Datasheet Smartpack2

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Smartpack just got

smarter!



New and improved interface


New and improved functionality
Improved statistics
Full hybrid support

Smartpack2

Distributed control system for medium to large power systems


Doc 242100.50X.DS3 - rev. 5

PRODUCT DESCRIPTION
New features and look on a well-tested
control platform

Simplifies operation in large multisite


systems

Smartpack2 is built on the proven software


platform that is used in Smartpack, making
it reliable and robust. Increased program
memory and new hardware allows for more
features and improved user interface. The
new modular distributed control system
simplifies connections.

Smartpack2 offers many off-site benefits if


it is connected to the internet. View the
system status, change parameters and
receive alarms at a multisite management
center. Use features such as battery
lifetime estimations, fuel consumption
through tank level measurement and
generator runtime, to plan for site service.
Use the energy logs to document the
amount of renewable energy used, and to
plan for site upgrades.

Power solutions
Elteks power solutions are based on
industry leading building blocks, fully
integrated into coherent, complete and
flexible solutions with one single Smartpack
controller overlooking all energy sources,
flow and storage. The entire installation
is easily and efficiently monitored and
controlled over the Internet by means of
advanced, yet user friendly software.

Eltek Grterudveien 8, 3003 Drammen, Norway

Phone: +47 32 20 32 00 Eltek 2015 www.eltek.com

Smartpack2
TELECOM

SYSTEM SOLUTION

Radio Base stations/ Cell Sites


Mobile Switching Center (MSC)
Microwave
Central Office
Cable
Broadband

INDUSTRIAL

SYSTEM SOLUTION

Power Utilities
Railway & Metro
Marine & Offshore
Oil & Gas
Low & High Voltage switchgear
Transformer & SUB Stations
Power Generation & Distribution
Emergency lighting systems
Industrial control systems
Process and Heavy industry

HYBRID

SYSTEM SOLUTION

Smartpack2 comes with advanced software to control power


systems with multiple power sources. It handles solar energy,
generators, unstable grids and is prepared for wind power.
Suitable applications may include (but not exclude):
Radio Base stations/ Cell Sites
Mobile Switching Center (MSC)
Microwave
Central Office
Cable
Broadband

DATA CENTER

SYSTEM SOLUTION

Distributed power solutions


Central power solutions
Front End/In-rack power

242100.50X.DS3 - rev. 5
Eltek Grterudveien 8, 3003 Drammen, Norway

Phone: +47 32 20 32 00 Eltek 2015 www.eltek.com

Smartpack2
DISTRIBUTED CONTROL SYSTEM
Three units are required to build a complete Smartpack2
control system.
Smartpack2 Master is the master controler and visible
part of the system.
Smartpack2 Basic handles housekeeping.
IO Monitor Type2 handles external inputs and outputs.
The system can be expanded with several Basic, I/O units
and other CAN nodes in the Smartpack family, all
connected via the CAN bus.

SYSTEM BUILDING BLOCKS


End user monitoring directly
through the ENU/Web interface
End user monitoring network
& equipment that uses TCP/IP
protocols such as SNMP

3G/GPRS

Eltek Multi Site Monitor (MSM)

KEY FEATURES

SCREEN
High contrast, high resolution TFT color display for easy
user-menu navigation

LAN LINE

VISUAL LEDS FOR LOCAL ALARMS


(Major, Minor, Power ON)

ETHERNET

Smartpack2 Master
WIRELESS

Monitoring and control via WEB Browser Ethernet port with HP


Auto MDI/MDI-X for detection and correction for straight-through
and crossover cables.

SNMP PROTOCOL

TRAP, SET and GET on ethernet. Email of TRAP alarms

PROGRAMMABLE RELAY OUTPUTS

6 programmable outputs for traditional remote monitoring.


Expandable with I/O Monitor CAN Nodes.

CAN 1

PROGRAMMABLE MULTIPURPOSE INPUTS

6 programmable multipurpose inputs (digital inputs or analog


signals). Expandable with I/O Monitor CANNodes.

