D-6

Catalogue numbers

E-1

D-1

Tripping curves

Additional characteristics

EasyPact CVS100 to 630


Protection of distribution systems

TM magnetic trip units


TM16D/25D

TM32D
DB400095

DB400094

10 000
5 000

10 000
5 000

2 000

2 000

1 000

1 000

500

500

200

200

100

100

50

50

20

20

10
t(s)

10

t(s)

TM16D/25D : Im = 12 x In

.5

.2

.2

.1
.05

.1
.05

.02
.01

.02
.01

t < 10 ms

.005

3 4 5 7 10

20 30

50 70 100

.002
.001
.5 .7 1

200 300

I / Ir

DB400101

DB400096

3 4 5 7 10

20 30

50 70 100

200 300

TM63D

10 000
5 000

10 000
5 000

2 000

2 000

1 000

1 000

500

500

200

200

100

100

50

50

20

20

10

10

t(s)

TM40D : Im = 12.5 x In

1
.5

5
2

TM63D : Im = 8 x In

1
.5

TM50D : Im = 10 x In

.2

.1
.05

.1
.05

.02
.01
.002
.001
.5 .7 1

.02
.01

t < 10 ms

.005

3 4 5 7 10
I / Ir

D-2

I / Ir

TM40D/50D

.2

t < 10 ms

.005

.002
.001
.5 .7 1

t(s)

TM32D : Im = 12.5 x In

.5

20 30

50 70 100

t < 10 ms

.005

200 300

.002
.001
.5 .7 1

3 4 5 7 10
I / Ir

20 30

50 70 100

200 300

Tripping curves

EasyPact CVS100 to 630


Protection of distribution systems
TM magnetic trip units (cont.)
TM125D/160D

10 000
5 000

DB400103

DB400102

TM80D/100D

10 000
5 000

2 000

2 000

1 000

1 000

500

500

200

200

100

100

50

50

20

20

10
t(s)

10

t(s)

TM80D/100D : Im = 8 x In

5
2
.5

.2

.2

.1
.05

TM160D : Im = 8 x In

.1
.05

.02
.01

.02
.01

t < 10 ms

.005
.002
.001
.5 .7 1

TM125D : Im = 10 x In

.5

3 4 5 7 10

20 30

50 70 100

.002
.001
.5 .7 1

200 300

I / Ir

10 000
5 000

DB400106

10 000
5 000

DB400104

TM320D/400D

2 000

2 000

1 000

1 000

500

500

200

200

100

100

50

50

20

20

10

10

t(s)

TM200D/250D :
Im = 10 x In

1
.5

3 4 5 7 10

20 30

50 70 100

200 300

5
2
.5
.2

.1
.05

.1
.05

.02
.01

.02
.01

t < 10 ms

.005

TM320D/400D :
Im = 5...10 x In

.2

.002
.001
.5 .7 1

I / Ir

TM200D/250D

t(s)

t < 10 ms

.005

t < 10 ms

.005

3 4 5 7 10
I / Ir

20 30

50 70 100

200 300

.002
.001
.5 .7 1

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

D-3

Tripping curves

Additional characteristics

EasyPact CVS400 to 630


Protection of distribution systems

TM500D

TM600D
DB400108

DB400107

10 000
5 000
2 000

10 000
5 000
2 000

1 000

1 000

500

500

200

200

100

100

50

50

20

20

10
t(s)

10

t(s)

TM500D :
Im = 510 x In

1
.5

.2
.1
.05

.02
.01

.02
.01

t < 10 ms

.005

3 4 5 7 10

20 30

50 70 100

200 300

DB400105
DB400105

10 000
5 000
Ir = 0.5...1 x In

500
200
100
50
20
10
5
2

Isd = 2...10 x Ir

1
.5
.2
.1
.05
.02
.01

Reflex tripping :
t < 10 ms

.005
.002
.001
.5 .7 1

I = 11 x In
2

3 4 5 7 10
I / Ir

D-4

.002
.001
.5 .7 1

3 4 5 7 10
I / Ir

ETS 2.3 electronic trip units

t(s)

t < 10 ms

.005

I / Ir

1 000

TM600D :
Im = 4.2...8.3 x In

.1
.05

2 000

2
.5

.2

.002
.001
.5 .7 1

20 30

50 70 100

200 300

20 30

50 70 100

200 300

Tripping curves

EasyPact CVS100 to 250


Motor protection

MA magnetic trip units


MA150 and MA220

10 000
5 000

DB115716

DB118546

MA2.5... MA100

2 000

10 000
5 000
2 000

1 000

1 000

500

500

200

200

100

20

10

10

t(s)

