HVAC System Analysis
HVAC System Analysis
HVAC System Analysis
Roof Top Unit (RTU #1-6) - The Roof Top Units are air handlers that are on the
roof of the building. Each unit heats and cools its own zone. Supply and return
ductwork connect to these units as they regulate and circulate air in each
designated area of the building. These units range from 2-5 ton nominal capacity
and are gas/electric units which use refrigerant to cool and natural gas to heat.
Ductwork - Ductwork is a system that delivers or removes air. It works with the
whole entire system moving supply, return and exhaust air. Duct for this project
varies as there is round flex duct and rectangular sheet metal ductwork.
Ductwork is typically insulated to regulate temperature control within the system.
Fire damper - These are a form of passive fire protection within ductwork. They
close shut when they are exposed to high temperatures preventing the spread of
a fire and/or smoke. Fire dampers can be found throughout the whole entire
HVAC system within round and rectangular ductwork.
HVAC piping - Piping for this building system features Type L copper for
refrigerant lines and Type M copper for condensate lines. The refrigerant lines
transfer refrigerant to the coils to cool the building and condensate lines transfer
Roof Top Exhaust Fans (REF #1-9) - The Roof Top Exhaust Fans are electric
powered fans that work to remove hot or humid air out of localized areas. This
allows fresh air to enter from supply duct. The warm air that is drawn out is pulled
through a ducting system and expelled outside. These exhaust fans are found in
the Locker Room, PPE/Boot Room, Hazmat/Decontamination Room, and all
restrooms/bathrooms. Rooms with larger room volume such as the Locker Room
typically have larger exhaust fans than those of smaller rooms since more fresh
air is needed in those areas.
Carbon Monoxide Sensor - This is a device that detects the presence of carbon
monoxide gas. When levels are high it activates fans to ventilate the area. This
sensor is located in the Apparatus Room, where fire trucks will be constantly.
Unit Heaters (UH #1-3) - These heaters are heated by natural gas and
conditions are changed by thermostatic control. For ventilation, there are
destratification fans and wall exhaust fans in the area. These heaters heat the
Apparatus Room most likely during colder weather.
Ceiling Diffuser and Return Grilles - These are covers over ductwork in the
ceiling of a room. Diffusers typically have channels or slots that direct supply air
flow in specific directions. Return Grilles extract air from a room and recycle it
through the system so it can be further conditioned.
Ceiling Diffuser (right) with nearby return grilles in a grid system and a return grille (left)
Brick vent (BV) - This vent serves as permanent means for ventilation in the
mechanical room of the building. It is placed in the wall of the building and they
typically vary in sizes based on standard masonry blocks.
Intake Louver (IL) - Louvers are shutters with horizontal angled slats designed
to take in air or exhaust it. An intake louver is located in the Apparatus Room
connected to the SCBA/Repair Room. The louver works to bring in air from
outside the building.
Wall Exhaust Fans (WEF #1-2) - Wall Exhaust Fans exhaust air to better
ventilate an area and essentially exhaust stale air. The Apparatus Room has
two motorized exhaust fans that exhaust air to better ventilate the air with fresh
air. One runs continuously which has a lower HP so there is constant ventilation
within the area.
Outdoor Vent Hood - The outdoor vent hood draws heat, odor, and smoke from
the gas grill in the patio area. Since the space is covered, outdoor ventilation is
needed in the area. An external blower on the roof pulls the unwanted air up
through the outdoor vent hood and discharges it into open space.
Kitchen Hood - The kitchen hood serves as a form of exhaust for any heat,
smoke, and odor that is produced in the kitchen. The hood pulls the unwanted air
through duct and it is expelled through a roof cap.
Roof Caps/Roof Dryer Caps - All of the roof caps ventilate the building. Roof
dryer caps are connected to dryers which expel the hot air produced from the
dryers to the roof. Specific roof caps are connected to equipment to allow proper
ventilate and expulsion of unwanted air. Belmont caps throughout standing seam
metal roof areas serve as attic ventilation.
Circulated by a compressor,
refrigerant is pumped to a
condensing coil, where it converts
from gas to liquid
impact would be material procurement. This project has many components, like
ductwork and roof top units. These can potentially have long lead times. It is key to get
these material submittals approved as soon as possible so they can be ordered so
potential delays in the schedule can be prevented. Some parts of the system cannot be
installed unless other components are there. Another schedule impact would be start
up, testing and balancing. After the whole system is installed, startup testing needs to
occur and adjustments need to be made to balance air movement systems and
hydronic systems before occupancy. Also, adjusting all air devices is necessary to
prevent drafts on occupants. This could potentially delay handing the system over to the
owner at the end of the project, thus delaying the date of completion. Coordination with
other trades is key, as there are integral parts of the HVAC system with the Electrical &
Plumbing systems. Shop drawings need to be checked and approved so that there are
no clashes within other systems such as plumbing or electrical. Poor coordination could
result in a clash in the field rather than just on a model or drawings, resulting in more
time to correct it, thus delaying the schedule.