Electrical Protection Devices
Electrical Protection Devices
Electrical Protection Devices
Contact us
Introduction
Protection against earth faults with RCDs | 2CSC 420 004 B0201 1
1
2
3
4
5
6
7
8
Introduction
Index
Brief history
1/2
Protection against earth faults with RCDs | 2CSC 420 004 B0201 1/1
Introduction
Brief history
Every year, many people are injured in electrical accidents
at home. Not everyone knows that many of these injuries
could be prevented by having RCD protection installed in the
houses consumer unit.
1/2
2CSC 420 004 B0201 | Protection against earth faults with RCDs
This ABB guide is also designed to help contractors communicate the benefits of RCD protection to customers.
ABB has always played a leading role in the development of Residual Current Devices, introducing ever more innovative devices on the market to satisfy its requirements.
Today, RCDs are widely used all over the world and ensure high levels of safety in the use of
electrical equipment.
It is not clear when and by whom the first RCD was developed, but it certainly appeared on the
market in the 1950s and was initially used by some utility companies to fight energy theft due
to the use of currents from phase to earth instead of phase to neutral.
With this aim, ABB built the first low sensitivity RCD in 1953 and a high sensitivity device in
1956. Residual Current Devices were later adopted to protect people against electric shock.
RCDs are now widely used in most of the world; in some cases this is required, while in others
their use is optional.
Protection against earth faults with RCDs | 2CSC 420 004 B0201 1/3
1/4
2CSC 420 004 B0201 | Protection against earth faults with RCDs
Index
Effects of current on the human body
2/2
2/4
Additional protection
2/7
Fire protection
2/8
2/9
Protection against earth faults with RCDs | 2CSC 420 004 B0201 2/1
The IEC 60479-1 Standard Effects of current on human beings and livestock is a guide about
the effects of current flowing through the human body to be used for the definition of electrical
safety requirements. This Standard shows, on a time-current diagram, four zones (Figure 1) to
which the physiological effects of alternating current (15 100 Hz) passing through the human
body have been related. Such zones are illustrated in Table 1.
c1 c2
c3
10000
5000
2000
1000
500
1
200
100
50
20
10
0.1
0.2
0.5
10
20
50
100
200
500
Figure 1: Time-current zones of the effects of alternating current on the human body
2/2
Protection against earth faults with RCDs | 2CSC 420 004 B0201
1000
2000
5000 10000
Zone
Effects
Usually no reaction
2
2
Usually no organic damage to be expected. Likelihood of cramp-like muscular contractions and difficulty in breathing; reversible disturbances of formation and conduction of
impulses in the heart, including atrial fibrillation and transient cardiac arrest without ventricular fibrillation increasing with current magnitude and time
Electricity causes a shock in us because it is an outside force that interferes with the internal
electricity our bodies nervous systems generate.
To fully understand why the chance encounter of these two electrical forces results in a shock
to our systems, we must first understand the fundamentals of electricity itself.
In scientific terms, electricity is considered a fundamental force, one that is extremely basic,
and has been in existence since the beginning of time.
Unfortunately, since the human body consists primarily of water, it too provides a superb conductor for electrical energy, or voltage.
If, by chance, outside electrical energy enters our bodies, now conductors, we will sustain
a shock when the voltage encounters, and interferes with, the internal electrical energy our
nervous systems produce. The shocks to our bodies, and the amount of damage the electricity
does to them, depends upon the voltage our bodies are subjected to, upon its level of energy,
and upon how much our bodies resist the flow of the electrical energy.
An electric shock is the pathophysiological effect of an electric current through the human
body.
Its passage essentially affects the muscular, circulatory and respiratory functions and sometimes results in serious burns. The degree of danger for the victim is a function of the magnitude
of the current, the parts of the body through which the current passes, and the duration of
current flow.
Curve C1 shows that when a current greater than 30 mA passes through a human being from
one hand to their feet, the person concerned is likely to be killed, unless the current is interrupted in a relatively short time.
The point 500 ms/100 mA close to the curve C1 corresponds to a probability of heart fibrillation of the order of 0.14%.
Protection of persons against electric shock must be provided for in LV installations in conformity with appropriate national standards and statutory regulations, codes of practice, official
guides and circulars, etc. Relevant IEC standards include: IEC 60364 series, IEC 60479 series,
IEC 60755, IEC 61008 series, IEC 61009 series and IEC 60947-2.
