KABELDON Outdoor Cable Termination
KABELDON Outdoor Cable Termination
KABELDON Outdoor Cable Termination
APSEA 5272 kV
Use
Flexible cable termination, suitable for installations in which
the termination can be installed in any angle. The termination
is not self-supporting.
top bolt
Standard
Meets the requirements of:
IEC 60840
top cap
Design
The cable termination is made up of modules comprising
a field controlling stress relief cone, sheds to increase the
creepage distance and a top cap.
sheds
stress cone
creepage current collector
Installation
The termination is installed easily, entirely without heat. The
stress cone and sheds are to be pushed on to the cable and
snapped together.
The following cable data should be stated when ordering:
Voltage
Diameter across prepared insulation
Conductor cross section
Conductor material Cu or Al
Screen, cross section and type
Outer diameter of the cable
APSEA 72
APSEA 52
Note:
Top bolt or cable lug is to be ordered separately, see following
pages.
33-66 mm
6/7 | Kabeldon cable accessories 1420 kV | Cable accessories for XLPE-insulated cables 52420 kV
30/40
125
Creepage distance
165
Voltage
Prepared insulation
level
Designation
Top cap
Creepage
type
distance min
Length A
Net
weight
kV
mm
mm
mm
52
3336
APSEA 521 U
THS
1150
580
kg/item
4
52
3639.5
APSEA 522 U
THS
1150
580
52
39.543
APSEA 523 U
THS
1150
580
52
4348
APSEA 524 U
THS
1150
580
52
4854
APSEA 525 U
THSA
1150
580
4
4
52
5460
APSEA 526 U
THSA
1250
650
52
6066
APSEA 527 U
THSA
1250
650
72
3336
APSEA 721 U
THS
1420
690
72
3639.5
APSEA 722 U
THS
1420
690
72
39.543
APSEA 723 U
THS
1420
690
72
4348
APSEA 724 U
THS
1420
690
72
4854
APSEA 725 U
THSA
1790
870
72
5460
APSEA 726 U
THSA
1790
870
72
6066
APSEA 727 U
THSA
1790
870
Extension kits
Designation
Extra creepage
Extension kit
Article number
~ 290
6235.0163*
~ 290
6235.0164*
~ 290
6235.0165*
~ 290
6235.0166*
~ 135
6235.0167**
~ 135
6235.0168**
~ 135
6235.0169**
180
Cable accessories for XLPE-insulated cables 52420 kV | Kabeldon cable accessories 1420 kV |
6/8
Top caps, cable lugs and top bolts are supplied by the piece.
Top hole
Top cap
Top cap
THS
THS
THS
THS
THSA
THSA
THSA
THSA
Max. diameter
mm
30
40
50
65
28
37
47
60
28
37
47
60
125
B
A/K-TBF SKR
Top bolt. Moment 45 Nm.
A
SCL-B
Bolt cable lug.
A/K-TBF SKR
SCL-B
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Top bolt
Cable lug
Cable lug
Cable lug
Cable lug
Cable lug
Description
A/K-TBF SKR
SCL-B
UKR
JSA 1
SCK 2
Al
Al
Al
Al
Al
Al
Al
Al
Al
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Al/Cu
Al/Cu
Al/Cu
Al/Cu
Al/Cu
Cable
Diameter
cross section
mm
120
150, 185
240
300, 400
500
630
800
1000
1200
120
150, 185
240
300, 400
500
630
800
1000
1200
1095
25150
50240
70300
300630
30
30
30
30
30
30
40
40
40
30
30
30
30
30
30
40
40
40
24
28
33
38
50
UKR 90
6/9 | Kabeldon cable accessories 1420 kV | Cable accessories for XLPE-insulated cables 52420 kV
weight
45
45
50
55
60
60
65
65
65
45
45
50
55
60
60
65
65
65
24
28
33
38
52
kg/item
0.5
0.5
0.8
0.8
0.9
0.9
1.2
1.2
1.1
1.6
1.6
2.4
2.4
2.8
2.8
4.0
3.8
3.5
0,10
0,25
0,30
0,35
0,90
mm
Use
Top bolt
Cable lug, if needed.
For fixing cables.
Earthing kit for cable with metallic sheath, e.g. lead.
Not needed if cable has only Cu-wire screen.
Screen connection for Al-foil radial waterproof cable.
Not needed if cable has only Cu-wire screen.
Net
See page
6/9
3/51
7/2
6/21
6/21