Koehler - Installation Manual 7-28EFOZD

Download as pdf or txt
Download as pdf or txt
You are on page 1of 76

Installation

Marine Generator Sets

Models:

9--32EOZD/7--28EFOZD

TP-6711

7/09

TP-6711

7/09

Table of Contents
Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Section 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Section 2 Location and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11


2.1 General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Section 3 Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Cooling System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.1
Intake Through-Hull Strainer (Seacock Cover) . . . . . . . . . . . . . . . . . . . . .
3.2.2
Seacock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.3
Seawater Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.4
Water Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.5
Closed Heat Exchanger (9--32EOZD/7--28EFOZD Models) . . . . . . . . . .

13
13
13
13
14
14
14
15

Section 4 Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


4.1 Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Exhaust Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Exhaust System Location, Mounting, and Installation . . . . . . . . . . . . . . . . . . . . . . .
4.3.1
Above-Waterline Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.2
Mid/Below-Waterline Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

17
17
17
18
19
20

Section 5 Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


5.1 Fuel Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Fuel Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Fuel Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Fuel/Water Separator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5 Fuel Pump Lift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6 Fuel Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

25
25
26
26
26
26
26

Section 6 Electrical System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


6.1 AC Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2.1
Circuit Breaker Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2.2
Circuit Breaker Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Installation In Steel or Aluminum Vessels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 Installation Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7 Remote Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

27
27
28
28
29
31
31
32
32
33

Section 7 Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35


Section 8 Reconnection/Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1 Four-Lead Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1.1
100--120-Volt Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1.2
100--120/200--240-Volt Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1.3
200--240-Volt Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2 Twelve-Lead Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3 ADC 2100 Adjustment after Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3.1
Configuration Mode Time Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3.2
Controller Software Version Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3.3
Setting the System Voltage and Frequency . . . . . . . . . . . . . . . . . . . . . . .
8.3.4
Adjusting the Voltage, Gain, and Volts/Hz, and Engine Speed . . . . . . .
8.3.5
Voltage Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3.6
Frequency Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TP-6711

7/09

53
54
54
54
55
57
58
58
58
58
64
64
65

Table of Contents

Appendix A Generator Selection and Wattage Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

69

Appendix B Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

70

Appendix C Generator Set Output Ratings Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

72

Table of Contents

TP-6711

7/09

Safety Precautions and Instructions


IMPORTANT SAFETY INSTRUCTIONS.

Electromechanical
equipment,
including generator sets, transfer
switches, switchgear, and accessories,
can cause bodily harm and pose
life-threatening
danger
when
improperly installed, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely. Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual has several types of safety
precautions and instructions: Danger,
Warning, Caution, and Notice.

Accidental Starting
WARNING

WARNING

Accidental starting.
Can cause severe injury or death.

Fire.
Can cause severe injury or death.

Disconnect the battery cables before


working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.

Do not smoke or permit flames or


sparks near fuels or the fuel system.

DANGER
Danger indicates the presence of a
hazard that will cause severe
personal injury, death, or substantial
property damage.

WARNING
Warning indicates the presence of a
hazard that can cause severe
personal injury, death, or substantial
property damage.

CAUTION
Caution indicates the presence of a
hazard that will or can cause minor
personal injury or property damage.

NOTICE
Notice communicates installation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publication to improve operator
recognition.
Replace missing or
damaged decals.

TP-6711

7/09

Engine Backfire/Flash
Fire

Disabling
the
generator set.
Accidental starting can cause
severe injury or death.
Before
working on the generator set or
connected equipment, disable the
generator set as follows: (1) Move the
generator set master switch to the OFF
position. (2) Disconnect the power to
the battery charger. (3) Remove the
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent starting of
the generator set by an automatic
transfer switch, remote start/stop
switch, or engine start command from a
remote computer.
Disabling
the
generator set.
Accidental starting can cause
severe injury or death.
Before
working on the generator set or
equipment connected to the set,
disable the generator set as follows:
(1) Press the generator set on/off
button to shut down the generator set.
All indicator lamps dim. (2) Disconnect
the power to the battery charger, if
equipped. (3) Remove the battery
cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent the
starting of the generator set by the
remote start/stop switch.

Servicing the fuel system. A flash


fire can cause severe injury or death.
Do not smoke or permit flames or
sparks near the fuel injection system,
fuel line, fuel filter, fuel pump, or other
potential sources of spilled fuels or fuel
vapors. Catch fuels in an approved
container when removing the fuel line
or fuel system.
Servicing the air cleaner. A sudden
backfire can cause severe injury or
death. Do not operate the generator
set with the air cleaner/silencer
removed.
Combustible materials. A sudden
flash fire can cause severe injury or
death. Do not smoke or permit flames
or sparks near the generator set. Keep
the compartment and the generator set
clean and free of debris to minimize the
risk of fire. Catch fuels in an approved
container. Wipe up spilled fuels and
engine oil.
Combustible materials. A fire can
cause severe injury or death.
Generator set engine fuels and fuel
vapors are flammable and explosive.
Handle these materials carefully to
minimize the risk of fire or explosion.
Equip the compartment or nearby area
with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BC for electrical fires or as
recommended by the local fire code or
an authorized agency.
Train all
personnel
on
fire extinguisher
operation
and
fire
prevention
procedures.

Safety Precautions and Instructions

Exhaust System

Fuel System

WARNING

Carbon monoxide.
Can cause severe
fainting, or death.

WARNING

Hazardous Noise
CAUTION

nausea,

Explosive fuel vapors.


Can cause severe injury or death.

Hazardous noise.
Can cause hearing loss.

The exhaust system must be


leakproof and routinely inspected.

Use extreme care when handling,


storing, and using fuels.

Never operate the generator set


without a muffler or with a faulty
exhaust system.

Carbon
monoxide
symptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in
exhaust gases. Carbon monoxide is an
odorless,
colorless,
tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Carbon
monoxide poisoning symptoms include
but are not limited to the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep. Alert others to the
possibility of carbon monoxide
poisoning. Seek medical attention if
the condition of affected persons does
not improve within minutes of breathing
fresh air.

The fuel system. Explosive fuel


vapors can cause severe injury or
death. Vaporized fuels are highly
explosive. Use extreme care when
handling and storing fuels. Store fuels
in a well-ventilated area away from
spark-producing equipment and out of
the reach of children. Never add fuel to
the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines. Use flexible
sections to avoid fuel line breakage
caused by vibration. Do not operate the
generator set in the presence of fuel
leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming
generator set operation.

Inspecting the exhaust system.


Carbon monoxide can cause severe
nausea, fainting, or death. For the
safety of the crafts occupants, install a
carbon monoxide detector. Never
operate the generator set without a
functioning carbon monoxide detector.
Inspect the detector before each
generator set use.
Operating the generator set. Carbon
monoxide can cause severe nausea,
fainting, or death. Be especially
careful if operating the generator set
when moored or anchored under calm
conditions because gases may
accumulate. If operating the generator
set dockside, moor the craft so that the
exhaust discharges on the lee side (the
side sheltered from the wind). Always
be aware of others, making sure your
exhaust is directed away from other
boats and buildings.
6

Safety Precautions and Instructions

Draining the fuel system. Explosive


fuel vapors can cause severe injury
or death. Spilled fuel can cause an
explosion. Use a container to catch fuel
when draining the fuel system. Wipe up
spilled fuel after draining the system.

Hazardous Voltage/
Moving Parts
WARNING

Hazardous voltage. Moving parts.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Servicing the generator set when it
is operating. Exposed moving parts
can cause severe injury or death.
Keep hands, feet, hair, clothing, and
test leads away from the belts and
pulleys when the generator set is
running. Replace guards, screens, and
covers before operating the generator
set.
Grounding electrical equipment.
Hazardous voltage can cause
severe injury or death. Electrocution
is possible whenever electricity is
present. Ensure you comply with all
applicable codes and standards.
Electrically ground the generator set,
transfer switch, and related equipment
and electrical circuits. Turn off the main
circuit breakers of all power sources
before servicing the equipment. Never
contact electrical leads or appliances
when standing in water or on wet
ground because these conditions
increase the risk of electrocution.

TP-6711

7/09

Disconnecting the electrical load.


Hazardous voltage can cause
severe injury or death. Disconnect
the generator set from the load by
turning off the line circuit breaker or by
disconnecting the generator set output
leads from the transfer switch and
heavily taping the ends of the leads.
High voltage transferred to the load
during testing may cause personal
injury and equipment damage. Do not
use the safeguard circuit breaker in
place of the line circuit breaker. The
safeguard circuit breaker does not
disconnect the generator set from the
load.
Short
circuits.
Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage. Do not contact electrical
connections with tools or jewelry while
making adjustments or repairs.
Remove all jewelry before servicing the
equipment.
Testing the voltage regulator.
Hazardous voltage can cause
severe injury or death. High voltage
is present at the voltage regulator heat
sink. To prevent electrical shock do not
touch the voltage regulator heat sink
when testing the voltage regulator.
(PowerBoostt, PowerBoostt III, and
PowerBoostt V voltage regulator
models only)
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severe injury or death.
Connect the generator set to the
building/marina electrical system only
through an approved device and after
the building/marina main switch is
turned off. Backfeed connections can
cause severe injury or death to utility
personnel working on power lines
and/or personnel near the work area.
Some states and localities prohibit
unauthorized connection to the utility
electrical
system.
Install
a
ship-to-shore transfer switch to prevent
interconnection of the generator set
power and shore power.

TP-6711

7/09

Testing live electrical circuits.


Hazardous voltage or current can
cause severe injury or death. Have
trained and qualified personnel take
diagnostic measurements of live
circuits. Use adequately rated test
equipment with electrically insulated
probes and follow the instructions of the
test equipment manufacturer when
performing voltage tests. Observe the
following precautions when performing
voltage tests: (1) Remove all jewelry.
(2) Stand on a dry, approved electrically
insulated mat. (3) Do not touch the
enclosure or components inside the
enclosure. (4) Be prepared for the
system to operate automatically.
(600 volts and under)

NOTICE
Fuse replacement. Replace fuses
with fuses of the same ampere rating
and type (for example: 3AB or 314,
ceramic). Do not substitute clear
glass-type fuses for ceramic fuses.
Refer to the wiring diagram when the
ampere rating is unknown or
questionable.

NOTICE
Saltwater damage. Saltwater quickly
deteriorates metals. Wipe up saltwater
on and around the generator set and
remove salt deposits from metal
surfaces.

Hot Parts
WARNING

Hot coolant and steam.


Can cause severe injury or death.
Before removing the pressure cap,
stop the generator set and allow it to
cool. Then loosen the pressure cap
to relieve pressure.

Notice
NOTICE
This generator set has been
rewired from its nameplate voltage
to

246242

NOTICE
Voltage reconnection. Affix a notice
to the generator set after reconnecting
the set to a voltage different from the
voltage on the nameplate. Order
voltage reconnection decal 246242
from
an
authorized
service
distributor/dealer.

Safety Precautions and Instructions

Notes

Safety Precautions and Instructions

TP-6711

7/09

Section 1 Introduction
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.

marine generator set. For operating instructions, refer


to the operation manual.

x:in:001:002:a

Use the specification sheets as a guide in planning your


installation. Use current dimension drawings and wiring
diagrams.

The safe and successful operation of a marine power


system depends primarily on the installation. See
Figure 1-1. Use this manual as a guide to install the

Marine generator set installations must comply with all


applicable regulations and standards.

1
18

3
17
16
4
15

5
14
9
13

8
6

12

11

7
10

585711

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

Exhaust mixer elbow (exhaust/water outlet) (not shown)


Heat exchanger (not shown)
Coolant recovery tank (located on the unit on some models)
Seawater strainer *
Seawater pump (seawater inlet)
Seawater line *
Seacock *
Craft stringers
Fuel feed pump (fuel inlet) *
Fuel return line *

Figure 1-1

7/09

Hose clamps
Fuel supply line *
Fuel/water separator (see Section 5 for more information)
Mounting tray
Battery/battery storage box
Battery cables
Exhaust hose or exhaust line *
Electrical leads (AC output leads/remote start panel leads)

* Indicated components must conform to USCG regulations.

Typical Generator Set Location and Mounting (Without Sound Shield)

Note: See text for complete explanation of installation


requirements.

TP-6711

11.
12.
13.
14.
15.
16.
17.
18.

Note: Use two hose clamps on each end of all flexible


exhaust hose connections.

Section 1 Introduction

Notes

10

Section 1 Introduction

TP-6711

7/09

Section 2 Location and Mounting


2.1 General Considerations
The key to installation is location. Before making final
plans for locating a generator set, consider the
following.

Installation Location Considerations


1. Choose a location that allows adequate space for
cooling and exhaust system installation, fuel
system installation, ventilation, and service access
to the generator set (engine and generator).
2. Use craft stringers or other available structural
members capable of supporting the generator sets
weight.
3. Seal the generator sets engine room from the
cabin to prevent exhaust gases and fuel vapors
from entering the cabin.
See the current generator set specification sheet or
Section 7 of this manual for generator set dimensions
and weights. See Figure 1-1 for a typical installation.