Im = 6 ... 14 x In
Im = 9 ... 14 x In
(MA100 4P)

1
.5

2
.5
.2

.1
.05

.1
.05

.02
.01

.02
.01

t < 10 ms

.005

3 4 5 7 10

20 30

50 70 100

Im = 9 ... 14 x In

.2

.002
.001
.5 .7 1

MA150

50

20

t(s)

MA220

100

Thermal withstand

50

Thermal withstand

t < 10 ms

.005
.002
.001
.5 .7 1

200 300

I / Ir

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

Reflex tripping.

MA500

10 000
5 000

DB400111

DB400110

MA320

2 000

10 000
5 000
2 000

1 000

1 000

500

500

200

200

100

t(s)

100

Thermal withstand

50

50

20

20

10

10

t(s)

5
2

.5

.5

.2

.2

Im = 6 ...13 x In

.1
.05

Im = 6 ...13 x In

.1
.05

.02
.01

.02
.01

t < 10 ms

.005
.002
.001
.5 .7 1

Thermal withstand

3 4 5 7 10
I / In

20 30

50 70 100

t < 10 ms

.005

200 300

.002
.001
.5 .7 1

3 4 5 7 10

20 30

50 70 100

200 300

I / In

D-5

DB115719

Additional characteristics

Tripping curves

The limiting capacity of a circuit breaker is its aptitude


to let through a current, during a short-circuit, that is
less than the prospective short-circuit current.

Ics = 100 % Icu

(Isc)

Prospective
Isc peak
Prospective
current

Current and energy limiting curves

The exceptional limiting capacity of the EasyPact CVS range greatly reduces the
forces created by fault currents in devices.
The result is a major increase in breaking performance.
In particular, the service breaking capacity Ics is equal to 100 % of Icu.
The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising
the following steps:
bb break three times consecutively a fault current equal to 100% of Icu
bb check that the device continues to function normally, that is:
vv it conducts the rated current without abnormal temperature rise
vv protection functions perform within the limits specified by the standard
vv suitability for isolation is not impaired.

Longer service life of electrical installations

Prospective
Isc

Current-limiting circuit breakers greatly reduce the negative effects of short-circuits


on installations.

Limited Isc
peak

Thermal effects
Less temperature rise in conductors, therefore longer service life for cables.

Actual
current
Limited
Isc
(t)

The exceptional limiting capacity of the EasyPact CVS range is


due to the rotating double-break technique (very rapid natural
repulsion of contacts and the appearance of two arc voltages
in-series with a very steep wave front).

Mechanical effects
Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars
being deformed or broken.
Electromagnetic effects
Fewer disturbances for measuring devices located near electrical circuits.

Current and energy limiting curves

The limiting capacity of a circuit breaker is expressed by two curves which are a
function of the prospective short-circuit current (the current which would flow if no
protection devices were installed):
bb the actual peak current (limited current)
bb thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor
with a resistance of 1 .

Maximum permissible cable stresses

The table below indicates the maximum permissible thermal stresses for cables
depending on their insulation, conductor (Cu or Al) and their cross-sectional area
(CSA). CSA values are given in mm2 and thermal stresses in A2s.
CSA

1.5 mm

2.5 mm

4 mm

6 mm

10 mm

2.97x104

8.26x104

2.12x105

4.76x105

1.32x106

4.10x104

1.39x105

2.92x105

6.56x105

1.82x106

16 mm

25 mm

35 mm

50 mm

Cu

3.4x106

Al

PVC

Cu

PRC

Cu

Al

5.41x105

Al
CSA
PVC
PRC

D-6

7.52x105
8.26x106

1.62x107

3.31x107

1.39x10

3.38x10

6.64x10

1.35x107

Cu

4.69x10

1.39x10

2.23x10

4.56x107

Al

1.93x106

9.23x106

1.88x107

4.70x106

Tripping curves

Current and energy limiting curves

DB116369
DB116369

Current-limiting curves
300

200
146
100
80
70
60
50
k

40

N CVS630

30
20

F CVS250

10
8
7
6
5
4
2

10

20

CVS400

CVS100
CVS160

30 40 50 70 100

200 300

kA rms

DB116371
DB116371

Energy-limiting curves
10

5
3
2
1.41
8
10
5
3
2
10
2

As

3
2
10

5
3
2
10

CVS630
CVS400

CVS250
CVS100
CVS160

5
3
2

10

20

30 40 50 70 100 150 200 300

kA rms

D-7

Catalogue numbers

E-2

EasyPact CVS

Catalogue numbers
Contents

Functions and characteristics


Installation recommendations
Dimensions and connection
Additional characteristics

