Engineering Standard: IPS-E-EL-100
Engineering Standard: IPS-E-EL-100
Engineering Standard: IPS-E-EL-100
ENGINEERING STANDARD
FOR
ELECTRICAL SYSTEM DESIGN
(INDUSTRIAL AND NON-INDUSTRIAL)
FIRST EDITION
FEBRUARY 2012
This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner.
Neither whole nor any part of this document may be disclosed to any third party, reproduced, stored
in any retrieval system or transmitted in any form or by any means without the prior written consent
of the Iranian Ministry of Petroleum.
Feb. 2012
IPS-E-EL-100(1)
FOREWORD
The Iranian Petroleum Standards (IPS) reflect the views of the Iranian Ministry of Petroleum and are
intended for use in the oil and gas production facilities, oil refineries, chemical and petrochemical
plants, gas handling and processing installations and other such facilities.
IPS are based on internationally acceptable standards and include selections from the items
stipulated in the referenced standards. They are also supplemented by additional requirements
and/or modifications based on the experience acquired by the Iranian Petroleum Industry and the
local market availability. The options which are not specified in the text of the standards are
itemized in data sheet/s, so that, the user can select his appropriate preferences therein.
The IPS standards are therefore expected to be sufficiently flexible so that the users can adapt
these standards to their requirements. However, they may not cover every requirement of each
project. For such cases, an addendum to IPS Standard shall be prepared by the user which
elaborates the particular requirements of the user. This addendum together with the relevant IPS
shall form the job specification for the specific project or work.
The IPS is reviewed and up-dated approximately every five years. Each standards are subject to
amendment or withdrawal, if required, thus the latest edition of IPS shall be applicable
The users of IPS are therefore requested to send their views and comments, including any
addendum prepared for particular cases to the following address. These comments and
recommendations will be reviewed by the relevant technical committee and in case of approval will
be incorporated in the next revision of the standard.
Feb. 2012
IPS-E-EL-100(1)
GENERAL DEFINITIONS
Throughout this Standard the following definitions shall apply.
COMPANY :
Refers to one of the related and/or affiliated companies of the Iranian Ministry of Petroleum such as
National Iranian Oil Company, National Iranian Gas Company, National Petrochemical Company
and National Iranian Oil Refinery And Distribution Company.
PURCHASER :
Means the Company" where this standard is a part of direct purchaser order by the Company,
and the Contractor where this Standard is a part of contract document.
CONTRACTOR:
Refers to the persons, firm or company whose tender has been accepted by the company.
EXECUTOR :
Executor is the party which carries out all or part of construction and/or commissioning for the
project.
INSPECTOR :
The Inspector referred to in this Standard is a person/persons or a body appointed in writing by the
company for the inspection of fabrication and installation work.
SHALL:
Is used where a provision is mandatory.
SHOULD:
Is used where a provision is advisory only.
WILL:
Is normally used in connection with the action by the Company rather than by a contractor,
supplier or vendor.
MAY:
Is used where a provision is completely discretionary.
Feb. 2012
CONTENTS:
IPS-E-EL-100(1)
Page No.
1. SCOPE ............................................................................................................................................ 4
2. REFERENCES ................................................................................................................................ 4
3. UNITS .............................................................................................................................................. 5
4. ENVIRONMENTAL AND SITE CONDITIONS ............................................................................... 5
5. GENERAL ....................................................................................................................................... 6
5.1 Definitions ................................................................................................................................ 6
5.2 Operational Safety and Reliability ....................................................................................... 11
5.3 Certificates, Declarations and Test Reports ...................................................................... 11
5.4 Quality Assurance and Control ........................................................................................... 12
5.5 Standards, Codes and Regulations .................................................................................... 12
5.6 Document List ....................................................................................................................... 12
6. BASIC ELECTRICAL SYSTEM DESIGN CONSIDERATION ..................................................... 12
6.1 Industrial Electrical System ................................................................................................. 12
6.2 Non-industrial electrical systems ........................................................................................ 40
6.3 Electrical Apparatus for Potentially Explosive Gas Atmospheres .................................. 51
7. DESIGN AND SELECTION REQUIREMENTS FOR EQUIPMENT ............................................. 51
7.1 Electric Network Supply and Emergency Systems (Diesel Generator ) ...................... 51
7.2 Switchgear, Controlgear and Substations ......................................................................... 62
7.3 Transformers ......................................................................................................................... 72
7.4 Electrical motors .................................................................................................................. 82
7.5 Electrical Protection, Metering & Control ........................................................................... 84
7.6 Batteries, Chargers and UPS ............................................................................................. 101
7.7 Power Cables ...................................................................................................................... 108
7.8 Static power factor correction equipment ........................................................................ 115
7.9 Overhead Lines ................................................................................................................... 117
7.10 Lighting ............................................................................................................................. 117
7.11 Earthing, Bonding and Lightning Protection ................................................................. 124
APPENDICES:
APPENDIX A DOCUMENT LIST .................................................................................................. 134
Feb. 2012
IPS-E-EL-100(1)
1. SCOPE
This recommendation covers the minimum requirements which shall be considered in design of
electrical systems in oil, gas, and petrochemical industries. It deals with planning, selection of
equipment, economics of design and hints to be taken care in operation and maintenance. It
describes criteria in selection of system voltage, fault consideration and discusses the safety and
protection of electrical system.
Note:
This is a revised version of this standard, which is issued as revision (1)-2012. Revision (0)1997 of the said standard specification is withdrawn.
2. REFERENCES
a) This recommendation is based on IEC standards and the following standards have been referred
in this document.
b) The following IPS standards may be referred in detail design engineering when required.
IPS
IPS-M-EL-131 (2)
IPS-M-EL-132 (2)
IPS-E-EL-110 (1)
IPS-M-EL-138 (0)
IPS-E-EL-160 (1)
IPS-I-EL-215 (1)
IPS-M-EL-136 (1)
IPS-M-EL-138 (0)
IPS-I-EL-217 (0)
IPS-M-EL-143 (2)
IPS-M-EL-144 (1)
IPS-M-EL-181 (2)
IPS-M-EL-151 (1)
IPS-M-EL-152 (2)
IPS-M-EL-190 (1)
IPS-M-EL-165 (0)
IPS-M-EL-220 (1)
IPS-M-EL-174 (2)
Feb. 2012
ISO
IPS-E-EL-100(1)
IPS-M-EL-176
IPS-M-EL-240 (0)
IPS-M-EL-271 (1)
IPS-M-EL-272 (1)
IPS-M-EL-273 (1)
Material Standard for Sub Marine Power Cables with Inherent Optical
Fibers
NFPA 70
3. UNITS
This Standard is based on International System of Units (SI), as per IPS-E-GN-100 except where
otherwise specified.
4. ENVIRONMENTAL AND SITE CONDITIONS
The following are the minimum typical information that shall be completed in conjunction with the
environmental conditions before engineering work proceeds on:
1) Site elevation ....................................... m above sea level
2) Maximum ambient temperature............................................. C
3) Minimum ambient temperature.............................................. C
4) Minimum relative humidity.............................. %
5) Atmosphere: Saliferrous, dust corrosive and subject to dust storms with concentration of 70-1412
mg/m, H2S may be present unless otherwise specified.
6) Lightning storms: Isoceraunic level......... storm-day/year
7) Earthquake zone.................................................
8) Wind direction (where relevant).........................................
9) Area classification (where applicable)
Feb. 2012
IPS-E-EL-100(1)
5. GENERAL
5.1 Definitions
For the purpose of this standard, the following definitions apply:
Certificate
Document issued by a recognized authority certifying that it has examined a certain type of
apparatus and, if necessary, has tested it and concluded that the apparatus complies with the
relevant standard for such apparatus.
Certificate of conformity
Certificate stating that the electrical apparatus complies with the relevant standards for apparatus
for potentially explosive atmospheres.
Declaration of compliance
Document issued by the manufacturer declaring that the electrical apparatus complies with the
requirements of IEC 60079-15.
Distribution of electricity
The transfer of electricity to consumers within an area of consumption.
Electrical installation
Civil engineering works, buildings, machines, apparatus, lines and associated equipment used for
the generation, conversion, transformation, transmission, distribution and utilization of electricity:
Emergency Lighting
Lighting provided for use when the supply to the normal lighting fails.
Escape Lighting
That part of the emergency lighting which is provided to ensure that the escape route is illuminated
at all material times.
Feb. 2012
IPS-E-EL-100(1)
Essential service
A service, which, when failing in operation or when failing if called upon, will affect the continuity,
the quality or the quantity of the product.
Firm capacity
The installed capacity less than stand-by capacity.
Frequency deviation
The difference between the system frequency at a given instant and the nominal value.
Hazardous area
An area in which an explosive gas atmosphere is or may be expected to be present in quantities
such as to require special precautions for the construction, installation and use of electrical
apparatus.
Installed capacity
The sum of the rated powers of equipment of the same kind (generators, transformers, converters,
etc.) in an electrical installation.
Non-essential service
A service that is neither vital nor essential.
Non-hazardous area
An area in which an explosive gas atmosphere is not expected to be present in quantities such as
to require special precautions for the construction, installation and use of electrical apparatus.
Rated value
A quantity value assigned, generally by the manufacturer, for a specific operating condition of a
component, device or equipment.
Site conditions
The external factors, e.g. altitude, air temperature, wind velocity, vibrations, earthquakes, black
body temperature, relative humidity, etc., which may influence the operation of a machine or
apparatus.
Feb. 2012
IPS-E-EL-100(1)
Spare capacity
The difference between firm capacity and the maximum calculated (peak) load.
Stand by capacity
The capacity provided for the purpose of replacing that which may be withdrawn from service under
planned or unplanned circumstances.
Test report
Document prepared by the manufacturer indicating in detail the tests and verifications to which the
electrical apparatus has been subjected, and their results.
Vital service
A service which, when failing in operation or when failing if called upon, can cause an unsafe
condition of the process and/or electrical installation, jeopardize life, or cause major damage to the
installation.
Voltage deviation
The difference, generally expressed as a percentage, between the voltage at a given instant at a
point in the system, and a reference voltage such as nominal voltage, a mean value of operating
voltage, or declared supply voltage.
Voltage dip
A sudden reduction of the voltage at a point in the system, followed by voltage recovery after a
short period of time, from a few cycles to a few seconds.
Voltage surge
A transient voltage wave propagating along a line or a circuit and characterized by a rapid increase
followed by a slower decrease of the voltage.
Feb. 2012
IPS-E-EL-100(1)
Note:
A dust layer maybe present and should be taken into account.
Note:
This zone can include areas in the vicinity of apparatus containing dust, from which, dust
can escape from leaks and form dust deposits in hazardous areas.
Controlgear
A general term covering switching devices and their combination with associated control,
measuring, protective and regulating equipment, also assemblies of such devices and equipment
with associated interconnections, accessories, enclosures and supporting structures, intended in
principle for the control of electric energy consuming equipment.
Converter
An operative unit for electronic power conversion comprising one or more electronic valve devices,
e.g. thyristors, associated firing and control circuits and, if necessary, filters and auxiliaries.
Distribution substation/switchboard
A substation/switchboard mainly used for distributing power to several plant substations.
Generating set
A group of rotating machines transforming mechanical or thermal energy into electricity.
Generator
A machine which converts mechanical power into electrical power.
9
Feb. 2012
IPS-E-EL-100(1)
Intake substation/switchboard
A substation/switchboard at which the supply provided by the public utility is interconnected with the
site's electrical distribution system.
Note:
An intake substation and a power plant substation may be combined as a single substation.
Inverter
A converter for conversion from DC to AC
Plain feeder
A feeder which consists of a cable or an overhead line only and does not have. An interconnected
transformer.
Plant substation/switchboard
A substation/switchboard mainly used for feeding one process or utility plant.
Note:
An intake substation and a power plant substation may be combined as a single substation.
Power transformer
A static piece of apparatus with two or more windings which, by electromagnetic induction,
transforms a system of alternating voltage and current into another system of voltage and current
usually of different values and at the same frequency for the purpose of transmitting electrical
power.
Rectifier
A converter for conversion from AC to DC.
10
Feb. 2012
IPS-E-EL-100(1)
Switchgear
A general term covering switching devices and their combination with associated control,
measuring, protective and regulating equipment, also assemblies of such devices and equipment
with associated interconnections, accessories, enclosures and supporting structures, intended in
principle for use in connection with generation, transmission, distribution and conversion of electric
power.
Switch room
A room in a substation or building intended exclusively for the installation of one or more
switchboards, distribution boards etc.
11
Feb. 2012
IPS-E-EL-100(1)
For electrical apparatus in Zone 0, Zone 1 and Zone 2 areas, a certificate of conformity shall be
obtained from the Manufacturer; For electrical apparatus in Zone 2 areas, which has type of
protection 'n', a declaration of compliance may be accepted instead of a certificate of conformity.
12
Feb. 2012
IPS-E-EL-100(1)
6.1.1.1 General
Minimum required Documents for basic and detail design shall be accordance with "Appendix A".
6.1.1.1.1 Safety
Safety takes to form: Safety to personnel, safety to materials, building and safety to electric
equipment.
Safety to personnel involves no compromise, only the safest system can be considered. Safety to
materials. Buildings and electric equipment may involve some compromise when safety of
personnel is not jeopardized. In general:
Safe and reliable supply of electrical supply electricity should be designed.
Safe condition for start-up and shut-down of plant shall be provided.
Safety of personnel and equipment during operation and maintenance shall be considered.
6.1.1.2.1 Obtain a general layout and mark it with the major loads at various locations and
determine the approximate total plant load in horsepower, kilowatts, and kilo volt-amperes.
Estimate the lighting, air-conditioning, and other loads from known data.
13
Feb. 2012
IPS-E-EL-100(1)
6.1.1.2.2 Determine the total connected load and calculate the maximum demand by using demand
and diversity factors.
6.1.1.2.3 Investigate unusual loads, such as the starting of large motors, or welding machines, and
operating conditions such as boiler auxiliary motors, loads that must be kept in operation under all
conditions, and loads that have a special duty cycle.
6.1.1.2.4 Investigate the various types of distribution system and select the system or systems best
suited to the requirements of the plant. Make a preliminary one line diagram of the power system.
6.1.1.2.5 If power is to be purchased from the utility, obtain such information concerning the supply
system or systems as:
performance data, voltage available, voltage spread, type of systems available, method of system
neutral grounding, and other data such as relaying, metering and the physical requirements of the
equipment. The interrupting rating and momentary ratings of power circuit breakers should be
obtained as well as the present and future short-circuit capabilities of the utility system at the point
of service to the plant. Investigate the utilitys power contract to determine if off-peak power at lower
rates available, and any other requirements, such as power factor and demand clauses, that can
influence power cost.
6.1.1.2.6 If considering a generating station for an industrial plant, such items should be determined
as : generating KVAR required including standby loads, generating voltage, and such features as
relaying, metering, voltage regulating equipment, synchronizing equipment and grounding
equipment. If parallel operation is contemplated, be sure to review this with the utility and obtain its
requirements.
6.1.1.2.7 A cost analysis may be required of the different voltage levels and various arrangements
of equipment to justify and properly determine the voltage and equipment selected. The study
should be made on the basis of installed cost including all the components in that section of the
system.
6.1.1.2.8 Check the calculations of short-circuit requirements to be sure that all breakers are of the
correct rating. Review the selectivity of various protective devices to assure selectivity during load
or fault disturbances.
6.1.1.2.9 Calculate the voltage spread and voltage drop at various critical points.
6.1.1.2.10 Determine the requirements of the various components of the electric distribution system
with special attention given to special operating and equipment conditions.
6.1.1.2.11 Review all applicable national and local codes for requirements and restrictions.
6.1.1.2.12 Check to see that the maximum safety features are incorporated in all parts of the
system.
6.1.1.2.13 Write specification on the equipment and include a one-line diagram as a part of the
specifications.
14
Feb. 2012
IPS-E-EL-100(1)
6.1.1.2.14 Obtain typical dimensions of equipment and make drawings of the entire system.
6.1.1.2.15 Determine if the existing equipment is adequate to meet additional load requirements.
Check such ratings as voltage, interrupting capacity, and current-carrying capacity.
6.1.1.2.16 Determine the best method of connecting the new part of the power system with the
existing system so as to have a minimum outage at minimum cost. Naturally the above procedure
will not automatically design the electric power system in itself; it must be used with good, sound,
basic engineering judgment.
6.1.1.5 Flexibility
Flexibility for expansion should be considered. In line with this, the engineer should strive for a
system design that will permit reasonable expansion with minimum downtime to existing production.
15
Feb. 2012
IPS-E-EL-100(1)
6.1.2 Load
6.1.2.1.1 Electrical equipment shall be rated to carry continuously the maximum load associated
with peak design production with an additional 20% contingency.
The ambient condition at which this rating applies shall be defined in equipment specifications and
unless otherwise approved by client shall not be less than 40C maximum air temperature at an
altitude not exceeding 1000 m above sea level.
6.1.2.1.2 Assessment of maximum load requirements of an installation shall allow for diversity
between various loads, drives or plants. The diversity factors used shall consider the coincidentally
requiring peak demands and shall be based on similar installations whenever possible. The use of
diversity factors shall result in "After Diversity Maximum Demands" (ADMD) being used for design
purposes.
16
Feb. 2012
IPS-E-EL-100(1)
6.1.3.1 General
The power supply system shall be designed to provide safe and economical operation. The safety
aspects should cover both plant and personnel. Economic considerations shall cover capital and
running costs and an assessment of the reliability and consequent availability of the system. The
cost of improved power systems reliability should be weighed against the progressive potential loss
incurred by loss of production. However a technical / economical study should be performed for
power supply source selection.
All negotiations with public utilities shall be the sole responsibility of client.
Feb. 2012
IPS-E-EL-100(1)
6.1.3.2.1 Critical loads by definition require a high degree of reliability of supply. This reliability may
be achieved by, in order of preference:
i) Providing another source of energy, such as batteries.
ii) Increasing the amount of normal supply generation equipment.
iii) Ensuring a number of alternative supply feeds is available to the loads.
iv) Providing local standby plant.
In cases where the provision of another source of energy is not practicable, the least cost of the
remaining alternatives should normally be adopted bearing in mind the additional servicing and fuel
requirements associated with standby generation.
6.1.3.2.2 Critical loads shall be supplied by reliable generators or other suppliers during
maintenance of the largest generator at coincidental to the unscheduled outage of the next largest
generator.
6.1.3.2.3 Where increased generating plant or local standby plant is selected to provide power to
critical loads, it shall be either diesel engine or gas turbine driven generator set(s) each with its own
dedicated fuel supply. Secure static power supplies may be selected depending on the nature of the
critical loads being supplied and on fuel availability for generator sets. The emergency equipment
shall be rated to have a spare capacity of 10%. The efficiency of operation of emergency equipment
is not a significant factor but its ability to start reliably and supply the loads under emergency
conditions is critical.
6.1.3.2.4 Emergency generator sets shall be capable of starting and running when no alternative
source of electrical AC power is available i.e., a black start capability. This shall be achieved by
compressed air starting with air receivers being capable of six engine starts from one air charge, or
by battery starting with a similar capability.
6.1.3.2.5 It shall not be possible to connect emergency generators to a load greater than their rated
capacity. Parallel operation of emergency diesel generators with grid supply shall not be permitted
and safe and reliable interlocks shall be considered for that. Manual facilities shall also be provided
for regular testing purposes.
Testing facilities should permit the loading of standby generator sets.
6.1.3.3.1 Generator circuits other than local emergency generators and public utility power intakes
shall be connected together at a common primary substation, the busbars of which are used as the
main load distribution center. In certain cases, however, generators and public utility power intakes
may be located at different points throughout the site, in which case there may be a number of
primary substations which shall be interconnected on the site.
6.1.3.3.2 The switchgear for primary substations shall comply with the requirements of
IPS-M-EL-144.
