UT35A-UT32A Digital Indicating Controllers Operation Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Operation

Guide

n Safety, Protection, and Modification of the Product

UT35A/UT32A
Digital Indicating Controllers
Operation Guide

IM 05P01D31-11EN

Installation and Wiring


3rd Edition : Jan. 2011

This operation guide describes installation, wiring, and other tasks required to make the
controller ready for operation.

Contents
1.
2.
3.
4.
5.
6.

Safety Precautions
Model and Suffix Codes
How to Install
Hardware Specifications
How to Connect Wires
Terminal Wiring Diagrams

Introduction
Thank you for purchasing the UT35A/UT32A Digital Indicating Controller.
This operation guide describes the basic operations of the UT35A/UT32A. The guide
should be provided to the end user of this product.
Be sure to read this operation guide before using the product in order to ensure
correct operation.
For details of each function, refer to the electronic manual. Before using the product,
refer to the table of Model and Suffix Codes to make sure that the delivered product
is consistent with the model and suffix codes you ordered. Also make sure that the
following items are included in the package.
Digital Indicating Controller (the model you ordered)...............................x1
Set of Brackets.........................................................................................x1
Unit Label (L4502VZ)...............................................................................x1
Tag Label (L4502VE)...............................................................................x1
(Only when ordered.)
Operation Guide (this document).............................................................x6 (A3 size)
(Installation and Wiring, Initial Settings, Operations, and Parameters)
Target Readers
l
This guide is intended for the following personnel;
Engineers responsible for installation, wiring, and maintenance of the equipment.
Personnel responsible for normal daily operation of the equipment.

1. Safety Precautions

(1) In order to protect the system controlled by this product and the product itself,
and to ensure safe operation, observe the safety precautions described in the
users manual. Use of the instrument in a manner not prescribed herein may
compromise the product's functions and the protection features inherent in the
device. We assume no liability for safety, or responsibility for the product's quality,
performance or functionality should users fail to observe these instructions when
operating the product.
(2) Installation of protection and/or safety circuits with respect to a lightning
protector; protective equipment for the system controlled by the product and the
product itself; foolproof or fail-safe design of a process or line using the system
controlled by the product or the product itself; and/or the design and installation
of other protective and safety circuits are to be appropriately implemented as the
customer deems necessary.
(3) Be sure to use the spare parts approved by YOKOGAWA when replacing parts
or consumables.
(4) This product is not designed or manufactured to be used in critical applications
that directly affect or threaten human lives. Such applications include nuclear
power equipment, devices using radioactivity, railway facilities, aviation
equipment, air navigation facilities, aviation facilities, and medical equipment.
If so used, it is the users responsibility to include in the system additional
equipment and devices that ensure personnel safety.
(5) Modification of the product is strictly prohibited.
(6) This product is intended to be handled by skilled/trained personnel for electric
devices.
(7) This product is UL Recognized Component. In order to comply with UL standards,
end-products are necessary to be designed by those who have knowledge of the
requirements.

CAUTION

Calls attention to actions or conditions that could cause injury to


the user or damage to the instrument or property and indicates precautions that should be taken to prevent such occurrences.

This instrument is an EMC class A product. In a domestic environment this product may cause radio interference in which case the
user needs to take adequate measures.

The equipment wholly protected by double insulation or reinforced insulation.

Functional grounding terminals


(Do not use this terminal as a protective grounding terminal).

n UT35A
Suffix code

Optional
suffix
code

Coating (*4)

n UT32A

[Style: S3]

Model

Optional
suffix
code

Suffix code

Type 1:
Basic
control

-0

Standard type

-1

Position proportional type

-2

Type 2:
Functions

Heating/cooling type
0

None

RS-485 communication (Max. 38.4 kbps, 2-wire/4wire)

2
Type 3:
Open networks

Standard type

-1

Position proportional type

-2

Heating/cooling type
0

None

2 additional DIs, 2 additional DOs

Type 3: Open
networks

5 additional DIs, 5 additional DOs


0

None

RS-485 communication (Max.38.4 kbps, 2-wire/4-wire)

Ethernet communication (with serial gateway function)

CC-Link communication
(with Modbus master function)

PROFIBUS-DP communication
(with Modbus master function)
DeviceNet communication
(with Modbus master function)

Display language (*1)

-1

English

-2

German

-3

French

-4

Spanish
0

White (Light gray)

Black (Light charcoal gray)

The instrument should be installed in indoor locations meeting the following


conditions:
Instrumented panel
This instrument is designed to be mounted in an instrumented panel. Mount the
instrument in a location where its terminals will not inadvertently be touched.
Well ventilated locations
Mount the instrument in well ventilated locations to prevent the instruments internal temperature from rising.
However, make sure that the terminal portions are not exposed to wind. Exposure
to wind may cause the temperature sensor accuracy to deteriorate. To mount multiple indicating controllers, see the external dimensions/panel cutout dimensions
which follow. If mounting other instruments adjacent to the instrument, comply with
these panel cutout dimensions to provide sufficient clearance between the instruments.
Locations with little mechanical vibration
Install the instrument in a location subject to little mechanical vibration.
Horizontal location
Mount the instrument horizontally and ensure that it is level, with no inclination to
the right or left.