A-1
B-1
C-1
D-1

EasyPact CVS100 to 250

E-3

EasyPact CVS400 to 630

E-15

E-1

E-2

EasyPact CVS

EasyPact CVS100 to 250


Contents

CVS100/160/250B: complete fixed/FC device

E-4
E-4
E-5

CVS100/160/250F: complete fixed/FC device

E-6
E-6

CVS100/160/250N: complete fixed/FC device

E-7
E-7

Add-on Vigi module: EasyPact and Vigi

E-8
E-8

Trip unit accessories

E-9
E-9

Installation and connection

E-10
E-10

Accessories

E-11
E-11

EasyPact and Vigi CVS100/160/250B (25 kA 380/415 V)


EasyPact and Vigi CVS100/160/250F (36 kA 380/415 V)
Vigi CVS100/160/250F (36 kA 380/415 V)
EasyPact CVS100/160/250NA
CVS100/160/250

EasyPact and Vigi CVS100/160/250


EasyPact and Vigi CVS100/160/250
EasyPact and Vigi CVS100/160/250

E-3

Catalogue numbers

CVS100/160/250B:
complete fixed/FC device

EasyPact and Vigi CVS100/160/250B


(25 kA 380/415 V)
EasyPact CVS100/160/250B
With TM-D thermal-magnetic trip unit
DB400150

EasyPact CVS100B (25 kA at 380/415 V)


Rating
3P 3d
TM16D
LV510300
TM25D
LV510301
TM32D
LV510302
TM40D
LV510303
TM50D
LV510304
TM63D
LV510305
TM80D
LV510306
TM100D
LV510307
EasyPact CVS160B (25 kA at 380/415 V)
Rating
3P 3d
TM100D
LV516301
TM125D
LV516302
TM160D
LV516303
EasyPact CVS250B (25 kA at 380/415 V)
Rating
3P 3d
TM160D
LV525301
TM200D
LV525302
TM250D
LV525303

4P 3d
LV510310
LV510311
LV510312
LV510313
LV510314
LV510315
LV510316
LV510317

4P 4d
LV510320
LV510321
LV510322
LV510323
LV510324
LV510325
LV510326
LV510327

4P 3d
LV516311
LV516312
LV516313

4P 4d
LV516321
LV516322
LV516323

4P 3d
LV525311
LV525312
LV525313

4P 4d
LV525321
LV525322
LV525323

EasyPact CVS100/160/250B
DB400153

With Magnetic trip unit MA

EasyPact CVS100B (25 kA at 380/415 V)


Rating
3P 3d
LV510430
MA2,5
LV510431
MA6,3
LV510432
MA12,5
LV510433
MA25
LV510434
MA50
LV510435
MA100
EasyPact CVS160B (25 kA at 380/415 V)
Rating
3P 3d
LV516430
MA100
LV516431
MA150
EasyPact CVS250B (25 kA at 380/415 V)
Rating
3P 3d
LV525435
MA150
LV525436
MA220

Vigi CVS100/160/250B
DB400153

With TM-D thermal-magnetic trip unit

E-4

Vigi CVS100B (25 kA at 380/415 V) equipped with MH Vigi module (200 to 440 V)
Rating
3P 3d
4P 3d
LV510360
LV510370
TM16D
LV510361
LV510371
TM25D
LV510362
LV510372
TM32D
LV510363
LV510373
TM40D
LV510364
LV510374
TM50D
LV510365
LV510375
TM63D
LV510366
LV510376
TM80D
LV510367
LV510377
TM100D

4P 4d
LV510380
LV510381
LV510382
LV510383
LV510384
LV510385
LV510386
LV510387

Vigi CVS160B (25 kA at 380/415 V) equipped with MH Vigi module (200 to 440 V)
Rating
3P 3d
4P 3d
LV516361
LV516371
TM100D
LV516362
LV516372
TM125D
LV516363
LV516373
TM160D

