Geotechnical Design: Worked Examples
Geotechnical Design: Worked Examples
Worked examples
Worked examples presented at the Workshop Eurocode 7: Geotechnical Design
Dublin, 13-14 June, 2013
Support to the implementation, harmonization and further development of the Eurocodes
Authors:
Andrew J. Bond, Bernd Schuppener,
Giuseppe Scarpelli, Trevor L.L. Orr
Editors:
Silvia Dimova, Borislava Nikolova, Artur V. Pinto
European Commission
Joint Research Centre
Institute for the Protection and Security of the Citizen
Contact information
Address: Joint Research Centre, Via Enrico Fermi 2749, TP 480, 21027 Ispra (VA), Italy
E-mail: [email protected]
Tel.: +39 0332 78 9989
Fax: +39 0332 78 9049
http://ipsc.jrc.ec.europa.eu/
http://www.jrc.ec.europa.eu/
Legal Notice
Neither the European Commission nor any person acting on behalf of the Commission
is responsible for the use which might be made of this publication.
Europe Direct is a service to help you find answers to your questions about the European Union
Freephone number (*): 00 800 6 7 8 9 10 11
(*) Certain mobile telephone operators do not allow access to 00 800 numbers or these calls may be billed.
A great deal of additional information on the European Union is available on the Internet.
It can be accessed through the Europa server http://europa.eu/.
JRC 85029
EUR 26227 EN
ISBN 978-92-79-33759-8
ISSN 1831-9424
doi: 10.2788/3398
Luxembourg: Publications Office of the European Union, 2013
European Union, 2013
Reproduction is authorised provided the source is acknowledged.
Printed in Italy
TABLE OF CONTENTS
CHAPTER 4...33
Retaining structures I
ii
iii
iv
vi
Borislava NIKOLOVA
Artur V. PINTO
Andrew J. BOND,
Bernd SCHUPPENER,
Trevor L.L.ORR
Trinity College,
TC250/SC7/EG3)
Dublin,
Ireland
(Convenor
of
Bernd SCHUPPENER,
Andrew J. BOND,
Trinity College,
TC250/SC7/EG3)
Dublin,
Ireland
(Convenor
of
Bernd SCHUPPENER,
vii
Giuseppe SCARPELLI,
ANNEX -
Trevor L.L.ORR
Trinity College,
TC250/SC7/EG3)
Dublin,
Ireland
(Convenor
of
Andrew J. BOND,
Worked examples
Andrew J. BOND,
Bernd SCHUPPENER,
Giuseppe SCARPELLI,
Trevor L.L.ORR
Trinity College,
TC250/SC7/EG3)
Silvia DIMOVA
Borislava NIKOLOVA
Artur V. PINTO
Dublin,
Ireland
(Convenor
of
Editors
viii
CHAPTER 1
Foreword
Foreword
S.Dimova, B.Nikolova, A.Pinto, A.J.Bond
Foreword
S.Dimova, B.Nikolova, A.Pinto, A.J.Bond
The construction sector is of strategic importance to the EU as it delivers the buildings and
infrastructure needed by the rest of the economy and society. It represents more than 10% of EU
GDP and more than 50% of fixed capital formation. It is the largest single economic activity and it is
the biggest industrial employer in Europe. The sector employs directly almost 20 million people.
Construction is a key element not only for the implementation of the Single Market, but also for other
construction relevant EU Policies, e.g. Sustainability, Environment and Energy, since 40-45% of
Europes energy consumption stems from buildings with a further 5-10% being used in processing
and transport of construction products and components.
The EN Eurocodes are a set of European standards which provide common rules for the design of
construction works, to check their strength and stability against live extreme loads such as fire and
earthquakes. In line with the EUs strategy for smart, sustainable and inclusive growth (EU2020),
Standardization plays an important part in supporting the industrial policy for the globalization era.
The improvement of the competition in EU markets through the adoption of the Eurocodes is
recognized in the "Strategy for the sustainable competitiveness of the construction sector and its
enterprises" - COM (2012)433, and they are distinguished as a tool for accelerating the process of
convergence of different national and regional regulatory approaches.
With the publication of all the 58 Eurocodes Parts in 2007, the implementation of the Eurocodes is
extending to all European countries and there are firm steps toward their adoption internationally. The
Commission Recommendation of 11 December 2003 stresses the importance of training in the use of
the Eurocodes, especially in engineering schools and as part of continuous professional development
courses for engineers and technicians, which should be promoted both at national and international
level. It is recommended to undertake research to facilitate the integration into the Eurocodes of the
latest developments in scientific and technological knowledge.
In light of the Recommendation, DG JRC is collaborating with DG ENTR and CEN/TC250 Structural
Eurocodes and is publishing the Report Series Support to the implementation, harmonization and
further development of the Eurocodes as JRC Scientific and Policy Reports. This Report Series
includes, at present, the following types of reports:
1.
Policy support documents Resulting from the work of the JRC in cooperation with partners
and stakeholders on Support to the implementation, promotion and further development of
the Eurocodes and other standards for the building sector;
2.
Technical documents Facilitating the implementation and use of the Eurocodes and
containing information and practical examples (Worked Examples) on the use of the
Eurocodes and covering the design of structures or its parts (e.g. the technical reports
containing the practical examples presented in the workshop on the Eurocodes with worked
examples organized by the JRC);
3.
Pre-normative documents Resulting from the works of the CEN/TC250 and containing
background information and/or first draft of proposed normative parts. These documents can
be then converted to CEN technical specifications
4.
5.
Editorial work for this Report Series is assured by the JRC together with partners and stakeholders,
when appropriate. The publication of the reports type 3, 4 and 5 is made after approval for publication
from the CEN/TC250 Co-ordination Group.
Foreword
S.Dimova, B.Nikolova, A.Pinto, A.J.Bond
The publication of these reports by the JRC serves the purpose of implementation, further
harmonization and development of the Eurocodes. However, it is noted that neither the Commission
nor CEN are obliged to follow or endorse any recommendation or result included in these reports in
the European legislation or standardization processes.
This report is part of the so-called Technical documents (Type 2 above) and contains a
comprehensive description of the practical examples presented at the workshop Geotechnical design
with the Eurocodes with emphasis on worked examples. The workshop was held on 13-14 June
2013 in Dublin, Ireland and was co-organized with CEN/TC250/Sub-Committee 7, the Ireland's
Department of the Environment, Community and Local Government, with the support of CEN and the
Member States. The workshop addressed representatives of public authorities, national
standardisation bodies, research institutions, academia, industry and technical associations involved
in training on the Eurocodes. The main objective was to facilitate training on Eurocode 7 related to
geotechnical design through the transfer of knowledge and training information from the Eurocode 7
writers (CEN/TC250 Sub-Committee 7) to key trainers at national level and Eurocode users.
The workshop was a unique occasion to compile a state-of-the-art training kit comprising the slide
presentations and technical papers with the worked examples for encompassing the most important
practical cases of geotechnical design. The present JRC Report compiles all the technical papers and
worked examples prepared by the workshop lecturers. The editors and authors have sought to
present useful and consistent information in this report. However, it must be noted that the report
does not present complete design examples and that the reader may identify some discrepancies
between chapters. The chapters presented in the report have been prepared by different authors and
are reflecting the different practices in the EU Member States. Users of information contained in this
report must decide themselves of its suitability for the purpose for which they intend to use it.
We would like to gratefully acknowledge the workshop lecturers and the members of CEN/TC250
Sub-Committee 7 for their contribution in the organization of the workshop and development of the
training material comprising the slide presentations and technical papers with the worked examples.
We would also like to thank the Ireland's Department of the Environment, Community and Local
Government, and especially John Wickham for the help and support in the local organization of the
workshop.
All the material prepared for the workshop (slides presentations and JRC Report) is available to
download from the Eurocodes: Building the future website (http://eurocodes.jrc.ec.europa.eu).
CHAPTER 2
Basis of design
Basis of design
A.J.Bond and B.Schuppener
Basis of design
A.J.Bond and B.Schuppener
2.1. Overview
The Eurocode family of design standards is illustrated in Figure 2.1.1 (after Bond & Harris, 2008). It
comprises:
o
Fig. 2.1.1 Eurocode family of design standards (after Bond and Harris, 2008)
Basis of design
A.J.Bond and B.Schuppener
In order to establish minimum requirements for the extent and content of geotechnical
investigations, calculations and construction control checks, the complexity of each
geotechnical design shall be identified together with associated risks EN 1997-1 2.1(8)P
a distinction shall be made between light and simple structures and small earthworks
for which ... the minimum requirements will be satisfied by experience and qualitative
geotechnical investigations, with negligible risk; [and] other geotechnical structures EN
1997-1 2.1(8)P continued
For structures and earthworks of low geotechnical complexity and risk, such as defined
above, simplified design procedures may be applied EN 1997-1 2.1(9)
Design requirements
Design procedure
Conventional types of
structure & foundation
with no exceptional
risk or difficult soil or
loading conditions
Structures or parts of
structures not covered
above
GC
Examples of structures in Geotechnical Category 2 include: spread, raft, and pile foundations; walls
and other structures retaining or supporting soil or water; excavations; bridge piers and abutments;
embankments and earthworks; ground anchors and other tie-back systems; and tunnels in hard, nonfractured rock and not subjected to special water tightness or other requirements.
Examples of structures in Geotechnical Category 3 include: very large or unusual structures;
structures involving abnormal risks, or unusual or exceptionally difficult ground or loading conditions;
Basis of design
A.J.Bond and B.Schuppener
structures in highly seismic areas; and structures in areas of probable site instability or persistent
ground movements that require separate investigation or special measures.
Less severe values of the partial factors recommended in Annex A of EN 1997-1 may be used for
temporary structures or transient design situations when the likely consequences justify it (EN 1997-1
2.4.7.1 (5)).
Table 2.3.1 summarizes the classification of actions according to EN 1990:
Table 2.3.1 Classification of actions
Action
Permanent
Variable
Accidental
Duration
Variation with
time
Examples
Likely to act
throughout
reference
period
Negligible or
monotonic
Neither negligible
nor monotonic
Significant
magnitude
Usually short
Basis of design
A.J.Bond and B.Schuppener
o
Use of calculations
An observational method
Design by calculation is illustrated in Figure 2.4.1 (after Bond & Harris, 2008).
where Ed = the design effect of actions and Rd = the corresponding design resistance (see EN 1997-1
exp. 2.5).
This expression applies to the following ultimate limit states:
o
GEO: Failure or excessive deformation of the ground, in which the strength of soil or rock
is significant in providing resistance
Bond and Harris (2008) recommend using the ratio of the design effect of actions to the
corresponding resistance to verify GEO:
GEO
Ed
100%
Rd
10
Basis of design
A.J.Bond and B.Schuppener
Frank et. al. (2004) define the ratio of the design resistance to the corresponding design effect of
actions:
ODF
Rd
1,0
Ed
Fig. 2.4.2 National choice of Design Approach for shallow foundations (after Bond, 2013)
11
Basis of design
A.J.Bond and B.Schuppener
Fig. 2.4.3 National choice of Design Approach for slopes (after Bond, 2013)
Verification of static equilibrium is expressed in Eurocode 7 by:
Edst ;d Estb;d Td
where Edst;d = the design value of the effect of destabilising actions; Estb;d = the design value of the
effect of stabilizing actions; and Td = the design value of any stabilizing shear resistance of the ground
or of structural elements.
This expression applies to the following ultimate limit state:
o
EQU: Loss of equilibrium of the structure or the ground considered as a rigid body, in which
the strengths of structural materials and the ground are insignificant in providing resistance
where Ed = design effect of actions (e.g. displacement, distortion) and Cd = design constraint (i.e.
limiting value of design effect). According to EN 1990, partial factors should normally be taken
equal to 1,0.
12
Basis of design
A.J.Bond and B.Schuppener
Complexity of design
Prescriptive measures
Calculation
Observation or testing
Limit states
o
Overall stability
References
Bond, A. J. (2013). Implementation and evolution of Eurocode 7, Modern Geotechnical Design Codes
of Practice, Arnold et al. (eds), Amsterdam: IOS Press, pp3-14.
Bond, A. J., and Harris, A. J. (2008). Decoding Eurocode 7, London: Taylor & Francis, 598pp.
EN 1997-1: 2004. Eurocode 7: Geotechnical design. Part 1: General rules. CEN.
Frank, R., Bauduin, C., Kavvadas, M., Krebs Ovesen, N., Orr, T., and Schuppener, B. (2004).
Designers guide to EN 1997-1: Eurocode 7: Geotechnical design General rules, London:
Thomas Telford.
Frank, R., Schuppener, B., Vogt, N., Weienbach, A. (2007), Verification of ultimate limit states in
geotechnical design in France and Germany, Revue europenne de gnie civil, vol. 11, n 5, Mai
2007, p. 621-641, France.
13
Basis of design
A.J.Bond and B.Schuppener
14
CHAPTER 3
Shallow foundations
Shallow foundations
G.Scarpelli and T.L.L.Orr
16
Shallow foundations
G.Scarpelli and T.L.L.Orr
3.1. Scope
This chapter deals with the geotechnical design of spread foundations according to Eurocode 7.
Section 6 of Eurocode 7 Part 1 presents the different aspects to be considered for designing shallow
foundations of buildings, bridges, walls, isolated columns etc. It applies to pad, strip, and raft
foundations and some provisions may be applied to deep foundations, such as caissons.
Section 6 is organized in the following subsections:
6.1. General
6.2. Limit states
6.3. Actions and design situations
6.4. Design and construction considerations
6.5. Ultimate limit state design
6.6. Serviceability limit state design
6.7. Foundations on rock; additional design considerations
6.8. Structural design of foundations
6.9. Preparation of the subsoil
Moreover, Eurocode 7 has the following five informative annexes that are specifically referred to in
Section 6 in relation to shallow foundation design that give useful information and guidance about
bearing resistance calculation, limiting values of structural deformations for serviceability of
constructions and foundation movements:
D. A sample analytical method for bearing resistance calculation;
E. A sample semi-empirical method for bearing resistance estimation;
F. Sample methods for settlement evaluation;
G. A sample method for deriving presumed bearing resistance for spread foundations on rock;
H. Limiting values of structural deformation and foundation movement.
failure by sliding
excessive settlements
17
Shallow foundations
G.Scarpelli and T.L.L.Orr
o
unacceptable vibrations
18
Shallow foundations
G.Scarpelli and T.L.L.Orr
Fig.3.2.2 Selection of the depth of a shallow foundation (from Bond & Harris, 2008)
It is clear that most of the foundation problems can be anticipated and avoided if the depth of a
foundation is appropriately selected. One of the design methods given in Error! Reference source
not found. shall be used to analyze the limit states for shallow foundations.
