Data Center Energy Handbook
Data Center Energy Handbook
Data Center Energy Handbook
Handbook
Simple Green Reliable
Summary
This handbook provides key model selection and system design parameters for key products
in Huawei's data center infrastructure, including the uninterruptible power supply (UPS),
precision air conditioner, power distribution equipment, and cabinet and aisle components
as well as the methods for configuring the modular data center and network management
system (NMS). For critical systems, this handbook also provides answers to FAQ and design
calculation methods so that users can quickly select modes and perform configuration and
system design.
CONTENTS
01
UP S
02
03
Features
High reliability: centralized bypass design, with no bypass current equalization risk; 1+1
redundancy control modules, communication bus redundancy design.
High efficiency with a low load: The efficiency can reach 96% when the load rate is
40%. The UPS can run with high efficiency at common load rates, which reduces the
energy consumption of UPS by more than 50% when compared with a traditional UPS.
UPS management: implements refined management for key power supply nodes,
supports intelligent operation and maintenance, predicts the failure of easily damaged
parts, and works with the smart network management system to grasp the UPS running
information anytime anywhere.
Model Overview
Maximum
Capacity
Model
Power Module
Configuration
Width
Remarks
125 kVA/kW
600 mm
120 kVA/kW
600 mm
200 kVA/kW
600 mm
320 kVA/kW
600 mm
480 kVA/kW
UPS5000-E-480KF480-SC (standard
version)
600 kVA/kW
UPS5000-E-600KF600-SC (standard
version)
UPS5000-E-600KF600-FC (full version)
800 kVA/kW
UPS5000-E-800KF800-SC (standard
version)
UPS5000-E-800KF800-FC (full version)
04
UP S
Modular design: All power modules, bypass modules, and energy control modules
(ECMs) are hot-swappable and support online capacity expansion and maintenance
(maintenance time is reduced to 5 minutes).
200/320 kVA
2. Bypass module
4. Control module
6. Output switch
05
Specifications
UPS5000-E125K-F125
UPS5000-E120K-F120
UPS5000-E200K-F200
UPS5000-E320K-F320
Rated capacity
(kVA/kW)
25125
40120
40200
40320
Number of power
modules
15
13
15
18
380/400/415 V AC
THDi
3%
0.99
Battery voltage
UP S
Model
Supported
Cabling mode
Width x height x
depth (mm)
Maintenance space
requirements
Weight (kg)
355
480
Efficiency
96%*
Parallel connection
Maximum: 4 units
Certification
Communications
293
359
Remarks:
*: UPS5000-E-125K-F125 efficiency: 95.5%
06
Model
UPS5000-E-480KF480-SC/FC
UPS5000-E-600KF600-SC/FC
UPS5000-E-800KF800-SC/FC
Rated capacity
(kVA/kW)
40480
40600
40800
Number of power
modules
112
115
120
380/400/415 V AC
THDi
3%
0.99
Battery voltage
07
Different sources
for mains input and
bypass input
Supported
Cabling mode
Width x height x
depth (mm)
Maintenance space
requirements
Weight (kg)
1000
Efficiency
96%
Parallel connection
Maximum: 4 units
Maintenance bypass
Switch configuration
Certification
Communications
1350
1670
120 kVA
200 kVA
UP S
Item
320 kVA
Mains Input
Mains input current (A)
Recommended
cable size (mm2)
L1/L2/L3/N
238
213
355
569
4 x 120
4 x 95
2 x (4 x 95)
2 x (4 x 120)
250 A/3P
250 A/3P
400 A/3P
630 A/3P
190
182
304
486
4 x 95
4 x 70
2 x (4 x 70)
2 x (4 x 95)
250 A/3P
250 A/3P
400 A/3P
630 A/3P
190
182
304
486
4 x 95
4 x 70
2 x (4 x 70)
2 x (4 x 95)
250 A/3P
250 A/3P
400 A/3P
630 A/3P
50
50
95
95
Bypass Input
Bypass input current (A)
Recommended
cable size (mm2)
L1/L2/L3/N
U/V/W/N
08
Item
400 kVA
480 kVA
600 kVA
800 kVA
711
853
1055
1407
2 x (4 x 185)
2 x (4 x 240)
2 x (4 x 240)
3 x (4 x 240)
800 A/3P
1000 A/3P
1250 A/3P
1600 A/3P
608
729
912
1216
2 x (4 x 150)
2 x (4 x 185)
2 x (4 x 240)
3 x (4 x 185)
630 A/3P
800 A/3P
1000 A/3P
1250 A/3P
608
729
912
1216
2 x (4 x 150)
2 x (4 x 185)
2 x (4 x 240)
3 x (4 x 185)
630 A/3P
800 A/3P
1000 A/3P
1250 A/3P
150
185
240
240
Mains Input
Mains input current (A)
Recommended
cable size (mm2)
L1/L2/L3/N
Recommended circuit
breaker
Bypass Input
Bypass input current (A)
Recommended
cable size (mm2)
L1/L2/L3/N
Recommended circuit
breaker
Output
Output current (A)
Recommended
cable size (mm2)
U/V/W/N
Recommended circuit
breaker
PE
Recommended cable size (mm2)
09
UP S
10
Features
The UPS uses the high frequency tower technology and has a low THDi and a high
power factor, effectively reducing the pollution of the power grid and therefore
avoiding interference with other devices
The efciency can be up to 96%, thereby signicantly reducing loss and OPEX.
The output power factor can reach more than 0.95, with the loading capability
increased more than 10% when compared with the traditional UPS, better matching
modern IT equipment that uses the power factor correction technology.
The UPS supports a wide input voltage range. This reduces the number of times
that the UPS transfers to battery mode. The reduced number of transfer times, in
combination with intelligent equalized and oat charging management and battery
hibernation technology, greatly extends the service life of batteries.
11
UP S
Model
UPS5000-A-30K
Rated Capacity
30 kVA
Model
UPS5000-A-60K
Rated Capacity
60 kVA
UPS5000-A-40K
40 kVA
UPS5000-A-80K
80 kVA
UPS5000-A-120K
120 kVA
Model
Rated
Capacity
UPS5000-A-400K-SC
400 kVA
UPS5000-A-500K-SC
500 kVA
UPS5000-A-400K-FC
UPS5000-A-500K-FC
400 kVA
500 kVA
Remarks
Model
Rated
Capacity
Standard
version
UPS5000A-600K-SC
600 kVA
The full
version
contains
the mains,
bypass,
and output
switches.
UPS5000A-800K-SC
800 kVA
UPS5000A-600K-FC
600 kVA
UPS5000A-800K-FC
800 kVA
Remarks
Standard version
12
Specifications
Model
13
UPS5000
-A-30K
UPS5000
-A-40K
UPS5000
-A-60K
UPS5000
-A-80K
Rated capacity
(kVA/kW)
30
Rated input
voltage
380/400/415 V AC
Battery voltage
Rated output
voltage
380/400/415 V AC
Different sources
for mains input
and bypass input
Supported
Width x height x
depth (mm)
Maintenance
space
requirements
Weight (kg)
70
Efciency
95.7%
Parallel connection
Maximum: 4 units
Maintenance
bypass
Protection level
IP20
Certication
Communications
40
60
80
UPS5000
-A-120K
120
160
200
UPS5000
-A-200K
UPS5000
-A-300K
UPS5000
-A-400K
UPS5000
-A-500K
UPS5000
-A-600K
UPS5000
-A-800K
Rated capacity
200 kVA
/200 kW
300 kVA
/300 kW
400 kVA
/380 kW
500 kVA
/475 kW
600 kVA
/570 kW
800 kVA
/760 kW
Rated input
voltage
380/400/415 V AC
Battery voltage
Rated output
voltage
380/400/415 V AC
Different sources
for mains input
and bypass input
Supported
Cabling mode
Routed from the top or bottom (a top entry cabinet is required for
routing cables from the top of a 300 kVA cabinet)
Width x height x
depth (mm)
Maintenance
space
requirements
Weight (kg)
360
Efciency
96%
Parallel
connection
Maximum: 4 units
Maintenance
bypass
Switch
conguration
Protection level
Certication
Communications
550
900
1000
2000 x
2000 x 850
2400 x
2000 x 850
1470
1770
UP S
Model
14
30 kVA
40 kVA
60 kVA
80 kVA
120 kVA
Mains Input
Mains input
current (A)
Recommended
cable size (mm2)
53
71
107
142
213
4 x 10
4 x 16
4 x 35
4 x 50
4 x 95
46
61
91
122
182
4 x 10
4 x 16
4 x 25
4 x 35
4 x 70
46
61
91
122
182
4 x 10
4 x 16
4 x 25
4 x 35
4 x 70
10
16
16
25
50
Bypass Input
Bypass input
current (A)
Recommended
cable size (mm2)
Output
Output current (A)
Recommended
cable size (mm2)
PE
Recommended
cable size (mm2)
200 kVA
300 kVA
400 kVA
500 kVA
600 kVA
800 kVA
355
533
675
844
1013
1351
Recommended
cable size (mm2)
2 x (4 x
95)
2 x (4 x
120)
2 x (4 x
185)
2 x (4 x
240)
2 x (4 x
240)
3 x (4 x
240)
Recommended
circuit breaker
400 A/3P 630 A/3P 800 A/3P 1000 A/3P 1250 A/3P 1600 A/3P
Item
Mains Input
Mains input
current (A)
Bypass Input
Bypass input
current (A)
15
304
456
608
760
912
1216
200 kVA
300 kVA
400 kVA
500 kVA
600 kVA
800 kVA
Recommended
cable size (mm2)
2 x (4 x
70)
2 x (4 x
95)
2 x (4 x
150)
2 x (4 x
240)
2 x (4 x
240)
3 x (4 x
185)
Recommended
circuit breaker
400 A/3P 630 A/3P 630 A/3P 800 A/3P 1000 A/3P 1250 A/3P
UP S
Item
Output
304
456
608
760
912
1216
Recommended 2 x (4 x
cable size (mm2) 70)
2 x (4 x
95)
2 x (4 x
150)
2 x (4 x
240)
2 x (4 x
240)
3 x (4 x
185)
Recommended
circuit breaker
400 A/3P 630 A/3P 630 A/3P 800 A/3P 1000 A/3P 1250 A/3P
PE
Recommended
cable size (mm2)
95
95
150
240
240
240
16
UPS5000 -E UPS5000 -E UPS5000 -A- UPS5000 -A(25-125 kVA) (40-800 kVA) (30-120 kVA) (200-800 kVA)
Standard
Standard
Standard
Standard
IP21 component
Short-distance battery
temperature sensor
Long-distance battery
temperature sensor
Parallel cable
BSC cable
iBattery
Intelligent battery
detector appearance
17
Function
Antiseismic kit
Strengthens the cabinet so that the cabinet can meet the requirements of
seismic fortication intensity of 9.