18
Feb. 2012
IPS-E-EL-100(1)
6.1.3.3.3 Busbar arrangements shall be selected to be cost effective, operationally flexible and safe.
The following technical points shall be taken into account:
i) Operational flexibility to permit loads and power supplies to be effectively connected under
schedule and unscheduled outages of circuits and busbar sections.
ii) Minimal switchgear per circuit and simple control and protection.
iii) Unscheduled loss of busbar sections shall not shut down the system beyond the level designed
and provided for.
iv) Scheduled maintenance of busbars shall be possible without system shutdowns beyond those
designed and provided for.
6.1.3.3.4 The location of the primary substations shall be considered in safe areas.
6.1.3.4 Synchronizing
6.1.3.4.1 Synchronizing or check synchronizing equipment shall be provided wherever more than
one source of power may be operated in parallel with another.
6.1.3.4.2 The simplest form of check synchronizing equipment shall comprise voltmeters and
synchroscope to show the voltage and frequency differences between the two systems that need to
be paralleled. A check synchronizing relay may be utilized to prevent operator mal-operation, but in
order to allow closing a power source on to a dead system, as is required under black start
conditions, the check synchronizing relay shall have a means of manual or automatic disconnection.
6.1.3.4.3 Synchronizing or check synchronizing facilities shall be fitted to busbar section and bus
coupler circuit breakers only when it is possible to run the two systems feeding either section of a
busbar completely segregated from the other. The numbers of circuit breakers provided with
synchronizing or check synchronizing facilities shall be kept to a minimum. A similar logic shall be
applied to public utility intake circuits. Alternatively, circuit breaker interlocking schemes shall be
installed to preclude the possibility of paralleling two sources of power where synchronizing facilities
are excluded. Synchronizing facilities shall be provided at the primary power supply voltage and
avoided at other voltages by use of appropriate circuit breaker interlocking.
6.1.3.5.1 Application
Secondary unit substations form the heart of all industrial plant electrical distribution systems. They
are used to step down the primary voltage to the utilization voltage at various load centers
throughout the plant. Many factors must be considered when selecting and locating substations.
Most important of these are:
i) Load grouping by KVA
ii) Voltage rating
iii) Service facilities
iv) Safety
v) Ambient conditions
vi) Continuity of service
vii) Aesthetic consideration
viii) Lightning protection requirements
ix) Space available
x) Outdoor vs. indoor location
19
Feb. 2012
IPS-E-EL-100(1)
20
IPS-E-EL-100(1)
Feb. 2012
High Voltage (HV): is defined as 10 kV and higher in a 3 phase, 3 wires, 50 Hz system and it
should be 10 KV, 11 KV, 20 KV, 33 KV, 63 KV, 66 KV, 132 kV and 230 KV. The low voltage is
normally restricted for supplying to utilization equipment directly.
The high and medium voltage is used most frequently for distribution purposes and also is
employed as utilization voltage particularly for motors rated 3.3, 6 and 11 kV.
The high voltages above 20 KV and the high voltages are mainly used for power distribution and or
transmission.
The frequency of power supply systems for onshore systems shall be 50 Hz. For offshore systems
the voltage of power system shall be based on engineering evaluation and decided by company
engineer.
100
full load voltage
The electrical power system shall be so designed to limit voltage drop (base on nominal voltage) in
the feeder cables to the following values:
21
Feb. 2012
IPS-E-EL-100(1)
1%
1%
5%
2%
3%
- The maximum voltage drop in the motor feeder cable during motor starting
15%
Note:
The total voltage drop to the terminals of motors shall not exceed 15% of the nominal system
voltage during the motor starting period under the worst conditions of the supply through
the distribution network.
For medium and high voltage motors the cable voltage drop at motor full load shall not exceed
3.25%.
22
IPS-E-EL-100(1)
Feb. 2012
Motor
Terminal Voltage
Line Voltage
Starting Torque
Full-Voltage
Starting Torque
Line Current
Full-Voltage
Starting Current
Full-voltage starter
1.0
1.0
1.0
Auto transformer
80 percent tap
65 percent tap
50 percent tap
0.80
0.65
0.50
0.64
0.42
0.25
0.88
0.46
0.30
0.80
0.64
0.80
0.50
0.45
0.375
0.25
0.20
0.14
0.50
0.45
0.375
Part-winding starter
(low-speed motors only)
75 percent winding
50 percent winding
1.0
1.0
0.75
0.50
0.75
0.50
0.57
0.33
0.33
* Notes:
1) For a line voltage not equal to the motor rated voltage multiply all values in the first
column by the ratio:
Actual voltage
Actual voltage
Actual voltage
23
IPS-E-EL-100(1)
Feb. 2012
Voltage Variation
Function of Voltage
90 Percent Voltage
(Voltage)
Decreases 19%
Increase 21%
Synchronous speed
Constant
No Change
No Change
Percent Slip
1/(Voltage)
Increase 20%
Decrease 17%
Full-Load Speed
(Synchronous Speed-Slip)
Decrease 1
Increase 1%
Decrease 2%
Practically No Change
Increase 1-2%
Increase 1/2-1%
Practically No Change
Decrease 1-2%
Increase 1%
Increase 2-3%
Increase 4-5%
Decrease 3%
Decrease 4%
Increase 5-6%
Efficiency
Full Load
3/4 Load
1/2 Load
---
Power Factor
Full Load
3/4 Load
1/2 Load
---
Full-Load Current
---
Increase 11%
Decrease 7%
Starting Current
---
Decrease 10-12%
Increase 10-12%
---
Increase 6-7C
Decrease 1-2C
Voltage
Decrease 19%
Increase 21%
Decrease Slightly
Increase Slightly
(Voltage)
* Note:
This data applies to motors above 25 horsepower (hp) .
6.1.6.1 General
6.1.6.1.1 The distribution network shall be designed to carry continuously at least 120% of the After
Diversity Maximum Demand (ADMD) associated with peak design production at the maximum
ambient conditions.
6.1.6.1.2 The selected distribution arrangement shall have a degree of reliability consistent with the
type of load being supplied, and with the power supply design philosophy which provides for
coincidental maintenance and unscheduled outage of the largest component of on site generating
plant or unscheduled outage of the largest feeder component of the power supply equipment.
6.1.6.3.1 The single radial system provide power to non-essential electrical loads or loads where
alternative sources of energy are available such as standby generating plant.
6.1.6.3.2 Each component of the single radial circuit shall be capable to supply 120% of the
required electrical load. Transformers or other plant which includes forced cooling equipment shall
not relay on the forced cooling arrangements to obtain the necessary rating.
24
Feb. 2012
IPS-E-EL-100(1)
6.1.6.4.1 Critical and essential loads shall be supplied by two or more identically rated radial
system.
6.1.6.4.2 In double radial systems, each circuit shall be capable of carrying 120% of the ADMD and
all busbars shall include bus-section switchgear. They shall be arranged to ensure that unscheduled
outage of any component of the circuit would not result in loss of power supply after the faulty
equipment has been disconnected from the system, the only exception to this is the bus-section
switch.
6.1.6.4.3 Double radially fed systems shall generally be operated in parallel with all bus-section
switches closed. Also provision shall be considered for operation in two out of three scheme
system.( non-parallel incomers)
6.1.6.4.4 Where switchgear fault levels are found to be above the values outlined in 6.1.8.3.2
attention shall be given to operating with bus-section breakers open as opposed to purchasing
higher fault level switchgear. Where an open bus-section breaker philosophy is being given
attention, the need to restore rapidly the supplies to drives shall determine whether automatic
closure of bus section circuit breaker(s) is to be employed. Schemes with auto-reclosure are
covered in 6.1.6.7.
6.1.6.5.1 Critical and essential loads may be alternatively supplied by triple identically rated radial
systems. These systems are preferred to double radial systems wherever there is an overall total
cost advantage.
6.1.6.5.2 Each circuit of triple fed radial systems shall be capable of providing 60% of the ADMD
and all busbars shall be split into at least three sections with two bus-section switches. This will
allow for the loss of any one of the three circuits, leaving the two healthy circuits still capable of
providing 120% of the ADMD.
6.1.6.5.3 Triple radial systems shall be provided where the power flow is relatively large. They shall
generally be operated with only two circuits in parallel to reduce switchgear fault levels. The
incoming circuit breaker on the third identically rated feeder shall be left open and automatically
closed in order to restore rapidly full supplies to the load. Triple radial system can also be operated
with two non-parallel circuits closed and one open circuit for reserve.
Note:
For typical electrical distribution network see following typical single line diagrams1,2 and 3.
6.1.6.6.1 Power may be distributed from a primary or central substation to number of subsidiary
load centers by using two primary cable feeders connected in a ring emerging from the source
busbar and controlled by circuit breakers.
6.1.6.6.2 Ring fed systems should normally duplicate only the primary cables to the load substation.
They may however, duplicate the load substation transformers and the low voltage busbar by
providing a low-voltage or secondary bus section breaker.
6.1.6.6.3 Ring fed systems may be operated with the ring closed or with it open at some point.
6.1.6.6.4 Where the ring feed is operated closed, intermediate primary circuit breakers, including
unit feeder protection, shall be provided at all vital or essential load centers on the ring, thereby
ensuring fault clearance of only the unhealthy section of the ring. The whole of the ring circuit shall
25
Feb. 2012
IPS-E-EL-100(1)
be fully rated to be capable of supplying 120% of the ADMD at all substations. Essential or critical
loads may be supplied by ring systems if they are operated closed, their choice shall be based on
the comparative reliability and cost as compared to the duplicate radial systems.
6.1.6.6.5 Ring fed systems which are operated open shall not include circuit breakers on the ring.
Fault clearance shall be achieved at the source substation and in that event power will be lost to all
loads fed between the source and the open point on the ring.
In order that a fully section of the primary ring may be disconnected and repaired without power loss
during the whole of the repair period, the ring shall include isolating means at every load substation.
These ring dependent on availability, cost, and the need for rapid reconnection of load.
Open operated ring fed systems shall be permitted only to supply non-industrial system. Their
choice shall be based on the comparative reliability and cost as compared with single radially fed
systems with a non-automatic standby power supply back-up.
6.1.6.7.1 Automatic transfer schemes shall be given attention where there is a need to obtain a
reliability level consistent with two or more sources of supply. Their use shall be economically
justified when compared against other ways of providing duplication of power sources, and shall be
limited to installations where there is a need to reduce switchgear short circuit levels either for
reasons of cost or non-availability. All schemes shall only include load transfers that never parallel
the preferred and emergency sources. Load transfer schemes may use circuit breakers, or on-load
transfer switches/contactors.
6.1.6.7.2 Load transfer schemes may be applied to either static loads or induction motor loads or
combination of the two. They shall not be used where synchronous motor loads are supplied. The
load transfer shall be arranged so that the residual voltage of induction motors has decayed to less
than 25% of the rated source voltage before the transfer is initiated. The rate of residual voltage
decay shall be calculated and the complete transfer scheme shall be subject to approval by the
client.
6.1.6.7.3 Induction motors which are controlled by circuit breakers, or contactors of the DC
controlled or AC controlled mechanically latched type shall include time delay under voltage
relaying. This relaying shall be set to trip the controller in typically 2 seconds or more on voltage
dips to below 85% of the rated voltage. Transfer schemes associated with switchgear supplying
these types of induction motor controllers shall be designed either to be capable of reaccelerating
the motors within if the transfer taken place within the motor under voltage tripping time, or time
delaying the transfer to be in excess of the motor under voltage tripping time.
6.1.6.7.4 Motors which are controlled by unlatched AC, contactors will inherently disconnect from
the supply on loss of voltage. Where it is required to restore power to these types of motor drives
the auto-transfer schemes shall be supplemented by contactors control schemes which restart
motors individually or in groups after a requisite time delay.
6.1.6.7.5 Load transfer schemes for the startup, run and loading of a standby generator on to a
busbar normally fed from a preferred AC source shall be initiated by time delayed under voltage
relaying set at 85% volts which shall trip the AC source and auto-start up the standby generator
simultaneously. No transfer time delay is required in this case as standby generators take many
seconds to be run up and loaded.
6.1.6.7.6 Power system re-acceleration and re-start studies to determine the most technically
acceptable and cost effective solution shall be carried out for each load transfer scheme considered
and all such studies and their conclusions shall be subject to approval by the client.
26
Feb. 2012
27
IPS-E-EL-100(1)
Feb. 2012
28
IPS-E-EL-100(1)
Feb. 2012
29
IPS-E-EL-100(1)
Feb. 2012
IPS-E-EL-100(1)
6.1.7.1 Power factor improving equipment shall be provided on all installation where energy is
imported from a public utility which applies a tariff penalty associated with low power factor energy
provision.
6.1.7.2 The equipment may be capacitors or synchronous motors depending on economics and
suitability over the range of known operating condition.
6.1.7.3 Where the public utility system is normally in parallel with on site generation, the generating
equipment shall be designed and operated to supply the load KVAR; this will avoid the need for
power factor improving equipment to be installed for the normal parallel operating mode and will
limit its provision to that required for standby (unparalleled operation alone).
6.1.7.4 The amount of power factor equipment provided shall be such as to avoid any possibility of
paying power factor penalties under the worst conceivable plant operating condition.
6.1.7.5 Any power factor improving equipment provided either to reduce system losses (or to raise
voltage levels alone) shall be subject to approval of client.
6.1.7.6 Where synchronous motors are supplied for power factor improvement, they shall include
constant power factor control equipment.
Note:
In order to avoid risks of over voltages or high transient torques, induction motors shall not
be switched as a unit with their power factor improving capacitors, unless the capacitive
current is less than the no load magnetizing current of the associated induction motor.
6.1.7.7 Correction can be applied in the form of individual, group or central compensation to set the
power factor at 0.95. A technical / economical study for the size and location of power factor
correction equipment shall be performed.
6.1.8.1.1 The fault currents that flow as a result of short circuits shall be calculated at each system
voltage for both three phase and phase to earth fault conditions. These calculated currents shall be
used to select suitably rated switchgear and to allow the selection and setting of protective device to
ensure that successful discriminatory fault clearance is achieved.
6.1.8.1.2 The voltage disturbance sustained during the faults and after fault clearance shall also be
ascertained to ensure that transient disturbances do not result in loss of supplies due to low
voltages or overstressing of plant insulation due to high voltages.
6.1.8.1.3 The calculation of fault currents shall include the fault current contribution from generators
and from synchronous and induction motors. Both the AC symmetrical and DC component of fault
currents shall be calculated at all system voltages. Public utility fault in feeds shall be obtained from
the public utility concerned, and they shall exclude any decrement associated with fault duration,
though maximum and minimum values consistent with annual load cycles shall be obtained.
6.1.8.1.4 Positive sequence impedances shall be used for calculating balanced three phase faults.
Positive, negative and zero sequence impedances shall be used for calculating unbalanced faults.
6.1.8.1.5 Three phase balanced fault current calculations shall be carried out to obtain prospective
circuit breaker ratings and shall include:
30
Feb. 2012
IPS-E-EL-100(1)
i) Asymmetric make capacity-expressed in peak amperes and calculated half a cycle after fault
inception. Both AC and DC current decrements shall be included for the half cycle.
ii) Asymmetric break capability-expressed in rms amperes calculated at a time at which the breaker
contacts are expected to part and allowing a maximum of 10 ms for instantaneous type protection
operation. Both AC and DC decrements shall be included for the selected time.
iii) Symmetrical break capability-expressed in rms amperes calculated at a time as defined in item
(ii) above. This assumes nil DC current component and shall allow for AC decrement for the
selected time.
6.1.8.1.6 Earth fault currents may be assumed to be no greater than the maximum phase fault
currents for solidly earthed systems. On systems where the earth fault currents are limited by
neutral earthing equipment, the currents may be assumed to include no decrement and shall be
considered constant whatever the level of bonding between the conductor and the faulted phase.
6.1.8.1.7 Both the AC and DC components of motor fault current contributions shall be calculated
and included in calculation of prospective fault currents. At the instant of fault inspection the AC
peak symmetrical component and the DC component shall be taken to be identical. Both values
shall be taken as the peak direct-on-line starting current, this being dictated by the motor locked
rotor reactance. Both these currents shall be taken to decay exponentially with time using AC and
DC short circuit time constants respectively. The AC time constant shall be determined by using the
ratio of the locked rotor reactance to the standstill rotor resistance. The DC time constant shall be
determined by using the locked rotor reactance to the stator resistance ratio. In the case of faults
not directly on the motor terminals, these time constants shall be modified to take account of
external impedances to the point of fault.
6.1.8.1.8 The calculation of individual fault current contributions shall be carried out for individual
motors of significant rating on the power system. Generally motors with ratings greater than 500 kw
should be treated in this way.
6.1.8.2.1 All switchgear and distribution equipment on the power system shall be capable of
carrying the prospective symmetrical fault currents for specified short time duration of 1 or 3
seconds without deleterious effect. The choice between 1 and 3 second durations shall be dictated
by availability, economics and fault current protection clearing times. Generally 3 second short time
rating is preferred to avoid the necessity for rapid protection. The back-up fault current protection
clearing times shall always be less than the equipment short time current rating.
6.1.8.2.2 The closure of switchgear on to a balanced or unbalanced fault shall not result in shock
load damage to healthy parts of the system as a result of peak asymmetrical make currents
following.
6.1.8.2.3 The selection of circuit breakers shall be dependent on the make and break duty which the
breaker is required to cater for switching devices that may be closed on to fault shall have the
necessary fault making capability.
6.1.8.2.4 Plant protected by fault current limiting HRC type fuses need not be designed to sustain
the prospective shock or thermal loads obtained by calculating system fault currents.
6.1.8.3.1 The power distribution system shall be designed to provide the required security and
quality of supply with prospective fault levels within the capability of commonly available switchgear
acceptable maximum short circuit symmetrical breaking current for various system voltages unless
otherwise specified or approved by company are as follows:
31
Feb. 2012
IPS-E-EL-100(1)
i) Power systems with a voltage in excess of 1000 V shall be so designed that the rms value of the
AC components of the short-circuit breaking current of the circuit breakers is to IEC 60056 and or
shall not exceed 25 KA.
ii) For power systems with a voltage less than 1000 volt, the rms value of the AC component of the
short circuit breaking current of circuit breaker designed shall be IEC 60157 and shall not exceed 50
KA.
If the power system design indicates prospective short circuit requirements exceeding the maximum
circuit breaker rating given above, the following alternatives should be considered:
i) Increase the system reactance, provided this causes no other technical or commercial problem.
ii) Change the operating mode by operating with certain breakers open and provide auto-transfer
facilities to reinstate the supply security and quality levels.
iii) Purchase switchgear and equipment to provide for the higher short circuit levels if these are
available.
iv) Provide fault current limiting devices other than fuses.
v) Carry out any combination of the alternatives listed in items (i) to (iv) above.
6.1.8.3.2 To have an idea of the short time withstand current for switchgear the following are to be
considered:
a) All short circuit studies to be carried out in compliance with requirements of IEC standards.
b) The minimum short time withstand current for busbars shall be according to figures given in
Table 3.
c) The minimum short time withstand current for low voltage busbars with explosion protection type
Exd (EExd) shall be 15 KA.
TABLE 3
RATED VOLTAGE
WITHSTAND CURRENT
20 KA (R.M.S.)
25 KA (R.M.S.)
25 KA (R.M.S.)
25 KA (R.M.S.)
25 KA (R.M.S.)
25 KA (R.M.S.)
50 KA (R.M.S.)
63-66 KV
33 KV
20 KV
* 11 KV
6 KV
* 3.3 KV
0.4 KV
32
Feb. 2012
IPS-E-EL-100(1)
iv) Loss of electronic and control equipment supplies resulting in maloperation. The provision of DC
or no break supplies for vital loads avoids the need to study this.
v) The extent of overvoltage on the system components resulting from fault clearance. This could
cause unacceptable transient recovery voltages occurring for short periods which may have a
destructive effect on electrical insulation.
