NCL Report
NCL Report
Contents
1.
Introduction
1.1 Types of substation
2.
Steps in designing a substation
2.1
Earthing & Bonding
2.2
Substation Earthing Calculation Methodology
2.3 Earthing Material
2.4 Layout of Substation
2.5 Design of Busbar
3.
Single line diagram of singrauli Substation
4.
Transformer
4.1 Current Transformer
4.2 Capacitor Voltage Transformer
4.3 CVT Frequency Response
4.4 Bus Voltage Representation of CVT
5.
Circuit Breaker
5.1 SF6 Circuit Breaker
5.2 Vacuum Circuit Breaker
6.
Protective Relay
6.1 Differential Relay
6.2 Overcurrent Relay
6.3 Directional Relay
6.4 Buchholz Relay
7.
Miscellaneous
7.1 Isolator
7.2 Wavetrap
7.3 Busbars
7.4 Substation Grounding System
7.5
Insulators
7.6
Earth Wires & OPGW
7.7
Conductors
7.8
Support Structure (POLE)
7.9
Types of Conductor for Power Transmission
7.10
DC Supply Room (Battery)
7.11
Lightening Arrester
8.
Conclusion
Introduction
The present day electrical power is generated, transmitted
and distributed in the form of the alternating current. The electric power is produced at power
plant stations which are located at favorable places generally quite away from the consumers.
It is delivered to the consumers through a large network of transmission and distribution. At
many places in the power system, it may be desirable and necessary to change some
characteristics e.g. voltage, ac to dc, frequency, power factor etc. of electric supply. This
accomplished by suitable apparatus called substation. For example; generation voltage (11
KV or 33 KV) at the power station is set up to high voltage (say 220 KV or 132 KV) for
transmission of electric power. The assembly of apparatus (e.g. transformer etc.) used for this
purpose in the substation. Similarly near the consumers localities, the voltage may have to be
step down to utilization level. This job is again accomplished by suitable apparatus called
substation. The assembly of apparatus to change some characteristic of electric power supply
is called substation
Types of Substation:
(A) According to the service requirement:
1) Transformer substation
2) Switch substation
3) Power factor correction substation
4) Frequency change substation
5) Converting substation
(B) According to the constructional features:
1) Indoor substation
2) Outdoor substation
3) Underground substation
4) Pole mounted substation
JAYANT 1
JAYANT-2
NIGAHI-1
NIGAHI-2
DUDHICHUA-1
DUDHICHUA-2
AMLORI-1
AMLORI-2
Rough description of singrauli 33/11 kV substation
Transformer
the voltage transformer. This makes CVTs more economical than the wound
voltage transformers under high voltage (over 100kV), as the latter one requires
more winding and materials
fig-current transformers
fig-potential transformer
fig-transformer(
Circuit Breaker
There are two types of C.B.:
1) Sulphur hexafluoride circuit breaker (SF6)
2) Vacuum circuit breaker
SF6 circuit breaker are being used in 132KV and Vacuum circuit breaker are being
used in 33KV side. SF6 Circuit Breaker In such circuit breaker, sulphar
hexafluoride (SF6) gas is used as the arc quenching medium. The SF6 is an
electronegative gas and has a strong tendency to absorb free electrons. The SF6
circuit breaker have been found to a very effective for high power and high
voltage service. SF6 circuit breakers have been developed for voltage 115 KV to
230 KV, power rating 10 MVA. Ratings: Make- Crompton Greaves Rated
voltage- 132 Kv Rated normal current- 3150A C.T. ratio- 800-400-200/1 Gas
weight- 8kg Gas Pressure- 7 kg/sq. cm Weight of oil- 150 liters
SF6 Circuit Breaker It consists of fixed and moving contacts. It has chamber,
contains SF6 gas. When the contacts are opened, the mechanism permits a high
pressure SF6 gas from reservoir to flow towards the arc interruption chamber. The
moving contact permits the SF6 gas to let through these holes.
Vacuum Circuit Breaker Vacuum circuit breakers are circuit breakers which are
used to protect medium and high voltage circuits from dangerous electrical
situations. Like other types of circuit breakers, vacuum circuit breakers literally
break the circuit so that energy cannot continue flowing through it, thereby
preventing fires, power surges, and other problems which may emerge. These
devices have been utilized since the 1920s, and several companies have
introduced refinements to make them even safer and more effective.