Table 3.2.1 Methods to analyze limit states (after Bond & Harris, 2008)
Method
Description
Constraints
Direct
Indirect
Prescriptive
Ed Rd
For serviceability limit state designs the inequality to be checked is:
Ed Cd
19
Shallow foundations
G.Scarpelli and T.L.L.Orr
where Ed is the design value of the effect of the actions, for example the settlement, calculated using
partial factors of unity, and Cd is the limiting value of the effect of an action, for example the limiting
value of the structural deformation or foundation movement as values given in Annex H, EN 1997-1.
Representation of the design action:
Ed Gj Gkj Q1Qk 1
j 1
i 1
Qi
0i Qki
where:
Gkj = characteristic permanent loads
Qki = characteristic variable loads
where:
Frep = representative value of actions
Xk = characteristic value of geotechnical parameters
ad = design value of geometrical data
M = partial factors for geotechnical parameters
R = partial factors for resistances
Symbol
Set
R,e
20
R1
R2
R3
1,0
1,1
1,0
Shallow foundations
G.Scarpelli and T.L.L.Orr
DA1 Combination 1:
A1 + M1 + R1
DA1 Combination 2:
A2 + M2 + R1
DA2:
A1+ M1+R2
DA3:
(A1 or A2)* + M2 + R3
Symbol
Unfavourable
Permanent
Favourable
Unfavourable
Variable
Set
Favourable
A1
A2
1,35
1,0
1,0
1,0
1,5
1,3
Symbol
Set
R1
R2
R3
Bearing
Rv
1,0
1,4
1,0
Sliding
Rh
1,0
1,1
1,0
Symbol
Value
M1
M2
1,0
1,25
Effective cohesion
1,0
1,25
Undrained strength
cu
1,0
1,4
Unconfined strength
qu
1,0
1,4
Effective cohesion
1,0
1,4
Weight density
1,0
1,0
Shearing resistance
Whereas there is a general consensus on how Design Approaches 1 and 3 are applied for ULS
verifications, there are two ways of performing verifications according to Design Approach 2: partial
factors are either applied to the actions at the source, or to the effect of the actions, at the end of the
calculation.
21
Shallow foundations
G.Scarpelli and T.L.L.Orr
In the design approach referred to as DA-2, the partial factors are applied to the characteristic actions
right at the start of the calculation and design values are then used. In the design approach referred to
as DA-2*, the entire calculation is performed with characteristic values and the partial factors are
introduced only at the end when the ultimate limit state condition is checked.
The resulting designs can be very different since for DA-2 the effective foundation breadth B and
length L (that is B = B-2e and L = L-2e) are governed by what is called the design value of
eccentricity, ed whereas for DA-2* the characteristic value of eccentricity, ek is used. The following
Error! Reference source not found..1 clarifies why ed >> ek.
Vd Rd
where Vd is the design action. Vd should include the self-weight of the foundation and any backfill on
it.
The design action, Vd includes both variable and permanent vertical loads; this latter includes all the
actions shown in Error! Reference source not found.3.2 which are:
a)
b)
Weight of foundation
c)
d)
e)
Uplift
22
Shallow foundations
G.Scarpelli and T.L.L.Orr
1 cot '
Ng 2 Nq 1 tan '
sc, sq, s
ic, iq, i
A = BL
effective foundation area (reduced area with load acting at its centre)
Eurocode 7 in 6.5.4 requires that special precautions be taken when the eccentricity of the loading
exceeds 1/3 of the width of a rectangular; i.e. when eB exceeds B/3 or eL exceeds L/3. It should be
noted that this is not the middle third rule, which requires the eccentricity not to exceed B/6 or L/6 so
as to avoid a gap forming between the foundation and the soil if the soil behaves as a purely elastic
material. A special precaution to be taken in the case of large load eccentricities is the inclusion of
tolerances of up to 0,10 m in the dimensions of the foundation.
23
Shallow foundations
G.Scarpelli and T.L.L.Orr
m=mB= [2+(B/L)]/[1+(B/L)]
m=mL= [2+(L/B)]/[1+(L/B)]
2
(rectangular shape)
sq= 1 + sin
(rectangular shape)
sg= 0,70
(rectangular shape)
24
Shallow foundations
G.Scarpelli and T.L.L.Orr
sc = 1,2
ic 0,5 1
1 H / ( Acu )
NOTE: For drained conditions, water pressures must be included as actions. The question then
arises, which partial factors should be applied to the weight of a submerged structure? Since the
water pressure acts to reduce the value of Vd, it may be considered as favourable, while the total
weight is unfavourable. Physically however, the soil has to sustain the submerged weight. For the
design of structural members, water pressure may be unfavourable.
NOTE: As the eccentricity influences the effective base dimensions it may be necessary to analyze
different load combinations, by considering the permanent vertical load as both favourable and
unfavourable and by changing the leading variable load.
Hd= Qh Qhk
G=1,35;
Qh=1,5
Qv=1,5;
Vunfavourable Hunfavourable
Vd= G Gk+ Qv Qvk ;
Hd= Qh 0 Qhk
G=1,35;
Qh=1,5
Qv=1,5;
Vfavourable Hunfavourable
Vd= G Gk+Qv Qvk
Hd= Qh Qhk
G=1,00;
Qv=0,0;
Qh=1,5
25
Shallow foundations
G.Scarpelli and T.L.L.Orr
where Rp,d is the contribution to resistance due to passive thrust that may develop in front of the
foundation.
For drained conditions the design shear resistance, Rd, shall be calculated either by factoring the
ground properties or the ground resistance as follows:
Rd = V'd tan d or Rd = (Vd tan k) / Rh
Normally it is assumed that the soil at the interface with concrete is remolded. So the design friction
angle d may be assumed equal to the design value of the effective critical state angle of shearing
resistance, 'cv,d, for cast-in-situ concrete foundations and equal to 2/3 'cv,d for smooth precast
foundations.
26
Shallow foundations
G.Scarpelli and T.L.L.Orr
The following three components of settlement have to be considered:
o
s0: immediate settlement; for fully-saturated soil due to shear deformation at constant volume
and for partially-saturated soil due to both shear deformation and volume reduction;
Fig.3.3.6 Definitions for checking SLS from Annex H of EN 1997-1 (after Bond and Harris,
2008)
Spread foundations and superstructures may suffer due to differential settlements and distortions.
The maximum acceptable relative rotations for open framed structures, frames and load bearing or
continuous brick walls are unlikely to be the same but range from about 1/2000 to about 1/300 to
prevent the occurrence of a serviceability limit state in the structure. A maximum relative rotation of
1/500 is acceptable for many structures. The relative rotation likely to cause an ultimate limit state is
about 1/150.
27
Shallow foundations
G.Scarpelli and T.L.L.Orr
For normal structures with isolated foundations, total settlements up to 50 mm are often acceptable.
Larger settlements may be acceptable provided the relative rotations remain within acceptable limits
and provided the total settlements do not cause problems with the services entering the structure, or
cause tilting etc. Acceptable limits for structural deformations are given in the following Table 3..
Table 3.4.1 Limiting deformations and damages of constructions
Type of structure
Type of damage/concern
Criterion
Limiting value(s)
Structural damage
Angular distortion
1/150-1/250
Angular distortion
1/500
Visual appearance
Tilt
1/300
Connection to services
Total settlement
50-75mm (sands)
75-135mm (clays)
Tall buildings
1/1200-1/2000
Structures with
unreinforced load
bearing walls
Cracking by sagging
Deflection ratio
1/2500 (L/H=1)
1/1250 (L/H=5)
Cracking by hogging
Deflection ratio
1/5000 (L/H=1)
1/2500 (L/H=5)
Bridges - general
Ride quality
Total settlement
100mm
Structural distress
Total settlement
63mm
Function
Horizontal movement
38mm
Structural damage
Angular distortion
1/250
Structural damage
Angular distortion
1/200
Deterministic: solve the soil-foundation interaction problem and deduce stresses and
deformations of the foundation (by using numerical methods with FEM or subgrade reaction
models)
28
Shallow foundations
G.Scarpelli and T.L.L.Orr
3.4.3. SLS ULS CHECK BY USING INDIRECT METHODS (SEE TABLE 3.4.1)
Terzaghi & Peck charts (1967) offer an example of using indirect methods for foundation design.
Charts give allowable bearing capacity for granular soils and a shallow foundation as a function of the
embedment ratio (D/B), foundation breadth B and corrected blow count N from SPT tests. The
allowable pressure values imply a settlement less than 25 mm.
The graphs of allowable bearing pressures against foundation width, B in Fig.3., which increase
linearly for small B values and then become constant above a certain B value, show that the
controlling limit state for pad foundations changes from bearing failure (ULS) for small B values to
excessive settlement (SLS) for large B values.
29
Shallow foundations
G.Scarpelli and T.L.L.Orr
Fig.3.3.8 Allowable bearing pressures from Terzaghi & Peck (1967) for large B
The reason for this is because, when B becomes larger, as shown in Fig.3.3.9 , the allowable bearing
pressure must reduce to keep the settlements below the assumed maximum value of 25 mm.
The Terzaghi & Peck design charts demonstrate how in practice foundation design can be governed
either by ULS or by SLS limit states. A sound foundation design shall always be based on both
checks; the calibration of partial factors in EC7 is such that the ULS and SLS are appropriately
balanced for normal design situations.
Fig.3.3.9 Allowable bearing pressures from Terzaghi & Peck (1967) for large B
vertical axis: applied vertical pressure (t/ft ); horizontal axis: breadth of the foundation, B (ft)
30
Shallow foundations
G.Scarpelli and T.L.L.Orr
Eurocode 7 does not provide new methods for the designing spread foundations
The design of spread foundations always implies the execution of a sound geotechnical
investigation, the selection of the most appropriate geotechnical model and characteristic
values of geotechnical parameters
The first step in the design of a spread foundation is to fix the required performance of the
construction and to select foundation geometry and embedment
Ultimate and serviceability limit state checks can be carried out using commonly recognized
procedures
Eurocode 7 provides recommended values of partial factors for ULS and SLS verifications.
The particular values to be used in a country are given in that countrys National Annex
References
Bjerrum, L. (1963), "Allowable Settlement of Structures," Proc., European Conf. on Soil Mech. and
Found. Engr., Weisbaden, Germany, Vol. 3, pp. 135-137.
Bond, A. J., and Harris, A. J. (2008). Decoding Eurocode 7, London: Taylor & Francis, 618pp.
EN 1997-1: 2004. Eurocode 7: Geotechnical design. Part 1: General rules. CEN.
Frank, R., Bauduin, C., Kavvadas, M., Krebs Ovesen, N., Orr, T., and Schuppener, B. (2004).
Designers guide to EN 1997-1: Eurocode 7: Geotechnical design General rules, London:
Thomas Telford.
Terzaghi, K & Peck, R B (1967) Soil mechanics in engineering practice 2nd Ed. Pub. John Wiley&
Sons
31
Shallow foundations
G.Scarpelli and T.L.L.Orr
32
CHAPTER 4
Retaining structures I
Retaining structures I
A.J.Bond and B.Schuppener
34
Retaining structures I
A.J.Bond and B.Schuppener
4.1. Scope
This Chapter concentrates on the design of gravity walls, which are walls of stone or plain or
reinforced concrete having a base with or without a heel, ledge, or buttress. A key feature of these
walls is that the weight of the wall itself plays a significant role in the support of the retained material.
Examples include: concrete gravity walls; spread footing reinforced concrete walls; and buttress walls.
Embedded walls are discussed in Chapter 7.
Composite retaining structures are walls composed of elements of the above two types (gravity and
embedded). Examples include: double sheet pile wall cofferdams; earth structures reinforced by
tendons, geotextiles, or grouting; structures with multiple rows of ground anchorages or soil nails.
Parts of this chapter will be relevant to the design of composite walls.
Section 9 of EN 1997-1 applies to retaining structures supporting ground (i.e. soil, rock or backfill)
and/or water and is sub-divided as follows:
9.1. General (6 paragraphs)
9.2. Limit states (4)
9.3. Actions, geometrical data and design situations (26)
9.4. Design and construction considerations (10)
9.5. Determination of earth pressures (23)
9.6. Water pressures (5)
9.7. Ultimate limit state design (26)
9.8. Serviceability limit state design (14)
Many provisions from EN1997-1, Section 6 Spread foundations (discussed in Chapter 3) also apply
to gravity walls.
Annex C of Eurocode 7, Part 1 Sample procedures to determine earth pressures provides
informative text relevant to retaining structures and is sub-divided as follows:
1. Limit values of earth pressure (3 paragraphs)
2. Analytical procedure for obtaining limiting active and passive earth pressures (14)
3. Movements to mobilise earth pressures (4)
35
Retaining structures I
A.J.Bond and B.Schuppener
Hd Hnom H
where Hd = design height of wall; Hnom = nominal height of wall; and H = allowance for unplanned
excavation. Table 4.2.1 below gives the recommended values of H with normal site control in place.
Table 4.2.1 Recommended values of H
Wall type
Cantilever
Supported
Eurocode 7s recommendations regarding water levels behind retaining walls distinguish between
design situations with and without reliable drainage. When the wall retains medium or low permeability
(i.e. mainly fine) soils, the wall should be designed for a water level above formation level.
o
Without reliable drainage, the water level should normally be taken at the surface of the
retained material.
With reliable drainage, the water level may be assumed to be below the top of the wall, but
there is then a maintenance requirement to ensure the drainage remains reliable.
One source of ambiguity in Eurocode 7 concerns whether water pressures should be factored or not.
For ultimate limit states (ULSs), EN 1997-1 states design values [of groundwater pressures] shall
represent the most unfavourable values that could occur during the design lifetime of the structure.
Whereas, for serviceability limit states (SLSs), it states design values shall be the most unfavourable
values which could occur in normal circumstances [EN 1997-1 2.4.6.1(6)P]. Although the first of
these statements is easy to interpret, it is not clear what normal circumstances are.
Furthermore, EN 1997-1 goes on to say design values of ground-water pressures may be derived
either by applying partial factors to characteristic water pressures or by applying a safety margin to
the characteristic water level [EN 1997-1 2.4.6.1(8)].
