Practical Applications
The principal purpose for the HCDP application is to calculate the
cricondentherm or HCDP at a fixed pressure for reporting and gas
quality monitoring. However, the ability to calculate the HCDP
at up to four different pressures provides some further practical
applications.
Figure 1 - Calculation errors for various gas compositions when using common fixed ratios of C6+ to calculate the cricondentherm
Page 2
The same principle can be used to compare the sample HCDP to the
ambient temperature to determine if the sample handling system is
working correctly, and is not being affected by ambient conditions.
Pre-heater Control
The calculated HCDP at the line pressure and the downstream
regulated pressure can be used at regulator stations to determine
the set-point of gas pre-heaters to optimize the heater performance,
lower heater operating costs, and reduce the risk of regulator
freezing or hydrate formation.
Page 3
www.RosemountAnalytical.com
www.Danalyzer.com
www.analyticexpert.com
www.twitter.com/RAIhome
AMERICAS
Emerson Process Management
Rosemount Analytical
Gas Chromatograph Center of Excellence
10241 West Little York, Suite 200
Houston, TX 77040 USA
Toll Free 866 422 3683
T +1 713 396 8880 (North America)
T +1 713 396 8759 (Latin America)
F +1 713 466 8175
[email protected]
EUROPE
Emerson Process Management
Bond Street, Dumyat Business Park
Tullibody FK10 2PB UK
T +44 1259 727220
F +44 1259 727727
[email protected]
42-NGC-AN-HDCP
ASIA-PACIFIC
Emerson Process Management
Asia Pacific Private Limited
1 Pandan Crescent
Singapore 128461
Republic of Singapore
T +65 6 777 8211
F +65 6 777 0947
[email protected]