Protection against earth faults with RCDs | 2CSC 420 004 B0201 2/3
Indirect contact: an electric shock is received from contact with something connected to the
electrical installation which would not normally be expected to be live, but has become so as
the result of a fault.
2/4
Protection against earth faults with RCDs | 2CSC 420 004 B0201
placing parts out of reach or using obstacles to prevent people from reaching live parts. This
protection is reserved for locations to which only skilled or trained persons have access.
Protection against earth faults with RCDs | 2CSC 420 004 B0201 2/5
2/6
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Protection against earth faults with RCDs | 2CSC 420 004 B0201 2/7
Analysis of these phenomena shows that fire risk due to electricity is linked to overheating due
to a poor coordination between the maximum rated current of the cable (or insulated conductor) and the overcurrent protection setting.
Overheating can also be due to modification of the initial method of installation (addition of
cables on the same support).
This overheating can be the origin of electrical arcing in humid environments. These electrical
arcs evolve when the fault current-loop impedance is greater than 0.6 and exist only when
an insulation fault occurs. Some tests have shown that a 300 mA fault current can cause a real
risk of fire.
Id << 300 mA
Humid dust
Beginning of fire
Some tests have shown that a very low leakage current (a few mA) can evolve and, from 300
mA, cause a fire in humid and dusty environments.
2/8
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Protection against earth faults with RCDs | 2CSC 420 004 B0201 2/9
L1
L2
L3
N
RB
RA
Figure 1
IK
L1
L2
L3
N
RB
RA
IK
Figure 2
In this type of electrical installation, the neutral is usually distributed and its function is making
the phase voltage (e.g. 230 V) available for the supply of the single-phase loads of residential
installations.
2/10
Protection against earth faults with RCDs | 2CSC 420 004 B0201
TN system
In TN systems, the neutral is directly earthed, whereas the exposed conductors are connected
to the same earthing arrangement of the neutral. TN electrical systems can be divided into
three types depending on whether the neutral and protective conductors are separate or not:
1. TN-S: the neutral conductor N and the protective conductor PE are separated (Figure 3)
L1
L2
L3
N
PE
Figure 3
2. TN-C: the neutral and protective functions are combined into a single conductor, called PEN
(Figure 4)
L1
L2
L3
PEN
Figure 4
Protection against earth faults with RCDs | 2CSC 420 004 B0201 2/11
L1
L2
L3
N
PE
TN-C
TN-S
Figure 5
In TN systems, the earth fault current returns to the power supply node through a direct metal
connection (PE or PEN conductor) without practically affecting the earth electrode (Figure 6).
IK
L1
L2
L3
PEN
Figure 6
2/12
Protection against earth faults with RCDs | 2CSC 420 004 B0201
IT system
IT systems have no directly earthed active parts, but may have live parts connected to earth
through high impedances (Figure 7). All the exposed-conductive-parts, separately or in a
group, are connected to an independent earth electrode.
L1
L2
L3
Rt
Figure 7
The earth fault current returns to the power supply node through the earthing arrangement of
the exposed conductors and the line conductors earth capacities.
L1
L2
L3
C3 C2 C1
Figure 8
Rt
IK
Protection against earth faults with RCDs | 2CSC 420 004 B0201 2/13
Main application
10100 A
2
TT
Remarks
TN
IT
2/14
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Index
Reference standard for RCD use
3/2
3/3
Standard of RCDs
3/7
Types of RCDs
3/8
3/10
3/13
3/14
Marking on RCDs
3/16
Test button
3/17
Protection against earth faults with RCDs | 2CSC 420 004 B0201 3/1
All IEC International Standards are fully consensus-based and represent the needs of key
stakeholders of every nation participating in IEC work. Every member country, no matter how
large or small, has one vote and a say in what goes into an IEC International Standard. IEC
standards are recognised by almost all countries in the world.
The IEC standard is covered in Europe by CENELEC (European Committee for Electrical
Standardisation) which publishes the relevant EN standards. Every nation, referring to the
CENELEC, transposes and translates EN standards into national standards.
International Electrotecnical
Commission:
IEC standard
3/2
Protection against earth faults with RCDs | 2CSC 420 004 B0201
IK
L1
L2
L3
N
RB
RA
IK
Protection by automatic disconnection of the supply used in TT system is with RCDs of sensitivity:
I 6n
50 V
RA
Where:
RA is the resistance of the earth electrode for the installation []
I n is the rated residual operating current of the RCD
For temporary supplies (to work sites, ) and agricultural and horticultural premises, the value
of 50 V is replaced by 25 V.