36
Retaining structures I
A.J.Bond and B.Schuppener
Bond and Harris (2008) discuss the ways in which this Application Rule has been interpreted by
practising engineers Fig.4.4.3 summarizes some of the more common interpretations.
Fig.4.4.3
a)
b)
c)
d)
e)
Possible ways of treating water pressures (after Bond & Harris, 2008)
Design water levels for ULS and SLS design situations
Characteristic water pressures for SLS design situation
Design pressures for ULS with no factor applied (= 1,0)
with the factor on permanent actions (G = 1,35) applied
with the factor on permanent actions (G = 1,35) applied to the
normal water level and the factor on variable actions (Q = 1,5)
applied to any rise in water level
f) with the factor on variable actions (Q = 1,5) applied throughout
Instinctively, many geotechnical engineers consider it wrong to apply partial factors to water
pressures, particularly when the density of groundwater is known to a reasonable accuracy. However,
the failure to apply partial factors because of their unreasonableness can lead to design situations
that are under-designed and may even be unsafe. Because of this, Bond and Harris (2008)
recommend a balanced approach to the issue, summarized as follows:
o
When partial factors G > 1,0 are applied to effective earth pressures, then pore water
pressures should also be multiplied by G > 1,0 but calculated from highest normal (i.e.
serviceability) water levels i.e. no safety margin is applied
When partial factors G = 1,0 are applied to effective earth pressures, then pore water
pressures should be multiplied by G = 1,0 but calculated from highest possible (i.e. ultimate)
water levels after an appropriate safety margin has been applied
Fig.4.2.4 illustrates these two design situations. Further clarification of how water pressures should
be handled is planned to be included in the next version of Eurocode 7, tentatively planned for 20182020.
Fig.4.2.4 Recommended treatment of water pressures for design (after Bond & Harris, 2008)
37
Retaining structures I
A.J.Bond and B.Schuppener
DA1
DA2
DA3
Combination
2*
Partial factors
applied to:
Actions
Material
properties
Actions and
resistance
Effects of
actions and
resistance
Structural
actions and
resistance
Partial factor
Sets*
A1+M1+R1**
A2+M2+R1**
A1+M1+R2**
A1+M1+R2**
A1/A2+M2+R3**
Fig.4.3.1 National choice of Design Approach for retaining walls (after Bond, 2013)
The values of the partial factors that are recommended by EN 1997-1 for Design Approach 1
Combinations 1 and 2 (DA1-1 and DA1-2) are summarized in Table 4.3.2 below.
38
Retaining structures I
A.J.Bond and B.Schuppener
Table 4.3.2 Partial factors for Design Approach 1
Parameter
Symbol
DA1-1
A1
M1
DA1-2
R1
A2
Unfavourable
1,35
Favourable
(G,fav)
1,0
Unfavourable
1,5
1,3
Favourable
(0)
(0)
cu
qu
Weight density ()
Rv
Rh
Re
M2
R1
1,0
1,25
1,0
1,4
1,0
1,0
1,0
The values of the partial factors that are recommended by EN 1997-1 for Design Approaches 2 and 3
(DA2 and DA3) are summarized in Table 4.3.3 below.
Table 4.3.3 Partial factors for Design Approaches 2 and 3
Parameter
Symbol
DA2/DA2*
A1
Permanent
action (G)
Variable
(Q)
action
Unfavourable
1,35
Favourable
(G,fav)
1,0
Unfavourable
1,5
Favourable
(0)
cu
qu
Weight density ()
Rv
M1
DA3
R2
A1
A2*
1,35
1.0
1,5
1.3
M2
R3
(0)
1,25
1,0
1,4
1,0
1,4
39
1,0
Retaining structures I
A.J.Bond and B.Schuppener
Parameter
Symbol
DA2/DA2*
A1
Rh
M1
DA3
R2
A1
A2*
M2
R3
1,1
1,4
Re
1,1
Fig.4.4.1 Pressures on a reinforced concrete wall (after Bond & Harris, 2008)
Care must be taken in choosing the values of the partial factors that are applied to the various
pressures acting on the wall:
o
The surcharge (q) behind the wall which extends to the wall face should be considered an
unfavourable action for the verification of bearing capacity; but it is a favourable action with
regards to resisting overturning and sliding and hence should be curtailed at the virtual place
in these design situations
The uplift from the water pressure beneath the wall base appears, at first glance, to be a
favourable action for verification of bearing pressure. However, since the source of this water
40
Retaining structures I
A.J.Bond and B.Schuppener
pressure is the same as that of the thrust Ua, for compatibility it should be regarded as
unfavourable (this is known as the single source principle)
Annex C of EN 1997-1 (+Corrigendum 1) gives expressions for active and passive earth pressures:
a Ka dz q u 2c Ka (1 a / c ) u
0
p K p dz q u 2c K p (1 a / c ) u
0
where
where
Ka, = active earth pressure coefficient for inclined thrust (= / v);
Ka
1 sin
1 sin
For the design of the wall stem, it may be necessary to assume at-rest conditions prevail behind the
wall, in which case the at-rest earth pressures coefficient K0 should be used instead of Ka:
41
Retaining structures I
A.J.Bond and B.Schuppener
For normally consolidated soil, assume at rest conditions if movement of structure is less than 0,05%
of the retained height. This expression is a combination of Meyerhofs equation for K0 and Kezdis
modification for sloping ground.
Fig.4.4.2 Pressures on a mass gravity wall (after Bond & Harris, 2008)
The earth pressures that act on the back face of the wall may be determined using the charts given in
Annex C of EN 1997-1, which are were developed by (but are not attributed to) Kerisel and Absi. They
are the same charts as appear in BS 8002. Kerisel and Absi assumed log-spiral failure surfaces and
hence their charts give upper bound values of Ka and Kp. The charts can only be used for walls with
vertical back faces. If the back face is inclined, then the following expressions developed by Brinch
Hansen (also given in Annex C of En 1997-1) may be used:
a Ka dz u Kaq q Kac c; p K p dz u K pq q K pc c
0
Ka
Kaq
Kac
2
K n cos cos ;
K n cos ;
K n 1 cot
K p
K pq
K pc
Kn
sin
1 sin
2mt cos1
;2mw cos
sin
sin
Bond and Harris (2008) have published charts (for vertical walls only) that make these expressions
easy to evaluate. Fig.4.4.3 shows one of these charts.
42
Retaining structures I
A.J.Bond and B.Schuppener
Fig.4.4.3 Chart showing Brinch Hansens passive earth pressure coefficient (after Bond &
Harris, 2008)
Ed Cd
where
Ed = design effect of actions (e.g. displacement, distortion);
Cd = design value of the appropriate constraint (i.e. limiting value of the design effect of actions).
For conventional structures founded on clays, Eurocode 7 allows settlement calculations to be
avoided if an ultimate limit state calculation for bearing resistance satisfies:
Ek
Rk
R,SLS
43
Retaining structures I
A.J.Bond and B.Schuppener
where
Ek = characteristic effects of actions;
Rk = characteristic resistance;
R,SLS = a partial resistance factor 3,0. (Note: this expression does not appear in EN 1997-1, but
can be deduced from its text.)
Verification of the serviceability of gravity walls is similar to that of shallow foundations see Chapter
3 for details.
Verification of ground conditions and of the location and general lay-out of the structure
Movements, yielding, stability of excavation walls and base; temporary support systems;
effects on nearby buildings and utilities; measurement of soil pressures on retaining
structures and of pore-water pressure variations resulting from excavation or loading
Annex J also lists items that need to be considered with regards to water flow and pore-water
pressures, including:
o
Finally, Annex J lists items that need to be considered as part of performance monitoring:
o
Settlement at established time intervals of buildings and other structures including those due
to effects of vibrations on metastable soils
Lateral displacement and distortions, especially those related to fills and stockpiles; soil
supported structures, such as buildings or large tanks; deep trenches
Water tightness
44
Retaining structures I
A.J.Bond and B.Schuppener
No specific guidance is given in EN 1997-1 for maintenance.
Vd Rd
Hd Rd Rpd
References
Bond, A. J. (2013). Implementation and evolution of Eurocode 7, Modern Geotechnical Design Codes
of Practice, Arnold et al. (eds), Amsterdam: IOS Press, pp3-14.
Bond, A. J., and Harris, A. J. (2008). Decoding Eurocode 7, London: Taylor & Francis, 618pp.
EN 1997-1: 2004. Eurocode 7: Geotechnical design. Part 1: General rules. CEN.
45
Retaining structures I
A.J.Bond and B.Schuppener
46
CHAPTER 5
48
5.1. Overview
Ground investigation and testing for geotechnical design is covered by EN 1997-2 (2004). EN 1997-2
is intended to be used in conjunction with EN 1997-1 and provides rules relating to:
o
general requirements for a number of commonly used laboratory and field tests
EN 1997-1 covers the establishment of characteristic values. As they are based on ground
investigations, the provisions for their determination will therefore also be explained in this chapter.
EN 1997-2 is mainly a standard for the geotechnical engineer and experts for soil and rock testing.
Only a small part of the standard is for the designer. This chapter will be restricted to those items
which are important for the designer.
Its importance for the designer is stressed in EN 1997-1 (2004), 2.4.1 (2) It should be considered
that knowledge of the ground conditions depends on the extent and quality of the geotechnical
investigations. Such knowledge and the control of workmanship are usually more significant to
fulfilling the fundamental requirements than is precision in the calculation models and partial factors.
EN 1997-2 has the following contents:
1. General
2. Planning of ground investigations
3. Soil and rock sampling and groundwater measurements
4. Field tests in soil and rock
5. Laboratory tests on soil and rock
6. Ground investigation report
with 23 Annexes.
EN 1997-2 only gives the general requirements for the field and laboratory tests; their execution is
standardized in separate EN ISO standards:
o
CEN ISO/TS (specifications) 17892 with 12 parts for standard laboratory tests
EN ISO 14688 and EN ISO 14689 specify the identification of soil and rock, while EN ISO 22475
standardizes sampling and groundwater measurements.
5.2. Definitions
In 1.5.3.1 of EN 1997-2 (2004), the definition of the term derived value is introduced as a value of a
geotechnical parameter obtained from test results by theory, correlation or empiricism. To distinguish
it from a characteristic value of a geotechnical parameter, the derived value is explained by the chart
presented in Fig.5.2.1. The process of evaluation test results starts with the numerical results of
different field and laboratory tests. The basis for the evaluation of all tests is a theory and for some
of them corrections and correlations have to be applied. This process is described in EN 1997-2.
The next step is the selection of characteristic values of geotechnical properties, taking into account:
o
49
information from other sources on the site, the soils and rock
Fig.5.2.1 General framework for the selection of derived and characteristic values of
geotechnical properties (after EN 1997-2)
for high-rise and industrial structures, a grid pattern with points at 15 m to 40 m distance
for large-area structures, a grid pattern with points at not more than 60 m distance
50
for linear structures (roads, railways, channels, pipelines, dikes, tunnels, retaining walls), a
spacing of 20 m to 200 m
for special structures (e.g. bridges, stacks, machinery foundations), two to six investigation
points per foundation
In this annex also investigation depths are given for the most common geotechnical structures. For
example for a pile foundation (see Figure 5.2.2) the following three conditions for the investigation
depth za should be met:
o
za 1,0bg
za 5,0 m
za 3DF
where DF is the pile base diameter; and bg is the smaller side of the rectangle circumscribing the
group of piles forming the foundation at the level of the pile base.
51
particle size
water content
water content
B
C
The annexes give valuable information on the evaluation of some field tests, for example see Table
5.3.2 for the cone penetration test.
52
Effective angle of
shearing
resistance, (')
Drained Young's
modulus, (E)
MPa
Very loose
Loose
Medium dense
Dense
Very dense
0,0 2,5
2,5 5,0
5,0 10,0
10,0 20,0
> 20,0
29 32
32 35
35 37
37 40
40 42
< 10
10 20
20 30
30 60
60 90
The annexes give valuable information on the evaluation of some laboratory tests, for example see
Table 5.3.3 for the incremental oedometer test.
Table 5.3.3 Incremental oedometer test. Recommended minimum number of tests for one soil
stratum (after EN 1997-2)
Variability in oedometer modulus Eoed
Comparable experience
None
Medium
Extensive
One oedometer test and classification tests to verify compatibility with comparable
knowledge (see Q.1(2), Annex Q, En 1997-2).
53
X k X m 1 knVX
where
Xm is the arithmetic mean value of the test results;
Vx is the coefficient of variation;
kn is a statistical coefficient depending on the number n of test results, the selected probability for
the occurrence of Xk and whether the coefficient of variation Vx is known or not.
Values for kn can be found in tables of textbooks on statistics and also in some textbooks on soil
mechanics and ground engineering (see, for example, Bond and Harris, 2008, Bauduin, 2002).
Schneider (1999) proposed a much simpler formula for the derivation of the characteristic mean
value:
cu,m,k cu,m 0,5 scu
sampling
Field tests:
o
Laboratory tests:
o
54
statistical evaluation
References
Bauduin, Ch.: (2002): Determination of characteristic values, in Geotechnical Engineering Handbook,
Volume 1: Fundamentals, Editor: Ulrich Smoltczyk, Ernst & Sohn
Bond, A. J., and Harris, A. J. (2008). Decoding Eurocode 7, London: Taylor & Francis, 598pp.
EN 1997-1: 2004. Eurocode 7: Geotechnical design. Part 1: General rules. CEN.
EN 1997-2: 2004. Eurocode 7: Geotechnical design - Part 2: Ground investigation and testing. CEN.
Schneider, H. R.: (1999): Determination of characteristic soil properties, in Proceedings of the 12th
European Conference on Soil Mechanics and Foundation Engineering, Amsterdam, Balkema,
Rotterdam, 1999, Vol. 1, pp 273 - 281.
55
56
CHAPTER 6
58
6.1. Overview
EN 1997-1 has no separate section on slope stability. The provisions for the design of slopes and
embankments are contained in Section 11: Overall stability and Section 12: Embankments. The
provisions in Section 11 apply to the overall stability of and movements in the ground, whether natural
or fill, around foundations, retaining structures, natural slopes, embankments or excavations. The
provisions in Section 12 apply to embankments for small dams and for infrastructure
The provisions for the verification against hydraulic failure are covered in Section 10 of EN 1997-1.
