IL-NT MRS 2.1 Reference Guide
IL-NT MRS 2.1 Reference Guide
IL-NT MRS 2.1 Reference Guide
InteliLite NT MRS
Modular Gen-set Controller
Compact Controller for Single Operating Gen-sets
(IL-NT MRS10/11/15/16 unit)
SW version 2.1, November 2012
Reference Guide
Table of Contents
Table of Contents .................................................................................................................................... 2
General Guidelines .................................................................................................................................. 5
What describes this manual? .............................................................................................................. 5
!! Warnings !! ....................................................................................................................................... 5
Symbols ............................................................................................................................................... 5
Text ..................................................................................................................................................... 6
Dangerous voltage .............................................................................................................................. 6
Adjust set points .................................................................................................................................. 6
General Description ................................................................................................................................. 7
Description of the controller system (with all options) ......................................................................... 7
What is in the package? ...................................................................................................................... 7
IL-NT RS232 Communication plug-in card ......................................................................................... 7
IL-NT RS232-485 Communication plug-in card ................................................................................ 11
IL-NT S-USB Service USB communication plug-in card .................................................................. 12
IB-Lite Ethernet communication plug-in card .................................................................................... 12
IL-NT-GPRS GSM and GPRS plug-in modem ................................................................................. 13
IL-NT AOUT8 Gauge driver module.................................................................................................. 14
IL-NT BIO8 Hybrid binary input/output module ................................................................................. 16
IC-NT CT-BIO7.................................................................................................................................. 17
IL-NT RD Remote display software................................................................................................... 18
Remote announciator IGL - RA15 ..................................................................................................... 18
IG IOM/PTM module ......................................................................................................................... 19
IG-IB Internet bridge .......................................................................................................................... 20
IL-NT Terminals ..................................................................................................................................... 21
IL-NT terminals and face ................................................................................................................... 21
Installation.............................................................................................................................................. 22
Mounting............................................................................................................................................ 22
Recommended Wiring ........................................................................................................................... 23
MRS Wiring Diagram ..................................................................................................................... 23
Getting Started ...................................................................................................................................... 24
How to install ..................................................................................................................................... 24
Current measurement ....................................................................................................................... 27
Earth Fault measurement (module) .................................................................................................. 29
Voltage measurement and generator connection types ................................................................... 30
Analog inputs..................................................................................................................................... 32
Binary inputs and outputs .................................................................................................................. 38
Recommended CAN/RS485 connection ........................................................................................... 39
Extension modules (CAN bus) connection ....................................................................................... 41
Inputs and Outputs ................................................................................................................................ 43
Binary inputs IL-NT - default ............................................................................................................ 43
Binary inputs list ............................................................................................................................. 43
Binary outputs IL-NT MRS16 - default ............................................................................................. 46
Binary outputs - list ............................................................................................................................ 46
Analog inputs..................................................................................................................................... 55
Analog outputs .................................................................................................................................. 56
Setpoints ................................................................................................................................................ 57
Password........................................................................................................................................... 57
Basic Settings.................................................................................................................................... 57
Comms Settings ................................................................................................................................ 61
Engine Params .................................................................................................................................. 64
Engine Protect ................................................................................................................................... 68
Gener Protect .................................................................................................................................... 69
*Extension I/O ................................................................................................................................... 72
Date/Time .......................................................................................................................................... 73
Sensors spec..................................................................................................................................... 74
NT
SMS/E-Mail ....................................................................................................................................... 74
Alternate Cfg ..................................................................................................................................... 76
*EarthFaultProt .................................................................................................................................. 77
*ECU-controlled engine support ............................................................................................................ 79
Identifying configured ECU ............................................................................................................... 80
Values read from ECU ...................................................................................................................... 81
Diagnostic messages read from ECU ............................................................................................... 81
Analog inputs..................................................................................................................................... 81
Connection description ...................................................................................................................... 82
Sensor Specification .............................................................................................................................. 85
Background of the sensor calibration ................................................................................................ 85
Default sensor curves ....................................................................................................................... 85
Function Description .............................................................................................................................. 86
OFF Mode ......................................................................................................................................... 86
MAN Mode ........................................................................................................................................ 86
AUT mode ......................................................................................................................................... 87
Alarm Management ............................................................................................................................... 88
Sensor Fail (FLS) ............................................................................................................................. 88
Warning (WRN) ................................................................................................................................. 88
Breaker open and cooling (BOC) ...................................................................................................... 88
Shut down (SD) ................................................................................................................................. 89
Voltage phase sequence detection ................................................................................................... 89
Gen-set Operation States ...................................................................................................................... 91
List of possible events ....................................................................................................................... 93
History file.......................................................................................................................................... 94
Init Screens ............................................................................................................................................ 97
Customer Logo screen ...................................................................................................................... 97
Firmware Init screen .......................................................................................................................... 97
Language screen .............................................................................................................................. 97
User Interface screen ........................................................................................................................ 97
Remote Control and Data Logging ........................................................................................................ 98
Direct connection to the PC .............................................................................................................. 98
PC software - LiteEdit ....................................................................................................................... 99
Modbus protocol ................................................................................................................................ 99
Remote Communication ...................................................................................................................... 105
Internet connection .......................................................................................................................... 105
SNMP connection ........................................................................................................................... 105
Recommended ISDN modem ......................................................................................................... 105
Recommended GSM modem.......................................................................................................... 105
Mobile SIM card setting ................................................................................................................... 106
Short guide how to start using IL-NT-GPRS module ...................................................................... 106
IL-NT-RD Remote display software ..................................................................................................... 109
General description ......................................................................................................................... 109
Warning ! ......................................................................................................................................... 109
IL-NT-RD Software installation........................................................................................................ 109
IL-NT-RD Wiring .............................................................................................................................. 110
Function description ........................................................................................................................ 113
SW compatibility .............................................................................................................................. 113
Maintenance ........................................................................................................................................ 114
Backup battery replacement ........................................................................................................... 114
Technical Data ..................................................................................................................................... 116
Inputs/Outputs overview .................................................................................................................. 116
Generator protections ..................................................................................................................... 116
Language support ........................................................................................................................... 117
Power supply ................................................................................................................................... 117
Operating conditions ....................................................................................................................... 117
#
Low Temperature modification ...................................................................................................... 117
Dimensions and weight ................................................................................................................... 118
Generator ........................................................................................................................................ 118
Binary inputs and outputs ................................................................................................................ 118
NT
NT
General Guidelines
What describes this manual?
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTION
controllers family that shall be followed during installation and maintenance of the Inteli NT genset
controllers.
It is intended for use by gen-set control panel builders and for everybody who is concerned with
installation, operation and maintenance of the gen-set.
This manual describes MRS 10/11/15/16 software, which is designed for single set applications.
What is the purpose of the manual?
This manual provides general information how to install and operate InteliLite-NT MRS controller.
This manual is dedicated for
Operators of gen-sets
Gen-set control panel builders
For everybody who is concerned with installation, operation and maintenance of the gen-set
!! Warnings !!
Remote control
NT
InteliLite controller can be remotely controlled. In case of the work on the gen-set check, that
nobody can remotely start the engine.
To be sure:
Disconnect remote control via RS232 line
Disconnect input REM START/STOP
or
Disconnect output STARTER and outputs GCB CLOSE/OPEN
NT
Because of large variety of InteliLite parameters settings, it is not possible to describe any
NT
combination. Some of InteliLite functions are subject of changes depend on SW version.
The data in this manual only describes the product and are not warranty of performance or
characteristic.
Symbols
Symbols used in this manual:
Grounding
point symbol
NT
AC voltage
symbol
DC voltage
symbol
Text
PAGE
Break Return
Generator protections
REMOTE START/STOP
*Something
^Something
Note:
ComAp believes that all information provided herein is correct and reliable and reserves the right to
update at any time. ComAp does not assume any responsibility for its use unless otherwise expressly
undertaken.
Note:
SW and HW must be compatible (e.g. IL-NT-MRS10 firmware and IL-NT MRS10 HW) otherwise the
function wil be disabled. If wrong software is downloaded, message HARDWARE INCOMPATIBLE
appears on controller screen. In this case download correct software and use Boot jumper
programming close Boot jumper and follow instructions in LiteEdit or follow video guide Boot
Jumper Programming at http://www.comap.cz/support/training/training-videos/.
NT
General Description
Description of the controller system (with all options)
NT
InteliLite -MRS is a comprehensive controller for single generating sets. IL-NT MRS 15/16 features
extended support of electronic engines and extension modules.
NT
InteliLite controllers are equipped with a powerful graphic display showing icons, symbols and bargraphs for intuitive operation, which sets, together with high functionality, new standards in Gen-set
controls.
InteliLite automatically starts the Gen-set, closes the Gen-set C.B. when all conditions are met, then
stops the engine on external signal or by pressing push buttons.
NT
InteliLite provides gas engine support without ventilation.
NT
The key feature of InteliLite is its easy-to-use operation and installation. Predefined configurations
for typical applications are available as well as user-defined configurations for special applications.
Description
NT
Optional / Obligatory
IL-NT MRS
InteliLite
central unit
Obligatory
IL-NT-RS232
IL-NT-RS232-485
IL-NT-S-USB
IB-Lite
IL-NT-GPRS
IL-NT-AOUT8
IL-NT-BIO8
IC-NT-CT-BIO7
**IL-NT RD
IGL-RA15
Remote annunciator
IG-IOM/PTM
IG-IB
AT-LINK-CONV
AT-LINK-CABLE
*Remote display for IL-NT controllers uses standard IL-NT controller with Remote display software
Hint:
For detailed information about extension modules used with IL-NT controllers, please see the IL-NTAccessory Modules manual.
IL-NT RS232 is optional plug-in card to enable InteliLite for RS232 communication. This is required
for computer or Modbus connectin. Card inserts into expansion slot back on the controller.
To insert the module, you must open the cover first (use screwdriver to open) and then insert the
module into slot. Once you have insert it, the module will snap under plastic teeth. It is supposed to be
NT
installed permanently. Should you need to remove it, the safest way is to remove whole back cover
and than remove module manually.
How to install RS232 communication module:
1. Insert a screwdriver into the slot of the cover.
NT
4. Break apart the small cover into two pieces. Do not throw away the smaller part!
NT
Hint:
When you insert RS 232 communication module, the boot jumper is hidden. For that reason we
recommend to use RS 232 communication module with the boot jumper placed on it. See pictures
below:
10
Hint:
Boot jumper programming In case of interrupted programming or other software failure is possible to
use the boot jumper programing to restore controller to working order. Connect controller to PC, run
LiteEdit and wait until connection bar at bottom turns red. Than run programming process via menu
Controller -> Programming and cloning Programming. Select correct firmware and confirm dialog.
Than follow instructions in LiteEdit.
Or follow video guide Boot Jumper Programming at http://www.comap.cz/support/training/trainingvideos/.
- Please see chapter IL-NT RS232 interface (optional card) for technical details.
IL-NT RS232-485 is optional plug-in card to enable InteliLite the RS232 and RS485 communication.
This is required for computer or Modbus connection. Card inserts into expansion slot back on the
controller. The IL-NT RS232-485 is a dual port module with RS232 and RS485 interfaces at
independent COM channels. The RS232 is connected to COM1 and RS485 to COM2.
To insert the module, please follow the instructions for IL-NT RS232 module, procedure is analogous.
You must open the cover first (use screwdriver to open) and then insert the module into slot. Once you
have insert it, the module will snap under plastic teeth. It is supposed to be installed permanently.
Should you need to remove it, the safest way is to remove whole back cover and than remove module
manually.
RS485
RS232
Boot jumper
RS485 Terminator jumper
Hint:
- Boot jumper programming In case of interrupted programming or other software failure is possible
to use the boot jumper programing to restore controller to working order. Connect controller to PC, run
LiteEdit and wait until connection bar at bottom turns red. Than run programming process via menu
Controller -> Programming and cloning Programming. Select correct firmware and confirm dialog.
Than follow instructions in LiteEdit.
Or follow video guide Boot Jumper Programming at http://www.comap.cz/support/training/trainingvideos/.
- Please see chapter IL-NT RS232-485 interface (optional card) for technical details.
NT
11
IL-NT S-USB is optional plug-in card to enable InteliLite for communication via USB port. This is
required for computer or Modbus connecting. Card inserts into expansion slot back on the controller.
To insert the module, you must open the cover first (use screwdriver to open) and then insert the
module into slot. Once you have inserted it, part of the module will remain over plastic box. It is
supposed to be used as a service tool. When you need to remove it, grab module in cutouts and pull it
up manually.
Hint:
-
Use the shielded USB A-B cable with this module! Recommended is ComAp cable Order
code: USB-LINK CABLE 1.8M.
Please see chapter IL-NT S-USB interface (optional card) for technical details.
Hint:
Boot jumper programming In case of interrupted programming or other software failure is possible to
use the boot jumper programing to restore controller to working order. Connect controller to PC, run
LiteEdit and wait until connection bar at bottom turns red. Than run programming process via menu
Controller -> Programming and cloning Programming. Select correct firmware and confirm dialog.
Than follow instructions in LiteEdit.
Or follow video guide Boot Jumper Programming at http://www.comap.cz/support/training/trainingvideos/.
NT
12
Use Ethernet UTP cable with RJ45 connector for connection of the module into your ethernet network.
The module can be also connected directly to a PC using cross-wired UTP cable.
Hint:
-
Modbus TCP protocol using IB-Lite communication module requires setting COM1 Mode =
DIRECT and COM2 Mode = MODBUS.
Connection to LiteEdit via IP address is not possible if AirGate function is enabled. In this case
use Airgate connection. If you require connection using IP address, kindly disable setpoint
Airgate [ENABLE, DISABLE].
For details see newest version of IB-Lite Reference Guide.
NT
13
IL-NT-GPRS is a modem plug-in module which support GPRS internet connection and also dial up
connection. This module incorporates support of AirGate technology for plug and play connection via
GPRS. Module is usually used for connection to remote monitoring and controlling system
WebSupervisor (http://websupervisor.comap.cz) or to LiteEdit PC software. Module is capable of
sending alarm SMS based on settings in SMS/Email setpoint group.
Hint:
Quick guide how to start using this module is in chapter Remote Communication - Short guide how to
start using IL-NT-GPRS module or on ComAp webpage http://www.comap.cz/products/detail/IL-NTGPRS.
NT
14
Installing IL-NT AOUT8 module is similar to installing RS 232 module. The difference is that module
fits to extension module slot and after installing IL-NT AOUT8 you do not put back the small cover.
IL-NT AOUT8 module:
Typical wiring
Hint:
Please see chapter IL-NT AOUT8 interface (optional card) for technical details.