The tripping times of RCDs are generally lower than those required in the majority of national
standards. The IEC 60364-4-41 specifies the maximum operating time of protective devices
used in TT system for protection against indirect contact as:
For all final circuits with a rated current not exceeding 32 A, the maximum disconnecting
time will not exceed the values indicated here below:
Uo [V]
T [s]
50 < Uo 120
0.3
0.2
0.07
Uo > 400
0.04
Protection against earth faults with RCDs | 2CSC 420 004 B0201 3/3
IK
L1
L2
L3
PEN
3
(TN-C)
PE
(TN-S)
To provide a protection for TN systems with automatic disconnection of the circuit, according
to IEC 60364-4 requirements, the following condition shall be fulfilled:
Zs
Ia
Uo
Where:
Zs is the impedance of the fault loop comprising the source, the live conductor up to the
point of the fault and the protective conductor between the point of the fault and the source
[];
Uo is the nominal a.c. r.m.s. voltage to earth [V]
I a is the current causing the automatic operation of the disconnecting protective device
IEC 60364-4-41 specifies the maximum operating time of protective devices used in TN system for protection against indirect contact:
For all final circuits with a rated current not exceeding 32 A, the maximum disconnecting time
will not exceed the values indicated in the table below:
Uo [V]
T [s]
50 < Uo 120
0.8
0.4
0.2
Uo > 400
0.1
3/4
Protection against earth faults with RCDs | 2CSC 420 004 B0201
L1
L2
L3
Ra
Ra
IK
A second earth fault on an IT system (unless occuring on the same conductor as the first fault)
results in a phase-phase or phase-to-neutral fault, and whether occurring on the same circuit
as the first fault, or on a different circuit, overcurrent protective devices would normally operate
an automatic fault clearance.
Ik
Ur
Rt
Where:
Rt is the total resistance, equal to the sum of the earth electrode (Ra) and the protective
conductor for the exposed conductive parts [];
Ur is the rated voltage between phases [V]
Disconnecting times for IT system depends on how the different installation and substation
earth electrodes are interconnected.
For final circuits supplying electrical equipment with a rated current not exceeding 32 A and
having their exposed conductors bonded with the substation earth electrode, the maximum
tripping time is given in the table below:
Uo [V]
T [s]
50 < Uo 120
0.8
0.4
0.2
Uo > 400
0.1
Protection against earth faults with RCDs | 2CSC 420 004 B0201 3/5
Application
Required
Recommended RCD
I6n [mA]
A/AC type
30...500
10...30
60364-4-482
30 and 300
60364-5-551
10...30
60364-7-701
10...30
60364-7-702
10...30
60364-7-703
10...30
300
500
300
10...30
10...30
10...30
IEC
B type
Q
60364-4-41
60364-7-704
60364-7-705
60364-7-706
60364-7-708
60364-7-712
3/6
Protection against earth faults with RCDs | 2CSC 420 004 B0201
300
Protection against earth faults with RCDs | 2CSC 420 004 B0201 3/7
RCCBs usually have a fault making and breaking capacity on the order of 1 kA. This means
that they can handle a fault of 1 kA on their own if it is a fault to earth. For overloads and line
to neutral short circuits, the Wiring Rules require other devices to provide protection. The
device used for short circuit protection may improve the short circuit rating of the RCCB when
they operate together. This allows an RCCB rated at, for example, 1000 A to be used in circuits where the actual fault level is higher than 1000 A.
In summary, RCCBs provide earth leakage protection, however a major point to remember
when applying them is that they must always be installed in conjunction with an appropriately
rated Short Circuit Protective Device (SCPD).
In
In
3/8
Protection against earth faults with RCDs | 2CSC 420 004 B0201
In
Protection against earth faults with RCDs | 2CSC 420 004 B0201 3/9
3/10
AC
Tripping
current
Protection against earth faults with RCDs | 2CSC 420 004 B0201
AC type RCDs are suitable for all systems where users have sinusoidal earth current. They are
not sensitive to impulsive leakage currents up to a peak of 250 A (8/20 wave form) such as
those which may occur due to overlapping voltage impulses on the mains (e.g.: switching of
fluorescent bulbs, X-ray equipment, data processing systems and SCR controls).
A type RCDs are not sensitive to impulsive currents up to a peak of 250 A (8/20 wave form).
