Calculo Overhead Ground Wire - OJO

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Methods to Determine Overhead Ground Wire Sizes in Distribution Systems

113

Methods to Determine Overhead Ground


Wire Sizes in Distribution Systems
Thanaphong Thanasaksiri 1 , Non-member
ABSTRACT
This paper presents an approach to analyze the
overhead ground wire (OHGW) sizes in distribution
system focus on the i2t of line to ground fault current.
For line to ground fault, the fault current and duration time when fault take place as well as the relay
operating time have been concerned. The Line Type
1, OHGW not connected to the neutral of substation power transformer, give the short circuit current
magnitude which is less than the current from Line
Type 2, OHGW connected to the neutral of substation power transformer. So the Line Type 1 gives the
smaller OHGW sizes than Line Type 2.
To find the suitable OHGW sizes, the fault current
magnitude, the duration time when fault take place
and the relay operating time have to be considered.
For the short circuit current is not greater than 3 kA,
the 25 mm2 can be used. For the short circuit current
is not greater than 7 kA, the 35 mm2 should be used
for distance of 500 m from the substation, 25 mm2
for line beyond that location should be used. For the
short circuit current is not greater than 12 kA, the
50 mm2 should be used for 500 m from substation,
35 mm2 should be used between 500 m-3 km and 25
mm2 for line beyond that location should be used.

Current splitting between OHGWs in one span is examined, and OHGW capabilities are presented.
To find the suitable OHGW sizes, the fault current
magnitude, the duration time when fault take place
and the relay operating time have to be concerned.
The relation between the current and time is shown
in (1).

kcm
t=
C 0i

(1)

Table 1: Constant C 0 of Three Materials as Temperature Varied


Temp
( C)
Cu
Al
Fe

50

100

200

300

500

1,000

10
16.7
29.2

7.78
12.2
21.6

5.59
9.21
16.5

5.13
7.92
14.3

4.36
6.70
12.2

3.62
5.51
10.2

Fusing
( C)
1084
657
1,600

Table 2: i2 t of OHGW Sizes


OHGW Size
25 mm2
35 mm2
50 mm2
70 mm2
95 mm2

1. INTRODUCTION

Manuscript received on July 31, 2009 ; revised on October


14, 2009.
1 The author is with The Department of Electrical Engineering ChiangMai University, 50200, Thailand, E-mail:
[email protected]

2.459 105

t = time, sec
kcm = conductor cross sectional area, kcm
(1 cmil = 5.067104 mm2 )
C 0 = constant as shown in Table 1

Keywords: Overhead Ground Wire, Distribution


System, Substation, Short Circuit Current, Relay

OHGWs are grounded conductors placed above


the phase conductors to intercept lightning strokes
which would otherwise directly strike the phases.
Lightning current is diverted to ground through a
pole ground lead. The approach to analyse the
OHGW wire size has been shown in [1]. The lightning
surge current is the first concern in this approach and
the line to ground fault is the other one. The other
methodology rating the OHGW size is described in
[2] which presents results showing the effect of various
system parameters on OHGW fault current requirements. The effect of grounding impedances, generator excitation systems, dc offsets and fault location.

i2 t Weaken (A2 -s)


2.35106
4.69106
1.00107
2.25107
3.84107

i2 t Melt (A2 -s)


4.81106
9.60106
2.05107
4.60107
7.86107

The duration time concerns with weaken and melting time for any conductors when fault occurred.
1. 1 Case 1 : Conductor Weaken
When the temperature goes up to 300 C the conductor begin to weaken. Let consider the OHGW of
five different sizes, 25 mm2 , 35 mm2 , 50 mm2 , 70 mm2
and 95 mm2 . From (1) and C 0 (14.3) from Table 1,
the value of i2 t can be found as shown in the second
column of Table 2.
1. 2 Case 2 : Conductor Melting
The melting point of Iron is 1600 C. From (1) and
C (10) from Table 1, the value of i2 t can be found as
shown in the third column of Table 2. The value in
Table 2 would be useful when consider the different
sizes of OHGW.
0

114

ECTI TRANSACTIONS ON ELECTRICAL ENG., ELECTRONICS, AND COMMUNICATIONS VOL.8, NO.1 February 2010

The Provincial Electricity Authority (PEA) uses


the relay operating time which is less than 0.1 s for
the distance of 500 m from substation, less than 0.5
s for the distance of 500 m-3 km from substation and
less than 1.0 s for the distance beyond 3 km from
substation.
2. SYSTEM MODELING
A section of a typical 22 kV overhead distribution
line has been modelled using ATPDraw [3] version of
EMTP. The configurations studied are shown in Fig.
1. Two line types have been investigated.