NT
15
NT
16
Hint:
Please see chapter IL-NT BIO8 interface (optional card) for technical details.
IC-NT CT-BIO7
Hybrid current input and binary input/output module
IC-NT CT-BIO7 is optional plug-in card. Through this card controller can accommodate one AC
current (CT) measuring input and up to 7 binary inputs or outputs. In LiteEdit PC configuration tool
(version 4.4 and higher) it is possible to easily choose if particular I/O will be binary input or output.
To insert the module, you must open the cover first (use screwdriver to open) and then insert the
module into slot. Once you have inserted it, the module will snap under plastic teeth. It is supposed to
be installed permanently. Should you need to remove it, the safest way is to remove whole back cover
and than remove module manually. Installing IC-NT CT-BIO7 module is similar to installing RS 232
module. The difference is that module fits to extension module slot and after installing IC-NT CTBIO7 you do not put back the small cover.
NT
17
Hint:
See more details in Earth Fault measurement or in IC-NT CT-BIO7 interface chapter.
NT
18
120 (4,7)
125 (4,9)
~ 25 (1,0)
106 (4,2)
54 (2,1)
44 (1,7)
165 (6,5)
~ 35 (1,4)
38 (1,5)
40 (1,6)
~ 75 (3,0)
Cutout
for Remote Announciator
180 (7,1)
185 (7,3)
167 x 108 mm
(6,6 x 4,3)
IG IOM/PTM module
IG-IOM and IGS-PTM modules are I/O extension modules equipped with 8 binary inputs, 8 binary
outputs, 4 analogue inputs and one analogue output. The module can be used for AMF25, MRS15,
16, 19 only.
Binary inputs and outputs are configurable the same way like inputs and outputs on iL.
Analogue inputs are configurable like iL with the limitation that the binary and tristate mode
can not be used on PTM module.
The protection of analogue IOM/PTM inputs is activated by overcrossing the limits, active only
when the engine is running.
IG-IOM analogue inputs are resistive (the same parameters like IL-NT) 0 -2,4 k. The
module IOM is designed for especially VDO resistive sensors.
IGS-PTM analogue inputs are configurable by jumpers to ranges 0-250, 0-100mV, 0-20mA.
The module can be used especially for Pt100 sensors and current sensors. The module PTM
is not suitable for VDO temperature sensor.
Hint:
- For connection details please refer to chapter Extension modules (CAN bus) connection.
- For a description of setting IGS-PTM module with current/voltage sensors please see the Extension
modules manual.
- When module is not configured by LiteEdit SW, controller does not show related values and
setpoints
- If IGS-PTM is not communicating to a controller, ShutDown protection on controller is activated.
NT
19
Hint:
If IGS-PTM is not communicating to a controller, ShutDown protection on controller is activated.
See the documentation of IGS-PTM for the technical and function description.
NT
NT
20
IL-NT Terminals
IL-NT terminals and face
NT
21
Installation
Mounting
The controller is to be mounted onto the switchboard door. Requested cutout size is 175x115mm. Use
the screw holders delivered with the controller to fix the controller into the door as described on
pictures below.
NT
22
Recommended Wiring
MRS Wiring Diagram
Hint:
It is possible to start Volvo and Scania engines via CAN bus. See Engines started via CAN bus
NT
23
Getting Started
How to install
During the configuration of controller or setpoints changes is required a password to the
controller. The default password from ComAp is 0.
General
To ensure proper function:
Use grounding terminals.
Wiring for binary inputs and analog inputs must not be run with power cables.
Analog and binary inputs should use shielded cables, especially when length >3m.
Hint:
Beware of heavy harnesses hanging down from controller terminals. Harnesses must be
tightened to panel doors or other suitable place as close to controller as possible.
Wiring
Tightening torque, allowable wire size and type, for the Field-Wiring Terminals:
Based on terminal type:
PA256:
Grounding
The shortest possible piece of wire should be used for controller grounding.
2
Use cable min. 2,5mm
Brass M4x10 screw with star washer securing ring type grounding terminal shall be used.
The negative - battery terminal has to be properly grounded.
Switchboard and engine has to be grounded in common spot. Use as short as possible cable
to the grounding point.
Power supply
To ensure proper function:
2
Use min. power supply cable of 1.5mm
NT
24
Maximum continuous DC power supply voltage is 36VDC. Maximum allowable power supply voltage
is 39VDC. The InteliLites power supply terminals are protected against large pulse power
disturbances. When there is a potential risk of the controller being subjected to conditions outside its
capabilities, an outside protection devise should be used.
It is necessary to ensure that potencial difference between generator current COM terminal and
battery - terminal is maximally 2V. Therefore is strongly recommended to interconnect
these two terminals together.
Hint:
NT
The InteliLite controller should be grounded properly in order to protect against lighting strikes!!
The maximum allowable current through the controllers negative terminal is 4A (this is dependent on
binary output load).
NT
For the connections with 12VDC power supply, the InteliLite includes internal capacitors that allow
the controller to continue operation during cranking if the battery voltage dip occurs. If the voltage
before dip is 10V, after 100ms the voltage recovers to 7 V, the controller continues operating. During
this voltage dip the controller screen backlight can turn off and on but the controller keeps operating.
It is possible to further support the controller by connecting the external capacitor and separating
diode or I-LBA module.
The capacitor size depends on required time. It shall be approximately thousands of microFarads.
The capacitor size should be 5 000 microFarad to withstand 150ms voltage dip under following
conditions:
Voltage before dip is 12V, after 150ms the voltage recovers to min. allowed voltage, i.e. 8V
Hint:
Before the battery is discharged the message "Low BackupBatt" appears.
Or by connecting special I-LBA Low Battery Adaptor module:
The I-LBA module ensures min. 350ms voltage dip under following conditions:
RS232 and other plug-in module is connected.
Voltage before dip is 12V and after 350ms the voltage recovers to min. allowed voltage 5V.
The I-LBA enables controller operation from 5VDC (for 10 to 30 sec).
The wiring resistance from battery should be up to 0.1 Ohm for I-LBA proper function.
Hint:
I-LBA may not eliminate voltage drop when used with low temperature (-40C) version of controller
and display heating element is on (below 5C). Current drain of heating element exhausts LBA
capacitors very fast .
NT
25
NT
26
Magnetic pick-up
To ensure proper function:
Use a shielded cable
MAGNETIC
PICK-UP
iL
Signal
a
D
C
Signal
GAC
Speed Control Unit
ESD 5500
+
Power
Supply
-
Power
Supply
+
Battery
Be aware of interference signal from Speed governor when one speed pick-up is used.
If engine will not start:
- Check ground connection from pick-up to controllers, eventually disconnect ground connection
to one of them
- Galvanically separate InteliLite RPM input using ComAp separation transformer RPM-ISO
(1:1)
NT
- Use separate pick-up for Speed governor and InteliLite
Hint:
In some cases the controller will measure a RPM value even though the gen-set is not running:
RPM is measured from the generator voltage (Gear teeth = 0)
IL-NT is measuring some voltage value on input terminals due to open fusing.
If RPM > 0 the controller will be put into a Not ready state and the engine will not be allowed to start.
Current measurement
The number of CTs is automaticaly selected based on selected value of setpoint ConnectionType
[3Ph4Wire / 3Ph3Wire / Split Ph / Mono Ph].
Hint:
-
Further informations about measurement limits are at setpoint CT Ratio [/5A] description in
chapter Setpoints - Basic Settings.
Generator currents and power measurement is suppressed if current level is bellow
<1% of CT range.
NT
27
It is necessary to ensure that potencial difference between generator current COM terminal and
battery - terminal is maximally 2V. Therefore is strongly recommended to interconnect
these two terminals together.
CT location
NT
28
Technical characteristics
-
Hint:
For more technical details see IC-NT CT-BIO7 interface.
Hint:
For more information about the application settings see EarthFaultProt setpoint group
Operating principle
When the measured current exceeds the set value, this indicates that part of the current is dispersed
to earth and after the set Earth Fault Del then Earth Fault Sd protection and AL EarthFault output are
activated. Earth Fault protection is not active when gen-set does not run and also when EF Protection:
DISABLED.
NT
29
NT
30
3 Phase 3 Wires
DELTA Connection
Hint:
Only L1, L2 and L3 wires should be connected. In case of HI-LEG (WILD-LEG, RED-LEG) DELTA
connection the N (neutral)
wire (in the diagram connected between T6 and T9) has to be disconnected.
No separation transformers for three wires voltage connection (without N) are needed.
Split Phase
DOUBLE DELTA Connection
NT
31
Hint:
There has been a change in wiring of monophase at voltage terminals between firmwares IL-NT1.4
and IL-NT1.5! Picture above shows connection for IL-NT 1.5. Wiring for older firmwares is described in
older IL-NT manuals, line L1 was connected to all three terminals L1,L2 and L3.
Mono Phase MONOPHASE Connection
Hint:
Switchboard lighting strike protection according standard regulation is expected for all 4 connection
types!!!
Hint:
Phase sequence check is not possible to evaluate under voltage 50V what causes that if measured
voltage 50V is within the allowed range, controller will not allow to close the GCB, even if relevant LED
diod on front panel of IL-NT lits.
Analog inputs
Three analog inputs are available on the IL-NT. First analog input is fixed to be used for engine Oil
Pressure.
Configuration
Each analog input can be configured by LiteEdit software following way. (First analog input is
dedicated to engine Oil pressure).
NT
32
LiteEdit
Type
Not used
Alarm
Monitoring
Name
Config
Analog
Binary (not supp. by PTM)
Tri-state (not supp. by PTM)
Physical dimension
Dim
bar,%,C,
Polarity
Contact
type
NC
NO
Protection direction
Protection
Over
Over+Fls
Under
Under+Fls
Resolution 0 0,00001
Possibility
Analog input isnt used
Analog is measured and used
for protection
Analog is only measured and
not used for protection
Up to 14 ASCII characters
Analog measuring in specified
range.
Binary: open/close - threshold
750 .
Three-state: open/close threshold 750 ,
Failure <10 or > 2400
Up to 4 ASCII characters
(Valid only for analog inputs)
Valid only for binary and threestate inputs
Valid only for binary and threestate inputs
Overstep. Sensor Fail does
not activate protection.
Overstep and Sensor Fail
activates protection.
Under step. Sensor Fail does
not activate protection.
Under step and Sensor Fail
activates protection.
User changeable and
configurable
Sensor resolution
(Valid only for analog inputs)
Each Analog input has separate set points for two level alarm setting. Analog input alarm levels and
delay adjust in Extension I/O and Engine Protect group.
Hint:
Description of Sensor fail evaluation can be found in chapter Alarm Management, article Sensor Fail
(FLS).
- POWER
COM
AI1
AI2
AI3
3 x RESISTIVE
SENSOR
NT
33
- POWER
COM
AI1
AI2
AI3
2x
470
Hint:
Description of analog inputs with COM terminal and 4 pins relates to units with HW version 1.3. Older
HW versions do not have COM terminal and use only 3 pins AI1, AI2 and AI3.
Wiring
Wiring diagrams of analog inputs for IL-NT HW 1.3:
NT
34
Analog inputs are designed for resistive sensors with resistance in range of 0 to 2,4k.
To ensure a proper function use shielded cables, especially for length over >3m.
COM terminal is dedicated to measure ground voltage potential difference between engine and
controller.
As binary input
Open, close state are detected, threshold level is 750 .
NT
35
NT
36
NT
R1
R2
150 [1%,0,5W] 100 [1%,0,5W]
680 [5%,2W] 100 [1%,0,5W]
1500 [5%,3W] 100 [1%,0,5W]
R = 160 [1%,0,5W]
Curve
AI 0-10V.CRV
AI 0-30V.CRV
AI 0-65V.CRV
AI 4-20mA.CRV
37
Hint:
Please note that external resistors disconnection, connection incorrect resistors or input voltage value
during operation may cause an analog input destruction.
Practical example: VDO pressure sensor 0 6bar with linear voltage output 0 10V
Conversion table
Vout [V] 0 1
2
3
4 5 6
7
8
9 10
P [bar] 0 0,6 1,2 1,8 2,4 3 3,6 4,2 4,8 5,4 6
Modify one of analog input in LiteEdit configuration and load curve AI 0-10V.CRV
Than you can change resolution and measured value name witch is default displayed at V (volts).
For example if you have connected pressure sensor and his output voltage is 5V for pressure 3bar
you can change value V in column Dim: to Bar and by sensor specification adjust all corresponding
values in this column. In this case you can change the value at row 6. from 5 to 3.
When you finish with adjusting the values click OK and Write to controller.
iL
+
Power
Supply
+
Battery
NT
38
LOAD
iL
+
Power
Supply
+
Battery
RS485 connection
The line has to be terminated by 120 Ohm resistors at both ends.
External units can be connected on the RS485 line in any order, but keeping line arrangement (no
tails, no star) is necessary.
Standard maximum link length is 1000m.
Shielded cable has to be used, shielding has to be connected to PE on one side (controller side).
A) For shorter distances (all network components within one room) picture 1
interconnect A and B; shielding connect to PE on controller side
B) For longer distances (connection between rooms within one building) picture 2
interconnect A, B, COM; shielding connect to PE in one point
C) In case of surge hazard (connection out of building in case of storm etc.) picture 3
NT
39
8.iS-AIN
Addr.: 1
CAN1
1.iS-AIN
H
COM
L
H
COM
L
CAN1
Addr.: 1
H
COM
L
H
COM
L
CAN1
1.iS-CU
CAN2 CAN1
120
H
COM
L
Addr.: 8
1.iS-BIN
Addr.: in1
out1
H
COM
L
7.iS-BIN
120
H
COM
L
CAN1
2.iS-CU
CAN2 CAN1
120
H
COM
L
Addr.: in13
out7
120
PT5-HF-12DC-ST (CAN)
PT5-HF-5DC-ST (RS485)
H/A
L/B
COM
NT
H/A
L/B
COM
40
CAN H
CAN L
CAN L
COM
CAN H
10 ohm
15nF
CAN L
COM
CAN H
EXTENSION
MODULES
IGS-PTM (optional)
IGL-RA15 (optional)
or
CAN L
CAN H
IL-NT
120 ohm
H
COM
120 ohm
IG-IOM (optional)
CAN H
CAN L
CAN H
CAN L
120 ohm
CAN H
CAN L
EXTENSION
MODULES
COM
CAN L
COM
CAN H
10 ohm
15nF
CAN L
COM
CAN H
IGS-PTM (optional)
or
CAN L
CAN H
IL-NT
120 ohm
H
COM
IGL-RA15
(optional)
CAN HI
CAN LO
Engine
Electronic Control Unit
120 ohm
IG-IOM (optional)
Connection rules
CAN bus line must be connected in series, from one unit to the next (no star, no cable stubs, no
branches) both ends must be by the 120-ohm (internal or external) resistor terminated. Maximal CAN
bus length is up to 200 meters.
