9886A Circuit Recommendataions

Download as pdf or txt
Download as pdf or txt
You are on page 1of 34

saue

Applications Manual

Section 4
Transmission Circuit
Recommendations

saue
Applications Manual

Section 4

Circuit Recommendations

Table of Contents
4.1

Transmission Circuit Components ........................................................................................... 3

4.1.1
4.1.2
4.1.3
4.1.4
4.1.5
4.1.6
4.1.7
4.1.8
4.1.9
4.1.10

4.2

Components for Special Functions ........................................................................................ 15

4.2.1
4.2.2
4.2.3
4.2.4
4.2.5

4.3

Introduction ....................................................................................................................................25
Circuit Recommendations .............................................................................................................. 25

Case Drain Routing Variations ............................................................................................... 27


One Charge Supply / Two Pumps .......................................................................................... 28
Charge From Implement Return Flow .................................................................................... 29
Multiple Motors....................................................................................................................... 30
Flow Dividers and Divider / Combiners .................................................................................. 31

4.10.1
4.10.2
4.10.3
4.10.4
4.10.5
4.10.6
4.10.7
4.10.8

Description .....................................................................................................................................23

Ganged Pumps ...................................................................................................................... 25

4.5.1
4.5.2

4.6
4.7
4.8
4.9
4.10

Introduction ....................................................................................................................................18
Circuit .............................................................................................................................................18
Component and Circuit Performance ............................................................................................ 20
Applications ...................................................................................................................................22

Wheel Assist .......................................................................................................................... 23

4.4.1

4.5

Flow Dividers / Combiners ............................................................................................................. 15


Flow Limiters .................................................................................................................................. 15
Counterbalance Valves .................................................................................................................. 16
Accumulators ................................................................................................................................. 16
Cylinders ........................................................................................................................................ 17

Remote Variable Pressure Limiter ......................................................................................... 18

4.3.1
4.3.2
4.3.3
4.3.4

4.4

Introduction ...................................................................................................................................... 3
Charge Pump ................................................................................................................................... 4
Controls ........................................................................................................................................... 5
Reservoir ......................................................................................................................................... 6
Conduit Sizing .................................................................................................................................. 7
Case Drain Requirements ............................................................................................................... 8
Heat Exchangers ............................................................................................................................. 8
Filters ...............................................................................................................................................9
Loop Flushing Shuttle .................................................................................................................... 12
Pressure Controls ..........................................................................................................................13

Introduction ....................................................................................................................................31
Heat Generation ............................................................................................................................ 31
Design Flow Range .......................................................................................................................31
Loop Flushing ................................................................................................................................ 32
Motor Life Reduction ...................................................................................................................... 32
Differential Flow for Steering ......................................................................................................... 33
Motor Speed Synchronization (Non-Propel) .................................................................................. 33
Recommendations for Trouble-Free Circuit ................................................................................... 33

saue
Applications Manual

Section 4

4.1

Transmission Circuit Components

4.1.1

Introduction

Transmission performance and component life are


functions of the hydraulic circuit design. Circuit design affects the ability of the various elements to
control system pressure, fluid temperature and other
factors relating to the quality of the fluid. The circuit
elements will interact with each other to produce
either desirable or undesirable results, depending on
their arrangement in the circuit.

Circuit Recommendations

A typical closed circuit schematic is shown in Figure


4-1. The closed circuit piston pump is normally factory equipped with a charge pump, charge pressure
relief valve, and a control. It may also be equipped
with high pressure protection devices such as relief
valves (shown) or pressure limiters. A loop flushing
shuttle valve can be integral to the pump or motor, or
may be installed externally. Other components such
as the reservoir, heat exchanger, and filter are added
by the user.

Circuit elements must be present to remove undesirable heat and contamination and to control the passage of cool, clean fluid into the main power loop.
Other circuit elements are present to control pressure
and, sometimes, to control flow.

The purpose of this article is to advise SauerSundstrand users on generally accepted circuit arrangements, but it does not, and cannot, describe all
possible circuits which may be appropriate for various applications. Transmission circuits are unique
designs and must be developed and tested to ensure
required performance and life.

Typical Closed Circuit Transmission Schematic

SERVO

HYDROSTATIC
PUMP

CHARGE
RELIEF

CHECK
RELIEF

CHARGE
RELIEF

HYDROSTATIC
MOTOR

HIGH
PRESSURE
RELIEF
CHARGE
PUMP

LOOP
FLUSHING
SHUTTLE

CONTROL
VALVE
HEAT
EXCHANGER

FILTER

Figure 4-1

saue
Applications Manual
4.1.2

Section 4

Circuit Recommendations

Charge Pump

A charge pump is absolutely necessary in a closed


circuit hydrostatic circuit. This article lists the various
functions of the charge pump, while Section 1.4 of
this applications manual describes charge pump
sizing considerations.

The charge pump functions associated with its charge


pressure are:

The charge pump functions associated with its volume flow rate are:

provide sufficient pressure to activate the servo


control system (on units with servo controls).

replenish loop fluid lost through volumetric inefficiency of the pump and motor(s).

control loop flushing flow by the differential pressure between the charge relief valve and the loop
flushing relief valve.

replenish loop fluid lost through the loop flushing


valve.
provide make-up fluid in the loop for load-induced
bulk modulus effects.
provide flow to activate the servo control piston
(on units with servo controls).
provide constant flow to the Electric Displacement
Control (EDC) for proper operation (on units with
EDCs).
provide a flow source for auxiliary circuit functions
such as releasing parking brakes or shifting motor
displacement.

maintain correct low loop pressure to ensure


sufficient hold down forces on the rotating groups.

provide a pressure source for auxiliary circuit


functions such as parking brake release.
All of these charge flow and charge pressure requirements must be accommodated in each mode of
operation or the system will experience poor performance or component damage. Sauer-Sundstrand
highly recommends that each application be scrutinized for sufficient charge flow and charge pressure
to ensure proper function in all modes of operation.
Most Sauer-Sundstrand hydrostatic pumps are offered with integral charge pumps sized for typical
installation requirements. Additional or alternate
charge flow sources can be utilized. A gear pump
mounted in tandem with the hydrostatic pump is often
a clean installation.

saue
Applications Manual
4.1.3

Section 4

Circuit Recommendations

Controls

The output flow of axial-piston hydrostatic pumps is


controlled by varying the swashplate angle per some
operator command. The two basic types of displacement controls are direct displacement control and
servo control.
Direct displacement controls simply use a mechanical lever attached to the swashplate upon which
the operator exerts a force, possibly through a linkage assembly. The force required to engage a direct
displacement control is a function of the system
pressure that the swashplate is working against.
There is no neutral deadband or swashplate feedback in a direct displacement control. Because the
required control force is a function of system pressure, direct displacement controls are generally only
suitable to light duty products.

Servo controls are an interface between the operator and the swashplate. The operator input is a low
force device which ports charge pressure to the servo
piston which moves the swashplate. Thus, the operator input is not dependent on system pressure. Servo
controls have a neutral deadband. Standard servo
controls also have a mechanical feedback mechanism which ensures that the swashplate position
stays where commanded. Several Sauer-Sundstrand
products are available with non-feedback servo
controls which are appropriate for certain applications. The three types of operator inputs for servo
controls are manual, electric, and hydraulic.

saue
Applications Manual
4.1.4

Section 4

Circuit Recommendations

Reservoir

In addition to providing the charge pump inlet with a


constant source of fluid, the reservoir also helps
remove air from the system and cool the fluid. The
reservoir also provides make-up fluid for volume
changes associated with fluid expansion or contraction, possible cylinder flow, and minor leakage.
The reservoir should be designed to accommodate
fluid volume changes for all modes of operation and
to promote de-aeration of the fluid as it passes
through the tank. The total reservoir volume (in gallons) should be between 1/2 and 1-1/2 times maximum charge pump flow (in GPM) for closed circuit
applications. The fluid volume should be approximately 80% of the total reservoir capacity. A large
reservoir promotes de-aeration better than a small
one. However, excessively large reservoirs may contribute to difficulties with fluid temperature and contamination control.
The reservoir may be pressurized or air breathing.
Pressurizing with a low pressure relief valve helps to
keep out dust and dirt as well as to prevent air leaks
in the charge pump suction line. However, the amount
of entrained air in the fluid increases with pressurized
reservoirs, and the pressure should be limited to 10
psig. A suction breaker relief valve is required for
pressurized reservoirs. In either case, an air breather
filter with adequate protection from environmental
contamination must be used.

Water contamination is harmful to transmission components, and reservoirs must be designed to prevent
the entrance of water into the reservoir. Since many
machines must withstand high pressure washing,
covers and other openings must be designed to
always seal tightly, especially after maintenance operations are performed.
The charge pump suction port must be near the
bottom of the reservoir, but not so near that settled
contaminants are sucked into the charge pump. The
return port should be located as far from the inlet port
as possible to provide maximum dwell time of the fluid
in the reservoir. The returning fluid must always
discharge below the fluid level, preferably through a
low velocity diffuser to prevent aeration. Reservoirs
should have a baffle(s) between the inlet and outlet
ports to ensure adequate dwell time and to prevent
surging and aeration of fluid.
A filler port should be provided which minimizes the
potential for contamination entering the system during servicing or operation. A drain port in the reservoir
is recommended to permit a complete change of
hydraulic fluid without disconnecting other hydraulic
fittings.
When designing a reservoir to serve multiple hydraulic systems, stagger the elevation of the fluid outlet
ports. If the fluid level becomes low during operation,
the system with the highest outlet port will malfunction first and provide a warning to the operator.

RETURN
FLOW

SEALED
FILLER CAP

PRESURE VALVE SUCTION BREAKER


BREATHER/FILTER

DIFFUSER

WATER TIGHT
CONSTRUCTION
TOP
VIEW

FLUID CAPACITY
5/8 CHARGE FLOW MIN.

SIDE
VIEW

FLUID CONTENT
1/2 CHARGE FLOW MIN.

BAFFLE

DRAIN

TO CHARGE
PUMP

Figure 4-2
Reservoir Design

saue
Applications Manual
4.1.5

Section 4

Circuit Recommendations

Conduit Sizing

Conduit sizing should be based on acceptable fluid


velocity and pressure drop through the conduit. Typical guidelines are:
Fluid Velocity (ft/sec)
Main system lines:

20-30

Case drain lines:

10-15

Suction lines:

4-6

Consult hydraulic hose and tube suppliers for recommendations on calculating pressure drop and for
applicable pressure ratings.
Undersized main system lines will result in heat
generation caused by high fluid velocity. Oversized
main system lines can contribute to charge pressure
droop by increasing the amount of fluid being compressed when system pressure rises.

Lines should be sized taking into account extremes in


temperature, fluid viscosity and required flow. Charge
pressure may have to be increased in order to accommodate cold fluid, long lines, or restrictions.
Undissolved air in hydraulic fluid can drastically reduce unit life. The main cause of aeration of the fluid
is air leaks, particularly on the inlet side of the charge
pump. Flow restrictions such as inadequate line size,
elbow fittings, and sudden changes in cross-sectional area can also contribute to aeration.
Inlet lines should be designed with a minimum number of joints. Recommended joint types are flared
fitting or O-ring seals. Pipe threads are not recommended. Also, shut-off valves in suction lines are not
recommended unless qualified for vacuum service.
Suction line length is critical to avoid aeration and
should be made as short as possible.

saue
Applications Manual
4.1.6

Section 4

Case Drain Requirements

All Sauer-Sundstrand closed circuit pumps and motors require case drain lines to relieve internal leakage. Also, flow passing over charge relief valves and
loop flushing valves must be removed through the
case drain line.
The main criteria for case drain line routing are:
back pressure on the unit cases
fluid velocity / line sizing considerations
cooling requirements.
Case drain lines can be routed in series through
multiple hydraulic unit cases. For circuits with loop
flushing, the loop flushing manifold would be the
initiation point of case drain flow and the pump would
be the unit immediately before the heat exchanger
(see Figure 4-1). This allows flow through all unit
cases for lubrication, cooling, and contamination
removal. The pressure drop through the heat exchanger is additive to the unit case pressure. If this
approach results in excessive unit case pressures,
alternate routing must be considered. Article 4.6 of
this application manual provides variations for case
drain circuits.
For hydraulic units with lip seals, case pressure
limitations are seal structural limitations. Exceeding
these values, even for short pulses, could result in
premature wear out or blow-out of the seal.

4.1.7

For units with metal face seals, continuous case


pressure capability is based on minimizing leaks from
the shaft seal, and on preventing gasket blow-out
during abnormal operations. This type of shaft seal is
not a leak-proof device. There is an oil film across
the seal at all times which results in normal seepage
of about one pint per 1000 hours of operation at
published case pressure limits. An increase in case
pressure will increase this seepage.
For systems with integral charge pumps, the charge
pressure relief valve is referenced to case pressure,
and the relevant charge pressure is actually the
differential above case pressure. When case pressures are elevated, particularly during transient peaks,
the differential charge pressure must be maintained.
Failure to maintain charge pressure differential
with respect to case pressure may result in damage to the hydraulic unit.
Systems with remote charge pumps should be tested
to ensure that charge pressure differential and low
loop pressure are always maintained. If a remote
charge relief valve is not referenced to hydraulic unit
case pressure, it is possible that the charge relief
valve will not follow case pressure transients due to
flow surges. The charge relief setting should be
verified to be sufficiently high to account for expected
peaks in case pressure.

Heat Exchangers

Heat exchangers should be sized to keep the fluid


within recommended temperature limits. This is normally done by selecting the worst continuous operating condition, and sizing for all the transmission loss
being cooled in the hottest ambient environment, at
the continuous temperature rating. For many machines, this occurs at the highest transmission output
speed obtainable. A rule of thumb often used is to
select a heat exchanger with a capacity equal to 1/3
the horsepower of the machine. Testing to verify
that temperature limits are maintained is highly
recommended.

Circuit Recommendations

Heat exchanger sizing may be affected by other


circuit elements. A loop flushing shuttle generally
decreases required capacity while flow restricting
valves increase it. Frequent relief valve operation will
increase the required heat exchanger capacity.
A bypass around the heat exchanger is usually
required to limit back pressure during cold starts.

saue
Applications Manual
4.1.8

Section 4

Circuit Recommendations

Filters

To prevent premature wear of the hydraulic components, it is imperative that only clean fluid enter the
hydrostatic circuit. A filter capable of maintaining the
fluid cleanliness to ISO 18/13 or better is recommended and may be located either on the inlet
(suction filtration) or discharge (charge pressure filtration) side of the charge pump. All Sauer-Sundstrand
pumps can be used with suction filtration, and several
can be equipped with charge pressure filtration adapters.

For closed circuit systems with suction filtration and


open circuit systems with return line filtration, a filter
with 35-45 = 75 (10 = 2) or better has been found to be
satisfactory. For closed circuit systems which share
a common fluid reservoir with open circuit systems, a
considerably higher filter efficiency is recommended.
This also applies to systems with gears or clutches
using a common reservoir. For these systems a filter
within the range of 15-20 = 75 (10 =10) or better is
typically required.

The selection of a filter depends on a number of


factors including the contamination ingression rate,
the generation of contaminants in the system, the
required fluid cleanliness, and the desired maintenance interval. Filters are selected to meet the above
requirements using rating parameters of efficiency
and capacity.

The filter capacity required depends on the amount


of contaminants ingressed into the system and retained in the filter and the desired maintenance
interval. As a rough guide, a capacity in grams equal
to twice the charge flow in GPM or 1/2 charge flow in
l/min has been found to be satisfactory for many
closed circuit systems.

Filter efficiency may be measured with a Beta ()


ratio as defined by ISO 4572 as the ratio of the
number of particles greater than a given size upstream of the filter to the number of particles greater
than the same size downstream of the filter. The Beta
ratio applies to a specific particle size measured in
microns. For example, 10 = 20 means that for every
100 particles of 10 micron diameter entering the filter,
only 5 particles of 10 micron diameter are found
downstream of the filter.

Since every hydraulic system is unique, the filtration


requirements and performance must be determined
by test. It is essential that monitoring of prototypes
and evaluation of components and performance
throughout the test program be the final criteria for
judging the adequacy of the filtration system.
On direct displacement non-servo controlled pumps,
a pressure drop indicator on the filter is recommended to warn against damage caused by low
charge pressure.

saue
Applications Manual

Section 4

Circuit Recommendations

Suction Filtration
The suction filter is placed in the circuit between the
reservoir and the inlet to the charge pump as shown
in Figure 4-3. A non-bypass filter is recommended
with a filter contamination monitor. A vacuum gauge,
located nearest the charge pump inlet, is suggested.
Inlet vacuums up to 6 in Hg (0.8 bar absolute) are
acceptable during normal system operation. An indicator set at 10 in Hg (0.7 bar absolute) is recommended for a filter change. Vacuums on the order of
20 in Hg (0.3 bar absolute) are acceptable during cold
start or intermittent conditions. Exceeding these values may result in charge pump cavitation, aerated
fluid, and life reduction of the hydraulic components.

Partial filter flow is achieved by incorporating the


charge pressure relief valve ahead of the filter element as shown in Figure 4-3. Only the volume of fluid
needed by the hydrostatic loop and servo control are
filtered. A non-bypass filter is recommended. Insufficient flow through the filter will result in inadequate
charge pressure and will be reflected in poor machine
performance. The filter must be capable of a pressure
drop equal to charge pressure without allowing the
filter x ratio to become less than one. A loop flushing
valve is recommended to increase the volume of
dirty fluid being removed from the pressure loop and
to increase the volume of make-up fluid passing
through the filter.

Charge Pressure Filtration

Full filter flow is achieved by incorporating the


charge pressure relief valve behind the filter element
as shown in Figure 4-4. All of the charge pump flow
is passed through the filter increasing the rate of
contamination removal from the system.

There are two basic types of charge pressure filtration; full flow and partial flow. In either case, the
pressure filter is located downstream of the charge
pump. Charge pressure filtration is often used in
systems where the inlet vacuum recommendations
would be exceeded if using a suction filter. Cold
weather applications and systems with a long inlet
lines are prime candidates for charge pressure filtration. Charge pressure filtration generally provides
greater filtering efficiency than suction filtration.
Charge pressure filters must be rated for at least the
maximum expected charge pressure per the application. Generally, filters rated at 35 bar (500 psi) minimum collapse pressure are acceptable. A 100m to
125m strainer located in the reservoir or in the
charge pump inlet line is recommended to protect the
charge pump from coarse contaminants.

10

With full flow filtration, a bypass valve is necessary to


prevent filter damage and to avoid contaminants from
being forced through the filter media by high pressure
differentials across the filter. In the event of a high
pressure drop associated with a blocked filter or cold
start-up condition, fluid will bypass the filter. Operating the system with an open bypass should be
avoided, and a visual or electrical contamination
indicator is recommended. Proper filter maintenance
is mandatory to prevent particle contaminants from
entering the system.
Refer to Section 3, Fluids and Filtration of this
applications manual for additional information.

saue
Applications Manual

Section 4

Circuit Recommendations

Pressure Filter Circuit - Charge Relief Upstream of Filter

CHARGE
RELIEF

CHARGE
RELIEF
FILTER

CHARGE
PUMP
LOOP
FLUSHING
SHUTTLE

SCREEN

TO CONTROL

Figure 4-3

Pressure Filter Circuit - Charge Relief Downstream of Filter

CHARGE
RELIEF

FILTER
BY-PASS

FILTER

SCREEN

TO CONTROL

Figure 4-4

11

saue
Applications Manual
4.1.9

Section 4

Circuit Recommendations

Loop Flushing Shuttle

There are two primary fluid loops in a closed circuit


transmission, each having a distinct design function
and associated circuit elements. These are the main
system power loop and the charge cooling loop. Fluid
is transferred between the loops by leakage, and if so
equipped, by the loop flushing shuttle. Fluid quality is
controlled primarily by the charge/cooling loop, but
the demand for high quality fluid is in the power loop.
The loop flushing shuttle is the circuit element which
is available to control this transfer of quality fluid.
The loop flushing shuttle removes some set volume
of fluid from the power loop which must be made up
by the charge pump. The fluid removed is presumably dirty and/or hot while the make-up fluid is cool
and clean. This greatly improves the heat and contamination transfer out of the power loop, improving
fluid quality and extending component life. While
some hydrostatic systems can operate satisfactorily
without a loop flushing shuttle, its addition can reduce
circuit problems where the power loop generates
heat or contaminants.
Sauer-Sundstrand offers loop flushing shuttles in
several configurations. Most closed circuit motors, as
well as the Series 42 pump family, are available with
integral loop flushing. A remote mounted loop flushing shuttle is also available.
Integral loop flushing valves reduce the number of
external components to be purchased and plumbed
into the system. Motor-mounted shuttle valves also
increase the volume of fluid flushing and cooling the
motor case.

The loop flushing shuttle is recommended for any of


the following conditions:
Sustained operation at low pressure and high
speed. This condition can create high mechanical
losses, low power loop leakage, and build-up of
heat in the power loop. In general, low pressure is
below 1000 PSI and high speed is above 2/3 full
angle rated (continuous) speed. Motor-mounted
shuttle valves are recommended for this condition.
Cylinders in the hydrostatic circuit. Cylinders allow ingression of contaminants at a significantly
higher rate than other circuit elements.
Flow restricting valves in the power loop. These
valves create heat in the loop. Note, however, that
a loop flushing shuttle must be placed upstream of
any divider-combiner valve. (See Article 4.10.)
Frequent operation of high pressure relief valves.
This creates heat. This restriction also applies to
the use of modulating relief valves in the main
power loop.
Long power loop lines. Pressure drop will be
higher than normal, increasing heat generation in
the loop. In general, long lines exceed 150 diameters in length.
Partial flow charge pressure filtration. A loop flushing shuttle is required to remove more fluid from
the power loop and, therefore, to replenish higher
volumes of cool, clean make-up fluid.
A higher degree of system reliability is obtained with
a loop flushing shuttle. A shuttle valve can improve an
unsatisfactory condition of built-in contamination or
marginal cooling. A motor-mounted shuttle can also
reduce the length of the case drain line from the
transmission to the reservoir. A shuttle valve can
potentially reduce cooler size. The final determination is made by evaluating trade-offs between the
shuttle, cooler, filter, configuration of lines and expected life.

12

saue
Applications Manual

Section 4

Circuit Recommendations

4.1.10 Pressure Controls


Closed circuit hydraulic systems require a means to
limit or control the maximum loop pressure to some
design value. Since hydraulic unit life decreases
substantially at high pressures, unit life may be unacceptably short if system pressure is not controlled.
The type of pressure protection selected will effect
the response time and power dissipation of the system.
Relief valves are fast acting and typically do not have
large pressure overshoots, provided the flow capacity of the valve is not exceeded. Full flow relief valves
are uncommon in most hydrostatic pumps. However,
high pressure relief valves dissipate power, sometimes in considerable amounts, and this is a source of
heat generation in the system. Hydrostatic units
should be sized and pressure relief valves set so that
the maximum pressure is reached less than 2% of
total operating time.
The pressure limiter, shown in Figure 4-5 is a nonpower dissipative high pressure control, and therefore limits the heat generated in the system. The
pressure limiting function can be used as an integral
part of the machine control system. However, if the
pressure limiter setting is high, the amount of time at
the pressure limit must be balanced against required
life.

Unlike a relief valve, the pressure limiter changes the


displacement of the pump in response to high system
pressure. When system pressure reaches the pressure limiter setting, the pressure limiter ports control
fluid to the servo system to destroke the swashplate
to the position required to maintain the set system
pressure. Pressure limiters can be used to control
winch payout loads because the swashplate will
travel into the opposite direction if required to maintain the set system pressure. In a typical propel
application, the pressure limiters act to reduce pump
displacement during acceleration or forward driving.
During deceleration or dynamic braking, the pressure
limiter acts to increase pump displacement.
The response time and overshoot of the pressure
limiter are a function of the pump displacement and
the rate of pressure overload. If the pump is at full
displacement when the pressure limiter activates, it
will take longer for the pump to destroke than if it was
at half stroke. Similarly, if the system experiences a
high pressure spike, there will be greater overshoot
than if the load developed slowly. To dissipate these
overshoots in the short time before the pressure
limiter becomes fully activated, the pressure limiter is
equipped with an internal relief valve to trim pressure
overshoot, so an external relief valve is usually not

Pressure Limiter Circuit


PRESURE
LIMITER
VALVE

PRESSURE
LIMITER
VALVE

SERVO
CHECK
VALVE

CONTROL
VALVE

Figure 4-5

13

saue
Applications Manual

Section 4

necessary. However, systems with control valves in


the power loop are an exception to this as they have
fast flow change characteristics. High flow, high pressure relief valves are required with directional or
switching valves in the power loop. Testing is recommended to determine the amount and duration of
pressure overshoot when using control valves in the
main power loop.
The pressure override, shown in Figure 4-6, is
another means of limiting system pressure in a hydraulic circuit. Like the pressure limiter, the pressure
override acts to destroke the swashplate in response
to high system pressures. When the set pressure is
reached, the servo control pressure (charge pressure) is blocked, and the two servo pistons are
hydraulically shunted. The pressure override does
not destroke the swashplate as quickly as the pressure limiter, but again, the response time and pressure overshoot are a function of pump displacement
and the rate of pressure overload. High pressure
relief valves are required to trim pressure spikes in
the short time before the pressure override becomes
fully activated. The recommended relief valve setting
is 1000 psi higher than the pressure override setting
to provide for adequate response and minimize interference between the two pressure controls.
Braking is also a special situation regarding pressure limiting devices. During downhill braking, the

Circuit Recommendations

pressure limiter or pressure override will act to increase vehicle speed if the pressure setting is reached.
This may decrease the amount of braking power
available from the transmission at high vehicle speed
as compared with a relief valve pressure control
system. Because the pressure limiter and pressure
override valves are nondissipative by design, the
engine absorptive power limits the amount of high
speed braking effort. With relief valves, some of the
power required for high speed, steep slope braking
can be dissipated over the reliefs by destroking the
pump.
Continued braking over relief valves will heat the
hydraulic fluid and may damage the transmission, so
only emergency situations should be considered for
use of reliefs. Since vehicles must also be equipped
with mechanical brakes which are suitable for emergency stops, emergency relief valve braking is usually redundant. In other words, a braking system
which is independent of the hydrostatic transmission must be provided which is adequate to
stop and hold the vehicle should the condition
develop.
Machines with dual path transmissions which depend on differential output speed to steer must verify
that the pressure control device does not prohibit
adequate steering control. This applies for both driving and braking.

Pressure Override Circuit

DISPLACEMENT
CONTROL

PRESSURE
OVERRIDE

Figure 4-6
14

saue
Applications Manual
4.2

Section 4

Circuit Recommendations

Components for Special Functions

Some applications may require additional circuit components in order to perform specific functions. A few of the
frequently used components are discussed in this article which includes suggestions and precautions on their use.

4.2.1

Flow Dividers / Combiners

Flow dividers are used in circuits where two motors in


parallel are supplied with a single pump. Typically, the
flow divider is expected to provide equal flow rates to
the motors to ensure positive traction or to provide
synchronized motor speeds. On propel circuits, the
flow divider also provides overspeed protection if one
motor loses traction.
Vehicle steering usually requires that the leftside and
rightside motors operate at different speeds. The flow
divider must have the capability to allow this differential flow split. Motor speed ratings must not be exceeded during steering differentials.
The pressure drop through the flow divider generates
heat in the system and should be considered when
sizing heat exchangers. Motor-mounted loop flushing
valves should not be used. Instead, an external loop
flushing valve should be located between the pump
and the flow divider to ensure proper system performance and correct flushing flow. The combining
mode should be reserved for the least-used travel
direction.

4.2.2

In the divide mode, the volumetric tolerance stack-up


of the motors and the flow divider may cause the
motor inlet to cavitate. Volumetric tolerance stack-up
includes the slight difference in motor displacement,
the difference in motor volumetric efficiency, and the
flow division capability of the flow divider. Anti-cavitation check valves may be required to protect the motor
inlets.
Thorough system testing is essential to verify
stable charge pressure and motor inlet pressures
under all operating modes. This includes all combinations of forward and reverse travel, vehicle steering, and at various pump displacements, pump
speeds, and motor displacements.

Flow Limiters

As their name implies, flow limiters are used to limit


the flow rate to a set value. In hydrostatic circuits, they
are used to prevent motor overspeed, especially in
multiple motor applications in the event of a loss of
traction. Because the flow limiter does not regulate
flow below the maximum setting, they do not make
good positive traction valves.

To prevent the possibility of inlet cavitation with an


overrunning load, the flow limiter must be mounted on
the outlet side of the motor. Flow limiters should be
sized to be active only during an overspeed event to
minimize the heat generation in the system. When the
flow limiter is active, the flow restriction will cause
higher-than-normal back pressure on the motor. Although this is not usually detrimental to the motor, it
can effect loop flushing flow and motor life.
System testing must be conducted to verify correct
performance.

15

saue
Applications Manual
4.2.3

Section 4

Counterbalance Valves

Counterbalance valves are normally used in open


circuit applications to hold a load while the pump is
idling. However, some hydrostatic winch applications
use counterbalance valves to maintain a payout tension.

4.2.4

While active, the counterbalance valve generates


considerable amounts of heat due to the flow rate and
pressure drop across the valve. Because the valve
generates high back pressure on the motor, a motormounted loop flushing valve cannot be used. An
external loop flushing valve should be considered.

Accumulators

An accumulator is rarely necessary in a closed loop


circuit. However, the two functions that an accumulator could serve in a hydrostatic system are to absorb
shock in the high pressure loop or to provide instantaneous low loop make-up flow. This instantaneous
make-up flow requirement is associated with fluid
compressibility problems, sometimes called the bulk

16

Circuit Recommendations

modulus effect. Systems with long lines or applications which experience load induced pressure spikes
are vulnerable to fluid compressibility and normally
require supplemental low loop make-up fluid for a
short time duration. However, the accumulator volume adds to the total volume of the system which is
subject to the fluid compressibility during a load
induced pressure spike.

saue
Applications Manual
4.2.5

Section 4

Circuit Recommendations

Cylinders

Generally, open loop circuits are chosen to control


hydraulic cylinders. However, a closed loop circuit
can be utilized if the correct precautions are observed.
One type of cylinder found on many mobile vehicles
is the hydraulic release parking brake. A 2-position 3way valve is typically used to either release the brake
with charge pressure or to apply the brake by venting
the cylinder to tank. This brake control sub-circuit is
actually an open circuit which simply utilizes charge
pressure as a convenient pressure source for brake
release. Although there is no sustained charge flow
requirement, there is an instantaneous flow requirement. In the vast majority of installations, this charge
flow requirement is insignificant. However, it could
become significant if the brake release line is very
long, if there are multiple brakes being released, or if
there are other charge flow demands occurring at the
same time.

A closed circuit installation of a single ended cylinder


requires special considerations due to the unequal
volumes of the rod and bore ends of the cylinder.
When the cylinder is activated from the bore end, the
input flow is greater than the exhaust flow. If the
charge pump is not able to make-up this volume
difference, the low loop side must be supplemented
through a check valve. Conversely, when the rod end
is pressurized, the return flow is greater than the input
flow. Generally, the internal charge relief valve is
unable to pass the increased low loop flow, and an
external shuttle and relief valve are necessary to
dump the flow to tank.
The input and exhaust flow differentials discussed
above are a function of the ratio of the rod and bore
end areas of the cylinder. The greater the area difference, the greater the flow differential that must be
accommodated with external circuitry.

A closed circuit installation of a double ended cylinder


is similar to a hydrostatic motor installation in that the
return flow from the cylinder is the same as the input
flow. Generally, no special considerations are required for charge pump sizing. Obviously, pump
control and high pressure protection is critical to avoid
system damage or heat generation when the cylinder
has reached the end of its stroke.

17

saue
Applications Manual

Section 4

4.3

Remote Variable Pressure Limiter

4.3.1

Introduction

Circuit Recommendations

A single sided Remotely Variable Pressure Limiter


(RVPL) circuit can be created by properly connecting
a high pressure pilot-operated relief valve to a standard Series 90 pump. Adding a RVPL circuit allows
for a pressure limiter setting that is adjustable and
lower than the internal pressure limiter. This added
control feature is useful for applications requiring
adjustable constant pressure control, such as drill rig
pull-downs and constant tension winches. More detailed information about applications is presented
after the explanation of the circuit.

4.3.2

Servo Gage Ports


SERVO CYLINDER
PRESSURE
GAGE PORT M4

SERVO CYLINDER
PRESSURE
GAGE PORT M5

Figure 4-7

Circuit

Figures 4-8 & 4-9 illustrate the external circuitry


required for a single sided RVPL. A high pressure line
must be routed from the appropriate system pressure
gage port on the pump (or other system pressure
source) to the inlet of a remotely mounted pilot
pressure relief valve (the RVPL valve). The output of
this valve is then returned to the appropriate servo
pressure gage port on the pump. Figure 4-7 shows
the series 90 pump gage ports.

The external RVPL valve becomes a second pressure limiter valve which is connected in parallel with
the internal pressure limiter valve. Of these two
valves, the one which is set at a lower pressure will
limit system pressure. The internal pressure limiter
should be set at a maximum desired system pressure, and it will limit maximum system pressure, even
if the external RVPL valve is adjusted to a higher
setting. Lower system pressures are maintained by
adjusting the external RVPL valve to settings lower
than the internal pressure limiter.

Remotely Variable Pressure Limiter Circuit For Series 90 Pumps


(Counterclockwise Rotation)
B N A
M3

M4

M5

OPTIONAL
ORIFICE
A

M1
REMOTELY VARIABLE
PRESSURE LIMITER
M2
B

L1

L2

Figure 4-8
18

saue
Applications Manual

Section 4

Circuit Recommendations

Remotely Variable Pressure Limiter Circuit For Series 90 Pumps


(Clockwise Rotation)
B N A
M3

M4

M5

OPTIONAL
ORIFICE
A

M1
REMOTELY VARIABLE
PRESSURE LIMITER
M2
B

L1

L2

Figure 4-9
The external RVPL valve will always be connected
to the system port in which it is desired to have the
RVPL function. However, the appropriate servo connection is dependent upon pump rotation shown in
Table 4-1.

Do not attempt to control the system delta pressure


near zero psi. The system gage pressure must always be above charge pressure and preferably no
less than 750 psi.
If independent control of both system pressures is
required, the RVPL circuit shown can be separately
applied to both sides of the pump. It is also possible
to control both system pressures to the same level
with a single external RVPL valve. However, the
external circuitry becomes more complex, and Sauer
-Sundstrand application engineering should be contacted for assistance.

WarningIf the servo gage port plumbing is reversed, the remote pressure limiter will not function.
If a two-level pressure limiter is desired without readjustment of the external RVPL valve, the external
valve can be switched in and out of the circuit with an
on/off valve (manually, hydraulically or solenoid operated) placed in series. This valve will switch pressure limiter operation between the internal and the
external valve settings. This logic can even be extended to more than two pressure limiter levels, using
additional external RVPL valves and on/off valves.

PUMP LOGIC CHART


ROTATION
RH (CW)

LH (CCW)

PORT

SYSTEM GAGE PORT

SERVO GAGE PORT

M1

M4

M2

M5

M1

M5

M2

M4

Table 4-1

19

saue
Applications Manual
4.3.3

Section 4

Component and Circuit Performance

Ideally, the external RVPL valve should have flow


characteristics close to that of the internal pressure
limiter valve. The critical characteristic is the pressure rise rate versus flow, which is the slope of a
pressure versus flow graph for the RVPL valve. The
desired pressure rise rate is 250 psi/gpm. A pressure
rise rate is illustrated in Figure 4-10. If the pressure
rise rate of the RVPL valve is higher (more than 250
psi/gpm), response of the RVPL will be slower than
that of the internal pressure limiter. If the pressure
rise rate of the RVPL valve is significantly lower (less
than 250 psi/gpm), the RVPL response will be faster.
The faster RVPL (high flow capability) can create
instability or overpressurize the servo.
Applications attempting to utilize faster RVPL responses should be thoroughly tested to insure adequate performance and life.
If it is desired to utilize an RVPL valve with an
inadequate pressure rise rate (flow capacity too high),
the desired pressure rise rate can be approximated by
placing an orifice in series with the external RVPL
valve. This configuration is shown as being optional
on the circuit diagram. If the RVPL valve has very little
pressure rise, an orifice of .070 inch diameter will
provide an acceptable pressure rise rate in the RVPL
circuit. If the pressure rise rate of the RVPL valve is
an intermediate value (low but not negligible), a larger
orifice may be used. The desired final result is a
combination of the external RVPL valve and the
orifice which has a pressure rise rate of 250 psi/gpm
at a flow rate of 1 gpm. The valve will typically operate
correctly while maintaining constant system pressure.
To minimize poor RVPL response with cold oil, 3/8
inch (#6) lines are recommended to and from the
external RVPL valve, particularly for long runs (10 feet
or more). The pump gage ports are #6 SAE straight
thread ports.
With the desired 250 psi/gpm pressure rise rate of the
external RVPL valve, the swashplate destroking performance of the RVPL will be similar to that of the
internal pressure limiter. However, it should be noted
that the RVPL will experience more pressure overshoot (pressure rise above its steady state setting)
during load transients requiring rapid destroking.
This will occur because the internal system pressure
relief valve will not operate in tandem with the external RVPL, as it does with the internal pressure limiter.

20

Circuit Recommendations

The system relief valve limits pressure overshoot of


the internal pressure limiter when swashplate response is not sufficient to limit system pressure to
200-400 psi above the limiter setting. When controlling with the external RVPL, the swashplate destroking
response rate will be a function of the system pressure overshoot above the steady state RVPL setting.
If the pressure rise rate of the RVPL circuit is a
constant 250 psi/gpm, the following table gives estimated 17 to 0 destroking times for various levels of
overshoot (assumes constant level of overshoot during destroking). Note that the use of a high flow RVPL
valve with a series orifice will result in slower response, particularly at the higher overshoot levels.
This is because the pressure rise rate for an orifice is
nonlinear, requiring more pressure overshoot to obtain a given flow.
Destroke Time (17 to 0) for
Pressure Overshoot
Pressure Overshoot
Series
90 Pump

250 psi

500 psi

750 psi

1000 psi

42cc

0.21 sec

0.11 sec

0.07 sec

0.05 sec

55cc

0.35 sec

0.18 sec

0.12 sec

0.09 sec

75cc

0.45 sec

0.23 sec

0.15 sec

0.11 sec

100cc

0.65 sec

0.32 sec

0.22 sec

0.16 sec

Table 4-2

The proposed RVPL circuit has the capability to push


the pump swashplate over center, even at low system
pressures, to maintain system pressure near the
RVPL setting. This is required in constant tension
winch applications, where the cable must pay out as
well as pay in to maintain constant pressure. In this
application, the pump displacement control will be
biased for full pay-in speed, and the RVPL will push
the pump swashplate over center to allow pay out.

saue
Applications Manual

Section 4

Circuit Recommendations

Desired Flow Characteristics of External RVPL Circuit


1000

System Pressure Rise Above Steady State Limiter Setting (PSI)

800

Pressure Rise Rate of


High Flow RVPL Valve with
0.070 in. Diameter Orifice
in Series

600

250 PSI / GPM Desired


Pressure Rise Rate
of RVPL Valve

400

200

0
1

-200

Steady State
Operating Point

-400

RVPL Valve Flow (GPM)


Figure 4-10
21

saue
Applications Manual
4.3.4

Section 4

Applications

As mentioned, the RVPL circuit is useful for applications requiring adjustable constant pressure control,
such as drill rig pulldowns and constant tension
winches. The circuit is normally used with a displacement control (manual, hydraulic or electrical). The
displacement control provides speed control when
the RVPL is set at a pressure higher than is required
to move the load. This allows precise load positioning
when the system is not in the constant pressure
mode. When operating at constant pressure, the
RVPL is adjusted to maintain a desired pressure
level, and the displacement control is set to limit the
maximum load speed. The RVPL is designed to
behave in a manner similar to the internal pressure
limiter to reduce pump displacement when the pressure reaches the RVPL setting.
In drilling applications, motor output torque is limited by limiting pressure with the RVPL. The RVPL
can be used to control drilling torque, with the internal
pressure limiter set at a higher pressure.
On a constant tension winch, the displacement
control is typically set to allow full pump displacement
to run full speed cable pay in, while constant cable
tension is maintained by means of the RVPL. The
ability of the RVPL to drive the pump swashplate over
center for a winch pay out condition makes it especially suitable for a mooring winch application. On a
mooring winch, the pumps displacement control is
set to pay in the cable at a certain speed. If the cable
tension increases to the point of the RVPL setting, the
pumps displacement will decrease to maintain the
pressure setting. If the tension is great enough, the
RVPL will drive the swashplate over center and the
pump will pay out cable. Consideration must be given
if the load can drive the swashplate to its maximum
displacement when paying out cable. Any flow generated by the load that the pump cannot take in will
either drive the pump faster or drive the pressure
higher. A relief valve can be used to limit the maximum pressure condition, but excessive heat will be
produced. In most cases the prime mover, acting in a
dynamic braking mode, will be the limiting factor. A
separate method of braking the load must be provided
to prevent engine or pump overspeed.

22

Circuit Recommendations

High inertia vehicles, such as railroad maintenance


machines, need control of deceleration forces. The
pump has a capability to be driven to a neutral
swashplate condition before the vehicle reaches a
zero speed. Without some method to prevent this
from occurring, the internal pressure limiter will drive
the pump towards maximum displacement during
dynamic braking. The pump, now acting as a motor,
will feed a large amount of torque into the engine due
to the pumps high pressure and displacement. This
may be more torque than what the engine can handle
in a braking mode. A circuit utilizing the RVPL, while
sensing travel direction, can be used to limit system
pressure while decelerating. By setting the RVPL at
a pressure level less than the internal pressure limiter,
torque can be absorbed by the prime mover at a safe
level. The system is designed such that the internal
pressure limiter controls the acceleration torque while
the RVPL controls the deceleration torque.
Certain applications require that maximum torque
levels be controlled, whereby the load is dependent
on a second hydraulic drive. For example, a drilling
operation may require the maximum torque on the drill
head to be controlled. The torque, however, will
depend on the rate of pull-down of the drill head. An
RVPL circuit could be used to limit torque in the
following manner: both the drilling pump and the pulldown pump would have their pressure limiter settings
set above the RVPL. The RVPL would sense system
pressure from the drilling circuit, but instead of feeding the RVPL signal back into the drilling pump, the
signal would feed into the pull-down pump to bring it
out of stroke. Drill torque is then controlled by the pulldown rate of the drill head.
As another example, a harvesting machine may
include two hydraulic systems: one system to propel
the machine and one system to feed crop into the
machine. In this application, the RVPL would sense
the pressure of the system gathering crop into the
machine, but its signal would be tied to the propel
system. When the gathering system pressure increases due to heavier crop, the RVPL will operate to
slow down the vehicle speed.
When two or more pumps are used in parallel, an
external pressure limiter is also recommended. For
more detailed information for this kind of application,
see Article 4.5, Ganged Pumps.

saue
Applications Manual
4.4

Wheel Assist

4.4.1

Description

Section 4

Circuit Recommendations

Additional traction is often needed on machines


working in poor traction conditions. The need may
only be to prevent stalling of the machine, or to
increase the drawbar pull or to assist in steerability.
Axles, or wheels, not usually used for the propel
function can be fitted with hydraulic motors to give
auxiliary tractive force. Each vehicle has its own
particular needs and each must be analyzed according to those needs.

Often the assist and main drive wheels are of different


diameter which then requires a different rpm for any
given vehicle speed. Likewise the turning radius
affects a speed change between the inside wheel and
the outside wheel. Maximum speed limits of the wheel
assist motors must be considered closely due to
these variations as well as any downhill speedup.
Flow dividers may be necessary to prevent full flow
from going to any one motor in any circumstance.

Some of the considerations that will influence the size


or type of wheel assist are:

Controlling a wheel assist function can be done in a


variety of ways. Variable motors, using main system
drive flow as the power source, can be stroked for
additional traction, manually or automatically, at some
designated pressure setting. Pressure compensated
motors stroked at a pre-selected pressure may work
well when traction coefficients are rather consistent.
For instance, if the main drive wheels are losing
traction at a pressure less than the wheel assist
pressure set point, the wheel assist motors would not
shift offering any additional traction.

weight distribution due to loading or grade

coefficients of traction

auxiliary drive wheel speed

wheel diameter

final drive ratios.

As a general rule, the wheels which are offering the


additional traction must not lose traction (spin out)
before the main drive axle wheels spin out. This is
especially true when fluid from the main propel circuit
is used for the wheel assist function. The traction
coefficient must be known, as well as the load distribution or the weight shift distribution. Variations in the
traction coefficient and load distribution may exist due
to changes in traction and operating grades.

Sensing a percentage of main drive wheel slip can be


the signal to the control system to add wheel assist
traction. Typically, a separate pump and motor arrangement would be used. In this case, the main
drive could be mechanical or hydraulically driven.
Application assistance is always available when wheel
assist drives are encountered.

Wheel speeds will change due to shifting into a


different final drive ratio or to changes in variable
motor displacements.

23

saue
Applications Manual

Section 4

The wheel assist shown in Figure 4-11 is accomplished with two variable motors and wheel ends on
the steerable wheels. These variable motors are
typically capable of both zero and full displacement.
While in a mode of low torque requirements, the
variable motors are in zero displacement. When
more tractive force is required, the motors are shifted
to full displacement.

Circuit Recommendations

The wheel assist shown in Figure 4-12 can accomplish the additional tractive force required with a
separate designated pump for the assist function.
This system can produce a fixed or variable tractive
force by the use of a electronic pressure control. By
controlling pressure level from zero to maximum by
operator input, just the right amount of assist traction
is possible. At a zero pressure command, vehicle
coast is possible.

Operator Controlled Wheel Assist

AXLE MOTOR

ENGINE PUMP

VARIABLE MOTORS
W/ WHEEL DRIVES

Figure 4-11

Pressure Controlled Wheel Assist

AXLE MOTOR

ENGINE PUMP PUMP

Figure 4-12

24

FIXED MOTORS
W/ WHEEL DRIVES

saue
Applications Manual
4.5

Ganged Pumps

4.5.1

Introduction

Section 4

The full through drive torque capability of the Series


90 pump is often used to eliminate the need for multi
pad pump drives. The Series 90 pump family has
found additional success with the through torque
drive by ganging pumps together. A ganged pump
is defined normally as two or more Series 90 pumps
bolted together with the output flows combined to

4.5.2

Circuit Recommendations

drive one load. The objective of the ganged pump is


to simulate the performance of one large pump with
the flow of two or more smaller pumps. Two smaller
pumps will have higher individual speed capabilities
than a large pump and therefore could offer an input
speed advantage. Ganging pumps has created an
entirely new set of larger pump displacements for
additional application flexibility.

Circuit Recommendations
is less than the RVPL setting. The remote pressure
limiter is a single side circuit. Two RVPL circuits are
necessary to control both sides of the loop.

In order for two pumps to operate and perform as one,


it is critical that each pump reacts similarly to the
common load. The Series 90 Pressure Limiter automatically adjusts pump displacement to limit pressure
when the limiter setting is reached, but is not practical
to assume that the valves in two pumps will be set
exactly the same. Therefore, the lowest valve in
either pump would attempt to regulate the pressure of
the entire system by controlling the displacement of
one pump. To prevent this undesirable effect, a single
external valve should be used to control both of the
ganged pumps simultaneously.

Both pumps must have a displacement control and it


is recommended that they be of the same style
(manual, hydraulic or electric). Do not use a cover
plate and slave the second pump from the first. The
displacement control adds the necessary swashplate
feedback so that both pump displacements are
matched closely to one another within the accuracy
and tolerance of the two controls. At pressures below
the RVPL setting the displacement control response
time for each pump is not affected by the RVPL
circuit. However, when the RVPL does function, the
system pressure limiter response time will approximately double due to the total volume of two servos
and added plumbing that needs to be pressurized
before the pumps will destroke.

The concept shown in the figure below is commonly


referred to as a Remote Variable Pressure Limiter
(RVPL) and details can be obtained from SauerSundstrand Application Engineering. Electrical Displacement Controls (EDCs) are shown in the figure.
The check valves are necessary to isolate the pump
servos from one another when the system pressure

A ganged pump with the RVPL regulating port A

RVPL VALVE

PORT "A"

LO

LO

EXTERNAL
HPRV

ED

ED

HI

HI
PORT "B"

Figure 4-13

25

saue
Applications Manual

Section 4

Since the internal pressure limiters (PL) of each


pump needs to be functionally removed, it is necessary that they be ordered, or adjusted, to avoid any
interference with the remote valve. The internal PLs
should be set at a minimum of 35 bar (500 psid) above
the setting of the remote pressure limiter valve. Since
the high pressure relief function of the Series 90 Multi
Function Valve is also eliminated when the integral
PLs are functionally removed, it is recommended
that an external high pressure relief valve capable of
short duration high flow be added to the circuit at a
pressure of 35 bar (500 psid) above the remote
pressure limiter setting.
It is recommended that both pumps be controlled
together. For example, an idle pump in neutral would
be forced over center when system pressure is created by a second individually controlled pump. Additionally, the displacement change resulting from the
operation of the pressure limiter is a result of a system
of sources acting on the pump swashplate. The
pumps should be controlled together so the net
forces on each pump are similar and, therefore, the
performance of the pressure limiter optimized.

26

Circuit Recommendations

Table 4-1 (p. 19) identifies the appropriate system


pressure and low pressure servo gage ports that are
used in the RVPL circuit based on input rotation. The
port labels shown in the table are consistent with the
Series 90 Technical Manual, pump outline and installation drawings.
Other control concepts and configurations are possible, but their acceptance would depend on the
application and performance expectations. Any
ganged pump application should be tested thoroughly for control and driveline performance. Ganged
Series 90 pumps have been a success in many
applications. For application assistance, or information on other control concepts, please consult your
Sauer-Sundstrand representative.

saue
Applications Manual
4.6

Section 4

Circuit Recommendations

Case Drain Routing Variations

The routing of case drains in a closed circuit system


should allow for adequate cooling of the hydraulic
fluid, but with minimum external plumbing. The figures in this section show the recommended case
drain routings for various pump/motor configurations.
Figure 4-14 shows the simplest method for routing
case flows for a pump/motor combination without
loop flushing. The figure shows that all of the case
flow goes through the motor housing. To ensure the
cases of the pump and motor are full of fluid at all
times, case outlets should come out at the top of the
unit and case inlets should come in at the bottom.
Figure 4-15 shows one method of case drain routing
for a system which incorporates loop flushing. This
method combines case flows for both the pump and
the motor.
An alternative routing for a loop flushing system is
shown in Figure 4-16. Here all of the case flow goes
through the pump. This system uses somewhat simpler plumbing than the previous method. However, it
has the disadvantage that the pump case temperatures will be greater

MOTOR
HYDROSTATIC
PUMP
HEAT
EXCHANGER

Figure 4-14

MOTOR
HYDROSTATIC
PUMP
HEAT
EXCHANGER

Figure 4-15

MOTOR

HEAT
EXCHANGER

Figure 4-16

27

saue
Applications Manual
4.7

Section 4

Circuit Recommendations

One Charge Supply / Two Pumps

It is possible to have one charge pump supply charge


flow to two separate pumps, providing charge flow is
great enough. The main advantage is that a single
line from the reservoir may simplify plumbing.
Figure 4-17 shows that only one of the pumps is
equipped with a charge pump, which supplies charge
flow to the second pump through its charge pressure
gage port. The charge pump must be sized large
enough to provide adequate charge flow to both
pumps for all operating conditions. This is especially
important at low speeds, since charge flow is less and
leakage losses are greater.

PV

PV

CHARGE
INLET

CHARGE PUMP
GAGE PORT
MV

Figure 4-17

28

MV

saue
Applications Manual
4.8

Section 4

Circuit Recommendations

Charge From Implement Return Flow

Often charge flow for a closed circuit system can be


provided by an implement pump, whose primary
function is to power an open circuit load such as a
cylinder, motor, etc. Figure 4-18 shows such an
arrangement, whereby one or more pumps are without charge pumps and receive all of their charge flow
from implement pump return flow. The main advantage to this method is the single inlet suction line from
the reservoir.

PV

Care must be taken that the implement pump return


flow from the load always exceeds the closed circuit
charge flow requirements for any operating condition. Also, a pressure filter should be placed between
the charge inlet and the return flow to keep contaminants from the implement circuit out of the hydrostatic
system.

CHARGE
INLET

PRESSURE
FILTER
IMPLEMENT
PUMP
LOAD
(CYLINDER, MOTOR, ECT.)

Figure 4-18

29

saue
Applications Manual
4.9

Section 4

Multiple Motors

Several motors can be combined in the same closed


circuit, but are normally only used in parallel. Series
operation of axial piston or bent axis motors loads the
bearings excessively causing substantial reductions
in life expectancy. Contact Sauer-Sundstrand if series circuits are under consideration.
Several motors driven in parallel from one pump
allow a potential motor overspeed situation. If one
motor is at a reduced load due to poor traction or other
unusual situation, it may overspeed and damage the
unit if not sized to accept all the pump flow. Flow
dividers, divider-combiners or flow limiters have been
used successfully to prevent motor overspeed.
Motor overspeed is a safety concern when the transmission is providing retarding power. For swashplate
motors, maximum speed may be limited by block lift
and accompanying loss of drive. Operation above
maximum speed is not permitted.
Flow dividers create heat, even during normal operation, as they continuously act during vehicle turns,
with load differentials, or due to normal tolerance
effects. Care must be used in sizing heat exchangers
when using flow dividers.
Flow divider performance is sensitive to the droop
built into the valve. A large droop should be used to
improve control stability and reduce the amount of
time the valve regulates. A flow droop of at least 30%
prior to the valve restricting at the pressure limit is
recommended. A cross-valve orifice may be required
to achieve this. This may affect motor sizing and
maximum speed expected and should be accounted
for when sizing units.
A divider-combiner valve can pressurize both motor ports when operating in the combining mode. The
frequency of this occurring must be anticipated as this
condition greatly reduces expected hydraulic unit life.
The combining mode should be used in the least
frequent travel direction. We recommend testing to
determine the level and duration of both motor ports
being pressurized.

30

Circuit Recommendations

A loop flushing shuttle should be used to keep cool


fluid flowing into the power loop. Flow in a loop
flushing shuttle must be accounted for when using
flow dividers or divider/combiners in a multiple motor
circuit. Because the charge relief valve in the shuttle
flows oil, a differential flow can exist from one side of
the loop to the other. If the shuttle is installed between
one motor and the flow control valve, charge flow
causes the valve to operate, even though all motors
may be at the same speed. A loop flushing shuttle
should be installed between the pump and flow
control valve in order to avoid this problem.
Motor speed may be controlled with the use of flow
limiters, which operate at a set maximum flow. This
type of valve only functions if overspeed is imminent,
and it typically operates a small amount of time. Flow
limiters should be installed to restrict motor return flow
to avoid cavitating the motor inlet when they function.
As this will pressurize both motor ports and reduce
expected life, frequency of operation must be determined.
Sauer-Sundstrand is available for obtaining suggestions on transmission circuit design. Contact your
Sauer-Sundstrand representative if questions of suitability exist. In any case, we recommend testing the
final circuit for sufficient time and under severe enough
conditions to determine acceptable performance and
life.
Multi-Motor Circuit With Flow Limiters

HYDROSTATIC
PUMP

HYDROSTATIC
MOTOR
LOOP
FLUSHING
SHUTTLE

Figure 4-19

saue
Applications Manual

Section 4

Circuit Recommendations

4.10 Flow Dividers and Divider / Combiners


4.10.1 Introduction
This article describes how flow dividers and dividercombiner valves are used in closed circuit applications and how special considerations must be taken
when using these components.
Flow dividers and flow divider-combiner valves are
normally used in vehicle propel circuits where two
motors are plumbed in parallel and supplied by a
single flow source. In such installations, they serve
potentially two purposes; to prevent one motor from
overspeeding if it loses contact with the ground, and
to ensure uniform output speed of both motors.
The basic difference between flow dividers and flow
divider-combiners is simply that the flow divider is not
designed to combine flow. In the divide mode, their

performance is effectively the same. A circuit using


flow dividers must either be a unidirectional system or
it must bypass the divider during reverse flow. Because most vehicle propel systems are bi-directional,
this article focuses on the divider-combiner with the
understanding that the comments made with respect
to the divide mode of operation are valid for both types
of valves.
The information presented in this article is based on
field experience using flow divider-combiners in closed
loop hydraulics. Valve suppliers should be consulted
regarding the performance, ratings, and sizing for
each application.