The terms for the failure modes: uplift (UPL), hydraulic heave, internal erosion and piping (all three
abbreviated by HYD) are defined and the verification against these four failures described.
Retaining structures
Some examples of limit modes for overall stability of retaining structures, which are presented in
Section 9 of EN 1997-1, are shown in Fig.6.2.5.
59
DA1.C1
G = 1,35
Q = 1,5
cu = 1,0
DA1.C2
G = 1,0
Q= 1,3
cu = 1,4
For drained analyses, in the case of DA1.C1 an increase in the vertical load increases the resistance
on the shear plane since the shearing resistance is a function of the normal stress due to the soil
weight that is causing the instability, so that the margin of safety is unchanged. Thus DA1.C1 does
not usually govern. Hence in drained analyses, DA1.C2 governs and the DA1 partial factors are:
o
DA1.C2
G = 1,0
Q = 1,3
= 1,25
60
z
h
S lip p lan e
b co s
Sd Rd
Considering a column of soil of width b and weight W, the destabilising design sliding force is:
Sd GW sin G z b cos sin
G z b cos2 tan k M
Substituting for Sd and Rd in the equilibrium inequality and setting M = 1,25 for DA1.C2 gives:
61
For comparison, using previous global factor design method, the global factor of safety FOS was
given by:
FOS
tan
tan
Spencers method is acceptable because both moment and force equilibrium equations are
satisfied
Bishops Simplified method is acceptable because moment equilibrium is satisfied and, while
force equilibrium is not satisfied, the interslice forces are horizontal
Fellenius method is not acceptable because, while moment equilibrium is satisfied, forces
equilibrium is not and the interslice forces are not horizontal
Table 6.2.3 Equations of equilibrium satisfied in methods of slices (Krahn, 2004)
Method
Moment Equilibrium
Force Equilibrium
Ordinary or Fellenius
Yes
No
Bishops Simplified
Yes
No
Janbus Simplified
No
Yes
Spencer
Yes
Yes
Morgenstern-Price
Yes
Yes
Corps of Engineers 1
No
Yes
Corps of Engineers - 2
No
Yes
Lowe-Karafiath
No
Yes
Yes
Yes
Yes
Janbu Generalized
Sarma vertical slices
62
Interslice
Shear (X)
Ordinary or Fellenius
No
No
No interslice forces
Bishops Simplified
Yes
No
Horizontal
Janbus Simplified
Yes
No
Horizontal
Spencer
Yes
Yes
Constant
Morgenstern-Price
Yes
Yes
Corps of Engineers 1
Yes
Yes
Corps of Engineers - 2
Yes
Yes
Lowe-Karafiath
Yes
Yes
Janbu Generalized
Yes
Yes
Yes
Yes
X = C + Etan
Method
mob
tan k
c
tan
c
n
n
F
F
M ;mob
M ;mob
M ;mob
ck b GW G ub tan k sec
1
tan tan k
GW sin
1
M ;mob
In DA1.C1, G = 1,35 is applied to permanent actions, including the soil weight force via the soil
weight density, and Q = 1,5 is applied to variable actions when analysing the overall factor of safety,
F using the method of slices. Then it is checked that F, which is equal to M;mob, is greater than or
equal to 1,0.
In the case of DA1.C2, G = 1,0 is applied to permanent actions, including the soil weight force via the
soil weight density, and Q = 1,5 is applied to variable actions when analysing the overall factor of
safety, F using the method of slices. Then it is checked that F, which is equal to M;mob, is greater than
or equal to 1,25.
63
Observing the movements and specifying actions to reduce or stop them, if necessary (i.e.
use the Observational Method)
6.3. Embankments
6.3.1. SCOPE AND CONTENTS
EN 1997-1 12.1(1)P states that the provisions in Section 12 shall apply to embankments for small
dams and for infrastructure. However, no definition is given for the word small. According to Frank et
al. (2004), it may be appropriate to assume small dams include dams (and embankments for
infrastructure) up to a height of approximately 10 m.
Section 12 Embankments is the shortest section of EN 1997-1, being just over four pages long. It has
the following sub-sections:
6.
General (2 paragraphs)
7.
8.
9.
10.
11.
12.
Since embankments are constructed by placing fill and sometimes involve ground improvement, the
provisions on fill in Section 5 should be applied. For embankments on ground with low strength and
high compressibility, EN 1997-1 12.4(4)P states that the construction process shall be specified, i.e.
in the Geotechnical Design Report, to ensure that the bearing resistance is not exceeded or
excessive movements do not occur during construction.
Excessive deformation
Limit states involving adjacent structures, roads and services are also included in the list.
All possible failure modes of an embankment need to be considered. Since embankments are often
constructed in different phases, with different load conditions, analyses should be carried out phase
by phase and in accordance with the Geotechnical Design Report. The design should show that
settlement of an embankment will not cause a serviceability limit state in the embankment or nearby
structures or services. The settlement of an embankment should be calculated using the principles of
EN 1997-1, Section 6.6.1, Settlement of foundations.
64
As the definitions of hydraulic failures vary considerably in Europe they are defined as follows:
o
Failure by uplift (UPL) occurs when pore-water pressure under a structure or a low
permeability ground layer becomes larger than the mean overburden pressure (due to the
structure and/or the overlying ground layer).
Failure by heave (HYD) occurs when upwards seepage forces act against the weight of the
soil, reducing the vertical effective stress to zero. Soil particles are then lifted away by the
vertical water flow and failure occurs (boiling).
Failure by internal erosion is produced by the transport of soil particles within a soil stratum, at
the interface of soil strata, or at the interface between the soil and a structure. This may finally
result in regressive erosion, leading to collapse of the soil structure.
Failure by piping is a particular form of failure, for example of a reservoir, by internal erosion,
where erosion begins at the surface, then regresses until a pipe-shaped discharge tunnel is
formed in the soil mass or between the soil and a foundation or at the interface between
cohesive and non-cohesive soil strata. Failure occurs as soon as the upstream end of the
eroded tunnel reaches the bottom of the reservoir (see Fig.6.8.1).
65
(6.0)
where:
Vdst ;d Gdst ;d Qdst ;d
Additional resistance to uplift may also be treated as a stabilising permanent vertical action Gstb;d.
If a structure is completely below the groundwater level, the water pressure acting on the top of the
structure could be regarded as a stabilising action and the water pressure acting on the bottom as a
destabilising action. As the stabilising and destabilising actions are multiplied by different partial factor
values, the safety against uplift would then depend on the water-depth above the structure. To avoid
this misinterpretation the Note to 2.4.2(9) of EN 1997-1 should be followed: Unfavourable (or
destabilising) and favourable (or stabilising) permanent actions may in some situations be considered
as coming from a single source. If they are considered so, a single partial factor may be applied to the
sum of these actions or to the sum of their effects.
udst ;d std ;d
(6.0)
;d
Sdst ;d Gstd
(6.0)
Using the same partial factors, a design with total stresses using Eqn.6.2 provides greater safety than
inequality Eqn.6.2. Moreover, using expression Eqn.6.2, the safety becomes dependant of the water
depth which is physically not correct. In the next version of EN 1997-1, expression Eqn.6.2 needs
further explanation so that the hydrostatic water pressure components of the udst and stb are not
multiplied by different partial factors as occurs when different partial factors are applied to udst;k and
stb;k.
The determination of the submerged weight Gstb;d and total vertical stress stb;d at the bottom of the
column pose no problems in the verification. The pore water pressure distribution and the seepage
force, however, are influenced very strongly by the geometry of the structure and the permeability
conditions of the ground. Therefore EN 1997-1 requires in 10.3(2)P: The determination of the
characteristic value of the pore-water pressure shall take into account all possible unfavourable
conditions, such as:
o
spatial effects such as narrow, circular or rectangular excavations below water level
66
direction of flow
The procedure to check the susceptibility of soil to internal erosion is shown in Fig.6..
67
No gap
Sections 11 and 12 set out the provisions for the design of slopes and embankments
When using the method of slices for slope stability, some simplified methods are not
acceptable
The relevance and importance of other sections of EN 1997-1 in the design of embankments
is noted, for example:
Verification of piping
68
References
BAW, (2011) Code of Practice - Stability of Embankments at German Inland Waterways
(downloadable: www.baw.de, > publications, > codes of practice, > MSD (2011))
EN 1997-1: 2004. Eurocode 7: Geotechnical design. Part 1: General rules. CEN.
Frank, R., Bauduin, C., Kavvadas, M., Krebs Ovesen, N., Orr, T., and Schuppener, B. (2004).
Designers guide to EN 1997-1: Eurocode 7: Geotechnical design General rules, London:
Thomas Telford.
Krahn, J. (2004) Stability modelling with SLOPE/W An Engineering Methodology, GEO-SLOPE/W
International Ltd, Canada
Orr, T.L.L. and Farrell E.R. (1998) Geotechnical design to Eurocode 7, Springer-Verlag, London
69
70
CHAPTER 7
Retaining structures II
Retaining structures II
A.J.Bond and G.Scarpelli
72
Retaining structures II
A.J.Bond and G.Scarpelli
7.1. Scope
This Chapter concentrates on the design of embedded walls, which are relatively thin walls of steel,
reinforced concrete, or timber supported by anchorages, struts, and/or passive earth pressure. The
bending capacity of such walls plays a significant role in the support of the retained material.
Examples include: cantilever steel sheet pile walls; anchored or strutted steel or concrete sheet pile
walls; and diaphragm walls.
Gravity walls are discussed in Chapter 4.
Composite retaining structures are walls composed of elements of the above two types (gravity and
embedded). Examples include: double sheet pile wall cofferdams; earth structures reinforced by
tendons, geotextiles, or grouting; structures with multiple rows of ground anchorages or soil nails.
Parts of this chapter will be relevant to the design of composite walls.
Section 9 of EN 1997-1 applies to retaining structures supporting ground (i.e. soil, rock or backfill)
and/or water and is sub-divided as follows:
7.1. General (6 paragraphs)
7.2. Limit states (4)
7.3. Actions, geometrical data and design situations (26)
7.4. Design and construction considerations (10)
7.5. Determination of earth pressures (23)
7.6. Water pressures (5)
7.7. Ultimate limit state design (26)
7.8. Serviceability limit state design (14)
Annex C of Eurocode 7 Part 1 Sample procedures to determine earth pressures provides informative
text relevant to retaining structures and is sub-divided as follows:
1. Limit values of earth pressure (3 paragraphs)
2. Analytical procedure for obtaining limiting active and passive earth pressures (14)
3. Movements to mobilise earth pressures (4)
73
Retaining structures II
A.J.Bond and G.Scarpelli
Hd Hnom H
Where Hd = design height of wall; Hnom = nominal height of wall and H = allowance for unplanned
excavation. Table 7.2.1 below gives the recommended values of H with normal site control in place.
Table 7.2.4 Recommended values of H with normal site control
Wall type
Cantilever
Supported
74
Retaining structures II
A.J.Bond and G.Scarpelli
Discussion of Eurocode 7s recommendations regarding water levels and factoring of water pressures
is included in Chapter 4 and will not be repeated here.
DA1
DA2
DA3
Combination
2*
Partial factors
applied to:
Actions
Material
properties
Actions and
resistance
Effects of
actions and
resistance
Structural actions
and resistance
Partial factor
Sets*
A1+M1+R1**
A2+M2+R1**
A1+M1+R2**
A1+M1+R2**
A1/A2+M2+R3**
Fig.7.3.1 National choice of Design Approach for retaining walls (after Bond, 2013)
75
Retaining structures II
A.J.Bond and G.Scarpelli
The values of the partial factors that are recommended by EN 1997-1 for Design Approach 1
Combinations 1 and 2 (DA1-1 and DA1-2) are summarized in Table 7.3.2 below.
Table 7.3.2 Values of the partial factors for Design Approach 1
Parameter
Symbol
DA1-1
A1
M1
DA1-2
R1
A2
Unfavourable
1,35
Favourable
(G,fav)
1,0
Unfavourable
1,5
1,3
Favourable
(0)
(0)
cu
qu
Weight density ()
Rv
Rh
Re
M2
R1
1,0
1,25
1,0
1,4
1,0
1,0
1,0
The values of the partial factors that are recommended by EN 1997-1 for Design Approaches 2 and 3
(DA2 and DA3) are summarized below.
Table 7.3.3 Values of the partial factors for Design Approaches 2 and 3
Parameter
Symbol
DA2/DA2*
A1
Permanent
action (G)
Variable
action (Q)
Unfavourable
Favourable
(G,fav)
1,0
Unfavourable
1,5
Favourable
M1
DA3
R2
A1
A2*
1,35
1.0
1,5
1.3
M2
1,35
(0)
(0)
1,0
c
76
1,25
R3
Retaining structures II
A.J.Bond and G.Scarpelli
Parameter
Symbol
DA2/DA2*
A1
Weight density ()
M1
DA3
R2
A1
A2*
M2
R3
cu
1,4
qu
1,0
Rv
1,4
Rh
1,1
1,0
1,4
Re
1,1
a Ka dz q u 2c Ka (1 a / c ) u
0
p K p dz q u 2c K p (1 a / c ) u
0
where
77
Retaining structures II
A.J.Bond and G.Scarpelli
The earth pressures that act on an embedded wall may be determined using the charts given in
Annex C of EN 1997-1, which were developed by (but are not attributed to) Kerisel and Absi. They are
the same charts as appear in BS 8002. Kerisel and Absi assumed log-spiral failure surfaces and
hence their charts give upper bound values of Ka and Kp. The charts can only be used for walls that
are vertical.
Alternatively, the following expressions developed by Brinch Hansen (also given in Annex C of EN
1997-1) may be used:
a Ka dz u Kaq q Kac c;
0
Ka
K n cos cos ;
K p
Kn
p K p dz u K pq q K pc c
0
Kaq
2
K n cos ;
K pq
Kac
K n 1 cot
K pc
sin
2mt cos1
;
sin
sin
2mw cos1
sin
Bond and Harris (2008) have published charts (for vertical walls only) that make these expressions
easy to evaluate. Fig.7..1 shows one of these charts.
Fig.7.4.1 Chart showing Brinch Hansens passive earth pressure coefficient (after Bond &
Harris, 2008)
A key parameter when using these charts is the value chosen for the design angle of interface friction
d. Eurocode 7 suggests d should be determined from soils design constant-volume angle of
shearing resistance cv,d using the expression:
78
Retaining structures II
A.J.Bond and G.Scarpelli
tan cv ,k
d kcv ,d k tan1
where
k is a constant (= 1 for soil against cast in-situ concrete or for soil against precast concrete);
cv,k is the soils characteristic constant-volume angle of shearing resistance;
is a partial factor.