Protective Relay
Differential relay
Buchholz relay
Busbars
When numbers of generators or feeders operating at the same voltage have to be
directly connected electrically, bus bar is used as the common electrical
component. Bus bars are made up of copper rods operate at constant voltage. The
following are the important bus bars arrangements used at substations: Single bus
bar system Single bus bar system with section alisation.
Auxiliary bus bar system In large stations it is important that break downs and
maintenance should interfere as little as possible with continuity of supply to
achieve this, duplicate bus bar system is used. Such a system consists of two bus
bars, a main bus bar and a spare bus bar with the help of bus coupler, which
consist of the circuit breaker and isolator. In substations, it is often desired to
disconnect a part of the system for general maintenance and repairs. An isolating
switch or isolator accomplishes this. Isolator operates under no load condition. It
does not have any specified current breaking capacity or current making capacity.
In some cases isolators are used to breaking charging currents or transmission
lines. While opening a circuit, the circuit breaker is opened first then isolator while
closing a circuit the isolator is closed first, then circuit breakers. Isolators are
necessary on supply side of circuit breakers, in order to ensure isolation of the
circuit breaker from live parts for the purpose of maintenance. A transfer isolator
is used to transfer main supply from main bus to transfer bus by using bus coupler
(combination of a circuit breaker with two isolators), if repairing or maintenance of
any section is required.
ALLUMINIUM BUSBAR
INSULATORS
Insulators proposed for use on this Project will be polymeric-type post insulators. They provide
a connection between conductors and structures and ensure electrical insulation between the
high voltage of the conductors and the (earthed) pole. The length of the insulators depends on
line voltage, clearance requirements and environmental considerations. For example,
additional length is required for acidic or salty air, neither of these conditions occurs within the
Project Area. Special galvanised steel of aluminium fittings connect both the line end of the
insulator to the conductors and the pole end to the structure.
Conductors
Conductors (wires) are the part of the power-line which transports high voltage
electricity. Conductors proposed to be used for the power-line would consist of a
stranded aluminium alloy with an overall diameter of around 33.8 mm. Each pole
structure would support six conductors, plus two earth wires to protect the line
from lighting strikes. For a typical double circuit 132 kV pole, the distance
between pairs of conductors on steel poles will be approximately 1.9 m on the
vertical plane and 4.6 m on the horizontal plane (Figure 3.1). Electrical continuity
on angle structures is provided by bridging conductors which are suspended
beneath the main conductors or around the outside of the pole connecting the
terminated conductors on either side of the pole. Where necessary, these
conductors are restrained by bridging insulators to maintain electrical clearance.
The minimum electrical clearance distance from the ground to the lowest point of
the conductors is 6.7 m; however as noted above, larger clearances are often
required by the DTMR over road and rail crossings. 7.8 Support
structures( POLE) :- Poles are self-supporting structures used to keep the high
voltage conductors separate from each other, clear from vegetation, the ground
and other obstacles. Minimum clearance requirements between energized
conductors and various types of obstacles are specified by the Electrical Safety
Regulations 2002. For this Project a mixture self-supporting concrete or steel poles
are envisaged. The distance between support structures (span) and their height is
determined by topography and clearance requirements. Poles are made in a range
of heights, generally in 1 m increments, to allow optimum height of structure to be
provided at each site. The standard overall length of a typical double-circuit RVPNL
concrete pole is around 25 to 40 m long. When installed, the out of ground height
to the top of the pole will typically be in the range of 20 to 35 m, with taller and
shorter structures used as required to suit the terrain and other constraints.
Typically, shorter poles are found on elevated areas such as hills, with taller poles
in gullies or where additional clearance is required over a mid-span obstacle. The
duty of a pole structure is related to the method by which it supports the
conductors and this in turn influences the type of structure used. The two means
of conductor support are intermediate and tension.
insulator (i.e. distance P) must not be less than one third of the gap length so that
the arc may not reach the insulator and damage it.