They are particularly suitable for protecting systems in which the user equipment has electronic devices for rectifying the current or phase cutting adjustment of a physical quantity (speed
temperature, light intensity etc.) supplied directly by the mains without the insertion of transformers and class I insulated (class II is, by definition, free of faults to earth).These devices may
generate a pulsating fault current with DC components which the A type RCD can recognise.
In addition to detecting residual current waveforms of type A, residual current protective devices of type B are used to detect smooth DC residual currents. type B RCDs are recommended for use with drives and inverters for supplying motors for pumps, lifts, textile machines,
machine tools etc., since they recognise a continuous fault current with a low level ripple.
Tripping values defined up to 2 kHz.
Type AC and A RCDs comply with IEC 61008/61009; type B for RCDs is not mentioned in
these reference standards: an international standard, IEC 62423, has been introduced in 2007,
specifying additional requirements for type B RCDs.
This new standard, IEC 62423, should only be referred to together with IEC 61008-1 (for
RCCBs) and IEC 61009-1 (for RCD-blocks and RCBOs), this means that B type RCDs must be
compliant with all the requirements of IEC 61008/9.
In addition there are other two type of RCDs according to the wave form of the earth leakage
currents:
Type F
Type B+
Type F RCDs are for loads with single-phase inverters and similar equipment (e.g. modern
washing machines), as an extension of type A.
or type F RCDs, additional tests have been added to those for type A, in order to simulate the
ground fault in presence of a single phase inverter.
Type F is characterised by a strong immunity to unwanted tripping.
Type F RCDs are not sensitive to impulsive currents up to a peak of 3,000A (8/20 wave form).
Type F RCDs give better protection with the spread of modern electronic appliances in domestic installations, where type A RCDs could not properly cover them. It effectively fixes, in an
official way, the problem of unwanted tripping with a non-selective RCD.
In IEC 61008-1 and IEC 61009-1 (RCDs for housholder and similar applications) only type AC
and A RCDs are covered, types F and B are not mentioned. IEC 62423 ed. 2 covers both type
F and B RCDs and it can only be used together with IEC 61008-1 and IEC 61009-1.
At the moment, type B+ are only introduced in a DIN VDE 0664-100 specification applicable in
Germany. Like type B residual current protection devices, type B+ residual current protection
devices are suitable for use in alternating current systems. Tripping conditions for type B+ residual current protection devices are defined at up to 20 kHz and lie within this frequency range
below a tripping value of 420 mA.
Protection against earth faults with RCDs | 2CSC 420 004 B0201 3/11
Type of RCD
additional protection
contacts
A S (selective)
B S (selective)
3/12
multifrequency
alternating
alternating
pulsating
multifrequency
current
current up to
current with DC
current
current
50/60Hz
1000 Hz
components
generated by
generated by
the single-pha-
the three-pha-
se inverter
se inverter
AC
A S (selective)
B S (selective)
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Protection against earth faults with RCDs | 2CSC 420 004 B0201 3/13
3/14
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Protection against earth faults with RCDs | 2CSC 420 004 B0201 3/15
Manufacturers name
Test button
Rated current
Rated residual operating current [I6n]
Rated voltage [Un]
Rated making and breaking capacity [Im]
Wiring diagram
ABB identity number
3/16
Protection against earth faults with RCDs | 2CSC 420 004 B0201
If your RCD does not switch off the electricity supply to the protected circuits when the test
button is pressed, or if it does not reset, get advice from a registered electrician.
If you do not have RCD protection fitted in your consumer unit, it is strongly suggested to
protect yourself by contacting an installer to ask for it because if you damage a hidden cable
when fixing something to a wall, you wont be protected against electric shock unless you
have an RCD in your consumer unit protecting that circuit.
0
1
Protection against earth faults with RCDs | 2CSC 420 004 B0201 3/17
3/18
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Index
ABBs range
4/2
4/8
Protection against earth faults with RCDs | 2CSC 420 004 B0201 4/1
DDA200
DDA800
I6n [A]
S200
0.563
S800
6100
The RD DIN rail series are residual current relays with an external toroidal transformer can
detect leakage currents and it is possible to set selectivity and intervention time.
The ELR series are front panel residual current relays. ELR allows monitoring and protection
of the low voltage distribution network through the use of toroidal transformers.
Electronic RCBOs series DS271, DSN201. In only one module width, these DIN rail residual
current circuit-breakers with overcurrent protection offer a technologically advanced and
comprehensive range with outstanding features, sizes, tripping characteristics and accessories.