33
Feb. 2012
IPS-E-EL-100(1)
Master element
Time-Delay starting or closing relay
Checking or interlocking relay
Master contactor
Stopping device
Starting circuit breaker
Reserved for future application
Control power disconnecting device
Reversing device
Unit sequence switch
Multifunction device
Over speed device
Synchronous-Speed device
Under speed device
Speed or frequency matching device
Reserved for future application
Shunting or discharge switch
Accelerating or decelerating device
Starting-To-Running transition contactor
Electrically operated valve
Distance relay
Equalizer circuit breaker
Temperature control device
Volts per hertz relay
Synchronizing or synchronism check device
Apparatus thermal device
Under voltage relay
Flame detector
Isolating contactor
Annunciator relay
Separate excitation device
Directional power relay
Position switch
Master sequence device
Brush-Operating or slip-ring Short-Circuiting device
Polarity or polarizing voltage device
Undercurrent or under power relay
Bearing protective device
Mechanical condition monitor
Field relay
Field circuit breaker
Running circuit breaker
Manual transfer or selector device
Unit sequence starting relay
Atmospheric condition monitor
Reverse-Phase or phase-balance current Relay
Phase-Sequence or phase balance voltage Relay
Incomplete sequence relay
Machine or transformer thermal relay
Instantaneous over current or rate-of rise Relay
34
Feb. 2012
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
IPS-E-EL-100(1)
35
Feb. 2012
IPS-E-EL-100(1)
6.1.12.1.1 Each substation and each on-site generator shall be provided with an alarm annunciation
system. This shall comprise an alarm panel which shall collect together all the alarm conditions
associated with that particular substation or generator. A common alarm shall be derived from each
substation or generator alarm panel for transmission to an emergency control center.
6.1.12.1.2 Each generator alarm panel shall have an alarm window associated with each separate
alarm condition required.
6.1.12.1.3 A window shall be provided on the substation alarm panel for each switchboard circuit
breaker way which has protective relaying.
Where battery chargers are provided for closing and tripping supplies a window shall be provided
on the substation alarm panel for each battery charger.
6.1.12.1.4 Each alarm window of a substation alarm panel shall be operated by the combined alarm
functions of the equipment the window is supposed to represent. For any circuit breaker each
protective relay shall provide a contact into a common alarm circuit which shall operate the
appropriate circuit breaker alarm window in the alarm panel. The alarms associated with a battery
charger shall form a common alarm to operate the appropriate battery charger alarm window in the
alarm panel.
6.1.12.3 Indications
Feb. 2012
IPS-E-EL-100(1)
Feb. 2012
IPS-E-EL-100(1)
To protect equipment
Human habits and practices in the interest of safety are difficult to establish and maintain,
interlocking of equipment either by manufacturer or by the user removes hazards and is
part of safe design and installation. As a general rule the starting point in determining the
interlocking is to consider the past accident history of injury or major material damage, the
of whether the use of an interlocking device to prevent the injury should be considered.
however
a critical
need for
question
It should be remembered that interlocking devices and their application go beyond protecting the
point of operation during the normal work process. They can be used to restrict, access areas
through gate operated controls or through other device such as castle interlock.
Interlocks can initiate visual or audible warnings or stop an operation or malfunction. Key type
interlocks are often employed for access and sequence control.
If a visual warning is desirable flashing red light may be considered. Immediately, there is the
problem of "burned out" light and the system is not "fail safe". Two lights in parallel offer redundancy
and are generally acceptable.
In a series of process operations interlocks can be provided which will afford the necessary safety
for operator and equipment in the event of failure of sequence timers or controllers.
The design and application of interlocks usually affect a critical safety function. It follows that they
must be extensively tested and proved be convenient to use, have fail safe provisions and if
applicable have detailed procedures to verify proper function.
Feb. 2012
IPS-E-EL-100(1)
Permanently piped fire extinguishing Co 2 systems shall also be installed over large oil-insulated
transformers or other oil-insulated apparatus where the value or importance of the apparatus and
nearby equipment justifies this expense. These systems may be arranged to discharge either
manually or automatically. One system employs water spray nozzles connected to a reliable and
strong water supply.
The grouping together of a number of valuable or important cables or wires in trenches, cable
boxes, junction boxes and manholes should be avoided, particularly if they have combustible
insulation. This applies to low, medium, and high-voltage installations, and lead sheathed cables as
well. A failure in one cable or conductor can cause an arc that ignites the insulation on one cable
and fire may destroy the entire group, or the arc can do extensive damage in the event of sustained
arcing. Where it is necessary to group such cables together, they should be protected with a
fireproof covering.
The control circuits in power houses and substations should be arranged so that they will not be
exposed to damage by arcing or fire. When possible, these wires should have asbestos or similar
fire-resistive coverings.
An adequate supply of fire extinguishers should be provided on the premises, particularly in the
vicinity of large quantities of electric apparatus. Extinguishers suitable for use on live electric
apparatus are the vaporizing liquid, carbon dioxide, and dry chemical types.
Where insulating oil or compound is present in large quantities in power houses, substations, and
motor rooms where there are many large motors present.
Note:
For further information on fire protection see the following Standards:
IPS-E-SF-260 Automatic detectors and fire alarm system
IPS-G-SF-126 Hand and wheel type fire extinguishers
IPS-E-SF-160 Co 2 gas fire extinguishing system
6.1.15 Special studies
Feb. 2012
IPS-E-EL-100(1)
system has transient stability if, after a large sudden disturbance it can regain and maintain
synchronous speed: a large sudden disturbance is one caused by faults and switching. In order to
develop the main principles simply it is assumed that the automatic voltage regulations and turbine
governors are too slow to act during the period of the analysis. Dynamic stability refers to the case
of transient stability where the regulations and governors are fast acting and are taken into account
in the analysis.
The stability limit of the system is the maximum (Steady state) power which can be transformed
through the system without loss of stability. The limits depend also on the magnitude, type and
location of the disturbance. The stability factor is the ratio of the stability limit to the actual loadpower transfer it can be shown that all the machines in a power exporting area can be reduced to
an equivalent generator "G" and similarly that all the machines in a power importing area can be
reduced to an equivalent synchronous motor M the distribution or transmission system which
connects these two areas is called interconnection (or tie line) the above two machine system can
be reduced to one machine connected to an infinite busbar a constant voltage and constant
frequency system.
Generally resistance will be neglected, relative to the inductive reactance of the system.
To analyze the transient and dynamic performance of power systems, after large load changes and
fault disturbances. These should be used to check:
a) The ability of the system to stay in synchronism.
b) Induction motor stability after start.
c) Re-acceleration and re-start schemes.
d) The need and effectiveness of under frequency load shedding schemes.
They should also be used to consider the technical merit of:
e) Auto changeover schemes.
f) Parallel or open operation or radial feeders.
g) Operation of fault limiting devices.
h) Insertion of switched reactors or capacitors, etc.
6.2.1 General
This recommendation covers the basic requirements to be considered in design of electrical
systems in non-industrial buildings that comprise all buildings outside the process area, e.g.
workshops, warehouses, canteens, administration and residential buildings, fire stations, training
centers, gatehouses, chemical stores, etc.
Feb. 2012
IPS-E-EL-100(1)
6.2.2.4 Investigate the various types of distribution system and select the system or systems best
suited to the requirements of the switchboard. Make a preliminary one line diagram of the power
system.
6.2.2.5 If power is to be purchased from the utility, obtain such information concerning the supply
system or systems as:
performance data, voltage available, voltage spread, type of systems available, method of system
neutral grounding, and other data such as relaying, metering and the physical requirements of the
equipment. The interrupting rating and momentary ratings of power circuit breakers should be
obtained as well as the present and future short-circuit capabilities of the utility system at the point
of service to the switchboard. Investigate the utilitys power contract to determine if off-peak power
at lower rates available, and any other requirements, such as power factor and demand clauses,
that can influence power cost.
6.2.2.6 A cost analysis may be required of the different voltage levels and various arrangements of
equipment to justify and properly determine the voltage and equipment selected. The study should
be made on the basis of installed cost including all the components in that section of the system.
6.2.2.7 Check the calculations of short-circuit requirements to be sure that all breakers are of the
correct rating. Review the selectivity of various protective devices to assure selectivity during load
or fault disturbances.
6.2.2.8 Calculate the voltage spread and voltage drop at various critical points.
6.2.2.9 Determine the requirements of the various components of the electric distribution system
with special attention given to special operating and equipment conditions.
6.2.2.10 Review all applicable national and local Codes for requirements and restrictions.
6.2.2.11 Check to see that the maximum safety features are incorporated in all parts of the system.
6.2.2.12 Write specification on the equipment and include a one-line diagram as a part of the
specifications.
6.2.2.13 Obtain typical dimensions of equipment and make drawings of the entire system.
6.2.2.14 Determine if the existing equipment is adequate to meet additional load requirements.
Check such ratings as voltage, interrupting capacity, and current-carrying capacity.
6.2.2.15 Determine the best method of connecting the new part of the power system with the
existing system so as to have a minimum outage at minimum cost.
Naturally the above procedure will not automatically design the electric power system in itself; it
must be used with good, sound, basic engineering judgement.
6.2.2.16 Estimate the future load, it is necessary to study building plans and area utilization plans of
the relevant area.
6.2.2.17 A general layout of the buildings should be available before the engineer can begin his
study. This layout usually gives the location and the size of the proposed building or buildings in the
initial particular project. The extent of the available layout gives the engineer an idea of the possible
expansion in the future, and must be considered by the engineer in planning the electric distribution
system.
6.2 2.18 The voltage regulation of system shall not exceed 5%.
Feb. 2012
IPS-E-EL-100(1)
from the high-voltage systems) and its component parts on the other hand transmit energy
economically to numerous main substations and consumer stations. The optimum values for high
voltage systems are the voltage levels of 11 and 20 kV or 33 kV.
6.2.4 Power distribution systems
6.2.4.1 General
a) In locations where there is a significant rising demand for power the selection of voltage levels in
the medium-voltage systems forms a particularly important part of the network planning. Frequently
because of the hitherto development, numerous voltage steps are found and because of several
transformation steps additional costs for investment and losses are incurred. It must, however, be
checked whether these voltage levels are adequate in the future for increasing demand or whether
a higher voltage system should be used. In this aspect it must be assessed whether an existing
intermediate voltage can be omitted partially or even completely or should be revised.
b) The distribution network shall be designed to carry continuously at least 120% of the After
Diversity Maximum Demand (ADMD) associated with peak design production at the maximum
ambient conditions.
c) The selected distribution arrangement shall have a degree of reliability consistent with the type of
load being supplied, and with the power supply design philosophy which provides for coincidental
maintenance and unscheduled outage of the largest component of on site generating plant or
unscheduled outage of the largest feeder component of the power supply equipment.
42
Feb. 2012
IPS-E-EL-100(1)
6.2.5.1 General
For the estimation of loads for large building complexes the physical arrangement (vertical or
horizontal) of the individual consumers and the distribution of load center within the building must be
taken into consideration. Apart from consumer equipments spread across an area, e.g. light fittings
and small appliances, mostly also concentrated loads (lifts, air conditioning equipment, or large
kitchens) must be supplied.
IPS-E-EL-100(1)
Feb. 2012
load peaks of individual system parts are taken into account when determining the power
requirements. It is necessary to take care of Maximum Demand and Diversity.
6.2.5.3 Maximum demand
Maximum demand (often referred to as MD) is the largest current normally carried by circuits,
switches and protective devices; it does not include the levels of current flowing under overload or
short circuit conditions. Assessment of maximum demand is sometimes straightforward. For
example, the maximum demand of a 220 V single-phase 8 kW shower heater can be calculated by
dividing the power (8 kW) by the voltage (220 V) to give a current of 36.3 A. This calculation
assumes a power factor of unity, which is a reasonable assumption for such a purely resistive load.
There are times, however, when assessment of maximum demand is less obvious. For example, if
a ring circuit feeds fifteen 13 A sockets, the maximum demand clearly should not be15 x 13 = 195
A, if only because the circuit protection will not be rated at more than 32 A. Some 13 A sockets may
feed table lamps with 60 W lamps fitted, whilst others may feed 3 kW washing machines; others
again may not be loaded at all. Guidance is given in Table 4.
Lighting circuits pose a special problem when determining MD. Each lamp-holder must be assumed
to carry the current required by the connected load, subject to a minimum loading of 100 W per
lamp holder (a demand of 0.45 A per lamp holder at 220 V). Discharge lamps are particularly
difficult to assess, and current cannot be calculated simply by dividing lamp power by supply
voltage. The reasons for this are:
1) control gear losses result in additional current,
2) the power factor is usually less than unity so current is greater,
3) chokes and other control gear usually distort the waveform of the current so that it contains
harmonics which are additional to the fundamental supply current.
TABLE 4 - CURRENT DEMAND OF OUTLETS
Type of outlet
2 A socket outlet
Other socket outlets
At least 0.5A
Rated current
Connected load, with minimum of 100
W
Lighting point
Shaver outlet, bell transformer or any
equipment of 5 W or less
May be neglected
Household cooker
Switches for circuits feeding discharge lamps shall be rated at twice the current they are required to
carry, unless they have been specially constructed to withstand the severe arcing resulting from the
switching of such inductive and capacitive loads.
When assessing maximum demand, account must be taken of the possible growth in demand
during the life of the installation. Apart from indicating that maximum demand must be assessed,
the Regulations themselves give little help. Suggestions for the assumed current demand of various
types of outlet are shown in Table 4.
Feb. 2012
IPS-E-EL-100(1)
installation requirements; the installation should have two ring circuits to feed the parts of the house
in question.
Most sockets, then, will feed smaller loads such as table lamps, vacuum cleaner, television or audio
machines and so on. The chances of all the sockets being used simultaneously is remote in the
extreme provided that the number of sockets (and ring circuits) installed is large enough. The
condition that only a few sockets will be in use at the same time, and that the loads they feed will be
small is called diversity.
By making allowance for reasonable diversity, the number of circuits and their rating can be
reduced, with a consequent financial saving, but without reducing the effectiveness of the
installation. However, if diversity is over-estimated, the normal current demands will exceed the
ratings of the protective devices, which will disconnect the circuits - not a welcome prospect for the
user of the installation! Overheating may also result from overloading which exceeds the rating of
the protective device, but does not reach its operating current in a reasonably short time. The
Regulations require that circuit design should prevent the occurrence of small overloads of long
duration.
The sensible application of diversity to the design of an installation calls for experience and a
detailed knowledge of the intended use of the installation. Future possible increase in load should
also be taken into account. Diversity relies on a number of factors which can only be properly
assessed in the light of detailed knowledge of the type of installation.
6.2.5.5 Applied diversity
Suggestions of values for the allowances for diversity are given in Table 5.
TABLE 5 - ALLOWANCE FOR DIVERSITY
Note the following abbreviations :
X is the full load current of the largest appliance or circuit
Y is the full load current of the second largest appliance or circuit
Z is the full load current of the remaining appliances or circuits
Type of final circuit
Lighting
* window-type cooler
or air conditioner
Heating and power
Cookers
Motors (but not lifts)
Instantaneous water
heaters
* Thermostatic water
heaters
Standard circuits
Sockets and stationary
equip.
Type of premises
Households
66% total demand
100%
100% up to 10 A + 50%
balance
10 A + 30% balance + 5 A for
socket
100%X + 75%(Y+Z)
100%X + 50%(Y+Z)
100%X + 100%Y + 25%Z
100%
100%
100%
100%X + 40%(Y+Z)
100%X + 40%(Y+Z)
100%X + 50%(Y+Z)
100%X + 75%(Y+Z)
100%X + 50%(Y+Z)
100%X + 75%Y + 40%Z
* Note: Depending on the ambient temperature the allowance for diversity can be considered
by designer.
6.2.6 Power supply in non- residential buildings
6.2.6.1 Supply and distribution considerations
In this section consideration is given to some of the special features and requirements of the
installations in stores, office and leisure premises and other non domestic medium sized
installations.
45
Feb. 2012
IPS-E-EL-100(1)
While single phase 25 A services are adequate for the smaller shop or office unit, premises with a
prospective maximum demand in excess of about 5 kW will be provided with a three phase 230/400
volt supply.
The service cable will be terminated in a cut-out located in agreement with the Electricity Authority
where applicable. This should preferably be in a separate room away from stored materials, work
areas etc., with adequate wall space for the meters, and the consumers switchgear, together with
access space for maintenance and alterations later. The switchboard will consist of a main fuseswitch or circuit breaker adequate in capacity for the installation, a busbar chamber and a number
of circuit switch-fuses or circuit breakers which will in turn supply distribution. It is usually more
economic to locate distribution boards as near as possible to the centers of the electrical load. Thus
a building on three floors would have a distribution board on each floor fed by sub-main cables from
the main switchboard.
Unless three-phase motors or other three-phase equipments are to be installed, the three phases of
the supply should be segregated within the building. The lighting and all power circuits in any one
area should be connected to the same phase so that the risk of 400 volt appearing between two
adjacent outlets or pieces of equipment is minimized. Where, for good practical reasons, this
separation cannot be achieved warning notices are required wherever two items of equipment
connected to different phases are simultaneously accessible.
6.2.6.2 Circuits for power-using equipment
The growth in the use of telecommunications equipment, office machinery and data transmission
equipment means that almost every desk and work station may need access to such facilities. The
trend away from small offices towards large flexible open-plan areas which can be replanned to suit
changing needs makes the provision of such facilities somewhat more difficult. However, the
installation of a network of floor trunking which, if laid in a 2 meter matrix, provides the flexibility the
user will require in the future without the risks which follow the use of long trailing flexes. Floor and
skirting trunking systems are available with two or three compartments so that circuits supplying
socket outlets, telephones and data processing equipment can be carried along the same route. A
wide variety of floor trunking systems are available which are adjustable to match the finished floor
level and carpet or other floor finishes can be applied to them to render them without being
obstructed.
General purpose power circuits in commercial premises will usually be wired on the ring circuit
principle, an adequate number of outlets within a 100 m area being connected to a 32 A fuse or
circuit breaker. However, this practice to connect sockets to a single ring should be exercised with
care. The installation designer must be satisfied that the prospective demand on that circuit will not
exceed the 32 A rating of the circuit protection.
Feb. 2012
IPS-E-EL-100(1)
47
Feb. 2012
IPS-E-EL-100(1)
b) Lighting circuit, first floor (although the total prospective load could be contained by 5 A circuit,
the consequences of a circuit failure plunging the whole dwelling into darkness should persuade the
designer to use two circuits).
*c) Immersion heater(s)(which must be on separate circuits, not connected to a ring main).
d) Kitchen/laundry area socket outlets.
e) Socket outlets ground floor.
f) Socket outlets-first floor. (Where applicable)
*g) Cooker circuit(s).
*Note: In rare cases.
Kitchen
Dining room areas
Living rooms
Each bedroom
Hall
Storage or garage
4-8
2-4
5-8
2-4
2-4
12
16 30
Not only must the number and distribution of socket outlets provide for the appliances the
householder may own, it must also provide for the fact that the positioning of furniture and the
utilization of appliances varies from family to family with time. Flexible cords between sockets and
appliance must always be as short as possible and never longer than 1.5-2 meters, from which it
follows that a dual socket should be available within 1.5 meters of every point in a room at which a
future occupier may wish to utilize an appliance or portable luminaries.
It is not necessary for every socket outlet to be connected into a ring circuit.
Often it is not fully appreciated that an adequate number of socket outlets must be provided if an
installation is to be safe under all conditions. Apart from the convenience of being able to use
appliance in any required position, a reasonable number of socket outlets will eliminate lengths of
trailing flex and other dangers.
The mounting height of the fittings above finished floor level shall be as follows:
- Socket outlet (general)
- Socket outlet (in kitchen)
- Light switch
- Door bell push wall type
30 cm
110 cm
110 cm
110 cm
Feb. 2012
IPS-E-EL-100(1)
sustained elsewhere. For the same reason, lamp holders within 2.5 meters of a bath must be
shrouded or totally enclosed and no fixed wall switches or heaters may be installed within reach of a
person using a bath or shower. Pull cord switches are permissible and are indeed the preferred way
of meeting the switching requirements of a bathroom.