IP21 component
Prevents water from dropping into the cabinet, protecting the cabinet to
IP21.
If you need to install the 120 kVA or 200 kVA cabinet against the wall, you
need to install the top outlet kit to meet heat dissipation requirements.
ECM extension
subrack
Install this subrack when the UPS is equipped with a backfeed protection
card and dry contact extension card.
Install a top entry cabinet to meet the requirements for routing cables
from the top of the UPS5000-A 320 kVA cabinet.
Dry contact
extension card
Backfeed
protection card
Provides backfeed detection and protection for the mains and bypass.
When backfeed occurs, the backfeed protection card sends signals to
trigger alarm signals or quickly disconnects the backfeed loop.
Intelligent battery
detector
Monitors battery voltages and temperatures and battery string charge and
discharge currents, and communicates with the PC over Modbus.
Battery grounding
failure detector
Ambient
temperature and
humidity sensor
UP S
Component
Short-distance
battery
Internal battery temperature sensor (distance: 2 m)
temperature sensor
Long-distance
External battery temperature sensor (distance: 50 m)
battery
temperature sensor
Parallel cable
BSC cable
iBattery
The wireless battery inspection solution iBattery uses the ZigBee wireless
network communication to detect the voltage, internal resistance,
temperature, of a single battery and the charge current. When compared
with the traditional wired battery detector, iBattery does not require
cabling, facilitating installation and maintenance.
18
Features
Rack/tower convertible, suitable for different installation scenarios
ne model supports multiple input and output power systems. Users only need to
O
change the input and output wiring configuration, which is convenient and flexible.
Prewarning for failure of key components notifies customers of maintenance before
failure occurs.
T he UPS supports various communication modes, such as Modbus, SNMP, USB, and
dry contacts, facilitating monitoring. The UPS allows warning by email and short
message.
T he number of batteries is adjustable, facilitating battery maintenance. Intelligent
battery charge and discharge management and intelligent hibernation function can
help extend the battery life span effectively.
igh efficiency helps the UPS get ECA energy saving certification from the United
H
Kingdom government and the first batch of "Energy Star" certification in Asia Pacific.
The UPS is green and power saving. It can achieve an efficiency of 94% (for 6 kVA),
94.5% (for 10 kVA), and 95% (for 15/20 kVA).
19
Specifications
Rated Capacity
1 kVA/0.8 kW
3 kVA/2.4 kW
Input/output system
1-input 1-output
1-input 1-output
Input connector
200/208/220/230/240 V AC
200/208/220/230/240 V AC
Battery voltage
RTS model: 24 V DC
RTL model: 36 V DC
RTS model: 72 V DC
RTL model: 96 V DC
200/208/220/230/240 V AC
200/208/220/230/240 V AC
Output socket
Efciency
88%
90%
H x W x D (mm)
88 x 438 x 310
Weight
12 kg (RTS)
7 kg (RTL)
29.3 kg (RTS)
15.1 kg (RTL)
Certication
Communications
20
21
Rated Capacity
6 kVA/
5.4 kW
10 kVA/
9 kW
15 kVA/
13.5 kW
20 kVA/
18 kW
1/1
1/1 or 3/1
Input wiring
L+N+PE
L+N+PE or 3Ph+N+PE
220/230/240
V AC
L-N: 220/230/240 V AC
0.99
Battery voltage
192-240 V DC
Output wiring
L+N+PE
L+N+PE or 3Ph+N+PE
Output socket
2 x C13 (10
A)
Rated output
voltage
220/230/240 V AC1%
Output frequency
Efficiency
94%
Noise
< 55 dB
H x W x D (mm)
86 x 430 x 585
Weight
14 kg
Certification
Communications
(192-240) V DC
94.5%
95%
58dB
130 x 430 x 685
16 kg
32 kg
Residual
Current
Circuit
Breaker
Input
50 A, 1P, D trip
curve
100 mA
Output
50 A, 1P
Input
63 A, 1P, D type
curve
100 mA
Output
63 A, 1P
3/1
Output
63 A, 1P
1/1
300 mA
Output
100 A, 1P
Bypass input
300 mA
25 mm
Main input
50 A, 3P, D trip
curve
300 mA
10 mm
Output
100 A, 1P
25 mm
Bypass input
300 mA
Main input
50 A, 3P, D trip
curve
Output
50 A, 3P
5001000
mA
adjustable 25 mm
Output
125 A, 1P
Bypass input
5001000
25 mm
mA
adjustable
Mains input
63 A, 3P, D trip
curve
300 mA
10 mm
Battery
63 A
16 mm
Output
125 A, 1P
25 mm
Bypass input
300 mA
Mains input
63 A, 3P, D trip
curve
Output
63A, 3P
Input/Output
Terminal
System
6 kVA 1/1
10 kVA
UP S
UPS
1/1
15 kVA 3/1
3/3
1/1
20 kVA 3/1
3/3
300 mA
300 mA
Cable Size
6 mm
10 mm
25 mm
10 mm
10 mm
22
Backup Time
Number
UPS
of Battery
Capacity
Packs
Battery
Capacity
Number
of
Batteries
9 Ah/12 V
2 packs
25%
50%
75% 100%
3x2
strings
60
40
25
15
9 Ah/12 V
3x4
strings
160
110
75
50
Battery box
(14)
65 Ah/12 V
3 x 1-4
strings
Maximum: 8 hours at
100% load
Built-in
battery
9 Ah/12 V
31
13
1 pack
9 Ah/12 V
45
17
11
2 packs
9 Ah/12 V
16
85
45
25
16
3 boxes
9 Ah/12 V
24
130
70
40
27
4 boxes
9 Ah/12 V
32
175
95
55
39
Battery
Capacity
Number
of
Batteries
30%
50%
80% 100%
20
36
19
40
77
46
25
19
60
120
68
43
29
80
174
92
57
46
20
26
12
40
57
32
17
12
60
88
53
29
23
80
125
70
44
32
40
35
18
80
79
48
26
19
120
125
70
44
32
160
171
96
57
48
1 pack
1 kVA
3 kVA
Number
UPS
of Battery
Capacity
Packs
6 kVA
10 kVA
15 kVA
6
8
23
7 Ah/12 V
9 Ah/12 V
9 Ah/12 V
Configuration
External
Internal
External
Configuration
External
External
External
20 kVA
UP S
Number
UPS
of Battery
Capacity
Packs
Number
of
Batteries
30%
50%
80% 100%
40
26
12
80
56
32
17
12
120
88
53
29
23
160
125
70
44
32
Battery
Capacity
9 Ah/12 V
Configuration
External
3 kVA
6 kVA
10 kVA
15 kVA
20 kVA
Battery pack
Parallel cable
PDU
Isolation
transformer
Temperature
and humidity
sensor
Temperature
sensor
Dry contact
extension card
SNMP card
Modbus card
Rail component
24
Small UPS:
Tower UPS2000-A Series
110 kVA
Introduction
The UPS2000-A series has a capacity ranging from 1 kVA to 10 kVA. The UPS can provide
uninterruptible and reliable power supply to branch offices, bank branches, and office
scenarios. It can be tower-mounted and has built-in batteries. The UPS adopts the
double-conversion technology, which can help eliminate the impact of nine power faults
and therefore effectively protect loads. The high power density design adopted is spacesaving. UPS2000-A is really a perfect power protection solution for small power scenarios.
Features
Adopts the online double-conversion technology and has strong adaptability to loads,
ensuring power supply quality and better protecting loads
Supports built-in batteries, space-saving, suitable for ofce scenarios
Up to 90% efciency in online mode, reducing electricity fees
Supports various communications modes, including Modbus, SNMP, USB, and dry
contact
Supports alarm information reporting by SMS and email
25
1/2/3 kVA
6/10 kVA
Specifications
1 kVA/0.8 kW
Rated Capacity
2 kVA/1.6 kW
Input socket
C14
220/230/240 V AC
Output socket
220/230/240 V AC1%
220/230/240 V AC
Efciency
88%
Operating temperature
040C
Noise
50 dB
D x W x H (mm)
Weight
Standard
backup
3 kVA/2.4 kW
C14
C20
89%
90%
Standard
backup
16.8 kg
27 kg
6.7 kg
7.4 kg
9.2 kg
Communications
26
Item
6 kVA
Standard
Version
10 kVA
Standard
Version
6 kVA
10 kVA
Professional Professional
Version
Version
6 kVA
/5.4 kW
10 kVA
/9 kW
6 kVA
/5.4 kW
Input wiring
L+N+PE
L+N+PE/L+L+PE
220/230/240 V AC
208/220/230/240 V AC
Output wiring
L+N+PE
L+N+PE/L+L+PE
220/230/240 V AC
208/220/230/240 V AC
6 mm2
10 mm2
6 mm2
10 mm2
50 A (D
trip curve)
63 A (D
trip curve)
50 A (D
trip curve)
63 A (D
trip curve)
50 A
63 A
50 A
63 A
Efciency
96%
> 5 minutes
(80% rated
load)
> 4 minutes
(80% rated
load)
> 6 minutes
(80% rated
load)
> 5 minutes
(80% rated
load)
Parallel capacity
Yes
Operating temperature
040OC
Noise
< 55 dB
580 x 250 x 605
D x W x H (mm)
Weight
Certication
Standard
backup
60 kg
66 kg
65 kg
71 kg
Long
backup
20 kg
21 kg
25 kg
26 kg
27
10 kVA
/9 kW
UPS2000
-A-1KTTL
UPS2000 UPS2000
-A-2KTTS -A-2KTTL
UPS2000
-A-3KTTS
UPS2000
-A-3KTTL
Battery pack
External
charger
Ambient
temperature
and humidity
sensor
Dry contact
card
Modbus card
OVCD board
Battery
temperature
sensor
UPS
UPS2000-A-6K
(TTS-S)
UPS2000-A-10K
(TTS-S)
UPS2000-A-6K
(TTS-P)
UPS2000-A-10K
(TTS-P)
SNMP card
Modbus card
Dry contact
card
Ambient
temperature
and humidity
sensor
Battery
temperature
sensor
GSM modem
Component
UP S
Component
Remarks:
Select one out of the SNMP card, Modbus card, and dry contact card.