4P 4d
LV516381
LV516382
LV516383

Vigi CVS250B (25 kA at 380/415 V) equipped with MH Vigi module (200 to 440 V)
Rating
3P 3d
4P 3d
LV525361
LV525371
TM160D
LV525362
LV525372
TM200D
LV525363
LV525373
TM250D

4P 4d
LV525381
LV525382
LV525383

CVS100/160/250F:
complete fixed/FC device

EasyPact and Vigi CVS100/160/250F


(36 kA 380/415 V)
EasyPact CVS100/160/250F
With TM-D thermal-magnetic trip unit
DB400150

EasyPact CVS100F (36 kA at 380/415 V)


Rating
3P 3d
TM16D
LV510330
TM25D
LV510331
TM32D
LV510332
TM40D
LV510333
TM50D
LV510334
TM63D
LV510335
TM80D
LV510336
TM100D
LV510337
EasyPact CVS160F (36 kA at 380/415 V)
Rating
3P 3d
TM100D
LV516331
TM125D
LV516332
TM160D
LV516333
EasyPact CVS250F (36 kA at 380/415 V)
Rating
3P 3d
TM160D
LV525331
TM200D
LV525332
TM250D
LV525333

4P 3d
LV510340
LV510341
LV510342
LV510343
LV510344
LV510345
LV510346
LV510347

4P 4d
LV510350
LV510351
LV510352
LV510353
LV510354
LV510355
LV510356
LV510357

4P 3d
LV516341
LV516342
LV516343

4P 4d
LV516351
LV516352
LV516353

4P 3d
LV525341
LV525342
LV525343

4P 4d
LV525351
LV525352
LV525353

EasyPact CVS100/160/250F
DB400155

With MA magnetic trip unit

EasyPact CVS100F (36 kA at 380/415 V)

Rating

3P 3d

MA2.5

LV510440

MA6.3

LV510441

MA12.5

LV510442

MA25

LV510443

MA50

LV510444

MA100

LV510445

EasyPact CVS160F (36 kA at 380/415 V)


Rating

3P 3d

MA100

LV516439

MA150

LV516440

EasyPact CVS250F (36 kA at 380/415 V)


Rating

3P 3d

MA150

LV525438

MA220

LV525439

E-5

Catalogue numbers

CVS100/160/250F:
complete fixed/FC device (cont.)
Vigi CVS100/160/250F
(36 kA 380/415 V)

Vigi CVS100/160/250F
With TM-D thermal-magnetic trip unit
DB400153

Vigi CVS100F (36 kA at 380/415 V) equipped with MH Vigi module (200 to 440 V)
Rating
3P 3d
4P 3d
TM16D
LV510390
LV510400
TM25D
LV510391
LV510401
TM32D
LV510392
LV510402
TM40D
LV510393
LV510403
TM50D
LV510394
LV510404
TM63D
LV510395
LV510405
TM80D
LV510396
LV510406
TM100D
LV510397
LV510407
Vigi CVS160F (36 kA at 380/415 V) equipped with MH Vigi module (200 to 440 V)
Rating
3P 3d
4P 3d
TM100D
LV516391
LV516401
TM125D
LV516392
LV516402
TM160D
LV516393
LV516403
Vigi CVS250F (36 kA at 380/415 V) equipped with MH Vigi module (200 to 440 V)
Rating
3P 3d
4P 3d
TM160D
LV525391
LV525401
TM200D
LV525392
LV525402
TM250D
LV525393
LV525403

E-6

4P 4d
LV510410
LV510411
LV510412
LV510413
LV510414
LV510415
LV510416
LV510417
4P 4d
LV516411
LV516412
LV516413
4P 4d
LV525411
LV525412
LV525413

CVS100/160/250NA:
complete fixed/FC device
EasyPact CVS100/160/250NA
EasyPact CVS100/160/250NA switch-disconnector
DB400155

With NA switch-disconnector unit

EasyPact CVS100NA
Rating
100
EasyPact CVS160NA
Rating
160
EasyPact CVS250NA
Rating
250