49
Feb. 2012
IPS-E-EL-100(1)
IPS-E-EL-100(1)
Feb. 2012
f) Galvanized steel conduit and fittings for the electrical installation of buildings.
g) i- Minimum cross section for ring circuit of socket is 2.5 mm
h) The size of conduit should be designed such that at most %40 of the cross section is occupied.
7.1.1 Scope
This standard covers the minimum requirements for design of industrial revolving field, cylindrical
pole construction, self exciting, brushless self regulating L.V. and M.V. & 3 phase (4 wires in L.V.)
50HZ 4 pole 1500 R.P.M. at 0.8 lagging P.F. AC generator.
7.1.2.1 General
1) All machines shall be of continuous running duty S1 and continuous Max. rating in addition diesel
driven units shall be capable of running at full. Load for one hour in every twelve hours.
2) The ingress degree of protection for rotating machines shall be IP54. The degree for all other
electrical equipments shall be as followings:
Off shore
outdoor locations
IP55
On shore
outdoor locations
IP54
On/Off shore
Indoor locations
IP42
IP40
3) Rotating machines which are to be located in a hazardous area shall be provided with and
appropriate type of protection.
4) The generator and its auxiliaries shall comply with IPS-M-EL-138 and part 7.1 of this standard
and may be used for based load generation or standby duties based on technical/economical
studies.
5) For generators above 1250 KVA, each generator set shall be provided with its own LV auxiliary
switchboards for the supply and control of all its motor driven auxiliaries. This switchboard should
be treated as an essential services switchboard.
51
Feb. 2012
IPS-E-EL-100(1)
7.1.2.3 Rotor
1) The shaft shall be precisely machined from high quality steel and adequately hardened and shall
carry the rotating field system , DC exciter rotor winding rotating three phases roll wave rectifier
assembly and cooling fan.
2) The complete rotor assembly shall be securely braced and statically and dynamically balanced
on completion. Balance weights shall be of non ductile material such as lead. And rotor design
shall allow for balance weights attaching if necessary.
3) The direction of the air flow shall be such that the discharged air does not pass over the driver.
The ventilation system shall include air intake filter.
4) The rotor shall include excitation system independent of external power supply.
5) Winding conductor of the rotor shall be copper with mica paper, glass cloth and epoxy resin
insulations. Impregnation and curing shall be either by the resin method or vacuum. And shall be
baked and treated to provide a hard setting , oil and moisture resistant anti-tracking finish suitable
for a dusty saline and tropical environ meant.
6) The direction of rotation shall be clearly and permanently indicated by means of an arrow on the
external surface of the frame at the N.D.E. painted or adhesive tape methods of indication are not
acceptable.
Circuits shall be
52
Feb. 2012
IPS-E-EL-100(1)
low voltage levels rotor current limitation is necessary to prevent the undesirable disconnection of
the generator due to overload of the rotorcraft current.
6) The A.V.R. shall be of solid state design and including protection against over voltage and be
provided with means to adjust the set point of the main generator output voltage over a range of
+10% nominal voltage rating at full load.
7) The A.V.R shall have an adjustable reactive current droop characteristic and be suitable for
reactive load sharing known as quadrate current compensation (Q.C.C.) providing the ability for
generators in parallel to share reactive currents in equal of proportional amounts.
8) The A.V.R shall allow 100% voltage to be generated at 80% of speed under all conditions of
operation.
9) Over fluxing control shall be provided, this shall not reduce excitation until frequency is less than
75% of rated frequency.
10) Max. excitation limitation and max. Volts/hertz facilities shall be included within the A.V.R. unit.
11) Temp. stability of the voltage regulation shall be better than 0.5% for temperature between max.
and min. of ambient temperatures.
12) The A.V.R shall regulate the voltage within 2.5% of the set point between No-Load and full-load
and for all speed droop variations. The regulation capability of the AC generation and A.V.R system
under transient conditions shall be arranged such that following any transient disturbance, voltage
shall be restored to 2.5% within 10 seconds, and voltage will be restored to 97% of nominal voltage
within 1 second.
Feb. 2012
IPS-E-EL-100(1)
ends of the shaft is less than 150mv-rms. The insulation method shall be permanent and non-deter
10 rating. This shall include any lube oil supply and drain connections to the bearing housing.
7) Machines shall be tested with their service bearings fitted. If transit bearings or other devices are
employed for transport purposes, clear labels starting this shall be affixed to the machine.
8) Bearing housings shall have provision for mounting two shaft proximity type vibration probes at
each radial bearing with the probes mounted 90 + 10 circumferentially apart and shall be furnished
with standard breather.
9) All bearings shall provide shaft access for vibration measurement through or adjacent to the
bearings.
10) The critical speeds of the rotor shall not be within 20% of any speed in the operating range nor
within 20% of two times operating speed range.
7.1.2.9 Earthing
1) The neutral point of the alternator in the connecting terminal box shall be grounded solidly or
through resistor.
2) Generator frame and skid shall have grounding bolts to be grounded.
Connections to the bearing housings of generators having insulated bearing pedestals shall ensure
that no connection, including that of the bearing sheath, provides a by pass around the insulation.
2
The generator shall be provided with at least two main earthing points to which 70mm copper cable
strip will be made. The location of the earth points shall be in an accessible place to enable
external connections to be made and subsequently inspected or tested. Any equipment which is
part of main generator skid shall be effectively bonded to the base frame. Any electrical equipment
which will be separately mounted from the base frame shall have provided, means for earth bonding
to the main frame.
Earth bonding by holding down bolts will be generally acceptable. However particular attention
should be made to the arrangements for bonding that equipment which may rest on insulating antivibration mountings. For these applications a supplementary earth bond may be necessary,
particularly if the item of equipment has an electrical supply.
54
Feb. 2012
IPS-E-EL-100(1)
Feb. 2012
IPS-E-EL-100(1)
7) The drivers of all machines shall be fitted with speed governing equipment.
Where the generator is to operate in isolation the governor shall provide isochronal oust control.
8) Where the generator is to operate in parallel with other generators then adjustable droop control
shall be provided.
9) Facilities shall provide to repeat informations and alarms to a remote control room, each alarm
signal shall be wired to output terminals in the unit control panel. A common remote alarm facility
shall also be arranged.
10) The following are accessories which may be selected depending on rating, voltage and
application of specific cases:
a) Power factor meter.
b) KVRH meter.
c) KWH meter.
d) Generator voltage.
e) Generator current.
f) Frequency meter
g) Hours run counter
h) Under/Over frequency protection.
i) Short circuit sustaining protection.
j) Ground fault protection.
k) Surge protection.
l) Differential protection.
m) Lightning arrested.
n) Synchronizing check recap.
o) KW Indicator.
p) Aver/Manual excitation null balance meter.
q) Running and incoming volt meters.
r) Running and incoming frequency meters.
s) Exciter field volt meter.
t) Exciter field ammeter.
u) Synchronizing lamps.
v) Alarm indications.
w) Synchrony scope
11) Electrical instruments shall be of the flush mounted, industrial grade, enclosed in dust and damp
proof casing, non projecting dial with non-glare, non-reflecting windows.
12) All abnormal conditions which would ultimately lead to a shutdown shall have warning pre
alarms where possible the interval between set points shall be sufficient for corrective action to be
taken.
13) In the event of an equipment trip a "first out" facility shall be provided to identify the original fault.
14) Repeat volt free contacts shall be provided for remote indication of each alarm and shutdown
condition wired to panel outgoing terminal.
15) Facilities shall be provided to permit remote acceptance of alarms.
16) For analogue additional remote signals 4-20mA transducers shall be used.
56
Feb. 2012
IPS-E-EL-100(1)
17) In the event of an automatic shutdown due to low engine lube oil pressure, over speed or high
jacket water temperature attempts to restart shall be automatically inhibited until the trip has been
locally reset.
18) All shutdowns except over speed, shall be via fuel cutoff, over speed shutdown shall be by both
fuel shutdown and air intake close up.
19) The package control system shall be fitted with a local/Remote control switch and a
manual/Auto standby/Off control switch, both switches shall be mounted on the control panel.
20) Local start and stop shall be by push buttons on the unit control panel, the local stop signals
shall be operative in both the local and remote modes of control. Terminals shall be provided for
multiple remote start and stop signals.
21) Facilities shall be provided for remote emergency shutdown of the set from the emergency
shutdown system.
22) With the local/Remote switch in the "Remote" position, remote control shall only be effective
with the remotely located mallow switch in the (Auto) position under these circumstances the
remote control shall enable a manual over ride start is the auto-start has failed a manual stop shall
also be provided at the remote control point. The auto start shall be initiated by a maintained close
to start contact.
23) In the "manual" or "auto standby" modes the generator shall automatically run up to the selected
speed upon start initiation.
24) As specific requirements facilities shall be provided for data logger and ground fault resistors.
7.1.2.12 Vibration
1) Bearing housings for hydro dynamic radial bearings shall have provision for the fitting of noncontacting dual proximity type vibration probes or accelerometers (rms velocity readings).
2) In a manner similar to temperature monitoring a complete package vibration monitoring system
shall be required.
3) The vibration amplitude of machines fitted with non-contacting vibration monitoring equipment
shall not exceed peak to peak level (unfiltered) of 63 micrometers including mechanical and
electrical run out. Total run out shall not exceed 13 micro meters.
4) The vibration level for machines fitted with flexible rotors passing through the first critical speed
shall be within the following limits:
a) Machines fitted with hydrodynamic bearing:
The peak to peak amplitude shall be less than 75% of the nominal bearing clear acne.
b) Machines fitted with rolling element bearings.
Less than three times the limits given below
The vibration limits for all machines not flitted with non contact vibration monitoring equipment shall
meet the requirements of bus 1999 part149 as follows:
For a shaft height less than 400mm table1 quality R.
For a shaft height 400mm or greater table2 column 1.
7.1.2.13 Noise
1) The Max. noise level at 1m away from the machine shall not exceed 85 db(A) when operating as
an alternator at rated voltage, rated speed at no load.
2) The noise emissions details of the machine shall be provided in octave bands. Also any narrow
band noise details that are noticeable to the ear shall be provided together in octave band or in
bands in which it occur.
57
Feb. 2012
IPS-E-EL-100(1)
3) Where the noise limiting requirements can not be met without the provision of noise reducing
features the levels with and without these features shall be stated.
Details of any noise reduction features shall be provided.
7.1.2.15 Enclosure
1) The enclosure shall be designed as an integral part of the package.
2) Outdoor installations would normally be expected to be supplied with an enclosure in order to be
weather proof. Indoor locations may be specified without enclosures and may involve separate
mounting of the cooler radiator, master fuel tank and exhaust system.
3) For offshore installations the enclosure walls shall have a minimum fire rating of A60 and shall
comply with local regulations.
4) The enclosure shall be designed to allow adequate access for routine maintenance and
operation and shall be equipped with as minimum lighting/ lighting points, over head lifting beams
and drainage.
7.1.2.16 Ventilation
1) Where diesel engine powered emergency generator package have an integral enclosure, a
ventilation system shall be provided to maintain the temperature of the enclosure at an acceptable
level during operation.
2) The ventilation fan shall be driven off the engine either directly or by the use of hydraulic
transmission, alternatively an electric motor drive may be used with power derived direct from the
generator via a local starter.
58
Feb. 2012
IPS-E-EL-100(1)
3) Where union closed diesel engine powered emergency generators are installed in dedicated
rooms any requirement for connections (e.g. power and control) to ventilation system will be
specified.
7.1.3.1 Performance
1) The engine continuous net brake power, fuel consumption and lubricating oil consumption and
overload power shall be declared under ISO conditions. It is to be recognized that the unit should be
capable of the emergency duty as required at the site max. ambient conditions.
2) The engines continuous net brake power at all operating conditions shall be sufficient to enable
the generator to produce power as specified in the name plate rating.
Feb. 2012
IPS-E-EL-100(1)
60
Feb. 2012
IPS-E-EL-100(1)
3) Where a gravity fed fuel systems are employed a locally operated manual valve shall be installed
in the fuel line to the engine at the tank outlet. If the tank is located within the room / enclosure this
valve shall also be operable from outside the room / enclosure.
4) The tank shall be provided with a man way opening , and connections for filling swan neck vent
flow, return, drain, over flow and instrumentation e.g. level gauge and high/low level alarms.
5) A thermo statically controlled tank heating system shall be provided if ambient conditions could
result in the viscosity of the fuel.
6) The fuel suction filters shall be of the duplex type with replaceable elements and a changeover
facility to permit removal and replacement of dither element without need for engine shutdown.
Filter mesh size shall be specified.
7) Provision shall be made for priming and bleeding the fuel injection system.
8) For unmanned installations high pressure fuel lines between remote fuel pumps and injectors
shall be double skinned, seamless tubing with fuel leak monitoring and alarm. On manned
installations the fuel lines may be as above or heavy seamless tubing.
9) Flame resistant flexible hoses shall be provided within the fuel supply and return piping systems
between the engine and off skid pipe work at the EDGE of the engine skid. There shall be no shut
off valve in the return line to the tank.
If two or more
2) The discharge location from the exhaust system will be specified. The extent of the vendors
supply will be identified.
3) Hot exhaust system piping within the confines of the package and constituting a danger to
0
personnel shall be insulated or protected to limit surface temperature to 65 C.
4) Where exhaust systems can be exposed to hazardous area conditions, they shall be water
cooled to limit surface temperature. The temperature and the length of the system requiring cooling
will be specified.
7.1.3.8 Couplings
1) It shall be possible to remove couplings without the need to move the engine or driven
equipment.
61
Feb. 2012
IPS-E-EL-100(1)
2) All flexible couplings incorporating a spacer piece shall be of a design in which the spacer piece
is positively constrained from flying out in the event of failure of the flexible elements.
3) The max. coupling torque shall be limited to a max. of 80% of the coupling rating.
7.2.1 General
Low voltage switchgear and control gear constitute the link between on the one hand the means of
generation (generators) transmission (cables) and, voltage transformation (transformers of electric
power and on the other hand the consuming equipment such as motors, lighting, heating and air
conditioning plant.)
The selection criteria grouped in five categories
7.2.1.1 Current
- Rated current of busbar
- Rated current of in feeds and bus section
- Rated current of outgoing feeders
62
Feb. 2012
IPS-E-EL-100(1)
7.2.1.4 Application
- Main switch board
- Industrial distribution board
- Non-industrial distribution board
- Motor control center
- Power factor correction equipment
- Control board
7.2.2.1 The equipment shall be a factory built assembly (F.B.A) from manufacturer capable of
providing an acceptable technical and commercial back- up service.
Feb. 2012
IPS-E-EL-100(1)
Feb. 2012
IPS-E-EL-100(1)
7.2.4.1 Busbars
7.2.4.1.1 Switchgear Installations for normal service conditions should be preferably equipped with
single busbar systems.
These are clean in their arrangement simple to operate, Require relatively little space and are low in
initial cost and operating expenses see Fig. 4.
65
Feb. 2012
IPS-E-EL-100(1)
66
Feb. 2012
IPS-E-EL-100(1)
7.2.4.2 For all of the above mentioned switchgear and controlgears the following rating terms may
be used:
Rated Frequency
The standard values of the rated frequency for MV/HV pole switchgear and controlgear are 50 Hz.
Note 1:
Out door switchgear shall only be considered for voltage exceeding 36 KV.
Note 2:
For existing extension or where the incoming circuit is one feeder and one transformer,
33KV/20kV and 11 KV may be used as outdoor switchgear.
67
Feb. 2012
IPS-E-EL-100(1)
7.2.4.4.1 Circuit breakers shall be controlled from remote control panel in a separate room.
7.2.4.4.2 Control of a motor starter shall be from a control station adjacent to the motor or control
panel in allocation remote from both the motor and starter equipment (ex. Control room)
7.2.4.4.3 stop control for motor starters located beside The shall form part of primary stop control
circuit and the use of interposing relays shall be avoided, if an interposing relay is unavoidable then
the circuits shall be fail safe.
7.2.4.4.4 For motor contactor unit directly controlled via control circuits over 600 meter long, the use
of interposing relay and/or 110 v.DC control shall be considered.
7.2.4.5.1 Access
Adequate clearance shall be provided around the switchgear for maintenance, operation, access
and anticipated extensions.
7.2.4.5.2 A minimum clearance of 2.5 meter in front and 1 meter in rear of switchboards shall be
considered. the appropriate distance in both end of switchboards shall be considered for future
extension. The minimum clearance for both ends shall be 2.5 meter to the wall. The equipment
manufacturer shall always be consulted for recommended clearances.
7.2.5 Substations
7.2.5.1 General
Substations shall contain all the equipment required for the safe and secure distribution of electricity
to a predetermined area, plant or region, such as H.V./M.V. and L.V. switchgear and control gear
installations, transformers and the pertaining auxiliary facilities.
The substation shall be located in non-hazardous areas and preferably near the center of the load
they are required to supply.
The location of the substations shall also be such that interference between H.V./M.V./L.V. cables,
instrument cables and other services, e.g. pipelines is minimized.
In exceptional cases e.g. in view of restricted space on offshore platforms, electrical substations
may be located in hazardous areas classified as zone 2, subject to approval by the principle. The
following requirements shall apply:
The interior of the building shall be pressurized in accordance with IEC 60079-13;
An over pressure of at least 50Pa (0.5 bar) shall be maintained, using a duplicate fan system with a
suitable dry element dust filtering system to ensure a supply of clean air, each fan being capable of
supplying the required pressure;
The fan system shall be suitable for a Zone 1 area and shall be supplied from tow independent
sources of electricity supply;
Both fans shall normally be in operation and shall have individual alarms to indicate failure in a
manned control center;
Feb. 2012
IPS-E-EL-100(1)
Open terminal outdoor substations should be sited at least 100 m from process unit battery limits. If
this separation is not feasible, switchgear shall be and installed in an indoor substation.
Note 1:
Outdoor switchgear shall be treated as sparking equipment, and the minimum distance from
the process unit should be determined from the analysis of gas cloud behavior by the
process engineering department.
The installation of all components shall be coordinated in accordance with IEC 60071.
The installation class and creepage distance of the isolators shall be selected in accordance with
the expected pollution rate and the likelihood of reduced possibility of maintenance. If not further
specified, a minimum creepage distance of 40 mm/KV shall be applied for insulators.
Note 2:
For further guidance refer to IEC 60815, and if necessary, consult with the local public utility.
Busbars and the connections to the equipments shall be made of copper aluminum tubes or
aluminum conductors. Bi-metallic connectors shall be used at joints between dissimilar metals.
Equipment support structures and line portals shall be of hot-dip galvanized steel and shall have
integral climbing facilities for repair and cleaning purposes.
A 2.4 m high, un climbable perimeter fence with (pad) lockable access gates shall be provided, but
no internal fencing, e.g. around transformers, is required, provided the ground and safety the
clearances stated in the above mentioned standards are satisfied.
Control and auxiliary cables shall be installed in hard covered, pre-cast concrete cable trenches the
top of which shall be surrounding ground level. The trenches shall be well drained and not stand
filled.
Note 3:
All supporting structures and equipments shall be earthed to the substation earthing
system.
The perimeter fence shall be earthed at regular intervals (maximum 30 m) by means of earth
electrodes directly connected to it.
Note 4:
The perimeter fence shall not be connected to the substation earth so as to avoid the danger
of touch voltage.
protection against lightning strikes shall be provided by means of over head earth wires
The substation equipments shall be protected against lightning and switching over voltages by
lightning arrestors.
Control, protection and auxiliary power supply equipments associated with outdoor switchgear shall
be installed in a building which shall comply with the relevant requirements of (7.3). This substation
building, if suitably sub-divided, could also accommodate other switchgear and controlgear at lower
voltages.
69
Feb. 2012
IPS-E-EL-100(1)
Note:
The separate room shall be considered for MV. Capacitor bank.