The ambient temperature and humidity sensor should be used together with the SNMP card
for monitoring the ambient temperature and humidity of the UPS.
An external charger can enhance the charger capacity of a UPS with long backup time. The
charger current is adjustable. For 1 kVA, 2 kVA, and 3 kVA UPSs, the maximum charge current
are 15 A, 12 A, and 10 A respectively.
28
Configuration
1 kVA
9 Ah/12 V
4 minutes
Built-in
2 kVA
9 Ah/12 V
4 minutes
Built-in
3 kVA
9 Ah/12 V
4 minutes
Built-in
1 kVA
2 kVA
3 kVA
Battery
Pack
Quantity
Battery
Capacity
Battery
Quantity
9 Ah/12 V
9 Ah/12 V
1-4
65 Ah/12 V
3 x (1-4)
9 Ah/12 V
6x2
85
45
25
17
9 Ah/12 V
6x4
175
95
55
39
9 Ah/12 V
8x2
85
45
25
17
9 Ah/12 V
8x4
175
95
55
39
25%
50%
75%
100%
3x2
77
39
21
15
3x4
159
83
47
36
Configuration
External
Battery
Quantity
6 kVA standard
7 Ah/12 V
16
5 minutes
Built-in
10 kVA standard
version
9 Ah/12 V
16
4 minutes
Built-in
6 kVA professional
version
7 Ah/12 V
20
6 minutes
Built-in
10 kVA professional
version
9 Ah/12 V
20
5 minutes
Built-in
Capacity
29
Battery Pack
Quantity
Battery
Capacity
Battery
Quantity
9 Ah/12 V
9 Ah/12 V
9 Ah/12 V
9 Ah/12 V
50%
75%
100%
20 x 2
77
46
25
19
20 x 4
174
92
57
46
20 x 2
57
32
17
12
20 x 4
125
70
44
32
Configuration
External
External
W: active power
K1: power factor
When the rated voltage and current are available, S (VA) = Voltage x Ampere
30
3. Calculate the total capacity of loads: S = S1 + S2 + ... + Sn, that is, sum of the
apparent power of each device, measured in VA.
4. Calculate the capacity of the UPS:
UPS selection
Determine the UPS model according to the UPS capacity calculated above and the actual
requirements (tower or modular).
Remarks
1. The preceding UPS conguration only meets the basic capacity requirements. For N+X
redundancy or dual-bus redundancy conguration, increase the number of devices
based on the actual situation.
2. For the modular UPS, modular redundancy configuration can be achieved. The
principle is to configure one redundant module for each five power modules.
For example, if five power modules are required, six modules are required for the
redundancy design; if 10 power modules are required, 12 modules are required for
the redundancy design.
3. Confirm the load type before selecting a UPS. For the electric machinery (inductive)
load, the impact current of the load during startup needs to be considered. The UPS
capacity must be able to bear the corresponding impact power. Generally, the impact
current of the electric machinery load is 68 times of the rated current.
31
Remarks
1. When calculating the total battery supply power, choose the active UPS power rather
than the apparent power (W rather than VA).
2. The number of battery strings connected in parallel should not exceed 4 for reliability
purposes.
32
Calculation steps
1. Calculate the highest operating voltage of battery string.
Vmax = VCV x Nbat
Vcv: equalized charging voltage per battery
Nbat: number of batteries per string
2. Calculate the battery discharge power.
P = PO/
PO: total UPS output power
: UPS inverter efciency
3. Calculate the largest total battery discharge current Imax (A)
Imax = P/Uoff
Uoff: end of discharge (EOD) voltage per cell
4. Calculate the largest uninterruptible current Iu (A)
IU = Imax /N
N: battery string quantity
5. Calculate the operating voltage (Highest battery string operating voltage Vmax x
Redundancy coefficient 1.2) and operating current (Uninterruptible current Iu x
Redundancy coefficient 1.2) of the battery breaker box to be selected.
6. Based on the largest battery short-circuit currents provided by vendors, determine the
tripping current of the battery breaker box to be selected.
7. Determine the battery bus bar box (BBB box) specications:
Voltage specification: same as the battery breaker box
Current specification: total highest battery discharge current I max x redundancy
coefficient 1.2
33
Calculation steps
1. Calculate the UPS operating current.
a. I IN =
S + PLOSS + PCHG
U
b. I O =
S
U
c. I BAT = * U
OFF
The highest uninterruptible current Iu is calculated to ensure the battery failure tolerance
capability when multiple battery strings are connected in parallel. That is, when one
battery string is abnormal and does not work, the remaining battery strings should be
able to provide the full load current to the UPS.
IIN: UPS input current
IO: UPS output current
IBAT: battery discharge current
S: UPS output apparent power
P: UPS load rate
PLOSS: UPS internal loss
PCHG: USP charge power
: battery inverter efficiency
U: UPS rated voltage
UOFF: battery string EOD voltage
2. Choose a cable type (such as RV or YJV) based on the insulation level, pressure
resistance, and temperature resistance requirements of the UPS cable.
3. Determine the cable model according to the current specication calculated in 1.
4. Conrm the cable length according to the site survey result.
5. Verify the voltage drop on the cable according to the calculation method provided by
cable vendor: The AC voltage drop on the cable should be no more than 2% of the
UPS output voltage, and the DC voltage drop on the cable should be no more than 1%
of the UPS output voltage.
6. If the voltage drop exceeds the requirement, choose the cable with larger size and
7. verify again by performing steps 3 through 5.
Remarks
When choosing a cable type, current redundancy should be considered:
For a single cable, the current-carrying capacity redundancy should not be less than 20%.
For multiple cables connected in parallel, the current-carrying capacity redundancy
after weighting should not be less than 30%.
34
FAQ
1. Q: How can I determine the load power factor?
A: Generally, the load power factor is 0.9 for servers and IT equipment and 0.8 for old
servers and IT equipment.
2. Q: Why is redundancy capacity considered for UPS configuration?
A: According to GB/T50174-2008-8.1.7, redundancy capacity should be considered
before the UPS capacity is finalized for two reasons. The first reason is to prevent the
UPS from running in overload status and ensure the reliability of power system. The
second reason is to ensure that the UPS still has sufficient capacity if extra load is added
to UPS in the future. The capacity calculated according to formula E 1.2P can satisfy
only the basic requirement of electric equipment, but not include the redundancy
capacity.
3. Q: Capacity can be expanded on demand by adding power modules for a modular
UPS. So, can the UPS capacity configuration be performed without redundancy
coefficient 1.2 considered?
A: No. The UPS capacity redundancy configuration is performed not only to meet
future capacity expansion requirements, but also to ensure that the UPS can still work
under the normal load range when the load increases, thereby ensuring the reliability
of the power supply system.
4. Q: What is the difference between redundancy configuration and parallel
configuration?
A: Redundancy is configured in terms of capacity. For example, both 1+1 and 2+0 are
parallel configurations. However, 1+1 is a parallel configuration with redundancy, but
2+0 is a parallel configuration without redundancy. For example, two 20 kVA UPSs
connected in parallel with 30 kVA load are 2+0 configuration without redundancy.
If one UPS fails, the system transfers to bypass mode and cannot provide power
protection. Two 20 kVA UPSs connected in parallel with 15 kVA load are 1+1
configuration with redundancy. If one UPS fails, the other UPS will take over the entire
load and run properly.
5. Q
: What is a single point failure? Do other vendors also provide design for single point
failure like the UPS5000-E does?
A: A single point failure is a failure at a point that leads to breakdown of the entire
system. To ensure reliable power supply to important loads, weak points that may
cause single point failure are not allowed in the UPS. Therefore, the redundancy design
should be considered during product design. When a point fails, the redundant part
can provide reliable power supply to important loads. Generally, UPS vendors conduct
the redundancy design for vulnerable and key components, such as the fan and
auxiliary power source. Huawei UPS5000-E has the unique energy control module (ECM)
redundancy in addition to redundancy for the preceding components. The system
can run properly even one ECM fails. For most UPSs in the industry, only one ECM is
configured.
6. Q: What will happen if one ECM is removed from a Huawei modular UPS?
A: The Huawei modular UPS has 1+1 redundancy design for the ECM. If one ECM is
removed or damaged, the other ECM smoothly takes over functions to ensure normal
system running. If both ECMs are removed, the UPS transfers to bypass mode to
provide uninterruptible power to customer equipment.
35
UP S
36
37
38
NetCol5000-A Series
(Air-Cooled, In-row)
25/35 kW in-row AC
20 kW in-row AC
39
NetCol
5000
035
Function
Description
Series name
Model range
Hyphen
Cooling mode
Cooling capacity
Air discharge
No.
Outdoor Unit
NetCol
500
038
No.