3P
LV510425

4P
LV510426

3P
LV516425

4P
LV516426

3P
LV525425

4P
LV525426

3P
LV510427

4P
LV510428

3P
LV516427

4P
LV516428

3P
LV525427

4P
LV525428

VigiCompact CVS100/160/250NA switch-disconnector


DB400153

With NA switch-disconnector unit

EasyPact CVS100NA
Rating
100
EasyPact CVS160NA
Rating
160
EasyPact CVS250NA
Rating
250

E-7

Catalogue numbers

Add-on Vigi module

EasyPact and Vigi CVS100/160/250

+ Vigi module or insulation monitoring


DB111464

Vigi module

E-8

ME type for CVS100/160 (200 to 440V)


MH type for CVS100/160 (220 to 440 V)
MH type for CVS250 (220 to 440 V)

3P
LV429212
LV429210
LV431535

4P
LV429213
LV429211
LV431536

Catalogue numbers

Accessories

EasyPact and Vigi


CVS100/160/250

Connection accessories (Cu or Al)


DB112225

Rear connections

Set of 3
Set of 4
Set of 3
Set of 4
Set of 10

LV429227
LV429228
LV429259
LV429260
LV429241

Set of 3
Set of 4

LV429218
LV429219

6.35 mm voltage tap for steel or aluminium connectors

Set of 10

LV429348

DB112231

Edgewise terminal extensions (1)

Set of 3
Set of 4

LV429308
LV429308

DB112232

Right-angle terminal extensions (1)

Set of 3
Set of 4

LV429261
LV429262

DB112233

Straight terminal extensions (1)

Set of 3
Set of 4

LV429263
LV429264

Spreaders from 35 to 45 mm pitch (1)

3P
4P

LV431563
LV431564

DB112226

1 x (25 to 95 mm) ; y 250 A

DB112225

LV429242
LV429243

Aluminium connectors

DB112726

Set of 3
Set of 4

Steel connectors

Clips for connectors

DB112227

1 x (1.5 to 95 mm) ; y 160 A

DB112235

Bare cable connectors

LV429235
LV429236

2 short
2 long

Aluminium connectors for 2 cables (1)

DB112724

1 x (120 to 185 mm) ; y 250 A

Terminal extensions

2 x (50 to 120 mm) ; y 250 A

(1) Supplied with 2 or 3 interphase barriers.

E-9

Accessories

EasyPact and Vigi


CVS100/160/250

Set of 3
Set of 4
Set of 3
Set of 4
Set of 3
Set of 4

LV429252
LV429256
LV429253
LV429257
LV429254
LV429258

Set of 3
Set of 4
Set of 3
Set of 4

LV429504
LV429505
LV429506
LV429507

DB400161

1 short terminal shield for breaker

3P
4P

LV429515
LV429516

DB400162

1 long terminal shield for breaker

3P
4P

LV429517
LV429518

DB112241

Interphase barriers for breaker

Set of 6

LV429329

DB400163

Crimp lugs for copper cable (1)

2 insulating screens for breaker (45 mm pitch)

3P
4P

LV429330
LV429331

DB112237

For cable 120 mm


For cable 150 mm
For cable 185 mm

Crimp lugs for aluminium cable (1)


DB112238

For cable 150 mm


For cable 185 mm

Insulation accessories

(1) Supplied with 2 or 3 interphase barriers.

E-10

Catalogue numbers

Accessories

EasyPact and Vigi


CVS100/160/250

Electrical auxiliaries
Auxiliary contacts (changeover)
DB112254
DB111454

Voltage releases

DB115631

29450
29452
LV429451

OF or SD or SDE or SDV
OF or SD or SDE or SDV low level
SDE adaptor, mandatory for trip unit TM, MA

Voltage
24 V 50/60 Hz
48 V 50/60 Hz
110-130 V 50/60 Hz
220-240 V 50/60 Hz and 208-277 V 60 Hz
380-415 V 50 Hz and 440-480 V 60 Hz
DC
12 V
24 V
30 V
48 V
60 V
125 V
250 V
MN 48 V 50/60 Hz with fixed time delay
Composed of:
MN 48 V DC
Delay unit 48 V 50/60 Hz
MN 220-240 V 50/60 Hz with fixed time delay
Composed of:
MN 250 V DC
Delay unit 220-240 V 50/60 Hz
AC

MX
LV429384
LV429385
LV429386
LV429387
LV429388
LV429382
LV429390
LV429391
LV429392
LV429383
LV429393
LV429394

MN
LV429404
LV429405
LV429406
LV429407
LV429408
LV429402
LV429410
LV429411
LV429412
LV429403
LV429413
LV429414
LV429412
LV429426
LV429414
LV429427