2.2 Location
Locate the generator set to allow easy service access to
the generator sets engine, controller, cooling, and fuel
system components. The engine compartment is often
the ideal location for the generator set if the propulsion
engine(s) does not obstruct access to the generator set
and controller.

Allow clearance for vibration and cooling during


operation. Allow a minimum of 38 mm (1.5 in.)
clearance on all sides (top, front, rear, and sides) of a
generator set without an optional sound shield. Refer to
the instruction sheet for minimum clearances for
sound-shielded units. Also, allow space for the power
takeoff (PTO) option, if equipped.

2.3 Mounting
Mount the generator set as high as possible to avoid
contact with bilge splash and lower-lying vapors and to
allow for downward pitch of the exhaust line toward the
exhaust outlet.
Kohler Co. recommends mounting the generator set on
a flat board attached to the craft stringers. Craft
stringers generally provide the best generator set
support. Ensure that the structural members can
support the generator sets weight and withstand its
vibration.
The generator set includes vibration mounts and a
mounting tray or skid. If desired, install additional
vibration isolating pads underneath the generator sets
base.
Use the four mounting holes in the mounting tray to
mount the generator set securely to the craft.
For angular operating limits, consult the operation
manual.

Marine Generator Set Installations in


European Union Member Countries
This generator set is specifically intended and approved
for installation below the deck in the engine
compartment. Installation above the deck and/or
outdoors would constitute a violation of European Union
Directive 2000/14/EC noise emission standard.

TP-6711

7/09

Section 2 Location and Mounting

11

Notes

12

Section 2 Location and Mounting

TP-6711

7/09

Section 3 Cooling System


3.2.1

3.1 Ventilation
Engine combustion, generator cooling, and expulsion of
flammable and lethal fumes require ventilation. Provide
ventilation compliant with USCG Regulations governing
sizing of vents and other considerations.
As a rule, size each inlet- and outlet-vent area to a
minimum of 13 sq. cm/30.5 cm (2 sq. in. per ft.) of the
crafts beam. Should this rule conflict with USCG
Regulations, follow USCG Regulations. For applications
with screened inlets, double the size (4 sq. in. per ft.) of
the hull/deck openings. Extend the vent ducts to bilges to
expel heavier-than-air fumes.

Intake Through-Hull Strainer


(Seacock Cover)

Install a screened-intake, through-hull strainer to


prevent entry of foreign objects. Use perforated,
slotted-hole, or unrestricted-hole design strainers. See
Figure 3-2 for examples of typical strainers. The inner
diameter of the strainer opening must be equal to or
greater than the inner diameter of the water-line hose to
the seawater pump.

For generator sets mounted in the engine compartment,


increase the air flow to allow for the generator sets
requirements. Install optional detection devices to
cause alarm, warning, or engine shutdown should
dangerous fumes accumulate in the compartment.

See the generator set specification sheet that shipped


with the generator set for air requirements. The air intake
silencer/cleaner provides combustion air to the engine.
Do not compromise the recommended minimum
clearance of 38 mm (1.5 in.) between a duct opening and
enclosure wall. The engine/generator performance will
decline if you compromise these guidelines. See
Figure 3-1 for allowable intake restriction.

3
4

Note: ISO 3046 derates apply. See Appendix C.

Model
9--32EOZD/7--28EFOZD

Figure 3-1

Allowable
Intake Restriction
635 mm H2O
(6.23 kPa) or less

Combustion Air Intake Restriction

3.2 Cooling System Components


The marine generator sets cooling system requires the
following components.

TP-6711

7/09

1.
2.
3.
4.
5.

Inside packing
Outside packing
Seacock cover
Direction of vessel movement
Typical intake through-hull strainers

Figure 3-2

1-789

Seacock Installation

Do not align the strainer (in relation to the crafts direction


of travel) with any other through-hull intakes. See
Figure 3-3. Flush mount the recommended through-hull
strainer. Install slotted-hole-design strainers with the
slots parallel to the direction of the vessels movement.

Section 3 Cooling System

13

1
4

3
2

Note: Position the intakes in relation to the vessels


1-789
travel so neither is in the wake of the other.
1.
2.
3.
4.

Generator set intake


Main engine intake
Aft (rearward)
Fore (forward)

Figure 3-3

Intake Strainer

Figure 3-4
Do not use a speed scoop or cup design intake
through-hull strainer because it can cause a ramming
effect and force water upward, past the seawater pump,
and into the engine cylinders when the vessel is moving
and the generator set is shut down.
Do not use hulls incorporating sea chests or other
designs that provide a positive pressure to the raw water
pump for the intake through-hull strainers. Positive
pressure forces water past the raw water pump and into
the engine. A sea chest is a concave molded-in-the-hull
chamber that aligns to the vessels direction of travel. A
sea chest configuration applies positive pressure similar
to a scoop-type through-hull strainer.

3.2.2

Seacock

Mount the seacock to the hull, assemble it to the intake,


and ensure that it is accessible for operation. Figure 3-2
shows a typical installation.

1-789

1. Seawater pump
2. Seawater strainer
3. Seacock

3.2.4

Seawater Strainer

Water Lines

Water lines from the seacock to the engine-driven


seawater pump are usually constructed of flexible hose.
Connect a flexible section of hose to the seawater pump
to allow the generator set to vibrate during operation.
Support a nonflexible water line within 102 mm (4 in.) of
its connection to the flexible section.
Keep the seawater hose as straight and short as
possible. If the hose is too long, usually over 4.6 m
(15 ft.), water suction problems may occur. See
Section 7 for the inlet water line hose size and the
seawater connection to the seawater pump inlet. Avoid
running the inlet pipe above the generator. See
Figure 3-5 for the seawater hose connection to the
seawater pump inlet.

Avoid overcaulking the seacock. Excess caulk reduces


water flow and, in some cases, develops a barrier that
can force water upward, past the seawater pump, and
into the engine cylinders when the vessel is moving and
the generator set is shut down.

3.2.3

Seawater Strainer

Mount the seawater strainer to the seacock or


permanent structure at a point not higher than the
seawater pump. Ensure that the strainer is accessible
for service. See Figure 3-4 for a typical installation.
Some seawater strainers include a seacock and an
intake through-hull strainer.
1

Maximum seawater inlet pressure at the seawater pump


is 34.5 kPa (5 psi). Excessive pressure will cause water
ingestion.

14

Section 3 Cooling System

1. Seawater pump inlet

Figure 3-5

TP-5586-6

Seawater Inlet Connection (Located at


the Inlet to the Seawater Pump), Typical
TP-6711

7/09

3.2.5

Closed Heat Exchanger


(9--32EOZD/7--28EFOZD Models)

A closed heat exchanger is the best cooling method for


most applications. See Figure 3-6 or Figure 3-7 for a
typical installation. Provide space to access the
water-cooled exhaust manifold pressure cap.
2

4
6
8

5
7

14

Arrow Description
Direction of Flow

10

Seawater
Freshwater (Coolant/Antifreeze)

11

12

13
TP-5586-6

1.
2.
3.
4.
5.
6.
7.

Engine block
Exhaust manifold
Exhaust mixer elbow
Outlet flapper (exhaust/water discharge)
Silencer (customer supplied)
Thermostat open
Thermostat

Figure 3-6

TP-6711

7/09

8.
9.
10.
11.
12.
13.
14.

Thermostat closed
Heat exchanger
Engine-driven seawater pump
Seawater strainer
Seacock
Intake strainer
Engine-driven water pump

Typical Closed/Heat Exchanger Cooling System (9/10/28/32EOZD, and 7/8.5/9/25/28EFOZD Models)

Section 3 Cooling System

15

2
3
4

7
6

8
9
14

13

12

11

Seawater
Freshwater (Coolant/Antifreeze)

10
TP-5592-6

1.
2.
3.
4.
5.
6.
7.

Oil cooler
Engine block
Thermostat
Water-cooled manifold
Heat exchanger
Exhaust mixer elbow
Water-cooled turbocharger

Figure 3-7

16

8.
9.
10.
11.
12.
13.
14.

Silencer (customer-supplied)
Exhaust outlet
Intake strainer
Seacock
Seawater strainer
Engine-driven seawater pump
Engine-driven water pump

Typical Closed/Heat Exchanger Cooling System (13--24EOZD and 11--20EFOZD Models)

Section 3 Cooling System

TP-6711

7/09

Section 4 Exhaust System


WARNING

Carbon monoxide.
Can cause severe
fainting, or death.

nausea,

The exhaust system must be


leakproof and routinely inspected.
Carbon monoxide symptoms. Carbon monoxide can
cause severe nausea, fainting, or death. Carbon monoxide
is a poisonous gas present in exhaust gases. Carbon
monoxide is an odorless, colorless, tasteless, nonirritating gas
that can cause death if inhaled for even a short time. Carbon
monoxide poisoning symptoms include but are not limited to
the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide
poisoning is possible, seek fresh air immediately and remain
active. Do not sit, lie down, or fall asleep. Alert others to the
possibility of carbon monoxide poisoning. Seek medical
attention if the condition of affected persons does not improve
within minutes of breathing fresh air.
Inspecting the exhaust system. Carbon monoxide can
cause severe nausea, fainting, or death. For the safety of
the crafts occupants, install a carbon monoxide detector.
Never operate the generator set without a functioning carbon
monoxide detector. Inspect the detector before each
generator set use.

TP-6711

7/09

Operating the generator set. Carbon monoxide can cause


severe nausea, fainting, or death. Be especially careful if
operating the generator set when moored or anchored under
calm conditions because gases may accumulate. If operating
the generator set dockside, moor the craft so that the exhaust
discharges on the lee side (the side sheltered from the wind).
Always be aware of others, making sure your exhaust is
directed away from other boats and buildings.

Note: Do not use copper tubing in diesel exhaust


systems. Sulfur in diesel exhaust causes rapid
deterioration of copper tubing exhaust systems,
resulting in exhaust/water leakage.

4.1 Types
Kohlerr generator sets covered in this manual use
either wet or dry exhaust systems. Dry exhaust systems
are common in commercial applications. See the
engine manual for specifications.

4.2 Exhaust Lines


Use water-cooled exhaust lines in all marine
installations. Keep the lines as short and straight as
possible. NFPA 302 Fire Protection Standard for
Pleasure and Commercial Motor Craft, Clause 4-3,
recommends using two corrosion-resistant hose
clamps with a minimum width of 13 mm (1/2 in.) on each
end of the flexible exhaust hose connections.
Kohler Co. requires a downward pitch of at least 13 mm
per 30.5 cm (1/2 in. per running foot). Use a flexible
exhaust hose that conforms to UL Standard 1129 for the
engines wet exhaust components between the mixer
elbow and the exhaust outlet.

Section 4 Exhaust System

17

4.3 Exhaust System Location,


Mounting, and Installation
Note: Should any information regarding installation
conflict with USCG Regulations, follow USCG
Regulations.
Mount the silencer independently to eliminate stress on
the exhaust system and the exhaust manifold/mixer
elbow. See Section 7 for the mixer elbow water line hose
size. See Figure 4-1 for the exhaust connection to the
mixer elbow. Provide an adequate hose length from the
exhaust mixer to the silencer to allow for generator set
movement.

Locate the exhaust outlet at least 10 cm (4 in.) above the


waterline when the craft is loaded to maximum capacity.
Install an exhaust port with the flap at the exhaust
(transom) outlet to prevent water backup in following
seas or when moving astern (backward). A lift in the
exhaust piping before the piping exits the craft prevents
backwash. See Figure 4-3, item 1. Support the exhaust
lines to prevent the formation of water pockets.
Exhaust system installation guidelines for various
generator set locations follow.
Information and
illustrations of stern- (rear) exhaust installations also
apply to side-exhaust installations. Where exhaust lines
require passage through bulkheads, use port (left)- or
starboard (right)- side exhaust outlets, also in
applications in which long exhaust lines to the transom
(rear) could cause excessive back pressure. See
Figure 4-2 for allowable back pressures.

Model

1
1. Water/exhaust outlet

Figure 4-1

18

Allowable
Exhaust Back
Pressure,
kPa
(mm H2O)

14/15EOZD
11.5/13EFOZD

9.81 (1000)

9/23/24EOZD
7/20EFOZD

11.77 (1200)

10/13/20/28/32EOZD
8.5/9/11/17/17.5/25/28EFOZD

15.30 (1560)

Figure 4-2

Allowable Exhaust Back Pressures

TP-5586-6

Mixer Elbow/Exhaust Connection,


Typical

Section 4 Exhaust System

TP-6711

7/09

4.3.1

Above-Waterline Installation

Install a customer-supplied silencer with the silencers


outlet at a maximum of 3 m (10 horizontal ft.) from the
center of the engines exhaust outlet. See Figure 4-3.
Mount a typical silencer with the inlet and outlet
horizontal and with the drain plug down. Use an exhaust

hose pitch of at least 13 mm per 30.5 cm (0.5 in. per


running foot). Some silencers require two support
brackets or hanger straps for installation to stringers or
other suitable structure.
Follow the instructions
provided with the silencer.
Install any lift (see
Figure 4-3, item 1) in the exhaust line below the engine
exhaust manifold outlet.
4
5
6

2
1
7
8
18
13

16
Waterline
12

17

10
15

14
19

1. Slight lift improves silencing and prevents water backwash


into the silencer (keep below the level of the exhaust
manifold outlet)
2. Silencer (customer-supplied)
3. Exhaust manifold outlet
4. Exhaust mixer elbow
5. Heat exchanger (locations vary by model)
6. Coolant recovery tank (located on the unit on some models)
7. Locate the coolant recovery tank at the same height as the
heat exchanger
8. Maximum seawater pump lift of 1 m (3 ft.)
9. Seawater strainer
10. Seacock
11. Intake strainer
12. Engine-driven seawater pump
13. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in.
per ft.)
14. Maximum distance between silencer and exhaust mixer
elbow of 3 m (10 ft.)

