Abb PLC
Abb PLC
Abb PLC
AA-BBBBBB-CC-DD-EEEFF
3276-GP-VD-050
Plants :
Sheet
086
Issue
Replaces:
Created from:
01.10.2007
Type / Code
ZSK380 / ZSK70
Jobname
TASNEE LDPE
Job-No.
Doc-Type
Count-No.
Fmt.
Rev.
FINAL
Wiebe
Remus
Aichroth
01-10-2007
02
UPDATE
Wiebe
Remus
Aichroth
10-05-2007
01
FIRST ISSUE
Wiebe
Laib
Laib
01-12-2006
Issue
Description
Prepared
Checked
Approved
This document is Tecnimonts property, and cannot be used by others for any purpose, without prior written consent
Date
03
3276-GP-VD-050
LDPE 400 KT/Y
Plants :
086
Sheet
Issue
ITEM:
Sigla:
REQUIRED QUANTITY:
Quantita richiesta:
3276-NN-SG-000115
3276-NN-SG-000116
AC MOTOR:
Motore in c.a.:
Converter HW Diagram
3 BHS 227357 E01
10
UF INPUT UNIT:
Unita di ingresso del UF:
ACS 6000 Line supply Unit,12 pulse diode bridge (without braking)
11
6-VFD-602
N
3276-NN-SG-000010
SCHEMA:
Configuration:
13
RATED VOLTAGE
Tensione nominale:
13800 +5%
14
NUMBER OF PHASES:
Numero fasi:
No.
15
RATED FREQUENCY:
Frequenza nominale:
Hz
60 +1%
16
direttamente a terra
solidly earthed
17
MVA
Skmax. =
FREQUENCY RANGE
a terra con resistore
earthed through resistor
40kA
(*)
isolato
insulated
Skmin = 1 Sec
19
HARMONIC DISTORTION:
Distorsione armonica:
POWER FACTOR
and Shall be within the level specified in IEC- 61000-2-4, table 2 to 5 class2.
> 0.95 (*)
Cosfi
20
>98,5 %
MAKE :
22
TYPE :
ABB
ACS 6105_L12_1a9_C24_W1a
03
3276-GP-VD-050
LDPE 400 KT/Y
Plants :
23
RATED OUTPUT :
24
OUTPUT VOLTAGE : V
25
26
OUTPUT FREQUENCY : Hz
27
28
approx.18 ( at 50 Hz
29
1.046
29
4.658
30
MVA
FROM
186
TO 3100
989
FROM
[ X ] DIODE
[ ] GTO
[ ] THYRISTOR
[ ] IGBT
32
[ ] DIODE
INSTALLATION
[ ] IN CABINET
[ ] GTO
[ X ] U-CONVERTER
[ ] IN OPEN AIR
[ ] IGBT
[ ] I-CONVERTER
Control Cabinets
33
TYPE OF PROTECTION :
34
2230
1024
500
35
1300
1137
36
CONVERTER DIMENSIONS (H x W x D) mm :
2161,5/ 2594
37
kW
38
NOTE:
Issue
5,312
31
086
Sheet
IP 32
kW
4930
78
4,7
IN CASE OF CONFLICT BETWEEN THE REQUIREMENTS OF THIS DATA-SHEET AND THE REFERENCED
SPECIFICATIONS, THIS DATA-SHEET PREVAILS.
03
AA-BBBBBB-CC-DD-EEEFF
Tecnimont Identification Code
3276-GP-VD-050
Plants :
1.
Sheet
086
Issue
General requirements
The panel shall be self-standing and shall be accessible from front.
The degree of protection of the panel shall be IP32.
The cable entry shall be from bottom of the panel.
The cable length between the motor and the converter panel is less than 300 meter.
Colour of the panel can be as per manufacturers standard.
Earth fault protection of motor and motor connection circuits shall be provided by suitable
device, according to the type of voltage system feeding the motor (IT or TN).
2.
3.
4.
5.
03
AA-BBBBBB-CC-DD-EEEFF
Tecnimont Identification Code
3276-GP-VD-050
Plants :
6.
Sheet
086
Issue
Storage temperatures
Oil and water temperatures
Oil throughput flow
Over/under voltage monitor
Overcurrent monitoring
Rotation/Torque monitoring
Operating hours counter system
Fault initial value recording
03
3276-GP-VD-050
Plants :
Sheet
081
Issue
Replaces:
Created from:
10.05.2007
Type / Code
ZSK380 / ZSK70
Jobname
TASNEE LDPE
Job-No.
Doc-Type
Count-No.
Fmt.
Rev.
Q1-A4D-01
FIRST ISSUE
Wiebe
Laib
Laib
13-11-2006
02
UPDATE
Wiebe
Remus
Aichroth
10-05-2007
03
FINAL
Wiebe
Remus
Aichroth
01-06-2007
Issue
Description
Prepared
Checked
Approved
This document is Tecnimonts property, and cannot be used by others for any purpose, without prior written consent
Date
03
AA-BBBBBB-CC-DD-EEEFF
6-VFD-602
Plants :
3276-GP-VD-050
Location: AL JUBAIL KSA
Sheet
280
Issue
FOR INFORMATION
DATE OF ISSUE:
Replaces:
Created from:
11.12.2007
Type / Code
ZSK380 / ZSK70
Jobname
TASNEE LDPE
Job-No.
Doc-Type
Count-No.
Fmt.
Rev.
Q1-A4D-01
FOR INFORMATION
Wiebe
Laib
Laib
11-12-2007
01
FIRST ISSUE
Wiebe
Laib
Laib
02-10-2007
Issue
Description
Prepared
Checked
Approved
This document is Tecnimonts property, and cannot be used by others for any purpose, without prior written consent
Date
02
PROJECT :
ORDER NO. :
0011042645
CUSTOMER :
ODP Helsinki
EQUIPMENT :
CONVERTER TYPE :
ACS 6105_L12_1a9_C24_W1a
S/N: 403
DOCUMENT :
CONVERTER HW DIAGRAM
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
FRONT PAGE
2006-09-29
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
No. of sh.
Sh.no.
Cont.sh.
35
001
002
page
4
title 2
title 1
001
002
DESIGNATION BLOCK
CROSS REFERENCES
DESIGNATION BLOCK
DESIGNATION BLOCK
101
102
103
104
105
134
141
161
168
171
178
184
190
192
201
207
261
262
271
275
277
278
304
371
375
391
411
441
454
6
title 3
rev.
ind.
-
FRONT PAGE
INDEX SHEET
006
007
008
009
FOR
OF SIGNALS
"FUNCTION OF ITEM"
"FUNCTION OF ITEM"
MAIN CIRCUIT
MAIN CIRCUIT
MAIN CIRCUIT
MAIN CIRCUIT
AUX POWER SUPPLY
PROFIBUS ADAPTER
STANDARD I/O
AUX POWER
CONVERTER
OVERVIEW
CONTROL
GUSP / CONTROL
EARTH FLT DETECTION
AUX POWER
CHARGING UNIT
DISCHARGING UNIT
DOOR MONITORING
DOOR MONITORING
COOLING
COOLING
CABINET TEMPERATURE
CABINET TEMPERATURE
FIBRE OPTIC CONNECTIONS
FIBRE OPTIC CONNECTIONS
FIBRE OPTIC CONNECTIONS
FIBRE OPTIC CONNECTIONS
MOTOR SIDE
LINE SIDE
MOTOR SIDE
CONVERTER INTERFACE
CONVERTER INTERFACE
CONVERTER INTERFACE
CONVERTER INTERFACE
CONVERTER INTERFACE
INTERNAL SIGNALS
AUX POWER DISTRIBUTION
AUX POWER SUPPLY
AUX POWER SUPPLY
AUX POWER SUPPLY
INTERNAL SIGNALS
CAPACITORS
CAPACITORS
INTERNAL SIGNALS
INTERNAL SIGNALS
INTERNAL SIGNALS
INTERNAL SIGNALS
INTERNAL SIGNALS
INTERNAL SIGNALS
INT-BOARD
INTERNAL SIGNALS
INTERNAL SIGNALS
INTERNAL SIGNALS
AMC BOARD
PINT-BOARD
INT-BOARD
DOOR INTERLOCKING
DOOR INTERLOCKING
CABINET
INT-BOARD
=COU / =INU
FT-LINK
FSCD BOARD
CONTROL
=COU1
=LSU1
=INU1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
INDEX SHEET
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
001
002
006
Classification of units
Numbering
1 2 3 4 5
6
+ NN AA NN AA NN .A...N...
+A 01
Rev. ind.
F
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
Cubicle No.
High voltage/group
Qualifying
Symbol
1 2 3
- A NNN AN
=
=
=
=
=
=
=
=
=
=
=
=
=
Section
Not used on
Converter level
E
Qualifying
Symbol
D
Not used on
Converter level
BCU
CBU
COU
EXU
IFU
INU
IRU
ISU
LSU
RBU
TEU
VLU
WCU
Section
Qualifying
Symbol
1 2 3
4 5
= N AA NN . AAA N
= ARU 1
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Section
Number (extension)
Number
Kind
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
002
006
007
DC+
NP
DC-
DC+
NP
DC-
INTERNAL WIRING:
REFERENCE TO RELEVANT STANDARD
DOCUMENT NR.
SHEET 112
3BHS119827E01
112.B1
112.B1
112.B1
111.B8
111.B8
111.B8
=INU2+A09
-INU2
3BHS119827E01
/191.A4
DC+
NP
DC-
SHEET
COORDINATE
/191.A4
SLAVE ELEMENT CAN
BE FOUND ON PAGE 191.A4
SHEET NUMBER
AND COORDINATE
WIRE NR OR NAME
-A4061
-A4011
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
CROSS REFERENCES OF SIGNALS
2006-09-29
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
006
007
008
A KIND OF ITEM
KIND OF ITEM
RELAYS,
MOTORS
MEASURING EQUIPMENT,
TESTING EQUIPMENT
CAPACITORS
DELAY DEVICES,
STORAGE DEVICES,
BINARY ELEMANTS
PROTECTIVE
DEVICES
EXAMPLES
MISCELLANEOUS
LETTER
CODE
TRANSDUCERS FROM
NON-ELECTRICAL
QUANTITY TO
ELECTRICAL QUANTITY
AND VICE-VERSA
RESISTORS
SIGNALLING
DEVICES
NOT USED
F
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
AMPLIFIERS,
REGULATORS
LETTER
CODE
K
L
M
N
P
Q
EXAMPLES
HEAVY DUTY CONTACTORS; AUXILIARY CONTACTORS; AUXILIARY
RELAYS; TIME DELAY RELAYS; FLASHING RELAYS AND REED RELAYS.
CHOKES, INDUCTION COILS.
DC MOTORS, AC SINGLE PHASE AND 3 PHASE MOTORS
DEVICES FOR ANALOG CONTROL, REGULATION AND COMPUTING;
ELECTRONIC AND ELECTROMECHANICAL REGULATORS; OPERATIONAL
AMPLIFIERS; INVERTING AMPLIFIERS; ISOLATING AMPLIFIERS;
IMPEDANCE BUFFERS; CONTROL EQUIPMENT SETS; MASTER ANALOG
CONTROLLERS; ANALOG COMPUTERS, INTEGRATED CIRCUITS WITH
ANALOG FUNCTIONS.
ANALOG, BINARY AND DIGITAL INDICATING AND RECORDING
MEASURING DEVICES (INDICATORS, RECORDERS, COUNTERS);
OSCILLOSCOPES; DATA DISPLAY DEVICES; SIMULATORS; TEST
ADAPTERS; POINTS FOR MEASURING,
TESTING AND SUPPLY.
MAIN CIRCUIT SWITCHES; SWITCHES WITH PROTECTIVE DEVICES;
CIRCUIT BREAKERS; HIGH-SPEED CIRCUIT BREAKERS; ISOLATORS;
ON-LOAD ISOLATORS; STAR-DELTA SWITCHES; POLE CHANGING
SWITCHES; CONTROLLER DRUMS; DISCONNECTING LINKS; CELL
SWITCHES; PROTECTIVE ISOLATORS; PROTECTIVE ON-LOAD
ISOLATORS; HOUSE-WIRING SWITCHES; PROTECTIVE MOTOR
SWITCHES
INDUCTORS
SWITCHING DEVICES
FOR POWER CIRCUITS
GENERATORS,
SUPPLIES
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
ASSEMBLIES
SUBASSEMBLIES
SWITCHES
SELECTORS
TRANSFORMERS
Date
Date
R
S
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
007
008
009
KIND OF ITEM
LETTER
CODE
EXAMPLES
KIND OF ITEM
MODULATORS,
TRANSDUCERS FROM ONE
ELECTRICAL QUANTITY
TO ANOTHER
FREQUENCY MODULATORS; (-DEMODULATORS); (CURRENT-), VOLTAGETO- FREQUENCY CONVERTERS; FREQUENCY- TO- VOLTAGE (CURRENT)
CONVERTERS; ANALOG- TO- DIGITAL CONVERTERS; DIGITAL- TOANALOG CONVERTERS; SIGNAL BUFFER STAGES; DIRECT CURRENT AND
DIRECT VOLTAGE CONVERTERS; DISCRIMINATORS, PARALLEL- TOSERIES CONVERTERS; SERIES- TO- PARALLEL CONVERTERS;
CODING DEVICES; DECODING DEVICES; OPTOCOUPLERS; REMOTE CONTROL
EQUIPMENT.
EQUIPMENT.
TUBES,
SEMI- CONDUCTORS
TRANSMISSION PATHS,
WAVE- GUIDES
TERMINALS,
PLUGS, SOCKETS
ELECTRICALLY OPERATED
MECHANICAL DEVICES
TERMINATIONS,
EQUALIZING DEVICES,
FILTERS, LIMITERS,
CABLE TERMINATIONS
6
LETTER
CODE
EXAMPLES
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
008
009
101
=LSU1+A01
-LSU1
DC+
DC+_A01 102.B1
NP_A01 102.B1
DC-_A01 102.B1
DC-
-E3151
=ACS6000/271.B1
COOLING
=ACS6000/261.B2
Door
supervis
-B3201
=ACS6000/277.D1
CABINET
TEMP.
-W412104 1
BOARD
-A3101
=ACS6000/441.B2
PINT-BOARD
C779
=ACS6000/178.B6
COU
INTERFACE
-S3201_02
-R3023
CONTROL
-G3101
-F3111
=ACS6000/190.D4
BOARD
UF C765
1L1
1L2
1L3
2L3
2L2
2L1
PE
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
BUSBAR CONFIGURATION 1
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
1L1_A01
1L2_A01
1L3_A01
2L3_A01
2L2_A01
2L1_A01
102.C1
102.D1
102.D1
102.D1
102.D1
102.D1
PE_A01 102.E1
2006-09-29 Title
MAIN CIRCUIT
2006-09-29
=LSU1 +A01
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
009
101
102
101.B8
101.B8
101.B8
DC+_A01
NP_A01
DC-_A01
BUSBAR CONFIGURATION 1
DC+
NP
DC-
DC+_A02
NP_A02
DC-_A02
103.B1
103.B1
103.B1
L1_A02
L2_A02
L3_A02
103.D1
103.D1
103.D1
PG_A02
PE_A02
103.E1
103.E1
-DOOR_INT
=ACS6000/261.A2
-K281...
-A2451
101.C8
101.D8
101.D8
101.D8
101.D8
101.D8
1L1_A01
1L2_A01
1L3_A01
2L3_A01
2L2_A01
2L1_A01
-A2501
=ACS6000/134.C2
NPBA12
ProfiB
=ACS6000/391.D6
TB820
-A2951
=ACS6000/391.A6
XV C 769
CONTROL
-A2401
=ACS6000/411.B2
AMC
BOARD
=INU:L1
=INU:L2
=INU:L3
=LSU:1L1
=LSU:1L2
=LSU:1L3
=LSU:2L3
=LSU:2L2
=LSU:2L1
-Q1001_1073
=ACS6000/171.A1
AUX POWER
-TERM_X1_2 -X131_132
=ACS6000/141.B2
PROCESS
INTERFACE
-TERM_X4
=ACS6000/201.A1
CBU
INTERFACE
=ACS6000/141.C7
MCB
INTERFACE
101.E8
PG
PE
PE_A01
150 mm
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
=COU1+A02
-COU1
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
101
102
103
102.B8
102.B8
102.B8
DC+_A02
NP_A02
DC-_A02
BUSBAR CONFIGURATION 1
DC+
=ACS6000/184.B6
GUSP
CONTROL
=ACS6000/261.D2
DOOR
MONITORING
-E4161
-B4201
=ACS6000/275.B2
COOLING
F
A
B
C
D
102.D8
102.D8
102.D8
L1_A02
L2_A02
L3_A02
102.E8
102.E8
PG_A02
PE_A02
Date
DC-
Name
0
DC+_A03
NP_A03
DC-_A03
104.B1
104.B1
104.B1
PG_A03
PE_A03
104.E1
104.E1
=ACS6000/454.B1
INT-BOARD
=ACS6000/278.D1
CABINET
TEMP.
-A4132
-F4011
-A4133
-F4012
=ACS6000/454.E1
SVA
XVC 767
-A4051
=ACS6000/271.B2
COOLING
NP
BOARD
-A4121
-E4151_53
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
=INU1+A03
-INU1
=ACS6000/454.E1
SCA
XVC 768
=ACS6000/375.B5
FSCD BOARD
=ACS6000/375.B5
FSCD BOARD
PG
PE
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
MAIN CIRCUIT
2006-09-29
=INU1 +A03
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
102
103
104
103.B8
103.B8
103.B8
DC+_A03
NP_A03
DC-_A03
BUSBAR CONFIGURATION 1
DC+
NP
DC-
INTERFACE =INU1
-A7101
-V7101
-F7101
-V7102
-F7102
=ACS6000/207.C4
IGCT
INTERFACE CONTROL
-A7091
-S7201_03
D
=ACS6000/201.D4
CHARGING
UNIT
=ACS6000/262.B2
DOOR
MONITORING
-E7151
-B7201
=ACS6000/271.C2
COOLING
103.E8
103.E8
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
=CBU1+A04
-CBU1
A
B
C
D
Date
=ACS6000/277.D8
CABINET
TEMP.
/201.A4
/201.A6
=ACS6000/207.D4
IGCT
=ACS6000/207.D5
VLSCD
BOARD
-Z7081
PG
PE
PG_A03
PE_A03
Name
0
-Q7121
=ACS6000/207.C5
VLSCD
BOARD
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
PE_A04
2006-09-29 Title
MAIN CIRCUIT
2006-09-29
=CBU1 +A04
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
105.E1
103
104
105
-TERM_X1
-TERM_X17
-TERM_X2
-TERM_X18
=ACS6000/161.A2
AUX POWER
400V,60Hz
=ACS6000/141.B1
STANDARD
I/O
=ACS6000/161.C2
SP. HEATER
230VAC
=ACS6000/141.C8
STANDARD
I/O
-TERM-X512
=ACS6000/192.B6
AUX POWER
230VAC
-TERM_X513
=ACS6000/161.A5
AUX POWER
400V_60Hz
-TERM_X515
=ACS6000/161.B5
SP. HEATER
1~ 230V
104.E8
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
=WCU1+A05
-WCU1
A
B
C
D
Date
=ACS6000/192.D6
AUX POWER
-G5021
-A5201
=ACS6000/391.D2
TB820
PE
PE_A04
Name
0
-TERM-X511
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
104
105
134
=COU1
+A02
-A2451
CUSTOMER
INTERFACE
NPBA_A
NPBA_B
/102.C3
NPBA-12
X1:1
X1:2
X1:3
X1:4
Data
Data
Data
Data
A
B
A
B
N
P
N
P
X2:8 SH
X2:7 DG
TXD
RXD
X2:5 +24V
X2:6 0V
DC
DC
GND
BUS
TERMINATION
ON
OFF
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
105
134
141
*) PROCESS INTERFACE
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
-W14102
=WCU1+A05
=COU1+A02
-TERM_X17
/105.B5
-X17 -W14101
1
1
DIGITAL INPUT
=COU1+A02
TERM_X17
-X17 -W04102
1
19
-TERM_X1_2
/102.D4
-X1
3 24VDC
2
4
PROCESS STOP INU1
3
5
4
6
OPERATION
PREVENTED INU1
5
15
6
16
OPERATION
1
17
18
2
EMERGENCY STOP
3
19
20
4
-X2 EMERGENCY STOP
5
71
6
72
EMERGENCY-OFF
73
7
74
8
EMERGENCY-OFF
75
9
10 76
EMERGENCY
11 77
RESET
12 78
EMERGENCY
20
21
22
23
24
2
3
4
5
6
DIGITAL INPUT
TERM_X1_2
-X2
79 24VDC
80
MCB STATUS CLOSED
81
82
MCB STATUS OPEN
31
32
MCB PRE-TRIP
DIGITAL OUTPUT
-TERM_X4
RESET
DIGITAL OUTPUT
TERM_X4
INU1 OPERATION
PREVENTED
-X4
55
TERM_X18
-X18
-W14105 1/BN
15
56
3/BK16
/102.E4
-X4
1
2
3
4
5
***) 7
***) 8
6
9
***) 51
***) 52
10
53
54
*) Details
**) Details
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
=WCU1+A05
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
-TERM_X18
/105.C5
-W14103 1 -X181
2
3
4
5
7
2
3
4
5
7
8
6
9
11
8
6
9
11
12 12
10 10
1/BN13
3/BK14
-W14104
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
134
141
161
AUX POWER
3x400V / 60HZ
-X1
=WCU1+A05
-TERM_X1
/105.B3
-X1
1
2
3
PE
-Q5003
-TERM_X2
/105.C3
-X2
1
2
PE
-W16101 1/BN
2/BU
3/BK
WCU1_L1 171.A5
WCU1_L2 171.A5
WCU1_L3 171.A5
-Q5004
-Z5001
-X554
-M5541 M -M5542 M
PUMP 1
PUMP 2
-Q5011
-K5451
-TERM_X515
/105.E5
-X515
PE
1
3
SHC_L
168.E7
2
4
PE
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
/105.D5
-X513
1
2
3
-Q5001
-TERM_X513
-Q5002
SPACE HEATER
CONVERTER
230VAC
-X2
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
141
161
168
TRANSP_UNIT 1
-E5011
161.C5
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
SHC_L
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
161
168
171
5
161.A6 WCU1_L1
161.A6 WCU1_L2
161.A6 WCU1_L3
=COU1+A02
-Q1001_1073
/102.D5
-X20
-Q1004
-T1012
.../230V
3
L3
-Q1003
-V1021
-Z1021
-Z1022
WCU
Date
178.C3 Q1061
LSU1
Name
0
E
F
G
H
Date
-Q1041
-C1026
...28
-C1021
...25
-R1022
-Q2981
24V
271.A1 A02_Q1014
A
B
C
D
-Q1073
-X24_P
I/O Ext. 24VDC
-X24_P2
24VDC
-X24_P1
24VDC
Name
CONTROL
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
GUSP
Date
Date
275.A1 A02_Q2981
WCU
-G1211
184.B3 Q1041
I/O
Ext.
-G1201
COOLING
-Q1051
-Q1061
-Q1071
Control PUMP
&
Regul. Valves
192.D2 Q1071
-X230V
Control
184.D3 Q1051_1
-Q1011
-Q1012
-E1011
192.C2 Q1012
-Q1013
-Q1014
L2
-Q1001
-T1021
-V1022
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
L1
201.E2 Q1003
CBU1
COOLING
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
168
171
178
=LSU1+A01
-G3101
=COU1+A02
AUX POWER DISTRIBUTION
C
171.E2
Q1061
/101.C2
CONTROL VOLTAGE
-X3
21
-W17801 BN
22
BU
-X311
1
2
PE
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
171
178
184
=INU1+A03
-G4101_13
=COU1+A02
AUX POWER DISTRIBUTION
171.E5
Q1041
/103.C2
-X3
65
-W18401 BN
66
BU
-X411
1
2
3
4
5
6
D
171.E3
Q1051_1
-X3
15
-W18402 BN
16
BU
GUSP
G4101
-G4111
G4102
-G4112
G4103
-G4113
~
~
/207.C2
/207.B2
/207.D2
/207.E2
/190.E2
/190.D2
CONTROL VOLTAGE
G4104
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
178
184
190
=LSU1
+A01
-F3111
/101.C6
=INU1
+A03
-G4113
/184.C6
X3.12
=INU1
+A03
-A4121
EAF
X3.11
X3.51
-W19001 A1
X3.52
SH
/454.B1
X1
X2
Sig-In
Sig-Gnd
X3:2 5AF
X3:1
Pwr_In
Pwr_Gnd
A1
TX
-W19002
FO
INT-BOARD
A818
POWER ON
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
184
190
192
=WCU1+A05
-TERM-X512
AC
/105.C5
171.C1
Q1012
WCU
-X3
7
-W19201 1/BN
2/BU
-X512
1
2
WCU
230VAC
=WCU1+A05
-TERM-X511
D
AC / DC
/105.D5
171.C2
Date
Name
Q1071
-X3
71
-W19202
WCU 72
1/BN
-X511
1
2/BU
-G5021/(22)
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
=COU1+A02
CONTROL VOLTAGE
A
B
C
D
Date
Name
0
E
F
G
H
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
190
192
201
=CBU1+A04
-CBU1
=ACS6000/104.A2
=COU1+A02
-X131_132
=CBU1+A04
-Q7121
/102.D5
=ACS6000/104.A4
-X715
1
2
OPEN
3
4
OPEN
3
4
5
6
CLOSED
11
7
8
9
CLOSED
12
10
-W20101 1
-X2
53
54
55
56
-C7011
-C7031
-C7051
-C7012
-A7091
-X2
13
-W20103
14
-X20
4
Q1003
171.E7
F
A
B
C
D
Date
Name
0
E
F
G
H
Date
-W20104
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
DC_+
DC_NP
DC_-
Name
/104.D2
-X714
1
1/BN
-X710
6
400V
2/BU
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
7
PE
0V
PE
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
192
201
207
=INU1
+A03
-G4111
DC_+
/184.B6
-V7101
X3.11
X3.51
-W20701 SH
X1.1 (-)
X3.52
A1
X1.2 (+)
/104.C6
/454.B1
-W20703
FO
-W20704
FO
=INU1
+A03
-A4121
-V7102
/104.D6
A1
/184.C6
X3.51
-W20702
X3.52
SH
X1.1 (-)
A1
X1.2 (+)
-F7102
/104.D6
INT-BOARD
A722
A211
DC_NP
=INU1
+A03
-G4112
=INU1
+A03
-A4121
-F7101
/104.C6
A1
X3.12
/454.B1
-W20705
FO
-W20706
FO
INT-BOARD
A723
A212
X3.11
DC_-
X3.12
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
=CBU1+A04
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
201
207
261
=COU1+A02
DOOR MONITORING
-DOOR_INT
/102.B5
230V
-K2814
-X3
10
-W26101 1
=LSU1+A01
DOOR INTERLOCKING
-K2811
-S3201_02
+24V
-X1 9
-W26102
-X312 1
-K2812
1
4/BU
3/BN
10
/101.C3
A2
A1
-X312
-W26105
=INU1+A03
-S4201_03
-W26106
-X412 1
4/BU
3/BN
10
/103.C3
A2
A1
-X412 4
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
chwekue
W.Kpfer
ACS 6000
Date
Date
DOOR_LOCK_1
262.A6
DOOR_LOCK
262.A6
LOOP2_1
262.A5
LOOP2
262.A5
LOOP3_1
262.A5
LOOP3
LOOP1_1
Prepared
Approved
Project name
262.A4
262.A3
262.A3
LOOP1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
207
261
262
-S7201_03
-X712 1
DOOR_LOCK_1
261.F6
261.F6
261.F5
LOOP2_1
261.F5
LOOP2
261.F5
LOOP3_1
DOOR_LOCK
-W26202
4/BU
3/BN
10
/104.D3
A2
A1
-X712 4
-W26207
-W26208
8
BN
BU
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-W26201 1
=CBU1+A04
LOOP3
LOOP1_1
LOOP1
4
261.F4
261.F3
3
261.F3
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
261
262
271
=COU1+A02
N
L1
/103.D2
-X312
11
2/BU
-W27104
=INU1+A03
-E4151_53
56
2/BU
55
1/BN
54
1/BN
-W27101
=LSU1+A01
-E3151
B /101.C2
-X412
11
12
12
-W27105
=CBU1+A04
-E7151
/104.D2
-X712
11
12
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X3 53
1/BN
A02_Q1014
171.E1
2/BU
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
262
271
275
=COU1+A02
A02_Q2981
0V
24VDC
68
63
-W27504
=INU1+A03
-E4161
64
/103.C2
-X413
3
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X1 67
2/BU
171.E7
1/BN
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
271
275
277
=COU1+A02
CABINET
TEMP.
-TEMP_LS1
-X1 1
=COU1+A02
+24V
-X2 51
-W27701 1
CABINET
TEMP.
-TEMP_CBU
+24V
-W27717
52
1
=LSU1+A01 -X313 1
-B3201
/101.C3
=CBU1+A04 -X713 1
-B7201
/104.D3
-X313 2
-X713 2
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
275
277
278
=COU1+A02
CABINET
TEMP.
-TEMP_INU
+24V
-X155
56
-W27801 1
=INU1+A03 -X413 1
-B4201
/103.C3
T
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X413 2
Date
A0
B
C
D
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
277
278
304
=INU1 INT-BOARD
A304
+A03
A303
-A4121
/454.B1
=INU1 INT-BOARD
A404
+A03
A403
-A4121
-W30401
FO
-W30402
FO
-W30405
-W30406
/454.B1
FO
FO
7
AMC-BOARD =COU1
+A02
-A2401
A704
A703
/411.B2
AMC-BOARD =COU1
+A02
-A2401
A702
A701
/411.B2
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
278
304
371
=INU1 INT-BOARD
+A03
A209
-A4121
/454.B1
INT-BOARD
-W37101 FO
-W37102
FO
=LSU1 PINT-BOARD
+A01
RX2
-A3101
/441.B2
PINT-BOARD
TX2
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A724
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
304
371
375
=LSU1
+A01
-A3101
/441.B2
=LSU1
+A01
-A3101
PINT-BOARD
TX0
-W37501 FO
PINT-BOARD
TX1
-W37502
=INU1
+A03
-A4121
INT-BOARD
A202
/454.B1
INT-BOARD
=INU1
A201
FO
+A03
-A4121
/454.B1
/441.B2
=INU1
+A03
-F4011
FSCD
/103.C6
=INU1
+A03
-F4012
FSCD
A2
A2
-W37513
-W37514
FO
PINT-BOARD
RX0
FO
PINT-BOARD
RX1
/103.D6
=LSU1
+A01
-A3101
/441.B2
=LSU1
+A01
-A3101
/441.B2
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
371
375
391
=COU1
+A02
-A2951
/102.C5
=INU1 INT-BOARD
+A03
A594
-A4121
XV C769 AE101
/454.B1
-W39103
FO
0V
X1.3
24V
X1.2
SIG
X1.1
A1
C
=COU1
+A02
-A2501
=WCU1
+A05
-A5201
/105.E5
FIBRE OPTIC CONNECTIONS
TB820
TX2
RX2
/102.C5
-X4
-W39101 FO
-W39102
-X5
TX1
RX1
FO
-X4
-X5
TB820
RX2
TX2
RX1
TX1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
375
391
411
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
Date
Name
0
/102.D4
=COU1
+A02
-A2401
E
F
G
H
RX CH1
TX
A709
A710
RX CH2
TX
A711
A712
RX CH3
TX
A707
A708
RX CH0
TX
AMC BOARD
A705
A706
DSP56311
RX INT0
TX
PANEL &
BUS
INTERFACE
A701
A702
6 X17
RS485
R P T2 S1 S0
+24V
0V
+24V
0V
Name
F M T1 S3 S2
X14:1
X14:2
X14:3
X14:4
Date
Prepared
Approved
Project name
chwekue
W.Kpfer
ICMC0-ASIC
ACS 6000
/304.A6
Date
Date
X1
64
EXTENSION
PORT
/304.A6
A715
A716
RX CH5
TX
A717
A718
RX CH6
TX
A719
A720
RX CH7
TX
X501
FLASH
MEMORY
SUBPRINT
X502
RX CH4
TX
A713
A714
PROM, SRAM
3BHS227357E01
RX INT1
TX
ICMC1-ASIC
Doc. des.
ATD
3BHS227357E01
Resp. dept.
Doc.No.
A703
A704
= ACS6000
+
Lang. EN
Last sh.
Sh.no.
Cont.sh.
391
411
441
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
Date
Name
0
=LSU1
+A01
-A3101
/101.C6
E
F
G
H
Date
chwekue
W.Kpfer
RX0
RX1
CHANNEL 1+2
RX2
CHANNEL 2
RX3
RX4
/375.B7
/375.B7
/371.D4
3
Prepared
Approved
Project name
ACS 6000
/371.D4
TX0
TX1
CHANNEL 1+2
TX2
CHANNEL 2
TX3
TX4
PINT-BOARD
Name
/375.A2
/375.A2
X11:1
X11:2
X12:1
X12:2
X13:1
X13:2
Date
Date
X14:1
X14:2
X16:1
X16:2
X15:1
X15:2
X21:1
X21:2
X22:1
X22:2
X23:1
X23:2
X24:1
X24:2
3BHS227357E01
X1:1
X1:2
X26:1
X26:2
X2:1
X2:2
Doc. des.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Resp. dept.
Doc.No.
X25:1
X25:2
Last sh.
Sh.no.
Cont.sh.
411
441
454
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
INT-BOARD
3300V
=INU1
+A03
-A4121
/103.C6
/103.C6
=INU1
+A03 SVA, XVC767..
-A4132
9MVA
Date
/103.D6
Name
0
Name
A812
A704
V568
V567
V566
V565
V564
V563
V562
V561
A816
A641
A205
A206
Prepared
Approved
Project name
A208
A705
A203
A805
A204
A804
A210
A814
A202
/375.A3
A815
A201
/375.A3
A715
A714
A531
A592
A541
A302
A551
A402
/207.D7
A212
A723
Doc. des.
A303
/391.A3
A593
A594
A304
/371.B4
/371.A4
A724
A209
A403
/304.A3
7
3BHS227357E01
ATD
3BHS227357E01
Resp. dept.
Doc.No.
A712
A713
A211
A722
/207.B7
A813
Date
Date
A207
2006-09-29 Title
2006-09-29
chwekue
W.Kpfer
A803
INT-BOARD
MOTOR SIDE
=INU1
ACS 6000
A703
V591
=INU1
+A03 SCA, XVC768..
-A4133
Date
E
F
G
H
A802
/190.E7
A818
A817
A702
/304.A3
A404
= ACS6000
+
Lang. EN
+24V 2
0V
+24V 1
X1:3
X1:2
X1:1
Last sh.
Sh.no.
Cont.sh.
V103
V113
441
454
COMPONENT :
DOCUMENT :
WIRING DIAGRAM
=COU1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
FRONT PAGE
2006-09-29
Doc. des.
29.09.2006
Resp. dept.
Doc.No.
ATD
= COU1
+
Lang. EN
3BHS227955E01
No. of sh.
Sh.no.
Cont.sh.
30
001
002
page
title 1
001
002
4
title 2
6
title 3
rev.
ind.
FRONT PAGE
INDEX SHEET
100
101
102
104
105
106
107
120
121
230
240
245
250
251
252
253
254
281
282
283
285
287
290
291
295
296
298
800
AC AUX DISTRIBUTION
230VAC AUX POWER DISTRIBUTION
CONTROL
GUSP AND CONTROL VOLTAGE
GUSP AND CONTROL VOLTAGE
Line Supply Unit CONTROL
AUX POWER SUPPLY 230VAC/24VDC
230VAC/24VDC DISTRIBUTION
230VAC/24VDC DISTRIBUTION
PANEL
AMC-BOARD
PROCESS INTERFACE
COUPLING DEVICE
DIGITAL INPUT MODULE
DIGITAL OUTPUT MODULE
DIGITAL INPUT MODULE
DIGITAL OUTPUT MODULE
DOORLOCK
EXTERNAL DIGITAL INPUT
EMERGENCY STOP
EMERGENCY-OFF
MONITORING
CONTROL UNIT / CAPACITOR BANK UNIT
MOTOR CABINET TEMPERATURE
MCB INTERFACE
MCB INTERFACE
COOLING FAN`S
FUNCTION EARTH
PULSE INTERFACE
POWER STAGE CONTROL
WATER COOLING UNIT
INTERNAL CIRCUIT
EXTERNAL I/O
FRONTDOOR
PROFIBUS ADAPTER
TB820
DI810 + TU830
DO810 + TU830
DI810 + TU830
DO820 + TU831
CONTROL
PROTECTION EARTH
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
INDEX SHEET
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
001
002
100
PE
1
-W004
-PE 1
-W637 1
-W022 1
-W009 1
-Q1003
1.14
1.22
-Q1001
1
3
5
1
3
5
-W018
-W019
13
21
A1
A2
-W024 1
1
-W636
1
-W025
2
4
6
/290.D8
14
22
2
4
6
-Q1004
1.13 /287.B4
1.21
-W001 1
1
-W002
1
-W003
1.14
1.22
1
3
5
2
4
6
1.13 /290.D4
1.21
-W873 1
-W871 1
-X20 1
-W872 1
T1012_1
NO SAFE LINE
CHARGING
VOLTAGE CBU
TRAFO
F
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
101.A1
-X20 4
102.A3
102.A3
102.A3
Date
Date
T1012_2
T1021_U
T1021_V
T1021_W
-W020 1
-W021
101.A1
-W005 1
1
-W006
1
-W007
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
230VAC
DISTRIBUTION
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
002
100
101
PE
2_0V
-W034 1
-W029 1
-W045 1
-W046 1
-W047 1
-W048
/102.A2
.D3
.C1
11 12 13 14
-PE1 1
-XN
.D1
-PE1 4
A
B
C
D
Date
.E1
-W033 1
-X3 7
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Name
E
F
G
H
Date
Name
-PE1 3
.E1
-W032 1
-PE 4
-E1011
-W780 1
-X3 53
WCU
CONTROL
230VAC
1.14
1.22
1.13/287.C4
1.21
-W050 1
CLAMP
DISTRIBUTOR
/120.A2
/120.D2
/120.F3
/121.A4
/121.D5
1 2 3 4
.B1
.B1
/281.E1
.E6
/290.E8
.E3
/102.D4 /281.E4
/102.E8
-XN
-W049 1
PE
-X230V
FAZ-C
-W044 1
-Q1014
FAZ-C
/281.A4
/290.D8
-W043 1
1.13/287.D2
1.21
-Q1013
11 12 13 14
FAZ-C
1.14
1.22
CLAMP
DISTRIBUTOR
-Q1012
-W039 1
-W040 1
-W037 1
-W038 1
1 2 3 4
FAZ-C
-W035 1
-W036 1
-X230V
-Q1011
1.14
1.22
/102.A1
.D2
-W030 1
-W031 1
.E1
1.13/287.C2
1.21
-PE1 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
0V
110V
120V
230V
380V
400V
415V
440V
460V
480V
500V
-T1012
2_230V
100.E7
100.E7
T1012_1
T1012_2
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
-W781 1
55
54
56
AIR COOLING
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
100
101
102
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
3
4
5
.E4
-W150 1
-X1021 2C
-W152 1
-W153
.E4
-X1021 3B
3C
-C1021
-X1021 3D
CU
.E4
5D
CU
-W154 1
2
4
105.B1
-X1021 5B
1
3
-R1022
CTRL_-DC
-C1029
-R1021
CTRL_+DC
-W156 1
105.B1
.E4
-W155 1
5E
-W157 1
2
4
101
102
104
Al
5F
4F
3 1
5C
-W161 1
1
3
Last sh.
Sh.no.
Cont.sh.
CU
-C1026
5A
-PE1 6
-W158 1
/101.E1
= COU1
+
Al
2
GSP_-DC -W162 1
100.E4
100.E4
100.E4
.E4
.E4
104.B1
T1021_U
T1021_V
T1021_W
-X1021 2F
-X1021 1F
9 7
6 5 4
2A
Doc. des.
-X1021 2B
.E4
-W159 1
GSP_+DC -W160 1
Lang. EN
3BHS227955E01
Resp. dept.
Doc.No.
104.B1
-Z1021
-Z1022
-V1022
VUO 60-12NO3
-XN
-W144 1
.E7
.B8
.D7
-W141 1
-PE1 5
/101.E1
5D 5A
5E 5B
5F 5C
-X230V
4 5 6
7 9
4D 4A
4E 4B
4F 4C
1V8
1V7
1V6
1V5
1V4
1V3
1V2
1V1
2N
PE
.B7
.C6
/101.C1 /101.D1
-W581 1 -W582 1
-W140
1 3
-W143 1
4E
-X1021
Date
Date
.E3
.C5
.C8
.D8
.B5
3D 3A
3E 3B
3F 3C
.E6
.D6
.C6
A2
15 /287.C7
25
-W139 1
-V1021
.E4
-W142 1
-X1021 1E
Name
script_ecscad_403
W.Kpfer
.B5
.C8
2D 2A
2E 2B
2F 2C
L3
A1
18
16
28
26
Date
Prepared
Approved
Project name
ACS 6000
.E3
.C5
1D 1A
1E 1B
1F 1C
L1
L2
-W138 1
-W137 1
2W 200V
380V 1W8
400V 1W7
415V 1W6
440V 1W5
460V 1W4
480V 1W3
500V 1W2
690V 1W1
-W136 1
DT
2V 200V
380V
400V
415V
440V
460V
480V
500V
690V
Name
E
F
G
H
VUO 60-12NO3
-T1021
Date
2U 200V
380V 1U8
400V 1U7
415V 1U6
440V 1U5
460V 1U4
480V 1U3
500V 1U2
690V 1U1
-F1021 EMR4-W500-2-C
Rev. ind.
-Q1041
1.14
1.22
FAZ-2-DC
1.13/287.C2
1.21
GSP_+DC
GSP_-DC
1+
3-
102.F6
102.F7
24+
-W060 1
-W061 1
-X3
65
66
INVERTER 1
GUSP
300VDC
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
102
104
105
-W072 1
-W073 1
-Q1051
106.B1
106.B1
1.14
1.22
FAZ-2-DC
+DC
-DC
1.13/287.A3
1.21
CTRL_+DC
CTRL_-DC
1+
3-
102.C8
102.C8
24+
-W066 1
-W067
16
-X3
15
INVERTER 1
CONTROL
300VDC
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
104
105
106
-W078 1
-W079 1
-Q1061
24+
107.B1
107.B1
1.14
1.22
FAZ-2-DC
+DC
-DC
1.13/287.A3
1.21
+DC
-DC
1+
3-
105.B8
105.B8
-W074 1
-W075
22
-X3
21
LSU 1
CONTROL
300VDC
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
105
106
107
-Q1071
1.13/287.B3
1.21
FAZ-2-DC
24+
24+
1.14
1.22
FAZ-2-DC
-Q1073
1+
3-
-W092 1
-W093 1
+DC
-DC
1+
3-
106.B8
106.B8
F
A
B
C
D
Date
Name
E
F
G
H
Date
Name
120.A2
120.A2
WCU
CONTROL
300VDC
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
SUPPLY48V_P1
SUPPLY48V_N1
71
72
-X3
121.A5
121.A5
SUPPLY24V_P1
SUPPLY24V_N1
-W080 1
-W081 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
106
107
120
1 2 3 4 5 6 7
-X24_P2.1 1
11 12 13 14 15 16 17
CLAMP
DISTRIBUTOR
11 12 13 14 15 16 17
CLAMP
DISTRIBUTOR
/240.C2
/251.A2
/298.A2
.E2
/283.A6
/245.D3
/281.A2
-X24_P2
2 3 4 5 6 7
CLAMP
DISTRIBUTOR
11 12 13 14 15 16 17
.B8
-X24_N2.1 1
CLAMP
DISTRIBUTOR
/240.C2
1 2 3 4 5 6 7
11 12 13 14 15 16 17
2 3 4 5 6 7
-X24_P2
13
.B5
-W864 1
-X24_P2.1 13
.B7
-X24_N2
.C5
13
-W865 1
11 12 13 14 15 16 17
.D8
/251.A2
/298.A2
/250.E4
.B8
.E2
-X24_N2
.C8
.E3
/250.E4
11 12 13 14 15 16 17
/290.C2
14
2 3 4 5 6 7
/290.E5
/285.E7
.D2
/295.C4
CLAMP
DISTRIBUTOR
/281.E1
U02
/283.E5
/245.D3
/295.C4
/281.A6
/290.B1
CLAMP
DISTRIBUTOR
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX
11
-X24_P1 4
.B4
-X24_N1 4
2 3 4 5 6 7
-X24_N1 1
-W114 1
-W115
.D2
SUPPLY24V_P1 107.E6
-X24_P1 1
.D2
U01
/290.B5
250W
LWN
2660-6
N 2
-G1201
PE 1
-W109 1
-W110
-W111
-X24_N2.1 13
.C7
.C4
-W116 1
-PE1 9
/101.E1
-W117 1
-W118
-X24_P2 4
.B5
-X24_N2
4 14
.C5
-W119 1
-PE1 10
/101.E1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
/101.E1
L 3
-PE1 8
3
SUPPLY24V_N1 107.E6
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
107
120
121
LWN
2660-6
U01
-W124 1
1
-W125
1 2 3 4
CLAMP
DISTRIBUTOR
11 12 13 14
-X24_N
1 2 3 4
.B8
-X24_N
.C8
-W123 1
CLAMP
DISTRIBUTOR
11 12 13 14
/285.F1
/282.C2
/283.F1
-X24_P
D
-X24_P
U02
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX
11
/285.D1
/282.B2
/283.D1
-G1211
N 2
PE 1
-W120 1
-W121
-W122
.D5
SUPPLY48V_N1
/101.E1
.D5
-PE1 11
-PE1 12
/101.E1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
5
107.E6
SUPPLY48V_P1
L 3
107.E6
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
120
121
230
ON - LED ACTIVATION
(MAIN SUPPLY ON INDICATION)
-H2301
EMERGENCY STOP
-W217 1
FAULT/ALARM
X1
NDPI_02
-W221 1
240.C2
-A2511
/251.B2
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
X1
X2
X1
X2
-H2302
-W222 1
-W223 1
-W220 1
CDP312_2
-W213 1
-S2304
24
/285.A4 23
V2
-S2303
14
/283.C2 13
14
/285.A1 22
34
42
X2
-S2302
14
13
-S2301
X1
X2
V1
Name
-W216 1
14
13
REF
L1+ 24V B4
C4
L1- 0V A4
RES
13
21
33
41
LOC
REM
-A2301
Date
EMERGENCY RESET
DRIVE
-W212 1
A
B
C
D
SUPPLY OFF
X1
X2
FUNC
ENTER
-W224 1
-W225 1
-A2511
/251.B2
L1+ 24V B5
C5
L1- 0V A5
PAR
ALARM / FAULT
LED ACTIVATION
(INDICATION LAMP)
C1_P2_DO06
-A2521
/252.E2
-W219 1
-W218 1
SUPPLY ON
CDP 312R
ACT
B5 L1+ 24V
C5
A5 L1- 0V
B4 L1+ 24V
C4
A4 L1- 0V
PANEL
7
EMERGENCY OFF
RESET LED ACTIVATION
(INDICATION LAMP)
C1_P2_DO07
-A2521
/252.E2
C1_P2_DO05
-A2521
/252.E2
-W214 1
-W215 1
FRONTDOOR
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
C1_P2_DO04
-A2521
/252.E2
B6 L1+ 24V
C6
A6 L1- 0V
B7 L1+ 24V
C7
A7 L1- 0V
C1_P1_DI04
C1_P1_DI05
LOCAL ON - ORDER
(PUSH BUTTON)
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
121
230
240
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
Date
230.E2
/120.B7
A709
A710
RX CH2
TX
A711
A712
RX CH3
TX
RX CH1
TX
A707
A708
DSP56311
RX CH0
TX
A705
A706
RX INT0
TX
RS485
-W589 FO
-W590 FO
R P T2 S1 S0
+24V
0V
+24V
0V
script_ecscad_403
W.Kpfer
FB_INU_RX
FB_INU_TX
F M T1 S3 S2
X14:1
X14:2
X14:3
X14:4
Prepared
Approved
Project name
ACS 6000
245.C7
245.C7
A701
A702
-A2401 AMC-BOARD
CDP312_2
Name
-W585 1
-W586 1
Date
-X24_P2.1 4
/120.C7
-X24_N2.1 4
Name
E
F
G
H
CONNECTED TO
=INU
ICMC0-ASIC
Date
Date
X1
64
EXTENSION
PORT
RX CH4
TX
A715
A716
RX CH5
TX
A717
A718
RX CH6
TX
A719
A720
RX CH7
TX
X501
FLASH
MEMORY
SUBPRINT
X502
-W605 FO
-W606 FO
A713
A714
PROM,SRAM
= COU1
+
TB820_RX
TB820_TX
RX INT1
TX
ICMC1-ASIC
Doc. des.
Lang. EN
3BHS227955E01
Resp. dept.
Doc.No.
250.C7
250.D7
A703
A704
CONNECTED TO
=INU
Last sh.
Sh.no.
Cont.sh.
230
240
245
-A2451
NPBA_A
NPBA_B
CUSTOMER
INTERFACE
NPBA-12
X1:1
X1:2
X1:3
X1:4
A
B
A
B
Data
Data
Data
Data
N
P
N
P
X2:8 SH
X2:7 DG
-X24_P2
-X24_N2
/120.B5
/120.C5
-W624 1
-W625 1
X2:5 +24V
X2:6 0V
DC
DC
GND
TXD
FB_INU_RX
240.E4
RXD
FB_INU_TX
240.E4
BUS
TERMINATION
ON
OFF
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
240
245
250
-A2501 TB820V2
CLUSTER ADRESS
4 5 6
3
7
2
8
1 0 9
F
R
P
Rx1
Rx2
ERx
C
Tx2
Rx2
Tx1
Rx1
BUS
X4
X5
CONNECTED TO
WCU
TB820_RX
TB820_TX
240.E8
240.E8
A2511 251.E1
OUT
SB
L-
SA
L+
-W238 1 -W239 1
-X24_P2 15
/120.B5
-X24_N2
/120.C5
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
15
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
245
250
251
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
C1_P1_DI07
C1_P1_DI08
/AUXILIARIES
PROTECTION
ALARM
/AUXILIARIES
PROTECTION
TRIP
SUPPLY
SWITCH
C1_P1_DI11
SUPPLY
SWITCH
C1_P1_DI12
C1_P1_DI09
C1_P1_DI10
C1_P1_DI13
EXCITATION CONTACTOR
FEEDBACK STATUS
CLOSED
C1_P1_DI14
/INU CUBICLE
TEMPERATURE HIGH
C1_P1_DI15
/COU CUBICLE
TEMPERATURE HIGH
C1_P1_DI16
/287.E4
/287.E2
/282.E3
Doc. des.
/291.E8
/291.E2
6.3A L2+
L2+
L2L2-
-W244 1
-W245 1
OUT
A2521
Last sh.
Sh.no.
Cont.sh.
24V_P2_1
24V_N2_1
= COU1
+
Lang. EN
3BHS227955E01
Resp. dept.
Doc.No.
/PROCESS STOP
/230.E5
STATUS
INU ISOLATOR2 OPEN
GROUNDING SWITCH2 CLOSED
/230.E4
C1_P1_DI06
/285.E6
STATUS
INU ISOLATOR2 CLOSED
GROUNDING SWITCH2 OPEN
C1_P1_DI05
C1_P1_DI04
-X24_N2
LOCAL ON - ORDER
(PUSH BUTTON)
C1_P1_DI03
/120.C5
/287.E7
-W242 1
-W243 1
BUS
Date
Date
C1_P1_DI02
/120.B5
Name
script_ecscad_403
W.Kpfer
B1
C1
A1
B2
C2
A2
B3
C3
A3
B4
C4
A4
B5
C5
A5
B6
C6
A6
B7
C7
A7
B8
C8
A8
B9
C9
A9
B10
B1
C1
C10
A1
A10
B11
C11
A11
B12
C12
A12
B13
C13
A13
B14
C14
A14
B15
C15
A15
B16
C16
A16
Date
Prepared
Approved
Project name
ACS 6000
C1_P1_DI01
-W240 1
-W241
DI810
F
R
W
KEY CODE
AA
IN
E
F
G
H
/UNDERVOLTAGE (RELAY)
L1L1-
-X24_P2
A2511
Name
-A2511 TU830
Date
250.D7
A
B
C
D
L1+
6.3A L1+
SUPERVISION
SUPERVISION
Rev. ind.
252.F1
252.F1
252.B1
250
251
252
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
C1_P2_DO03
C1_P2_DO04
ON - LED ACTIVATION
(MAIN SUPPLY ON INDICATION)
C1_P2_DO05
C1_P2_DO06
ALARM / FAULT
LED ACTIVATION
(INDICATION LAMP)
C1_P2_DO07
EMERGENCY OFF
RESET LED ACTIVATION
(INDICATION LAMP)
C1_P2_DO08
C1_P2_DO09
C1_P2_DO10
C1_P2_DO12
ESTOP IN PROGRESS
(ACTIVATED)
C1_P2_DO11
C1_P2_DO13
C1_P2_DO14
EXCITATION CONTACTOR
ORDER ON COMMAND
Doc. des.
C1_P2_DO15
C1_P2_DO16
SUPERVISION
OUT
-W248 1
-W249 1
A2531
Last sh.
Sh.no.
Cont.sh.
24V_P2_2
24V_N2_2
= COU1
+
Lang. EN
3BHS227955E01
Resp. dept.
Doc.No.
L2+
6.3A
L2+
L2L2-
C1_P2_DO02
BUS
-W246 1
-W247 1
Date
Date
/283.B8
C1_P2_DO01
/230.B7
SUPERVISION
/230.B8
IN
Name
script_ecscad_403
W.Kpfer
/230.B5
A2521
Date
Prepared
Approved
Project name
ACS 6000
/230.B4
B1
C1
A1
B2
C2
A2
B3
C3
A3
B4
C4
A4
B5
C5
A5
B6
C6
A6
B7
C7
A7
B8
C8
A8
B9
C9
A9
B10
C10
A10
B11
C11
A11
B12
C12
A12
B13
C13
A13
B14
C14
A14
B15
C15
A15
B16
C16
A16
F
R
W
O
KEY CODE
AA
TU830
24V_P2_1
24V_N2_1
Name
E
F
G
H
L1+
6.3A
L1+
L1L1-
-A2521 DO810
Date
251.E8
A
B
C
D
251.A8
251.A8
Rev. ind.
253.E1
253.A1
253.A1
251
252
253
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
252.F8
252.F8
DI810
F
R
W
KEY CODE
AA
IN
24V_P2_2
24V_N2_2
A2531
Name
-A2531 TU830
Date
252.B8
A
B
C
D
L1+
E
F
G
H
6.3A L1+
Date
SUPERVISION
/LSU CUBICLE
TEMPERATURE HIGH
C1_P3_DI03
/CBU CUBICLE
TEMPERATURE HIGH
C1_P3_DI04
/CBU CHARGING
OVERLOAD
C1_P3_DI05
C1_P3_DI06
C1_P3_DI07
/EMERGENCY STOP
C1_P3_DI08
BUS
Date
Date
C1_P3_DI09
C1_P3_DI11
/EARTH FAULT
MAIN CIRCUIT ALARM2
C1_P3_DI12
C1_P3_DI13
C1_P3_DI14
C1_P3_DI15
A.) MCB OK
(PRESIGNAL & TRIPPED & AVAILABLE)
B.) /MCB2 OK
(PRESIGNAL & TRIPPED & AVAILABLE)
C1_P3_DI16
/291.E7
/290.E4
/290.E1
/290.E2
/283.E8
/281.E8
/282.E5
Doc. des.
/282.E4
/282.E7
6.3A L2+
L2+
L2L2-
OUT
= COU1
+
Lang. EN
3BHS227955E01
Resp. dept.
Doc.No.
/EARTH FAULT
MAIN CIRCUIT ALARM1
/291.E3
C1_P3_DI10
/291.E4
C1_P3_DI02
/291.E5
-W250 1
-W251 1
B1
C1
A1
B2
C2
A2
B3
C3
A3
B4
C4
A4
B5
C5
A5
B6
C6
A6
B7
C7
A7
B8
C8
A8
B9
C9
A9
B10
B1
C1
C10
A1
A10
B11
C11
A11
B12
C12
A12
B13
C13
A13
B14
C14
A14
B15
C15
A15
B16
C16
A16
script_ecscad_403
W.Kpfer
C1_P3_DI01
L1L1-
Name
Prepared
Approved
Project name
ACS 6000
/ARU3 CUBICLE
TEMPERATURE HIGH
SUPERVISION
Rev. ind.
A2541
Last sh.
Sh.no.
Cont.sh.
254.B2
252
253
254
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
Date
Name
E
F
G
H
253.E8
Date
A2541
Name
Date
Date
A3
B4
/295.B6
A5
B6
/295.B7
A6
B7
/290.B5
A7
B8
/296.B1
A8
C1_P4_DO03
C1_P4_DO04
MCB -ORDER
CLOSE COMMAND
C1_P4_DO05
/MCB -ORDER
OPEN COMMAND
C1_P4_DO06
/MCB ORDER
TRIP
C1_P4_DO07
C1_P4_DO08
DRIVE CHARGED
(DC LINK VOLTAGE >
MCB CLOSING LEVEL)
A4
B5
BUS
/295.B5
C1_P4_DO02
A2
B3
/290.B6
C1_P4_DO01
-A2541 DO820
A1
B2
IN
/290.B8
F
R
W
O
KEY CODE
AD
script_ecscad_403
W.Kpfer
TU831
Prepared
Approved
Project name
ACS 6000
B1
OUT
-R2541
Doc. des.
TB807
= COU1
+
Lang. EN
3BHS227955E01
Resp. dept.
Doc.No.
IN
Last sh.
Sh.no.
Cont.sh.
253
254
281
DOORS
CLOSED
DOORS
RELEASE
DEENERGIZE
-X24_P1 6
-X230V
/120.B4
-W316 1
22
24
-K2902
A
B
C
D
Date
Name
14
15
A2
-W308 1
LOOP 2
-X3 6
-W310 1
-K2814
4s
-W312 1
-W311 1
A1
A2
11 .D6
21 .D8
31
E
F
G
H
Date
-K2812
-W309 1
18 15 .C6
16
28 25 .D8
26
Name
18
16
4s
Prepared
Approved
Project name
ACS 6000
/101.D1
25
.E2
-W324 1
A1
-A2531
/253.B2
A2
14
14
12
24
22
34
32
Date
Date
28
26
12
14
-K2813
26
28
-K2811
-W314 1
-XN
script_ecscad_403
W.Kpfer
-W325 1
A2
18 15 .C6
16
28 25 .C8
26
/290.B2
.E3
GROUND
SWITCH
OPEN
-K2901
25
-K2814
-W323 1
A1
-W313 1
14
12
24
22
34
32
10
LOOP 3
A2
.E3
22
24
21
-K2812
-W327 1
-W326 1
DOOR
CLOSED
-W322 1
A1
A1
-K2811
.E2
11
/290.B2
11 /290.B8
21 /285.C7
31 /285.A6
21
10
9
22
-W329 1
L2+ 24VB13
C13
L2- 0V A13
A2
12
-K2902
-W321 1
11
15
.E3
14
12
21
DOOR
RELEASE
DEENERGIZE
-K2812
32
34
22
-W328 1
-W320 1
31
LOOP 1
11
.E3
11
DOOR 1
-XN
/101.D1
-K2814
A1
DOOR N
/120.C4
11
-K2811
-X24_N1 6
-W303 1
12
-X1 10
-W307 1
K3
16
18
-X3 5
285.A7
-W318 1
24V_P1
K2
/285.D1
-W306 1
-W304 1
-W300 1
-F2851
RELEASE
CLOSED
21
14
22
/290.B2
-X1 8
-W301 1
-X1 9
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-W317 1
K1
13
21
-S2811
-X24_P1 16
11
/101.C1
-W305 1
-W299 1
SWINGFRAME
MONITORING
13
/120.B4
-W298 1
-X1 7
DOORS
CLOSED
CONTROL
C1_P3_DI13
CUBICLE DOOR(S) FEEDBACK STATUS CLOSED
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
254
281
282
PROCESS STOP
MCB STATUS
CLOSED
MCB STATUS
OPEN
/MCB
( PRESIGNAL &
TRIPPED )
-X24_P
-X2 79
-W331 1
80
81
-W333 1
82
31
-W334 1
32
EMERG_STOP
-X1 3
-W330 1
283.C4
F
A
B
C
D
Date
Name
E
F
G
H
Date
Name
/253.B2
A1
12
14
12
14
-A2531
/253.B2
11
-W354 1
-A2531
/253.B2
L2- 0V
-A2531
.C7
L2- 0V
L2- 0V
/251.B2
-W352
11 .D7
21
31
-K2825
L2+ 24VB14
C14
A14
11
-A2511
-W350
L2+ 24VB13
C13
A13
-W346
-K2824
.C6
14
12
24
22
34
32
-W355 1
11
-K2823
.C4
11 .D5
21
31
14
12
24
22
34
32
-W353 1
12
14
12
14
-K2821
-W341 1
L2+ 24VB16
C16
A16
-W351 1
-W347 1
.C3
-W340 1
11 .D4
21
31 /285.B6
14
12
24
22
34
32
-K2825
A2
-W338 1
11 .D3
21
31
14
12
24
22
34
32
A2
-W337 1
L2- 0V
12
11
/121.C8
-K2824
L2+ 24VB15
C15
A15
-X24_N
-K2823
A2
-K2821
-W345 1
A2
A1
A1
-W344 1
A1
-W343 1
-W336 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
/121.B8
12
C1_P1_DI13
C1_P3_DI15
C1_P3_DI14
C1_P3_DI16
/PROCESS STOP
A.) MCB OK
(PRESIGNAL & TRIPPED & AVAILABLE)
B.) /MCB2 OK
(PRESIGNAL & TRIPPED & AVAILABLE)
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
281
282
283
EMERGENCY-STOP
LOOP (I>> -HW)
/EMERGENCY-STOP
-X24_P2
/120.B5
-X2 75
285.A4
76
-X2 59
60
-X2 17
18
-W367 1
26
28
-W361
-W370 1
-K2833
ESTOP IN PROGRESS
(ACTIVATED)
-A2521 A2521 DO12
19
20
/252.E2
-W366 1
-W368 1
-W369 1
-W866 1
25
.E7
-W363 1
14
/230.C7
-W360 1
-W365 1
K1
K2
K2
K3
K1
K1
K2
K2
K2
0,15s..10min
-W357 1
Date
Name
13
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
-W867 1
/120.C5
42
34
24
A2
PE
14
-X24_N2
A
B
C
D
33
K2
.D1
K3
24
34
K3
-W377 1
-W379 1
-W374 1
-K2831
-F2831
41
.C7
K1
K1
K3
K3
/121.C8
K2
.D1
-W373 1
.C8
33
13
T22
T12
T12
K3
K1
24V
-X24_N
-F2831
14
K2
T34
.C6
S1
X1
X2
T11
BN5930
24VDC
A1
-F2831
K2
.D1
K1
K1
K3
/121.B8
-W356 1
-F2831
13
23
-X24_P
25
.E5
K1
282.B7
-K2831
-W380 1
23
26
28
13
-S2304
-W372 1
13
-W364 1
-W358 1
28
26
.E6
-W378 1
EMERG_STOP
25
-K2832
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-W359 1
-W371 1
-W362 1
A1
-K2832
A2 0,15s..10min
-W375 1
18 15 /285.C1
16
28 25 .C3
26
A1
A2
A1
-K2833
2s
A2
-W376 1
18 15 /285.C2
16
28 25 .C3
26
-A2531
/253.B2
18 15 /285.C1
16
28 25 .B3
26
Doc. des.
Resp. dept.
Doc.No.
L1-
ESR
/EMERGENCY-STOP
C8
0V A8
L1+ 24V B8
2
EMERGENCY-STOP
RESET
B12L2+ 24V
C12
A12 L2- 0V
A2531 DI08
/EMERGENCY STOP
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
282
283
285
-F2851
.D1
A
B
C
D
Date
/121.C8
Name
24
41
42
-A2511
/251.B2
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
-Z2852
A1
/120.C4
11
A2
-X24_N1 13
C1_P1_DI02
42
34
K2
-W421 1
K2
14
K2
PE
A2
-W389 1
K1
K1
.D1
K2
24
K1
K3
22
24
A2
-K2851
A1
-F2851
K1
K2
K2
-W427 1
L1+ 24V B2
C2
L1- 0V A2
K1
-W425 1
-W422 1
K3
-X24_N
-W424 1
.D8
41 .D6
/290.C8
33
23
13
T22
K1
K3
K1
24V
T12
T12
K3
.B7
/281.A6
K2
T34
X2
S1
X1
-W388 1
BN5930
24VDC
-K2852
62
18
16
16
18
15
-W387 1
T11
-F2851
-W401 1
-W406 1
11
A1
D -X24_P
/121.B8
-K2813
/281.E6
61
15
/283.E6
-W386 1
-K2833
/283.E7
61
15
-K2832
-W426 1
-W423 1
.D7
-W409 1
-W385 1
62
16
18
-K2851
K2
K3
-W408 1
-K2831
/283.E5
295.B4
K1
31
-K2823
/282.C4
EMERG_LOOP_OK
-W407 1
-W398 1
-K2852
-K2813
/281.E6
-Z2851
2
1
24
/230.C7
-W399 1
-W395 1
23 24V_P1 281.A7
78
32
34
23
-W394 1
21
77
-S2304
ESR
-W397 1
-W396 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
22
/230.C3
EMERG. OFF 1
-W382
-X2 71 72 73 74
-W393 1
-S2301
22 23 24 25 26 27 28
-W390 1 -W391 1
-W392 1
21
-W383 1
-W840 1
-X1 51 52-X2 21
-W381 1
34
32
283.A2
/EXTERNAL
EMERGENCY RESET
/EXTERNAL
EMERGENCY-OFF
31
2
EMERGENCY-OFF
CUBICLES
-W400 1
Doc. des.
Resp. dept.
Doc.No.
13
21
31
43
53
61
14
22
32
44
54
62
/296.B7 13
/296.C3 21
/296.C6 31
43
53
61
.C6
= COU1
+
Lang. EN
3BHS227955E01
14
22
32
44
54
62
Last sh.
Sh.no.
Cont.sh.
/296.C7
/296.C4
/296.C6
.C6
283
285
287
1.13
-Q1051
1.14
/105.C3
-W283 1
-W295 1
1.13
1.13
-W284 1
-Q1061
-Q2981
/298.A2
-W285 1
1.13
-W294 1
1.13
-Q1071
-Q1004
1.14
/100.C7
1.14
/107.C2
1.13
1.13
-W293 1
-Q1041
-Q1014
/104.C3
1.14
1.14
/101.C7
-W280 1
-W297 1
16
18
1.13
-W292 1
-Q1012
-F1021
/101.C4
1.14
/102.A1
15
-W296 1
1.13
-W279 1
-Q1011
1.14
/101.C2
C1_P1_DI12
F
A
B
C
D
Date
Name
/AUXILIARIES SUPPLY
PROTECTION SWITCH
TRIP
Date
Name
E
F
G
H
/251.B2
C1_P1_DI11
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
/AUXILIARIES SUPPLY
PROTECTION SWITCH
ALARM
2006-09-29 Title AUX POWER SUPPLY
Date
MONITORING
2006-09-29
Date
L1- 0V
-A2511
L1+ 24V B1
C1
A1
L2- 0V
/251.B2
-A2511
L2- 0V
/251.B2
C12
A12
-A2511
L2+ 24VB12
C11
A11
-W289 1
-W278 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
1.14
1.14
/106.C4
C1_P1_DI01
/UNDERVOLTAGE (RELAY)
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
285
287
290
CBU GROUNDING
SWITCH CLOSED
CBU - HV
CHARGING ORDER
CBU - LV
CHARGING ORDER
A1
/120.B4
-K2902
A1
B1
A2
-W441 1
/281.E6
-W448 1
33
-X24_N1 17
K1
A
B
C
D
Date
C1_P3_DI07
C1_P3_DI05
/CBU CHARGING
OVERLOAD
Name
/253.B2
E
F
G
H
Date
Name
/253.B2
Prepared
Approved
Project name
-X24_N1 12
/120.C4
script_ecscad_403
W.Kpfer
ACS 6000
-XN
-W443 1
-X2 11
24V
L1-
L1+ 24V B7
C7
L1- 0V A7
-A2531
1
2
-W451 1
-W442 1
-W439
-Z2901
/100.C5
L1-
C6
0V A6
-A2531
A1
1.13
/100.C5
12
-Q1003
-Q1003
-W437 1
L1+ 24V B6
/101.C1
C1_P3_DI06
/253.B2
-X230V
C5
0V A5
-W436
-A2531
-W449 1
-K2902
.B2
K2
/285.D1
-W438 1
24
22
.B2
-F2851
-W445 1
K3
L1+ 24V B5
-K2901
-W444 1
-W435 1
21
11 .D3
21 /281.B4
31 /281.C7
11
-W434 1
14
12
24
22
34
32
1.14
11 /281.D6
21 .D2
31
14
12
24
22
34
32
34
/120.C4
14
12
A2
-W432 1
-W433 1
-K2813
A2
A2
-K2901
B2
-X24_P1 12
-W431 1
-W447 1
-W450
12
14
/120.B4
-W430 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X24_P1 17
A7
-W428 1
/254.E3
56
B7
54
55
-W429 1
-A2541 C1_P4_DO01
/254.E3
-W440 1
-X2 53
RELEASE CBU
GROUNDING SWITCH
ELECTRICAL LOCKING
A1
CBU GROUNDING
SWITCH OPEN
11
/101.D1
12
13
12
14
24V
TO CBU
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
287
290
291
LINE SIDE
CONTROL
LINE SIDE
-X1 1
1
2
61
8
MOTOR SIDE
DC LINK
(CBU)
LSU1
-W463 1
CBU
2
INU1
-W465 1
62
65
-W458 1
66
-X2 51
52
-X1 55
56
-W459 1
-W456 1
-W455 1
-W457 1 -W461 1
-W462 1
-W464 1
-W466 1 -W467 1
-W460 1
-W468 1
F
A
B
C
D
Date
Name
-A2511
/251.B2
L2+ 24VB15
C15
L2- 0V A15
-A2531
/253.B2
L1+ 24V B4
C4
L1- 0V A4
-A2531
/253.B2
L1+ 24V B2
C2
L1- 0V A2
-A2531
/253.B2
L1+ 24V B3
C3
L1- 0V A3
-A2531
/253.B2
L2+ 24VB16
C16
L2- 0V A16
-A2511
/251.B2
L1+ 24V B1
C1
L1- 0V A1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
6
LINE SIDE
C1_P1_DI16
C1_P3_DI03
C1_P3_DI02
C1_P3_DI01
C1_P3_DI04
C1_P1_DI15
/COU CUBICLE
TEMPERATURE HIGH
/LSU CUBICLE
TEMPERATURE HIGH
/ARU3 CUBICLE
TEMPERATURE HIGH
/CBU CUBICLE
TEMPERATURE HIGH
/INU CUBICLE
TEMPERATURE HIGH
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
290
291
295
A
MCB -ORDER
CLOSE COMMAND
/MCB -ORDER
OPEN COMMAND
/MCB ORDER
TRIP
285.A8
-W516 1
-X24_P1 15
A6
A5
A4
-W520 1
EMERG_LOOP_OK
B6
/254.E3
B5
/254.E3
B4
-W521 1
-W517 1
-W518 1
/120.B4
-X24_N1 15
/120.C4
-W801 1
CONNECTED TO
INU
MCB
-K2952
-K2953
-W526 1
-W527 1
A1
-K2954
A2
-W525 1
A1
-K2951
A2
-K2950
A1
A2
A1
A2
0V X1.3 -W522
A2
-W519 1
A1
-W528 1
A1
E
14
24
34
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
/254.E3
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
11 /296.C2
21 /296.D2
31 /296.D2
14
24
34
11 /296.C1
21 /296.D1
31 /296.D1
14
12
24
22
34
32
11 /296.E3
21 /296.D3
31 /296.C3
Doc. des.
Resp. dept.
Doc.No.
14
24
34
11 /296.D7
21 /296.D7
31 /296.C7
14
12
24
22
34
32
= COU1
+
Lang. EN
3BHS227955E01
11 /296.E5
21 /296.D5
31 /296.C5
Last sh.
Sh.no.
Cont.sh.
291
295
296
MCB
ORDER CLOSE
A
MCB
ORDER OPEN 1
COIL : (+)
MCB
ORDER OPEN 2
MCB
ORDER TRIP
(-)
DRIVE CHARGED
(DC LINK VOLTAGE >
MCB CLOSING LEVEL)
-A2541 C1_P4_DO08
/254.E3
-K2851
A8
B8
/285.D7
14
14
-W554 1
-W905 1
-W532 1
-K2852
-W533
A
B
C
D
Date
Name
E
F
G
H
Date
Name
34
31
31
/295.D7
32
-W544 1
-W552 1
-K2953
/295.D7
24
-W551 1
-W908 1
14
11
-K2954
/295.D7
11
-W550 1
-W542 1
Prepared
Approved
Project name
-K2953
14
12
14
12
/295.D8
-W534 1
-W902 1
-K2953
/285.D8
-W545 1 -W543 1
-W906 1
11
34
31
/295.D6
-K2852
21
21
24
/295.D8
-W553 1
21
-W546 1
-K2952
/295.D5
/285.D7
-K2954
-W537 1 -W535 1
-K2950
-K2851
32
22
-W536 1
/295.D8
34
32
/285.D8
-W549 1 -W909 1
31
31
21
21
22
-K2954
-K2852
-X4 2
/295.D6
-W903 1
-W529 1
/285.D7
-W548 1
22
24
21
21
24
31
/295.D6
-K2851
-K2952
/295.D5
34
-K2951
-W547 1
-W541 1 -W907 1
-W538 1
-W904 1
-W530 1
/295.D6
-K2950
/295.D6
31
14
/295.D5
-W531 1
-K2951
-K2952
-K2950
34
32
11
/295.D6
-W540 1
22
24
-K2951
11
14
-W539 1
13
/285.D8
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
13
-W555 1
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
10
52 51
53
Doc. des.
Resp. dept.
Doc.No.
54
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
295
296
298
-X24_N2
/120.C5
-X24_P2 7
1+
3-
-Q2981
24+
1.14
1.22
FAZ-2-DC
>
0..60C
-W570 1
-W576 1
-W574 1
-W579 1
-W571 1
-X1 57
-W575 1
-W580 1
58
63 64
67 68
-W578 1
-W573 1
INU
-W577 1
-W572 1
CONNECTED TO
M
=
F
A
B
C
D
Date
Name
E
F
G
H
Date
M
=
Name
M
=
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
M
=
Date
Date
-M1
M
=
-M2
-M3
M
=
-M4
M
=
Doc. des.
Resp. dept.
Doc.No.
RD
BU
-M4
RD
BU
-M3
RD
BU
-M2
-E2982
RD
BU
RD
BU
RD
BU
-M1
RD
BU
RD
BU
-E2981
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
/120.B5
-W568 1
-W569 1
1.13/287.A4
1.21
M
=
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
296
298
800
=COU1
DC+
DC-
=INU:L1
=INU:L2
=INU:L3
=LSU:1L1
=LSU:1L2
=LSU:1L3
=LSU:2L3
=LSU:2L2
=LSU:2L1
PG
PE
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
BUSBAR CONFIGURATION 1
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
298
800
COMPONENT :
E
DOCUMENT :
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
2006-09-29 Title
FRONT PAGE
2006-09-29
Doc. des.
22.09.2006
Resp. dept.
Doc.No.
ATD
= WCU1
+
Lang. EN
3BHS227354E01
No. of sh.
Sh.no.
Cont.sh.
16
001
002
title 1
4
title 2
001
002
FRONT PAGE
INDEX SHEET
500
501
502
520
521
522
523
540
541
545
554
571
573
574
AC AUX DISTRIBUTION /
SPACE HEATER
POWER SUPPLY
COUPLING DEVICE
DIGITAL INPUT MODULE
DIGITAL OUTPUT MODULE
ANALOG INPUT MODULE
INTERNAL DIGITAL INPUT
WATER COOLING PUMP
THERMOSTAT
WATER COOLING CONTROL
EXTERNAL DIGITAL INPUT
EXTERNAL DIGITAL OUTPUT
COOLING FAN`S
6
title 3
rev.
ind.
-
COOLING CONTROL
CONTROL
TB820
DI810 + TU830
DO820 + TU831
AI810 + TU830
3 - WAY VALVE
HEATING
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
page
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
INDEX SHEET
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
001
002
500
COOLING PUMP 1
COOLING PUMP 2
POWER SUPPLY
COU
1/BN
2/BU
3/BK
1
3
5
1
3
5
2
4
6
FN258-16/29
Cy
R1
Cx
A
B
C
D
Date
Name
E
F
G
H
Date
Name
CONNECTED TO
COU
554.A4
554.A4
554.A4
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
R2
R1
MOT2_U
MOT2_V
MOT2_W
MOT1_U
MOT1_V
MOT1_W
554.A2
554.A3
554.A3
L3_OUT
Cy
L2_OUT
L1_OUT
1/BN
2/BU
3/BK
1/BN
2/BU
3/BK
-W010
Cx
Cx
-W006
E_IN
3*480VAC/16A
-Z5001
E_OUT
-W014 1
-W015
-W016
L3_IN
1.13 /540.A3
1.21
1.14
1.22
A2
2
4
6
2
4
6
A2
A1
L2_IN
/541.D4
-Q5004
13
21
13
21
A1
-Q5003
/540.A6 14
22
1
3
5
1.13 /540.A1
1.21
1.14
1.22
-Q5002
/541.D3
-W011 1
-W012 1
-W013 1
-W007 1
-W008 1
-W009 1
L1_IN
-W003 1
-W004 1
-W005 1
1
3
5
/540.A5 14
22
-F5001..3
2
4
6
-Q5001
Rev. ind.
-X1 1 2 3 PE
-W001
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Date
Date
2006-09-29 Title
AC AUX DISTRIBUTION /
2006-09-29
COOLING CONTROL
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
002
500
501
230VAC
50/60Hz
A
-Q5011?
1/BN
2/BU
-PE1 2
/502.C7
2
4
-W031
1
3
FAZ
32
34
12
14
-W033 1
1
-W034
31
/545.D6
11
-K5451
-W035 1/BN
2/BU
GNYE
-X515 1 2
3 4
PE
CONNECTION
BOX
-E5011
SPACE HEATER
CONVERTER
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X2 1 2 PE
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
SPACE HEATER
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
500
501
502
WCU CONTROL
300VDC
-
-PE1 5
.C7
2/BU
GNYE
-W043
1/BN
-PE1 3 -X511 1
.C7
-W059 1
-PE 2
.D7
2 3 4 5 6 7 8
U02
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX
11
U01
-PE1 1
250W
24V
LWN
2660-6
-G5021
PE
/500.E6
/501.B4
.B2
.B8
-W046 1
-W047
-W048 1
-W049
-W050
-W051
1
1
-PE
1
.B8
1 2 3 4 5 6 7 8 9 10
GROUNDING BAR
F
A
B
C
D
Date
Name
E
F
G
H
Date
Name
24V_N2
574.B2
574.B2
24V_P2
24V_N1
520.E4
520.E4
24V_P1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
POWER SUPPLY
2006-09-29
CONTROL
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
501
502
520
TB820V2
CLUSTER ADRESS
4 5 6
7
3
2
8
1 0 9
F
R
P
Rx1
Rx2
ERx
X4
Tx2
Rx2
X5
CONNECTED TO
COU
Tx1
Rx1
BUS
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
521.E1
24V_P1
-W064 1
24V_N1
521.A1
521.A1
24V_N1
-W063 1
502.E2
502.E2
24V_P1
A5211
OUT
SB
L-
SA
L+
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-A5201
Date
Date
2006-09-29 Title
COUPLING DEVICE
2006-09-29
TB820
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
502
520
521
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-W065
-W068
-W067
24V_N1
24V_P1
L1+
L1+
L1-
Name
script_ecscad
W.Kpfer
C2_P1_DI02
WCU PUMP 1
CONTACTOR-FEEDBACK
STATUS CLOSED
C2_P1_DI03
WCU PUMP 2
CONTACTOR-FEEDBACK
STATUS CLOSED
C2_P1_DI04
C2_P1_DI05
C2_P1_DI06
C2_P1_DI07
C2_P1_DI08
BUS
C2_P1_DI09
C2_P1_DI11
C2_P1_DI12
/WCU PROTECTION
SWITCH ALARM
C2_P1_DI13
/WCU CUBICLE
TEMPERATURE HIGH
C2_P1_DI14
C2_P1_DI15
Doc. des.
6.3A
/540.D6
/554.C7
/554.D7
/540.D8
/545.D2
L2+
L2+
L2L2-
OUT
= WCU1
+
Lang. EN
Last sh.
Sh.no.
Cont.sh.
A5221
3BHS227354E01
Resp. dept.
Doc.No.
C2_P1_DI16
/540.D5
C2_P1_DI10
/540.D3
2006-09-29 Title
DIGITAL INPUT MODULE
2006-09-29
DI810 + TU830
/540.D1
Date
Date
WCU PUMP 2
THERMAL PROTECTION RELAY
STATUS CLOSED
B1
C1
A1
B2
C2
A2
B3
C3
A3
B4
C4
A4
B5
C5
A5
B6
C6
A6
B7
C7
A7
B8
C8
A8
B9
C9
A9
B10
C1
A1
B11
C11
A11
B12
C12
A12
B13
C13
A13
B14
C14
A14
B15
C15
A15
B16
C16
A16
Prepared
Approved
Project name
ACS 6000
WCU PUMP 1
THERMAL PROTECTION RELAY
STATUS CLOSED
L1-
C2_P1_DI01
SUPERVISION
24V_P1
-W066
TU830
DI810
F
R
W
KEY CODE
AA
IN
Date
24V_N1
-A5211
A5211
Name
E
F
G
H
6.3A
SUPERVISION
520.E7
Date
520.E7
A
B
C
D
520.D7
Rev. ind.
523.A1
523.A1
522.B2
520
521
522
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
Date
Name
E
F
G
H
521.E8
Date
A5221
Name
/541.B7
A5
B6
/541.B8
A6
B7
2006-09-29 Title
DIGITAL OUTPUT MODULE
2006-09-29
DO820 + TU831
A7
B8
A8
C2_P2_DO03
C2_P2_DO04
C2_P2_DO05
C2_P2_DO06
A4
B5
/541.B4
C2_P2_DO02
BUS
A3
B4
Date
Date
/541.B3
A2
B3
C2_P2_DO01
-A5221 DO820
A1
B2
IN
/545.B6
F
R
W
O
KEY CODE
AD
script_ecscad
W.Kpfer
TU831
Prepared
Approved
Project name
ACS 6000
B1
C2_P2_DO07
C2_P2_DO08
WCU CHILLER
ORDER ON
COMMAND
OUT
A5231
Doc. des.
523.E1
= WCU1
+
Lang. EN
3BHS227354E01
Resp. dept.
Doc.No.
Last sh.
Sh.no.
Cont.sh.
521
522
523
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
521.A8
521.A8
522.B7
Date
C2_P3_AI05
AMBIENT TEMPERATURE
SUPERVISIONTRANSDUCER
C2_P3_AI06
C2_P3_AI07
Doc. des.
C2_P3_AI08
TB807
522
523
540
-W073 1 24V_P1
-W074 1 24V_N1 545.C5
545.E5
OUT
-R5231
= WCU1
+
Last sh.
Sh.no.
Cont.sh.
IN
L2+
L2+
L2L2-
/545.D3
6.3A
Lang. EN
3BHS227354E01
Resp. dept.
Doc.No.
/554.E7
/554.E5
C2_P3_AI04
/554.E4
MUX.
BUS
2006-09-29 Title
ANALOG INPUT MODULE
2006-09-29
AI810 + TU830
/554.E3
-W071 1
-W072 1
Date
Date
C2_P3_AI03
/554.E2
script_ecscad
W.Kpfer
Name
Prepared
Approved
Project name
ACS 6000
C2_P3_AI02
L1+
L1+
L1L1-
B1
B2
C1
C2
A1
A2
B3
B4
C3
C4
A3
A4
B5
B6
C5
C6
A5
A6
B7
B8
C7
C8
A7
A8
B9
B10
C9
C10
A9
A10
B11
B12
C11
C12
A11
A12
B13
B14
C13
C14
A13
A14
B15
B16
C15
C16
A15
A16
C2_P3_AI01
24V_P1
24V_N1
TU830
AI810
F
R
W
KEY CODE
AE
IN
Date
-A5231
A5231
Name
E
F
G
H
6.3A
1.13
13
1.14
1.14
-Q5741
/574.B4
-Q5003
/500.C4
14
-Q5002
/500.C2
14
-Q5003
/500.C4
1.14
-Q5002
/500.C2
13
1.13
1.13
1.13
-Q5011
1.14
-W095 1
F
A
B
C
D
Date
-W092 1
-W093 1
-A5211
/521.B2
-A5211
/521.B2
-W097
-A5211
/521.B2
L2+ 24VB13
C13
L2- 0V A13
-W090 1
-W091 1
L1+ 24V B4
C4
L1- 0V A4
-A5211
/521.B2
L1+ 24V B1
C1
L1- 0V A1
-A5211
/521.B2
-W088 1
-W089 1
L1+ 24V B3
C3
L1- 0V A3
-W086 1
-W087 1
L1+ 24V B2
C2
L1- 0V A2
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-W162 1
C2_P1_DI01
C2_P1_DI02
C2_P1_DI03
C2_P1_DI04
C2_P1_DI13
WCU PUMP 1
THERMAL PROTECTION RELAY
STATUS CLOSED
WCU PUMP 2
THERMAL PROTECTION RELAY
STATUS CLOSED
WCU PUMP 1
CONTACTOR-FEEDBACK
STATUS CLOSED
WCU PUMP 2
CONTACTOR-FEEDBACK
STATUS CLOSED
/WCU PROTECTION
SWITCH ALARM
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
INTERNAL DIGITAL INPUT
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
523
540
541
WCU CONTROL
230VAC
60Hz
A6
B6
A5
B5
A4
B4
-W160 1
A3
2
230V~_N
230V~_L
-X512 1
B3
-W101 1
-W102 1
-W103 1
C
-W100 1
-W106 1
-W108 1
-W107 1
-W109 1
14
12
24
22
34
32
F
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
WATER COOLING PUMP
2006-09-29
3 - WAY VALVE
11 .D7
21 .D8
31
Doc. des.
Resp. dept.
Doc.No.
21
22
24
-W110 1
554.A1 CLOSE_230V~_L
-K5542
.D6
554.A1 230V~_N
-W105 1
11
-K5542
.D6
554.A1 OPEN_230V~_L
-W104 1
-K5542
A2
-Z5412
12
14
A1
A1
-Q5003
/500.C4
A2
-Z5411
A2
-Q5002
/500.C2
A1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
540
541
545
B1
zero span
I
523.A8
24V_P1
-W158 1
-W159
-W116 1
F
A
B
C
D
Date
Name
C2_P3_AI06
/WCU CUBICLE
TEMPERATURE HIGH
AMBIENT TEMPERATURE
SUPERVISIONTRANSDUCER
Date
A2
U I
MUX
C2_P1_DI14
E
F
G
H
-K5451
B11
B12
L2+ 24V
C11
C12
L2- 0V A11
A12
-A5231
/523.B2
L2+ 24VB14
C14
L2- 0V A14
A1
-W113 1
-W114 1
-A5211
/521.B2
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
TEMPERATURE SENSOR
4-20mA
-50-100C
2
3
-B5631
A1
PT100
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
523.A8
24V_N1
14
12
34
32
Date
Date
2006-09-29 Title
THERMOSTAT
2006-09-29
HEATING
11 /501.D3
31 /501.D3
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
541
545
554
PE
-X554 U1
V1
W1
PE
-X554 U2
500.E4
MOT2_W
500.E4
MOT2_V
500.E4
MOT2_U
500.E2
MOT1_W
500.E2
MOT1_V
500.E2
MOT1_U
541.F7
541.F7
3
V2
W2
PE
-M5542
-B5523
-B5502
-B5501
bar
4...20
mA
4...20
mA
C2_P3_AI01
WCU COOLING WATER
CONDUCTIVITY-TRANSDUCER
F
A
B
C
D
Date
Name
E
F
G
H
Date
Name
5 6
7 8
9 10
U I
MUX
C2_P3_AI02
WCU COOLING WATER PUMP
INPUT SIDE PRESSURETRANSDUCER
script_ecscad
Prepared
W.Kpfer
Approved
Project name
ACS 6000
/523.B2
U I
MUX
-A5231
/523.B2
U I
MUX
L1- 0V
-A5231
L1+ 24V
/523.B2
L1- 0V
-A5231
B7
B8
C7
C8
A7
A8
3 4
B5
B6
C5
C6
A5
A6
9 10
L1+ 24V
U I
MUX
7 8
L1- 0V
L1+ 24V
/523.B2
1 2
L1+ 24V
-A5231
L1- 0V
B1
B2
C1
C2
A1
A2
-W122 1 2
3 4
B3
B4
C3
C4
A3
A4
-X551 5 6
C2_P3_AI03
C2_P3_AI04
WCU COOLING WATER PUMP
WCU COOLING WATER
OUTPUT SIDE PRESSURETEMPERATURE (INTERNAL)TRANSDUCER
TRANSDUCER
2006-09-29 Title
Date
WATER COOLING CONTROL
2006-09-29
Date
L1+ 24V
L1- 0V
-A5211
-X552
24VDC 10
LS 11
0V 12
5
/521.B2
4...20
mA
-X553 1
-A5211
2
3
bar
4...20
mA
-W161 1
/521.B2
A8 C8B8
-X552
24VDC 7
LF
8
9
0V
C2_P1_DI07
-M5541
C2_P1_DI08
A7 C7B7
4
5
6
-A5231
/523.B2
L1+ 24V
L1- 0V
B9
L2+ 24V B10
C9
C10
L2- 0V A9
A10
-K5541
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X553 4
OPEN_230V~_L
CLOSE_230V~_L
230V~_N
541.F8
U I
MUX
C2_P3_AI05
WCU COOLING WATER
TEMPERATURE (EXTERNAL)TRANSDUCER
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
545
554
571
PROCESS STOP
NOT USED
/EMERGENCY-STOP
/EMERGENCY-STOP
/EXTERNAL
EMERGENCY-OFF
/EXTERNAL
EMERGENCY-OFF
6
EMERGENCY-STOP
RESET
( OPTIONAL )
EMERGENCY-OFF
RESET
( OPTIONAL )
MCB STATUS
CLOSED
8
MCB STATUS
OPEN
/MCB
( PRESIGNAL &
TRIPPED )
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
CONNECTED TO
COU
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X17
PE
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
EXTERNAL DIGITAL INPUT
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
554
571
573
CONNECTED TO
COU
CONNECTED TO
COU
16
15
14
13
12
11
10
-X18
PE
MCB
ORDER CLOSE
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
MCB
ORDER OPEN 1
E
F
G
H
Date
Name
MCB
ORDER OPEN 2
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
INU OPERATION
PREVENTED
MOTOR 1
MCB
ORDER TRIP
Date
Date
2006-09-29 Title
EXTERNAL DIGITAL OUTPUT
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
571
573
574
-Q5741
24+
1.14
1.22
FAZ_DC
1.13/540.A8
1.21
1+
3-
>
M
=
-M2
M
=
-M3
-M4
M
=
RD
BU
RD
BU
RD
BU
-M1
2/BU
-E5741
RD
BU
-W156
1/BN
-B5741
-W155 1
M
=
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
502.E2 24V_P2
502.E2 24V_N2
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
COOLING FAN`S
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
573
574
COMPONENT :
DOCUMENT :
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
A
B
C
D
Date
13.03.01
01-07-25
01-08-07
01-08-09
Name
S.SCHLEGEL
R. SEILER
P. OBERLE
S.SCHLEGEL
E
F
G
H
Date
03-06-24
03-10-14
07.05.04
06-07-06
Name
S.SCHLEGEL
ST.DUSS
P.OBERLE
P.OBERLE
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
FRONT PAGE
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
No. of sh.
17
Cont.sh.
Sh.no.
page
title 1
title 2
1
2
4
5
400
401
402
403
404
405
410
411
412
413
415
416
420
rev.
ind.
title 3
FRONT PAGE
INDEX SHEET
BUS BAR ARRANGEMENT
CIRCUIT DIAGRAM OVERVIEW
LOCAL DC LINK
OVERCURRENT MONITORING
PHASE-LEG L1
PHASE-LEG L2
PHASE-LEG L3
EMC FILTER
AUX POWER SUPPLY
GATE UNIT POWER SUPPLY
PULSE CONTROL AND
AC CURRENT AND DC VOLTAGE
AIR TO AIR HEAT EXCHANGERS
FAN SUPPLY INT- BOARD
DOOR MONITORING
H
H
E
E
F
E
E
E
H
E
E
H
H
G
G
DC - MEASUREMENT
CURRENT MEASUREMENT
MEASUREMENT INTERFACE
MEASUREMENT
CABINET TEMP. MONITORING
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
A
B
C
D
Date
13.03.01
01-07-26
01-08-07
01-08-09
Name
S.SCHLEGEL
R.SEILER
P. OBERLE
S.SCHLEGEL
E
F
G
H
Date
03-06-24
03-10-14
07.05.04
06-07-06
Name
S.SCHLEGEL
ST.DUSS
P.OBERLE
P.OBERLE
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
INDEX SHEET
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Cont.sh.
Sh.no.
DC+
DC_NP
DC-
DC BUS back
DC+
DC_NP
DC-
DC BUS middle
DC+
DC_NP
DC-
DC BUS front
DC+
DC_NP
DCDC_+
DC_NP
DC_-
OPTION
DC+
DC_NP
DC-
DC_+
DC_NP
DC_-
OPTION
DC+
DC_NP
DC-
DC_+
DC_NP
DC_-
UNIT BEFORE
*)
L1
L1
*)
L2
L2
UNIT BEFORE
*)
L3
L3
TERMINAL UNIT
SEE CONVERTER
HW DIAGRAM
OPTION
PG
NEXT UNIT
DC_+
DC_NP
DC_-
=COU or TEU
PG
PE
PE
*)
*) Earthing connection points
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
NEXT UNIT
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
ST.DUSS
W.KPFER
ACS 6000
Date
Date
03-06-24
03-06-26
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Cont.sh.
Sh.no.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-VC1
-C1
-VF4
-VF3
-VF2
-VF1
-VR4
-VR3
-VR2
-VR1
-VN2
-VN1
-C2
S.SCHLEGEL
E.SUTER
ACS 6000
Prepared
Approved
Project name
-L4051
XDC_+
-G4021
-VC2
-L4011
-R4022/3
-R4024/5
-R4001
-A4001
Option
-C4001.1
-C4001
-R4053
-C4001.2
Phase Frame
-L4012 XDC_-
-R4052
-C4053
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
-C4052
-R4002
DC_+
DC_-
-R4051
-C4051
Name
Date
A
B 01-07-25 R.SEILER
C 01-08-07 P. OBERLE
D 01-08-09 S.SCHLEGEL
DC_NP
Rev. ind.
Date
Date
-R4034/5
Phase L1
-RS1
-R4032/3
-G4031
01-03-05
01-04-02
-VC2
-VF4
-VF3
-VF2
-VF1
-VR4
-VR3
-VR2
-VR1
-VN2
-VN1
-RS1
Doc. des.
-R4042/3
-G4041
-VC2
ATDD
3BHS119662E01
Resp. dept.
Doc.No.
-R4044/5
Phase L2
-C1
Title
-L4052
-VC1
-C2
-VC1
-C1
-VF4
-VF3
-VF2
-VF1
-VR4
-VR3
-VR2
-VR1
-VN2
-VN1
-L4053
Phase Frame
L1
L2
L3
Last sh.
4
5
400
-RS1
Phase L3
Phase Frame
= INU
+
Lang. E
Sh.no.
Cont.sh.
-C2
A
DC_+
HVD
-U4001 XV C770 AE01
X2_1
-A4001
X2
DC_NP
X2_3
DC_NP
402.C1
DC_-
401.D1
DC_-
-R4001
X2_5
-C4001
-W40002 BK
C4001.1
DC_NP
C4001.2
-W40003 BK
-W40005
BK
-R4002
DC_-
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
DC_+
401.A1
BK
-W40001 BK
DC_+
Name
Date
A
B 01-07-25 R. SEILER
C 01-08-07 P. OBERLE
D 01-08-09 S.SCHLEGEL
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
LOCAL DC LINK
DC - MEASUREMENT
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
5
400
401
-W40101 BK
A
400.A8
DC_+
-L4011
XDC_+
402.A1
-F4011 FSCD
S2
402.A7
Tx
Tx
5V
20V
50V
100V
110V
A1
CL_+
S1
A2
BK
-W40106
FSCD_EXT_+
-W40102 FO
D
400.F8
DC_-
-L4012
FSCD_+
=NEXT_UNIT
412.A4
XDC_-
402.F1
-F4012 FSCD
BK
-W40109
5V
20V
50V
100V
110V
402.F7
S1
A1
CL_-
S2
A2
-W40103 BK
Tx
Tx
-W40108 BK
FSCD_EXT_-
-W40104 FO
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-W40105 BK
Name
Date
A
B 01-07-25 R. SEILER
C 01-08-07 P. OBERLE
D 01-08-09 S.SCHLEGEL
Date
Name
E 03-06-24 S.SCHLEGEL
F 03-10-14 ST.DUSS
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
OVERCURRENT MONITORING
FSCD_-
Doc. des.
Resp. dept.
Doc.No.
ATDD
=NEXT_UNIT
412.A5
= INU
+
Lang. E
3BHS119662E01
Last sh.
400
Cont.sh.
402
Sh.no.
401
X1:1 (-)
411.E2
GU_VF1U_2
VF1.2
X1:2 (+)
-VR1
-R4022
-VC1
CL_+
403.A7
U
DC_NP
405.A1
403.C1
CL_XDC_-
403.F7
403.F1
-W40203
1
VF1.1
403.A1
-R4023
-W40202
GU_VF1U_1
411.E2
VF1.A1 -VF1 A1
a
VF1U
XDC_+
412.E2
-W40204
411.E2
GU_VF2U_2
VF2.2
X1:2 (+)
400.C8
DC_NP
412.E2
VF3U
VF3.A1-VF3 A1
411.E2
GU_VF3U_1
VF3.1
X1:1 (-)
411.E2
GU_VF3U_2
VF3.2
X1:2 (+)
-VR2
-VN1
-RS1
-C1
X1:1 (-)
VF2.1
GU_VF2U_1
411.E2
VF2.A1-VF2 A1
c
VF2U
412.E2
XCL+
XPH
DC_NP
-VN2
-C2
-VR3
CL_+
-W40201
c
-G4021
401.B4
XDC_+
XDC_+
XCL-
GU_VF4U_2
VF4.2
X1:2 (+)
-VC2
-R4024
-W40205
XDC_401.D8
401.E4
XDC_-
Name
Date
A 13.03.01 S.SCHLEGEL
B 01-07-25 R.SEILER
C
D 01-08-09 S.SCHLEGEL
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
PHASE-LEG L1
411.E3
-VR4
-W40208
-R4025
X1:1 (-)
VF4.1
GU_VF4U_1
411.E3
-W40206
VF4.A1-VF4 A1
c
412.E3
VF4U
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
401.A8
-W40207
CL_-
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
401
402
403
411.E4
GU_VF1V_2
VF1.2
X1:2 (+)
-VR1
-R4032
-VC1
X1:1 (-)
VF1.1
XDC_+
404.A1
CL_+
404.A7
V
DC_NP
405.C1
404.C1
CL_XDC_-
404.F7
404.F1
-W40303
-R4033
GU_VF1V_1
411.E4
VF1.A1 -VF1 A1
VF1V
CL_+
-W40301
-G4031
412.E3
-W40302
-W40304
XCL+
GU_VF2V_2
VF2.2
X1:2 (+)
-RS1
-C1
XPH
DC_NP
VF3.1
X1:1 (-)
411.E5
GU_VF3V_2
VF3.2
X1:2 (+)
-VR3
-VN2
-C2
GU_VF3V_1
411.E5
VF3.A1-VF3 A1
a
VF3V
412.E4
DC_NP
-VN1
411.E5
-VR2
X1:1 (-)
VF2.1
GU_VF2V_1
411.E5
VF2.A1-VF2 A1
c
VF2V
412.E3
402.C8
402.A8
XDC_+
XDC_+
XCL-
GU_VF4V_2
VF4.2
X1:2 (+)
-VC2
-R4034
-W40305
XDC_402.F8
402.F8
XDC_-
Name
Date
A 13.03.01 S.SCHLEGEL
B 01-07-25 R.SEILER
C
D 01-08-09 S.SCHLEGEL
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
PHASE-LEG L2
411.E5
-VR4
-W40308
-R4035
X1:1 (-)
VF4.1
GU_VF4V_1
411.E5
-W40306
VF4.A1-VF4 A1
c
412.E4
VF4V
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
402.A8
-W40307
CL_-
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
402
403
404
X1:1 (-)
411.E7
GU_VF1W_2
VF1.2
X1:2 (+)
-VR1
-R4042
-VC1
VF1.1
-R4043
-W40402
GU_VF1W_1
411.E7
VF1.A1 -VF1 A1
a
VF1W
-W40403
412.E4
CL_+
-W40401
c
-G4041
403.A8
XDC_+
-W40404
XCL+
GU_VF2W_2
VF2.2
X1:2 (+)
403.C8
DC_NP
412.E5
VF3W
VF3.A1-VF3 A1
411.E8
GU_VF3W_1
VF3.1
X1:1 (-)
411.E8
GU_VF3W_2
VF3.2
X1:2 (+)
-VN1
-RS1
-C1
411.E7
-VR2
X1:1 (-)
VF2.1
GU_VF2W_1
411.E7
VF2.A1-VF2 A1
c
VF2W
412.E5
XPH
W
DC_NP
DC_NP
-VN2
405.D1
405.F1
-C2
-VR3
8
XDC_+
XDC_+
XCL-
GU_VF4W_2
VF4.2
X1:2 (+)
-VC2
-R4044
-W40405
XDC_403.F8
403.F8
XDC_-
Name
Date
A 13.03.01 S.SCHLEGEL
B 01-07-25 R.SEILER
C
D 01-08-09 S.SCHLEGEL
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
PHASE-LEG L3
411.E8
-VR4
-W40408
-R4045
X1:1 (-)
VF4.1
GU_VF4W_1
411.E8
-W40406
VF4.A1-VF4 A1
c
412.E5
VF4W
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
403.A8
-W40407
CL_-
Doc. des.
Resp. dept.
Doc.No.
ATDD
XDC_-
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
403
404
405
1
402.C8
-L4051
-T4051
L1
=TEU OR COU *)
IU_IU_M
IU_+
413.C2
413.C2
413.C2
+
M
-
-Z4051
3
2
-W40501 1
B
403.C8
-L4052
-T4052
L2
=TEU OR COU *)
+
M
-
3
2
-W40502 1
-W40511
-L4053
IV_IV_M
IV_+
-T4053
-C4051
-W40512
-C4052
-C4053
413.D2
413.C2
413.C2
L3
=TEU OR COU *)
BK
BK
DC_NP
Name
Date
A
B 01-07-25 R. SEILER
C
D 01-08-09 S.SCHLEGEL
DC_NP
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H 06-07-06 P.OBERLE
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
-W40540
Title
BK
-W40509
BK
-W40508
3
2
-W40503 1
IW_IW_M
IW_+
404.C8
BK
-W40507
-W40506
-R4053
-R4052
-R4051
-W40505
BK
BK
-W40504
+
M
-
404.C8
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-W40510
EMC FILTER
CURRENT MEASUREMENT
413.C2
413.C2
413.C2
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
404
405
410
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
411.A7
GUSP3_0V_2
-W41027
BK
Prepared
Approved
Project name
U0
S.SCHLEGEL
E.SUTER
ACS 6000
GNYE
BU
BN
GUSP3_+27V_2 -W41019 BK
L 3
411.A8
GUSP3_0V_1
411.A7
N 2
PHASE L2
GUSP3_+27V_1 -W41017 BK
PHASE L1
411.A8
-W41016 BK
411.A5
GUSP2_0V_2
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX1
11 AUX2
12
411.A5
GUSP2_+27V_2 -W41015 BK
-W41014 BK
=COU
PE
GUSP2_0V_1
=COU
411.A5
BN
GUSP2_+27V_1 -W41013 BK
L 3
BU
-X411 PE
411.A5
-W41012 BK
GNYE
-W41002
GUSP1_0V_2
N 2
-W41001
411.A2
LXN
1604-6
411.A2
GUSP1_+27V_2 -W41011 BK
-W41010 BK
-G4102
GUSP1_0V_1
LXN
1604-6
411.A2
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX1
11 AUX2
12
U0
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
GUSP1_+27V_1 -W41009 BK
-G4101
-W41026
BK
Name
Date
A
B 01-07-25 R. SEILER
C
D 01-08-09 S.SCHLEGEL
411.A2
Rev. ind.
Date
Date
-G4103
5
PE
BU
BN
PHASE L3
GNYE
6
7
BN
=COU
=COU
CONTROL
BU
L 3
GNYE
N 2
PE
PE 1
-W41004
-W41023 BK
-W41024 BK
-W41025 BK
U02
413.E2
412.A8
412.A8
ADCVI_+24V
INT_+24V
INT_0V
Last sh.
Sh.no.
Cont.sh.
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX
11
U01
-W41021 BK
-W41022 BK
L 3
LWN
2660-6
-W41029
BK
= INU
+
Lang. E
ADCVI_0V
ADCVI_-24V
N 2
-G4104
Doc. des.
ATDD
3BHS119662E01
Resp. dept.
Doc.No.
413.E2
413.E2
-W41003
U0
-W41020 BK
LXN
1604-6
Title
-W41028
BK
01-03-05
01-04-02
-W41018 BK
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX1
11 AUX2
12
PE
410
405
411
-W41030
PE
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
GUSP
KU C755 AE105 /
AE106
PHASE L3
PHASE L2
410.F5
410.F6
410.F5
410.F6
3
5
Subprint:
1: 3BHB003688R0101
2: 3BHB005245R0101
A1
PWF_GUSP2 -W41110
X1.1 GUSP2_0V_1
X1.2 GUSP2_0V_2
X1.3 GUSP2_+27V_1
X1.4 GUSP2_+27V_2
GUSP
KU C755 AE105 /
AE106
DC
AC
SH
COAX
SH
COAX
0V
+27V
FO
412.A3
SH
COAX
2 2 2 2
Title
GU_VF2V_1 -W41109
GU_VF2V_2 -W41109
=VLU_RBU/BCU/3
2) =VLU_RBU/BCU/4
GU_VF3V_1 -W41106
403.D1
GU_VF3V_2 -W41106
403.D1
GU_VF4V_1 -W41107
403.E1
GU_VF4V_2 -W41107
403.E1
403.C1
403.C1
X3.11
X3.12
X3.21
X3.22
X3.31
X3.32
X3.41
X3.42
X3.51
X3.52
X3.61
X3.62
X3.71
X3.72
- + - + - + - + - + - + - +
=CBU_DIU/3
1) =CBU_DIU/4
GU_VF1V_1 -W41108 SH
403.B1
GU_VF1V_2 -W41108 COAX
403.B1
1 2
01-03-05
01-04-02
410.F3
410.F4
410.F3
410.F4
-G4112
S.SCHLEGEL
E.SUTER
Date
Date
410.F1
410.F2
410.F1
410.F2
Subprint:
1: 3BHB003688R0101
2: 3BHB005245R0101
A1
PWF_GUSP1-W41105
X1.1 GUSP1_0V_1
X1.2 GUSP1_0V_2
X1.3 GUSP1_+27V_1
X1.4 GUSP1_+27V_2
PHASE L1
DC
AC
- + - + - + - + - + - + - +
SH
COAX
SH
COAX
0V
+27V
FO
Prepared
Approved
Project name
ACS 6000
412.A3
SH
COAX
2 2 2 2
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
GU_VF2U_1 -W41104
GU_VF2U_2 -W41104
=VLU_RBU/BCU/1
2) =VLU_RBU/BCU/2
GU_VF3U_1 -W41101
402.D1
GU_VF3U_2 -W41101
402.D1
GU_VF4U_1 -W41102
402.E1
GU_VF4U_2 -W41102
402.E1
402.C1
402.C1
X3.11
X3.12
X3.21
X3.22
X3.31
X3.32
X3.41
X3.42
X3.51
X3.52
X3.61
X3.62
X3.71
X3.72
2) In case of VLU/RBU/BCU
-G4111
1 2
Name
Date
A
B 01-07-25 R. SEILER
C 01-08-07 P. OBERLE
D 01-08-09 S.SCHLEGEL
1) In case of DIU
F
Rev. ind.
-G4113
0V
+27V
X1.1 GUSP3_0V_1
X1.2 GUSP3_0V_2
X1.3 GUSP3_+27V_1
X1.4 GUSP3_+27V_2
GUSP
KU C755 AE105 /
AE106
DC
Subprint:
1: 3BHB003688R0101
2: 3BHB005245R0101
A1
PWF_GUSP3 -W41115
AC
410
411
Last sh.
412
SH
COAX
SH
COAX
2 2 2 2
= INU
+
Lang. E
Cont.sh.
Sh.no.
FO
412.A3
SH
COAX
1 2
GU_VF2W_1 -W41114
GU_VF2W_2 -W41114
=LSU1_EAF/1
3)=LSU1_EAF/2
GU_VF3W_1 -W41111
404.D1
GU_VF3W_2 -W41111
404.D1
GU_VF4W_1 -W41112
404.E1
GU_VF4W_2 -W41112
404.E1
404.C1
404.C1
X3.11
X3.12
X3.21
X3.22
X3.31
X3.32
X3.41
X3.42
X3.51
X3.52
X3.61
X3.62
X3.71
X3.72
- + - + - + - + - + - + - +
Doc. des.
ATDD
3BHS119662E01
Resp. dept.
Doc.No.
=LSU2_EAF/1
4)=LSU2_EAF/2
GU_VF1W_1 -W41113 SH
404.B1
GU_VF1W_2 -W41113 COAX
404.B1
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
402.E1
S.SCHLEGEL
E.SUTER
403.B1
403.D1
Date
Date
404.A1
01-03-05
01-04-02
404.B1
VF4U
-W41204 FO
VF1V
-W41205 FO
VF2V
-W41206 FO
VF3V
-W41207 FO
VF4V
-W41208 FO
VF1W
-W41209 FO
VF2W
-W41210 FO
VF3W
-W41211 FO
VF4W
-W41212 FO
A812
A704
A703
V568
V567
V566
V565
V564
V563
V562
V561
A816
A641
A205
PWF_GUSP3
411.E8
A206
PWF_GUSP2
411.E6
411.E3
A803
A207
PWF_GUSP1
A813
A208
IOC1
A705
A203
IOC2
413.B7
A805
A204
FSCD_+
401.C7
A804
A210
FSCD_-
401.F7
A814
A202
VLSCD/FSCD_EXT_+ =UNIT_BEFORE
A815
A201
VLSCD/FSCD_EXT_- =UNIT_BEFORE
413.B7
If pos. 34 =2
In case of double VLU
for INU1 & INU2
A531
A592
A541
A302
A551
A402
A715
A714
1) FB+
1) CTRL+
1) FB1) CTRL-
A211
A722
A212
A723
Doc. des.
ATDD
MCB
=COU
2) FT_LINK_TX
=NEXT_UNIT FT_LINK_RX
=UNIT_BEFORE
2)
VLU_LINK_TX
ADCVI_D_RX
ADCVI_D_TX
ADCVI_C_RX
ADCVI_C_TX
AMC3_B_RX
A303
A593
A594
A304
A724
A209
A403
AMC3_B_TX
AMC3_A_RX
AMC3_A_TX
A404
413.C7
413.C7
413.C7
413.C7
=COU
=COU
=COU
3BHS119662E01
Resp. dept.
Doc.No.
A712
A713
VLU_LINK_RX
404.E1
-W41203 FO
V591
Title
404.D1
VF3U
A802
403.E1
-W41202 FO
Prepared
Approved
Project name
ACS 6000
403.A1
VF2U
A818
A817
A702
402.D1
-W41201 FO
INT-BOARD
UFC760BE42
/ BE142
Date
Name
E 03-06-24 S.SCHLEGEL
F
G 04-05-10 P.OBERLE
H 06-07-06 P.OBERLE
402.B1
VF1U
-A4121
If you have a
Double INU + LSU,
make this conection
Name
Date
A
B 01-07-26 R. SEILER
C 01-08-07 P. OBERLE
D 01-08-09 S.SCHLEGEL
402.A1
F
Rev. ind.
=COU
= INU
+
Lang. E
+24V 2
0V
+24V 1
X1:3
X1:2
X1:1
INT_+24V
INT_0V
-W41213
410.F8
410.F8
411
412
Last sh.
413
Sh.no.
Cont.sh.
V103
V113
A4
A6
-W41311 FO
-W41301 FO
IOC2
IOC1
A8
A1
-W41302 FO
-W41303 FO
ADCVI_C_RX
ADCVI_C_TX
A9
A2
-W41304 FO
-W41305 FO
ADCVI_D_RX
ADCVI_D_TX
400.B5
405.B7
405.B7
405.B7
405.E7
405.E7
405.E7
405.C7
405.C7
405.C7
UDC
UF C762 AE101
-A4132
X21
9
IU_+
IU_M
IU_-
X3:1
X3:2
X3:3
IW_+
IW_M
IW_-
X4:1
X4:2
X4:3
IV_+
IV_M
IV_-
X6:1
X6:2
X6:3
SVA
XV C767
FOR VOLTAGE
ADJUSTMENT
sub-D
-A4133
SCA
+24V XV C768
FOR CURRENT
-24V ADJUSTMENT
X7:1
X7:2
X7:3
412.A4
412.A4
412.A6
412.A6
412.A6
412.A6
A10
A3
X8:1
X8:2
X8:3
410.F8
410.F7
410.F7
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-A4131
A
B
C
D
Date
13.03.01
01-07-26
01-08-07
01-08-09
Name
S.SCHLEGEL
R.SEILER
P. OBERLE
S.SCHLEGEL
ADCVI_+24V
ADCVI_0V
ADCVI_-24V
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H 06-07-06 P.OBERLE
X1:1
X1:2
X1:3
Prepared
Approved
Project name
+15V
-15V
+5V
GND
+24V
0V POWER
-24V SUPPLY
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
Doc. des.
MEASUREMENT
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
412
413
415
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
Rev. ind.
Name
2
3
PE
14
1) 2)
21
1) 2)
GNYE
PE
-W41505
BN
BU
13
-W41503 BK
GNYE
20
-X412
M
-M2 1~
ST.DUSS
M.BRNNIMANN
1
1
2
2
3
3
PE PE
-W41504
BN
BU
-X412
1
1
2
2
3
3
PE PE
-X412
Prepared
Approved
Project name
ACS 6000
M
-M1 1~
-X4151
230VAC
-X412
-W41502
12
11
BK
BK
-X4152
2L1
L
N BN 2L2
BU 2PE
YE/GN
-W41501
>
-E4151
Date
Name
E
F
G 07.05.04 P.OBERLE
H
1L1
L
N BN 1L2
BU 1PE
YE/GN
OPTION
0...60C
Date
A
B
C
D
4
-E4152
Date
Date
1
1
2
2
3
3
PE PE
-X4154
M
-M2 1~
2L1
L
N BN 2L2
BU 2PE
YE/GN
1
1
2
2
3
3
PE PE
-W41506
BN
BU
GNYE
-W41507
BN
BU
GNYE
22
15
PE
23
16
PE
1L1
L
N BN 1L2
BU 1PE
YE/GN
Title
M
-M1 1~
03-10-10
03-10-14
-X4153
-E4153
Doc. des.
M
-M2 1~
= INU
+
Lang. E
1
1
2
2
3
3
PE PE
-X4156
1
1
2
2
3
3
PE PE
-W41508
BN
BU
GNYE
-W41509
BN
BU
GNYE
24
17
PE
25
PE
18
Last sh.
Cont.sh.
Sh.no.
2L1
L
N BN 2L2
BU 2PE
YE/GN
-X4155
M
-M1 1~
ATDD
3BHS119662E01
Resp. dept.
Doc.No.
1L1
L
N BN 1L2
BU 1PE
YE/GN
413
415
416
OPTION
A
24VDC
4
RD
BU
1
2
-X4161
1
2
-W41601
1) 2)
1
2
-X413
-E4161
RD
BU
M
=
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
1) 2)
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
ST.DUSS
M.BRNNIMANN
ACS 6000
Date
Date
03-10-10
03-10-14
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
415
Cont.sh.
420
Sh.no.
416
DOOR 1
MONITORING
DOOR 2
MONITORING
DOORLOCK
MONITORING
CABINET TEMPERATURE
MONITORING
>
32
BK
BK
-W42005
-X413
10
5
9
DOOR_LOCK
4
8
LOOP 2
-W42004
22
21
0..60C
TRIANGULAR KEY
FOR MANUAL RELEASE
A2
11
2
6
-W42003
2
2
-X412
-W42002
ACTUATOR
ALL CONTACTS
IN LOCKED
POSITION
C
-W42001
A1
14
22
-S4203
13
21
14
22
-S4202
13
21
-S4201
12
=COU
1)
=COU
DOOR_LOCK
FROM COU OR
UNIT BEFORE
1)
FROM COU OR
UNIT BEFORE
TO COU OR
NEXT UNIT
LOOP 2
FROM COU OR
UNIT BEFORE
LOOP 3
TO COU OR
NEXT UNIT
LOOP 3
FROM COU OR
UNIT BEFORE
LOOP 1
FROM COU OR
UNIT BEFORE
TO COU OR
NEXT UNIT
LOOP 1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
A
B
C
D
Date
13.03.01
01-07-26
01-08-07
01-08-09
Name
S.SCHLEGEL
R. SEILER
P. OBERLE
S.SCHLEGEL
Date
E 03-06-24
F 03-10-14
G 07.05.04
H
Name
S.SCHLEGEL
ST.DUSS
P.OBERLE
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
DOOR MONITORING
CABINET TEMP. MONITORING
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
416
420
COMPONENT :
DOCUMENT :
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
A
B
C
D
Date
01-07-23
01-08-10
02-07-09
02-10-23
Name
R. SEILER
S.SCHLEGEL
S.SCHLEGEL
S.SCHLEGEL
E
F
G
H
Date
03-06-25
03-10-30
07.05.04
05-07-06
Name
S.SCHLEGEL
ST.DUSS
P.OBERLE
P.OBERLE
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
FRONT PAGE
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
No. of sh.
12
Cont.sh.
Sh.no.
page
title 1
title 2
rev.
ind.
title 3
FRONT PAGE
INDEX SHEET
POWER STAGE
300
PHASE-LEG 1L1/2L1
301
PHASE-LEG 1L2/2L2
302
PHASE-LEG 1L3/2L3
302A
E
HOKES
310
PULSE INTERFACE
311
315
320
DOOR MONITORING
G
CABINET TEMP. MONITORING
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
A
B
C
D
Date
01-07-24
01-08-10
02-07-09
02-10-23
Name
R. SEILER
S.SCHLEGEL
S.SCHLEGEL
S.SCHLEGEL
E
F
G
H
Date
03-06-25
03-10-30
07.05.04
05-07-06
Name
S.SCHLEGEL
ST.DUSS
P.OBERLE
P.OBERLE
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
INDEX SHEET
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
Last sh.
Sh.no.
Cont.sh.
1
2
4
DC BUS middle
DC+
UNIT BEFORE
DC+
DC-
DC-
DC BUS front
OPTION
DC+
DC+
DC_-
DC_+
DCDC_-
DCDC_+
CABLE
DC_NP
=COU or TEU
-1L1 *)
2L2
-2L3
2L3
UNIT BEFORE
F
A
B
C
D
Date
YE/GN
2L3
TERMINAL UNIT
SEE CONVERTER
HW DIAGRAM
-W401
OPTION
Name
-W402
PG
PG
PE
PE
Date
Name
E
F
G
H 05-07-06 P.OBERLE
Prepared
Approved
Project name
ST.DUSS
W.KPFER
ACS 6000
Date
Date
03-06-25
03-06-26
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
NEXT UNIT
2L1
-2L2
2L2
-2L1
YE/GN
2L1
1L3
1L3
DC_NP
1L2
-1L3
DC_-
1L2
1L1
-1L2
DC_+
1L1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
NEXT UNIT
Last sh.
Sh.no.
Cont.sh.
2
4
5
XDC_+
-V3006
-V3007
-V3016
-V3017
-V3026
-V3027
-C3021
-V3005
-V3008
-V3015
-V3018
-V3025
-V3028
-R3021
-L3021
DC_+
1L1
1L2
1L3
C
XDC_NP
-V3004
-V3001
-V3014
-V3011
-V3024
-V3021
-R3022
-V3003
-V3002
-V3013
-V3012
-V3023
-V3022
-C3022
-R3023
DC_NP
D
2L1
2L2
2L3
XDC_-
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
Date
A 19.07.01
B 01-08-10
C
D 02-10-23
Name
S.SCHLEGEL
S.SCHLEGEL
S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
POWER STAGE
CIRCUIT DIAGRAM OVERVIEW
-L3022
DC_-
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
Last sh.
Sh.no.
Cont.sh.
4
5
300
XDC_+
XDC_+
-W30013 BK
310.F5
310.F5
T3007_2
T3007_1
-T3008
c
a
-V3005
-V3007
rd
302A.C4
310.F6
310.F6
T3008_2
T3008_1
4
3
2
1
8
7
6
5
wt
rd
-V3008
-W30007 BK
-W30008 BK
RC_+_0P
XDC_NP
310.F3
310.F3
T3001_2
T3001_1
wt
XDC_NP_C1
-W30012 BK
XDC_NP_C2
-T3002
c
a
-V3003
XDC_NP
310.F4
310.F4
T3002_2
T3002_1
8
7
6
5
4
3
2
1
wt
rd
-V3002
XDC_-_C
XDC_-
301.F2
XDC_-
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
301.C1
301.C2
-V3001
rd
-W30010 BK
Name
Date
A
B 01-08-10 S.SCHLEGEL
C 02-07-09 S.SCHLEGEL
D 02-10-23 S.SCHLEGEL
301.C2
-W30003 BK
-W30004 BK
2L1
8
7
6
5
-V3004
4
3
2
1
-T3001
-W30011 BK
-W30001 BK
-W30002 BK
301.A2
-W30005 BK
-W30006 BK
1L1
wt
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-V3006
8
7
6
5
4
3
2
1
-T3007
XDC_+_C
RC_+
302A.B4
301.A1
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
PHASE-LEG 1L1/2L1
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
301.F1
Last sh.
Sh.no.
Cont.sh.
5
300
301
-W30113 BK
-T3018
c
a
-V3015
310.F7
310.F6
T3018_2
T3018_1
XDC_NP_C1
XDC_NP_C2
wt
rd
-V3018
-W30101 BK
-W30102 BK
-V3014
-T3011
310.F4
310.F4
T3011_2
T3011_1
4
3
2
1
8
7
6
5
wt
-W30111 BK
XDC_NP_C1
-W30112 BK
XDC_NP_C2
-T3012
-V3013
XDC_NP
302.C1
302.C2
-V3011
rd
310.F5
310.F5
T3012_2
T3012_1
8
7
6
5
4
3
2
1
wt
rd
-V3012
-W30110 BK
XDC_-_C
XDC_-_C
302.F2
XDC_-
XDC_-
Name
Date
A
B 01-08-10 S.SCHLEGEL
C 02-07-09 S.SCHLEGEL
D 02-10-23 S.SCHLEGEL
302.C2
-W30103 BK
-W30104 BK
2L2
300.F7
8
7
6
5
4
3
2
1
-W30107 BK
-W30108 BK
300.C7
rd
300.C7
302.A2
-V3017
XDC_NP
XDC_+_C
302.A1
-W30105 BK
-W30106 BK
1L2
wt
T3017_2
T3017_1
8
7
6
5
310.F6
310.F6
4
3
2
1
-T3017
c
a
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
XDC_+_C
-V3016
7
XDC_+
300.A7
300.F8
XDC_+
300.C8
300.A8
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
PHASE-LEG 1L2/2L2
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
302.F1
Last sh.
Sh.no.
Cont.sh.
300
301
302
-T3028
c
310.F6
310.F6
T3028_2
T3028_1
8
7
6
5
wt
rd
-V3028
-W30207 BK
-W30208 BK
XDC_NP_C1
XDC_NP
XDC_NP_C2
-V3024
-T3021
310.F4
310.F3
T3021_2
T3021_1
4
3
2
1
8
7
6
5
wt
-V3021
rd
wt
rd
-W30203 BK
-W30204 BK
2L3
-T3022
-V3023
302A.E4
RC_-
310.F4
310.F4
T3022_2
T3022_1
8
7
6
5
4
3
2
1
-V3022
-W30220 BK
XDC_-_C
XDC_-
XDC_-
Name
Date
A
B 01-08-10 S.SCHLEGEL
C 02-07-09 S.SCHLEGEL
D 02-10-23 S.SCHLEGEL
302A.C2
-W30201 BK
-W30202 BK
RC_-_0P
302A.C4
301.F7
4
3
2
1
301.C7
rd
301.C7
-V3027
XDC_NP
302A.B2
-W30205 BK
-W30206 BK
wt
T3027_2
T3027_1
310.F5
310.F5
8
7
6
5
4
3
2
1
-T3027
1L3
-V3025
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
XDC_+_C
-V3026
7
XDC_+
301.A7
301.F8
XDC_+
301.C8
301.A8
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
PHASE-LEG 1L3/2L3
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
302A.E2
Last sh.
Sh.no.
Cont.sh.
301
302
302A
IF LSU 14MVA
DC+
DC+
DC+
DC+
XDC_+
302.A8
-W30209 BK
RC_+
300.A3
RC_+_0P
300.C3
RC_-_0P
302.D3
-L3021
-C3021
-W30210 BK
-R3021
C
-W30211 BK
XDC_NP
302.C8
XDC_NP
-R3023
-W30212 BK
-W412104 BK
-W30213 BK
-R3022
DC_NP
CABLE TO NEAREST
UNIT EQUIPPED WITH
NP-BAR
-W30217 BK
EAF2
311.A5
-W30216 BK
EAF1
311.A5
-W30214 BK
-C3022
XDC_-
OPTION
F
A
B
C
D
Date
Name
302.E3
-L3022
IF LSU 14MVA
IF LSU1
302.F8
RC_-
IF LSU2
-W30215 BK
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
IF LSU2
IF LSU1
OPTION
DC-
DC-
DC-
DCE
F
G
H
Date
Name
Prepared
Approved
Project name
S.SCHLEGEL
W.KPFER
ACS 6000
Date
Date
03-05-07
03-06-25
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
Last sh.
Sh.no.
Cont.sh.
302
302A
310
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
Rev. ind.
Name
Date
A 01-07-24 R. SEILER
B 01-08-10 S.SCHLEGEL
C
D 02-10-23 S.SCHLEGEL
-A3101
= NEXT_UNIT FT_LINK
X23:1
X23:2
X24:1
X24:2
X26:1
X26:2
X1:1
X1:2
X2:1
X2:2
-W31016 BK
BK
1
N
L
X25:1
X25:2
-W31015
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX
11
X22:1
X22:2
11
T3018_1
T3018_2
10
12
Doc. des.
301.C4
301.C4
X21:1
X21:2
-W31001 BN
BU
GNYE
PULSE INTERFACE
ATDD
3BHS119885E01
Resp. dept.
Doc.No.
302.C4
302.C4
T3028_1
T3028_2
=COUx
=COUx
T3008_1
T3008_2
X16:1
X16:2
-X311 1
2
PE
PE
300.C4
300.C4
X15:1
X15:2
LWN
1902-6
T3017_1
T3017_2
X14:1
X14:2
-G3101
301.B4
301.B4
X13:1
X13:2
-W31030
T3027_1
T3027_2
X12:1
X12:2
U0
302.B4
302.B4
X11:1
X11:2
PE
T3007_1
T3007_2
FT_LINK= UNIT_BEFORE
-W31014 BK
Title
300.B4
300.B4
-W31002
1
2
-W31003
1
2
-W31004
1
2
-W31005
1
2
-W31006
1
2
-W31007
1
2
-W31008
1
2
-W31009
1
2
-W31010
1
2
-W31011
1
2
-W31012
1
2
-W31013
1
2
FSCD+= UNIT_BEFORE
FSCD-= UNIT_BEFORE
LOGIC
T3012_1
T3012_2
01-03-06
01-08-07
301.E4
301.E4
T3022_1
T3022_2
Date
Date
302.E4
302.E4
T3002_1
T3002_2
300.E4
300.E4
T3011_1
T3011_2
301.D4
301.D4
T3021_1
T3021_2
302.D4
302.D4
S.SCHLEGEL
E.SUTER
T3001_1
T3001_2
CHANNEL 1
RX0
RX1
CHANNEL 1+2
RX2
CHANNEL 2
RX3
RX4
CHANNEL 1
TX0
TX1
CHANNEL 1+2
TX2
CHANNEL 2
TX3
TX4
Prepared
Approved
Project name
ACS 6000
300.D4
300.D4
PINT
DD C779 BE02
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
= NEXT_UNIT FSCD+
= NEXT_UNIT FSCD-
= LSU
+
Lang. E
Last sh.
Sh.no.
Cont.sh.
302A
310
311
302A.D7
302A.D7
CONFIGURATION
WITH
3/5MVA
IF
NO
DC
SAFE
LINE
VOLTAGE
-V3111
VUO 60-12NO3
C
-T3111
EES 50
X230:1
X40:1
OR
SUPPLY
1
3
-W31103
BK
4
5
6
-W31105
BK
7
9
-F3111
EAF
UF C765 AE102
BK
-W31104
BK
-W31106
Sig_In
Sig_Gnd
X1
X2
COAX
X40:2
X3:2 5AF
X3:1
SH
X230:2
OTHER
DRIVE
TX
=INUx
(to
Master
Int-Board)
Pwr_In
Pwr_Gnd
S1
ON
OFF
SH
ALL
A1
1234
1150V
825V
660V
500V
2 PE
-W31102
COAX
-W31101
INU
230V
-X314 1
OPTION
-X173
BN
BU
YEGN
POWER ON
CONFIGURATION
E
=INUx
=INUx
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
=INU
DRIVE
SINGLE
EAF1
EAF2
-C3111
IF
Name
Date
A 01-07-24 R.SEILER
B 01-08-10 S.SCHLEGEL
C
D 02-10-23 S.SCHLEGEL
Date
Name
E
F 03-10-30 ST.DUSS
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
Last sh.
310
Cont.sh.
315
Sh.no.
311
OPTION
A
230VAC
1) 2)
1) 2)
12
M
-M1 1~
F
A
B
C
D
Date
Name
Date
E
F
G 07.05.04
H
Name
P.OBERLE
Prepared
Approved
Project name
14
PE
GNYE
BN
BU
-W31505
2L1
L
BN 2L2
N
BU 2PE
YE/GN
1
1
2 2
3 3
PE PE
-X3151
-E3151
1L1
L
BN 1L2
N
BU 1PE
YE/GN
BN
BU
-W31504
>
1
1
2 2
3 3
PE PE
KTS 01141
0...60C
-B3151
PE
-X312
21
-X312
-X3152
-X312
13
BK
GNYE
-W31502
BK
-W31501
BK
-W31503
20
-X312
11
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
M
-M2 1~
ST.DUSS
M.BRNNIMANN
ACS 6000
Date
Date
03-10-30
03-10-31
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
Last sh.
311
Cont.sh.
320
Sh.no.
315
DOOR
MONITORING
DOORLOCK
MONITORING
CABINET TEMPERATURE
MONITORING
ALL CONTACTS
IN LOCKED
POSITION
21
A2
11
>
ACTUATOR
32
22
A1
14
22
-S3202
13
21
-S3201
12
TRIANGULAR KEY
FOR MANUAL RELEASE
BK
-W32006
-X313
BK
-W32005
6
10
3
7
2
6
TO COU OR LOOP 3
NEXT UNIT
TO COU OR LOOP 1
NEXT UNIT
-W32003
-X312
-W32001
=COU
=COU
TO COU OR LOOP 2
NEXT UNIT
FROM COU OR DOOR_LOCK
UNIT BEFORE
1) DOOR_LOCK
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
Name
Date
A 01-07-24 R. SEILER
B 01-08-10 S.SCHLEGEL
C
D 02-10-23 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F
G 07.05.04 P.OBERLE
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
DOOR MONITORING
CABINET TEMP. MONITORING
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
Last sh.
Sh.no.
Cont.sh.
315
320
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Date
Name
I 06-07-06 P.OBERLE
J
K
L
M
N
O
P
Date
Name
COMPONENT :
DOCUMENT :
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
FRONT PAGE
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
No. of sh.
16
Cont.sh.
Sh.no.
page
title 1
title 2
1
2
4
5
6
700
701
703
705
708
709
710
712
713
715
720
rev.
ind.
title 3
FRONT PAGE
INDEX SHEET
BUS BAR ARRANGEMENT
CBU CIRCUIT DIAGRAM OVERVIEW
OVERVIEW CAPACITORS ARRANGEMENT
BALANCING RESISTORS
DC LINK CAPACITORS
DC LINK CAPACITORS
DC LINK CAPACITORS
GROUNDING NETWORK
CHARGING UNIT
DISCHARGING UNIT
EARTHING ISOLATOR
CONTROL EARTHING ISOLATOR
AIR TO AIR HEAT EXCHANGERS
DOOR MONITORING
I
I
I
F
G
F
F
F
E
F
F
E
H
I
G
AUXILIARIES
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Date
Name
I 06-07-06 P.OBERLE
J
K
L
M
N
O
P
Date
Name
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
INDEX SHEET
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Cont.sh.
Sh.no.
OPTION
DC+
DC_NP
DCDC+
DC_NP
DCOPTION
DC+
DC_NP
DC-
DC BUS back
DC+
DC_NP
DC-
DC BUS middle
NEXT UNIT
DC+
DC_NP
DC-
DC BUS front
DC+
DC_NP
DCOPTION
=CBU
Additional CBU
depends on
drive configuration
UNIT BEFORE
DC_+1
DC_NP1
DC_-1
DC_+1
DC_NP1
DC_-1
DC_+2
DC_NP2
DC_-2
DC_+2
DC_NP2
DC_-2
DC_+3
DC_NP3
DC_-3
DC_+3
DC_NP3
DC_-3
PG
PG
PE
PE
Date
Name
I 06-07-06 P.OBERLE
J
K
L
M
N
O
P
Date
Name
Prepared
Approved
Project name
P.OBERLE
W.KPFER
ACS 6000
Date
Date
03-06-25
03-06-26
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
NEXT UNIT
DC_+
DC_NP
DC_-
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
UNIT BEFORE
Last sh.
Cont.sh.
Sh.no.
DC_+
-A7091
OPTION
OPTION
-K7201
-A7101
OPTION
-R7001
-V7091
-V7095
-V7092
-R7003
In case
of 3 rows
CBU
-C7011/...
-V7096
-R7101
-V7101
-C7101
AUX.
DC_NP
-T7091
-Z7081
OPTION
-R7002
-V7093
-C7102
-L7081
-R7081/2
-V7097
-Q7121
-C7081/2
PG
-V7098
-V7102
-R7102
In case
of 3 rows
CBU
-R7004
-V7094
PE
-R710B1/...6
DC_-
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-R710A1/...6
Name
Date
A
B
C
D 01-08-10 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
4
5
6
<= row 1
<= row 3
<= row 1
<= row 3
=CBU right
<= row 2
=CBU left
B
*)
*)
-C7011
-C7012
-C7013
-C7013
-C7012
-C7011
-C7031
-C7032
-C7033
-C7033
-C7032
-C7031
-C7051
-C7052
-C7053
-C7053
-C7052
-C7051
2 rows CBU
2 rows CBU
3 rows CBU
3 rows CBU
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
<= row 2
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
P.OBERLE
M.BRNNIMANN
ACS 6000
Date
Date
03-10-20
03-10-24
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Cont.sh.
700
Sh.no.
DC+
DC_NP
DCOPTION
DC+
DC_NP
DC-
DC BUS back
DC_+
DC_NP
DC_DC+
DC_NP
DC-
DC BUS middle
NEXT UNIT
OPTION
DC+
DC_NP
DC-
DC+
DC_NP
DC-
DC BUS front
In case of
2 rows CBU
DC+
DC_NP
DC-W70001
BK
-R7001
2
-W70003
-W70002
BK
-R7002
1
-W70004
BK
BK
-W70005
BK
-R7003
1
2
-W70003
-W70002
BK
-R7002
2
1
-W70006
BK
-R7004
1
2
-W70004
BK
BK
DC_+1 701.A2
DC_NP1 701.C2
DC_-1 701.E2
CHARGING
UNIT
E
709.A8
DC_+
709.E8
DC_-
Date
A 28.03.01
B
C 01-07-26
D 01-08-10
Name
S.SCHLEGEL
R.SEILER
S.SCHLEGEL
703.A2
703.C2
703.E2
DC_+3
DC_NP3
DC_-3
705.A2
705.C2
705.E2
DC_+4
DC_NP4
DC_-4
710.A1
710.C3
710.F1
DC_NP7
DC_NP8
708.A2
708.A6
DC_+6
DC_NP6
DC_-6
712.B3
712.B3
712.B3
OPTION
TO LSU IF CBU IS NEAREST TO LSU
DC_+2
DC_NP2
DC_-2
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G 07.05.04 P.OBERLE
H
Prepared
Approved
Project name
CAPACITOR
BK
-R7001
2
1
DIU
-W70001
EARTH
GND
ISOLATOR NETWORK
In case of
3 rows CBU
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
UNIT BEFORE
DC_NP
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
BALANCING RESISTORS
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
700
701
A
DC_+1
Row 1
*)
*)
*)
Row 2
Row 3
OPTION
DC_+1
700.C8
-C7011
-C7012
-C7013
C7011.1
C7012.1
C7013.1
DC_NP1
DC_NP1
C7011.2
C7012.2
C7013.2
E
700.C8
DC_-1
DC_-1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
700.C8
Name
Date
A 28.03.01 S.SCHLEGEL
B
C
D 01-08-10 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
DC LINK CAPACITORS
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
700
Cont.sh.
703
Sh.no.
701
A
DC_+2
Row 1
*)
*)
*)
Row 2
Row 3
OPTION
DC_+2
700.D8
-C7031
-C7032
-C7033
C7031.1
C7032.1
C7033.1
DC_NP2
DC_NP2
C7032.2
C7031.2
C7033.2
E
700.D8
DC_-2
DC_-2
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
700.D8
Name
Date
A 28.03.01 S.SCHLEGEL
B
C
D 01-08-10 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
DC LINK CAPACITORS
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
701
Cont.sh.
705
Sh.no.
703
A
DC_+3
Row 1
*)
*)
*)
Row 2
Row 3
OPTION
DC_+3
700.D8
-C7051
-C7052
-C7053
C7051.1
C7052.1
C7053.1
DC_NP3
DC_NP3
C7052.2
C7051.2
C7053.2
E
700.D8
DC_-3
DC_-3
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
700.D8
Name
Date
A 28.03.01 S.SCHLEGEL
B
C
D 01-08-10 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
DC LINK CAPACITORS
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
703
Cont.sh.
708
Sh.no.
705
1
A
-Z7081
OPTION
OPTION
DC_NP7
700.E8
DC_NP8
BK
700.E8
BK
GNYE
-W70811
GNYE
-W70810
BK
-W70807
-C7082
-X716 1
-C7081
-W70809
BK
-W70806
-W70804 BK
=COU
BK
-W70805
BK
-R7082
-R7081
-L7081
-F7081
-W70803 BK
-W70808
BK
-W70802
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-W70801
PG
PG
PE
PE
Name
Date
A 28.03.01 S.SCHLEGEL
B
C 01-07-26 R.SEILER
D 01-08-10 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
GROUNDING NETWORK
ACTIVE ISOLATION MEASUREMENT
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
705
708
709
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
-W70908
-W70907
-W70906
700.F1
a
a
c
c
a
S.SCHLEGEL
R.SEILER
S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G
H
DC_-
-V7098
-W70909
Name
700.E1
-V7097
-V7094
E
DC_+
-V7093
a
-X2 2
-X710 1
2
3
=COU
4
(depends
on supply
5
voltage)
6
7
=COU
PE
-W70902 GNYE
PU180/63/E 3.3kVA
5kVA
690V
3900V
575V
500V
460V
415V
380V *)
0V
0V
PE
/720.E8
A2
A1
-W70904
-W70901
BK1
BK2
BK3
BK4
BK5
BK6
BK7
-X2 1
-K7201
-V7096
-W70903
a
-V7092
-T7091
Date
A
B 02.04.01
C 01-07-26
D 01-08-10
-V7095
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-V7091
OPTION
-W70905
-A7091
Date
Date
01-03-02
01-04-02
Title
CHARGING UNIT
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
708
709
710
-W71024
VLSCD
XV C724 BE
B1
A1
OF1
A2
OF2
B2
-R710A6
-W71034
-W71041
-R710A5
-W71033
-W71032
-R710A2
-W71042
-W71007
-W71003
-F7101
-W71023
-R710A4
-W71031
-R710A3
-W71022
-W71021
-W71001
DC_+4
-R710A1
FB+/3
=INU
-X7 1
-W71010
-W71011
=INU
(-)
CBU_DIU/2
X1.2
(+)
-W71012
X1.1
=INU
=INU
OPTION = Option1+Option2
13 to 18 capacitors installed
in the complete converter
=> -R710A1...-R710A6
=> -R710B1...-R710B6
=INU
-W71013
-C7102
-V7102 A1
CTRL-/3
-W71014
CBU_DIU/3
X1.1
(-)
CBU_DIU/4
X1.2
(+)
700.E8
-C7101
-W71040 GNYE
-W71015
1
=INU
OPTION = Option1
7 to 12 capacitors installed
in the complete converter
=> -R710A1...-R710A4
=> -R710B1...-R710B4
CBU_DIU/1
-R7102
-W71016
-W71017
=INU
-R7101
-V7101 A1
CTRL+/3
PE
PE
-X7 3
-W71009
700.E8
-R710B2
-W71006
DC_-4
Name
Date
A 28.03.01 S.SCHLEGEL
B
C 01-07-26 R.SEILER
D 01-08-10 S.SCHLEGEL
-R710B6
-W71038
VLSCD
XV C724 BE
B1
A1
OF1
A2
OF2
B2
-W71043
-R710B5
-W71037
-W71036
-R710B4
-W71028
-W71035
-R710B3
-W71027
-W71026
-R710B1
-W71025
-F7102
-W71005
Option 2
Option 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
Option 2
Option 1
700.E8
5
-W71002
OPTION
-A7101
-W71044
FB-/3
=INU
-W71004
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
DISCHARGING UNIT
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
709
710
712
DC_+6
DC_NP6
DC_-6
-W71201 BK
-W71202 BK
-W71203 BK
-W71204
GNYE
PE
A1 A2
1
3
5
7
2
4
A
B
C
-Q7121
6
8
/713.D2
/713.D3
/713.D4
/713.D5
700.E8
700.E8
700.F8
/713.E7
PE
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
A
B
C
D
Date
28.03.01
02.04.01
01-07-26
01-08-10
Name
S.SCHLEGEL
S.SCHLEGEL
R.SEILER
S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
EARTHING ISOLATOR
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
710
712
713
COU1
290.B3
COU1
290.D6
-W71308
10
-F7131
2
-W71315
BK
-W71307
-W71306
BK
BK
BK
-W71305
-W71304
-W71303
BK
BK
BK
-W71302
-W71301
BK
(+)
-W71316 BK
(+)
-X715 1
-S7131 S1
E
GROUNDING
SWITCH
OPEN 1
Name
Date
A
B
C 01-07-26 R.SEILER
D 01-08-10 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H 05-12-01 P.OBERLE
GROUNDING
SWITCH
OPEN 2
Prepared
Approved
Project name
GROUNDING
SWITCH
CLOSED 1
P.OBERLE
E.SUTER
ACS 6000
GROUNDING
SWITCH
CLOSED 2
Date
Date
01-03-02
01-04-02
Title
S2 H1
BK
BK
-Q7121
/712.C5
-W71310
X2
-Q7121
/712.C5
21
-W71309
-Q7121
/712.C5
-W71314 BK
22
-W71313 BK
X1
13
-Q7121
/712.C5
-W71311
BK
-W71312
BK
14
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
COU1
290.B2
BK
A1 A2
-Q7121
/712.C5
LAMP TEST
UNLOCK
GROUNDING
SWITCH
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
712
713
715
OPTION
A
230VAC
1) 2)
1) 2)
12
BK
M
-M1 1~
F
A
B
C
D
Date
Name
Date
E
F
G 07.05.04
H
Name
P.OBERLE
Prepared
Approved
Project name
14
PE
GNYE
BN
BU
-W71505
2L1
L
BN 2L2
N
BU 2PE
YE/GN
1
1
2 2
3 3
PE PE
-X7151
-E7151
1L1
L
BN 1L2
N
BU 1PE
YE/GN
BN
BU
-W71504
>
1
1
2 2
3 3
PE PE
KTS 01141
0...60C
-B7151
PE
-X712
-X7152
-X712
21
13
-X712
GNYE
-W71502
BK
-W71501
BK
-W71503
20
-X712
11
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
M
-M2 1~
P.OBERLE
M.BRNNIMANN
ACS 6000
Date
Date
03-10-30
03-10-31
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
713
Cont.sh.
720
Sh.no.
715
DOOR
MONITORING
DOORLOCK
MONITORING
CABINET TEMPERATURE
HIGH VOLTAGE
RELAIS
0..60C
I
J
K
L
Date
Name
M
N
O
P
Date
Name
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
BK
X2
=COU OR CBU
=COU OR CBU
A1 A2 /709.A6
-W72007
BK
X1
-W72006
-W72031
PE
-X714
-K7201
1)
1)
TO COU OR LOOP 2
NEXT UNIT
FROM COU OR DOOR_LOCK
UNIT BEFORE
TO COU OR LOOP 3
NEXT UNIT
TO COU OR LOOP 1
NEXT UNIT
Option:
1 door cubicle
PE
BU
-X713
6
10
3
7
-W72004
BN
TRIANGULAR KEY
FOR MANUAL RELEASE
21
A2
11
2
6
-W72003
32
22
A1
12
14
22
>
-W72002
-X712
-W72001
KTO 1140
ACTUATOR
ALL CONTACTS
IN LOCKED
POSITION
13
21
13
21
-B7201
-S7203
-S7202
14
22
-S7201
-W72004
BK
-A7091
Option:
2 doors cubicle
-W72030 PE
OPTION
CHARGING UNIT
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Date
Date
01-03-02
01-04-02
Title
DOOR MONITORING
AUXILIARIES
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
715
720
AA-BBBBBB-CC-DD-EEEFF
FOR ACS6000
6E-1701A/B
Plant:
3276-GP-VD-050
Location: AL JUBAIL KSA
Sheet
114
02
Issue
FOR INFORMATION
DATE OF ISSUE:
Replaces:
Created from:
12.12.2007
Type / Code
ZSK380 / ZSK70
Jobname
TASNEE LDPE
Job-No.
Doc-Type
Count-No.
Fmt.
Rev.
FINAL
Wiebe
Laib
Aichroth
12-12-2007
01
FIRST ISSUE
Wiebe
Remus
Aichroth
19-04-2007
Issue
Description
This document is Tecnimonts property, and cannot be used by others for any purpose, without prior written consent
Prepared
Checked
Approved
Date
No.
Design change
Date
Design
Appr.
F2
APPROX 1360
312
V77
E1
V61
V75
V60
F3
V11
V78
E2
V63
V62
V16
V76
V13
623
26
V12
V32
V15
V85
70
V18
V83
392
10
150
270
710
191
312
1137
271
168
V19
854
V17
1100
V84
V86
V20
35
16
)
(x4
235
V14
REM:
555
980
Appr.
Design
Drawn
TI
EN
EN
Date
2007-03-06
AXELTOFTAVGEN 170
BOX 265
ABB SCHWEIZ AG
ACS6000 HEAT EXCHANGER
WATER COOLING SYSTEM
HEAT EXCHANGER UNIT
S-261 23 LANDSKRONA
SWEDEN
Issue
Date
2007-03-06
1
Scale
Project No.
3617
1:2
Drawing No.
1-3617-210
Frequency Converter
Documentation
(as built)
Dept. / Author
Date of issue
Lang.
APR/AVLD Wiebe
13.07.2007
en
Printdate
Document name
Rev. / revised by
Page
Converter_final docu_253528.doc
-/-
1/3
Project:
Tasnee LDPE
Adjustable-speed drive system for ZSK 320 Main drive
Table of contents
Chapter
Description
ACC1 +ACS 600 Documentation
Document no.
Rev.
ACC1
ACC1 Dimension Drawing
3BFA 6803AT01
3BFT 6903AT
3BFA 2400106
3BFA 24011006
3BFA 24011201
3BFA6803AT
3BFA6803AT
AC800M_Controller Hardware
3BSE019193R201
3BFA6803AT
15299-1
05200-1
V1.1
A
Safety
1.2
1.3
Mechanical installation
1.4
Electrical installation
1.5
Information on commissioning
1.6
Operation
1.7
1.8
1.9
Appendixes
A
4-4197-050
Options:
Frequency Converter
Documentation
(as built)
Dept. / Author
Date of issue
Lang.
APR/AVLD Wiebe
13.07.2007
en
Printdate
Document name
Rev. / revised by
Page
Converter_final docu_253528.doc
-/-
2/3
3BFE 64341588
ACC1
ACC1 Dimension Drawing
3BFA 6803AT01
3BFT 6903AT
3BFA 2400106
3BFA 24011006
3BFA 24011201
3BFA6803AT
3BFA6803AT
AC800M_Controller Hardware
3BSE019193R201
3BFA6803AT
15299-1
05200-1
Mechanical drawings
Layout drawing
3BHS224276
Paulinia line up
3BFA5814AT01
Terminal unit
3BHS196575
3BHS196601
Base frame
3BHS199089
Electrical diagrams
Setting list of protection devices
3BHS22427D01_322
3BHS224268
Converter HW diagram
3BHS224281E01
3BHS224279E01
3BHS224278E01
3BHS119662E01
3BHS119885E01
3BHS119836E01
3BHS119828E01
Parts list
ACS 6000 Electrical part list
V1.1
3BHS208495
Test reports
Factory acceptance test (FAT) converter
Frequency Converter
Documentation
(as built)
Dept. / Author
Date of issue
Lang.
APR/AVLD Wiebe
13.07.2007
en
Printdate
Document name
Rev. / revised by
Page
Converter_final docu_253528.doc
-/-
3/3
Quality assurance
Certificates IQNET and SQS
9-3360-601
!
!
"#
#$% ! #$& '()%$ # *'
" 0$ #$& ./ 6 .//2 34&3/
"#
+#
'#, *+!$
"
$% "
$! + #$ * ($ "+-
&
!" $0
'(,
+ #
&&
&
'()
'+
(
''
'
)
'' (
-
"
*!$
*%
"
'
''
'
)
'
( *!$
'
'
'
'
, '++'
, '++'
,
(
'
'
%
!
"#
#$% ! #$& '()%$ # *'
" 0$ #$& ./ 6 .//2 34&3/
"#
+#
'#, *+!$
"
$% "
$! + #$ * ($ "+-
!" $0
'(,
+ #
"
. (' )+
/ ,
*%
"#
#$% ! #$& '()%$ # *'
" 0$ #$& ./ 6 .//2 34&3/
"#
+#
'#, *+!$
"
$% "
$! + #$ * ($ "+-
"
!" $0
'(,
+ #
+
+
+
+
&(
1' (
"
&
*%
&, ( +2 +
&, ( +2
&'
+2 +
&'
+2
' ( )
+ &#) .' 3 +
+ &#) .' 3
* +
&' 4
&' 4
%
5
'
*#& ' (
"#
#$% ! #$& '()%$ # *'
" 0$ #$& ./ 6 .//2 34&3/
"#
+#
'#, *+!$
"
$% "
$! + #$ * ($ "+-
!" $0
'(,
+ #
# -
*'++'
"
&
1' (
*%
# .
)5!)22 0
# -
( "&
+6
& +
&
"#
#$% ! #$& '()%$ # *'
" 0$ #$& ./ 6 .//2 34&3/
"#
+#
'#, *+!$
"
$% "
$! + #$ * ($ "+-
!" $0
'(,
+ #
&
"/
0
&2 (
+ " /10
&' (
/#0
& )
2
/20
& '
(
&)
/(0
06 &)
.')
6( 0
7')
( '+ ,'
( .')
3
&
) 1' (
! ) 5 2' /
9 )
:
9! '22 (:
9!
2
(:
4 "
% .
&+' 1 (&; +2
&+' 1 (&< +2
&+' 1 (&1 +2
0 . . .
2.
+2
( ' .
"#
#$% ! #$& '()%$ # *'
" 0$ #$& ./ 6 .//2 34&3/
"#
+#
'#, *+!$
"
$% "
$! + #$ * ($ "+-
$
!" $0
'(,
+ #
"
&
4 "
5
' 1&; +2 +
' 1&; +2
' 1&; +2=!
4 "
2
' 1&< +2 +
' 1&< +2
' 1&< +2=!
4 "
4
' 1&1 +2 +
' 1&1 +2
' 1&1 +2=!
&
&
&
'
( (
+1' (&
) 1' (&
1' (
'
,' (
"#
#$% ! #$& '()%$ # *'
" 0$ #$& ./ 6 .//2 34&3/
"#
+#
'#, *+!$
"
$% "
$! + #$ * ($ "+-
!" $0
'(,
+ #
6 %
#%
*7
!
"#
(
4'
'
"
&
,
(
&
) 1' (&
5
+6
!1
!
(
&
!1 22 (
'
(
&
) 1' (&
# .
)5!,* '
!
'
&
+1' (
) 1' ("
&
) 1' (
&
7
*
2&' (
&
7
2&
"
# ,
"#
#$% ! #$& '()%$ # *'
" 0$ #$& ./ 6 .//2 34&3/
"#
+#
'#, *+!$
"
$% "
$! + #$ * ($ "+-
%
!" $0
'(,
+ #
> ?
*. 2 >*?
2 '
2
"
"#
#$% ! #$& '()%$ # *'
" 0$ #$& ./ 6 .//2 34&3/
"#
+#
'#, *+!$
"
$% "
$! + #$ * ($ "+-
!" $0
'(,
+ #
! "
#$% ! #$& '
)#* +,!$
%$& - + ./((0((1
$2
)3*
, #
"
%&
&
''
)
'
)
& '
& '
%& '
%&
'
''
(
)*
& &
+ %
'
, -% . /0 1
4
(
4
!
&
4
(
'
2 +
'
24+
3 4 (
&
41
#15 4
'
6 2'
3 &
'
&
&
3
' )*
.
&
" 8
2
" 89
2
"! 8 %
2
"# 8 9 6 29'
"/ 8 " 8 $; 29
' ).
& $-%$ 3
' ).
& $-%$ 3
&
: 0 $-%$ 3
& $-%$ 3
6
%
.
''
.)
& <3
& 6
+,-7
= 7
7(
&
&
'
"
"
+
#
"
'
&
%& '
>
)
"
>7 ;
( 6
! "
#$% ! #$& '
)#* +,!$
%$& - + ./((0((1
$2
)3*
, #
"
!
+'
+ %
).
?
& ' ?
( 7
2 @' ?
&
@;;;
'3
+ %
()
! 9
+ %
). + %
# 4& : &
/
&
?
:
'
2)
& ( ;D
' ) '' (
0
B
& 6 A
& ( 7
C>
)
&
3
D 2 @( @'
'& . & &
'
3
! "
#$% ! #$& '
)#* +,!$
%$& - + ./((0((1
$2
)3*
, #
&
& '
' &
4
"
&
' &
2 ''
& ( ;D
4 ' )
'
E 9
&
''
&
'
7(
&
+
&
& &
%&
1
'
& '
'
() '
& '
!3
D7(
'
&
'
! "
#$% ! #$& '
)#* +,!$
%$& - + ./((0((1
$2
)3*
, #
"
"
9
%&
#
+
()
( 7
$!%#
&'(&)
&
'%
#
'
!# 3
! "
#$% ! #$& '
)#* +,!$
%$& - + ./((0((1
$2
)3*
, #
"
$5 9 +3
6 7
637
%&
8,
0
6
4
5 %
0 %F
! "
#$% ! #$& '
)#* +,!$
%$& - + ./((0((1
$2
)3*
, #
"
!
!
"# $ !
"
%$!
%&' # %&( ")*+'& % ,) $% " "
)"+*%$ ) % -% ")%. ,-#&
'3"% ")*.
- %" %&( 0! 9 0119 2(:2. $ 3&" %&( 02 2 0112 /(0;
'&( / , 0!1
112
&3 " 4
&
)5
''- 5 - $% +*%-) $ ,)
50111
&# 6 *7118
!
"
!
&
&
&
*&+&
'
) &
) &
(
,
,
,%
)
+
'(
(
..#
,-
%
,
)
+ )+& +& -
- - )+ '
++'0
) &
( # *
# *(
1 & 2 3&
$
4 - &
&
&
&
5& &
&
& *' 6
7
"
%$!
%&' # %&( ")*+'& % ,) $% " "
)"+*%$ ) % -% ")%. ,-#&
'3"% ")*.
- %" %&( 0! 9 0119 2(:2. $ 3&" %&( 02 2 0112 /(0;
'&( / , 0!1
112
&3 " 4
&
)5
''- 5 - $% +*%-) $ ,)
50111
&# 6 *7118
.& &
4 '
1 &
&
&
)
3&
/0
"
& &6
)' 6&
&-
- - 1 3 +& 8 3
+ & 6& )
&
6&
6&
4 & 4 6?
++'
1
3
&
: 6&
$
6& &
&
6&
&
& &
'
89 :
+9+ 39 - &
';
- 6&
)
) &
1? +& & =
- -)
> 6&
) & = 46 6
++' &&- &: 6& &&&
#
6& < ) @& ) )& &
)
+ 6 ) & 3' 6 ) &
++ 4 6
&
'
1 2
@& #
& -& + A + 6
-- & >
%
#
3 %
((
%
%
&++ 6&
- - 5&
=- B 6 &
&++ 6&
- - 5&
=- B 6 &
& &++' &5& '
& ) @&
5&)
&
5&
>
@ 5&
>
* 5&
>
*
)& &
&>
%
$&+ 4 6& +
6& &C = 46 6 6 +- 3& &- &-> 6&'
3&
@& (4 - 4
D 6 & 6&
&
6& &C = +' 6&
&
5&
&
1 & - 5&
- 5& ) &
& +
"
%$!
%&' # %&( ")*+'& % ,) $% " "
)"+*%$ ) % -% ")%. ,-#&
'3"% ")*.
- %" %&( 0! 9 0119 2(:2. $ 3&" %&( 02 2 0112 /(0;
'&( / , 0!1
&-
112
&3 " 4
&C ( +-&
) +&
&
&
)5
''- 5 - $% +*%-) $ ,)
50111
%
&# 6 *7118
&
$&+ 4 +
) &+ )
&
'(
6&
) &
= 46 6
&+
&-
+ 3 +
&
- &&- &-
&
++ ++ 4
&
4 < ) )& +'
'(
) &
6 5&
& E
- )+ '&1EAF
6& 4 &
& E
% - )+ '&6& 2
1EAF
6& 4 &
& E
- )+ '&6& 2
1EAF
6& 4 &
& E
, - )+ '&6& 2
1EAF
6& 4 &
& E
- )+ '&6& 2
1EAF
6& 4 &
AC
3& CC G, 6
+
- )+ '&- 6& 2
1 1EAF
6& 4 &
2 3&
- 5& - )+ '&- ) &+ *&
2
1 1EA
6
3&
- 5& AC )+&>
&+ 6 % - 5&
2
1F% 1EAF%
2 3&
& - )+ '&- ) &+
*& 2
1 1EA
6
3&
&
2 3&
&C
& - )+ '&) &+ *& 2
1 1EA
6
3&
&C
&
6&
*&+&
6
1
6
1
6
1
6
1
6
1
'
&
&+ 6 4 )
3+ &
- )+ '
* ++&
6 & 6 5& +' & + 3
4 ) &
) &
"#$ %&' ?
46 6 &&- &!" )
!"
&# + &
"#$ %&'
&C
&>
!"
"#$ %&'
(
) & > 6
&
& 6 - 5&
&
6 & 6 5&
) &
-+
"#$ %&'
) &
&+&
!" ? )
&+-
)+&>
/ #
&
5&
6
) &
5&
6
) &
5& % 6
) &
+&
%
+ 3
&
&+ 3
4 + 3
&+ 3
"
%$!
%&' # %&( ")*+'& % ,) $% " "
)"+*%$ ) % -% ")%. ,-#&
'3"% ")*.
- %" %&( 0! 9 0119 2(:2. $ 3&" %&( 02 2 0112 /(0;
'&( / , 0!1
112
&3 " 4
&
)5
''- 5 - $% +*%-) $ ,)
50111
&# 6 *7118
!"
*%
&C
)+&>
) & > 6
&
) &
&+&
&+-
/ #
5&
6
) &
5&
6
) &
5& % 6
) &
!"
&# + &
&C
"#$ %&'
) & > 6
4 + 3
&+ 3
) &
&+&
&+-
)+&>
/ #
+&
5&
6
) &
5&
6
) &
5& % 6
) &
&
%
+&
&
&+ 3
&
3& - &
& 6
) &
&+ 3
4 + 3
&+ 3
"
%$!
%&' # %&( ")*+'& % ,) $% " "
)"+*%$ ) % -% ")%. ,-#&
'3"% ")*.
- %" %&( 0! 9 0119 2(:2. $ 3&" %&( 02 2 0112 /(0;
'&( / , 0!1
112
&3 " 4
&
)5
''- 5 - $% +*%-) $ ,)
50111
,
&# 6 *7118
'
,
(
-
H) &
-
.-
+ )+&
' +
6
6 - )+ ' )
&&&
&&-&- ) &+
- - )+ '
3+&
+ # +
& & ++'
() &
+'
6 -&
5&
) &
* & - - )+ '(
) &
& / &+ &-0 & 6 6& ! &C )+&>
- 5& - & B 6 5& 4 & )&
& - )+ '&&+ &- 4 3& 6 --& 3' &+' &
) & *&+&
) &
+ 3 +) &
6 - 3+&
+ )+&
) &
& - )+ '&6& )
& 3&+ 4 + - 5&
) &
+ &+&
) &
' - B &&- - 3+& &5& '
) &
& 3' &
,%
.-
+&
++'0
*&+&
3' + <
4 6
+&
6&
&
&5& ' ) )& '
+& +
& 6 &C
'6 ;
&
&
"
%$!
%&' # %&( ")*+'& % ,) $% " "
)"+*%$ ) % -% ")%. ,-#&
'3"% ")*.
- %" %&( 0! 9 0119 2(:2. $ 3&" %&( 02 2 0112 /(0;
'&( / , 0!1
112
&3 " 4
&
)5
''- 5 - $% +*%-) $ ,)
50111
&# 6 *7118
( # *
&+
4 -
+,$#
= && !
-*-
& )&
6& ) &
6 4
+'
&
&4
++ )6 &
&-
&
&
- - ;/'
" 12 #'"$#
:3@&
107 "/
3&
++
+ 3& &
+- 6 4 + <&
3&
) &-
1'#<
&
6& )6
5&-=
!
&
) &
&
+ 2 ': -
- -
& B
&->
)
+,$#
&
+,$#
& )&
& - )+ '
-&+& &
!0120. ." -
3&
3&
&-
&4
& ,
"
%$!
%&' # %&( ")*+'& % ,) $% " "
)"+*%$ ) % -% ")%. ,-#&
'3"% ")*.
- %" %&( 0! 9 0119 2(:2. $ 3&" %&( 02 2 0112 /(0;
'&( / , 0!1
&
112
&3 " 4
6& ) @&
&
)5
''- 5 - $% +*%-) $ ,)
50111
I
&# 6 *7118
" 12 #'"$#
'.
01
+,$# - - ;#0> !" =+"/ "=0 1'+. "#'. &0#1 # '. =+"/ 2/'
" 12 #'"$# -
"
%$!
%&' # %&( ")*+'& % ,) $% " "
)"+*%$ ) % -% ")%. ,-#&
'3"% ")*.
- %" %&( 0! 9 0119 2(:2. $ 3&" %&( 02 2 0112 /(0;
'&( / , 0!1
112
&3 " 4
&
)5
''- 5 - $% +*%-) $ ,)
50111
&# 6 *7118
,-
# *(
A5& -&
A5&
)+ '
+ 3 +) &
) & +&
) & A5&
)+ &-
&
-& & &5& = 46 6
&
) &
E*
+ ) & 3'
<&= 4 ++
"
%$!
%&' # %&( ")*+'& % ,) $% " "
)"+*%$ ) % -% ")%. ,-#&
'3"% ")*.
- %" %&( 0! 9 0119 2(:2. $ 3&" %&( 02 2 0112 /(0;
'&( / , 0!1
112
&3 " 4
&
)5
''- 5 - $% +*%-) $ ,)
50111
L
&# 6 *7118
3&
6&
&
&
&
&
&+ &
3&
&+ &
&+ &
&
&
H =
H
4 -
&
&
- ) &
&
-! +
"E
5& B +
+ < ' 6
7
$
4 - &
&
4 -
I
L
&
- - 5& &+&
&
1 &L
((
L
L
L
L%
#
&+ + < 4 - 4
5& &+&
4 &&
& &+&
4 -
&+
K 5&*&+K "& &
&*&+K -
"
%$!
%&' # %&( ")*+'& % ,) $% " "
)"+*%$ ) % -% ")%. ,-#&
'3"% ")*.
- %" %&( 0! 9 0119 2(:2. $ 3&" %&( 02 2 0112 /(0;
'&( / , 0!1
112
&3 " 4
6-
&
)5
''- 5 - $% +*%-) $ ,)
50111
&# 6 *7118
&
&
((
#
&+ + < & 4 4 -
&+1 <K K %
,
I
L
%
,
%
,
I
L
%
,
%
G
%
,
)
* K "E- K "E- K "E
"E
&
"E
+ &
"E+ &
"E) 4&
" - K " - K " %- K " - K " ,- K " - K " I- K " - K " L- K " - K " - K " - K & " - K & " - K & " %- K & " - K & " ,- K & " - K " &
K " &
K & " &
K 2
K - & ) C
K - & ) C
& & )
"4"4"4-
)& 4 ) &+
"E (% 4 "E ( 4 &
"E
3&
"E
&
"E
(5 + &
"E
(5 + &
"E
4&
&
&
& %&
& ,&
& I&
& L&
&
&
AC
&
AC
&
AC
& %AC
&
AC
& ,AC
&
&4 &4 AC
&4 &
&
3&
CK & )&
&
CK & )&
&
&
& & )&
&
)E
)E
)E
E & )
& )
K & )
"
%$!
%&' # %&( ")*+'& % ,) $% " "
)"+*%$ ) % -% ")%. ,-#&
'3"% ")*.
- %" %&( 0! 9 0119 2(:2. $ 3&" %&( 02 2 0112 /(0;
'&( / , 0!1
112
&3 " 4
<K
C
C
C
C
C
C
C
C
C
C
&
)5
''- 5 - $% +*%-) $ ,)
50111
&# 6 *7118
5&
&
&
((
7
2
"
"
.
,
I
$&
$&
6
6
*
%
,
%
%
%
%%
%
%,
%
%I
%
%L
%
%
%
% %
%
% ,
%
,
I
L
%
,
,
,
,
,%
,
,,
,
'
+
++-
& - 5&
3&
5&
6
5&
- '
5& 6
+
& )&
&
5& ++
& )&
&
5& ++
& )&
&
5& 3&
& )&
& (A 5& 3&
& )&
& 2 (A 5& 6
&
& )&
&
5& 6
&
& )&
&
5&
4 5& 4 &
4 5& )&&+5 + &
5& + +5 + &
5&
&
+5 + &
5& 5 + &
+5 + &
5&
+
4 5&
+
4 5&
+
4 -%
5&
+4 5&
+4 5&
+4 -%
5&
+4 5&
&
& & 4
5&
+
4 5&
+
4 5&
+
4 -%
5&
+4 5&
+4 5&
+4 -%
5&
+4 5&
&
& & 4
5& % +
4 5& % +
4 5& % +
4 -%
5& %
+4 5& %
+4 5& %
+4 -%
5& %
+4 5& % &
& & 4
5&
+
4 5&
+
4 5&
+
4 -%
5&
+4 5&
+4 5&
+4 -%
5&
+4 5&
&
& & 4
5& , +
4 5& , +
4 5& , +
4 -%
&
&
K
K
*)&&1 &
+ &
+
K
+
K
+
K
+K
+K
+K
+K
&
+
K
+
K
+
K
+K
+K
+K
+K
&
% +
K
% +
K
% +
K
% +K
% +K
% +K
% +K
% &
+
K
+
K
+
K
+K
+K
+K
+K
&
, +
K
, +
K
, +
K
+
+
& )
& )2
& )
& )
-
-%
-%
K
-%
-%
K
-%
-%
K
-%
-%
K
-%
"
'&( / , 0!1
112
&3 " 4
6
M
M
M
M
M
M
M
C
C
C
C
C
C
C
C
C
)
N
C
C
C
C
%$!
&
)5
''- 5 - $% +*%-) $ ,)
50111
&# 6 *7118
,I
,
,L
,
,
,
, %
,
, ,
%
,
I
L
& *' 6
, +K
, +K
, +K
, +K
, &
+
K
+
K
+
K
+K
+K
+K
+K
&
I +
K
I +
K
I +
K
I +K
I +K
I +K
I +K
I &
-%
K -%
-%
K -%
-%
K -
5&
5&
5&
5&
5&
5&
5&
5&
5&
5&
5&
5&
5&
5&
5&
5&
5&
5&
5&
5&
5&
,
,
,
,
,
+
+
+
+
&
+
+
+
+
+
+
+
&
I +
I +
I +
I
+
I
+
I
+
I
+
I &
4
4
4
4
-%
& & 4 4 4 -%
4 4 4 -%
4 & & 4 4 4 -%
4 4 4 -%
4 & & -
4 -
4 -
4 -
7
((
I
I
I
I%
I
I,
1
1
1
1
1
1
1
7
+
+
+
+
+
+
& O&
&
6
& '
&.
&
&
& *& -
+
+
+
+
+
+
"
%$!
%&' # %&( ")*+'& % ,) $% " "
)"+*%$ ) % -% ")%. ,-#&
'3"% ")*.
- %" %&( 0! 9 0119 2(:2. $ 3&" %&( 02 2 0112 /(0;
'&( / , 0!1
112
&3 " 4
+ '&
+
6
+- '
+6
+
&
+ & -
&
)5
''- 5 - $% +*%-) $ ,)
50111
%
&# 6 *7118
&3-$-)
-
6 8
6*8
"
!
"
"
5&
--&+>
--&- A5& -&
+ )+& -
& + 4=
& 6 6=
) = AC
+)
H)
)- &
= ) &
+
& 3+&= & 3+&#-
,
I,
%# P
#
%$!
'&( / , 0!1
# P
%# P
3+&
"
112
&3 " 4
<-
,
L,
&
)5
''- 5 - $% +*%-) $ ,)
50111
&# 6 *7118
"
!"
$
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
'
%
( $ ))
* +,
%
' *
%
! )
.(
%
! )/
% .(
%
* '
$ ))
1 %
1 %
/ $
1 %
-'
&
0
$
$ ))
#
'
#
0
#
-'
%
)
-4
! '
$ ))
%
!
'
)
&
7 +
" 8 /%(
(
%
%
)
#
#
#
%
( $ ))
0
0
0
2
2
3
3
5
%
%
&
%
&
%
&
( &
0
2
3
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
( &
( '
8 %
( &
( / (
%
()
&
%
/ (
%
&8 % 9 '
( ' : /
8 %
'
+ 9'
)
%9 & /
%
,( '
/
7$ ,(
% /
8 % /
'
% )
/ :
: /
) /
4
/
/ +
%9
&
! %
'
& )
%
( $ ))
& )
( '
/
/ ( '
( /
' *
))
: / ;-<
'
(
/
(> &
:
/ (
&/ ( '
6*
%
/
* 7!= . 8 % + :
9
'
$ )) ? /
/ &/ / (
/ / (
))
/
'
( $ ))
/
+,(
%
$6 *
7* +,(
' :( &
%
/ / (
))
/ / (
(
% 9 :/ /
(
)
/ ( '
( ))
(
> & ( 4 @$ )) A
)?
* +,
/
/
/ ( '
C .8 % /
/
))
/ (
/ :
/ : + : / / (
( +,(
%
( &
))
B /
(( '
.
.
.
.
(9 (9
: ( &9
( '
9'
&
(
&
(+
(
& )
&/
'
%
(( '
.
.
.
.
) : /%
: / (
)
)
+
:
(
!
.
.
.
) : /%
: / (
+
:
(
#
.
.
.
!
) : /%
: / (
+
(
)
(( '
& %
"
(
(( '
$
:
(
(
(( '
% & '
()
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
.
.
.
/
+,(
) : /%
: / (
+
%
:
(
(
(( '
))
)
) : ( & )
)
/ :
)
'
)
/
'
)
) : /%
: (
: / ( (
'
> 1 : / &/?
)
+ 8
>
$ ))
,
.
.
.
.
.
.
*+
.
'
)
.
.
.
.
.
'
) : /%
: / (
4
))
,
: ( & )
)
/ :
)
% / / &/
) /
: (
8 %
#
.
'
) : /%
:
: / ( (
))
,
!
.
.
.
.
% / / &/
.
.
.
.
-'
/
)
: (
(
%
>
/
9 !$ $,'
&
0
) : /%
: / (
+
))
: (
(
)
%
(
+
!
(
.(
% :
'
) % $ ))
&
' (
('
% +%
%> &
#? (
)
(
)
.%
( ) :/
)
% ( : / ( 4 $/ 8 ( +
'
@ ))
A+
"%
&@
A
(( : /
' :
)
9 :/ /
%
(
% ) !
)
(
% (: /
( @(
A .+
' - / :
'
)
& 4 / (
%
) ' % :
!
#
#" !
#'( $ #') * &+
/ (
(
/
&
'3 . 4 56++
,5-
"&#
%
&
)/
% .(
/ (
)
#*
%> &
/
%9
/
&
' % )
&(
' (
' (
)
.(
% / (
%
) $ ))
.
% (: /& % 4
(
'
* '
/
'
9 /
' :
(: /
)
/ )
+ (
( :/
E: 8
E /
+%
& %8 % "
/
)) ( ( E: 8
E / (
%: /
8 %
/
& )) & /
8 ( +
/+
+
&9
$ ))
(1 2
))
(
+ :
/
9+
"
$ %
9 /
'
&
/ !$3
(
% @
>( ' ?
)
#
'( )
1
( /
$ ))
(
*$ %
/
(
& )
)
/ (
@( : A9 / /
A, 4
%
:
/
))
%
!
!
!#
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
1 %
$6 *
7-
$6 *
,8 %D *
C ,8 %D *
$6 *
!* *-
-$ -!*- ,8 %D
;-<
6*
+,(
'
; ,8 %D ;
-; - .8 %D ;
B; ,8 %D ;
;$ -!*- ,8 %D
+,(
6 ,8 %D ;
$6 *
'
'
'
* 7!= ,8 %D $/ &
* 7!= ,8 %D $/ &
-;6 ,8 %D ;
( '
( '
))
))
% + 8: (
: (
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
1 %
/ $
1 %
.
.+
/
/
( ' (
/
8 %
8 %
( ' (
8 %
/ !
8 %
%
& )) +
( $ ))
( '
8 %
.+
/ :
)
/ +
/ (
))
%,
&
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
$ ))
%
)
)1
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
-4
,1 *+
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
'
/1
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
$ ))
&
01 4
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
'
!
%
'
1!
/ ( '
*
*
/ :
&
(
'
/ (
'
'
'
%
&
(
'
( :
% :
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
&
1!
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
&
"1 !
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
7 +
&
7 +
)
+
' : (
& > &
$1 !
%
( &
+ ' : (
( &
(
' :9
: &
(
+ /
+
5? @ ' A / :
& > &
& 9
@
:
' , (
' A/
( &
&
+ && ( ' 9 :/ / / '
(; ( ' , ((
%
%
+
( &
?
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
(61 !
((1 !
17
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
" 8 /%(
( &
()1 !
% &
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
# -'
%
/
)
C
:
'
& (
%
%
) & (
( (
' (
( )+ / &
(
+
%
%
)
)
(,1
,
(
)
(
(
% (
!
))
9 :/ /
/
%
(C
%.
)(
% !
( ( ' :/ /
%
/ ' +
' !
(%
) &
)
+
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
(/1 '
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
'3"%",&
5
!
$
-
7 8
758
9"
/
'
! (
%,
4
( (
-' (
%
!$3
!$3
0
(
( -'
(( (
#
#
#
2
(
9
:(
(
%
0
20
!
#
#" !
#'( $ #') * &+
'3 . 4 56++
,5-
"&#
%
&
1
1
1
1
1(3)
ABB
COMPONENT LIST
3BFA6803AT611
PROJECT:
STRUCTURE:
I.D.:
POSITIONS
TASNEE COPERION
EHKE
ACC1
ITEM
CODE
A10
64168533
ABB
A11
A12.1
A12.2
3BSE018157R1
3BSE018135R1
3BSE030220R1
1
1
1
1
1
1
1
1
1
ABB Sweden
ABB Sweden
ABB Sweden
ABB Sweden
ABB Sweden
ABB Sweden
ABB Sweden
ABB
Norelco
ABB
6
2
3
2
1
1
1
1
ABB
ABB
ABB
ABB
ABB
ABB
ABB
ABB
HIMA
A14
A121...A123,A141,A151,A161
A131, A132
A121... A123
A131, A132
A141
A151
A161
A50, A51
3BSC950089R2
3BSE008534R1
3BSE008536R1
3BSE008538R1
3BSE013234R1
3BSE013235R1
3BSE008508R1
3BSE008514R1
3BSE008518R1
3BSE008522R1
3BSE008516R1
3BSE008538R1
07.02.2007
Rev. 2
QUANTITY
MANUFACTURER
2(3)
ABB
COMPONENT LIST
3BFA6803AT611
PROJECT:
STRUCTURE:
I.D.:
POSITIONS
TASNEE COPERION
EHKE
ACC1
ITEM
CODE
G11
ABB
ABB
F10
F11
F12-F13
F14
1
1
2
1
ABB STOTZ
ABB STOTZ
ABB STOTZ
ABB STOTZ
F21
1
3
ABB STOTZ
ABB
F21
F22, F24
F23
1
2
1
5
ABB STOTZ
ABB STOTZ
ABB STOTZ
ABB
F100
F101.1, F101.2
2
2
AEG
GENERAL ELECTRIC
3
1
1
ABB STOTZ
ABB STOTZ
ABB STOTZ
G12
07.02.2007
Rev. 2
QUANTITY
MANUFACTURER
3(3)
ABB
COMPONENT LIST
PROJECT:
STRUCTURE:
I.D.:
POSITIONS
TASNEE COPERION
EHKE
ACC1
ITEM
AUXILIARY CONTACT S2-H20
F41
K41
3BFA6803AT611
CODE
QUANTITY
5
MANUFACTURER
ABB
1
1
ABB
ABB
ABB
Q10
1
1
ABB
ABB
Q141
1
1
1
3
ABB
ABB
ABB
ETI
07.02.2007
Rev. 2
WEIDMULLER
WEIDMULLER
WEIDMULLER
WEIDMULLER
WEIDMULLER
WEIDMULLER
WEIDMULLER
! "#
"
$ %
&
'
!
()
#$% ! #$& '()%$ # *' "#
45&22, " 6$ #$& 41 7 1..3 47&28
+#
'#, *+!$
*
/
"
(
+ $ + #$ * ($ "+0
!" '(,
+ #
#$& 12 3 1..3
$ '
+$
'
+$
!
$ ' +$ +$
'
+$ +$
" #
()
#$% ! #$& '()%$ # *' "#
45&22, " 6$ #$& 41 7 1..3 47&28
+#
'#, *+!$
*
/
"
(
+ $ + #$ * ($ "+0
!" '(,
+ #
#$& 12 3 1..3
!( (
(-..
()
#$% ! #$& '()%$ # *' "#
45&22, " 6$ #$& 41 7 1..3 47&28
+#
'#, *+!$
*
/
"
(
+ $ + #$ * ($ "+0
(
!" '(,
+ #
#$& 12 3 1..3
&
7
2
=
5
3
8
4.
44
41
47
42
4=
45
4
9
+-4.
)!"$
"
2>1.
"
(( ;
<
&
4
1
7
2
=
5
3
-
2>1.
? .>47.. 4@
()
#$% ! #$& '()%$ # *' "#
45&22, " 6$ #$& 41 7 1..3 47&28
+#
'#, *+!$
*
/
"
(
+ $ + #$ * ($ "+0
!" '(,
+ #
#$& 12 3 1..3
'& &
'
'
:
%(
:
7
2
%
%
.
.
.
3
-
4
1
7
2
=
5
3
-
'-1.
'
<
<
(
:
>%
>#
>*
>
>+
?
: ("5... %
"
+
: ("5... %
"
%
)@6@
%
)@6@
(
&
>%
>#
>+
?
: ("5... %
"
<&
.7<
?
.2<
A 42.
A 4=.
.3<
'-1.
()
#$% ! #$& '()%$ # *' "#
45&22, " 6$ #$& 41 7 1..3 47&28
+#
'#, *+!$
*
/
"
(
+ $ + #$ * ($ "+0
,
!" '(,
+ #
#$& 12 3 1..3
'& &
4
1
7
2
=
5
3
-
2>1.
2>1.
2>1.
%
%
%
& 2>1.
& 2>1.
& 2>1.
? .>47.. 4@
? .>41.B
? .>4..3
()
#$% ! #$& '()%$ # *' "#
45&22, " 6$ #$& 41 7 1..3 47&28
+#
'#, *+!$
*
/
"
(
+ $ + #$ * ($ "+0
*
!" '(,
+ #
#$& 12 3 1..3
" #
$
$
" -
. $
''
$
$
'/
()
#$% ! #$& '()%$ # *' "#
45&22, " 6$ #$& 41 7 1..3 47&28
+#
'#, *+!$
*
/
"
(
+ $ + #$ * ($ "+0
!" '(,
+ #
#$& 12 3 1..3
ControlIT
AC 800M Controller Hardware
Hardware and Operation
Version 1.1
Users Guide
ControlIT
$&0&RQWUROOHU+DUGZDUH
Hardware and Operation
Users Guide
3BSE 019 193R201
127,&(
The information in this document is subject to change without notice and should not be construed as a commitment by
ABB Automation Products AB. ABB Automation Products AB assumes no responsibility for any errors that may appear
in this document.
In no event shall ABB Automation Products AB be liable for direct, indirect, special, incidental, or consequential damages
of any nature or kind arising from the use of this document, nor shall ABB Automation Products AB be liable for
incidental or consequential damages arising from use of any software or hardware described in this document.
This document and parts thereof must not be reproduced or copied without ABB Automation Products ABs written
permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose.
&(0$5.,1*
This product meets the requirements specified in EMC Directive 89/336/EEC and in Low Voltage Directive 73/23/EEC.
75$'(0$5.6
IndustrialIT,
ControlIT and
OperateIT
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
7DEOHRI&RQWHQWV
7$%/(2)&217(176
&KDSWHU,QWURGXFWLRQ
1.1
1.2
Product Overview...................................................................................................4
1.2.1
Product Scope......................................................................................15
1.2.2
1.3
1.4
1.5
Conventions..........................................................................................................19
1.6
Terminology .........................................................................................................20
&KDSWHU,QVWDOODWLRQ
2.1
2.1.2
Cables ..................................................................................................25
2.1.3
2.1.4
Enclosures ...........................................................................................28
2.2
2.3
2.4
2.5
2.6
2.7
Installation of CEX-bus........................................................................................46
2.8
2.9
2.10
2.11
2.12
2.13
2.14
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
7DEOHRI&RQWHQWV
&217(176FRQWLQXHG
&KDSWHU&RQILJXUDWLRQ
3.1
General Information............................................................................................. 61
3.2
3.3
3.4
3.5
I/O Systems.......................................................................................................... 64
3.6
3.6.2
3.6.3
&KDSWHU2SHUDWLRQ
4.1
4.2
Start-up................................................................................................................. 75
4.3
4.4
&KDSWHU0DLQWHQDQFH
ii
5.1
5.2
5.3
5.4
5.5
5.5.2
5.5.3
5.5.4
5.5.5
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
7DEOHRI&RQWHQWV
&217(176FRQWLQXHG
$SSHQGL[$6DIHW\,QVWUXFWLRQV
A.1
General .................................................................................................................95
A.2
A.3
A.4
Machine Safety.....................................................................................................97
A.4.1
A.4.2
Maintenance ........................................................................................97
A.4.3
$SSHQGL[%+DUGZDUH0RGXOHV
B.1
B.2
B.3
B.4
B.5
B.6
B.7
B.8
B.9
B.10 Cabinets..............................................................................................................130
B.11 Miscellaneous Equipment ..................................................................................137
B.11.1
B.11.2
B.11.3
B.11.4
B.11.5
$SSHQGL[&3RZHU&RQVXPSWLRQ
C.1
General ...............................................................................................................141
C.2
iii
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
7DEOHRI&RQWHQWV
&217(176FRQWLQXHG
$SSHQGL['5HFRPPHQGHG&RPSRQHQWV
D.1
$SSHQGL[('LUHFWLYH&RQVLGHUDWLRQV
E.1
E.2
$SSHQGL[)(QYLURQPHQWDO'DWD
F.1
iv
F.1.2
F.1.3
F.1.4
F.1.5
F.1.6
F.1.7
F.1.8
F.1.9
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
7DEOHRI&RQWHQWV
,//8675$7,216
Figure 1-1.
Figure 1-2.
Figure 1-3.
Figure 1-4.
Figure 1-5.
Figure 1-6.
Figure 1-7.
Figure 2-1.
Figure 2-2.
Figure 2-3.
Figure 2-4.
Figure 2-5.
Figure 2-6.
Figure 2-7.
Figure 2-8.
Figure 2-9.
Figure 3-2.
Figure 3-3.
Figure 3-4.
Figure 5-1.
Figure 5-2.
Figure 5-3.
Figure B-1.
PM860/TP830 ...........................................................................................99
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
7DEOHRI&RQWHQWV
Figure B-2.
Figure B-3.
Figure B-4.
Figure B-5.
Figure B-6.
Figure B-7.
Figure B-8.
Figure B-9.
vi
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
7DEOHRI&RQWHQWV
7$%/(6
Table 1-1.
Table 1-2.
Related Documentation.............................................................................17
Table 1-3.
Table 1-4.
Terminology ..............................................................................................20
Table 2-1.
Table 2-2.
Table 2-3.
Table 2-4.
Table 2-5.
Table 2-6.
Table 2-7.
Table 2-8.
Table 3-1.
Table 4-1.
Table 4-2.
Table 4-3.
Table 4-4.
Table 5-1.
Table 5-2.
Table 5-3.
Table 5-4.
Table 5-5.
Table 5-6.
Table B-1.
Table B-2.
Table B-3.
Table B-4.
Table B-5.
Table B-6.
Table B-7.
Table B-8.
vii
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
7DEOHRI&RQWHQWV
Table B-9.
Table B-10. PSUs SD821, 822 and 823 - Mounting Dimensions ............................. 124
Table B-11.
viii
Table C-1.
Table C-2.
Table C-3.
Table D-1.
Table D-2.
Table D-3.
Table D-4.
Table D-5.
Table F-1.
Table F-2.
Chapter 1 Introduction
Chapter 1, Introduction
Provides an overview of the hardware platform AC 800M together with information
on related documents. This chapter also provides a list of product versions,
conventions, and a short glossary of related terms & acronyms.
Chapter 2, Installation
A guide to the various installation activities such as:
Building requirements
Grounding requirements
Mounting dimensions.
Chapter 3, Configuration
Provides information on the hardware configuration for the AC 800M Controller.
Chapter 4, Operation
Includes information on start-up and shut-down procedures together with
verification procedures for the AC 800M Controller.
Chapter 5, Maintenance
Contains information relating to the AC 800M maintenance requirements.
It is intended to provide system and module fault-finding procedures together with
module specific maintenance procedures. The information contained in this chapter
is aimed at the Maintenance/Service Engineer level.
Safety Instructions
EMC/LVD Directives.
Tip indicates advice on, for example, how to design your project or how to use a
certain function.
Although :DUQLQJ hazards are related to personal injury, and &DXWLRQ hazards are
associated with equipment or property damage, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore, it is
important to comply fully with all :DUQLQJ and &DXWLRQ notices.
Processor module
Baseplate: TP830
When equipped with the specified Control Software, the AC 800M Controller will
act either as a stand-alone process controller, or as a controller performing local
control tasks in a control network consisting of many interconnected controllers,
operator stations and servers.
To the AC 800M Controller various I/O systems can be connected either directly
(S800 I/O) or via Profibus-DP.
I/O System
Processor
module
S800 I/O
module
LED
Status
Indicators
Battery
Isolator Tag
INIT
Push button
Rx/Tx
Optic Ports
Tx/RX
Status
Indicators
External Battery
Supply Socket
Power Supply
and
Supervision Signal
Socket (SS822)
CN1/CN2
Ports
DIN-rail
Locking Device
COM3/COM4
Ports
Central Processor Unit (CPU) Module (PM860), with CPU and Power Supply
boards
Refer to Figure 1-4. PM860- Functional Block Diagram. The CPU board contains
the MPC860 CPU, 8 Mbyte RAM, 2 Mbyte Flash PROM, controllers for all built-in
communication interfaces, real-time clock, LED indicators, INIT push button and
a CompactFlash interface.
The main function of the power supply board is to generate an isolated, short circuit
proof +5V and +3.3V supplies for the PM860 and I/O modules. The board also
contains opto-isolated RS232-C drivers/receivers for the service port together with a
back-up battery holder for memory/real time clock, (RTC).
The termination board, housed in the TP830 Baseplate, is where the majority of
the external connections takes place. It is grounded to the DIN-rail by means of
the metallic components of the housing. The termination board is provided with
screw terminals for power supply and redundant power supply monitoring,
RJ45 connectors for the control network and serial port, a connector for the service
port, the electrical Modulebus and the CEX-Bus.
All modules on the CEX-bus and the electrical Modulebus are powered by
the 24 V d.c. connected to the TP830 Baseplate.
It is possible to connect a S800 I/O cluster directly to the Modulebus plug located on
the right hand side of the TP830 Baseplate. The optical Modulebus port on the CPU
module allows for connection of up to seven additional S800 I/O clusters. A cluster
may consist of up to 12 x S800 I/O modules giving a total of 96 x S800 I/O
modules. S800 I/O modules can also be connected to the AC 800M Controller via
PROFIBUS-DP.
The processor module has a communication expansion bus connector located on
the left hand side of the TP830 Baseplate. This CEX-bus provides for extending
the on-board communication ports with additional communication modules.
PROFIBUS-DP, FOUNDATION Fieldbus and dual RS232-C ports are some
examples of module types available for connection to the CEX-bus.
CPU Module
PM860
Cover
Assembly
CEX-bus
Socket
Modulebus Socket
Fuses
CEX-bus/Modulebus
Baseplate
TP830
Power
d.c.
+3.3V d.c.
System and
user mem.
Optical
CEX-bus
+5V d.c.
Electrical
Modulebus
controller
CEX-bus
controller
Battery
External
battery
+BV
(+3.3V)
CompactFlash
CPU
Communication
controllers
ID
prom
INIT
Logic
Ethernet
Ethernet
RS232
RS232
B
R
CN1
4
CN2
COM3
COM4
Figure 1-5 provides examples of the various ways to connect the S800 I/O modules.
It can be seen, by reference to the top right area of Figure 1-5, that connected to
the electrical Modulebus of a AC 800M Controller is 1 cluster (or group) of
modules, (maximum number of modules per cluster is 12). However, to the optical
Modulebus, a further 7 clusters, each cluster comprising of up to 12 modules, can be
added, thus achieving a total count of 96 modules per AC 800M Controller when
using only the Modulebus.
However, to the left on Figure 1-5, can be seen a PROFIBUS-DP segment, which
allows for a large increase in the numbers of modules connected to each AC 800M
Controller. Here the segment is shown as having a Fieldbus Communications
Interface (FCI) unit (type CI830), connected to the PROFIBUS-DP network.
The use of FCI modules allows the selection of modules from several I/O families.
The expansion modules available removes any restrictions on the number of I/O that
can be connected, thereby creating the situation that the upper limit could possibly
be in the several hundreds of thousands.
For further examples please refer to the relevant documentation for respective
I/O system.
10
Max 6 Modules
C1851
C1853
PROFIBUS-DP FOUNDATION
Fieldbus H1
PM860
CPU
DI810
AI810
DO810
Optical
TB820
1 Segment of
PROFIBUS-DP
DI810
AI810
AO820
See
Note 1
To 6 Additional Optical
Modulebus Clusters
Optical
CI830
DI810
AI810 AO820
See Note 3
TB820 DI810
Optical
AI810
AO820
Additional stations
up to maximum of
32 stations per Segment
Repeater Unit
11
Modulebus
The Modulebus has an electrical and a fibre-optical interface, which are logically
the same buses. A maximum of twelve I/O modules can be connected to
the Electrical Modulebus and up to seven clusters can be connected to the fibreoptical Modulebus. The fibre-optical interface is intended for local distribution of
I/O clusters and for connection of engineered and standard drives.
Figure 1-6 provides details of the fibre optic connectors, together with
the PM860 optical Modulebus ports.
PM860
Tx
Tx
Tx
Tx
Rx
Rx
Rx
Rx
CN1
CN2
COM3
L+
LSA
SB
COM4
Rx
Tx
Simplex Fiber Optic Cable Connector
Front View
12
Control Software
The firmware functions loaded into the controller (real time executive system,
real time clock, redundant communication)
The license management that defines what part of the total scope of functions
that you can use in a specific controller.
ABB Automation Products has provided each TB830 Baseplate with a unique
Ethernet address, (Media Access Control (MAC) address). This provides every
CPU with a hardware identity which in future releases can be used by a license
management system.
This functionality takes the form of two identification addresses which reside in
the Flash memory of the TP830 Baseplate. The lowest address, (a 12 character Hex
code), is located on a adhesive label attached to the TP830 Baseplate and is used by
the licensing management system. The remaining address is the lowest +1.
See Figure 1-7 for label location details.
Refer to &RQWURO%XLOGHU6WDUWLQJXSDQG,QVWDOODWLRQ see Section 1.4, Related
Documentation and Media, for details on how to load the software and to use
the Ethernet, (MAC), address.
13
SE00263650
ETHERNET: 00-00-23-0A-00-8E
14
3URGXFW6FRSH
This document describes the various processor modules, communication modules,
power supplies and enclosures (cabinets & racks) that make up
the AC 800M Controller. It also provides information on how to install, operate and
maintain the hardware. For information on the Control Software, please refer to
the manual$&0& &RQWURO6RIWZDUHDQG7RROV. See Section 1.4, Related
Documentation and Media.
Allows for the use of low-cost, sealed enclosures due to extremely low module
heat dissipation, even at ambient 40C (104 F)
15
The AC 800M hardware platform has been allocated a version number starting at
1.0. This version number is required to keep the configuration of all modules and
components, on the AC 800M platform, together and will act as a reference in the
future between different documents. As the AC 800M hardware platform
configuration grows in future releases, the version number will increase
accordingly.
Table 1-1 shows the product version release history of AC 800M.
7DEOH $&05HOHDVH+LVWRU\
Version
Description
1.0
1.1
16
1 x 24 V d.c. Power Supply Module, (for example SD821 24 V d.c. @ 2.5 A.).
Title
S800 I/O General
Information and
Installation
S800 I/O Modules and
Termination Units
Description
Users Guide
Describes the general installation and
configuration for the S800 I/O system.
Users Guide
Describes the standard I/O modules and
termination units in the S800 I/O system.
Users Guide
Describes the PROFIBUS-DP FCI within
the S800 I/O system.
Users Guide
Describes how to install and wire
a FOUNDATION Fieldbus H1.
Terminal Diagrams
AC 800M
Terminal Diagrams
S800 I/O
17
Title
Control Builder M
Beginners Handbook,
Starting up and
Installation
Description
Users Guide
Installation and start-up of the various
software packages that are contained on
the Control Builder CD.
This manual also provides a tutorial
on how to create applications.
AC 800M/C Control
Software and Tools
Users Guide
AC 800M/C
Communication,
Protocols and Design
Users Guide
Describes the different communication
protocols that can be used with
the Control Software and gives information
on how to design a network.
AC 800M/C Control
Functions, Alarm,
Analog Control and
Controllers
Users Guide
AC 800M/C
Users Guide
FOUNDATION Fieldbus Details how the
FOUNDATION Fieldbus H1 is
integrated in the controllers and the
OperateIT A platform
AC 800M/C Controller
Users Guide
Integration, Engineering Describes how to connect and configure
Methods
the controllers with the OperateIT A platform
18
Title
PROFIBUS Web Site
(Fieldbus Online)
ControlIT for AC 800M/C
Media
Description
1.5 Conventions
The following conventions are used throughout this document for the presentation
of material:
19
1.6 Terminology
The following is a list of terms and acronyms used in this document.
7DEOH 7HUPLQRORJ\
Term/Acronym
20
Description
AC 800M
AC 800M Controller
Cabinet
Central I/O
CEX-bus
CF or CompactFlash
Controller
COTS
CPU
DCS
DIN-rail
EMC
Electro-Magnetic Compatibility.
EEPROM
Ethernet
Description
FCI
FF
GSD
IEC
IEEE
LED
LVD
MAC
Module
MTU
Node
OCS
PELV
PLC
PROFIBUS-DP
PROM
21
22
Description
RAM
Redundancy
Remote I/O
SELV
UPS
&KDSWHU ,QVWDOODWLRQ
This chapter contains guidelines for planning the installation of
an AC 800M controller system, (refer to Section 2.1.1, Site Selection and Building
Requirements). This section does not provide a complete list of measures to be
taken with respect to the environment and other on-site conditions.
The equipment should be adapted to the actual application by means of a thorough
and correctly scoped system definition, ordering procedures and design
requirements. This chapter also describes practical on-site installation procedures,
specific to AC 800M modules, (refer to Section 2.2 onwards).
23
When planning a control system installation, please consider the following points:
24
Temperature:
Vibration:
Cooling:
Free space in front of the cabinet. In addition, consider how much space is
required to fully open the cabinet doors. For safety reasons there must always
be adequate space available, even with the doors in the fully open position.
2.1.2 Cables
The Laying of Field Cables
There are no special requirements for the laying of field and communication cables
connected to AC 800M, except for:
All cables connected to AC 800M should be run 30 cm (12) away from power
cables not belonging to AC 800M, and 10 cm (4) away from cables belonging
to class 4 of relevant international immunity standard.
25
Communications
For other applications it is possible to use unshielded cables. Signal and return
conductor are always to be located in the same cable.
Lightning Strike Protection
Industrial installations and power plants are normally provided with well-integrated
grounding nets installed together with the power distribution system. In installations
with this type of grounding system, it is not necessary to install additional lightning
strike protection facilities unless using overhead wiring or suspended cables in an
outdoor environment.
Large dispersed plants such as water supply installations and oil refineries will
however, have an inadequate grounding system installed and therefore signal cables
may be routed above ground. In such cases, it will still be necessary to install
suitable lightning strike protection equipment.
Should any cables be discovered outside the grounding system (even for short
distances, such as 10 m (9.1 yds)), it will be necessary to install lightning strike
protection equipment.
It is not necessary to use mains net filters when using the SD821/822/823 power
supply modules.
26
Safety Switch
Fuse Type
10 A
Slow to Rupture
Should the configuration be other than that stated, detailed instructions for
calculating current consumptions can be found in the relevant I/O manuals.
For the AC 800M Controller, refer to Appendix C, Power Consumption.
27
The SD82x series of power supply modules easily handle short power interruptions
(<20 ms) that can normally occur within any industrial environment. Despite this,
it is sometimes necessary to protect certain applications against brief voltage
failures by the installation of an Uninterruptable Power Supply (UPS) device.
The AC 800M controller will shut down safely in event of a power failure.
During the down time, the current supply of the application memory and the system
clock is backed up by the internal battery supply. In systems subject to long non
operational periods, it is recommended that an external battery back-up unit is
installed. When the power supply is reconnected, the AC 800M Controller will
re-start and run the application as normal.
If the effects of unexpected shutdowns are not permissible, it is highly
recommended that the AC 800M Controller is fully protected by receiving its
supply from an Uninterruptable Power Supply (UPS) source.
2.1.4 Enclosures
General
The AC 800M and S800 I/O modules are of protection class IP20 and each module
is individually CE-marked. They can be used without any additional enclosure but
due to normal industrial environment it is recommended to use a higher protection
class than IP20 by adding a suitable enclosure.
Normally the use of an additional enclosure will not influence the EMC
characteristics of the controller.
Enclosure Mounting
28
ABB Cabinets
As a suitable enclosure, ABB recommend the following two cabinets, which have
been specially adapted for mounting the AC 800M Controller and the S800 I/O.
Both are sealed with protection class IP54 and can support the Controller and
S800 I/O modules without the requirement for additional cooling equipment.
29
Mounting Procedure for PM860, CI851, CI852 and CI853 Modules, Complete
with Baseplates
Rotate the locking device to the 23(1position (1) and hook the upper lip, to
the rear of the module baseplate, securely over the upper edge of the DIN-rail
and gently snap the baseplate fully into the mounting position.
2.
Rotate the locking device to the 6/,'(position (2). Now gently slide the
module along the DIN-rail to the desired mounting position and gently attach it
to the adjacent module baseplate using the connector plugs and sockets.
Ensure that the baseplates plugs and sockets are fully aligned when the modules are
about to be interconnected or damage to the pins will occur. Under no
circumstances use excessive force!
3.
30
1. OPEN
2. SLIDE
3. LOCKED
31
Ensure that the AC 800M modules are electrically isolated before removing them
from a DIN-rail!
Use the procedure detailed below to remove a module, complete with baseplate:
1.
2.
3.
Rotate the locking device tothe6/,'( position (2), on the module baseplate
to be removed.
Note that the SLIDE sequence must be carried on the module baseplates, adjacent to
the module which is to be removed, in order to provide adequate access and removal
space.
4.
32
5.
Turn the locking device anti-clockwise to 23(1 position (1) and ease
the module baseplate outwards and upwards at the base. Lift the module to
remove it from the DIN-rail.
The module baseplates can easily be disconnected from each other by simply using
a flat bladed screwdriver and gently easing it between the two modules,
refer to Figure 2-4.
F
R
Rx1
F
R
Rx/Tx
Tx1
RTS
F
R
P
B
Rx2
Tx2
INIT
CI851
CI853
COM1
COM2
PM860
CN1
33
The baseplates have incorporated a two part, pre-set Alpha code locking device
which, due to the fact that the modules are very similar in design, prevents the
installation of an incompatible type of module onto baseplate, should the Alpha
codes not agree. All identical module types will have the same, factory pre-set,
two letter alpha code installed prior to delivery.
The following module types have two part, pre-set Alpha code locking devices
installed:
7DEOH )DFWRU\3UHVHW$OSKD&RGHs
Module
Key Position 1
Key Position 2
CI851 PROFIBUS-DP
Interface
CI852 FOUNDATION
Fieldbus H1 Interface
Various - refer to
Product/User Guide
Various - refer to
Product/User Guide
For further details on pre-set Alpha codes, refer to the relevant module
documentationSee Section 1.4, Related Documentation and Media.
Care must be taken to ensure that the correct module is matched with the correct
baseplate, or damage to the equipment will occur. Should force appear necessary
when installing a module onto a baseplate, this is a positive indication that the
Alpha code lock/module compatibility may be incorrect.
Refer to Figure 2-5 for further details of the Alpha code lock arrangement.
The mechanical keys are delivered pre-set and must not be altered. This is done to
prevent the removable interface to be placed on the wrong type of baseplate.
34
Pre-Set
Alpha Code Keys
35
Remove the bus terminations from the sides of the processor module.
2.
3.
Press them gently together and make sure that the Modulebus and the CEX-bus
is correctly connected, via the connectors on the baseplates and MTUs.
4.
Reinsert the bus terminations into the modules farthest away from the PM860
processor module.
5.
36
a.
For the CEX-bus TB850 (TB851 if cable TK850 is used), see Figure 2-8
and Figure 2-9.If no modules are used on the CEX-bus, no bus
termination is required.
b.
The power leads and, if applicable, power supervision signals from SS822
to the screw terminals SA and SB, refer to Figure 2-6.
b.
c.
d.
37
6.
Connect the optical Modulebus to the optical contacts on the PM860, see
Figure 1-2 and Figure 1-6. Information regarding optical cable selection and
cable lengths is provided in the S800 I/O documentation, refer to Section 1.4,
Related Documentation and Media.
Note that the connection to the optical Modulebus is carried out in the same way for
the CPU module PM860 as for the Fieldbus Communication Interface (FCI) in
S800 I/O.
7.
Do not remove the plastic tab until the controller is powered-up in the normal way.
The CPU memory will start to consume battery power immediately the plastic tab is
removed as no power supply is connected to the CPU.
Communications Ports
CN1 and CN2
The control network connects to one or two RJ45 connectors depending on single or
redundant network option. CN1 and CN2 are RJ45 ports for Ethernet.
Use a RJ45 connector for IEEE802.3 (Ethernet) for connecting with a category
5 Shielded Twisted Pair cable (STP class 5).
The IEEE standard language is a class 5 cable 10/100Base-T/TX max 100 m
(109 yds). The STP is suitable only in non industrial (office) environment. Only use
STP in a protected environment to connect to the Commercial Off-The-Shelf,
(COTS), Ethernet components, (HUBS/Transceivers/on so forth), that convert to
optical fibre. ABB recommend the use of optical fibre in an industrial environment,
for example use 62.5/125 100Base-FX with max distance 1500 m (1640 yds).
38
Designation
Direction
Description
TD+
Out
TD-
Out
RD+
In
4-5
Not used
RD-
In
7-8
Not used
Housing
Shield
Shield
COM3 Port
The COM3 is an RS232-C port with modem signals. This port is used for serial
protocols such as Modbus, Siemens 3964R, COMLI or the customers own design.
7DEOH 73&20&RQQHFWLRQV
Pin
Designation
Direction
Description
RTS
Out
Request To Send
DTR
Out
TD
Out
Transmit Data
0V
Signal ground
0V
Signal ground
RD
In
Receive Data
DCD
In
CTS
In
Clear To Send
Housing
Shield
Shield
39
COM4 Port
The COM4 port is a RS232-C port that is opto-isolated and without modem signals.
Connect Control Builder to this port when connecting directly to the controller,
without the need use the remote tool connection, via the Control Network.
7DEOH 73&20&RQQHFWLRQV
Pin
40
Designation
Direction
Description
Not used
Not used
TD
Out
Transmit Data
0V
Signal ground
0V
Signal ground
RD
In
Receive Data
Not used
Not used
Housing
Shield
Shield
Mount the module on the DIN-rail, (refer to Section 2.2 and 2.3 ).
2.
3.
4.
If this is at the end of the PROFIBUS-DP cable, switch the bus termination
ON. However, if this is not at the end of the bus cable, leave the bus
termination switched OFF.
PROFIBUS-DP Connection
41
Installation of PROFIBUS-DP
Designation
Description
Shield
Shield/protective ground
Not Used
B-line
GND Bus
GND Bus
+5 V Bus
A-line
Not used
For installation of the fieldbus, the recommended certified fieldbus devices and
related components, refer to the352),%86'3GRFXPHQWDWLRQ, see Section 1.4,
Related Documentation and Media. Shielded twisted-pair cables must be used for
connecting the PROFIBUS-DP.
Additional information about PROFIBUS-DP and other suitable components is
available, on the Internet, at the PROFIBUS User Organization web site.
42
Mount the module on the DIN-rail (see also Section 2.2 and 2.3 ).
2.
3.
Connect the FF H1 bus to the male DB9 connector, located on the TP852 Baseplate.
7DEOH &,DQG73)281'$7,21)LHOGEXV&RQQHFWRU
Pin
Signal Function/Designation
1-5
Not used
6 FB-P
7 FB-N
8-9
Not used
43
44
Mount the module on the DIN rail (see also Section 2.2 and 2.3 ).
2.
Connect the cable (maximum 15 m (16.4 yds)) to the contact on the baseplate.
Connect the cable screen to the ground terminal within the connector,
the screen will then be grounded via CI583.
3.
If cable lengths longer than 15 m (16.4 yds) are required, a short distance
modem, TC562, must be used. If used, mount the modem on a DIN-rail in a
suitable position, connect a 24 V d.c. power supply to the modem and connect
the cable,TK853V01, from CI853 to the TC562 modem input terminals.
4.
Connectors
Connect the RS232-C channels to the RJ45 connectors marked COM1 and COM2
on the TP853 Baseplate.
7DEOH &,56&,QWHUIDFH&20DQG&20&RQQHFWRUV
Pin
Designation
Direction
1-9
Description
See COM3 on PM860
45
Only one TK850 CEX-bus extension cable may be used in a CEX-bus. The length
of the cable is 0.7 m (2.3).
46
2.
Set the mains switch on the front of the power supply module to the required
input voltage setting
a.
b.
3.
4.
5.
The L- output (0V) (see Figure 2-10) of the power supply units can be used without
being grounded. When equipment is delivered, installed in cabinets,
the L- output (0V) is not grounded. If grounding is required, the power supply units
L- output (0V) can be grounded directly or via a suitable resistor.
All terminals marked L+ are internally connected within the power supply module.
The same applies for terminals marked L-.
47
Mount the components of the mains breaker unit onto the DIN-rail, close to the
incoming power supply, in the following order listed below, (from left to right),
and as shown in Figure 2-7.
a.
The 2 terminals for the incoming Live and Neutral mains power (3).
These terminals are equipped with built-in jumpers which, if necessary,
may be opened to provide complete mains input power isolation.
d.
e.
f.
g.
2.
Connect the incoming mains, protective earth terminals, mains breaker and
distribution terminals as shown in Figure 2-7.
3.
Install the two required links (7), fuse-holders (8) and jumpers (9), onto
the distribution terminals. Fit the required fuses into the fuse-holders,
(glass-tube type, 5 x 20 mm (0.2 x 0.8 inch)).
48
PE - Green/Yellow
4
2
5
6
7
1
8
PE - Green/Yellow
PS2
MAINS
PE - Green/Yellow
PS1
PE - Green/Yellow
49
Terminator
TB850
F
R
Rx/Tx
RTS
F
R
Rx/Tx
RTS
PM860
CPU module
CI851
CI851
50
F
R
Tx1
Rx1
Tx2
Rx2
F
R
Rx/Tx
F
R
Rx/Tx
RTS
PM860
CPU module
CI853
CI852
CI851
COM1 COM2
TK850 Cable
F
R
Tx1
Rx1
Tx2
Rx2
F
R
Tx1
Rx1
Tx2
Rx2
F
R
Rx/Tx
CI853
CI853
CI852
COM1 COM2
COM1 COM2
Terminator
TB851
51
Mount the voting device SS822 onto the DIN-rail adjacent to the power
supplies.
2.
SA
SB
L+ L+ LOK
L-
L+ L+ LOK
SD821
N
PE
L-
SD821
N
PE
Supervision
signals to
PM860/TP830
OK+ F OK+ F
A
SS822
A+B+L+ L+ L-
L+
Mains
Input
L-
Protective Earth
+24V
0V
52
2.
For connecting the external battery module, SB821, use the 2 m (2.2 yds) cable
TK821V020. Plug one end into the battery module and plug the other end of
TK821V020 into the external battery supply socket of the PM860 CPU
module,see Figure 1-2.
3.
It is necessary to remove the internal battery from the PM860 when using
an external battery source in order to avoid reducing the available memory
back-up time due to the batteries being connected in parallel.
Do not connect the TK821V020 cable until the AC 800M Controller has been
powered-up normally. If no normal power supply is connected to the PM860 CPU
module, the CPU memory will immediately start to consume battery power if
the cable is connected.
Remember to always install a fresh internal or external battery at the end of
the installation phase, as the original battery will have been heavily used due to
frequent blackouts during the system installation.
53
Modulebus
Expansion
Cable
Aluminium
Profile
Cable
Duct
Mains Breaker
Unit
SD821
24 V Distribution
Terminals
54
Mains Breaker
Unit
SD821
(Modules)
SD821
(Field)
24 V Distribution
(Modules in Cabinet)
24 V Distribution
(Field Equipment)
55
SD822
Redundant
Power
Supply Units
(Field
Equipment)
Mains
Breakers
SS822
Voting
Units
SD822 Redundant
Power Supply Units
56
TB820
TB820
Mains Breaker
Unit
24 V Distribution
SD822
57
Unobstructed areas
>240 mm
(9.4)
>25 mm (1.0)
>50 mm (2.0)
Unobstructed areas
>25 mm (1.0)
58
Battery
isolator tag
To be removed
for connecting
of the battery
59
60
&KDSWHU &RQILJXUDWLRQ
*HQHUDO,QIRUPDWLRQ
Using the engineering tool, Control Builder, it is possible to configure hardware
(I/O and communication modules), and make application programs with control
languages according to IEC61131-3. You can compile and run programs off-line as
an aid to process simulation before finally downloading an application to the
controller. The Control Builder offers a set of options each with its own set of
properties. Simply select the option that corresponds most closely to the system
requirements. For further information, refer to Section 1.4, Related Documentation
and Media.
The Control Builder Online Help facility provides detailed step-by-step information
on the procedures to be taken when creating an application for
the AC 800M Controller.
&RQQHFWLRQRIWKH&RQWURO%XLOGHU0
The Control Builder, installed in a PC, is normally connected to
the AC 800M Controller. It is connected via the Control Network and the CN1 or
CN2 ports on the controller. This is displayed in Figure 3-1.
Alternatively you can connect the Control Builder via the COM4 port (RS232-C) on
the AC 800M Controller. Use the tool cable TK212 and a serial port on the PC.
Note, if the firmware in the AC 800M is not running correctly, then it is likely that it
is not possible to use the CN1 and CN2 ports. Regardless, the connection via the
COM4 port is always available.
61
&RQQHFWLRQWRD&RQWURO1HWZRUN
The Control Network is a private IP network domain for both real time data and
general system communication between industrial computers. It is scalable from a
very small network with a few nodes, to a large network containing a number of
Network Areas and many hundreds of nodes.
Controllers mounted
in cabinets
AC 800M
AC 800M
AC 800M
AC 800M
I/O
I/O
I/O
I/O
AC 800M
AC 800M
AC 800M
I/O
I/O
I/O
STP
STP
Only use
STP inside
areas with
common
grounding
STP
FO or STP
Hub
WARNING
FO or STP
Switch
Hub
USE FO GENERALLY
FO
NON-INDUSTRIAL
ENVIRONMENT
Switch
Control Builder
Operator Station
62
It can use different and mixed link implementations such as Fast Ethernet and PPP.
It provides for full redundancy to achieve high network availability.
The AC 800M controller is always connected to the Control Network via a STP
(Shielded Twisted Pair) cable. Should the local environment be of the industrial
nature, the AC 800M / Control network connection must be converted over to
a Fibre Optic (FO) cable. This is achieved by installing a Switch/Hub which has
both optical and electrical ports. Refer to Figure 3-1.
The Control Network is described in $&0&&RPPXQLFDWLRQ3URWRFROVDQG
'HVLJQ. Refer to Section 1.4, Related Documentation and Media.
&RPPXQLFDWLRQ3RVVLELOLWLHV
Located on the processor module (PM860/TP830), are the following
communication ports which are available for the following functions:
CN1 and CN2 are used for connection to the Control Network. Both are RJ45
ports for Ethernet (IEEE802.3) and connection is normally achieved by using
category 5 shielded twisted pair cable, (STP class 5). However, as previously
stated, within industrial environments it is recommended that all STP cable are
converted to optical fibre.
COM3 is a RJ45 port for RS232-C with modem signals. Example of protocols
are Modbus, Siemens 3964R, COMLI or to the customers own design. Please
refer to the &RQWURO6RIWZDUHGRFXPHQWDWLRQfor additional detailed
information. Refer to Section 1.4, Related Documentation and Media.
COM4 is a RJ45 port for connection of service tools (see Chapter 3.2).
The port has no modem signals.
63
CI852
(FOUNDATION Fieldbus)
CI853
(RS232-C)
Total
1
6
For information relating to available serial protocols for the CI853 interface,
see COM3 above.
,26\VWHPV
There are two methods of connecting I/O systems to the AC 800M controller:
PROFIBUS-DP for all I/O systems and modules that are equipped with an
adapter suitable for PROFIBUS-DP connections.
The S800 I/O modules can also be connected via the Fieldbus Communication
Interface CI830.
List of supported I/O systems and modules is found in $&0&&RQWURO6RIWZDUH
DQG7RROV, see Section 1.4, Related Documentation and Media.
Modulebus
The Modulebus in the AC 800M controller consists of one electrical unit and one
optical unit:
64
Electrical
Modulebus
PM860
Local
TB820
Remote
TB820
Maximum of 7
clusters (groups)
Optical
Modulebus
TB820
65
PROFIBUS-DP
S800 I/O and/or S800L I/O via Fieldbus Communication Interface (FCI)
CI830, refer to 6,2GRFXPHQWDWLRQSee Section 1.4, Related
Documentation and Media.
S200 I/O and/or S200L I/O via Fieldbus Adapter 200-APB12, refer to
6,2GRFXPHQWDWLRQ SeeSection 1.4, Related Documentation and Media.
GSD files with configuration data for the I/O modules is imported to
the Control Builder via a dedicated GSD Import Tool.
Note that the total number of I/O modules to be configured within a controller can
be restricted depending on the module range parameter of your license. The license
management is fully described in&RQWURO%XLOGHU%HJLQQHUV+DQGERRN6WDUWLQJ
XS ,QVWDOODWLRQrefer to Section 1.4, Related Documentation and Media.
For further information relating to the various I/O systems, refer to Section 1.4,
Related Documentation and Media.
3RZHU6XSSO\6\VWHP
The configuration of power supply system for an AC 800M controller is very
straightforward.
Configurations
Figure 3-3 shows a series of simple circuit diagrams to indicate the various
possibilities for connecting the incoming mains power, via the mains breaker,
66
the power supply modules and the SS822 voting devices, to the 24 V d.c.
distribution terminals.
The AC 800M Controller and its I/O system are normally located in one or several
enclosures or cabinets. The cabinet housing the AC 800M Controller can also
contain I/O modules connected to the controller via the electrical modulebus, the
optical modulebus or the communication interface for PROFIBUS-DP.
Cabinet containing the AC 800M controller
It is strongly recommended to
use power supply in HDFK cabinet for Powering Modules (only when cabinets
are mounted side by side, power to the modules can be taken from another
cabinet)
use VHSDUDWH power supplies for Powering Modules and Powering Field
Equipment, refer to Figure 2-12 and Figure 2-13.
3RZHULQJ0RGXOHVLQ&DELQHW
This power supply is connected only to modules within the cabinet such as
PM860 which also powers all communication interfaces (via the CEX-bus) and
all S800 I/O modules connected to its electrical modulebus.
TB820V2 (optical modem for S800 I/O) which also powers all
S800 I/O modules connected to its electrical modulebus.
67
CI830 (PROFIBUS-DP interface for S800 I/O) which also powers all
S800 I/O modules connected to its electrical modulebus.
PROFIBUS-DP adapters for other I/O systems (depending on how the supply
arrangement is done for the I/O modules it can be necessary to connect power
to each I/O module).
The main configuration rule for this power supply is that the cables carrying the
24V never go outside the cabinet.
3RZHULQJ)LHOG(TXLSPHQWRXWVLGH&DELQHW
This power supply is intended for supplying power to process signals and
equipment located outside the cabinet.
Interferences
Powering field equipment from a power supply located in the AC 800M Controller
cabinet often requires the use of long 24 V d.c. cables which can easily pick up local
interference and direct it straight back to the power supply modules. Follow the
rules about Field Cables, given in Section 2.1.2, Cables, when installing the cables.
Short-circuit at the power supply output
The SD82x series power supply has no extra energy reservoir at their outputs.
In case of a short-circuit the output voltage of the power supply will fall rapidly.
Short-circuits (even if fuses are installed in the 24 V d.c. distribution system) or
large load changes can produce unwanted voltage dips in the power supply.
To avoid any influences on the AC 800M Controller from any of the field
equipment, it is strongly recommended that separate power supplies are installed
(refer to Figure 2-12 and Figure 2-13).
Sectioning the field equipment
68
other groups then it is recommended to use one power supply for each group of field
equipment.
To use fuses in the 24 V d.c. distribution system will not work properly. If a shortcircuit occurs in one group the power supply voltage will most likely drop before
any fuse is blown and consequently all groups will have a voltage drop in their
supply.
Cable protection
Fuses in the 24 V d.c. distribution system for cable protection only can be used.
Allow the power supply (which has an output current limitation at overload/short
circuit situations) to have a spare capacity of at least 3-4 times the rated current
value of the largest fuse connected to the power supply and remember to include the
resistance of long cables in the calculation.
Connection alternatives
The power supply for field equipment can be connected in the same manner as that
used for connecting and powering the AC 800M modules, see Figure 3-3.
It should be pointed out however, that the same Mains Breaker Unit can be used to
control and isolate both power supplies or, alternatively, independent Mains
Breakers can be used on each spur, see the examples shown in Figure 3-4.
3RZHULQJIURP([WHUQDO9GF6RXUFH
The AC 800M Controller can be powered from an external +24 V d.c. source.
This source is often common for many different equipments in a plant area and can
result in long power cables to the AC 800M Controller. Furthermore heavy load
changes can cause variations of the controller supply voltage and it can be necessary
to take precautions against low voltages to prevent controller malfunction.
If there is a risk that the +24 V on the power terminals of PM860 can be lower than
19.2 V for more than 1 ms, an energy reservoir must be used for Powering Modules
(refer to chapter 3.6). The recommended solution is to use a d.c./d.c. converter in the
controller cabinet. This converter can also provide an isolation between the
AC 800M supply and the external d.c. source and eliminate grounding problems
between the controller and other parts connected to the same source.
69
Supply to
Modules
SD
82x
Mains
Mains Breaker
24 V dc
Distribution
Terminals
Power
Supply
Mains
Supply to
Modules
Mains Breaker
SS
822
SD
82x
Voting
Device
24 V dc
Distribution
Terminals
Power
Supplies
Mains 1
Supply to
Modules
Mains Breaker
SS
822
SD
82x
Mains 2
Voting
Device
24 V dc
Distribution
Terminals
Mains Breaker
Power
Supplies
70
Supply to
Modules
Mains
SD
82x
24 V dc
Distribution
Terminals
Mains Breaker
Independent
Power Supplies
Supply to
Field
Equipment
SD
82x
24 V dc
Distribution
Terminals
Supply to
Modules
SD
82x
Mains
Mains Breaker
Independent
Power Supplies
24 V dc
Distribution
Terminals
Supply to
Field
Equipment
SD
82x
Mains Breaker
Independent Mains
Breaker Units
24 V dc
Distribution
Terminals
71
72
&KDSWHU 2SHUDWLRQ
This chapter describes the operation of the AC 800M Controller, comprising of a
PM860 CPU module together with various optional modules, (refer to Appendix B,
Hardware Modules, for additional technical information on the optional modules).
F (ault)
Color
Red
Function
R (un)
Green
Normal state - ON
Re-start (INIT) extinguishes R(un)
temporarily. At restart the (INIT) push
button is pressed (3 sec. or more) until
R(un) flashes.
Software program may also operate it.
P (owok)
Green
Normal state - ON
When illuminated, provides an indication
that dc/dc converter in PM860 is generating
valid +5 V and +3.3 V d.c. supply
voltages.No software control.
73
B (attery)
Color
Function
Green
Normal state - ON
Illuminated when condition of internal or
external battery is satisfactory.
The LED is controlled by a software battery
voltage test - BATTOK (1).
Tx
Yellow
Data Transmission
CN1 + CN2
COM3 + COM4
Flashes in synchro with Tx traffic
Rx
Yellow
Data Reception
CN1 + CN2
COM3 + COM4
Flashes in synchro with Rx traffic
(1) The software performs cyclic battery voltage level tests via a dedicated input for controlling the
LED.The battery provides back-up power to the application memory and the real time clock
during power down. The battery is either accessible via the cover panel of the PM860 or
connected externally to the external battery connector. The battery voltage is tested by the SW.
The voltage is common for both internal and external battery. For this reason, ensure the
internal battery is removed when using an external battery, as having two batteries connected in
parallel will result in greatly reduced capacity.
INIT
Type
Manual Push
button
Function
Initiates
1. Cold Restart if INIT is pushed less than
2.5 seconds.
2. Controller Reset if INIT is pushed more
than 3 seconds.
74
Connectors
Engraving
Function
+24 V d.c.supply
L-
0V
SA
SB
External Battery Connection
SH
B+
B-
Tx
Rx
MODULEBUS
CEX-BUS
6WDUWXS
For information about:
Firmware download
Controller IP address
Downloading application
Updating firmware
75
6WDUW0RGHV
Warm Start
The tasks controlling the application starts. Variable values are initialized unless
they are marked 5HWDLQ or &ROGUHWDLQ.
To initiate a warm restart, disconnect the power supply for a few seconds.
The warm restart function will automatically be initiated on power restoration,
following a power failure.
Cold Restart
The application program is restarted. Variable values are initialized unless they are
marked &ROGUHWDLQ.
To initiate a cold restart, the Controller must be restarted by briefly pressing
the INIT push button, (less than 2.5 seconds).
Controller Reset
The system is stopped. The application program and the variables are erased.
To initiate Controller reset, press the Controller INIT push button (more than
3 seconds) until the Run LED begins to flash. A controller reset must be performed
if the system is in an undefined position and consequently unavailable to the user.
9HULILFDWLRQRI6DWLVIDFWRU\$&02SHUDWLRQ
In order to check that the AC 800M Controller is operating satisfactorily after
start-up, refer to Table 4-4, AC 800M Controller - Verification of Satisfactory
System Operation, which is provided to assist the Operator to assure themselves
that the AC 800M Controller plus all associated modules is operating correctly.
76
Check the status of each LED indicator and compare it against the criteria listed in
the table. If the status is other than that listed, refer to Section 5.5, Fault Finding
Procedures.
7DEOH $&0&RQWUROOHU9HULILFDWLRQRI6DWLVIDFWRU\6\VWHP2SHUDWLRQ
AC 800M
Controller
Status
LED Indicator
Status
303URFHVVRU0RGXOH
F(ault) Red LED must be OFF
OK
OK
OK
OK
&,352),%86'30RGXOH
F(ault) Red LED must be OFF
OK
OK
&,)281'$7,21)LHOGEXV0RGXOH
F(ault) Red LED must be OFF
OK
OK
&,56&,QWHUIDFH0RGXOH
F(ault) Red LED must be OFF
OK
OK
77
78
&KDSWHU 0DLQWHQDQFH
This chapter provides details of the preventive an corrective maintenance
requirements for the AC 800M Controller together with fault finding procedures for
both the system and individual units.
:DUQLQJBefore attempting any maintenance or fault finding procedures, read the
Appendix A, Safety Instructions. Failure to do this could lead to situations where
personnel are placed in danger and/or damage caused to equipment.
3UHYHQWLYH0DLQWHQDQFH)UHTXHQF\6FKHGXOH
7DEOH 3UHYHQWLYH0DLQWHQDQFH)UHTXHQF\6FKHGXOH
Frequency
Equipment
Procedure
At Regular, User
Defined,
Intervals
Complete
System
Security of attachment
LED function
Correct any defects found.
2 Years
PM860
Internal Battery
(if fitted)
Change battery
Refer to Section 5.2, Changing the Battery
(Internal Battery)
5 Years
SB821
External Battery
(if fitted)
Change battery
Refer to Section 5.2, Changing the Battery
(External Battery)
79
&KDQJLQJWKH%DWWHU\
Internal Battery
The internal battery is mounted within the PM860 CPU module. As the battery is
the non-rechargeable type, it is important that battery is changed on a regular basis
to confirm its serviceability, refer to the Maintenance Frequency Schedule for
further details. Removal of the right-hand cover exposes an engraved detail on
the battery housing indicating the correct battery polarity arrangement. See
Figure 5-1 and 5-2.
When using an SB821external battery source it is important that the PM860 internal
battery is removed completely from its housing. Failure to do this will result in a
shorter than expected back-up time, as the both batteries will be connected in
parallel. In addition, supervision status is only provided for one battery.
It is possible to replace the internal battery with the AC 800M Controller on-line.
However, the usual safe working practices must be observed at all times.
However, a battery change must be carried out if any of the following circumstances
occurs:
For reasons of safety, only change the battery when the AC 800M is powered up.
80
Captive Screw
Cover
Internal
Battery
Holder
81
2.
3.
Insert a serviceable battery in position, ensuring that the battery polarity and
orientation is correct.
4.
5.
Refit the PM860 right-hand cover and tighten the captive screw.
6.
F
R
P
B
INIT
Internal
Battery
+
-
PM860
Tx
Rx
Tx
Rx
CN1
CN2
Tx
Rx
COM3
Tx
Rx
COM4
82
The external battery is mounted within the SB821 External Battery module.
As the battery is the non-rechargeable type, it is important that battery is changed on
a regular basis to confirm its serviceability, see Maintenance Frequency Schedule.
Removal of the external cover exposes the battery and battery housing. See
Figure 5-3. Take care to ensure that the polarity and orientation is correct when the
battery is replaced.
When using an SB821external battery source it is important that the PM860 internal
battery is removed. Failure to do this will result in a shorter than expected back-up
time, as both batteries will be connected in parallel. In addition, supervision status is
only provided for one battery.
However, a battery change must be carried out if any of the following circumstances
occurs:
83
84
1.
2.
3.
Carefully remove the SB821 module cover and identify the external battery.
4.
Read and comply with the Warning label / text located on the external battery.
5.
6.
Insert a serviceable battery in position, ensuring that the battery polarity and
orientation is correct. For further details on the battery, see Section B.8, SB821
External Battery - AC 800M Memory Back-up.
7.
Replace the cover, mount the unit on the DIN rail, and reconnect the cable
connector.
8.
9.
!
X1
B- B+ SH
85
0RGXOH&KDQJH2Q/LQH
With change on-line means adding or removing modules in a controller without
disturbing the execution of the running application program.
Modules are connected to the CEX-bus and to the electrical Modulebus (S800 I/O).
&(;EXV
Communication interfaces
CI851, CI852 or CI853
0RGXOHEXV
S800 I/O modules
&RUUHFWLYH0DLQWHQDQFH3URFHGXUHV
Changing Fuses - Modulebus and CEX-bus
Use the procedure detailed below to change the TP830 internal Modulebus and
CEX-bus fuses:
1.
2.
3.
Identify both the Modulebus and CEX-bus fuse-holders which are mounted on
the TP830 Baseplate, to the right-hand side.
4.
86
5.
6.
7.
Refit the PM860 CPU module and tighten the spring-loaded captive screws.
8.
87
)DXOW)LQGLQJ3URFHGXUHV
)DXOW)LQGLQJWKH303URFHVVRU0RGXOH
7DEOH 30)DXOW)LQGLQJ3URFHGXUH
Fault
F(ault) LED is ON
If condition persists:
Load application
Reload application
88
)DXOW)LQGLQJWKH,QWHUQDO%DWWHU\6%([WHUQDO%DWWHU\
7DEOH ,QWHUQDO6%([WHUQDO%DWWHU\)DXOW)LQGLQJ
Fault
)DXOW)LQGLQJWKH352),%86'3&,
7DEOH 352),%86'3&,)DXOW)LQGLQJ
Fault
Neither R(un) nor F(ault)
LEDs are ON
89
F(ault) LED is ON
Repair as necessary
)DXOW)LQGLQJWKH)281'$7,21)LHOGEXV&,
7DEOH )281'$7,21)LHOGEXV&,)DXOW)LQGLQJ
Fault
R(un) and F(ault) The CI852 board is in the process of being restarted or
LEDs are not ON configured. Allow time for this to finalize
If the condition persists, and all modules on the CEX-bus have
non-illuminated LEDs:
F(ault) LED is ON Use the Control Builder software to demand status information
from the CI852 module and proceed accordingly:
90
Incorrectly addressed
Be incorrectly terminated
The network
problem is
proving very
difficult to solve
91
92
)DXOW)LQGLQJWKH2QERDUG56&&KDQQHOV&,
7DEOH 2QERDUG56&&KDQQHOV&,)DXOW)LQGLQJ
Fault
OR
The connected device is
transmitting, but the Rx1/Rx2
LEDs are not flashing
The Tx/Rx signals are flashing
concurrently with the
transmission, but the messages
are not being received correctly
by the connected device.
93
94
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
6HFWLRQ$ *HQHUDO
A.1 General
Always comply with the following Safety Instructions when installing and
operating an AC 800M Controller system, in order to minimize the risks of injury to
personnel and/or damage to the equipment. Local statutory regulations, should they
be stricter, must always take precedence over the following Safety Instructions.
The Safety Instructions are classified as mandatory reading for all suitably qualified
personnel intending to operate the AC 800M Controller.
$ :DUQLQJVDQG,QIRUPDWLRQ6\PEROVLQWKH7H[W0DUJLQ
Observe the symbols for warnings and information located in other Chapters and
Appendices of this manual. The symbols are placed in the left margin, adjacent to
paragraphs requiring special attention. An explanation of the symbols can be found
by referring to Chapter 1, Introduction - Use of Warning, Caution, Information, and
Tip Symbols.
$ 3HUVRQQHODQG3URFHVV6DIHW\
7$.(&$5($7$//7,0(6 - This will prevent accidents from occurring and
help protect valuable equipment.
A control system is a general tool which can be used to perform control of various
processes. Responsibility for attaining and maintaining a satisfactory level of safety
must therefore rest with the personnel who engineer, operate and maintain the
equipment. It is important that they have an intimate knowledge of, all the control
functions available, the inherent safety risks that may be involved in the process,
and possess the imaginative ability to anticipate situations in which accidents may
occur.
95
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[$ 6DIHW\,QVWUXFWLRQV
96
The AC 800M Controller system should be shut down before such actions are
taken.
Never connect the mains power supply to the equipment during installation
work.
Take extreme care when the mains power supply is connected the system, as it
is capable of causing injury or death to a human being.
Ensure that all personnel operating or maintaining the installation knows the
exact location of both the equipment safety isolating switch and the mains
power supply isolating switch and exactly how to operate them.
When the sub-sections of the process are checked and a test run has been
performed, a responsible person must check out interlocking chains, and so
forth. All concerned personnel must be fully informed regarding test runs that
are to be performed.
Process technicians are to be present when testing and operating the process
objects.
Never operate any System Initialization push buttons if any uncertainty exists
about exactly what occurs, within the system, during initialization. $/:$<6
&+(&.),567
Remember at all times, that the control system can be controlled from a remote
engineering station, connected at another node, via Control Network.
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
6HFWLRQ$ 0DFKLQH6DIHW\
The level of safety can be improved considerably by taking steps to bring the
process to a safe state when power supplies, communication links or parts of the
control system fail. Such steps may, for instance, require the installation of valves or
relays which automatically return to a fail-safe position.
$ 0DFKLQH6DIHW\
Observe the following safety rules:
To avoid discharges of static electricity, ground both yourself and any tools
used before handling printed circuit boards and other sensitive pieces of the
equipment.
All electronic devices are sensitive to the ESD (electrostatic discharge) effect.
To avoid accidental damages while handling printed circuit boards, it is
recommended a wrist strap, earthed to the chassis, is worn. The wrist strap
must have a built-in protective resistor.
$ %HIRUHUHSODFLQJ,20RGXOHV
All procedures for replacing I/O modules can be found by referring to the relevant
I/O documentation.
Removing or replacing I/O modules with the system power connected can cause
injury to personnel and damage to equipment. It is therefore vital that total
disconnection of the power supply takes place, on the process side, before removal
or insertion of I/O modules takes place.
$ 0DLQWHQDQFH
It is recommended that a suitable supply of spare components in maintained in stock
to prevent avoidable periods of system downtime.
Ensure that back-up copies of the current application program are made, at regular
pre-determined intervals, to prevent avoidable periods of system downtime.
97
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[$ 6DIHW\,QVWUXFWLRQV
$ 2SHUDWLQJ(QYLURQPHQW
Before the AC 800M Controller system is brought on-line, investigate which
environmental conditions are applicable. The following points are very important:
The product must not be exposed to conditions which exceed those values
stated in the relevant technical specifications.
The product must not be used in an environment where it is exposed to strong
electrical interference. Electrical machines can produce interference which
exceed the permitted levels for the equipment, for example, during repair work.
All products must be handled with appropriate precautions with regard to
electrostatic damage.
Cables which may cause electrical interference, (for example, power supply cables),
must not be installed adjacent to bus cables carrying fast digital signals. Ensure that
a minimum distance of 10 cm (4) is provided between them when installed inside
cabinets.
Hazardous Electrical Supplies
Operational and maintenance procedures, during which personnel may come into
contact with high-voltage supplies, should only be carried out by those personnel
that are fully trained in the maintenance of electrical equipment within those
environments and are fully aware of all the risks involved.
98
$SSHQGL[% +DUGZDUH0RGXOHV
% 3030DQG733URFHVVRU0RGXOH
.H\)HDWXUHV
The data for PM856 are the same as for PM860 except for performance of
application program execution.
99
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
7HFKQLFDO'DWD
0HPRU\
3RZHU,QSXW&RQQHFWRU
5 W typical
10 W typical
&XUUHQW&RQVXPSWLRQ
180 mA typical
(300 mA max.)
100
5HGXQGDQW3RZHU6XSSO\6WDWXV,QSXWV
Inputs designated
SA, SB
30 V
15 V
8V
These inputs are status inputs and the threshold levels are limits for logic
0 or 1 on the inputs, they are not power fail limits.
3RZHU5HVHUYRLU
The CPU module has an internal power reservoir, lasting for 5 ms, which is
sufficient for the CPU to make a controlled power down.
&1 &1(WKHUQHW&RPPXQLFDWLRQ
Communication speed
10 Mbit/s
Signal levels
IEEE802.3, 10Base -T
Connector
RJ45
&206HULDO&RPPXQLFDWLRQ
Connector
RJ45
Modem support
Yes
101
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
&206HULDO&RPPXQLFDWLRQ
Connector
RJ45
Modem support
No
(OHFWULFDO0RGXOHEXV
I/O capacity - 1 x S800 I/O base cluster with up to 12 x S800 I/O modules.
Optical Modulebus
%DWWHU\%DFNXS
102
%DFNXSWLPH
Internal battery
External battery
Minimum 18 months
'DWDIRULQWHUQDOEDWWHU\
Battery type:
Battery size:
Lithium content:
0.3 g.
'DWDIRUH[WHUQDOEDWWHU\
See SB821
(OHFWURPDJQHWLF&RPSDWLELOLW\DQG(OHFWULFDO6DIHW\
3HUIRUPDQFH'DWD
The CPU modules PM856 and PM860 have the same internal design. They differ
only in performance when executing an application program.
Using the same application program in PM856 and PM860 the difference in
execution time can be expressed as:
Execution time in PM856 = 2 *Execution time in PM860
Example: If a certain application program has an execution time of PVLQ
30, the same application program will have an execution time ofPVLQ
30.
0HFKDQLFDO'DWD
3URWHFWLRQ5DWLQJ
103
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
0RGXOH6L]H
Width
119 mm (4.7)
Height
186 mm (7.3)
Depth
135 mm (5.3)
Width is measured along the DIN-rail, depth is measured from wall and height is
measured vertically inclusive lock mechanism.
0RGXOH:HLJKW
104
% &,DQG73352),%86'3,QWHUIDFH
.H\)HDWXUHV
F
R
Rx/Tx
RTS
CI851
Front View
CI851 / TP851
105
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
,QGLFDWRUV
106
Function
F(ault) /Red
R(un) /Green
Rx/Tx /Yellow
RTS /Yellow
)XQFWLRQDO%ORFN'LDJUDP
Communication
Extension Bus
Communication
Extension Bus
+24V
D.c./d.c.
converter
Bus interface
+5V
Communication module
AnyBus -M PROFIBUS-DP
Communication line
107
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
7HFKQLFDO6SHFLILFDWLRQ
Value
Type Designation
Type
DP Master Class I
Protocol
PROFIBUS-DP
Transmission rate
Galvanic isolation
Yes
Status indicators
Connector
DB9, female
Current consumption
3.6 W typical
Capacity
Max 32 loads
Protection Rating
Weight
Dimensions
W 59 x H 185 x D 127.5 mm
108
% &,DQG73)281'$7,21)LHOGEXV+,QWHUIDFH
.H\IHDWXUHV
F
R
Rx/Tx
Transformer isolated
No power consumed from the FF H1 bus
No power is supplied to the FF H1 bus
Simple DIN-rail mounting
Pre-set, two letter Alpha code lock installed in module base
to prevent incorrect mounting of non-compatible
components.
'HVFULSWLRQ
CI852
Front View
CI852 / TP852
109
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
Communication
Extension Bus
+24V
D.c./d.c.
converter
Bus interface
+5V
Communication module
with FOUNDATION
fieldbus interface
Communication line
110
Indicators
The CI852 FOUNDATION Fieldbus H1 interface has the following LED indicators.
7DEOH % &,)281'$7,21)LHOGEXV+/(',QGLFDWLRQV
Indication/Color
Function
F(ault) /Red
R(un) /Green
Rx/Tx /Yellow
Technical Data
Description
Type designation
Type
Number of channels
Protocols
Transmission rate
20 - 247
Galvanic isolation
By means of transformer
111
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
112
Description
Status indicators
Connector
Heat dissipation
3.4 W typical
Protection Rating
Weight
Dimension
F
R
Tx1
Rx1
Modem support
Tx2
Rx2
CI853
COM1
COM2
Front View
CI853 / TP853
113
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
)XQFWLRQDO%ORFN'LDJUDP
Communication
Extension Bus
Communication
Extension Bus
+24V
D.c./d.c.
converter
Bus interface
+5V
Microprocessor with
FPROM, SRAM,
Dual Port RWM and
two serial interfaces
Communication lines
114
Indicators
Function
F(ault) /Red
R(un) /Green
Tx1 /Yellow
Rx1 /Yellow
Tx2 /Yellow
Rx2 /Yellow
Technical Data
Description
Type
Number of channels
2 channels
Communication
CI853
Protocol
115
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
116
Description
Transmission rate
Galvanic isolation
Unisolated
Status indicators
Connector
Current consumption
(from CEX-bus 24 V d.c.)
Heat Dissipation
2.4 W typical
Protection Rating
Weight
Dimension
(package CI853K01with
CI853 and TP853)
The Power Supply Units, (PSU), are designed to meet all the applicable electrical safety data stated
by the EN 50178 harmonized European Standard Publication and the additional safety and function
data required by EN 61131-2 and UL 508.
The secondary output circuitry is accepted for SELV or PELV applications.
SELV according to EN 50178, EN 60950 and VDE 0100 Part 410.
For PELV applications; in accordance with EN 50178.
Protection Rating
117
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
110 mm (4.3)
50 mm (2.0)
103 mm (4.1)
97 mm (3.8)
SD821
L PE
230
44 mm
(1.7)
(4.9)
125 mm
L+ L+ L- LOK
Mains Voltage
Selection Switch
(115 / 230)
118
110 mm (4.3)
103 mm (4.1)
65 mm (2.6)
97 mm (3.8)
SD822
N
230
L PE
44 mm
(1.7)
125 mm
(4.9)
L+ L+ L- LOK
Mains Voltage
Selection Switch
(115 / 230)
119
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
110 mm (4.3)
120 mm (4.7)
103 mm (4.1)
125 mm
(4.9)
97 mm (3.8)
SD823
N
L PE
OK
L+ L+ L- L-
44 mm
(1.7)
115V
230V
ABB recommend the use these robust and reliable power supply units, (PSUs), for providing power
to the AC 800M Controller, when connected to an industrial mains network of installation category
III. All three PSUs can be used for both non-redundant and redundant applications, as well as load
sharing functions.
The three PSUs were designed as switch mode power converters, that is, converting a.c. mains
supply voltage to a regulated 24 V d.c. output. The three converters have rated output capacities
as follows:
SD823 = 24 Volts d.c. regulated @ 10 A
SD822 = 24 Volts d.c. regulated @ 5 A
SD821 = 24 Volts d.c. regulated @ 2.5 A
120
The mains input voltage is set to either 115 V or 230 V by means of a switch mounted on the front
face of the module. The factory default for this switch is in the 230 V position.
The output voltage of all three PSUs is, as stated, a regulated, low noise, 24 V d.c. A green LED,
mounted on the PSU front panel, indicates that the output circuit is providing the correct output
voltage level. The double connectors, provided on the 24 V d.c. output terminals, allow for the
connection of more than one equipment.
A surge current limiter within the PSU circuit, provides a soft-start feature. The controlled power-on
of a PSU therefore, will not trip fuses or earth-fault circuit breakers. In addition, the normal
disturbances that occur within an industrial main network will not cause any transient fault
conditions or trips to occur.
This means that the surge current limiter will effectively reduce the peak inrush current, caused by a
power disruption, to a level that the PSU can tolerate.
This soft-start, surge current limiter facility provides ease of design for the system power
distribution circuits.
X1
X2
Fuse
L+
LED
L+
LL-
PE
Chopper
121
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
Basic with protective conductor. The primary circuit is separated from all other live circuit by
reinforced insulation.
Rated insulation voltage Primary to Secondary 300 V a.c.
Dielectric test voltage 3000 V a.c. (EN 60950).
Internal primary main fuses are arranged to meet the requirements of electrical safety publications
for connection to the Phase - Neutral terminals of primary main network; TN network, 1 (one) fuse.
Recommended primary external fuse:
Micro Circuit Breaker (MCB) 10 Amperes, characteristic B.
7DEOH % 3RZHU6XSSO\8QLWV)XVHVDQG3URWHFWLYH'HYLFHV
Fuse
SD821
SD822
SD823
3.15 AT
4 AT
6.3 AT
10 A (1)
10 A (1)
10 A (1)
<5 A
<10 A
<20 A
3 A> I
I <5 A
6 A< I
I< 10 A
12 A< I
I<20 A
32 V typ
29 V typ
35 V typ
122
Technical Data
SD821
SD822
SD823
Converter Converter Converter
2.5 A
5A
10 A
60 W
120 W
240 W
24 V
24 V
24 V
160 VA
70 W
280VA
135 W
690 VA
265 W
115/230 V
a.c.
115/230 V
a.c.
115/230 V
a.c.
85 - 110%
85 - 110%
85 - 110%
Mains/input voltage,
max. a.c.= 45-65 Hz
138/275 V
a.c.
138/275 V
a.c.
138/275 V
a.c.
25 A
15 A
30 A
0.47 typ
0.5 typ
0.5 typ
Heat dissipation
8.6 W
13.3 W
26.7 W
Efficiency factor
87% typ
90% typ
90% typ
+-2%
+-2%
+-2%
25 mV
25 mV
30 mV
>20 ms
>20 ms
>20 ms
5A
10 A
20 A
123
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
SD821
Converter
SD822
Converter
SD823
Converter
65 mm (2.6)
120 mm (4.7)
124
Mounting spacing
W mm
10 mm (0.4)
15 mm (0.6)
15 mm (0.6)
Mounting spacing
H mm
25 mm (1.0)
25 mm (1.0)
25 mm (1.0)
Weight (lbs)
The SS822 Voting Unit has been specifically designed to be employed as a control unit within
a redundant power supply configuration. The output connections from two identical Power Supply
Units, (PSUs), are connected to the SS822 Voting Unit, see Chapter 3, Configuration, Figure 3-3
and Figure 3-4.
The SS822 Voting Unit separates the redundant PSUs, supervises the voltage supplied,
and generates supervision signals to be connected to the computer system. Green LEDs, mounted
on the front panel of the SS822, provide a visual indication that the correct output voltage is being
delivered. Simultaneously with the green LED illuminating, a voltage free contact closes the path to
the corresponding OK connector. SS822 Voting Unit trip levels, (2 off), are factory preset,
see Table B-11 SS822 Voting Unit - Supervision Data, for details.
110 mm (4.3)
103 mm (4.1)
50 mm (2.0)
97 mm (3.8)
SS822
A+B+L+L+L-
44 mm
(1.7)
(4.9)
125 mm
OK+ F OK+ F
A
B
125
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
SS822
0.7 V
30 V
0.7 V
SS822 Voter
20 A
24 V
500 W
2 x 24 V d.c.
35 V d.c
Heat dissipation
10 W
35 A (Overload)
Protection Rating
Dimensions, Width
50 mm (2.0)
126
SS822 Voter
Mounting spacing W mm
10 mm (0.4)
Mounting spacing H mm
25 mm (1.0)
Weight (lbs)
U
J
The TC562 Short Distance Modem module can be used both for point-to-point communication and
for communication over a distance between different equipment or modules, for example between a
computer and a printer or a robotic device. ABB recommend their use when the distance between
modules/equipment exceeds 15 m. For further details refer to documentation from the manufacturer,
Westermo.
Using a modem allows the distance between equipment to be as much as 18000 m, and can provide
a data transmission speedof up to 38400 bit/s, depending on the distance. The modems are
manufactured to be simply mounted onto a standard 35 mm DIN-rail.
The transfer between the modems take place along two twisted-pairs, one at full/half duplex and
the other at simplex. The transfer distance is totally dependent of the cables resistance and
capacitance. ABB recommend a cable area of minimum 0.2 mm2 with a capacitance between
40-80 pF/m within an industrial environment.
127
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
In a office environment, ABB recommend a cable area of minimum 0.14 mm2, and the capacitance
of between 40-100 pF/m. Use a shielded cable in a heavily industrial environment and a unshielded
cable in a office environment. A shielded cable is often given a higher capacitance and therefore will
provide a higher data transmission speed.
7HFKQLFDO'DWD
Type
Transfer
Power Supply
Power Consumption
3W
Dimension
Weight
128
Meter (yds)
bit/s
1000 (1094)
19200
2500 (2734)
9600
5000 (5468)
4800
8000 (8749)
2400
12000 (13123)
1200
18000 (19685)
600
% 6%([WHUQDO%DWWHU\$&00HPRU\%DFNXS
'HVFULSWLRQ
Type
Lithium battery,
low rate
Nominal Voltage
3.6 V
Capacity
16 Ah
Back-up Time
Min.18 Months
Amount of lithium
5.6 gram
(0.18 oz.)
SB821
6L]H
IEC R20 (33 x 60 mm)
ANSI Size D (1.3 x 2.4)
0HFKDQLFV
85.6 mm (3.4)
Depth
51 mm (2)
Height
136 mm (5.4)
Weight
!
X1
B- B+ SH
129
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
% ',15DLO76
The figure below shows the profile and dimensions in mm (inch.) of the DIN Rail TS 35/7.5.
The normal supplied length is 2 meters (6.6), (to standard DIN 46 277, EN 50 022).
7.5
(0.3)
7.5
(0.3)
35
(1.4)
6
27
(0.2)
(1.1)
15
(0.6)
10
(0.4)
% &DELQHWV
ABB recommend the following two models of Cabinets for the enclosure and mounting of
the AC 800M Controller plus associated modules and equipment:
130
50)ORRU0RXQWHG&DELQHW7HFKQLFDO'DWD
Cable Entry
Weight(2)
Doors
Double
(1) The dimensions includes door and rear plate. If lifting angles are used add 53 mm on the height.
(2) The weight does not include equipment to be installed within the cabinet.
131
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
2125
(84)
840 (33)
A-A
512 (21.2)
14 (4x) Mounting Holes
702 (27.8)
419 (15.7)
132
0RXQWLQJWKH50&DELQHWWRWKH)ORRU
Four holes, located in the base of the cabinet, are provided to allow attachment of the cabinet to
the floor. When attaching the cabinet to the floor, use size M13 fixings (nuts and bolts or expansion
bolts). Each bolting point features two D14 mm holes for the M13 fixtures. If drilling is necessary,
ensure that dust and other foreign matter does not enter any equipment that may be already mounted
in the cabinet. Please note the minimum distances, (as stated below), from cabinet to walls and
ceiling. If necessary, use washers as a packing between the floor and the cabinet base, to level the
cabinet prior to final installation. The use of large diameter plain washers is recommended to ensure
the maximum connection area between the cabinet base and the expansion bolts threads.
0LQLPXP'LVWDQFHVIRU0RXQWLQJ
These minimum distances are a free space, 150 mm (5.9) high between the top of the cabinet and
the ceiling or the underside of any beam, duct or similar structure over the cabinet. If you have
cables entering the cabinet from above, the space available should be at least 1000 mm (39.4) high
to provide an adequate working space. The distance between the rear and the sides of the cabinet and
an adjacent wall shall be no less than 40 mm (1.6). This will ensure adequate ventilation in and
around the cabinets.
5(:DOO0RXQWHG&DELQHW7HFKQLFDO'DWD
Cable Entry
Weight(2) Cabinet
46 kg (101 lb)
Doors
Double
(1) The dimensions includes door and rear plate. If lifting angles are used add 53 mm (2.1) on the
height.
(2) The weight does not include equipment to be installed within the cabinet.
133
25 mm (1)
1000 mm (39.3)
1020 mm (40.1)
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
773 mm (30.4)
800 mm (31.5)
330 mm
(13)
719 mm (28.3)
A-A
FL 21
FL 21
255 mm
(10.4)
230 mm
(9.1)
300 mm
(11.8)
637 mm (25.1)
134
(0.4)
D=17mm
(0.67)
998mm (39.3)
D=10mm
D=10mm (0.4)
773mm (30.4)
135
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
0RXQWLQJWKH5(&DELQHWRQD:DOO9HUWLFDO6XUIDFH
Four D10 holes, one located at each rear corner of the RE820 cabinet, are provided to allow
attachment of the cabinet to a wall or vertical surface. Note the minimum distances for mounting,
(as stated below), from the cabinet to adjacent walls and ceiling, prior to measuring and marking
the intended drilling points.
Using a spirit level, ensure that the cabinet will be level on the wall, prior to drilling any mounting
holes. When attaching the cabinet to the wall, use size M10 fixings (nuts and bolts or expansion
bolts). When drilling, take steps to ensure that dust and other foreign matter does not enter any
equipment that may be already mounted in the cabinet.
If necessary, add washers as a packing between the wall stand-off mountings and the cabinet
backplate, to level the cabinet prior to final installation. Use wall stand-off mountings, as required.
The use of large diameter plain washers is recommended to ensure the maximum connection area
between the cabinet and the expansion bolts threads.
0LQLPXP'LVWDQFHVIRU0RXQWLQJ
These minimum distances are a free space, 150 mm (5.9) high between the top of the cabinet and
the ceiling or the underside of any beam, duct or similar structure over the cabinet. If cables entering
the cabinet from above, the space available should be at least 1000 mm (39.4) high to provide
an adequate working space.
The distance between the rear and the sides of the cabinet to any adjacent wall shall be no less than
40 mm (1.6). This will ensure adequate ventilation in and around the cabinets. Use wall stand-off
mountings, as required.
136
% 0LVFHOODQHRXV(TXLSPHQW
% 7%7HUPLQDWRUIRU&(;EXV0DOH
TB850 Terminator for CEX-bus.
Terminator
TB850
F
R
Rx/Tx
RTS
F
R
Rx/Tx
RTS
PM860
CPU module
CI851
CI851
137
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
F
R
Rx/Tx
F
R
Rx/Tx
RTS
PM860
CPU module
CI853
CI852
CI851
COM1 COM2
TK850 Cable
F
R
Tx1
Rx1
Tx2
Rx2
F
R
Tx1
Rx1
Tx2
Rx2
F
R
Rx/Tx
CI853
CI853
CI852
COM1 COM2
COM1 COM2
Terminator
TB851
138
% &(;EXV([WHQVLRQ&DEOH7\SH7.
An extension cable, (length 0.7 meter (2.3)), complete with connector (type DB25P- metal
housing). Used to provide connectivity to Communication Interface modules between adjacent
DIN-rails.
% 7RRO&DEOH7\SH7.
7HFKQLFDO'DWD
&RQQHFWRUV
3.0 m (9.84)
AC 800M
RJ45 plug
RTS 1
DTR 2
TD 3
0V 4
0V 5
RD 6
DCD 7
CTS 8
Shield
8 CTS
6 DSR
2 RD
1 DCD
50V
3 TD
4 DTR
7 RTS
Shield
PC
Female 9-pin,
D-type connector
139
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[% +DUGZDUH0RGXOHV
% $O3URILOH6XSSRUW)RU',15DLO
All modules comprising the AC 800M controller are mounted on DIN rails
(type: TS 35/7.5). However, the DIN rail itself is not rigid enough to support the
modules on its own. For that reason a support, such as an Al-profile, which has been
specifically designed for supporting DIN rails is recommended (see Figure B-18).
Refer to price list for additional information.
The key features of the Al-profile are:
No drilling required, profile incorporates pre-formed channels suitable for selftapping screws.
Pre-formed
channels
Al-profile
DIN rail
Cable Duct
140
$SSHQGL[& 3RZHU&RQVXPSWLRQ
& *HQHUDO
At 40 C (104 F) ambient, it is considered unnecessary to calculate the heat
dissipation requirements for a standard AC 800M Controller with
S800 I/O configuration, mounted within ABB floor or wall mounted cabinets.
For a standard AC 800M Controller configuration, housed within a floor or wall
mounted cabinet, the recommended fuse rating for the external mains supply
is as follows:
7DEOH & $&00RXQWHGLQ$%%&DELQHW)XVH5HTXLUHPHQWV
)XVH5DWLQJ
10 A
)XVH7\SH
Slow to Rupture
Should the configuration be other than that stated, detailed instructions for
calculating current consumptions can be found in the following text.
The tables below present the current consumption and power dissipation of all
relevant hardware modules included in AC 800M Controller
Use this information:
The values given in the tables are typical and adapted to these kinds of applications.
It is assumed that 70 percent of the channels on a module are active simultaneously.
141
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[& 3RZHU&RQVXPSWLRQ
& &XUUHQW&RQVXPSWLRQDQG3RZHU'LVVLSDWLRQ
&XUUHQW&RQVXPSWLRQDQG3RZHU'LVVLSDWLRQ
Refer to Table C-2 for typical current consumption and power dissipation data for
AC 800M modules.
7DEOH & 7\SLFDO&XUUHQW&RQVXPSWLRQDQG3RZHU'LVVLSDWLRQ'DWDIRU
$&00RGXOHV
&XUUHQWDW9
Module
7\SLFDO
3RZHU'LVVLSDWLRQ
0D[
7\SLFDO
5HPDUNV
0D[
PM860
180 mA
300 mA
5.0 W
8.0 W
CI851
150 mA
200 mA
3.6 W
5.0 W
CI852
140 mA
200 mA
3.4 W
5.0 W
CI853
100 mA
150 mA
2.4 W
3.6 W
(1)
(1) These figures are for the PM860 alone. For current consumption data relating to the CEX-bus and
the Modulebus modules, see Table C-3 below.
The PM860 supplies the following currents to modules on the CEX-bus and
the Modulebus.
7DEOH & 30&XUUHQW6XSSO\WR&(;EXVDQG0RGXOHEXV
Bus
+5V
(1)
Modulebus
max. 1.5 A
CEX-bus
Not Applicable
+24V
max. 1.0 A
max. 2.4 A
142
1.
2.
3.
4.
To calculate the requirement for a specific power supply unit, add all the 24 V
current consumptions, as follows:
,tot = ,m1 + ,m2 + .... + ,modules Table C2 + ,CI830 + ,TB820
143
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[& 3RZHU&RQVXPSWLRQ
144
$SSHQGL[' 5HFRPPHQGHG&RPSRQHQWV
' 5HFRPPHQGHG&RPSRQHQWV
All of the recommended components, listed below, were successfully used during
ABBs exhaustive testing phase, prior to the launch of the AC 800M Controller.
7DEOH ' 5HFRPPHQGHG&RPSRQHQWV352),%86'3
Component
PROFIBUS-DP
Description
FOUNDATION
Fieldbus
Description
145
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[' 5HFRPPHQGHG&RPSRQHQWV
Description
HUBS
(For NonIndustrial
Environments)
(Industrial
Environments)
SWITCHES
(Industrial
Environments
CABLES
146
DIN rail
Accessories
Description
Phoenix:
TS 35/7.5
147
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[' 5HFRPPHQGHG&RPSRQHQWV
Description
Process Cables
Mains
RS232-C
RKFK 3x1.5mm2
Belden
Unitronic
FOUNDATION Fieldbus
CY 3 x 0.25mm2
CY 7x 0.25mm2
Unitronic
Belden
PROFIBUS-DP
Unitronic
Unitronic-Bus L2/F.I.P
Belden
148
Belden 3079A
$SSHQGL[( 'LUHFWLYH&RQVLGHUDWLRQV
Relevant products comply with EMC Directive 89/336/EEC and Low-Voltage
Directive 73/23/EEC. The products are provided with a CE marking.
The units are IP20 semi-protected equipment and must be mounted in non-public
localities.
1RWHIf you use other power supplies except SD821 SD822 or SD823 to provide
24 V d.c. they must also be CE marked.
To fulfill the CE low-voltage directive, the power supply shall provide a secondary
safety extra low voltage (SELV) or a protected extra low voltage (PELV).
SD821, SD822 and SD823 power supply modules fulfil these requirements.
149
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[( 'LUHFWLYH&RQVLGHUDWLRQV
150
$SSHQGL[) (QYLURQPHQWDO'DWD
) (QYLURQPHQWDO'DWDIRU$XWRPDWLRQ3URGXFWVZLWKLQ$%%
The immunity of products from ABB Automation Products to environmental factors
during operation, transportation and storage is summarized in this section.
,QGXVWULDOHQYLURQPHQWhas a power network supplied from a high or medium
voltage transformer dedicated for the supply of an installation feeding
manufacturing or similar plants. The ,QGXVWULDOHQYLURQPHQW is characterized
by the existence of industrial apparatus, heavy frequently switched inductive or
capacitive loads and the associated magnetic fields are high.
Control products incl. I/O-systems (e.g. Advant, Freelance, Harmony) are normally
intended for ,QGXVWULDOHQYLURQPHQW.
The products, manufactured by ABB or others, are normally type tested or
evaluated to ensure compliance with the environmental standards specified below.
The environmental specifications applicable to peripheral equipment, for example
printers, may differ. Please refer to the data sheets of the products concerned.
The degree to which the units withstand environmental influence depends on their
components and their design. The system enclosures, the types of cable and how
these are routed determine the environmental specification of the complete system.
151
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[) (QYLURQPHQWDO'DWD
Climatic Conditions
Operative
Range
Compliance
with Standard
-25 to +70 C
&DELQHWV (1):
+5 to +40C
8QLWV (2)
+5 to +55C
+10 to +40 C (3)
Temp. change
3 C/min.
EN 61131-2
Humidity
RH=5-95%
RH=20-80% (3)
noncondensation
RH=5-95%
RH=20-80% (3)
max 29g/m3
noncondensation
EN 61131-2
Altitude
3000 m
2000 m
EN 61131-2
Temperature
Pollution degree
Corrosion
152
Transportation
and Storage
Degree 2
EN 61131-2
IEC 60664
Vibration
Transportation
and Storage
Operative
Range
Compliance
with Standard
EN 61131-2
Mechanical Conditions
<55dB (A)
2
(3)
DAT drives; 5 g,
3ms
Fall in package
<10kg: 1m
EN 61131-2
(3)
DAT drives; 5 g,
3ms
EN 61131-2
10-40kg: 0.5m
>40kg: 0.25m
>100kg: 0.025m
(1)
(2)
(3)
(4)
153
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[) (QYLURQPHQWDO'DWD
F.1.2 CE Compliance
All products comply with EMC Directive 89/336/EEC and Low Voltage
Directive 73/23/EEC (relevant products fulfil also the Teleterminal Directive).
The products are provided with a CE marking. Some products require enclosure,
as specified in User Guides, to meet the EMC Directives.
Compliance to the Directives is verified by the practice of the following standards
at the minimum:
154
EN 50178 for all new products, e.g. S100 and S800 family, or good electrical
safety practice based on EN 60950, EN 61010, EN 50178, EN60439,
IEC60255 depending on the product.
Environment Factor
Emission
Compliance with
Standard
Class A
EN 55011
10V/m
EN 61000-4-3
-Radiated
-Conducted
Electromagnetic Compatibility Conditions
Immunity
-Radiated RF field
Immunity
ENV 50 204
10V
EN 61000-4-3
Immunity
4 kV contact discharge
EN 61000-4-2
-ESD (Electrical
Discharge)
8 kV air discharge
Immunity
Immunity
IEC 60255-22-1
Immunity
30 A/m, cont.
EN 61000-4-8
-Power frequency
magnetic field
Immunity
2 kV, common
-Surge
1 kV, differential
-Conducted RF field
EN 61000-4-4
-Damped oscillatory
wave
EN 61000-4-5
155
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[) (QYLURQPHQWDO'DWD
Environment Factor
156
Industrial
Environment
Compliance with
Standard
47 - 63 Hz, 5%
IEC 60255-6
Main voltage
interruption, a.c.
Max 10ms
EN 61000-4-11
Overvoltage
Category
Class III
Permanently
connected equipment
Overvoltage
Category
Class II
-Non-permanently
connected equipment
157
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
$SSHQGL[) (QYLURQPHQWDO'DWD
Cables extend beyond the area covered by the earth line network
158
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
,QGH[
,1'(;
$
AC 800M 95
Alpha Code Lock 34
%
Battery
External
How to Change 84
Internal
How to Change 80
&
Cabinet 20, 29, 130
CEX-bus Extension Cable
TK850 46
CI851
Communication Interface 4
CI852
Communication Interface 4
CI853
Communication Interface 4
CN1 Port
RJ45 Port for Ethernet 38
CN2 Port
RJ45 Port for Ethernet 38
Cold Restart 76
COM3
RS232C Port 39
COM4
RS232C Port 40
Connection To
Control Network 63
Foundation Fieldbus H1 43
Profibus-DP 41
Connectors 75
Control Builder 20, 61
Control Network
Connection To 63
Controller Reset 76
CPU 20
Current Consumption 142
'
DIN-rail 20
(
Electro-Magnetic Compatibility 25
External Battery
How to Change 84
)
Foundation Fieldbus H1
Connection To 43
Fuse Requirement 141
Fuses
How to Change 86
Fusing of External Mains Supply Cable 27
*
Grounding 97
+
How to Change
External Battery 84
Fuses 86
Internal Battery 80
,
I/O units 97
I/O-systems 151
Internal Battery
How to Change 80
159
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
,QGH[
/
LED Indicators 73
Locking Device 30
RS232C Port
COM3 39
COM4 40
3
Planning
Cable routing 25
Cooling 24
Grounding 25
Laying of Field Cables 25
Lightning Protection 26
Temperature 24
To remember 24
Type of Field Cables 26
Vibration 24
PM856 1
PM860
CPU Unit 4, 7
Power supply 96, 98
Precautions 98
Processor Module (PM860/TP830) 7
Product overview 4
Profibus-DP 66
Connection To 41
Protective Earth 27
Protective resistor 97
Push Buttons 74
Safety Switch 27
SB821
Battery Back-up Module 4
External Battery Module 83
SD821
Power Supply Module 4
SD822
Power Supply Module 4
SD823
Power Supply Module 4
Signal noise 98
SS822 52, 125
Switches 74
7
TB850
Terminator for CEX-bus 50
TB851
Terminator for CEX-bus 51
Terminator for CEX-bus
TB850 50
TB851 51
TK850
CEX-bus Extension Cable 46
TP830
Baseplate 4, 7
TP851 41, 105
TP852 43, 109
TP853 45, 113
5
Removing Modules
How To 32
RJ45 38
160
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
,QGH[
Type Designation
CI851 4
CI852 4
CI853 4
PM856 1
PM860 4, 7
SB821 4, 83
SD821 4
SD822 4
SD823 4
TP830 4, 7
:
Warm Start 76
161
$&0&RQWUROOHU+DUGZDUH8VHUV*XLGH
,QGH[
162
! "#$
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
#
))
( ! ##
&*
#
)
,# -(
! "
( ! ##
&*
( ! ##
&*
%
)
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
%
-,!$ *
**/ #!# #
%
5
'
* )
-*#
2 -,!$ * 6
2; -,!$ * 65
; # 3
0$/ ( #
; # 3
; (
; # 3
; (2 <
; # 3
; (2 /
; / -,!$ *
5
'
#
#
. *
. *
. *
. *
. *
( #
( #
( #
. *
#
#
#
#
#
#
#
#
#
-, *
$
. *
0$!# #-
=!-
2
)2 ))
)2; # 3(
! # #
; # 3
0$
*= *#
&
'
(" (
')*
++
&(
1 2
1 2
1 2
+
3 -)) 4 ( # #- "
** 3 ($
- #
3 (
" $
3 (
"
-,!$ # 3 *
6 7 !
89 : *
-,!$ # 3 *
65 7; / 89 : *
5
%
1 2
1 2
.( +/ $
(
2 '2& *
& ' #
& ' #
! (
-* >
#
; (
; (
1 2
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
%
+ #
#$&
.( +/
S800 I/O Digital Input
DI800_1
DI_W1auxSwCloseQ51
DI_AuxSwCloseQ71
Move_16_Bool
In1
Out1
In2
Out2
In3
Out3
In4
Out4
In5
Out5
In6
Out6
In7
Out7
In8
Out8
In9
Out9
In10
Out10
In11
Out11
In12
Out12
In13
Out13
In14
Out14
In15
Out15
In16
Out16
WCU1auxSwClose3
AC800auxSwClose3
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
DeviceFault3
DeviceAlarm3
c.DeviceWarning
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
5
+ #
#$&
&
RS2and
Set Q1
R1
R2
gReset
gAuxSupplyFlt
Form_CommonDiagWord
0
0
2DeviceAlarm
2DeviceFault
gMT1almAct
gMT1fltAct
0
0
0
0
ConvB16Dint
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
gCommonDiagWord
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
'
+ #
#$&
Emergency Stop
SetEstop
RS2and
Set Q1
R1
R2
gEstop
gReset
WatchDogHw
PulseGenerator
Enable
Out
PulseTime ParError
PeriodTime
c.Time_250ms
c.Time_500ms
WatchDogHwUpdate
Form_WatchdogWord
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
WatchDogWord_IN
ConvB16Dint
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
WatchDogWord
:=
WatchDogWord_OUT
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
%
5
'
%
5
'
$
2)
2)
2)
2)
2)
2)
2)
2)
)
)
)
)
)
)
)
)
)
.- 3 *)
.- 3 *#
*1
,
*1
* ) *)
* ) *#
$ ( ) *)
$ ( ) *#
.- 3 *4 *)
.- 3 *4 *#
( ; (
*1
,
*1
* ) *)
* ) *#
$ ( ) *)
$ ( ) *#
%
5
. *
. *
. *
. *
. *
. *
. *
. *
. *
. *
( #
. *
. *
. *
. *
. *
. *
2%
)2)
( ; (
) " .- 3 *#
) "
* ) *#
* #
&
'
(" (
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
.( +/ $
2 '2& *
& ' #
! (
! (
2 2
*2 " .-
')*
1
1
1
1
1
1
1
1
++
2
2
2
2
2
2
2
2
&(
%
%
%'
%5
%%
%
%
%
"
"
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
! .( +/
S800 I/O Digital Input
DI800_3
DI_mTR1buchAlm
DI_mTR1buchFlt
DI_mTR1oilTempAlm
DI_mTR1oilTempFlt
DI_mTR1oilLevMin
DI_mTR1oilLevMax
DI_mTR1windTempAlm
DI_mTR1windTempFlt
0
0
0
0
0
0
0
0
Move_16_Bool
In1
Out1
In2
Out2
In3
Out3
In4
Out4
In5
Out5
In6
Out6
In7
Out7
In8
Out8
In9
Out9
In10
Out10
In11
Out11
In12
Out12
In13
Out13
In14
Out14
In15
Out15
In16
Out16
mTR1bucholzAlm2
mTR1bucholzFlt2
mTR1oilTempAlm2
mTR1oilTempFlt2
mTR1oilLevMin2
mTR1oilLevMax2
mTR1windTempAlm2
mTR1windTempFlt2
"
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+
+ #
#$&
Main Transformer 1
1mTR1windTempAlm
1mTR1oilTempAlm
>=1
mTrafo1OilTempFlt
RS2and
Set Q1
R1
R2
1mTR1oilTempFlt
gReset
>=1
1mTR1windTempFlt
mTrafo1buchFlt
RS2and
Set Q1
R1
R2
1mTR1bucholzFlt
Form_mTR1diagWord
gMCB1closed
1mTR1bucholzAlm
0
1mTR1oilLevMin
1mTR1oilLevMax
0
0
0
0
ConvB16Dint
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
mTR1diagWord3
>=1
gMT1fltAct4
>=1
gMT1almAct
"
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
Move_TR_Panel_Profibus
In1
Out1
In2
Out2
In3
Out3
In4
Out4
In5
Out5
In6
Out6
In7
Out7
In8
Out8
In9
Out9
In10
Out10
In11
Out11
In12
Out12
In13
Out13
gMT1diagWord
&
"
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
Fault Class
2gMT1fltAct
>=1
gFC1_TR
'
"
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
$
;
;
(= ; $ # 3
( #
. *
. *
&
'
(" (
')*
++
&(
#
#
#
+
-, *
# *; (
-, *
# *; ( 9$ # 3
(
5
'
%
5
'
;
2 #! ( "
2 #; /#)
2 #; @#)
2 #; ;#)
* )!-)
* ); (
* ); (
** -, !# #
2 #
# #
2 #
#! (
2 #
# A!;
!; 2
3
!; 2
( #
(
.
*
*
*
*
*
#
#
*
*
*
*
#
*
#
#
#
#
#
#
#
#
#
#
#
#
#
#
.
(
(
.
1
1
1
1
2
2
2
2
-, * =
( "
# *; (
" ) 1 ? .
'
'
'%
1 2
1 2
1 2
-, *
-, *
= !# #- ; (
= !# #- ; ( 9 (*= ( 3
-, *
= !# #- ; ( 9 (*= ( *
#
*
#
+
!; # # 3 . #
!;
!;
!;
!;
!;
!;
!;
. *
( #
. *
. *
. *
. *
. *
#
#
#
#
#
#
#
+
5
5
5
-,
-,!- *= *#
-,!$ *
0 * 1 #
((
;
((
;
((
!;
((
!;
((
& # #- * (
((
;
((
# #
((
# A- =
((
#< ) A
((
#! ( #
((
#! (! *
((
# A #
((
#@ *#
((
!;
(( <
2 -,!$ * 6
2
""
2
2 )
=!#
2
"2
2 -,!$ * 6
.
.
.
.
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
.
.
.
.
.
.
.
*
*
*
*
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
*
*
*
*
*
*
*
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
5%
5
55
5'
5
5
5+
'
'
'
'%
2 # !# #
2 $ !- *=
2
#
2 )
= ""
2
2>
* *)
2
(=
2
(= "
2
(= 2
(
2; ( ) *)
.
.
.
.
.
.
.
.
.
.
.
*
*
*
*
*
*
*
*
*
*
*
#
#
#
#
#
#
#
#
#
#
#
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
5
'
+
%
%
%
%%
%
%5
%'
%
%
%+
%
5
'
2
2
-, ! A
3
$ # 3
-, *
3.#
-, *
-, *
-, *
-, *
-, *
-, *
-, *
.#
= !# #- ; ( 9 # #
= !#
= !#
= !#
= !#
= !#
= !#
= !#
#######-
;
;
;
;
;
;
;
(
(
(
(
(
(
(
+#
'#, *+!$
9 "*# *
9 "*# *
9 -,
A
9 3
9$ # 3(
* #
%
5
'
+
5
#
!
'
*#
( "
-,@ *#
,#
* #
,#
*
-*#9 :
A- #
A- #
5
#
- 9 :
#
9 : -,!$ # 3 *
6 7 #
: *
%
'
$ !-
-,89
*=9 :
5
5
%
'
%&
"#
'
94
'
"
%
$ '(,
%
+ #
#$&
%
'
'5
''
'
'
'+
$
2; ( )
""
)
#
#
*#
.
.
.
.
.
.
.
.
.
.
.
.
(
(
(
.
.
.
.
.
.
.
.
.
.
.
(
(
(
.
(
=!#
""
">
*#
>
*(
>
>
*
-*#; (
-*#; (%
-*#; (
%
5
'
+
(
(
3
3
*
*
#
%
5
'
+
+
+
+
+%
+
+5
+'
+
+
++
>
>
* * )
*
& # #- * (
;
; (
# -,!$ *
# #
# #
#
# A- =
# A- =04
#1 ( . #
#< ) A
&
*
*
*
*
*
*
*
*
*
*
*
*
#
#
#
*
*
*
*
*
*
*
*
*
*
*
#
#
#
*
#
*
. *
( #
*
*
( #
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
'
(" (
')*
1 2
++
&(
+
!#
(
(
+
%
%
%
. *
. *
( #
*
*
($ (
( #
( #
*
( #
*
($ (
. *
. *
( #
( #
*
*
($ (
($ (
. *
. *
. *
. *
*
( #
. *
. *
( #
. *
. *
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
%%
!; !#
%
%5
%'
%
!;) (-* #
!;
3.# (
!;
!#
!; (=
.
.
.
.
*
*
*
*
#
#
#
#
%
5
'
%
5
'
%
5
'
# #
= #
-*# *
-*# *
-*# *
93 3
#=
-*# *
9* $
#=
& # ## *; (
#
#
#
#
#
#
7 #
#< ) A04
# !# #
# !#
#! ( #
#! ( # )
#! ( "
#! ( "2!
#! (! *
# A #
# A#
#; /# )
#; /#)
#; /#) 2!
#; /#) *)
#; /#) *#
#; @# )
#; ;# )
#; @#)
#; ;#)
#; @#) 2!
#; ;#) 2!
#; @#) *)
#; ;#) *)
#; @#) *#
#; ;#) *#
#@ *#
#@ *#
#
#; ) *)
#; ) *#
!;
!; * )
!; ""
#9
#9
#- * 7 #
8
#- * 7 *8
" A- = 04 7 #
8
" A- = 04 7 *8
* ( 7B8
) * " A- = 04
8
) * " A- = 04 7
#- *
#
#
(
# A-
*
#- *
*#
#- *
!# #- ; (
!# #- ; (9 * )
!# #- ; (9 )
= ""
7 ""
# 8
!# #- ; (9 )
= #
7 "" % # 8
!# #- ; (9 ) (-* #
!# #- ; (9
!# #- ; (9 (=
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
*8
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
%
%
%+
$
!; (= "
!; (= !; ) #
!;#
(
*=
$ !#
-
- #
. *
. *
. *
. *
( #
. *
. *
-
'
- #!
<
%
+
5
! ( # .
!# # -*
!# #- ; (
2 )
&
#
#
#
#
#
#
#
*( #
2 )
*( #
*
. *
( #
#
#
#
'
(" (
')*
++
&(
!#
!#
!#
!#
(
####"
;
;
;
;
,#
* " -*#
( = 93
7 -# -#8
( = 93
7 -#8
# #3 .= *-
()
(9 (= "
(9 (= (9 ) #
(9 #
(
#
-
#)
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
" #3 (
'
"
%
$ '(,
5
+ #
#$&
%
5
'
%
5
'
%
5
'
+
%
%
%
%%
%
%5
%'
%
%
%+
%
5
'
+
5
2
2
2
-, * =!- *= *#
-,
(= -, ! A)
* -* # 2 )
3
"" )
3
)
3
* 1
) 2
& # ## *2 -, *
2
2
2
2
( # #
( # #
( # #
( # # %
( # #
( # # %
""! #
"" )
# ! #
#
)
#
#
)
)2 ;
)2 ;
)2 * ); (
)2 * ); (
)2 -*#; (
)2 -*#; (%
)2 -*#; (
)2
;
)2
; (
)2!# #- ; (
> #2 !;
> #2 !;
> #2 !;
# ; (
/
# ; (
@
# ; (
;
2 ""
* #
-* >
# 2
!# # -*
!# # )
2
# *
+
2 2
2 2
2 2
(
!
!
.( +/ $
* 2 ** 2 **
"
-
1 2
0 -
* -* #
( =
(3 -
"
! (
) 2( #
)1
2 '2& *
2 '2& *
2 2& *
2 2& *
2
!
2
!
2
!
2
!
2
!
2
!
! (
"
! (
"
!
3
#
#
#
& ' #
& ' #
& ' #
& ' #
& ' #
& ' #
& ' #
& ' #
!# #(
& ' #
&# ' &
&# ' &
&# ' &
2 2
2 2
2 2
!
2
-* >
2
#
*2
" .-
"
# *2 2
()
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
'
+ #
#$&
.( +/
Start Pulse
StartPulse
1
0
StartTimer
Trigger
Request Out
Periodic
Period
TOf
In Q
PT ET
StartPulse2
c.Time_10s
+ ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
Move_16_Bool
In1
Out1
In2
Out2
In3
Out3
In4
Out4
In5
Out5
In6
Out6
In7
Out7
In8
Out8
In9
Out9
In10
Out10
In11
Out11
In12
Out12
In13
Out13
In14
Out14
In15
Out15
In16
Out16
MotAuxSwClose10 23
AuxSwClose10 23
Fan1fuse22
Fan1run22
PowerSupply10 23
DI800_2
DI_DriveOn
DI_DriveOff
DI_MotorStart
DI_Reset
DI_EmergencyStop
0
0
0
0
0
0
0
0
0
0
0
Move_16_Bool
In1
Out1
In2
Out2
In3
Out3
In4
Out4
In5
Out5
In6
Out6
In7
Out7
In8
Out8
In9
Out9
In10
Out10
In11
Out11
In12
Out12
In13
Out13
In14
Out14
In15
Out15
In16
Out16
DriveOn17
DriveOff17
MotorStart17
Reset17
EmergencyStop17
, ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
19MSWreadyOn
19MSWreadyRef
19MSWreadyRun
11GeneralTrip
19MSWeOff
7MotWTmpAlm
7MotWTmpFlt
11GeneralAlarm
DO_ReadyOn
DO_ReadyRef
DO_ReadyRun
DO_Tripped
DO_EmergencyOff
DO_WindTmpAlm
DO_WindTmpFlt
DO_GeneralAlm
DO800_2
22FanGrp1on
0
0
0
0
0
0
0
Move_8_Bool
In1
Out1
In2
Out2
In3
Out3
In4
Out4
In5
Out5
In6
Out6
In7
Out7
In8
Out8
DO_FanOn
()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+
+ #
#$&
Move_8_RealIO_values
In1
Out1V
In2
Out2V
In3
Out3V
In4
Out4V
In5
Out5V
In6
Out6V
In7
Out7V
In8
Out8V
Out1S
Out2S
Out3S
Out4S
Out5S
Out6S
Out7S
Out8S
MotW1Utmp7
MotW1Vtmp7
MotW1Wtmp7
MotW1Utmp_S9
MotW1Vtmp_S9
MotW1Wtmp_S9
AI800_2
AI_MotSpdRef
Move_8_RealIO_values
In1
Out1V
In2
Out2V
In3
Out3V
In4
Out4V
In5
Out5V
In6
Out6V
In7
Out7V
In8
Out8V
Out1S
Out2S
Out3S
Out4S
Out5S
Out6S
Out7S
Out8S
MotSpdRef21
MotSpdRef_S
()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
Move_8_Real
In1
Out1
In2
Out2
In3
Out3
In4
Out4
In5
Out5
In6
Out6
In7
Out7
In8
Out8
AO_MotorActSpeed
AO_MotorActTorque
AO_MotorActCurrent
()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
DDCS Communication
MCW=60.01
ACW1=60.02
ACW2=60.03
Drivedataset100
Move_DDCS
In1 Out1
In2 Out2
In3 Out3
17MCW
18ACW1
18ACW2
ddcsMCW
ddcsACW1
ddcsACW2
NREF=60.04
Drivedataset102
Move_DDCS
In1 Out1
In2 Out2
In3 Out3
21NREF
ddcsNREF
ddcsMSW=61.01
ddcsASW1=61.02
ddcsASW2=61.03
Drivedataset101
Move_DDCS
In1 Out1
In2 Out2
In3 Out3
ddcsMSW
ddcsASW1
ddcsASW2
MSW19
ASW120
ASW220
ddcsMotSpdAct=61.04(1.08)
ddcsMotTorqAct=61.05(1.12)
ddcsMotCurrAct=61.06(1.11)
Drivedataset103
Move_DDCS
In1 Out1
In2 Out2
In3 Out3
ddcsMotSpdAct
ddcsMotTorqAct
ddcsMotCurrAct
MotSpdAct21
MotTorqAct21
MotCurrAct21
ddcsMotSpeedScaling=63.01(50.01)
ddcsMotVoltage=63.02(1.18)
ddcsMotFrequency=63.03(2.20)
Drivedataset111
ddcsMotSpeedScaling
ddcsMotVoltage
ddcsMotFrequency
Move_DDCS
In1 Out1
In2 Out2
In3 Out3
MotSpeedScaling21
MotVoltageAct21
MotFrequency21
ddcsMCBstatusClosed=63.04(5.10)
ddcsMotNomFreq=63.05(6.17)
Drivedataset113
Move_DDCS
In1 Out1
In2 Out2
In3 Out3
ddcsMCBstatusClosed
ddcsMotNomFreq
MCBstatusClosed21
MotNomFreq21
()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
4MotW1Utmp
c.AlmMotWind1Utemp
c.FltMotWind1Utemp
gReset
MotW1Utemp26
MotW1UtmpAlm8
MotW1UtmpFlt10 12
MotorWinding1V
PT100_0_200
TempIn
TempOut
AlarmLim TempAlarm
FaultLim TempFault
Reset
4MotW1Vtmp
C.AlmMotWind1Vtemp
C.FltMotWind1Vtemp
MotW1Vtemp26
MotW1VtmpAlm8
MotW1VtmpFlt10 12
MotorWinding1W
PT100_0_200
TempIn
TempOut
AlarmLim TempAlarm
FaultLim TempFault
Reset
4MotW1Wtmp
C.AlmMotWind1Wtemp
C.FltMotWind1Wtemp
MotW1Wtemp26
MotW1WtmpAlm8
MotW1WtmpFlt10 12
>=1
MotWTmpAlm3 11 22
>=1
MotWTmpFlt3 11
# ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
%
+ #
#$&
Alarm Words
Form_AlarmWord1
0
0
0
0
0
0
0
7MotW1UtmpAlm
7MotW1VtmpAlm
7MotW1WtmpAlm
0
0
0
0
0
0
ConvB16Dint
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
AlarmWord126
Form_AlarmWord2
0
0
0
0
0
0
0
0
0
0
0
0
0
0
19MSWalarm
0
ConvB16Dint
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
AlarmWord226
+
DINT_TO_BOOL
AlarmSum18
% ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
Diagnostic Word
Form_MeasDiagWord
CheckStatusCodes
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
c.IOunitOK
4MotW1Utmp_S
4MotW1Vtmp_S
4MotW1Wtmp_S
MeasDiagWord26
& ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
5
+ #
#$&
Fault Words
Form_FaultWord1
0
0
0
0
7MotW1UtmpFlt
7MotW1VtmpFlt
7MotW1WtmpFlt
0
0
0
0
24CH4linkLost
19MSWtripped
0
0
0
ConvB16Dint
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
FaultWord126
Form_FaultWord3
0
0
0
2MotAuxSwClose
2AuxSwClose
2PowerSupply
12FC1diag
12FC2diag
12FC2hipDiag
12FC2lopDiag
13Estop
19MSWeOff
0
0
0
0
ConvB16Dint
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
FaultWord326
Form_FaultWord4
22Fan1Grp1ovld
0
22Fan1Grp1ackFlt
0
0
0
0
0
0
0
0
0
0
0
0
0
ConvB16Dint
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
FaultWord426
10
' ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
'
+ #
#$&
>=1
GeneralTrip3
7MotWTmpAlm
19MSWalarm
gMT1almAct
>=1
GeneralAlarm3
11
+ ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
Fault Classification
gFC1_TR
>=1
FC118
>=1
FC218
>=1
FC2hip18
>=1
FC2lop18
0
7MotW1UtmpFlt
7MotW1VtmpFlt
7MotW1WtmpFlt
23AuxSupplyFlt
0
0
22FanGrpFC2lop
0
>=1
FCestopTimer
&
20ASW2_FC1
20ASW2_FC2
20ASW1_FC2hip
20ASW1_FC2lop
>=1
TOn
In Q
PT ET
FCestop13
>=1
FC1diag10
>=1
FC2diag10
>=1
FC2hipDiag10
>=1
FC2lopDiag10
0
c.Time_5s
0
12
, ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
Emergency Stop
24CH4linkLost
12FCestop
>=1
Estop10 17
:=
gEstop
13
()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+
+ #
#$&
&
0
19MSWremote
0
0
0
0
19MSWeOff
RemLoc
DIremoteOn
MSW_RemoteOn
ASW2_AuxOnSeq
DIauxOnLocal
DIauxOffLocal
AuxOnRemote
AuxOffRemote
MSW_EmergOff
AuxCtrlOn
LubPumpOn
JupPumpOn
MotFanGrpOn
LocalOn
AuxOn15
MotFanOn22
14
()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
%
$ '(,
"
%
+ #
#$&
DDCS Control
All Aux ON State
14AuxOn
22FanGrp1on
19MSWprocessStop
&
AllAuxOnState
AuxOnSequenceTimer
TOf
In Q
PT ET
20ASW2auxOnSeq
c.Time_5s
AuxOnReadyRun
>=1
RS
Set Q1
R1
20ASW2_FC2
ACW1readyRun18
PulseGenerator_1
1
c.Time_500ms
c.Time_1s
PulseGenerator
Enable
Out
PulseTime
ParError
PeriodTime
ACW1watchDog18
15
()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
%
$ '(,
"
%
+ #
#$&
Status Word
19MSWreadyRef
20ASW1startinhibit
&
Form_StatusWord
&
0
0
0
0
0
0
0
0
0
0
0
0
gReset
ConvB16Dint
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
StatusWord26
16
()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
%
$ '(,
"
%
+ #
#$&
2DriveOn
2DriveOff
2EmergencyStop
13Estop
>=1
FC2reset
RS
Set Q1
R1
2Reset
>=1
Form_MCW
gReset
1
2MotorStart
1
1
1
0
0
1
0
1
0
0
0
ConvB16Dint
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
MCW6
17
# ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
%
$ '(,
"
%%
+ #
#$&
Form_ACW1
1
15ACW1readyRun
1
15ACW1watchDog
0
0
0
0
0
0
0
0
0
0
0
0
ConvB16Dint
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
ACW16
Form_ACW2
8AlarmSum
0
12FC1
12FC2
0
0
12FC2lop
12FC2hip
0
0
0
0
0
0
0
0
ConvB16Dint
I1
O_Dint
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
ACW26
18
% ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
%
$ '(,
"
%
+ #
#$&
6MSW
MSWreadyOn3
MSWreadyRun3
MSWreadyRef3 16 25
MSWtripped10 11
MSWonInhibited
MSWalarm8 11
MSWremote14
MSWprocessStop15
MSWmodulating
EoffTimer
EoffSet
TOf
In Q
PT ET
RS2and
Set Q1
R1
R2
EstopTimer
EstopSet
c.Time_2s
MSWeOff3 10 14 22
gReset
TOf
In Q
PT ET
RS2and
Set Q1
R1
R2
MSWeStop
>=1
EstopOrOff
19
& ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
%
$ '(,
"
%5
+ #
#$&
Get_ASW1
6ASW1
DintToBit16FB
Integer BoolStruct
B0
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
B14
B15
ASW1startinhibit16
ASW1zerospd
ASW1_FC2hip12
ASW1_FC2lop12
Get_ASW2
6ASW2
DintToBit16FB
Integer BoolStruct
B0
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
B14
B15
ASW2_FC112
ASW2_FC212 15
ASW2watchDog24
ASW2auxOnSeq14 15
ASW2charging
20
' ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
%
$ '(,
"
%'
+ #
#$&
6MotVoltageAct
Comp_dint
I1 I1_H_I2
I2
Equal
I1_L_I2
gMCB1closed
DINT_TO_REAL
MotVoltage26
3.15
6MotFrequency
DINT_TO_REAL
ABS
MotFrequencyHz
0.1
MotNomFreqHz
6MotNomFreq
DINT_TO_REAL
/
0.1
/
MAX
1.0
Motor actual torque %
6MotTorqAct
DINT_TO_REAL
MotTorqueAct5
*
6MotCurrAct
DINT_TO_REAL
6MotSpdAct
DINT_TO_REAL
20000
6MotSpeedScaling
ABS
MotLoadAbsPct26
MotCurrActA5 26
/
INT_TO_REAL
DINT_TO_REAL
MotSpdActrpm5
/
10.0
ABS
SpeedActAbs26
4MotSpdRef
REAL_TO_DINT
100.0
*
20000
:=
NREF6
21
+ ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
%
$ '(,
"
%
+ #
#$&
Fan Control
Fan_Control
14MotFanOn
2Fan1fuse
2Fan1run
7MotWTmpAlm
19MSWeOff
gReset
Fancontrol_1_1
Mot_Fan1_OnOff
Mot_Fan1_Ovld
Mot_Fan1_Ack
Mot_Temp_Alm
Eoff
Reset
Mot_Fan1_On
Mot_Fan1_OvldFlt
Mot_Fan1_AckFlt
Mot_Fan_FC
FanGrp1on3 15
Fan1Grp1ovld10
Fan1Grp1ackFlt10
FanGrpFC2lop11 12
22
, ()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
%
$ '(,
"
%
+ #
#$&
2MotAuxSwClose
2AuxSwClose
2PowerSupply
gAuxSupplyFlt
AuxiliarySupplyFlt
RS2and
Set Q1
R1
R2
gReset
>1)
>1) AuxSupplyFlt11 12 14
23
()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
%
$ '(,
"
%+
+ #
#$&
Channel 4 WatchDog
Chan4OnTimer
TOn
In Q
PT ET
20ASW2watchDog
c.Time_3s
Chan4OffTimer
TOf
In Q
PT ET
>=1
Channel4Link
RS2and
Set Q1
R1
R2
gReset
CH4linkLost10 13
24
()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
19MSWreadyRef
RunningTimeReset
TimeCountersOut
RunningCounters
:=
RunningCountSrc
25
()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
8AlarmWord1
8AlarmWord2
10FaultWord1
10FaultWord3
10FaultWord4
9MeasDiagWord
>1)
>2)
Move_Drive_Panel_Profibus
In1
Out1
In2
Out2
In3
Out3
In4
Out4
In5
Out5
In6
Out6
In7
Out7
In8
Out8
In9
Out9
In10
Out10
In11
Out11
In12
Out12
In13
Out13
In14
Out14
In15
Out15
In16
Out16
In17
Out17
In18
Out18
In19
Out19
In20
Out20
In21
Out21
In22
Out22
In23
Out23
In24
Out24
In25
Out25
In26
Out26
In27
Out27
In28
Out28
In29
Out29
gD1statusWord
gD1speedAct
gD1loadAct
gD1currentAct
gD1voltageAct
gD1motWind1Utemp
gD1motWind1Vtemp
gD1motWind1Wtemp
gD1alarmWord1
gD1alarmWord2
gD1faultWord1
gD1faultWord3
gD1faultWord4
gD1measDiagWord
gD1runningDays
gD1runningHours
>1) RunningCounters.RunningDays
>2) RunningCounters.RunningHours
26
()
()
*
!
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
+ #
#$&
! "
3 #7 8
(
**
! "#$
"
%&
#$% ! #$& '()%$ # *'
/0 1 /..1 23&56
"#
+#
'#, *+!$
'
"
%
$ '(,
%
+ #
#$&
NORELCO EHKE
(Norpower 4000)
Instructions for
installation, commissioning and
service
NORELCO
15297-1
Page 1
NORELCO
15297-1
Page 2
NORELCO
15297-1
max. 90
When transporting with rollers, the switchboard should always be on its transportation pallet.
Make always sure that the switchboard can not fall down in any phase of the transportation.
Page 3
NORELCO
15297-1
Page 4
NORELCO
15297-1
35
t
Page 5
NORELCO
15297-1
500
490
450
20
750
740
700
20
1000
955
905
20
After the connection has been made, the cable compartment shields should be attached back on.
Bolt/Nut size
Tightening moment. Nm
M6
M8
M10
M12
M16
9
22
44
75
190
TABLE 1: The tightening momentum of the busban connection bolts according to the bolt
size
Page 6
NORELCO
15297-1
Check that no components have become loose or broken during the transportation or installation.
IN case the painting has been damaged, paint again these places using the spray. The color of
doors and covers is beige Oxyplast 928 and other visible structural parts dark grey BH8715.
Cabling instruction
When cabling always clean well the connection surfaces. In aluminium connection use connection
grease.
With cable crimp terminals always use pressure washers and make tightening with momentum
according to Table 1.
Use the indicated tightening momentums and cable recommendations for terminals in the
switchboard.
Cabling is done either through the cabling section or alternatively from top/bottom of the
switchboards directly to the equipment.
Cables can be attached to the C-profile rails in the cabling section. Cabling from the cabling
section to the compartment is made through plastic C-type glands. The glands can be punctured
e.g. with a knife.
Other installation friendly features are:
there are lots of C-profiled rails in the cable channel. These can be used to fix cable connectors and
cables
the cabling can be made either from above or from below. It is always made through the standard
bottom or ceiling plate and glands
The value of the insulation resistance should be greater than values in the table below (A2-1994)
when the measuring time is 1 min. The test equipment should be able to feed a current of 1 mA.
Nominal voltage of the Test voltage (stable)
circuit
V
Insulation resistance
Mohm
max.. 500V
500
>= 0.5
> 500V
1000
>= 1.0
Page 7
NORELCO
15297-1
Page 8
NORELCO
15297-1
NORELCO
P.O. Box 28
FIN-57201 Savonlinna
FINLAND
tel. +358-15-57 67 70
fax +358-15-57-67-710
Page 9
NORELCO
05200-1
Contents
General description
Description of the switchboard systems
Technical specification of the systems
The structure of the switchboard systems
Sectional modules
Transportation and installation
The standard outgoing unit modules
Drawing of a NorPower switchboard: Inside
Drawing of a NorPower switchboard: Covers
Page 1
1
2
3
4
5
6
7
8
9
NORELCO
05200-1
The
Page 2
NORELCO
05200-1
E H R K E -R
W=withdrable units
F=fixed unit
R=removable unit
M=LV switchgear of a sub-station
NORELCO multicubicle
switchboard system
Empty=ordinary degree of protection
R=splash proof decreeof protection
NORELCO switchboard system
current)
Id y n max. 220 kA
current)
50 kA, 725V, 0.3 s (laboratory tested value)
2500V
withdrawable (W), removable (R) or fixed (F)
IP20 inside, max. compartimentation Form 4
IP30
(IEC 529)
IP30, IP44 or IP54
(IEC 529)
IP30, IP44 or IP54
(IEC 529)
400V, 690V,
50/60 Hz
250A - 1600A
It h max. 25 kA, 1s (thermic short-circuit current)
Id y n max. 63 kA
2500V
always fixed
IP 30
(IEC 529)
Page 3
NORELCO
05200-1
Busbars
EHKE
Withdrawable
EHKE
Removable
EHKE
Fixed
NKE
2250
65mm,included
2250
65mm,included
2250
65mm,included
1900
300mm, option
X
X
X
X
X
X
X
X
X
X
-
X
X
-
X
X
-
X
X
X
X
X
X
X
-
X
X
-
X
X
-
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
-
X
X
X
X
X
X
X
X
Page 4
NORELCO
05200-1
Sectional modules
Page 5
NORELCO
05200-1
Bolt/Nut size
Tightening moment.
Nm
M6
M8
M10
M12
M16
9
22
44
75
190
Installation hints
There are features that make the installation easier e.g.
there are lots of C-profiled bars in the cable
channel. These can be used to fix cable connectors
and cables
the cabling can be made either from above or from
below. It is always made through the standard
bottom or ceiling plate (see pictures 1 and 2)
it is easy to connect the cables directly to the poles
and connectors inside the switchboard
Installation
Fixing onto the floor is made by using the external fixing
hooks. This is the easiest way to fix a switchboard on a
floor.
www.norelco.fi
Page 6
1)
37 kW
45 kW
Direct starter
Direct starter
5.5 kW
7.5 kW
11 kW
15 kW
7.5 kW
< 4 kW
7.5 kW
11 kW
15 kW
Reversing
f-s =fuse-switch
Page 7
Reversing
Reversing
Reversing
Reversing
Reversing
S/D-starter
S/D-starter
S/D-starter
S/D-starter
15 kW
11 kW
15 kW
11 kW
7.5 kW
5.5 kW
< 4 kW
NFR15
NFR11
NFR7
NFR15
NFR11
NFR7
NFR5
NFR4
NFS75
75 kW
Direct starter
75 kW
55 kW
NFS55
NFS45
NFS37
NFS30
Direct starter
55 kW
45 kW
37 kW
30 kW
f-s 250 A
f-s 250 A
f-s 250 A
f-s 125 A
f-s 125 A
switch 40 A
switch 40 A
switch 40 A
Compo
nent 1)
switch 40 A
switch 40 A
switch 40 A
NWYD7
switch 40 A
NWR7
NWR5
NWS7
NWS5
Code
f-s 125 A
f-s 125 A
f-s 125 A
f-s 125 A
NRYD7
f-s 125 A
f-s 63 A
f-s 125 A
f-s 125 A
NRYD7
NRYD5
f-s 63 A
f-s 63 A
f-s 400 A
f-s 400 A
30 kW
Direct starter
NFS22
f-s 125 A
f-s 125 A
f-s 125 A
f-s 125 A
f-s 125 A
Compo
nent 1)
Withdrawable (W)
200
width 250mm
R,W
R,W
R,W
R,W
R,W
R,W
R,W
R,W
R,W
R,W
R,W
R,W
F,R,W
F,R
F,R
200
R,W
R,W
R,W
05200-1
22 kW
NRS7
22 kW
15 kW
NFS11
f-s 63 A
NRS5
Direct starter
15 kW
Direct starter
11 kW
NFS7
f-s 63 A
11 kW
Direct starter
7.5 kW
NFS5
fuse/mcb
Code
7.5 kW
Direct starter
5.5 kW
NFS4
Compo
nent 1)
Removable (W)
5.5 kW
Direct starter
< 4 kW
690 V
Code
Fixed (F)
NFS15
< 4 kW
Direct starter
400 V
NORELCO
NORELCO MULTI-CUBICLE TYPE SWITCHBOARD SYSTEMS
In the table below all the module sizes of the standard outgoing units (motor starter units) have been given.
Here the F stands for fixed outgoing units (EHKE-F and EHRKE-F), R for removable units (EHKE-R and
EHRKE-R) and W for withdrawable units (EHKE-W).
When ordering standard outgoing units please mention the order code, voltage, component type and width,
height of the module and the colour of the switchboard (if not standard colour).
NORELCO
05200-1
The incoming
section, width
500mm
2.
An outgoing section,
circuits with fuseswitches and
moulded case
circuit breakers
3.
4.
An outgoing section
with motor control
feeders, one with a
fuse-switch and the
other with a MCCB
5.
An outgoing section
with withdrawable
(cassette) and
removable units, a
500mm section can
also have 250mm
units
6.
7.
8.
N/PE- shunt
9.
Page 8
NORELCO
05200-1
The incoming
section, width
500mm, one
module of 1200mm
(height) and two
modules of 300mm
(height)
2.
An outgoing section
with fixed units,
width 500mm, one
module of 600mm
and four modules of
300mm
3.
4.
An outgoing section
with motor control
feeders, width
750mm, two
modules of 600mm
and two modules of
300mm
5.
An outgoing section
with withdrawable
(cassette) and
removable units,
two modules of
400mm, three
modules of 200mm
(width 500) and four
modules of 200mm
(width 250)
6.
The pressure
hatches for short
circuit situation
pressure relief
7.
8.
9.
A- and V-meters
with a 7-position
CAM-switch
Page 9
ABB
ACS 6000
Medium Voltage Drives
3 to 27 MVA
Users Manual
ABB
Document No.:
Issued:
03-06-2005
ABB reserves all rights to this document, also in the event of patent issue
or registration of any other industrial property protection right. Misuse, in
particular duplication and forwarding to third parties, is not permitted.
This document has been checked with due care and attention. However,
should the user find any errors, these should be reported to ABB.
ABB aims to maintain the most modern standard, therefore, entries in this
manual may differ from the actual product.
ABB
Table of Contents
General Information
Contact Information
Related Documentation
Quality Certificates and Applicable Standards
Chapter 1 - Safety
1-1
1.1
1.2
1.3
1.4
1.5
1-1
1-1
1-2
1-3
1-4
2-1
2.1
2.1.1
2.1.2
2.1.3
2.2
2.2.1
2.2.2
2.3
2.4
2.5
2-1
2-1
2-1
2-1
2-4
2-4
2-4
2-5
2-6
2-6
Transportation
Transport Conditions
Unpacking and Inspection
Loading and Unloading
Storage
Storage Conditions
Storage
Storage and Handling Instructions for Spare Parts
Disposal of Packaging Materials
Disposal of Components
3-1
3.1
3.2
3.2.1
3.2.2
3.2.3
3.3
3.4
3.4.1
3.4.2
3.4.3
3-1
3-1
3-1
3-2
3-2
3-2
3-4
3-4
3-4
3-6
Overview
Installation Site
Ambient Conditions
Dimensions and Clearances
Foundation, Floor Levelling and Cable Ducts
Identifying Converter Units
Installing the Converter
Raw Water Circuit
Mechanical Door Interlock
Installation Procedure
1 (4)
ABB
3.4.4
3.4.5
3.4.6
3.4.7
3.4.8
3.4.9
3.4.10
3.4.11
3.4.12
3.4.13
2 (4)
3-7
3-9
3-9
3-10
3-13
3-14
3-16
3-19
3-20
3-23
4-1
Overview
Cables
Internal Wiring
Busbars and Ground Connections
External Power Cabling
Connecting Incoming Feeder and Motor Cables
Connecting Braking Resistor Cables
Connecting Excitation Cables
Connecting Auxiliary Power and Control Cables
Connecting Auxiliary Power Cable
Connecting Control Cables in WCU
Connecting Cables for Serial Communication
and Encoders
Connecting Position Encoder Cables in
Marine Drives
Connecting the Heating Cable
4-1
4-2
4-3
4-5
4-8
4-8
4-10
4-11
4-13
4-14
4-14
4-17
4-25
4-27
5-1
5.1
5-1
Chapter 6 - Operation
6-1
7-1
7.1
7.2
7.3
7.4
7.4.1
7-1
7-2
7-3
7-6
7-8
Overview
Identification Mode
Actual Signal Display Mode
Parameter Mode
Parameter Lock
ABB
7.5
7.6
7.6.1
7.6.2
7.6.3
Function Mode
Operational Commands
Selecting Local/Remote
Setting the Direction of Rotation
Entering a Setpoint
7-8
7-9
7-9
7-10
7-11
8-1
8.1
8.2
8.2.1
8.2.2
8.3
8-2
8-3
8-3
8-3
8-4
Safety Instructions
Specific Maintenance Tasks
Cleaning
Checking Wire and Cable Connections
Standard Procedure for Troubleshooting
Appendix B - Options
Appendix C - Mechanical Drawings
Appendix D - Electrical Diagrams
Appendix E - Parts List
Appendix F - Test Reports
Appendix G - Signal and Parameter Table
Appendix H is provided to file the Signal and Parameter Table. The table
includes a complete description of all control parameters and their default
setting.
If the Signal and Parameter Table is not included in the Appendix, the
commissioning engineer will hand out a copy to the customer after commissioning of the converter has been completed. The Signal and
Parameter Table can also be obtained from ABB. For contact address see
section General Information.
3 (4)
ABB
4 (4)
ABB
General Information
Contact Information
If information is required beyond the instructions in this manual, ABB can
be contacted as follows:
ABB Switzerland Ltd
CH-5300 Turgi, Switzerland
Phone:
Fax:
Related Documentation
The following documents can be optained from ABB for supplementary
information.
Title
Document
Number
3BHS125090
3BHS125149
3BHS125150
3BHS125092
3BHS125393
3BHS125088
3BHS125093
3BHS130246
3BHS196243
3BHS204855
3BHS202077
1 (2)
ABB
Quality Certificates and Applicable Standards
The following certificates and conformity declarations are available with
ABB:
ISO 9001 / ISO 14001 certificates stating that ABB Switzerland Ltd has
implemented and maintains a management system which fulfills the requirements of the normative standards
EC Conformity Declaration
List of standards the converter complies with
2 (2)
ABB
Chapter 1 - Safety
1.1
Installation Personnel
Operating Personnel
Maintenance
Personnel
1.2
Preparing the water cooling unit for operation (if present in the
converter)
The operating personnel include all persons who operate the converter as
required for the application using the control panel(s) of the converter or a
supervisory control system. Operating the converter does not require
special knowledge of converter technology. However, the operator must
know the functions of the control panel.
The maintenance personnel are mainly responsible for:
Maintenance tasks
Owners Responsibilities
It is the owners responsibility to ensure that each person involved in the
installation, operation or maintenance of the converter has received the
appropriate training and has thoroughly read and clearly understood the
relevant safety instructions.
The technical specifications and the approved purpose of the converter
must be strictly adhered to.
The owner must ensure that the converter is operated under proper
conditions and in a fully serviceable state. The specified service intervalls
and ambient conditions for the converter must be followed.
Unauthorized modifications and constructional changes of the converter
are not permitted.
1-1 (4)
ABB
Chapter 1 - Safety
1.3
Safety Instructions
Safety instructions are used to highlight a potentially dangerous situation
when working on the converter. Safety instructions must be strictly
followed! Non-compliance can jeopardise the safety of personnel, the
machine and the environment.
DANGER!
Indicates an imminent hazardous situation. If not observed, it will lead to
death or life-threatening injury.
WARNING!
Indicates a potentially dangerous situation. If not observed, it could result
in death or life-threatening injury.
CAUTION!
NOTICE!
Indicates important information related to personal safety and protection
of property.
1-2 (4)
IMPORTANT!
Emphazises hints and highlights information.
ABB
1.4
Chapter 1 - Safety
1-3 (4)
ABB
Chapter 1 - Safety
1.5
Danger Zones
Figure 1-1 indicates the danger zones of the converter.
Line
Supply
Unit
Terminal Control
Unit
Unit
Inverter
Unit
Capacitor
Bank
Unit
High voltage!
Do not attempt to open doors of
medium voltage units by force when
converter is energized.
The doors are electromechanically
interlocked. When the light GROUNDING SWITCH UNLOCKED is on, the
converter can be grounded and then
the doors can be opened.
Water
Cooling
Unit
High voltage!
Do not remove any
bolted walls or plates
when converter is energized or before converter
is grounded.
Figure 1-1
1-4 (4)
Danger Zones
ABB
Chapter 2 - Transportation, Storage and Disposal
2.1
2.1.1
Transportation
Transport Conditions
The transport conditions are based on IEC 721-3-2 'Classification of
environmental conditions: Classification of groups of environmental
parameters and their severities; Transportation'.
2.1.2
Classification:
Transport time:
max. 2 month
Compare the complete delivery with the purchase order and the
packing list.
2.1.3
Do not lift and move the converter or a transport unit using a forklift. The
frame of the cabinets could be damaged. If a crane is not available contact
ABB for instructions on other means of moving. See section General
Information for contact address.
CAUTION!
2-1 (6)
ABB
CAUTION!
When transporting the converter ensure that no dirt enters. Keep doors
closed. Metallic dust in particular may cause damage and lead to
malfunction when the converter is powered up.
CAUTION!
The roof plates of medium voltage units are equipped with pressure relief
flaps. Do not stand on roof due to danger of collapse.
When lifting a converter equipped with a base frame always use the
lifting lugs which are attached to the base frame. The lugs can be
removed after the converter has been installed at its final location.
Do not pass a lifting cable through the fastening hole of a lug. Use a
safety hook to attach a cable to a lug.
2-2 (6)
Lift the converter slowly and steadily to the required clearance height
maintaining the converter in upright position.
ABB
Protect
edges !
30
Figure 2-1 Cabinets with Base Frame and without Door Handles
30
Figure 2-2 Cabinets with Base Frame and Marine-type Door Handles
MAX.
120
Cable angle
indicated on
cabinet roof
2-3 (6)
ABB
2.2
2.2.1
Storage
Storage Conditions
The minimum requirements for storage are based on IEC 721-3-1
'Classification of environmental conditions: Classification of groups of
environmental parameters and their severities; Storage'.
Classification:
2.2.2
Storage
If the converter is taken out of service for a longer time proceed as follows:
1
Cover all cable inlets and ventilation slots with an impermeable plastic
or aluminum foil and a wooden panel.
2-4 (6)
ABB
2.3
2-5 (6)
2.4
ABB
2.5
Wooden frame
Wooden pallet
Polyethylene sheet
Plywood
Silicagel
Disposal of Components
At the end of the life time of the converter dispose of the following
components according to local regulations:
2-6 (6)
Batteries
Capacitors
Electronic devices
ABB
Chapter 3 - Mechanical Installation
NOTICE!
All installation work must be carried out by qualified personnel in
compliance with local regulations.
See Chapter 1 - Safety for explanation on how the safety messages are
categorized and used in this manual.
3.1
Overview
The mechanical installation includes the following steps:
3.2
Installation Site
3.2.1
Ambient Conditions
Ambient factors such as temperature, relative humidity, air contamination,
shock and vibration must be in compliance with the stated maximum
permissible levels.
3-1 (24)
ABB
3.2.2
3.2.3
3.3
Packing List
3-2 (24)
the packing label on the back wall of each converter unit (ARU, LSU,
CBU etc.). The packing label is only visible after the packaging has
been removed.
ABB
the nearest Lloyd's agent may be contacted. Please also inform the contact person with ABB Schweiz AG
shown on this packing list.
ABB item
Customer item
Qty. Unit.
001201
Identnumber
PC
Commodity description
Converter 1: Transport Unit 1
Drives
Mailing address:
Phone:
Telex:
Facsimile:
CH-5401 Baden/Schweiz
+41 58 589 27 95
755749 abb ch
+41 58 589 29 84
Qty. Unit.
Identnumber
Commodity description
001221
PC
cross wiring
001222
PC
WCU accessory
001223
PC
001500
PC
3BHB013202R0001
Drives
Mailing address:
Phone:
Telex:
Facsimile:
CH-5401 Baden/Schweiz
+41 58 589 27 95
755749 abb ch
+41 58 589 29 84
The number in this place (4th. digit from right) states the converter to which
the accessories belong. In this example they belong to converter 1.
Figure 3-2
Packing Label
The packing labels on the back walls of converter units can also be used
to identify the converter (see Figure 3-3).
3-3 (24)
ABB
ABB
Packing Label
0000
Material no
3BHB009964R1500
1 ST
Material
Material Document
004902892300012004
001241
3.4
3.4.1
3.4.2
3-4 (24)
ABB
Figure 3-4
Procedure
The solenoid interlocks are mounted behind the name plate on the doors
of the medium voltage units (see arrows in Figure 3-5).
Figure 3-5
Remove the name plate of the door to be opened and insert the key
through the opening in the door (see Figure 3-6) into the triangular
counterpart of the solenoid interlock (see Figure 3-7).
Figure 3-6
Door Opening
Turn the key from the locked to the unlocked position to release
the interlock (when looking through the opening at an angle the
symbols are visible). The door can now be opened.
3-5 (24)
ABB
Unlocked position
Locked position
Figure 3-7
!
3.4.3
IMPORTANT!
After the mechanical and electrical installation has been finished, it is the
task of the commissioning engineer to check that the manual release of all
solenoid interlocks is in the locked position. Otherwise, the converter
cannot be started up.
Installation Procedure
Depending on the configuration, the converter is delivered in one unit or in
several transport units, which are joined and fixed to the floor at the
installation site. See Appendix C - Mechanical Drawings to identify the
units and their position in the lign-up. Transport units must be ligned up as
shown on the Layout Drawing. The units can be ligned up either beginning
from the left or the right.
Parts needed for the installation (bolts, washers, joining pieces etc.) are
supplied with the converter in a separate box.
Observe the following points when installing the converter:
Drill the floor fixing holes before moving the converter unit(s) to the
final location.
CAUTION!
3-6 (24)
When installing the converter ensure that no dirt enters. Always close the
doors when work is discontinued and completely cover openings. Metallic
dust in particular may cause malfunction when the converter is powered
up and cause damage.
ABB
CAUTION!
The roof plates of medium voltage units are equipped with pressure relief
flaps. Do not stand on roof due to danger of collapse.
NOTICE!
When joining two cabinets do not damage or dislocate the EMC sealing
strip which is glued onto the outer joining surface of the cabinet frame.
NOTICE!
Do not weld cabinets without base frame to the floor. The corrosion
protection will become ineffective.
NOTICE!
The roof plates of the cabinets are not designed as a mounting base for
foreign devices, cable ducts etc. Therefore, it is not permitted to install any
foreign devices on the cabinet roofs.
3.4.4
If the transport unit has water pipes, remove the protective covers
from each water pipe end.
!
ACS 6000 Users Manual
IMPORTANT!
When aligning a transport unit make sure that two joining water pipes have
a linear misalignment of a maximum of +/- 3 mm (see Figure 3-8).
3-7 (24)
ABB
Figure 3-8
Join the transport units using the supplied M6 screws, item 1 in Table
3-1. Number and position of connecting points are illustrated in Figure
3-9.
Front of cabinet
Figure 3-9
Connect the wiring ducts using the supplied M6 screws and nuts,
washers and spring washers, items 1, 2, 3 and 4 in Table 3-1.
Connecting points
3-8 (24)
ABB
Table 3-1
Installation Material
Item
3.4.5
Type
M6x20
Washer
Spring washer
Ident. Number
Use
3BHE004520R0003
Connection of transport
unit
M6x20
NB312350P0260
A 6.4/12.5
NB335050P0607
NB335805P0509
HZN452198P0016
M6 A2-70
IMPORTANT!
This section is applicable for marine converters and converters with
insulation protection IP 54.
The self-adhesive sealing tape (supplied with the converter) prevents
water from entering into the gap between two joining roof plates. The tape
has to be installed where two transport units have been joined. Gaps
within a transport unit have been sealed with a tape in the factory already.
Proceed as follows:
Attach the tape on the whole length of the joining crossbars (see
Figure 3-11).
Sealing Tape
3.4.6
3-9 (24)
ABB
Joining pieces
Installation Material
Item
3.4.7
Type
Ident. Number
Joining piece
8x80x220 mm
3BHB011552R0001
Bolt
M16x45
NB312350R0465
Washer
A17/30
NB335050R0611
!
Roof Attachments
IMPORTANT!
This section is only applicable for marine drives.
To prevent tilting, the cabinets are fixed to the ceiling or the back wall of
the drive room by means of roof attachments which also serve as vibration
dampers. All parts of a complete roof attachment assembly are listed in
Table 3-3.
See Appendix C - Mechanical Drawings for
Table 3-3
Installation Material
Item
3-10 (24)
Type
Ident. Number
3BHB11553R0001
3BHB11553R0002
Rubber pad
80x220 mm
3BHB12579R0001
2 Sleeves
3BHB012580R0001
ABB
Table 3-3
Type
Ident. Number
2 Bolts
M12x80
NB312450P8127
2 Washers
13x45x4
3BHL001710P0001
2 Nuts
M12
3BHB011779R0002
2 Washers
A13/24
NB335050P0610
1 4 mm
factory mounted
within a transport
unit
Check that the roofside steel brackets have been mounted according
to Appendix C - Mechanical Drawings.
Align the rubber pad and the wallside steel bracket with the roofside
steel bracket (see Figure 3-14).
Insert one of the sleeves into a mounting hole until the sleeve is flush
with the surface of the second bracket.
3-11 (24)
ABB
Join the parts with one set of the supplied bolts, nuts and washers,
with the nut on the roofside bracket and the bolt on the wallside
bracket (see Figure 3-15). Tighten the bolted connection by hand.
Insert the second sleeve and join the parts with the remaining bolt, nut
and washers. Tighten the bolted connection by hand.
Finally, tighten the bolted connections until the rubber of the sleeves
starts to bulge (see Figure 3-15).
To be mounted on site:
2nd steel bracket
Rubber pad
30 m m
Sleeve
Nut
Bolt
Fix the cabinets to the ceiling or the back wall with suitable struts. The
struts are not part of the delivery.
When fixing the cabinets to the ceiling, it is recommended to use two
struts per roof attachment as illustrated in Figure 3-16 a.
Struts connecting the cabinet to the wall should be mounted in a 90
angle to the converter as illustrated in Figure 3-16 b.
!
3-12 (24)
IMPORTANT!
When fixing the struts to the ceiling, do not mount the struts in a 90 angle
to the cabinet roof as illustrated in Figure 3-16 c.
ABB
45
45
90
Recommended!
Recommended!
Not recommended!
3.4.8
Place the heat exchanger on the mounting frame and align the screw
holes on the underside of the heat exchanger with the screw holes of
the mounting frame (one screw hole in each corner, see Figure 3-17).
Fasten the heat exchanger to the frame using the supplied screws
and washers.
Plug the power leads into the connectors on the roof (see Figure 318) and fasten the coupling rings.
3-13 (24)
ABB
3.4.9
Connect the pipe ends by sliding the pipe joint over the two joining
pipe ends.
47
mm
Figure 3-20 Centering a Pipe Joint
3-14 (24)
ABB
IMPORTANT!
When adjusting a pipe joint make sure that the locking part of the pipe joint
is at a minimum distance of 55 mm from a DC busbar.
Front of cabinet
5 5 min
mm .
Locking part of
pipe joint
m
55 min.
m
After adjusting a pipe joint, alternately tighten the bolts only lightly.
Tighten the bolts with a torque wrench to the final torque rate
indicated on the pipe joints outer surface.
Torque rate
IMPORTANT!
Do not tighten bolts above indicated torque rate.
3-15 (24)
ABB
IMPORTANT!
Sealing lip may touch pipe end. Turn and move pipe joint smoothly.
Clean pipe joint and treat bolts with an appropriate
lubricant before refitting.
IMPORTANT!
All joining pieces and bolts must be orientated exactly as shown in Figure
3-23 to Figure 3-26 to maintain the required distance between busbars of
different polarity.
When fitting the joining pieces make sure that the bolt head is on the
busbar side and the nut is on the side of the joining piece.
IMPORTANT!
Tightening torque for bolted busbar connections: 30 Nm.
The bolts must be greased to maintain the required contact pressure.
Use the items listed inTable 3-4 when joining the busbars.
Table 3-4
Installation Material
Item
Hexagon head bolt
Type
Ident. Number
M12x35
NB 312350P8118
Strain washer
Hexagon head nut
3-16 (24)
GZN 490084P0111
M6 A2-70
HZN 452198P0022
Joining piece
3BHB009410R0001
Grease
GJN598105P0153
ABB
Top of cabinet
Front of cabinet
Joining piece
NP
Top of cabinet
Front of cabinet
Joining piece
+
NP
NP
3-17 (24)
ABB
Top of cabinet
Front of cabinet
Joining piece
NP
+
NP
NP
Front of cabinet
Top of cabinet
Strain washer on each side
of a connection!
Joining piece
+
NP
NP
+
NP
NP
3-18 (24)
ABB
IMPORTANT!
Tightening torque for bolted busbar connections: 30 Nm.
The bolts must be greased to maintain the required contact pressure.
Mount the joining pieces for safety ground busbar (PE) and power ground
busbar (PG) as shown in Figure 3-27 using the items listed inTable 3-5.
Table 3-5
Installation Material
Item
Hexagon head bolt
Type
Ident. Number
M12x40
NB 312350P8119
Strain washer
Hexagon head nut
GZN 490084P0111
M6 A2-70
HZN 452198P0022
Joining piece
3BHB009221R0001
Grease
GJN598105P0153
PG busbar
Strain washer on each side
of a connection!
Pipe joint
Connecting piece
PE busbar
Front of cabinet
Figure 3-27 Connecting Ground Busbars
3-19 (24)
ABB
IMPORTANT!
Tightening torque for bolted busbar connections: 30 Nm.
The bolts must be greased to maintain the required contact pressure.
Table 3-6
Installation Material
Item
Hexagon head bolt
Type
Ident. Number
M12x40
NB 312350P8119
Strain washer
Hexagon head nut
Grease
3-20 (24)
GZN 490084P0111
M6 A2-70
HZN 452198P0022
GJN598105P0153
ABB
Connecting Points on
the Right of TEU
Figure 3-28 shows the connecting points of AC busbars of ARU, INU and
IFU when located on the right of a terminal unit.
Connecting points
for phase L3 of IFU
L3
L2
Connecting points for
phase L2 of ARU/INU
L1
3-21 (24)
ABB
Connecting Points on
the Left of TEU
Figure 3-29 shows the connecting points of AC busbars of ARU, INU and
IFU when located on the left of a terminal unit.
L3
L2
L1
3-22 (24)
ABB
IMPORTANT!
Tightening torque for bolted busbar connections: 30 Nm.
The bolts must be greased to maintain the required contact pressure.
Table 3-7
Installation Material
Item
Type
Ident. Number
Remarks
M12x50
NB 312450P8121
single busbars
M12x80
NB 312450P8127
double busbars
M12x60
NB 312350P0418
Strain washer
Hexagon head nut
GZN 490084P0111
M6 A2-70
Grease
Connecting Points on
the Right of TEU
HZN 452198P0022
GJN598105P0153
Connecting points
3-23 (24)
ABB
Single busbars in
7 and 9 MVA units
require M12x40 bolts
Double busbars in
14 MVA units
require M12x40 bolts
3-24 (24)
ABB
Chapter 4 - Electrical Installation
NOTICE!
All installation work must be carried out by qualified personnel in
compliance with local regulations.
See Chapter 1 - Safety for explanation on how the safety messages are
categorized and used in this manual.
Power must not be applied to the drive system without the consent of the
ABB commissioning staff.
DANGER!
Hazardous voltage!
To ensure safety, the converter must be installed in accordance with the
instructions in this manual. Improper work can lead to life-threatening
injury or death.Take appropriate measures to prevent that mains and
auxiliary power can be switched on.
4.1
Overview
The electrical installation includes the following steps:
Understanding
Electrical Drawings
Abbreviations
Internal wiring
see section 4.3 Internal Wiring
Ground cable
see section 4.4 Busbars and Ground Connections
Power cables
see section 4.5 External Power Cabling
Heating cables
see section 4.9 Connecting the Heating Cable
4-1 (28)
ABB
and above. Both versions have a different physical layout and can be
present in a drive line-up. To distinguish the cabinets, the following
abbreviations are used:
Tools
4.2
COU Type 2 and TEU Type 2 for power ratings of 7 MVA and above.
ABB offers various tool sets which contain all necessary tools and
equipment for installation, commissioning and maintenance of the
converter. The content of the tool sets is described in manual Tool Sets for
Installation, Commissioning and Maintenance.
Cables
Power Cables
Control Cables
Signal Type
Cross-Section
Speed Encoder
0.5 mm2
4 x (2+1)
Position Encoder
0.5 mm2
4 x (2+1
Analog In
Analog Out
Digital In
Digital Out
Synchronization
Cables
4-2 (28)
ABB
4.3
Internal Wiring
Cables for internal wiring are prepared inside the cabinets. All necessary
data for each individual connection, i.e.
Cable numbers
Cable type
Cross-section
Location of terminals
Pull all cables through the cable duct located at the top of the
cabinets. Cut-outs in the ducts provide entry into the cabinets.
Cable duct
Figure 4-1
Lay the cables and wires in their designated trays and cable ducts as
shown in Figure 4-2.
4-3 (28)
ABB
Front of cabinet
Cable trays A for:
- Auxiliary supply
- Control cables
Figure 4-2
IMPORTANT!
When fastening IGCT power supply cables on mounting rail C (see Figure
4-2) make sure that the cables are at a minimum distance of 5 mm from
the nearest metall part.
IMPORTANT!
Handle fiber optic cables with care. Do not touch the ends of the fibers,
they are extremely sensitive to dirt. When unplugging a fiber optic cable,
always hold it at the connector not at the fiber.
Observe the maximum long-term tensile load of 1.0 N and the minimum
bend radius of 25 mm.
4-4 (28)
ABB
4.4
TEU
INU
WCU
CBU
EXU
(CIU)
DC (-)
DC (NP)
DC (+)
1L1
1L2
1L3
L3
L2
L1
2L3
2L2
2L1
PG
PE
PG to PE connection in CBU
DC Busbars
The DC busbars connect the line rectifiers (ARU or LSU) with motor
inverter(s) (INU) and CBU. In multi-motor configurations up to four DC
busbar arrangements can be installed (see Chapter 3 - Mechanical
Installation, 3.4.10 Joining DC Busbars). The busbars are mounted in the
upper part of the converter and are marked with DC (+), DC (-) and DC
(NP).
Protective Earth
4-5 (28)
ABB
The ground cable is tied to a connecting bar which is accessible from the
front of the cabinets (see Figure 4-5 to Figure 4-6).
IMPORTANT!
The ground cable must be connected to the ground busbar of the
converter at only one point: at the busbar inside the TEU closest to the
CBU. See Converter Hardware Diagram in Appendix D - Electrical
Diagrams for project-specific illustration.
The connection must be in compliance with local regulations.
Connection details:
Connecting bar
for
grounding cable
4-6 (28)
ABB
Connecting point
for
ground cable
Figure 4-5
Connecting point
for
grounding cable
Figure 4-6
Power Ground
4-7 (28)
ABB
4.5
describe cable entry using EMC ROX modules. These modules are not in
ABBs scope of supply.
Information on EMC ROX modules can be optained from www.roxtec.com
and from the Power Cable Specification.
See the Layout Drawing in Appendix C - Mechanical Drawings for the
dimensions of the EMC ROX frame(s).
If EMC ROX modules are not used, cable transits in accordance with local
regulations must be installed.
4.5.1
NOTICE!
Do not cut cables inside the terminal unit. Make sure that waste from cable
cutting and stripping cannot enter the converter. Any waste which
accidentally dropped into the converter must be retrieved. The waste
could cause damage or malfunction.
4-8 (28)
Cable armor must be in contact with the EMC ROX module as shown
in Figure 4-7 (see also Power Cable Specification). If non-armored
cables are used, the cable shield must be in contact with the EMC
ROX module.
ABB
Pull the conductors into the cabinet and install the EMC ROX
modules.
Figure 4-7
Entry plate
Check the insulation of each cable before connection and verify that
the results are within the specification of the cable manufacturer.
CAUTION!
High voltages will be present in the terminal unit. High voltages can cause
flashover between the potential of a phase conductor and ground.
A minimum clearance of 55 mm must be maintained between each cable
and the terminals of any other phase.
Connect the shield ends of all conductors to the power ground busbar
(PG).
Enter the ground cable into the cabinet through the entry plate and
fasten it to the PE ground busbar.
Connect the armor of all cables to the power ground busbar (PG).
Mount top plates and rear walls of all cabinets and fasten them with
the supplied screws.
4-9 (28)
ABB
IMPORTANT!
All provided screws must be mounted and tightened to achieve best EMC.
4.5.2
IMPORTANT!
This section is only applicable for converters with a Braking Chopper Unit
(BCU).
The braking resistor cables are connected inside a BCU.
Cable entry can either be from the top or from the bottom. Project specific
cable entry is illustrated on the Layout Drawing in Appendix C Mechanical Drawings.
NOTICE!
Do not cut cables inside the terminal unit. Make sure that waste from cable
cutting and stripping cannot enter the converter. Any waste which
accidentally dropped into the converter must be retrieved. The waste
could cause damage or malfunction.
Proceed as follows:
4-10 (28)
Cable armor must be in contact with the EMC ROX module as shown
in Figure 4-7 (see also Power Cable Specification). If non-armored
cables are used, the cable shield must be in contact with the EMC
ROX module.
Pull the conductors into the cabinet and install the EMC ROX module.
Check the insulation of each cable before connection and verify that
the results are within the specification of the cable manufacturer.
ABB
CAUTION!
High voltages will be present in the terminal unit. High voltages can cause
flashover between the potential of a phase conductor and ground.
A minimum clearance of 55 mm must be maintained between each cable
and the terminals of any other phase.
Connect the shield ends of all conductors to the power ground busbar
(PG) (see Figure 4-8).
Connect the armor of all cables to the power ground busbar (PG).
Connecting point of
cable shield
Cable entry
Figure 4-8
4.5.3
IMPORTANT!
This section is only applicable for converters with synchronous motors.
Information on cable connection can be found on the Converter Hardware
Diagram in Appendix D - Electrical Diagrams.
The incoming feeder and motor cables can be entered either from the top
or from the bottom of a cabinet. Project specific cable entry is illustrated
on the Layout Drawing in Appendix C - Mechanical Drawings.
Proceed as follows:
Enter the conductors through the EMC sleeves of the entry plate as
shown in Figure 4-9:
Strip the cable insulation at the point of entry. Tighten
4-11 (28)
ABB
Mounting bracket
Rubber grommet
Entry plate
EMC sleeve
3rd. insulated conductor
Strip conductor
insulation to
expose shield
Mounting bracket
Outer sheath
Top entry
Bottom entry
Figure 4-9
4-12 (28)
ABB
4.6
Remove outer
sheath in this area
4-13 (28)
ABB
4.6.1
4.6.2
Proceed as follows:
Enter the control cables into the WCU through the entry plate (see
Figure 4-12).
Remove the rubber grommets from the entry plate
and cut them to adequate diameter for the auxiliary
power cable. To ensure proper sealing, cut along the
diameter marking that corresponds to the cable
diameter (see Figure 4-10). Slide the grommet onto
the cable. The grommet must fit tight to prevent water
from entering the cabinet. If necessary, seal the
junctions with silicone rubber.
Cable routing
Pull the cables through the cable transit (see Figure 4-14).
Shielded cables are prepared as illustrated in Figure
4-11. Remove the cable insulation in the area of the
cable transit to bring the conductive parts of the EMC
ROX module in contact with the cable shield.
4-14 (28)
Connect the cables to the terminals below the cable transit according
to the Converter Hardware Diagram in Appendix D - Electrical
ABB
Diagrams.
Bottom Cable Entry
Proceed as follows:
Remove the cover (if present) of the cable entry. The cover can either
be discarted or used as an entry plate.
Enter the cables through the floor and run them up the side wall as
illustrated in Figure 4-14.
Pull the cables through the cable transit (see Figure 4-14).
Shielded cables are prepared as illustrated in Figure
4-11. Remove the cable insulation in the area of the
cable transit to bring the conductive parts of the EMC
ROX module in contact with the cable shield.
4-15 (28)
ABB
Cable transit
Cable routing
C-rail
4-16 (28)
Connect the cables to the terminals below the cable transit according
to the Converter Hardware Diagram in Appendix D - Electrical
Diagrams.
ABB
4.7
When cables are entered through the roof, EMC cable glands have to be
used. These cable glands are not part of the delivery.
Remove the entry plate and drill a hole adequate for the diameter of
the cable gland.
Cut off the cable sheath on the length of cable between the cable
gland and the connection point.
Prepare the cable in the area of the cable gland according to Figure
4-16.
4-17 (28)
ABB
Pull the cable through the cable gland, attach the cable gland to the
entry plate and fasten the entry plate to the roof.
Cable routing
Front of cabinet
Cable trays A for control cables
4-18 (28)
At the end of cable tray A run the cable down into the cable duct to its
destination inside the COU (see Figure 4-18 regarding COU type 1 or
Figure 4-19 regarding COU type 2).
ABB
4-19 (28)
ABB
If twisted pair cable is used, leave the unshielded cable ends twisted
up to the device terminals.
Connect the cable shields as described in section Bottom Cable
Entry.
Bottom Cable Entry
If control cables are entered through the bottom, rubber grommets must
be used to seal the entry plate. The rubber grommets are not part of the
delivery.
Proceed as follows:
Remove the entry plate and drill a hole adequate for the diameter of
the rubber grommet.
Enter the cable through the bottom entry plate. Depending on the
type of COU, run the cable to the duct on the right (see Figure 4-20
regarding COU type 1) or to the duct on the left (see Figure 4-21,
Figure 4-22 and Figure 4-23 regarding COU type 2).
Entry plate
Cable routing
Entry plate
Cable routing
4-20 (28)
ABB
Entry plate
Routing cable
along water pipe
Figure 4-22 Bottom Cable Entry COU Type 2
Run the cable up the cable duct and lead the cable through the cable
transit.
Cable transit through the frame is the same for both types of COU.
Figure 4-24 illustrates cable transit through the frame inside a COU
type 2.
Cut the rubber grommet(s) to the correct size.
Remove the cable shield in the area of the grounding
bracket.
Ground the overall cable shield.
Fix the cable to the side wall.
Front
Cable routing
4-21 (28)
ABB
Front
Cable transit
Grounding brackets
for overall cable shield
Cable duct
Figure 4-24 Cable Transit
Run the cable along the horizontal cable duct and down through the
vertical duct to its destination inside the COU (see Figure 4-25
regarding COU type 1 and Figure 4-26 regarding COU type 2).
4-22 (28)
ABB
Rubber grommets
Figure 4-26 Routing Control Cable in COU Type 2
Grounding Cable
Shields
IMPORTANT!
The individual shields and the overall shield of encoder cables must not
be connected to the terminals of the encoder adapter but to the separate
shield grounding point next to it (see Figure 4-27).
The unshielded cable ends must be as short as possible. The shield ends
which are fixed to the grounding clamp must be not longer than 50 mm.
The shields of serial communications cables, however, are terminated at
the fieldbus adapter as shown on the Converter Hardware Diagram in
Appendix D - Electrical Diagrams.
4-23 (28)
ABB
SK 9
SK 10
SK 8
4-24 (28)
ABB
4.8
IMPORTANT!
This section is only applicable for marine converters used for azipod
propulsion.
In applications for azipod propulsion, fibre-optic cables are used for signal
transmission between position encoder(s) and the associated receiver(s)
in the converter. The number of the pulse encoders and the location of the
receiver(s) in the converter depends on the application. The receiver(s)
can either be installed in the Water Cooling Unit (WCU) or a Control Unit
(COU). See Converter Hardware Diagram in Appendix D - Electrical
Diagrams for project specific details.
NOTICE!
If a fiber-optic cable is damaged or improperly installed, data transmission
can be affected and the equipment can mulfunction. To prevent such
problems always follow the handling and installation guidelines.
Handling and
Installation Guidelines
The conduit starts at the Azipod Information Unit (AIU) and ends
inside the converter.
On the AIU side, the conduit starts at the rubber cable penetrations
through which the fiber-optic cable is entered into the cabinet.
On the converter side, the conduit enters through the entry plate with
about 10 to 20 mm of conduit extending from the entry plate.
Routing Cables
through WCU
Cover the cable end with a cap to protect the tip of the fiber against
scratches before pulling the cable through the conduit.
Do not exceed the maximum tensile load and the minimum bend
radius of the cable. See cable specification for information.
When using cable ties be careful not to deform the fiber-optic cable.
Do not use tie guns.
Proceed as follows when routing cables through the Water Cooling Unit
(WCU):
4-25 (28)
ABB
After the cables have been pulled through the cable transit inside the
WCU run the cables through the WCU as indicated with the dashed
line in Figure 4-29.
Cable transit
Receiving connector
4-26 (28)
ABB
4.9
4-27 (28)
ABB
4-28 (28)
ABB
Chapter 5 - Information on Commissioning
5.1
familiar with medium and low voltage equipment and with local safety
regulations,
5-1 (2)
5-2 (2)
ABB
ABB
Chapter 6 - Operation
The instruction manual applicable for the converter is filed at the end of the
manual.
6-1 (2)
ABB
Chapter 6 - Operation
6-2 (2)
ABB
Chapter 7 - CDP Control Panel
7.1
Overview
The CDP control panel is the basic user interface for operating, controlling
and monitoring the converter.
The panel messages and parameter settings used in this chapter are
typical examples to illustrate the related instructions and display functions.
They may differ from the actual messages and parameter settings in your
converter.
Alphanumeric display
(4 lines x 20 characters)
Enter button
Start button
Stop button
7-1 (12)
ABB
Keypad Modes
7.2
Identification mode
Identification Mode
After the converter has been energized or after the panel has been
connected to the converter for which the auxiliary voltage has been
switched on already, the identification display appears showing the panel
version and then the ID-number of the converter. When the control panel
is being initialized the display changes as follows:
........
After 2-3 seconds:
1 L ->
0.0 rpm 0
Status...
Earth Iso clos
MotorSpeed 0.00 rpm
Power
0.0 %
7-2 (12)
ABB
7.3
The Actual Signal Display appears first when the Actual Signal Display
mode has been selected. However, when the converter is in a fault
condition, the Fault Display will be shown instead.
The Actual Signal Display is used to monitor the converter without
interfering the operation of the converter. Three selectable actual values
are shown continuously on the display.
The panel will automatically return to the Actual Signal Display mode
from other modes within one minute when no buttons are pressed
(exceptions: Status Display and Common Reference Display when in
Drive Selection mode and Fault Display mode).
A complete list of selectable actual signals can be found in the Signal and
Parameter Table.
The fault memory includes information on the 64 most recent fault events
that occurred in the converter. The name of the fault and the actual time
are displayed. The procedure for selecting and clearing the fault history is
described in Table 7-3.
When a fault or warning is generated in the converter, the message will be
displayed immediately, except when in Drive Selection mode.
Changing from the Fault Display mode to other display modes is possible
without resetting the fault first. When no buttons are pressed, the fault or
warning text is displayed as long as the fault is pending.
The Actual Signal Display mode is selected by pressing the ACT button.
ACT
1 L ->
600.0 rpm 0
Status...
Rdy MCB on
MotorSpeed 0.00 rpm
Power
0.0 %
7-3 (12)
ABB
When in Actual Signal Display mode, the fast UP/DOWN buttons allow
to toggle between Actual Signal Display and Fault History Display.
1 L ->
600.0 rpm 0
1 LAST FAULT
Overspeed
001231 12:30:02.3256
Table 7-1
Step
Function
1.
Button to be
pressed
HOLD
ACT
2.
RELEASE
ACT
Table 7-2
Function
1.
Button to be
pressed
ACT
2.
1 L ->
600.0 rpm 1
DriveStatus Running
MotorSpeed 600.00 rpm
Power
75.0 %
3.
Display
1 L ->
600.0 rpm 0
Status
ReadyOn
MotorSpeed 0.00 rpm
Power
0.0 %
1 L ->
600.0 rpm 0
Status
ReadyOn
MotorSpeed 0.00 rpm
Power
0.0 %
ENTER
7-4 (12)
1 L ->
600.0 rpm 1
DriveStatusWord
MotorSpeed
Power
Step
4.
Display
to select a parameter
group
1 L ->
600.0 rpm 0
1 Actual Signals
13 Power
0.0 %
1 L ->
600.0 rpm 0
2 Actual Signals
01 Excitation Cur
ABB
Table 7-2
Step
Function
5.
6.a
6.b
Button to be
pressed
Display
1 L ->
600.0 rpm 0
1 Actual Signals
09 NP Voltage
0.0 V
ENTER
ACT
PAR
FUNC
DRIVE
1 L ->
600.0 rpm 0
Status
ReadyOn
MotorSpeed 0.00 rpm
NP Voltage 0.0 V
1 L ->
600.0 rpm 0
Status
ReadyOn
MotorSpeed 0.00 rpm
Power
0.0 %
Table 7-3
Step
Function
1.
Button to be
pressed
ACT
2.
3.
Display
1 L ->
600.0 rpm 0
Status
ReadyOn
MotorSpeed 0.00 rpm
Power
0.0 %
1 L ->
600.0 rpm 0
1 Last Fault
+ Panel Lost
Power
0.0 %
1 L ->
600.0 rpm 0
2 Last Fault
Speed Ref Lost
980224 10:45:32.0705
1 L ->
1 Last
600.0 rpm 0
Fault
H
Min
7-5 (12)
ABB
Table 7-3
Step
Function
4.
Table 7-4
Button to be
pressed
1 L ->
600.0 rpm 0
Status
ReadyOn
MotorSpeed 0.00 rpm
Power
0.0 %
Step
Function
1.
Button to be
pressed
ACT
2.
7.4
Display
Display
1 L ->
600.0 rpm 0
ACS 1000
*** Fault ***
Panel Lost
1 L ->
600.0 rpm 0
Status
ReadyOn
MotorSpeed 0.00 rpm
Power
0.0 %
Parameter Mode
NOTICE!
Parameters must only be set by qualified personnel. Do not change any
parameter, if the meaning of the parameter and the effects of the change
are not fully understood. Running the drive system with incorrect data can
result in improper operation, reduction of control accuracy and damage of
equipment.
Parameters allow the converter to be configured and set-up specifically for
an application (see also Signal and Parameter Table).
Parameters are organized in functional groups. All control functions are
represented by a parameter group and can be activated and set-up
individually.
Selecting Parameters
7-6 (12)
The Parameter mode is used to check and change parameters. When this
mode is entered for the first time after the auxiliary voltage of the converter
has been switched on, the display will show the first parameter of
parameter group 11. The next time, the Parameter mode is entered, the
previously selected parameter is shown.
ABB
** Warning **
Step
Function
1.
Button to be
pressed
PAR
2.
to select a different
group
3.
to select a parameter
4.
6.a
1 L ->
600.0 rpm 0
75 OPTION MODULES
01 IOEC3 OptionBoard
YES
1 L ->
600.0 rpm 0
75 OPTION MODULES
01 IOEC3 OptionBoard
YES
1 L ->
600.0 rpm 0
75 OPTION MODULES
02 IOEC4 OptionBoard
NO
ENTER
5.
Display
1 L ->
600.0 rpm 0
75 OPTION MODULES
02 IOEC4 OptionBoard
[NO]
1 L ->
600.0 rpm 0
75 OPTION MODULES
02 IOEC4 OptionBoard
[YES]
ENTER
1 L ->
600.0 rpm 0
75 OPTION MODULES
02 IOEC4 OptionBoard
YES
7-7 (12)
ABB
Table 7-5
Step
Function
6.b
Button to be
pressed
ACT
PAR
FUNC
DRIVE
Display
1 L ->
600.0 rpm 0
75 OPTION MODULES
02 IOEC4 OptionBoard
NO
7.4.1
Parameter Lock
Unwanted parameter entry can be prevented by activating the Parameter
Lock function which is part of group 16 SYSTEM CTR INPUTS.
The Parameter Lock is activated by setting parameters 16.02 and 16.03
accordingly. The user pass code can be changed by setting parameters
16.04 and 16.05. For more details see Signal and Parameter Table.
To activate the Parameter Lock:
7.5
Set the correct pass code. If not known see Signal and Parameter
Table for details.
Function Mode
Step
Function
1.
Button to be
pressed
FUNC
7-8 (12)
Display
1 L ->
0.0 rpm 0
UPLOAD
<= <=
DOWNLOAD
=> =>
CONTRAST
4
ABB
Table 7-6
Step
Function
2.
to select a function (a
blinking cursor indicates
the selected function)
Button to be
pressed
Display
1 L ->
UPLOAD
DOWNLOAD
CONTRAST
3.
ENTER
4.
5.a
5.b
ENTER
ACT
PAR
FUNC
DRIVE
0.0 rpm 0
<= <=
=> =>
4
1 L ->
0.0 rpm
CONTRAST
[4]
1 L ->
0.0 rpm
CONTRAST
[6]
1 L ->
0.0 rpm 0
UPLOAD
<= <=
DOWNLOAD
=> =>
CONTRAST
6
1 L ->
0.0 rpm 0
UPLOAD
<= <=
DOWNLOAD
=> =>
CONTRAST
4
7.6
7.6.1
Operational Commands
Selecting Local/Remote
Local control mode is selected by pressing the
panel.
Local Control
LOC
REM
7-9 (12)
ABB
Remote Control
Selecting Local/Remote
Button to be
pressed
Step
Function
1.
2.
LOC
REM
1 ->L
Status
MotorSpeed
Power
550.0 rpm 1
Running
0.00 rpm
0.0 %
1 ->
Status
MotorSpeed
Power
550.0 rpm 1
Running
0.00 rpm
0.0 %
7.6.2
Display
LOC
REM
When the motor is running, the arrow indicates the actual sense of
rotation.
When the motor is not running, the arrow indicates the preselected
sense of rotation.
1 L <600.0 rpm 1
Status
Running
MotorSpeed 600.00 rpm
Power
40.0 %
When the direction of rotation is changed while the motor is running, the
speed will automatically ramp to zero and the motor will accelerate in
opposite direction to the preset speed. The direction of the arrow on the
display changes to the new direction when the motor has reached zero
speed.
7-10 (12)
ABB
7.6.3
Entering a Setpoint
The setpoint can be changed via the control panel at any time, when set
to LOCAL.
Table 7-8
Entering a Setpoint
Step
Function
1.
2.
3.
Button to be
pressed
ACT
PAR
FUNC
600.0 rpm 1
Running
600.00 rpm
50.0 %
1 L ->
[ 550.0 rpm] 1
Status
Running
MotorSpeed 550.00 rpm
Power
50.0 %
(fast change)
1 L ->
Status
MotorSpeed
Power
1 L ->
[ 600.0 rpm] 1
Status
Running
MotorSpeed 600.00 rpm
Power
50.0 %
REF
(slow change)
4.
Display
ACT
PAR
FUNC
DRIVE
1 L ->
Status
MotorSpeed
Power
550.0 rpm 1
Running
550.00 rpm
50.0 %
7-11 (12)
ABB
7-12 (12)
ABB
Chapter 8 - Maintenance and Troubleshooting
Maintenance and parts replacement on the converter must only be carried
out by qualified personnel in compliance with local regulations.
It is strongly recommended to carry out all maintenance work according to
the maintenance schedule at the end of this chapter and the applicable
service instructions, on time and at the stated intervals.
During the warranty period, any repair work must be carried out
exclusively by ABB service personnel. After the warranty period, repair
work may only be carried out by qualified personnel.
ABB offers maintenance and service training courses. Customer staff
having successfully attended such courses, will be certified to do
maintenance and repair work on the converter. To maintain safe and
reliable operation of the converter, ABB recommends taking out a service
contract with the ABB service organization. For more information contact
the ABB service organization. For contact address see section General
Information.
All maintenance activity should be recorded in the maintenance log book
including:
Date and time of the maintenance work
Description of the maintenance work
In case of water-cooled converters:
Conductivity, temperature, pressure and water level
of the cooling water before and after the maintenance
routine
Supplementary information on maintenance and troubleshooting can be
obtained from the following manuals:
8-1 (4)
ABB
8.1
Safety Instructions
DANGER!
Hazardous voltage!
Do not try to gain access to the converter transformer, the medium voltage
units of the converter nor the motor as long as the drive system is
energized and not grounded.
DANGER!
Voltages from external control circuits may be present inside the
converter, even if mains and auxiliary power are shut off. Take appropriate
measures before working on the converter: de-energize and disconnect all
external devices!
DANGER!
The driven machine can cause the motor to rotate! Always disconnect,
short-circuit or block the motor before work is started.
NOTICE!
Before power is applied to the converter, check that:
NOTICE!
The cooling system may start automatically as soon as the auxiliary
voltage is switched on.
8-2 (4)
ABB
8.2
8.2.1
Cleaning
Dust on electrical components and wiring can cause malfunction and
damage the components.
Proceed as follows:
8.2.2
Check all power and control cable connections and tighten them if
necessary. Check that all plugs and connectors are tight.
IMPORTANT!
Capacitor bushings will be damaged when excessive force is applied. Do
not exceed the maximum tightening torque when tightening the capacitor
terminals. The tightening torque values are printed on a label which is
attached on the capacitor. If not otherwise specified, the maximum torque
must not exceed 20 Nm.
8-3 (4)
ABB
8.3
Do not switch off the auxiliary voltage or try to reset a fault message
before all essential information at the time of the occurance of the
fault condition has been saved.
Call up the Fault History Display on the CDP control panel. See
Chapter 7 - CDP Control Panel for further information.
Do not clear the fault buffer now!
Save the content of the data logger, when a PC is available which has
the DriveWindow or DriveDebug tool installed.
The data logger provides useful information (e.g. waveforms of
voltage, current, torque etc.) for efficient troubleshooting.
After the fault has been rectified, start the converter as described in
Chapter 6 - Operation.
8-4 (4)
ABB
Maintenance Schedule
0
Start-up
R
I
I
I
I
I
I
R
I
R
I
I
I
I
R
I
I
I
I
I
I
R
R
R
R
I
I
R
R
I
I
I
I
I
I
R
I
R
R
I
I
R
I
I
I
I
I
I
R
R
R
I
I
I
R
R
I
I
I
I
I
I
R
I
R
R
I
I
I
R
I
I
I
I
I
I
R
R
R
R
I
R
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
14
15
16
17
18
19
20
R
I
I
I
I
I
I
R
I
R
I
I
I
I
R
I
I
I
I
I
I
R
R
R
R
I
I
R
R
I
I
I
I
I
I
R
I
R
R
I
I
R
I
I
I
I
I
I
R
R
R
I
I
I
R
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
P
P
P
I
I
I
I
P
I
I
I
I
I
I
I
R
P
P
P
I
I
I
I
I
I
I
I
I
I
I
I
I
P
P
P
I
I
I
I
I
I
I
I
I
I
I
I
I
P
P
P
Cooling
Air Filters
Cooling fan (if installed)
De-ionizer and mech. filters
Cooling pump seals
Cooling pumps
Heat exchanger
Aux Cooling fan (if installed)
Aging
Battery of UPS (if installed)
Connections and Surroundings
Cable and DC Bus connection
torques
Dustiness, corrosion and
temperature
Improvements
SW / HW upgrade
Based on product notes
Measurements
Basic measurements with aux.
supply voltage / control of
protection settings
Optical connected boards with
transmitter
Fiber optic cables
Clamp capacitors
Snubber capacitors
DC capacitors (CBU)
Spare Parts
Spare Parts
Legend:
Replacement of component
Inspection (visual inspection, correction and replacement if needed)
Performance of on-site work (commissioning, tests, measurements, etc.)
R
I
P
1 (2)
ABB
2 (2)
ABB
ACS 6000
Medium Voltage Drives
3 bis 27 MVA
Operating Instructions
ACS 6000 with Line Supply Unit (LSU)
ABB
Document No.:
Issued:
13-03-2006
ABB reserves all rights to this document, also in the event of patent issue
or registration of any other industrial property protection right. Misuse, in
particular duplication and forwarding to third parties, is not permitted.
This document has been checked with due care and attention. However,
should the user find any errors, these should be reported to ABB.
ABB aims to maintain the most modern standard, therefore, entries in this
manual may differ from the actual product.
ABB
Table of Contents
Chapter 1 - Overview
1-1
2-1
2.1
2.2
2.3
2.3.1
2.3.2
2.4
2-1
2-1
2-3
2-3
2-4
2-5
Control Panels
Switches
Control Panels
Control Panel on COU 1
Control Panel on COU 2
Grounding Switch
Chapter 3 - Operation
3-1
3.1
3.1.1
3.1.2
3.2
3.3
3.4
3.5
3-1
3-1
3-2
3-4
3-5
3-6
3-7
Starting
Checks before Switching on
Starting the Converter
Stopping
Deenergizing
Emergency Off
Alarm and Fault Messages
1 (2)
ABB
2 (2)
ABB
Chapter 1 - Overview
NOTICE!
Only qualified personnel shall operate the drive system, i.e. personnel
who are familiar with the machine and the operation of the drive system
and the hazards involved.
Refer to Users Manual, Chapter 1 - Safety, for explanation on how the
safety messages are categorized and used in this manual.
This manual outlines the local operation of the converter using the CDP
control panel and the control switches as illustrated in section Chapter 2 Local Control Elements after the converter has been installed and
commissioned.
Remote control of the converter via a PLC or remote stations is not
described in this manual. If the converter is controlled from remote, see
the applicable manuals for information.
1-1 (2)
ABB
Chapter 1 - Overview
1-2 (2)
ABB
Chapter 2 - Local Control Elements
The location of the control units (COU) in the drive and the location of the
operating devices are illustrated on the layout drawing in Appendix B Mechanical Drawings.
2.1
Overview
2.1.1
Control Panels
The following control panels are provided for local operation of a converter
which is equipped with a line supply unit (LSU) and one or several inverter
units (INU):
2.1.2
Switches
Main Supply
The on/off switches for the main supply are installed on the door of COU 1
(see Figure 2-1).
Emergency Off
Grounding Switch
The grounding switch is installed on the capacitor bank unit (CBU) (see
Figure 2-3). The switch can only be actuated if released by the converter.
DC Link Isolator
Output Switches
2-1 (6)
ABB
IMPORTANT!
The user of the drive system must ensure that the motor does not rotate
before the switch is actuated.
The motorized switches are opened or closed automatically by the
converter depending on the operating status of the drive and the settings
of the parameters provided for this function. The possible parameter
settings are shown in Appendix D - Signal and Parameter Table.
!
Lamp Test
IMPORTANT!
The operating personnel must be informed about the types of output
switches present in the converter and the parameter settings for opening
and clossing.
2-2 (6)
ABB
2.2
2.2.1
Control Panels
Control Panel
used to start and stop the motor
displays status messages of the converter
displays alarm and fault messages
used to reset alarm and fault messages
Illuminated Pushbuttons
OFF opens the main cicuit breaker
ON closes the main cicuit breaker
Alarm / Fault Lamp
ALARM: flashing light
Fault: permanent light
Emergency off Reset Switch
Figure 2-1
2-3 (6)
ABB
2.2.2
Control Panel
used to start and stop the motor
displays status messages of the converter
displays alarm and fault messages
used to reset alarm and fault messages
Figure 2-2
2-4 (6)
ABB
2.3
Grounding Switch
Grounding Switch
used to ground the converter
2.4
Figure 2-4
Opening and closing of the DC link isolator is only possible after the DC
link has been deenergized. When the converter is in operation, it must first
be stopped and the DC link be discharged. Discharging of the DC link is
initiated by opening the main circuit breaker. The discharged condition of
the DC link is indicated with the lamp Grounding Switch Unlocked. As
soon as the lamp lights up, the grounding switch of the converter (located
on the door of the CBU) can be turned into the grounded position and
operation of the DC link isolator is released. When the signal is present,
the isolator moves to the position which has been selected.
2-5 (6)
ABB
2-6 (6)
ABB
Chapter 3 - Operation
3.1
3.1.1
Starting
Check that no tools and foreign objects are left inside the converter.
Verify that:
all internal circuit breakers of the converter have
been closed,
the auxiliary power supply of the converter has been
switched on.
See Appendix C - Electrical Diagrams to identify the circuit breakers.
NOTICE!
The cooling system may start automatically as soon as the auxiliary
voltage has been switched on.
4
Check that all doors have been closed and locked and all covers have
been mounted.
Medium voltage units of the converter include an interlocking system
which operates in conjunction with the grounding switch and the
electrical interlocks from the main circuit breaker.
The interlocking system ensures that power cannot be initialized to
the converter unless all doors have been closed and the grounding
switch has been turned to position
(not grounded).
(grounded).
Doors of control and cooling cabinets are not integrated into the
interlocking system and can always be opened.
3-1 (8)
ABB
Chapter 3 - Operation
DANGER!
High Voltage!
All bolted covers must be fitted to prevent unintended touching of
energized components.
5
Figure 3-1
3.1.2
REM
button.
3-2 (8)
ABB
Chapter 3 - Operation
1 L ->
0.0 rpm 0
Status...
ReadyOn
MotorSpeed 0.00 rpm
Power
0.0 %
11
Press the ON button on the door of COU1 to charge the DC link. The
ON button flashes during charging:
The status line of the INU control panel changes to Charging:
1 L ->
0.0 rpm 0
Status...
Charging
MotorSpeed 0.00 rpm
Power
0.0 %
After charging has been finished, the main circuit breaker closes
automatically, the ON button lights up permanently and the display of
the first INU control control panel and the additional control panels (if
present) changes to ReadyRun:
1 L ->
0.0 rpm 0
Status...
ReadyRun
MotorSpeed 0.00 rpm
Power
0.0 %
All inverters can now be started.
12 Enter a setpoint.
See User Manual, Chapter 7 - CDP Control Panel, for information on
entering a setpoint.
3-3 (8)
ABB
Chapter 3 - Operation
1 L ->
600.0 rpm 0
Status...
Magnetizing
MotorSpeed 0.00 rpm
Power
0.0 %
After the motor has been magnetized, the motor speed is ramped up
to the setpoint. As soon as the motor starts to turn the display of the
INU control panel shows Running:
1 L ->
Status...
600.0 rpm
Running
MotorSpeed
Power
3.2
600.00 rpm
30.0 %
Stopping
Proceed as follows to stop a motor:
The motor stops according to the preset stop function and the
converter stops modulating. Stop modes are preset in parameters.
While the motor stops, the status line of the display shows Stopping:
1 L ->
600.0 rpm 1
Status...
Stopping
MotorSpeed 300.00 rpm
Power
20.0 %
As long as the stopping sequence is in progress, the converter can
always be restarted by pressing the
panel.
When the converter has stopped modulating, the CDP control panel
displays Ready to Start:
1 L ->
600.0 rpm 0
Status...
Rdy to Strt
MotorSpeed
0.00 rpm
Power
0.0 %
3-4 (8)
ABB
Chapter 3 - Operation
As long as the main circuit breaker has not been opened, the motor
can be started again.
.
3.3
Deenergizing
DANGER!
Hazardous voltage!
Do not try to gain access to the converter transformer, the medium voltage
units of the converter nor the motor as long as the drive system is
energized and not grounded.
To disconnect the converter from the main power supply, do the following:
1
Press the Offline button to disconnect the converter from the main
power supply. The following happens:
Main circuit breaker opens
DC link discharges
Offline button lights up
After the DC link has been discharged, the display shows:
1 L ->
600.0 rpm 0
Status...
Rdy MCB on
MotorSpeed
0.00 rpm
Power
0.0 %
IMPORTANT!
Do not turn the grounding switch to position grounded, before the
light GROUNDING SWITCH UNLOCKED is on. Otherwise, the switch will
be damaged.
3-5 (8)
ABB
Chapter 3 - Operation
Figure 3-2
1 L ->
600.0 rpm 0
Status...
ErthIsoClos
MotorSpeed
0.00 rpm
Power
0.0 %
5
3.4
Emergency Off
The emergency off button is located on each control unit of the converter
(see also Figure 2-1).
Figure 3-3
3-6 (8)
ABB
Chapter 3 - Operation
1 L ->
600.0 rpm 0
Status...
EmergencyOff
MotorSpeed
0.00 rpm
Power
0.0 %
The converter can be started again after the emergency off button has
been extracted and the reset button on the control panel has been
pressed. The emergency off button returns to its initial position when
turned to the right.
3.5
Fault: a fault always shuts down the affected inverter or the whole
drive. The type of shut-down depends on the origin of the fault.
In general, a fault condition must be corrected and the fault be
manually reset before the converter can be started again.
Depending on the type of fault, the main circuit breaker (MCB) is
opened by the converter or stays closed. Since the MCB is controlled
and monitored entirely by the converter, no external opening
command must be given to the MCB when a fault condition occurs.
Some of the alarm and fault messages are related to other equipment in
use (MCB, transformer, cooling system) and the configuration of the drive
system. For more information on alarms and faults see Signal and
Parameter Table.
3-7 (8)
ABB
Chapter 3 - Operation
3-8 (8)
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without ex press authority is strictly
forbidden.
ABB Swizerland Ltd
MV - Drives
Specification
For
Main Circuit Breaker
Issued
Dietmar Gamp
13.10.2005
Check / rel.
Werner Kpfer
21.10.2005
Resp. dept.
No. of sh.
4
Protection Design Requirements
ATDAD
Document No. Typ Part
3BHS 125149E81
Lang.
en
Rev. ind.
Sheet
1 Notice of Changes
Rev. Index
Page
Description
Date
Chap.
-
Dept. / Name
All
13.10.2005 / Ga
2 Table of Contents
1
3BHS 125149E81
Lang.
en
Rev. ind.
Sheet
3BHS 125149E81
Lang.
en
Rev. ind.
Sheet
3.1.2
3.1.3
Overload Protection
The last area, identified, as Overload Protection should provide long-term overload
protection with an inverse time characteristic. This area is intended to protect the
transformer and cables from long term thermal overload.
3BHS 125149E81
Lang.
en
Rev. ind.
Sheet
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
ABB Swizerland Ltd
ACS 6000
Specification
For
Main Circuit Breaker
Issued
Dietmar Gamp
13.10.2005
Check / rel.
Werner Kpfer
21.10.2005
Resp. dept.
ATDAD
11
No. of sh.
3BHS 125149E60
Lang.
en
Rev. ind.
Sheet
1 Notice of Changes
Rev. Index
Page
Description
Date
Chap.
Dept. / Name
All
13.10.2005 / Ga
5, 11
20.03.2006 / Ga
All
18.04.2006 / Ga
2 Table of Contents
1
Notice of Changes
Table of Contents
Abstract
3.1
3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
3.2
3.2.1
3.2.2
MCB operation in Test Position (MCB disconnected from the Bus Bar)
3.2.3
3.2.4
3.2.5
3.2.5.1
3.2.5.2
Opening loop with two opening coils and trip circuit supervision (Option for marine application) 10
3.2.5.3
Opening loop with two opening coils, Second coil (YO 2) for 230VAC operation only (Option) 11
3BHS 125149E60
Lang.
en
Rev. ind.
Sheet
Abstract
The Main Circuit Breaker (MCB) is one of the most important devices to protect the whole
system in case of a failure. In spite of the high reliability of the drive, faults might happen
because of certain unfortunate circumstances like human failure, material defects, etc. In
such a situation the correct operation of the Main Circuit Breaker will protect the drive for
risks of damages. Therefore a correct operation of the Main Circuit Breaker is inalienable.
This document specifies a proper Main Circuit Breaker for the ACS 6000 drive.
The Main Circuit Breaker should preferably be an SF6-gas insulated or a vacuum type circuit
breaker. It should also meet the specific drive requirements that need a correct coordination
with the instrumentation and protection equipment.
The MCB must be able
3.1
To connect and maintain nominal load currents and clear short-circuit currents
3.1.1
<= 30 VDC
6,0 A
2,4 A
<= 220VDC
0,5A
Table 1
3BHS 125149E60
Lang.
en
Rev. ind.
Sheet
<= 30 VDC
6,0 A
6,0 A
<= 220VDC
2,3 A
Table 2
3.1.2
Input to close in response to the close command MCB order close from the ACS
6000 drive control system
Input to open in response to the open command MCB order open 1 and MCB
order open 2 from the ACS 6000 drive control system
Input to trip in response to the trip command, MCB order trip from the control
circuit undervoltage coil.
In order to ensure the correct operation of the ACS 6000 drive under fault
condition a maximum total MCB breaking time of 60ms has to be guaranteed.
Breaking time is the defined time interval between the energizing of the
opening coil and the extinguishing of the current flow in all poles.
The ACS6000 control part itself will guarantee to keep the additional delay time
to less than 15ms in case of short circuit. Therefore an overall response time of
less than 75 ms can be reached what is required due to the fuse-less design of
the converter.
3.1.3
3.1.4
Relay output indicating MCB status closed to the ACS 6000 drive control system.
Relay output indicating MCB status open to the ACS 6000 drive control system.
Relay
output
indicating
MCB
pre-trip,
direct
to
the
drive.
The signal must be generated as fast as possible, before the MCB opens.
Hence an additional auxiliary relay for the signal MCB pre-trip shall be
avoided due to the time limitation.
Relay output indicating MCB IS AVAILABLE, i.e. MCB not in test position, not
locked, not drawn out, not grounded, not faulty to the main control system.
3BHS 125149E60
Lang.
en
Rev. ind.
Sheet
3.1.5
MV - Switchgear
MCB
MCB order close
MCB status closed
-Q0
Protection
Relay
(*1) or (*2)
Either the signal MCB
Oredr Open 2" or
MCB Oredr Trip can
be used to open the
main circuit breaker by
a second signal.
-Q5
Transformer
DI
ACS 6000
DO
3BHS 125149E60
Lang.
en
Rev. ind.
Sheet
3.2
3.2.1
Additionally to
not disturbed.
the
external
release
conditions
the
MCB
shall
be
MV-Switchgear
Main Circuit
Breaker
Earthing Switch
&
Release to close
Main Circuit Breaker
By Others
ABB
&
pre - trip
Controlvoltage available
3BHS 125149E60
Lang.
en
Rev. ind.
Sheet
MV-Switchgear
Synchronisation
Voltage
Main Circuit
Breaker
Earthing Switch
&
Release to close
Main Circuit Breaker
By Others
ABB
&
pre - trip
Controlvoltage available
MCB operation in Test Position (MCB disconnected from the Bus Bar)
Control switches, selector switches and status indication shall be provided on the
switchgear door.
Selector switch shall be two-position type, namely Local and Remote.
In test position the breaker can be closed either from the local push button or from
remote depending on the position of the selector switch.
If the selector switch is in remote it shall be possible to test all interlocks. Therefore all
circuit breaker indications as well as software and hardware interlock functions shall
remain operative
If the selector switch is in local it shall be possible to close the circuit breaker at any time.
Therefore no interlock function shall remain active
3.2.3
3BHS 125149E60
Lang.
en
Rev. ind.
Sheet
3.2.4
MCB
order close
MCB
order close
ACS 6000
MCB
(+ VDC)
External release
conditions
MCB Internal
release conditions
-Q0
A1
-YC
(ON)
A2
(0 VDC)
3BHS 125149E60
Lang.
en
Rev. ind.
Sheet
MCB pre-trip
(+)
DI
ACS 6000
MCB
(+ VDC)
MCB internal
trip signals
manual
open
MCB internal
trip signals
external
trip signals
external
trip
-Q0
-YO 1
(OFF)
A1
A1
A2
A2
MCB
internal trip
-YU
(Undervoltage coil)
(0 VDC)
Earthing switch
open
Undervoltage
coil
3BHS 125149E60
Lang.
en
Rev. ind.
Sheet
3.2.5.2 Opening loop with two opening coils and trip circuit supervision (Option for marine
application)
Should an interruption occur in a trip circuit a possible network fault would not be
disconnected, and the fault would have to be cleared by another protection relay
upstream in the power system. The supervision function is particularly important when
there is only one tripping coil.
The trip circuit supervision relay from ABB (Type SPER) or equivalent requires a
separate auxiliary supply voltage in the range 40 265Vdc, connected to input 18-28.
Normally the same voltage as that feeding the supervision circuit is used.
When terminals 11-21 are connected over the trip contacts, the current generator of the
supervision relay forces a small current to flow through the circuit to be supervised.
Please refer to document 1MRS 750231-MUM EN, SPER 1B1 C4, SPER 1C1 and
SPER 1C2 Supervision relay for details about the trip circuit supervision relay.
MCB pre-trip
(+)
DI
ACS 6000
MCB
40 . 265 VDC
Battery Sys . 1
40 .265 VDC
Battery Sys . 2
MCB internal
trip signals
ABB
SPER 11
external
trip signals
21 18
Type: 1C1
16
manual
open
MCB internal
trip signals
28
ABB
SPER 11
external
trip signals
15 17
16
remote
indication
28
external
trip
15 17
remote
indication
-Q0
MCB
internal trip
-Q0
A1
-YO 1
(OFF)
21 18
Ty pe: 1C1
-YO 2
(OFF)
A2
(0 VDC)
Earthing switch
open
A1
A2
(0 VDC)
Signal output MCB pre-trip, shall be sent to the drive as fast as possible, therefore
additional auxiliary relays for pre-trip indication shall be avoided due to time
requirements.
3BHS 125149E60
Lang.
en
Rev. ind.
Sheet
10
230VAC
from
ACS 6000
Contact close --> MCB
"OFF" command
MCB pre-trip
(+)
DI
ACS 6000
MCB
(+ VDC)
MCB internal
trip signals
MCB internal
trip signals
external
trip signals
external
trip signals
external
trip
-Q0
A1
-YO 1
(OFF)
manual
open
A1
-YO 2
(OFF)
A2
MCB
internal trip
A2
(0 VDC)
Earthing switch
open
3BHS 125149E60
Lang.
en
Rev. ind.
Sheet
11
ABB
ACS 6000
Medium Voltage Drives
3 to 27 MVA
Users Manual
Water Cooling Unit
with External Heat Exchangers
ABB
Project:
Tasnee Coperion
Order No.:
1-1042645
Document No.:
Issued:
26-06-2007
ABB
Table of Contents
Chapter 1 - Safety
1-1
2-1
2.1
2.2
2.3
2.4
2.5
2.5.1
2.5.2
2.5.3
2.6
2.6.1
2.6.2
2.6.3
2.6.4
2.7
3-1
3.1
3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
3.2
3.2.1
3.2.2
3.2.3
3-1
3-1
3-1
3-2
3-2
3-3
3-3
3-3
3-3
3-4
4-1
4.1
4.2
4-1
4-2
Water Conductivity
Water Pressure
1 (2)
ABB
4.3
Water Temperature
4-2
5-1
Appendices
2 (2)
ABB
Chapter 1 - Safety
This manual should be read thoroughly and understood before work on
the cooling system is started.
See ACS 6000 User's Manual, Chapter 1- Safety for explanation on how
the safety messages are categorized and used in this manual.
NOTICE!
The cooling system may start automatically as soon as the auxiliary
voltage is switched on. The pump is switched on depending on
temperature and conductivity of the pure water or internal air temperature.
NOTICE!
Valves, tubes and hoses are delicate parts. Do not bend or put any
pressure on the valves, tubes and hoses.
NOTICE!
Where possible, all components and sub-assemblies weighting over 25 kg
have been clearly marked with weight details. Pumps and electric motors
are equipped with lifting eyes as supplied by the manufacturers. If lifting of
heavy and/or awkwardly positioned items is necessary, extreme caution
shall be exercised. Safe, reliable mechanical lifting equipment shall be
used wherever possible. Under no circumstances shall items be lifted by
means of straps, ropes, chains etc. connected to piping or other system
components.
1-1 (2)
ABB
Chapter 1 - Safety
1-2 (2)
ABB
Chapter 2 - Starting up the Cooling System
NOTICE!
Do not run the pumps if the cooling circuit is empty, not even for a short
time. If a pump runs dry the pump seals will be damaged immediately.
2.1
Open valves V1, V2, V5, V51, V52, V91, V92 in the pure water circuit.
Open valves V31 and V32 ffnen, if an excitation unit (EXU) is part of
the drive.
Check that the following valves and vent plugs in the pure water
circuit are closed:
Drain valves V81, V82, V83, V84
Make-up water valve V55
Vent plug V70
Vent valve V75 (at heat exchanger E1)
Vent valve V76 at heat exchanger E2)
2-1 (12)
ABB
2.2
Check that the pipe joints are in place, properly adjusted and the
locking bolts are tightened.
The cooling system is filled through make-up water valve V55 (ISO-R ").
When filling the cooling system, deionized or distilled water shall be used
preferably. If deionized or distilled water is not available, the water must
have at least drinking quality, see Table 2-1.
If in doubt about the quality of the drinking water on your premises contact
your local water utility.
Table 2-1
Parameter
Value
pH
7 8.5
Specific conductivity
< 300 S / cm
Hardness
3 10 dH
Chloride (Cl)
Copper (Cu)
Undissolved particles
< 5 mgl
IMPORTANT!
!
!
IMPORTANT!
IMPORTANT!
A preset pressure is not needed in the expansion vessel.
Proceed as follows:
1
2-2 (12)
ABB
IMPORTANT!
Do not take off the cap of a vent valve completely. Only loosen it.
2
Fill the cooling system (max. 15 l/min) until the expansion tank is
approx. 80 % full.
Close the vent valves one after another when water starts to trickle
out of them.
Vent the pumps through the vent plug at the pump head (see Figure
2-1).
Vent plugs
Figure 2-1
6
2-3 (12)
ABB
2.3
Switch off the motor starters Q5002 and Q5003 of the pumps (see
Figure 2-3).
Close the disconnect terminals of each pump. They are located in the
terminal section located at the top of the cabinet (see Figure 2-2).
Pump 1
Pump 2
Figure 2-2
3
Disconnect Terminals
DANGER!
Hazardous voltage!
After switching on the auxiliary power supply, voltages up to 690 VAC are
present in the water cooling unit.
After switching on the auxiliary voltage, the alarm messages CW1
Pump1Overload and CW1Pump2Overload and the fault message
CW1 NoWtrPumpOn will come up on the display of the control panel
of COU 1.
Do not reset the alarms and the fault because they prevent the pumps
from being switched on automatically by the control system of the
converter.
4
2-4 (12)
ABB
IMPORTANT!
If a pump runs in the wrong direction of rotation, interchange any two of
the three phases U, V or W of the power supply cable feeding the water
cooling unit. Switch off the supply voltage before interchanging a phase
conductor.
Pump 1
Figure 2-3
Pump 2
Pump Motor Starters
Open valve V70 to release the air and close the valve again.
NOTICE!
Pay attention to the direction of the vent hole and make sure that escaping
water does not cause injury to persons or damage to the motor or other
components.
8
Vent the pumps according to section 2.2 Filling the Cooling System,
step 4.
Repeat the above procedure (step 6 to 7) two or three times until the
air is completely released from the water cooling circuit.
10 Check the water level in the expansion vessel. Add water if the level
is below 80 %.
11
Run the pump(s) for about 30 minutes to release all entrapped air
through the expansion vessel.
The pump(s) will be switched on automatically if the following conditions are fullfilled:
The auxiliary power supply is on
2-5 (12)
ABB
2.4
Starting up
Proceed as follows:
1
Check that valves of the heat exchanger which will be taken into operation are in the correct position (see also section 2.5 Changing over
the Heat Exchangers During Operation)
Check that:
The auxiliary power supply is switched on.
The motor starters of both pumps are switched on.
The emergency off is not activated (this condition
depends on parameter setting).
Any pump related alarms/faults displayed on the
control panel of COU 1 are reset.
Parameter 35.01 CW1 PUMPS AMOUNT is set to
TWO.
(If not familiar with checking and changing
parameters, see Chapter 7 - CDP Control Panel,
section 7.4 Parameter Mode of the User's Manual of
the converter).
If the above conditions are fulfilled, pump 1 will start to run automatically.
2-6 (12)
ABB
ment circuit can be increased. While pump 1 is running adjust the flow
in the water treatment circuit to a maximum of 15 l/min at the flow
regulating valve. When adjusting the flow, the alarm message CW1
IntCoolWtrFlow will appear on the display of the control panel on
COU 1 indicating that the water flow is low.
Adjust the flow in the water treatment circuit to approximately 5 l/min
at the flow regulating valve (B5523).
5
Switch on both motor starters and then reset the alarms and faults.
When all the above steps have been carried out in the correct manner, the
water cooling system is fully operational.
2-7 (12)
ABB
2.5
2.5.1
Overview
F3
F2
V75
V61
V63
V60
V62
V11
V13
Pure water
from converter
V32
V76
V18
V16
E1
E2
Pure water
to converter
V19
V12
V14
V85
V84
V86
V15
V83
V17
Raw water inlet
V20
Figure 2-4
2-8 (12)
Z2
ABB
The heat exchanger unit is equipped with two heat exchangers. One heat
exchanger is always in operation whereas the other unit is on standby.
Most of the pure water flows through the heat exchanger in operation.
Only a small part of the pure water is directed through the standby unit via
valve V32 to ensure that the water conductivity in the standby unit stays at
a low level.
The raw-water side of the standby heat exchanger should be drained to
prevent fouling. A bypass circuit as used on the pure-water side to allow a
small water flow, is not recommended. The small flow would lead to an
accumulation of slurry and particles inside the heat exchanger, which
could decrease the cooling capacity of the heat exchanger over time. The
standby heat exchanger shall therefore only be filled when a changeover
of the heat exchangers is required.
The changeover from one heat exchanger to the other is done manually.
2.5.2
2.5.3
Close the bleed and drain valves V78/V86 on the raw-water side.
Drain the heat exchanger on the raw-water side through valve V85 to
prevent fouling.
Close the bleed and drain valves V77/V85 on the raw-water side.
Drain the heat exchanger E2 on the raw-water side through valve V86
to prevent fouling.
2-9 (12)
ABB
2.6
2.6.1
2.6.2
Open valves V83, V85, V75 and V77 to drain the heat exchanger.
2.6.3
2-10 (12)
Open valves V84, V86, V76 and V78 to drain the heat exchanger.
ABB
2.6.4
2.7
2-11 (12)
ABB
IMPORTANT!
When filling cooling water while the converter is in operation, the drive may
trip on a conductivity fault. Fill the water in slowly to avoid a trip. Filling rate:
less or equal 2 l/min.
4
2-12 (12)
ABB
Chapter 3 - Draining the Cooling System
3.1
IMPORTANT!
When draining the cooling system according to section 3.1.1, 3.1.2 and
3.1.3, water remains in the deionizer vessel, the pumps and the filter. See
section 3.2 if the colling system has to be emptied completely.
Proceed as follows:
1
3.1.1
Open drain valve V82 and drain the cooling system through the
factory mounted water hose.
Draining takes about 1 to 2 hours depending on the filling quantity.
3.1.2
Connect the suction side of the filling pump to the make-up water
valve V55.
3-1 (4)
ABB
3.1.3
3.1.4
Open drain valve V81 and drain the cooling system through the
factory mounted water hose.
Before opening the drain plug take measures to catch the water.
Wrap a cloth around the drain plug to prevent water from spraying into
the cabinet.
Remove the drain plug of the resistor (required spanner size: 19 mm)
and catch the water with a suitable vessel.
Drain plug
Figure 3-1
3
3-2 (4)
Water-cooled Resistor
ABB
3.1.5
3.2
3.2.1
3.2.2
Loosen and slide aside the pipe joint which connects the water
cooling unit to the feeding pipe of the adjoining cabinet. Slide the pipe
joint into the adjoining cabinet to force the escaping water to run into
the water cooling unit.
Before opening the drain plugs take measures to catch the water.
Drain plugs
Figure 3-2
3-3 (4)
ABB
3.2.3
3-4 (4)
Open valve V55 and press air through the deionizer vessel until the
water stops running out of filter Z2.
ABB
Chapter 4 - Checking Actual Values
It is recommended to record the values of conductivity, water temperature
and pressure regularly to determine when water has to be added or the
ion exchange resin renewed.
Actual values can be monitored while the converter is in operation.
Water conductivity and pressure depend on the water temperature. Only
values registered at the same temperature should be compared.
DANGER!
Hazardous voltage!
When the drive is in operation, voltages are present in the control units.
Do not touch any live ciruitry.
4.1
Water Conductivity
The actual value of the water conductivity (displayed in S/cm) can be
read
on the conductivity meter B5503 in the WCU 1 or
on the control panel of COU 1.
Proceed as follows:
Reading the
Conductivity on the
Control Panel
Select the Actual Display mode on the control panel (see ACS 6000
User's Manual, Chapter 7 - CDP Control Panel, section 7.3 Actual
Signal Display Mode).
4-1 (2)
ABB
4.2
Water Pressure
The actual value of the water pressure (displayed in bar) can be read
on the pressure transmitter B5501 (output pressure)
in WCU 1 or
on the control panel of COU 1.
Proceed as follows:
Select the Actual Display mode on the control panel (see ACS 6000
User's Manual, Chapter 7 - CDP Control Panel, section 7.3 Actual
Signal Display Mode).
4.3
Water Temperature
The actual value of the water temperature (displayed in C) can be read
on the control panel of COU 1.
Proceed as follows:
Select the Actual Display mode on the control panel (see ACS 6000
User's Manual, Chapter 7 - CDP Control Panel, section 7.3 Actual
Signal Display Mode).
4-2 (2)
ABB
Chapter 5 - Tightening Torques, Threaded Connections
Table 5-1
Hexagon
Screw
Nut
Washer
(D x d x t)
Gasket
(D x d x t)
25
M12-55
M12
24 x 13 x 2
73 x 40 x 1.5
24 - 33 Nm
32
M16-65
M16
30 x 73 x 3
84 x 48 x 1.5
60 - 80 Nm
40
M16-65
M16
30 x 73 x 3
92 x 57 x 1.5
60 - 80 Nm
50
M16-70
M16
30 x 73 x 3
107 x 66 x 1.5
60 - 80 Nm
65
M16-70
M16
30 x 73 x 3
128 x 23 x 1.5
60 - 80 Nm
80
M16-75
M16
30 x 73 x 3
144 x 97 x 1.5
60 - 80 Nm
100
M16-80
M16
30 x 73 x 3
60 - 80 Nm
DN
5.1
5-1 (2)
5-2 (2)
ABB
ABB
Appendices
1 (2)
ABB
2 (2)
No.
Design change
V78 MOVED
Date
Design
Appr.
2007-05-02
EN
TI
F2
V61
FINE WATER
INLET ANSI 2"
V11
V75
V77
V60
V19
V16
RAW WATER
OUTLET
COUNTER
FLANGE
ANSI 3"
E1
V12
V83
DRAIN
HOSE 12
V15
V85
V13
V76
F3
V63
V32
V62
V78
V18
RAW WATER
INLET
COUNTER
FLANGE
ANSI 3"
E2
FINE WATER
OUTLET
ANSI 2"
V14
V17
V84
V86
Z2
V20
DRAIN
HOSE 12
Appr.
Design
Drawn
TI
EN
EN
Date
2007-03-06
AXELTOFTAVGEN 170
BOX 265
ABB SCHWEIZ AG
ACS 6000 029SG
HEAT EXCHANGER
WATER COOLING SYSTEM
FLOW DIAGRAM
S-261 23 LANDSKRONA
SWEDEN
Issue
Date
2007-05-02
2
Scale
Project No.
1: 1
3617
Drawing No.
3-3617-001
ABB
ACS 6000
Medium Voltage Drives
3 to 27 MVA
Data Sheet
Water Cooling Units
Closed to Atmospheric Pressure
ABB
Document No.:
Issued:
29-06-2005
ABB reserves all rights to this document, also in the event of patent issue
or registration of any other industrial property protection right. Misuse, in
particular duplication and forwarding to third parties, is not permitted.
This document has been checked with due care and attention. However,
should the user find any errors, these should be reported to ABB.
ABB aims to maintain the most modern standard, therefore, entries in this
manual may differ from the actual product.
ABB
Table of Contents
1
2
2.1
2.2
3
1-1
1-2
1-2
1-2
1-3
1 (2)
ABB
2 (2)
ABB
1
Industrial water
Deionized water
137 kW
270 kW
250 l/min
490 l/min
290 l/min
520 l/min
400 l/min
700 l/min
nominal 1
32C
32C
min.
10C
10C
37C
37C
min.
10C
10C
nominal
<0,3 S
<0,3 S
alarm
0,5 S
0,5 S
trip
0,7 S
0,7 S
40%
40%
40%
40%
70 kPa
140 kPa
350 kPa
350 kPa
650 kPa
650 kPa
1000 kPa
1000 kPa
nominal
max.
Inlet temperature
Outlet temperature
Conductivity
WCU-S-052SG
WCU-M-052SG
nominal 1
Flow
WCU-S-029SG
WCU-M-029SG
WCU-S-052SG
WCU-M-052SG
nominal
Glycol content 2
max.
Pressure drop 1
nominal
1000 kPa 1
Design pressure
Test pressure
1500 kPa
1000 kPa 1
1500 kPa
WCU-S-029SG
WCU-M-029SG
Pump motor power3
WCU-S-052SG
WCU-M-052SG
5.5 kW
50 Hz
6.3 kW
60 Hz
7.5 kW
50 Hz
8.6 kW
60 Hz
380 V
10.6 A
440 V
10.4 A
380 V
14.1 A
440 V
14.4 A
400 V
10.3 A
460 V
10.1 A
400 V
13.8 A
460 V
13.8 A
415 V
10.4 A
480 V
10.2 A
415 V
13.8 A
480 V
13.2 A
1 (4)
ABB
2
2.1
200
180
160
140
120
100
80
60
40
20
0
100
150
200
250
300
350
400
450
2.2
300
250
200
150
100
50
0
100
200
300
400
500
600
700
800
2 (4)
ABB
3
Value
pH
79
Specific conductivity
< 500 S / cm
Hardness
3 15 dH
Cloride (Cl)
Undissolved particles*
0 - 300 mg CaCO3/l
The materials used in the external cooling system on the raw water side
are stainless steel (AISI 316 and AISI 304L) and NBR rubber. Any
chemicals compatible with these materials may be used as additives.
3 (4)
ABB
4 (4)
NO
PAGE
DESIGN CHANGE
DATE
SIGN
APPR
1 UNITS
Appr
Design
TI
EN
Drawn
EN
Date
2007-03-06
Issue
Date
1
Project No.
3617
2007-03-06
No. of pages
1(3)
Dwg No.
LIST OF COMPONENTS
4-3617-050
AXELTOFTAVGEN 170 BOX 265 S-261 23 LANDSKRONA, SWEDEN PHONE: +46 418-45 07 00 FAX: +46 418-120 19
LIST OF COMPONENTS
ITEM QTY
DESCRIPTION
MANUFACTURER
TYPE
DATA
CONNEC
Dwg No.:
4-3617-050
Issue:
MATERIAL
REM
ART:NO AS
E1
HEAT EXCHANGER
TRANTER
GC-16M-34
2100027 3
E2
HEAT EXCHANGER
TRANTER
GC-16M-34
2100027 3
F2
SAFTEY VALVE
ARMATEC
AT4587-D4-9,0-20NPT
STAINLESS STEEL
F3
SAFTEY VALVE
ARMATEC
AT4587-D4-9,0-20NPT
STAINLESS STEEL
V11
BALL VALVE
VENTIM
VM 4492
DN50
AISI316L
3120179 3
V12
BALL VALVE
VENTIM
VM 4492
DN50
AISI316L
3120179 3
V13
BALL VALVE
VENTIM
VM 4492
DN50
AISI316L
3120179 3
V14
BALL VALVE
VENTIM
VM 4492
DN50
AISI316L
3120179 3
V15
BALL VALVE
VENTIM
VM 4492
DN50
AISI316L
3120179 3
V16
BALL VALVE
VENTIM
VM 4492
DN50
AISI316L
3120179 3
V17
BALL VALVE
VENTIM
VM 4492
DN50
AISI316L
3120179 3
V18
BALL VALVE
VENTIM
VM 4492
DN50
AISI316L
3120179 3
V19
BALL VALVE
VENTIM
VM 4492
DN50
AISI316L
3120179 3
V20
BALL VALVE
VENTIM
VM 4492
DN50
AISI316L
3120179 3
V32
BALL VALVE
DIE ERSTE
VM 4357
V60
BALL VALVE
DIE ERSTE
VM 4359
ISO-Rp3/4
AISI316/304
V61
BALL VALVE
DIE ERSTE
VM 4359
ISO-Rp3/4
AISI316/304
V62
BALL VALVE
DIE ERSTE
VM 4359
ISO-Rp3/4
AISI316/304
V63
BALL VALVE
DIE ERSTE
VM 4359
ISO-Rp3/4
AISI316/304
V75
DEAERATION VALVE
WHITEY
SS-4P-4RT
ISO-R 1/4
AISI316
3120139
V76
DEAERATION VALVE
WHITEY
SS-4P-4RT
ISO-R 1/4
AISI316
3120139
V77
BALL VALVE
DIE ERSTE
VM 4359
ISO-Rp 1
AISI304/316
3120149 3
V78
BALL VALVE
DIE ERSTE
VM 4359
ISO-Rp 1
AISI304/316
3120149 3
V83
BALL VALVE
DIE ERSTE
VM 4357
3120138 3
V84
BALL VALVE
DIE ERSTE
VM 4357
3120138 3
V85
BALL VALVE
DIE ERSTE
VM 4359
ISO-Rp 1
AISI304/316
3120149 3
V86
BALL VALVE
DIE ERSTE
VM 4359
ISO-Rp 1
AISI304/316
3120149 3
Z2
FILTER
KROMBACH
VM6303
DN50
GG25
2560011 4
3120138 3
1
3120148 3
3120148 3
3120148 3
3120148 3
2(3)
LIST OF COMPONENTS
ITEM QTY
DESCRIPTION
MANUFACTURER
TYPE
DATA
CONNEC
Dwg No.:
4-3617-050
Issue:
MATERIAL
REM
ART:NO AS
REMARKS
1)
INCL. PADLOCK
3(3)
ABB Drives
Installation and
Start-up Guide
PROFIBUS Adapter Module
NPBA-12
Safety Instructions
Overview
This chapter states the safety instructions that must be followed when
installing and operating the NPBA-12 PROFIBUS Adapter Module.
The material in this chapter must be studied before attempting any
work on, or with, the unit.
Warnings
Notes
Safety Instructions
General Safety
Instructions
ii
Table of Contents
Safety Instructions
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-i
Warnings and Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-i
General Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-ii
Table of Contents
Chapter 1 Introduction to This Guide
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
What This Guide Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conventions Used in This Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Further Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1-1
1-1
1-2
1-2
Chapter 2 Overview
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
The NPBA-12 PROFIBUS Adapter Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Delivery Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Warranty and Liability Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Chapter 3 Mechanical Installation
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Mounting Outside the Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Mounting Inside the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Chapter 4 Electrical Installation
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
General Cabling Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Earthing the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
DIP Switch Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
NPBA-12 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Drive Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
PROFIBUS and Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
iii
Table of Contents
Chapter 5 Programming
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PROFIBUS Connection Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
5-1
5-1
5-5
Chapter 6 Communication
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
PROFIBUS-DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Service Access Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Communication Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
PPO Message Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
The Control Word and the Status Word. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Actual Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Parameters in Cyclic Communication (DP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
Parameters in Acyclic Communication (DPV1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
Chapter 7 Fault Tracing
Status LED Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Appendix A PROFIBUS Parameters
Appendix B Definitions and Abbreviations
PROFIBUS Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
PROFIBUS Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Appendix C Technical Data
DDCS Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Fieldbus Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-2
NPBA-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
Appendix D Ambient Conditions
Ambient Conditions, Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Ambient Conditions, Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Ambient Conditions, Transportation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
iv
Overview
Intended Audience
The Guide is intended for the people who are responsible for installing,
commissioning and using a PROFIBUS Adapter Module with an ABB
drive. The reader is expected to have a basic knowledge of electrical
fundamentals, electrical wiring practices, the drive, the use of the drive
control panel, and the PROFIBUS protocol family.
1-1
Conventions Used in
This Guide
Communication Module
Data sets are clusters of data sent through the DDCS link between the
NPBA-12 Adapter Module and the drive. Each data set consists of
three 16-bit words, ie. data words. The Control Word (sometimes called
the Command Word) and the Status Word, References and Actual
Values (see Chapter 6) are types of data words; the contents of some
data words are user-definable.
NPBA-12 PROFIBUS
Adapter Module
Parameter
Further Information
1-2
Chapter 2 Overview
Overview
PROFIBUS
2-1
Chapter 2 Overview
The NPBA-12
PROFIBUS Adapter
Module
PROFIBUS
Master
Slave Stations
NPBA-12
PROFIBUS ADAPTER
TXD
ABB Drive
RXD
RESET
MASTER
MSG
DDCS
Status LEDs
(For descriptions see Chapter 7)
ABB Drive
+24V
0V
DG
SH
Figure 2-1 The construction of the PROFIBUS link and the NPBA-12 Adapter Module.
2-2
Chapter 2 Overview
Compatibility
Delivery Check
The warranty for your ABB drive and options covers manufacturing
defects. The manufacturer carries no responsibility for damage due to
transport or unpacking.
In no event and under no circumstances shall the manufacturer be liable for damages and failures due to misuse, abuse, improper installation, or abnormal conditions of temperature, dust, or corrosives, or
failures due to operation above rated capacities. Nor shall the manufacturer ever be liable for consequential and incidental damages.
The period of manufacturer's warranty is 12 months, and not more than
18 months, from the date of delivery. Extended warranty may be available with certified start-up. Contact your local distributor for details.
Your local ABB Drives company or distributor may have a different warranty period, which is specified in their sales terms, conditions, and
warranty terms.
If you have any questions concerning your ABB drive, contact your
local distributor or ABB Drives office.
The technical data and specifications are valid at the time of printing.
ABB reserves the right to subsequent alterations.
2-3
Chapter 2 Overview
2-4
Overview
Mounting Outside
the Drive
10 mm
Earthing
Tab
10 mm
3-1
Mounting Inside
the Drive
3-2
Overview
General Cabling
Instructions
Arrange the bus cables as far away from the motor cables as possible.
Avoid parallel runs. Use bushings at cable entries.
Handle fibre optic cables with care. When unplugging optic cables,
always grab the connector, not the cable itself. Do not touch the ends
of the fibres with bare hands as the fibre is extremely sensitive to dirt.
The maximum long term tensile load for the fibre optic cables is 1 N.
The minimum short term bend radius is 25 mm.
The NPBA-12 module earth is connected to the rail onto which the
module is mounted. If the rail is fastened to an earthed metallic
assembly plate, the module is automatically earthed, and no external
earthing wire is needed. If the rail is fastened to a base that is not
earthed, the rail must be connected to the nearest earthing terminal.
However, the earthing wire should not be connected to the same
terminal as the power cable screens. (See the mounting instructions in
Chapter 3.)
4-1
DIP switch SW1 on the printed circuit board of the NPBA-12 is used to
switch on bus termination. Bus termination prevents signal reflections
from the cable ends. SW1 should be set to ON if the module is installed
at the end of the bus.
Note: The built-in termination circuitry of the NPBA-12 is of the active
type, so the module has to be powered for the termination to work. If
the module needs to be switched off during operation of the network,
the bus can be terminated by connecting a 220 ohm, 1/4 W resistor
between the A and B lines.
The DIP switch on the circuit board can be accessed as shown below.
Bottom View
Side View
SW
4-2
OF
ON
NPBA-12 Connections
Drive Connection
PROFIBUS ADAPTER
TXD
RXD
DDCS
RESET
MASTER
MSG
DDCS
+24V
0V
DG
SH
Figure 4-2 Fibre optic link connecting the NPBA-12 to the drive.
PROFIBUS and Power
Connections
The bus cable and the external power supply are connected to terminal
blocks X1 and X2 on the NPBA-12.
The terminal blocks are described below.
X1
Description
X2
Description
+24V
0V
DG
SH
4-3
PROFIBUS Wiring
Examples
There are two wiring examples below for standard PROFIBUS cable
consisting of a twisted pair and screen.
A
PROFIBUS
MASTER
NPBA-12
A
NPBA-12
X1 1 2 3 4
X1 1 2 3 4
X2
SH
DG
0V
SH
DG
5 6 7 8
+24V
X2
0V
GND
+24V
A
B
5 6 7 8
B
PROFIBUS
MASTER
NPBA-12
A
NPBA-12
X1 1 2 3 4
X1 1 2 3 4
X2
SH
DG
0V
SH
DG
5 6 7 8
+24V
X2
0V
GND
+24V
A
B
5 6 7 8
Figure 4-3 Connection diagram for the standard PROFIBUS cable. Only connection (B) enables the
removal of the intermediate module without disturbing the bus.
4-4
Chapter 5 Programming
Overview
Configuring the
System
PROFIBUS Connection
Configuration
5-1
Chapter 5 Programming
Parameter Name
Default
Setting
Alternative Settings
MODULE TYPE
(Read-only)
NPBA-12 Vx.x
PROTOCOL
(0) DP
PPO TYPE
(0) PPO 1; (1) PPO 2; (2) PPO 3; (3) PPO 4; (4) PPO 5
(0) PPO 1
NODE NUMBER
2 to 126
1 to 4
CUT-OFF TIMEOUT
0 to 255
30
COMM PROFILE
(0) STOP
MODULE TYPE
PROTOCOL
PPO TYPE
NODE NUMBER
5-2
This parameter selects the PPO message type for the PROFIBUS
connection. See Figure 6-1 for available PPO message types.
Each device on the PROFIBUS link must have a unique node number.
This parameter is used to define a node number for the drive it is
connected to.
Chapter 5 Programming
This parameter defines the number of data sets sent in each direction
in PPO messages; e.g.. if this parameter is set to 1, only data sets 1
(master to drive) and 2 (drive to master) are used. Setting this
parameter to 4 enables all eight data sets shown in Figure 6-1: data
sets with odd numbers (1,3,5,7) are sent by the master to the drive and
those with even numbers (2,4,6,8) are sent by the drive to the master
(providing DATA SET INDEX is set to FBA DSET 1). Please note that
different drive types support different numbers of data sets; see the
drive documentation.
Defines the offset for data set indexes (numbers). See the drive
documentation for information.
FBA DSET 1 (no offset)
The first data set sent from the master to the drive (the Control Word) is
Data Set 1 (DS1).
FBA DSET 10 (offset 9)
The first data set sent from the master to the drive (the Control Word) is
Data Set 10 (DS10).
CUT-OFF TIMEOUT
This parameter defines the behaviour of the NPBA module in the event
that no messages are received from the PROFIBUS controller.
0
The NPBA cyclically sends the last valid Control Word and References
to the drive until new values are received from the controller.
1 255
The NPBA stops communicating with the drive after a timeout, the
actual length of which equals the setting multiplied by 20 milliseconds.
The behaviour of the drive in case the DDCS communication stops
depends on its parameter settings; consult the drive documentation.
Normal operation is resumed after valid messages are again received
from the controller.
5-3
Chapter 5 Programming
COMM PROFILE
Drive SW Version
Setting to Use
ACS 400
1.0.5.6 or later
ABB DRIVES
ACxA5000 or later
AHxA2000
AHxA5000 or later
ABB DRIVES
AMxM103a or later
ABB DRIVES
APxA1100 or later
ABB DRIVES
AF0A1020 or later
ABB DRIVES
ACxA2000 or later
ABB DRIVES
ACS 800
ASXR7000 or later
ABB DRIVES
CSA 2.8/3.0
ABB DRIVES
CSA 2.8/3.0
ACS 1000
ABB DRIVES
ACS 6000
ABB DRIVES
DCS 400
ABB DRIVES
DCS 500
DC21x226 or later
ABB DRIVES
ABB DRIVES
The NPBA-12 relays the Control Word as is from the PROFIBUS
master to the drive. The Status Word is relayed to the master as
received from the drive, except bit 15 which is used as a DDCS
communication error indicator. The Control and Status Word bits are
assigned as defined by the ABB Drives Profile (based on the
PROFIBUS standard).
CSA 2.8/3.0
The Control Word and the Status Word are altered in order to match
the drive Control and Status Words to those defined by the PROFIBUS
profile.
CONTROL ZERO MODE
This parameter defines the operation of the NPBA module in the event
that only messages consisting of zeros are received from the
PROFIBUS controller. This is the case e.g. when the controller is
switched from RUN to STOP mode.
STOP
The messages are forwarded to the drive as such. This will usually
cause the drive to stop; for more information, consult the drive
documentation.
FREEZE
The last-received valid Control Word and References are sent to the
drive until new values are received from the PROFIBUS controller.
5-4
Chapter 5 Programming
Control Locations
5-5
Chapter 5 Programming
5-6
Chapter 6 Communication
Overview
PROFIBUS-DP
The services of the PROFIBUS Data Link Layer (Layer 2) are used by
PROFIBUS-DP through Service Access Points (SAPs). Precisely
defined functions are assigned to individual SAPs.
For further information on Service Access Points, refer to the manual of
the PROFIBUS master, PROFIDRIVE The PROFIBUS Profile for
Adjustable Speed Drives, or the EN 50170 standard.
Communication
Start-up
Short Name
61
Set_Prm
62
Chk_Cfg
60
Slave_Diag
128 (Default)
Data_Exch
Name
6-1
Chapter 6 Communication
SAP 61 (Set_Prm)
Byte
Hex
Value
B8
Description
Station_Status
1
0
Reserved
WD_On
0 = Watchdog on
Freeze_Req
1 = Slave is requested to process in freeze mode
Sync_Req
1 = Slave is requested to process in SYNC mode
Unlock_Req
Lock_Req
2 to 3
0B
5 to 6
6012
00
SAP 62 (Chk_Cfg)
SAP 62 selects the PPO type to be used. (The same type must be
selected with both SAP 62 and NPBA-12 Configuration Parameter
PROFIBUS MODE.) The table below gives the Hex frame that must be
sent to the drive to select the PPO type.
Cfg_Data (Configuration Data)
Type: Octet String - Length: 1 to 32
6-2
PPO Type
Hex Frame
F3 F1
F3 F5
F1
F5
F3 F9
Chapter 6 Communication
SAP 60 (Slave_Diag)
Byte
1
Description
Station_Status_1
x
Station_Status_2
x
Station_Status_3
x
0
Reserved
Diag.Ext_Diag_Overflow (Set by Slave)
4
5 to 6
Diag.Master_Add
The address of the master that parameterised this slave
Ident_Number (for NPBA-12: 6012h)
6-3
Chapter 6 Communication
Description
Ext_Diag_Data
The number of bytes reserved for Extended Diagnosis (including this byte)
Fixed to 2
Ext_Diag_Data
0 = OK
4 = Actual value channel is not updated (last value retained)
SAP 128
(Data_Exchange)
6-4
Chapter 6 Communication
Parameter
Identification
Control data
Actual data
ID
IND
VALUE
Process Data
DS 1
DS 3
CW
SW
DW 2.1
DW 2.2
DW 2.3
DW 3.1
DW 4.1
DW 3.2
DW 4.2
DS 4
DW 3.3
DW 4.3
DW 5.1
DW 6.1
DW 5.2
DS 7
DW 1.2
DS 2
DW 1.3
DS 5
DW 1.1
DW 6.2
DS 6
DW 5.3
DW 6.3
DW 7.1
DW 8.1
DS 8
Type 1*
Type 2
Type 3*
Type 4
Type 5
Parameter Identification:
ID Parameter Identification
IND Index for Arrays
VALUE Parameter Value (Max. 4 bytes)
Process Data:
CW Control Word (from Master to Slave; see Table 6-2)
SW Status Word (from Slave to Master; see Table 6-3)
REF Reference (from Master to Slave)
ACT Actual Value (from Slave to Master)
PD Process Data (application-specific)
DS Data Set
DW Data Word
6-5
Chapter 6 Communication
References
References are 16-bit words containing a sign bit and a 15-bit integer.
A negative reference (indicating reversed direction of rotation) is
formed by calculating the twos complement from the corresponding
positive reference.
ABB drives can receive control information from multiple sources
including analogue and digital inputs, the drive control panel and a
communication module (e.g. NPBA-12). In order to have the drive
controlled through PROFIBUS, the communication module must be
defined as the source for control information, e.g. Reference. The
scaling of the integer received from the master as Reference is drivespecific. See its Programming Manual for available control source
selections and Reference scaling factors.
Actual Values
6-6
Chapter 6 Communication
Table 6-2 The Control Word (PROFIBUS Parameter 967). The upper case boldface text refers to the
states shown in Figure 6-2.
Bit
0
Name
Value
Proceed to STATE/Description
ON
OFF1
OFF2
OPERATION_
ENABLE
RAMP_OUT_
ZERO
Normal operation.
Proceed to RAMP FUNCTION GENERATOR: OUTPUT ENABLED
Normal operation.
Proceed to RAMP FUNCTION GENERATOR: ACCELERATOR ENABLED
OFF3
RAMP_HOLD
RAMP_IN_
ZERO
RESET
INCHING_1
INCHING_2
10
REMOTE_CMD
11 to 15
Control Word <> 0 or Reference <> 0: Retain last Control Word and Reference
Control Word = 0 and Reference = 0: Fieldbus (DDCS) control enabled
Drive-specific. (See the drive documentation for information)
6-7
Chapter 6 Communication
Table 6-3 The Status Word (PROFIBUS Parameter 968). The upper case boldface text refers to the
states shown in Figure 6-2.
Bit
0
Name
RDY_ON
RDY_RUN
RDY_REF
Value
STATE/Description
READY TO SWITCH ON
READY TO OPERATE
OFF1 ACTIVE
OPERATION ENABLED
0
3
TRIPPED
OFF_2_STA
OFF_3_STA
SWC_ON_INHIB
FAULT
No fault
OFF2 inactive
OFF2 ACTIVE
OFF3 inactive
OFF3 ACTIVE
SWITCH-ON INHIBITED
0
7
10
ALARM
AT_SETPOINT
REMOTE
ABOVE_LIMIT
Warning/Alarm
No Warning/Alarm
11 to 14
15
6-8
Drive-specific
DDCS_ERROR
DDCS communication OK
Chapter 6 Communication
SWITCH-ON
INHIBITED
MAINS OFF
Power ON
(SW Bit6=1)
PROFIBUS
State Machine
(CW Bit0=0)
NOT READY
TO SWITCH ON
A B C D
(SW Bit0=0)
OPERATION
INHIBITED
CW = Control Word
SW = Status Word
n = Speed
I = Input Current
RFG = Ramp Function Generator
f = Frequency
(SW Bit0=1)
(SW Bit2=0)
from any state
operation
inhibited
FAULT
(SW Bit1=1)
(SW Bit3=1)
(CW Bit7=1)
Emergency Stop
OFF3 (CW Bit2=0)
(CW Bit3=1
and
SW Bit12=1)
OFF3
ACTIVE
(SW Bit5=0)
Emergency Stop
OFF2 (CW Bit1=0)
OFF2
ACTIVE
(SW Bit4=0)
n(f)=0 / I=0
(CW Bit4=0)
OPERATION
ENABLED
C D
(SW Bit2=1)
A
(CW Bit5=0)
(CW Bit4=1)
RFG: OUTPUT
ENABLED
D
B
(CW Bit6=0)
(CW Bit5=1)
RFG: ACCELERATOR
ENABLED
C
(CW Bit6=1)
OPERATING
(SW Bit8=1)
6-9
Chapter 6 Communication
Parameters in Cyclic
Communication (DP)
IND
Process Data
CW REF
SW ACT (PD1, PD2...)
VALUE
15 14 13 12 11 10
Request Label
Response Label
Parameter Number
*Request Signal
*Not used (=0)
The Request Label is used by the master when transmitting data to the
slave, while the Response Label is used by the slave as a positive or
negative acknowledgement. The tables below show the Request/
Response functions.
Request Labels (from Master to Slave)
Request
Response Labels
Function
Ackn. (+)
Ackn. (-)
1, 2
No task
7, 8
7, 8
*4
*5
7, 8
*6
4, 5
7, 8
*7
7, 8
*8
7,8
*9
6-10
Chapter 6 Communication
Function
No response
10
6-11
Chapter 6 Communication
Example: Write
Write:
CW
Param. Value
REF
Request
23
CB
00
00
00
00
00
01
04
7F
34
15
Response
13
CB
00
00
00
00
00
00
03
37
34
15
IND
Param. Value
SW
ACT
Example: Read
Read:
CW
Param. Value
REF
Request
13
96
00
00
00
00
00
00
04
7F
34
15
Response
13
96
00
00
00
00
00
02
03
37
34
15
IND
Param. Value
SW
ACT
Parameters in Acyclic
Communication
(DPV1)
6-12
The tables below describe the Status LED indications during both the
start-up sequence and operation.
MASTER
Power-on
MSG
DDCS
OFF
OFF
OFF
OFF
OFF
OFF
DDCS link
initialisation
OFF
OFF
Transfer rate
detection
OFF
GREEN
PROFIBUS
communication
establishment
GREEN
GREEN
Operation
GREEN
GREEN
GREEN
7-1
Remedy
MASTER
MSG
DDCS
RED
RED
OFF
OFF
RED
RED
(Last valid
state)
(Last valid
state)
RED
GREEN
FLASHING
RED
FLASHING
GREEN
PROFIBUS
communication failure
(no data exchange)
FLASHING
RED
RED
FLASHING
GREEN
*All errors that occur on the DDCS link between the NPBA-12 and the drive are reported to the PROFIBUS master
(bit 15 of the Status Word is turned on).
7-2
Parameter Name
Data
Type
R/W
918
NODE ADDRESS
UINT16
947
FAULT NUMBER
UINT16
963
UINT16
964
DEVICE IDENTIFICATION
UINT16
Description
965
PROFILE NUMBER
UINT16
967
CONTROL WORD
UINT16
968
STATUS WORD
UINT16
971
STORE
UINT16
R/W
996*
UINT16
Sets the day counter of the real-time clock of the drive. Day 1
corresponds to 1 January 1980.
997*
UINT32
Sets the time counter of the real-time clock of the drive. The value
corresponds to the number of 100 s ticks since midnight.
0 = No action
1 = Save drive parameters to non-volatile memory
*The values of Parameters 996 and 997 are sent to the drive when parameter 997 is written.
A-1
A-2
PROFIBUS Definitions
Acyclic Communication
Array
Broadcast
Command Word
Communication Object
Control Word
Cyclic Communication
Device Class
Drivecast
Fault
GSD File
Index
Information Report
Master
Multicast
Name
Nibble
Set of 4 bits
Object Dictionary
Object List
Parameter
B-1
Parameter Description
Specification of a parameter
Parameter Number
Parameter address
Parameter/Process
Data Object
Process Data
Data that contains Control Word and Reference value or Status Word
and Actual value. May also contain other (user-definable) control
information
Profile
Request Label
Response Label
Slave
Status Word
Warning
B-2
PROFIBUS Abbreviations
The text in italics is the original German term.
.con
Confirmation
.ind
Indication
.req
Request
.res
Response
ACT
Actual Value
Istwert
AK
ALI
CR
Communication Reference
Kommunikationsreferenz (Kommunikationsbeziehung)
DP
Decentralised Periphery
Dezentrale Peripherie
DP-ALI
DPV1
FDL
FMS
FSU
HIW
HSW
ISW
KR (KB)
Main Reference
Hauptsollwert
see ACT
see CR
PA
Process Automation
Prozessautomatisierung
PD
Process Data
Prozessdaten
PKE
Parameter Identification
Parameter-Kennung
PKW
B-3
B-4
PNU
Parameter Number
Parameternummer
PPO
PWE
Parameter Value
Parameter-Wert
PZD
see PD
PZDO
SAP
SOW
Reference
Sollwert
SPM
Request Signal
Spontanmeldung
STW
Control Word
Steuerwort
ZSW
Status Word
Zustandswort
DDCS Link
Minimum
Maximum
Unit
Storage Temperature
-55
+85
Installation Temperature
-20
+70
50
25
mm
35
mm
1000
cycles
Topology: Point-to-point
Serial Communication Type: Asynchronous, half Duplex
Transfer Rate: 4 Mbit/s
Protocol: Distributed Drives Communication System (DDCS)
Connectors: Blue receiver; grey transmitter
C-1
Fieldbus Link
Line B
DIN 19245 Part 1
Impedance
135 to 165
(3 to 20 MHz)
100 to 130
(f > 100 kHz)
Capacitance
< 30
< 60
pF/m
Resistance
< 110
/km
Wire gauge
> 0.64
> 0.53
mm
Conductor area
> 0.34
> 0.22
mm2
Parameter
Unit
187.5
500
1500
3000
6000
12000
Line A
1200
1000
400
200
100
100
100
Line B
1200
600
200
Topology: Multi-drop
Serial Communication Type: Asynchronous, half Duplex
Transfer Rate: 9.6, 19.2, 44.45, 93.75, 187.5, 500, 1500, 3000, 6000,
or 12000 kbit/s
Protocol: PROFIBUS-DP, PROFIBUS-DPV1
C-2
NPBA-12
Description
X2
Description
+24V
0V
DG
SH
General:
All materials are UL/CSA approved
Complies with EMC Standards EN 50081-2 and EN 50082-2
C-3
C-4
Ambient Conditions,
Operation
Ambient Conditions,
Storage
Ambient Conditions,
Transportation
D-1
D-2
NPBA-12/EN
3BFE 64341588 R0125 REV B
EFFECTIVE: 06.10.2003
ABB Oy
AC Drives
P.O.Box 184
FIN-00381 Helsinki
FINLAND
Telephone: +358 10 222 000
Fax:
+358 10 222 2681
Internet:
www.abb.com/automation
ABB Inc.
Automation Technologies
Drives & Motors
16250 West Glendale Drive
New Berlin, WI 53151
USA
Telephone: 262 785-3416
800-HELP-365
Fax:
262 785-8525
LD GRB - 01
Data sheet
SHORT DESCRIPTION
The LD GRB-01 is a Gray-coded absolute encoder interface, used for fast and accurate
measurement of the absolute position of a rotor via a position encoder terminal.
The communication with the encoding terminal is done over a 24V electrical interface. This
interface can be either parallel or serial. The LD GRB-01 can also deliver analog signals to
a speed monitoring instrument and a pulse encoder.
The communication with the controller platform AMC-3 is done over an optical DDCS
interface with one sender (Tx) and one receiver (Rx).
The node address of the LD GRB-01 can be set with a micro switch
Rev.
04-09-10
A.Greuter
04-10-20
O.Olsson
Department 1
Department 2
ATDR
Rev.
Issued:
04-10-19 O. Olsson
Check 1:
04-10-20 T. Baechle
Check 2:
Format
A4
Language
Page
No. of
pages
Released:
-2-
LD GRB - 01
TABLE OF CONTENTS
SHORT DESCRIPTION ..................................................................................................................1
1
LED DISPLAYS.............................................................................................................3
3.1
3.2
CONNECTORS .............................................................................................................3
Electrical Connector X1 .................................................................................................3
Optical fiber connectors .................................................................................................3
4.1
4.2
4.3
4.4
4.5
4.6
4.7
ORDER INFORMATION................................................................................................8
-3-
LD GRB - 01
APPLICATION EXAMPLE
A frequently used example of an application for the Grey encoder is when it is connected between
a SCYC 55830 (Tacho terminal board) and an AMC-3 (Application & Motor control board). In some
applications also NTAC (Pulse encoder interface) is connected to pulse outputs. See the block
diagram below:
GRAY CODED
ENCODER
OPTIONAL
SCYC
55830
Tacho
terminal
board
External
24VDC
power
supply
F
R
W
P
OPTIONAL
24 VDC SUPPLY
Power
Supply
output
24 VDC
LD GRB - 01
PULSE
OUTPUT
SPEEDOMETER
OUTPUT
Tx
NTAC
Pulse
encoder
interface
Speed
monitoring
Instrument
Optical
DDCS 10Mbit
AMC-3
controller
board
Rx
Node Address
selector swith
M
SSI -GRAY
CODED
ENCODER
SSI
Encoder
Terminal
board
SERIAL RS-422
Power Supply
input 24 VDC
LED DISPLAYS
On the front panel are 4 LEDs located which are used as a status display.
3
3.1
Meaning
FAULT
LED colour
RED
Abbr
F
CONF_FAIL
WARNING
RED / GREEN
YELLOW
R
W
POWER_ON
GREEN
Explanation
ON after power-up.
ON after DDCS time-out.
ON when power failure signal activated
ON if SSI link in not OK
OFF after first accepted DDCS telegram.
RED if configuration has failed, GREEN if O.K.
ON when last received SSI-telegram has failed.
OFF when last received SSI-telegr. O.K.
ON when internal 5V level O.K. (hardware)
CONNECTORS
Electrical Connector X1
The electrical connector X1 contains of three rows of screw terminals. These rows are named A, B
and C. Each row has 18 screw terminals and therefore totally 54 connectors are available on the
connector X1.
3.2
There is one optical transmitter and one optical sender on the LD GRB-01. These optical
components are connecting the LD GRB to the AMC-3 controller. The sender (Tx) is light grey or
light blue. The receiver (Rx) is dark grey.
-4-
4
4.1
ELECTRICAL RATINGS
Power supply input
24 VDC 10%
maximum 1.3 A
Input voltage:
Input current:
Row and pin
in terminal X1
4.2
LD GRB - 01
Signal
C1
C2
24VDC input
24VDC input
C3
C4
4.3
Signal name
Row and
pin in X1
Signal name
A1
Bit 0-
B1
Bit 0+
A2
Bit 1-
B2
Bit 1+
A3
Bit 2-
B3
Bit 2+
A4
Bit 3-
B4
Bit 3+
A5
Bit 4-
B5
Bit 4+
A6
Bit 5-
B6
Bit 5+
A7
Bit 6-
B7
Bit 6+
A8
Bit 7-
B8
Bit 7+
A9
Bit 8-
B9
Bit 8+
A10
Bit 9-
B10
Bit 9+
A11
Bit 10-
B11
Bit 10+
A12
Bit 11-
B12
Bit 11+
A13
Bit 12-
B13
Bit 12+
A14
Bit 13-
B14
Bit 13+
A15
Bit 14-
B15
Bit 14+
A16
Bit 15-
B16
Bit 15+
Pin in X1
The GRB board has 16 galvanically opto isolated digital inputs for parallel Gray interface
connection. The signal resolution of this parallel interface is selectable in the range10 to 16
bits. The order of the bits could be inverted by the software via an AMC-table parameter.
Nominal voltage
Inputs ON level
Inputs OFF level
24VDC
+18...+24 V
0...+13 V
(DI0...DI15)
-5-
4.4
LD GRB - 01
Signal
C13
CLK+
C14
CLK-
C15
DATA+
C16
DATA-
Alternatively to parallel signals from the grey encoder terminal, a pattern called SSI
(Synchronous Serial Interface) can be used as transfer protocol for data to the LD GRB-01.
Number of bits selectable:
Parity check selectable:
Physical link
4.5
4.6
Signal
name
C7
CHA+
C8
CHA-
C9
CHB+
C10
CHB-
C11
CHZ+
C12
CHZ-
Pulse signals are driven from RS422 drivers on the LD GRB-01. These pulses can for
example be received by a NTAC Pulse encoder interface which can be connected to the LD
GRB-01. Signal isolation must be done in the pulse receiving equipment.
CHA
CHB
CHZ
-6-
4.7
LD GRB - 01
Speedometer output
Row and Pin
in terminal X1
Signal
name
C17
SO+
A17
SO-
A18
SO-
B17
SO-
Remarks
B18
SOThe actual motor speed can be monitored via this output interface delivered by the
LD GRB-01. The interface is a low voltage analog output for a high impedance panel
instrument. The instrument can be connected between the SO and DGND terminals. The
analog output is generated by an operation amplifier, thus signal isolation must be done in
the signal-receiving instrument.
CONNECTION EXAMPLE
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
POWER SUPPLY
OUTPUT TO
ENCODER
A1
B1
A2
B2
A3
B3
A4
B4
A5
B5
A6
B6
A7
B7
A8
B8
A9
B9
A10
B10
A11
B11
C5
C6
LD GRB - 01
C7
A+
C8
AC9
B+
C10
B-
C17
B18
NTAC-02
OUTPUT
SPEEDOMETER
OUTPUT
DDCS 10Mbit
24 VDC
0 VDC
24 VDC
0 VDC
C1=C2
C3=C4
POWER
SUPPLY INPUT
TO LD GRB
SWI = 3
-7-
LD GRB - 01
Pin
a
a
1
2
a
a
Signal
Row
Pin
Signal
Row
Pin
Bit 0 Bit 1 -
B
B
1
2
Bit 0 +
Bit 1 +
c
c
1
2
24VDC input
24VDC input
Bit 2 -
Bit 2 +
Bit 3 -
Bit 3 +
a
a
5
6
Bit 4 Bit 5 -
b
b
5
6
Bit 4 +
Bit 5 +
c
c
5
6
Bit 6 -
Bit 6 +
Bit 7 -
Bit 7 +
Bit 8 -
Bit 8 +
10
Bit 9 -
10
Bit 9 +
10
11
Bit 10 -
11
Bit 10 +
11
12
Bit 11 -
12
Bit 11 +
12
13
Bit 12 -
13
Bit 12 +
13
14
Bit 13 -
14
Bit 13 +
14
15
Bit 14 -
15
Bit 14 +
15
16
Bit 15 -
16
Bit 15 +
16
17
DGND
17
DGND
17
SO
18
DGND
18
DGND
18
N.C.
Signal
-8-
118
RX
F
R
W
P
120
B1
A1
C1
B2
C2
A2
B3
C3
A3
B4
A4
C4
B5
A5
C5
B6
C6
A6
B7
C7
A7
B8
A8
C8
B9
A9
C9
B10
C10
A10
B11
C11
A11
B12
A12
C12
B13
A13
C13
B14
C14
A14
B15
C15
A15
B16
C16
A16
B17
A17
C17
B18
C18
A18
TX
110
ENVIRONMENTAL CONDITIONS
Operation:
Storage:
0 +70 C
-25 +85 C
ORDER INFORMATION
LD GRB - 01
ABB Drives
Users Manual
Safety Instructions
Overview
This chapter states the safety instructions that must be followed when
installing and operating the NDBU-85/95 DDCS Branching Unit. The
material in this chapter must be studied before attempting any work on,
or with, the unit.
Warnings
Notes
Safety Instructions
General Safety
Instructions
ii
Table of Contents
Safety Instructions
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Warnings and Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
General Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
Table of Contents
NDBU-85/95 DDCS Branching Units
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
NDBU-85C, NDBU-95C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Optical Component Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Cable Length and Optical Power Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Setting the Optical Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Settings and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Address (S1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Communication Mode (X13; NDBU-95 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Transmission Speed (X12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Optical Power (X2X11). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Power Supply (X1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
NDBU-85 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
NDBU-95 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Technical Data, NDBU-85 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Technical Data, NDBU-95 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Optical Component Types in ABB Drive Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
iii
Table of Contents
iv
Overview
The NDBU-85 and NDBU-95 branching units are used for distributing a
DDCS-protocol control link to several drives. The controlling unit can be
e.g. a PC equipped with DriveWindow and a DDCS interface; an
Advant application controller (such as an AC 80); or a Fieldbus
Communication Interface (FCI, type CI810) equipped with a TB810/
TB811 Optical ModuleBus Port.
Note: NDBU branching units cannot be used on DDCS links for which
the data rate is selected through software.
Using NDBU branching units, the usual ring topology of a DDCS link
can be replaced with a star topology, which is useful to ensure
uninterrupted communication in case one unit on the ring fails or must
be shut down for maintenance.
The NDBU-85 is able to handle conventional DDCS-protocol input
only; the NDBU-95 supports DDCS and DriveBus. The NDBU-95 has
an additional jumper-selectable regeneration mode in which any
message received from one follower unit is forwarded to all follower
units.
Both the NDBU-85 and the NDBU-95 have one input channel (MSTR)
and nine output channels (CH0 to CH8). When chaining branching
units, it is recommended to use CH0 as the forwarding output to the
slave unit.
NDBU-85C, NDBU-95C
Optical Component
Types
Plastic optical fibre (POF) cables can be used with both 5 MBd and
10 MBd optical components. 10 MBd components also enable the use
of Hard Clad Silica (HCS) cables, which allow longer connection
distances thanks to their lower attenuation. HCS cables cannot be
used with 5 MBd optical components.
The optical component types used in ABB drive equipment are
presented on page 12.
Cable Length and
Optical Power Setting
Settings and
Connections
The NDBU units are configured using the jumpers and DIP switches on
the circuit board, which can be accessed by removing the cover of the
metal housing. This is done by loosening the two screws on top, then
sliding the cover sideways until released.
C H
C H
T X D 2
8
V 1 9
R X D
V 1 8
T X D
V 1 7
R X D
V 1 6
T X D
8
1
8
1
C H
V 1 5
R X D
V 1 4
T X D
2
8
1
X 8
V 1 2
T X D 2
8
1
8
1
R X D
V 1 0
T X D
X 1 2
4
1
M O D E
X 1 3
NDBU-95
only
8
1
M B IT /S
R X D
C H
X 9
V 1 3
V 1 1
S 1
X 1 0
A D D R E S S
C H
X 1 1
1 2 3 4 5 67 8
DIP
C H
ON
V 2 0
X 7
X 6
V 9
R X D
V 8
C H
C H
C H
T X D
2
X 5
7
V 7
R X D
V 6
T X D
2
X 4
7
V 5
R X D
V 4
T X D
2
X 3
7
V 3
R X D
V 2
T X D
M A S T E R
V 1
8
1
7
X 2
R X D
+ 5 V O K
X 1
S U P P L Y
V O L T A G E
+ 2 4 V
F 1
T 5 0 0 m A
0 V
Address (S1)
ON
DIP
(1)
(2)
(4)
(8)
(16)
(32)
(64)
(128)
1 2 3 4 5 6 7 8
Usage
(125)
124
NDBU 1
(123)
122
NDBU 2
(121)
120
NDBU 3
(1)
(2)
(4)
(8)
(16)
(32)
(64)
(128)
ON
ON
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
OFF
OFF OFF
ON
OFF
OFF OFF
ON
ON
OFF
ON
OFF
ON
ON
(77)
76
NDBU 25
OFF OFF
ON
ON
Communication Mode
(X13; NDBU-95 only)
2
1
4
3
2
1
4
3
MODE
X13
DDCS/DriveBus
(Default)
REGEN
Master
Master
MSTR
MSTR
CH0
CH1
CH2
CH0
Transmission Speed
(X12)
CH1
CH2
Jumper X12 sets the transmission speed of the NDBU unit. The setting
must match the transmission speed of the connected equipment. The
settings for some commonly used equipment are as follows:
PC with DriveWindow: 1 Mbit/s
ModuleBus (AC 70, AC 80, FCI [CI810]): 4 Mbit/s
DriveBus (AC 80): 4 Mbit/s (provisionally 8 Mbit/s)
The NDBU-85 can be set to 1, 2 or 4 Mbit/s; the NDBU-95 can be set to
1, 2, 4 or 8 Mbit/s.
2
1
8
7
2
1
8
7
2
1
8
7
2
1
8
7
MBIT/S
MBIT/S
MBIT/S
MBIT/S
1 Mbit/s
(Default)
2 Mbit/s
4 Mbit/s
8 Mbit/s
(NDBU-95 only)
Note: Set the jumper to the Disabled (DIS) position on all unused
channels to reduce heat generation.
2
1
8
7
X_
2
1
8
7
2
1
X_
Short
8
7
2
1
8
7
X_
Medium
(Default)
X_
Long
Disabled
Recommended settings:
Optical
Component
Type
Transmission
Speed
1 MBit/s
Cable
Type
POF
Cable Length
[m]
Optical
Power
Setting
0.1 5
Short
(2) 5 10
Medium
(5) 10 15
Long
0.1 4
Short
(2) 4 7
Medium
(5) 7 10
Long
0.1 5
Short
(0.1) 5 20
Medium
(0.1) 5 30
Long
0.1 50
Medium
(0.1) 50 200
Long
5 MBd
2 or 4 MBit/s
POF
POF
10 MBd
HCS
Diagnostic LEDs
The diagnostic LEDs on the circuit board of the NDBU unit can be
viewed through the holes in the metal housing.
Each fibre optic channel has two LEDs labelled TXD and RXD. These
indicate messages being transmitted (TXD) or received (RXD). In
normal operation, these LEDs should be flashing continuously on all
channels that are in use.
The +5V OK LED indicates that the logic circuitry of the NDBU is
receiving its supply voltage of 5 V. This LED should be illuminated
when the NDBU is powered.
Mechanical
Installation
NDBU-85 Dimensions
1 0
8 4
N D B U -8 5
4 1
N D B U -8 5
D D C S
B R A N C H IN G
U N IT , 8 + 1 C H
T X D
V 1 2 0
C H 8
R X D
V 1 1 9
T X D
A D D R E S S
V 1 1 8
C H 7
R X D
S 1
V 1 1 7
V 1 1 6
T X D
0
1
C H 6
R X D
V 1 1 5
T X D
V 1 1 4
C H 5
M B IT /S
+ + + +
+ + + +
R X D
V 1 1 3
1
X 1 2
T X D
V 1 1 2
C H 4
R X D
V 1 1 1
T X D
2 6 4
V 1 1 0
C H 3
R X D
V 1 0 9
V 1 0 8
T X D
C H 2
R X D
V 1 0 7
V 1 0 6
T R A N S M
S E T T IN G
+ + + + X 2 + + + + X 1 1
T X D
C H 1
R X D
D
L O N
M E D IU
S H O R
V 1 0 5
IS
G
M
T
T X D
V 1 0 4
C H 0
R X D
V 1 0 3
T X D
V 1 0 2
M S T R
R X D
V 1 0 1
+ 5 V O K
X 1
1
2
2 4 V D C
0 V
6 3 9 8 5 3 6 8
NDBU-95 Dimensions
8 4
1 0
N D B U -9 5
4 1
N D B U -9 5
T X D
V 1 2 0
C H 8
D D C S
B R A N C H IN G
U N IT , 9 C H
R X D
V 1 1 9
T X D
V 1 1 8
C H 7
A D D R E S S
8
V 1 1 7
R X D
S 1
T X D
V 1 1 6
C H 6
D D C S /
D R IV E B U S
R E G E N
R X D
V 1 1 5
T X D
V 1 1 4
C H 5
M O D E
X 1 3
M B IT /S
+ + +
+ + +
1 2 4 8
R X D
V 1 1 3
1
0
X 1 2
T X D
V 1 1 2
C H 4
R X D
V 1 1 1
T X D
V 1 1 0
C H 3
2 6 4
V 1 0 9
R X D
T X D
V 1 0 8
C H 2
R X D
V 1 0 7
T R A
S E T
+ +
+ +
T X D
V 1 0 6
C H 1
R X D
V 1 0 5
N S
T IN
+
+
M
+
G
X 2 X 1 1
D
L O N
M E D IU
S H O R
IS
G
M
T
V 1 0 4
T X D
C H 0
R X D
V 1 0 3
T X D
V 1 0 2
M S T R
R X D
V 1 0 1
+ 5 V O K
X 1
2 4 V D C
2
0 V
6 3 9 8 5 3 4 1
Technical Data,
NDBU-85
Technical Data,
NDBU-95
10
Block Diagrams
M A S T E R
O R A P P L IC A T IO N
C O N T R O L L E R )
(P C
D D C S
1 , 2 o r 4 M b it/s
N D B U -8 5
R
T
M
2 4 V
5 V
A D D R . S E T T IN G
D IP S W IT C H
T X D S IG N A L
R E G E N E R A T IO N
T R A N S M .
D R IV E R
IN T E N S . C N T R L
J U M P E R S
T X D
D D C S R E C E IV E R
9
S P E E D S E L E C T .
J U M P E R S
R X D
C H E N A B L E
IN T E N S . C N T R L
J U M P E R S
R X D S IG N A L
R E G E N E R A T IO N
O U T P U T M A S K IN G A N D
T R A N S M IT T E R D R IV E S
T
8
T
7
...
6
IN P U T M A S K IN G A N D
L O G IC O R F U N C T IO N
9
T
2
T
1
R
0
R
8
R
7
...
T O
R
2
R
1
...
T O
S U B
N D B U -8 5 /-9 5
D R IV E
F R O M
F R O M S U B
N D B U -8 5 /-9 5
D R IV E
. . .
D R IV E 7
D R IV E 8
...
(P C
D R IV E 1
M A S T E R
O R A P P L IC A T IO N
C O N T R O L L E R )
D D C S : 1 ,2 o r 4 M b it/s
D R IV E B U S : 4 o r 8 M b it/s
N D B U -9 5
R
T
M
2 4 V
5 V
A D D R . S E T T IN G
S W IT C H
T X D S IG N A L
R E G E N E R A T IO N
D D C S R E C E IV E R
9
T R A N S M .
D R IV E R
IN T E N S . C N T R L
J U M P E R S
T X D
S P E E D S E L E C T .
J U M P E R S
R X D
C H E N A B L E
IN T E N S . C N T R L
J U M P E R S
R X D S IG N A L
R E G E N E R A T IO N
M O D E S E L E C T .
J U M P E R
O R
1 8
O U T P U T M A S K IN G A N D
T R A N S M IT T E R D R IV E S
T
8
T
7
...
6
T
2
IN P U T M A S K IN G A N D
L O G IC O R F U N C T IO N
T
1
R
8
...
T O
D R IV E 8
D R IV E
D R IV E 7
R
7
R
6
...
R
R
1
R
0
...
T O
S U B
N D B U -8 5 /-9 5
F R O M
. . .
F R O M S U B
N D B U -8 5 /-9 5
D R IV E
D R IV E 1
11
Optical Component
Types in ABB Drive
Equipment
The following table provides the types of the optical components used
in ABB drive equipment.
Unit
NAMC-03 Controller
Channel
5 MBd
30 mA max
CH0 CH3
CH0, CH2
10 MBd
30 mA
10 MBd
50 mA max
NAMC-04 Controller
NAMC-11 Controller
NAMC-51 Controller
NDCO-01 DDCS Communication Option
(for NAMC-11 and NAMC-51)
NDCO-02 DDCS Communication Option
(for NAMC-11 and NAMC-51)
NDCO-03 DDCS Communication Option
(for NAMC-11 and NAMC-51)
CH1, CH3
CH1
+
+
CH2, CH3
CH0, CH2, CH3
+
+
NAMC-21 Controller
CH1
CH0, CH1
NAMC-22 Controller
CH2, CH3
CH0
+
+
+
+
+
MSTR, CH0
AC 80 Advant Controller
+
CH0 (DriveBus),
CH3
CH1, CH2
12
+
+
NDBU-85/95 EN
3BFE 64285513 R0125
EFFECTIVE: 01.10.2000
SUPERSEDES: NONE
ABB Industry Oy
Drives
P.O.Box 184
FIN-00381 Helsinki
FINLAND
Telephone: +358 10 22 2000
Fax:
+358 10 22 22681
Internet:
www.abb.com/automation
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd.
Layout drawing
Project:
Coperion Tasnee
Item:
Extruder 4.4 MW
Order/Tender No.:
Coperion W&P
Converter Type:
ACS 6105_L12_1a9_C24_W1a
Converter S/N:
403
Issued
Hartmut Wiebe
Check / rel.
Resp. dept.
2006-07-13
Final
DEAPR/AVLD
Document Number.
No. of pages
Coperion Tasnee
Layout Drawing
ATB06003DE R1
7
Lang.
en
Rev. ind.
Page
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd.
Sheet index
Cover sheet ............................................................................................................................................................................................................... 1
Sheet index ................................................................................................................................................................................................................. 2
Layout drawing / Converter line up ......................................................................................................................................................................... 3
Unit designation / Cable entry / Cable exit / Water entry / Attachments .......................................................................................................... 4
Unit designation / Weight / Amount of water / Watercirquit ............................................................................................................................... 5
Transportation unit / Cabinet enclosure ................................................................................................................................................................. 6
Revision history.......................................................................................................................................................................................................... 7
Document Number.
ATB06003DE R1
Lang.
en
Rev. ind.
Page
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd.
Unit designation
Cable entry
Cable exit
Water entry
Attachments
Document No.
+A01
+A02
+A03
+A04
+A05
Bottom
Bottom
3BHS196575
3BHS234225
3BHS199089
= LSU1
= COU1
= INU1
= CBU1
= WCU1
Base Frame(s)
Document Number.
ATB06003DE R1
Lang.
en
Rev. ind.
Page
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd.
Unit designation
Weight [kg]
Watercirquit
+A01
+A02
+A03
+A04
+A05
600
700
1450
1000
60
20
10
40
25
100
WCU1
WCU1
WCU1
WCU1
WCU1
Total:
= LSU1
= COU1
= INU1
= CBU1
= WCU1
195
Document Number.
ATB06003DE R1
Lang.
en
Rev. ind.
Page
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd.
Transportation unit
Weight [kg]
Unit 1
4700
Converter
4700
Cabinet enclosure
Installation:
Degree of protection:
Surface of cable termination bars:
Color of cabinets:
Indoor
IP 32 (standard)
to be specified
RAL 7032 / light gray
Document Number.
ATB06003DE R1
Lang.
en
Rev. ind.
Page
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd.
Revision history
Revision
Description
Document Number.
ATB06003DE R1
Lang.
en
Rev. ind.
Page
Water connections
Cable connections
Option:
Plate undrilled
Front view
Cooling water connection(1:5)
Fig. 1
20 Flange DN50
269
4x18
Converter interface:
23 terminals for
Aux. power supply
125
165
Converter interface:
22 terminals for Standard
and Optional I/O Signals
25
4x19.1
120.7
152.4
122 5
C
325
A-A
164
100 5
21
240 5
85
554 5
14
300.5
36
125.5
720
19 Floor cut-out
Fig. 2
Profiles for fixation
of external cables
17
16
27 Cable routing
Prepared:
07.02.2007
O.Ackermann
Reviewed:
150.5
170
J.Rees
Approved:
450
40
18 Drain connection
W.Kpfer
Dervd. from:
Resp. dep:
3BHS196601
07.02.2007
ATDCK
07.02.2007
ATDC
Revision:
50
Scale:
Doc-type:
ZAB
en
No.of sh:
100
Sheet no:
3BHS234225_E01
Schweiz AG
A3
Language:
A) 16.02.2007 R. Sacher
anoth. no:
5
Pressure
5 relief vent
Cable duct 1
Front view
95
3 Phase designation
depends on the
converter line up
(Fig. 1 or Fig. 2)
800
935
Fig. 1
=INU L3
left
2L2
1L1 1L3
2L3 2L1
1L2
184
Fig. 2
=LSU 1L1
left
900
120.5
50
113.5
1L3
2L2
1L2
2L3 2L1
L1
L3
L2
=LSU
right
Protective
earth (PE) 11
=INU
right
Connecting point 12
for earthing set
18
213.5
40
42
1000
720
219
13
Connection point
for grounding
10 cable (PE)
hole: D=13mm
thickness: 5mm
610
19 Floor cut-out
160
A-A
50
6 Roxtec frame
2 Undrilled plate
8 Cable entry for
serial communication,
position and speed encoder
14 Thickness 10mm
225
170
190
1000
Prepared:
Dervd. from:
S.Rheinegger 04-02-04
Reviewed:
Resp. dep:
R.Sacher
417,5
04-02-04
04-02-04
50
100
A3
Language:
en
No.of sh:
1
Sheet no:
3BHS196575
Switzerland Ltd
Doc-type: Format:
ATDMP
Revision:
We reserve all rights in this document and in the information contained
therein. Reproduction, use or disclosure to third parties without express
authority is strictly forbidden.
c ABB Switzerland Ltd 1994
Scale:
ZAB
Approved:
W.Kpfer
anoth. no:
ACS6000_Settings_SN 403.xls
403
Remarks
=LSU1+A01
Device
-B3201
-B3151
=COU1+A02
Device
-A2451
-A2501
-A2511
-A2521
-A2531
-A2541
-B2911
-B2981
-F1021
-F1021
-F1021
-K2812
-K2814
-K2831
-K2832
-K2833
-Q1001
-Q1003
-Q1003
-Q1004
-Q1004
Description
Cabinet temp. Monitoring
Air / air heat exch. ON
Description
Profibus / INU
Bus termination
Module Bus
CLUSTER ADDRESS
Module Bus
KEY CODE
Module Bus
KEY CODE
Module Bus
KEY CODE
Module Bus
KEY CODE
Cabinet temp. Monitoring
Cooling fans in swingfame ON
Undervoltage relay
Undervoltage relay / 380V Connected
Undervoltage relay / 380V Connected
Door release deenergized
Doors closed control
Emergency stop
Emergency stop
Emergency stop
Aux. Power supply 3x400VAC
(Transformer 2,5kVA)
Charging voltage CBU (Transformer
400V/3900V, 3,3kVA)
Irm =15 x Ir
Aux. Power supply (Transformer
400V/230V, 1,5kVA for air/air heat
exchanger)
Aux. Power supply (Transformer
400V/230V, 2,8kVA for air/air heat
exchanger)
HW-Diagram No.
Used type
KTO1140
KTS1141
3BHS119885E01
HW-Diagram No.
Used type
NPBA-12
3BHS227955e01
Setting range
0...60C
0...60C
Setting range
ON / OFF
0..9
1
AA
DO810
AA
DI810
AA
DO820
AD
55C
0...60C
45C
Time delay Symbol [] 0.2s
Umin.
335V
Umax..
455V
fix
4s
fix
4s
0,15s...600s
10s
0,15s...600s
10s
2s
KTO1140
KTO1141
EMR4
EMR4
EMR4
Time relay
Time relay
Time relay
Time relay
Time relay
0...60C
3,6A
PKZM
PKZ2
PKZ2
......
......
8.2A
123A
PKZM
3,8 A
PKZM
7,0 A
HW-Diagram No.
Used type
KTO1140
KTS1141
3BHS119662E01
=CBU1+A04
Device
-B7201
-B7151
HW-Diagram No.
Used type
KTO1140
KTS1141
3BHS119828E01
Description
Cabinet temp. Monitoring
Air / air heat exch. ON
HW-Diagram No.
Used type
TB820V2
3BHS227354e01
Sign:
Setting Test field
DI810
Description
Cabinet temp. Monitoring
Air / air heat exch. ON
Description
Module Bus
CLUSTER ADDRESS
Test field
TB820V2
=INU1+A03
Device
-B4201
-B4151
=WCU1+A05
Device
-A5201
Sign:
Setting
60C
50C
Setting range
0...60C
0...60C
Setting range
0...60C
0...60C
Setting range
0..9
Date: 2007-07-06
Page
1 of 2
Sign:
Setting
60C
50C
Test field
Sign:
Setting
60C
50C
Test field
Sign:
Setting Test field
Documnet No.:
3BHS227347D01_Rev_ -
ACS6000_Settings_SN 403.xls
Installation: Coperion W&P/ Tasnee
Order number: 0011042645
Type code: ACS 6105_L12_1a9_C24_W1a
Converter S/N: 403
Module Bus
DI810
KEY CODE
Module Bus
DO820
KEY CODE
Module Bus
AI810
KEY CODE
Cooling fans in swingfame ON
KTO1141
Cabinet temp. Monitoring
KTO1140
Cooling pump 1
PKZ2/ZM
Irm =15xIr
PKZ2/ZM
Cooling pump 2
PKZ2/ZM
Irm =15xIr
PKZ2/ZM
*) pls. compare nominal current on the
name plate of the pump motor, setting have
to be readjusted
Power supply COU / Converter with air/air
heatexchanger
PKZM
Date: 2007-07-06
0...60C
0...60C
403
AA
AD
AE
45C
55C
10,3A *)
.......... A
10,3A *)
.......... A
15,7A
Page
2 of 2
Documnet No.:
3BHS227347D01_Rev_ -
Front view
**
**
**
**
160
6.3
65 / 2.56
1000 / 39.4
1176 / 46.3
*
29 Shipping split
A-A
940 / 37
30 Lifting
42 / 1.65
30 / 1.18
30
/ 1. 1
8
75 / 2.95
150 / 5.9
32
Dervd. from:
Prepared:
O.Ackermann
30.09.04
.
Resp. dep:
Reviewed:
H.U.Lscher
30.09.04
30.09.04
Scale:
Doc-type: Format:
1:20
ZAB
Base frame
Fixing and lifting details
ATCK
Take over dep:
Approved:
W.Kpfer
anoth. no:
50
Language:
en
No.of sh:
Revision:
We reserve all rights in this document and in the information contained
therein. Reproduction, use or disclosure to third parties without express
authority is strictly forbidden.
c ABB Schweiz AG 1994
A3
B) 13.11.2006 O.Ackermann
3BHS199089
Switzerland Ltd
100
Sheet no:
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd.
Project:
Item:
Extruder 4.4 MW
Customer:
ODP Helsinki
ACS 6105_L12_1a9_C24_W1a
Converter S/N:
403
Issued
Check / rel.
Resp. dept.
J. Stutz
D. Frei
/
No. of pages
3BH227361
5
Lang.
en
Rev. ind.
Page
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd.
Sheet index
Cover sheet ............................................................................................................................. 1
Sheet index ............................................................................................................................. 2
1.) Auxiliary supplies converter ............................................................................................ 3
2.) Converter cooling / raw water consumption / losses into air ..................................... 4
3.) Converter cooling / internal water cirquit ...................................................................... 4
4.) Converter cooling / losses into air.................................................................................. 4
Revision history....................................................................................................................... 5
Document Number.
3BH227361
Lang.
en
Rev. ind.
Page
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd.
Description
=WCU1 pump
=CBU1 charging transformer
[kVA] continuous
7.1
-
0.9
0.9
8.9
0.9
0.9
12.2
Consumption
1 x 230 V / 60 Hz
Description
=WCU1 space heater
Space heater total:
Space heater
[kW] continuous
0.49
0.5
Document Number.
3BH227361
Lang.
en
Rev. ind.
Page
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd.
2.) Converter Cooling / Raw water consumption / Losses into water, approx. values
Consumption
Description
(size)
=WCU1 (W1)
Losses
min. required
flow rate
[l/min]
150
Power losses
into water
[kW]
69.8
Document Number.
3BH227361
Lang.
en
Rev. ind.
Page
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd.
Revision history
Revision
-
Description
first issue / 2007-07-06 / J. Stutz
Document Number.
3BH227361
Lang.
en
Rev. ind.
Page
PROJECT :
ORDER NO. :
0011042645
CUSTOMER :
ODP Helsinki
EQUIPMENT :
CONVERTER TYPE :
ACS 6105_L12_1a9_C24_W1a
S/N: 403
DOCUMENT :
CONVERTER HW DIAGRAM
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
FRONT PAGE
2006-09-29
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
No. of sh.
Sh.no.
Cont.sh.
35
001
002
page
4
title 2
title 1
006
007
008
009
DESIGNATION BLOCK
CROSS REFERENCES
DESIGNATION BLOCK
DESIGNATION BLOCK
101
102
103
104
105
134
141
161
168
171
178
184
190
192
201
207
261
262
271
275
277
278
304
371
375
391
411
441
454
6
title 3
rev.
ind.
-
FRONT PAGE
INDEX SHEET
001
002
FOR
OF SIGNALS
"FUNCTION OF ITEM"
"FUNCTION OF ITEM"
MAIN CIRCUIT
MAIN CIRCUIT
MAIN CIRCUIT
MAIN CIRCUIT
AUX POWER SUPPLY
PROFIBUS ADAPTER
STANDARD I/O
AUX POWER
CONVERTER
OVERVIEW
CONTROL
GUSP / CONTROL
EARTH FLT DETECTION
AUX POWER
CHARGING UNIT
DISCHARGING UNIT
DOOR MONITORING
DOOR MONITORING
COOLING
COOLING
CABINET TEMPERATURE
CABINET TEMPERATURE
FIBRE OPTIC CONNECTIONS
FIBRE OPTIC CONNECTIONS
FIBRE OPTIC CONNECTIONS
FIBRE OPTIC CONNECTIONS
MOTOR SIDE
LINE SIDE
MOTOR SIDE
CONVERTER INTERFACE
CONVERTER INTERFACE
CONVERTER INTERFACE
CONVERTER INTERFACE
CONVERTER INTERFACE
INTERNAL SIGNALS
AUX POWER DISTRIBUTION
AUX POWER SUPPLY
AUX POWER SUPPLY
AUX POWER SUPPLY
INTERNAL SIGNALS
CAPACITORS
CAPACITORS
INTERNAL SIGNALS
INTERNAL SIGNALS
INTERNAL SIGNALS
INTERNAL SIGNALS
INTERNAL SIGNALS
INTERNAL SIGNALS
INT-BOARD
INTERNAL SIGNALS
INTERNAL SIGNALS
INTERNAL SIGNALS
AMC BOARD
PINT-BOARD
INT-BOARD
DOOR INTERLOCKING
DOOR INTERLOCKING
CABINET
INT-BOARD
=COU / =INU
FT-LINK
FSCD BOARD
CONTROL
=COU1
=LSU1
=INU1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
INDEX SHEET
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
001
002
006
Not used on
Converter level
Classification of units
Numbering
BCU
CBU
COU
EXU
IFU
INU
IRU
ISU
LSU
RBU
TEU
VLU
WCU
1 2 3 4 5
6
+ NN AA NN AA NN .A...N...
+A 01
Cubicle No.
High voltage/group
Qualifying
Symbol
1 2 3
- A NNN AN
F
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
Section
Not used on
Converter level
E
=
=
=
=
=
=
=
=
=
=
=
=
=
Qualifying
Symbol
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Qualifying
Symbol
1 2 3
4 5
= N AA NN . AAA N
= ARU 1
Section
Section
Number (extension)
Number
Kind
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
002
006
007
DC+
NP
DC-
DC+
NP
DC-
INTERNAL WIRING:
REFERENCE TO RELEVANT STANDARD
DOCUMENT NR.
SHEET 112
3BHS119827E01
111.B8
111.B8
111.B8
112.B1
112.B1
112.B1
=INU2+A09
-INU2
3BHS119827E01
/191.A4
DC+
NP
DC-
SHEET
COORDINATE
/191.A4
SLAVE ELEMENT CAN
BE FOUND ON PAGE 191.A4
SHEET NUMBER
AND COORDINATE
WIRE NR OR NAME
-A4061
-A4011
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
CROSS REFERENCES OF SIGNALS
2006-09-29
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
006
007
008
KIND OF ITEM
KIND OF ITEM
RELAYS,
MOTORS
MEASURING EQUIPMENT,
TESTING EQUIPMENT
CAPACITORS
DELAY DEVICES,
STORAGE DEVICES,
BINARY ELEMANTS
PROTECTIVE
DEVICES
EXAMPLES
MISCELLANEOUS
LETTER
CODE
TRANSDUCERS FROM
NON-ELECTRICAL
QUANTITY TO
ELECTRICAL QUANTITY
AND VICE-VERSA
RESISTORS
SIGNALLING
DEVICES
NOT USED
F
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
AMPLIFIERS,
REGULATORS
LETTER
CODE
K
L
M
N
P
Q
EXAMPLES
HEAVY DUTY CONTACTORS; AUXILIARY CONTACTORS; AUXILIARY
RELAYS; TIME DELAY RELAYS; FLASHING RELAYS AND REED RELAYS.
CHOKES, INDUCTION COILS.
DC MOTORS, AC SINGLE PHASE AND 3 PHASE MOTORS
DEVICES FOR ANALOG CONTROL, REGULATION AND COMPUTING;
ELECTRONIC AND ELECTROMECHANICAL REGULATORS; OPERATIONAL
AMPLIFIERS; INVERTING AMPLIFIERS; ISOLATING AMPLIFIERS;
IMPEDANCE BUFFERS; CONTROL EQUIPMENT SETS; MASTER ANALOG
CONTROLLERS; ANALOG COMPUTERS, INTEGRATED CIRCUITS WITH
ANALOG FUNCTIONS.
ANALOG, BINARY AND DIGITAL INDICATING AND RECORDING
MEASURING DEVICES (INDICATORS, RECORDERS, COUNTERS);
OSCILLOSCOPES; DATA DISPLAY DEVICES; SIMULATORS; TEST
ADAPTERS; POINTS FOR MEASURING,
TESTING AND SUPPLY.
MAIN CIRCUIT SWITCHES; SWITCHES WITH PROTECTIVE DEVICES;
CIRCUIT BREAKERS; HIGH-SPEED CIRCUIT BREAKERS; ISOLATORS;
ON-LOAD ISOLATORS; STAR-DELTA SWITCHES; POLE CHANGING
SWITCHES; CONTROLLER DRUMS; DISCONNECTING LINKS; CELL
SWITCHES; PROTECTIVE ISOLATORS; PROTECTIVE ON-LOAD
ISOLATORS; HOUSE-WIRING SWITCHES; PROTECTIVE MOTOR
SWITCHES
INDUCTORS
SWITCHING DEVICES
FOR POWER CIRCUITS
GENERATORS,
SUPPLIES
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
ASSEMBLIES
SUBASSEMBLIES
SWITCHES
SELECTORS
TRANSFORMERS
Date
Date
R
S
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
007
008
009
KIND OF ITEM
LETTER
CODE
EXAMPLES
KIND OF ITEM
MODULATORS,
TRANSDUCERS FROM ONE
ELECTRICAL QUANTITY
TO ANOTHER
FREQUENCY MODULATORS; (-DEMODULATORS); (CURRENT-), VOLTAGETO- FREQUENCY CONVERTERS; FREQUENCY- TO- VOLTAGE (CURRENT)
CONVERTERS; ANALOG- TO- DIGITAL CONVERTERS; DIGITAL- TOANALOG CONVERTERS; SIGNAL BUFFER STAGES; DIRECT CURRENT AND
DIRECT VOLTAGE CONVERTERS; DISCRIMINATORS, PARALLEL- TOSERIES CONVERTERS; SERIES- TO- PARALLEL CONVERTERS;
CODING DEVICES; DECODING DEVICES; OPTOCOUPLERS; REMOTE CONTROL
EQUIPMENT.
EQUIPMENT.