E-11

Accessories

EasyPact and Vigi


CVS100/160/250

Rotary handles
DB112259

Direct rotary handle

LV429337

With black handle

Extended rotary handle

LV429338

DB112260

With black handle

Locks
DB400164

By removable device

29370

DB400165

Toggle locking device for 1 to 3 padlocks

By fixed device

29371

Locking of rotary handle


DB112263

Keylock adaptor (keylock not included)


Keylock (keylock adaptor not included)

E-12

Ronis 1351B.500
Profalux KS5 B24 D4Z

LV429344
41940
42888

Catalogue numbers

Accessories

EasyPact and Vigi


CVS100/160/250

Interlocking
DB111486

With toggles

29354

DB111487

Mechanical interlocking for circuit breakers

With rotary handles

LV429369

Interlocking with key (2 keylocks / 1 key) for rotary handles


E26766

Keylock kit (keylock not includd) (1)


1 set of 2 keylocks (1 key only, keylock kit not
included)

Ronis 1351B.500
Profalux KS5 B24 D4Z

LV429344
41950
42878

Installation accessories
E21641

E21641

Front-panel escutcheons

IP40 toogle escutcheon (small cut-out)


IP40 escutcheon for Rotary handle
IP40 escutcheon for Vigi module

29315
LV429317
LV429316

Bag of accessories

LV429375

1 adaptor

LV429305

10 toggle extensions
Bag of screws
12 snap-in nuts (fixed/FC)

LV429313
LV429312
LV510100
LV516060
LV429226

IP40

DB115615

Lead-sealing accessories

DB112739

Din rail adaptor

E18624

Spare parts

1 set of 10 identification labels

M6 for CVS100B/F
M8 for CVS160/250B/F

(1) For only 1 device.

E-13

E-14

EasyPact CVS

EasyPact CVS400 to 630


Contents

CVS400/630: complete fixed/FC device

E-16

Add-on Vigi module: EasyPact and Vigi

E-20

Accessories

E-21

EasyPact and Vigi CVS400/630F/N


EasyPact CVS400/630N (36 kA 380/415 V)
EasyPact CVS400/630NA
CVS400/630

EasyPact and Vigi CVS400/630

E-16
E-18
E-19
E-20
E-21

E-15

CVS400/630:
complete fixed/FC device

Catalogue numbers

EasyPact and Vigi


CVS400/630F/N
EasyPact CVS400/630F
With TM-D thermal-magnetic trip unit
DB400008

EasyPact CVS400F (36 kA at 380/415 V)


Rating

3P 3d

4P 3d

4P 4d

TM320D

LV540305

LV540308

LV540311

TM400D

LV540306

LV540309

LV540312

EasyPact CVS630N (36 kA at 380/415 V)


Rating

3P 3d

4P 3d

4P 4d

TM500D

LV563305

LV563308

LV563311

TM600D

LV563306

LV563309

LV563312

EasyPact CVS400/630N
With TM-D thermal-magnetic trip unit
DB400008

EasyPact CVS400F (50 kA at 380/415 V)


Rating

3P 3d

4P 3d

4P 4d

TM320D

LV540315

LV540318

LV540321

TM400D

LV540316

LV540319

LV540322

EasyPact CVS630F (50 kA at 380/415 V)


Rating

3P 3d

4P 3d

4P 4d

TM500D

LV563315

LV563318

LV563321

TM600D

LV563316

LV563319

LV563322

Vigi add-on module CVS400/630F


With TM-D thermal-magnetic trip unit
DB400016

Vigi CVS400F (36 kA at 380/415 V)


Rating

3P 3d

4P 3d

4P 4d

TM320D

LV540335

LV540338

LV540341

TM400D

LV540336

LV540339

LV540342

Vigi CVS400N (36 kA at 380/415 V)


Rating

3P 3d

4P 3d

4P 4d

TM500D

LV563335

LV563338

LV563341

TM600D

LV563336

LV563339

LV563342

Vigi add-on module CVS400/630N


With TM-D thermal-magnetic trip unit
DB400016

Vigi CVS400N (50 kA at 380/415 V)


Rating

3P 3d

4P 3d

4P 4d

TM320D

LV540345

LV540348

LV540351

TM400D

LV540346

LV540349

LV540352

Vigi CVS630N (50 kA at 380/415 V)