2. 3 Phase to Ground Fault Model


The single line to ground fault on phase A has been
simulated along the 22 kV overhead distribution line
by using ATPDraw. The pole number 1, 2, 3, 5, 8, 10,
20, 30, 40, 50, 60, 70, 80, 90 and 100 are the fault pole
locations. Fig. 2 shown the fault current path, If is
the total fault current from phase A to pole, IGndImp
is the current pass through grounding impedance ,
IGwRight is the current flow to the right through the
overhead ground wire, IGwLef t is the current flow to
the left through the OHGW.

2. 1 Line Type Model


Line type 1 : OHGW not connected to the neutral of substation power transformer. Line Type 2
: OHGW connected to the neutral of substation
power transformer as found in [4]. The grounding
impedances of the line are 5 and 25 and the ground
grid resistance is 1 . The line span 40 m (100 poles)
has been modelled.

Fig.2: Current Flow Direction of Phase to Ground


Fault on Overhead Distribution Line Section

3. RESULTS
3. 1 Short Circuit Current from Simulation
Fig. 3-6 shown the results of each current path
from the simulation using ATPDraw.

Fig.1: Typical 22 kV Overhead Distribution Line


Section

2. 2 Power Transformer Model


The wtrafo3.exe and BCTRAN in ATPDraw have
been used for transformer model. The parameters of
power transformer used for the simulation is shown
in Table 3.
Table 3: Parameters for Substation Power Transformer
Short
Circuit Test
Impedances

Losses(kW)

HVHVLV- HVHVLVLV
TV
TV
LV
TV
TV
15.13% 26.21% 8.7% 143.5 201.17 201.17

Open
Circuit
Test
Losses
(kW)
23.6

Fig.3: Phase to ground fault current along the line,


Line Type 1, 5 grounding impedance
In Fig. 3 and 4 which is the case of Line Type
1, the If and IGwLef t currents go uphill when the
fault locations are placed on pole number 1 to 5 and
go downhill when the fault locations moved beyond
the pole number 6. Unlike the IGndImp and IGwRight
currents which go downhill from the substation to the
end of line. The grounding impedance plays a significant role to the fault current though. The fault current decreases as the grounding impedance increase.

Methods to Determine Overhead Ground Wire Sizes in Distribution Systems

115

In Fig. 5 and 6, Line Type 2, the fault current go


downhill except for the IGndImp and IGwRight which
goes uphill when the fault locations are placed on pole
number 1 to 5 and go downhill when the fault locations moved beyond the pole number 6. The grounding impedance affect to the fault current in the manner that the IGndImp and IGwRight currents decrease
as the grounding impedance increase. The decreasing of currents pushes the IGwLef t current increase
instead.
From Table 2, the relation between the current and
weaken time can be shown in Fig. 7 and Fig. 8 for
the relation between the current and melting time.

Fig.4: Phase to ground fault current along the line,


Line Type 1, 25 grounding impedance

Fig.7: Threshold of Damage Curves (weaken)

Fig.5: Phase to ground fault current along the line,


Line Type 2, 5 grounding impedance

Fig.8: Threshold of Damage Curves (melting)

Fig.6: Phase to ground fault current along the line,


Line Type 2, 25 grounding impedance

Table 4 shows the melting current magnitude for


different OHGW sizes of Line Type 1 and 2 at 5
footing impedance from the simulation. Table 5
shows the melting duration time correspond to the
melting current from Table 4. Table 6 shows melting
current magnitude for different OHGW sizes of Line
Type 1 and 2 at 25 footing impedance from the
simulation. Table 7 shows the melting duration time
correspond to the melting current from Table 6.
From Table 4-7, the Line Type 1 gives the short
circuit current magnitude which is less than the short

116

ECTI TRANSACTIONS ON ELECTRICAL ENG., ELECTRONICS, AND COMMUNICATIONS VOL.8, NO.1 February 2010

Table 4:
Melting Current Magnitude at 5
Grounding Impedance
Line
Type
1
2

Melting Current Magnitude (kA) for Different OHGW Sizes


25 mm2
25 mm2
50 mm2
70 mm2
95 mm2
7.26
10.25
14.79
22.43
29.34
14.29
20.18
29.46
44.14
57.73