70
Feb. 2012
IPS-E-EL-100(1)
The battery room shall be designed to contain the battery bank only. The size of the room shall be
adequate to allow access to at least three sides of each battery bank for maintenance purposes.
The doors shall be lockable and fitted with an internal panic bolt. The ceiling shall be flat. A water
tap, eye wash basin, sink and drain shall be installed in the room.
All non current carrying metalwork in the room, e.g. cable tray, battery stands etc. shall be bonded
to earth. All metalwork shall be protected against corrosion.
Heating, ventilation and/or air condition of battery rooms shall be included in the HVAC system of
the building.
Exhaust fan motors shall have type of protection 'e' or 'd', gas group C, exhausting to the outside of
the battery room.
The luminaries and convenience outlets shall be suitable for Zone 1, gas group C.
Flexible cables to the batteries may be installed provided they are the EPR or H07 RN-F type or
equivalent.
Smoke and hydrogen detectors shall be considered for battery rooms with alarm indication in
control room.
7.2.6.1 Switchgear room floor level shall be at least 1 meter above surrounding ground level.
Feb. 2012
IPS-E-EL-100(1)
Package substations shall be supplied as complete factory assembled and tested transportable
units.
The HV switchgear, transformer and LV switchgear shall be located in separate compartments,
each accessible from the outside by lockable doors. Sufficient space shall be available in the
compartments to terminate cables and operate the switchgear safely. The switchgear
compartments shall be at least protected to IP 55. The transformer compartment of oil filled
transformer shall be equipped with a leak-proof oil contaminant area.
Note:
Dry type transformers may be mounted on site with the LV switchgear or in a separately
fenced enclosure in the LV switchgear compartment.
Heating, ventilation and/or air-conditioning provisions shall be made in the substation as appropriate
and as necessary to ensure that specified operating temperature limits of the installed equipment
are not exceeded.
Each compartment shall be provided with luminaries and convenience outlets of the weatherproof
industrial type.
7.3 Transformers
7.3.1 General
7.3.1.1 Scope
Note 1:
Dry type transformers shall comply with the requirements of IPS-M-EL-151(1).
Note 2:
Oil immersed transformers shall comply with the requirements of IPS-M-EL-152(1).
72
IPS-E-EL-100(1)
Feb. 2012
7.3.1.3.1 Transformers are identified according to cooling method employed . Letter symbols used
in conjunction with cooling are given in Table 7.
SYMBOL
O
L
G
W
A
KIND OF CIRCULATION
SYMBOL
Natural
Forced (oil not directed)
Forced ( directed oil)
N
F
D
7.3.1.3.2 Transformers shall be identified by four symbols for each cooling method for which a
rating is assigned by the manufacturer .
7.3.1.3.3 Dry-type transformers without protective enclosures are identified by two symbols only for
the cooling medium that is in contact with the windings or the surface coating of windings with an
overall coating ( e.g. epoxy resin) .
7.3.1.3.4 The order in which the symbols are used shall be as given in Table 8. Oblique strokes
shall be used to separate the group symbols for different cooling methods .
2ND LETTER
3RD LETTER
4TH LETTER
Kind of cooling
medium
Kind of cooling
medium
Kind of circulation
Kind of circulation
7.3.1.3.5 Examples:
AN: for dry type transformer without a protective enclosure or with a ventilated enclosure and with
natural air cooling.
73
IPS-E-EL-100(1)
Feb. 2012
ANAN: for dry type transformer in a non-ventilated protective enclosure natural air cooling inside
and outside the enclosure.
ONAN/ONAF, ONAN/OFAF: for oil immersed transformers in which the alternatives of natural or
forced cooling with non-directed oil flow are possible .
ODAF: for an oil-immersed transformer with forced-directed oil circulation and forced air circulation.
7.3.1.4.1 Rated power: Transformers shall be continuously rated . The ratings shall be determined
from the series given in table II of IEC60076-1 . Preferred values of rated power for three phase
transformers are:
5 / 6.3 / 8 / 10 / 12.5 / 16 / 20 / 25 / 31.5 / 40 / 50 / 63 / 80 / 100 / 125 / 160 / 200 / 250 / 315 / 400 /
500 / 630 / 800 / 1000 KVA and etc .
7.3.1.4.2 Rated voltage: The rated voltages of transformer windings shall be selected from IEC
60038 . The followings are most commonly used voltages in oil industries:
230 v / 400 v / 3.3 kV / 6 or 6.6 kV / 10 or 11 kV / 20 kV / 33 kV / 63 or 66 kV .
7.3.1.4.3 Rated ratios : The rated ratio is defined as ratio of primary to secondary voltage at full
load & 0.85 lagging power factor with principal tapping. the most common voltage ratios are in
Table 9.
TABLE 9 - COMMON RATED RATIOS
PRIMARY VOLTAGE
(KV)
3.3 / 6 or 6.6 / 10 or 11 / 20 / 33
10 or 11 / 20 / 33 / 63 or 66
10 or 11 / 20 / 33 / 63 or 66
20 / 33 / 63 or 66
33 / 63 or 66
63 or 66
SECONDARY VOLTAGE
(KV)
0.4
3.3
6 or 6.6
10 or 11
20
33
7.3.1.4.4 Rated impedance voltage: Unless a specific transformer impedance voltage is required,
the values shall be chosen from typical values given in Table I of IEC60076-5 (table 10). The
impedance voltage shall be that applicable to principal tapping and rated current. Typical values of
impedance voltage for transformers with two windings are as follows:
IMPEDANCE VOLTAGE
(%)
4.0
5.0
6.25
7.15
8.35
10.0
7.3.1.4.5 Rated short circuit capacity: The short circuit withstands ability of transformers and
reactors will be in accordance with IEC 60076-5. If the short circuit apparent power of the system is
greater than those given in Table II of IEC 60076-5 (table 11), the manufacturer shall be informed.
Short circuit apparent powers of the systems which may be used in absence of specification are as
follows:
74
IPS-E-EL-100(1)
Feb. 2012
3.3
7.2 / 12 / 17.5 / 24
36
52 / 72.5
150
500
1500
2500
Note:
A reserve of power for the expected yearly rate of increase of power (KVA) must be
considered if required.
A schedule based on the plant design capacity of the installed electrical loads shall be prepared. In
this electrical load list , loads are determined as continuous, intermittent and standby.
7.3.2.1.1 First step is to find peak load value in kW's & KVAR 's .
If :
A = Sum of all continuously operating loads.
B = Sum of all intermittent loads.
C = Sum of all standby loads.
Then :
Maximum normal running load = X A +Y B
Peak load = X A + Max {Y B, largest intermittent load} + Max {Z C, largest standby load}
X, Y, Z are diversity factors determined by principal.
The following default values for X, Y, Z could be used for initial load assessments or if diversity
factors have not been finalized.
X = 100%
Y = 75%
Z = 10%
7.3.2.1.2 After calculating peak load value, maximum load KVA is determined by using total power
factor (or using total KVAR value).
Peak load (kW)
Maximum load ( KVA ) =
Total power factor
or
Maximum load ( KVA ) = peak load ( kw ) + peak load ( KVAR )
2
7.3.2.1.3 The required KVA is determined by multiplying maximum load KVA by 120% for
possibility of future expansion . Since the value of required KVA is not normally the same as a
standard value , the transformer KVA will be the nearest standard transformer rating above the
required KVA .
7.3.2.1.4 The required transformer KVA may be increased by load flow & motor starting studies
due to voltage drop calculations .For the starting study , the greatest electric motor should be
considered with other normal loads connected .
75
Feb. 2012
IPS-E-EL-100(1)
Note 1:
The percentage of total intermittent load that contribute to the normal running load will
depend on plant operation .
Note 2:
The second term in peak load formula is the biggest value between Y B
individual intermittent load.
and largest
Note 3:
The third term in peak load formula is the biggest value between Z C and largest individual
standby load.
Note 4:
Transformers shall be rated for maximum ambient temperature.
Note 5:
Maximum rating of transformers feeding plant substations should be such that the rated
current of their secondary winding does not exceed 2000 A when feeding an MV
switchboard, or 2500 A when feeding an LV switchboard . This results in the following
maximum ratings:
1600 KVA if feeding LV switchboard.
10 MVA if feeding MV 3.3 KV switchboard.
20 MVA if feeding MV 6 or 6.6 KV switchboard.
40 MVA if feeding MV 10 or 11 KV switchboard.
Note 6:
Higher ratings should be considered only if a significant cost saving can be proven.
Note:
Using of unit transformers shall be decided based on economical considerations.
76
Feb. 2012
IPS-E-EL-100(1)
i) The unit transformer shall be capable of withstanding full voltage motor starting current for 15
seconds unless otherwise specified.
ii) The voltage drop at the motor terminals at startup shall not exceed 15%.
7.3.3.2.1 Oil immersed transformers: oil immersed transformers or reactors shall either be of the
sealed tank type or conservator type. The advantages of sealed tank design are their almost
maintenance-free operation and with certain designs there is a space saving because of the
absence of external pipe work.
Transformers for outdoor use and rated up to and including 2500 KVA shall be of the oil-filled
hermetically sealed type .Transformers above 2500 KVA should be conservator type .
Note: Using of sealed type transformers above 2500 KVA shall be decided by company
representative.
7.3.3.2.2 Dry-type transformers: In locations where fire risk must be minimized e.g. in public and
residential buildings, on offshore platforms etc., dry-type transformer having cast resin encapsulated
windings can be used. Cast resin encapsulated transformers are recognized as almost notcombustible, self-extinguishing and electrically unaffected by high humidity. They shall be used for
ratings up to and including 1250 KVA with secondary voltage 400/230 v.
7.3.3.4.1 Off-circuit tap changer: Unless otherwise specified all transformers should have an offcircuit tap changer with a principal and four additional tappings. Tapping range shall be 5% in four
equal steps of 2.5% of the nominal primary voltage.
7.3.3.4.2 On-load tap changer: Main incoming supply transformers receiving power from public
utility and rated 5 MVA and above with primary rated voltages equal or above 36 kV are usually
fitted with on-load tap changers. There is no need for on-load tap changer if voltage variation range
is less than 5%. Transformers at the end of long transmission lines (normally longer than 50 km)
may need to have on-load tap changer. Maximum voltage variation at transformer location shall be
calculated in project specification stage (engineering studies).
77
Feb. 2012
IPS-E-EL-100(1)
7.3.3.4.3 The use of on-load tap changers fitted to site distribution transformers shall be permitted
only if it is anticipated that plant non-transient voltage variations of greater than 6% could occur as
a result of normal process operations and also that there would be process disruption if a
transformer was switched out of circuit to alter the tapping out.
7.3.3.4.4 Tapping range and tap steps : On-load tap changers should have a minimum tapping
range of 7.5% in 13 taps with 12 tap steps of 1.25%, unless voltage variations dictate a wider
range and more steps. Generally tapping range shall be at least 120% of anticipated/calculated
voltage variation.
Note 1:
On-load tap changers shall be of automatic voltage control type. They shall also be manually
operated either at the transformer or from a remote control location in substation or control
room.
Note 2:
The high speed resistance type of on-load tap changer is preferred.
Note 3:
Where on-load tap changers are required , they shall comply with IEC60214 & IEC60542.
Note 4:
Tapping range and tap steps are normally determined by transformer manufacturer
according to voltage variation, rated power and rated system voltage.
Note 5:
On-load tap changers are not normally required on generator step-up transformers.
Note 6:
Reactors shall not be fitted with on-load tap changer and earthing transformers shall not be
fitted with any type of tap changer .
78
Feb. 2012
IPS-E-EL-100(1)
iii) A unit which usually runs as a base load has occasional periods of high load demand that would
be outside the normal cyclic loading capabilities of the transformer or reactor.
Note 1:
Any requirement for forced cooling, and whether this is to be fitted at the time of initial
purchase or to be added at a later date, shall be as specified in data sheet .
Note 2:
If provision for forced cooling is specified, the manufacturer shall allow for this in the
transformer design.
7.3.4.1.1 Effect of altitude on transformer temperature rise: The effect of the decreased air
density due to high altitude is to increase the temperature rise of transformers which are dependant
upon air for dissipation of heat losses. For a naturally cooled transformer ( . . AN ), the limit of
C
average winding temperature rise shall be reduced by 1 for every interval of 400 m by which the
installations altitude exceed 1000 m. For a forced cooled transformer ( . . AF ) , the reduction shall
C
be 1 for every 250 m .
7.3.4.1.2 Rated operation at high altitude: Transformers can be operated at rated KVA at
altitudes greater than 1000 m without exceeding temperature limits provided the average
temperature of cooling air does not exceed the value of Table 12 for the respective altitude .
Note:
It is recommended that the average temperature of cooling air be calculated by averaging 24
consecutive hourly readings . When the outdoor air is the cooling medium , the average of
maximum and minimum daily temperatures may be used .
79
IPS-E-EL-100(1)
Feb. 2012
1000 m
2000 m
3000 m
4000 m
Oil-immersed self-cooled
Oil-immersed forced-air-cooled
30
30
28
26
25
23
23
20
30
30
30
27
26
22
24
22
15
21
18
7
30
30
30
24
22
15
19
14
0
14
6
-15
Dry-type self-cooled
1 ) 55 C rise
2 ) 80 C rise
3 ) 150 C rise
Dry-type forced-air-cooled
1 ) 55 C rise
2 ) 80 C rise
3 ) 150 C rise
7.3.4.1.3 Operation at less than rated KVA at high altitude: Transformers can be operated at
altitudes greater than 1000 m without exceeding temperature limits provided the load to be carried
is reduced to below ratings by the percentages given in Table 13 for each 100 meters that the
altitude is above 1000 m.
CORRECTION FACTOR
( PERCENT )
Oil-immersed self-cooled
0.4
Oil-immersed forced-air-cooled
0.5
Dry-type self-cooled
0.3
Dry-type forced-air-cooled
0.5
80
IPS-E-EL-100(1)
Feb. 2012
Note:
Transformers built according to different design concepts are likely to present different
impedance level and different variation trends across the tapping range.
U ka
R
S = S ra +
R
S rb
U kb
R
Where
S : Total power ( KVA )
S ra : Rated power of transformer with lower impedance voltage (U ka )
S rb : Rated power of transformer with higher impedance voltage ( U kb )
R
7.3.4.3.1 Earthing transformers are three phase transformers (or reactors ) used to provide an
artificial loading neutral for earthing of a system at a point where it is otherwise un-earthed.
Connecting to earth can be done directly or through an earthing resistor.
Earthing transformers are usually connected either in zigzag or star/delta. A delta connected
winding may be of the open type to adjust the zero- sequence impedance.
Note :
Earthing transformers may be specified with a low voltage winding having a continuous
rated power for substation auxiliary supply .
Ratings :
7.3.4.3.2 Rated voltage of the main winding: Unless operating conditions justify the selection of a
higher value, the rated voltage shall be equal to the line voltage of the associated system .
7.3.4.3.3 Rated neutral current: The rated neutral current shall be specified to be not less than the
highest value of continuous current under service conditions , for example phase unbalance.
7.3.4.3.4 Rated zero-sequence impedance: The value of zero-sequence impedance may either
be let open in the specification or be specified. (for example when the earthing transformer itself is
used to limit the earth fault current)
81
Feb. 2012
IPS-E-EL-100(1)
Note:
Earthing transformers shall be designed to withstand without damage the thermal and
dynamic effects of the rated current.
7.3.4.4 Reactors
According to IEC60289, there are approximately eight different types of reactors. The most
important type that may be used in NIOC fields is as follows:
7.3.4.4.1 Current limiting reactors: The reactors intended for limiting the short-time current under
system fault conditions or starting of AC motors. During normal operation a continuous current flows
through the current limiting reactor.
Ratings:
7.3.4.4.2 Rated continuous current: Unless otherwise specified, the rated continuous current is a
symmetrical three- phase current. Preferred values of the rated continuous current shall correspond
to the series R10 in ISO standard 3.
7.3.4.4.3 Rated short-time current: The rated short-time current shall be specified to be not less
than the highest value of current under recognized fault or starting conditions.
7.3.4.4.4 Rated short-time current duration: Unless otherwise specified, the rated short-time
current duration shall be 2 seconds for current-limiting reactors.
7.3.4.4.5 Rated impedance: The value of rated impedance shall be specified together with the
rated short-time current in accordance with the system parameters and the recognized case of
system faults.
Note:
Current limiting reactors shall be designed to withstand the thermal and dynamic effects of
the rated short-time current for its rated duration.
7.4.1 General
Electrical motors are one of the most important components in oil , gas and petrochemical plants.
The following general requirements shall be considered in design and selection of the rotating
electric machines.
7.4.1.1 All the electrical motors shall be designed for the load characteristics and operational duty of
the driven equipment.
82
Feb. 2012
IPS-E-EL-100(1)
7.4.1.2 All the electrical motors and their accessories shall comply with sound engineering practices
to have an expected lifetime of minimum 20 years. (Excepting rolling element bearings).
7.4.1.3 Unless there is a clear technical/economic justification for preferring a synchronous motor
over an induction motor, the squirrel cage induction motor generally would be recommended.
7.4.1.4 Synchronous motors generally should not be considered at ratings below 2 MW.
7.4.1.5 Synchronous motors shall be brush-less and the exciter shall consist of a brush-less three
phase synchronous generator, rotating rectifier , a pilot exciter if applicable ,field protection and
shorting functions shall be accomplished by solid state control.
7.4.1.6 For synchronous motors, the excitation system shall be equipped with an automatic power
factor controller to maintain the set power factor within a margin of +-2.5% .
7.4.1.7 The DC motors could be used for special application such as fans, blenders , drilling mud
pumps &seal or lube auxiliary pumps and etc .
7.4.1.8 The application of the VFD (variable frequency drive) systems shall be considered where it
can be justified that the VFD system will benefit the operation, maintenance and efficiency of the
plant. A technical /economical study regarding the above shall be performed and submitted to
company engineer for approval.
7.4.2.1 The motors will be generally installed outdoor in areas where the presence of flammable gas
or vapor is foreseen. In case where the motor will be installed indoor, it will be indicated in data
sheet.
7.4.2.2 The electrical motor shall meet the requirements of the classified areas as specified in this
specification and indicated in data sheet.
7.4.3.1 The voltage levels adapted in the oil, gas and petrochemical industries of Iran are based on
the IEC recommendation No 60038 and part 6.1.5.1 of this standard.
7.4.3.2 The low voltage system is generally 400/230 volt with solidly earthed neutral.
7.4.3.3 The voltage of the motors rated up to 0.4 kW can be selected as 230 volt single phase and
neutral. If capacitor type single phase motor is used, the capacitor shall be metal clad with paper
dielectric. Motors for critical services such as compressor auxiliaries, lube oil systems, special
pumps, etc. shall be 400 volts, 3 phase.
7.4.3.4 The voltage of the motors 0.4 kW up to 150 kW shall be 400 volt three phase. The voltage of
150 kW motors can be selected as 400, 3300 or 6000 volt depending upon the availability of such
voltage levels.
7.43.5 For special applications or existing facilities, other voltages may be specified. The nominal
voltage of the motor will be indicated in data sheet.
7.4.3.6 The voltage of the motors rated 150 kW to 1000 kW shall be 3.3 KV or 6 kV.
7.4.3.7 The voltage of the motors above 1000 kW can be selected as 6 kV or 10 kV or 11 KV
based on technical and economical considerations of the electrical power supply system, in
particular the voltage drop during starting of the motor.
7.4.3.8 All rotating machines shall be capable of operating continuously at rated torque at any
frequency between -2% and +2% of the nominal frequency together with a voltage variation of
5%. The nominal frequency is 50Hz.
83
Feb. 2012
IPS-E-EL-100(1)
7.4.3.9 The motors shall be capable of performing its primary functions at voltage variation of 10%
and frequency variation of 5% according to IEC 60034-1. For generator and synchronous motor
voltage variation shall be considered as 8%.
7.4.4.1 Frame sizes and dimensions and the kW ratings of the motors shall be in accordance with
IEC 60072-1.