2 additional DIs and 2 additional DOs


0

Display language (*1)

-1

English

-2

German

-3

French

-4

Spanish
0

Optional suffix codes

Always "-00"
/LP

24 V DC loop power supply (*2)

/HA

Heater break alarm (*3)

/DC

Power supply 24 V AC/DC

/CT

Coating (*4)

English, German, French, and Spanish can be displayed as the guide display.
The /LP option can be specified in the combination of Type 1 code (any of "-0" or "-1")
and Type 2 code (any of "0" or "1.") Additionally, when the Type 2 code is "1", the RS-485
communication is 2-wire system.
The /HA option can be specified when the Type 1 code is "-0" or "-2."
When the /CT option is specified, the UT32A does not conform to the safety standards (UL
and CSA) and CE marking.

n Accessories (sold separately)


The following is an accessory sold separately.
LL50A Parameter Setting Software
Suffix code

Rear of
controller

Note

Black (Light charcoal gray)


-00

Keep this angle


within 30

30

White (Light gray)

-00

Front panel
of controller

None

Fixed code

*3:
*4:

Description
Digital Indicating Controller (provided with retransmission output or 15 V DC loop power supply, 2 DIs,
and 3 DOs) (Power supply: 100-240 V AC)

UT32A

*1:
*2:

n Installation Location

Description
Parameter Setting Software

Terminal Cover
For UT35A: Model UTAP001; For UT32A: Model UTAP002
Users Manual (A4 size)

Note: Users Manual can be downloaded from a website.

Note: Contains all manuals.

Description

-0

Type 2:
Functions

Case color

Power supply 24 V AC/DC

/CT

Digital Indicating Controller


(provided with retransmission output or 15 V DC loop
power supply, 2 DIs, and 3 DOs)
(Power supply: 100-240 V AC)

Identifies important information required to operate the instrument.

(1) YOKOGAWA makes no warranties regarding the product except those stated in
the WARRANTY that is provided separately.
(2) The product is provided on an "as is" basis. YOKOGAWA assumes no liability to
any person or entity for any loss or damage, direct or indirect, arising from the
use of the product or from any unpredictable defect of the product.

/DC

[Style: S3]

Note
n Warning and Disclaimer

Heater break alarm (*3)

Brackets
Part number: L4502TP (2 pcs for upper and lower sides)

2. Model and Suffix Codes

Type 1:
Basic
control

24 V DC loop power supply (*2)

/HA

Users Manual (CD-ROM), Model: UTAP003

UT35A

AC/DC

*3:
*4:

3. How to Install

Always "-00"
/LP

English, German, French, and Spanish can be displayed as the guide display.
The /LP option can be specified in the combination of Type 2 code (any of "0" or "1") and
Type 3 code (any of "0" or "1".)
The /HA option can be specified when the Type 1 code is -0 or -2.
When the /CT option is specified, the UT35A does not conform to the safety standards (UL
and CSA) and CE marking.

Model

Model

AC

*1:
*2:

LL50A

CAUTION

WARNING

Optional suffix codes

Case color

l Power Supply
Ensure that the instruments supply voltage matches the voltage
of the power supply before turning ON the power.
WARNING
l Do Not Use in an Explosive Atmosphere
Do not operate the instrument in locations with combustible
or explosive gases or steam. Operation in such environments
constitutes an extreme safety hazard. Use of the instrument in
environments with high concentrations of corrosive gas (H2S,
SOX, etc.) for extended periods of time may cause a failure.
l Do Not Remove Internal Unit
The internal unit should not be removed by anyone other than
YOKOGAWA's service personnel. There are dangerous high
voltage parts inside. Additionally, do not replace the fuse by
yourself.
l Damage to the Protective Construction
Operation of the instrument in a manner not specified in the
users manual may damage its protective construction.

The following symbol is used on the instrument. It indicates the possibility of injury
to the user or damage to the instrument, and signifies that the user must refer to
the users manual for special instructions. The same symbol is used in the users
manual on pages that the user needs to refer to, together with the term WARNING
or CAUTION.

Calls attention to actions or conditions that could cause serious


or fatal injury to the user, and indicates precautions that should be
taken to prevent such occurrences.

-00

Fixed code

n Waste Electrical and Electronic Equipment (WEEE),


Directive 2002/96/EC
This is an explanation of how to dispose of this product based on Waste Electrical
and Electronic Equipment (WEEE), Directive 2002/96/EC. This directive is only valid
in the EU.

Marking
This product complies with the WEEE Directive (2002/96/EC)
marking requirement.
This marking indicates that you must not discard this electrical/
electronic product in domestic household waste.

Product Category
With reference to the equipment types in the WEEE directive Annex 1, this
product is classified as a Monitoring and Control instrumentation product.
Do not dispose in domestic household waste. When disposing products in the EU,
contact your local Yokogawa Europe B.V. office.

If the instrument is moved from a location with low temperature and low humidity
to a place with high temperature and high humidity, or if the temperature changes
rapidly, condensation will result. Moreover, in the case of thermocouple inputs,
measurement errors will result. To avoid such a situation, leave the instrument in the
new environment under ambient conditions for more than 1 hour prior to using it.
Do not mount the instrument in the following locations:
Outdoors
Locations subject to direct sunlight or close to a heater
Install the instrument in a location with stable temperatures that remain close to an
average temperature of 23C. Do not mount it in locations subject to direct sunlight
or close to a heater. Doing so adversely affects the instrument.
Locations with substantial amounts of oily fumes, steam, moisture, dust, or
corrosive gases
The presence of oily fumes, steam, moisture, dust, or corrosive gases adversely
affects the instrument. Do not mount the instrument in locations subject to any of
these substances.
Areas near electromagnetic field generating sources
Do not place magnets or tools that generate magnetism near the instrument. If the
instrument is used in locations close to a strong electromagnetic field generating
source, the magnetic field may cause measurement errors.
Locations where the display is difficult to see
The instrument uses an LCD for the display unit, and this can be difficult to see
from extremely oblique angles. Mount the instrument in a location where it can be
seen as much as possible from the front.
Areas close to flammable articles
Absolutely do not place the instrument directly on flammable surfaces. If such a circumstance is unavoidable
150 mm
and the instrument must be placed close to a flammable
item, provide a shield for it made of 1.43 mm thick plated
150 mm
150 mm
steel or 1.6 mm thick unplated steel with a space of at
150 mm
least 150 mm between it and the instrument on the top,
bottom, and sides.
Areas subject to being splashed with water

Be sure to turn OFF the power supply to the controller before installing it on the panel to avoid an electric shock.