Figure 4-3

TP-6711

7/09

11

TP-5856-4

15. Maximum distance between silencer and exhaust outlet of


1.5 m (5 ft.)
16. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in.
per ft.)
17. Minimum exhaust outlet distance above waterline of 10 cm
(4 in.). Note: Vessel fully loaded.
18. Maximum silencer vertical lift of 1.2 m (4 ft.)
19. If the total exhaust length exceeds 4.6 m (15 ft.), Kohler
recommends increasing the exhaust hose to the next
larger diameter. See Figure 4-2 and Figure 4-5.
Note:

Data applies to both rear- and side-exhaust installations.

Note:

Use two hose clamps on each end of all flexible exhaust


hose connections.

Note:

Read the text for complete explanation of dimensions


and other installation considerations.

Typical Above-Waterline Installation

Section 4 Exhaust System

19

4.3.2

Mid/Below-Waterline Installation

Follow USCG Regulations for installing an antisiphon


provision to prevent raw water entry into the engine.
Use the siphon break if the exhaust manifold outlet is
located less than 23 cm (9 in.) above the waterline when
the craft is loaded to maximum capacity. Install the
siphon break at least 31 cm (1 ft.) above the waterline
using the instructions provided with the siphon break kit.

Note: An improperly installed siphon break will cause


engine damage and may void the warranty.
Install the siphon break above the highest point in the
exhaust line between the heat exchanger and the
exhaust mixer. See Figure 4-4 for the siphon break
connection. Support the siphon break and hoses to
maintain their position and function. Allow a slight offset
to clear the stringers or other permanent structures.
Protect the siphon break air inlet from dirt and debris.
Note: To prevent water leakage on the generator set, do
not mount the siphon break directly over the
generator set.
Note: Ensure that the siphon breaks cap is tight before
operating the generator set.

Models without Sound Shield


9/10EOZD
7/9EFOZD

1
1. Heat exchanger
2. Exhaust mixer
3. Cut hose and connect siphon break and hardware

Figure 4-4

Mount a typical silencers base no more than 1.2 m (4 ft.)


below the highest point in the exhaust line. Attach a
separate wood mounting base to the hull stringers or
other suitable structures.
Use the silencer
manufacturers recommendation for securing the
silencer to the hull. Mount the silencer with the outlet not
more than 3 m (10 horizontal ft.) from the engines
exhaust manifold outlet. Use a USCG-type certified
marine exhaust hose.

Models with Sound Shield


9/10EOZD
7/9EFOZD

13/14/15/20/23/24/28/32EOZD
13/14/15/20/23/24/28/32EOZD
11/11.5/13/17/17.5/20/25/28EFOZD 11/11.5/13/17/17.5/20/25/28EFOZD

Figure 4-5

20

Siphon Break Connection, Typical

Exhaust Hose
Diameter
mm (in.)
51 (2.0)
76 (3.0)

Exhaust Hose Sizes

Section 4 Exhaust System

TP-6711

7/09

Note: Read the text for complete explanation of


dimensions and other installation
considerations.

Note: Use two hose clamps on each end of all


flexible exhaust hose connections.

2
3

Note: Data applies to both rear- and side-exhaust


installations.
Note: Damage caused by water ingestion will not
be covered by the generator warranty.

24

7
25

23

10
6
4

20

11
Waterline

26
22

16

19

12
15

21
13

18
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.

Cap
Reed valve
Mounting base
Maximum silencer vertical lift of 1.2 m (4 ft.)
Exhaust mixer elbow distance above waterline; if less than
23 cm (9 in.), a siphon break is required
Minimum siphon break distance above waterline of 30.5 cm
(1 ft.)
Siphon break
Exhaust mixer elbow
Heat exchanger (locations vary by model)
Coolant recovery tank (located on the unit on some models)
Indicates the coolant recovery tank is at the same height as the
heat exchanger
Seawater strainer
Seacock
Intake strainer
Engine-driven seawater pump
Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.)

Figure 4-6
TP-6711

7/09

17

14

17. Maximum distance between silencer and exhaust mixer elbow


of 3 m (10 ft.)
18. Maximum distance between silencer and exhaust outlet of
1.5 m (5 ft.)
19. Silencer (customer-supplied)
20. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm
(0.5 in. per ft.)
21. Maximum distance between exhaust outlet and generator of
4.6 m (15 ft.)
22. Minimum exhaust outlet distance above waterline of 10 cm
(4 in.)
23. Exhaust hose
24. Gas/water separator (optional). Install directly above the
canister muffler.
25. Distance above waterline for drain outlet from silencer must be
equal to or greater than water drain (item 18) to be greater
than 30.5 cm (1 ft.)
26. Water drain distance below waterline

Typical Mid- and Below-Waterline Installation with Optional Gas/Water Separator


Section 4 Exhaust System

21

1
2

8
9
10

22

Waterline

11

20

21

16

12

19

15
13

17

18

14

TP-5856-4

23
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.

Cap
Reed valve
Mounting base
Maximum silencer vertical lift of 1.2 m (4 ft.)
Exhaust mixer elbow distance above waterline; if less than
23 cm (9 in.), a siphon break is required
Minimum siphon break distance above waterline of 30.5 cm
(1 ft.)
Siphon break
Exhaust mixer elbow
Heat exchanger (locations vary by model)
Coolant recovery tank (located on the unit on some models)
Indicates the coolant recovery tank is at the same height as the
heat exchanger
Seawater strainer
Seacock
Intake strainer
Engine-driven seawater pump
Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.)

Figure 4-7

22

17. Maximum distance between silencer and exhaust mixer elbow


of 3 m (10 ft.)
18. Maximum distance between silencer and exhaust outlet of
1.5 m (5 ft.)
19. Silencer (customer-supplied)
20. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm
(0.5 in. per ft.)
21. Minimum exhaust outlet distance above waterline of 10 cm
(4 in.)
22. Exhaust hose (see Figure 4-5 for hose sizes)
23. If the total exhaust length exceeds 4.6 m (15 ft.), Kohler
recommends increasing the exhaust hose to the next larger
diameter. See Figure 4-2 and Figure 4-5.
Note: Read the text for complete explanation of dimensions and
other installation considerations.
Note:

Use two hose clamps on each end of all flexible exhaust


hose connections.

Note:

Data applies to both rear- and side-exhaust installations.

Typical Mid- and Below-Waterline Installation

Section 4 Exhaust System

TP-6711

7/09

Note:

Read the text for complete explanation of


dimensions and other installation considerations.

Note:

Use two hose clamps on each end of all flexible


exhaust hose connections.

Note:

Data applies to both rear- and side-exhaust


installations.

Note:

Damage caused by water ingestion will not be


covered by the generator warranty.

1
2
3

7
9
10

8
19

11
25
24

15
5
16

16

26

4
22

20

16

23

18

12

17
27

13

21
14
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.

Cap
Reed valve
Mounting base
Maximum silencer internal vertical lift of 1.2 m (4 ft.)
Exhaust mixer elbow distance above waterline; if less than
23 cm (9 in.), a siphon break is required
Minimum siphon break distance above waterline of 30.5 cm
(1 ft.)
Siphon break
Exhaust mixer
Heat exchanger
Coolant recovery bottle
Indicates the coolant recovery tank is at the same height as
the heat exchanger
Seawater strainer
Seacock
Intake strainer
Engine-driven seawater pump
Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in.
per ft.)

Figure 4-8

TP-6711

7/09

17. Maximum distance between silencer and exhaust mixer


elbow of 3 m (10 ft.)
18. Water drain distance below waterline
19. Combination silencer that contains lift muffler and gas water
separating sections in single component (customer-supplied)
20. Distance above waterline for drain outlet from silencer must
be equal to or greater than water drain (item 18) to be greater
than 30.5 cm (1 ft.)
21. Exhaust outlet to be diameter appropriate so exhaust back
pressure does not exceed limit at engine exhaust manifold
22. Minimum exhaust outlet distance above waterline of 10 cm
(4 in.)
23. Exhaust hose
24. Height of internal lift tube to be below generator exhaust
manifold
25. Kohler recommends generator be located at elevation that
exhaust mixer elbow is above silencer exhaust outlet
26. Seawater pump lift
27. Waterline

Exhaust System with Combination Silencer/Gas Water Separator

Section 4 Exhaust System

23

Notes

24

Section 4 Exhaust System

TP-6711

7/09

Section 5 Fuel System


2

WARNING
1

Explosive fuel vapors.


Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.

Note: Do not modify the tank or the propulsion engine


fuel system. Equip the craft with a tank that
allows one of the two pickup arrangements.
Note: Fuel system installations must conform to USCG
Regulations.
Note: Use pipe sealant on all threaded fittings to
prevent fuel leakage. Use pipe sealant that
resists gasoline, grease, lubrication oil, common
bilge solvents, salt deposits, and water.

1-788

1. Fuel line to propulsion engine


2. Fuel line to generator set

Figure 5-1

Multiple Dip Tube Arrangement


m:is:102:001

5.1 Fuel Tank


Most marine generator sets draw fuel from the same fuel
tank as the crafts propulsion engine(s). If the tanks fuel
pickup opening allows a multiple dip tube, use a multiple
dip tube arrangement. See Figure 5-1. The multiple dip
tube arrangement incorporates a shorter dip tube for the
generator set and a longer dip tube for the propulsion
engine. With this arrangement, the generator set runs
out of fuel before the propulsion engine during a low fuel
supply situation. Equip the fuel system with a fuel/water
separator to remove any accumulated dirt and water.

TP-6711

7/09

Section 5 Fuel System

25

5.2 Fuel Lines

5.3 Fuel Filters

Return the generator set fuel return line to the fuel tank.
Locate the fuel return line as far as practical from the fuel
pickup to allow the tank fuel to cool the return fuel before
delivery back to the fuel injectors. Incoming fuel cools
the injectors to achieve maximum engine efficiency.

Conform to USCG Regulations regarding inline fuel


filters or strainers.

Note: Do not tee into the main propulsion engines fuel


line.

For 9--32EOZD and 7--28EFOZD models, install a


fuel/water separator between the fuel tank and the
electric fuel pump. The fuel/water separator must
contain a primary filter of 30--50 micron filtration
capability, sized for at least 15 gph to allow for the return
fuel flow.

Note: Fuel
Return
Dip
Tube
(9--32EOZD/
7--28EFOZD Models). Kohler Co. recommends
utilizing a fuel return dip tube located below the
fuel supply dip tube. This will prevent air from
entering the return lines, draining the fuel
injection pump, and thus causing starting failure
or hard starting of the generator set. The dip tube
depth should be at least as deep as the main
engine fuel pick-up dip tube.
Under no circumstances should the propulsion engine
and generator set share pickup or return lines (through a
tee arrangement) that would allow the larger engine to
starve fuel from the smaller engine. It is possible that the
operation of either engine could completely drain the
fuel line of the other engine and make starting difficult.
Use a flexible hose section to connect the metallic line
from the fuel tank to the engines fuel pump inlet
connection point. Also, use a flexible hose section to
connect the metallic line from the fuel tank to the fuel
return connection point. The flexible section allows the
generator set to vibrate during operation.

Model
9--32EOZD and 7--28EFOZD

Figure 5-2

5.4 Fuel/Water Separator

5.5 Fuel Pump Lift


See Figure 5-3 for fuel pump lift capabilities.

Model
9--32EOZD
7--28EFOZD

Figure 5-3

Fuel Pump Lift


m (ft.)
1.2 (4)

Fuel Pump Lift

5.6 Fuel Consumption


Consult the current generator set specification sheets
for generator set fuel consumption rates.

Fuel Line
ID Size
mm (in.)
9.7 (3/8)

Fuel Line ID Size (Max.)

See Figure 5-2 for the ID size of the customer-supplied


fuel line that connects to the fuel pump and fuel return.
Route the fuel lines from the fuel tank in a gradual incline
to the enginedo not exceed the height of the generator
set and do not route fuel lines above the generator set.
Comply with USCG Regulation 46CFR182.20
regarding fuel lines and supports.
See Section 7 for fuel feed pump inlet connection and
fuel return line connection.

26

Section 5 Fuel System

TP-6711

7/09

Section 6 Electrical System


WARNING

1
2

Hazardous voltage. Moving parts.


Can cause severe injury or death.

Operate the generator set only when


all guards and electrical enclosures
are in place.
Electrical backfeed to the utility. Hazardous backfeed
voltage can cause severe injury or death. Connect the
generator set to the building/marina electrical system only
through an approved device and after the building/marina
main switch is turned off. Backfeed connections can cause
severe injury or death to utility personnel working on power
lines and/or personnel near the work area. Some states and
localities prohibit unauthorized connection to the utility
electrical system. Install a ship-to-shore transfer switch to
prevent interconnection of the generator set power and shore
power.

5
4
585771
1. Line side connections from generator
2. AC circuit breaker
3. L1/L2 phase (black) leads.
Load side customer
connection points.
4. L0 neutral (white) lead
5. GRD ground (green) lead

Figure 6-1

AC Voltage Connections in Junction Box

6.1 AC Voltage Connections

9--24EOZD Models

Make AC connections to the generator set inside the


junction box. Typically, the generator set connects to a
ship-to-shore transfer switch that allows the use of
shore/utility power when docked or generator set power
when docked or at sea. The wiring then connects to a
main circuit breaker box (panel board) that distributes
branch circuits throughout the craft. See Figure 6-1 for
AC voltage connections to the generator set. See
Section 8 for reconnection of the generator set.
1, 2
Top View
(Shown with junction box cover removed)
28/32EOZD Models

1. Neutral (L0) connection


2. Ground (GRD) connection

Figure 6-2

TP-6711

7/09

Neutral and Ground Connections


(9--32EOZD Models Shown)

Section 6 Electrical System

27

6.2 Circuit Protection


The AC circuit breakers (optional) protect the wiring
from the AC circuit breakers to the vessels distribution
panel. AC circuit breakers trip when they detect a fault in
the output circuit.

Amps Voltage
18
480
480

10EOZD (3 ph.)

600

240

7EFOZD

240

7EFOZD

480

10EOZD (3 ph.)

40

600

11.5EFOZD, 17.5EFOZD,
20EFOZD (3 ph.), 25EFOZD (3 ph.),
24EOZD

42

240

35

240
50

Circuit Breaker Considerations

Mounting location. Mount the circuit breakers in the


generator sets junction box. See Section 6.2.2.
Sizing. Use the generator set voltage/frequency
configuration to determine the circuit breaker
amperage. If the generator set voltage configuration
changes, change the circuit breaker to provide optimum
protection.
For circuit breaker application and selection
information, contact an authorized distributor/dealer.

9EFOZD

9EOZD, 9EFOZD, 10EOZD

11EFOZD
11EFOZD

480

11.5EFOZD, 14EOZD

600

25EFOZD (3 ph.), 28EFOZD (3 ph.),


28EOZD (3 ph.), 32EOZD (3 ph.)

13EFOZD

11.5EFOZD, 13EOZD, 13EFOZD

600

17.5EFOZD, 20EOZD (3 ph.),


28EFOZD (3 ph.)

240

14EOZD, 15EOZD

17.5EFOZD, 20EOZD (3 ph.),


20EFOZD (3 ph.)

9EOZD, 17EFOZD, 17.5EFOZD

60

70

240

600
240

17EFOZD

480

20EFOZD (3 ph.), 25EFOZD (3 ph.),


24EOZD

240

10EOZD

20EFOZD (1 & 3 ph.)

20EOZD (1 & 3 ph.),


20EFOZD (1 ph.)

480

25EFOZD (3 ph.), 24EOZD,


28EFOZD (3 ph.), 28EOZD (3 ph.)

240

23EOZD, 24EOZD,
25EFOZD (1 & 3 ph.)

480

28EFOZD (3 ph.), 28EOZD (3 ph.),


32EOZD (3 ph.)

80

85

Have a qualified electrician or technician install circuit


breakers and reconnect the generator set. Comply with
all governing standards and codes.

240
90

100
2

28EFOZD (1 & 3 ph.)

32EOZD (3 ph.), 28EFOZD ( 3 ph.)

28EFOZD (1 & 3 ph.),


28EOZD (1 & 3 ph.)

28EFOZD (3 ph.),
32EOZD (3 ph.)

240

32EOZD (1 & 3 ph.)

600

32EOZD (1 & 3 ph.)

240
125
600

150

Figure 6-3

28

Section 6 Electrical System

Model(s)
8.5EFOZD, 10EOZD (3 ph.)
11.5EFOZD, 14EOZD,
17.5EFOZD, 20EOZD (3 ph.)

Note: Circuit breaker ampere rating and availability are


subject to change.

6.2.1

3
3

30
33

After correcting the fault, reset the AC circuit breaker(s)


by placing them in the ON position. Restart the unit. Do
not start the unit under load. See Figure 6-3 for AC
circuit breaker ratings. The units voltage configuration
determines the circuit breaker selection.

Number
of Poles

AC Circuit Breaker Ratings, Listed By


Amps

TP-6711

7/09

WARNING

Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.

WARNING

Hazardous voltage. Moving parts.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.

Short circuits. Hazardous voltage/current can cause


severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Electrical backfeed to the utility. Hazardous backfeed
voltage can cause severe injury or death. Connect the
generator set to the building/marina electrical system only
through an approved device and after the building/marina
main switch is turned off. Backfeed connections can cause
severe injury or death to utility personnel working on power
lines and/or personnel near the work area. Some states and
localities prohibit unauthorized connection to the utility
electrical system. Install a ship-to-shore transfer switch to
prevent interconnection of the generator set power and shore
power.

6.2.2

Circuit Breaker Installation

1. Place the generator set master switch in the OFF


position.
2. Disconnect the generator set engine starting
battery, negative (--) lead first.
3. Remove the screws and remove the access cover.
4. Remove the screws and nuts to remove the circuit
breaker cover plate. Save the mounting hardware.
5. Install the circuit breaker from the inside of the
cutout panel and mount it using existing screws
removed in step 4. Position the circuit breaker with
the ON in the normal upright position or to the left
side. Cover the cutout opening, if applicable, with
the circuit breaker cover plate. Use existing screws
to mount the cover plate. See Figure 6-4.
6. See Section 8 for voltage reconnection.

Grounding electrical equipment. Hazardous voltage can


cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.

Note: Kohlerr marine diesel generator sets are


fully frequency adjustable and voltage
reconnectable. To determine reconnection
options, check the models specification
sheet.
7. Install insulation boots over stator lead terminals if
the kit includes insulation boots.
Note: See Section 8 for wiring instructions.

TP-6711

7/09

Section 6 Electrical System

29

8. Make the recommended connections for the


following four reconnection systems using circuit
breakers:
Two-pole circuit breaker with a single-voltage
system (example: 120-volt, 3-wire). Attach
stator leads marked 2 and 4 to the side of the circuit
breaker marked LINE. Install the jumper lead
across the LINE side of circuit breaker terminals
(see Section 8). Attach stator leads 1 and 3 to L0.
Single-pole circuit breaker with a 120-volt,
2-wire, single-voltage system. Attach stator
leads marked 2 and 4 to the side of the circuit
breaker marked LINE (see Section 8). Attach stator
leads 1 and 3 to L0.
Two-pole circuit breaker with a dual-voltage
system (example: 120/240-volt, 3-wire). Attach
stator leads marked 1 and 4 to the side of the circuit
breaker marked LINE. Do not use a jumper lead
(see Section 8). Attach stator leads 2 and 3 to L0.
EOZD/EFOZD Models (with ADC 2100):
Single-pole circuit breaker with a 240-volt,
2-wire, single-voltage system. Attach the stator
lead marked 1 to the side of the circuit breaker
marked LINE (see Section 8). Bolt together leads
2 and 3 and tape to insulate from ground. Attach
the stator lead marked 4 to L0.
9. Connect the stator lead(s) used for neutral
connection to the L0 stud. See the illustrations in
Section 8.
10. Connect the side of the circuit breaker marked
LOAD to the ship-to-shore switch or craft wiring.
Attach insulation boots to the black leads if the kit
includes insulation boots. With a single-pole circuit
breaker use one black lead (L1). With a two-pole
circuit breaker use two black leads, L1 and L2.
Connect the neutral (white) lead to the L0 stud.
Connect the equipment ground (green) lead to
GRD stud.

30

Section 6 Electrical System

Note: Wire material. Use stranded copper for all


wiring. Use wire gauges and insulation,
conductor temperature ratings, sheath
stripping, conductor support and protection,
conductor terminals and splices, and
overcurrent protection (circuit breakers,
fuses) that conform to standards and codes.
Note: Follow USCG Regulations CFR33, Part 183
(Pleasurecraft) and CFR46 (Commercial
Craft) for marine applications.
Note: Wire protection. Use plastic bushings,
rubber grommets, and/or cable ties as
necessary to protect and secure wiring from
sharp objects, the exhaust system, and any
moving parts.
11. Replace the controller cover or circuit breaker box
access panel.
12. Reconnect the generator set engine starting
battery, negative (--) lead last.
13. Make voltage or frequency adjustments according
to Section 8.
Note: Voltage/frequency adjustable.
Some
four-lead
generator
sets
are
not
voltage/frequency adjustable. To determine
adjustment possibilities, check the models
specification sheet or service manual. If you
are reconnecting the generator set from a
single-voltage
to
a
dual-voltage
configuration (example: from 120-volt to
120/240-volt) or a dual voltage to a single
voltage (example: from 120/240-volt to
120-volt) with the same primary voltage, do
not
adjust
the
voltage/frequency
adjustment. Adjust the voltage/frequency
for frequency changes or setting changes of
the primary voltage (example: from 120-volt
to 100-volt).
Refer to the models
specification sheet for reconnection
capability.

TP-6711

7/09

5
5

1
3
1

5
5

GM30331-

1. Circuit breaker
2. Circuit breaker plate
3. Circuit breaker mounting hardware

Figure 6-4

4. Cover plate
5. Use existing hardware
6. Screw (qty. 2) and nut (qty. 2)

Circuit Breaker Mounting (9--32EOZD and 7--28EFOZD Models)

6.3 Installation In Steel or


Aluminum Vessels
Installation of a generator set in a vessel constructed of
a material capable of conducting current (e.g., steel or
aluminum) is subject to considerations not normally
encountered in fiberglass or wood vessels. These
differences include equipment grounding, grounding of
neutral conductors, ground-fault protection, and
isolation of galvanic currents.
Note: Isolated ground kits are available as options for
steel- or aluminum-hulled vessels. Consult your
local dealer/distributor for more information.
The scope of these topics is too extensive to be fully
discussed here. Consult your local marine authority for
more information.
Before installing the generator set, check the available
wiring diagrams in the operation manual to become
familiar with the electrical system.

6.4 Installation Regulations


The U.S. Coast Guard governs generator set
installation in U.S. pleasurecraft and commercial
vessels. Refer to the applicable regulations below:

U.S. Pleasurecraft Installation


Regulations
Title 33CFR, Chapter I, U.S. Coast Guard, Part 183
1. Subpart IElectrical Equipment
2. Subpart JFuel Systems

U.S. Commercial Vessel Installation


Regulations
Title 46CFR, Chapter I, U.S. Coast Guard
1. Part 111Electrical Systems
2. Part 182Machinery Installation
m:sc:001:001

TP-6711

7/09

Section 6 Electrical System

31

6.5 Battery
Batteries and their installation must conform to USCG
Regulations 183.420 (a) through (g). Provide generator
sets with batteries separate from the propulsion
engines whenever possible. The starting/charging
systems of both the generator set and the engine must
have a common negative (--) ground.
USCG Regulation 183.415, Grounding, requires
connection of a common conductor to each grounded
cranking-motor circuit. Size the conductor to match the
larger of the engines two battery cables. Figure 6-5 lists
recommended minimum cable sizes for generator set
battery connections at various generator set-to-battery
distances. Connecting a common conductor to each
grounded cranking motor circuit prevents the starting
motor current from using alternative electrical paths
should the cranking motor ground circuit be restricted or
open because of oxidation or loose hardware.
Alternative electrical paths include metallic fuel lines
that can pose a hazard. See Section 7 for locations of
the battery connections to the generator set.
Required Battery Cable
(Minimum)
Distance (from battery to
generator set)

2.5 m (8.3 ft.) 5 m (16.4 ft.)

Battery Voltage

12V

24V

12V

24V

9EOZD/7EFOZD

#2

--------

#1

--------

10--24EOZD/8.5--20EFOZD

#2

#4

# 1/0

#2

28--32EOZD/25--28EFOZD

#2

#4

# 1/0

#2

Figure 6-5

32

Kohler Co. recommends using one 12-volt battery (or


two for 24-volt systems, as the spec requires) to start the
generator. See Figure 6-6 for minimum cold cranking
amps (CCA) recommendations.
12-Volt Starting Battery Size CCA
at --18C (0F) or 100 Amp. Hr.
Models

CCA

9--15EOZD, and 7--13EFOZD

500

20/23/24EOZD, and
17/17.5/20EFOZD

650

28/32EOZD and 25/28EFOZD

800

Figure 6-6

Battery Recommendations

6.6 Wiring
Use only stranded copper wire. Conform to USCG
Regulations 183.425 through 183.460 for wire gauges
and insulation, conductor temperature ratings, sheath
stripping, conductor support and protection, conductor
terminals and splices, and over-current protection
(circuit breakers, fuses). Use rubber grommets and
cable ties as necessary to protect and secure the wire
from sharp objects, the exhaust system, and moving
parts.