Table 5: Melting Duration Time at 5 Grounding


Impedance
Line
Type
1
2

Melting Duration Time (s) for Different OHGW Sizes


25 mm2
25 mm2
50 mm2
70 mm2
95 mm2
0.0913
0.0458
0.0215
0.0096
0.0056
0.0236
0.0118
0.0055
0.0025
0.0014

Table 6:
Melting Current Magnitude at 25
Grounding Impedance
Line
Type
1
2

Melting Current Magnitude (kA) for Different OHGW Sizes


25 mm2
25 mm2
50 mm2
70 mm2
95 mm2
5.35
7.55
11.02
16.51
21.60
15.48
21.86
31.92
47.83
62.55

Table 7: Melting Duration Time at 25 Grounding


Impedance
Line
Type
1
2

Melting Duration Time (s) for Different OHGW Sizes


25 mm2
25 mm2
50 mm2
70 mm2
95 mm2
0.1682
0.0845
0.0396
0.0198
0.0103
0.0201
0.0101
0.0047
0.0021
0.0012

circuit current from Line Type 2. So the Line Type


1 gives the smaller OHGW sizes than Line Type 2.
For Line Type 1, as the grounding impedance getting higher, the duration time increase. On the other
hand, for Line Type 2, the duration time decrease
when the grounding impedance increase. Both of
them are the minimum duration time for the maximum fault current flow through the OHGW.
3. 2 OHGW Sizes from Calculation

500 m-3 km and the 95 mm2 beyond that location


should be used. For the short circuit current is not
greater than 12 kA, the 50 mm2 should be used for
500 m from substation, 95 mm2 should be used between 500 m-3 km and the OHGW size greater than
95 mm2 for line beyond that location should be used.
3. 3 OHGW Sizes from Calculation and Simulation
Consider the maximum short circuit current, If,
along the line from the simulation in Fig. 3-6. The
short circuit current decreased when the short circuit
location move out from the substation. The reduced
short circuit current means the 10 kA short circuit
current is reduced to 8.5 kA for the distance of 500
m-3 km from substation and reduced to 4.2 kA for
the distance that is greater than 3 km from substation. The reduced short circuit current means the 12
kA short circuit current is reduced to 8 kA for the
distance of 500 m-3 km from substation and reduced
to 4 kA for the distance that is greater than 3 km
from substation. This implies that the OHGW sizes
from Table 8 can be reduced to the sizes shown in
Table 9.
Table 9: OHGW Sizes from Calculation and Simulation Using Reducing Short Circuit Current
Short Circuit
Current (kA)
3
7
10
12

OHGW Sizes (mm2 ) at Different


Substation [time]
500 m
500 m-3 km
25 [0.5350]
25 [0.5350]
35 [0.1959]
50[0.9263]
50 [0.2046]
70[0.6359]
50 [0.1421]
70 [0.7179]

Distance from
> 3 km
25[4.8147]
35[1.8145]
50[1.1600]
50[1.2789]

Table 8 shows OHGW sizes at different constant


short circuit current magnitude (3, 7, 10 and 12 kA)
for the different distance from substation and also
the melting time in seconds (numbers in parenthesis). The 500 m from substation corresponds to the
relay operating time which is less than 0.1 s. The
500 m-3 km from substation corresponds to the relay
operating time which is less than 0.5 s. The 3 km
from substation corresponds to the relay operating
time which is less than 1.0 s.

For the short circuit current is not greater than 3


kA, the 25 mm2 can be used. For the short circuit
current is not greater than 7 kA, the 35 mm2 should
be used for distance of 500 m from the substation, 50
mm2 between 500 m-3 km and the 35 mm2 beyond
that location should be used. For the short circuit
current is not greater than 12 kA, the 50 mm2 should
be used for 500 m from substation, 70 mm2 should
be used between 500 m-3 km and 50 mm2 for line
beyond that location should be used.

