Notifier FCM 1 Supervised Control Module
Notifier FCM 1 Supervised Control Module
Notifier FCM 1 Supervised Control Module
CURRENT RATING
MAXIMUM VOLTAGE
LOAD DESCRIPTION
APPLICATION
3A
30 VDC
Resistive
Non Coded
2A
30 VDC
Resistive
Coded
.9 A
110 VDC
Resistive
Non Coded
.9 A
125 VAC
Resistive
Non Coded
.5 A
30 VDC
Inductive (L/R=5ms)
Coded
1A
30 VDC
Inductive (L/R=2ms)
Coded
.5 A
125 VAC
Inductive (PF=.35)
Non Coded
.7 A
75 VAC
Inductive (PF=.35)
Non Coded
Specifications
Normal Operating Voltage:
Maximum Current Draw:
Average Operating Current:
External Supply Voltage:
Maximum:
Drain on External Supply:
Temperature Range:
Humidity:
Dimensions:
Accessories:
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during
shipping. To ensure that the switch contacts are in their correct state, modules must be made to communicate with the panel before
connecting circuits controlled by the module.
12 Clintonville Rd
Northford, CT 06472-1653
(203) 484-7161
Before Installing
This information is included as a quick reference installation
guide. Refer to the control panel installation manual for detailed
system information. If the modules will be installed in an existing
operational system, inform the operator and local authority that
the system will be temporarily out of service. Disconnect power
to the control panel before installing the modules.
General Description
FCM-1 Supervised Control Modules are intended for use in intelligent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. This module
is used to switch an external power supply, which can be a DC
power supply or an audio amplifier (up to 80 VRMS), to notification appliances. It also supervises the wiring to the connected
loads and reports their status to the panel as NORMAL, OPEN, or
SHORT CIRCUIT. The FCM-1 has two pairs of output termination
points available for fault-tolerant wiring and a panel-controlled
LED indicator. This module can be used to replace a CMX-2 module that has been configured for supervised wiring operation.
9
8
7
6
5
LOOP
Compatibility Requirements
To ensure proper operation, this module shall be connected to a
compatible Notifier system control panels only (list available from
Notifier).
67 8 9
5
10
11
4
3
12
13
2
1 0 15 14
TENS
8
7
6
9
5
4
3
2
10
ONES
BACK OF
MODULE
LABEL
3
4
ADDRESS
A78-2318-18
A78-2318-07
J1 UNDER LABEL
Mounting
The FCM-1 mounts directly to 4 square electrical boxes (see
Figure 2A). The box must have a minimum depth of 21/8 . Surface
mounted electrical boxes (SMB500) are available.
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. When using control modules
in nonpower limited applications, the CB500 Module
Barrier must be used to meet UL requirements for the
separation of power-limited and nonpower-limited terminals and wiring. The barrier must be inserted into a 4
x4 x21/8 junction box, and the control module must be
placed into the barrier and attached to the junction box
(Figure 2A). The power-limited wiring must be placed
into the isolated quadrant of the module barrier (Figure
2B).
1. Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
Figure 2B:
LO
OP
4 5 6 78
3
9
2
10
NS 1
0 15
1211
4 5 6 7 8 14 13
3
9
ON
2
ES 1
0
AD
DR
ES
S
7 TE
LO
OP
4 5 6 78
3
9
TEN 21
10
S 0
1211
15
4 5 6 7 8 14 13
3
9
ON
2
ES 1
0
AD
DR
ES
S
ISOLATED
QUADRANT
A78-2611-11
A78-2610-08
N500-46-00
www.PDF-Zoo.com
I56-1169-07
2001 Notifier
N500-46-00
I56-1169-07
COMMUNICATION LINE
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
)-(
)+(
TO NEXT
DEVICE
)-(
)+(
CONTROL
MODULE
9
8
7
6
47K EOL
RESISTOR
ELR-47K
5
LOOP
)+(
67 8 9
5
10
11
4
3
12
13
2
1 0 15 14
TENS
6789
5
4
3
2
10
ONES
)-(
)+(
1
2
3
4
Figure 5. Typical wiring for speaker supervision and switching, NFPA Style Y:
ADDRESS
)+(
)+(
)+(
EOL RESISTOR IS
INTERNAL AT
TERMINALS 8 & 9
)(
)(
6
5
LOOP
)+(
ONES
)(
)+(
1
2
3
4
ADDRESS
)+(
7
6
5
67 8 9
5
10
11
4
3
12
13
2
1 0 15 14
6789
5
4
3
2
10
TENS
ONES
0
1
2
)(
)+(
3
4
ADDRESS
)+(
AUDIO CIRCUIT
DO NOT LOOP WIRE AROUND TERMINALS
3 & 4. BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
)(
AUDIO AMPLIFIER, 70.7 Vrms MAX.