Battery Cable Sizing Recommendations

Section 6 Electrical System

TP-6711

7/09

6.7 Remote Connection

Component

Kohler Co. offers several remote panels for connection


to the generator set. Contact your local Kohlerr
distributor/dealer for detailed descriptions.
See
Figure 6-7 for the location of the remote start panel
connection to the generator set controller. Kohler Co.
also offers wiring harnesses in various lengths with a
connector keyed to the controller box connector. A
pigtail harness is also offered which includes the
appropriate connector on one end and has pigtails that
the installer can use to connect to a customer-supplied
start/stop switch or separate lights and hourmeter.
Consult wiring diagrams, ADVs, and instruction sheets
for connection information/details.
9--32EOZD and 7--28EFOZD Models. These models
use a 12-pin connector for the remote interface
connection. See Figure 6-7 for the connectors location.
See Figure 6-8 for the correct customer-supplied plug
and pin part numbers.

Amp Part No.

Kohler Part No.

Plug

350735-1

229998

Pin

350218-6

241618

Cable Seal

794280-1

GM29252

Interface Seal

794279-1

GM29507

Cavity Plug

770377-1

GM28769

Figure 6-8

Connector Components (EOZD/EFOZD


Models)

Note: Gauge senders. Gauge senders are available


for most generator sets. If using customersupplied gauges, be sure they are compatible
with generator set senders.
Contact an
authorized Kohlerr service distributor/dealer.
Gauges and senders are available as service
items from an authorized Kohlerr service
distributor/dealer.

ADV6843b-a

1. Remote interface connector

Figure 6-7

TP-6711

7/09

Remote Interface Connector,


EOZD/EFOZD Models, Typical (Shown
on Sound-Shielded Units)

Section 6 Electrical System

33

Notes

34

Section 6 Electrical System

TP-6711

7/09

Section 7 Installation Drawings


Use the drawings in this section for installation
purposes. Consult the supplier and verify that the
drawings are the most current for your specifications.
Installation drawings show exhaust outlet locations, fuel
inlet and return connections, siphon break locations,
and battery connections. See Figure 7-1 for installation
drawing identification.

Model No.
9EOZD and 7EFOZD
with sound shield

Drawing
ADV-7385AADV-7385B-

Page
36
37

with keel cooling


10EOZD and 8.5/9EFOZD
with sound shield
with keel cooling
13/14/15EOZD and
11/11.5/13EFOZD

ADV-7385CADV-7384AADV-7384BADV-7384C-

38
39
40
41

ADV-7383A-

42

with sound shield


with keel cooling
20/23/24EOZD and
17/17.5/20EFOZD

ADV-7383BADV-7383C-

43
44

ADV-7382A-B
ADV-7382B-B

45
46

ADV-7382C-B

47

ADV-7382D-B

48

ADV-7381A-A
ADV-7381B-A
ADV-7381C-A
ADV-7381D-A

49
50
51
52

with sound shield


with keel cooling for models
20EOZD and 17/17.5EFOZD
with keel cooling for models
23/24EOZD and 20EFOZD
28/32EOZD and 25/28EFOZD
with sound shield
with keel cooling
with electric clutch

Figure 7-1

TP-6711

7/09

Installation Drawings

Section 7 Installation Drawings

35

NOTE: Dimensions are shown in mm [in.].

Figure 7-2
36

ADV-7385A-

Dimension Drawing, 9EOZD and 7EFOZD

Section 7 Installation Drawings

TP-6711

7/09

NOTE: Dimensions are shown in mm [in.].

Figure 7-3
TP-6711

7/09

ADV-7385B-

Dimension Drawing, 9EOZD and 7EFOZD with Sound Shield


Section 7 Installation Drawings

37

NOTE: Dimensions are shown in mm [in.].

Figure 7-4
38

ADV-7385C-

Dimension Drawing, 9EOZD and 7EFOZD with Keel Cooling

Section 7 Installation Drawings

TP-6711

7/09

NOTE: Dimensions are shown in mm [in.].

Figure 7-5
TP-6711

7/09

ADV-7384A-

Dimension Drawing, 10EOZD and 8.5/9EFOZD


Section 7 Installation Drawings

39

NOTE: Dimensions are shown in mm [in.].

Figure 7-6
40

ADV-7384B-

Dimension Drawing, 10EOZD and 8.5/9EFOZD with Sound Shield

Section 7 Installation Drawings

TP-6711

7/09

NOTE: Dimensions are shown in mm [in.].

Figure 7-7
TP-6711

7/09

ADV-7384C-

Dimension Drawing, 10EOZD and 8.5/9EFOZD with Keel Cooling


Section 7 Installation Drawings

41

NOTE: Dimensions are shown in mm [in.].

Figure 7-8
42

ADV-7383A-

Dimension Drawing, 13/14/15EOZD and 11/11.5/13EFOZD

Section 7 Installation Drawings

TP-6711

7/09

NOTE: Dimensions are shown in mm [in.].

Figure 7-9
TP-6711

7/09

ADV-7383B-

Dimension Drawing, 13/14/15EOZD and 11/11.5/13EFOZD with Sound Shield


Section 7 Installation Drawings

43

NOTE: Dimensions are shown in mm [in.].

ADV-7383C-

Figure 7-10 Dimension Drawing, 13/14/15EOZD and 11/11.5/13EFOZD with Keel Cooling
44

Section 7 Installation Drawings

TP-6711

7/09

NOTE: Dimensions are shown in mm [in.].

ADV-7382A-B

Figure 7-11 Dimension Drawing, 20/23/24EOZD and 17/17.5/20EFOZD


TP-6711

7/09

Section 7 Installation Drawings

45

NOTE: Dimensions are shown in mm [in.].

ADV-7382B-B

Figure 7-12 Dimension Drawing, 20/23/24EOZD and 17/17.5/20EFOZD with Sound Shield
46

Section 7 Installation Drawings

TP-6711

7/09

NOTE: Dimensions are shown in mm [in.].

ADV-7382C-B

Figure 7-13 Dimension Drawing, 20EOZD and 17/17.5EFOZD with Keel Cooling
TP-6711

7/09

Section 7 Installation Drawings

47

NOTE: Dimensions are shown in mm [in.].

ADV-7382D-B

Figure 7-14 Dimension Drawing, 23/24EOZD and 20EFOZD with Keel Cooling
48

Section 7 Installation Drawings

TP-6711

7/09

NOTE: Dimensions are shown in mm [in.].

ADV-7381A-A

Figure 7-15 Dimension Drawing, 28/32EOZD and 25/28EFOZD


TP-6711

7/09

Section 7 Installation Drawings

49

NOTE: Dimensions are shown in mm [in.].

ADV-7381B-A

Figure 7-16 Dimension Drawing, 28/32EOZD and 25/28EFOZD with Sound Shield
50

Section 7 Installation Drawings

TP-6711

7/09

NOTE: Dimensions are shown in mm [in.].

ADV-7381C-A

Figure 7-17 Dimension Drawing, 28/32EOZD and 25/28EFOZD with Keel Cooling
TP-6711

7/09

Section 7 Installation Drawings

51

NOTE: Dimensions are shown in mm [in.].

ADV-7381D-A

Figure 7-18 Dimension Drawing, 28/32EOZD and 25/28EFOZD with Electric Clutch
52

Section 7 Installation Drawings

TP-6711

7/09

Section 8 Reconnection/Adjustments
WARNING

Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.

TP-6711

7/09

WARNING

Hazardous voltage. Moving parts.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.

Section 8 Reconnection/Adjustments

53

8.1 Four-Lead Reconnection


The following information illustrates the reconnection of
four-lead generator sets. In all cases, conform to the
National Electrical Code (NEC).
NOTICE
Voltage reconnection. Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.

8.1.1

100--120-Volt Configurations

8.1.2

100--120/200--240-Volt
Configurations

The 100--120/200--240-volt configuration does not use


a jumper lead. If the unit was originally wired for straight
100--120 volt, 3-wire, remove the jumper lead (see
Figure 8-1 for location). Select a two-pole circuit
breaker. Application of two single-pole circuit breakers
does not conform to NEC requirements for supplying a
200--240-volt load, even if the breakers are
mechanically attached together. Leads L1 and L2 are
for different phases; never connect them together.

If the installation requires a factory two-pole circuit


breaker, do not connect the load-side terminals of the
circuit breaker together; see Figure 8-1.
If the
installation requires a 100--120-volt, 2-wire system, use
a single-pole circuit breaker. See Figure 8-2. When
connecting stator phase leads together, size the output
lead (L1) to handle the amperage. Use a jumper lead on
the line side of the circuit breaker to balance the load of
the generator set.

L0 (Neutral)
Ground
Load
Side
Line
Side

L0 (Neutral)
Ground
Load
Side

Line
Side

L0
GRD.
L1
Single-Pole
Circuit
Breaker

L0
GRD.
4

L1
L2
Two-Pole
Circuit
Breaker

Stator Leads
60 Hz
L0--L1
L0--L2

Figure 8-2

50 Hz

100--120 Volt
100--120 Volt

100--120 Volt
100--120 Volt

100--120-Volt, 2-Wire Configuration


L0 (Neutral)

Figure 8-1

GRD.

Ground

Jumper
lead
4

L0

L1
L2

Load
Side

Factory
Two-Pole
Circuit
Breaker

100--120-Volt, 3-Wire Configuration


Line
Side

100--120/200--240-Volt,
3-Wire

Stator Leads
60 Hz
L0--L1
L0--L2
L1--L2

Figure 8-3

54

Section 8 Reconnection/Adjustments

100--120 Volt
100--120 Volt
200--240 Volt

50 Hz
100--120 Volt
100--120 Volt
200--240 Volt

100--120/200--240-Volt, 3-Wire
Configuration

TP-6711

7/09

8.1.3

200--240-Volt Configurations

The 200--240-volt configuration does not use a jumper


lead. If the unit was originally wired for straight 100--120
volt, 3-wire, remove the jumper lead (see Figure 8-1 for
location). See Figure 8-4 for EOZD/EFOZD models
equipped with the ADC 2100.
L0 (Neutral)

L0
GRD.

Ground

L1

Load
Side
Line
Side

Single-Pole
Circuit
Breaker
Tape to insulate
from ground

Stator Leads
60 Hz
L0--L1

Figure 8-4

TP-6711

7/09

200--220--240 Volt
2 Wire
50 Hz

200-240 Volt 200--220--240 Volt

200--220--240-Volt, 2-Wire Configuration


for EOZD/EFOZD Models with
ADC 2100

Section 8 Reconnection/Adjustments

55

Electroswitch
2-Wire Generator Sets

3-Wire Generator Sets

L1
To Generator
Set

L1
2

To Shore
Power

L2

L2
6

To Generator
Set

11

12

To Shore
Power

L0
10

To Load
To Load

Kraus Naimler/American Solenoid


(Early Rectangular Design)

2-Wire Generator Sets

3-Wire Generator Sets


L1

L1
To Generator
Set

5 To Shore
Power

10

14

L2

L2
8

To Generator
Set

To Shore
Power

L0
13

To Load
To Load

Kraus Naimler/American Solenoid


(Newer Round Design)

2-Wire Generator Sets

3-Wire Generator Sets


L1

L1
To Generator
Set
L2

To Shore
Power

11

10

L2
8

To Generator
Set

To Shore
Power

L0
12

To Load
To Load
TP-5399-5

Figure 8-5

56

Marine Manual (Ship-to-Shore) Transfer Switch

Section 8 Reconnection/Adjustments

TP-6711

7/09

The following information illustrates the reconnection of


twelve-lead generator sets. In all cases, conform to the
National Electrical Code (NEC).

Kraus Naimler/American Solenoid


4-Wire, 3-Phase Generator Sets

L1

L1
3

To Generator 7
Set

L2

L3

L2
To Shore
Power

Reconnect the stator leads of the generator set to


change output phase or voltage. Refer to the following
procedure and connection schematics. Follow all safety
precautions at the front of this manual and in the text
during the reconnection procedure.
NOTICE

L3
11

10

12

Voltage reconnection. Affix a notice to the generator set after


reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.

9
L0

L0
15

14

16

13

Twelve-Lead Reconnection Procedure


L1 L2

L3

L0

To Load

Figure 8-6

I-940

Marine Manual (Ship-to-Shore) Transfer


Switch, continued

8.2 Twelve-Lead Reconnection


The
reconnection
procedure
details
voltage
reconnections only. If the generator set requires
frequency changes, adjust the governor and voltage
regulator. See the generator set service manual for
information regarding frequency adjustment.