E-16

Rating

3P 3d

4P 3d

4P 4d

TM500D

LV563345

LV563348

LV563351

TM600D

LV563346

LV563349

LV563352

CVS400/630:
complete fixed/FC device
EasyPact and Vigi
CVS400/630F/N
EasyPact CVS400/630F

DB400020

With MA magnetic trip unit

6500 3000
6000
5500
5000 4500

3500
4000

EasyPact CVS400F (36 kA at 380/415 V)


Rating
MA320
EasyPact CVS400N (50 kA at 380/415 V)
Rating
MA320
EasyPact CVS630F (36 kA at 380/415 V)
Rating
MA500
EasyPact CVS630N (50 kA at 380/415 V)
Rating
MA500

3P 3D
LV540550

LV540552

LV563550

LV563552

E-17

Catalogue numbers

CVS400/630:
complete fixed/FC device
EasyPact CVS400/630N
(36 kA 380/415 V)

EasyPact CVS400/630F
DB400021

ETS 2.3 electronic trip unit (LS0I protection)


EasyPact CVS400F (36 kA at 380/415 V)
EasyPact CVS630F (36 kA at 380/415 V)

565

4P 3d, 4d, 3d + N/2


LV540506
LV563506

400 A
630 A

3P 3d
LV540510
LV563510

4P 3d, 4d, 3d + N/2


LV540511
LV563511

400 A
630 A

3P 3d
LV540520
LV563520

4P 3d, 4d, 3d + N/2


LV540521
LV563521

400 A
630 A

3P 3d
LV540524
LV563524

4P 3d, 4d, 3d + N/2


LV540525
LV563525

7
10

630

3P 3d
LV540505
LV563505

3
505

400 A
630 A

440
370
315

EasyPact CVS400/630N
DB400021

ETS 2.3 electronic trip unit (LS0I protection)


EasyPact CVS400N (50 kA at 380/415 V)
EasyPact CVS630N (50 kA at 380/415 V)

5
4
3
505

565

630

7
8
10

440
370
315

Vigi add-on module CVS400/630F


DB400022

ETS 2.3 electronic trip unit (LS0I protection)


Vigi CVS400F (36 kA at 380/415 V)
Vigi CVS630F (36 kA at 380/415 V)

565

630

7
8

3
505

10

440
370
315

Vigi add-on module CVS400/630N


DB400022

ETS 2.3 electronic trip unit (LS0I protection)


Vigi CVS400N (50 kA at 380/415 V)
Vigi CVS630N (50 kA at 380/415 V)

5
4
3
505
440
370
315

E-18

565

630

7
8
10

CVS400/630:
complete fixed/FC device
EasyPact CVS400/630NA

DB400023

EasyPact CVS400/630 NA switch-disconnector


EasyPact CVS400 NA
EasyPact CVS600 NA, 45 mm pitch

3P
LV540400
LV563400

4P
LV540401
LV563401

3P
LV540402
LV563402

4P
LV540403
LV563403

DB400024

Vigi CVS400/630 NA switch-disconnector


Vigi CVS400 NA
Vigi CVS600 NA, 45 mm pitch

E-19

Add-on Vigi module

Catalogue numbers

EasyPact and Vigi CVS400/630

+ Vigi module or insulation monitoring module


DB111464

Vigi module

E-20

Type MB

200 to 440 V

3P
LV432455

4P
LV432456

Accessories

EasyPact and Vigi CVS400/630

Connection accessories (Cu or Al)


DB112225

Rear connections

E22040

Aluminium connector 1x (35 to 300 mm)

Set of 3
Set of 4

LV432479
LV432480

E22041

Aluminium connector 2x (35 to 300 mm)

Set of 3
Set of 4

LV432481
LV432482

Voltage plug for aluminium connector 1 or 2 cables

Set of 10

LV429348

Right-angle terminal extension

Set of 3
Set of 4

LV432484
LV432485

E21276

Edgewise terminal extensions

Set of 3
Set of 4

LV432486
LV432487

E21012

Cable connectors (1)