Function
Description
Series name
Model range
Cooling mode
A: air cooled
Cooling capacity
NetCol5000-A Configuration
NetCol5000-A interior
EC fan
High efcient
evaporator
DC inverter
compressor
40
Technical Specifications
NetCol5000-A Indoor Unit Technical Specications
Item
Air supply mode
Power supply
Unit
Model
NetCol5000- NetCol5000- NetCol5000A020H
A025H
A035H
Horizontal ow
V/Phase/ 380-415/3/50
Hz
(60)
380-415/3/50, 380415/3/60
40C DB/20% RH
Total cooling
capacity
kW
23.4
29.4
38.1
Sensible cooling
capacity
kW
23.4
29.4
38.1
Total cooling
capacity
kW
21.5
27.2
35.7
Sensible cooling
capacity
kW
21.5
27.2
35.7
Total cooling
capacity
kW
20.7
25.8
35.0
Sensible cooling
capacity
kW
20.7
25.8
35.0
Total cooling
capacity
kW
19.2
23.9
33.0
Sensible cooling
capacity
kW
19.2
23.9
33.0
37C DB/24% RH
35C DB/26% RH
Cooling
performance
parameters
32C DB/29% RH
30C DB/34% RH
Total cooling
capacity
41
kW
18.2
22.7
31.2
Sensible cooling
capacity
kW
17.6
22.7
31.2
Air volume
m3/h
4,000
4,600
6,500
Refrigerant
R410A
PTC electric
heating
Heating capacity
kW
Electrode
humidier
Humidier
capacity
kg/h
Water pipe
diameter
Indoor
unit power
distribution
parameters
Unit
Model
NetCol5000- NetCol5000- NetCol5000A020H
A025H
A035H
Installation
distance L 25 m
inch
Liquid
pipe:1/2, gas
pipe: 5/8
Installation
distance
25 < L 60 m
inch
Humidier pipe
mm
Liquid pipe:
5/8, gas pipe:
3/4
DN19
Self-draining pipe
mm
DN19
Condensate
drainpipe
mm
DN19
23 (16.5)
29.0 (23.0)
32.0 (26.0)
Recommended
switch capacity
32
40
40
Recommended
cable size
mm2
5 x 4
5 x 6
5 x 6
300 1000
2000
230
350
T1 condition:
NetCol500A032
T1 condition:
NetCol 500A032
T1 condition:
NetCol500A038
T3 condition:
NetCol500A038
T3 condition:
NetCol500A038
T3 condition:
NetCol500A072
WxDxH
mm
Indoor unit
weight
Net weight
kg
Outdoor
unit
Indoor unit
dimensions
Type
Quantity
Integer
Refrigerant
copper pipe
diameter
Item
: The data in parentheses applies to the indoor unit without the electric heater and humidier.
Note:
Air cooled type cooling capacity calibrating condition: outdoor ambient temperature
35C
T1 condition: highest user-dened temperature 45C; T3 condition: highest userdened temperature 55C
NetCol5000-A020H supports only pipe routing from the bottom. Other models
support pipe routing from the top and bottom.
Data is subject to change without prior notice.
42
Outdoor unit
dimensions
Top view of
recommended
space for horizontal
installation
Top view of
recommended space
for vertical installation
43
NetCol500
-A0325
Unit
NetCol500
-A0385
NetCol500
-A0725
Power source
V/Ph/Hz
380480/3/50, 380480/3/60
Fan quantity
Integer
Net weight
kg
110
130
185
Operating temperature
of standard unit
20C to +45C
20C to +55C
20C to +55C
Operating temperature
of low-temperature
component element
40C to +45C
2.5
2.5
4.5
Recommended circuit
breaker
1370 (1220) x
1094 x 1160 (720)
2200 (2050)
1094 1100 (654)
mm
5 x 2.5 (380-415 V)
4 x 2.5 (440-480 V)
Dimensions:
W1 (W2) x D x H1 (H2)
mm
1350 (1220) x
1094 1160 (720)
Recommended cable
specications
20C to +55C
Remarks:
1. T1 condition for NetCol5000-A020H unit: 15C to + 45C, T3 condition: 5C to +52C
2. The temperature to be used should be determined to match the indoor unit.
Location Relationship
Max. Height
Difference Allowed
20 m (10 m for a 20 kW
unit)
5m
60 m
Note: Contact Huawei if the installation distance exceeds the maximum value allowed.
44
NetCol5000-C Series
(Chilled-Water, In-row)
30 kW in-row AC
45
NetCol5000-C Configuration
NetCol5000-C interior
DC power
Air lter
3-way
regulating
valve
Control box
Pipe
Surface
cooler
EC fan
Technical Specifications
Indoor Unit Technical Specications
Item
Unit
NetCol5000-C030H
Power supply
V/Ph/Hz
200240/1/50, 200240/1/60
Supply/Return water
7oC/12oC
10oC/15oC
13oC/18oC
15oC/20oC
40C DB/18% RH
Total cooling capacity
kW
37.70
33.77
30.00
27.33
37.70
33.77
30.00
27.33
m/h
6.48
5.76
5.18
4.68
kPa
98
90
74
62
37C DB/21% RH
Total cooling capacity
kW
33.91
30.00
26.04
23.44
33.91
30.00
26.04
23.44
m/h
5.90
5.18
4.46
4.03
kPa
92
74
60
47
46
Unit
NetCol5000-C030H
kW
31.29
27.31
23.53
20.83
31.29
27.31
23.53
20.83
Item
35C DB/23%RH
Total cooling capacity
Water ow rate
m/h
5.44
4.68
4.11
3.60
kPa
84
62
50
39
kW
27.26
23.37
19.44
16.77
27.26
23.37
19.44
16.77
32C DB/28% RH
Total cooling capacity
Water ow rate
m/h
4.68
4.03
3.36
2.88
kPa
62
49
33
19
kW
21.92
17.92
14.01
11.31
21.92
17.92
14.01
11.31
28C DB/35%RH
Total cooling capacity
Water ow rate
m/h
3.74
3.06
2.41
1.94
kPa
42
29
15
11
Air ow rate
m3/h
5100
mm
DN25
Condensate water
forcible drainpipe
diameter
mm
Condensate water
drainpipe diameter
mm
5.5A
Recommended circuit
breaker
10
2
2 x 2.5
Dimensions (W x H x D)
mm
Net weight
kg
230 (240)
The data in parentheses applies to the unit with a 200 mm-deep frame kit.
47
2
2
4
7
5
6
6
7
1 Top cover
2 Front panel
3 Exhaust valve
4 Door lock
5 Side panel
6 Caster
7 Leveling foot
Specications
Unit model
Dimensions (H x W x D mm)
203
43.2
Environmental specications
Installation mode
48
49
NetCol8000-A Series
(Air Cooled, In-room, R410A)
Air Conditioning System
50 kW downflow AC
100 kW downflow AC
50
NetCol8000-A Configuration
NetCol8000-A interior
Strong and weak
electrical isolation,
enhancing the
electrical safety
High efciency
scroll
compressor
Infrared
humidier
EC fan
TTechnical Specifications
Indoor Unit Technical Specications
Item
Unit
Power supply
Air supply method
Cooling
performance
parameters
PTC electric
heating
51
NetCol8000A050D
NetCol8000A100D
V/Ph/Hz 380415/3/50
-
Downow
Downow
Total cooling
capacity
kW
50.0
100.0
Sensible cooling
capacity
kW
46.8
93.5
Air ow rate
m3/h
14,000
28,000
Refrigerant
R410A
Heating capacity
kW
EC fan
12
Infrared
humidier
Refrigerant
copper pipe
diameter
Indoor
unit power
distribution
parameters
Unit
NetCol8000A050D
NetCol8000A100D
Humidier capacity
kg/h
10
mm
DN19
mm
DN19
Installation distance L 30
m
mm
mm
38.0
76.0
Recommended circuit
breaker
50.0
100.0
5 x 16
5 x 25
mm2
Cable specication
Compressor
and indoor
fans
Fan quantity
Integer 1
Compressor quantity
Integer 1
1140 890
1980
2280 890
1980
kg
415
830
T1 condition: NetCol500-A072
T3 condition: NetCol500-A088
Indoor unit
dimensions
WxDxH
mm
Indoor unit
weight
Net weight
Model
Outdoor unit
Quantity
unit
Water pipe
diameter
Item
Note:
Nominal cooling condition for air-cooled models: return air temperature 24C, relative
humidity 50%, condensing temperature 45C
Data is subject to change without prior notice.
52
Outdoor unit
dimensions
Top view of
recommended
space for horizontal
installation
Top view of
recommended space
for vertical installation
53
NetCol500-A072
Power supply
V/Ph/Hz
380415/3/50
NetCol500-A088
Fan quantity
Integer
Net weight
kg
150
200
Operating temperature of
standard unit
30C to +45C
20C to +55C
3.15
6.25
Recommended circuit
breaker
Item
10
2
Cable specication
mm
5 x 2.5
Dimensions:
W1 (W2) x D x H1 (H2)
mm
Location Relationship
20 m
60 m
5m
60 m
Note: Contact Huawei if the installation distance exceeds the maximum value allowed.
54
NetCol8000-C Series
(Chilled-Water, In-room)
30150 kW precision AC
55
Technical Specifications
Indoor Unit Technical Specications
Item
NetCol8000
-C050D
V/Ph/
Hz
NetCol8000
-C050U
NetCol8000
-C070D
NetCol8000
-C070U
NetCol8000
-C120D
NetCol8000
-C150D
Downow
Upow
Downow
Upow
Total cooling
capacity
kW
57.5
56.5
75.0
74.0
Downow Downow
124.0
150.0
Sensible cooling
capacity
kW
47.7
46.5
60.0
59.2
101.7
120.0
Air ow rate
m3/h
12,600
12,350
14,000
13,750
26,600
28,000
Fan quantity
Integer
Water ow rate
l/s
2.8
2.7
3.6
3.5
6.0
7.2
Water pressure
drop
kPa
80
78
100
100
90
100
Chilled water
inlet/outlet pipe
diameter
Humidier
water inlet pipe
diameter
Condensate
water drainpipe
diameter
3/4 inch
Electric heating
capacity
kW
Humidier
capacity
kg/h
1-5/8 inch
Power supply
Unit
2-1 /8 inch
12
10
20.0
19.8
21.3
21.1
38
39.4
Recommended
circuit breaker
25
25
25
25
50
50
Cable
specication
mm2
5x6
5x6
5x6
5x6
5 x 10
5 x 10
Dimensions
(W x D x H)
mm
Note:
Nominal cooling condition for chilled water models: return air temperature 24C, relative
humidity 50%, inlet/outlet water temperature 7C/12C
Data is subject to change without prior notice.
