General conditions and function limitations, notes for configuration and operation
These notes take precedence over statements contained in other documents.
Because these notes contain important information for the installation and use of the software, please read them carefully.
Brief description
Circumstances
Possible work-around
Affected DO
Since version
SINAMICS_SW - General
TFS313093
When deleting an OA application in the drive using Starter, only the OA application
saved in the flash is deleted and not the OA application on the memory card. At the
next power cycle, the OA application is copied from the memory card back to the
flash.
4.7 HF1
TFS315275
The component number display in the alarm window in the web server in the
Component column is incorrect, and cannot be used.
None
4.7 HF1
The "Load to file system" function is not executed in the drive unit if the configuration
was carried out by the OEM, and the Profibus address was set greater than 99. The
drive unit then remains in the "Carry out first commissioning" state.
4.7 HF1
SINAMICS_SW - Upload/Download
TFS315790
SINAMICS_SW - DRIVE-CLiQ
TFS313140
The function for recognizing that two or more Control Units are connected to one
None.
DRIVE-CLiQ line is not reliable. Depending on topology and the time of the
connection, scheduled fault F01357 "Topology: Two Control Units identified on the
DRIVE-CLiQ line" may not be issued. Instead, the Control Unit that was inserted later
is ignored, or one of the Control Units will not be able to be operated once the system
has been switched on.
S120M
4.7 HF1
TFS313142
For an illegal DRIVE-CLiQ ring wiring, the message F01375 "Topology: Actual
Remove the DRIVE-CLiQ ring wiring, and then
topology, duplicate connection between two components" is issued, which is correct. switch off/switch on.
However, the message is not only issued for the drive object involved, but for all drive
objects, which is incorrect. If the ring wiring is disconnected, the faults cannot be
acknowledged.
4.7 HF1
4.7 HF1
SINAMICS_SW - EPOS
TFS313170
TFS313175
4.7 HF1
TFS313176
4.7 HF1
Restrictions for SINAMICS S120 / S150 software V4.7 incl. SSP for STARTER
In the operating mode traversing blocks and reference point approach, message
A07496 "EPOS: Enable not possible" is not output if the position controller has not
been enabled at the instant in time that the traversing blocks or reference point
approach mode was selected.
-1-
22.07.2014
SIEMENS
TFS
Brief description
Circumstances
Possible work-around
Affected DO
Since version
For the following parameters there are differences between offline and online
parameterization for telegram 390: r2081[8] "BI: Binector-connector converter status
word 2" , p2082[0,1,2,3,8,9,10,11] "BI: Binector-connector converter, status word 3"
For indices p2082[0,1,2,3,8,9,10,11] "BI: Binectorconnector converter status word 3" the
corresponding interconnections must be manually
established to the corresponding bits at the
DC_CTRL DO according to the table: 2082, 0,
53010, 8, 2082, 1, 53010, 10, 2082, 2, 53010, 12,
2082, 3, 53010, 14, 2082, 8, 53010, 0, 2082, 9,
53010, 2, 2082, 10, 53010, 4, 2082, 11, 53010, 6,
4.7 HF1
TFS313153
Select p2079 "IF1 PROFIdrive PZD telegram selection extended" = 396 results in
error message when downloading. On the CU, with p2079 "IF1 PROFIdrive PZD
telegram selection extended", erroneously, more telegrams are listed than are
actually supported. In case of doubt, the same selection as for p0922 applies.
4.7 HF1
TFS313183
This only involves PROFIBUS if diagnostic alarms are activated. If, when
acknowledging, several faults are simultaneously signaled as going, then while
acknowledging, a bit in the Profibus telegram is not consistent for a brief time.
None
4.7 HF1
4.7 HF1
Users are not aware of this, as the fault display in Step7 (HWCn) or TIA does not use
the ID-related diagnostics, but the status is derived from other telegram data
(ChannelErrorVector DS1).
SINAMICS_SW - PROFIBUS communication
TFS313137
TFS313636
If a CU320-2DP, configured using GSD, is operated with clock cycle synchronism via Switch off the CU320-2DP and switch on again.
PROFIBUS connected to a SIMOTION control system, after being downloaded to
SIMOTION with modified DP clock cycle, SIMOTION technology error 20005 type 1,
basic 0x1h can be output. Faults are present at the CU320-2DP, which cannot be
acknowledged.
4.7 HF1
4.7 HF1
TFS313155
4.7 HF1
4.7 HF1
With the setting "Fast flying restart" active (p1780 "Motor model adaptations
configuration" bit 11 "Fast flying restart with voltage model for induction motor" =1)
and a system with long motor cable (e.g. 100m) and a du/dt filter, starting and flying
restart for low speeds do not function. Fault F30001 "Power unit overcurrent".
TFS313166
Restrictions for SINAMICS S120 / S150 software V4.7 incl. SSP for STARTER
-2-
Vector
4.7 HF1
22.07.2014
SIEMENS
TFS
Brief description
Circumstances
Possible work-around
Affected DO
Since version
If odd-numbered dividers (for example: 1/3; 1/5 etc.) are used to calculate the pulse
frequency, and set in p1800 "Pulse frequency setpoint", when using safety without
encoder in the SERVO control, leads to Alarm C01711 "SI Motion P1 (CU): Defect in
a monitoring channel"/C030711 "SI Motion P2: Defect in a monitoring channel" with
fault value 3 or fault value 56.
4.7 HF1
4.7 HF1
SINAMICS_SW - Topology
TFS313177
After a POWER ON, sporadically it can occur that power units (S120M) are not
identified after powering up, and Alarm F07800 "Drive: No power unit present" is
output.
TFS314635
If a motor module or a CUAx with power module, which are available in the reference Carry out a power off/on. When doing this, it must be Vector
topology, are inserted in cyclic operation (Control Unit has already powered up and is ensured that the component is simultaneously
exchanging data), then an internal software error (F1000) that cannot be
switched on with the Control Unit.
acknowledged is output.
4.7 HF1
TFS328185
4.7 HF1
4.7 HF1
4.7 HF1
Error when calculating closed-loop control The drive remains in F1000 "Internal software error", if initially a switchover is made
parameters if a switchover to referred
to a referred unit (%, p505 "Selecting the system of units" =2/4) and then the
units was made prior to this
automatic calculation of the motor/closed-loop control parameter (p340 "Automatic
calculation motor/control parameters" =1) is initiated. In so doing, reference
parameter p2001 "Reference voltage" and the following are recalculated, and then
the appropriate limit is exceeded for the new calculation of the dependent parameter.
Restrictions for SINAMICS S120 / S150 software V4.7 incl. SSP for STARTER
Drive signals alarm 1711 " SI Motion P1 (CU): Defect in a monitoring channel" and
fault value 6165 or 6166, respectively 30711 and 6165 or 6166. These alarms cannot
be acknowledged. During the configuration of PROFIsafe, the settings on the IDevice and on the drive side can be changed separately. If a difference results
between the I-Device and drive side during the changes, the specified alarms are
triggered. According to the safety guidelines, these alarms cannot be acknowledged
and the drive cannot be started.