Advocates of critical state soil mechanics would argue that it is unnecessary to apply a partial factor to
cv,k in this expression, provided its value is chosen carefully, since it is already a pessimistic value.
For this reason, the UK National Annex states that It might be more appropriate to select the design
value of cv directly. A future version Eurocode 7 might propose a reduced value for the partial factor,
for example:
tan cv ,k
d kcv ,d k tan1
,cv
p,d
p ,k
Re
This gives the potential to treat passive earth pressure as an action, in which case it may be classified
as favourable, that is:
p,d G p,k
with G = 1,35, typically.
One other treatment is possible when material properties are factored but actions and resistances
are not (as in Design Approach 1, Combination 2) then:
p,d p,k
79
Retaining structures II
A.J.Bond and G.Scarpelli
Bond and Harris (2008) studied the effects of these different options and concluded for Design
Approach 1 at least that treating passive pressure as an unfavourable action, although the least
intuitive option, is the most consistent choice. This is equivalent to applying the single source principle
and considering the action to be the pressure distribution obtained from the algebraic sum of active
and passive earth pressures.
Fig.4..2 illustrates the movement v needed for the ground next to an embedded wall to reach a state
of active or passive failure, expressed as a percentage of the wall height h. When movements are
less than that needed for active conditions, consideration should be given to using at-rest earth
pressures in the walls design.
Fig.7.9.2 Normalized movement v/h needed to trigger limit states (after Bond & Harris, 2008)
80
Retaining structures II
A.J.Bond and G.Scarpelli
careful thought about the way passive earth pressures should be handled as a resistance,
as a favourable action, or as an unfavourable action (invoking the single source principle)
References
Bond, A. J. (2013). Implementation and evolution of Eurocode 7, Modern Geotechnical Design Codes
of Practice, Arnold et al. (eds), Amsterdam: IOS Press, pp3-14.
Bond, A. J., and Harris, A. J. (2008). Decoding Eurocode 7, London: Taylor & Francis, 618pp.
EN 1997-1: 2004. Eurocode 7: Geotechnical design. Part 1: General rules. CEN.
81
Retaining structures II
A.J.Bond and G.Scarpelli
82
Deep foundations
T.L.L.Orr and A.J.Bond
CHAPTER 8
Deep foundations
Deep foundations
T.L.L.Orr and A.J.Bond
84
Deep foundations
T.L.L.Orr and A.J.Bond
8.1. Scope
This Chapter examines the provisions in Section 7 of EN 1997-1 for the design of pile foundations.
These provisions apply to end-bearing piles, friction piles, tension piles and transversely loaded piles.
They apply to piles installed by driving, jacking and screwing or boring, and piles installed with or
without grouting. It is noted that the provisions of Section 7 should not be applied directly to piles that
are intended as settlement reducers, as in some piled raft foundations.
Reference is made in Eurocode 7 to other CEN standards that are relevant to the design of pile
foundations. A design standard that is referred to is the part of Eurocode 3 for the structural design of
steel piles:
o EN 1993-5: Eurocode 3, Part 5: Design of Steel Structures Piling
Reference is also made to the following execution standards for the carrying out of piling work:
o
EN 14199:2005 - Micropiles
Another CEN standard that is relevant to the design of piles but not referred to in Eurocode 7 is the
material standard:
o
85
Deep foundations
T.L.L.Orr and A.J.Bond
to which piles may be subjected. Piles may be loaded axially and/or transversely. They may also be
loaded due to displacement of the surrounding soil. This may be due to:
o
Consolidation
Swelling
Adjacent loads
Creeping soil
Landslides, or
Earthquakes
The loads from the surrounding soil due to these causes need to be considered as they can affect
piles by causing downdrag (negative skin friction), heave, stretching, transverse loading and
displacement. According to EN 1997-1 7.3.3(1)P 1, if ultimate limit state design calculations are
carried out with the downdrag load as an action, its value shall be the maximum, which could be
generated by the downward movement of the ground relative to the pile. Usually, in this situation, the
design values of the strength and stiffness are upper values, which is a more conservative approach.
However, although EN 1997-1 indicates that downdrag can be included in ultimate limit state
calculations, normally downdrag is only relevant in serviceability limit states, causing additional pile
settlement.
The limit states that need to be considered in the design of piles are the following:
o Loss of overall stability
o
Excessive settlement
Excessive heave
Unacceptable vibrations
One of the special features of Eurocode 7 is that it provides checklists, which are lists of factors to be
taken into account or considered in a particular design situation. In the design of piles, a checklist is
provided of the factors that affect the selection of the type of pile. Orr and Farrell (1998) have
presented this checklist in the form of Table 8.3.1 with a column to be ticked when each particular
factor has been considered.
The results of static load tests, which have been demonstrated, by means of calculations or
otherwise, to be consistent with other relevant experience
Empirical or analytical calculation methods whose validity has been demonstrated by static
load tests in comparable situations
The results of dynamic load tests whose validity has been demonstrated by static load tests in
comparable situations
86
Deep foundations
T.L.L.Orr and A.J.Bond
o
The observed performance of a comparable pile foundation, provided that this approach is
supported by the results of site investigation and ground testing
Table 8.3.1 Checklist of factors affecting selection of pile type (after Orr and Farrell, 1999)
Selection of pile type
Checked
The use of static pile load tests for pile design has been underlined in the above text to highlight the
emphasis and importance placed on static pile load tests in the design of piles to Eurocode 7 since
the first three approaches all refer to static load tests while the fourth approach refers to observed
performance and ground testing. Eurocode 7 provides the following requirements concerning static
load tests:
o
Static load tests may be carried out on trial piles, installed for test purposes only, before the
design is finalised, or on working piles, which form part of the foundation (7.4.1(3))
If one pile load test is carried out, it shall normally be located where the most adverse ground
conditions are believed to occur (7.5.1(4)P)
Between the installation of the test pile and the beginning of the load test, adequate time shall
be allowed to ensure that the required strength of the pile material is achieved and the porewater pressures have regained their initial values (7.5.1(6)P)
Fc;d Rc;d
where Fc;d is the design axial compression load and Rc;d is the pile compressive design resistance.
87
Deep foundations
T.L.L.Orr and A.J.Bond
The two sets of recommended partial factors on actions and the effects of actions provided in Table
8.4.1 (representing Table A3 of Annex A of EN 1997-1).
Table 8.4.1 Recommended partial factors on actions and effects of actions
Action
Permanent
Variable
Symbol
Unfavourable
Favourable
Unfavourable
Favourable
Set
A1
A2
DA1.C1, DA2
DA3 (structural actions)
DA1.C2
DA3 (geotech.actions)
1,35
1,0
1,0
1,0
1,5
1,3
G
Q
The self-weight of the pile should be included when calculating the design axial compressive load,
Fc;d, along with any downdrag, heave or transverse loading. However the common practice of
assuming that the weight of the pile is balanced by that of the overburden allowing both to be
excluded from Fc;d and Rc;d is permitted, where appropriate. The pile weight may not cancel the weight
of the overburden if:
f)
g)
h)
88
Deep foundations
T.L.L.Orr and A.J.Bond
a) Characteristic pile resistance from static load tests
For piles in compression, it is often difficult to identify the ultimate limit state from static load test
results because the pile load-settlement plot shows a continuous curvature. In these cases, Eurocode
7 states that the settlement of the pile top equal to 10% of the pile base diameter should be adopted
as the "failure" criterion. The characteristic pile resistance Rc;k is then determined directly (i.e. not
estimated) from the measured pile resistance Rc;m values (ultimate limit state resistances) by applying
correlation factors, 1 and 2 , related to number of piles tested, to the mean and minimum measured
resistances according to equation:
Rc;m
Rc;m min
mean
Rc;k Min
;
1
2
The recommended values for 1 and 2 for n pile load tests, given in Table A.9 of EN 1997-1 Annex A,
are shown in Table 8.4.1.
Table 8.4.1 Recommended correlation factors 1 and 2 to determine characteristic pile
resistance from pile load test results
n
1,4
1,3
1,2
1,1
1,0
1,4
1,2
1,05
1,0
1,0
The values for 1 and 2 in Table 8.4.1 show the advantage of carrying out more load tests since the
correlation values reduce as the number of load tests increases so that higher Rc;k values are
determined. For structures which have sufficient stiffness to transfer loads from weak to strong
piles, the values may be divided by 1,1 provided they are not less than 1,0.
a)
Part 2 of EN 1997 includes the following Annexes with methods to calculate the compressive
resistance, Rc;cal of a single pile from profiles of ground test results:
o
D.6
D.7
Example of a method to determine the compressive resistance of a single pile Equations are provided in this Annex to calculate the maximum base resistance and
shaft resistance from the qc values obtained from an electrical CPT.
E.3
When a number of profiles of tests are carried out, e.g. CPTs, the characteristic total pile compressive
resistance Rc;k or the base and shaft resistances Rb;k and Rs;k, may be determined directly by applying
correlation factors 3 and 4 to the set of pile resistances calculated from the test profiles using, for
example, the methods referred to in the Annexes above. This procedure is referred to as the Model
Pile procedure by Frank et al. (2004). The values of the correlation factors 3 and 4, depend on the
number of test profiles, n and they are applied to the mean and minimum Rc;cal values according to the
following equation:
89
Deep foundations
T.L.L.Orr and A.J.Bond
3
4
The recommended values for 3 and 4 for n profiles of test results, given in Table A.10 of EN 1997-1,
are shown in Table 8.4.2 and differ from the factor values for design from pile load tests.
Table 8.4.2 Recommended correlation factors 3 and 4 to determine characteristic pile
resistance from ground test results
n
10
1,4
1,35
1,33
1,31
1,29
1,27
1,25
1,4
1,27
1,23
1,20
1,15
1,12
1,08
Rb;k Ab qb;k
Rs;k As;i qsi ;k
where:
Ab = the nominal plan area of the base of the pile;
Asi = the nominal surface area of the pile in soil layer i
qb;k = the unit base resistance
qsi;k = the unit shaft resistance in soil layer i
In this alternative procedure, the characteristic unit pile resistances qb;k and qs;k are calculated using
appropriate values for the ground parameters. These would normally be cautious values, i.e.
characteristic values. In a note to EN 1997-1 7.6.2.3(8), it is stated that when the alternative
procedure is used to calculate the design pile compressive or tensile resistance, the partial factors b
and s may need to be corrected by a model factor larger than 1,0. A number of countries, such as
Ireland as explained in Section 8.6.2 below, have introduced such a model factor.
Rc;d Rc;k t
If the pile resistance is separated into base and shaft components, the design resistance is obtained
by dividing the characteristic base and shaft resistances, Rb;k and Rs;k, by the relevant partial factors,
b and s:
90
Deep foundations
T.L.L.Orr and A.J.Bond
The R1 partial factor values are greater than 1,0 for bored and CFA piles in compression, but
are equal to 1,0 for driven piles
The R2 partial factors are the same for all three different types of pile
The R3 partial factors are all equal to 1,0 for all three different types of pile
The R4 partial factors are all greater than 1,0 and greater than the R2 partial factor values
For piles in tension, only the shaft resistance factor is relevant and this has the same value for
all three types of pile
Table 8.4.3 Recommended partial resistance factors for driven, bored and CFA piles
Resistance
Symbol
Set
R1
R2
R3
R4
1,0
1,1
1,0
1,3
Shaft (compression)
1,0
1,1
1,0
1,3
Total/combined (compression)
1,0
1,1
1,0
1,3
Shaft in tension
s;t
1,25
1,15
1,1
1,6
Base
1,25
1,1
1,0
1,6
Shaft (compression)
1,0
1,1
1,0
1,3
Total/combined (compression)
1,15
1,1
1,0
1,5
Shaft in tension
s;t
1,25
1,15
1,1
1,6
1,1
1,1
1,0
1,45
Shaft (compression)
1,0
1,1
1,0
1,3
Total/combined (compression)
1,1
1,1
1,0
1,4
Shaft in tension
s;t
1,25
1,15
1,1
1,6
91
Deep foundations
T.L.L.Orr and A.J.Bond
The combinations of sets of partial factor values that should be used for Design Approach 1 are as
follows:
DA1.C1:
A1 + M1 + R1
DA1.C2:
A2 + M1 or M2 + R4
It should be noted that, unlike in the case of all other geotechnical design situation, in the design of
pile foundations, DA1 is a partial resistance factor rather than a material factor approach since for
both C1 and C2 the design resistance is obtained by applying the partial resistance factor Sets R1 or
R4, which are mostly 1,0, to the characteristic base and shaft resistances, and applying the partial
material factor Set M1 = 1,0 to the ground parameters; Set M2 > 1,0 is only used for C2 to calculate
unfavourable design actions on piles owing e.g. to negative skin friction.
The combinations of sets of partial factor values that should be used for Design Approach 2 are as
follows:
DA1.C1:
A1 + M1 + R2
As in the case of Design Approach 1, this is a partial resistance factor approach as Set M1 = 1.0, but
the Set R2 values differ from the Set R1 values.
The combinations of sets of partial factor values that should be used for Design Approach 3 are as
follows:
DA1.C1:
(A1* or A2) + M2 + R3
where * and indicate that the partial action factor Set A1 is applied to structural actions and A2 is
applied to geotechnical actions. Since all the R3 values are unity, DA3 should not be used for piles
designed from pile load tests or from resistances calculated from profiles of test results as it provides
no safety on the resistance.
92
Deep foundations
T.L.L.Orr and A.J.Bond
7.6.4.1(2) has the important note that for piles bearing in medium-to-dense soils and for tension
piles, the safety requirements (i.e. partial factors) for the ultimate limit state design are normally
sufficient to prevent the occurrence of a serviceability limit state in the supported structure. Preventing
the occurrence of a serviceability limit state by means of the ultimate limit state partial factors is an
indirect design method. Since it is often difficult to predict the settlement of a pile foundation, many
countries have adopted this indirect design method for pile foundations and have either increased the
values for the ULS design of piles or have included a model factor so as to satisfy the SLS
(settlement) as well as the ULS (safety against failure) requirements.