7.4.4.2 Motors shall be sized, taking into consideration the appropriate multiplying factor/s related to
each type and size of the driven equipment. The size of the motors versus the driven equipment
shall be according to the recommendations of the driven equipment specifications.
7.5.1 General
7.5.1.1 This section specifies those items which apply generally to the selection and application of
protective relays witch are supplied to provide electrical power system protection for National
84
Feb. 2012
IPS-E-EL-100(1)
Iranian Oil Company installation.Importance , voltage level and cost are the considerations in
selection of protection systems.
7.5.2.1.1 Single or more non parallel incomers supplied from public utility and no on-site generation
i) Phase fault overcurrent protection (50,51)
85
Feb. 2012
IPS-E-EL-100(1)
Note:
For outdoor substation busbar protection is an option.
7.5.2.1.2 Parallel incomers supplied from public utility and no on-site generation the protection
requirement shall be as described in 7.5.2.1.1 with the addition of directional overcurrent and
directional earth fault protection for each incomer.
Note:
If unit feeder protection is considered ,directional protection relays may not be required.
7.5.2.2.1 Cables or very short over head lines(less than 5 K.m.) without load end switchgear
For the cables and overhead lines directly connected to plant such as transformers without
switchgear at load end the following protections shall be considered:
i) Phase fault overcurrent protection (50,51).
ii) Earthfault protection (50N,51N).
The protection installed at source end shall be comprised both cables / overhead lines and also
load end.
7.5.2.2.2 Cables or very short over head lines(less than 5 K.m.)with switchgear at both ends
In addition to the above protections, differential protection shall be provided on all 3.3,6,11,20,33,66
K.V. feeders where:
i) Feeders can be operated in parallel.
ii) Short circuit overcurrent and earth fault protection clearance time is required.
86
Feb. 2012
IPS-E-EL-100(1)
Inter tripping with remote end circuit breakers shall be provided on duplicate feeders.
7.5.3.1. This subsection specifies the electrical protection requirements for generators. It does not
cover mechanical protective requirements of prime mover/generators.
Note:
The method of connection of a generator to the electrical power system (direct or unit
connection ) dictates the type of neutral earthing and protective relaying requirements.
7.5.3.2 Low voltage generator from 100 KVA up to and include 500 KVA
i) IDMT phase overcurrent protection (50,51)
ii) Earth fault protection (50N,51N)
iii) Undervoltage protection (27)
iv) Over voltage protection (59)
v) Frequency relay (81)
vi) Overload protection (49)
vii) Reverse power relay (32) for generators which may be operated in parallel to gether or with
other power sources.
7.5.3.2.1 All above protections,exept over voltage protection, shall trip the generator breaker
device.Over voltage protection shall also shut down the generator.
Note:
The current transformers for short circuit protection purpose(phase and earth) should be
placed on neutral point terminal box.
87
Feb. 2012
IPS-E-EL-100(1)
7.5.3.5.2. Where two or more generators required operate in parallel mode ;synchroscope shall be
used.
IPS-E-EL-100(1)
Feb. 2012
Note:
Fuse is the minimum protection requirement for both primary and secondary sides.
7.5.4.3 Transformers above 250 KVA rating up to and including 2500 KVA (sealed type)
a) Primary side
i) Phase fault overcurrent protection (50,51)
ii) Earth fault protection
(50N,51N)
b) Secondary side
i) Phase fault overcurrent protection (50,51)
ii) Earth fault protection (50N,51N)
iii) Standby earth fault relay (51G) for transformers rating of 500 KVA and above. This relay shall
be of I.D.M.T. type.
iv) Overload relay (49).
v) Oil temperature device with alarm and trip contacts for transformers rating of 500KVA and
above (26).
vi) Resetting
Contacts (63P).
sudden
pressure,
spring
loaded,
relief
device
with
operating
89
Feb. 2012
IPS-E-EL-100(1)
a) Primary side
i)
b) Secondary side
i) Phase fault overcurrent protection (50,51).
ii) Earth fault protection (50N,51N).
iii) Stand by earth fault relay (51G).
v) Restricted earth fault relay (64).
vi) Breker failure protection (50BF)
Feb. 2012
IPS-E-EL-100(1)
The microprocessor based temperature monitor conjunction with RTDs placed in each winding may
be used.
ii) Over fluxing protection where supply frequency assumed to be varied in large scale(for example
transformers supplied via a local generator) (24).
7.5.4.10.1 Transformer protection trip shall be via dedicated hand reset lock out relays.
7.5.4.10.2 The following trips shall be generally operates the relevant lock out relay.
91
Feb. 2012
IPS-E-EL-100(1)
7.5.4.10.3. The intertrip send and receive relay shall be located respectively on secondary and
primary switchgears. All protective relays which tripped secondary lock out relay shall energize
send relay and consequently this relay shall send a signal to energize receive relay on primary
switch- gear and the latest shall trip the circuit breakers.
7.5.5.1 This subsection specifies induction and synchronous motor protection requierments. The
protection of special motors is not covered.
Feb. 2012
IPS-E-EL-100(1)
7.5.5.3.1.1 Main fuses shall be used only in motor starters. this fuses shall be striker pin type and
shall have facilities to trip starter and have their own indications when operated.
7.5.5.3.1.2 Eearth fault or earth leakage protection shall be supplied by a corebalance current
transformers and the minimum setting of relay shall be started at least 10% of motor full load
current.
7.5.5.3.2.1 Winding temperature relay shall have 6 channels to accept ,measures and monitoring 6
RTDs separately.
7.5.6.1 Differential busbar protection should be considered for voltage level of 33 and 63/66 K.V.
outdoor primary substations where the integrity of power supplies and plant operation would be
seriously impaired by loss of a busbar or section of baranch.
7.5.6.2 For metal clad indoor switchgear with busbar insulation as specified in "IPS-M-EL-144 (2)"
the differential busbar protection is not needed.
7.5.6.3.2 Differential busbar protection schemes shall employ high impedance type voltage
operated relays with stabilizing resistors.
93
Feb. 2012
IPS-E-EL-100(1)
7.5.6.3.3 High impedance differential schemes shall have dedicated matched C.T.s of the same
ratio in all incoming and outgoing circuits on the protected busbar or section. Therefore where
busbars are sectionalized by breakers each section shall have its own differential scheme with
C.T.s arranged to over lap at sectionalizing breakers. Class X C.T.s shall be used.
7.5.6.4.1 Test links shall be provided on all C.T.s circuits to facilitate busbar differential scheme
testing.
7.5.6.4.2 busbar protection trips shall be via a single dedicated specific hand reset lock out relay
which shall be arranged to trip the appropriate busbar breakers.
7.5.7.1 All capacitor units shall have individually internal fuse elements (according to IEC-60593). If
this is not feasible for certain types of L.V. capacitors, internal over pressure disconnections shall be
provided.
7.5.7.2 All capacitors shall have direct connected means of discharge. L.V. capacitors must
discharge to a residual voltage <75 volts within 3minutes. A maximum discharge time of 10 minutes
is allowed for M.V. capacitors.
7.5.7.3 External H.R.C. fuses are used only for short circuit protection of both M.V. and L.V.
capacitors and do not provide adequate protection against overcurrent.operation of each fuse of
each bank shall disconnect dedicated contactor by means of striker pin or over voltage relay which
is paralleled to that fuse . For M.V. capacitors the minimum accepted rating of fuse is 1.35 times
the rated capacitor current.(acc. to IEC- 60871-3).
7.5.7.4 In case where the capacitor is controlled by circuit breaker, phase and earth fault protection
relays shall be provided.
7.5.7.5 For capacitor banks above 300 KVAR which controlled by contactor, C.T. operated over
load relays should be used. The tripping current of these relays should be set to 1.43 times the
rated current of the capacitor bank.
7.5.7.6 for large capacitor banks exceeding 1000 KVAR the capacitors shall be connected in double
star with unbalance protection monitoring the star point voltage, or with unbalance current
protection between neutrals (according to IEC-60871-3).
7.5.7.7 Air cored reactors shall be installed with M.V. capacitor banks to limit the inrush currents.
7.5.7.8 An interlock system shall be provided for all automatically controlled M.V. capacitor banks to
prevent re-energizing when the residual voltage is above 10% of rated voltage.
7.5.7.9 In those cases where a capacitor is connected in parallel with an electric motor a single
swhich gear device and associated relays and/or fuses that control and protect both the motor and
the capacitor shall be provided.
7.5.8.1 The lines used in company fields are basically distribution lines and voltage levels are used
up to and include 66 KV. Because of many considerations it is not possible to establish firm rules for
line protection. However, the system design engineer should consider that the operation of
protection on the system will be fully discriminative.
Feb. 2012
IPS-E-EL-100(1)
i) Motors
As described in subsection 7.5.5
ii) Capacitors
As described in subsection 7.5.7
iii) Cables
a) Cables with breaker or isolator at both ends:
For circuits up to 100 A fuse or MCCB and for circuits more than 100 A fuse- contactor or
MCCB together with earth leakage function (decided by company representative if required)
and circuit breaker shall be associated with 505150N51N protection
95
Feb. 2012
IPS-E-EL-100(1)
v) Socket outlets
Outlet circuit shall be protected by phase short circuit protection device and by current operated
earth leakage protective devices, which are according with IEC 60947-2. i.e. residual current circuit
breaker (RCCB). The RCCB operating current shall be 30 mA.
7.5.9.4 Lighting
All lighting circuits shall be protected by suitable fuse or MCB.
7.5.10.1 Metering and instrumentation are essential to satisfactory plant operation. the amount
depending upon the size and complexity of the plant, as well as economic factors. instruments and
meters are need to monitor plant operating conditions as well as for power billing purposes and for
determination of production costs.
Feb. 2012
IPS-E-EL-100(1)
breaker.
iii) Multifunction microprocessor based power measurement meter class 1 (KW, KVAR, KWH, max.
demand, KVARH and so on). Relevant softwear and hardware for comunication porpose and
configuration shall be considered.
a) Process area
i) Ammeters shall be provided for motors above 4 KW except for those driving motorized valve,
cranes and winches , furnace fan without vane control and general ancillary equipment such as
drinking water coolers, etc..
ii) Ammeter shall be located adjacent to or be incorporated in the associated push button station.
Current transformer and ammeter for this purposes preferably of accuracy class 3.
97
Feb. 2012
IPS-E-EL-100(1)
c) Special cases
In certain cases where supervisory control is exercised from a central control position, it may be
necessary to have a meter located at the central control position, typical cases are those of
remotely control crude oil forwarding pumps and /or other process pump derives. when such
arrangements are required they will be specified in view of distances. where indicated in the single
line diagram/and or data sheet, 4-20 MA out put transducer/s complying with IEC 60688 shall be
provided for selected analogue signals to be transmitted to a remote supervisory system such as
distributed control system (DCS). All MV motor starter shall have transducers and for LV motor
starters decided by company representative.
d) General
i) All remote ammeters shall be operated from a current transformer mounted in the motor starter
panel.
ii) Scales shall be selected so that full load current appears between 50% and 70% of full angular
deflection. full load motor current (design value) shall be indicated by a red line on the scale.
iii) Ammeters for motors shall be capable of repeatedly withstanding the appropriate motor starting
current without accuracy being impaired. the ammeter scal shall be shown 6 times motor reted
current.
7.5.10.9 Generators
98
Feb. 2012
IPS-E-EL-100(1)
7.5.11.1.1 Switchgear on M.V. and H.V. system shall not be controlled directly from the front of the
circuit breaker panel. The operation of switchgear shall be from a separate control panel within the
substation or from a completely separate room. The closing of switchgear shall be provided in front
of switchgear panel only for test position.
7.5.11.1.2 Local tripping facilities shall be provided even when remote control is applied.
7.5.11.1.3 Automatic transfer system shall be applied to LV, MV and HV incomers. This system
initiates closing order to bus section C.B. when one of the incomers losses their supply.
7.5.11.1.4 Manual transfer system shall be applied to LV, MV and HV motor control center. This
achieved by means of synchro check relay and relevant selector switches. By this system it shall be
possible to change each incomer by bus section C.B. and vice versa without any interruption of
supply. Use of PLC devices with suitable lader diagram (alghoritm) is acceptable.
7.5.11.1.5 Automatic transfer shall be applied to L.V. emergency generator and main supply. This is
achieved by own generator solid state control system. Adequate interlocks shall be considered to
prevent closing of main circuit breaker and generator circuit breaker simultaneously.
7.5.11.1.6 When the main supply restored, transfer from generator to mains shall be achieved by a
pushbutton installed in generator control panel.
7.5.11.2.1 Tripping of all circuit breakers shall be initiated by separate tripping relay (86). The relay
operating coil shall be energized by protective schemes. The relay shall be heavy duty and hand
reset type with clear reset trip indication.
7.5.11.2.2 The triping and closing circuit, alarm circuit, microproccessor based meters and relays
auxiliary supply and C.B. motor charging supply circuit shall be supplied by four distinct fuses with
appropriate sizes.
99
Feb. 2012
IPS-E-EL-100(1)
7.5.11.2.3. Each feeder at least shall have four indication lamps on panel:
i)
ii)
The trip circuit supervision system (T.C.S.) shall be achieved by use of digital input of
microproccessor base relay with assosiated LED, or with separate T.C.S relay.
7.5.12.1 General
A Suitable Power management system shall be provided to facilitate management of the whole
electrical Power generation and distribution system within utility plants. The power management
system shall be designed in such away to allow:
i)
ii)
Main distribution system (HV/MV AND main LV switchgears) operation and reconnection
Feb. 2012
IPS-E-EL-100(1)
7.6.1 General
This section defines general requirements for electrical power switchgear substation supplies and
distribution for control systems. Such control systems may include instrumentation, data collection,
fire and gas detection systems, telecommunication equipment, computers and associated
equipment and may be onshore or offshore, within established infrastructures or in remote
locations.
U3T
101
Feb. 2012
IPS-E-EL-100(1)
Note 1:
Emergency and shutdown systems such as ESD and F&G shall be classified class A.
Note 2:
Some equipment requires a single power source and then sub-divides this for multiple
purposes. Where any of these purposes are classified as Class A, then the entire system
shall be classified as Class A.
Note 3:
Flame failure devices or monitoring equipment on certain items of machinery which are
critical to the whole or major part of a plant shall be considered as Class A systems.
7.6.1.3 Class B systems
Class B systems are defined as those which their malfunction or failure can cause any of the
following:
A degradation of normal control or monitoring of the plant or process where alternative methods of
control, such as local plant control panels, hand wheels etc are available.
A loss of alarm annunciation facilities not Covered by 7.6.1.2.
7.6.2.1 Design of DC power supplies shall comply with IPS-M-EL-174(2) and AC power supplies
shall comply with IPS-M-EL-176(2).
7.6.2.2 Voltage levels of supplies to all equipment shall be selected according to a sensible
evaluation of systems which may be already existed on a plant. Supplies to control systems should
not exceed nominal voltages of 120V r.m.s AC or 120V Dc (nominal 24V DC. for control instruments
supply and 110 volts DC is used for switchgear supply shall be considered as default).
7.6.2.3 Wherever possible, power supply equipment shall be located in a non hazardous area.
102
Feb. 2012
IPS-E-EL-100(1)
7.6.3.1 Class A power supplies shall automatically maintain a continuously uninterrupted electricity
supply within required control system tolerances upon failure or deterioration of the primary source,
or any other item of the power conversion equipment.
7.6.3.2 Duplicate fully rated rectifier-battery systems shall be used. The AC supplies to the rectifiers
shall be supplied from different switchboards or different busbars of the same switchboard. Where
standby or emergency generation is available, at least one of the AC supplies to the rectifiers shall
be supplied from the generator busbar.
7.6.3.3 Class A power systems shall be designed such that upon the occurrence of a fault in any
one incoming power circuit, the faulty circuit shall be isolated without supply disruption and the
alternative supply shall then maintain the load within the defined tolerance.
7.6.3.4 Autonomy time for, class A, dc loads shall be as indicated in IPS-E-IN-180.
7.6.3.5 Autonomy time for F& G systems shall be as indicated in IPS-E-SF-260.
7.6.3.6 Autonomy time for switchgear control system in attendant plants shall be as indicated in
IPS-M-EL-174(2).
7.6.3.7 Autonomy time for switchgear control system in non attendant plants shall be 8 hours.
7.6.3.8 Each charger shall be sized to supply total load plus 0.2C 5 of total battery capacity required.
Feb. 2012
IPS-E-EL-100(1)
Where DC is not technically acceptable to the manufacturer of the control equipment, AC power
supply is acceptable. In such case dual redundant ups shall be used. Dual parallel redundant ups
are indicated in Fig. 8.
104
Feb. 2012
IPS-E-EL-100(1)
105
Feb. 2012
IPS-E-EL-100(1)
106
Feb. 2012
IPS-E-EL-100(1)
7.6.6.2 Class B
7.6.6.2.1 Class B power supply may be DC or AC and after primary power supply loss shall
automatically maintain continuity of supply.
7.6.6.2.2 In case of DC power supply, a single battery charger with one bank of battery as indicated
in Fig. 10 can be used.
7.6.6.2.3 For ac power supply single UPS as indicated in Fig. 11 can be used. For material standard
refer to be made to IPS-M-EL-176(1) single unit.
7.6.7.1 Introduction
Since Hydrogen gas is normally evolved during charging phase of battery operation, some
requirements regarding battery room construction shall be considered.
107
Feb. 2012
IPS-E-EL-100(1)
7.6.7.2.1 All electrical equipments installed inside of battery room shall be explosion proof type.
7.6.7.2.2 A Hydrogen in air mixture of 4% or greater substantially increases the risk of an
explosion. The concentration of Hydrogen shall be kept below 1 % to provide a safety factor. For
volume of Hydrogen release and ventilation refer to battery manufacturer recommendations.
7.6.7.2.3 Smoke detectors and Hydrogen detectors shall be installed in battery rooms.
7.6.7.2.4 The room ceiling shall be flat to ensure that pockets of trapped Hydrogen gas do not
occur. False ceiling shall not be used for battery rooms.
7.6.7.2.5 Carbon Dioxide portable fire extinguisher shall be installed in battery rooms.
7.6.7.2.6 Batteries installed outside battery rooms, e.g. in service plant, shall be installed in non
metallic cabinets. These cabinets shall be naturally ventilated and either house the battery alone or
the battery in combination with the associated battery charger.
7.6.7.2.7 In battery rooms, eyewash fountain and flow water drain shall be provided.
7.6.7.2.8 The floor and walls of battery rooms shall be covered by ceramic tiles.
7.6.7.2.9 No trench shall be constructed in battery rooms.
7.6.7.2.10 The door of battery rooms shall be opened toward outside.
7.6.7.2.11 The size of a room shall be adequate to allow access to at least three sides of each
battery bank for maintenance purposes.
Air inlets to be located near the floor & outlet openings at the high point in the room,
See Fig. 12:
7.7.1 Scope
This standard specifies the requirements for the design, selection, application and installation of
multicore and single core cables which are required to have copper conductors for use on systems
up to and including 33 kV for the purpose of power, control, indication and protection.
108
Feb. 2012
IPS-E-EL-100(1)
7.7.2.1.1 The voltage designation or rating, Uo/U, should be selected from the standard ratings
given in the relevant cable standard, e.g. 600/1000V, 3600/6000V, etc., and shall be appropriate to
the type of system and the earthing arrangements. Uo is the voltage between phase conductors
and earth and U is the voltage between phase conductors.
7.7.2.1.2 The voltage levels adopted in the oil, gas and petrochemical industries of Iran are based
on the IEC 60038.
7.7.2.1.3 The cables designated up to and including 0.6/1 kV rms are called low voltage (LV)
cables, the cables designated above 0.6/1 kV rms and up to and including 3.6/6 kV rms are called
medium voltage (MV) cables, and the cables designated 6/10 kV, 12/20 kV and 18/30 kV are called
high voltage (HV) cables.
7.7.2.2.1 Cables shall be sized to operate within their current carrying capacity as determined by
the maximum continuous temperature of the insulation, see Table 14.
