How To Select The Suitable OLTC
How To Select The Suitable OLTC
How To Select The Suitable OLTC
MR Germany
Oliver Khne
Gnter Panzer
Maneesh Mandapathil
Order Processing
India, OEMs
India
I.
14.12.2011
Page 2
14.12.2011
Page 3
Example:
80 MVA
3
Vector group
YNyn0
230 kV
+ 15 %
n = Number of steps
+ 12 steps
Umax = 264,5 kV
Umin = 195,5 kV
U st
Connection type
reversing
R U
n 3
1660V
I max
S
U min
236A
V III 250 Y not suitable! TD V, page 4
14 27 3W
Maschinenfabrik Reinhausen GmbH 2008
Page 4
Ua
Distance b:
Consider MR factor 2
TD M, page 20
Ub
R U
2
3
R
U
2
Ua
Ub
0.3 230kV
2
3
0.3
230kV
2
19.9kV
34.5kV
14.12.2011
Page 5
245 kV
Graded insulation
72.5 kV
123 kV
170 kV
TD M, page 6
14.12.2011
Page 6
At line end
in the center
14.12.2011
Page 7
Example:
120 MVA
3
Dyn11
Umax = 142.6 kV
132 kV
Umin = 121.4 kV
+8%
n = Number of steps
+ 8 steps
U st
Connection type
reversing
R U
n
1320V
I max
S
U min 3
329.4 A
10 19 3W
Maschinenfabrik Reinhausen GmbH 2008
14.12.2011
Page 8
Ub
U max
Ub
Ua
R
U
2
Ua
0.16
132kV 10.6kV
2
TD VV, page 5
TD M, page 6
14.12.2011
Page 9
TD VV, page 5
3x M I 351 -170/B-10 19 3W
TD M, page 6
14.12.2011
Page 10
Insulation to ground f: U b
Ub
Distance a:
Ua
R
U
2
Ua
0.16
132kV 10.6kV
2
Distance b:
Ub
R
U
2
Ub
0.16
132kV 10.6kV
2
b"
a"
U max
14.12.2011
Page 11
b & f: 650 kVp / 275 kVrms (as per IEC for U=132kV)
a"
14.12.2011
Page 12
Ub
U
2
Ub
132kV
2
Ua
0.16
132kV 10.6kV
2
0.08 132kV
76.6kV
Distance a:
Ua
R
U
2
TD VV, page 5
3x M I 351 -123/B-10 19 3W
TD M, page 6
14.12.2011
Page 13
b & f: 650 kVp / 275 kVrms (as per IEC for U=132kV)
According to technical data book we now need to go for Um =170 kV for M-type OLTC
VV III 400 D-145-10 19 3W
3x M I 351 -170/B-10 19 3W
TD M, page 6
14.12.2011
Page 14
U2
14.12.2011
Page 15
Example:
100 MVA
3
Vector group
YNa0d11
230 kV
Umax = 264.5 kV
Umin = 195.5 kV
138 kV
+ 15 %
n = Number of steps
+ 10 steps
U st
Connection type
reversing
R U
n 3
1992V
I max
S
U min
296A
V III 350 D not suitable!
12 23 3W
Maschinenfabrik Reinhausen GmbH 2008
14.12.2011
Page 16
Example:
Distance a:
Ua
R
2
Distance b:
Ub
R
U
2
Consider MR factor 2
U
3
Ua
0.3 230kV
2
3
Ub
0.3
230kV
2
19.9kV
34.5kV
14.12.2011
Page 17
EV1104
U1
U1
U2
U2
14.12.2011
Page 18
TD M, page 6
TD VRC, page 15
Maschinenfabrik Reinhausen GmbH 2008
14.12.2011
Page 19
Page 20
insulation to ground f: 650 kVp / 275 kVrms (as per IEC for U=138kV)
In line with technical data book we confirm selection of
3x M I 351 - 300 / D -12 23 3W
for connection as per figure 2a
14.12.2011
Page 21
KPLC
Kenya
KPLC schematic
- Price is more representative (Quoted price comes very close to final price in case of order)
14.12.2011
Page 22
14.12.2011
Page 23