10
Recommended
1,4
1,35
1,33
1,31
1,29
1,27
1,25
2,1
2,03
2,0
1,97
1,94
1,91
1,88
Recommended
1,4
1,27
1,23
1,20
1,15
1,12
1,08
2,1
1,91
1,85
1,80
1,73
1,68
1,62
93
Deep foundations
T.L.L.Orr and A.J.Bond
Table 8.6.2 Recommended partial resistance factors and equivalent Irish values after
application of model factor of 1,75
Resistance
Set
Symbol
R1
R2
R3
R4
Recommended
1,0
1,1
1,0
1,3
1,75
1,925
1,75
2,275
Recommended
1,0
1,1
1,0
1,3
1,75
1,925
1,75
2,275
1,25
1,1
1,0
1,6
2,1875
1,925
1,75
2,8
Recommended
1,0
1,1
1,0
1,3
1,75
1,925
1,75
2,275
1,1
1,1
1,0
1,45
1,925
1,925
1,75
2,5375
Recommended
1,0
1,1
1,0
1,3
1,75
1,925
1,75
2,275
Base
Shaft (compression)
Base
Shaft (compression)
Recommended
Equivalent Irish values
Shaft (compression)
Recommended
Equivalent Irish values
The importance of static pile load tests in the design of piles to Eurocode 7 is emphasised
Eurocode 7 provides an innovative method for determining the characteristic pile resistance
directly from the results of pile load tests or from profiles of tests using values
The values are based on the number of pile load tests or the number of soil test profiles and
hence offer more economical designs for more pile load tests or more soil test profiles
DA3 should not be used for the design of piles from pile load tests or from soil test profiles as
its resistance factors are all equal to 1,0
SLS requirements need to be satisfied and model factors or increased factors in ULS
calculations have been introduced in many countries NAs to provide an indirect design
method to ensure that the occurrence of an SLS as well as a ULS is sufficiently unlikely.
94
Deep foundations
T.L.L.Orr and A.J.Bond
References
EN 1997-1: 2004. Eurocode 7: Geotechnical design. Part 1: General rules. CEN.
Frank, R., Bauduin, C., Kavvadas, M., Krebs Ovesen, N., Orr, T., and Schuppener, B. (2004).
Designers guide to EN 1997-1: Eurocode 7: Geotechnical design General rules, London:
Thomas Telford
NSAI (2005) Irish National Annex to Eurocode 7: Geotechnical design Part 1: General rules, National
Standards Authority of Ireland, Dublin, 2005
Orr, T.L.L. and Farrell E.R. (1998) Geotechnical design to Eurocode 7, Springer-Verlag, London
95
Deep foundations
T.L.L.Orr and A.J.Bond
96
ANNEX
Worked examples
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
98
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
A.1. Introduction
This Annex contains worked examples to accompany the various chapters of this report.
roof loading
partition loading
wind (horizontal)
The characteristic weight density of reinforced concrete is c,k =25 kN/m and of water w,k = 10 kN/m .
99
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Atot Bx By 720m2
The tributary area above the stability wall has area:
By bw
A
2
1 Bx
2 Nx
2
28,5m
Floor:
Screed on roof:
Raised floor:
Self-weight of water tank on roof - only half total weight is carried by the core wall
w tank ,Gk
1
w ,k dtank l tank btank 250kN (removable)
2
on roof:
on floors:
h Bx
44,2kN
2 2
on roof:
Qw ,rf ,Qk qw ,k
on each floor:
Qw ,fl ,Qk qw ,k h
Bx
88,3 kN
2
100
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Nw ,Qk 0kN
first floor:
second floor:
roof:
total:
on permanent actions:
G =G,B=1,35
Q,w=Q,B=1,5
Q,I =Q,B=1,5
Combination factors:
o
for wind
w =1,0
fl =0,i,B =0,7
rf =0,i,H =0
N
6MEd
Pmax,Ed Ed
355kN
2
bfdn l fdn bfdn l fdn
Combination 2 - wind as leading variable action, vertical actions favourable, partial factors
from Set B
Design value of normal action effect:
101
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
MEd Q,w w Mw ,Qk 2405 kNm
N
6MEd
45kN
Pmax,Ed Ed
2
bfdn l fdn bfdn lfdn
Line of action is outside the middle-third and eccentricity is:
MEd
1,47kN
NEd
Pmax,Ed
NEd
8
345kN
3 lfdn 2e 2
for wind
w =0,w =0,6
fl =1
rf =1
N
Pmax,Ed Ed
bfdn l fdn
6MEd
296kN
2
bfdn l fdn
Combination 4 - wind as leading variable action, vertical actions unfavourable, partial factors
from Set C
Partial factors:
o
on permanent actions:
G =G,C = 1
Combination factors:
o
w =1,0
for wind:
102
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
o
fl = 0,i,B = 0,7
rf = 0,i,H = 0
Combination 5 - wind as leading variable action, vertical actions favourable, partial factors
from Set C
Design value of normal action effect:
for wind:
w = 0,w = 0,6
fl = 1
rf = 1
on permanent actions:
G = G,SLS = 1
Q,w =Q,SLS = 1
Q,i = Q,SLS = 1
103
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Combination factors:
o
for wind:
w = 2,w = 0
fl = 2,i,B = 0,3
rf = 2,i,H = 0
Combination 8 - wind as leading variable action, vertical actions favourable, partial factors for
SLS
Design value of normal action effect:
for wind :
w = 2,w = 0
fl = 2,i,B = 0,3
rf = 2,i,H = 0
104
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
105
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
C2
C3
C4
C5
C6
-460,147
Qk
-108,138
Gk
-687,103
Qk
-222,355
Gk
-627,8
Qk
-154,012
Gk
-623,915
Qk
-152,261
Gk
-685,011
Qk
-222,231
Gk
-416,982
Qk
-108,103
106
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
107
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
qc (MPa)
20
40
100
u2 (MPa)
200
300
0,0
10
10
10
15
15
15
20
z (m)
z (m)
z (m)
fs (kPa)
qt (MPa)
20
20
25
25
25
30
30
30
35
35
35
40
40
40
108
0,5
1,0
1,5
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Qt
100
200
300
400
500
10
10
15
15
z (m)
z (m)
Fr
20
50
100
20
25
25
30
30
35
35
40
40
Fig.A.3.8 Normalized point resistance and friction from CPTu tests
Eu -
Ed -
oedometric modulus
Ed (MPa) = 4qc
109
150
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Fig.A.3.9 Empirical correlation for the ratio Eu/Cu as a function of the overconsolidation ratio.
Ip is the soil plasticity index.
Cv = 210 cm /s
z = 25 m
- sample depth
W =32,74 %
110
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
=19 kN/m
zw = 2,5 m
- unit weight,
- water depth
111
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
k
k
Soil 1: medium
sand (0-20 m)
dense
= 18.5 kN/m3
c = 0 = 38
E = 30 MPa
Cv=2*10 cm /s
Cu = 80 kPa
Fig.A.3.111 The soil geotechnical model adopted for the shallow foundation design
DA1-1
DA1-2
Partial factors
A1+M1+R1
A2+M2+R1
Vd (kN)
7395,74
5661,00
Nq
48,87
23,17
74,80
27,72
sq
1,04
1,04
0,95
0,98
Rd (kN)
15320,80
5676,52
Rd / Vd
2,07
1,00
Table A.3.2. Adopted factors and results obtained by using design approach DA2
B=1,21
DA2
Partial factors
A1+M1+R2
112
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Vd (kN)
7160,10
Nq
48,87
74,80
sq
1,03
0,98
Rd (kN)
7150,58
Rd / Vd
1,00
Table A.3.3. Adopted factors and results obtained by using design approach DA3
B=1,74
DA3
Partial factors
A1 / A2+M2+R3
Vd (kN)
7590,75
Nq
23,17
27,72
sq
1,04
0,98
Rd (kN)
7612,07
Rd / Vd
1,00
Fig.A.3.122 Graphs of the utilization ratio Rd/Vd with friction k for constant B in the three
design approaches DA1, DA2 and DA3.
113
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
I (Hi ) I Hi 1
i 1
Ei
s0 qB
(1 2 )
114
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
E (kPa)
H/B
D/B
L/B
0
1
(m)
167,32
1,50
21,40
50
0,3
30000
666,7
1
14,3
1
1,8
0,014
64,77
B (m)
15,50
L (m)
21,40
H1 (m)
20
H2 (m)
50
0,30
0,50
115
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
cu (kPa)
80,00
Eu (kPa)
32000
E (kPa)
30000
H1 / B
1,29
H2 / B
64,52
D/B
L/B
1,38
0 (1)
1,00
1 (1)
0,50
0 (2)
1,00
1 (2)
0,70
(m)
0,021
Hi
c'
Hi
log
C
1 e0 s v' 0
v' 0 v
log
c
c'
With the calculation scheme shown in the Fig,A.3.6, stress increments (by means of influence factors
of Fig.A.3.16) and settlements can be obtained as detailed in Table A.3.6 and in Table A.3.7.
In the first table, settlement calculation was limited at a depth where the stress increment is lower than
10% of the in situ effective stress. This is justified by a small overconsolidation of the clayey soil
deposit due to cementation. In the second table this effect is not considered and the settlement
calculation was extended to a depth comparable with the building width. Final settlement values are
3,3 cm and 24,3 cm respectively.
116
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
1/2
1/2
2
2
2mn m2 n 2 1
1 2mn m n 1
m2 n 2 2
1
z q
tan
4 m2 n 2 m2 n 2 1 m2 n 2 1
m2 n 2 m2 n 2 1
117
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Table A.2.6 Consolidation settlement for the 10% stress increment limitation scheme
z
z
(from
g.s.)
(m)
(m)
(kPa)
(kPa)
(kPa)
1,00
0,50
20,25
374,63
174,13
200,50
0,91
21,67
0,11
222,17
0,86
0,023
0,012
2,00
0,50
20,75
383,88
179,03
204,84
0,90
20,87
0,10
225,71
0,86
0,022
0,011
3,00
0,50
21,25
393,13
183,94
20919
0,90
20,10
0,10
229,29
0,86
0,021
0,010
4,00
0,50
21,75
402,38
188,84
213,53
0,90
19,37
0,09
232,90
0,86
0,020
0,010
5,00
0,50
22,25
411,63
193,75
217,88
0,89
18,68
0,09
236,55
0,86
0,019
0,009
6,00
0,50
22,75
420,88
198,65
222,22
0,89
18,01
0,08
240,24
0,86
0,018
0,009
7,00
0,50
23,25
430,13
203,56
226,57
0,89
17,38
0,08
243,95
0,86
0,017
0,009
8,00
0,50
23,75
439,38
208,46
230,91
0,88
16,78
0,07
247,69
0,85
0,016
0,008
layers
e0
z/z
(kPa)
z_fin
ef
(kPa)
Sed
(m)
9,00
0,50
24,25
448,63
213,37
235,26
0,88
16,20
0,07
251,46
0,85
0,015
0,008
10,00
0,50
24,75
457,88
218,27
239,60
0,88
15,66
0,07
255,26
0,85
0,015
0,007
11,00
0,50
25,25
467,13
223,18
243,95
0,88
15,13
0,06
259,08
0,85
0,014
0,007
12,00
0,50
25,75
476,38
228,08
248,29
0,87
14,63
0,06
262,93
0,85
0,013
0,007
13,00
0,50
26,25
485,63
232,99
252,64
0,87
14,16
0,06
266,79
0,85
0,013
0,006
stot =
0,033
z
(from g.s.)
(m)
(m)
(kPa)
(kPa)
(kPa)
(kPa)
1,00
2,00
21.00
388.50
181.49
207.02
20.48
0.10
227.50
0.86
0.022
0.043
2,00
2,00
23.00
425.50
201.11
224.40
17.69
0.08
242.90
0.86
0.017
0.035
3,00
2,00
25.00
462.50
220.73
241.78
15.39
0.06
257.17
0.85
0.014
0.029
4,00
2,00
27.00
499.50
240.35
259.16
13.48
0.05
27.64
0.84
0.012
0.024
5,00
2,00
29.00
536.50
259.97
276.54
11.88
0.04
288.42
0.84
0.010
0.020
6,00
2,00
31.00
573.50
279.59
293.92
10.54
0.04
304.46
0.83
0.008
0.017
7,00
2,00
33.00
610.50
299.21
311.30
9.40
0.03
320.70
0.83
0.007
0.014
8,00
2,00
35.00
647.50
318.83
328.68
8.43
0.03
337.11
0.82
0.006
0.012
9,00
2,00
37.00
684.50
338.45
346.06
7.60
0.02
353.65
0.81
0.005
0.010
10,00
2,00
39.00
721.50
358.07
363.44
6.88
0.02
370.31
0.81
0.004
0.009
11,00
2,00
41.00
758.50
377.69
380.82
6.25
0.02
387.07
0.80
0.004
0.008
12,00
2,00
43.00
795.50
397.31
398.20
5.71
0.01
403.90
0.80
0.003
0.007
13,00
2,00
45.00
832.50
416.93
415.58
5.23
0.01
420.81
0.79
0.003
0.006
14,00
2,00
47.00
769.50
436.55
432.96
4.81
0.01
437.76
0.78
0.003
0.005
15,00
2,00
49.00
906.50
456.17
450.34
4.43
0.01
454.77
0.78
0.002
0.005
stot =
0,243
layers
z/z
z_fin
ef
(kPa)
Sed
(m)
Patterns of time settlement curves are computed by means of Terzaghis one dimensional
consolidation theory. Given the average degree of consolidation Um, the corresponding time factor Tv
is obtained as summarized in Fig.A.3.178:
118
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
T Um2
;
4
T 1,781 0,933log 100 Um (%)
Um 2
per Um 60%
(Terzaghi)
per Um 60%
Fig.A.3.17 Main results from Terzaghis solution of the one dimensional consolidation
problem (d in the figure is H in the text)
c t
H2
The end of consolidation time is strongly influenced by the assumed drainage length H. The selection
of the drainage length is based on the interpretation of CPTu tests of Fig. A.3.6 Results from
CPTu testingFig. A.3.6; H values are different for the two settlement calculation schemes: if the ten
per cent limitation is adopted, only 3 metres of clay is considered, so that 2H=3 m and the resulting
time-settlement plot is given in Fig.A.3.189. If the 10% limitation is removed, the drainage length is the
half of the maximum distance between two sandy layers, approximately 7 metres from Fig. A.3.6. For
this reason H= 3,5 m in the second scheme and the resulting time-settlement plot is given in Fig.A.3..
Adopting the limitation of 10% for the stress increment, the final settlement is Ed = (3,3 + 2,1) cm.
Therefore Ed Cd = 5 cm and the SLS requirement can be considered as satisfied.
Fig.A.3.189 Time settlement curve for the single footing scheme (H=1,5 m)
119
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Fig.A.3.20 Time settlement curve for the whole footing scheme (H=3,5 m)
120
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Geometry
Width wall heel is:
bheel B bt ts 2,25m
Height of fill above wall heel is:
Hheel hf tb 7,62m
Depth to base of footing is:
d tb 0,8m
M2
1,25
1,25
tan k 32,5
d atan
27
Design effective cohesion:
c 'd
c 'k 0
= kPa
c 0
Actions
Characteristic self-weight of wall (permanent action) is:
o
wall stem
wall base
121
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
H hf
274kN/m
2
Design active earth pressure coefficient (for calculating inclined thrust) is:
cos cos 2 cos 2
d
K a,d
2
2
cos( ) 0,365
0,486
0,457
Partial factors
A1
1,35
1,5
from Set
: G
and Q
A2
1
1,3
Design thrust (inclined at angle to the horizontal) from earth pressure on back of virtual plane is:
1
271,4
2
Ea,Gd G Ka,d k Hheel
kN/m
2
268,2
from ground
20,8
from surcharge Ea,Qd Q Ka,d qQk Hheel
kN/m
24,1
total
292,2
Ea,d Ea,Gd Ea,Qd
kN/m
292,3
122
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
1
285,7
from ground MGd Ea,Gd Hheel cos( ) Bsin( )
kNm/m
3
282,3
1
46,8
from surcharge MQd Ea,Qd Hheel cos( ) Bsin( )
kNm/m
3
54,1
332,5
total design destabilising moment is: Mdst ,d =MGd MQd
kNm/m
336,4
b
from backfill Mfill ,Gd G,fav k bheel H B heel
2
total design stabilising moment is: Mstb,d =Mstem,Gd Mbase,Gd Mfill ,Gd MQd ,fav 1068kNm/m
B
152,1kNm/m
2
bheel
hf H
2 B 3 766,9kNm/m
bheel
12,7kNm/m
2
Mstb,d Mdst ,d
NEd
1,03
=
m
1,31
0,92
B
x
m
2
0,64
Bearing resistance
Design bearing capacity factors:
2
tan
24,6
Nq,d e d tan 45 d
2 13,2
30,1
N ,d 2 Nq,d 1 tan d
12,4
123
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
HEd
iq 1
mB
0,38
=
0,26
m 1
B
0,23
i i q mB
0,13
Partial factors
from Set R1: Rv = 1
Design bearing resistance (in terms of pressure) is:
o
from overburden
k dNq,d sq i q
qRvq,d
Rv
142,2
kPa
51,6
from body-mass
1 B 'd k N ,d s i 137,6
qRv ,d
kPa
Rv
2
40,4
total
279,8
qRv ,d =qRvq,d qRv ,d
kPa
92
A.4.3. VERIFICATIONS
Verification of resistance to sliding
Partial factors
from Set R1: Rh = 1
For cast-in-place concrete, interface friction angle is k=1 times the constant-volume angle of shearing
Assume cv,k =30
d kcv ,k 30
Design sliding resistance (drained), ignoring adhesion (as required by EN 1997-1 exp. 6.3a)
HRd
'Degree of utilization'
413,9
kN/m
321,6
HEd 66
H
1,51
= % or 'Overdesign factor' ODF Rd =
HRd 85
HEd 1,17
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
Verification of bearing resistance
124
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Design bearing resistance is:
574,4
NRd
kN/m
241,8
'Degree of utilization'
NEd 125
NRd 0,8
=
=
% or 'Overdesign factor' ODF
NRd 230
NEd 0,43
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
Verification of resistance to toppling
Design de-stabilizing moment is:
332
MEd ,dst MGd MQd
kNm/m
336
'Degree of utilization'
MEd ,dst
MEd ,stb
M
31
3,21
% or 'Overdesign factor' ODF= Ed ,stb
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
wall stem
wall base
H hf
274kN/m
2
125
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Characteristic total self-weight of wall including backfill is then:
WGk Wwall ,Gk Wfill ,Gk 457kN/m
Design active earth pressure coefficient (for calculating inclined thrust) is:
K a,k
2
2
cos( ) 0,365
Characteristic inclined thrust (at angle to the horizontal) from earth pressure on back of virtual plane
is:
2
Ea,Gk Ka,k k Hheel
201kN/m
2
from ground
total
from ground
from surcharge
126
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
B
152,1kNm/m
2
b
from backfill Mfill ,Gk k bheel H B heel
2
total design stabilising moment is: Mstb,k =Mstem,Gk Mbase,Gk Mfill ,Gk 1055,5kNm/m
bheel
hf H
2 B 3 766,9kNm/m
Mstb,k Mdst ,k
NEk
=1,53m
ek
B
x 0,42m
2
Nq,k e
tan 45
24,6
2
HEk
iq 1
mB
=0,38
mB 1
i i q mB 0,23
Characteristic bearing resistance (in terms of pressure) is:
o
from overburden
from body-mass
qRv ,k
total
1
B ' k N ,d s i 207,8 kPa
2
127
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
A.4.5. VERIFICATIONS
Verification of resistance to sliding
Partial factors from Set A1: G = 1,35; G,fav = 1 and Q = 1,5.
Design thrust (at angle to the horizontal) from earth pressure on back of virtual plane is:
Ea,Gd G Ea,Gk 271,4kN/m
from ground
total
Partial factors
from Set R2: Rh = 1,1.
For cast-in-place concrete, interface friction angle is k=1 times the constant-volume angle of shearing
Assume cv,k =30
k kcv ,k 30
Design sliding resistance (drained), ignoring adhesion (as required by EN 1997-1 exp. 6.3a)
HRd
'Degree of utilization'
278,4kN/m
H
HEd
=99% or 'Overdesign factor' ODF Rd =1,01
HEd
HRd
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
Verification of bearing resistance
Partial factors
from Set R2: Rv = 1,4.
Design bearing resistance is:
NRd
NRk
768,4kN/m
Rv
NEd 716,9kN/m
128
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
'Degree of utilization'
N
NEd
=93% or 'Overdesign factor' ODF Rd =1,07
NEd
NRd
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
Verification of resistance to toppling
Design de-stabilizing moment is:
MEd ,dst GMGk QMQk 332kNm/m
'Degree of utilization'
MEd ,dst
MEd ,stb
MEd ,stb
MEd ,dst
3,17
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
DETERMINE
The following example (see Fig.A.5.10) explains the application of EN 1997-1, paragraph (10) and the
NOTE. The ground has been investigated by 3 borings, where 11 samples have been taken from stiff
clay. These samples were tested in the laboratory to determine the strength of the ground. There is
some scatter in the undrained shear strength cu of the soil, but no trend to the strength with increasing
depth nor an apparent difference between the borings. So it can be assumed that the undrained shear
strength is normally distributed.
The first part of the NOTE to 2.4.5.2(10) refers to a situation where a cut is planned e.g. for a railway
line. Here the geotechnical designer has to verify the stability of the slope and as a first step he has to
select the characteristic value for the undrained shear strength cu. The potential slip surface lies in the
volume of ground of which several test results have been performed. So the characteristic value can
be determined as a cautious estimate of the mean value with a confidence level of 95%.
The second part of the NOTE refers to the situation where we have a footing, for which the designer
has to verify the ground bearing capacity. The footing only has a small zone of ground governing the
behaviour at the limit state. So this zone might be in an area, where the local strength might be lower.
In this case the characteristic value is a local low value (index: l,k), defined as a 5% fractile.
129
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Fig.A.5.10 Examples of the selection of characteristic ground parameters mean value and
local values
The evaluation of the 11 tests gives a mean value of the undrained shear strength of cu,m = 79 kPa
with a coefficient of variation Vcu = 0,08. The characteristic values for the two situations are shown in
Table A.5.5. It can be seen that, in this case, the simple formula of Schneider (1999) gives the same
result as the refined statistical formula.
Table A.5.5 Statistical evaluation of test results
Equation
kn
cu,k (kPa)
0,55
75,5
75,8
1,89
67,2
130
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
(A.0)(7.9)
where Ab and As,i are the base area and the shaft areas in the various strata, qb;k and qs;i;k are
characteristic values of base resistance and shaft friction in the various strata, obtained from values of
ground parameters.
To determine qb;k and qs;i;k Tables D.3 and D.4 of Annex D in EN 1997-2 are used (see Table A.5.6
and
131
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Unit base resistance pb, in MPa, at average cone
penetration resistance qc (CPT) in MPa
qc=10
qc=15
qc=20
qc=25
0,02
0,70
1,05
1,40
1,75
0,03
0,90
1,35
1,80
2,25
0,10(=sg)
2,00
3,00
3,50
4,00
qc=15
qc=20
qc=25
0,02
0,70
1,05
1,40
1,75
0,03
0,90
1,35
1,80
2,25
0,10(=sg)
2,00
3,00
3,50
4,00
0,040
10
0,080
15
0,120
s/Db
132
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
qc=10
qc=15
qc=20
qc=25
0,02
0,70
1,05
1,40
1,75
0,03
0,90
1,35
1,80
2,25
0,10(=sg)
2,00
3,00
3,50
4,00
s/Db
qc=10
qc=15
qc=20
qc=25
0,02
0,70
1,05
1,40
1,75
0,03
0,90
1,35
1,80
2,25
0,10(=sg)
2,00
3,00
3,50
4,00
133
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Fig.A.5.12. Undrained shear strength cu as results of UU triaxial tests with specimen from
samples of 6 borings
To evaluate the test results with respect to the base and shaft resistance of piles Tables B.4 and B.2
of Annex B in DIN 1054:2002 were used (see Table A.5.8 and Table A.5.9).
Table A.5.8 Unit shaft resistance qs,k of cast in situ piles in clay
Undrained shear strength cu,k
2
MN/m
0,025
0,025
0,10
0,040
0,20
0,060
134
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Table A.5.9 Unit base resistance qb,k of cast in situ piles in clay
Normalized pile
settlement
s/Ds bzw. s/Db
0,20
0,02
0,35
0,90
0,03
0,45
1,10
0,10 (sg)
0,80
1,50
135
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
In EN 1997-1 2.4.7.4, we find the following provisions for uplift:
(1)P Verification for uplift (UPL) shall be carried out by checking that the design value of the
combination of destabilising permanent and variable vertical actions (Vdst;d) is less than or equal to the
sum of the design value of the stabilising permanent vertical actions (G stb;d) and of the design value of
any additional resistance to uplift (Rd):
Vdst,d Gstb;d + Rd
(2.8)
where
Vdst,d = Gdst;d + Qdst;d
(2) Additional resistance to uplift may also be treated as a stabilising permanent vertical action
(Gstb;d).
The partial factors of safety used in Germany and Ireland are presented in Table A.10.1.
Table A.10.1 UPL partial factors and model factor used in Germany and Ireland
Factor
EN 1997-1
German NA
and DIN 1054
Irish NA
G;dst
1,0
1,0
1,0
G;stb
0,9
0,9
0,9
Q;dst
1,5
1,5
1,5
1,25
1,25
1,25
s;t
1,4
1,4
2,0
0,8
Factor type
In a first step a UPL-verification with the weight of the structure only is performed.
Self-weight base-slab:
concrete = 24,0 kN/m
Base-slab:
d = 1,0 m,
Base-area:
A = ab = 10,05,0 = 50,00 m
dSPW 0,03 m;
Weight per unit area:
0
steel 78,0 kN / m
g = 78,00,03 = 2,34 kN/m,
136
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Water-pressure:
Uk = Hwba = 5000 kN
The wall friction angle is assumed to be a = 2/3 k. For horizontal surface area and vertical wall the
earth pressure coefficient is Kah,k = 0,25 (from Figure C 1.1 of EN 1997-1 for k = 32,5) and
tan a = 0,397. The earth pressure is assumed to act only on the outer surface of the sheet pile wall:
4400 kN
Hence UPL requirement is not satisfied. So additional tension piles are required.
EN 1997-1 states in 7.6.3 (3)P For tension piles, two failure mechanisms shall be considered:
o
uplift of the structure and the block of ground containing the piles.
The design value of tensile action F t,d from the structure on the tension-pile is determined assuming
the ultimate limit state GEO is fulfilled using Design Approach 2 (DA2):
Ft ,d Ud (Rd Gd )
Ft ,d Uk G
Rk
Gk G,inf
Where
G = 1,20
for unfavourable actions (according to DIN 1054 for transient situations: construction
period)
G,inf = 1,00 for favourable effects of actions.
Inserting the values gives:
137
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Rt ,d Ltot qs,k D / P 39,25 Ltot
138
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Where:
n: number of piles,
L: length of piles
la = 5,0 m greater grid distance piles,
lb = 3,33 m smaller grid distance piles,
= 10,0 kN/m submerged weight soil
= 0,80 model factor for the weight
Gsoil ,k 3 (5,0 3,3 (10 1/ 3 5,0 3,33 cot 32,5)) 8,0 10 2740kN
Inserting the values in the extended Eqn.6.1 (eq. (2.8), EN1997-1):
Uk G,dst
Rk Gsoil ,k G,stb
5000 6906 kN
Hence the requirement for uplift is fulfilled with the tension piles.
Irish verification of uplift failure is carried out either by treating the side-wall force, R as stabilising
resistance or, to be conservative and since it may be small due to soil disturbance, by ignoring it.
It should be noted that care is needed when treating R as a resistance and applying to obtain Rd.
o
This is because if k,inf = 32,5 is used, i.e. the inferior characteristic value, and the UPL factor
o
o
= 1,25 from Table A.10.1 is applied to tan(k,inf) to obtain d = 27,0 so that d = 2/3d = 18,0
giving
Ka;d
=
0,31,
the
design
wall
frictional
resistance
Rd=Eah,d tand=
2
2(10+5)15 0,5100,310,325=3400 kN, which is greater than the characteristic value calculated
using the values given above, i.e. Rk = Eah,k tank = 84370,397 = 3349 kN, so that this provides no
margin of safety, which is not acceptable.