LV432475
LV432476

2 short
2 long

Spreaders

3P
4P
3P
4P

LV432490
LV432491
LV432492
LV432493

Set of 3
Set of 4
Set of 3
Set of 4

LV432500
LV432501
LV432502
LV432503

Set of 3
Set of 4
Set of 3
Set of 4

LV432504
LV432505
LV432506
LV432507

3P
4P
3P
4P
Set of 6
3P
4P
3P
4P

LV432591
LV432592
LV432593
LV432594
LV432570
LV432595
LV432596
LV432578
LV432579

Terminal extension (1)

52.5 mm
70 mm

E18602

Crimp lugs for copper cable (1)

For cable 240 mm2


For cable 300 mm
Supplied with 2 (or 3) interphase barriers

E30908

Crimp lugs for aluminium cable (1)

For cable 240 mm


For cable 300 mm
Supplied with 2 (or 3) interphase barriers

E18618

Insulation accessories

Short terminal shield, 45 mm (1 piece)

E18606

Long terminal shield, 45 mm (1 piece)


Interphase barriers
2 insulating screens (70 mm pitch)

52,5 mm
70 mm

(1) supplied with 2 or 3 interphase barriers

E-21

Catalogue numbers

Accessories

EasyPact and Vigi


CVS400/630

Electrical auxiliaries
Auxiliary contacts (changeover)

29450
29452
LV540050

E18608

OF or SD or SDE or SDV
OF or SD or SDE or SDV low level
SDE adaptor mandatory for trip unit TM, MA and ETS2.3

E18609

Voltage releases

E-22

Voltage
24 V 50/60 Hz
48 V 50/60 Hz
110-130 V 50/60 Hz
220-240 V 50/60 Hz and 208-277 V 60 Hz
380-415 V 50 Hz and 440-480 V 60 Hz
DC
Voltage
12 V
24 V
30 V
48 V
60 V
125 V
250 V
MN 48 V 50/60 Hz with fixed time delay
Composed of:
MN 48 V DC
Delay unit 48 V 50/60 Hz
MN 220-240 V 50/60 Hz with fixed time delay
Composed of:
MN 250 V DC
Delay unit 220-240 V 50/60 Hz
AC

MX
LV429384
LV429385
LV429386
LV429387
LV429388

MN
LV429404
LV429405
LV429406
LV429407
LV429408

LV429382
LV429390
LV429391
LV429392
LV429383
LV429393
LV429394

LV429402
LV429410
LV429411
LV429412
LV429403
LV429413
LV429414
LV429412
LV429426
LV429414
LV429427

Accessories

EasyPact and Vigi


CVS400/630
Rotary handle
E18611

Direct rotary handle

LV432597

Standard black handle

Extended rotary handle

LV432598

E18612

Standard extended rotary handle

Locks
E18621

By removable device

29370

E18613

Toggle locking device for 1 to 3 padlocks

By fixed device

32631

E18620

Locking of the rotary handle

Keylock adaptor (keylock not included)


Keylock (keylock adaptor not included)

Ronis 1351B.500
Profalux KS5 B24 D4Z

LV432604
41940
42888

E-23

Accessories

Catalogue numbers

EasyPact and Vigi


CVS400/630

Interlocking
E21288

With toggles

32614

E18780

Mechanical interlocking for circuit breakers

With rotary handles

LV432621

Interlocking with key (2 keylocks/1 key) for rotary handles


E26766

Keylock kit (keylock not included) (1)


1 set of 2 keylocks (1 key only, keylock kit not included)

Ronis 1351B.500
Profalux KS5 B24 D4Z

LV432604
41950
42878

(1) for only 1 device

Installation accessories
E21641

Front-panel escutcheons

IP40 Toggle escutcheon (small cut-out)

32556

IP40 escutcheon for rotary handle

LV432558

IP40 escutcheon for Vigi module

LV429316

Lead-sealing accessories

LV429375

Spare parts
Front-panel escutcheons

Toggle extension

LV432553

Bag of screws

LV432552

1 set of 10 identification labels

LV429226

Test
E21290

Mini test kit for STR trip units

43362

E36271

Test kits

Portable test kit for STR trip units

34547

Spare test plug for portable test kit 34547

34503

Wiring kit (spare part)

34546

E-24

Notes

E-25

Notes

E-26

35, rue Joseph Monier


CS 30323
F- 92506 Rueil Malmaison Cedex
RCS Nanterre 954 503 439
Capital social 896 313 776
www.schneider-electric.com
LVED210011EN

As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.

This document has been printed on ecological paper

Design: Schneider Electric


Photos: Schneider Electric
Printed: