BS8519 2010

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12
At a glance
Powered by AI
The key takeaways are that BS 8519 provides guidance on selecting and installing fire-resistant power and control cable systems for life safety and fire fighting applications. It identifies three categories of circuits based on fire survival times and recommends appropriate cable tests and categories for different applications.

The three categories of fire survival times recognized in BS 8519 are: Category 1 - 30 minute fire survival time, Category 2 - 60 minute fire survival time, Category 3 - 120 minute fire survival time.

For life safety systems it is recommended that the system should be capable of remaining operational for 60 minutes in large and/or complex buildings and 30 minutes in others. For fire fighting systems it is recommended that the system should be capable of servicing active systems for 60 minutes or 120 minutes depending on the specific application.

A brand of the

FP Guide to BS 8519:2010

A guide
to the selection of cable
types in accordance with
the recommendations of
BS 8519:2010
Selection and installation
of fire-resistant power
and control cable systems
for life safety and firefighting applications Code of practice
by T.L. Journeaux

BS 8519:2010 SELECTION AND INSTALLATION OF FIRE-RESISTANT CABLES FOR LIFE SAFETY AND FIRE FIGHTING APPLICATIONS

Contents
Introduction

Page 3

BS 7346-6 and the 2006 edition of Approved Document B

Page 3

Fire survival times

Page 3

Cable selection and test methods

Page 4

Cable sizing and the effects of fire temperature

Page 5

Guidance on installation practice

Page 5

Protection of High Voltage supply cables

Page 5

Key Applications

Page 6

Key issues for specifiers

Page 6

Fire resistant cables - application standards

Page 7

Guidance notes

page 8

Printed August 2010


Reviewed and reprinted April 2014

BS 8519:2010 SELECTION AND INSTALLATION OF FIRE-RESISTANT CABLES FOR LIFE SAFETY AND FIRE FIGHTING APPLICATIONS

Introduction
BS 8519 is a new Code of practice giving guidance and recommendations for the Selection and installation of fireresistant power and control cable systems for life safety and fire-fighting applications:-

> It specifically covers high rise and complex buildings and recognises that the fire engineered solutions
>
>
>
>
>
>

developed for such buildings require a high level of performance from components of the building services

including electrical supplies.
It is intended for designers, contractors, regulators and enforcers, fire authorities and inspectors.
It identifies electrical loads defined as life safety or fire-fighting and recommends minimum categories for
particular applications.
It identifies three categories of circuits (Categories 1, 2 and 3) with fire survival times of 30 min, 60 min and
120 min.
It identifies appropriate cable tests for the categories.
It aims to ensure that the level of circuit integrity of the cables is not compromised by other electrical system
components.
It does NOT give recommendations for the wiring of fire detection and fire alarm systems which are covered by
BS 5839-1, BS 5839-6, BS 5839-8 and BS 5839-9 or emergency lighting systems covered by BS 5266-1.

BS 8519 was published in February 2010 and became effective immediately.

Relationship between BS 7346-6 and the 2006 edition of Approved Document B of The
Building Regulations
BS 8519:2010 is a complete revision of BS 7346-6:2005 Components for smoke and heat control systems - Part 6:
Specification for cable systems which has been withdrawn. The new CoP has an expanded scope to all life safety
and fire-fighting systems except fire detection, fire alarm and emergency lighting. It includes much new and revised
technical guidance relevant to the selection and installation of fire-resistant cables. The cable test method previously
given in Annex B of BS 7346-6 has previously been published separately as BS 8491.
For large and complex buildings, Approved Document B (5.38) refers to BS 7346-6 for guidance on the selection of
cables that need to operate for an extended period during a fire. This guidance is now found in BS 8519.