WARNING

YOKOGAWA ELECTRIC CORPORATION


Network Solutions Business Division
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN
YOKOGAWA CORPORATION OF AMERICA
Head office and for product sales
2 Dart Road, Newnan, Georgia 30265, USA
YOKOGAWA EUROPE B.V.
Headquarters
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS

www.yokogawa.com/ns

All Rights Reserved, Copyright 2010 Yokogawa Electric Corporation


IM 05P01D31-11EN page /12

4. Hardware Specifications

n Mounting the Instrument Main Unit


Provide an instrumented panel steel sheet of 1 to 10 mm thickness.
After opening the mounting hole on the panel, follow the procedures below to install
the controller:
1) Insert the controller into the opening from the front of the panel so that the
terminal board on the rear is at the far side.
2) Set the brackets in place on the top and bottom of the controller as shown in the
figure below, then tighten the screws of the brackets. Take care not to overtighten
them.

WARNING

This instrument is for Measurement Category I (CAT.I). Do not use it


for measurements in locations falling under Measurement Categories II, III, and IV.

Bracket
(top mounting hardware)

Panel

Direction to insert the


controller
Insert the controller
into the opening at
the front of the panel.

Terminal board

Category

Insert a screwdriver into the


brackets to tighten the screws.
Appropriate
tightening torque:
0.25 Nm

Bracket
(bottom mounting hardware)

Entrance IV
Cable

Measurement
category

Internal Wiring
II
III
T
I
Outlet

Description

Remarks

CAT.I

For measurements performed on circuits not


directly connected to MAINS.

II

CAT.II

For measurements performed on circuits diAppliances, portable equiprectly connected to the low-voltage installation. ment, etc.

III

CAT.III

For measurements performed in the building


installation.

Distribution board, circuit


breaker, etc.

IV

CAT.IV

For measurements performed at the source of


the low-voltage installation.

Overhead wire, cable


systems, etc.

n Input Specifications
Tighten the screws with appropriate tightening torque within 0.25
Nm. Otherwise it may cause the case deformation or the bracket
damage.
CAUTION Make sure that foreign materials do not enter the inside of the
instrument through the cases slit holes.

Universal Input (Equipped as standard)


Number of inputs: 1
Input type, instrument range, and measurement accuracy: See the table below,
Instrument Range

Input Type

-270.0 to 1370.0C

n External Dimensions and Panel Cutout Dimensions


96 (3.78)

65 (2.56)

Bracket

94.6 (3.72)

96 (3.78)

91.6 (3.61)

20 (0.79)

Thermocouple

Bracket

(53) (2.09)
+0.8

92 0
+0.03
(3.62 0 )
+0.8

92 0

+0.03

(3.62 0

UT32A

(25)
(0.98)

0.0 to 1800.0C

32 to 3300F

0.0 to 1700.0C

32 to 3100F

0.0 to 1700.0C

32 to 3100F

-200.0 to 1300.0C

-270.0 to 1000.0C

0.0 to 2300.0C

32 to 4200F

Platinel 2

0.0 to 1390.0C

32.0 to 2500.0F

N stands for the number of controllers to be


installed.
However, the measured value applies if N5.
Normal tolerance:
(value of JIS B 0401-1998 tolerance class IT18)/2

11 (0.43) 65 (2.56)

Unit: mm (approx. inch)


Bracket Terminal cover

0.0 to 400.0C

0.0 to 1900.0C

32 to 3400F

W97Re3W75Re25

0.0 to 2000.0C

32 to 3600F

0.2% of instrument range 1 digit

JPt100

-200.0 to 500.0C
-150.00 to 150.00C

RTD

-200.0 to 850.0C
-200.0 to 500.0C
-150.00 to 150.00C

0.1% of instrument range 1 digit


-300.0 to 1000.0F
(Note 1)
-200.0 to 300.0F

-200.0 to 300.0F

Standard signal

105.2 (4.14)

91.6 (3.61)

94.6 (3.72)

96 (3.78)

DC voltage/current

1.000 to 5.000 V

+0.6

[(N-1)48+45] 0

+0.02

92 +0.8
0
(3.62+0.03
0 )

N stands for the number of controllers to be


installed.
However, the measured value applies if Nr5.

92 +0.8
0

+0.6

45 0

+0.02

(1.77 0

(25)
)

(0.98)

0.00 to 20.00 mA
0.0 to 100.0 mV

Side-by-side close mounting

([(N-1)1.89+1.77] 0

0.1% of instrument range 1 digit

-10.00 to 20.00 mV

Bracket

(3.62+0.03
0 )

0.1% of instrument range 1 digit

0.400 to 2.000 V
4.00 to 20.00 mA

1 to 10 mm (0.04 to 0.39 inch) (panel thickness)

(53) (2.09)

0.1% of instrument range 1 digit

-300.0 to 1560.0F 0.1% of instrument range 1 digit


-300.0 to 1000.0F (Note 1)

0.00 to 10.00 V

145 (5.71)
min.

0.1% of instrument range 1 digit

PR20-40

0.000 to 2.000 V

70 (2.76)
min.

0.2% of instrument range 1 digit


(Note 2)
0.5% of instrument range 1 digit for
800C or more
Accuracy is not guaranteed for less
than 800C.

