Generator Protection
Generator Protection
Protection
Topic Outline
I.
II.
Generator Configuration
Generator Configuration
Generator Configuration
Generator Configuration
Generator Connections
Direct Connected
Unit Connected
Sample Nameplate
Generator Grounding
Generator Grounding
10
Generator Grounding
11
12
13
14
15
16
Protection Requirements
To detect faults on the generator
To protect generator from the effects of abnormal
power system operating conditions
To isolate generator from system faults not cleared
remotely
17
18
19
20
RTDs
21
Differential Protection
High-Speed protection that can detect three-phase, phase to
22
Differential Protection
23
Differential Protection
24
Overcurrent Protection
For small generators this may be the only protection applied.
50/51
25
Overcurrent Protection
Some helpful points in setting overcurrent relays:
From C37.102-2005:
Use IOC and TOC unit having an EI characteristic.
IOC is set to 115% FLC and is used to torque-control TOC unit
TOC unit is set to 75%-100% FLC and a time settings operating
7sec @ 218% FLC or coordinate with downstream relay.
From ABCs of Overcurrent Protection:
Set protection above FLC and above decrement curve in the
lowest decade.
Set protection below overload curve.
Set protection to intersect with the decrement curve in the second
lowest decade.
26
Overcurrent Protection
27
28
29
30
31
32
33
Low-Impedance Grounding
The grounding resistor or reactor is selected to limit the
34
Low-Impedance Grounding
35
High-Impedance Grounding
High-resistance generator neutral grounding uses a
36
High-Impedance Grounding
An SLG fault is generally limited to 3 to 25 primary
amperes.
Others only uses resistor aside from transformers but the
fault current is limited to 5A.
37
High-Impedance Grounding
38
Overvoltage/Overcurrent Schemes
59G works on fundamental
frequency (3V0)
Typically set at 5V
Measures maximum at
40
41
43
44
45
46
47
48
49
Heating
Flux distortion causing violent vibration of rotor
Desirable to detect presence of first earth fault and give
an alarm.
50
51
52
53
55
56
58
59
60
Abnormal Frequency
Protection (81)
61
62
63
64
65
67
68
69
71
72
73
74
Loss-of-Excitation
Protection (40)
75
Loss-of-Field Protection
Causes of loss-of-field:
Accidental trip of field breaker
Field open circuit
Field short circuit
Voltage regulator system failure
Loss of supply to excitation system
Loss-of-Field Protection
On loss-of-field, apparent impedance of fully loaded machine
travels from loaded value in the 1st quadrant to the 4th quadrant
close to X axis at value just above the direct axis transient
reactance (about 2-7 seconds).
77
Loss-of-Field Protection
78
Loss-of-Field Protection
For small and less important machines, a single-zone
offset mho is used to detect this condition. For larger
machines, two-zone offset mho is used.
Smaller Circle (#1)
Diameter of 1.0 pu impedance on machine base
Small almost instantaneous time delay
Offset equal to Xd/2
Larger Circle (#2)
Diamter of Xd
Time delay of 30-60 cycles
Loss-of-Field Protection
Two-zone Offset Mho characteristic
80
Negative-Sequence
Current(46)
81
Negative-Sequence Protection
In the real world, IA does not necessarily equal to IB and IC
Unbalances are caused by:
System asymmetries
Unbalanced loads
Unbalanced system faults
Open phases
Produce negative-sequence currents-induce a double frequency
current
82
Negative-Sequence Protection
I2 crosses the air gap, appears in rotor as double-frequency
current
Flows in rotor surface, non magnetic wedges
Severe overheating, melting of wedges into air gap
Standards permits 5-10% of I2
Short-time limits expressed as 22 = , where K is a design
constant
83
Negative-Sequence Protection
84
Negative-Sequence Protection
Short-time
values apply for
120 seconds or
less. Beyond
120 seconds,
the continuous
capability
should be used.
85
Negative-Sequence Protection
86
Anti-motoring or Reverse
Power (32R)
87
Generator Motoring
Occurs when the energy supply to the prime mover is cut
off while the generator is still on the line. A primary
indication of motoring is the flow of real power into the
generator.
Estimated power required to motor the idling prime mover
is:
88
89
Out-of-Step Protection
When a fault occurs on the power system, the generator can
Out-of-Step Protection
91
Out-of-Step Protection
Adverse Effects
Out-of-Step Protection
Determination of Electrical Center
93
Out-of-Step Protection
94
Out-of-Step Protection
95
Out-of-Step Protection
96
Inadvertent Energization
97
Inadvertent Energization
When an offline generator is energized (w/o field) on turning gear
or coasting to a stop, the generator behaves as an induction motor
and can be damaged within a few seconds
Causes:
Operating Errors
Open Breaker Flashovers
Control Circuit Malfunctions
98
Inadvertent Energization
When an offline generator is energized (w/o field) on turning gear
or coasting to a stop, the generator behaves as an induction motor
and can be damaged within a few seconds
Causes:
Operating Errors
Open Breaker Flashovers
Control Circuit Malfunctions
99
Inadvertent Energization
The following protection elements may detect or can be set to
detect inadvertent energizing:
Loss of Field Protection
Reverse Power
Negative-sequence overcurrent
Breaker Failure
System backup
100
Inadvertent Energization
Inadvertent energization protection needs to be in service when the
generator is out of service.
Dedicated protection:
Directional Overcurrent
Frequency Supervised Overcurrent
Distance Relay
Voltage Supervised Overcurrent
Auxilliary Contact-Enabled Overcurrent
Overcurrent Supervised by Multiple Elements
101
Loss-of-Potential (60)
102
Loss-of-Potential
Loss of the voltage transformer (VT) signal can occur because
of a number of cases, most commonly fuse failure.
It could be VT or wiring failure, an open circuit in the draw-out
assembly, an open contact due to corrosion or blown fuse
Such loss can cause protective relay misoperation or failure or
generator voltage regulator runaway, which can lead to
generator overexcitation
It is important to detect loss-of-potential condition, sometimes
called, fuse loss (60FL)
103
Loss-of-Potential
104
105
106
108
Tripping Modes
109
Tripping Modes
Simultaneous Tripping
110
Tripping Modes
Unit Separation
111
Tripping Modes
These tripping scheme must be review and applied according to
the present generator application
Selection would depend on the ff:
Type of prime mover
Impact of the sudden loss of output power on the electrical
system and prime mover
Safety to personnel
Operating experience
Management of unit auxiliary loads during emergency
shutdown.
112
Tripping Modes
113
114
Sample Logic
115
Sample Logic
116
Sample Logic
117
Sample Logic
118
References:
Protective Relaying: Principles and Applications by Blackburn
IEEE Tutorial on Synchronous Generators
Basler BE1-11g manual
IEEE Seminar on Protective Relaying by Russ Patterson
C37.101-2006
C37.102-2006
119