56
57
Note: 1.15 is the AC margin coefficient, 1.05 is UPS heat dissipation margin coefficient, and SCC is
the sensible cooling capacity
Example
A data center uses a contained dual-aisle module. Ten IT cabinets are configured for the
module. The rated power of each cabinet is designed as 11 kW. The module has built-in
UPS and batteries. If air cooled in-row ACs (with humidifier) each with a sensible cooling
capacity of 35 kW and N+1 redundancy need to be used, how many ACs are required?
Solution:
Module IT power consumption: W = 10 x 11 x 0.67 = 73.7 kW
Required cooling capacity: C = W x 1.15 x 1.05 = 89 kW
Required AC quantity: N1 = C/35 = 2.5 (rounded up to 3)
With N+1 redundancy considered, total AC quantity: N2 = N1 + 1 = 4
Schematic arrangement
PDF
UPS
IT
AC
IT
IT
AC
IT
IT
IT
IT
Battery
cabinet
AC
IT
IT
AC
IT
58
AC quantity=AC heat load/AC cooling capacity (Round up the quantity if the result is
not an integer.)
Redundancy principle: Adopt 8+1 redundancy. That is, when the AC quantity is equal
to or less than 8, 1 backup AC is required; when the AC quantity is greater than 8
and no more than 16, 2 backup ACs are required, and so on.
Example
The B data center computer room area is 300 m2, the UPS power room area is 50 m2,
and there are a total of 70 cabinets, with the rated power of each cabinet designed as
7 kW. The computer room uses the underfloor flow mode (100 kV downflow air cooled
AC), and the UPS power room uses the upflow mode (12.5 kW upflow air cooled AC).
The sensible heat ratio is 0.87. The room structure heat load is 0.1 kW/m2 x room area (m2),
and the lighting heat load is 0.02 kW/m2 x room area (m2). How many ACs are required in
the computer room and UPS power room separately?
Solution:
Computer room IT power: W = 70 x 7 x 0.67 = 328.3 kW
Computer room environment heat load: A = (0.1 + 0.02) x 300 = 36 kW
UPS power room environment heat load: B = (0.1 + 0.02) x 50 = 6 kW
Computer room AC heat load: Q1 = 1.15 x (1 + 3%) x W/0.87 + 1.15 x A/0.87 = 493 kW
AC quantity N1 = Q1/100 = 4.9 (rounded up to 5)
UPS power room AC heat load: Q2 = 1.15 x 10% x W/0.87 + 1.15 x B/0.87 = 53.3 kW
AC quantity N2 = Q2/30= 1.8 (rounded up to 2)
With 8+1 redundancy considered, ACs required in the computer room N3 = 5 + 1 = 6;
ACs required in the UPS power room N4 = 2 + 1 = 3
59
If only the type and size of the room are obtained, you can
calculate the cooling capacity as follows:
Q=SxP
Q: Total cooling capacity (kW), S: Computer room area (m2), P: Estimation cold index
(selected according to the estimation factor that varies depending on the room type)
Cold Load Coefcient P
350500 w/m2
Transmission room
250350 w/m2
6002000 w/m2
100010000 w/m2
350500 w/m2
350400 w/m2
250300 w/m2
350400 w/m2
200250 w/m2
150200 w/m2
60
Precision AC FAQ
1.
2.
Q: How many temperature and humidity sensors are congured for the Huawei air
cooled in-row AC?
A: In standard configuration, there are three built-in supply air temperature sensors,
two built-in return air temperature sensors, and one return air temperature and
humidity sensor. A maximum of six external temperature and humidity sensors can
be optionally configured.
3.
Q: How many temperature and humidity sensors are congured for the Huawei
chilled water in-row AC?
A: In standard configuration, there are six built-in temperature sensors (two for
supply air, two for return air, one for water inlet, and one for water outlet) and a
built-in return air temperature and humidity sensor. A maximum of five external
temperature and humidity sensors can be optionally configured.
4.
Q: What are the heating and humidication congurations for Huawei ACs?
A: All Huawei ACs use PTC electric heating. In-row ACs use electrode humidifiers and
in-room-level ACs use infrared humidifiers.
5.
Q: What are the AC types in modular data centers? How to ensure the safety of
chilled water ACs?
A: Both air cooled and chilled water ACs (in-row) are supported. Safety measures
for the water chilled AC: 1. If a raised floor is available, chilled water pipes can be
routed from under the floor; if there is no raised floor, chilled water pipes must be
routed from the top of the aisle and there must be physical isolation. 2. Set heat
preservation for pipes. 3. Condensate collection and draining are automatically
performed in the AC.
6.
Q: What are the working principles and pipe routing methods of air cooled and
chilled water in-row ACs?
A: The working principle of the air cooled in-row AC is the same as the home air
conditioner, that is, achieving refrigeration by migrating the heat from indoors to
outdoors based on the refrigerant state changes. A chilled water AC uses the cold
water from chillers to migrate heat from indoors to the chillers. Both air cooled
and chilled water ACs support pipe routing from the top and bottom (except
NetCol5000-A020). Pipe routing from the top is used in most cases.
61
7.
8.
9.
Q: What are the differences and disadvantages of in-row cooling when compared
with the traditional downow mode?
A: In-row ACs are more energy efficient and require no raised floor, bringing
less workload. They also support high-density deployment, which can effectively
eliminate the issue of partial hot spots. The traditional downflow mode requires
a raised floor, imposing high requirements for the floor height of a building. The
engineering for the downflow mode is more complex than in-row ACs and the
energy-saving effect is not as good as in-row ACs. The power density supported by
the downflow mode is generally not more than 5 kW per rack, and the partial hot
spot issue is more prominent.
10. Q: Huawei modular data center uses the horizontal mode. If the customer has
determined the downow mode as a preference, which is a more suitable mode
for us?
A: The underfloor downflow mode applies to a power density of less than 5 kW
per rack. The horizontal mode applies to a power density of 3 kW or more per rack.
The future trends are high power density and high integration. Therefore, using the
modular horizontal air supply mode conforms to the service development trends in
the future.
62
PDU8000 Selection
& Configuration
63
P DU
64
Scenarios
The centralized power distribution solution applies to small, medium, and large date
centers.
Small- and medium enterprise data center
Central communications data center
Central headquarters data center
IDC data center
Configuration
The following gure shows the centralized power distribution solution for data centers.
The UPS, UPS input/output PDU, and air conditioner PDU provide centralized power
supply for micro-modules in N data centers. The UPS and PDU are deployed in N+1
redundancy (or 2N). One precision PDU is deployed inside each micro-module to supply
power to each rack and monitor basic parameters such as voltage current, and harmonic.
AC
UPS
input
PDU
UPS
Rack
Rack
AC
Rack
Rack
Rack
Rack
Precision
Rack
PDU
Rack
Rack
AC
Rack
Rack
Rack
Rack
Rack
Rack
Rack
AC
Rack
Rack
Rack
Rack
Precision
Rack
PDU
Rack
Rack
AC
Rack
Rack
Rack
Rack
Rack
Rack
Rack
AC
Rack
Rack
Rack
Rack
Precision
Rack
PDU
Rack
Rack
AC
Rack
Rack
Rack
Rack
AC
AC
PDU
Power
input
Rack
UPS
output
PDU
AC
65
Scenarios
Configuration
The following gure shows the centralized and integrated power distribution solution for
data centers. UPS and PDU are deployed inside each micro-module, and integrated into
a rack. Huawei integrated PDU supports three 3 U high UPSs, and up to three 20 kVA
UPS2000-Gs (2+1) can be congured.
electric
supply
Power
input
AC
Rack
Rack
Rack
AC
Rack
Rack
Rack
Rack
UPS
+
PDU
Rack
Rack
Rack
AC
Rack
Rack
Rack
Rack
AC
Rack
Rack
Rack
AC
Rack
Rack
Rack
Rack
UPS
+
PDU
Rack
Rack
Rack
AC
Rack
Rack
Rack
Rack
AC
Rack
Rack
Rack
AC
Rack
Rack
Rack
Rack
UPS
+
PDU
Rack
Rack
Rack
AC
Rack
Rack
Rack
Rack
66
P DU
The distributed and integrated power distribution solution is suitable for micro-modules
of small data centers (total IT load power below 40 kVA inside a micro-module).
Small enterprise date center
Branch communications date center
Branch headquarters data center
Monitoring command center
Scenarios
The distributed (UPS+PDU independent) power distribution solution applies to micromodules of medium and large data centers.
Internet date center
Headquarters data center
Disaster recovery center
Large cloud data center
Configuration
The following gure shows the distributed (UPS+PDU independent) power distribution
solution. UPS and PDU are distributed inside each micro-module. UPS, PDU, and battery
racks are separately deployed.
AC
Rack
Rack
Rack
AC
Rack
Rack
Rack
Rack
PDU
UPS
BAT PDU
Rack
AC
Rack
Rack
Rack
Rack
AC
Rack
Rack
Rack
AC
Rack
Rack
Rack
Rack
PDU
UPS
BAT PDU
Rack
AC
Rack
Rack
Rack
Rack
AC
Rack
Rack
Rack
AC
Rack
Rack
Rack
Rack
PDU
UPS
BAT PDU
Rack
AC
Rack
Rack
Rack
Rack
Power
input
67
UPS PDU
Introduction
The UPS PDU is an intelligent PDU designed
for UPSs in data centers. With considerate size
design, it supports exible deployment. The PDU
can either be deployed abreast with the modular
UPS rack inside the aisle containment in a
modular data center or deployed independently
outside the containment. The PDU consists of a
rack, an ATS, a meter, copper bars, cables, and
accessories. The input/output PDU is xed.