1. Place the generator master switch in the OFF


position.
2. Disconnect generator set engine starting battery,
negative (--) lead first.
3. Disconnect power to battery charger, if equipped.
4. Use Figure 8-7 to determine the generator set
voltage configuration. Note the original voltage
and reconnect the generator set as needed.

115/230

115/230

230
EM-250000

Note:

Current Transformers (CTs) are not used on all sets. CT dot or HI toward generator.

Figure 8-7

TP-6711

7/09

Generator Reconnection

Section 8 Reconnection/Adjustments

57

8.3 ADC 2100 Adjustment after


Reconnection

8.3.3

The controller is factory-set for the generator set voltage


and frequency. If the generator set is reconnected to a
different voltage and frequency, follow the procedures in
this section to reconfigure the controller to the new
voltage and/or frequency. Set the system voltage and
frequency and then adjust the voltage, gain, and engine
speed.

Follow the instructions in Figure 8-8 to enter the


configuration mode while the engine is not running and
select the new voltage and frequency setting. The
settings are shown in Figure 8-9. An X in the Display
column in Figure 8-8 indicates a number from 0 to 9.

8.3.1

Configuration Mode Time Out

The controller will automatically exit the configuration


mode without saving any changes after about
11 seconds if no buttons are pressed. Start the
configuration procedure over again from the beginning if
the controller exits the configuration mode before the
settings have been saved.

8.3.2

Controller Software Version


Number

Setting the System Voltage and


Frequency

Press the Select button to step through to the Save


mode as shown in Figure 8-8. Do not change any other
parameters. If any other parameters are changed
inadvertently while navigating the controller menus,
reset them to the settings shown in Figure 8-9 and then
save the settings. When SAVE is displayed, press the
up arrow to save the new settings or the down arrow to
discard the changes and exit the configuration mode
without saving.
Pressing the Select button when SAVE is displayed
returns to the first parameter, system voltage/frequency
(Uu).

The application software for controller operation is


factory-loaded onto the Advanced Digital Control. At
times, it may be necessary to check the software version
number for troubleshooting purposes.
The controllers application software version number is
displayed on the LED screen during the key sequence to
enter the configuration mode, after the Select button has
been pressed and held for about five seconds. For
example, u3.20 will be displayed for software
version 3.20.
Note: The engine type (EC) and the engine data input
type (ED) are factory set and should only be
changed
by
an
authorized
Kohler
dealer/distributor. Incorrect settings will make
your unit non-functional.

58

Section 8 Reconnection/Adjustments

TP-6711

7/09

With the generator set engine stopped, hold the Select button while moving the generator set master
switch to the RUN position. (The generator set engine will not start.)
Button Sequence

Notes

Display *

To enter the configuration mode. Hold the


select button until the display shows the
software version number(approximately 5
seconds), and continue to hold while pressing
the up and down arrows as shown.

XX.XX

Hold the Select button:

Wait 5 seconds, then press:

Press:
or

To select the nominal system


voltage/frequency according to Figure 8-9.

Uu0X

To step through the other parameters to the


SAVE mode. (Do not change any other
parameters.)

SAVE

To save changes.

YES

To discard changes without saving.

no

Press:

Press:

or

TP6195

* X in this display indicates a number from 0 to 9. See Figure 8-9. A bold X indicates the digit that changes during adjustment.

Figure 8-8

TP-6711

7/09

Setting the Nominal System Voltage and Frequency (only) after Generator Reconnection

Section 8 Reconnection/Adjustments

59

Marine Diesel Model


7EFOZD
8.5EFOZD
(3 Ph)
9EFOZD
(1 Ph)

9EOZD

10EOZD
(1 Ph)

EOZD
EFOZD

10EOZD
(3 Ph)

11EFOZD

11.5EFOZD
(3 Ph)

13EOZD
13EFOZD

Volts,
Hz

Market

Engine
Type

Data
Inputs

Battery
Voltage

CANbus
Comm.

Voltage, Phases
230 V, 1 Ph, 2 W

Uu*

Uc

Ec

Ed[

Bt

Cn]

115/230 V, 1 Ph, 3 W

12

240 V, 1 Ph, 2 W

13

1 (std.)
or
3 (ops) [

230/400 V, 3 Ph, 4 W, Wye

230 V, 1 Ph, 2 W

12 or 24

115/230 V, 1 Ph, 3 W

1 (std.)
or
3 (ops) [

1 (std.)
or
3 (ops) [

12

Freq.
Hz
50

50

50

60

60

60

240 V, 1 Ph, 2 W

13

120/240 V, 1 Ph, 3 W

120 V, 1 Ph, 3 W

120 V, 1 Ph, 2 W

120/240 V, 1 Ph, 3 W

120 V, 1 Ph, 3 W

120 V, 1 Ph, 2 W

120/240 V, 3 Ph, 4 W, Delta

10

127/220 V, 3 Ph, 4 W, Wye

16

220/380 V, 3 Ph, 4 W, Wye

19

240/416 V, 3 Ph, 4 W, Wye

20

230 V, 1 Ph, 2 W

115/230 V, 1 Ph, 3 W

50

50

240 V, 1 Ph, 2 W

13

115/230 V, 1 Ph, 3 W

115/230 V, 3 Ph, 4 W, Delta

14

110/190 V, 3 Ph, 4 W, Wye

17

120/208 V, 3 Ph, 4 W, Wye

18

220/380 V, 3 Ph, 4 W, Wye

21

230/400 V, 3 Ph, 4 W, Wye

240/416 V, 3 Ph, 4 W, Wye

22

120/240 V, 1 Ph, 3 W

230 V, 1 Ph, 2 W

60
50

115/230 V, 1 Ph, 3 W

240 V, 1 Ph, 2 W

13

0
(No Can),
1 or 6
(J1939),
7 or 9
(Smartcraft)
]

1 (std.)
or
3 (ops) [

12 or 24

* Use voltage/frequency parameters Uu07--Uu23 only with ADC application program version 1.20 or higher.
[ See Figure 8-10 for Ed settings with optional sender kits.
] See Figure 8-11 for Cn settings with optional digital gauges (gauges are available on selected models only).
Note: Replacement controllers from Kohler Aftermarket Parts are shipped with factory settings for the 8.5/12RES.
Note: Setting the Ec parameter automatically selects the Ed parameter for the standard data inputs for that engine.
If you change Ec, check the Ed setting.

60

Section 8 Reconnection/Adjustments

TP-6711

7/09

Marine Diesel Model

14EOZD
(3 Ph)

15EOZD
17EFOZD
(1 Ph)

17.5EFOZD
(3 Ph)

20EOZD
(1 Ph)

EOZD
EFOZD

20EOZD
(3 Ph)

20EFOZD

20EFOZD
(3 Ph)

23EOZD

24EOZD
(3 Ph)

Freq.
Hz

60

60
50

50

60

60

50

50

60

60

Voltage, Phases
120/240 V, 1 Ph, 3 W

Volts,
Hz

Market

Engine
Type

Data
Inputs

Battery
Voltage

CANbus
Comm.

Uu*

Uc

Ec

Ed[

Bt

Cn]

12 or 24

0
(No Can),
1 or 6
(J1939),
7 or 9
(Smartcraft)
]

120/208 V, 3 Ph, 4 W, Wye

11

127/220 V, 3 Ph, 4 W, Wye

16

120/240 V, 3 Ph, 4 W, Delta

10

139/240 V, 3 Ph, 4 W, Wye

10

277/480 V, 3 Ph, 4 W, Wye

120/240 V, 1 Ph, 3 W

230 V, 1 Ph, 2 W

115/230 V, 1 Ph, 3 W

240 V, 1 Ph, 2 W

13

115/230 V, 1 Ph, 3 W

115/230 V, 3 Ph, 4 W, Delta

14

110/190 V, 3 Ph, 4 W, Wye

17

120/208 V, 3 Ph, 4 W, Wye

18

220/380 V, 3 Ph, 4 W, Wye

21

230/400 V, 3 Ph, 4 W, Wye

240/416 V, 3 Ph, 4 W, Wye

22

120/240 V, 1 Ph, 3 W

120/240 V, 1 Ph, 3 W

120/208 V, 3 Ph, 4 W, Wye

11

127/220 V, 3 Ph, 4 W, Wye

16

120/240 V, 3 Ph, 4 W, Delta

10

139/240 V, 3 Ph, 4 W, Wye

10

277/480 V, 3 Ph, 4 W, Wye

230 V, 1 Ph, 2 W

115/230 V, 1 Ph, 3 W

240 V, 1 Ph, 2 W

13

115/230 V, 1 Ph, 3 W

115/230 V, 3 Ph, 4 W, Delta

14

110/190 V, 3 Ph, 4 W, Wye

17

120/208 V, 3 Ph, 4 W, Wye

18

220/380 V, 3 Ph, 4 W, Wye

21

230/400 V, 3 Ph, 4 W, Wye

240/416 V, 3 Ph, 4 W, Wye

22

120/240 V, 1 Ph, 3 W

120/240 V, 1 Ph, 3 W

120/208 V, 3 Ph, 4 W, Wye

11

127/220 V, 3 Ph, 4 W, Wye

16

120/240 V, 3 Ph, 4 W, Delta

10

139/240 V, 3 Ph, 4 W, Wye

10

277/480 V, 3 Ph, 4 W, Wye

1 (std.)
or
3 (ops) [

2 w.o.
preheater
or 9 w/
preheater

* Use voltage/frequency parameters Uu07--Uu23 only with ADC application program version 1.20 or higher.
[ See Figure 8-10 for Ed settings with optional sender kits.
] See Figure 8-11 for Cn settings with optional digital gauges (gauges are available on selected models only).
Note: Replacement controllers from Kohler Aftermarket Parts are shipped with factory settings for the 8.5/12RES.
Note: Setting the Ec parameter automatically selects the Ed parameter for the standard data inputs for that engine.
If you change Ec, check the Ed setting.

TP-6711

7/09

Section 8 Reconnection/Adjustments

61

Marine Diesel Model


25EFOZD
(1 Ph)

25EFOZD
(3 Ph)

28EFOZD
(1 Ph)

EOZD
EFOZD

28EFOZD
(3 Ph)

28EOZD
(1 Ph)

28EOZD
(3 Ph)

32EOZD
(1 Ph)

32EOZD
(3 Ph)

Freq.
Hz

Voltage, Phases
230 V, 1 Ph, 2 W

50

50

Data
Inputs

Battery
Voltage

CANbus
Comm.

Uu*

Uc

Ec

Ed[

Bt

Cn]

12 or 24

0
(No Can),
1 or 6
(J1939),
7 or 9
(Smartcraft)
]

115/230 V, 1 Ph, 3 W

240 V, 1 Ph, 2 W

13
6
14

110/190 V, 3 Ph, 4 W, Wye

17

120/208 V, 3 Ph, 4 W, Wye

18

220/380 V, 3 Ph, 4 W, Wye

21

230/400 V, 3 Ph, 4 W, Wye

240/416 V, 3 Ph, 4 W, Wye

22

230 V, 1 Ph, 2 W

115/230 V, 1 Ph, 3 W

240 V, 1 Ph, 2 W

13

115/230 V, 1 Ph, 3 W

115/230 V, 3 Ph, 4 W, Delta

14

110/190 V, 3 Ph, 4 W, Wye

17

120/208 V, 3 Ph, 4 W, Wye

18

220/380 V, 3 Ph, 4 W, Wye

21

230/400 V, 3 Ph, 4 W, Wye

240/416 V, 3 Ph, 4 W, Wye

22

120/240 V, 1 Ph, 3 W

120/240 V, 1 Ph, 3 W

120/208 V, 3 Ph, 4 W, Wye

11

127/220 V, 3 Ph, 4 W, Wye

16

120/240 V, 3 Ph, 4 W, Delta

10

139/240 V, 3 Ph, 4 W, Wye

10

277/480 V, 3 Ph, 4 W, Wye

120/240 V, 1 Ph, 3 W

60

60

Engine
Type

115/230 V, 1 Ph, 3 W

60

60

Market

115/230 V, 3 Ph, 4 W, Delta

50

50

Volts,
Hz

120/240 V, 1 Ph, 3 W

120/208 V, 3 Ph, 4 W, Wye

11

127/220 V, 3 Ph, 4 W, Wye

16

120/240 V, 3 Ph, 4 W, Delta

10

139/240 V, 3 Ph, 4 W, Wye

10

277/480 V, 3 Ph, 4 W, Wye

1 (std.)
or
3 (ops) [

* Use voltage/frequency parameters Uu07--Uu23 only with ADC application program version 1.20 or higher.
[ See Figure 8-10 for Ed settings with optional sender kits.
] See Figure 8-11 for Cn settings with optional digital gauges (gauges are available on selected models only).
Note: Replacement controllers from Kohler Aftermarket Parts are shipped with factory settings for the 8.5/12RES.
Note: Setting the Ec parameter automatically selects the Ed parameter for the standard data inputs for that engine.
If you change Ec, check the Ed setting.