USE ONLY MODELS AA-30, AA100 OR AA-120. AMPLIFIER
)+(
MUST PROVIDE WIRING SUPERVISION PER NFPA.
SUPERVISION
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.
SEE NOTIFIER INSTALLATION MANUAL FOR DETAILED INFORMATION.
WHEN A 70.7V AUDIO AMPLIFIER IS USED, TERMINALS 1 AND 2 ARE POWER LIMITED,
WHILE TERMINALS 3-9 ARE NONPOWER LIMITED. IN THIS CASE THE CB500 BARRIER
IS REQUIRED. OTHERWISE, ALL TERMINAL WIRING IS POWER LIMITED.THE CB500
INCLUDES A LABEL INDICATING WHICH TERMINALS ARE NONPOWER LIMITED. THIS
LABEL MUST BE PLACED OVER THE POWER-LIMITED TERMINAL INFORMATION ON
THE NAMEPLATE LABEL, PRESENT ON THE MODULE HOUSING.
A78-2284-11
Figure 6. Typical fault tolerant wiring for speaker supervision and switching, NFPA Style Z:
)(
)+(
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS
3 & 4. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
)(
)+(
COMMUNICATION LINE
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
TO NEXT
DEVICE
FROM PANEL OR
PREVIOUS DEVICE
CONTROL
MODULE
)(
LOOP
)+(
67 8 9
5
10
11
4
3
12
13
2
1 0 15 14
TENS
8
7
6
9
5
4
3
2
10
)(
47 K EOL
RESISTOR
ELR-47K
A78-2282-12
)(
CONTROL
MODULE
COMMUNICATION LINE
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
)(
)+(
Figure 4. Typical fault tolerant notification appliance circuit configuration, NFPA Style Z:
TO NEXT
DEVICE
TO NEXT
DEVICE
SPEAKER SWITCHING CIRCUIT - NFPA STYLE W
SPEAKERS MUST BE LISTED FOR FIRE PROTECTION. REFER
TO THE RELAY CONTACT RATING TABLE FOR MAXIMUM LOAD.
FROM PANEL OR
PREVIOUS DEVICE
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS
3 & 4. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
)-(
)+(
COMMUNICATION LINE
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
CONTROL
MODULE
47 K EOL
RESISTOR
IS INTERNAL
AT TERMINALS
8 AND 9
)(
)(
6
5
LOOP
)+(
67 8 9
5
10
11
4
3
12
13
2
1 0 15 14
6789
5
4
TENS
3
2
10
ONES
0
1
2
)(
)+(
3
4
ADDRESS
)+(
AUDIO CIRCUIT
DO NOT LOOP WIRE AROUND TERMINALS
3 & 4. BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
)(
AUDIO AMPLIFIER, 70.7 Vrms MAX.
USE ONLY MODELS AA-30, AA100 OR AA-120. AMPLIFIER
)+(
MUST PROVIDE WIRING SUPERVISION PER NFPA.
SUPERVISION
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.
SEE NOTIFIER INSTALLATION MANUAL FOR DETAILED INFORMATION.
WHEN A 70.7V AUDIO AMPLIFIER IS USED, TERMINALS 1 AND 2 ARE POWER LIMITED,
WHILE TERMINALS 3-9 ARE NONPOWER LIMITED. IN THIS CASE THE CB500 BARRIER
IS REQUIRED. OTHERWISE, ALL TERMINAL WIRING IS POWER LIMITED.THE CB500
INCLUDES A LABEL INDICATING WHICH TERMINALS ARE NONPOWER LIMITED. THIS
LABEL MUST BE PLACED OVER THE POWER-LIMITED TERMINAL INFORMATION ON
THE NAMEPLATE LABEL, PRESENT ON THE MODULE HOUSING.
A78-2285-10
A78-2283-12
N500-46-00
www.PDF-Zoo.com
I56-1169-07
N500-46-00
I56-1169-07