4/2
Protection against earth faults with RCDs | 2CSC 420 004 B0201
IEC 61009
Family name
DS201 - DS202C
Number of poles
1p+N, 2P
Sensitivity [mA]
Type
A, AC, APR
4500 (DS201 L)
6000 (DS201 - DS202C)
10000 (DS201 M - DS202C M)
Tripping curves
B, C, K
IEC 61008
Family name
F200
Number of poles
2P, 4P
Sensitivity [mA]
Type
Special versions
Protection against earth faults with RCDs | 2CSC 420 004 B0201 4/3
IEC 61009
Family name
Number of poles
2P, 3P, 4P
Sensitivity [mA]
30
Type
A, AC
Tripping curves
B, C, K
Family name
DDA200
Number of poles
2P, 3P, 4P
25, 40, 63
Sensitivity [mA]
Type
Special versions
To be used in conjunction with S200 MCBs (with equal or lower rated current)
4/4
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Family name
DDA800
Number of poles
2P, 3P, 4P
63, 100
Sensitivity [mA]
Type
To be used in conjunction with S800 MCBs (with equal or lower rated current)
IEC 62020
Family name
RD2
Sensitivity
from 30 mA up to 2 A
from 0 s (instantaneous) up to 5 s
Features
Test push-button
Reset push-button
Green ON LED that signals power supply presence
Red TRIP LED that signals relay operation
1 output contact
Protection against earth faults with RCDs | 2CSC 420 004 B0201 4/5
Standard
Family name
RD3
Sensitivity
from 30 mA up to 30 A
from 0 s (instantaneous) up to 10 s
Features
Test push-button
Reset push-button
Green ON LED that signals power supply presence
Red TRIP LED that signals relay operation
2 output contacts
RD3 M
RD3 P
like RD3 M + IDn% LED bar + autoreset setting + no trip test function
Operating voltage
[V]
ELR48P
ELR72
ELR72P
ELR96
ELR96P
ELR96PF
ELR96PD
24, 48,
24, 48,
24, 48,
24, 48,
24, 48,
110, 230,
110, 230,
110, 230
110, 230
110, 230
110,
110,
400 a.c.
400 a.c.
a.c./
a.c./
a.c./
230, 400
230, 400
24, 48,
24, 48,
24, 48,
a.c./
a.c./
115 d.c.
110 d.c.
115 d.c.
24, 48
24, 48
Frequency filter
Type
Sensitivity setting
[A]
from 0.03 to 30
[s]
from 0 to 5
d.c.
d.c.
Yes
Yes
I6n
Tripping time
setting 6t
4/6
Contacts
[no.]
Contact capacity
[A]
5 (250 V a.c.)
Dimensions
[mm]
48x48
72x722
72x72
96x96
96x96
96x96
96x96
Digital display
Yes
Standards
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Family name
DS271
Number of poles
1P+N
Sensitivity [mA]
Type
A, AC
10000
Tripping curves
B, C
DSN201
Residual current circuit breakers with overcurrent protection
Standard
Family name
DSN201
Number of poles
1P+N
6...25
10, 30
Type
A, AC
6000
Tripping curves
C
L1
L1
Electronic
trip unit
IF
FE
Protection against earth faults with RCDs | 2CSC 420 004 B0201 4/7
Instantaneous
APR
Selective
250
3000
5000
4/8
Protection against earth faults with RCDs | 2CSC 420 004 B0201
In [A]
I6 [A]
1xI6
1xI6
500 A
Generic
any
any
0.3
0.15
0.04
0.04
S (selective)
any
> 0.030
0.13-0.5
0.06-0.2
0.05-0.15
0.04-0.15
The indicated maximum tripping times are also valid for A type RCDs, but increasing the current values by a factor of 1.4 for RCDs with In > 0.01 A and of factor 2 for RCDs with In
0.01
The range of ABB RCDs also includes APR (anti-disturbance) devices which trip according to
the limit times allowed by the Standards for instantaneous RCDs. This function is due to the
slight tripping delay (approx. 10 ms) relative to the standard instantaneous ones.