Table 8: OHGW Sizes from Calculation Using Constant Short Circuit Current 2

Table 10: OHGW Sizes from Calculation and Simulation Using Reducing Current along OHGW

Short Circuit
Current (kA)
3
7
10
12

OHGW Sizes (mm ) at Different Distance from


Substation [time]
500 m
500 m-3 km
> 3 km
25 [0.5350]
25 [0.5350]
35 [1.0665]
35 [0.1959]
70 [0.9377]
95 [1.6093]
50 [0.2046]
95 [0.7859]
50 [0.1421]
95 [0.5458]
-

For the short circuit current is not greater than


3 kA, the 25 mm2 can be used for the distance of 3
km from substation and 35 mm2 from that location
should be used. For the short circuit current is not
greater than 7 kA, the 35 mm2 should be used for distance of 500 m from the substation, 70 mm2 between

Short Circuit
Current (kA)
3
7
10
12

OHGW Sizes (mm2 ) at Different


Substation [time]
500 m
500 m-3 km
25 [0.5350]
25 [4.8147]
35 [0.1959]
25[0.9102]
50 [0.2046]
35[0.5999]
50 [0.1421]
35 [0.5999]

Distance from
> 3 km
25[19.259]
25[3.3436]
25[1.2037]
25[1.2037]

To determine the suitable OHGW sizes. Consider the current distribution of IGwLef t and IGwRight
along the OHGW from the simulation in Fig. 3-6.
The short circuit current decreased when the short
circuit location move out from the substation. The
reduced short circuit current means the 10 kA short

Methods to Determine Overhead Ground Wire Sizes in Distribution Systems

circuit current is reduced to 4 kA for the distance of


500 m-3 km from substation and reduced to 2 kA for
the distance that is greater than 3 km from substation. The reduced short circuit current means the 12
kA short circuit current is reduced to 4 kA for the
distance of 500 m-3 km from substation and reduced
to 2 kA for the distance that is greater than 3 km
from substation. This implies that the OHGW sizes
from Table 9 can be reduced to the sizes shown in
Table 10.
From Table 10, for the short circuit current is not
greater than 3 kA, the 25 mm2 can be used. For the
short circuit current is not greater than 7 kA, the 35
mm2 should be used for distance of 500 m from the
substation and 25 mm2 beyond that location should
be used. For the short circuit current is not greater
than 12 kA, the 50 mm2 should be used for 500 m
from substation, 35 mm2 should be used between 500
m-3 km and 25 mm2 for line beyond that location
should be used.
4. CONCLUSIONS
The Line Type 1, OHGW not connected to the
neutral of substation power transformer, give the
short circuit current magnitude which is less than the
current from Line Type 2, OHGW connected to the
neutral of substation power transformer. So the Line
Type 1 gives the smaller OHGW sizes than Line Type
2.
The suitable OHGW sizes for line to ground fault
when concerned with the short circuit current magnitude, duration time and relay operating time can
be found. For the short circuit current is not greater
than 3 kA, the 25 mm2 can be used. For the short
circuit current is not greater than 7 kA, the 35 mm2
should be used for distance of 500 m from the substation and 25 mm2 beyond that location should be
used. For the short circuit current is not greater than
12 kA, the 50 mm2 should be used for 500 m from
substation, 35 mm2 should be used between 500 m-3
km and 25 mm2 for line beyond that location should
be used.
5. ACKNOWLEDGEMENT
This project was conducted with the supports
of PEA, Thailand, in collaboration with ChiangMai
University, Thailand. The author would like to express their appreciation of these supports.
References
[1]

[2]

T. Thanasaksiri, An Approach to Analyze the


Overhead Ground Wire for Distribution Lines,
Proceedings of The IASTED International Conference, Nov 28-Dec 1, 2004, Clearwater Beach,
Florida, USA.
S. R. Lambert, Minimum Shield Wire SizeFault Current Considerations, IEEE Transac-

[3]
[4]

117

tions on Power Apparatus and Systems, vol.


PAS-102, No. 3, Mar. 1983.
L. Prikler, H. K. Hidalen, ATPDraw version
5 for Windows 9x/NT/2000/XP/Vista, 2008.
L. M. Popovic, Practical Method for Evaluation Ground fault Current Distribution in Station, Towers and Ground Wire, IEEE Transaction on Power Delivery, vol. 13, pp 123-128, Jan.
1998.

Thanaphong Thanasaksiri received


the bachelor degree in electrical engineering from Kings Mongkut Institute
of Technology Ladkrabang, Thailand, in
1994 and master of science in electrical engineering from Clemson University, USA, in 1997. His current research interests include, power system
analysis, transient overvoltages in power
and telecommunication systems, modeling of system transients using EMTP
and analysis of power system protection under system transients.

You might also like