Generally, the gap length is so adjusted that breakdown should occur at 80% of
spark-voltage in order to avoid cascading of very steep wave fronts across the
insulators. Under normal operating conditions, the gap remains non-conducting.
On the occurrence of a high voltage surge on the line, the gap sparks over and the
surge current is conducted to earth. In this way excess charge on the line due to
the surge is harmlessly conducted to earth
2. Expulsion type arrester This type of arrester is also called protector tube and is
commonly used on system operating at voltages up to 33kV. It essentially consists
of a rod gap AA in series with a second gap enclosed within the fiber tube. The
gap in the fiber tube is formed by two electrodes. The upper electrode is
connected to rod gap and the lower electrode to the earth. One expulsion arrester
is placed under each line conductor. On the occurrence of an over voltage on the
line, the series gap AA spanned and an arc is stuck between the electrodes in the
tube. The heat of the arc vaporizes some of the fiber of tube walls resulting in the
production of neutral gas. In an extremely short time, the gas builds up high
pressure and is expelled through the lower electrode, which is hollow. As the gas
leaves the tube violently it carries away ionized air around the arc. This deionizing effect is generally so strong that the arc goes out at a current zero and
will not be reestablished.
Expulsion type arrester
3. Valve type arrester Valve type arresters incorporate non linear resistors and are
extensively used on systems, operating at high voltages. It consists of two
assemblies
(i) series spark gaps and (ii) non- linear resistor discs in series. The non-linear
elements are connected in series with the spark gaps. Both the assemblies are
accommodated in tight porcelain container. The spark gap is a multiple assembly
consisting of a number of identical spark gaps in series. Each gap consists of two
electrodes with fixed gap spacing. The voltage distribution across the gap is line
raised by means of additional resistance elements called grading resistors across
the gap. The spacing of the series gaps is such that it will withstand the normal
circuit voltage. However an over voltage will cause the gap to break down causing
the surge current to ground via the non-linear resistors. The non-linear resistor
discs are made of inorganic compound such as thyrite or metrosil. These discs are
connected in series. The non-linear resistors have the property of offering a high
resistance to current flow when normal system voltage is applied, but a low
resistance to the flow of high surge currents. In other words, the resistance of
these non-linear elements decreases with the increase in current through them
and vice-versa.
Non-linear resistor discs Under normal conditions, the normal system voltage is
insufficient to cause the breakdown of air gap assembly. On the occurrence of an
over voltage, the breakdown of the series spark gap takes place and the surge
current is conducted to earth via the non-linear resistors. Since the magnitude of
surge current is very large, the non-linear elements will offer a very low resistance
to the passage of surge. The result is that the surge will rapidly go to earth instead
of being sent back over the line. When the surge is over, the non-linear resistors
assume high resistance to stop the flow of current. FIG- Valve type arrester
POWER LINE CARRIER COMMUNICATION:- Power line communication (PLC) carries
data on a conductor that is also used simultaneously for AC electric power
transmission or electric power distribution to consumers. It is also known as power
line carrier, power line digital subscriber line (PDSL), mains communication, power
line telecommunications, or power line networking (PLN). A wide range of power
line communication technologies are needed for different applications, ranging
from home automation to Internet access which is often called broadband over
power lines (BPL). Most PLC technologies limit themselves to one type of wires
(such as premises wiring within a single building), but some can cross between
two levels (for example, both the distribution network and premises wiring).
Typically transformers prevent propagating the signal, which requires multiple
technologies to form very large networks. Various data rates and frequencies are
used in different situations. A number of difficult technical problems are common
between wireless and power line communication, notably those of spread
spectrum radio signals operating in a crowded environment. Radio interference,
for example, has long been a concern of amateur radio groups
LIGHTNING ARRESTERS
TRAINING REPORT
ON
NORTHERN COALFIELD LIMITED
SINGRAULI(M.P)
AT
BYSHILPA YADAV
BACHELOR OF TECHNOLOGY
ELECTRICAL ENGINEERING
SECTION-EL(N1),7TH SEM
1301020068
CONCLUSION
The implant training was completed successfully. I learnt things like how actually
substation works.
I also learnt maintenance and tests carried out in substation.
I understood the operation and real time working of different equipments in the
substation.
The training will definitely help me in my future