Characterization of Frictional Interference in Closelyspaced Reinforcements in MSE Walls
Characterization of Frictional Interference in Closelyspaced Reinforcements in MSE Walls
Characterization of Frictional Interference in Closelyspaced Reinforcements in MSE Walls
--Armin W. Stuedlein, PhD, PE, Principal Investigator, James J. Walters, and Andrew W. Strahler
School of Civil and Construction Engineering, Oregon State University, Corvallis, OR
This material was also supported by the National Science Foundation under Grant No. CMMI 1100903.
PROBLEM STATEMENT
The use of reinforced earth in the United States began in 1972; since then,
Mechanically Stabilized Earth (MSE) walls have grown in popularity, and can be
found along nearly every state and interstate highway corridor. Due to their
inherent flexibility, MSE walls are being constructed to greater heights, in nonlinear geometries, with multiple tiers and with very tight reinforcement spacing.
For example, the four-tier West MSE wall at Sea-Tac International Airport (STIA
see Fig. 1) was recently constructed to 46 m height, and is now the tallest wall in
the Western Hemisphere (Stuedlein et al. 2010a). Tall walls (i.e., greater than 15
m in height) will proliferate due to increasing urbanization, right-of-way issues,
and wetland mitigation; in other words, they offer a sustainable alternative to
conventional grade separation, due to reduced mining and hauling of earth
materials and reduced footprint. However, our understanding of the working
stress behavior, including reinforcement strains and displacements, of tall, single
and multi-tier walls is unsatisfactory. The research proposed herein aims to
address one of several knowledge gaps in the understanding of tall MSE wall
behavior: prediction of reinforcement loads impacted by frictional interference of
closely-spaced reinforcements associated with tall walls and/or walls in
seismically active regions.
6 mm
2 mm
(a)
(e)
(d)
(f)
50 mm
(c)
125 mm
Fig. 4 Views of soil test boxes: (a) single strip pullout box and load frame, (b) view of instrumentation at the front of the
single strip pullout box, (c) external view of large multi-strip pullout box, (d) internal view of the multi-strip pullout
box, where up to nine strips can be tested simultaneously, (e) view of the partially filled large soil box, and (f) view at
front of the large soil box.
6 mm
(a)
(b)
100
The fill material used in this study was a well-graded sandy gravel, identical
to the fill material used in the 3RD Runway Project at SeaTac International
Airport. A comprehensive large-diameter triaxial test program was undertaken to
determine the stiffness and strength of the fill material for comparison to the
pullout test results. Figure 3a, 3b, and 3c shows typical stress-strain, principal
stress ratio-strain, and volumetric strain-strain curves for the densely compacted
fill material, respectively, whereas Figure 3d shows the variation of the friction
angle with effective confining pressure for a range in relative densities of the fill
material.
80
Pulloutload(kN)
Fig. 2 Steel ribbed reinforcement dimensions (a) elevation view, and (b) cross-section.
200-1-2
0
0
10-1-5
-4
6
8
Axial strain, 1 (%)
10
12
14
1000-1-1
100-1-3
500-1-3
50-1-3
300-1-1
20-1-4
10
200-1-2
10-1-5
60
(b)
(c)
R = 0.96
-3
55
-2
R = 0.97
'd (deg.)
0
0
50-1-3
20-1-4
Fig 1. Perspective aerial viewed from the northwest of the new third runway at Sea-Tac International Airport.
-1
0
50
45
'3/Patm = 0.096
40
2
0
20-1-4
300-1-1
50-1-3
500-1-3
10
(d)
35
100-1-3
1000-1-1
0.1
1
Normalized effective confining pressure, '3 /Patm
Fig. 3 Constitutive behavior of the sandy gravel fill material from large-diameter triaxial strength tests: (a) principal
stress difference versus axial strain, (b) principal stress ratio versus axial strain, (c) volumetric strain versus axial
strain, and (d) peak drained friction angle versus normalized confining stress.
4
Current design model
2
0
20
40
60
80
50
100
150
200
250
300
350
Fig. 5 Results of single-strip pullout tests: (a) load-displacement response for various overburden pressures, and
(b) apparent friction coefficient as a function of overburden pressures deduced from this and other studies.
100-1-3
1
20kPa1
Pmax
v As
Present study
10
LoadMultiplierforCenterStrips
'1 / '3
300-1-1
50kPa2
f*
Displacement(mm)
(b)
500-1-3
75kPa1
40
1000-1-1
100kPa2
150kPa1
60
10
200kPa1
20
10
(a)
12
20 mm
(b)