4.10.2 Heat Generation


The pressure drop across the divider-combiner is
typically on the order of 200 to 600 psi in the divide
mode. Many valves will have an even greater pressure drop in the combine mode. This pressure drop is
a source of heat generation in the circuit which should
be accounted for when sizing the heat exchanger.
The heat generation can be minimized if the dividercombiner is by-passed during modes of operation
when it is not needed in the circuit.

4.10.3 Design Flow Range


Flow divider-combiners are designed for optimum
performance within a specified range of flow rates.
Operation outside of the specified range will significantly reduce the reliability of the valve and will likely
cause circuit problems as well. Consult the valve
supplier for correct sizing on each application.

31

saue
Applications Manual

Section 4

Circuit Recommendations

4.10.4 Loop Flushing


If loop flushing is desired in a circuit using a flow
divider-combiner, it must be located between the
pump and the flow divider-combiner. If loop flushing is
attempted at the motors, problems can occur during
both the divide and combine modes of operation.
During the divide mode of operation, the low loop side
of the motor should be at charge pressure. However,
on propel applications where the two motors are
effectively tied together by the ground, the high pressure side of one motor can actually be subjected to a
vacuum (see section 4.10.8, Recommendations for a
Trouble Free Circuit) due to volumetric discrepancies
in the divider-combiner and the motors. If this occurs,

the loop flushing shuttle will shift and attempt to draw


fluid from the inlet side of the motor, compounding the
vacuum problem.
During the combine mode of operation, the low loop
pressure at the motors is elevated by the pressure
drop across the divider-combiner, which can be several hundred psi. Thus, the loop flushing relief valve
at the motor, being subjected to this considerably
higher pressure, would dump significantly more fluid
than in the divide mode of operation. This could
potentially cause increased case pressures and/or a
loss of charge pressure in the combine mode of
operation.

Loop Flushing When Used With a Divider-Combiner


ON/OFF
TRACTION
VALVE

DIVIDING FLOW
CROSS-BLEED
ORIFICE
LOOP
FLUSHING
VALVE

MF
MF

COMBINING FLOW

Figure 4-20

4.10.5 Motor Life Reduction


Hydraulic unit life is highly dependent on system
pressure. In the combine mode of operation, when the
low loop pressure is potentially several hundred psi
greater than charge pressure, the motor life can be
adversely affected. Although the delta pressure across
the motor (the pressure that transmits torque) may be
at some prescribed design value, the actual pressure

32

seen by the motor rotating group is the sum of the


high and low sides of the loop. Therefore, the frequency of operating in the combine mode must be
anticipated and included in the duty cycle to calculate
a predicted unit life. Operation in the combine mode
should be minimized if long motor life is critical.

saue
Applications Manual

Section 4

Circuit Recommendations

4.10.6 Differential Flow for Steering


On a typical propel system, the motors must rotate at
moderately different speeds in order for the vehicle to
negotiate a smooth turn. To accomplish this, the flow
divider-combiner must allow differential flows. The
combine mode is often much less capable of handling

this differential flow during a steering event. Motor


speed ratings must not be exceeded during the steering event. Consult the valve supplier for specifications
on differential flow in both divide and combine modes
of operation.

4.10.7 Motor Speed Synchronization (Non-Propel)


Several non-propel types of applications require two
(or more) motors operating at the same speed to
correctly perform a work function. Depending on the
output speed accuracy required, a flow divider-combiner may or may not be an acceptable means of
accomplishing the objective.
The system performance will be limited by the volumetric tolerance stack-up of the motors and the
divider-combiner. This includes the slight difference
in motor displacement, the slight difference in motor
volumetric efficiency, and the flow division capability
of the divider-combiner. Because the flow divider is
not a perfect device, it will not send exactly the same
volume of fluid to the two motors. Because the motors

are not perfect devices, their speed given the same


volume of fluid will be slightly different. As the system
loads up, the motor volumetric efficiency of the two
motors will decrease at slightly different rates. The
result of these imperfections is that the two motors will
probably not rotate at exactly the same speed. The
acceptability of a system can only be determined by
testing.
If a system requires a high level of accuracy, the best
way to control two (or more) motors at the same
output speed is with a one pump per motor. A microcontroller used in conjunction with speed sensors at
the motors and EDCs at the pumps would provide
the best synchronization.

4.10.8 Recommendations for Trouble-Free Circuit


Several circuit problems may arise when using flow
dividers in closed loop hydraulics. These problems
seem to be very sensitive to system dynamics and do
not surface on each and every installation. The
severity of the problems may fluctuate on a given
machine with fluid temperature, vehicle speed, and
grade. To combat these problems, the following
recommendations are provided with Figure 4-20 to
help design trouble-free circuits.

Provide anti-cavitation check valves to the inlet

The loop flushing valve must be located between


the pump and the flow divider-combiner per the
discussions presented above.

side of both motors. This is necessary because


the volumetric tolerance stack-up of the motors
and the divider-combiner can cause one motor to
cavitate in a typical propel application. If one
motor requires slightly more fluid to rotate at the
same speed as its partner motor (and if the two
motors are tied together by the ground) then it will
starve. Because its inlet pressure drops, the motor is doing no work. On some machines this could
go unnoticed indefinitely. The same scenario occurs if the divider-combiner were to split the flow
unevenly.

Bypass the divider-combiner in the combine mode

Work closely with a divider-combiner supplier to

of operation with either check valves or ON/OFF


valves. Having eliminated the combiner from the
circuit, it will provide no motor speed regulation or
limitation in the event of a wheel spin-out.

select the most appropriate valve for the application. Take into account flow and pressure ratings,
pressure and temperature compensation, differential flow capability, and volumetric effectiveness.

Test the vehicle extensively in all modes of operation to ensure correct functional performance as
well as correct circuit performance.

33

saue
Hydraulic Power Systems
SAUER-SUNDSTRAND Hydraulic Power Systems - Market Leaders Worldwide
SAUER-SUNDSTRAND is a world leader in the design and
manufacture of Hydraulic Power Systems. Research and
development resources in both North America and Europe
enable SAUER-SUNDSTRAND to offer a wide range of
design solutions utilizing hydraulic power system
technology.

SAUER-SUNDSTRAND specializes in integrating a full


range of system components to provide vehicle designers
with the most advanced total-design system.
SAUER-SUNDSTRAND is Your World Source for
Controlled Hydraulic Power Systems.

Heavy Duty Axial Piston


Pumps and Motors

Heavy Duty Bent Axis


Variable Motors

Cartridge Motors/
Compact Wheel Drives

Medium Duty Axial Piston


Pumps and Motors

Microcontrollers and
Electrohydraulic Controls

Hydrostatic Transmission
Packages

Open Circuit Axial Piston Pumps

Gear Pumps and Motors

Genuine Service Parts

Worldwide Service Support


SAUER-SUNDSTRAND provides comprehensive worldwide service for its
products through an extensive network of Authorized Service Centers
strategically located in all parts of the world.
Look to SAUER-SUNDSTRAND for the best in WORLDWIDE SERVICE.

Genuine Parts
Original
Ersatzteile

saue
BLN-9886 July 1997 Rev. A

SAUER-SUNDSTRAND COMPANY
2800 East 13th Street
Ames IA 50010 U.S.A.
Phone: (515) 239-6000 FAX: (515) 239-6618

SAUER-SUNDSTRAND GMBH & CO.


Postfach 2460 D-24531 Neumnster
Krokamp 35 D-24539 Neumnster Germany
Phone: (04321) 871-0 Fax: (04321) 871 465

You might also like