Figure 8-9

62

Controller Parameter Settings, Marine Diesel Models

Section 8 Reconnection/Adjustments

TP-6711

7/09

Optional Sender Kits and Ed Setting

Power Modes

The installation of optional sender kits may require a


change to the Ed (engine data inputs) setting. See
Figure 8-10 for the Ed settings with optional sender kits.
No Change means the installation of the kit does not
require a change to the Ed setting.

Use Figure 8-11 to determine power down times.

Note: The Ec setting can affect the Ed setting. If you


change the Ec setting, check the Ed setting and
change it if necessary to match the value shown
in the tables for your unit.
Note: Installation of an optional electronic governor kit
with a magnetic pickup does not require a change
to the Ed setting.
Model
9--32EOZD
7--28EFOZD

Sender Kit

Ed

None

GM32112-KA1 and -KP1 *

GM50552-KA1 [

No Change

Figure 8-10 Ed Settings with Optional Sender Kits


Cn Communication Parameter
See Figure 8-11 for communication parameter settings.
If your generator set is connected to a remote digital
gauge, refer to Figure 8-11 or the instruction sheet
provided with the gauge to determine the
communication parameter Cn setting.

Gauge Kit
None

D 48-hour power down.

If the ADC 2100


communication parameter setting is Cn00 or Cn07,
the controller will power down after 48 hours of
inactivity. If the generator set has been started, the
controller will power down 48 hours after the
generator set stops.

D Continuous power mode.

If the ADC 2100


communication parameter setting is Cn01, the
controller will not power down. The controller
remains powered at all times to maintain CAN
communications and allow remote start
commands from the CAN gauge.

D 1-hour

* OP and WT sender kits


[ Oil pressure sender kits
] Electronic governor kit

Gauge
Description

With the generator set master switch in the AUTO


position, there are three possible controller power
modes:

Cn
Setting

Power
Down
Time

Cn00

48
Hours

GM32337-KP1 Remote
Digital Gauge
(3 inch)

Cn01

Never/
None

Cn06

1 Hour

GM46035-KP1 Remote
Digital Gauge
(3 inch)

Cn07

48
Hours

GM50822-KP1 Remote
Digital Gauge
(2 inch)

Cn09

1 Hour

CAN
Description

power down.
If the ADC 2100
communication parameter setting is Cn06 or Cn09,
the controller will power down after 1 hour of
inactivity. In this mode, a remote start/stop switch
or the generator set master switch must be used to
activate the controller after it has powered down.
ADC 2100 application code version 1.21 or higher
is required for the 1-hour power down option.

Note: After controller power down, a remote digital


gauge will not have power and therefore will not
be able to send a start signal to activate the
controller.
Note: Kohlers 2-inch digital gauge allows wake-up of
the controller remotely.

No CAN

J1939

Smartcraft

Figure 8-11 Communication Parameter Cn Settings


(optional gauges are available on
selected models only)

TP-6711

7/09

Section 8 Reconnection/Adjustments

63

8.3.4

Adjusting the Voltage, Gain, and


Volts/Hz

After setting the system voltage and frequency, check


the output voltage and frequency and adjust, if
necessary, using the following procedures. Follow the
instructions in Figure 8-18 to adjust the voltage, gain,
volts/Hz while the engine is running. An X in the Display
column in Figure 8-18 indicates a number from 0 to 9.
Use the up arrow to increase a setting or the down arrow
to decrease the setting.

Voltage Adjustment Procedure


1. With the generator set off, connect a digital
voltmeter to the output leads or an electrical outlet
on the load side of the generator set. Set the meter
to measure voltage.
2. Start the generator set by moving the generator set
master switch to the RUN position.
3. Use the ADC controller to adjust the voltage
(parameter 1P) until the output voltage reaches the
desired value. See Figure 8-12.

Pressing the Select button when SAVE is displayed


returns to the first parameter, voltage adjust (1P).
Note: A digital multimeter that measures voltage and
frequency is required for these adjustments.

8.3.5

Voltage Adjustment
WARNING

Measured
Voltage, VAC
85--132
180--251

Approximate
Voltage Change per Step, VAC
Coarse Adjust

Fine Adjust

5
7

0.5
0.7

Figure 8-12 Voltage Adjustment


4. Adjust the voltage stability (gain, parameter 2P) to
minimize light flicker.
5. Readjust the voltage, if necessary.

Hazardous voltage. Moving parts.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.

Volts per Hertz (Hz) Adjustments


The cut-in frequency is pre-set for 58 Hz (60 Hz system)
or 48 Hz (50 Hz system). When the frequency falls
below the cut-in, output voltage is reduced to relieve the
engine. The amount of the voltage reduced is set by the
3P parameter. Monitor engine speed and output voltage
as loads are applied.
D If there is excessive droop in engine speed and little

droop in voltage, increase the 3P value.


D If there is little engine speed droop but excessive

voltage droop, decrease the 3P value.


The amount of voltage droop is approximately 0.5% of
system voltage for each step of 3P, including each cycle
(Hz) below the cut-in frequency.

3P
0
1
2
3
4
5
6
7
8
9

Voltage Droop for Each Engine


Below Cut-in Frequency
0
0.5%
1.0%
1.5%
2.0%
2.5%
3.0%
3.5%
4.0%
4.5%

Figure 8-13 Voltage Droop Adjustments

64

Section 8 Reconnection/Adjustments

TP-6711

7/09

1. Readjust the voltage stability (gain, parameter 2P),


if necessary.
2. Readjust the voltage (parameter 1P), if necessary.
3. Stop the generator set.

8.3.6

Frequency Adjustment

The engine speed determines the generator output


frequency; 60 Hz units operate at 1800 rpm and 50 Hz
units run at 1500 rpm. Adjust the engine governor to
change the output frequency using the following
procedure.

Frequency Adjustment Procedure


To check the engine speed, use a frequency meter
connected to the load leads or use a hand tachometer. If
adjustment is needed, loosen the locking nut on the
speed adjusting screw. Turn the screw clockwise to
increase the speed (and frequency). To decrease the
speed, turn the screw counterclockwise. Tighten the
locking nut when the correct setting is reached. See
Figure 8-14.

TP-6711

7/09

607146

1. Speed adjusting screw


2. Locking nut

Figure 8-14 Governor Adjustment

Section 8 Reconnection/Adjustments

65

Controller Configuration Mode (Use with Figure 8-9, Controller Parameters):


Hold the Select button:

Display:
Move the generator set master switch to the RUN
position. (The generator set engine will not start.)

Wait about 5 seconds until the display shows the


program version number. (The number may be
different than the one shown here.)

1 0 4

Press the down arrow key and then the up arrow


key 3 times to enter the configuration mode.
(This is the controller password.)

Uu 0 x

Now release the Select button.


Press:
or

To set the voltage/frequency setting see Figure 8-9.

Uu 0 x

To step to the next parameter, unit configuration


Uc.
or

To set the unit configuration setting to Uc00, if


necessary.

Uc 0 0

To step to the next parameter, engine type Ec.

or

To set the engine type, if necessary.

E c 0 x

To step to the next parameter, advanced


configuration mode or save mode selection.

Ad n c

Now either save your settings or enter the Advanced Configuration Mode to
set the engine data inputs, battery voltage, and communications.
Press:
To enter advanced configuration mode.
Go to Figure 8-16.

E d 0 x

To proceed to the save mode without


entering the advanced configuration mode.
Go to Figure 8-17.

S AV E

OR:
or

Note: Shaded boxes show which number in the controller display changes when the up or down arrow
key is pressed. x denotes any number from 0 to 9.
Figure 8-15 Configuration Mode (system voltage/frequency, unit configuration, and engine type parameters)

66

Section 8 Reconnection/Adjustments

TP-6711

7/09

Pressing the up arrow key at the Adnc display (See Figure 8-15) puts you
into the Advanced Configuration Mode.
Press:
or

E d 0 x

To set the engine data input type.

To enter battery voltage selection mode.

or

To toggle between 12 and 24 VDC.

12-volt models
24-volt models

B t 1 2
B t 2 4

To enter communications selection mode.

To set the communications parameter.


or
To enter SAVE mode. Go to Figure 8-17.

C n 0 x
S AV E

Note: Shaded boxes show which number in the controller display changes when the up or down arrow
key is pressed. x denotes any number from 0 to 9.
Figure 8-16 Advanced Configuration Mode (engine data input types, battery voltage, and engine
communications)

There are 3 options when the display says SAVE:


Press:
To return to the first parameter, system voltage/frequency
Uu, to check or change settings before saving. See
Figure 8-15.

S AV E
Uu 0 x

or
To save changes.

Y E S

To discard changes without saving.

n o

or

Yesor no flashes when the up or down arrow is pressed and then


the controller exits the configuration mode. The display returns to
the runtime hours.

x x x x

Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to the
last saved settings when the master switch is moved to the OFF/RESET position.
* x in the runtime hours display above denotes any number from 0 to 9.
Now move the master switch to OFF/RESET.
Figure 8-17 Save Mode (after configuring generator set parameters)
TP-6711

7/09

Section 8 Reconnection/Adjustments

67

Output Voltage Adjustment Mode:

Display :*

Move the generator set master switch to the RUN position. The generator set
engine starts and the controller display shows the engine runtime hours.

x x x x

Hold:

Wait about 5 seconds until the display changes from runtime hours
to the program version number.

x. x x

Press the down arrow key and then the up arrow key 3 times to enter the
adjustment mode. (This is the controller password.)

1 P x x

The controller is now in the voltage coarse adjustment mode.


Press:
or

To raise or lower the voltage in large increments


(approximately 5--7 volts per step).

To enter fine voltage adjustment mode.

or

1 P x x

1 P x x

To raise or lower the voltage in smaller increments


(approximately 0.5--0.7 volts per step).

To enter coarse voltage stability (gain) adjustment mode.

2 P x x
or

To raise or lower the voltage stability (gain) in large


increments.

To enter fine voltage stability (gain) adjustment mode.

or

To raise or lower the voltage stability (gain) in smaller


increments.

To enter volts/Hz adjustment mode.

or

2 P x x

3 P 0 x

To raise or lower the volts/Hz:


0.5% per step 00 = 0; 09 = 4.5%

* Shaded boxes show which character in the controller display changes for each adjustment. x in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model.

TP6196

Figure 8-18 Output Voltage and Frequency Adjustments


68

Section 8 Reconnection/Adjustments

TP-6711

7/09

Appendix A Generator Selection and Wattage Requirements


are DC powered by a 12-volt battery. Make sure the
calculated total wattage includes only lights actually on
the generator set AC circuit.

Consider total wattage requirements (lights, motors,


appliances) when selecting a generator set or when
sizing wattage usage in which available space and
construction limit the size of the generator set.

Air Conditioners
Motors

The starting characteristics of air conditioners vary


greatly; one 12,000 Btu unit has, for example, lower
starting requirements than a 10,000 Btu unit of another
variety. When using only one unit, there is usually no
starting problem, provided the lighting and appliance
load is not too high when starting the unit.

When figuring generator set capacity requirements for


loads that include electric motors, consider the high
current demanded by the motors during startup. The
inrush or starting current is typically 2--3 times higher
than that required when the motor reaches normal
operating speed. Allow reserve for inrush demands plus
other loads which could be on the line as the electric
motor starts. Use Figure 1 as a guide when selecting
generator set capacity requirements involving motor
loads.
Motor
HP

Starting (Inrush)
Watts

Running
Watts

1/4

750

330

1/3

1000

400

1/2

1500

600

3/4

2000

750

3300

1100

4000

2000

5000

3000

Figure 1

Simultaneous starting of two air conditioning units,


however, can present problems if the generator set
capacity is marginal. Because of the variation in starting
characteristics among air conditioners, this publication
makes no statements regarding multiple-motor starting
capabilities of the generator set covered. Consider
delayed starting or use of easy-starting devices on air
conditioner units whenever simultaneously starting
more than one motor.
See Figure 2 for typical air conditioner requirements.
Information will vary with manufacturer.

Appliances
Generator sets often furnish AC for appliances such as
TV, stereo, electric water heater, etc. With the exception
of the resistance-type loads such as the water heater,
requirements for appliances are usually low. Do not
overlook such loads when figuring total requirements.
Allow reserve capacity for anticipated appliance loads to
avoid overloading a generator set.

Motor Requirements

Lighting
To calculate lighting load, add the wattage of each
generator set-operated lamp. Note that not all of the
lights or lamps are on the generator set AC circuit; some

Air Conditioner Size (Btu/Hr.)