139
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Hence a superior characteristic value k,sup needs to be used. This is obtained, after Bond and Harris
o
o
(2008), by assuming a normal distribution for and a standard deviation of 3 so that k,sup = 32,5 +
o
21,6243,0=42,2 . Then applying the partial factor of 1,25 as a multiplier to tank,sup gives
o
d,sup=48,6 and hence an Rd value of 2465 kN with a margin of safety of 1,13 on the characteristic
value.
Using the Eqn.6.1 (eq. (2.8), EN 1997-1):
Ud Gd Rd
Uk G,dst Gk G,stb Rd
Hence using the characteristic actions given above and the factors in 2 gives:
Ed Rd
Ed Uk G Gk G,inf 5000G 2253G;inf
Rt ,d Rt ,k / s;t Rd Ltot qs,k D / s;t Rd Ltot 350,5 / s;t Rd Ltot 54,98 / s;t Rd
Hence substituting for Ed and Rd in eq. (2.5) from EN 1997-1 the length of the piles for stability is
given by the equation:
Ltot s;t (5000G 2253G;inf Rd ) / 54,98
Substituting the appropriate partial factor values and Rd values in this equation gives the required
piles lengths:
DA1.C1:
DA1.C2:
Hence design length is the larger of DA1.C1 and DA1.C2, which 39,0 m and therefore 4 piles, each
10 m long are required. This is more than for the DA2 design given above, which uses a reduced G
value of 1,2 for transient situations during the construction period.
It should be noted that due to the large balancing forces, DA1.C1 controls the design in this example,
not DA1.C2 as is usually the case.
140
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
(2.9a)
Sdst;d Gstb;d
(2.9b)
For the situation in thin column is assumed for which EAU give a formula for the hydraulic head hr
above the ground level of the excavation at the toe of the wall. The embedment length of the wall has
previously been determined using ULS-design.
Fig.A.6.5 Geometry of the sheet pile wall and the hydraulic conditions
With the embedment length t and the hydraulic head hr the hydraulic gradient i in the infinitesimal thin
column can be computed. This gives the seepage force:
Gk V 10V
With partial factors of G,dst = 1,35 and G,stb = 0,9 Eqn.6.3 (eq. (2.9b), EN 1997-1) becomes:
Sk G,dst Gk G,stb
141
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
uk
Also Eqn.6.2 (eq. (2.9a), EN1997-1) gives sufficient safety against hydraulic heave, however, the
margin of safety is clearly smaller.
142
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Geometry
Allowing for an unplanned excavation in ULS verifications, the design retained height of the wall is:
DRAINED
Material properties
Partial factors
M1
1
from Set
:
M
2
1,25
tan k 38
d atan
32
Characteristic value of soil's constant-volume angle of shearing resistance is assumed to be:
cv ,k 30
Angle of wall friction is k = 0.67 times the soil's constant-volume angle of shearing resistance:
d kcv ,d 20
0,26
7,39
K p,h = K p (d ; d ;0; 0)
5,18
Actions
Partial factors
A1
1,35
1,5
from Set
: G
; G,fav 1 and Q
A
2
1
1,3
143
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
1,35
G,fav =G
Q 1,11
=
G 1,3
1
1
1790
MEd ,dst G Ka,h k (Hd d )3 Q /G qk (Hd d )2
kNm/m
2
3
2040
1
2 1789
0,1
%
1
1
272
Pa,Ed =G Ka,h k (Hd d )2 Q /G qk (Hd d )
kN/m
2
291
1
190
Pp,Ed G,fav K p,h k d 2
kN/m
2
209
144
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Fa,Ed =
94,6kN/m
The depth of zero shear force in the retaining wall can be found (approximately) from:
5,42
m
5,57
PEd
G K a ,h
1
k
2
0
= kN/m
0
1
1
296
=
kNm/m
303
A.7.3. VERIFICATIONS
Verification of resistance to overturning
'Degree of utilization'
MEd ,dst
MEd ,stb
MEd ,stb 1
100
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
Verification of bending resistance
Partial factor on yield strength of steel is
B = 1,0
BWel fyk
M 0
497kNm/m
'Degree of utilization'
M
MEd
61% or 'Overdesign factor' ODF= c,Rd 1,64
MEd
Mc,Rd
145
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
Verification of shear resistance
Projected shear area is:
Av
tw (h tf )
3724 mm2 /m
b
Av fyk
3 M 0
763,2kNm
'Degree of utilization'
Vpl ,Rd
VEd
9,3
11% or 'Overdesign factor' ODF=
VEd
Vpl ,Rd
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
Verification of resistance to anchor pull-out
Design pull-out resistance of anchor is:
Fa,Rd =Ra,d =130kN/m
'Degree of utilization'
Fa,Ed
Fa,Rd
Fa,Rd
Fa,Ed
1,37 .
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
DRAINED
Material properties
Partial factors
from Set M1: = 1
Characteristic angle of shearing resistance:
k = 38,0
Characteristic value of soil's constant-volume angle of shearing resistance is assumed to be:
cv,k = 30
Angle of wall friction is k=0,67 times the soil's constant-volume angle of shearing resistance:
k=kcv,k = 20
Earth pressure coefficients from Annex C of EN 1997-1:
146
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Q
G
1,11
1
1
1
2
2
G,fav K p,h k d Hd + d
3
2
MEd ,stb =
2188kNm/m
Re
0,4%
Pp,Ed
1
2
G,fav K p,h 2 k d
222kN/m
Re
147
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Hence axial force transferred to the anchor is:
Fa,Ed =
PEd
101,9kN/m
cos
The depth of zero shear force in the retaining wall can be found (approximately) from:
PEd
G K a ,h
5,63m
1
k
2
1
1
A.7.5. VERIFICATIONS
Verification of resistance to overturning
'Degree of utilization'
MEd ,dst
MEd ,stb
MEd ,stb
MEd ,dst
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
Verification of bending resistance
Partial factor on yield strength of steel is
B = 1,0
BWel fyk
M 0
497kNm/m
'Degree of utilization'
M
MEd
67% or 'Overdesign factor' ODF= c,Rd 1,5
MEd
Mc,Rd
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
Verification of shear resistance
Projected shear area is:
148
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Av
tw (h tf )
3724 mm2 /m
b
Av fyk
3 M 0
763,2kNm
'Degree of utilization'
Vpl ,Rd
VEd
8,7
12% or 'Overdesign factor' ODF=
VEd
Vpl ,Rd
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
Verification of resistance to anchor pull-out
Design pull-out resistance of anchor is:
Fa,Rd =Ra,d =130kN/m
'Degree of utilization'
Fa,Ed
Fa,Rd
Fa,Rd
Fa,Ed
1,28 .
The design is unacceptable if the degree of utilization is > 100% (or overdesign factor is < 1)
Gk = 6,0 MN
Qk = 3,2 MN
The design involves determining the number of piles to support the building. The number of piles is to
be determined on the basis of static pile load tests.
Geometry
It has been decided to use bored piles, 1,2 m in diameter and 15 m long.
Measured pile resistance
Static pile load tests have been performed on site on four piles of the same diameter and length as
the chosen piles.
The results of the load-settlement curves are plotted in the figure opposite.
149
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
In accordance with 7.6.1.1(3), settlement of the pile top equal to 10% of the pile base diameter
3
sg = (10/100)1,210 = 120 mm has been adopted as the "failure" criterion for the piles.
From the load-settlement graphs for each pile (Figure A.8.1) this gives:
o
Pile 1
Rm = 2,14 MN
Pile 2
Rm = 1,96 MN
Pile 3
Rm = 1,73 MN
Pile 4
Rm = 2,33 MN
150
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
A.8.1.1. Design Approach 1
Combinations of sets of partial factors
DA1.C1:
A1 + M1 + R1
DA1.C2:
A2 + M1 + R4
Design actions
DA1.C1
DA1.C2
Characteristic resistances
DA1.C1
DA1.C2
Design equation
Fc;d Rc;d
12,9 1,50n
n 12,9 / 1,5
DA1.C2
10,2 1,15n
n 10,2 / 1,15
n 8,6 piles
n 8,9 piles
Design resistances
DA2
Design equation
151
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Fc;d Rc;d
n 12,9 / 1,57
n 8,2 piles
Gk = 300 kN
Qk = 150 kN
The ground consists of dense sand beneath loose sand with soft clay and peat to 16,5m. One CPT
test profile is available. The pile foundation design involves determining the design length, L of the
piles.
Geometry
It has been decided to use bored piles with a diameter D = 0,45m.
Material properties
1 CPT was carried out and the results are shown in Figure A.8.2.
152
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
qc = 15
qc = 20
qc = 25
0,02
0,70
1,05
1,40
1,75
0,03
0,90
1,35
1,80
2,25
0,10 (= sg)
2,00
3,00
3,50
4,00
NOTE Intermediate values may be interpolated linearly. In the case of cast in-situ piles with pile
base enlargement, the values shall be multiplied by 0,75.
s
is the normalised pile head settlement
Ds
is the diameter of the pile shaft
Db
is the diameter of the pile base
sg
is the ultimate settlement of pile head
153
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Table A.8.2 Unit shaft resistance ps of cast in-situ piles in coarse soil with little or no fines
Average cone penetration resistance qc (CPT)
MPa
0,040
10
0,080
> 15
0,120
pb 2,5 MPa
ps 0,1 MPa
Characteristic pile resistance
o
Ab 0,452 / 4 0,159 m2
As 0,45 1,414 m2 /m
Hence, applying the recommended correlation factors 3 and 4, which are both the same and equal to
1,4 for one profile of test results because the mean and minimum calculated resistances are the same
so that 3 and 4 = = 1,4, and the characteristic base and shaft compressive pile resistances are:
Rb;k Rb;cal / 398 / 1,4 284kN
Rs;k Rs;cal / 141 Ls / 1,4 101 Ls
DA1.C2
Design resistances
DA1.C1
154
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
DA1.C2
Design equation
Fc,d Rc,d
Ls 3,99 m
DA1.C2
Ls 4,08 m
Design resistances
DA2
Design equation
Fc,d Rc,d
Ls 4,05 m
155
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Gk = 600 kN
Qk = 300 kN
The ground consists of about 3m Brown Dublin Boulder Clay over Black Dublin Boulder Clay to great
depth. A large number of SPT results are available.
The pile foundation design involves determining the design length, L of the piles.
Geometry
It has been decided to use driven piles with a diameter D = 0,45 m.
Material properties
Figure A.8.3 shows tests results of SPT N values plotted against depth. Shaft resistance in Brown
Dublin Boulder Clay is ignored.
156
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
A cautious average N value:
Nav,cau = 45
Plasticity Index of the Dublin Boulder Clay:
PI = IP = 14%
If length of pile in Black Dublin Boulder Clay providing shaft resistance is Ls, then pile shaft area is:
As DLs 0,45 Ls 1,414Ls m2
157
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Hence characteristic base resistance:
Rb;k Ab qb;k 0,159 2430 386 kN
DA1.C12
Design resistances
DA1.C1
Rc;d
DA1.C2
Rc;d
Rb;k
bx R;d
Rb;k
bx R;d
Rs;k
sx R;d
Rs;k
sx R;d
153 Ls
386
221 87,4Ls kN
1,0 1,75 1,0 1,75
153 Ls
386
170 67,3Ls kN
1,3 1,75 1,3 1,75
Design equation
Fc,d Rc,d
Ls 11,9 m
DA1.C2
Ls 12,2 m
158
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
Design resistances
DA2
Rc;d
Rb;k
bx R;d
Rs;k
sx R;d
153 Ls
386
201 79,5Ls kN
1,1 1,75 1,1 1,75
Design equation
Fc,d Rc,d
Ls 13,3 m
Design resistances
DA3
Ab Nq cu;k / cu
DLs 0, 4cu;k / cu
R;d s
158 62,3Ls
1,75 1,0
1,75 1, 0
Design equation
Fc;d Rc;d
R;d b
Ls 17,7 m
159
Worked examples
A.J.Bond, B.Schuppener, G.Scarpelli, T.L.L.Orr
A.8.2.4. Conclusions from Example 3
o
The design pile lengths obtained from ground strength parameters using the alternative
procedure and the model factor in the Irish National Annex are:
DA1 L = 15,5 m
DA2 L = 16,5 m
DA3 L = 21,0 m
Application of the model factor of 1,75 as well as the material factor of 1,4 to obtain the design
resistance when using DA3, results in DA3 providing a longer design pile length and hence
the least economical Design Approach in Ireland
If the building were to be constructed in Germany, the partial recommended in the German
NA have been increased by a model factor of 1,27, compared to the model factor of 1,75 in
the Irish NA, which gives a design pile length of 12,0 m in Germany using DA2 compared to
16,5 m using DA2 in Ireland.
160
European Commission
EUR 26227 EN Joint Research Centre Institute for the Protection and Security of the Citizen
Title: Eurocode 7: Geotechnical Design
Authors: Andrew J. Bond, Bernd Schuppener, Giuseppe Scarpelli, Trevor L.L. Orr
Editors: Silvia Dimova, Borislava Nikolova, Artur V. Pinto
Abstract
This document is a report with worked examples summarizing the general rules, basic design principles and design
methods for geotechnical design following Eurocodes. It comprises an overview of Eurocode 7 with focus on the
design requirements, actions and design situations, and limit states. Different aspects to be considered for designing
shallow foundations, gravity walls, embedded walls and deep foundations are covered in the report. The provisions of
Eurocode 7 for ground investigations and testing for geotechnical design, overall stability of and movements in the
ground, slopes, hydraulic failure modes and verifications against them are also presented. The Annex contains worked
examples to accompany the various chapters of this report.
The materials were prepared and presented at the workshop Eurocode 7: Geotechnical Design held on 13-14 June
2013 in Dublin, Ireland. The workshop was organized by JRC with the support of DG ENTR and CEN, and in
collaboration with CEN/TC250/Sub-Committee 7 and Irelands Department of the Environment, Community and Local
government.
The document is part of the Report Series Support to the implementation, harmonization and further development of
the Eurocodes prepared by JRC in collaboration with DG ENTR and CEN/TC250 Structural Eurocodes.
z
LB-NA-26227-EN-N
As the Commission's in-house science service, the Joint Research Centre's mission is to provide
EU policies with independent, evidence-based scientific and technical support throughout the
whole policy cycle. Working in close cooperation with policy Directorates-General, the JRC
addresses key societal challenges while stimulating innovation through developing new
methods, tools and standards, and sharing its know-how with the Member States, the scientific
community and international partners.