For CAN data cables details see chapter Technical data Communication interface. CAN cable
shielding connect to IL-NT COM terminal.
IL-NT contains internal fix 120-ohm resistor and must be located on the CAN bus end. New units with
HW version 1.3 have terminating resistor jumper located at CAN terminal.
New IG-IOM and IGS-PTM units contain internal jumper removable 120-ohm resistor (in older IOM
types are fix resistors). To be sure check resistor presence by ohmmeter. Unit with internal resistor
connect to the end of CAN line.
Following connections are supported (IOM, PTM, ECU order is not important).
IL- NT IG-IOM
IL- NT IGS-PTM
IL- NT IGL-RA15
IL- NT IG-IOM IGL-RA15
IL- NT IGS-PTM IGL-RA15
It is possible to connect only one IG-IOM or IGS-PTM and one IGL-RA15 to IL-NT.
Use
button in LiteEdit configuration window to activate CAN (J1939) interface with ECU.
NT
41
NT
42
Rem Start/Stop
BI2
Access Lock
BI3
Emergency Stop
BI4
Remote OFF
BI5
Sd Override
BI6
RemControlLock
Alarm
If the input is closed (or opened) selected alarm is activated.
Binary Alarm configuration items
Name
Contact type
Alarm type
Alarm active
NC
NO
Warning
BOC
Shut down
All the time
Engine running only
GCB Feedback
Use this input for indication, whether the generator circuit breaker is open or closed.
Hint:
IL-NT controller can work even without breaker feedbacks, in this case do not configure the feedback
to binary inputs.
For more details see chapter GCB fail detection.
NT
43
Rem Start/Stop
External request for engine run. AUT mode only.
Emergency Stop
If the input is opened, shut down is immediately activated. Input is inverted (normally closed) in default
configuration.
Hint:
In case of controller hardware or software fail, safe stop of the engine doesnt have to be ensured. To
back-up the Emergency Stop function it is recommended to connect separate circuit for disconnection
of Fuel Solenoid and Starter signals.
Sd Override
If the input is closed all alarms are disabled except the binary input EMERGENCY STOP and "engine
overspeed protection".
Hint:
Alarm Sd Override is indicated in the AlarmList if Sd Override mode active to inform the operator that
the engine is not protected.
Access Lock
If the input is closed, no setpoints can be adjusted from controller front panel and gen-set mode (OFFMAN-AUT) cannot be changed.
Hint:
Access lock does not protect setpoints and mode changing from LiteEdit. To avoid unqualified
changes the selected setpoints can be password protected.
Also the buttons Fault reset, Horn reset are not blocked at all and buttons Start and Stop in MAN
mode are not blocked.
Remote OFF
If closed, iL is switched to OFF mode (there are four modes OFF-MAN-AUT-TEST). When opens
controller is switched back to previous mode.
Hint:
This binary input should be connected to schedule timer switch, to avoid start of engine.
Remote MAN
If the input is active, MAN mode is forced to the controller independently on the position of the MODE
selector.
Remote AUT
If the input is active, AUT mode is forced to the controller independently on the position of the MODE
selector. If another of remote inputs is active, then the REMOTE AUT input has the lowest priority.
RemControlLock
If the input is active, setpoints writing or command sending from the external terminal is disabled.
Emergency MAN
If the input is activated the controller behaves like when switched to OFF Mode. Opens all binary
outputs. There is one exception STOP SOLENOID doesnt activate on this transition.
NT
44
Detection of "running" engine and subsequent alarm message "Wrn Stop Fail" is blocked.
The controller shows Emerg Man state and the engine can not be started.
Generator current and power measurement is active in this mode, regardless of the actual state of the
engine.
After the input is open again, the controller recovers to previous state and behaves according to the
actual situation .
Function is active in any controller mode.
Start Button
Binary input has the same function as Start button on the InteliLite front panel. It is active in MAN
mode only.
Stop Button
Binary input has the same function as Stop button on the InteliLite front panel. It is active in MAN
Mode only.
Hint:
Changed function of Stop Button. After the first pressing from running state, there is a standard delay
and controller change state to cooling. After holding the button down for 2 seconds controller goes to
stop state. The same holds true for BI Stop Button.
FaultResButton
Binary input has the same function as Fault reset button on the InteliLite front panel.
HornResButton
Binary input has the same function as Horn reset button on the InteliLite front panel.
^GCB button
Binary input has the same function as GCB button on the InteliLite front panel. It is active in MAN
mode only.
Lang Selection
Not configured
Language selection is done only through the controller display. Pressing ENTER and PAGE buttons
concurrently and then only PAGE button separately.
Configured on any binary input
If the output is opened the first (default) language is active and if the input is closed then the second
language is active. In case there is more languages available in the controller it is not possible to
select any other language even through the controller display.
Alt. Config.
This BI can switch between basic controller settings in Alternate Cfg setpoint group.
NT
45
Starter
BO2
Fuel Solenoid
BO3
GCB Close/Open
BO4
Prestart
BO5
Ready To Load
BO6
Alarm
Hint:
The description of binary outputs of a controller relates also to IOM/PTM modules.
Starter
The closed relay energizes the starter motor.
The relay opens if:
the firing speed is reached or
maximum time of cranking is exceeded or
request to stop comes up
Fuel Solenoid
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
EMERGENCY STOP comes or
Cooled gen-set is stopped or
in pause between repeated starts
Stop Solenoid
The closed output energizes stop solenoid to stop the engine. This output is deactivate 10s after the
still engine conditions are evaluated.
Hint:
For more detail see chapter Stop engine conditions in chapter Gen-set Operation States
Hint:
The engine can be started anytime, if all symptoms say the engine is steady regardless of the fact the
Stop Solenoid can still be active (in that case it is deactivated before cranking).
Stop Pulse
Output is active for 1 second after Stop Solenoid output activation. This signal is sent to ECU in case
of engine stop request.
Ignition
The output closes after reaching value of CrankRPM, fixed 30RPM. Opens after stopping of the
engine or in pause during repeated start.
NT
46
Prestart
The output closes prior to the engine start (Prestart) and opens when Starting RPM speed is reached.
During crank attempts the output is closed too.
The output could be used for pre-glow, pre-heat or prelubrication.
Cooling Pump
The output closes when gen-set starts and opens after stop of the engine.
Idle/Nominal
The output Idle/Nominal closes after the timer Idle Time elapses. The Idle Time counter starts to
countdown when Starting RPM reached. The Underspeed protection is not evaluated during fixed 5
seconds period after reaching Starting RPM. A Start Fail protection occurs if the RPM drop below
2RPM during idle.
Hint:
Connect binary output Idle/Nominal to speed governor to switch the speed: opened = IDLE,
closed=NOMINAL.
Air Valves
Closes together with Prestart. Opens after the engine is stopped.
Stopped engine conditions: RPM = 0, Engine Params: Starting Oil P, D+ (when enabled).
Alarm
The output closes if :
any warning or shutdown comes up or
the gen-set malfunctions
The output opens if
FAULT RESET is pressed
The output closes again if a new fault comes up.
Horn
The output closes if:
any warning or shutdown comes up or
the gen-set malfunctions
The output opens if:
FAULT RESET is pressed or
HORN RESET is pressed or
Max time of HORN is exceeded (Horn Timeout)
The output closes again if a new fault comes up.
GCB Close/Open
MRS11, 16:
The output controls the generator circuit breaker.
MRS10, 15 (GCB no GCB button):
The output closes automatically (in MAN or AUT mode) after engine is started,
Min Stab Time elapsed, and generator voltage and frequency is in limits.
Hint:
Supposed time to close (reaction time) of GCB is 0,1 sec.
IL-NT controller can work even without breakers feedback, in this case do not configure the feedback
to binary inputs.
For more details see chapter GCB fail detection.
GCB ON Coil
The output activates Generator Circuit Breaker coil.
47
GCB UV Coil
The output controls Generator Circuit Breaker coil after voltage drop-out.
Ready
The output is closed if following conditions are fulfilled:
Gen-set is not running and
No Shut down is active
Controller is not in OFF Mode
Ready To Load
The output is closed if genset is running and all electric values are in limits no alarm is active - it is
possible to close GCB or it is already closed. The output opens during cooling state.
Running
Output closes if the engine is in Running state.
Cooling
The output closes when gen-set is in Cooling state.
Supplying Load
Closed when the generator current is > 0,5% of the CT ratio.
Exact formulas:
Output is closed when the current at least in one phase is for 1 sec over CT ratio/200+2
Output is opened when the current in all three phases is for 1 sec below CT ratio/200+2
Hint:
Values are truncated after division, not rounded.
Fault Reset
The output is a copy of Fault Reset button on controller and binary input FaultResButton.
Gen Healthy
The output is copy of generator status LED on iL front panel. The output is closed if genset is running
and all genset electric values are in limits.
Exerc Timer 1
Output activates when Timer 1 is active. Simultaneously, gen-set is started when it is in AUT mode.
See setpoint Timer1..2Function [No Func/Auto Run/Mode OFF] for details.
Exerc Timer 2
Output activates when Timer 2 is active. See setpoint Timer1..2Function [No Func/Auto Run/Mode
OFF] for details.
Glow Plugs
The output closes prior to the engine start (by Prestart Time) and opens at the beginning of cranking
time. In case of repeated crank attempts the output closes always prior to the other engine start
attempts (by Prestart Time) and is opened during crank attempts.
NT
48
Fuel Pump
Output closes when the value of Fuel Level lies under the value of Fuel Pump ON setpoint and opens
when value of Fuel Pump OFF is reached.
Hint:
Fuel pump function is internaly connected to analog input 3 to monitor the actual fuel level in tank. It is
a prerequisite for this function to use a fuel level sensor at this analog input.
Temp Switch
This switch is assigned to the controllers analog input 2 commonly used for water temperature
sensing. The setpoints TempSwitch ON and TempSwitchOFF for on and off level adjustment are
located in the setpoint group Engine Params. Typical usage for this binary output can be activation of
fans or heaters. The output behaves based on the setpoint adjustment as described on picture lower:
NT
49
Power Switch
This switch is assigned to the gen-set active power. The setpoints PowerSwitch ON [kW] and
PowerSwitch OFF [kW] for on and off level adjustment are located in the setpoint group Engine
Params. Typical usage for this binary output can be switching of dummy load. The output behaves
based on the setpoint adjustment as described on picture lower:
Hint:
Power switch function and corresponding binary output is activated 30s after the engine is running.
Maintenance
Output closes if the Maintenance alarm activates, i.e. the gen-set has been running for more than
Engine Protect:WrnMaintenance.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Ctrl HeartBeat
Output signalizes Watchdog Reset. In a healthy state it blinks at 500ms : 500ms rate. When Watchdog
Reset occurs, it stops blinking.
Mode OFF
The output is closed, if OFF Mode is selected.
Mode MAN
The output is closed, if MAN Mode is selected.
NT
50
Mode AUT
The output is closed, if AUT Mode is selected.
AL D+ Fail
Output closes if gen-set is running and D+ input not energized.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Hint:
Treshhold level for D+ input is 80% supply voltage.
AL Gen >V
The output closes if the generator overvoltage shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Gen <V
The output closes if the generator undervoltage shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Gen Volts
The output closes if the generator over/under voltage shutdown alarm or voltage asymmetry shutdown
alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Gen Freq
Output closes if the generator over/under frequency shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Gen >Freq
Output closes if the generator over frequency alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Gen <Freq
Output closes if the generator under frequency alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL OverloadBOC
Output closes if the generator overload alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
NT
51
AL Stop Fail
Output closes when the engine has to be stopped, but speed or frequency or voltage or oil pressure is
detected (Still Engine conditions). This protection goes active when Stop Time setpoint value exceed
and any Running engine conditions are detected after stop command or under conditions for activating
Wrn Stop Fail alarm on Still engine:
- for generator voltage < 50% of nominal voltage, Sd Stop Fail has delay 1s
- for generator voltage > 50% of nominal voltage, Sd Stop Fail has delay 200ms
- for oil pressure > starting oil pressure, Sd Stop Fail has delay 1s
For detected RPM, there is no delay.
Hint:
For more details see chapter Stop engine conditiones in chapter Gen-set Operation states
With start goes this protection inactive.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Overspeed
Output closes if the gen-set over speed alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Underspeed
Output closes if the gen-set under speed alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Start Fail
Output closes after the gen-set start-up fails.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Overcurrent
Output closes if the generator
*IDMT over current or
current unbalance or
short current alarm activates.
The output opens, if Alarm is not active and FAULT RESET is pressed
AL BatteryFail
Output closes when IL-NT performs reset during start procedure (probably due to weak battery) or
when battery under/over voltage warning appears.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL EarthFault
Output closes when Earth Fault Current is detected (extension module is needed).
The output opens, if
alarm is not active and
NT
52
Hint:
For more details see chapter Earth Fault Measurement
AL Common Wrn
Output closes when any warning alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed
AL Common Sd
Output closes when any shut-down alarm appears.
The output opens, if
No sd alarm is active and
FAULT RESET is pressed
AL Common BOC
The output closes when any BOC alarm appears.
The output opens, if:
No BOC alarm is active and
FAULT RESET is pressed
AL Common Fls
Output closes when any Sensor Fail alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed
AL AI1 Sd
Output closes if the engine oil pressure (configured to the first analog input) shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL AI1 Wrn
Output closes if the engine oil pressure (configured to the first analog input) warning alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL AI2 Sd
Output closes if the engine water temperature (configured to the second analog input) shutdown alarm
activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL AI2 Wrn
Output closes if the engine water temperature (configured to the second analog input) warning alarm
activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
NT
53
AL AI3 Sd
Output closes if the engine Fuel Level (configured to the third analog input) shutdown alarm activates.
AL AI3 Wrn
Output closes if the engine Fuel Level (configured to the third analog input) warning alarm activates.
BI1..6 Status
* IOM BI1..7 Status
The outputs give an information about the assigned binary input.
In case the assigned binary input is configured to alarm type, then the output closes when the alarm
activates. It opens if
alarm is not active and
FAULT RESET is pressed
In case the assigned binary input is configured to any control function, the output propagates the state
of the input.
* AL IOM AI1..4 Sd
Output closes if shutdown alarm on the appropriate IOM/PTM analog input activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
* ExtBI1..7 Status
The outputs give an information about the assigned binary input.