TUBES,
SEMI- CONDUCTORS
TRANSMISSION PATHS,
WAVE- GUIDES
TERMINALS,
PLUGS, SOCKETS
ELECTRICALLY OPERATED
MECHANICAL DEVICES
TERMINATIONS,
EQUALIZING DEVICES,
FILTERS, LIMITERS,
CABLE TERMINATIONS
6
LETTER
CODE
EXAMPLES
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
008
009
101
=LSU1+A01
-LSU1
DC+
DC+_A01 102.B1
NP_A01 102.B1
DC-_A01 102.B1
DC-
-E3151
=ACS6000/271.B1
COOLING
=ACS6000/261.B2
Door
supervis
-B3201
=ACS6000/277.D1
CABINET
TEMP.
-W412104 1
BOARD
-A3101
=ACS6000/441.B2
PINT-BOARD
C779
=ACS6000/178.B6
COU
INTERFACE
-S3201_02
-R3023
CONTROL
-G3101
-F3111
=ACS6000/190.D4
BOARD
UF C765
1L1
1L2
1L3
2L3
2L2
2L1
PE
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
BUSBAR CONFIGURATION 1
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
1L1_A01
1L2_A01
1L3_A01
2L3_A01
102.C1
102.D1
102.D1
102.D1
2L2_A01 102.D1
2L1_A01 102.D1
PE_A01 102.E1
2006-09-29 Title
MAIN CIRCUIT
2006-09-29
=LSU1 +A01
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
009
101
102
=COU1+A02
-COU1
101.B8
101.B8
DC+_A01
NP_A01
BUSBAR CONFIGURATION 1
DC+
DC-_A01
NP
DC-
DC+_A02
NP_A02
DC-_A02
103.B1
103.B1
103.B1
L1_A02
103.D1
-DOOR_INT
=ACS6000/261.A2
-K281...
-A2451
101.C8
101.D8
101.D8
101.D8
101.D8
101.D8
1L1_A01
1L2_A01
-A2501
=ACS6000/134.C2
NPBA12
ProfiB
=ACS6000/391.D6
TB820
-A2951
=ACS6000/391.A6
XV C 769
CONTROL
-A2401
=ACS6000/411.B2
AMC
BOARD
1L3_A01
2L3_A01
2L2_A01
2L1_A01
=INU:L1
=INU:L2
=INU:L3
=LSU:1L1
=LSU:1L2
=LSU:1L3
=LSU:2L3
=LSU:2L2
=LSU:2L1
-Q1001_1073
=ACS6000/171.A1
AUX POWER
-TERM_X1_2 -X131_132
=ACS6000/141.B2
PROCESS
INTERFACE
-TERM_X4
L2_A02
L3_A02
=ACS6000/201.A1
CBU
INTERFACE
=ACS6000/141.C7
MCB
INTERFACE
101.E8
PG
PE
PE_A01
PG_A02
PE_A02
103.D1
103.D1
103.E1
103.E1
150 mm
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
101.B8
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
101
102
103
=INU1+A03
-INU1
102.B8
102.B8
DC+_A02
NP_A02
BUSBAR CONFIGURATION 1
DC+
DC-_A02
=ACS6000/184.B6
GUSP
CONTROL
=ACS6000/261.D2
DOOR
MONITORING
-E4161
-B4201
=ACS6000/275.B2
COOLING
102.D8
L1_A02
L2_A02
L3_A02
102.E8
102.E8
PG_A02
PE_A02
F
A
B
C
D
Date
Name
0
104.B1
104.B1
104.B1
PG_A03
104.E1
=ACS6000/454.B1
INT-BOARD
=ACS6000/278.D1
CABINET
TEMP.
-A4132
-F4011
-A4133
-F4012
=ACS6000/454.E1
SVA
XVC 767
-A4051
=ACS6000/271.B2
COOLING
DC-
DC+_A03
NP_A03
DC-_A03
BOARD
-A4121
-E4151_53
102.D8
102.D8
NP
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
102.B8
=ACS6000/454.E1
SCA
XVC 768
=ACS6000/375.B5
FSCD BOARD
=ACS6000/375.B5
FSCD BOARD
PG
PE
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
PE_A03
2006-09-29 Title
MAIN CIRCUIT
2006-09-29
=INU1 +A03
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
104.E1
102
103
104
=CBU1+A04
-CBU1
103.B8
103.B8
DC+_A03
NP_A03
BUSBAR CONFIGURATION 1
DC+
NP
DC-_A03
DC-
INTERFACE =INU1
-A7101
-V7101
-F7101
-V7102
-F7102
=ACS6000/207.C4
IGCT
INTERFACE CONTROL
-A7091
-S7201_03
D
=ACS6000/201.D4
CHARGING
UNIT
=ACS6000/262.B2
DOOR
MONITORING
-E7151
-B7201
=ACS6000/271.C2
COOLING
103.E8
103.E8
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
103.B8
A
B
C
D
Date
=ACS6000/277.D8
CABINET
TEMP.
/201.A4
/201.A6
=ACS6000/207.D4
IGCT
=ACS6000/207.D5
VLSCD
BOARD
-Z7081
PG
PE
PG_A03
PE_A03
Name
0
-Q7121
=ACS6000/207.C5
VLSCD
BOARD
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
PE_A04
2006-09-29 Title
MAIN CIRCUIT
2006-09-29
=CBU1 +A04
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
105.E1
103
104
105
-TERM_X1
-TERM_X17
-TERM_X2
-TERM_X18
=ACS6000/161.A2
AUX POWER
400V,60Hz
=ACS6000/141.B1
STANDARD
I/O
=ACS6000/161.C2
SP. HEATER
230VAC
=ACS6000/141.C8
STANDARD
I/O
-TERM-X512
=ACS6000/192.B6
AUX POWER
230VAC
-TERM_X513
=ACS6000/161.A5
AUX POWER
400V_60Hz
-TERM_X515
=ACS6000/161.B5
SP. HEATER
1~ 230V
104.E8
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
=WCU1+A05
-WCU1
A
B
C
D
Date
=ACS6000/192.D6
AUX POWER
-G5021
-A5201
=ACS6000/391.D2
TB820
PE
PE_A04
Name
0
-TERM-X511
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
104
105
134
=COU1
+A02
-A2451
CUSTOMER
INTERFACE
NPBA_A
NPBA_B
/102.C3
NPBA-12
X1:1
X1:2
X1:3
X1:4
Data
Data
Data
Data
A
B
A
B
N
P
N
P
X2:8 SH
X2:7 DG
TXD
RXD
X2:5 +24V
X2:6 0V
DC
DC
GND
BUS
TERMINATION
ON
OFF
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
105
134
141
*) PROCESS INTERFACE
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
-W14102
=WCU1+A05
=COU1+A02
-TERM_X17
/105.B5
-X17 -W14101
1
1
DIGITAL INPUT
=COU1+A02
TERM_X17
-X17 -W04102
1
19
-TERM_X1_2
/102.D4
-X1
3 24VDC
2
4
PROCESS STOP INU1
3
5
4
6
OPERATION
PREVENTED INU1
5
15
6
16
OPERATION
1
17
18
2
EMERGENCY STOP
3
19
20
4
-X2 EMERGENCY STOP
5
71
6
72
EMERGENCY-OFF
7
73
74
8
EMERGENCY-OFF
75
9
10 76
EMERGENCY
11 77
RESET
12 78
EMERGENCY
20
21
22
23
24
2
3
4
5
6
DIGITAL INPUT
TERM_X1_2
-X2
79 24VDC
80
MCB STATUS CLOSED
81
82
MCB STATUS OPEN
31
32
MCB PRE-TRIP
DIGITAL OUTPUT
-TERM_X4
RESET
DIGITAL OUTPUT
TERM_X4
INU1 OPERATION
PREVENTED
-X4
55
TERM_X18
-X18
-W14105 1/BN
15
56
3/BK16
/102.E4
-X4
1
2
3
4
5
***) 7
***) 8
6
9
***) 51
***) 52
10
53
54
*) Details
**) Details
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
=WCU1+A05
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
-TERM_X18
/105.C5
-W14103 1 -X181
2
3
4
5
7
2
3
4
5
7
8
6
9
11
8
6
9
11
12 12
10 10
1/BN13
3/BK14
-W14104
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
134
141
161
AUX POWER
3x400V / 60HZ
-X1
=WCU1+A05
-TERM_X1
/105.B3
-X1
1
2
3
PE
-Q5003
-TERM_X2
/105.C3
-X2
1
2
PE
-W16101 1/BN
2/BU
3/BK
WCU1_L1 171.A5
WCU1_L2 171.A5
WCU1_L3 171.A5
-Q5004
-Z5001
-X554
-M5541 M -M5542 M
PUMP 1
PUMP 2
-Q5011
-K5451
-TERM_X515
/105.E5
-X515
PE
1
3
SHC_L
168.E7
2
4
PE
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
/105.D5
-X513
1
2
3
-Q5001
-TERM_X513
-Q5002
SPACE HEATER
CONVERTER
230VAC
-X2
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
141
161
168
TRANSP_UNIT 1
-E5011
161.C5
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
SHC_L
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
161
168
171
5
161.A6 WCU1_L1
161.A6 WCU1_L2
161.A6 WCU1_L3
=COU1+A02
-Q1001_1073
/102.D5
-X20
-Q1004
-T1012
.../230V
3
L3
-Q1003
-T1021
-V1021
-Z1021
-Z1022
WCU
Date
178.C3 Q1061
LSU1
Name
0
E
F
G
H
Date
-Q1041
-C1026
...28
-C1021
...25
-R1022
-Q2981
24V
271.A1 A02_Q1014
A
B
C
D
-Q1073
-X24_P
I/O Ext. 24VDC
-X24_P2
24VDC
-X24_P1
24VDC
Name
CONTROL
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
GUSP
Date
Date
275.A1 A02_Q2981
WCU
-G1211
184.B3 Q1041
I/O
Ext.
-G1201
COOLING
-Q1051
-Q1061
-Q1071
Control PUMP
&
Regul. Valves
192.D2 Q1071
-X230V
Control
184.D3 Q1051_1
-Q1011
-Q1012
-E1011
192.C2 Q1012
-Q1013
-Q1014
L2
-Q1001
-V1022
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
L1
201.E2 Q1003
CBU1
COOLING
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
168
171
178
=LSU1+A01
-G3101
=COU1+A02
AUX POWER DISTRIBUTION
C
171.E2
Q1061
/101.C2
CONTROL VOLTAGE
-X3
21
-W17801 BN
22
BU
-X311
1
2
PE
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
171
178
184
=INU1+A03
-G4101_13
=COU1+A02
AUX POWER DISTRIBUTION
171.E5
Q1041
/103.C2
-X3
65
-W18401 BN
66
BU
-X411
1
2
3
4
5
6
D
171.E3
Q1051_1
-X3
15
-W18402 BN
16
BU
GUSP
G4101
-G4111
G4102
-G4112
G4103
-G4113
~
~
/207.C2
/207.B2
/207.D2
/207.E2
/190.E2
/190.D2
CONTROL VOLTAGE
G4104
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
178
184
190
=LSU1
+A01
-F3111
/101.C6
=INU1
+A03
-G4113
/184.C6
X3.12
=INU1
+A03
-A4121
EAF
X3.11
X3.51
-W19001 A1
X3.52
SH
/454.B1
X1
X2
Sig-In
Sig-Gnd
X3:2 5AF
X3:1
Pwr_In
Pwr_Gnd
A1
TX
-W19002
FO
INT-BOARD
A818
POWER ON
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
184
190
192
=WCU1+A05
-TERM-X512
AC
/105.C5
171.C1
Q1012
WCU
-X3
7
-W19201 1/BN
2/BU
-X512
1
2
WCU
230VAC
=WCU1+A05
-TERM-X511
D
AC / DC
/105.D5
171.C2
Date
Name
Q1071
-X3
71
-W19202
WCU 72
1/BN
-X511
1
2/BU
-G5021/(22)
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
=COU1+A02
CONTROL VOLTAGE
A
B
C
D
Date
Name
0
E
F
G
H
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
190
192
201
=CBU1+A04
-CBU1
=ACS6000/104.A2
=COU1+A02
-X131_132
=CBU1+A04
-Q7121
/102.D5
=ACS6000/104.A4
-X715
1
2
OPEN
3
4
OPEN
3
4
5
6
CLOSED
11
7
8
9
CLOSED
12
10
-W20101 1
-X2
53
54
55
56
-C7011
-C7031
-C7051
-C7012
-A7091
-X2
13
-W20103
14
-X20
4
Q1003
171.E7
F
A
B
C
D
Date
Name
0
E
F
G
H
Date
-W20104
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
DC_+
DC_NP
DC_-
Name
/104.D2
-X714
1
1/BN
-X710
6
400V
2/BU
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
7
PE
0V
PE
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
192
201
207
=INU1
+A03
-G4111
DC_+
/184.B6
-V7101
X3.11
X3.51
-W20701 SH
X1.1 (-)
X3.52
A1
X1.2 (+)
/104.C6
/454.B1
-W20703
FO
-W20704
FO
INT-BOARD
A722
A211
DC_NP
=INU1
+A03
-G4112
=INU1
+A03
-A4121
-V7102
/104.D6
A1
/184.C6
=INU1
+A03
-A4121
-F7101
/104.C6
A1
X3.12
X3.51
-W20702
X3.52
SH
X1.1 (-)
A1
X1.2 (+)
-F7102
/104.D6
/454.B1
-W20705
FO
-W20706
FO
INT-BOARD
A723
A212
X3.11
DC_-
X3.12
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
=CBU1+A04
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
201
207
261
=COU1+A02
DOOR MONITORING
-DOOR_INT
/102.B5
230V
-K2814
-X3
10
-W26101 1
=LSU1+A01
DOOR INTERLOCKING
-K2811
-S3201_02
+24V
-X1 9
-W26102
-X312 1
-K2812
1
4/BU
3/BN
10
/101.C3
A2
A1
-X312
-W26105
=INU1+A03
-S4201_03
-W26106
-X412 1
4/BU
3/BN
10
/103.C3
A2
A1
-X412 4
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
chwekue
W.Kpfer
ACS 6000
Date
Date
DOOR_LOCK_1
262.A6
DOOR_LOCK
262.A6
LOOP2_1
262.A5
LOOP2
262.A5
LOOP3_1
262.A5
LOOP3
LOOP1_1
Prepared
Approved
Project name
262.A4
262.A3
262.A3
LOOP1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
207
261
262
-S7201_03
-X712 1
DOOR_LOCK_1
261.F6
261.F6
261.F5
LOOP2_1
261.F5
LOOP2
261.F5
LOOP3_1
DOOR_LOCK
-W26202
4/BU
3/BN
10
/104.D3
A2
A1
-X712 4
-W26207
-W26208
8
BN
BU
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-W26201 1
=CBU1+A04
LOOP3
LOOP1_1
LOOP1
4
261.F4
261.F3
3
261.F3
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
261
262
271
=COU1+A02
N
L1
/103.D2
-X312
11
2/BU
-W27104
=INU1+A03
-E4151_53
56
2/BU
55
1/BN
54
1/BN
-W27101
=LSU1+A01
-E3151
B /101.C2
-X412
11
12
12
-W27105
=CBU1+A04
-E7151
/104.D2
-X712
11
12
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X3 53
1/BN
A02_Q1014
171.E1
2/BU
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
262
271
275
=COU1+A02
A02_Q2981
0V
24VDC
68
63
-W27504
=INU1+A03
-E4161
64
/103.C2
-X413
3
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X1 67
2/BU
171.E7
1/BN
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
271
275
277
=COU1+A02
CABINET
TEMP.
-TEMP_LS1
-X1 1
=COU1+A02
+24V
-X2 51
-W27701 1
CABINET
TEMP.
-TEMP_CBU
+24V
-W27717
52
1
=LSU1+A01 -X313 1
-B3201
/101.C3
=CBU1+A04 -X713 1
-B7201
/104.D3
-X313 2
-X713 2
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
275
277
278
=COU1+A02
CABINET
TEMP.
-TEMP_INU
+24V
-X155
56
-W27801 1
=INU1+A03 -X413 1
-B4201
/103.C3
T
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X413 2
Date
A0
B
C
D
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
277
278
304
=INU1 INT-BOARD
A304
+A03
A303
-A4121
/454.B1
=INU1 INT-BOARD
A404
+A03
A403
-A4121
-W30401
FO
-W30402
FO
-W30405
-W30406
/454.B1
FO
FO
AMC-BOARD =COU1
+A02
-A2401
A704
A703
/411.B2
AMC-BOARD =COU1
+A02
-A2401
A702
A701
/411.B2
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
278
304
371
=INU1 INT-BOARD
+A03
A209
-A4121
/454.B1
INT-BOARD
-W37101 FO
-W37102
FO
=LSU1 PINT-BOARD
+A01
RX2
-A3101
/441.B2
PINT-BOARD
TX2
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A724
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
304
371
375
=LSU1
+A01
-A3101
/441.B2
=LSU1
+A01
-A3101
PINT-BOARD
TX0
PINT-BOARD
TX1
-W37501 FO
INT-BOARD
A202
-W37502
INT-BOARD
A201
FO
=INU1
+A03
-A4121
/454.B1
=INU1
+A03
-A4121
/454.B1
/441.B2
=INU1
+A03
-F4011
FSCD
/103.C6
=INU1
+A03
-F4012
FSCD
A2
A2
-W37513
-W37514
FO
PINT-BOARD
RX0
FO
PINT-BOARD
RX1
/103.D6
=LSU1
+A01
-A3101
/441.B2
=LSU1
+A01
-A3101
/441.B2
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
371
375
391
=COU1
+A02
-A2951
/102.C5
=INU1 INT-BOARD
+A03
A594
-A4121
XV C769 AE101
/454.B1
-W39103
FO
0V
X1.3
24V
X1.2
SIG
X1.1
A1
C
=WCU1
+A05
-A5201
=COU1
+A02
-A2501
/105.E5
FIBRE OPTIC CONNECTIONS
TB820
TX2
RX2
/102.C5
-X4
-W39101 FO
-W39102
-X5
TX1
RX1
FO
-X4
-X5
TB820
RX2
TX2
RX1
TX1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
chwekue
W.Kpfer
ACS 6000
Date
Date
Doc. des.
3BHS227357E01
Resp. dept.
Doc.No.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Last sh.
Sh.no.
Cont.sh.
375
391
411
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
Date
Name
0
/102.D4
=COU1
+A02
-A2401
E
F
G
H
RX CH1
TX
A709
A710
RX CH2
TX
A711
A712
RX CH3
TX
A707
A708
RX CH0
TX
AMC BOARD
A705
A706
DSP56311
RX INT0
TX
PANEL &
BUS
INTERFACE
A701
A702
6 X17
RS485
R P T2 S1 S0
+24V
0V
+24V
0V
Name
F M T1 S3 S2
X14:1
X14:2
X14:3
X14:4
Date
Prepared
Approved
Project name
chwekue
W.Kpfer
ICMC0-ASIC
ACS 6000
/304.A6
Date
Date
X1
64
EXTENSION
PORT
/304.A6
A715
A716
RX CH5
TX
A717
A718
RX CH6
TX
A719
A720
RX CH7
TX
X501
FLASH
MEMORY
SUBPRINT
X502
RX CH4
TX
A713
A714
PROM, SRAM
3BHS227357E01
RX INT1
TX
ICMC1-ASIC
Doc. des.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Resp. dept.
Doc.No.
A703
A704
Last sh.
Sh.no.
Cont.sh.
391
411
441
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
Date
Name
0
=LSU1
+A01
-A3101
/101.C6
E
F
G
H
Date
chwekue
W.Kpfer
RX0
RX1
CHANNEL 1+2
RX2
CHANNEL 2
RX3
RX4
/375.B7
/375.B7
/371.D4
3
Prepared
Approved
Project name
ACS 6000
/371.D4
TX0
TX1
CHANNEL 1+2
TX2
CHANNEL 2
TX3
TX4
PINT-BOARD
Name
/375.A2
/375.A2
X11:1
X11:2
X12:1
X12:2
X13:1
X13:2
Date
Date
X14:1
X14:2
X16:1
X16:2
X15:1
X15:2
X21:1
X21:2
X22:1
X22:2
X23:1
X23:2
X24:1
X24:2
3BHS227357E01
X1:1
X1:2
X26:1
X26:2
X2:1
X2:2
Doc. des.
ATD
= ACS6000
+
Lang. EN
3BHS227357E01
Resp. dept.
Doc.No.
X25:1
X25:2
Last sh.
Sh.no.
Cont.sh.
411
441
454
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
INT-BOARD
3300V
=INU1
+A03
-A4121
/103.C6
/103.C6
=INU1
+A03 SVA, XVC767..
-A4132
9MVA
Date
/103.D6
Name
0
Name
A812
A704
V568
V567
V566
V565
V564
V563
V562
V561
A816
A641
A205
A206
Prepared
Approved
Project name
A208
A705
A203
A805
A204
A804
A210
A814
A202
/375.A3
A815
A201
/375.A3
A715
A714
A531
A592
A541
A302
A551
A402
/207.D7
A212
A723
Doc. des.
A303
/391.A3
A593
A594
A304
/371.B4
/371.A4
A724
A209
A403
/304.A3
7
3BHS227357E01
ATD
3BHS227357E01
Resp. dept.
Doc.No.
A712
A713
A211
A722
/207.B7
A813
Date
Date
A207
2006-09-29 Title
2006-09-29
chwekue
W.Kpfer
A803
INT-BOARD
MOTOR SIDE
=INU1
ACS 6000
A703
V591
=INU1
+A03 SCA, XVC768..
-A4133
Date
E
F
G
H
A802
/190.E7
A818
A817
A702
/304.A3
A404
= ACS6000
+
Lang. EN
+24V 2
0V
+24V 1
X1:3
X1:2
X1:1
Last sh.
Sh.no.
Cont.sh.
V103
V113
441
454
COMPONENT :
DOCUMENT :
WIRING DIAGRAM
=COU1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
0
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
FRONT PAGE
2006-09-29
Doc. des.
29.09.2006
Resp. dept.
Doc.No.
ATD
= COU1
+
Lang. EN
3BHS227955E01
No. of sh.
Sh.no.
Cont.sh.
30
001
002
page
title 1
100
101
102
104
105
106
107
120
121
230
240
245
250
251
252
253
254
281
282
283
285
287
290
291
295
296
298
800
4
title 2
6
title 3
rev.
ind.
FRONT PAGE
INDEX SHEET
001
002
AC AUX DISTRIBUTION
230VAC AUX POWER DISTRIBUTION
CONTROL
GUSP AND CONTROL VOLTAGE
GUSP AND CONTROL VOLTAGE
Line Supply Unit CONTROL
AUX POWER SUPPLY 230VAC/24VDC
230VAC/24VDC DISTRIBUTION
230VAC/24VDC DISTRIBUTION
PANEL
AMC-BOARD
PROCESS INTERFACE
COUPLING DEVICE
DIGITAL INPUT MODULE
DIGITAL OUTPUT MODULE
DIGITAL INPUT MODULE
DIGITAL OUTPUT MODULE
DOORLOCK
EXTERNAL DIGITAL INPUT
EMERGENCY STOP
EMERGENCY-OFF
MONITORING
CONTROL UNIT / CAPACITOR BANK UNIT
MOTOR CABINET TEMPERATURE
MCB INTERFACE
MCB INTERFACE
COOLING FAN`S
FUNCTION EARTH
PULSE INTERFACE
POWER STAGE CONTROL
WATER COOLING UNIT
INTERNAL CIRCUIT
EXTERNAL I/O
FRONTDOOR
PROFIBUS ADAPTER
TB820
DI810 + TU830
DO810 + TU830
DI810 + TU830
DO820 + TU831
CONTROL
PROTECTION EARTH
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
INDEX SHEET
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
001
002
100
PE
1
-W004
-PE 1
-W637 1
-W022 1
-W009 1
-Q1003
1.14
1.22
-Q1001
1
3
5
1
3
5
-W018
-W019
13
21
A1
A2
-W024 1
1
-W636
1
-W025
2
4
6
/290.D8
14
22
2
4
6
-Q1004
1.13 /287.B4
1.21
-W001 1
1
-W002
1
-W003
1.14
1.22
1
3
5
2
4
6
1.13 /290.D4
1.21
-W873 1
-W871 1
-X20 1
-W872 1
T1012_1
NO SAFE LINE
CHARGING
VOLTAGE CBU
TRAFO
F
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
101.A1
-X20 4
102.A3
102.A3
102.A3
Date
Date
T1012_2
T1021_U
T1021_V
T1021_W
-W020 1
-W021
101.A1
-W005 1
1
-W006
1
-W007
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
230VAC
DISTRIBUTION
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
002
100
101
PE
2_0V
-W034 1
-W029 1
-W044 1
-W045 1
11 12 13 14
-PE1 1
-XN
.D1
-W047 1
-W048
-W049 1
A
B
C
D
Date
-PE1 4
-PE1 3
.E1
-W032 1
-PE 4
.E1
-W033 1
-X3 7
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Name
E
F
G
H
Date
Name
-W050 1
-E1011
-W780 1
-X3 53
WCU
CONTROL
230VAC
1.14
1.22
1.13/287.C4
1.21
FAZ-C
-W046 1
CLAMP
DISTRIBUTOR
/120.A2
/120.D2
/120.F3
/121.A4
/121.D5
1 2 3 4
.B1
.B1
/281.E1
.E6
/290.E8
.E3
/102.D4 /281.E4
/102.E8
-XN
-Q1014
FAZ-C
PE
/102.A2
.D3
.C1
1.13/287.D2
1.21
-Q1013
/281.A4
/290.D8
-W043 1
-X230V
-W039 1
-W040 1
11 12 13 14
FAZ-C
1.14
1.22
CLAMP
DISTRIBUTOR
-Q1012
-W037 1
-W038 1
1 2 3 4
FAZ-C
-W035 1
-W036 1
-X230V
-Q1011
1.14
1.22
/102.A1
.D2
-W030 1
-W031 1
.E1
1.13/287.C2
1.21
-PE1 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
0V
110V
120V
230V
380V
400V
415V
440V
460V
480V
500V
-T1012
2_230V
100.E7
100.E7
T1012_1
T1012_2
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
-W781 1
55
54
56
AIR COOLING
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
100
101
102
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
3
4
5
.E4
-W150 1
-X1021 2C
-W152 1
-W153
.E4
-X1021 3B
3C
-C1021
-X1021 3D
CU
.E4
5D
CU
-W154 1
2
4
105.B1
-X1021 5B
1
3
-R1022
CTRL_-DC
-C1029
-R1021
CTRL_+DC
-W156 1
105.B1
.E4
-W155 1
5E
-W157 1
2
4
101
102
104
Al
5F
4F
3 1
5C
-W161 1
1
3
Last sh.
Sh.no.
Cont.sh.
CU
-C1026
5A
-PE1 6
-W158 1
/101.E1
= COU1
+
Al
2
GSP_-DC -W162 1
100.E4
100.E4
100.E4
.E4
.E4
104.B1
T1021_U
T1021_V
T1021_W
-X1021 2F
-X1021 1F
9 7
6 5 4
2A
Doc. des.
-X1021 2B
.E4
-W159 1
GSP_+DC -W160 1
Lang. EN
3BHS227955E01
Resp. dept.
Doc.No.
104.B1
-Z1021
-Z1022
-V1022
VUO 60-12NO3
-XN
-W144 1
.E7
.B8
.D7
-W141 1
-PE1 5
/101.E1
5D 5A
5E 5B
5F 5C
-X230V
4 5 6
7 9
.C8
.D8
.B5
4D 4A
4E 4B
4F 4C
1V8
1V7
1V6
1V5
1V4
1V3
1V2
1V1
2N
PE
.B7
.C6
/101.C1 /101.D1
-W581 1 -W582 1
-W140
1 3
-W143 1
4E
-X1021
Date
Date
.E3
.C5
3D 3A
3E 3B
3F 3C
.E6
.D6
.C6
A2
15 /287.C7
25
-W139 1
-V1021
.E4
-W142 1
-X1021 1E
Name
script_ecscad_403
W.Kpfer
.B5
.C8
2D 2A
2E 2B
2F 2C
L3
A1
18
16
28
26
Date
Prepared
Approved
Project name
ACS 6000
.E3
.C5
1D 1A
1E 1B
1F 1C
L1
L2
-W138 1
-W137 1
2W 200V
380V 1W8
400V 1W7
415V 1W6
440V 1W5
460V 1W4
480V 1W3
500V 1W2
690V 1W1
-W136 1
DT
2V 200V
380V
400V
415V
440V
460V
480V
500V
690V
Name
E
F
G
H
VUO 60-12NO3
-T1021
Date
2U 200V
380V 1U8
400V 1U7
415V 1U6
440V 1U5
460V 1U4
480V 1U3
500V 1U2
690V 1U1
-F1021 EMR4-W500-2-C
Rev. ind.
-Q1041
1.14
1.22
FAZ-2-DC
1.13/287.C2
1.21
GSP_+DC
GSP_-DC
1+
3-
102.F6
102.F7
24+
-W060 1
-W061 1
-X3
65
66
INVERTER 1
GUSP
300VDC
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
102
104
105
-W072 1
-W073 1
-Q1051
106.B1
106.B1
1.14
1.22
FAZ-2-DC
+DC
-DC
1.13/287.A3
1.21
CTRL_+DC
CTRL_-DC
1+
3-
102.C8
102.C8
24+
-W066 1
-W067
16
-X3
15
INVERTER 1
CONTROL
300VDC
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
104
105
106
-W078 1
-W079 1
-Q1061
24+
107.B1
107.B1
1.14
1.22
FAZ-2-DC
+DC
-DC
1.13/287.A3
1.21
+DC
-DC
1+
3-
105.B8
105.B8
-W074 1
-W075
22
-X3
21
LSU 1
CONTROL
300VDC
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
105
106
107
-Q1071
1.13/287.B3
1.21
FAZ-2-DC
24+
24+
1.14
1.22
FAZ-2-DC
-Q1073
1+
3-
-W092 1
-W093 1
+DC
-DC
1+
3-
106.B8
106.B8
F
A
B
C
D
Date
Name
E
F
G
H
Date
Name
120.A2
120.A2
WCU
CONTROL
300VDC
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
SUPPLY48V_P1
SUPPLY48V_N1
71
72
-X3
121.A5
121.A5
SUPPLY24V_P1
SUPPLY24V_N1
-W080 1
-W081 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
106
107
120
1 2 3 4 5 6 7
-X24_P2.1 1
11 12 13 14 15 16 17
CLAMP
DISTRIBUTOR
11 12 13 14 15 16 17
CLAMP
DISTRIBUTOR
/240.C2
/251.A2
/298.A2
.E2
/283.A6
/245.D3
/281.A2
-X24_P2
2 3 4 5 6 7
CLAMP
DISTRIBUTOR
11 12 13 14 15 16 17
.B8
-X24_N2.1 1
CLAMP
DISTRIBUTOR
/240.C2
1 2 3 4 5 6 7
11 12 13 14 15 16 17
2 3 4 5 6 7
-X24_P2
13
.B5
-W864 1
-X24_P2.1 13
.B7
-X24_N2
.C5
13
-W865 1
11 12 13 14 15 16 17
.D8
/251.A2
/298.A2
/250.E4
.B8
.E2
-X24_N2
.C8
.E3
/250.E4
11 12 13 14 15 16 17
/290.C2
14
2 3 4 5 6 7
/290.E5
/285.E7
.D2
/295.C4
CLAMP
DISTRIBUTOR
/281.E1
U02
/283.E5
/245.D3
/295.C4
/281.A6
/290.B1
CLAMP
DISTRIBUTOR
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX
11
-X24_P1 4
.B4
-X24_N1 4
2 3 4 5 6 7
-X24_N1 1
-W114 1
-W115
.D2
SUPPLY24V_P1 107.E6
-X24_P1 1
.D2
U01
/290.B5
250W
LWN
2660-6
N 2
-G1201
PE 1
-W109 1
-W110
-W111
-X24_N2.1 13
.C7
.C4
-W116 1
-PE1 9
/101.E1
-W117 1
-W118
-X24_P2 4
.B5
-X24_N2
4 14
.C5
-W119 1
-PE1 10
/101.E1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
/101.E1
L 3
-PE1 8
3
SUPPLY24V_N1 107.E6
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
107
120
121
LWN
2660-6
U01
-W124 1
1
-W125
1 2 3 4
CLAMP
DISTRIBUTOR
11 12 13 14
-X24_N
1 2 3 4
.B8
-X24_N
.C8
-W123 1
CLAMP
DISTRIBUTOR
11 12 13 14
/285.F1
/282.C2
/283.F1
-X24_P
D
-X24_P
U02
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX
11
/285.D1
/282.B2
/283.D1
-G1211
N 2
PE 1
-W120 1
-W121
-W122
.D5
SUPPLY48V_N1
/101.E1
.D5
-PE1 11
-PE1 12
/101.E1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
5
107.E6
SUPPLY48V_P1
L 3
107.E6
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
120
121
230
ON - LED ACTIVATION
(MAIN SUPPLY ON INDICATION)
-H2301
EMERGENCY STOP
-W218 1
SUPPLY ON
-W217 1
X1
FAULT/ALARM
240.C2
-A2511
/251.B2
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
X1
X2
-H2302
-W222 1
-W223 1
-W220 1
CDP312_2
-W213 1
X1
X2
X1
X2
-W221 1
-S2304
24
/285.A4 23
NDPI_02
-S2303
14
/283.C2 13
V2
-S2302
14
13
14
/285.A1 22
X2
V1
Name
-W216 1
14
13
-S2301
L1+ 24V B4
C4
L1- 0V A4
33
41
REF
34
42
RES
13
21
LOC
REM
-A2301
Date
EMERGENCY RESET
DRIVE
-W212 1
A
B
C
D
-W224 1
-W225 1
-W219 1
SUPPLY OFF
X1
X2
FUNC
ENTER
ALARM / FAULT
LED ACTIVATION
(INDICATION LAMP)
C1_P2_DO06
-A2521
/252.E2
-A2511
/251.B2
L1+ 24V B5
C5
L1- 0V A5
PAR
CDP 312R
ACT
B5 L1+ 24V
C5
A5 L1- 0V
B4 L1+ 24V
C4
A4 L1- 0V
PANEL
7
EMERGENCY OFF
RESET LED ACTIVATION
(INDICATION LAMP)
C1_P2_DO07
-A2521
/252.E2
C1_P2_DO05
-A2521
/252.E2
-W214 1
-W215 1
FRONTDOOR
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
C1_P2_DO04
-A2521
/252.E2
B6 L1+ 24V
C6
A6 L1- 0V
B7 L1+ 24V
C7
A7 L1- 0V
C1_P1_DI04
C1_P1_DI05
LOCAL ON - ORDER
(PUSH BUTTON)
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
121
230
240
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
Date
230.E2
/120.B7
A709
A710
RX CH2
TX
A711
A712
RX CH3
TX
RX CH1
TX
A707
A708
DSP56311
RX CH0
TX
A705
A706
RX INT0
TX
RS485
-W589 FO
-W590 FO
R P T2 S1 S0
+24V
0V
+24V
0V
script_ecscad_403
W.Kpfer
FB_INU_RX
FB_INU_TX
F M T1 S3 S2
X14:1
X14:2
X14:3
X14:4
Prepared
Approved
Project name
ACS 6000
245.C7
245.C7
A701
A702
-A2401 AMC-BOARD
CDP312_2
Name
-W585 1
-W586 1
Date
-X24_P2.1 4
/120.C7
-X24_N2.1 4
Name
E
F
G
H
CONNECTED TO
=INU
ICMC0-ASIC
Date
Date
X1
64
EXTENSION
PORT
RX CH4
TX
A715
A716
RX CH5
TX
A717
A718
RX CH6
TX
A719
A720
RX CH7
TX
X501
FLASH
MEMORY
SUBPRINT
X502
-W605 FO
-W606 FO
A713
A714
PROM,SRAM
= COU1
+
TB820_RX
TB820_TX
RX INT1
TX
ICMC1-ASIC
Doc. des.
Lang. EN
3BHS227955E01
Resp. dept.
Doc.No.
250.C7
250.D7
A703
A704
CONNECTED TO
=INU
Last sh.
Sh.no.
Cont.sh.
230
240
245
-A2451
NPBA_A
NPBA_B
CUSTOMER
INTERFACE
NPBA-12
X1:1
X1:2
X1:3
X1:4
A
B
A
B
Data
Data
Data
Data
N
P
N
P
X2:8 SH
X2:7 DG
-X24_P2
-X24_N2
/120.B5
/120.C5
-W624 1
-W625 1
X2:5 +24V
X2:6 0V
DC
DC
GND
TXD
FB_INU_RX
240.E4
RXD
FB_INU_TX
240.E4
BUS
TERMINATION
ON
OFF
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
240
245
250
-A2501 TB820V2
CLUSTER ADRESS
4 5 6
3
7
2
8
1 0 9
F
R
P
Rx1
Rx2
ERx
C
Tx2
Rx2
Tx1
Rx1
BUS
X4
X5
CONNECTED TO
WCU
TB820_RX
TB820_TX
240.E8
240.E8
A2511 251.E1
OUT
SB
L-
SA
L+
-W238 1 -W239 1
-X24_P2 15
/120.B5
-X24_N2
/120.C5
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
15
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
245
250
251
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
/AUXILIARIES SUPPLY
PROTECTION SWITCH
ALARM
C1_P1_DI11
/AUXILIARIES SUPPLY
PROTECTION SWITCH
TRIP
C1_P1_DI12
/PROCESS STOP
C1_P1_DI13
EXCITATION CONTACTOR
FEEDBACK STATUS
CLOSED
C1_P1_DI14
/INU CUBICLE
TEMPERATURE HIGH
C1_P1_DI15
/COU CUBICLE
TEMPERATURE HIGH
C1_P1_DI16
C1_P1_DI09
C1_P1_DI10
/287.E4
/287.E2
/282.E3
C1_P1_DI08
/230.E5
/230.E4
C1_P1_DI07
/285.E6
STATUS
INU ISOLATOR2 OPEN
GROUNDING SWITCH2 CLOSED
C1_P1_DI06
STATUS
INU ISOLATOR2 CLOSED
GROUNDING SWITCH2 OPEN
C1_P1_DI05
-X24_N2
C1_P1_DI04
/120.C5
LOCAL ON - ORDER
(PUSH BUTTON)
/287.E7
-W242 1
-W243 1
Doc. des.
C1_P1_DI03
/120.B5
B1
C1
A1
B2
C2
A2
B3
C3
A3
B4
C4
A4
B5
C5
A5
B6
C6
A6
B7
C7
A7
B8
C8
A8
B9
C9
A9
B1
B10
C1
C10
A10
A1
B11
C11
A11
B12
C12
A12
B13
C13
A13
B14
C14
A14
B15
C15
A15
B16
C16
A16
BUS
Date
Date
C1_P1_DI02
L1+
L1L1-
-W240 1
-W241
Name
script_ecscad_403
W.Kpfer
/291.E8
/291.E2
6.3A L2+
L2+
L2L2-
-W244 1
-W245 1
OUT
A2521
Last sh.
Sh.no.
Cont.sh.
24V_P2_1
24V_N2_1
= COU1
+
Lang. EN
3BHS227955E01
Resp. dept.
Doc.No.
DI810
F
R
W
KEY CODE
AA
IN
Date
Prepared
Approved
Project name
ACS 6000
C1_P1_DI01
6.3A L1+
-X24_P2
A2511
Name
E
F
G
H
/UNDERVOLTAGE (RELAY)
-A2511 TU830
Date
250.D7
A
B
C
D
SUPERVISION
SUPERVISION
Rev. ind.
252.F1
252.F1
252.B1
250
251
252
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
C1_P2_DO03
C1_P2_DO04
ON - LED ACTIVATION
(MAIN SUPPLY ON INDICATION)
C1_P2_DO05
C1_P2_DO06
ALARM / FAULT
LED ACTIVATION
(INDICATION LAMP)
C1_P2_DO07
EMERGENCY OFF
RESET LED ACTIVATION
(INDICATION LAMP)
C1_P2_DO08
C1_P2_DO09
C1_P2_DO10
C1_P2_DO12
ESTOP IN PROGRESS
(ACTIVATED)
C1_P2_DO11
C1_P2_DO13
C1_P2_DO14
EXCITATION CONTACTOR
ORDER ON COMMAND
Doc. des.
C1_P2_DO15
C1_P2_DO16
SUPERVISION
OUT
-W248 1
-W249 1
A2531
Last sh.
Sh.no.
Cont.sh.
24V_P2_2
24V_N2_2
= COU1
+
Lang. EN
3BHS227955E01
Resp. dept.
Doc.No.
L2+
6.3A
L2+
L2L2-
C1_P2_DO02
BUS
-W246 1
-W247 1
Date
Date
/283.B8
C1_P2_DO01
/230.B7
SUPERVISION
/230.B8
IN
Name
script_ecscad_403
W.Kpfer
/230.B5
A2521
Date
Prepared
Approved
Project name
ACS 6000
/230.B4
B1
C1
A1
B2
C2
A2
B3
C3
A3
B4
C4
A4
B5
C5
A5
B6
C6
A6
B7
C7
A7
B8
C8
A8
B9
C9
A9
B10
C10
A10
B11
C11
A11
B12
C12
A12
B13
C13
A13
B14
C14
A14
B15
C15
A15
B16
C16
A16
F
R
W
O
KEY CODE
AA
TU830
24V_P2_1
24V_N2_1
Name
E
F
G
H
L1+
6.3A
L1+
L1L1-
-A2521 DO810
Date
251.E8
A
B
C
D
251.A8
251.A8
Rev. ind.
253.E1
253.A1
253.A1
251
252
253
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
C1_P3_DI04
/CBU CHARGING
OVERLOAD
C1_P3_DI05
C1_P3_DI06
C1_P3_DI07
/EMERGENCY STOP
C1_P3_DI08
BUS
Date
Date
C1_P3_DI09
C1_P3_DI11
/EARTH FAULT
MAIN CIRCUIT ALARM2
C1_P3_DI12
C1_P3_DI13
C1_P3_DI14
C1_P3_DI15
A.) MCB OK
(PRESIGNAL & TRIPPED & AVAILABLE)
B.) /MCB2 OK
(PRESIGNAL & TRIPPED & AVAILABLE)
C1_P3_DI16
/291.E3
/291.E7
/290.E4
/290.E1
/290.E2
/283.E8
/281.E8
/282.E5
Doc. des.
/282.E4
/282.E7
6.3A L2+
L2+
L2L2-
OUT
= COU1
+
Lang. EN
3BHS227955E01
Resp. dept.
Doc.No.
/EARTH FAULT
MAIN CIRCUIT ALARM1
/291.E4
C1_P3_DI10
/291.E5
/CBU CUBICLE
TEMPERATURE HIGH
B1
C1
A1
B2
C2
A2
B3
C3
A3
B4
C4
A4
B5
C5
A5
B6
C6
A6
B7
C7
A7
B8
C8
A8
B9
C9
A9
B1
B10
C1
C10
A10
A1
B11
C11
A11
B12
C12
A12
B13
C13
A13
B14
C14
A14
B15
C15
A15
B16
C16
A16
C1_P3_DI03
L1+
L1L1-
/LSU CUBICLE
TEMPERATURE HIGH
6.3A L1+
-W250 1
-W251 1
C1_P3_DI02
Name
script_ecscad_403
W.Kpfer
24V_P2_2
24V_N2_2
DI810
F
R
W
KEY CODE
AA
IN
Date
Prepared
Approved
Project name
ACS 6000
C1_P3_DI01
252.F8
252.F8
A2531
Name
E
F
G
H
/ARU3 CUBICLE
TEMPERATURE HIGH
-A2531 TU830
Date
252.B8
A
B
C
D
SUPERVISION
SUPERVISION
Rev. ind.
A2541
Last sh.
Sh.no.
Cont.sh.
254.B2
252
253
254
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
Date
Name
E
F
G
H
253.E8
Date
A2541
Name
Date
Date
A3
B4
/295.B6
A5
B6
/295.B7
A6
B7
/290.B5
A7
B8
/296.B1
A8
C1_P4_DO03
C1_P4_DO04
MCB -ORDER
CLOSE COMMAND
C1_P4_DO05
/MCB -ORDER
OPEN COMMAND
C1_P4_DO06
/MCB ORDER
TRIP
C1_P4_DO07
C1_P4_DO08
DRIVE CHARGED
(DC LINK VOLTAGE >
MCB CLOSING LEVEL)
A4
B5
BUS
/295.B5
C1_P4_DO02
A2
B3
/290.B6
C1_P4_DO01
-A2541 DO820
A1
B2
IN
/290.B8
F
R
W
O
KEY CODE
AD
script_ecscad_403
W.Kpfer
TU831
Prepared
Approved
Project name
ACS 6000
B1
OUT
-R2541
Doc. des.
TB807
= COU1
+
Lang. EN
3BHS227955E01
Resp. dept.
Doc.No.
IN
Last sh.
Sh.no.
Cont.sh.
253
254
281
DOORS
CLOSED
DOORS
RELEASE
DEENERGIZE
-X24_P1 6
-X230V
/120.B4
-W316 1
22
24
-K2902
A
B
C
D
Date
Name
15
.E2
-W308 1
LOOP 2
-X3 6
-W310 1
4s
-W312 1
-W311 1
A1
A2
A2
-K2812
-W309 1
4s
11 .D6
21 .D8
31
E
F
G
H
Date
18 15 .C6
16
28 25 .D8
26
Name
Prepared
Approved
Project name
ACS 6000
18
16
-K2813
/101.D1
26
28
25
-K2811
.E2
-W314 1
-XN
script_ecscad_403
W.Kpfer
-W325 1
A2
18 15 .C6
16
28 25 .C8
26
GROUND
SWITCH
OPEN
-K2901
/290.B2
.E3
-W323 1
A1
-W313 1
14
12
24
22
34
32
10
LOOP 3
-K2814
-K2814
22
24
21
12
14
A1
A2
-W327 1
-W326 1
DOOR
CLOSED
-W322 1
11
A1
-K2811
.E3
25
10
-K2812
-W324 1
A1
-A2531
/253.B2
A2
14
14
12
24
22
34
32
Date
Date
28
26
A2
22
/290.B2
11 /290.B8
21 /285.C7
31 /285.A6
21
-K2902
-W321 1
11
15
.E3
14
12
21
12
DOOR
RELEASE
DEENERGIZE
-K2812
-W329 1
L2+ 24VB13
C13
L2- 0V A13
32
34
22
-W328 1
-W320 1
31
12
LOOP 1
11
.E3
11
DOOR 1
-XN
/101.D1
-K2814
A1
DOOR N
/120.C4
11
-K2811
-X24_N1 6
-W303 1
16
18
-X3 5
-X1 10
-W307 1
K3
-W318 1
285.A7
K2
/285.D1
-W306 1
-W304 1
24V_P1
14
-W300 1
-F2851
RELEASE
CLOSED
21
14
22
/290.B2
-X1 8
-W301 1
-X1 9
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-W317 1
K1
13
21
-S2811
-X24_P1 16
11
/101.C1
-W305 1
-W299 1
SWINGFRAME
MONITORING
13
/120.B4
-W298 1
-X1 7
DOORS
CLOSED
CONTROL
C1_P3_DI13
CUBICLE DOOR(S) FEEDBACK STATUS CLOSED
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
254
281
282
PROCESS STOP
MCB STATUS
CLOSED
MCB STATUS
OPEN
/MCB
( PRESIGNAL &
TRIPPED )
-X24_P
-X2 79
-W331 1
80
81
-W333 1
82
31
-W334 1
32
EMERG_STOP
-X1 3
-W330 1
283.C4
F
A
B
C
D
Date
Name
E
F
G
H
Date
Name
-A2531
/253.B2
A1
12
14
-A2531
/253.B2
11
L2- 0V
/253.B2
-W354 1
L2+ 24VB16
C16
A16
-A2531
.C7
L2- 0V
L2- 0V
/251.B2
-W352
11 .D7
21
31
-K2825
L2+ 24VB14
C14
A14
11
-A2511
-W350
L2+ 24VB13
C13
A13
-W346
-K2824
.C6
14
12
24
22
34
32
-W355 1
11
-K2823
.C4
11 .D5
21
31
14
12
24
22
34
32
-W353 1
12
14
12
14
-K2821
-W341 1
12
14
-W351 1
-W347 1
.C3
-W340 1
11 .D4
21
31 /285.B6
14
12
24
22
34
32
-K2825
A2
-W338 1
11 .D3
21
31
14
12
24
22
34
32
A2
-W337 1
L2- 0V
12
11
/121.C8
-K2824
L2+ 24VB15
C15
A15
-X24_N
-K2823
A2
-K2821
-W345 1
A2
A1
A1
-W344 1
A1
-W343 1
-W336 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
/121.B8
12
C1_P1_DI13
C1_P3_DI15
C1_P3_DI14
C1_P3_DI16
/PROCESS STOP
A.) MCB OK
(PRESIGNAL & TRIPPED & AVAILABLE)
B.) /MCB2 OK
(PRESIGNAL & TRIPPED & AVAILABLE)
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
281
282
283
EMERGENCY-STOP
LOOP (I>> -HW)
/EMERGENCY-STOP
-X24_P2
/120.B5
-X2 75
285.A4
76
-X2 59
60
-X2 17
18
-W367 1
26
28
-W361
-W370 1
-K2833
ESTOP IN PROGRESS
(ACTIVATED)
-A2521 A2521 DO12
19
20
/252.E2
-W366 1
-W368 1
-W369 1
-W866 1
25
.E7
-W363 1
14
/230.C7
-W360 1
-W365 1
K1
K3
K1
K1
K2
K2
K2
0,15s..10min
-W357 1
Date
Name
13
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
-W867 1
/120.C5
42
34
24
A2
PE
14
-X24_N2
A
B
C
D
33
K3
34
K3
-W377 1
-W379 1
-W374 1
-K2831
K2
.D1
24
K1
K2
K2
-F2831
41
.C7
K1
K3
K3
/121.C8
K2
.D1
-W373 1
.C8
33
13
T22
T12
T12
K3
K1
24V
-X24_N
-F2831
14
K2
T34
.C6
S1
X1
X2
T11
BN5930
24VDC
A1
-F2831
K2
.D1
K1
K1
K3
/121.B8
-W356 1
-F2831
13
23
-X24_P
25
.E5
K1
282.B7
-K2831
-W380 1
23
26
28
13
-S2304
-W372 1
13
-W364 1
-W358 1
28
26
.E6
-W378 1
EMERG_STOP
25
-K2832
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-W359 1
-W371 1
-W362 1
A1
-K2832
A2 0,15s..10min
-W375 1
18 15 /285.C1
16
28 25 .C3
26
A1
A2
A1
-K2833
2s
A2
-W376 1
18 15 /285.C2
16
28 25 .C3
26
-A2531
/253.B2
18 15 /285.C1
16
28 25 .B3
26
Doc. des.
Resp. dept.
Doc.No.
L1-
ESR
/EMERGENCY-STOP
C8
0V A8
L1+ 24V B8
2
EMERGENCY-STOP
RESET
B12L2+ 24V
C12
A12 L2- 0V
A2531 DI08
/EMERGENCY STOP
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
282
283
285
-F2851
.D1
-W389 1
A
B
C
D
Date
/121.C8
Name
24
41
42
-A2511
/251.B2
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
42
Date
Date
-Z2852
/120.C4
A1
-X24_N1 13
C1_P1_DI02
11
A2
K2
-W421 1
K2
34
K2
K1
.D1
K2
24
K1
14
K1
PE
A2
K3
22
24
A2
-K2851
A1
-F2851
K1
K2
K2
-W427 1
L1+ 24V B2
C2
L1- 0V A2
K1
-W425 1
-W422 1
K3
-X24_N
-W424 1
.D8
41 .D6
/290.C8
33
23
13
T22
K1
K3
K1
24V
T12
T12
K3
.B7
/281.A6
K2
T34
X2
S1
X1
-W388 1
BN5930
24VDC
-K2852
62
18
16
16
18
15
-W387 1
T11
-F2851
-W401 1
-W406 1
11
A1
D -X24_P
/121.B8
-K2813
/281.E6
61
15
/283.E6
-W386 1
-K2833
/283.E7
61
15
-K2832
-W426 1
-W423 1
.D7
-W409 1
-W385 1
62
16
18
-K2851
K2
K3
-W408 1
-K2831
/283.E5
295.B4
K1
31
-K2823
/282.C4
EMERG_LOOP_OK
/281.E6
-W407 1
-W398 1
-K2852
-K2813
-Z2851
2
1
24
/230.C7
-W399 1
-W395 1
23 24V_P1 281.A7
78
32
34
23
-W394 1
21
77
-S2304
ESR
-W397 1
-W396 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
22
/230.C3
EMERG. OFF 1
-W382
-X2 71 72 73 74
-W393 1
-S2301
22 23 24 25 26 27 28
-W390 1 -W391 1
-W392 1
21
-W383 1
-W840 1
-X1 51 52-X2 21
-W381 1
34
32
283.A2
/EXTERNAL
EMERGENCY RESET
/EXTERNAL
EMERGENCY-OFF
31
2
EMERGENCY-OFF
CUBICLES
-W400 1
Doc. des.
Resp. dept.
Doc.No.
13
21
31
43
53
61
14
22
32
44
54
62
/296.B7 13
/296.C3 21
/296.C6 31
43
53
61
.C6
= COU1
+
Lang. EN
3BHS227955E01
14
22
32
44
54
62
Last sh.
Sh.no.
Cont.sh.
/296.C7
/296.C4
/296.C6
.C6
283
285
287
1.13
-Q1051
1.14
/105.C3
-W283 1
-W295 1
1.13
1.13
-W284 1
-Q1061
-Q2981
/298.A2
-W285 1
1.13
-W294 1
1.13
-Q1071
-Q1004
1.14
/100.C7
1.14
/107.C2
1.13
1.13
-W293 1
-Q1041
-Q1014
/104.C3
1.14
1.14
/101.C7
-W280 1
-W297 1
16
18
1.13
-W292 1
-Q1012
-F1021
/101.C4
1.14
/102.A1
15
-W296 1
1.13
-W279 1
-Q1011
1.14
/101.C2
C1_P1_DI12
F
A
B
C
D
Date
Name
/AUXILIARIES SUPPLY
PROTECTION SWITCH
TRIP
Date
Name
E
F
G
H
/251.B2
C1_P1_DI11
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
/AUXILIARIES SUPPLY
PROTECTION SWITCH
ALARM
2006-09-29 Title AUX POWER SUPPLY
Date
MONITORING
2006-09-29
Date
L1- 0V
-A2511
L1+ 24V B1
C1
A1
L2- 0V
/251.B2
C11
A11
-A2511
L2- 0V
/251.B2
C12
A12
-A2511
L2+ 24VB12
-W289 1
-W278 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
1.14
1.14
/106.C4
C1_P1_DI01
/UNDERVOLTAGE (RELAY)
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
285
287
290
CBU GROUNDING
SWITCH CLOSED
CBU - HV
CHARGING ORDER
CBU - LV
CHARGING ORDER
A1
/120.B4
-K2902
A1
B1
A2
-W441 1
/281.E6
-W448 1
33
-X24_N1 17
K1
A
B
C
D
Date
C1_P3_DI07
C1_P3_DI05
/CBU CHARGING
OVERLOAD
Name
/253.B2
E
F
G
H
Date
Name
/253.B2
Prepared
Approved
Project name
-X24_N1 12
/120.C4
script_ecscad_403
W.Kpfer
ACS 6000
-XN
-W443 1
-X2 11
24V
L1-
L1+ 24V B7
C7
L1- 0V A7
-A2531
1
2
-W451 1
-W442 1
-W439
-Z2901
/100.C5
L1-
C6
0V A6
-A2531
A1
1.13
/100.C5
12
-Q1003
-Q1003
-W437 1
L1+ 24V B6
/101.C1
C1_P3_DI06
/253.B2
-X230V
C5
0V A5
-W436
-A2531
-W449 1
-K2902
.B2
K2
/285.D1
-W438 1
24
22
.B2
-F2851
-W445 1
K3
L1+ 24V B5
-K2901
-W444 1
-W435 1
21
11 .D3
21 /281.B4
31 /281.C7
11
-W434 1
14
12
24
22
34
32
1.14
11 /281.D6
21 .D2
31
14
12
24
22
34
32
34
/120.C4
14
12
A2
-W432 1
-W433 1
-K2813
A2
A2
-K2901
B2
-X24_P1 12
-W431 1
-W447 1
-W450
12
14
/120.B4
-W430 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X24_P1 17
A7
-W428 1
/254.E3
56
B7
54
55
-W429 1
-A2541 C1_P4_DO01
/254.E3
-W440 1
-X2 53
RELEASE CBU
GROUNDING SWITCH
ELECTRICAL LOCKING
A1
CBU GROUNDING
SWITCH OPEN
11
/101.D1
12
13
12
14
24V
TO CBU
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
287
290
291
LINE SIDE
CONTROL
LINE SIDE
-X1 1
1
2
61
DC LINK
(CBU)
LSU1
-W463 1
MOTOR SIDE
CBU
2
INU1
-W465 1
62
65
-W458 1
66
-X2 51
52
-X1 55
56
-W459 1
-W456 1
-W457 1 -W461 1
-W455 1
-W462 1
-W464 1
-W466 1 -W467 1
-W468 1
-W460 1
F
A
B
C
D
Date
Name
-A2511
/251.B2
L2+ 24VB15
C15
L2- 0V A15
-A2531
/253.B2
L1+ 24V B4
C4
L1- 0V A4
-A2531
/253.B2
L1+ 24V B2
C2
L1- 0V A2
-A2531
/253.B2
L1+ 24V B3
C3
L1- 0V A3
-A2531
/253.B2
L2+ 24VB16
C16
L2- 0V A16
-A2511
/251.B2
L1+ 24V B1
C1
L1- 0V A1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
6
LINE SIDE
C1_P1_DI16
C1_P3_DI03
C1_P3_DI02
C1_P3_DI01
C1_P3_DI04
C1_P1_DI15
/COU CUBICLE
TEMPERATURE HIGH
/LSU CUBICLE
TEMPERATURE HIGH
/ARU3 CUBICLE
TEMPERATURE HIGH
/CBU CUBICLE
TEMPERATURE HIGH
/INU CUBICLE
TEMPERATURE HIGH
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
290
291
295
A
MCB -ORDER
CLOSE COMMAND
/MCB -ORDER
OPEN COMMAND
/MCB ORDER
TRIP
285.A8
-W516 1
-X24_P1 15
A6
A5
A4
-W520 1
EMERG_LOOP_OK
B6
/254.E3
B5
/254.E3
B4
-W521 1
-W517 1
-W518 1
/120.B4
-X24_N1 15
/120.C4
CONNECTED TO
INU
MCB
-K2952
-K2953
-W526 1
-W527 1
A1
-K2954
A2
-W525 1
A1
-K2951
A2
-K2950
A1
A2
A2
A1
0V X1.3 -W522
A2
-W519 1
A1
-W801 1
-W528 1
A1
E
14
24
34
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
/254.E3
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
11 /296.C2
21 /296.D2
31 /296.D2
14
24
34
11 /296.C1
21 /296.D1
31 /296.D1
14
12
24
22
34
32
11 /296.E3
21 /296.D3
31 /296.C3
Doc. des.
Resp. dept.
Doc.No.
14
24
34
11 /296.D7
21 /296.D7
31 /296.C7
14
12
24
22
34
32
= COU1
+
Lang. EN
3BHS227955E01
11 /296.E5
21 /296.D5
31 /296.C5
Last sh.
Sh.no.
Cont.sh.
291
295
296
MCB
ORDER CLOSE
A
MCB
ORDER OPEN 1
COIL : (+)
MCB
ORDER OPEN 2
MCB
ORDER TRIP
(-)
DRIVE CHARGED
(DC LINK VOLTAGE >
MCB CLOSING LEVEL)
-A2541 C1_P4_DO08
/254.E3
-K2851
A8
B8
/285.D7
14
-W532 1
14
-W554 1
-W905 1
-K2852
-W533
A
B
C
D
Date
Name
E
F
G
H
Date
Name
34
31
31
/295.D7
32
-W544 1
-W552 1
-K2953
/295.D7
24
-W551 1
-W908 1
14
11
-K2954
/295.D7
11
-W550 1
-W542 1
Prepared
Approved
Project name
-K2953
14
12
14
12
/295.D8
-W534 1
-W902 1
-K2953
/285.D8
-W545 1 -W543 1
-W906 1
11
34
31
/295.D6
-K2852
21
21
24
/295.D8
-W553 1
21
-W546 1
-K2952
/295.D5
/285.D7
-K2954
-W537 1 -W535 1
-K2950
-K2851
32
22
-W536 1
/295.D8
34
32
/285.D8
-W549 1 -W909 1
31
31
21
21
22
-K2954
-K2852
-X4 2
/295.D6
-W903 1
-W529 1
/285.D7
-W548 1
22
24
21
21
24
31
/295.D6
-K2851
-K2952
/295.D5
34
-K2951
-W547 1
-W541 1 -W907 1
-W538 1
-W904 1
-W530 1
/295.D6
-K2950
/295.D6
31
14
/295.D5
-W531 1
-K2951
-K2952
-K2950
34
32
11
/295.D6
-W540 1
22
24
-K2951
11
14
-W539 1
13
/285.D8
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
13
-W555 1
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
10
52 51
53
Doc. des.
Resp. dept.
Doc.No.
54
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
295
296
298
-X24_N2
/120.C5
-X24_P2 7
1+
3-
-Q2981
24+
1.14
1.22
FAZ-2-DC
>
0..60C
-W570 1
-W576 1
-W574 1
-W579 1
-W571 1
-X1 57
-W575 1
-W580 1
58
63 64
67 68
-W578 1
-W573 1
INU
-W577 1
-W572 1
CONNECTED TO
M
=
F
A
B
C
D
Date
Name
E
F
G
H
Date
M
=
Name
M
=
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
M
=
Date
Date
-M1
M
=
-M2
-M3
M
=
-M4
M
=
Doc. des.
Resp. dept.
Doc.No.
RD
BU
-M4
RD
BU
-M3
RD
BU
-M2
-E2982
RD
BU
RD
BU
RD
BU
-M1
RD
BU
RD
BU
-E2981
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
/120.B5
-W568 1
-W569 1
1.13/287.A4
1.21
M
=
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
296
298
800
=COU1
DC+
DC-
=INU:L1
=INU:L2
=INU:L3
=LSU:1L1
=LSU:1L2
=LSU:1L3
=LSU:2L3
=LSU:2L2
=LSU:2L1
PG
PE
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
BUSBAR CONFIGURATION 1
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad_403
W.Kpfer
ACS 6000
Date
Date
Doc. des.
Resp. dept.
Doc.No.
= COU1
+
Lang. EN
3BHS227955E01
Last sh.
Sh.no.
Cont.sh.
298
800
COMPONENT :
E
DOCUMENT :
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
2006-09-29 Title
FRONT PAGE
2006-09-29
Doc. des.
22.09.2006
Resp. dept.
Doc.No.
ATD
= WCU1
+
Lang. EN
3BHS227354E01
No. of sh.
Sh.no.
Cont.sh.
16
001
002
title 1
4
title 2
001
002
FRONT PAGE
INDEX SHEET
500
501
502
520
521
522
523
540
541
545
554
571
573
574
AC AUX DISTRIBUTION /
SPACE HEATER
POWER SUPPLY
COUPLING DEVICE
DIGITAL INPUT MODULE
DIGITAL OUTPUT MODULE
ANALOG INPUT MODULE
INTERNAL DIGITAL INPUT
WATER COOLING PUMP
THERMOSTAT
WATER COOLING CONTROL
EXTERNAL DIGITAL INPUT
EXTERNAL DIGITAL OUTPUT
COOLING FAN`S
6
title 3
rev.
ind.
-
COOLING CONTROL
CONTROL
TB820
DI810 + TU830
DO820 + TU831
AI810 + TU830
3 - WAY VALVE
HEATING
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
page
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
INDEX SHEET
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
001
002
500
COOLING PUMP 1
COOLING PUMP 2
POWER SUPPLY
COU
1/BN
2/BU
3/BK
1
3
5
1
3
5
2
4
6
FN258-16/29
Cy
R1
Cx
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
L3_OUT
CONNECTED TO
COU
554.A4
554.A4
554.A4
554.A2
554.A3
554.A3
R2
R1
MOT2_U
MOT2_V
MOT2_W
MOT1_U
MOT1_V
MOT1_W
Cy
L2_OUT
L1_OUT
1/BN
2/BU
3/BK
1/BN
2/BU
3/BK
-W010
Cx
Cx
-W006
E_IN
3*480VAC/16A
-Z5001
E_OUT
-W014 1
-W015
-W016
L3_IN
1.13 /540.A3
1.21
1.14
1.22
A2
2
4
6
A2
A1
L2_IN
/541.D4
L1_IN
13
21
A1
2
4
6
/541.D3
-Q5004
13
21
-Q5003
/540.A6 14
22
1.14
1.22
-Q5002
-W011 1
-W012 1
-W013 1
1
3
5
-W007 1
-W008 1
-W009 1
1.13 /540.A1
1.21
-W003 1
-W004 1
-W005 1
1
3
5
/540.A5 14
22
-F5001..3
2
4
6
-Q5001
Rev. ind.
-X1 1 2 3 PE
-W001
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Date
Date
2006-09-29 Title
AC AUX DISTRIBUTION /
2006-09-29
COOLING CONTROL
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
002
500
501
230VAC
50/60Hz
A
-Q5011?
1/BN
2/BU
-PE1 2
/502.C7
2
4
-W031
1
3
FAZ
32
34
12
14
-W033 1
1
-W034
31
/545.D6
11
-K5451
-W035 1/BN
2/BU
GNYE
-X515 1 2
3 4
PE
CONNECTION
BOX
-E5011
SPACE HEATER
CONVERTER
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X2 1 2 PE
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
SPACE HEATER
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
500
501
502
WCU CONTROL
300VDC
-
-PE1 5
.C7
2/BU
GNYE
-W043
1/BN
-PE1 3 -X511 1
.C7
-W059 1
-PE 2
.D7
2 3 4 5 6 7 8
U02
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX
11
U01
-PE1 1
250W
24V
LWN
2660-6
-G5021
PE
/500.E6
/501.B4
.B2
.B8
-W046 1
-W047
-W048 1
-W049
-W050
-W051
1
1
-PE
1
.B8
1 2 3 4 5 6 7 8 9 10
GROUNDING BAR
F
A
B
C
D
Date
Name
E
F
G
H
Date
Name
24V_N2
574.B2
574.B2
24V_P2
24V_N1
520.E4
520.E4
24V_P1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
POWER SUPPLY
2006-09-29
CONTROL
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
501
502
520
TB820V2
CLUSTER ADRESS
4 5 6
3
7
2
8
1 0 9
F
R
P
Rx1
Rx2
ERx
X4
Tx2
Rx2
X5
CONNECTED TO
COU
Tx1
Rx1
BUS
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
521.E1
24V_P1
-W064 1
24V_N1
521.A1
521.A1
24V_N1
-W063 1
502.E2
502.E2
24V_P1
A5211
OUT
SB
L-
SA
L+
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-A5201
Date
Date
2006-09-29 Title
COUPLING DEVICE
2006-09-29
TB820
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
502
520
521
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-W065
-W068
-W067
24V_N1
24V_P1
L1+
L1+
L1-
Name
script_ecscad
W.Kpfer
C2_P1_DI02
WCU PUMP 1
CONTACTOR-FEEDBACK
STATUS CLOSED
C2_P1_DI03
WCU PUMP 2
CONTACTOR-FEEDBACK
STATUS CLOSED
C2_P1_DI04
C2_P1_DI05
C2_P1_DI06
C2_P1_DI07
C2_P1_DI08
BUS
C2_P1_DI09
C2_P1_DI11
C2_P1_DI12
/WCU PROTECTION
SWITCH ALARM
C2_P1_DI13
/WCU CUBICLE
TEMPERATURE HIGH
C2_P1_DI14
C2_P1_DI15
Doc. des.
6.3A
/540.D6
/554.C7
/554.D7
/540.D8
/545.D2
L2+
L2+
L2L2-
OUT
= WCU1
+
Lang. EN
Last sh.
Sh.no.
Cont.sh.
A5221
3BHS227354E01
Resp. dept.
Doc.No.
C2_P1_DI16
/540.D5
C2_P1_DI10
/540.D3
2006-09-29 Title
DIGITAL INPUT MODULE
2006-09-29
DI810 + TU830
/540.D1
Date
Date
WCU PUMP 2
THERMAL PROTECTION RELAY
STATUS CLOSED
B1
C1
A1
B2
C2
A2
B3
C3
A3
B4
C4
A4
B5
C5
A5
B6
C6
A6
B7
C7
A7
B8
C8
A8
B9
C9
A9
B10
C1
A1
B11
C11
A11
B12
C12
A12
B13
C13
A13
B14
C14
A14
B15
C15
A15
B16
C16
A16
Prepared
Approved
Project name
ACS 6000
WCU PUMP 1
THERMAL PROTECTION RELAY
STATUS CLOSED
L1-
C2_P1_DI01
SUPERVISION
24V_P1
-W066
TU830
DI810
F
R
W
KEY CODE
AA
IN
Date
24V_N1
-A5211
A5211
Name
E
F
G
H
6.3A
SUPERVISION
520.E7
Date
520.E7
A
B
C
D
520.D7
Rev. ind.
523.A1
523.A1
522.B2
520
521
522
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
Date
Name
E
F
G
H
521.E8
Date
A5221
Name
/541.B7
A5
B6
/541.B8
A6
B7
2006-09-29 Title
DIGITAL OUTPUT MODULE
2006-09-29
DO820 + TU831
A7
B8
A8
C2_P2_DO03
C2_P2_DO04
C2_P2_DO05
C2_P2_DO06
A4
B5
/541.B4
C2_P2_DO02
BUS
A3
B4
Date
Date
/541.B3
A2
B3
C2_P2_DO01
-A5221 DO820
A1
B2
IN
/545.B6
F
R
W
O
KEY CODE
AD
script_ecscad
W.Kpfer
TU831
Prepared
Approved
Project name
ACS 6000
B1
C2_P2_DO07
C2_P2_DO08
WCU CHILLER
ORDER ON
COMMAND
OUT
A5231
Doc. des.
523.E1
= WCU1
+
Lang. EN
3BHS227354E01
Resp. dept.
Doc.No.
Last sh.
Sh.no.
Cont.sh.
521
522
523
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Rev. ind.
A
B
C
D
521.A8
521.A8
522.B7
Date
C2_P3_AI05
AMBIENT TEMPERATURE
SUPERVISIONTRANSDUCER
C2_P3_AI06
C2_P3_AI07
Doc. des.
C2_P3_AI08
TB807
522
523
540
-W073 1 24V_P1
545.C5
-W074 1 24V_N1 545.E5
OUT
-R5231
= WCU1
+
Last sh.
Sh.no.
Cont.sh.
IN
L2+
L2+
L2L2-
/545.D3
6.3A
Lang. EN
3BHS227354E01
Resp. dept.
Doc.No.
/554.E7
/554.E5
C2_P3_AI04
/554.E4
MUX.
BUS
2006-09-29 Title
ANALOG INPUT MODULE
2006-09-29
AI810 + TU830
/554.E3
-W071 1
-W072 1
Date
Date
C2_P3_AI03
/554.E2
script_ecscad
W.Kpfer
Name
Prepared
Approved
Project name
ACS 6000
C2_P3_AI02
L1+
L1+
L1L1-
B1
B2
C1
C2
A1
A2
B3
B4
C3
C4
A3
A4
B5
B6
C5
C6
A5
A6
B7
B8
C7
C8
A7
A8
B9
B10
C9
C10
A9
A10
B11
B12
C11
C12
A11
A12
B13
B14
C13
C14
A13
A14
B15
B16
C15
C16
A15
A16
C2_P3_AI01
24V_P1
24V_N1
TU830
AI810
F
R
W
KEY CODE
AE
IN
Date
-A5231
A5231
Name
E
F
G
H
6.3A
-Q5002
1.13
13
-Q5741
/574.B4
-Q5003
/500.C4
14
/500.C2
1.14
1.14
/500.C4
1.14
-Q5003
/500.C2
14
-Q5002
13
1.13
1.13
1.13
-Q5011
1.14
-W095 1
F
A
B
C
D
Date
-A5211
/521.B2
-W092 1
-W093 1
-A5211
/521.B2
-W097
-A5211
/521.B2
L2+ 24VB13
C13
L2- 0V A13
-W090 1
-W091 1
L1+ 24V B4
C4
L1- 0V A4
-A5211
/521.B2
L1+ 24V B1
C1
L1- 0V A1
-A5211
/521.B2
-W088 1
-W089 1
L1+ 24V B3
C3
L1- 0V A3
-W086 1
-W087 1
L1+ 24V B2
C2
L1- 0V A2
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-W162 1
C2_P1_DI01
C2_P1_DI02
C2_P1_DI03
C2_P1_DI04
C2_P1_DI13
WCU PUMP 1
THERMAL PROTECTION RELAY
STATUS CLOSED
WCU PUMP 2
THERMAL PROTECTION RELAY
STATUS CLOSED
WCU PUMP 1
CONTACTOR-FEEDBACK
STATUS CLOSED
WCU PUMP 2
CONTACTOR-FEEDBACK
STATUS CLOSED
/WCU PROTECTION
SWITCH ALARM
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
INTERNAL DIGITAL INPUT
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
523
540
541
WCU CONTROL
230VAC
60Hz
A6
B6
A5
B5
A4
B4
-W160 1
A3
2
230V~_N
230V~_L
-X512 1
B3
-W101 1
-W102 1
-W103 1
C
-W100 1
-W106 1
-W108 1
-W107 1
-W109 1
14
12
24
22
34
32
F
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
WATER COOLING PUMP
2006-09-29
3 - WAY VALVE
11 .D7
21 .D8
31
Doc. des.
Resp. dept.
Doc.No.
21
22
24
-W110 1
554.A1 CLOSE_230V~_L
-K5542
.D6
554.A1 230V~_N
-W105 1
11
-K5542
.D6
554.A1 OPEN_230V~_L
-W104 1
-K5542
A2
-Z5412
12
14
A1
A1
-Q5003
/500.C4
A2
-Z5411
A2
-Q5002
/500.C2
A1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
540
541
545
B1
zero span
I
523.A8
24V_P1
-W158 1
-W159
-W116 1
F
A
B
C
D
Date
Name
C2_P3_AI06
/WCU CUBICLE
TEMPERATURE HIGH
AMBIENT TEMPERATURE
SUPERVISIONTRANSDUCER
Date
A2
U I
MUX
C2_P1_DI14
E
F
G
H
-K5451
B11
B12
L2+ 24V
C11
C12
L2- 0V A11
A12
-A5231
/523.B2
L2+ 24VB14
C14
L2- 0V A14
A1
-W113 1
-W114 1
-A5211
/521.B2
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
TEMPERATURE SENSOR
4-20mA
-50-100C
2
3
-B5631
A1
PT100
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
523.A8
24V_N1
14
12
34
32
Date
Date
2006-09-29 Title
THERMOSTAT
2006-09-29
HEATING
11 /501.D3
31 /501.D3
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
541
545
554
PE
-X554 U1
V1
W1
PE
-X554 U2
500.E4
MOT2_W
500.E4
MOT2_V
500.E4
MOT2_U
500.E2
MOT1_W
500.E2
MOT1_V
500.E2
MOT1_U
541.F7
541.F7
3
V2
W2
PE
-M5542
-B5523
-B5502
-B5501
bar
4...20
mA
4...20
mA
C2_P3_AI01
WCU COOLING WATER
CONDUCTIVITY-TRANSDUCER
F
A
B
C
D
Date
Name
E
F
G
H
Date
Name
5 6
7 8
9 10
U I
MUX
C2_P3_AI02
WCU COOLING WATER PUMP
INPUT SIDE PRESSURETRANSDUCER
script_ecscad
Prepared
W.Kpfer
Approved
Project name
ACS 6000
/523.B2
U I
MUX
-A5231
/523.B2
U I
MUX
L1- 0V
-A5231
L1+ 24V
/523.B2
L1- 0V
-A5231
B7
B8
C7
C8
A7
A8
3 4
B5
B6
C5
C6
A5
A6
9 10
L1+ 24V
U I
MUX
7 8
L1- 0V
L1+ 24V
/523.B2
1 2
L1+ 24V
-A5231
L1- 0V
B1
B2
C1
C2
A1
A2
-W122 1 2
3 4
B3
B4
C3
C4
A3
A4
-X551 5 6
C2_P3_AI03
C2_P3_AI04
WCU COOLING WATER PUMP
WCU COOLING WATER
OUTPUT SIDE PRESSURETEMPERATURE (INTERNAL)TRANSDUCER
TRANSDUCER
2006-09-29 Title
Date
WATER COOLING CONTROL
2006-09-29
Date
L1+ 24V
L1- 0V
-A5211
-X552
24VDC 10
LS 11
0V 12
5
/521.B2
4...20
mA
-X553 1
-A5211
2
3
bar
4...20
mA
-W161 1
/521.B2
A8 C8B8
-X552
24VDC 7
LF
8
0V
9
C2_P1_DI07
-M5541
C2_P1_DI08
A7 C7B7
4
5
6
-A5231
/523.B2
L1+ 24V
L1- 0V
B9
L2+ 24V B10
C9
C10
L2- 0V A9
A10
-K5541
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X553 4
OPEN_230V~_L
CLOSE_230V~_L
230V~_N
541.F8
U I
MUX
C2_P3_AI05
WCU COOLING WATER
TEMPERATURE (EXTERNAL)TRANSDUCER
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
545
554
571
PROCESS STOP
NOT USED
/EMERGENCY-STOP
/EMERGENCY-STOP
/EXTERNAL
EMERGENCY-OFF
/EXTERNAL
EMERGENCY-OFF
6
EMERGENCY-STOP
RESET
( OPTIONAL )
EMERGENCY-OFF
RESET
( OPTIONAL )
MCB STATUS
CLOSED
8
MCB STATUS
OPEN
/MCB
( PRESIGNAL &
TRIPPED )
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
CONNECTED TO
COU
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
-X17
PE
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
EXTERNAL DIGITAL INPUT
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
554
571
573
CONNECTED TO
COU
CONNECTED TO
COU
16
15
14
13
12
11
10
-X18
PE
MCB
ORDER CLOSE
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
A
B
C
D
Date
Name
MCB
ORDER OPEN 1
E
F
G
H
Date
Name
MCB
ORDER OPEN 2
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
INU OPERATION
PREVENTED
MOTOR 1
MCB
ORDER TRIP
Date
Date
2006-09-29 Title
EXTERNAL DIGITAL OUTPUT
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
571
573
574
-Q5741
24+
1.14
1.22
FAZ_DC
1.13/540.A8
1.21
1+
3-
>
M
=
-M2
M
=
-M3
-M4
M
=
RD
BU
RD
BU
RD
BU
-M1
2/BU
-E5741
RD
BU
-W156
1/BN
-B5741
-W155 1
M
=
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
502.E2 24V_P2
502.E2 24V_N2
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
script_ecscad
W.Kpfer
ACS 6000
Date
Date
2006-09-29 Title
COOLING FAN`S
2006-09-29
Doc. des.
