If a turbine generator set is running at synchronous speed and the turbine trips due to low steam pressure or another reason, the generator will draw power from the system instead of supplying it, causing the generator to operate like a motor which could damage the turbine blades. Reverse power protection is used to stop the generator in this situation to avoid this.

Uploaded by

Naresh Pattanaik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views2 pages

Answer: Is This Answer Correct ?

If a turbine generator set is running at synchronous speed and the turbine trips due to low steam pressure or another reason, the generator will draw power from the system instead of supplying it, causing the generator to operate like a motor which could damage the turbine blades. Reverse power protection is used to stop the generator in this situation to avoid this.

Uploaded by

Naresh Pattanaik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

If T.

G set is running on synchronus speed and turbine is


triped on low steam pressure or some other resion, The
Generator will take the power from system instated of
giving and Generator will work as Motor,that will harmful
to Turbine [Link] avoiding this reverse power
protection are used to stop the Generator.
Is This Answer Correct ?

48 Yes

Answer / Ramji
The Generator will run still since there some steam trapped
in Turbine. This suitation is called Low Forward Power since
there is not enough Steam to run the Generator in desired
speed. This occurs because of some trapped steam in turbine
for some seconds. Now Days special vents doors are designed
in turbine to release these steam on account of tripping of
turbines
But Normally in protection Trip Logic of Generators there
will be Class:A, Class:B, Class:C
For Class A Gen Breaker will trip for below faults
U/V Stage-2 , O/V , Low Forward Power, Reverse Reactive
power, Neg Ph Seq ,Over Voltage
For Class B Turbine Breaker will Trip which also trip Gen
breaker instantly for below faults
Differential protection , Restricted Earth Fault .....

For Class C Grid Breaker will trip for below faults


Over Frequency and Under Frequency Under Voltage stage-1
and Over voltage
Because when you trip Gen Breaker for Under voltage it will
result in whole plant black out so for stage-1 tripping of
grid breaker will do
similarly for All turbine faults the Gen Breaker is tripped
so that it is isolated from the system