20 (0.79)

General mounting

0.15% of instrument range 1 digit

-450.0 to 1800.0F 0.1% of instrument range 1 digit for


-300.0 to 1600.0F 0C or more
0.2% of instrument range 1 digit for
-300.0 to 750.0F
less than 0C
1.5% of instrument range 1 digit for
-200.0 to 1000.0F
less than -200.0C of thermocouple E.

Pt100

48 (1.89)

-200.0 to 900.0C

0.15% of instrument range 1 digit


for 400C or more
5% of instrument range 1 digit for
less than 400C

0.1% of instrument range 1 digit


-300.0 to 2400.0F 0.25% of instrument range 1 digit
for less than 0C

+0.8

145 (5.71)
min.

92 0

+0.03

0.0 to 400.0C

+0.8

[(N-1)96+92] 0
([(N-1)3.78+3.62] +0.03 )

(3.62 0

-270.0 to 400.0C

-200.0 to 400.0C

Side-by-side close mounting

117 (4.61) min.

-200.0 to 1200.0C

1 to 10 mm (0.04 to 0.39 inch) (panel thickness)

General mounting

J
T

Terminal cover

105.2 (4.14)

UT35A

-270.0 to 1000.0C
-200.0 to 500.0C

Unit: mm (approx. inch)

11
(0.43)

Accuracy

-450.0 to 2500.0F 0.1% of instrument range 1 digit for


-450.0 to 2300.0F 0C or more
0.2% of instrument range 1 digit for
-200.0 to 1000.0F
less than 0C
-300.0 to 2300.0F 2% of instrument range 1 digit for
-450.0 to 750.0F less than -200.0C of thermocouple K
1% of instrument range 1 digit for
-200.0 to 750.0F less than -200.0C of thermocouple T

Normal tolerance:
(value of JIS B 0401-1998 tolerance class IT18)/2

The accuracy is that in the standard operating conditions: 232C, 5510%RH, and power
frequency at 50/60 Hz.
Note 1: 0.3C 1 digit in the range between 0 and 100C, 0.5C 1 digit in the range
between -100 and 200C.
Note 2: W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988

Input sampling (control) period: 200 ms


Burnout detection:
Functions at TC, RTD, and standard signal.
Upscale, downscale, and off can be specified.
For standard signal, burnout is determined to have occurred if it is 0.1 V or 0.4
mA or less.
Input bias current: 0.05 A (for TC or RTD)
Measured current (RTD): About 0.16 mA
Input resistance:
TC or mV input: 1 M or more
V input: About 1 M
mA input: About 250

Allowable signal source resistance:


TC or mV input: 250 or less

Effects of signal source resistance: 0.1 V/ or less
DC voltage input: 2 k or less

Effects of signal source resistance: About 0.01%/100
Allowable wiring resistance:
RTD input: Max. 150 /wire (The conductor resistance between the three wires
shall be equal.)
Wiring resistance effect: 0.1C/10
Allowable input voltage/current:
TC, mV, mA and RTD input: 10 V DC
V input: 20 V DC
mA input: 40 mA
Noise rejection ratio:
Normal mode: 40 dB or more (at 50/60 Hz)
Common mode: 120 dB or more (at 50/60 Hz)
For 100-240 V AC, the power frequency can be set manually. Automatic
detection is also available.
For 24 V AC/DC, the power frequency can be set manually.
Reference junction compensation error:
1.0C (15 to 35C)
1.5C (-10 to 15C and 35 to 50C)
Applicable standards: JIS/IEC/DIN (ITS-90) for TC and RTD

n Analog Output Specifications


Number of outputs:
Control output: 1
Cooling-side control output of Heating/cooling type (Retransmission output
terminal): 1
Output type: Current output or voltage pulse output
Current output: 4 to 20 mA DC or 0 to 20 mA DC/load resistance of 600 or less
Current output accuracy: 0.1% of span (5% of span for 1 mA or less)
The accuracy is that in the standard operating conditions: 232C, 5510%RH,
and power frequency at 50/60 Hz.
Voltage pulse output:
Use: Time proportional output
On-voltage: 12 V or more/load resistance of 600 or more
Off-voltage: 0.1 V DC or less
Time resolution: 10 ms or 0.1% of output, whichever is larger

n Contact Input Specifications


Number of inputs: See the table of Model and Suffix Codes.
Input type: No-voltage contact input or transistor contact input
Input contact rating: 12 V DC, 10 mA or more
Use a contact with a minimum on-current of 1 mA or more.
ON/OFF detection:
No-voltage contact input:

Contact resistance of 1 k or less is determined as ON and contact

resistance of 50 k or more as OFF.
Transistor contact input:

Input voltage of 2 V or less is determined as ON and leakage current must

not exceed 100 A when OFF.
Minimum status detection hold time: Control period +50 ms
Use: SP switch, operation mode switch, and event input

n Transistor Contact Output Specifications


Number of outputs: See the table of Model and Suffix Codes.
Output type: Open collector (SINK current)
Output contact rating: Max. 24 V DC, 50 mA
Output time resolution: Min. 200 ms

n Heater Break Alarm Specifications


Number of inputs: 2
Number of outputs: 2 (transistor contact output)
Use: Measures the heater current using an external current transformer (CT) and
generates a heater break alarm when the measured value is less than the break
detection value.
Current transformer input resistance: About 9.4
Current transformer input range: 0.0 to 0.1 Arms (0.12 Arms or more cannot be applied.)
Heater current setting range: OFF, 0.1 to 300.0 Arms
Heater current measured value display range: 0.0 to 360.0 Arms

Note: The CT ratio can be set. CT ratio setting range: 1 to 3300

Within 1 s (63% of analog output response time when a step change of 10 to 90% of
input span is applied)

Recommended CT: CT from U.R.D., Ltd.