The graph shows the comparison of the qualitative tripping curves for:
a 30 mA instantaneous RCD
a 30 mA APR instantaneous RCD
a 100 mA selective RCD (type S)
T (s)
0,5
0,3
0,2
0,15
0,13
APR 30 mA
Selective 300 mA
Tripping time
0,10
0,06
0,05
0,04
0,01
Instantaneous 30 mA
Idn (mA)
0
30
Ist. 30 mA
Sel. 300 mA
Idn
60
2 x Idn
100
150
300
600
1500
Idn
2 x Idn
5 x Idn
5 x Idn
Protection against earth faults with RCDs | 2CSC 420 004 B0201 4/9
Advantages
Compared with the devices which are normally used in emergency circuits, DDA 200 AE
blocks have the following advantages:
positive safety
no unwanted tripping if there is a temporary reduction or interruption of the mains voltage
efficient immediate operation even after long off-service periods of the installation
Use
Application of the DDA 200 AE blocks complies with the requirements of IEC 60364-8. They
are therefore suitable, for example, for escalators, lifts, hoists, electrically operated gates, machine tools, car washes and conveyor belts.
No more than one DDA 200 AE can be controlled using the same control circuit. Each DDA
200 AE requires a dedicated control circuit.
L max
1
W 1.5 mm
4
Y1Y2
NAE
RAE/2
RAE/2
RAE/2
RAE/2
1
NAE
3
6
1
2
3
4
5
6
Polarised relay
Sensor winding
Induction toroid
Supplementary primary windings
Single or multiple push-button unit
Test button
4/10
Protection against earth faults with RCDs | 2CSC 420 004 B0201
DDA202 A AE
L max = 230 m
DDA203 A AE
L max = 60 m
DDA204 A AE
L max = 230 m
N
Protection against earth faults with RCDs | 2CSC 420 004 B0201 4/11
RCDs 16 2/3Hz
F200 16 2/3 Hz are suitable for in distribution networks with frequency of 16 2/3 Hz: this kind
of network was developed at the beginning of 20th century for electrical traction systems
and is currently adopted in some European countries (e.g. Switzerland, Germany, Norway etc.)
4/12
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Index
ABB RCDs
5/2
Protection against earth faults with RCDs | 2CSC 420 004 B0201 5/1
AMERICA
Country
Approval
Canada
CSA
United States
UL
Argentina
IRAM
Brazil
UCIEE
Naval approval
Country
Approval
United States
ABS
ASIA OCEANIA
Country
Approval
Taiwan
BSMI
China
CCC
India
BIS-ISI
Singapore
PSB
Malaysia
SIRIM
Australia
OFT
New Zeeland
OFT
5/2
Protection against earth faults with RCDs | 2CSC 420 004 B0201
At the international level there are significant differences between the laws which apply in
relation to marks: there is the principle of territoriality of national marks, meaning the effects of
registration of a trade mark extend only to the territory of the state which has granted it.
The authority of the Country issues the CB certificates attesting that the products conform
to IEC standards, avoiding repetition of the admission tests by various foreign institutions to
whom the manufacturer may submit an application for certification of its products.
The manufacturer with CB certification can apply to use the mark of any foreign institution
which has agreed to approve the CB for that category of products and after dealing with
practices administrative provisions of the individual bank and get the granting of the relevant
mark if the standards of that Country do not provide for deviations from the IEC standards.
Otherwise the Institute abroad has the right to repeat any test, in particular those for which
national rules provide for deviations. The duration of the CB certificate is 3 years.
Every Nation has its own certification authority and a quality mark.
The obtained markings must be reported on the product.
Below is a map with main markings around the world
EUROPE
Country
Approval
Austria
VE
Belgium
CEBEC
Belarus
STB
Denmark
DEMKO
Finland
FIMKO
France
NF (LCIE)
Germany
VDE
UK
BSI
Italy
IMQ
Norway
NEMKO
Netherlands
KEMA-KEUR
Portugal
CERTIF
Russia
GOST_R
Spain
AENOR
Sweden
SEMKO
Switzerland
SEV
Ukraine
GOST_Uk
Naval approval
Country
Approval
France
BV
Norway
DNV
Germany
GL
UK
LR
Italy
RINA
Russia
Protection against earth faults with RCDs | 2CSC 420 004 B0201 5/3
5/4
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Index
Use of a 4P RCCB in a 3-phase circuit without neutral
6/2
6/4
6/7
6/10
Protection against earth faults with RCDs | 2CSC 420 004 B0201 6/1
5/6 7/8/N
2/1 4/3
6/5 8/7/N
In case of installation in a 3-phase circuit without neutral, if the concatenate voltage is between
110 and 254 V (277 V according to UL 1053) for the correct working of the test button there
are two possible solutions:
1) To connect the 3-phase to the terminals 3/4 5/6 7/8/N and the terminals 4/3 6/5 8/7/N
(supply and load side respectively)
2) To connect the 3-phase normally (supply to terminals 1/2 3/4 5/6 and load to terminals 2/1
4/3 6/5) and to bridge terminal 1/2 and 7/8/N in order to bring to the terminal 7/8/N the
potential of the first phase. In this way the test button is supplied with the phases concatenate voltage.