Note:
Several factors are involved in the sizing of conductors and whilst continuous current
capacity is paramount, others such as voltage drop and ability to carry short circuit currents
must not be neglected.
7.7.2.2.2 In assessing the size of conductor required for a given design current the following factors
shall be taken into account:
- Ambient temperature
- Grouping and proximity to other loaded cables
- Method of installation
- Thermal conductivity of the medium in which the cable is installed.
- Thermal conductivity of the cable constituents.
7.7.2.2.3 The design current,
109
IPS-E-EL-100(1)
Feb. 2012
Note:
The maximum current should account for appropriate application of diversity factors. Such
allowances require the judgement of a qualified electrical engineer with knowledge of the
operational requirements of the plant.
Typically, where switchboards are fed by transformers, the incoming cables are sized to the rating
of the transformer. Where there are no infeed transformers to the switchboard or sub-distribution
panel, then the infeed cables are sized to the rating of the incoming switch or busbar whichever is
the smaller.
7.7.2.2.4 Where cables are laid in mixed groups of different types, sizes and loading, the group
rating factor of each cable should be calculated or assessed for each cable, taking into
consideration the thermal effect of all the other cables of the group. IEC 60287 provides the
mathematical basis for determining individual cables ratings when installed in mixed groups.
7.7.2.2.5 For 3 phase, 4 wire circuits, multicore cables the neutral conductor shall be no smaller
than 50% of the size of the phase conductors. Reduced sizing of neutral conductors should not be
applied where there is likely to be serious load imbalance, significant harmonic distortion in normal
service or in any circuit where the load is predominately discharge lighting.
7.7.2.3.1 The short time maximum current carrying capacity of the cable should be considered with
regards the current/time characteristics of the circuit protection device to ensure that cables do not
suffer damage due to overheating under maximum through fault conditions. In some cases,
particularly where cables are protected by non-current limiting circuit breakers, the cable size is
determined by the magnitude and duration of the maximum through fault current, rather than by the
continuous current capacity or voltage drop constraints.
7.7.2.3.2 The minimum cross-sectional area should be assessed from the following formula:
A=
I t
K
(mm 2 )
where:
A = Cross sectional area of the conductor
(mm 2 )
Insulation
Cable types
PVC
PVC
EPR
XLPE
Up to 185 mm
2
240 mm and above
All types
All types
Maximum
working
temp
o
T1 C
70
70
85
90
Final temp
at end of
short circuit
o
T2 C
150
130
220
250
Value of K
for temps
T 1 ,T 2
109
95
134
143
The values of K given in Table 14 assume that the cable is operating at its maximum current
carrying capacity. If this is not the case, true value may be determined from the formula:
110
Feb. 2012
K = 225.7 Ln
IPS-E-EL-100(1)
234.5 + T2
234.5 + T1
o
7.7.2.4.1 Cables shall be sized so that the maximum voltage drop between the supply source and
the load when carrying the design current does not exceed that which will ensure safe and efficient
operation of the associated apparatus, or 5% of nominal voltage, whichever is lower.
The supply source will be the switchboard or MCC upstream of the load, at which the voltage can
be adjusted. This adjustment can be made either by changing taps on the incoming transformers or
through AVRs of directly connected generators. In the majority of cases the load will be connected
directly to the supply source through a single cable. However there will be cases where the load is
fed from a sub-circuit and in such cases there may be two interposing cables between the load and
the supply source. In such cases the permissible voltage drop of 5% needs to be accounted for
from the supply source through the two series connected cables to the load terminals.
The maximum cable length for a low-voltage motor of given rating may be calculated from the
following formulas:
Ls =
Vs 1000
3I s ( R cos s + X sin s )
Lr =
Vr 1000
3I r ( R cos r + X sin r )
I = Motor current
(A)
Subscripts r and s refe r to running and starting values of the above parameters respectively.
7.7.2.4.2 Cables shall be sized so that during motor starting, voltages throughout the network shall
not fall by more than 15% of nominal values.
7.7.2.4.3 For medium and high-voltage motors, the voltage drop along the cable to the motor due to
the load current shall not exceed 3.25% of nominal voltage during normal running at full load.
111
Feb. 2012
IPS-E-EL-100(1)
7.7.2.6 Documentation
The documentation requirements for the cable system design shall be agreed with the company
representative. The following is a guide of typical requirements:
7.7.2.6.1 Design dossier including basis of cable sizing together with specimen calculations. This
dossier should normally form part of the permanent records of the site.
7.7.2.6.2 Cable routing diagrams.
7.7.2.6.3 Constructional details of cable traywork and cable tray support systems.
7.7.2.6.4 Cross sections of cable routes showing the actual arrangement of cables, and separation
distances.
7.7.2.6.5 Interconnection diagrams showing the cable numbers, the core identification numbers and
equipment terminal numbers.
7.7.2.6.6 Cable schedules.
7.7.2.6.7 Cable gland schedule.
CT secondary
VT secondary
Interlock / intertrip circuits
Pilot wire differential circuits
Note:
The requirements of the preceding paragraph do not apply to motor control and ammeter
circuits to a Remote Control unit (RCU), nor to combined power and control circuits to small
LV motors.
112
Feb. 2012
IPS-E-EL-100(1)
7.7.3.1.8 The armouring of single core power cables shall be made of non magnetic materials.
7.7.3.1.9 All power, lighting, control and earthing cables shall be in accordance with the latest
version of IPS-M-EL-271, 272 and 273.
7.7.3.2 Medium and high voltage power cables
Medium and high voltage cables shall be copper conductor with Cross Linked Polyethylene (XLPE)
insulation, lead sheathed, single wire armoured and PVC overall jacket.
2
MV and HV multicore and single core cables shall have a minimum cross sectional area of 50 mm .
2
MV and HV multicore cables shall have a maximum cross sectional area of 240 mm .
2
MV and HV single core cables shall have a maximum cross sectional area of 400 mm , Unless
otherwise approved by the company representative.
Selection of single or multicore cables shall be approved by the company representative.
For low voltage single core power cable, conductor sizes up to and including 10 mm can be solid
copper.
Unless otherwise approved by the company representative, the maximum conductor cross section
2
2
shall be limited to 240 mm for low voltage 3 and 4 core power cables and 400 mm for low voltage
single core power cables.
a) In areas where high temperature is expected, mineral insulated or heat resistant coppersheathed cables (MICC) shall be used for small power and control.
b) Where mineral insulated cables are specified, the cables shall be copper conductor, copper
sheathed with PVC outer covering. The mineral insulated cables shall be manufactured
according to IEC 60702-1.
c) Mineral insulated copper-sheathed cable (MICC) should in general be restricted to domestic,
commercial and light industrial applications such as in offices, accommodation modules,
substations, control rooms and workshops. Its inherent, but limited, fire resistant properties can
make MICC suitable for essential circuits such as fire alarms, although it may also be used more
generally for power, lighting, heating and air conditioning plant.
113
Feb. 2012
IPS-E-EL-100(1)
d) MICC shall not be used in situations where the equipment to which it is connected is subject to
vibration or where the cable may need to be disconnected regularly for maintenance. A loop of
cable shall be formed just before the gland where MICC is connected to a motor.
e) Where MICC is to be used in a highly inductive circuit, precautions may need to be taken to
protect against breakdown due to the high transient voltage which occurs on switching the
current off. In such cases, cables shall be protected by suitable surge suppressers across the
supply terminals.
f) MICC used indoors in dry locations may be bare copper sheathed. However, where such cables
are used outdoors or where appearance is to be a consideration, they shall have an over sheath
of PVC.
7.7.3.3.5 Wires
Low voltage wires shall be stranded or solid copper conductor, PVC insulated, rated voltage 600
volt according to IEC 60227. Wires shall be suitable for installation in rigid steel galvanized conduits
2
or truncking. Minimum cross section shall be 2.5 mm . Wires in conduit systems shall be applied
only for lighting, communication and convenience outlets in closed buildings in non-hazardous
areas. The insulation color of low voltage wires shall be according to IPS-M-EL-271.
7.7.3.4.1 Conductors shall be longitudinally water sealed stranded copper wires, conforming to
class 2 of IEC 60228.
7.7.3.4.2 The insulation shall be extruded Cross Linked Polyethylene (XLPE). Ethylene-Propylene
Rubber (EPR) insulation may be quoted as an option.
7.7.3.4.3 Cables used offshore for any application other than one calling for a fire resistant cable,
should normally be Flame retardant. For small projects requiring limited quantities, cables by EPR
insulated, galvanised steel or copper alloy braid armour,accordance to IEC 60092-3 shall be used
where economical or expedient.
7.7.3.4.4 Where an armour is required for single core cables it shall consist of a phosphor bronze
wire braid complying with IEC 60092-3.
Note:
Submarine cables selection shall be accordance with the IPS-M-EL-273(1).
114
Feb. 2012
IPS-E-EL-100(1)
7.7.3.5.1 When cable routes are being planned, special fire risk areas shall be avoided as far as
possible. Fire risk diagram(s) indicating areas of fire risk and the sources of fire hazard shall be
produced.
7.7.3.5.2 Within a special fire risk area, the following types of circuit shall be fire resistant, i.e. able
to continue operating in the presence of a fire of specified temperature and duration.
- Circuits necessary to provide a safe and orderly shutdown of the plant, including essential
instrumentation and monitoring circuits.
- Emergency or 'escape' lighting.
- Cables essential for the operation of life saving equipment, e.g. fire alarms, evacuation alarms,
gas detection, etc.
7.7.3.5.3 Depending on the application and the fire withstand requirements, cables shall be Fire
resistant cable. Alternatively, MICC may be used, subject to the restrictions of section 7.7.3.3.
7.7.3.5.4 Cables in special fire risk areas which do not fall into any of the categories of 7.7.3.5.2
shall have flame retardant properties in accordance with IEC 60332-3.
7.7.3.5.5 For most installations, except as required in 4.5.2, fire resistant cables should not be
specified solely to attempt to keep a plant operating in the event of a fire. In the case of the
emergency lighting, a combination of floodlighting and selfmaintained luminaries should be used to
reduce the amount of cable exposed to fire risk.
115
Feb. 2012
IPS-E-EL-100(1)
In which :
Q C : Absolute reactive power of capacitor
V eff : RMS voltage of capacitor
I eff : RMS current of capacitor
F : Frequency
C : capacitance
3) Distortions and harmonics which are due to non linear loads result in decreasing power factor
and this can not be corrected by capacitors however it needs filters.
4) Where the calculated system power factor at full load is less than 85% lagging, capacitor bank/s
shall be installed. The capacitor bank/s shall be sized to improve the system power factor to 95%
lagging at system full load.
5) In case where the calculated system power factor at full load is more than 85% but less than 90%
lagging, power factor correction capacitor/s will be required when power is received from outside
source/s. In such case the capacitor bank/s shall be sized to improve the system power factor to
95% lagging at system full load.
6) Capacitor banks can be installed in the main power plant or individual substations.
7) Capacitor banks shall be permanently energized. Installation of capacitors parallel to individual
motors which is switched on and off together with the motor is not desirable.
8) Low voltage capacitors shall be of the self-healing type and shall comply with the requirements of
IEC 60831 and may be of either three phase or single phase construction.
9) For further information refer to latest version of IPS-M-EL-181.
IPS-E-EL-100(1)
Feb. 2012
Cos 1 = 0.6 Cos 2 = 0.96
P = 300 0.6 =180 Kw , tan 1 = 1.33 , tan 2 = 0.29
So: Q C = 180 (1.33-0.29) = 187 KVAR
R
U3T
U3T
7.10 Lighting
Scope :The purpose of this section is the provision of lighting fitting, illumination, emergency,
security lighting and special lighting for the industrial and non industrial plant areas.
7.10.1.1 The lighting in the process plants shall be fluorescent type in white color as far as practical,
flood lights with mercury vapor lamps can be used where applicable.
7.10.1.2 Long life lamps in combination with electronic ballasts shall be used in new installations,
and for upgrading old installations, so as to take advantage of their increased lumen
efficiency and economic life.
7.10.1.3 The lighting fixtures for street lighting and high industrial buildings such as generator
buildings, compressor buildings, workshops and similar, shall be with mercury vapor lamps. In view
of the restarting time of this type of lighting after a voltage dip, sufficient fluorescent luminaries shall
be installed for basic lighting requirements of the area, equivalent to emergency lighting
requirements.
7.10.1.4 Consideration shall be given to the use of floodlighting, especially around the perimeter of
process and production plants. Care must be exercised to ensure that this does not result in
shadows, especially at operating locations.
7.10.1.5 Low pressure sodium discharge lamps shall not be used in process area, as they
constitute a fire hazard in the event of breakage.
For selection of lighting equipment refer to IPS-M-EL-161(1).
3TU
3T
7.10.2.1 Plant lighting circuits shall be fed from dedicated lighting distribution boards installed in the
plant substations.
7.10.2.2 Plant lighting circuits shall be single phase and neutral or three phases and neutral. Plant
lighting distribution boards shall include 20% spare outgoing circuits.
117
IPS-E-EL-100(1)
Feb. 2012
7.10.2.3 Adjacent luminaries shall not be supplied from the same circuit, or in case of three phase
circuits, from the same phase.
7.10.2.4 As far as practical fluorescent lighting shall be used throughout the plant installations. The
lighting system shall be designed to give illumination levels as shown in Table 15.
Lighting installations shall be designed to obviate stroboscopic effects.
7.10.2.5 Luminaries on structures shall be so located that maintenance and lamp changing can be
effected without the use of ladders or scaffolding. In cases where luminaries mounted from an
elevated walkway or platform does not overhang it, the lamp post shall be arranged to swivel for
maintenance purposes. In high buildings, such as compressor and turbo generator houses,
maintenance and lamp-changing shall be possible by using the overhead crane.
7.10.2.6 Where no structure is available to support luminaries, fixed lighting poles of adequate
length with high pressure discharge floodlighting shall be used to supplement the fluorescent
luminaries. Lighting poles shall be in accordance with IPS-M-EL-161(1).
3TU
U3T
7.10.2.7 For fixed floodlighting columns lamp changing will be carried out using a mobile platform,
e.g. vehicle mounted. Alternatively, hinged lighting columns may be used, if space is available for
the columns to be lowered.
7.10.2.8 Plant lighting circuits shall be designed for automatic switching via photo-electric relays.
7.10.2.9 Control circuits for photo-electric relays shall be fail-safe, i.e. to switch the lights on if a
fault occurs in the photo-electric relay. The plant lighting shall be designed in such a way that in
daytime the lighting of furnaces, boilers and the ground level plant can be switched on by means of
a switch overriding the appropriate photo-electric relay contact. The remaining photo-electric relayoperated plant lighting shall have the facility to be switched off at night-time. These override
switches shall be located either outside the plant substation or in the control room, as required by
plant operations. Moreover, the lighting distribution board shall be provided with an override switch
for maintenance purposes.
7.10.2.10 Level gauge lights shall not be switched by the above-mentioned photo-electric relays
and shall have no maintenance override switches. Level gauge lights should normally be on.
7.10.2.11 Internal lighting of non-process buildings and substations shall be switched inside the
building.
7.10.2.12 Lighting near navigational waters, e.g. jetties and loading platforms, shall not hinder
navigation in any way.
7.10.2.13 The lighting installation in the control rooms shall be designed for switching off,
independently, ceiling lighting groups to suit operators need. The luminaries shall be situated in
such a way that reflection on Video Display Units (VDUs), instrument windows and displays is
avoided.
7.10.2.14 In Zone 1 and 2 hazardous areas, fluorescent luminaries with type of protection Exe
shall be used. Luminaries for level gauge lighting shall be of the fluorescent type, bracket-mounted.
7.10.2.15 High pressure discharge luminaries in hazardous areas shall have type of protection
Exd. An isolating switch shall be included within the fitting to prevent the luminary from being
energized when it is not fully assembled.
7.10.2.16 For standardization reasons the same type of Exd or Exe luminaries should be used in
all plant areas, whether classified Zone 1, Zone 2 or non-hazardous.
7.10.2.17 In hazardous areas classified as zone 0 according to article 4 of standard IPS-M-EL161(1), no lighting fixtures shall be installed.
U
7.10.2.19 In hazardous areas classified as zone 1, the lighting fixtures shall be flameproof Exd type
with a degree of protection IP65. The gas group classification of Exd fixtures shall be at least group
IIB. Where hydrogen or acetylene is present, the gas group classification shall be group IIC. The
maximum surface temperature of Exd fixtures shall be suitable for the appropriate gas in the subject
o
area and shall in no case be more than 200 C which corresponds to T3 according to IEC 60079-0
(Exd IIBT3 or Exd IICT3).
P
118
IPS-E-EL-100(1)
Feb. 2012
7.10.2.20 In hazardous areas classified as zone 2 the lighting fixtures shall be increased safety Exe
according to IEC 60079-7. Lighting fixtures suitable for zone 1 as specified in 5.3.11 can also be
used in zone 2 areas. The lighting fixtures with explosion protection of ExnA or ExnC in accordance
with IEC 60079-15 can be used in zone 2 areas with prior approval of the Engineer. The maximum
surface temperature of Exe and Exn fixtures shall be suitable for the appropriate gas in the subject
o
area and shall in no case be more than 200 C which corresponds to T3 according to IEC 60079 .
7.10.2.21 For standardization purpose, the same type of lighting fixtures selected for zone 2 areas
shall be used in safe areas of industrial plants.
7.10.3.1 Fixed emergency lighting shall be installed at strategic points in the installations, including
control rooms, substations, fire stations, first-aid rooms, watchmens offices, the main entrances,
and in all other buildings and areas where required for safety reasons. Location and electrical
arrangement shall be such that danger to personnel in the case of a power failure is prevented, and
escape routes are lit.
7.10.3.2 The emergency lighting system shall consist of a number of standard luminaries of the
normal lighting installation, which shall be fed via circuits having a stand-by supply from an
emergency generator or from a battery with an autonomy time of at least 2 Hr. In remote areas,
where only a few fittings are required, self power emergency may be used.
7.10.3.3 In the case of an emergency generator supply, a number of luminaries in the control room
and the basement of the control room, as well as field auxiliary rooms, shall have a standby supply
from an independent source with battery back-up to avoid complete darkness during start-up time of
the diesel.
7.10.3.4 The number of emergency luminaries as part of the total number of fittings shall be
determined as follows:
- Utility Area
20%
- Process Area
10%
- Administrative Area
5%
50%
30%
7.10.3.5 The escape luminaries shall generally be part of the emergency luminarys installation, but
the luminaries shall have integral batteries rated to maintain the lighting for at least 30 minutes.
Escape luminaries shall be provided in all buildings so as to lead personnel out of the building along
defined escape routes to defined muster points, which shall also be illuminated.
7.10.4.1 Street and fence lighting shall be fed from lighting distribution boards installed in a
conveniently located plant substation. These lighting distribution boards may either be dedicated to
street and fence lighting, or be one or more sub-sections of a plant lighting distribution board. This
lighting shall also be photo-electric relay controlled and provided with a maintenance override
switch, as for ground level plant lighting.
119
Feb. 2012
IPS-E-EL-100(1)
7.10.4.2 Generally, for street/fence lighting three phase and neutral LV supply shall be used. Each
lighting pole shall include a fuse box as well as a four pole terminating box for looping the feeder
cable. Tee cable joints are not allowed. Adjacent luminaries shall not be supplied from the same
fuse. Fence lighting shall be placed in such a way that the fence as well as the area outside the
fence will be illuminated. Normally fence lighting intensity shall be equivalent to the street lighting
intensity stated in Table 15.
7.10.4.3 For fence lighting, the fixtures with high pressure mercury vapor lamps or high pressure
sodium vapor lamps can be used, as selected by the Engineer. Sodium vapor lamps shall not be
used in areas where fire hazard is envisaged.
7.10.4.4 If special security fence lighting is required, unless otherwise specified, a floodlight
installation shall be designed, based on HP discharge lighting with a minimum illumination of 10 lux
(for CCTV Monitors) at any point in the area between the fence and 5 m outside the fence.