CTL-6-S-H: CT ratio 800, measurable current range: 0.1 to 80.0 Arms
CTL-12L-30: CT ratio 3000, measurable current range: 0.1 to 180.0 Arms
Heater current measurement period: 200 ms
Heater current measurement accuracy: 5% of current transformer input range
span 1digit (CT error is not included.)
Heater current detection resolution: Within 1/250 of current transformer input range
span
Break detection On-time: Min. 0.2 second (for time proportional output)

n Relay Contact Output Specifications

n 24 V DC Loop Power Supply Specifications

Contact type and number of outputs:


Control output: contact point 1c; 1 point
Heating/cooling type: contact point 1a; 2 points for both heating and cooling sides
Alarm output: contact point 1a; 3 points (common is independent)
Contact rating:
Contact point 1c (control output): 250 V AC, 3 A or 30 V DC, 3A (resistance load)
Contact point 1a (control output): 240 V AC, 3A or 30 V DC, 3A (resistance load)
Contact point 1a (alarm output): 240 V AC, 1A or 30 V DC, 1 A (resistance load)
Use: Time proportional output, alarm output, FAIL output, etc.
Time resolution of control output: 10 ms or 0.1% of output, whichever is larger

Use: Power is supplied to a 2-wire transmitter.


Power supply: 21.6 to 28.0 V DC
Rated current: 4 to 20 mA DC
Maximum supply current: About 30 mA (with short-circuit current limiting circuit.)

n Step Response Time Specifications

Note: This cannot be used for a small load of 10 mA or less.

n Position Proportional Output Specifications


Position signal input:
Slide resistance: 100 to 2.5 k of total resistance

100% side and slide line: with disconnection detection

0% side: without disconnection detection
Current input: 4 to 20 mA (with disconnection detection)
Sampling period: 50 ms
Measurement resolution: 0.1% of input span
Position proportional relay output:
UT35A: contact point 1a; 2 points, 250 V AC, 3 A or 30 V DC, 3 A (resistance load)
UT32A: contact point 1a; 2 points, 240 V AC, 3 A or 30 V DC, 3 A (resistance load)
Note: This cannot be used for a small load of 10 mA or less.

n Retransmission Output Specifications

Safety and EMC Standards


Safety: Compliant with IEC/EN61010-1 (CE), approved by CAN/CSA C22.2
No.61010-1 (CSA), approved by UL61010-1.

Installation category: CAT. II Pollution degree: 2

Measurement category: I (CAT. I)

Rated measurement input voltage: Max. 10 V DC

Rated transient overvoltage: 1500 V (Note)
Note: This is a reference safety standard value for Measurement Category I of IEC/EN/CSA/
UL61010-1. This value is not necessarily a guarantee of instrument performance.

EMC Conformity standards:


CE marking

EN61326-1 Class A, Table 2 (For use in industrial locations)

EN61326-2-3

EN 55011 Class A, Group1

EN 61000-3-2 Class A

EN 61000-3-3
C-tick mark

EN 55011 Class A, Group1
The instrument continues to operate at a measurement accuracy of within 20% of
the range during testing.

Number of outputs: Retransmission output; 1, shared with 15 V DC loop power


supply or Cooling-side control output.
Current output: 4 to 20 mA DC or 0 to 20 mA DC/ load resistance of 600 or less
Current output accuracy: 0.1% of span (5% of span for 1 mA or less)
The accuracy is that in the standard operating conditions: 232C, 5510%RH,
and power frequency at 50/60 Hz.

n 15 V DC Loop Power Supply Specifications


(Shared with retransmission output or Cooling-side control output.)
Power supply: 14.5 to 18.0 V DC
Maximum supply current: About 21 mA (with short-circuit current limiting circuit)

IM 05P01D31-11EN page /12

Construction, Installation, and Wiring

Effects of Operating Conditions

Dust-proof and drip-proof: IP56 (for front panel) (Not available for side-by-side
close mounting.)
Material: Polycarbonate (Flame retardancy: UL94V-0)
Case color: White (Light gray) or Black (Light charcoal gray)
Weight: 0.5 kg or less
External dimensions (mm):
UT35A: 96 (W) 96 (H) 65 (depth from the panel face)
UT32A: 48 (W) 96 (H) 65 (depth from the panel face)
(Depth except the projection on the rear panel)
Installation: Direct panel mounting; mounting bracket, one each for upper and
lower mounting
Panel cutout dimensions (mm):
UT35A: 92+0.8/0 (W) 92+0.8/0 (H)
UT32A: 45+0.6/0 (W) 92+0.8/0 (H)
Mounting attitude: Up to 30 degrees above the horizontal. No downward titling allowed.
Wiring: M3 screw terminal with square washer (for signal wiring and power wiring)

Power Supply Specifications and Isolation


Power supply:
Rated voltage: 100-240 V AC (+10%/-15%), 50/60 Hz

24 V AC/DC (+10%/-15%) (for /DC option)
Power consumption: UT35A: 18 VA (DC:9 VA, AC: 14 VA if /DC option is specified)


UT32A: 15 VA (DC:7 VA, AC: 11 VA if /DC option is specified)
Data backup: Nonvolatile memory
Power holdup time: 20 ms (for 100 V AC drive)
Withstanding voltage
Between primary terminals and secondary terminals: 2300 V AC for 1 minute
Between primary terminals: 1500 V AC for 1 minute
Between secondary terminals: 500 V AC for 1 minute
(Primary terminals: Power* and relay output terminals; Secondary terminals:
Analog I/O signal terminals, contact input terminals, communication terminals
and functional grounding terminals.)

*: Power terminals for 24V AC/DC models are the secondary terminals.