If the circuit is supplied with a concatenate voltage higher than 254 V, as in the typical case of
3-phase net with concatenate voltage of 400 V - or 480 V according to UL 1053 - (and voltage
between phase and neutral of 230 V or 277 V according to UL 1053), it is not possible to use
these connections because the circuit of the test button will be supplied at 400 V and could be
damaged by this voltage.
1/2 3/4
5/6 7/8/N
2/1 4/3
6/5 8/7/N
Rest
I6n
Rest [1]
0.03
3300
0.1
1000
0.3
330
0.5
200
In order to allow the correct operation of the test button also in 3-phase nets at 400 V - 480 V
according to UL 1053 - (concatenate voltage) it is necessary to connect the phases normally
(supply to terminals 1/2 3/4 5/6 and load to terminals 2/1 4/3 6/5) and to jump terminal 4/3
and 8/7/N by mean of an electric resistance as indicated above.
In this way, the test button circuit is fed at 400 V - 480 V according to UL 1053 - but for example in an RCCB with In=0.03 A there will be the Rest=3.3 kOhm resistance in series to the
test circuit resistance. Rest will cause a voltage drop that leaves a voltage less than 254 V in
the test circuit - 277 V according to UL 1053. Rest resistance must have a power loss higher
than 4 W.
In normal operation of the RCCB (test circuit opened) the Rest resistance is not powered, so it
does not cause any power loss.
6/2
Protection against earth faults with RCDs | 2CSC 420 004 B0201
1/2
3/4 5/6
2/1
4/3 6/5
Protection against earth faults with RCDs | 2CSC 420 004 B0201 6/3
25 A
40 A
63 A
80 A
100 A
125 A
SN201L/S201L Na
4.5
4.5
SN201/S201 Na
SN201M/S201M Na
10
10
S202L
10
10
S202
20
20
20
S202M
25
25
25
S202P
40
25
25
S802N
36
36
36
S802S
50
50
36
36
36
50
50
50
50
Fuse 25 gG
100
Fuse 40 gG
60
60
Fuse 63 gG
20
20
20
Fuse 100 gG
10
10
10
10
10
Fuse 125 gG
10
F 202
400-415 V circuits with isolated neutral (IT) under double faults
6/4
25 A
40 A
SN201N/SN201/SN201M
S201L/S201L Na/S202L
4.5
4.5
63 A
S201/S201 Na/S202
S201M/S201M Na/S202M
10
10
10
S201P/S201P Na/S202P
25
15
15
80 A
100 A
125 A
S801N/S802N
20
20
20
20
20
20
S801S/S802S
25
25
25
25
25
25
Protection against earth faults with RCDs | 2CSC 420 004 B0201
F 204
Three-phases circuits with neutral (y/D) 230-240 V/400-415 V*
25 A
40 A
63 A
80 A
100 A
125 A
SN201L/S201L/S201LNa*
4.5
4.5
SN201/S201/S201Na*
SN201M/S201M/S201MNa*
10
10
S202L*
10
10
S202*
20
20
20
S202M*
25
25
25
S202P*
40
25
25
S802N*
36
36
36
36
36
36
S802S*
50
50
50
50
50
50
Fuse 25 gG
100
Fuse 40 gG
60
60
Fuse 63 gG
20
20
20
Fuse 100 gG
10
10
10
10
10
Fuse 125 gG
6
10
F 204
Three-phases circuits with neutral (y/D) 230-240 V/400-415 V
25 A
40 A
S203L/S204L
4.5
4.5
63 A
S203/S204
S203M/S204M
10
10
10
S203P/S204P
25
15
15
80 A
100 A
125 A
S803N/S804N
20
20
20
20
20
20
S803S/S804S
25
25
25
25
25
25
Fuse 25 gG
50
Fuse 40 gG
30
30
Fuse 63 gG
20
20
20
Fuse 100 gG
10
10
10
10
10
Fuse 125 gG
10
Protection against earth faults with RCDs | 2CSC 420 004 B0201 6/5
63 A
80 A
100 A
125 A
SN201L
10
10
SN201
15
15
S201M
20
20
S203L/S204L
10
10
S203/S204
20
20
20
S203M/S204M
25
25
25
S203P/S204P
40
25
25
S803N-S804N
36
36
36
36
36
36
S803S-S804S
50
50
50
50
50
50
Fuse 25 gG
100
Fuse 40 gG
60
60
Fuse 63 gG
20
20
20
Fuse 100 gG
10
10
10
10
10
Fuse 125 gG
6/6
40 A
Protection against earth faults with RCDs | 2CSC 420 004 B0201
10
B
k
Vertical selectivity
Vertical selectivity may also be established for residual current tripping, bearing in mind that
in working back from system peripheral branches to the main electrical panels, the risk of unskilled persons coming into contact with dangerous parts is significantly reduced.