COMPREHENSIVE LOGGING
BACKUP OF CRITICAL CONTROL FEATURES IN BASIC

OR
SP2 Basic Industrial

UNIT.

CAN 1

AUTOMATIC BATTERY MONITORING AND TEST


BATTERY LIFETIME INDICATION
BATTERY USED AND REMAINING CAPACITY (AH OR %)
MONITORING
USER DEFINED ALARM GROUPING
(boolean logic for grouped alarms)

UPLOADING AND DOWNLOADING OF CONFIGU-

Optional CAN Node(s)

CAN 2

SP2 Basic

RATION FILES WITH SD CARD OR POWERSUITE


(Windows application).

SD CARD SLOT FOR DOWNLOADING/UPLOADING


OF LOGS AND SETUP

Power module(s)

COMPREHENSIVE GENERATOR/HYBRID/DC SOLAR


SYSTEM CONTROL AND MONITORING FEATURES

Power module(s)

Customer
equipment
RS-485/232
MODBUS-RTU

242100.50X.DS3 - rev. 5
Eltek Grterudveien 8, 3003 Drammen, Norway

Phone: +47 32 20 32 00 Eltek 2015 www.eltek.com

Smartpack2
SMARTPACK2 WEB INTERFACE - REMOTE MONITORING AND CONTROL

REMOTE MONITORING

LOCAL MONITORING
No PC? No problem!
The Smarpack2 high resolution display, allows the user easy
access to complete configuration and status messages without the use of an on-site PC.

Key system status parameters displayed by default:

alarms, battery voltage, rectifier current and load current.

Single key-hit to display list of triggered alarms.


All configurations and setup available from the menus.
High resolution and contrast excellent reading
and able to show complex content.

Multilanguage (changeable on the fly): English, Chinese


Through the internet or on-site directly from PC!

System overview with status as home page.


Graphs show changes over time of various system
variables.

Configure alarm limits and all other parameters



through self explanatory symbols and menus.


Security Protocols; SSL, Secure FTP server,
FTPS with SSL/TLS.
Download logs (event, energy, generator, battery,)

Simp., Chinese Trad., Russian, Norwegian and pending


languages: Finish, French, German, Greek, Italian,
Polish, Portuguese, Spanish, Swedish and Turkish.
Disable external alarms while servicing.
Access control pin code to change configuration

Setup data and logs bring your SD card.

Convenient storage for backup and transportation.


Easy and robust to roll out a set of systems with
identical setup.

242100.50X.DS3 - rev. 5
Eltek Grterudveien 8, 3003 Drammen, Norway

Phone: +47 32 20 32 00 Eltek 2015 www.eltek.com

Smartpack2
SMARTPACK2 MASTER

3.2 Graphical TFT, high resolution color display


Ethernet for remote or local monitoring and
control via responsive WEB Interface

Front GUI fault finding in One click


SD Card slot
Multi language menu

SMARTPACK2 BASIC

Located inside the system only available to service


personnel.

Powers all control units attached to the CAN bus.


Handles LVD control.
Takes control of critical system function in case of a
Master Controller failure.

Short of CAN power or LVD control add more Basic units

SMARTPACK2 BASIC INDUSTRIAL

Full high-voltage range 110Vdc and 220Vdc


Positive and floating distribution
Earth fault detection
Additional voltage measurements without adding CAN Nodes
High(er) resolution current sense inputs for better accuracy
Serial ports for special communication protocols
Data center 380Vdc system compatible
High capacity systems, up to 960 power modules

CAN NODES (OPTIONAL)

AC Mains Voltage, current, frequency and energy






consumption
Battery symmetry, current and fuse monitoring
Alarm outputs and control inputs
Load branch current and fuse
Climate control of fan/filter cabinets
Generator control/fuel tank level measurements