Insulation resistance: Between power supply terminals and a grounding terminal


20 M or more at 500 V DC
Isolation specifications

Effect of ambient temperature:


Voltage or TC input: 1 V/C or 0.01% of F.S./C, whichever is larger
Current input: 0.01% of F.S./C
RTD input: 0.05C/C (ambient temperature) or less
Analog output: 0.02% of F.S./C or less
Effect of power supply voltage fluctuation
Analog input: 0.05% of F.S. or less
Analog output: 0.05% of F.S. or less
(Each within rated voltage range)

5. How to Connect Wires

This product

Control, retransmission (analog) output terminals

A safety
voltage circuit

(not isolated between the analog output terminals)


Valve position (feedback) input terminals

Functional
insulation

Control relay (contact point c/contact point a x 2) output terminals


Alarm-1 relay (contact point a) output terminals

Internal

Power

Alarm-2 relay (contact point a) output terminals

circuits

supply

Alarm-3 relay (contact point a) output terminals


Position proportional relay output terminals
Contact input terminals (all)
RS-485 communication terminals (2 ports)
24 V DC loop power supply terminals
Contact output (transistor) terminals
Ethernet communication terminal

A safety
voltage circuit
Functional
insulation

A safety
voltage circuit

Reinforced insulation
A hazardous
voltage circuit

A safety
voltage circuit

A hazardous
voltage circuit

Reinforced insulation

A hazardous
voltage circuit

A hazardous
voltage circuit

Reinforced insulation
A hazardous
voltage circuit

A hazardous
voltage circuit

Reinforced insulation

PROFIBUS-DP/DeviceNet/CC-Link communication terminals


Current transformer input terminals

The circuits divided by lines are insulated mutually.

Environmental Conditions
Normal Operating Conditions:
Ambient temperature: -10 to 50C (-10 to 40C for side-by-side close mounting)
For the CC-Link option, 0 to 50 C (0 to 40 C for side-by-side close mounting)
Ambient humidity: 20 to 90% RH (no condensation allowed)
Magnetic field: 400 A/m or less
Continuous vibration at 5 to 9 Hz: Half amplitude of 1.5 mm or less, 1oct/min for 90
minutes each in the three axis directions
Continuous vibration at 9 to 150 Hz: 4.9 m/s2 or less, 1oct/min for 90 minutes each
in the three axis directions
Short-period vibration: 14.7 m/s2, 15 seconds or less
Shock: 98 m/s2 or less, 11 ms
Altitude: 2000 m or less above sea level
Warm-up time: 30 minutes or more after the power is turned on
Startup time: Within 10 seconds

*: The LCD (a liquid crystal display) is used for a display portion of this product.
The LCD has a characteristic that the display action becomes late at the low
temperature. However, the control function is not affected.

Transportation and Storage Conditions:


Temperature: -25 to 70C
Temperature change rate: 20C/h or less
Humidity: 5 to 95% RH (no condensation allowed)

(A)

5.5 3.3

(F)

Recommended tightening torque: 0.6 Nm


Applicable wire size: Power supply wiring 1.25 mm2 or more
0.25 to 1.65 (22 to 16)

( d)
3.3

(A)
5.5

(F)

Name and Manufacturer

External AC power supply

UT35A/UT32A

Power supply, relay contact outputs

600 V Grade heat-resistant PVC insulated wires, JIS C


3317(HIV), 0.9 to 2.0 mm2

Thermocouple

Shielded compensating lead wires, JIS C 1610

RTD

Shielded wires (three/four conductors), UL2482 (Hitachi Cable)

Other signals (other than contact input/output) Shielded wires


Other signals (contact input/output)

Unshielded wires

RS-485 communication

Shielded wires

Ethernet communication

100 BASE-TX (CAT-5)/10 BASE-T

PROFIBUS-DP communication

Dedicated cable for PROFIBUS-DP (Shielded two-wires)

DeviceNet communication

Dedicated cable for DeviceNet (Shielded five-wires)

CC-Link communication

Dedicated cable for CC-Link (Shielded three-wires)

UTs contact

CR filter
(Mount it directly
to the relay coil
terminal (socket).)

Relay
(Use one with a relay coil
rating less than the UTs
contact rating.)

PROFIBUS-DP/CC-Link Connector (wiring side) (Part number: A1987JT)


DeviceNet Connector (wiring side) (Part number: L4502BW)
Recommended tightening torque: 0.5 to 0.6 Nm

6. Terminal Wiring Diagrams


Do not use an unassigned terminal as the relay terminal.
Do not use a 100-240 V AC power supply for the 24 V AC/DC
model; otherwise, the instrument will malfunction.

CAUTION

UT35A
OUT

Control output
Relay contact output
NC

101

NO

102

(Suffix code: Type1=-0)

Terminal wiring differs in Heating/cooling


control and Position proportional control.
Refer to the terminals of Position
proportional control output and
Heating/cooling control output below.
Factory default: Control output is relay.

103

Factory default: PV input


type is undefined.