Protection against earth faults with RCDs | 2CSC 420 004 B0201 6/7
0.5 I1
I1
I1
0.5 I2
I2
I2
B
Dubious
selectivity
Certain
selectivity
Certain
selectivity
t [s]
Legend
I1
t1
1 Theoretical safety
curve
I2
t2
3 No-response limit
times
4 RCD B tripping
characteristic
x I
6/8
Protection against earth faults with RCDs | 2CSC 420 004 B0201
inst
30
inst
10
30
100
300
300
500
500
1000
1000
inst
inst
inst
inst
inst
inst
Q
Q
Q
Q
Q
Q
Q
Q
100
inst
Q
300
inst
Q
300
Q
500
inst
500
1000
inst
1000
The tripping time on RCDs is not adjustable. It is set according to a predetermined time current characteristic with an intrinsic delay for small currents, tending to disappear as the current
grows.
IEC 61008 and 61009 establish the tripping times relative to the type of RCD and the In (see
the table):
Type AC
In [A]
I6n [A]
1xI6
1xI6
500 A
Generic
any
any
0.3
0.15
0.04
0.04
S (selective)
any
> 0.03
0.13-0.5
0.06-0.2
0.05-0.15
0.04-0.15
Example:
Downstream F200 A type 30mA
Upstream F200 A S type 300mA
Fault = 300 mA
F200 A type 30mA will open between 0 and 0.04s
F200 A Selective type 300 mA stays closed up to 0.13s
100% Selectivity because 0.13s is greater than 0.04s
Protection against earth faults with RCDs | 2CSC 420 004 B0201 6/9
?
30 mA
ON!
30 mA
30 mA
ON
OFF
3 sec
When the RCCB trips in presence of an insulation fault, the auto-reclosing device
does not allow re-closing.
?
30 mA
OFF!
30 mA
30 mA
OFF
OFF
3 sec
6/10
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Protection against earth faults with RCDs | 2CSC 420 004 B0201 6/11
6/12
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Index
Unwanted tripping of RCDs
7/2
7/3
7/5
Protection against earth faults with RCDs | 2CSC 420 004 B0201 7/1
APR types suit all applications where it is necessary to ensure safety and continuity of supply
while preventing unwanted tripping.
Typical examples of this can be found in these situations:
Environments subjected to overvoltage due to lightning
Simultaneous switching on of fluorescent lamps with electronic ballasts
Simultaneous switching of IT apparatus (computers or electronic devices)
Devices with capacitors which connect phases to the earth installed in long circuits
Switching on of motor softstarter/speed variator
7/2
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Protection against earth faults with RCDs | 2CSC 420 004 B0201 7/3
F202 PV B, F204 B
230...400
Number of poles
2, 4
Type
B, B S (selective version)
Standard
IEC 61008
IEC 62423 (for instantaneous version)
E DIN VDE 0664 pt. 100 (for selective version)
up to 63
230...400
30, 300
Number of poles
2, 3, 4
Type
B, B S (selective version)
Standard
7/4
Protection against earth faults with RCDs | 2CSC 420 004 B0201
t [s]
0,5
0,3
0,2
0,06
0
l n [A]
1
2
3
5
10
1
0,5
0,3
0,1
0,03
2
3
5
10
30
Protection against earth faults with RCDs | 2CSC 420 004 B0201 7/5
7/6
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Index
ABB leading RCD technology
8/2
Protection against earth faults with RCDs | 2CSC 420 004 B0201 8/1
8/2
Protection against earth faults with RCDs | 2CSC 420 004 B0201
Protection against earth faults with RCDs | 2CSC 420 004 B0201 8/3
ABB SACE
A division of ABB S.p.A.
Line Protection Devices
Viale dellIndustria, 18
20010 Vittuone (MI) - Italy
Tel.: +39 02 9034 1
www.abb.com
Contact us