In case the assigned binary input is configured to alarm type, then the output closes when the alarm
activates. It opens if
alarm is not active and
FAULT RESET is pressed
In case the assigned binary input is configured to any control function, the output propagates the state
of the input.
Hint:
Valid when extension module IL-NT BIO8 or IL-NT CT-BIO7 is configured.
ECU Comm OK
If the ECU is not communicating and all values from ECU show #### the output is not active. If the
ECU communicates the output is active.
ECU YellowLamp
The output copies warning information from ECU.
NT
54
ECU PowerRelay
The output closes at the beginning of prestart and opens if the engine shall be stopped.
This output can be used to indicate when the ECU should be powered up i.e. only while the engine is
running.
This output also influences evaluation of communication failure with ECU and related FLS alarms from
analog inputs read from the ECU. If the output is configured (which means configured on physical
binary output or VPIO output), the issuing of communication error is blocked during Prestart and
Stopping procedure as shown in the picture.
Beginning of
Prestart
Fuel
solenoid
deactivation
ECU PwrRelay
End of
Prestart
ECU
communication
failure alarm
blocked
Engine
stopped
Analog inputs
It is possible to configure on each Analog input:
Reading from IL Analog inputs or from Engine Control Unit via CAN bus (J1939)
Sensor characteristics from the list, or custom sensor curve
Value dimension (e.g. psi - bars, F - C, % - l)
Sensor resolution
Warning and shut-down limits are adjusted in Engine Protect group.
The analog inputs are configurable. Use LiteEdit software to modify configuration. Default
configuration is:
Oil Pressure
Oil pressure analog input. Default VDO sensor in range 0 to 10.0 bars.
Water Temp
Water temperature analog input. Default VDO sensor in range 40 to 120 C.
Fuel Level
Fuel Level analog input. Default VDO sensor 0-180R = 0-100%
Hint:
For further information about analog inputs configuration see Analog inputs.
NT
55
RPM
Oil pressure
Water temperature
Fuel Level
ECU State
Fuel Rate
Manifold temp
Boost Pressure
Percent Load
ECU
ECU or IL-NT AI1
ECU or IL-NT AI2
ECU or IL-NT AI3
ECU
ECU
ECU
ECU
ECU
Use LiteEdit to enable/disable J1939 interface and to configure IL-NT analog inputs.
Hint:
RPM reading is automatically switched to pickup or generator voltage measuring (depends on Basic
setting: Gear Teeth value) if J1939 fails.
Analog outputs
Optional plug in card IL-NT AOUT8 provides eigth Pulse-With-Modulation (PWM) outputs. These are
intended to drive VDO style analog gauges. This is to provide visual indication of typically ECU values
without installing aditional sensors on the engine. PWM signal emulates sensor which would be
typically mounted on the engine.
Any value from controler may be configured to the outputs. Use LiteEdit PC SW to configure
coresponding sensor/gauge curve and value selection.
NT
56
Setpoints
Password
EnterPassword
Password is a four-digit number. Password enables change of relevant protected setpoints.
Use or keys to set and ENTER key to enter the password.
Hint:
There is only 1 level of a password.
ChangePassword
Use or keys to set and ENTER key to change the password.
Hint:
At first the password has to be entered before the new password can be changed.
During the configuration of controller or setpoints changes is required a password to the
controller. The default password from manufacturer is 0. Maximum value of password is
9999.
Controller has following functions:
Automatic checking of password during change to be maximally 9999, if it is bigger value it will
be automatically changed to 0. LiteEdit (LE) will prevent to write bigger value than 9999.
Cyclic rotation of value of password in case of using arrows on controller
Basic Settings
Gen-set Name
User defined name, used for InteliLite identification at remote phone or mobile connection.
Gen-set Name is max 14 characters long and have to be entered using LiteEdit software.
Nomin Power
[kW]
Nomin Current
[A]
It is current limit for generator *IDMT over current and short current protection and means maximal
continuous generator current. See Gener Protect: *Amps IDMT Del, Short Crct Sd setpoints.
Nominal Current can be different from generator rated current value.
Step:
1A
Range:
1 - 10000 A
CT Ratio
[/5A]
57
NT
58
PT Ratio
[/1]
NomVolts Ph-N
[V]
NomVolts Ph-Ph
[V]
59
Step:
Range:
1V
138 35000 V
Nominal Freq
[Hz]
Gear Teeth
[-]
Nominal RPM
[RPM]
ControllerMode
Reset To MAN
DISABLED:
ENABLED:
[ENABLED/DISABLED]
BacklightTime
[min]
When this timer exceed than the display backlight is switched off.
Step:
1
Range:
0 241min
ConnectionType
3Ph4Wire:
3Ph3Wire:
Split Phase:
Mono Phase:
Hint:
For more details about connection types see Voltage measurement and generator connection types
chapter.
For details about influence of Connection type setting on voltage values in history check History file
chapter.
CT Location
Load:
GenSet:
[Load/GenSet]
60
automatic engine start. This function is active for Shut down protection only.
Hint:
More details about this function is introduced in chapter CT Location.
Comms Settings
ControllerAddr (1 .. 32)
[-]
Controller identification number. It is possible to set controller address different from the default value
(1) so that more IL controllers can be interconnected (via RS485) and accessed e.g. from Modbus
terminal.
Hint:
When opening connection to the controller it's address has to correspond with the setting in PC tool.
From LiteEdit it is only possible to connect to controllers with address 1.
COM1 Mode
[DIRECT/MODEM/MODBUS/ECU LINK]
COM2 Mode
[DIRECT/MODBUS/ECU LINK]
Communication protocol switch for the COM2 channel, if dual communication module is pluged in.
DIRECT:
LiteEdit communication protocol via direct cable.
MODBUS:
Modbus protocol. See detailed description in InteliCommunication guide.
ECU LINK:
Protocol for communication with Cummins engines via Modbus.
Hint:
For details on communication speed and other technical parameters please see chapter Technical
Data.
For detail description see chapter Modbus protocol. Since IL-NT version 1.3 controller supports
register oriented modbus.
Hint:
Modbus TCP protocol using IB-Lite communication module requires setting COM1 Mode = DIRECT
and COM2 Mode = MODBUS.
ModemIniString
If your modem needs some additional initialization AT commands (i.e. because of national telephony
network differencies), it can be entered here. Otherwise leave this setpoint blank.
ModbusComSpeed
If the Modbus mode is selected on COM1 or COM2 channels, the Modbus communication speed in
bps can be adjusted here.
IBLite IP Addr
[-]
If DHCP is DISABLED this setpoint is used to adjust the IP address of the ethernet interface of the
controller. Ask your IT specialist for help with this setting.
NT
61
If DHCP is ENABLED this setpoint is used to display the IP address, which has been assigned by the
DHCP server.
IBLite NetMask
[-]
If DHCP is DISABLED this setpoint is used to adjust the IP address of the ethernet interface of the
controller. Ask your IT specialist for help with this setting.
If DHCP is ENABLED this setpoint is used to display the IP address, which has been assigned by the
DHCP server.
IBLite GateIP
[-]
If DHCP is DISABLED this setpoint is used to adjust the IP address of the gateway of the network
segment where the controller is connected.
If DHCP is ENABLED this setpoint is used to display the gateway IP address which has been
assigned by the DHCP server.
A gateway is a device which connects the respective segment with the other segments and/or
Internet.
IBLite DHCP
[ENABLED/DISABLED]
The setpoint is used to select the method how the ethernet connection
is adjusted.
DISABLED:
The ethernet connection is adjusted fixedly according to the setpoints
IP Addr, NetMask, GateIP, DNS IP Address.
This method should be used for classic ethernet or Internet connection. When this type of connection
is opening the controller is specified by it's IP address. That means it would be inconvenient if the IP
address were not fixed (static).
ENABLED:
The ethernet connection settings is obtained automatically from the DHCP
server. The obtained settings is then copied to the related setpoints.
If the process of obtaining the settings from DHCP server is not successful
the value 000.000.000.000 is copied to the setpoint IP address and the
module continues trying to obtain the settings.
ComAp Port
[0 - 65535]
This setpoint is used to adjust the port number, which is used for ethernet connection to a PC with any
of ComAp PC program (i.e. InteliLIte, InteliMonitor). This setpoint should be adjusted to 23, which is
the default port used by all ComAp PC programs. A different value should be used only in special
situations as e.g. sharing one public IP address among many controllers or to overcome a firewall
restrictions.
APN Name
[-]
Name of APN access point for GPRS network provided by GSM/GPRS operator.
[-]
[-]
AirGate
[ENABLED/DISABLED]
62
This is a standard mode, in which the controller listens to the incoming traffic
and answers the TCP/IP queries addressed to him. This mode requires the
controller to be accessible from the remote device (PC), i.e. it must be
accessible at a public and static IP address if you want to connect to it from
the Internet.
ENABLED:
This mode uses the "AirGate" service, which hides all the issues with static/public address into a black
box and you do not need to take care about it. You just need only a connection to the Internet. The
AirGate server address is adjusted by the setpoint AirGate IP.
AirGate IP
[-]
This setpoint is used for entering the domain name or IP address of the AirGate server. Use the free
AirGate server provided by ComAp at address airgate.comap.cz if your company does not operate it's
own AirGate server.
[-]
Use this setpoint to enter the user name for the SMTP server.
[-]
Use this setpoint to enter the password for the SMTP server.
SMTP Server IP
[-]
This setpoint is used for entering the domain name (e.g. smtp.yourprovider.com) or IP address (e.g.
74.125.39.109) of the SMTP server. Please ask your internet provider or IT manager for this
information.
Hint:
You may also use one of free SMTP servers, e.g. smtp.gmail.com. However, please note that some
free SMTP servers may cause delays (in hours..) when sending e-mails.
If you do not want to send active e-mails, you may leave this setpoint blank, as well as other setpoints
related to SMTP server and e-mail settings.
Proper setting of SMTP-related setpoints as well as controller mailbox are essential for sending alerts
via e-mails.
[-]
Enter an existing e-mail address into this setpoint. This address will be used as sender address in
active e-mails that will be sent from the controller.
Time Zone
[-]
This setpoint is used to select the time zone where the controller is located. See your computer time
zone setting (click on the time indicator located in the rightmost position of the the windows task bar) if
you are not sure about your time zone.
Hint:
If the time zone is not selected properly the active e-mails may contain incorrect information about
sending time, which may result in confusion when the respective problem actually occured.
DNS IP Address
[-]
If DHCP is DISABLED this setpoint is used to adjust the domain name server (DNS), which is needed
to traslate domain names in e-mail addresses and server names into correct IP addresses.
If DHCP is ENABLED this setpoint is used to display DNS server, which has been assigned by the
DHCP server.
NT
63
Engine Params
Starting RPM
[%]
Starting Oil P
[Bar]
Prestart Time
[s]
MaxCrank Time
[s]
CrnkFail Pause
[s]
Crank Attempts
[-]
Idle Time
[s]
Idle time delay starts when RPM exceeds Starting RPM. Start fail is detected when during Idle state
RPM decreases below 2.
During the Idle time timer running the binary output Idle/Nominal is opened when it elapses the
Idle/Nominal output closes. Binary output Idle/Nominal opens during Cooling period again.
Step:
1s
Range:
0 600 s
NT
64
Starting
RPM
M
RP
R PM
RPM = 2
BO Starter
BO IDLE/RATED
Idle Time
Electric protections
active
[s]
Minimum time after reaching of defined level of RPM to the closing GCB.
Step:
1s
Range:
1 300 (Max Stab Time) s
[s]
Maximum time after start to get proper voltage level of the generator.
Step:
1s
Range:
1 (Min stab time) 300 s
Hint:
When generator voltage within Max Stab Time does not reach defined limits (Generator protection
group) , an alarm occurs and the genset will shut down
Cooling Speed
[IDLE/NOMINAL]
Selects the function of the Binary output IDLE/NOMINAL during engine Cooling state.
NOMINAL : Cooling is executed at Nominal speed and generator protections are active.
IDLE: Cooling is executed at Idle speed and generator protections are switched off.
Hint:
When ECU is connected the predefined value 900 RPM for IDLE speed is requested.
Hint:
Binary output IDLE/NOMINAL must be configured and connected to speed governor. Engine Idle
speed must be adjusted on speed governor
Cooling Time
[s]
Stop Time
[s]
Under normal conditions the engine must certainly stop 10s before this period will exceed. The period
starts by issuing stop command.
Step:
1s
Range:
0 600 s
Hint:
For more details see chapter Stop engine conditions in chapter Gen-set Operation states
NT
65
Fuel Solenoid
[ DIESEL / GAS ]
D+ Function
[ENABLED/CHRGFAIL/DISABLED]
ENABLED: The D+ terminal is used for both functions running engine detection and charge fail
detection.
CHRGFAIL: The D+ terminal is used for charge fail detection only
DISABLED: The D+ terminal is not used.
Hint:
The magnetization current is provided independently on this setpoint value.
The D+ charge fail protection becomes active after Engine Params:Idle Time reaches zero.
ECU FreqSelect
[PRIMARY/SECONDARY/DEFAULT]
This setpoint should be used only for Volvo and Scania engines.
Volvo Volvo Aux is selected in ECU configuration:
Primary or secondary engine speed is set by Frequency select bits in VP Status frame.
Scania Scania S6 Singlespeed is selected in ECU configuration:
Nominal engine speed is chosen by Nominal speed switch 1 and 2 from DLN1 frame when the engine
is running on nominal speed, i.e. binary output Idle/Nominal is active. When the output is not active
(engine is running on Idle speed), the setpoint ECU FreqSelect is not taken into account.
ECU SpeedAdj
[%]
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%.
Step:
1%
Range:
0 100%
Hint:
NT
66
The minimum value 0% is equal to 90% of nominal speed. Maximum value 100% is equal to 110% of
nominal speed.
Fuel Pump ON
[%]
When the actual value of Fuel Level is lower or equals to this value then the binary output Fuel Pump
is activated.
Step:
1
Range:
0 100 %
[%]
When the actual value of Fuel Level is higher or equals to this value then the binary output Fuel Pump
is deactivated.
Step:
1
Range:
0 100 %
Hint:
The two setpoints above are compared to Analog Input 3 (usually used for Fuel Level)
It is a prerequisite for this function to use a fuel level sensor at this analog input.
TempSwitch ON
[-]
Threshhold level for switching on the binary output TempSwitch. This function is connected with
controller's analog input 2.
Step:
1
Range:
-100 .. 10000 [-]
TempSwitchOFF
[-]
Threshhold level for switching off the binary output TempSwitch. This function is connected with
controller's analog input 2.
Step:
1
Range:
-100 .. 10000 [-]
Hint:
The description of Power Switch function is in chapter Binary outputs - list at Temp Switch.
