This document outlines a 6-stage process with actions at each stage including reducing furnace units (RFU) for different priority potlines or tripping a potline entirely. Stage 1 involves 3 RFU of the highest priority potline at 48.5Hz with a 500ms time delay. Stage 2 reduces units of the second priority potline at 48Hz and 200ms delay. Stage 3 trips the highest priority potline at 47.6Hz and 200ms delay.

Uploaded by

Ashish Sada
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
42 views2 pages

New Microsoft Office Excel Worksheet

This document outlines a 6-stage process with actions at each stage including reducing furnace units (RFU) for different priority potlines or tripping a potline entirely. Stage 1 involves 3 RFU of the highest priority potline at 48.5Hz with a 500ms time delay. Stage 2 reduces units of the second priority potline at 48Hz and 200ms delay. Stage 3 trips the highest priority potline at 47.6Hz and 200ms delay.

Uploaded by

Ashish Sada
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

SL

1
2
3
4
5
6

Stages
Stage 1
Stage 2
Stage 3
Stage 4
Stage 5
Stage 6

IPP BUS
BUS1
BUS1
BUS1
BUS2
BUS2
BUS2

Frequency
48.5
48
47.6
48.5
48
47.6

Time
delay(ms)
500
200
200
500
200
200

Trip
Trip
Trip
Trip

CILMS ACTION
3 RFU of Priority 1 potline
3 RFU of Priority 2 potline
Trip Priority 1 potline
3 RFU of Priority 1 potline
3 RFU of Priority 2 potline
Trip Priority 1 potline