P DU
Features
Single or dual power inputs
A maximum input capacity of 1600 A, optional 800 A, 1000 A, or 1200 A
Reliable design, compliant with IEC60950 and GB4943, CCC and CE certifications, Level B/C
surge protection
The mains input and bypass input can use different power sources; supports stand-alone or
parallel deployment
Outputs: a maximum of six 630 A MCBs; optional six 630 A MCBs, six 250 A MCBs, or four
800 A MCBs
Intelligent monitoring, interaction with HUAWEI NetEco to implement comprehensive
monitoring and real-time alarming
Front and rear access
Specifications
Item
Dimensions (HWD)
Weight
Power system
Input capacity
Outputs
Surge protection
Maintenance code
Installation code
Cable routing
Specications
2000 mm x 800 mm x 850 mm
500 kg
380/400/415 V 50/60 Hz
Optional: 630 A, 800 A, 1000 A, 1200 A, 1600 A,
optional ATS
Optional: 6 x 630 A/3P, 6 x 400 A/3P MCB or 4 x 800
A/3P MCB
B/C level
Front and rear access
Floor mounted, able to combine with IT racks
Routed in and out from the top
68
Typical Configuration
PE
Power II
PC Level ATS
OTM800E4C8D220C
L11~L31,N
FU1~3
HY HG HR
FU7
L12~L32,N
FU4~6
800/5A,0.5
QFS
S204 C32
PD510-M14
Current
QF3
QF1
QF2
QF4
QF5
QF6
QF7
T5N400 TMA T5N400 TMA T5N400 TMA T3N250 TMD T3N250 TMD T1N160 TMD T1N160 TMD
R400 FF 3P R400 FF 3P R400 FF 3P R250 FF 3P R250 FF 3P R32 FFC 3P R32 FFC 3P
FS
Max:40kA
3*400A/3P+2*250A/3P+2*32A/3P
69
Power
Voltage
Typical Configuration
UPS Output PDF
W D H (mm) 800 850 2000
Qty:1
Input 2
Input 1
N1
N2
1QF
T3N250 TMD
R250 FF 3P
Maintenace Bypass
N3
2QF
T3N250 TMD
R250 FF 3P
3QF
T5N400 TMA
R400 FF 4P
padlock
P DU
L11~L31,N
FU1~3
HY
HG HR
FU7
PE
L12~L32,N
Power
Voltage
PD510-M14
Current
400/5A,0.5
QFS
S204 C32
FU4~6
QF1
QF2
QF5
QF6
T3N250 TMD T3N250 TMD T3N250 TMD T3N250 TMD
R250 FF 3P
R250 FF 3P
R250 FF 3P
R250 FF 3P
FS
Max:40kA
6*250A/3P
70
Precision PDU
(Full-size)
Introduction
The precision PDU (full-size) applies to the
intelligent power distribution management
system for IT racks in data centers. The PDU
collects comprehensive data and sends the data
to the monitoring system to enable real- time
monitoring and effective management over the
power distribution system, thereby assuring a
green IDC.
Features
Dual power inputs, 2N power supply
Large-capacity power distribution, optional input capacity below 630 A, a maximum
of 144-pole outputs.
Reliable design, compliant with IEC60950 and GB4943, CCC and CE certications,
Level B/C surge protection.
Intelligent monitoring, 7-inch monitoring screen, interaction with HUAWEI NetEco for
comprehensive monitoring, real-time alarming, and remote management
Easy maintenance, front and rear access
Specifications
71
Item
Specications
Dimensions (HWD)
Weight
350 kg
Power system
380/400/415 V 50/60 Hz
Input capacity
Outputs
Surge protection
B/C level
Maintenance mode
Installation mode
Cable routing
Typical Configuration
Power I
1L11~1L31,1N
1L13,1N
1FU1~3
1FU7
HG
P DU
HY
Voltage
HR
2N
PE
2FU7
2QF
T3N250 TMD
R250 FF 3P
2L11~2L31,2N
Power II
2L13,2N
1L12~1L32,1N
2FU1~3
HY
HG
2FS
20kA
2QFS
S204 C32
HR
NOTE
1. Routed in and out from the top.
2. Cabinet color: black
50A/25mA,0.5
2QF48
S201 C32
2FU4~6
50A/25mA,0.5
2QF47
S201 C32
Voltage
50A/25mA,0.5
2QF2
S201 C32
1FU4~6
50A/25mA,0.5
2QF1
S201 C32
1L12~1L32,1N
50A/25mA,0.5
1QF48
S201 C32
250/5A,0.5
50A/25mA,0.5
1QF47
S201 C32
Current
Power
monitoring
system
50A/25mA,0.5
1QF2
S201 C32
Current
50A/25mA,0.5
48*32A/1P
1QF1
S201 C32
250/5A,0.5
1QF
T3N250 TMD
R250 FF 3P
1N
PE
1QFS
S204 C32
1FS
20kA
48*32A/1P
72
Precision PDU
(Half-size)
Introduction
The precision PDU (half-size) is an intelligent
PDU designed for data centers. With compact
design and large capacity, it supports flexible
deployment. The PDU can be deployed abreast
with IT racks inside the aisle containment in a
modular data center or deployed independently
outside the containment.
Features
Dual power inputs, 2N power supply
Large capacity, optional input capacity below 630 A, a maximum of 132-pole outputs
Reliable design, compliant with IEC60950 and GB4943, CCC and CE certications,
Level B/C surge protection
Intelligent monitoring, 7-inch monitoring screen, interaction with HUAWEI NetEco for
comprehensive monitoring, real-time alarming, and remote management
Front access
Specifications
73
Item
Specications
Dimensions (HWD)
Weight
250 kg
Power system
380/400/415 V 50/60 Hz
Input capacity
Outputs
Surge protection
B/C level
Maintenance mode
Front access
Installation mode
Cable routing
Typical Configuration
Power I
1L11~1L31,1N
1L13,1N
1L12~1L32,1N
1QF1~2
32A/3P
MCB
50A/25mA,0.5
HY
Voltage
50A/25mA,0.5
1QF3~26
32A/1P
MCB
1FU4~6
1FU7
1FU1~3
HG
1N
PE
1QF
200A/3P
MCCB
200/5A,0.5
1QFS
S204 C32
1FS
20kA
P DU
HR
Current
Power
monitoring
system
Current
Voltage
2*2*32A/3P+24*32A/1
2N
PE
2FU7
2FU4~6
2QF
200A/3P
MCCB
50A/25mA,0.5
2QF3~26
32A/1P
MCB
2FU1~3
2FS
20kA
2QFS
S204 C32
200/5A,0.5
HY
HG
HR
NOTE
1. The side door is double-swing,
and cables are routed from the top.
2. Cabinet color: black
2L11~2L31,2N
Power II
2L13,2N
1L12~1L32,1N
2QF1~2
32A/3P
MCB
50A/25mA,0.5
74
Precision PDU
(with Isolation Transformer)
Introduction
The isolation transformer PDU
is an intelligent PDU designed
for modular data centers. The
PDU has an isolation transformer
inside and distributes optimized
power to IT racks while
measuring electrical parameters
and boosting or decreasing
voltage.
Features
Internal isolation transformer, which decreases the neutral-ground voltage and delivers
pure and stable power to IT equipment
Optional input capacity below 400 A, a maximum of 72-pole outputs
Reliable design, CCC and CE certications, Level B/C surge protection
Intelligent monitoring, 7-inch monitoring screen, interaction with HUAWEI NetEco for
comprehensive monitoring, real-time alarming, and remote management.
Front access
Specifications
75
Item
Specications
Dimensions (HWD)
Weight
1500 kg
Power system
380/400/415 V 50/60 Hz
Input capacity
Outputs
Maximum 72 x 1P or 24 x 3P
Surge protection
B/C level
Maintenance mode
Installation mode
Cable routing
Typical Configuration
Precision PDU (with isolate transformer)
W D H (mm) 1000 800 2000
Qty:1
1N
1QF
T3N250 TMD
R250 FF 3P
250/5A,0.5
PE
PE
L11~L31,N
FU1~3
P DU
2N
Transformer120kVA
380V/380V 50Hz
Uk%=4, Dyn11
HY
HG HR
FU7
2QF
T3N250 TMD
R250 FF 4P
Power
L12~L32,N
FU4~6
Voltage
Current
250/5A,0.5
QFS
S204 C32
monitoring
system
QF1
S203 C40
50A/25mA,0.5
QF2
S203 C40
50A/25mA,0.5
QF18
S203 C40
50A/25mA,0.5
FS
Max:40kA
18*40A/3P
76
Features
Single or dual power inputs
Optional input capacity below 630 A
Reliable design, compliant with IEC60950 and GB4943, CCC and CE certications,
Level B/C surge protection
Up to 108-pole (063 A/1P) or 36 (063 A/3P) outputs
Intelligent monitoring: interaction with HUAWEI NetEco for comprehensive monitoring
and real-time alarming
Front and rear access
Specifications
77
Item
Specications
Dimensions (H x W x D)
Weight
300 kg
Power system
380/400/415 V 50/60 Hz
Input capacity
Output current
063 A/route
Outputs
Surge protection
B/C level
Maintenance mode
Installation mode
Cable routing
Typical Configuration
PE
QF9
QF10
QF1
T1N160 TMD T1N160 TMD S203 C40
R100 FFC 3P R100 FFC 3P
NOTE
1. Routed in and out from the top.
2. Cabinet color: black
QFS
S204 C32
FS
20kA
P DU
L11~L31,N
FU1~3
FU7
HY
Voltage
QF18
S201 C20
FU4~6
QF17
S203 C40
L12~L32,N
QF16
S203 C63
QF
T6N800
PR221DS-LSI
R800 FF 3P
800/5A,0.5
QF15
S203 C40
HG HR
PD510-M14
Power
Current
QF25
S201 C20
9*100A/3P+7*40A/3P+1*63A/3P+9*20A/1P+4*16A/1P
QF26
S201 C20
QF27
S201 C16
QF30
S201 C16
78
Integrated PDU
Introduction
The integrated PDU is an intelligent AC
PDU designed for small- and mediumsized modular data centers. It integrates
the PDUs for UPSs, air conditioners, and IT
equipment. The integrated PDU features
small footprint, high cost efficiency, and
high integration. It is widely used in power
supply and distribution systems for smalland medium-sized modular data centers.
Features
A combination of functions available in the PDUs for UPSs, air conditioners and IT
equipment
Less than 1 m footprint, high cost efciency
Large capacity, optional input capacity below 400 A, maximum of 72-pole outputs.
Reliable design, compliant with IEC60950 and GB4943, CCC and CE certications,
Level B/C surge protection.
One to three 3 U rack-mounted UPSs housed in an integrated PDU below 250 A
Interaction with HUAWEI NetEco for comprehensive monitoring, real-time alarming,
and remote management
Easy maintenance, front and rear access
Specifications
Item
Dimensions (HxWxD)
Weight
Power system
Input capacity
Output current
Outputs
Surge protection
Maintenance mode
Installation mode
Cable routing
79
Specications
2000 mm x 600 mm x 1200 mm
320 kg
380/400/415 V 50/60 Hz
ATS optional: 630 A two inputs, 400 A, 250 A, 160 A,
or 125 A
050 A/route
Maximum 72 x 1P MCB or 24 x 3P MCB
B/C level
Front and rear access
Floor mounted, able to combine with IT racks
Routed in and out from the top
Typical Configuration
Integrated PDU
Power
L11~L31,1N
1QF
160A/3P
MCCB
FU1~3
HY
HG HR
FU7
L12~L32,N
FU4~6
Voltage
Power
monitoring
system
Current
150/5A,0.5
1N
PE
1FS
60kA
1QF5
80A/3P
MCCB
UPS input
padlock
1QF6
80A/4P
MCCB
1QF1~2
32A/3P
MCB*2
Air
maintenance
conditioning
bypass
12
P DU
1QFS
63A/4P
MCB
1QF3~4
32A/1P
MCB*2
standby
12
30kVA
UPS
External
1QF7
63A/3P
MCCB
2N
PE
2QFS
32A/4P
MCB
2FS
20kA
QF1~3
32A/1P
MCB*3
computer
room 1~3
QF4~5
16A/1P
MCB*2
Monitor
and
other
QF6
63A/1P
MCB
TV wall
QF7
32A/3P
MCB
the 5 floor
of the
confidential
room
QF8~10
32A/1P
MCB*3
Double
screen
computer,
standby MCB
1 and 2
QF11~12
16A/1P
MCB*2
standby
MCB 1 and
2
QF13
63A/1P
MCB
standby
QF14
32A/3P
MCB
standby
6*32A/1P+2*32A/3P+2*63A/1P+4*16A/1P
80
81
Cabi ne t
82
NetHos Cabinet
The NetHos cabinet complies with the International Electrotechnical
Commission (IEC) 60297-1/-2 standard. The server cabinet provides a stable
and reliable installation space for data center servers to ensure safe server
operation. The network cabling cabinet provides integrated cabling and
cable management spaces for the data center.
Cabinets in a modular data center feature the same dimensions, and have
aid ducts at the front and rear.
Cabinet appearance
83
1. Front door
2. Frame
3. Side door
4. Rear door
5. Cover
6. Floor
Cabi ne t
84
Cabinet Specifications
Item
Specications
Dimensions
(H x W x D)
Color
Black
Texture of material
Air duct
Installation space
Installation method
Single panel for front door and double panels for rear door
Empty weight
Protection level
IP20
Note:
1 U is equal to 1.75 inches and is about 44.45 mm. U is the height unit defined in the
International Electrotechnical Commission (IEC) 60297 Standard.
The net weight of an empty cabinet is the weight of the rack, front door, rear door,
side panels, and top cover.
Slope passing capability indicates the maximum slope that the cabinet can go through
with castors when there is no interference between the cabinet bottom and the ground.
85
Cabinet Accessories
Cabinet accessories include the bottom sealing plate, cabinet lighting components,
ground copper bar, guide rail, xed tray, adjustable tray, cabling tray, cable fastener, cable
rack, depth-direction cable manager, and ller panel.
86
LED
A contact switch automatically turns
on the lights when the cabinet doors
are open and turns the lights off when
the doors are closed. It uses advanced
NC contacts with high sensitivity.
Contact switch
87
Guide rail
A guide rail is used to facilitate device installation. It uses a standard design and
support the installation of standard devices without occupying any U space. The
guide rails have a bearing capacity up to 50 kg, and are usually used in pairs.
Guide rail
Fixed tray
Cabi ne t
Fixed tray
Adjustable tray
An adjustable tray is used to
support internal devices. Its depth
can be adjusted to match the
distance between two mounting
bars. It does not support drawer
maintenance.
Adjustable tray
88
Cabling tray
A cabling tray is used for
forward and backward
cabling. It uses unique
mounting ears to facilitate
device installation.
Cabling tray
Cable fastener
A cable fastener is installed
on a vertical column in the
cabinet to secure cables.
Cable fastener
Cable tray
A 1 U cable tray is used inside
the cabinet horizontally.
1 U cable tray
89
Filler panel
If certain space in the cabinet is not occupied, install filler panels in that position
to prevent wind from passing through and make the cabinet look more elegant.
Cabi ne t
1 U ller panel
2 U ller panel
90
PDU2000
The NetHos series cabinets are configured with power distribution units, and are
classified as basic cabinets and monitoring cabinets.
PDU2000
PDU2000
Type
Basic type
PDU2000
Monitoring
PDU2000
91
Item
Specications
Remarks
220240 V AC
N/A
Maximum
input current
Output distribution
specications
380415 V AC
Maximum
input current
32 A/1 P; 16 A/3 P
Output distribution
specications
Maximum
input current
32 A
Output distribution
specications
18 x C13+3 x C19
Measures and
displays the
input current,
voltage, and
status of
each phase,
and supports
monitoring
by the
management
system over
RS485 and
network ports.
Aisle Components
The micro-modular data center supports dual-row and single-row cold and hot aisle
containments. The aisle containment is 1200 mm wide. Dual-row aisle containment
consists of equipment cabinets (server cabinets, cabling cabinet, UPS, PDC, air conditioner,
and battery cabinet), aisle doors, skylights, cable troughs, and cable ladders. Single-row
aisle containment consists of equipment cabinets (server cabinets, cabling cabinet, UPS,
PDC, air conditioner, and battery cabinet), aisle doors, skylights, cable troughs, and aisle
enclosure frames.
Dual-row aisle 1200 mm
1.
2.
3.
4.
5.
6.
7.
Cabi ne t
able trough
C
Skylight
Cable rack
PDU
UPS
Battery cabinet
In-row air
conditioner
8. Server cabinet
9. Network cabling
cabinet
10. Aisle door
1. C
able trough
2. Network
cabling
cabinet
3. In-row air
conditioner
4. Server cabinet
5. Battery cabinet
6. UPS
7. PUD
8. Aisle door
9. Skylight
10. Aisle enclosure
92
Aisle door
End doors are installed on both ends of the aisle containment, which makes the
module independent, improves equipment efficiency, and helps onsite personnel
or devices move into or out of the aisle containment. Micro-module aisle doors
are classified as sliding and revolving doors. In the dual-row aisle containment
scenario, both types of doors can be installed. In the single-row aisle containment
scenario, only revolving doors can be installed. To implement aisle-level access
control, you need to select revolving doors.
Sliding door
Sliding doors have two
dimensions respectively for 2 m
and 2.2 m high cabinets:
H x W x D = 2300 mm x 1400
mm x 54 mm
H x W x D = 2500 mm x 1400
mm x 54 mm
Note: In the single-row aisle containment
scenario, sliding door guide rails cannot
be installed on one side; therefore, sliding
doors cannot be installed.
Schematic diagram of
sliding door
Revolving door
Double-swing doors are open
outwards with an opening angle of
110 degrees. Sealing brushes are
installed at the bottom of the door
panel to seal the module.
Double-swing doors have two
dimensions respectively for 2 m and
2.2 m high cabinets:
H x W x D = 2300 mm x 1400 mm x
80 mm
H x W x D = 2500 mm x 1400 mm x
80 mm
93
Double-swing door
Skylight
A skylight is used for sealing an aisle containment. Skylights are classified as
control skylights, rotating skylights, and flat skylights.
Skylight
1. Control skylight
2. Rotating skylight
3. Flat skylight
Note:
A revolving skylight is designed with an eccentric structure. When the electronic lock is
triggered, a rotating skylight falls under gravity. If a re extinguishing system is installed
inside a module, select non-rotating skylights. If a module shares the re extinguishing
system of the equipment room, select rotating skylights.
Cabi ne t
Size
Applicable Cabinet
Control
skylight
1178 mm 590 mm 34 mm
1120 mm 590 mm 33 mm
1120mm790mm33mm
1120 mm 590 mm 33 mm
1120 mm 290 mm 33 mm
1120 mm 790 mm 33 mm
Rotating
skylight
Flat skylight
94
Cable trough
Cabinet cable troughs are classified as signal cable troughs and power cable
troughs. They are used to route signal cables and power cables respectively. This
ensures that strong current cables are separated from weak current cables.
Cable troughs are clamped onto the cabinet top cover. A cable trough is
assembled using two brackets, pallets, and baffles (used to separate weak current
optical fibers from weak current network cables and strong current route A from
strong current route B).
1
300 mm cable trough
1. Control board
2. Side board
3. Pallet
1. Control board
2. Side board
3. Pallet
4. Line slot end plate
4
3
95
Size (L x W x H)
Applicable Cabinet
NetCol5000-C
Cable ladder
Cable ladders are classified as power cable ladders and signal cable ladders. Cable
ladders are used for cabling in the following scenarios:
Between two modules
Between cabinets in two rows in a module
Cross-column installation of module units
Cable ladders are configured based on the actual situation.
Cable ladder
1. End cap
2. Ladder line
4. Fixed plate
Cabi ne t
7. Ground bolt
Installation Height
2500 mm x 400 mm
400
2500 mm x 400 mm
200
Note: Installation height indicates the distance from the top of the cabinet to the top of the cable ladder.