(Equipped

PV input

PV as standard)

TC input

RTD input
A 201

202

B 203

Heating/cooling control output


Heating/cooling relay contact output (Suffix code: Type 1=-2)

203

202

204

203

E4-terminal area

OUT2

Cooling NO
-side

101

OUT

Heating NO
-side

102

101
-112

501
-512

401
-412

COM

103

101

501

401

102

502

103

Wiring direction

(Equipped

Contact output

ALM as standard)

Alarm-3 output
(PV high limit)

AL3

Common

105

Alarm-2 output
( PV low limit)

106

Common
Alarm-1 output
(PV high limit)

AL2

AL1

Common

UT

104

E1-terminal area
201
-212

301

201

302

202

503

303

203

104

504

304

204

105

505

305

205

106

506

306

206

107

507

407

207

108

508

408

208

109

509

409

110

510

410

111

511

411

211

112

512

412

212

210

24 V AC/DC power supply

110
111
112

Allowable range:
(24
100-240 V AC (10%)
(free voltage)
50/60 Hz shared

0-20 mA DC,
4-20 mA DC,
Voltage pulse (12V)

110

111
112

V AC/DC power supply: Optional suffix code /DC)

Position proportional control output


Feedback input
100%

HIGH
(direct)

507

205
206

LOW
(reverse)

508

511

COM

509

0% 512

Contact rating: 250 V AC, 3A Resistance: 100 to 2.5 k


30 V DC, 3 A
(resistance load) Feedback input
Current (mA)
input

+ 510
511
- 512

When feedback input is current

(Suffix code: Type 1=-2)

Control output

OUT (Suffix code: Type1=-0, -1 or -2)

Current/voltage pulse output Retransmission output 15 V DC loop power supply


Default: Undefined
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12 V)

207
208

0-20 mA DC,
4-20 mA DC

207

14.5-18.0 V DC
(Max. 21 mA DC)

208

207
208

Default: 4-20 mA DC

Can be used for retransmission output or 15 V DC loop power supply when


current/voltage pulse output is not used for control output.
Current output range can be changed.
In Position proportional type, can be used for retransmission output or 15 V
DC loop power supply.

Contact input

DI (Equipped as standard)

VALV

No-voltage
contact

UT Transistor

210 DI2

contact

210

AUTO when DI1=ON


MAN when DI1=OFF

211 DI1

211

Common

212 COM

212

(Suffix code: Type1=-1)

510

RET/OUT2

External contact input

108

Relay contact output

206

Can not be used for retransmission output or


15 V DC loop power supply when
current/voltage pulse output is used.
Can be used for retransmission output or 15 V
DC loop power supply when control output is
not used.
Current output range can be changed.

STOP when DI2=ON


RUN when DI2=OFF

109

RET (Equipped as standard)

Cooling-side control output

E3-terminal area

Power supply
N

14.5-18.0 V DC
(Max. 21 mA DC)

Current/voltage pulse output

301
-306

107

Relay contact rating: 240 V AC, 1 A


30 V DC, 1 A (resistance load)

100-240 V AC power supply

206

Load resistance 600 or less


Default: 4-20 mA DC

Current (mA) input Voltage (mV, V) input

Contact rating: 250 V AC, 3 A


30 V DC, 3 A (resistance load)

Retransmission output

Retransmission output 15 V DC loop power supply Can be used for 15 V DC loop


power supply when not used for
Default: PV
retransmission output.
retransmission
205
205
4-20 mA DC or
0-20 mA DC

b 202

203

External contact output (relay)

Provide electricity from a single-phase power supply. If the


power is noisy, install an isolation transformer on the primary
side, and use a line filter on the secondary side. When measures
CAUTION
against noise are taken, do not install the primary and secondary
power cables close to each other.
If there is a risk of external lightning surges, use a lightning
arrester etc.
For TC input, use shielded compensating lead wires for wiring.
For RTD input, use shielded wires that have low conductor
resistance and cause no significant differences in resistance
between the three wires.
Since the control output relay has a life span (resistance load of
100,000 times), use the auxiliary relay to perform ON/OFF control.
The use of inductance (L) loads such as auxiliary relays, motors
and solenoid valves causes malfunction or relay failure; always
insert a CR filter for use with alternating current or a diode for
use with direct current, as a spark-removal surge suppression
circuit, into the line in parallel with the load.
After completing the wiring, the terminal cover is recommended
to use for the instrument.

AC Relay Wiring

Cable Specifications and Recommended Cables


Purpose

Diode
(Mount it directly
to the relay coil
terminal (socket).)

Relay
UTs contact
(Use one with a relay coil rating
less than the UTs contact rating.)

4.2

Contact rating: 240 V AC, 3 A


30 V DC, 3 A (resistance load)

When connecting two or more crimp-on terminal lugs to the


single terminal block, bend the crimp-on terminal lugs before
tightening the screw.
CAUTION Note that the wiring of two or more crimp-on terminal lugs to the
single high-voltage terminal of the power supply and relay, etc.
does not comply with the safety standard.

External DC power supply

Relay

COM

This product

Functional
insulation

UT35A/UT32A

Applicable terminal lug Applicable wire size mm2 (AWG#)

This product

DC Relay Wiring

(d )

M3

Wiring work must be carried out by a person with basic electrical


knowledge and practical experience.
WARNING Be sure to turn OFF the power supply to the controller before
wiring to avoid an electric shock. Use a tester or similar device
to ensure that no power is being supplied to a cable to be
connected.
As a safety measure, always install a circuit breaker (an IEC
60947-compatible product, 5 A, 100 V or 220 V AC) in an easily
accessible location near the instrument. Moreover, provide
indication that the switch is a device for turning off the power to
the instrument.
Install the power cable keeping a distance of more than 1 cm
from other signal wires.
The power cable is required to meet the IEC standards concerned
or the requirements of the area in which the instrument is being
installed.
Wiring should be installed to conform to NEC (National Electrical
Code: ANSI/NFPA-70) or the wiring construction standards in
countries or regions where wiring will be installed.
For control relay output, alarm relay output, and power terminal
connections, use heat-resistant cables.
Since the insulation provided to each relay output terminal is
Functional insulation, provide Reinforced insulation to the
external of the device as necessary. (Refer to the drawing below.)

PV (universal ) input terminals

Recommended Crimp-on Terminal Lugs

UT
+5V
DI2
+5V
DI1
COM

Contact rating: 12 V DC, 10 mA or more

Function can be assigned to the terminals with no function.