PowerSwitch ON
[kW]
Threshold level for switching the binary output Power Switch on.
Step:
1
Range:
0 32000 kW
PowerSwitchOFF
[kW]
Threshold level for switching the binary output Power Switch off.
Step:
1
Range:
0 32000 kW
Hint:
The description of Power Switch function is in chapter Binary outputs - list at Power Switch.
FuelTankVolume
[l]
MaxFuelDrop
[%/h]
Setpoint indicates the maximum allowable drop of fuel in fuel tank per running hour. When the engine
is not running the maximal allowed fuel drop-off is preset to 5% of fuel tank volume per hour.
NT
67
In case of detection of theft/leak the alarm "Wrn FuelTheft" is raised and same alarm is send via SMS
and displayed by WebSupervisor (if used).
Step:
1
Range:
0 50%
Hint:
Set 0 to disable Fuel Theft Protection function into MaxFuelDrop setpoint.
Engine Protect
ProtectHoldOff
[s]
During the start of the gen-set, some Engine Protections have to be blocked (e.g. Oil pressure).
The protections are unblocked after the ProtectHoldOff time. The time starts after reaching Starting
RPM.
Step:
1s
Range:
0 300 s
Hint:
The protections sequence diagram can be found in Alarm time chart in chapter Alarm Management. It
displayes when and what protections are active.
Horn Timeout
[s]
Max time limit of horn sounding. Set to zero if you want to leave the output HORN open. Horn timeout
starts again from the beginning if a new alarm appears before previous Horn timeout has elapsed.
Step:
1s
Range:
0 600 s
Overspeed Sd
[%]
AI1 Wrn
[ Bar]
AI1 Sd
[ Bar]
AI1 Del
[s]
NT
68
AI2 Wrn
[]
AI2 Sd
[]
AI2 Del
[s]
AI3 Wrn
[]
AI3 Sd
[]
AI3 Del
[s]
Batt Undervolt
[V]
Batt Overvolt
[V]
[s]
WrnMaintenance
[h]
Counts down when engine running. If reaches zero, an alarm appears. When the value 10000 is set,
than the Maintanance function is disabled and counter does not count. Counter value disappear in
controllers statictics. Maximum value for running countdown is 9999.
Step:
1h
Range:
0 10000 h
Gener Protect
Hint:
NT
69
Overload BOC
[%]
Threshold for generator overload (in % of Nominal power) protection. Protection is BOC (Breaker
Open and genset Cooldown).
Step:
1% of Nominal power
Range:
0 200%
Overload Del
[s]
[%]
BOC (Breaker Open and genset Cooldown) occurs when generator current reaches Short Crct BOC
limit.
Step:
1 % of Nominal current
Range:
100 - 500 %
[s]
[s]
IDMT curve shape selection. Amps IDMT Del is Reaction time of IDMT protection for 200%
overcurrent Igen = 2* Nomin Current.
Step:
0,1 s
Range:
0,1 - 600,0 s
IDMT is very inverse generator over current protection. Reaction time is not constant but depends on
generator over current level according following formula.
Amps IDMT Del * Nomin Current
Reaction time =
Igen -
Nomin Current
Hint:
Reaction time is limited up to 3600 sec = 1 hour. IDMT protection is not active for Reaction time values
longer than 1 hour.
Igen is maximal value of all measured phases of generator current.
EXAMPLE of Reaction time for different over current levels. Values in column 200% are IDMT Curr
Del.
NT
70
Reaction time
Overcurrent
100 %
101 %
200 % =
IDMT Curr
Del
0,2 s
110 %
No action
20 s
2s
2s
No action
200 s
20 s
20 s
No action
2000 s
200 s
40 s
No action
No action
(Reaction
time 1 hour)
400 s
Reaction time
Igen
Nominal Current
Short Crct Sd
[%]
Threshold for generator current asymmetry (unbalance). Protection is BOC (Breaker Open and genset
Cooldown).
Step:
1% of Nominal current
Range:
1 200% of Nominal current
[s]
Gen >V Sd
[%]
Threshold for generator overvoltage. All three phases are checked. Maximum out of three is used.
Step:
1% of Nominal voltage
Range:
0(Gen <V BOC) 200%
[%]
Threshold for generator undervoltage. All three phases are checked. Minimum out of three is used.
Step:
1% of Nominal voltage
Range:
0% 200 (Gen >V Sd)%
Hint:
NT
71
Over- and undervoltage protection is evaluated according to Basic Settings: ConnectionType setting.
3Ph4Wire and 3Ph3Wire connections are evaluated according to Ph-Ph nominal voltage (NomVolts
Ph-Ph) and Split Phase and Mono Phase connections are evaluated according to Ph-N nominal
voltage (NomVolts Ph-N).
Gen V Del
[s]
[%]
[s]
[%]
[%]
[s]
*Extension I/O
IOM AI1..4 Wrn
[]
The warning level for IOM ANALOG INPUT 1..4 alarm detection.
Step:
1
Range:
-100 - +10000
IOM AI1..4 Sd
[]
The shutdown level for IOM ANALOG INPUT 1..4 alarm detection.
Step:
1
Range:
-100 - +10000
[s]
NT
72
Configuration
Under
Over
Under+fls
Over+fls
Protection
Protection is activated only when measured value is under measured level.
Protection is activated only when measured value is over measured level.
Level 2 protection is activated by Sensor Fail as well.
Level 2 protection is activated by Sensor Fail as well.
[]
Calibrating constant to adjust the measured value of IOM/PTM analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Step:
1
Range:
-1000 +1000
Date/Time
Some of parameters in this group are only available at specific models of IL-NT.
[min]
*#SummerTimeMod
*#Time
[HHMMSS]
*#Date
[DDMMYYYY]
Actual date.
NT
73
*Timer1..2 ON Time
Day time when Timer output activates.
*Timer1..2Duration
Duration of Timer output is active.
Step:
1 min
Range:
1 1440 s
Test Period
Duration of testing run timer. This timer will run the engine with specified period for specified time
duration.Timer starts at time of restarting the controller, or during start of engine with transition from
Idle to Running state.
This setpoint is only available at models IL-NT MRS10 and MRS11.
Step:
1 day
Range:
1 240 days
Test Duration
Duration of testing run of engine.
This setpoint is only available at models IL-NT MRS10 and MRS11.
Step:
1 min
Range:
1 240 min
Sensors spec
AI1, AI2, AI3 Calibration
[]
Calibrating constant to adjust the measured value of IL analog inputs. Physical dimension
of calibrating constant is corresponding to Analog input.
Step:
1
Range:
-1000 +1000
Hint:
Calibration constants have to be adjusted when measured value is near the alarm level.
User curves can be defined by LiteEdit software.
SMS/E-Mail
Remote alarm messaging
If a GSM modem and/or Internet bridge is connected to the controller, the controller can send SMS
messages and/or emails in the moment when a new alarm appears in the Alarm list. The message will
contain a copy of the Alarm list.
NT
74
To enable this function, you should select with setpoints Yel Alarm Msg and Red Alarm Msg, which
levels of alarms shall be announced (red/yellow/both) and also enter valid GSM phone number and/or
e-mail address to the setpoints TelNo/Addr Ch1 and TelNo/Addr Ch2. It is possible to put either a
GSM number or e-mail to both setpoints.
NOTE:
An internet module must be available for sending of e-mails. Similarly, a GSM modem is necessary for
sending of SMS.
Hint:
There are 5 attempts for any active call (SMS/E-Mail). Timeout for connection is 90 sec and after 120
sec controller starts the next attempt. During the time the IL-NT is trying to send an active call type,
incoming calls are blocked.
[ON/OFF]
Set this setpoint to ON if you want to get messages when a yellow (warning) alarm occurs.
Hint:
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1 resp. TelNo/Addr Ch2.
[ON/OFF]
Set this setpoint to ON if you want to get messages when a red (shutdown or BOC) alarm occurs.
Hint:
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1 resp. TelNo/Addr Ch2.
Event Msg
[ON/OFF]
Set this setpoint to ON if you want to get messages when a new event occur .
Hint:
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1 resp. TelNo/Addr Ch2.
TelNo/Addr Ch1, 2
Enter either a valid GSM phone number or e-mail address to this setpoint, where the alarm messages
shall be sent. Type of active call is considered from the value of this parameter. If it consist @ it is
supposed to be e-mail address and active e-mail is sent. If the value is number, without @, it is
supposed to be the telephone number and active SMS is sent.
Hint:
For GSM numbers use either national format (i.e. like number you will dial if you want to make a local
call) or full international format with "+" character followed by international prefix in the begin.
Phone numbers and emails can be modified from controller display or from PC.
Following buttons are used for phone number modification
- ENTER for
- opening the modification
- confirmation of particular number change and jump to the next position
- confirmation of the last number and closing of the modification
- MODE for
- while adjusting character press Mode button to jump between character groups to
fasten the process.
- and for - particular number/character change
Particular numbers/character can take values: from 0 to 9, a to z, various symbols and empty
space.
NT
75
SMS Language
[1/2]
Alternate Cfg
Based on the value on BI Alt. Config is selected controller configuration 1 or configuration 2 (all related
setpoints are placed in Alternate Cfg group).
Hint:
Controller will react on change of binary input only while engine is stopped. On successful change of
input the new record in history ("Nominal1Active", "Nominal2Active") is added.
Hint:
If the configuration 1 will contain setting for 50Hz and configuration 2 for 60Hz it is possible to use this
feature for 50/60 Hz switch.
[RPM]
[Hz]
[V]
NomVolts Ph-Ph1..2
[V]
[A]
It is current limit for generator *IDMT over current and short current protection and means maximal
continuous generator current. See Gener Protect: *Amps IDMT Del, Short Crct Sd setpoints.
Nominal Current can be different from generator rated current value.
Step:
1A
Range:
1 - 10000 A
ConnectionType 1..2
76
ECU FreqSelect1..2
[PRIMARY/SECONDARY/DEFAULT]
This setpoint should be used only for Volvo and Scania engines.
Volvo Volvo Aux is selected in ECU configuration:
Primary or secondary engine speed is set by Frequency select bits in VP Status frame.
Scania Scania S6 Singlespeed is selected in ECU configuration:
Nominal engine speed is chosen by Nominal speed switch 1 and 2 from DLN1 frame when the engine
is running on nominal speed, i.e. binary output Idle/Nominal is active. When the output is not active
(engine is running on Idle speed), the setpoint ECU FreqSelect is not taken into account.
[%]
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%.
Step:
1%
Range:
0 100%
Hint:
The minimum value 0% is equal to 90% of nominal speed. Maximum value 100% is equal to 110% of
nominal speed.
*EarthFaultProt
Hint:
More information are availible in Earth fault Measurement chapter.
EF Protection
[ENABLED/DISABLED]
NT
77
EF CT Ratio
[/5A]
EarthFault Sd
[A]
EarthFault Del
[s]
NT
78
If the connected engine is Cummins with GCS engine control unit communicating via Modbus it is
NT
79
necessary to set the setpoint Basic settings: COM1 Mode = ECU LINK or COM2 Mode = ECU LINK.
Loss of communication causes a warning alarm. On the contrary the ECU can be switched off at
quiescent engine that means not-communicating ECU is in that moment normal situation. All values
from ECU shall show ####, but no alarm is displayed. The output ECU Comm OK follows the real
situation which means it is not active anytime when the ECU does not communicate.
The output ECU PowerRelay closes at the beginning of prestart and opens if the engine shall be
stopped. It can be used to switch the ECU on and off. If the putput is configured but not active the
ECU communication alarm is blocked.
The engine is started via standard contact output or via CAN bus depending on ECU capabilities.
NT
80
Analog inputs
Reading of mentioned values from ECU enables to use analog inputs of the unit for other purposes,
e.g. measuring, displaying and alarm activation related to various quantities. The configuration thus
allows to use three analog inputs on the central unit and four analog inputs on IG-IOM/IGS-PTM
module if connected.
NT
81
Connection description
The following diagrams show how to connect the engine control unit to the InteliLite controller:
RS-232C
Interface
Modem or PC
NOT USED
SPRINKLER
+24 V
LOAD
REMOTE OFF
EMERGENCY STOP
ACCESS LOCK
CONTROL
SIGNALS
ALARM
READY TO LOAD
PRESTART
8 7 6 5 4 3 2 1
8-pole Deutsch
connector
L3
L2
RPM
ECU
DIESEL/GAS ENGINE
GENERATOR
L1
Generator C.B.
GEN C.B.
BINARY OUTPUTS
REMOTE S/S
BO ECU PwrRelay
BO ECU CommOK
( EDCIII) / ECU CommError( EMSII)
FUEL LEVEL
NT
82
RS-232C
Interface
Modem or PC
SCANIA S6
NOT USED
SPRINKLER
+24 V
LOAD
REMOTE OFF
EMERGENCY STOP
ACCESS LOCK
CONTROL
SIGNALS
ALARM
READY TO LOAD
PRESTART
1 2 3 4 5 6 7 8 9 10
ECU
10 -pin EMS B1
connector
L3
RPM
L1
GENERATOR
DIESEL/GAS ENGINE
L2
Generator C.B.
GEN C.B.
BINARY OUTPUTS
REMOTE S/S
GND
+ 24 V DC
FUEL LEVEL
NT
83
DATA1+
RS232
DATA1-
RxD
TxD
10-30
VDC
RS485
NOT USED
SPRINKLER
+24 V
LOAD
REMOTE OFF
EMERGENCY STOP
ACCESS LOCK
REMOTE S/S
ALARM
READY TO LOAD
PRESTART.
GEN C.B.
Generator C.B.
FUEL SOLENOID
BINARY OUTPUTS
CONTROL
SIGNALS
L3
L2
RPM
GENERATOR
L1
STARTER
D-SUB 06
CONNECTOR
ECU
DIESEL/GAS ENGINE
FUEL SOLENOID
STARTER
D+
BATTERY
NT
84
Sensor Specification
Background of the sensor calibration
To correct measuring error of each analog input (pressure, temperature, level) calibrating constants
within 10 % of measure range should be set. Two calibrating constants are set in physical units - bar,
o
C, % .Calibration is made by adding the value of setpoint AIxCalibration directly to the calculated
value at analog input.
Hint:
The calibration must be done at the operational point of the analog input (e.g. 80C, 4.0Bar etc..)
Min Value
0
0
0
0
0
0
25
25
80
80
0
0
0
0
0
40
50
100
120
0
Max Value
5
7
10
80
100
150
150
160
300
320
100
5
10
72
145
120
150
250
300
100
Unit
Bar
Bar
Bar
Psi
Psi
Psi
C
C
F
F
%
Bar
Bar
Psi
Psi
C
C
F
F
%
Hint:
You can find detail information on sensors in LiteEdit Reference Guide and details about sensor fails
in this manual in chapter Alarm Management - Sensor Fail (FLS).
NT
85
Function Description
OFF Mode
No start of the gen-set is possible. Outputs STARTER, GCB CLOSE/OPEN and FUEL SOLENOID are
not energized.
No reaction if buttons START,STOP,^GCB ON/OFF are pressed.
MAN Mode
START. - starts the gen-set.
^GCB ON/OFF
The controller closes GCB.
The controller opens GCB when closed.
If the generator voltage is out of the limits, the controller does not to respond to the GCB
ON/OFF
STOP stops the gen-set.
Hint:
The engine can run without load unlimited time.
The controller does not automatically stop the running gen-set in MAN Mode.
The controller does not start the gen-set when binary input REM START/STOP is closed.
Action
PRESTART on
Prestart Time counter
started
Cranking
NT
Next state
Prestart
Not Ready
Ready
STARTER on
4
FUEL SOLENOID on
MaxCrank Time counter
started
STARTER off
PRESTART off
Cranking
STARTER off
PRESTART off
Cranking
Starting
86
State
Crank
3
pause
Starting
Stop request
Loaded
Cooling
Stop
Action
STARTER off
FUEL SOLENOID off
STOP SOLENOID on
CrankFail Pause timer
started
STARTER off
PRESTART off
STARTER on
4
FUEL SOLENOID on
STOP SOLENOID off
MaxCrank Time counter
started
1
READY TO LOAD on
Min, Max Stab Time
counter started
FUEL SOLENOID off
STOP SOLENOID on
FUEL SOLENOID off
STOP SOLENOID on
READY TO LOAD off
Cooling Time timer
started
2
READY TO LOAD off
FUEL SOLENOID off
Next state
Crank pause
Shutdown (Start
fail)
Cranking
Running
Shutdown
Shutdown (Start
fail)
Cooling
Shutdown
Loaded
Running
Shutdown
Stop
Shutdown
Running
Ready
Stop (Stop fail)
if all generator parameters OK and Min Stab Time elapsed, indicates that GCB is possible to close.
In AUTO Mode closes in this moment GCB automatically.
2
Hint:
Threshold level for D+ input is 80% supply voltage, activation delay is 1s (to override short firings
during cranking for example in cold conditions).
AUT mode
The controller does not respond to buttons START, STOP, GCB ON/OFF. Engine start/stop request
is given by binary input REM START/STOP.
NT
87
Alarm Management
Following alarms are available:
Sensor Fail
Warning
Breakers open and cooling (BOC)
Shut down
Mains failure
R2
R3
R4
R5
Range of sensor
Sensor Fail of analog inputs is detected in three ways. First when measured resistance value is lower
than half of the lowest point of sensor characteristics. Second when measured resistance value is
higher than 112,5% of highest point of sensor characteristics. Or when data from ECU are missing.
Sensor Fail is indicated by ##### symbol instead measured value.
Sensor Fail is only evaluated for values of sensor curve within range 1..14999Ohm.
When the sensor characteristic curve consists values 0 or 15000, the sensor fault for
shortcircuit/sensor fail is not evaluated.
Maximum allowable resistance value for sensor characteristics is 15000 Ohms.
Warning (WRN)
When warning comes up, only alarm outputs and common warning output are closed.
Possible warnings:
See List of possible events
NT
88
Idle Time
5 sec
Underspeed
"Engine running only" protections, engine
water temperature luboil pressure
ProtectHoldoff
Stop
GCB opened
GCB closed
Switched to
nominal speed
Start
Starter OFF
"All the time" configured protections, I >, I >>, RPM >>, mains failure detection
NT
89
closed
BO GCB close/open
BO GCB close/open
opened
closed
BI GCB feedback
BI GCB feedback
active
opened
active
Alarm detection:
immediatelly
When BO GCB close/open opens there is 5 sec delay for GCB fail detection.
BO GCB close/open
opened
BI GCB feedback
Time delay
5 sec
opened
active
When BO GCB close/open closes, there is 5sec delay for GCB fail detection:
closed
BO GCB close/open
BI GCB feedback
Time delay
5 or 2 sec
closed
active
Alarm: GCB fail
Hint:
You can solve state of GCB fail by pressing Fault Reset button.
Generally it is possible to use IL-NT controller without feedback inputs (not configured).
Controller will work with breakers anyway.
NT
90
91
Stop engineconditions
If no engine running conditions are validated than the controller will wait extra 10s before leaving the
Machine state Stop and than it will release the Binary output Stop solenoid.
Stop Solenoid
Output
10 s
Engine run
Cooling Time
RPM / Frequency
D+
Oil Pressure
Generator voltage
Fuel Solenoid is
opened
On
Off
Stop Time
Gen-set stoped
Stop
Time
When the total time of stopping will exceed setpoint Stop time (in Engine Params) than the Stop fail
warning and related binary outputs are activated. The controller will continuously try to stop the
engine.
Stop Solenoid
Output
10 s
Engine run
Cooling Time
RPM / Frequency
D+
Oil Pressure
Generator voltage
Fuel Solenoid is
opened
On
Off
Stop Time
Stop
NT
Gen-set stoped
Time
92
Sd Start Fail
ParamFail
Sd Gen Lx >V
BOC Gen Lx <V
(where x=1,2,3)
BOC Overload
NT
Information on binary
output available (See
Description
list of Binary outputs)
WRN
YES
Value measured on analog input 1 is
lower than AI1 Wrn setpoint.
SD
YES
Value measured on analog input 1 is
lower than AI1 Sd setpoint.
WRN
YES
Value measured on analog input 2 is
greater than AI2 Wrn setpoint.
SD
YES
Value measured on analog input 2 is
greater than AI2 Sd setpoint.
WRN
YES
Value measured on analog input 3 is
greater than AI3 Wrn setpoint.
SD
YES
Value measured on analog input 3 is
greater than AI3 Sd setpoint.
WRN
YES
Battery voltage is out of limits given by
Batt Undervolt/Batt OverVolt
setpoints.
WRN
YES
Warning alarm configurable on the
input of IG-IOM/IGS-PTM.
SD
YES
Shutdown alarm configurable on the
input of IG-IOM/IGS-PTM.
Configurable
YES
Configurable Warning/BOC/Shutdown
alarms on the inputs of IL-NT.
SD
YES
If the controller switches off during
starting sequence due to bad battery
condition it doesnt try to start again
and activates this protection.
SD
YES
Gen-set start failed. All crank attempts
were tried without success.
NONE
NO
Wrong checksum of parameters.
Happends typically after downloading
new firmware or changing of the
parameter. The controller stays in
INIT mode. Check all parameters,
write at least one new parameter.
SD
YES
The generator voltage is out of limits
given by Gen <V BOC and Gen >V Sd
BOC
setpoints.
BOC
YES
The generator voltage is unbalanced
more than the value of Volt Unbal
BOC setpoint.
BOC
YES
The generator frequency is out of
limits given by Gen >Freq BOC and
Gen <Freq BOC setpoints.
BOC
NO
The generator current is unbalanced.
BOC
NO
Generator current exceeds the limit
for IDMT protection given by Nominal
current and Amps IDMT Del setpoints.
BOC
YES
The load is greater than the value
Protection
type
93
Protection
type
Information on binary
output available (See
list of Binary outputs)
Sd Earth Fault
SD
YES
Sd Overspeed
SD
YES
Sd Underspeed
SD
YES
EmergencyStop
SD
NO
GCB Fail
Sd RPMMeasFail
SD
SD
NO
NO
WRN
YES
WrnMaintenance
WRN
NO
Wrn FuelThef
ChargeAlt Fail
WRN
WRN
YES
Sd Override
WRN
NO
WRN
NO
SD
NO
WRN
WRN
WRN
NO
NO
NO
Events specification
Description
given by Overload setpoint.
This alarm is activated when Eart
Fault value exceeds Earth Fault Sd
limit for at least Earth Fault Del period.
The protection comes active if the
speed is greater than Overspeed
setpoint.
During starting of the engine when the
RPM reach the value of Starting RPM
setpoint the starter is switched off and
the speed of the engine can drop
under Starting RPM again. Then the
Underspeed protection becomes
active. Protection evaluation starts 5
seconds after reaching StartingRPM.
If the input Emergency Stop is opened
shutdown is immediately activated.
Failure of generator circuit breaker.
Failure of magnetic pick-up sensor for
speed measurement. This alarm
appears, if starter was disengaged for
other reason than overcrossing
starting speed (like oil pressure or D+)
and at the end of timer Max Crank
Time there are no RPMs > Starting
speed detected.
Gen-set stop failed. See descrition at
Gen-set Operation States chapter.
The period for servicing is set by the
WrnMaintenance setpoint. The
protection comes active if the running
hours of the engine reach this value.
Fuel theft indication alarm.
Failure of alternator for charging the
battery.
The protection is active if the output
Sd Override is closed.
Warning alarm in case of lost
connection to IGL-RA15 module.
Shutdown alarm in case of lost
connection to IG-IOM/IGS-PTM
module.
ECU alarm list is not empty
RTC backup battery is flat
Genset voltage phases are not wired
correctly. MCB closing is prohibited by
chontroller.
History file
InteliLite NT stores a record of each important event into the history file. The history file seats 100+
records. When the history file is full, the oldest records are removed.
Number of history records varies with number of configured modules.
NT
94
For different ConnectionType [3Ph4Wire / 3Ph3Wire / Split Ph / Mono Ph] different voltages are
shown in history file. In fact always Ph-Ph voltage is shown, but due to different connections the result
is following:
1. For 3Ph4Wire:
a. Vg1 = Gen. Ph-Ph voltage L1-L2
b. Vg2 = Gen. Ph-Ph voltage L2-L3
c. Vg3 = Gen. Ph-Ph voltage L3-L1
2. For 3Ph3Wire:
a. Vg1 = Gen. Ph-Ph voltage L1-L2
b. Vg2 = Gen. Ph-Ph voltage L2-L3
c. Vg3 = Gen. Ph-Ph voltage L3-L1
3. For Split Ph:
a. Vg1 = Gen. Ph-Ph voltage L1-L2
b. Vg2 = Gen. Ph-N voltage L2
c. Vg3 = Gen. Ph-N voltage L1
4. For Mono Ph:
a. Vg1 = Gen. Ph-N voltage L1
b. Vg2 = 0
c. Vg3 = 0
The mains voltages are displayed in history analogously.
Hint:
To force history download in LiteEdit (direct, modem or Internet) open History window and select
History | Read history command.
Hint:
The first history record after the controller is switched on, programmed or watchdog reset occurs
contains diagnostic values instead of operational. Some fields in these records seem to have
nonsense values. Do not take these values into account.
Hint:
Some of the controller models doesnt have RTC. In this case there is no Date column and the Time
column contains information about running hours.
Record structure
Abbreviation
Num
Reason
Date
Time
Mode
RPM
Pwr
PF
LChr
Gfrq
Vg1
Vg2
Vg3
Ig1
Ig2
Ig3
UBat
OilP
EngT
FLvl
BIN
BOUT
NT
Historical value
Number of historical event
Event specification
Date of historical event in format DD/MM/YY
Time of historical event in format HH:MM:SS
Controllers mode
Engine speed
Generator active power
Generator PF
Character of the load
Generator frequency
Generator voltage L1-L2 or *see description above
Generator voltage L2-L3 or *see description above
Generator voltage L3-L1 or *see description above
Generator current L1
Generator current L2
Generator current L3
Battery voltage
IL-NT Analog input 1 value ( default Oil pressure)
IL-NT Analog input 2 value ( default Water temperature)
IL-NT Analog input 3 value ( default Fuel Level)
Binary inputs IL-NT
Binary outputs IL-NT
95
BIOE*
Binary inputs/outputs plug-in module (when IL-NT-BIO8 module is configured)
FC*
ECU alarm FailureCode (when ECU is configured)
FMI*
ECUalarm Failure Mode Identifier (when ECU is configured)
AIM1*
IG-IOM, IGS-PTM Analog input 1 value (when configured IG-IOM, IGS-PTM)
AIM2*
IG-IOM, IGS-PTM Analog input 2 value (when configured IG-IOM, IGS-PTM)
AIM3*
IG-IOM, IGS-PTM Analog input 3 value (when configured IG-IOM, IGS-PTM)
AIM4*
IG-IOM, IGS-PTM Analog input 4 value (when configured IG-IOM, IGS-PTM)
BIM*
IG-IOM, IGS-PTM Binary inputs (when configured IG-IOM, IGS-PTM)
BOM*
IG-IOM, IGS-PTM Binary outputs (when configured IG-IOM, IGS-PTM)
EF
Earth fault current
*Depends if enabled in configuration (see more details in LiteEdit-4.4-Reference Guide.pdf)
NT
96
Init Screens
Each InteliLite NT controller holds informations about serial number, uploaded firmware version and
others. These informations are displayed on so called Init Screens. It is possible to call this screens
from any measurement screen by pressing ENTER and PAGE buttons concurrently and then only
PAGE button separately.
Inits screens consists of:
Language screen
IL-NT controller offers configurable language support. On this screen si possible to switch between
languages configured in controller.
Other way to change language is by binary input Lang Selection.
NT
97
RS232, USB or RS485 interface can be used for direct cable connection to a PC. The setpoint COM1
Mode or COM2 Mode (according to the interface used) must be set to DIRECT position for this kind of
connection.
NT
98
PC software - LiteEdit
On the PC (for direct or modem connection) has to be installed the ComAps software package
LiteEdit. (based on Windows 95 or newer platform)
LiteEdit enables:
read the quantities
adjust all set points
control the engine
configure the controller
select software configuration
modify alarm inputs and outputs
modify password, commands protections
direct, modem or Internet communication
Modbus protocol
The selection of the function of IL serial port is done via the setpoint COMx Mode in Basic settings
99
The complete description of Modbus communication protocol can be found in Modbus Protocol
Reference Guide PI-MBUS-300 and Open Modbus Specification Release 1.0. Both documents are
available from web site at http://www.modicon.com/openmbus/ .
Communication object vs. Register
All the data intended for communication has its representation as communication objects in the
controller. The communication object is represented by the n-byte array in the controller memory and
identified by the unique 16-bit communication object number. The register, according to Modbus
communication protocol, represents a two-byte data and in communication functions is referenced by
16-bit register address. Further in the description of communication functions the communication
object number will always be used as a register address and length of the communication object
will be expressed by number of registers. Just one communication object can be read or written
by one communication function.