96
97
98
Simple
Wireless weak currents, bus for strong currents, and integrated module design,
reducing the engineering cost by 30%
Digital video surveillance and control, network management, simplifying O & M and
saving manpower cost by 20%
Green
96% highly efcient power supply and all frequency-conversion efcient cooling
Precision cooling between L0/L1/L2, posting PUE no greater than 1.45 in Shenzhen
China
Efcient
Three-level reliability design for parts, components, and the system, posting availability
of 99.999%
Automatic power-off and recovery in the case when a battery is on re
99
Specifications
IDS2000/5000 Architecture
Item
Specications
Dimensions
Design
requirements
Cabinet quantity
Single row: 24; dual row: 48
per module
Input power
Height
Load bearing
1.1 kN/m
Fire
extinguishing
21 kW/R
Operating
conditions
System
100
Item
Design
requirements
Cabinet
Air-cooled
in-row air
conditioner
Chilled-water
in-row air
conditioner
Rack-mounted
UPS
Modular UPS
101
Specications
Reliability level
Altitude
Installation
mode
Dimensions
(H x W x D)
Installation
space
42 U/47 U
Protection level
IP20
Cooling
capacity
20 kW/25 kW/35 kW
Indoor unit
dimensions
(H x W x D)
Input power
Refrigerant
R410A
Cooling
capacity
30 kW
Indoor unit
dimensions
(H x W x D)
Input power
Refrigerant
Water/ethylene glycol
Input power
Rated capacity
10/15/20 kVA
Input power
Rated capacity
40800 kVA
Model Selections
System
Power
Type
Component
Modular UPS
Integrated
UPS
UPS5000-E + PDF
Cooling
UPS2000-G
Integrated UPS
In-row aircooled/
chilled
watercooled
Chilled water-cooled
NetCol5000-C
Item
Solution
Access
Fire extinguishing
Air-cooled
NetCol5000-A
Cabling/Pipe routing
Cabling from the top and pipe routing from the top
and bottom are recommended.
102
Air-Cooled Solutions
Typical conguration for air-cooled solutions:
Specications
600 mm-wide network cabling cabinet: 2000 mm
(2200 mm) x 5400 mm 3600 mm
Dimensions (H x W x D)
800 mm-wide network cabling cabinet: 2000 mm
(2200 mm) x 5600 mm x 3600 mm
103
Input power
Total IT power
36 kW
4 kW
Operating condition
T1
Reliability level
Tier II
Altitude
Installation
Specications
600 mm-wide network cabling cabinet: 2000 mm
(2200 mm) 7500 mm 3600 mm
Dimensions (H x W x D)
15
Input power
Total IT power
75 kW
5 kW
Operating condition
T1
Reliability level
Tier II
Altitude
Installation
104
iManager NetEco
Logical Architecture
Server
Switch
Collector
Collector
RS485
PDU
105
UPS
Cabinet
FE
AC
ATS
Camera
RS485
Access
system
Temperature
sensor
Smoke
sensor
Water
sensor
Core Components
Data collector - ECC500
The energy control center ECC500 is located between the upper-level network
management system and the lower-level monitoring equipment. It plays a central role in
signal connection, convergence, processing, and reporting.
Up to 15 PCS
AI/DI equipment
quantity
Up to 128 PCS
Equipment dimensions
Operating voltage
100240 V AC
Others
RS485 extension
interface
106
The centralized management server is the control center of the entire system. It is
responsible for data analysis, centralized processing, alarm, storage and so on.
Technical
Specications
Basic Version
Standard Version
Enterprise
Version
Number of
intelligent nodes
supported
50500
5001000
10002000
CPU/RAM/
Storage capacity
1 x E5-2609
/8 GB/1200 GB
2 x E5-2609
/32 GB/2400 GB
4 x E7-4820 V2
/64 GB/6000 GB
Supported
protocol
Supported device
type
Remarks:
An intelligent node is a device that communicates with the NetEco platform using the
communication protocol. Common layer-1 intelligent devices in the data center include: ECC
(collector), UPS, AC, humidier, PDF (electricity meter), PDU (monitoring), ATS, diesel generator,
camera, access control control system and so on.
107
Capacity
management
Temperature
cloud
3D view
management
Northbound
interface
Alarm
management
Work order
management
View
management
Report
management
Asset
management
Server
Database/OS
platform
Southbound
interface
Web UI
License
System
platform
Energy
management
Communication protocol
Collection
layer
Power system
Environmental
system
Data convergence
Security system
Cooling system
Other systems
Software Functions
Basic Function
Basic function
Energy analysis
You can master an overall PUE status of the equipment room, optimize the PUE by
analyzing the consumption reports, and provide backup data for improving the unit
PUE.
Capacity
management
Temperature cloud
The overall temperature distribution of the equipment room is clearly displayed and
hence a cold island and a hot island can be effectively distinguished.
SNMP northbound
interface
Alarms and performance data received by the NetEco can be sent to the upper
network management system (EMS) for centralized management.
Third-party system
integration
108
Work order
management
Configuration Method
Install hardware before software and the lower layer before upper layer:
1. Determine the objects to be monitored and congure hardware equipment.
UPS, precision AC, PDF, access control system, video, water, and smoke sensor and
other monitoring content
ECC and switch
Server
2. Determine the number of intelligent devices, configure the software package.
Congure optional function software as required.
Intelligent Micro-Module
Management System Conguration
Application
109
Recommended Configuration
No.
Item
Description
Quantity
Remarks
For access
of 25
intelligent
nodes
1 Software
Basic software
1.2
Additional client
quantity
Optional,
max.: 15
1.3
Work order
management
Optional
1.4
Energy
management
Optional
1.5
SNMP
northbound
interface
Optional
1.6
Temperature
cloud
Optional
Capacity
management
Optional
1.7
1.1
110
No.
Item
Description
Quantity
Management
server
2.2
Operating
system
2.3
Database system
Enterprise Edition MySQL
software
3.1
Data collector
ECC500
3.2
Switch
3.3
Primary power
supply
3.4
Temperature
and humidity
sensor
3.7
Smoke sensor
3.8
Camera
3.9
NVR
Huawei-developed NVR
3000 GB-SATA-7200rpm-3.5,
dedicated for video
surveillance
3 Hardware Components
General hard
3.10
disk
3.11
Skylight
controller
Access control
3.12
system
Double door
3.13 electromagnetic
lock
3.14 IC card reader
2
13.56 MHz-wiegand26/34
13.56 MHz
30
111
Remarks
FAQ
Q: How are cables routed separately for strong and weak currents of the IDS2000?
A: Cables are routed separately through the strong-current cable trough and weakcurrent cable trough on the top of the module to avoid interference.
2.
Q: Can the UPS and server be placed in the same room to save area?
A: Yes, the UPS can be placed in the same room with the server. In most cases, the
UPS should not be too large. If the UPS capacity exceeds 600 kVA, the UPS should
be placed in two rooms (with the concentration of the toxic substances such as the
hydrogen and hydrogen sulde emitted by batteries considered).
3.
Q: Huawei modular data center uses the horizontal mode. If the customer has
determined the downow mode as a preference, which is a more suitable mode
for us?
A: The power density supported by the underoor downow mode is low (35 kW
per rack). The horizontal mode supports high power density scenarios (Huawei's
solution supports 21 kW per rack at most), meeting different requirements in low,
medium, and high power density scenarios. The future trends are high power density
and high integration. Therefore, using the modular horizontal air supply mode
conforms to the service development trends in the future.
4.
Q: What are the AC types in modular data centers? How to ensure the safety of
chilled water ACs?
A: Both air cooled and chilled water ACs (in-row) are supported. Safety measures
for the water chilled AC: 1. If a raised oor is available, chilled water pipes can be
routed from under the oor; if there is no raised oor, chilled water pipes must be
routed from the top of the aisle and there must be physical isolation. 2. Set heat
preservation for pipes. 3. Condensate collection and draining are automatically
performed in the AC.
5.
Q: What are the differences and disadvantages of in-row cooling when compared
with the traditional downow mode?
A: In-row ACs are more energy efficient and require no raised floor, bringing
less workload. They also support high-density deployment, which can effectively
eliminate the issue of partial hot spots. The traditional downflow mode requires
a raised oor, imposing high requirements for the oor height of a building. The
engineering for the downflow mode is more complex than in-row ACs and the
energy-saving effect is not as good as in-row ACs. The power density supported by
the downow mode is generally not more than 5 kW per rack, and the partial hot
spot issue is more prominent.
6.
112
1.
7.
8.
Q: What are the peripheral facilities of the modular data center? Can Huawei help
to consider them?
A: The main peripheral facilities include the facility that introduces mains to the
building where the data center is located, diesel generator, substation, UPS,
refrigeration station of the building, re extinguishing and security facilities. Huawei
can perform integrated delivery with peripheral facilities.
9.
Q: How Huawei solves the re protection issue for the modular data center?
A: The IDS2000 modular data center itself is not integrated with a fire control
network system. Instead, with the help of the computer room building fire
extinguishing system, when re occurs, the smoke and temperature and humidity
sensors in the module generate alarm signals. The syklight in the contained module
can open let the re gas diffuse in the module for re extinguishing purposes.
10. Q: What type of cable routing is adopted for the Huawei modular data center
solution?
A: Cable routing from the top is adopted for the IDS2000 modular data center
solution. Uniquely designed cable troughs on the top of the module allow
weak-current cables to be routed separately with strong-current cables to avoid
electromagnetic interference.
11. Q: I use Huawei's data center solution. Must I use the management system in the
previous recommended conguration?
A: No. The recommended conguration is the cost-effective conguration solution
provided by Huawei after testing. Customers can raise their management system
conguration requirements specic to a project.
12. Q: Huawei has deployed data centers around the world. Can these data centers be
centrally managed using the NetEco management system?
A: Yes. The network architecture based Huawei NetEco management system can
centrally monitor and manage global data centers.
13. Q: How do I query the data center running status and handle faults?
A: The NetEco management system provides the web browsing terminal that allows
login from multiple people simultaneously. Users can use the Internet Explorer 8
browser to log in to the system and manage data centers.
14. Q: Can I use the Huawei NetEco management system if my data center did not
use Huawei equipment?
A: Yes. The Huawei data center NetEco management system is compatible with
equipment from multiple vendors.
113
114
Telecom Energy
Smart PV Plant
Smart PV Controller
Smart Array Controller
Smart PV Management System