Charge Transfer System Spec
Charge Transfer System Spec
Charge Transfer System Spec
1.0
GENERAL
1.1
Definition
The Charge Transfer System (CTS) is form of lightning protection that has been
developed to prevent lightning strikes to a site and to the protective system itself. The
system dissipates (leaks off) the charge induced by the storm cell onto the protected area
by transferring that charge to the surrounding air by Point Discharge. The resulting
potential between the protected site and the storm clouds is thereby reduced significantly,
thereby preventing direct strikes.
1.2
System Performance
System Composition
The Charge Transfer System shall be composed of three basic properly integrated
subsystems conforming to the following specifications:
1.3.1 The Dissipator or Ionizer Assembly shall be designed to fit the subject
facility in such a manner as to prevent a strike or the initiation of one from the
facility and shall conform to the following specifications without exception:
a.
The Ionizer assembly shall be made of Charge Transfer
System wire whose geometry shall have been determined by
laboratory simulation tests to provide maximum ion current for a
given electric field strength. Refer to Figure 4. Each point shall
be separated so as to maximize ion current during a storm.
Quality Assurance
Manufacturers qualifications: Firms regularly engaged in manufacture of CTS,
related ground systems, and installation of protective systems of the scope and
type herein required, and whose products have been in satisfactory use in similar
service for not less than 10 years shall be qualified for this project.
1.5
1.6
Acceptable Manufacturers
The preapproved manufacturer of the point discharge type lightning protection
systems is Lightning Eliminators & Consultants, Inc. (LEC), 6687
Arapahoe Road, Boulder, Colorado 80303 USA (303) 447-2828. Any other
candidate must be proved to be equal. Installers must be supported by a qualified
Installation Engineer, with at least 5 years of experience.
2.0
System Composition
2.1
The CTS shall be composed of three basic, properly designed and integrated
subsystems, each of which shall conform to the following specifications.
The Ionizer Assembly shall be designed to safely interface with the customers
facility without degrading its specific mission or structural integrity.
The assembly shall be designed to shape, or conform to the shape of the lines
of equipotential as the form around the facility to be protected. Under no
circumstances shall it create or permit to be created, discontinuities that may
form or permit to be formed streamers from the Ionizer or from within its
protected facility. It shall be so designed that all of the Ionizer points go into
ionization at approximately the same time or voltage level.
The Ionizer shall be designed so as to provide the required number of sharp points
per unit area, related to approximately 45 meters square per Ionizer. In no case
shall the Ionizer assembly provide less than the required number of points as
calculated for the given site. Calculations are required with the design.
The Ionizer shall be made from a stainless steel wire providing a matrix of points,
at least 10 centimeters from an adjacent set of points.
Each Ionizer assembly shall be mounted in such a way as to assure an
unobstructed view of the storms electrostatic field from any direction. In no
case shall it or any other device on the same structure be mounted such that the
electrostatic field is limited, shadowed or obscured from the Ionizer.
The Ionizer assembly performance shall be qualified in accordance with the test
procedure specified within Appendix 1.
2.2
2.3
2.3.1 All components of the CTS shall be designed with withstand a wind force of
at least 80 miles per hour (130 km/hr).
2.3.2 The CTS shall be designed and deployed so as to not require periodic
maintenance at intervals of less than 5 years. Yearly inspections and
chemically activated ground electrodes recharging and recertifications are
expected.
2.3.3 All materials shall be selected to assure compatibility with each other and with the
protected system to avoid galvanic corrosion.
3.0
3.1
The Ionizer
The lightning protection systems shall be installed as indicated in accordance
with equipment manufacturers drawings and written instructions, and in
compliance with applicable requirements of National Electric Code (NEC).
Installation of the lightning prevention system shall be coordinated with other
work, including electrical wiring as necessary to interface the installation of the
lightning prevention system.
3.2
3.3
Bonding
Bonding requirements for facilities using Charge Transfer System strike
prevention technology is much simpler than that required for the common
lightning collector concepts. Since there will be no lightning strikes to the site,
bonding requirements are limited to the establishment of an equal potential
reference point or Common Point Ground.
4.0
Personnel Training
APPENDIX 1
ASSESSING THE PERFORMANCE
OF AN IONIZER PANEL
The Ionizer Panel is the primary component of a Charge Transfer System (CTS) or
Charge Dissipation System (CDS). These panels are a component or a CTS system
building block, designed to prevent the termination of a lightning strike to any thus
protected area. Preventing the termination requires a method of collecting the charge
induced on that site and transferring that charge to the Ionizer as fast as the charging
mechanism creates or induces the charge. The Ionizer must then transfer that charge back
to the storm cell, at the same rate, using air molecules as the transfer medium.
Ionizer efficiency shall be assessed within an Electrostatic Field Simulator, by plotting the
ionization current of a sample panel as a function of the applied voltage. The Ionizer
panel must be typical of that design used for the CTS. The ionization current must be
measured as a function of the voltage applied to the Ionizer, when the spacing between
that Ionizer Panel and the simulator high voltage plate is set at 1/2 meter. Refer to Figure
3 for the Test Setup.
The test procedure shall consist of a series of current measurements as a function of the
applied voltage. The steps should be in increments of about 1 kV, starting at 10 kV and
increasing to at least 100 kV. No arc is to form between the panel and the simulator plate.
An arc disqualifies the test. The actual ionization current measured should equal or
exceed that illustrated by Figure 4. Again, this shall be without any arc produced within
the Ionizer, or between it and the simulator anode plate.
At peak voltages, the Ionizer must also be producing visible corona. The following
factors are considered significant:
1.
2.
3.
The test facility shall be at least 2.5 meters square to create the
required electric field without fringe effects.
4.
The metering system shall have been calibrated prior to the test, and
shall offer scales of from 0 to at least 5,000 microamperes.