Hint:
To obtain communication object numbers it is possible to download the actual controller description
on-line from controller or from (ail) archive and use export data function from LiteEdit software.
Communication object list (exported from default IL-NT-MRS16 archive)
Setpoints of MRS16:
Name
Firmware ver.
IL-NT-2.0
R:18.05.2012
IL-NT
Application
Date
MRS16
7.6.2012
App.
ver. Ser. num. Filename
2,0 12345678 IL-NT-MRS16-2.0.AIL
Group
Name
Value
Com.
Dimension obj.
Basic Settings
Gen-set Name
IL-NT
8637
Basic Settings
Nominal Power
200
kW
8276
5000
Unsigned 16
Basic Settings
Nomin Current
350
8275
10000
Unsigned 16
Basic Settings
CT Ratio
2000
/5A
8274
5000
Unsigned 16
Basic Settings
PT Ratio
/1
9579
0,1
500
Unsigned 16
Basic Settings
NomVolts Ph-N
231
8277
80
20000
Unsigned 16
Basic Settings
NomVolts Ph-Ph
400
11657
80
40000
Unsigned 16
Basic Settings
Nominal Freq
50
Hz
8278
45
65
Unsigned 16
Basic Settings
Gear Teeth
120
8252
500
Unsigned 16
Basic Settings
Nominal RPM
1500
8253
100
4000
Unsigned 16
Basic Settings
ControllerMode
OFF
8315
String list
Basic Settings
Reset To MAN
DISABLED
9983
String list
Basic Settings
Backlight Time
15
Basic Settings
ConnectionType
3Ph4Wire
11628
Comms Settings
ControllerAddr
24537
Comms Settings
COM1 Mode
DIRECT
24522
String list
Comms Settings
COM2 Mode
DIRECT
24451
String list
Comms Settings
ModemIniString
24436
Long string
NT
RPM
min
10121
Low limit
High limit
Data type
Short string
241
Unsigned 8
String list
32
Unsigned 8
100
Comms Settings
ModbusComSpeed
9600
24477
String list
Comms Settings
IBLite IP Addr
192.168.1.254
24376
Short string
Comms Settings
IBLite NetMask
255.255.255.0
24375
Short string
Comms Settings
IBLite GateIP
192.168.1.1
24373
Short string
Comms Settings
IBLite DHCP
ENABLED
24259
Comms Settings
ComAp Port
23
24374
Comms Settings
APN Name
24363
Long string
Comms Settings
24361
Long string
Comms Settings
24360
Short string
Comms Settings
AirGate
ENABLED
24365
String list
Comms Settings
AirGate IP
airgate.comap.cz
24364
Long string
Comms Settings
24370
Long string
Comms Settings
24369
Short string
Comms Settings
SMTP Server IP
24368
Long string
Comms Settings
Contr MailBox
24367
Long string
Comms Settings
Time Zone
GMT+1:00
24366
String list
Comms Settings
DNS IP Address
8.8.8.8
24362
Short string
Engine Params
Starting RPM
25
8254
50
Unsigned 8
Engine Params
Starting Oil P
4,5
Bar
9681
10
Integer 16
Engine Params
Prestart Time
8394
600
Unsigned 16
Engine Params
MaxCrank Time
8256
255
Unsigned 8
Engine Params
CrnkFail Pause
8257
60
Unsigned 8
Engine Params
Crank Attempts
8255
10
Unsigned 8
Engine Params
Idle Time
12
9097
600
Unsigned 16
Engine Params
8259
10
Unsigned 16
Engine Params
10
8313
300
Unsigned 16
Engine Params
Cooling Speed
NOMINAL
Engine Params
Cooling Time
30
8258
3600
Unsigned 16
Engine Params
Stop Time
60
9815
600
Unsigned 16
Engine Params
Fuel Solenoid
DIESEL
9100
String list
Engine Params
D+ Function
DISABLED
9683
String list
Engine Params
Fuel Pump ON
20
10100
-100
90
Integer 16
Engine Params
90
10101
20
10000
Integer 16
Engine Params
TempSwitch ON
90
8688
-100
10000
Integer 16
Engine Params
TempSwitch OFF
75
8689
-100
10000
Integer 16
Engine Params
PowerSwitch ON
100
kW
11658
32000
Integer 16
Engine Params
PowerSwitchOFF
50
kW
11659
32000
Integer 16
Engine Params
FuelTankVolume
200
11103
10000
Unsigned 16
Engine Params
MaxFuelDrop
25
%/h
12373
50
Unsigned 8
Engine Protect
ProtectHoldOff
8262
300
Unsigned 16
Engine Protect
Horn Timeout
10
8264
600
Unsigned 16
Engine Protect
Overspeed Sd
115
8263
50
150
Unsigned 16
Engine Protect
AI1 Wrn
Bar
8369
-10
1000
Integer 16
Engine Protect
AI1 Sd
Bar
8370
-10
1000
Integer 16
NT
bps
String list
0
65535
10046
Unsigned 16
String list
101
Engine Protect
AI1 Del
8365
900
Unsigned 16
Engine Protect
AI2 Wrn
80
8375
-100
10000
Integer 16
Engine Protect
AI2 Sd
90
8376
-100
10000
Integer 16
Engine Protect
AI2 Del
8371
900
Unsigned 16
Engine Protect
AI3 Wrn
20
8381
-100
10000
Integer 16
Engine Protect
AI3 Sd
10
8382
-100
10000
Integer 16
Engine Protect
AI3 Del
10
8377
900
Unsigned 16
Engine Protect
Batt Overvolt
36
9587
18
40
Integer 16
Engine Protect
Batt Undervolt
18
8387
40
Integer 16
Engine Protect
8383
600
Unsigned 16
Engine Protect
WrnMaintenance
9999
9648
10000
Unsigned 16
Gener Protect
Overload BOC
120
8280
200
Unsigned 16
Gener Protect
Overload Del
8281
600
Unsigned 16
Gener Protect
250
8282
100
500
Unsigned 16
Gener Protect
0,04
9991
10
Unsigned 16
Gener Protect
8283
60
Unsigned 16
Gener Protect
50
8284
200
Unsigned 16
Gener Protect
8285
600
Unsigned 16
Gener Protect
Gen >V Sd
110
8291
70
200
Unsigned 16
Gener Protect
70
8293
110
Unsigned 16
Gener Protect
Gen V Del
8292
600
Unsigned 16
Gener Protect
10
8288
200
Unsigned 16
Gener Protect
8289
600
Unsigned 16
Gener Protect
110
8296
85
200
Unsigned 16
Gener Protect
85
8298
110
Unsigned 16
Gener Protect
8297
600
Unsigned 16
Date/Time
60
min
8979
240
Unsigned 8
Date/Time
SummerTimeMod
DISABLED
8727
String list
Date/Time
Time
0:00:00
24554
Time
Date/Time
Date
1.1.2006
24553
Date
Date/Time
Timer1Function
No Func
11660
String list
Date/Time
Timer1 Repeat
NONE
10045
String list
Date/Time
Timer1 ON Time
5:00:00
10042
Time
Date/Time
Timer1Duration
Date/Time
Timer2Function
No Func
11661
String list
Date/Time
Timer2 Repeat
NONE
10202
String list
Date/Time
Timer2 ON Time
5:00:00
10199
Time
Date/Time
Timer2Duration
min
10201
1440
Unsigned 16
Sensors Spec
AI1Calibration
Bar
8431
-100
100
Integer 16
Sensors Spec
AI2Calibration
8407
-1000
1000
Integer 16
Sensors Spec
AI3Calibration
8467
-1000
1000
Integer 16
SMS/E-Mail
OFF
NT
min
10044
8482
1440
Unsigned 16
String list
102
SMS/E-Mail
OFF
8484
String list
SMS/E-Mail
Event Msg
OFF
10926
String list
SMS/E-Mail
TelNo/Addr Ch1
9597
Long string
SMS/E-Mail
TelNo/Addr Ch2
9598
Long string
SMS/E-Mail
SMS Language
Alternate Cfg
Nominal RPM 1
1500
Alternate Cfg
Nominal Freq 1
Alternate Cfg
Alternate Cfg
11394
Unsigned 8
RPM
9915
100
4000
Unsigned 16
50
Hz
9913
45
65
Unsigned 16
NomVoltsPh-N 1
230
12052
80
20000
Unsigned 16
NomVoltsPh-Ph1
400
12055
80
40000
Unsigned 16
Alternate Cfg
Nomin Current1
350
12049
10000
Unsigned 16
Alternate Cfg
Connect Type 1
3Ph4Wire
Alternate Cfg
Nominal RPM 2
1800
RPM
9916
100
4000
Unsigned 16
Alternate Cfg
Nominal Freq 2
60
Hz
9914
45
65
Unsigned 16
Alternate Cfg
NomVoltsPh-N 2
120
12053
80
20000
Unsigned 16
Alternate Cfg
NomVoltsPh-Ph2
208
12056
80
40000
Unsigned 16
Alternate Cfg
Nomin Current2
350
12050
10000
Unsigned 16
Alternate Cfg
Connect Type 2
3Ph4Wire
12058
String list
12059
String list
Values of MRS16:
Name
Firmware ver.
IL-NT-2.0
R:18.05.2012
IL-NT
Application
Date
App. ver.
Ser. num.
MRS16
7.6.2012
2,0
12345678
Group
Name
Value
Dimension
Com. obj.
Data type
Engine
RPM
RPM
8209
Unsigned 16
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Generator
Gen kW
Gen kW L1
Gen kW L2
Gen kW L3
Gen kVAr
Gen kVAr L1
Gen kVAr L2
Gen kVAr L3
Gen kVA
Gen kVA L1
Gen kVA L2
Gen kVA L3
Gen PF
Gen Char
Gen PF L1
Gen Char L1
Gen PF L2
Gen Char L2
Gen PF L3
Gen Char L3
Gen Freq
Gen V L1-N
Gen V L2-N
Gen V L3-N
Gen V L1-L2
Gen V L2-L3
Gen V L3-L1
0
0
0
0
0
0
0
0
0
0
0
0
0
kW
kW
kW
kW
kVAr
kVAr
kVAr
kVAr
kVA
kVA
kVA
kVA
8202
8524
8525
8526
8203
8527
8528
8529
8565
8530
8531
8532
8204
8395
8533
8626
8534
8627
8535
8628
8210
8192
8193
8194
9628
9629
9630
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 8
Char
Integer 8
Char
Integer 8
Char
Integer 8
Char
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
NT
0
0
0
0
0
0
0
0
0
0
Hz
V
V
V
V
V
V
Filename
IL-NT-MRS162.0.AIL
103
Generator
Generator
Generator
Gen A L1
Gen A L2
Gen A L3
0
0
0
A
A
A
8198
8199
8200
Unsigned 16
Unsigned 16
Unsigned 16
Controller I/O
Controller I/O
Controller I/O
Controller I/O
Controller I/O
Controller I/O
Controller I/O
Controller I/O
Controller I/O
Controller I/O
Controller I/O
Battery Volts
D+
Oil Pressure
Engine Temp
Fuel Level
Bin Inputs
Bin Outputs
GSM SignalLvl
GSM ErrorRate
GSM Diag Code:
AirGate Diag:
V
V
Bar
C
%
8213
10603
8227
8228
8229
8235
8239
11895
12199
11270
11271
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Binary 16
Binary 16
Unsigned 16
Unsigned 8
Unsigned 8
Unsigned 8
Controller I/O
AirGate ID:
12385
Long string
Controller I/O
Modem Status:
0
0
0
0
0
[000000]
[000000]
0
0
0
0
No
Connection
No
Connection
12485
Short string
Statistics
Statistics
Statistics
Statistics
Statistics
Statistics
Statistics
Statistics
Genset kWh
Genset kVArh
Run Hours
Num Starts
Maintenance
Num E-Stops
Shutdowns
TotFuelConsum
0
0
0
0
9999
0
0
0
8205
8539
8206
8207
9648
11195
11196
9040
Integer 32
Integer 32
Integer 32
Unsigned 16
Unsigned 16
Unsigned 32
Unsigned 32
Unsigned 32
IL Info
IL Info
IL Info
IL Info
IL Info
IL Info
IL Info
IL Info
IL Info
Engine State
Breaker State
Timer Text
Timer Value
FW Version
Application
FW Branch
PasswordDecode
DiagData
#####
#####
#####
0
2
4
1
#####
#####
8330
8455
8954
8955
8393
8480
8707
9090
10050
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 16
Unsigned 8
Unsigned 8
Unsigned 8
Unsigned 32
Unsigned 32
Date/Time
Date/Time
Time
Date
#####
#####
24554
24553
Time
Date
NT
h
h
104
Remote Communication
Hint:
Refer to InteliCommunication guide for all additional information.
Internet connection
IL-NT controllers can be monitored from LiteEdit over the Internet using Internet Bridge (IG-IB)
connected to the controller RS232 port. Or via plug-in card IB-Lite directly plugged in
communication slot on back side of the controller.
SNMP connection
For SNMP protocol support it is possible to use converter Modbus RTU - SNMP with ComAp order
code GNOME SNMP CONVERTER IL-NT.
For more details see IL-NT, IA-NT, IC-NT Communication Guide available here:
http://www.comap.cz/products/detail/intelilite-nt-amf-25/downloads/#tabs
Askey TAS-200E
ASUScom TA-220ST
Develo Microlink ISDN i
Siemens M20, TC35, TC35i, ES75, MC39 (Cinterion MC55i is NOT recommended)
Wavecom M1200/WMOD2
Wavecom - Maestro 20, dual 900/1800MHz.
Wavecom Fastrack M1306B, dual 900/1800 MHz (Fastrack M1206B is NOT recommended)
FALCOM A2D, dual 900/1800MHz.
105
Analog
modem
Analog
modem
or
GSM
modem
GSM
modem
106
6.
7.
8.
9.
10.
11.
accessible by PAGE button from any measurement screen on controller. Setpoints can be set
on controllers front panel keyboard or by LiteEdit 4.5 and higher.
Switch off ComAp controller.
Place the SIM card into slot on IL-NT-GPRS card, plug in the IL-NT-GPRS card into
communication slot on back side of ComAp controller.
Connect the antenna to designated SMA connector.
Connect power supply to IL-NT-GPRS module. It supports 8-36V DC voltage.
Power up the system.
Wait for approx 2 - 4 minutes for first connection of the system to AirGate. AirGate will
generate automatically the AirGate ID value. Then navigate to last of measurement screens
where you will find signal strength bar and AirGate ID identifier.
Once this AirGate ID is displayed, connection via AirGate was succesfull. This value will be
needed for LiteEdit or WebSupervisor connection. Kindly make a note for future reference.