242100.50X.DS3 - rev. 5
Eltek Grterudveien 8, 3003 Drammen, Norway

Phone: +47 32 20 32 00 Eltek 2015 www.eltek.com

Smartpack2
CONTROL FEATURES
Control system

Battery

Rectifier

Generator

Output Voltage

Battery Current

Available information

On/Off control for cyclic

Measurement
Load Current Calculation
Energy Calculation
Load/Battery Disconnect
Real Time Clock with
Battery Backup
Stored Site Text/
ID and Messages
Position (long/lat) for
auto placement
Test of Relay Outputs
Alarm grouping of events
for relay outputs

Measurement
Battery Temperture
Measurement
Battery Testing (acc.
to discharge table
or set time limit)
Setup of Battery Data/Table
Battery Capacity Indication
Battery Boost Charging
-Auto Ah discharge or
voltage threshold
-Interval or Manual
Temperature Compensated Charging
Charge Current Limitation
Battery Low Voltage Disconnect
-Temperature dependent
(optional)
-Mains independent (optional)

about each rectifier, e.g.


serial number, version,
internal temperature
Individual Rectifier Current Measurement
Individual Rectifier Input Voltage
Efficiency Management
Emergency Voltage
Startup delay
Detailed internal
alarms summary
Current ramp control
for Data Centers

charging and fuel reduction

Start-up delay of
power system

Fuel consumption logging




and alarming based on


tank level measurement
Discharge cycle counter/
Generator run hour logging
DoD [%] logging w/
time stamp
Generator On/Off based
on battery voltage

ALARMS/EVENTS AVAILABLE
Power & control system

Load

Battery

Rectifier

AC Mains Low (2-level)


AC Phase Volt-

Load Disconnect

Battery Voltage (4-lev-

age x3 (2-level)

Digital Inputs (programmable descriptions)

Events trigger by inputs

- Service mode (block


relays)
-Generator running
-Lower charge current limit
-Battery test
-Boost inhibit
-Emergency low voltage
-Clear manual reset alarms.

-Voltage or Timer (from


mains failure) based
-Mains independent
(optional)
Load Fuse
Load Current

el, optional 8-level)


Battery Temperature (2-level)
Battery Used Capacity (2-level) [Ah or %]
Battery Remaining Capacity (2-level) [Ah or %]
Battery Fuse
Symmetry Failure (2-level)
-Only with BM Can Node
Battery Quality after test (2-level)
Battery Current (4-level)
Battery Life Time (2-level)
[from temperature log]

Rectifier Failure (2-level)


Rectifier Capacity (2-level)
Rectifier Current (2-level)
Rectifier Avg. Temperature (2-level)
Rectifier Current
Share (2-level)

Note:
Alarms can be set up with monitoring of minor and major levels. Hysteresis and time delay is user configurable. All average
and peak levels on analogue values are auto logged in Event log

242100.50X.DS3 - rev. 5
Eltek Grterudveien 8, 3003 Drammen, Norway

Phone: +47 32 20 32 00 Eltek 2015 www.eltek.com

Smartpack2
SPECIFICATIONS
MASTER
Part number

242100.500

Power consumption

Max 4.5W

MTBF

> 1 300 000 hours Telcordia SR-332 Issue I, method III (a)
(Tambient : 25C)

Display

32k colour TFT QVGA (320x240)

10/100 BASE-T
HP Auto MDI/MDI-X

Ethernet port
Removable media

SD card

SNMP

v1, v2c, v3 GET, SET & TRAP

Web

Webpower; XHTML 1, java script, SSL

Networking

SMTP Client and NTP Client, FTP, FTPS/TLS

Event log

10 500 time stamped events

Data log

10 000 time stamped values of 10 user defined monitoring points

Dimensions (WxHxD)

156 x 72 x 38 mm / 6,4 x 3 x 1,6

BASIC
Part number

242100.501

Operating temperature

-20 to +70C (-4 to 158F)

Storage temperature

-40 to +85C (-40 to 185F)

Input voltage

20-172 VDC (20 -75 VDC***) Shutdown: < 18 VDC

Power consumption

Max 1.5A Max 4.5A (3x LVD max loaded)