7,000

9,000

12,000

16,000

24,000

Voltage

115

230

115

230

115

230

115

230

Full load amps

9.3

4.8

9.9

5.0

11.8

6.3

16.3

8.0

11.6

Rated load amps

7.7

4.0

7.0

3.5

8.9

4.8

13.0

6.2

10.2

Locked rotor amps

34.0

20.0

40.0

20.0

50.0

31.0

75.0

36.0

56.0

Starting (inrush) watts

3910

4600

4600

4600

5750

7130

8630

8280

12,900

886

920

805

805

1020

1100

1500

1430

2350

Running watts

Figure 2

TP-6711

230

Typical Marine Air Conditioner Requirements, 60 Hz

7/09

Appendix

69

Appendix B Abbreviations
The following list contains abbreviations that may appear in this publication.
A, amp
ABDC
AC
A/D
ADC
adj.
ADV
AHWT
AISI
ALOP
alt.
Al
ANSI

AO
API
approx.
AR
AS
ASE
ASME
assy.
ASTM
ATDC
ATS
auto.
aux.
A/V
avg.
AVR
AWG
AWM
bat.
BBDC
BC
BCA
BCI
BDC
BHP
blk.
blk. htr.
BMEP
bps
br.
BTDC
Btu
Btu/min.
C
cal.
CARB
CB
cc
CCA
ccw.
CEC
cfh
cfm

ampere
after bottom dead center
alternating current
analog to digital
analog to digital converter
adjust, adjustment
advertising dimensional
drawing
anticipatory high water
temperature
American Iron and Steel
Institute
anticipatory low oil pressure
alternator
aluminum
American National Standards
Institute
(formerly American Standards
Association, ASA)
anticipatory only
American Petroleum Institute
approximate, approximately
as required, as requested
as supplied, as stated, as
suggested
American Society of Engineers
American Society of
Mechanical Engineers
assembly
American Society for Testing
Materials
after top dead center
automatic transfer switch
automatic
auxiliary
audiovisual
average
automatic voltage regulator
American Wire Gauge
appliance wiring material
battery
before bottom dead center
battery charger, battery
charging
battery charging alternator
Battery Council International
before dead center
brake horsepower
black (paint color), block
(engine)
block heater
brake mean effective pressure
bits per second
brass
before top dead center
British thermal unit
British thermal units per minute
Celsius, centigrade
calorie
California Air Resources Board
circuit breaker
cubic centimeter
cold cranking amps
counterclockwise
Canadian Electrical Code
cubic feet per hour
cubic feet per minute

70 Appendix

CG
CID
CL
cm
CMOS
cogen.
Com
conn.
cont.
CPVC
crit.
CRT
CSA
CT
Cu
cu. in.
cw.
CWC
cyl.
D/A
DAC
dB
dBA
DC
DCR
deg.,
dept.
dia.
DI/EO
DIN

DIP
DPDT
DPST
DS
DVR
E, emer.
EDI
EFR
e.g.
EG
EGSA
EIA
EI/EO
EMI
emiss.
eng.
EPA
EPS
ER
ES
ESD
est.
E-Stop
etc.
exh.
ext.
F

center of gravity
cubic inch displacement
centerline
centimeter
complementary metal oxide
substrate (semiconductor)
cogeneration
communications (port)
connection
continued
chlorinated polyvinyl chloride
critical
cathode ray tube
Canadian Standards
Association
current transformer
copper
cubic inch
clockwise
city water-cooled
cylinder
digital to analog
digital to analog converter
decibel
decibel (A weighted)
direct current
direct current resistance
degree
department
diameter
dual inlet/end outlet
Deutsches Institut fur Normung
e. V.
(also Deutsche Industrie
Normenausschuss)
dual inline package
double-pole, double-throw
double-pole, single-throw
disconnect switch
digital voltage regulator
emergency (power source)
electronic data interchange
emergency frequency relay
for example (exempli gratia)
electronic governor
Electrical Generating Systems
Association
Electronic Industries
Association
end inlet/end outlet
electromagnetic interference
emission
engine
Environmental Protection
Agency
emergency power system
emergency relay
engineering special,
engineered special
electrostatic discharge
estimated
emergency stop
et cetera (and so forth)
exhaust
external
Fahrenheit, female

fglass.
FHM
fl. oz.
flex.
freq.
FS
ft.
ft. lbs.
ft./min.
g
ga.
gal.
gen.
genset
GFI

fiberglass
flat head machine (screw)
fluid ounce
flexible
frequency
full scale
foot, feet
foot pounds (torque)
feet per minute
gram
gauge (meters, wire size)
gallon
generator
generator set
ground fault interrupter

GND,
gov.
gph
gpm
gr.
GRD
gr. wt.
HxWxD
HC
HCHT
HD
HET
hex
Hg
HH
HHC
HP
hr.
HS
hsg.
HVAC

ground
governor
gallons per hour
gallons per minute
grade, gross
equipment ground
gross weight
height by width by depth
hex cap
high cylinder head temperature
heavy duty
high exhaust temperature
hexagon
mercury (element)
hex head
hex head cap
horsepower
hour
heat shrink
housing
heating, ventilation, and air
conditioning
high water temperature
hertz (cycles per second)
integrated circuit
inside diameter, identification
International Electrotechnical
Commission
Institute of Electrical and
Electronics Engineers
improved motor starting
inch
inches of water
inches of mercury
inch pounds
incorporated
industrial
internal
internal/external
input/output
iron pipe
International Organization for
Standardization
joule
Japanese Industry Standard
kilo (1000)
kelvin
kiloampere
kilobyte (210 bytes)

HWT
Hz
IC
ID
IEC
IEEE
IMS
in.
in. H2O
in. Hg
in. lbs.
Inc.
ind.
int.
int./ext.
I/O
IP
ISO
J
JIS
k
K
kA
KB

TP-6711

7/09

kg
kg/cm2

kilogram
kilograms per square
centimeter
kgm
kilogram-meter
kilograms per cubic meter
kg/m3
kHz
kilohertz
kJ
kilojoule
km
kilometer
kOhm, k kilo-ohm
kPa
kilopascal
kph
kilometers per hour
kV
kilovolt
kVA
kilovolt ampere
kVAR
kilovolt ampere reactive
kW
kilowatt
kWh
kilowatt-hour
kWm
kilowatt mechanical
L
liter
LAN
local area network
L x W x H length by width by height
lb.
pound, pounds
lbm/ft3
pounds mass per cubic feet
LCB
line circuit breaker
LCD
liquid crystal display
ld. shd.
load shed
LED
light emitting diode
Lph
liters per hour
Lpm
liters per minute
LOP
low oil pressure
LP
liquefied petroleum
LPG
liquefied petroleum gas
LS
left side
Lwa
sound power level, A weighted
LWL
low water level
LWT
low water temperature
m
meter, milli (1/1000)
M
mega (106 when used with SI
units), male
m3
cubic meter
m3/min.
cubic meters per minute
mA
milliampere
man.
manual
max.
maximum
MB
megabyte (220 bytes)
MCM
one thousand circular mils
MCCB
molded-case circuit breaker
meggar
megohmmeter
MHz
megahertz
mi.
mile
mil
one one-thousandth of an inch
min.
minimum, minute
misc.
miscellaneous
MJ
megajoule
mJ
millijoule
mm
millimeter
mOhm, m
milliohm
MOhm, M
megohm
MOV
metal oxide varistor
MPa
megapascal
mpg
miles per gallon
mph
miles per hour
MS
military standard
m/sec.
meters per second
MTBF
mean time between failure
MTBO
mean time between overhauls
mtg.
mounting

TP-6711

7/09

MW
mW
F
N, norm.
NA
nat. gas
NBS
NC
NEC
NEMA
NFPA
Nm
NO
no., nos.
NPS
NPSC
NPT
NPTF
NR
ns
OC
OD
OEM
OF
opt.
OS
OSHA
OV
oz.
p., pp.
PC
PCB
pF
PF
ph.,
PHC
PHH
PHM
PLC
PMG
pot
ppm
PROM
psi
pt.
PTC
PTO
PVC
qt.
qty.
R
rad.
RAM
RDO
ref.
rem.
RFI
RH
RHM
rly.

megawatt
milliwatt
microfarad
normal (power source)
not available, not applicable
natural gas
National Bureau of Standards
normally closed
National Electrical Code
National Electrical
Manufacturers Association
National Fire Protection
Association
newton meter
normally open
number, numbers
National Pipe, Straight
National Pipe, Straight-coupling
National Standard taper pipe
thread per general use
National Pipe, Taper-Fine
not required, normal relay
nanosecond
overcrank
outside diameter
original equipment
manufacturer
overfrequency
option, optional
oversize, overspeed
Occupational Safety and Health
Administration
overvoltage
ounce
page, pages
personal computer
printed circuit board
picofarad
power factor
phase
Phillips head crimptite (screw)
Phillips hex head (screw)
pan head machine (screw)
programmable logic control
permanent-magnet generator
potentiometer, potential
parts per million
programmable read-only
memory
pounds per square inch
pint
positive temperature coefficient
power takeoff
polyvinyl chloride
quart
quantity
replacement (emergency)
power source
radiator, radius
random access memory
relay driver output
reference
remote
radio frequency interference
round head
round head machine (screw)
relay

rms
rnd.
ROM
rot.
rpm
RS
RTV
SAE

root mean square


round
read only memory
rotate, rotating
revolutions per minute
right side
room temperature vulcanization
Society of Automotive
Engineers
scfm
standard cubic feet per minute
SCR
silicon controlled rectifier
s, sec.
second
SI
Systeme international dunites,
International System of Units
SI/EO
side in/end out
sil.
silencer
SN
serial number
SPDT
single--pole, double--throw
SPST
single--pole, single--throw
spec, specs
specification(s)
sq.
square
sq. cm
square centimeter
sq. in.
square inch
SS
stainless steel
std.
standard
stl.
steel
tach.
tachometer
TD
time delay
TDC
top dead center
TDEC
time delay engine cooldown
TDEN
time delay emergency to
normal
TDES
time delay engine start
TDNE
time delay normal to
emergency
TDOE
time delay off to emergency
TDON
time delay off to normal
temp.
temperature
term.
terminal
TIF
telephone influence factor
TIR
total indicator reading
tol.
tolerance
turbo.
turbocharger
typ.
typical (same in multiple
locations)
UF
underfrequency
UHF
ultrahigh frequency
UL
Underwriters Laboratories, Inc.
UNC
unified coarse thread (was NC)
UNF
unified fine thread (was NF)
univ.
universal
US
undersize, underspeed
UV
ultraviolet, undervoltage
V
volt
VAC
volts alternating current
VAR
voltampere reactive
VDC
volts direct current
VFD
vacuum fluorescent display
VGA
video graphics adapter
VHF
very high frequency
W
watt
WCR
withstand and closing rating
w/
with
w/o
without
wt.
weight
xfmr
transformer

Appendix 71

Appendix C Generator Set Output Ratings Procedure


Kohler Co. develops the kilowatt output rating of a Kohlerr
marine generator set based upon the calculations
specified in ISO 3046 and ISO 8528-1. The calculations
correct for environmental variables encountered in a

generator set installation.


Figure 1 outlines the
calculations. Figure 2 contains examples of how heat
variables affect generator set ratings.

Generator Output corrected = Generator Output observed x Correction Factor


Output power is expected to be within 5% of the specified rating when corrected to reference conditions.
Correction factors are determined using the following formulas:
1.

For naturally aspirated compression-ignition engines (power limited by excess air):


C.F. = [1.175 (29.2 / Dry Barometer in. Hg)1 (Temperature _F + 460/537).75 -- .175]
x Alternator Efficiency Reference / Alternator Efficiency Observed

2.

For turbocharged compression ignition engines:


C.F. = [1.175 (29.2 / Barometer Observed in. Hg).7 (Temperature _F + 460/537)2 -- .175]
x Alternator Efficiency Reference / Alternator Efficiency Observed

3.

For turbocharged and intercooled compression ignition engines:


C.F. = [1.175 (29.2 / Barometer Observed in. Hg).7 (Temperature _F + 460/537)1.2 -- .175]
x Alternator Efficiency Reference / Alternator Efficiency Observed

Reference conditions:
Temperature: 77_F; Pressure: 29.2 in. Hg dry barometer.
Kohler sound shield increases ambient intake air approx. 12_F
Approximate derates:
Temperature: approximately 1% per 10_F (turbocharged engines have a greater derate);
Pressure (altitude): approximately 4% per 1000 ft. (1 in. Hg)

Figure 1

Generator Output

KEY
60 Hz
50 Hz

8.0
7.9
7.8
7.7
7.6
7.5
7.4
7.3
7.2
7.1
7.0
6.9
6.8
6.7
6.6
6.5
6.4
6.3
6.2
6.1
6.0
5.9
5.8
5.7
5.6
5.5
75 77

80

85

90

95

100

105

110

115

120

Temperature (_F)

Figure 2

72

Example: 6.5EFOZ/8EOZ kW Derates (ISO 3046/ISO 8258-1)

Appendix

TP-6711

7/09

TP-6711

7/09

73

74

TP-6711

7/09

TP-6711

7/09

75

KOHLER CO. Kohler, Wisconsin 53044


Phone 920-565-3381, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPower.com

TP-6711

7/09

E 2009 by Kohler Co. All rights reserved.

Kohler Power Systems


Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65)6264-6422, Fax (65)6264-6455

You might also like