Resp. dept.
Doc.No.
= WCU1
+
Lang. EN
3BHS227354E01
Last sh.
Sh.no.
Cont.sh.
573
574
COMPONENT :
DOCUMENT :
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
A
B
C
D
Date
13.03.01
01-07-25
01-08-07
01-08-09
Name
S.SCHLEGEL
R. SEILER
P. OBERLE
S.SCHLEGEL
E
F
G
H
Date
03-06-24
03-10-14
07.05.04
06-07-06
Name
S.SCHLEGEL
ST.DUSS
P.OBERLE
P.OBERLE
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
FRONT PAGE
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
No. of sh.
17
Cont.sh.
Sh.no.
page
title 1
title 2
1
2
4
5
400
401
402
403
404
405
410
411
412
413
415
416
420
rev.
ind.
title 3
FRONT PAGE
INDEX SHEET
BUS BAR ARRANGEMENT
CIRCUIT DIAGRAM OVERVIEW
LOCAL DC LINK
OVERCURRENT MONITORING
PHASE-LEG L1
PHASE-LEG L2
PHASE-LEG L3
EMC FILTER
AUX POWER SUPPLY
GATE UNIT POWER SUPPLY
PULSE CONTROL AND
AC CURRENT AND DC VOLTAGE
AIR TO AIR HEAT EXCHANGERS
FAN SUPPLY INT- BOARD
DOOR MONITORING
H
H
E
E
F
E
E
E
H
E
E
H
H
G
G
DC - MEASUREMENT
CURRENT MEASUREMENT
MEASUREMENT INTERFACE
MEASUREMENT
CABINET TEMP. MONITORING
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
A
B
C
D
Date
13.03.01
01-07-26
01-08-07
01-08-09
Name
S.SCHLEGEL
R.SEILER
P. OBERLE
S.SCHLEGEL
E
F
G
H
Date
03-06-24
03-10-14
07.05.04
06-07-06
Name
S.SCHLEGEL
ST.DUSS
P.OBERLE
P.OBERLE
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
INDEX SHEET
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
DC+
DC_NP
DC-
DC BUS back
DC+
DC_NP
DC-
DC BUS middle
DC+
DC_NP
DC-
DC BUS front
DC+
DC_NP
DCDC_+
DC_NP
DC_-
OPTION
DC+
DC_NP
DC-
DC_+
DC_NP
DC_-
OPTION
DC+
DC_NP
DC-
DC_+
DC_NP
DC_-
UNIT BEFORE
*)
L1
L1
*)
L2
L2
UNIT BEFORE
*)
L3
L3
TERMINAL UNIT
SEE CONVERTER
HW DIAGRAM
OPTION
PG
NEXT UNIT
DC_+
DC_NP
DC_-
=COU or TEU
PG
PE
PE
*)
*) Earthing connection points
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
NEXT UNIT
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
ST.DUSS
W.KPFER
ACS 6000
Date
Date
03-06-24
03-06-26
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
4
5
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-VC1
-C1
-VF4
-VF3
-VF2
-VF1
-VR4
-VR3
-VR2
-VR1
-VN2
-VN1
-C2
S.SCHLEGEL
E.SUTER
ACS 6000
Prepared
Approved
Project name
-L4051
XDC_+
-G4021
-VC2
-L4011
-R4022/3
-R4024/5
-R4001
-A4001
Option
-C4001.1
-C4001
-R4053
-C4001.2
Phase Frame
-L4012 XDC_-
-R4052
-C4053
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
-C4052
-R4002
DC_+
DC_-
-R4051
-C4051
Name
Date
A
B 01-07-25 R.SEILER
C 01-08-07 P. OBERLE
D 01-08-09 S.SCHLEGEL
DC_NP
Rev. ind.
Date
Date
-R4034/5
Phase L1
-RS1
-R4032/3
-G4031
01-03-05
01-04-02
-VC2
-VF4
-VF3
-VF2
-VF1
-VR4
-VR3
-VR2
-VR1
-VN2
-VN1
-RS1
Doc. des.
-R4042/3
-G4041
-VC2
ATDD
3BHS119662E01
Resp. dept.
Doc.No.
-R4044/5
Phase L2
-C1
Title
-L4052
-VC1
-C2
-VC1
-C1
-VF4
-VF3
-VF2
-VF1
-VR4
-VR3
-VR2
-VR1
-VN2
-VN1
-L4053
Phase Frame
L1
L2
L3
Last sh.
4
5
400
-RS1
Phase L3
Phase Frame
= INU
+
Lang. E
Sh.no.
Cont.sh.
-C2
A
DC_+
HVD
-U4001 XV C770 AE01
X2_1
-A4001
X2
DC_NP
X2_3
DC_NP
402.C1
DC_-
401.D1
DC_-
-R4001
X2_5
-C4001
-W40002 BK
C4001.1
DC_NP
C4001.2
-W40003 BK
-W40005
BK
-R4002
DC_-
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
DC_+
401.A1
BK
-W40001 BK
DC_+
Name
Date
A
B 01-07-25 R. SEILER
C 01-08-07 P. OBERLE
D 01-08-09 S.SCHLEGEL
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
LOCAL DC LINK
DC - MEASUREMENT
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
5
400
401
-W40101 BK
A
400.A8
DC_+
-L4011
XDC_+
402.A1
-F4011 FSCD
S2
402.A7
Tx
Tx
5V
20V
50V
100V
110V
A1
CL_+
S1
A2
BK
-W40106
FSCD_EXT_+
-W40102 FO
D
400.F8
DC_-
-L4012
FSCD_+
=NEXT_UNIT
412.A4
XDC_-
402.F1
-F4012 FSCD
BK
-W40109
5V
20V
50V
100V
110V
402.F7
S1
A1
CL_-
S2
A2
-W40103 BK
Tx
Tx
-W40108 BK
FSCD_EXT_-
-W40104 FO
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-W40105 BK
Name
Date
A
B 01-07-25 R. SEILER
C 01-08-07 P. OBERLE
D 01-08-09 S.SCHLEGEL
Date
Name
E 03-06-24 S.SCHLEGEL
F 03-10-14 ST.DUSS
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
OVERCURRENT MONITORING
FSCD_-
Doc. des.
Resp. dept.
Doc.No.
ATDD
=NEXT_UNIT
412.A5
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
400
401
402
X1:1 (-)
411.E2
GU_VF1U_2
VF1.2
X1:2 (+)
-VR1
-R4022
-VC1
CL_+
403.A7
U
DC_NP
405.A1
403.C1
CL_XDC_-
403.F7
403.F1
-W40203
1
VF1.1
403.A1
-R4023
-W40202
GU_VF1U_1
411.E2
VF1.A1 -VF1 A1
a
VF1U
XDC_+
412.E2
-W40204
411.E2
GU_VF2U_2
VF2.2
X1:2 (+)
400.C8
DC_NP
412.E2
VF3U
VF3.A1-VF3 A1
411.E2
GU_VF3U_1
VF3.1
X1:1 (-)
411.E2
GU_VF3U_2
VF3.2
X1:2 (+)
-VR2
-VN1
-RS1
-C1
X1:1 (-)
VF2.1
GU_VF2U_1
411.E2
VF2.A1-VF2 A1
c
VF2U
412.E2
XCL+
XPH
DC_NP
-VN2
-C2
-VR3
CL_+
-W40201
c
-G4021
401.B4
XDC_+
XDC_+
XCL-
GU_VF4U_2
VF4.2
X1:2 (+)
-VR4
-VC2
-R4024
-W40205
XDC_401.D8
401.E4
XDC_-
Name
Date
A 13.03.01 S.SCHLEGEL
B 01-07-25 R.SEILER
C
D 01-08-09 S.SCHLEGEL
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
PHASE-LEG L1
-W40208
2
411.E3
X1:1 (-)
VF4.1
GU_VF4U_1
411.E3
412.E3
VF4.A1
-R4025
-W40206
-VF4 A1
VF4U
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
401.A8
-W40207
CL_-
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
401
403
402
411.E4
GU_VF1V_2
VF1.2
X1:2 (+)
-VR1
-R4032
-VC1
X1:1 (-)
VF1.1
XDC_+
404.A1
CL_+
404.A7
V
DC_NP
405.C1
404.C1
CL_XDC_-
404.F7
404.F1
-W40303
-R4033
GU_VF1V_1
411.E4
VF1.A1 -VF1 A1
VF1V
CL_+
-W40301
-G4031
412.E3
-W40302
-W40304
XCL+
GU_VF2V_2
VF2.2
X1:2 (+)
-VN1
-RS1
-C1
411.E5
-VR2
X1:1 (-)
VF2.1
GU_VF2V_1
411.E5
VF2.A1-VF2 A1
c
VF2V
412.E3
XPH
DC_NP
GU_VF3V_1
VF3.1
X1:1 (-)
411.E5
GU_VF3V_2
VF3.2
X1:2 (+)
-VR3
-VN2
-C2
411.E5
VF3.A1-VF3 A1
c
VF3V
412.E4
DC_NP
402.C8
402.A8
XDC_+
XDC_+
XCL-
GU_VF4V_2
VF4.2
X1:2 (+)
-VR4
-VC2
-R4034
-W40305
XDC_402.F8
402.F8
XDC_-
Name
Date
A 13.03.01 S.SCHLEGEL
B 01-07-25 R.SEILER
C
D 01-08-09 S.SCHLEGEL
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
PHASE-LEG L2
-W40308
2
411.E5
X1:1 (-)
VF4.1
GU_VF4V_1
411.E5
412.E4
VF4.A1
-R4035
-W40306
-VF4 A1
VF4V
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
402.A8
-W40307
CL_-
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
402
404
403
X1:1 (-)
411.E7
GU_VF1W_2
VF1.2
X1:2 (+)
-VR1
-R4042
-VC1
VF1.1
-R4043
-W40402
GU_VF1W_1
411.E7
VF1.A1 -VF1 A1
a
VF1W
-W40403
412.E4
CL_+
-W40401
c
-G4041
403.A8
XDC_+
-W40404
XCL+
GU_VF2W_2
VF2.2
X1:2 (+)
403.C8
DC_NP
412.E5
VF3W
VF3.A1-VF3 A1
411.E8
GU_VF3W_1
VF3.1
X1:1 (-)
411.E8
GU_VF3W_2
VF3.2
X1:2 (+)
-VN1
-RS1
-C1
411.E7
-VR2
X1:1 (-)
VF2.1
GU_VF2W_1
411.E7
VF2.A1-VF2 A1
c
VF2W
412.E5
XPH
W
DC_NP
DC_NP
-VN2
405.D1
405.F1
-C2
-VR3
8
XDC_+
XDC_+
XCL-
GU_VF4W_2
VF4.2
X1:2 (+)
-VR4
-VC2
-R4044
-W40405
XDC_403.F8
403.F8
XDC_-
Name
Date
A 13.03.01 S.SCHLEGEL
B 01-07-25 R.SEILER
C
D 01-08-09 S.SCHLEGEL
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
PHASE-LEG L3
-W40408
2
411.E8
X1:1 (-)
VF4.1
GU_VF4W_1
411.E8
412.E5
VF4.A1
-R4045
-W40406
-VF4 A1
VF4W
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
403.A8
-W40407
CL_-
Doc. des.
Resp. dept.
Doc.No.
ATDD
XDC_-
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
403
405
404
1
402.C8
-L4051
-T4051
L1
=TEU OR COU *)
IU_IU_M
IU_+
413.C2
413.C2
413.C2
+
M
-
-Z4051
3
2
-W40501 1
B
403.C8
-L4052
-T4052
L2
=TEU OR COU *)
+
M
-
3
2
-W40502 1
-W40511
-L4053
IV_IV_M
IV_+
-T4053
-C4051
-W40512
-C4052
-C4053
413.D2
413.C2
413.C2
L3
=TEU OR COU *)
2
1
BK
3
2
-W40503 1
-R4053
DC_NP
Name
Date
A
B 01-07-25 R. SEILER
C
D 01-08-09 S.SCHLEGEL
DC_NP
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H 06-07-06 P.OBERLE
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
-W40540
Title
BK
-W40509
BK
-W40508
-W40506
IW_IW_M
IW_+
404.C8
BK
-W40507
BK
-R4052
-R4051
-W40505
BK
-W40504
BK
+
M
-
404.C8
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-W40510
EMC FILTER
CURRENT MEASUREMENT
413.C2
413.C2
413.C2
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
404
410
405
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
411.A7
GUSP3_0V_2
-W41027
BK
Prepared
Approved
Project name
U0
S.SCHLEGEL
E.SUTER
ACS 6000
GNYE
BU
BN
GUSP3_+27V_2 -W41019 BK
L 3
411.A8
GUSP3_0V_1
411.A7
N 2
PHASE L2
GUSP3_+27V_1 -W41017 BK
PHASE L1
411.A8
-W41016 BK
411.A5
GUSP2_0V_2
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX1
11 AUX2
12
411.A5
GUSP2_+27V_2 -W41015 BK
-W41014 BK
=COU
PE
GUSP2_0V_1
=COU
411.A5
BN
GUSP2_+27V_1 -W41013 BK
L 3
BU
-X411 PE
411.A5
-W41012 BK
GNYE
-W41002
GUSP1_0V_2
N 2
-W41001
411.A2
LXN
1604-6
411.A2
GUSP1_+27V_2 -W41011 BK
-W41010 BK
-G4102
GUSP1_0V_1
LXN
1604-6
411.A2
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX1
11 AUX2
12
U0
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
GUSP1_+27V_1 -W41009 BK
-G4101
-W41026
BK
Name
Date
A
B 01-07-25 R. SEILER
C
D 01-08-09 S.SCHLEGEL
411.A2
Rev. ind.
Date
Date
-G4103
5
PE
BU
BN
PHASE L3
GNYE
6
7
BN
=COU
=COU
CONTROL
BU
L 3
GNYE
N 2
PE
PE 1
-W41004
-W41023 BK
-W41024 BK
-W41025 BK
U02
413.E2
412.A8
412.A8
ADCVI_+24V
INT_+24V
INT_0V
Last sh.
Sh.no.
Cont.sh.
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX
11
U01
-W41021 BK
-W41022 BK
L 3
LWN
2660-6
-W41029
BK
= INU
+
Lang. E
ADCVI_0V
ADCVI_-24V
N 2
-G4104
Doc. des.
ATDD
3BHS119662E01
Resp. dept.
Doc.No.
413.E2
413.E2
-W41003
U0
-W41020 BK
LXN
1604-6
Title
-W41028
BK
01-03-05
01-04-02
-W41018 BK
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX1
11 AUX2
12
PE
405
410
411
-W41030
PE
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
GUSP
KU C755 AE105 /
AE106
PHASE L3
PHASE L2
410.F5
410.F6
410.F5
410.F6
3
5
Subprint:
1: 3BHB003688R0101
2: 3BHB005245R0101
A1
PWF_GUSP2 -W41110
X1.1 GUSP2_0V_1
X1.2 GUSP2_0V_2
X1.3 GUSP2_+27V_1
X1.4 GUSP2_+27V_2
GUSP
KU C755 AE105 /
AE106
DC
AC
SH
COAX
SH
COAX
0V
+27V
FO
412.A3
SH
COAX
2 2 2 2
Title
GU_VF2V_1 -W41109
GU_VF2V_2 -W41109
=VLU_RBU/BCU/3
2) =VLU_RBU/BCU/4
GU_VF3V_1 -W41106
403.D1
GU_VF3V_2 -W41106
403.D1
GU_VF4V_1 -W41107
403.E1
GU_VF4V_2 -W41107
403.E1
403.C1
403.C1
X3.11
X3.12
X3.21
X3.22
X3.31
X3.32
X3.41
X3.42
X3.51
X3.52
X3.61
X3.62
X3.71
X3.72
- + - + - + - + - + - + - +
=CBU_DIU/3
1) =CBU_DIU/4
GU_VF1V_1 -W41108 SH
403.B1
GU_VF1V_2 -W41108 COAX
403.B1
1 2
01-03-05
01-04-02
410.F3
410.F4
410.F3
410.F4
-G4112
S.SCHLEGEL
E.SUTER
Date
Date
410.F1
410.F2
410.F1
410.F2
Subprint:
1: 3BHB003688R0101
2: 3BHB005245R0101
A1
PWF_GUSP1-W41105
X1.1 GUSP1_0V_1
X1.2 GUSP1_0V_2
X1.3 GUSP1_+27V_1
X1.4 GUSP1_+27V_2
PHASE L1
DC
AC
- + - + - + - + - + - + - +
SH
COAX
SH
COAX
0V
+27V
FO
Prepared
Approved
Project name
ACS 6000
412.A3
SH
COAX
2 2 2 2
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H
GU_VF2U_1 -W41104
GU_VF2U_2 -W41104
=VLU_RBU/BCU/1
2) =VLU_RBU/BCU/2
GU_VF3U_1 -W41101
402.D1
GU_VF3U_2 -W41101
402.D1
GU_VF4U_1
-W41102
402.E1
GU_VF4U_2 -W41102
402.E1
402.C1
402.C1
X3.11
X3.12
X3.21
X3.22
X3.31
X3.32
X3.41
X3.42
X3.51
X3.52
X3.61
X3.62
X3.71
X3.72
2) In case of VLU/RBU/BCU
-G4111
1 2
Name
Date
A
B 01-07-25 R. SEILER
C 01-08-07 P. OBERLE
D 01-08-09 S.SCHLEGEL
1) In case of DIU
F
Rev. ind.
-G4113
0V
+27V
X1.1 GUSP3_0V_1
X1.2 GUSP3_0V_2
X1.3 GUSP3_+27V_1
X1.4 GUSP3_+27V_2
GUSP
KU C755 AE105 /
AE106
DC
Subprint:
1: 3BHB003688R0101
2: 3BHB005245R0101
A1
PWF_GUSP3 -W41115
AC
410
411
Last sh.
412
SH
COAX
SH
COAX
2 2 2 2
= INU
+
Lang. E
Cont.sh.
Sh.no.
FO
412.A3
SH
COAX
1 2
GU_VF2W_1 -W41114
GU_VF2W_2 -W41114
=LSU1_EAF/1
3)=LSU1_EAF/2
GU_VF3W_1 -W41111
404.D1
GU_VF3W_2 -W41111
404.D1
GU_VF4W_1 -W41112
404.E1
GU_VF4W_2 -W41112
404.E1
404.C1
404.C1
X3.11
X3.12
X3.21
X3.22
X3.31
X3.32
X3.41
X3.42
X3.51
X3.52
X3.61
X3.62
X3.71
X3.72
- + - + - + - + - + - + - +
Doc. des.
ATDD
3BHS119662E01
Resp. dept.
Doc.No.
=LSU2_EAF/1
4)=LSU2_EAF/2
GU_VF1W_1 -W41113 SH
404.B1
GU_VF1W_2 -W41113 COAX
404.B1
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
402.E1
S.SCHLEGEL
E.SUTER
403.B1
403.D1
Date
Date
404.A1
01-03-05
01-04-02
404.B1
VF4U
-W41204 FO
VF1V
-W41205 FO
VF2V
-W41206 FO
VF3V
-W41207 FO
VF4V
-W41208 FO
VF1W
-W41209 FO
VF2W
-W41210 FO
VF3W
-W41211 FO
VF4W
-W41212 FO
A812
A704
A703
V568
V567
V566
V565
V564
V563
V562
V561
A816
A641
A205
PWF_GUSP3
411.E8
A206
PWF_GUSP2
411.E6
411.E3
A803
A207
PWF_GUSP1
A813
A208
IOC1
A705
A203
IOC2
413.B7
A805
A204
FSCD_+
401.C7
A804
A210
FSCD_-
401.F7
A814
A202
VLSCD/FSCD_EXT_+ =UNIT_BEFORE
A815
A201
VLSCD/FSCD_EXT_- =UNIT_BEFORE
413.B7
If pos. 34 =2
In case of double VLU
for INU1 & INU2
A715
A714
1) FB+
1) CTRL+
1) FB1) CTRL-
A531
A592
A541
A302
A551
A402
A211
A722
A212
A723
Doc. des.
ATDD
MCB
=COU
2) FT_LINK_TX
=NEXT_UNIT FT_LINK_RX
=UNIT_BEFORE
2)
VLU_LINK_TX
ADCVI_D_RX
ADCVI_D_TX
ADCVI_C_RX
ADCVI_C_TX
AMC3_B_RX
A303
A593
A594
A304
A724
A209
A403
AMC3_B_TX
AMC3_A_RX
AMC3_A_TX
A404
413.C7
413.C7
413.C7
413.C7
=COU
=COU
=COU
3BHS119662E01
Resp. dept.
Doc.No.
A712
A713
VLU_LINK_RX
404.E1
-W41203 FO
V591
Title
404.D1
VF3U
A802
403.E1
-W41202 FO
Prepared
Approved
Project name
ACS 6000
403.A1
VF2U
A818
A817
A702
402.D1
-W41201 FO
INT-BOARD
UFC760BE42
/ BE142
Date
Name
E 03-06-24 S.SCHLEGEL
F
G 04-05-10 P.OBERLE
H 06-07-06 P.OBERLE
402.B1
VF1U
-A4121
If you have a
Double INU + LSU,
make this conection
Name
Date
A
B 01-07-26 R. SEILER
C 01-08-07 P. OBERLE
D 01-08-09 S.SCHLEGEL
402.A1
F
Rev. ind.
=COU
= INU
+
Lang. E
+24V 2
0V
+24V 1
X1:3
X1:2
X1:1
INT_+24V
INT_0V
-W41213
410.F8
410.F8
411
412
Last sh.
413
Sh.no.
Cont.sh.
V103
V113
A4
A6
-W41311 FO
-W41301 FO
IOC2
IOC1
A8
A1
-W41302 FO
-W41303 FO
ADCVI_C_RX
ADCVI_C_TX
A9
A2
-W41304 FO
-W41305 FO
ADCVI_D_RX
ADCVI_D_TX
400.B5
405.B7
405.B7
405.B7
405.E7
405.E7
405.E7
405.C7
405.C7
405.C7
UDC
UF C762 AE101
-A4132
X21
9
IU_+
IU_M
IU_-
X3:1
X3:2
X3:3
IW_+
IW_M
IW_-
X4:1
X4:2
X4:3
IV_+
IV_M
IV_-
X6:1
X6:2
X6:3
SVA
XV C767
FOR VOLTAGE
ADJUSTMENT
sub-D
-A4133
SCA
+24V XV C768
FOR CURRENT
-24V ADJUSTMENT
X7:1
X7:2
X7:3
412.A4
412.A4
412.A6
412.A6
412.A6
412.A6
A10
A3
X8:1
X8:2
X8:3
410.F8
410.F7
410.F7
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-A4131
A
B
C
D
Date
13.03.01
01-07-26
01-08-07
01-08-09
Name
S.SCHLEGEL
R.SEILER
P. OBERLE
S.SCHLEGEL
ADCVI_+24V
ADCVI_0V
ADCVI_-24V
Date
Name
E 03-06-24 S.SCHLEGEL
F
G
H 06-07-06 P.OBERLE
X1:1
X1:2
X1:3
Prepared
Approved
Project name
+15V
-15V
+5V
GND
+24V
0V POWER
-24V SUPPLY
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
Doc. des.
MEASUREMENT
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
412
413
415
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
Rev. ind.
Name
2
3
PE
14
1) 2)
21
1) 2)
GNYE
PE
-W41505
BN
BU
13
-W41503 BK
GNYE
20
-X412
M
-M2 1~
ST.DUSS
M.BRNNIMANN
1
1
2
2
3
3
PE PE
-W41504
BN
BU
-X412
1
1
2
2
3
3
PE PE
-X412
Prepared
Approved
Project name
ACS 6000
M
-M1 1~
-X4151
230VAC
-X412
-W41502
12
11
BK
BK
-X4152
2L1
L
N BN 2L2
BU 2PE
YE/GN
-W41501
>
-E4151
Date
Name
E
F
G 07.05.04 P.OBERLE
H
1L1
L
N BN 1L2
BU 1PE
YE/GN
OPTION
0...60C
Date
A
B
C
D
4
-E4152
Date
Date
1
1
2
2
3
3
PE PE
-X4154
M
-M2 1~
2L1
L
N BN 2L2
BU 2PE
YE/GN
1
1
2
2
3
3
PE PE
-W41506
BN
BU
GNYE
-W41507
BN
BU
GNYE
22
15
PE
23
16
PE
1L1
L
N BN 1L2
BU 1PE
YE/GN
Title
M
-M1 1~
03-10-10
03-10-14
-X4153
-E4153
Doc. des.
M
-M2 1~
= INU
+
Lang. E
1
1
2
2
3
3
PE PE
-X4156
1
1
2
2
3
3
PE PE
-W41508
BN
BU
GNYE
-W41509
BN
BU
GNYE
24
17
PE
25
PE
18
Last sh.
Cont.sh.
Sh.no.
2L1
L
N BN 2L2
BU 2PE
YE/GN
-X4155
M
-M1 1~
ATDD
3BHS119662E01
Resp. dept.
Doc.No.
1L1
L
N BN 1L2
BU 1PE
YE/GN
413
415
416
OPTION
A
24VDC
4
RD
BU
1
2
-X4161
1
2
-W41601
1) 2)
1
2
-X413
-E4161
RD
BU
M
=
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
1) 2)
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
ST.DUSS
M.BRNNIMANN
ACS 6000
Date
Date
03-10-10
03-10-14
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
415
Cont.sh.
420
Sh.no.
416
DOOR 1
MONITORING
DOOR 2
MONITORING
DOORLOCK
MONITORING
CABINET TEMPERATURE
MONITORING
>
32
BK
BK
-W42005
-X413
10
5
9
DOOR_LOCK
4
8
LOOP 2
-W42004
22
21
0..60C
TRIANGULAR KEY
FOR MANUAL RELEASE
A2
11
2
6
-W42003
2
2
-X412
-W42002
ACTUATOR
ALL CONTACTS
IN LOCKED
POSITION
C
-W42001
A1
14
22
-S4203
13
21
14
22
-S4202
13
21
-S4201
12
=COU
1)
=COU
DOOR_LOCK
FROM COU OR
UNIT BEFORE
1)
FROM COU OR
UNIT BEFORE
TO COU OR
NEXT UNIT
LOOP 2
FROM COU OR
UNIT BEFORE
LOOP 3
TO COU OR
NEXT UNIT
LOOP 3
FROM COU OR
UNIT BEFORE
LOOP 1
FROM COU OR
UNIT BEFORE
TO COU OR
NEXT UNIT
LOOP 1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
A
B
C
D
Date
13.03.01
01-07-26
01-08-07
01-08-09
Name
S.SCHLEGEL
R. SEILER
P. OBERLE
S.SCHLEGEL
Date
E 03-06-24
F 03-10-14
G 07.05.04
H
Name
S.SCHLEGEL
ST.DUSS
P.OBERLE
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-05
01-04-02
Title
DOOR MONITORING
CABINET TEMP. MONITORING
Doc. des.
Resp. dept.
Doc.No.
ATDD
= INU
+
Lang. E
3BHS119662E01
Last sh.
Sh.no.
Cont.sh.
416
420
COMPONENT :
DOCUMENT :
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
A
B
C
D
Date
01-07-23
01-08-10
02-07-09
02-10-23
Name
R. SEILER
S.SCHLEGEL
S.SCHLEGEL
S.SCHLEGEL
E
F
G
H
Date
03-06-25
03-10-30
07.05.04
05-07-06
Name
S.SCHLEGEL
ST.DUSS
P.OBERLE
P.OBERLE
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
FRONT PAGE
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
No. of sh.
12
Cont.sh.
Sh.no.
page
title 1
title 2
rev.
ind.
title 3
FRONT PAGE
INDEX SHEET
POWER STAGE
300
PHASE-LEG 1L1/2L1
301
PHASE-LEG 1L2/2L2
302
PHASE-LEG 1L3/2L3
302A
E
HOKES
310
PULSE INTERFACE
311
315
320
DOOR MONITORING
G
CABINET TEMP. MONITORING
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
A
B
C
D
Date
01-07-24
01-08-10
02-07-09
02-10-23
Name
R. SEILER
S.SCHLEGEL
S.SCHLEGEL
S.SCHLEGEL
E
F
G
H
Date
03-06-25
03-10-30
07.05.04
05-07-06
Name
S.SCHLEGEL
ST.DUSS
P.OBERLE
P.OBERLE
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
INDEX SHEET
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
Last sh.
Sh.no.
Cont.sh.
1
2
4
DC BUS middle
DC+
UNIT BEFORE
DC+
DC-
DC-
DC BUS front
OPTION
DC+
DC+
DC_-
DC_+
DCDC_-
DCDC_+
CABLE
DC_NP
=COU or TEU
-1L1 *)
2L2
-2L3
UNIT BEFORE
F
A
B
C
D
Date
2L3
YE/GN
2L3
TERMINAL UNIT
SEE CONVERTER
HW DIAGRAM
-W401
OPTION
Name
-W402
PG
PG
PE
PE
Date
Name
E
F
G
H 05-07-06 P.OBERLE
Prepared
Approved
Project name
ST.DUSS
W.KPFER
ACS 6000
Date
Date
03-06-25
03-06-26
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
NEXT UNIT
2L1
-2L2
2L2
-2L1
YE/GN
2L1
1L3
1L3
DC_NP
1L2
-1L3
DC_-
1L2
1L1
-1L2
DC_+
1L1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
NEXT UNIT
Last sh.
Sh.no.
Cont.sh.
2
4
5
XDC_+
-V3006
-V3007
-V3016
-V3017
-V3026
-V3027
-C3021
-V3005
-V3008
-V3015
-V3018
-V3025
-V3028
-R3021
-L3021
DC_+
1L1
1L2
1L3
C
XDC_NP
-V3004
-V3001
-V3014
-V3011
-V3024
-V3021
-R3022
-V3003
-V3002
-V3013
-V3012
-V3023
-V3022
-C3022
-R3023
DC_NP
D
2L1
2L2
2L3
XDC_-
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
Date
A 19.07.01
B 01-08-10
C
D 02-10-23
Name
S.SCHLEGEL
S.SCHLEGEL
S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
POWER STAGE
CIRCUIT DIAGRAM OVERVIEW
-L3022
DC_-
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
Last sh.
Sh.no.
Cont.sh.
300
XDC_+
XDC_+
-W30013 BK
310.F5
310.F5
T3007_2
T3007_1
wt
-T3008
c
a
-V3005
-V3007
rd
302A.C4
310.F6
310.F6
T3008_2
T3008_1
4
3
2
1
8
7
6
5
wt
rd
-V3008
-W30007 BK
-W30008 BK
RC_+_0P
XDC_NP
310.F3
310.F3
T3001_2
T3001_1
wt
XDC_NP_C1
-W30012 BK
XDC_NP_C2
-T3002
c
a
-V3003
XDC_NP
310.F4
310.F4
T3002_2
T3002_1
8
7
6
5
4
3
2
1
wt
rd
-V3002
XDC_-_C
XDC_-
301.F2
XDC_-
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
301.C1
301.C2
-V3001
rd
-W30010 BK
Name
Date
A
B 01-08-10 S.SCHLEGEL
C 02-07-09 S.SCHLEGEL
D 02-10-23 S.SCHLEGEL
301.C2
-W30003 BK
-W30004 BK
2L1
8
7
6
5
-V3004
4
3
2
1
-T3001
-W30011 BK
-W30001 BK
-W30002 BK
301.A2
-W30005 BK
-W30006 BK
1L1
8
7
6
5
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-V3006
4
3
2
1
-T3007
XDC_+_C
RC_+
302A.B4
301.A1
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
PHASE-LEG 1L1/2L1
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
301.F1
Last sh.
Sh.no.
Cont.sh.
300
301
-W30113 BK
-T3018
c
a
-V3015
310.F7
310.F6
T3018_2
T3018_1
XDC_NP_C1
XDC_NP_C2
wt
rd
-V3018
-W30101 BK
-W30102 BK
-V3014
-T3011
310.F4
310.F4
T3011_2
T3011_1
4
3
2
1
8
7
6
5
wt
-W30111 BK
XDC_NP_C1
-W30112 BK
XDC_NP_C2
-T3012
-V3013
XDC_NP
302.C1
302.C2
-V3011
rd
310.F5
310.F5
T3012_2
T3012_1
8
7
6
5
4
3
2
1
wt
rd
-V3012
-W30110 BK
XDC_-_C
XDC_-_C
302.F2
XDC_-
XDC_-
Name
Date
A
B 01-08-10 S.SCHLEGEL
C 02-07-09 S.SCHLEGEL
D 02-10-23 S.SCHLEGEL
302.C2
-W30103 BK
-W30104 BK
2L2
300.F7
8
7
6
5
4
3
2
1
-W30107 BK
-W30108 BK
300.C7
rd
300.C7
302.A2
-V3017
XDC_NP
XDC_+_C
302.A1
-W30105 BK
-W30106 BK
1L2
wt
T3017_2
T3017_1
8
7
6
5
310.F6
310.F6
4
3
2
1
-T3017
c
a
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
XDC_+_C
-V3016
7
XDC_+
300.A7
300.F8
XDC_+
300.C8
300.A8
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
PHASE-LEG 1L2/2L2
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
302.F1
Last sh.
Sh.no.
Cont.sh.
300
301
302
-T3028
c
310.F6
310.F6
T3028_2
T3028_1
8
7
6
5
wt
rd
-V3028
-W30207 BK
-W30208 BK
XDC_NP_C1
XDC_NP
XDC_NP_C2
-V3024
-T3021
310.F4
310.F3
T3021_2
T3021_1
4
3
2
1
8
7
6
5
wt
-V3021
rd
wt
rd
-W30203 BK
-W30204 BK
2L3
-T3022
-V3023
302A.E4
RC_-
310.F4
310.F4
T3022_2
T3022_1
8
7
6
5
4
3
2
1
-V3022
-W30220 BK
XDC_-_C
XDC_-
XDC_-
Name
Date
A
B 01-08-10 S.SCHLEGEL
C 02-07-09 S.SCHLEGEL
D 02-10-23 S.SCHLEGEL
302A.C2
-W30201 BK
-W30202 BK
RC_-_0P
302A.C4
301.F7
4
3
2
1
301.C7
rd
301.C7
-V3027
XDC_NP
302A.B2
-W30205 BK
-W30206 BK
wt
T3027_2
T3027_1
8
7
6
5
310.F5
310.F5
4
3
2
1
-T3027
1L3
-V3025
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
XDC_+_C
-V3026
7
XDC_+
301.A7
301.F8
XDC_+
301.C8
301.A8
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
PHASE-LEG 1L3/2L3
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
302A.E2
Last sh.
Sh.no.
Cont.sh.
301
302
302A
IF LSU 14MVA
DC+
DC+
DC+
DC+
XDC_+
302.A8
-W30209 BK
RC_+
300.A3
RC_+_0P
300.C3
RC_-_0P
302.D3
-L3021
-C3021
-W30210 BK
-R3021
C
-W30211 BK
XDC_NP
302.C8
XDC_NP
-R3023
-W30212 BK
-W412104 BK
-W30213 BK
-R3022
DC_NP
CABLE TO NEAREST
UNIT EQUIPPED WITH
NP-BAR
-W30217 BK
EAF2
311.A5
-W30216 BK
EAF1
311.A5
-W30214 BK
-C3022
XDC_-
OPTION
F
A
B
C
D
Date
Name
302.E3
-L3022
IF LSU 14MVA
IF LSU1
302.F8
RC_-
IF LSU2
-W30215 BK
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
IF LSU2
IF LSU1
OPTION
DC-
DC-
DC-
DCE
F
G
H
Date
Name
Prepared
Approved
Project name
S.SCHLEGEL
W.KPFER
ACS 6000
Date
Date
03-05-07
03-06-25
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
Last sh.
Sh.no.
Cont.sh.
302
302A
310
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
Rev. ind.
Name
Date
A 01-07-24 R. SEILER
B 01-08-10 S.SCHLEGEL
C
D 02-10-23 S.SCHLEGEL
-A3101
= NEXT_UNIT FT_LINK
X23:1
X23:2
X24:1
X24:2
X26:1
X26:2
X1:1
X1:2
X2:1
X2:2
-W31016 BK
BK
1
N
L
X25:1
X25:2
-W31015
1
2 +
3 +
4 5 6 +
7 +
8 9 10 AUX
11
X22:1
X22:2
11
T3018_1
T3018_2
10
12
Doc. des.
301.C4
301.C4
X21:1
X21:2
-W31001 BN
BU
GNYE
PULSE INTERFACE
ATDD
3BHS119885E01
Resp. dept.
Doc.No.
302.C4
302.C4
T3028_1
T3028_2
=COUx
=COUx
T3008_1
T3008_2
X16:1
X16:2
-X311 1
2
PE
PE
300.C4
300.C4
X15:1
X15:2
LWN
1902-6
T3017_1
T3017_2
X14:1
X14:2
-G3101
301.B4
301.B4
X13:1
X13:2
-W31030
T3027_1
T3027_2
X12:1
X12:2
U0
302.B4
302.B4
X11:1
X11:2
PE
T3007_1
T3007_2
FT_LINK= UNIT_BEFORE
-W31014 BK
Title
300.B4
300.B4
-W31002
1
2
-W31003
1
2
-W31004
1
2
-W31005
1
2
-W31006
1
2
-W31007
1
2
-W31008
1
2
-W31009
1
2
-W31010
1
2
-W31011
1
2
-W31012
1
2
-W31013
1
2
FSCD+= UNIT_BEFORE
FSCD-= UNIT_BEFORE
LOGIC
T3012_1
T3012_2
01-03-06
01-08-07
301.E4
301.E4
T3022_1
T3022_2
Date
Date
302.E4
302.E4
T3002_1
T3002_2
300.E4
300.E4
T3011_1
T3011_2
301.D4
301.D4
T3021_1
T3021_2
302.D4
302.D4
S.SCHLEGEL
E.SUTER
T3001_1
T3001_2
CHANNEL 1
RX0
RX1
CHANNEL 1+2
RX2
CHANNEL 2
RX3
RX4
CHANNEL 1
TX0
TX1
CHANNEL 1+2
TX2
CHANNEL 2
TX3
TX4
Prepared
Approved
Project name
ACS 6000
300.D4
300.D4
PINT
DD C779 BE02
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
= NEXT_UNIT FSCD+
= NEXT_UNIT FSCD-
= LSU
+
Lang. E
Last sh.
Sh.no.
Cont.sh.
302A
310
311
302A.D7
302A.D7
CONFIGURATION
WITH
3/5MVA
IF
NO
DC
SAFE
LINE
VOLTAGE
-V3111
VUO 60-12NO3
C
-T3111
EES 50
X230:1
X40:1
OR
SUPPLY
1
3
-W31103
BK
4
5
6
-W31105
BK
7
9
-F3111
EAF
UF C765 AE102
BK
-W31104
BK
-W31106
Sig_In
Sig_Gnd
X1
X2
COAX
X40:2
X3:2 5AF
X3:1
SH
X230:2
OTHER
DRIVE
TX
=INUx
(to
Master
Int-Board)
Pwr_In
Pwr_Gnd
S1
ON
OFF
SH
ALL
A1
1234
1150V
825V
660V
500V
2 PE
-W31102
COAX
-W31101
INU
230V
-X314 1
OPTION
-X173
BN
BU
YEGN
POWER ON
CONFIGURATION
E
=INUx
=INUx
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
=INU
DRIVE
SINGLE
EAF1
EAF2
-C3111
IF
Name
Date
A 01-07-24 R.SEILER
B 01-08-10 S.SCHLEGEL
C
D 02-10-23 S.SCHLEGEL
Date
Name
E
F 03-10-30 ST.DUSS
G
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
Last sh.
Sh.no.
Cont.sh.
310
311
315
OPTION
A
230VAC
1) 2)
1) 2)
12
M
-M1 1~
F
A
B
C
D
Date
Name
Date
E
F
G 07.05.04
H
Name
P.OBERLE
Prepared
Approved
Project name
14
PE
GNYE
BN
BU
-W31505
1
1
2 2
3 3
PE PE
-X3152
-X3151
-E3151
1L1
L
BN 1L2
N
BU 1PE
YE/GN
BN
BU
-W31504
>
1
1
2 2
3 3
PE PE
KTS 01141
0...60C
-B3151
PE
-X312
21
-X312
2L1
L
BN 2L2
N
BU 2PE
YE/GN
-X312
13
BK
GNYE
-W31502
BK
-W31501
BK
-W31503
20
-X312
11
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
M
-M2 1~
ST.DUSS
M.BRNNIMANN
ACS 6000
Date
Date
03-10-30
03-10-31
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
Last sh.
311
Cont.sh.
320
Sh.no.
315
DOOR
MONITORING
DOORLOCK
MONITORING
CABINET TEMPERATURE
MONITORING
ALL CONTACTS
IN LOCKED
POSITION
21
A2
11
>
ACTUATOR
32
22
A1
14
22
-S3202
13
21
-S3201
12
TRIANGULAR KEY
FOR MANUAL RELEASE
BK
-W32006
-X313
BK
-W32005
6
10
3
7
2
6
TO COU OR LOOP 3
NEXT UNIT
TO COU OR LOOP 1
NEXT UNIT
-W32003
-X312
-W32001
=COU
=COU
TO COU OR LOOP 2
NEXT UNIT
FROM COU OR DOOR_LOCK
UNIT BEFORE
1) DOOR_LOCK
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
Name
Date
A 01-07-24 R. SEILER
B 01-08-10 S.SCHLEGEL
C
D 02-10-23 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F
G 07.05.04 P.OBERLE
H
Prepared
Approved
Project name
S.SCHLEGEL
E.SUTER
ACS 6000
Date
Date
01-03-06
01-08-07
Title
DOOR MONITORING
CABINET TEMP. MONITORING
Doc. des.
Resp. dept.
Doc.No.
ATDD
= LSU
+
Lang. E
3BHS119885E01
Last sh.
Sh.no.
Cont.sh.
315
320
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Date
Name
I 06-07-06 P.OBERLE
J
K
L
M
N
O
P
Date
Name
COMPONENT :
DOCUMENT :
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
FRONT PAGE
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
No. of sh.
16
Cont.sh.
Sh.no.
page
title 1
title 2
1
2
4
5
6
700
701
703
705
708
709
710
712
713
715
720
rev.
ind.
title 3
FRONT PAGE
INDEX SHEET
BUS BAR ARRANGEMENT
CBU CIRCUIT DIAGRAM OVERVIEW
OVERVIEW CAPACITORS ARRANGEMENT
BALANCING RESISTORS
DC LINK CAPACITORS
DC LINK CAPACITORS
DC LINK CAPACITORS
GROUNDING NETWORK
CHARGING UNIT
DISCHARGING UNIT
EARTHING ISOLATOR
CONTROL EARTHING ISOLATOR
AIR TO AIR HEAT EXCHANGERS
DOOR MONITORING
I
I
I
F
G
F
F
F
E
F
F
E
H
I
G
AUXILIARIES
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Date
Name
I 06-07-06 P.OBERLE
J
K
L
M
N
O
P
Date
Name
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
INDEX SHEET
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
2
4
OPTION
DC+
DC_NP
DCDC+
DC_NP
DCOPTION
DC+
DC_NP
DC-
DC BUS back
DC+
DC_NP
DC-
DC BUS middle
NEXT UNIT
DC+
DC_NP
DC-
DC BUS front
DC+
DC_NP
DCOPTION
=CBU
Additional CBU
depends on
drive configuration
UNIT BEFORE
DC_+1
DC_NP1
DC_-1
DC_+1
DC_NP1
DC_-1
DC_+2
DC_NP2
DC_-2
DC_+2
DC_NP2
DC_-2
DC_+3
DC_NP3
DC_-3
DC_+3
DC_NP3
DC_-3
PG
PG
PE
PE
Date
Name
I 06-07-06 P.OBERLE
J
K
L
M
N
O
P
Date
Name
Prepared
Approved
Project name
P.OBERLE
W.KPFER
ACS 6000
Date
Date
03-06-25
03-06-26
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
NEXT UNIT
DC_+
DC_NP
DC_-
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
UNIT BEFORE
Last sh.
Sh.no.
Cont.sh.
4
5
DC_+
-A7091
OPTION
OPTION
-K7201
-A7101
OPTION
-R7001
-V7091
-V7095
-V7092
-R7003
In case
of 3 rows
CBU
-C7011/...
-V7096
-R7101
-V7101
-C7101
AUX.
DC_NP
-T7091
-Z7081
OPTION
-R7002
-V7093
-C7102
-L7081
-R7081/2
-V7097
-Q7121
-C7081/2
PG
-V7098
-V7102
-R7102
In case
of 3 rows
CBU
-R7004
-V7094
PE
-R710B1/...6
DC_-
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-R710A1/...6
Name
Date
A
B
C
D 01-08-10 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
4
5
6
<= row 1
<= row 3
<= row 1
<= row 3
=CBU right
<= row 2
=CBU left
B
*)
*)
-C7011
-C7012
-C7013
-C7013
-C7012
-C7011
-C7031
-C7032
-C7033
-C7033
-C7032
-C7031
-C7051
-C7052
-C7053
-C7053
-C7052
-C7051
2 rows CBU
2 rows CBU
3 rows CBU
3 rows CBU
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
<= row 2
A
B
C
D
Date
Name
E
F
G
H
Date
Name
Prepared
Approved
Project name
P.OBERLE
M.BRNNIMANN
ACS 6000
Date
Date
03-10-20
03-10-24
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
700
DC+
DC_NP
DCOPTION
DC+
DC_NP
DC-
DC BUS back
DC_+
DC_NP
DC_DC+
DC_NP
DC-
DC BUS middle
NEXT UNIT
OPTION
DC+
DC_NP
DC-
DC+
DC_NP
DC-
DC BUS front
In case of
2 rows CBU
DC+
DC_NP
DC-W70001
BK
-R7001
2
-W70003
-W70002
BK
-R7002
1
-W70004
BK
BK
-W70005
BK
-R7003
1
2
-W70003
-W70002
BK
-R7002
2
1
-W70006
BK
-R7004
1
2
-W70004
BK
BK
DC_+1 701.A2
DC_NP1 701.C2
DC_-1 701.E2
CHARGING
UNIT
E
709.A8
DC_+
709.E8
DC_-
Date
A 28.03.01
B
C 01-07-26
D 01-08-10
Name
S.SCHLEGEL
R.SEILER
S.SCHLEGEL
703.A2
703.C2
703.E2
DC_+3
DC_NP3
DC_-3
705.A2
705.C2
705.E2
DC_+4
DC_NP4
DC_-4
710.A1
710.C3
710.F1
DC_NP7
DC_NP8
708.A2
708.A6
DC_+6
DC_NP6
DC_-6
712.B3
712.B3
712.B3
OPTION
TO LSU IF CBU IS NEAREST TO LSU
DC_+2
DC_NP2
DC_-2
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G 07.05.04 P.OBERLE
H
Prepared
Approved
Project name
CAPACITOR
BK
-R7001
2
1
DIU
-W70001
EARTH
GND
ISOLATOR NETWORK
In case of
3 rows CBU
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
UNIT BEFORE
DC_NP
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
BALANCING RESISTORS
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
700
701
A
DC_+1
Row 1
*)
*)
*)
Row 2
Row 3
OPTION
DC_+1
700.C8
-C7011
-C7012
-C7013
C7011.1
C7012.1
C7013.1
DC_NP1
DC_NP1
C7011.2
C7012.2
C7013.2
E
700.C8
DC_-1
DC_-1
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
700.C8
Name
Date
A 28.03.01 S.SCHLEGEL
B
C
D 01-08-10 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
DC LINK CAPACITORS
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
700
Cont.sh.
703
Sh.no.
701
A
DC_+2
Row 1
*)
*)
*)
Row 2
Row 3
OPTION
DC_+2
700.D8
-C7031
-C7032
-C7033
C7031.1
C7032.1
C7033.1
DC_NP2
DC_NP2
C7031.2
C7032.2
C7033.2
E
700.D8
DC_-2
DC_-2
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
700.D8
Name
Date
A 28.03.01 S.SCHLEGEL
B
C
D 01-08-10 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
DC LINK CAPACITORS
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
701
703
705
A
DC_+3
Row 1
*)
*)
*)
Row 2
Row 3
OPTION
DC_+3
700.D8
-C7051
-C7052
-C7053
C7051.1
C7052.1
C7053.1
DC_NP3
DC_NP3
C7051.2
C7052.2
C7053.2
E
700.D8
DC_-3
DC_-3
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
700.D8
Name
Date
A 28.03.01 S.SCHLEGEL
B
C
D 01-08-10 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
DC LINK CAPACITORS
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
703
705
708
1
A
-Z7081
OPTION
OPTION
DC_NP7
700.E8
DC_NP8
BK
700.E8
BK
GNYE
-W70811
GNYE
-W70810
BK
-W70807
-C7082
-X716 1
-C7081
-W70809
BK
-W70806
-W70804 BK
=COU
BK
-W70805
BK
-R7082
-R7081
-L7081
-F7081
-W70803 BK
-W70808
BK
-W70802
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-W70801
PG
PG
PE
PE
Name
Date
A 28.03.01 S.SCHLEGEL
B
C 01-07-26 R.SEILER
D 01-08-10 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
GROUNDING NETWORK
ACTIVE ISOLATION MEASUREMENT
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
705
709
708
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
-W70908
-W70907
-W70906
700.F1
a
a
c
c
a
S.SCHLEGEL
R.SEILER
S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G
H
DC_-
-V7098
-W70909
Name
700.E1
-V7097
-V7094
E
DC_+
-V7093
a
-X2 2
-X710 1
2
3
=COU
4
(depends
on supply
5
voltage)
6
7
=COU
PE
-W70902 GNYE
PU180/63/E 3.3kVA
5kVA
690V
3900V
575V
500V
460V
415V
380V *)
0V
0V
PE
/720.E8
A2
A1
-W70904
-W70901
BK1
BK2
BK3
BK4
BK5
BK6
BK7
-X2 1
-K7201
-V7096
-W70903
a
-V7092
-T7091
Date
A
B 02.04.01
C 01-07-26
D 01-08-10
-V7095
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
-V7091
OPTION
-W70905
-A7091
Date
Date
01-03-02
01-04-02
Title
CHARGING UNIT
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
708
709
710
-W71024
VLSCD
XV C724 BE
B1
A1
OF1
A2
OF2
B2
-R710A6
-W71034
-W71041
-R710A5
-W71033
-W71032
-R710A2
-W71003
-F7101
-W71023
-R710A4
-W71031
-R710A3
-W71022
-W71021
-W71001
DC_+4
-R710A1
-W71042
-W71007
FB+/3
=INU
-X7 1
-W71010
-W71011
=INU
(-)
CBU_DIU/2
X1.2
(+)
-W71012
X1.1
=INU
=INU
OPTION = Option1+Option2
13 to 18 capacitors installed
in the complete converter
=> -R710A1...-R710A6
=> -R710B1...-R710B6
=INU
-W71013
-C7102
-V7102 A1
CTRL-/3
-W71014
CBU_DIU/3
X1.1
(-)
CBU_DIU/4
X1.2
(+)
700.E8
-C7101
-W71040 GNYE
-W71015
1
=INU
OPTION = Option1
7 to 12 capacitors installed
in the complete converter
=> -R710A1...-R710A4
=> -R710B1...-R710B4
CBU_DIU/1
-R7102
-W71016
-W71017
=INU
-R7101
-V7101 A1
CTRL+/3
PE
PE
-X7 3
-W71009
700.E8
-R710B2
-W71006
DC_-4
Name
Date
A 28.03.01 S.SCHLEGEL
B
C 01-07-26 R.SEILER
D 01-08-10 S.SCHLEGEL
-R710B6
-W71038
VLSCD
XV C724 BE
B1
A1
OF1
A2
OF2
B2
-W71043
-R710B5
-W71037
-W71036
-R710B4
-W71028
-W71035
-R710B3
-W71027
-W71026
-R710B1
-W71025
-F7102
-W71005
Option 2
Option 1
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
Option 2
Option 1
700.E8
5
-W71002
OPTION
-A7101
-W71044
FB-/3
=INU
-W71004
Date
Name
E 03-06-25 S.SCHLEGEL
F 03-10-20 ST.DUSS
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
DISCHARGING UNIT
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
709
710
712
DC_+6
DC_NP6
DC_-6
-W71201 BK
-W71202 BK
-W71203 BK
-W71204
GNYE
PE
A1 A2
1
3
5
7
2
4
A
B
C
-Q7121
6
8
/713.D2
/713.D3
/713.D4
/713.D5
700.E8
700.E8
700.F8
/713.E7
PE
F
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
A
B
C
D
Date
28.03.01
02.04.01
01-07-26
01-08-10
Name
S.SCHLEGEL
S.SCHLEGEL
R.SEILER
S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
Date
Date
01-03-02
01-04-02
Title
EARTHING ISOLATOR
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
710
713
712
COU1
290.B3
COU1
290.D6
-W71308
10
-F7131
2
-W71315
BK
-W71307
-W71306
BK
BK
BK
-W71305
-W71304
-W71303
BK
BK
BK
-W71302
-W71301
BK
(+)
-W71316 BK
(+)
-X715 1
-S7131 S1
E
GROUNDING
SWITCH
OPEN 1
Name
Date
A
B
C 01-07-26 R.SEILER
D 01-08-10 S.SCHLEGEL
Date
Name
E 03-06-25 S.SCHLEGEL
F
G
H 05-12-01 P.OBERLE
GROUNDING
SWITCH
OPEN 2
Prepared
Approved
Project name
GROUNDING
SWITCH
CLOSED 1
P.OBERLE
E.SUTER
ACS 6000
GROUNDING
SWITCH
CLOSED 2
Date
Date
01-03-02
01-04-02
Title
S2 H1
BK
BK
-Q7121
/712.C5
-W71310
X2
-Q7121
/712.C5
21
-W71309
-Q7121
/712.C5
-W71314 BK
22
-W71313 BK
X1
13
-Q7121
/712.C5
-W71311
BK
-W71312
BK
14
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
COU1
290.B2
BK
A1 A2
-Q7121
/712.C5
LAMP TEST
UNLOCK
GROUNDING
SWITCH
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
712
715
713
OPTION
A
230VAC
1) 2)
1) 2)
12
BK
M
-M1 1~
F
A
B
C
D
Date
Name
Date
E
F
G 07.05.04
H
Name
P.OBERLE
Prepared
Approved
Project name
14
PE
GNYE
BN
BU
-W71505
1
1
2 2
3 3
PE PE
-X7152
-X7151
-E7151
1L1
L
BN 1L2
N
BU 1PE
YE/GN
BN
BU
-W71504
>
1
1
2 2
3 3
PE PE
KTS 01141
0...60C
-B7151
PE
-X712
2L1
L
BN 2L2
N
BU 2PE
YE/GN
-X712
21
13
-X712
GNYE
-W71502
BK
-W71501
BK
-W71503
20
-X712
11
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Swizerland Ltd 2002
M
-M2 1~
P.OBERLE
M.BRNNIMANN
ACS 6000
Date
Date
03-10-30
03-10-31
Title
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
713
Cont.sh.
720
Sh.no.
715
DOOR
MONITORING
DOORLOCK
MONITORING
CABINET TEMPERATURE
HIGH VOLTAGE
RELAIS
0..60C
I
J
K
L
Date
Name
M
N
O
P
Date
Name
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
BK
X2
=COU OR CBU
=COU OR CBU
A1 A2 /709.A6
-W72007
BK
X1
-W72006
-W72031
PE
-X714
-K7201
1)
1)
TO COU OR LOOP 2
NEXT UNIT
FROM COU OR DOOR_LOCK
UNIT BEFORE
TO COU OR LOOP 3
NEXT UNIT
TO COU OR LOOP 1
NEXT UNIT
Option:
1 door cubicle
PE
BU
-X713
6
10
3
7
-W72004
BN
TRIANGULAR KEY
FOR MANUAL RELEASE
21
A2
11
2
6
-W72003
32
22
A1
12
14
22
>
-W72002
-X712
-W72001
KTO 1140
ACTUATOR
ALL CONTACTS
IN LOCKED
POSITION
13
21
13
21
-B7201
-S7203
-S7202
14
22
-S7201
-W72004
BK
-A7091
Option:
2 doors cubicle
-W72030 PE
OPTION
CHARGING UNIT
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Date
Date
01-03-02
01-04-02
Title
DOOR MONITORING
AUXILIARIES
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
715
720
DOOR
MONITORING
DOORLOCK
MONITORING
CABINET TEMPERATURE
HIGH VOLTAGE
RELAIS
32
Date
Name
M
N
O
P
Date
Name
Prepared
Approved
Project name
P.OBERLE
E.SUTER
ACS 6000
BK
X2
=COU OR CBU
A1 A2 /709.A7
-W72007
BK
1
X1
PE
-X714
-K7201
=COU OR CBU
TO COU OR LOOP 2
NEXT UNIT
FROM COU OR DOOR_LOCK
UNIT BEFORE
1)
FROM COU OR DOOR_LOCK
UNIT BEFORE
1)
TO COU OR LOOP 3
NEXT UNIT
TO COU OR LOOP 1
NEXT UNIT
PE
-W72006
-X713
6
10
4
8
3
7
-W72004
BN
21
A2
11
2
6
-W72003
-W72031
22
A1
12
14
22
1
TRIANGULAR KEY
FOR MANUAL RELEASE
Option:
1 door cubicle
-X712
0..60C
-W72002
-W72001
ACTUATOR
ALL CONTACTS
IN LOCKED
POSITION
13
21
13
21
-B7201
KTO 1140
>
-S7203
BU
-S7202
14
22
-S7201
-W72004
BK
-A7091
Option:
2 doors cubicle
2
-W72030 PE
OPTION
CHARGING UNIT
Rev. ind.
We reserve all rights in this document and in the information contained therein. Reproduction, use or
disclosure to third parties without express outhority is strictly forbidden. C ABB Switzerland Ltd 2002
Date
Date
01-03-02
01-04-02
Title
DOOR MONITORING
AUXILIARIES
Doc. des.
Resp. dept.
Doc.No.
ATDD
= CBU
+
Lang. E
3BHS119828E01
Last sh.
Sh.no.
Cont.sh.
715
720
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
INSTALLATION
Tasnee Cop
ORDER NO
11042645
COMPONENT
ACS 6105_L12_1a9_C24_W1a
SERIAL NO.
SN 403
DOCUMENT
Based on
Prep.
Appr.
Project
Order-No.:
Ackermann O.
14.12.06
Doc. kind
J.Kappeler
Tasnee Coperion
1-1042645
14.12.06
Title
Doc.
Item
des.
des.
Resp. dept.
Doc. No.
3BHS227358
Lang.
Rev. ind.
en
Page
No. of p.
1
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Sheet index
1.
2.
3.
4.
5.
6.
7.
Prep.
Appr.
Project
Order-No.:
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
2
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Prep.
Appr.
Project
Order-No.:
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
3
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Row
Designation
Ident.-No
Description
Quantity
Unit
PC
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
-E5011/12
3BHB016006R2900
-A3101
-B3151
-B3201
-C3021
-C3022
-E3151
-F3111
-G3101
-L3021
-L3022
-R3021
-R3022
-R3023
-S3201
-S3202
-T3001
-T3002
-T3007
-T3008
-T3011
-T3012
-T3017
-T3018
-T3021
-T3022
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
3BHE006805R0002
3BHE007154R0010
3BHL000986P8000
3BHB009946R0001
3BHB009946R0001
3BHB014038R2007
3BHE003604R0102
3BHL000986P7001
3BHB009181P0001
3BHB009181P0001
HIES308461R0012
HIES308461R0012
3BHL000406P0101
3BHB001306R0002
3BHB006872P0002
3BHB004719R0001
3BHB004719R0001
3BHB004719R0001
3BHB004719R0001
3BHB004719R0001
3BHB004719R0001
3BHB004719R0001
3BHB004719R0001
3BHB004719R0001
3BHB004719R0001
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
4
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Row
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
Designation
Ident.-No
Description
Quantity
Unit
-T3027
-T3028
-V3001
-V3002
-V3003
-V3004
-V3005
-V3006
-V3007
-V3008
-V3011
-V3012
-V3013
-V3014
-V3015
-V3016
-V3017
-V3018
-V3021
-V3022
-V3023
-V3024
-V3025
-V3026
-V3027
-V3028
3BHB004719R0001
3BHB004719R0001
3BHL000986P3016
3BHL000986P3016
3BHL000986P3011
3BHL000986P3011
3BHL000986P3011
3BHL000986P3011
3BHL000986P3016
3BHL000986P3016
3BHL000986P3016
3BHL000986P3016
3BHL000986P3011
3BHL000986P3011
3BHL000986P3011
3BHL000986P3011
3BHL000986P3016
3BHL000986P3016
3BHL000986P3016
3BHL000986P3016
3BHL000986P3011
3BHL000986P3011
3BHL000986P3011
3BHL000986P3011
3BHL000986P3016
3BHL000986P3016
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
THERMOSTAT_KTS01141*250V AC
THERMOSTAT KTO1140 (NORMAL CLOSED CONT.)
CAPACITOR 2*1600UF, 2866V, FILM
1
1
1
PC
PC
PC
-B7151
-B7201
-C7011
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
3BHE007154R0010
3BHL000986P8000
3BHB015651P0001
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
5
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Row
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
Prep.
Appr.
Project
Order-No.:
Designation
Ident.-No
Description
-C7012
-C7031
-C7051
-C7081
-C7082
-C7101
-C7102
-E7151
-F7101
-F7102
-F71531
-F71531
-H7131
-K7201
-L7081
-Q7121
-R7001
-R7002
-R7081
-R7082
-R7101
-R7102
-R710A1
-R710A2
-R710B1
-R710B2
-S7131
-S7131
-S7131
-S7201
-S7203
3BHB015651P0001
3BHB015651P0001
3BHB015651P0001
3BHL000986P0006
3BHL000986P0006
3BHL000606P0002
3BHL000606P0002
3BHB014038R2007
3BHE009017R0102
3BHE009017R0102
3BHB019265R0405
3BHE010837R0000
3BHB018266R0001
3BHL000986P4000
3BHL000734P0003
3BHL000259P0003
3BHB010662R0500
3BHB010662R0500
HIES308461R0012
HIES308461R0012
3BHL000406P0002
3BHL000406P0002
HIES308461R0001
HIES308461R0001
HIES308461R0001
HIES308461R0001
3BHB012871R0001
3BHB012873R0004
3BHB018252R0001
3BHB001306R0002
3BHB006872P0002
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Quantity
Unit
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
6
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Row
35
36
37
38
39
40
41
42
43
44
45
Designation
Ident.-No
Description
Quantity
Unit
-T7091
-V7091
-V7092
-V7093
-V7094
-V7095
-V7096
-V7097
-V7098
-V7101
-V7102
3BHL000986P2102
3BHL000986P3001
3BHL000986P3001
3BHL000986P3001
3BHL000986P3001
3BHL000986P3001
3BHL000986P3001
3BHL000986P3001
3BHL000986P3001
3BHL000385P0101
3BHL000385P0101
1
1
1
1
1
1
1
1
1
1
1
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
1
1
1
1
1
1
3
3
1
1
1
1
1
1
1
1
1
1
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
-A4121
-A4131
-A4132
-A4133
-B4151
-B4201
-C1
-C2
-C4051
-C4052
-C4053
-E4151
-E4152
-E4153
-E4161
-F4011
-F4012
-G4021
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
3BHE004573R0042
3BHE006412R0101
3BHB007209R0102
3BHB007211R0101
3BHE007154R0010
3BHL000986P8000
3BHL000986P0006
3BHL000986P0006
3BHB009183P0001
3BHB009183P0001
3BHB009183P0001
3BHB014038R2007
3BHB014038R2007
3BHB014038R2007
3BHB014024R0010
3BHE014023R0101
3BHE014023R0101
3BHB009885R0021
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
7
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Row
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
Prep.
Appr.
Project
Order-No.:
Designation
Ident.-No
Description
-G4031
-G4041
-G4101
-G4102
-G4103
-G4104
-G4111
-G4112
-G4113
-L4011
-L4012
-L4051
-L4052
-L4053
-R4022
-R4023
-R4024
-R4025
-R4032
-R4033
-R4034
-R4035
-R4042
-R4043
-R4044
-R4045
-R4051
-R4052
-R4053
-RS1
-S4201
3BHB009885R0021
3BHB009885R0021
3BHL000986P7000
3BHL000986P7000
3BHL000986P7000
3BHL000986P7002
3BHB005243R0105
3BHB005243R0105
3BHB005243R0105
3BHB009181P0001
3BHB009181P0001
3BHB009182P0001
3BHB009182P0001
3BHB009182P0001
HIES308461R0012
HIES308461R0012
HIES308461R0012
HIES308461R0012
HIES308461R0012
HIES308461R0012
HIES308461R0012
HIES308461R0012
HIES308461R0012
HIES308461R0012
HIES308461R0012
HIES308461R0012
HIES308461R0001
HIES308461R0001
HIES308461R0001
3BHB010662R0120
3BHB001306R0002
PHASE S-093N
PHASE S-093N
AC-DC CONV. 27V 500W TYPE LXN 1604-6
AC-DC CONV. 27V 500W TYPE LXN 1604-6
AC-DC CONV. 27V 500W TYPE LXN 1604-6
AC-DC CONV +/-24V DUAL250W TYPELWN2660-6
KU C755 AE105:GATEUNITPWRSUPL: GUSP VAR.
KU C755 AE105:GATEUNITPWRSUPL: GUSP VAR.
KU C755 AE105:GATEUNITPWRSUPL: GUSP VAR.
REACTOR 0,005MH, 2200A, AIR
REACTOR 0,005MH, 2200A, AIR
REACTOR 0,0012MH, 1800A, AIR
REACTOR 0,0012MH, 1800A, AIR
REACTOR 0,0012MH, 1800A, AIR
RESISTOR WATERCOOLED 2.5 OHM
RESISTOR WATERCOOLED 2.5 OHM
RESISTOR WATERCOOLED 2.5 OHM
RESISTOR WATERCOOLED 2.5 OHM
RESISTOR WATERCOOLED 2.5 OHM
RESISTOR WATERCOOLED 2.5 OHM
RESISTOR WATERCOOLED 2.5 OHM
RESISTOR WATERCOOLED 2.5 OHM
RESISTOR WATERCOOLED 2.5 OHM
RESISTOR WATERCOOLED 2.5 OHM
RESISTOR WATERCOOLED 2.5 OHM
RESISTOR WATERCOOLED 2.5 OHM
RESISTOR 12 OHM (WATER COOLED)
RESISTOR 12 OHM (WATER COOLED)
RESISTOR 12 OHM (WATER COOLED)
RESISTOR 1000W, 12K, 10%
DOOR-POSITION SWITCH SZ2586+SZ2587
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Quantity
Unit
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
8
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Row
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
Designation
Ident.-No
Description
Quantity
Unit
-S4202
-S4203
-T4051
-T4052
-T4053
-U4001
-VC1
-VC2
-VF1
-VF2
-VF3
-VF4
-VN1
-VN2
-VR1
-VR2
-VR3
-VR4
3BHB001306R0002
3BHB006872P0002
3BHB014827R0001
3BHB014827R0001
3BHB014827R0001
3BHE021083R0101
3BHL000397P0001
3BHL000397P0001
3BHB013085R0001
3BHB013085R0001
3BHB013085R0001
3BHB013085R0001
3BHL000986P3002
3BHL000986P3002
3BHL000986P3002
3BHL000986P3002
3BHL000986P3002
3BHL000986P3002
1
1
1
1
1
1
3
3
3
3
3
3
3
3
3
3
3
3
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
1
1
1
1
1
1
1
1
1
1
1
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
-A2301
-A2401
-A2451
-A2501
-A2511
-A2511
-A2521
-A2521
-A2531
-A2531
-A2541
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
3BHL000764P0001
3BHE010751R0101
3BHL000510P0012
3BSE013208R0001
3BSE008508R0001
3BSE013234R0001
3BSE008510R0001
3BSE013234R0001
3BSE008508R0001
3BSE013234R0001
3BSE008514R0001
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
9
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Row
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
Prep.
Appr.
Project
Order-No.:
Designation
Ident.-No
Description
-A2541
-A2951
-B2911
-B2981
-C1021
-C1026
-C1029
-E1011
-E2981
-E2982
-F1021
-F2831
-F2851
-G1201
-G1211
-H2301
-H2302
-H2302
-H2302
-K2811
-K2812
-K2813
-K2814
-K2821
-K2823
-K2824
-K2825
-K2831
-K2832
-K2833
-K2851
3BSE013235R0001
3BHE006373R0101
3BHL000986P8000
3BHE007154R0010
3BHB010945R0001
3BHB010945R0001
3BHB001170P0001
3BHB018764R0001
3BHB014025R0010
3BHB014025R0010
3BHB010917R0001
3BHB011243R0001
3BHB011243R0001
3BHL000986P7002
3BHL000986P7002
3BHB015055R0001
3BHB012864R0002
3BHB012869R0001
3BHB012871R0002
3BHL001374P0001
3BHB001576P0240
3BHL001374P0001
3BHB001576P0240
3BHL001374P0001
3BHL001374P0001
3BHL001374P0001
3BHL001374P0001
3BHB001576P0240
3BHB001576P0240
3BHB001576P0240
3BHB006467P0004
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Quantity
Unit
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
10
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Row
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
Prep.
Appr.
Project
Order-No.:
Designation
Ident.-No
Description
-K2851
-K2852
-K2852
-K2901
-K2901
-K2902
-K2902
-K2950
-K2951
-K2952
-K2953
-K2954
-Q1001
-Q1003
-Q1003
-Q1004
-Q1004
-Q1011
-Q1011
-Q1011
-Q1012
-Q1012
-Q1012
-Q1013
-Q1013
-Q1014
-Q1014
-Q1014
-Q1041
-Q1041
-Q1051
3BHB006467P0010
3BHB006467P0004
3BHB006467P0010
3BHL001374P0001
3BHL001376P0001
3BHL001374P0001
3BHL001376P0001
3BHB010569R0001
3BHB010569R0001
3BHB010568R0001
3BHB010569R0001
3BHB010568R0001
3BHL000479P0004
3BHB000605P0107
3BHL000499P0003
3BHL000479P0006
3BHL000499P0002
3BHB000623P1006
3BHB000630P1001
3BHL000629P1003
3BHB000623P1003
3BHB000630P1001
3BHL000629P1003
3BHB000623P1003
3BHB000630P1001
3BHB000623P1007
3BHB000630P1001
3BHL000629P1003
3BHB012515R1005
3BHL000629P1003
3BHB012515R1004
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Quantity
Unit
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
11
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Row
Designation
Ident.-No
Description
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
-Q1051
-Q1061
-Q1061
-Q1071
-Q1071
-Q1073
-Q2981
-Q2981
-R1021
-R1022
-R2541
-S2301
-S2302
-S2302
-S2302
-S2302
-S2303
-S2303
-S2303
-S2303
-S2304
-S2304
-S2304
-S2304
-S2811
-T1012
-T1021
-V1021
-V1022
-Z1021
-Z1022
3BHL000629P1003
3BHB012515R1004
3BHL000629P1003
3BHB012515R1004
3BHL000629P1003
3BHB012515R1004
3BHB012515R1001
3BHL000629P1003
HUCD430225P0007
HUCD430225P0007
3BSE008538R0001
3BHB001869R0100
3BHB012865R0004
3BHB012869R0001
3BHB012870R0001
3BHB012871R0001
3BHB012865R0003
3BHB012869R0001
3BHB012870R0001
3BHB012871R0001
3BHB012869R0001
3BHB012870R0001
3BHB012871R0005
3BHB012873R0005
3BHB001306R0002
3BHB015647R0001
3BHB010944R0001
3BHB012331R0001
3BHB012331R0001
3BHB012330R0001
3BHB012330R0001
Prep.
Appr.
Project
Order-No.:
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Quantity
Unit
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
12
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Row
Designation
Ident.-No
Description
Quantity
Unit
105
106
107
-Z2851
-Z2852
-Z2901
3BHB006541P0002
3BHB006541P0002
3BHB000606P0002
1
1
1
PC
PC
PC
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
-A5201
-A5211
-A5211
-A5221
-A5221
-A5231
-A5231
-B5451
-B5631
-B5741
-E5741
-F5001
-F5002
-F5003
-G5021
-K5451
-K5542
-K5542
-PE
-Q5001
-Q5002
-Q5002
-Q5003
-Q5003
-Q5004
-Q5011
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
3BSE013208R0001
3BSE008508R0001
3BSE013234R0001
3BSE008514R0001
3BSE013235R0001
3BSE008516R0001
3BSE013234R0001
3BHL000986P8000
3BHB015149R0001
3BHE007154R0010
3BHB014025R0010
GZN 640007P0007
GZN 640007P0007
GZN 640007P0007
3BHL000986P7002
3BHB011880R0001
3BHL001374P0230
3BHL001376P0001
3BHE004742R0001
1SCA022456R9710
3BHB000605P0108
3BHL000499P0003
3BHB000605P0108
3BHL000499P0003
3BHL000479P0007
3BHL000622P1005
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
13
14
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Row
27
28
29
30
31
32
33
Prep.
Appr.
Project
Order-No.:
Designation
Ident.-No
Description
-Q5011
-Q5741
-Q5741
-R5231
-Z5001
-Z5411
-Z5412
3BHL000629P1003
3BHB012515R1001
3BHL000629P1003
3BSE008538R0001
3BHB011317R0001
3BHB000606P0002
3BHB000606P0002
Ackermann O.
J.Kappeler
Tasnee Coperion
1-1042645
14-12-06
14-12-06
Doc. kind
Title
Doc.
Item
des.
des.
Quantity
Unit
1
1
1
1
1
1
1
PC
PC
PC
PC
PC
PC
PC
Resp. dept.
Doc. No.
Lang.
3BHS227358
en
No. of p.
14
14