120
Feb. 2012
IPS-E-EL-100(1)
121
IPS-E-EL-100(1)
Feb. 2012
TABLE 15 - ILLUMINANCES LEVELS
MINIMUM
ILLUMINANCE
LUX
AREA OR ACTIVITY
ELEVATION
MILLIMETER
I PROCESS AREAS
A) General process units
Pump rows, valves, manifolds
Heat exchangers
Maintenance platforms
Operating platforms
Cooling towers (equipment areas)
Furnaces
Ladders and stairs (inactive)
Ladders and stairs (active)
Gage glasses
Instruments (on process units)
Compressor houses
Separators
General area
B) Control rooms and houses
Ordinary control house
Instrument panel
Console
Back of panel
Central control house
Instrument
Back of pane
C) Specialty process units
Conveyors
Conveyor transfer points
50
30
10
50
50
30
30
50
50
50
200
50
10
Ground
Ground
Floor
Floor
Ground
Ground
Floor
Floor
Eye level
Eye level
Floor
Top of bay
Ground
300
300
300
100
500
500
100
Floor
1700
760
760
Floor
1700
900
20
50
Surface
Surface
50
150
200
Ground
Floor
1100
200
50
Floor
Ground
5
10
5
Floor
Ground
Floor
50
100
100
Floor
Point
Point
20
20
150
50
50
Ground
Ground
Floor
Floor
1200
4
2
Ground
Ground
Ground
II NONPROCESS AREA
A) Loading, unloading, and cooling water
pump houses, Pump area
General control area
Control panel
B) Boiler and air compressor plants
Indoor
Outdoor equipment 50
C) Tank fields (where lighting is required)
Ladders and stairs
Gating area
Manifold area
D) Loading racks
General area
Tank car
Tank trucks, loading point
E) Tanker dock facilities
F) Electrical substations and switch yards
Outdoor switch yards
General substation (outdoor)
Substation operating aisles
General substation (indoor)
Switch racks
G) Plant road lighting (where lighting is
required)
Frequent use (trucking)
Infrequent use
H) Plant parking lots
I) Aircraft obstruction lighting
122
IPS-E-EL-100(1)
Feb. 2012
III Buildings
A) Offices
500
B) Laboratories
Qualitative, quantitative and physical test
Research, experimental
Pilot plant, process and specialty
Glassware, washrooms
Fume hoods
Stock rooms
500
500
300
300
300
150
900
900
Floor
900
900
Floor
50
5
50
100
200
300
Floor
Ground
760
760
760
1200
200
500
150
300
200
200
300
Floor
760
Floor
760
760
760
760
100
100
Floor
Floor
100
150
50
Floor
Floor
Floor
G) Cafeteria
Eating
Serving area
Food preparation
General, halls, etc.
300
300
300
100
760
900
900
Floor
100
Floor
700
760
Notes:
a) These illumination values are recommended practice to be considered in the design of
new facilities.
b) Indicates vertical illumination.
c) Refer to port authority for required navigational lights.
d) Luminance may be different from those recommended for other industries because of the
nature of area.
e) Refer to local aviation authority for requirements of obstruction lighting and marking.
123
IPS-E-EL-100(1)
Feb. 2012
TABLE 16 - THE PRINCIPAL LIGHT SOURCES FOR GENERAL LIGHTING PURPOSES AND
THEIR CHARACTERISTICS
Types
Metal Halide
LEDs (Light-Emitting
Diodes)
A metal-halide
lamp is a mercury
vapor with other
compounds
(known as halides)
added to the arc
tube to improve
both color and
luminous efficacy.
45-100 lm/W
8000 to 12000 h
Warm White to
White 3000K4200K
commercial office
space,
manufacturing
plants,
warehouses,
sports lighting, and
roadways.
45-110 lm/W
16000 to 20000 h
Warm yellow 2000K
45-80 lm/W
50000h
White to daylight 3500K6000K
Characteristics
Working Principle
Luminous Efficiency
Useful life
Color rendering
Application area
Note:
1 Lux 1 candela/m
1 Candela one lumen. per steroidal
7.11 Earthing, Bonding and Lightning Protection
7.11.1 General
Proper earthing is essential to safe and satisfactory performance of a power system and an
industrial plant. There are four requirements for such earthing:
1) Providing a low impedance path for return of fault currents, so that an over current protection
device can act quickly to clear the fault.
2) Maintaining a low potential difference between exposed metal parts to avoid personnel hazards
during normal and fault condition.
3) Protect properties in the event of static charges and transient phenomena (lightning, switching
operation) which may caused fire and explosion.
124
Feb. 2012
IPS-E-EL-100(1)
7.11.2.1 General
The regulation that one point of every system shall be earthed is designed primarily to preserve the
security of the system by ensuring that potential on each conductor is restricted to such a value as
is consistent with the level of insulation applied. From the point of view of safety, it is equally
important that earthing should ensure efficient and fast operation of protective gear in the case of
earth faults. The system earth resistance must be such that when any fault occurs against which
earthing is designed to give protection; the protective gear will operate to make the faulty feeder or
equipment harmless. In most cases such operation involves isolation of the faulty feeder or
equipment by circuit breakers or fuses. The common classifications of earthing in this standard are
as follows:
a) Solidly earthed
b) Resistance earthed
7.11.2.2.1 M.V and H.V system neutrals shall be earthed TNS at each source of supply.
7.11.2.2.2 M.V and H.V Transformer neutral with secondary voltage less than 36kV shall be
resistance earthed. The rating of each resistor shall be such that to limit the earth fault current
approximately equal to the rated full load current of the transformer secondary.
7.11.2.2.3 In situation where generators are to be directly connected to the main H.V switchboard,
each generator should be earthed via its own earthing resistor. This however, is subject to
verification that the zero sequence, triple harmonic current (3rd, 9th, 15th, etc.) that could circulate
through the resistors under various loading conditions of the generators would not be damaging to
the resistors.
7.11.2.2.4 The rating of each resistor should be such as to limit the magnitude of earth fault current
to the rated full load current or manufacturer recommended value of the generator to which is
connected . These resistors should be solid type and shall be rated to withstand the respective E/F
current for duration of not less than 10 seconds.
Note:
In any case the earthing current shall not exceed 630 A.
7.11.2.2.5 In situations where generators of dissimilar rating characteristics or, Loadings are to be
operated in parallel such as to give rise to circulating currents resulting from triple harmonics then
the system shall be earthed via one earthing resistor only. Each generator shall then be provided
with a suitable switching device to facilitate connection of any machine to the single earthing
resistor.
7.11.2.2.6 For grid in feed system voltages above 36 kV, the neutral point of transformers should
be solidly earthed. In these situations high earth fault current flows in the general mass of earth in
the vicinity of the substation so earthing arrangement must be designed such that these currents do
not results dangerous step and touch potential. Detailed guidance is given in IEEE standard 80.
125
Feb. 2012
IPS-E-EL-100(1)
7.11.3.1 For the earthing of electrical system, equipment and structures, each installation shall have
one common earth grid connected to at least two groups of earth electrodes. The resistance of this
grid to general mass of earth shall no be less than the value specified by this standard when one
group of electrodes is disconnected for the purpose of measuring or inspection. The earth grid shall
extend throughout the plant in form of a plant ring with branch interconnections to the equipment
and structures to be earthed and shall from part of a single earth grid for whole site.
Note:
Instrument earthing such as intrinsically safe, non-intrinsically shall be considered and
installed as stated in proper instrument IPS.
7.11.4.1.1 A bar of high conductivity hard drawn copper shall be fixed inside the trench or cable
gallery of the substation to which the earth bars of all switchboards and the metallic enclosures of
all low voltage ancillary equipment shall be connected.
7.11.4.1.2 All main switchboards shall be connected to substation earthing system at two separate
points. The tank of each main transformer shall be connected directly to the plant main earth grid.
7.11.4.1.3 The armouring and metallic sheath (if provided) of all multi core cables shall be bonded
to the switchboard earth bar via termination or the gland. Where single core cables are used they
shall be bonded to earth at one end only. The earthed end should be at hazardous end (if any).
7.11.4.1.4 The enclosures of all high and medium voltage motors shall be connected directly to the
plant main earth grid or to local earth electrodes. A common earth electrode may be used for
several motors in the same area.
7.11.4.1.5 The enclosure of low voltage equipments shall be bonded to the plant main earth grid.
126
Feb. 2012
IPS-E-EL-100(1)
7.11.4.2.1 Vessels
Two earthing connections shall be taken from the vessel to main plant earthing grid. This is not
necessary done for the vessel which is mounted directly on the steelwork with well conducting to
the earth. Where the vessel is too remote from the plant as to make connection to the main earthing
system impractical, two connections shall be taken from the vessel to separate earth electrodes.
7.11.5.1 Lightning protection system if required shall be designed and installed in accordance with
IEC 61024 or BS 6651.
7.11.5.2 In order to protect against a direct lightning stroke as a minimum the tallest structure on the
plant shall be directly earthed as close to the base as possible with a minimum of two electrodes
(less than 5 Ohm) and interconnected with main plant earthing grid.
7.11.5.3 Metal structures, e.g. vessels, etc., do not require additional protection beyond the earthing
requirements specified in the equipment earthing.
7.11.5.4 The connection to earth should be as short and straight as possible.
7.11.5.5 Where the plant is located in proximity to the process area substation the lightning earthing
system shall be connected to the power earthing system at two points.
7.11.5.6 In all areas classified as hazardous, steelwork such as stairways, cable racks, handrails,
etc., which is mounted on or attached to non-metallic structures shall be bonded to the general
earthing system either directly or via other earthed metal at intervals not exceeding 30 m.
7.11.5.7 Non-metallic structure less than 9 m in height do not generally require lighting protection.
If greater than 18 m in height, they shall be provided with lightning protection.
7.11.5.8 The need for lightning protection on non-metallic structures between 9 m and 18 m in
height shall be determined taking into account the heights of other adjacent structures, the
nearness of flammables materials, consequences of damage, etc.
7.11.5.9 Metallic guy ropes used for supporting metallic or non-metallic stacks or other structure
shall be bonded at their upper ends to the stack or structure if metallic, or to the lightning protective
system in the case of non-metallic stacks or structures. The lower end of each guy rope shall be
directly earthed.
7.11.5.10 For offshore installations, all plant which is not in metallic contact with earthed structural
steelwork shall be connected to the platform steelwork and no separate lightning earthing system is
required.
127
Feb. 2012
IPS-E-EL-100(1)
7.11.6.1 The steel deck and structure of an offshore installation is an inherently very low impedance
structure capable of conducting earth fault currents without giving rise to sparks or dangerous
potential differences. Good electrical continuity is achieved by intimate metal to metal contact
through equipment fixing bolt, clamping, riveting or by welding, such that bonding cables need not
be used between pieces of non-electrical equipment and between equipment earth and the steel
deck.
7.11.6.2 Earthing conductors are required to bond the main components of the generation and
distribution system (namely M.V and L.V generators, transformers, reactors, switchboards, motors
and UPS units) to the platform steelwork. They shall be individually identified, and record on
drawings. The metallic sheath and armour of a submarine cable shall be solidly bonded to the
platform steelwork at both ends of the cable.
7.11.7.1 Special attention shall be paid to electronic and instrumentation system earthing, if
required for computer and control system. These equipments shall be separately earthed from the
electrical earth system. This separate earth system called clean earth" or instrument earth or
computer earth (less than 1 Ohm) as relevant, can be one or a number of separate and
independent earth system depending on manufacturers requirement.
7.11.7.2 The clean earth electrode(s) shall be located outside of resistance zone of power earthing
electrode(s) (radius of this zone is generally 15 20 m).
7.11.7.3 The earth conductor between instrument clean earth bar in the auxiliary room and the
clamp type earth bar in the instrument clean earth pit shall be braided or armoured. This braiding or
armoring shall be bonded to the electrical earthing system to shield this earth conductor from
surface stray earth currents which may cause unwanted interference.
7.11.7.4 The instrument clean earth and electrical earthing system shall be inter connected by a
2
single 70 mm earth wire in each field auxiliary room or control room.
7.11.7.5 Where interconnection between instrument clean earth and electrical earthing system may
be subjected the effect of electrical storms, or high voltage induced, the interconnecting lines or
cables shall be equipped with suitable surge diverters to prevent damage to instrument equipment.
128
Feb. 2012
IPS-E-EL-100(1)
7.11.9.2 Buried earthing and protective conductors should normally be bare copper cable or tapes.
However, if there is a likelihood of corrosion PVC sheathed, colored yellow / green type shall be
used.
7.11.9.3 Joints in protective conductors should be avoided.
7.11.9.4 The following metal parts are not permitted for use as protective conductor or as protective
bonding conductors:
- Metallic water pipes
- Pipes containing flammable gases or liquids
- Constructional parts subjected to mechanical stress in normal service
- Flexible metal parts
- Support wires
7.11.9.5 Protective conductors may consist of one or more of following:
a) a conductor in multicore cables
b) insulated or bare conductor in a common enclosure with live conductors
c)fixed installed bare or insulated conductor
d) metallic cable sheath, cable screen, cable armor, wire braid concentric conductor, metallic
conduit subject to the conditions stated in 7.11.9.5 "a" and "b".
7.11.9.6 Where the installation contains equipment having metal enclosures such a low voltage
switchgear and controlgear assemblies or busbar trunking system, the metal enclosures or frames
may be used as protective conductors if they simultaneously satisfy the flowing three requirements:
a) Their electrical continuity shall be assured by construction or by suitable connection so as to
ensure protection against mechanical, chemical or electrochemical deterioration.
b) They comply with the requirement of protective conductor sizing and jointing.
c) They shall permit the connection of other protective conductors at every predetermined tap off
point.
S=
I 2 .t
K
Where:
2
129
Feb. 2012
IPS-E-EL-100(1)
Conductor size
in mm2
20 KA / 1 s
25 KA / 1 s
31.5 KA / 1 s
40 KA / 1 s
50 KA / 1 s
63 KA / 1 s
80 KA / 1 s
270
270
270
270
2120
2120
2150
Note:
2
270 means, 70mm cable connected to two side switchgear and controlgear.
TABLE 18 - MINIMUM EARTHING / PROTECTIVE CONDUCTOR SIZE FOR VARIOUS
APPLICATIONS
APPLICATION
SIZE / mm2
70
70
35
25
25
Branch to non-electrical equipment exposed to lightning , e.g. tanks, columns and tall structures
70
25
70
70
70
25
Feb. 2012
IPS-E-EL-100(1)
7.11.10.6 Earth strip or conductor electrodes should be used where high resistivity soil underlies
shallow surface layers of low resistivity. They are frequently in form of untinned strip not less than
25 mm by 1.5 mm in section, but may be of bare copper conductor with cross section area not less
2
70 mm . In this case the company engineer approval is needed.
7.11.10.7 If several strip electrodes are required for connection in parallel in order to reduce the
resistance the separation should be made by 2 meters.
7.11.10.8 The depth of strip embedding from the ground surface shall not be less than 50 cm.
7.11.10.9 Employing of structural steelwork as an earth electrode shall be limited in offshore
installations.
7.11.10.10 Plates are not generally recommended because of used in small numbers, they least
reliable type of made electrode. However may be suited in very rocky or coralloid land in which an
earth well may be required.
7.11.10.11 Where the resistance of a single plate is higher than the required value, two or more
plates may be used in parallel, provided that each plate is installed outside the resistance area of
any other. This separation shall not be less than 2m.
7.11.10.12 Where each plates are used either copper type or cost iron type the thickness, shall not
be less than 3mm and 12mm receptivity and the size employed shall not be greater than 1.2m by
1.2m.
7.11.10.13 The depth at which plates are set shall be such as to ensure that the surrounding soil is
always damp.
7.11.10.14 each earth electrode shall be terminated in a suitable pit for inspection and measuring
purposes.
7.11.10.15 where a group of electrodes are used at least one more than the required minimum
number of electrodes shall be installed. By this means, each electrode can be disconnected one at
the time for testing without affecting the integrity of the power earthing system.
7.11.11 Soil resistivity
7.11.11.1 The resistance to earth of an electrode of given dimensions is dependent on the electrical
resistivity of the soil in which it is installed. Soil resistivity is varied according to the type of soil,
moisture content, degree of compaction, chemical composition and soil temperature. The latest
factor is only important near and below freezing point. The type of soil largely determines its
resistivity. Typical values of soil resistivities are given in table 19 for preliminarily.
7.11.11.2 Soil resistivity measurements shall be made at the proposed electrode locations. These
measurements and earthing system design should be carried out at an early stage of the project so
that the electrode locations are compatible with plot plant.
7.11.11.3 Where there is any option, a site should be chosen for the electrodes which are not
naturally well drained. Locations where the ground is kept moist by water flowing over it shall be
avoided. Wherever possible, dry sandy or rocky ground should also be avoided.
7.11.11.4 The effect of possible seasonal increases in electrode resistance due to drying out or
freezing of ground shall be taken into account. Wherever possible, the each electrode should be
installed deep enough to reach the water table or permanent moisture level, deeper than frost is
likely to penetrate and to reach stable ground conditions. For more information refer to IEEE 80 and
ISIRI 4123.
7.11.11.5 Soil resistivity may be reduce 15-90% by chemical treatment, depending upon the kind
and texture of the soil. There are several chemicals suitable for this purpose, including sodium
carbonate, magnesium and copper sulfate, calcium chloride and common salt (addition of less than
one part by weight of salt to 200 of soil moisture has been found to reduce the resistivity by 80
percent).
7.11.11.6 Before chemical treatment is applied to soil, it should be verified that no deleterious effect
on the electrode material will result.
131
Feb. 2012
IPS-E-EL-100(1)
Type of soil
Alluvium and
lighter clays
A
Normal and high
rainfall (e.g. greater
than 500 mm a year)
C
Underground
waters
(saline)
Probable
value
Range of
Values
encountered
Range of
Values
encountered
Range of
Values
encountered
Ohm cm
Ohm cm
Ohm cm
Ohm cm
500
100 to 500
1 000
500 to
1 000 to
2000
10 000
1 000 to
5 000 to
3 000
30 000
Clays
(excluding
alluvium)
2 000
Marls (e.g.
keuper marl )
B
Low rainfall and desert
conditions (e.g. less than 250
mm a year )
5 000
3 000 to
10 000
Porous
limestone (e.g.
chalk )
10 000
300 to 1 000
1 000 to 3 000
3 000 to
30 000
30 000
Porous
sandstone
(e.g. Keuper
100 000
100 000
Sandstone
and clay
shales )
Quartzite,
compact and
crystalline
limestone (e.g.
carboniferous,
marble, etc.)
10 000 to
30 000 to
300 000
100 000
3 000 to
upwards
10 000
100 000
200 000
100 000
up wards
Clay slates
and slatey
shales
Granite
Fissile slates,
Schists Gneiss
and Igneous
rocks
132
IPS-E-EL-100(1)
Feb. 2012
7.11.11.7 Earthing system resistance value, the resistance required varies inversely with fault
current to earth. A suitably low resistance is necessary under all climatic conditions, depending on
the system voltage and fault current level. The resistance and hence possible rise in potential
between the main earth system and general mass of earth should be as low as can economically be
contrived. However the resistance value for different earth system is specified in table 20 and shall
be considered.
TABLE 20 EARTH RESISTANCE VALUE FOR DIFFERENT EARTHING SYSTEM
APPLICATION
EARTHING SYSTEM
RESISTANCE
VALUE
In
<1
<1
<2
<4
<1
Domestic *
<5
<5
<1
* On condition that suitable earthing protective devices RCPD (Residual Current Protection Device)
/ RCD (Residual Current Device) have been used.
133
Feb. 2012
APPENDICES
APPENDIX A
DOCUMENT LIST
134
IPS-E-EL-100(1)
Feb. 2012
135
IPS-E-EL-100(1)
Feb. 2012
136
IPS-E-EL-100(1)