Contactor outputs

3 x LVD control outputs

Configurable inputs

3x NO/NC/Temperature: NTC probe

System connections:
Voltage sense
Current sense
Battery fuse*
Load fuse*

24V, 48V, 60V & 110V** systems


0-20mV and 0-60mV range shunts
Battery fuse sense, Open/Closed
Load fuse sense, Open/Closed, Pull- Up/Down, Diode Matrix

Ground fault

Simple bridge circuit detection

Max basic nodes

8 units on a single CAN-bus

Dimensions (WxHxD)

155 x 35 x 80 mm / 6.4 x 1.4 x 3.3

BASIC INDUSTRIAL
Part number

242100.601

Operating temperature

-20 to +70C (-4 to 158F)

Storage temperature

-40 to +85C (-40 to 185F)

Power consumption

Max 1.6A

Electric isolation

7 different isolated sections

Customer connections:
Configurable Inputs

3x, digital, temperature / voltage /current measurements.


- NO/NC, Pull Up/Dn, Diode Matrix: -10V> +10V (2mV full range)
- Current measurements: 4-20mA (ext. sense resistor 100-500)
- Temperature measurements: NTC probe
Table continues on next page
Specifications are subject to change without prior notice

242100.50X.DS3 - rev. 5
Eltek Grterudveien 8, 3003 Drammen, Norway

Phone: +47 32 20 32 00 Eltek 2015 www.eltek.com

Smartpack2
BASIC INDUSTRIAL - CONTINUED

Relay outputs

3x, NO-C-NO, 0-220V, 30W (max. 1A), configurable

Serial communication

RS232C port and RS485 port

System connections:

Voltage sense inputs

3x, Max. 420VDC, Symmetry& battery monitoring

Current sense inputs

2x, for 20mV to 60mV current shunts

Battery fuse sense inputs

1x, NO/NC, Pull Up/Dn, Diode Matrix: -10V> +10V (2mV full range)

Load fuse sense inputs

1x, NO/NC, Pull Up/Dn, Diode Matrix: -10V> +10V (2mV full range)

LVD contactor outputs

3x, 10-420V, 1A, Configurable as latching or non-latching


LVD Supply input: 10-420V, 1A

CAN interface

2 x, CAN bus systems (separated and isolated)

Earth fault detection

1x, internal Isolation input

Power system compatibility

Industrial & Telecom, Positive, negative and floating DC distributions

Max number of controller nodes

10 on a single CAN-bus, in addition to Smartpack2 Master controller

Controller configuration

Front keys in the Smartpack2 Master controller, via CWUI in an


standard web browser (Controllers Web-based User Interface)
and via PowerSuite application

Dimensions

(WxHxD) 146.0 x 146.0 x 45.6 mm / (5.7 x 5.7 x 1.8)

I/O MONITOR (TYPE 2)


Configurable Inputs

6x NO/NC/Analog Voltage [0-75V]

Alarm Outputs

6x RelayDry/Form C
[Max 75V/2A/60W]

Max I/O Monitors

14 units on a single CAN-bus

Power Consumption

Max 3.6W

Dimensions (WxHxD)

135.1 x 23.5 x 59mm / 5.3 x 0.9 x 2.3

CONTROL DEVICES/CAN NODES


Part no:

Description

242100.300

Battery Monitor

242100.301

Load Monitor

242100.304

I/O Monitor (Outdoor)

242100.306

I/O Monitor Type 3

242100.200

Smartnode RS232/485

242100.500

Smartpack2 Master

242100.501

Smartpack2 Basic

242100.601

Smartpack2 Basic Industrial

242100.603

Fleximonitor

242100.502

I/O Monitor Type 2

*Only Open/Closed for 110V **Basic ver. U1.3 ***Basic ver. 1.0 - 1.2
Specifications are subject to change without prior notice

242100.50X.DS3 - rev. 5
Eltek Grterudveien 8, 3003 Drammen, Norway

Phone: +47 32 20 32 00 Eltek 2015 www.eltek.com

You might also like