Fire Survival Times


Three fire survival times are recognised in BS 8519, according to the specific life safety or fire-fighting application.
For life safety systems it is recommended that the system should be capable of remaining operational for 60 minutes
in large and/or complex buildings and 30 minutes in others.
For fire fighting systems it is recommended that the system should be capable of servicing active systems for 60
minutes or 120 minutes depending on the specific application.
The fire survival times are allocated categories for ease of reference:

> Category 1 - 30 minute fire survival time


> Category 2 - 60 minute fire survival time
> Category 3 - 120 minute fire survival time

BS 8519:2010 SELECTION AND INSTALLATION OF FIRE-RESISTANT CABLES FOR LIFE SAFETY AND FIRE FIGHTING APPLICATIONS

Cable Selection and Test Methods


Cable requirements for the three categories are split between power cables (larger cables generally for 3 phase
circuits) and control cables (smaller cables with conductor sizes up to and including 4mm2 and excluding 3 phase
power circuits). Power cables would include supplies to plant (motors, fans etc.) whereas control cables would include
interconnections (often ELV) to associated alarm and detection systems providing signals.
Power cables of 20mm overall diameter and above should meet the required fire survival time (30 min, 60 min or
120 min) when tested to BS 8491. This is the same requirement as given in BS 7346-6 and is also the same as the
F30, F60 and F120 categories of BS 7846.
Prysmian FP600S high performance power cables meet the requirements for Category 1 (30 min), Category 2
(60 min) and Category 3 (120 min). Power cables that have overall diameter less than 20mm cannot currently
be tested to BS 8491, but their use is allowed provided that they can be demonstrated to give the same level of
resistance to fire, direct impact and water jet as required by BS 8519.
Control Cables of conductor size up to and including 4mm2 should meet the required fire survival time (30 min, 60
min or 120 min) when tested to BS EN 50200 together with an additional test for resistance to fire, impact and water
spray.
For Category 1, this additional test is to BS EN 50200 Annex E for 30 minutes and thus the requirement is the same as
for standard cables to the fire alarm standard BS 5839-1.
For Category 2, this additional test is to BS 8434-2 and thus the requirement is the same as for enhanced cables to
the fire alarm standard BS 5839-1.
For Category 3, this additional test is variant of BS 8434-2 with amended burning and water application times and the
details are given in BS 8519 Annex B.


54

BS 8519:2010 SELECTION AND INSTALLATION OF FIRE-RESISTANT CABLES FOR LIFE SAFETY AND FIRE FIGHTING APPLICATIONS

Cable sizing for the effects of fire temperature


The conductor temperature of a cable in a fire will rise above the maximum conductor temperature upon which
tabulated current rating and voltage drop data is based. This will have implications for voltage drop and the effects of
fault currents, which may be significant in certain applications.
Annexes of BS 8519 give guidance on the review of these factors together with a recommendation that the advice of
the cable manufacturer should be sought.
The content of these informative annexes is based upon Prysmian guidance notes which are included in this booklet.
Sizing of circuit protective conductors (CPCs) is also addressed in BS 8519. Where supplementing of the cable armour
with a separate external CPC is necessary to achieve the correct earth fault impedance, it is recommended that the
external CPC should be not less than 25% of the cross-sectional area of the phase conductor.

Guidance on installation practice


In order to ensure that the circuit integrity of the installed cables is not compromised by other components of the
system such as fixings, containment system, glands and joints, BS 8519 gives some detailed recommendations on cable
installation practice. Joints, of course, should be avoided unless absolutely essential.
It is recommended that cable fixings and fixing centres should be in accordance with the cable manufacturers
recommendations. Such recommendations for Prysmian FP cables are given in the appropriate cable data sheet.
It is recommended that robust armoured cables (such as those meeting BS 8491 and BS 7846) are installed either fixed
direct to the building structure or on a cable management system. In cases where additional mechanical protection
is required, installation on a cable management system or in a containment system is recommended. Any such cable
management systems are required to maintain their function in the presence of the same flame, mechanical impact
and water jet conditions and for the same time period as required for the cables, although no specific tests are given
as they are still in the process of development. Manufacturers of fire rated cable management systems should be
consulted regarding the design and specification of compliant systems. (See table 12 of guidance note no.1 wiring regs
BS 7671).

Protection of High Voltage Supply Cables


For security of supply, BS 8519 recommends that mains supply cables serving life safety and fire fighting systems
should directly enter the fire rated switch rooms and not pass through the building. However, it is recognised that in
certain instances such cables may have to be routed through the building, in which case they should be fire protected
by a protective system for the appropriate survival time.
As suitable HV cables with intrinsic resistance to fire are not available, normal cables (e.g. BS 7835) should be used with
appropriate protection. Protection may be achieved by installation of the cable within a concrete trench with concrete
cover, routing within a dedicated shaft or void of the appropriate fire rating, or enclosure throughout their length by
passive fire protection material giving 120 minute fire resistance together with the capability of withstanding the effects
of a water jet after such exposure. Certain high performance systems based on composite panels of fibre reinforced
cement bonded to steel sheets are claimed to be suitable.
BS 8519 recommends that the performance of the enclosure should be assessed in accordance with BS EN 1366-5:2003
for integrity and thermal insulation under conditions of fire outside the duct. In order to ensure no adverse effect on
o
the cable, the measured temperature inside the duct should not exceed the initial temperature by more than 180 C.
Manufacturers of fire rated systems suitable for cable protection should be consulted regarding the design of compliant
systems.
o

Restriction of the temperature rise within the fire protective system to 180 C will ensure that XLPE insulated cables to
BS 7835 will operate for the required 120 minutes.

BS 8519:2010 SELECTION AND INSTALLATION OF FIRE-RESISTANT CABLES FOR LIFE SAFETY AND FIRE FIGHTING APPLICATIONS

Key Applications
Key applications where the guidance and recommendations of BS 8519 would be appropriate to ensure best practice
and provide a secure means of compliance with Approved Document B would include:

> Supply and control of Smoke barriers, Smoke control dampers, Smoke curtains and Smoke fans
> Supply and control of Fire barriers
> Supply and control of Smoke and Heat Exhaust Ventilation Systems
> Supply and control to pressurization systems
> Fire-fighting and evacuation lift supplies
> Sprinkler pumps, water mist, gaseous, powder, water spray and automatic foam extinguishing systems
> Wet riser pumps

Key issues for specifiers


> BS 8519 is an important new Code of Practice giving guidance and recommendations for the selection and

installation of fire resistant power and control cables for a range of life safety and fire fighting applications.

> BS 8519 does not cover the wiring of fire detection and fire alarm systems which are still covered by the pre-
exsting BS 5839-1, BS 5839-6, BS 5839-8 and BS 5839-9 or emergency lighting systems which are covered
by the pre-existing BS 5266-1.

> BS 8519 replaces BS 7346-6, which is withdrawn and provides a secure route to compliance with Approved

Document B of The Building Regulations for large and complex buildings.

> BS 8519 introduces the concept of time based fire survival times (30 min, 60 min and 120 min) defined as
Categories 1, 2 and 3 for both power and control cables.

> BS 8519 references existing test methods and performance levels (BS 8491, BS EN 50200, BS 8434-2) except
in the case of Category 3 control cables where a variant of BS 8434-2 is defined.

> BS 8519 does not require the development of any new cable types to meet its new requirements as existing
Prysmian FP cables are already available to meet each of the performance categories for both power
and control applications.

BS 8519:2010 SELECTION AND INSTALLATION OF FIRE-RESISTANT CABLES FOR LIFE SAFETY AND FIRE FIGHTING APPLICATIONS

BS 8519:2010 SELECTION AND INSTALLATION OF FIRE-RESISTANT CABLES FOR LIFE SAFETY AND FIRE FIGHTING APPLICATIONS

Guidance Notes: As printed in BS 8519:2010


A Current ratings and voltage
drop for cables in a fire:
When a cable is involved in a fire, the
conductor temperature will rise above the
maximum conductor temperature upon which
the tabulated current rating and voltage drop
data given in Prysmian Cables & Systems Ltd.
data sheets is based.
In carrying a set current, a cable with
its conductor temperature at 950 oC will
experience a greater temperature rise due to
current loading than a cable with its conductor
temperature at 90 oC. However, the additional
temperature rise due to this factor will be less
that 50 oC and is not significant in relation to
the temperature rise caused by fire.
The voltage drop at typical fire temperatures
will be higher that at 90 oC and this may be
significant for certain types of load. Assuming
a worst case of the total length of the cable
run in the fire, it may be necessary to increase
the conductor size as illustrated in the
following examples.

Voltage drop calculations for


cables in a fire:
The process of calculating voltage drop of a
cable is normally straight forward. Tabulated
values are multiplied by the length of run and
current to be carried, to give the expected
voltage drop.
It should be noted that the tabulated values
assume that the cable conductor temperature
is at its maximum permitted normal operating
temperature.
If the cable is involved in a fire, the conductor
temperature and hence the resistance would
be higher, therefore the voltage drop would
be higher.

Example 1.1:
Assume a 2 core 2.5mm2 FP400 cable carrying
5 A over 50 m. Assume 2 m are at 750 oC
and the rest of the cable is at 90 oC. Volt drop
would be:
(19 x 0.001 x 5 x 48) + (19 x 0.001 x 3.0342
x 5 x 2) = 5.14 V
Example 1.2:
Assume a 2 core 2.5mm2 FP400 cable carrying
5 A over 50 m. Assume all 50 m are at 750
o
C. Volt drop would be:
19 x 0.001 x 3.0342 x 5 x 50 = 14.41 V.
Example 2.0:
Assume a 2 core 120mm2 FP600S cable
carrying 200 A over 50 m. In normal
operation the volt drop would be:
0.42 x 0.001 x 200 x 50 = 4.2 V
Where 0.42 is the mV/A/m for FP600S
120mm2 at 90 oC.
Example 2.1:
Assume a 2 core 120mm2 FP600S cable
carrying 200 A over 50 m. Assume 2m are at
750 oC and the rest of the cable is at 90oC.
Volt drop would be:
(0.42 x 0.001 x 200 x 48) + (0.42 x 0.001 x
3.0342 x 200 x 2) = 4.45 V.
Example 2.2:
Assume a 2 core 120mm2 FP600S cable
carrying 200 A over 50 m. Assume all 50 m
are at 750 oC. Volt drop would be:
0.042 x 0.001 x 3.042 x 200 x 5 = 12.74 V

The problem in determining the voltage drop


for a run of cable in a fire is to know the
conductor temperature at each point along
its length. Therefore assumptions have to
be made in calculating what the voltage drop
would be.

As can be seen from these examples, although


the voltage drop has increased from normal
operation, with part of a cable or all the
cable in a fire, the percentage drop from a
240 V single phase supply does not increase
significantly.

To illustrate the effect of assuming different


lengths of cable being involved in a fire, two
sets of examples are given, one based on 5 A
and the other based on 200 A load.

This to say :
Example 1, would give 1.98%, 2.14% and
6% respectively.
Example 2, would give 1.75%, 1.9% and
5.3% respectively.

Example 1.0:
Assume a 2 core 2.5mm2 FP400 cable carrying
5 A over 50 m.
In normal operation the voltage drop would
be:
19 x 0.001 x 5 x 50 = 4.75 V.
Where 19 is the mV/A/m for FP400 2.5mm2
at 90 oC

From these percentage volt drop values, it


would seem unlikely that a fire would have
a significant effect on most equipment being
supplied by the cable, even in the example of
the worst case given above.
However if it is required to limit the volt drop
to 4% for the example when the whole length
of cable is in the fire, e.g. motors running fire
fighting water pumps; then the cable sizes in
examples 1.2 and 2.2 would have to be

BS 8519:2010 SELECTION AND INSTALLATION OF FIRE-RESISTANT CABLES FOR LIFE SAFETY AND FIRE FIGHTING APPLICATIONS

Notes...


























BS 8519:2010 SELECTION AND INSTALLATION OF FIRE-RESISTANT CABLES FOR LIFE SAFETY AND FIRE FIGHTING APPLICATIONS

Notes...



























10

BS 8519:2010 SELECTION AND INSTALLATION OF FIRE-RESISTANT CABLES FOR LIFE SAFETY AND FIRE FIGHTING APPLICATIONS

Notes...



























11

A brand of the

Sales enquiries
Tel: 0845 767 8345
Fax: 023 8029 5465

Overseas sales enquiries


Tel: +44 (0) 23 5029 5481
Fax: +44 (0) 23 8029 5465

UK Technical helpline
Tel: 0845 767 8345
Fax: 023 8029 5002

Overseas technical
Tel: +44 (0) 23 8029 5481
Fax: +44 (0) 23 8029 5002

Prysmian Cables & Systems Limited


Chickenhall Lane
Eastleigh
Hampshire
SO50 6YU
United Kingdom
www.prysmian.co.uk
www.fpcables.co.uk

Information hotline
Tel: +44 (0) 23 8029 5029
Fax: +44 (0) 23 8029 5437

Should you have any concerns about


unsafe, non-approved or counterfeit
cable, please contact the ACI
Tel: 020 8946 6978
Email: [email protected]

You might also like