AirGate Connection dialog in LiteEdit:
Should you encounter any troubles with connection, check the faultcodes on the same screen
and find detailed description in Diagnostic codes listed lower.
12. Open LiteEdit PC software or enter your WebSupervisor account at
http://websupervisor.comap.cz.
Hint: For opening a new WebSupervisor account kindly send e-mail to
[email protected] your Name, Login name, E-mail address and Timezone. We will
create free account for you. Details at: http://www.comap.cz/products/detail/WebSupervisor .
NT
107
108
General description
Remote display software works as remote display and control for the master InteliLite-NT or
InteliDrive Lite controller. Genset/Engines can be controlled from remote display as well as from
master controller. All remote display screens (Measure, Setpoints and History) displays the same data
like master controller. Front panel buttons on both controllers work the same way. All remote display
LEDs shows the same state as corresponding LEDs on master controller.
Warning !
It is highly recommended to use the same type and model of controller for master and remote
display. Only in such case is assured the proper function of all buttons, LED diods and display.
Another combinations of HW types and models from Master controller and remote display are
not supported nor tested!
NT
109
CAUTION!
Check the statistic value "Engine hours" after firmware upgrade. Change of statistical values if
necessary is possible only by LiteEdit software (password is required).
IL-NT-RD Wiring
IL-NT-RD can be connected to InteliLite-NT or InteliDrive Lite controller via RS232 or RS485
communication line. It is possible to connect only up to two remote displays to one master controller, if
they are using different communication COMs. It is not supported to connect two or more remote
displays to one communication line, eg. RS485. It is possible to monitor only one master controller
from one remote display at the time.
Connection process
Remote display after power on automaticaly starts to search for any master controller connected. It
starts to search on COM1 from master controllers address 1 to 32 and later on COM2 from address 1
to 32. Remote display tries two communication speeds 38400 bps and 56000bps.
During this process is displayed text Detecting on screen and progress bar below counts from 0 to
100%. This process takes approx. 10-15 seconds. Than is 5 seconds pause and process continues
again until compatible master controller is found.
Not supported types of controllers, not supported application, or controllers that are not properly
comunicating are skipped during the search.
110
2.
3.
4.
5.
IL-NT
ID-Lite
IL-NTRS232
RS 232 (COM1)
IL-NTRS232
Remote Display
IL-NT
ID-Lite
Master controller
Up to 10 meters:
It is recommended to use standard Null-modem cable for local connection between controller and
remote display, although the three wires (TxD, RxD, GND) RS 232 connection is enough for direct
communication:
IL-NT/ID-Lite
connector
D-SUB9 female
RxD 2
TxD 3
GND 5
IL-NT-RD connector
D-SUB9 female
3 TxD
2 RxD
5 GND
NT
111
IL-NT
ID-Lite
IL-NTRS232-485
RS 232 (COM1)
IL-NTRS232-485
Remote Display
IL-NT
ID-Lite
Master controller
OR
IL-NT
ID-Lite
IL-NTRS232-485
RS 485 (COM2)
IL-NTRS232-485
Remote Display
IL-NT
ID-Lite
Master controller
OR
IL-NT
ID-Lite
IL-NTRS232-485
RS 232 (COM1)
IL-NTRS232-485
Remote Display 1
IL-NT
ID-Lite
IL-NT
ID-Lite
Master controller
IL-NTRS232-485
RS 485 (COM2)
Remote Display 2
Case 1) RS232
Master controller settings:
ControllerAddr = 1..32
COM1 Mode = DIRECT
Case 2) RS485
Master controller settings:
ControllerAddr = 1..32
COM2 Mode = DIRECT
Case 3) RS232 +RS485
Master controller settings:
ControllerAddr = 1..32
COM1 Mode = DIRECT
COM2 Mode = DIRECT
It is possible to make a RS232 direct connection with IL-NT-RS232 module on one side and IL-NTRS232-485 module on the other side.
112
ADVANTECH ADAM 4520: RS232 to RS422/485 converter, DIN rail, automatic RS485 bus
supervision, no external data flow control signals, galvanic isolated, baud rate 38400 or 56000 bps.
Any connected RS 232 to RS 422/485 converter has to be set to passive DSR signal (when DSR
connected) after switch on.
Function description
Remote display IL-NT-RD works as remote display and control of the master InteliLite-NT or InteliDrive
Lite controller. It is supposed and highly recommended that both, remote display and master are using
the same HW type and model of controller. Another types and models of master and remote display
are not supported nor tested. All remote displays LEDs shows the same state as corresponding LEDs
on master controller. Front panel buttons on both controllers work in the same way. Genset/Engine
can be controlled from remote display as well as from master controller. User can switch screens, set
password, change setpoints and view history records.
All IL-NT-RD screens Init, Measure, Setpoints and History display the same data like in the master
controller.
Master device is always able to work without connected Remote display.
Interruption of the serial line between master device and Remote display has no effect to the master
controller.
If the serial line between master device and remote display is interrupted, or communication cannot be
established, remote display shows its Init screen and message Trying and all LEDs are off.
Once remote display finds compatible master it shows Preparing and downloads configuration table
from master controller.
After the configuration from master is downloaded remote display jump to master controllers Init
screen and all LEDs and blinking.
It is possible to switch to remote displays Init screen to check its version and serial number of used
controller and communication status by pressing PAGE button for 3 seconds.
SW compatibility
IL-NT-RD sw. version 1.1 is compatible with masters SW:
All InteliLite-NT standard software from ver. 1.1
All ID-Lite standard software from ver. 1.0
Chosen IL-NT and ID-Lite customer branches
Some of the future IL-NT, ID-Lite versions may require upgrade of the IL-NT-RD software.
NT
113
Maintenance
Backup battery replacement
The internal backup battery should be replaced approx. every 5-7 years. Replace the battery, if the
alarm Low BackupBatt occurs. Follow these instructions:
1. Disconnect all terminals from the controller and remove the controller from the switchboard.
2. Release the rear cover using a flat screwdriver or another suitable tool.
NT
114
5. Put the rear cover back. Use slight pressure to lock the snaps into the housing. Pay attention
that the cover is in correct position and not upside down!
6. Plug the modules back into the slots.
7. Power the controller on, adjust date and time and check all setpoints.
Hint:
When internal RTC battery becomes flat, controller function (e.g. Ready for stand by) does not change
until controller power supply is switched off. Some time before the battery is completely exhausted, a
warning message appears in Alarmlist: "RTCbatteryFlat".
After the next power switch on (with flat battery already) controller:
Genset is still possible to run
All new history records will have not valid date and time stamp.
Time and Date values are set not valid value
Statistics values are random
Timers (Timer1..2 Function) will not be executed
Fuel theft protection may not work
NT
115
Technical Data
Inputs/Outputs overview
Model
IL-NT MRS10
IL-NT MRS11
IL-NT MRS15
IL-NT MRS16
BIN
6+8*+8**
6+8*+8**
6+8*+8**
6+8*+8**
Gen.
Mains Gen.
BOUT
AI
AOUT COM1 COM2 CAN RPM Voltage Voltage Current
6+8*+8**
3
8*
Y*
Y*
N
Y
Y
N
Y
6+8*+8**
3
8*
Y*
Y*
N
Y
Y
N
Y
6+8*+8** 3+4*
8*
Y*
Y*
Y
Y
Y
N
Y
6+8*+8** 3+4*
8*
Y*
Y*
Y
Y
Y
N
Y
Note:
* With optional extension module
IGS-PTM or IG-IOM
** With optional plug-in module
Y -Available
N -Not available
Generator protections
ComAp gen-set controllers provide following range of generator protections.
For each protection adjustable limit and time delay are available.
Comparison table with ANSI codes:
ANSI
IL-NT
code
Protection
MRS10
59
Overvoltage
27
Undervoltage
47
Voltage Assymetry
81H
Overfrequency
81L
Underfrequency
50+51
Overcurrent
***
46
Current Unbalance
32
Overload
51N+64
Earth Fault
32R
Reverse Power
25
Synchronism Check 47
Phase Rotation
**
37
Undercurrent
55
Power Factor
71
Gas (Fuel) Level
Note:
**
***
IL-NT
MRS11
***
**
IL-NT
MRS15
**
IL-NT
MRS16
**
Not available
Available
Fixed setting
Shortcurrent only
NT
116
Language support
IL-NT in firmware version 1.5 supports following language code pages:
Code page
0
134
162
177
204
238
Language
West European languages
Chinese
Turkish
Hebrew
Russian
East European languages
Windows code
Windows 1252
GB 2312
Windows 1254
Windows 1255
Windows 1251
Windows 1250
Power supply
Voltage supply
Consumption
8-36V DC
40-430mA depend on supply voltage and
temperature
0,104A at 8VDC
0,080A at 12VDC
0,051A at 24VDC
0,044A at 30VDC
0,040A at 36VDC
Hint:
For the supply voltage less than 7V the backlight of the display is switched off.
Short-term voltage drops (e.g. during the engine cranking) do not affect the operation at all.
Operating conditions
o
-20..+70 C
o
-40..+70 C
o
-30..+80 C
IP65
95% without condensation
EN 61010-1:95 +A1:97
EN 50081-1:94, EN 50081-2:96
EN 50082-1:99, EN 50082-2:97
5 - 25 Hz, 1,6mm
25 - 100 Hz, a = 4 g
2
a = 200 m/s
Vibration
Shocks
#
LCD display limits controller operating temperature range to 20 C - + 70 C even if the other
electronic components work in wider temperature range.
NT
Internal preheating foil is mounted in InteliLite LT to extend display operational temperature range.
o
Preheating starts at temperature below 5 C and preheating power depends on temperature and
power supply voltage.
NT
117
Technical data
Operating temperature
Storage temperature
IL-NT Standard
o
o
-20 C..+70 C
o
o
-30 C..+80 C
Order code:IL-NT-xxxxx LT
o
o
-40 C..+70 C
o
o
-30 C..+80 C
180x120x55mm
450g
Generator
Nominal frequency
Frequency measurement tolerance
50-60Hz
0,2Hz
Current inputs
Nominal input current (from CT)
Load (CT output impedance)
CT input burden
Max. measured current from CT
Current measurement tolerance
Max. peak current from CT
Max. continuous current
5A
< 0,1
< 0,2 VA per phase (In=5A)
10 A
2% from the Nominal current
150 A / 1s
12 A
Voltage inputs
Measuring voltage range
Maximal measured voltage
Input resistance
Voltage measurement tolerance
Overvoltage class
6
4,2 k
0-36 VDC
<0,8 VDC
>2 VDC
8-36 VDC
6
0,5 A
118
36 VDC
Analog inputs
Not electrically separated
Number of inputs
Resolution
Maximal resistance range
Resistance measurement tolerance
3
10 bits
2500
2 % 2 out of measured value
D+ Terminal
CHARGE ALT D+ Function:
Max. CHARGE ALT D+ output current
Guaranteed level for signal Charging OK
300 mA
80% of supply voltage
200m
250kBd
120
twisted pair (shielded)
Following dynamic cable parameters are important especially for maximal 200 meters CAN bus length
and 32 iS-COM units connected:
Nominal Velocity of Propagation
min. 75% (max. 4,4 ns/m)
2
Wire crosscut
min.0,25 mm
Maximal attenuation (at 1 MHz)
2 dB / 100m
Recommended Industrial Automation & Process Control Cables:
BELDEN (see http://www.belden.com):
3082A DeviceBus for Allen-Bradley DeviceNet
3083A DeviceBus for Allen-Bradley DeviceNet
3086A DeviceBus for Honeywell SDS
3087A DeviceBus for Honeywell SDS
3084A DeviceBus for Allen-Bradley DeviceNet
3085A DeviceBus for Allen-Bradley DeviceNet
3105A Paired EIA Industrial RS485 cable
LAPP CABLE
Unitronic BUS DeviceNet Trunk Cable
Unitronic BUS DeviceNet Drop Cable
Unitronic BUS CAN
NT
119
10m
Up to 57.6 kBd (DIRECT), 38.4kBd Analog
Hint:
This module is supported with SW version IL-NT 1.3 and newer.
5m
Up to 57.6 kBd (DIRECT), 38.4kBd Analog
NT
120
8
250Hz
0.5 A
36 VDC
1
10 bits
Number of inputs 1
Nominal input current (from CT) 5A
Load (CT output impedance) < 0.1
Max measured current from CT 10A
Current measurement tolerance 2% from Nominal current
Max peak current from CT 150A / 1s
Max continuous current 10A
(All values in RMS)
BINARY INPUTS
Number of inputs 7
Input resistance 4.7k
Input range
0-36 VDC
Voltage level for close contact indication (Logical 1) <0.8 VDC
Voltage level for open contact indication (Logical 0) >2 VDC
Max voltage level for open contact indication
8-36 VDC
Binary inputs
Number of inputs
Input resistance
Input range
Voltage level for close contact indication (Logical 1)
Voltage level for open contact indication (Logical 0)
Max voltage level for open contact indication
8
4,7k
0-36 VDC
<0,8 VDC
>2 VDC
8-36 VDC
8
0,5 A
2A
121
36V
Hint:
Binary inputs are not galvanicaly isolated.
Please see detail about wiring and description at chapter IL-NT BIO8 Hybrid binary input/output
module.
IGS-PTM
Voltage supply
Consumption
Mechanical dimensions:
Interface to controller
Binary inputs and outputs
Analog output
8-36V DC
0,1A depend on supply voltage
40 x 95 x 45 mm , DIN rail (35 mm) mounted
CAN
see IG-IOM
see IG-IOM
Analog inputs
Not electrically separated
Number of inputs
Resolution
Maximal resistance range
Maximal voltage range
Maximal current range
Resistance measurement tolerance
Voltage measurement tolerance
Current measurement tolerance
4
10 bits
0 250
0 100 mV
0 20 mA
1 % 2 out of measured value
1,5 % 1mV out of measured value
2,5 % 0,5mA out of measured value
IGL-RA15
Power supply
Voltage supply
Consumption
8-36V DC
0,35-0,1A (+1A max horn output)
Depend on supply voltage
Operating conditions
Operating temperature
Storage temperature
Protection front panel
-20..+70 C
o
-40..+80 C
IP65
180x120x55mm
950g
Horn output
Maximum current
Maximum switching voltage
1A
36 VDC
IG-IB
Voltage supply
Consumption
Mechanical dimensions:
NT
8-36V DC
0,1A depend on supply voltage
95 x 96 x 43 mm , DIN rail (35 mm) mounted
122
Interface to controller
Interface to modem
Interface to Ethernet
Operating temperature
Storage temperature
NT
RS232
RS232
RJ45 (10baseT)
o
-30..+70 C
o
-30..+70 C
123