Heater break alarm

HBA (Optional suffix code /HA)

External contact output (transistor)


UT
Heater break alarm-1 HAL1 507
output

Heater break alarm-2


output

HAL2 508

Common

COM 509

Heater current detection input


510
CT1
CT2
COM

511
512

Transistor contact rating: 24 V DC, 50 mA

IM 05P01D31-11EN page /12

UT35A (Continued from page 3)

UT32A
301-306

E4-terminal area E1-terminal area


101
-112

501
-512

401
-412

301
-306

201
-212

101

501

401

301

201

102

502

302

202

Contact input

E1-Terminal Area
DI (Suffix code: Type 2=2)

No-voltage
contact

UT

Transistor contact

301 COM

Common

301

303

203

Factory default: No function

302 DI11

302

104

504

304

204

Factory default: No function

303 DI12

303

Factory default: No function

304 DI13

304

505

305

205

506

306

206

107

507

407

207

108

508

408

208

109

509

409

110

510

410

210

111

511

411

211

112

512

412

212

305

305 DI14

Factory default: No function

306

306 DI15

Factory default: No function

Contact rating: 12 V DC, 10 mA or more

COM
DI11
DI12
DI13
DI14
DI15

UT

UT

Factory default: No function DO45 501

+5V
+5V
+5V

202
203

Contact rating: 250 V AC, 3 A


30 V DC, 3 A (resistance load)

COM 506

Common

Function can be assigned


to the terminals with no
function.

101

OUT

Heating NO
-side

102

COM

103

Contact rating: 240 V AC, 3 A


30 V DC, 3 A (resistance load)

24 V DC loop power supply

21.6-28.0 V DC
(Max. 30 mA DC)

505

(Optional suffix code /LP)

Contact output

101

301

201

102

302

202

103

303

203

104

304

204

ALM (Equipped
as standard)

External contact output (relay)

506

Alarm-3 output
(PV high limit)

AL3

Common
Alarm-2 output
(PV low limit)

AL2

Common

COM 306

AL1

Common

UT

104
105

N
L

SDB(+) 407

(Suffix code: Type 3=2)

Upper side LED (baud rate)

409

RDB(+) 410

Color

Amber

Lit

100M bps
10M bps

Unlit

Lower side LED (link activity)

RDA(-) 411

Color

Green

Lit

Linked

Blink

Active

Unlit

Link failure

390

Data

CHK line
RDY

2
4

PROFIBUS
communication wiring,
DGND
terminating resistors are
Pin Signal name
Description
separately needed.
+5V bus power
1 VP
These are to be prepared by
users. (390 : 2 pcs. 220 :
Data signal
2 RxD/TxD-P
(positive data receive/transmit) 1 pc., or an active
terminator.)
Data signal
390

RS-485
RSB(+) 407
RSA(-) 408

409

SG

PROF

(Suffix code: Type 3=4)

RxD/TxD-P
220
If the UT is located at the end
RxD/TxD-N of a segment for the

Data
ERR line

SDA(-) 408
SG

VP
1

RxD/TxD-N

DGND

SHIELD

Signal ground

110
DB

L ERR

L RUN

5
Pin Signal name

Description

FG
SLD

Flame ground

2
3

DG

DB

RX/TX signal ground


RX/TX - signal

DA

RX/TX + signal

CC-L

DA

CHK

Unlit

CHK
(red)

User profile error

Normal
No power, or
Communication
failure

Not connected, or
communication
failure (flashing)

Normal

LED
CHK
(red)

Shield

Lit
User profile error/
Address error

L ERR Communication failure


(red) (CRC error)

If the UT is located at
the end of a segment
for the CC-Link
communication wiring,
terminating resistors
are separately needed.
These are to be
prepared by users.
(110 : 1 pc.)

CAN_H
121

CHK

MNS

5
Pin Signal name
1

V+

Description
DeviceNet power supply 24V

CAN_H

RX/TX + signal

DRAIN

CAN_L

Shield/Drain wire
RX/TX - signal

5
Unlit
Normal

Normal

No carrier
L RUN Normal
detected/
(green) Communicating successfully Communication
timeout

LED
CHK
(red)

RS-485
RSB(+) 407
RSA(-) 408
SG

409

CAN_L

V-

DNET

(Suffix code: Type 3=5,


except Type 2=3)
If the UT is located at the
end of a segment for the
DeviceNet
communication wiring,
terminating resistors are
separately needed.
These are to be
prepared by users. (121
: 1 pc.)

DeviceNet power supply common


Lit/flashing
User profile error

110

111

Optional suffix code /DC)

110

Normal. Communicating
successfully (green, lit).
Not connected (green, flashing).
MNS Critical link failure (red, lit).
(green/ Communication timeout (red,
red) flashing)
At power-on/Communication
faulted (green/red, flashing)

207

108

308

208

109

309

110

310

0-20 mA DC,
4-20 mA DC,
Voltage pulse (12 V)

111

311

211

112

312

212

207
208

Default: Undefined
0-20 mA DC,
4-20 mA DC

Feedback input
100%

HIGH
(direct)

101

LOW
(reverse)

102

311

COM

103

0% 312

14.5-18.0 V DC
(Max. 21 mA DC)

208

207
208

Default: 4-20 mA DC

DI (Equipped as standard)

Feedback input

312
When feedback input is current

No-voltage
contact

UT Transistor
contact

210 DI2

210

AUTO when DI1=ON


MAN when DI1=OFF

211 DI1

211

Common

212 COM

212

310

311

UT
+5V
DI2
+5V
DI1
COM

Contact rating: 12 V DC, 10 mA or more

Function can be assigned to the terminals with no function.

Heater break alarm

HBA (Optional suffix code /HA)

External contact output (transistor)


UT
Heater break alarm-1 HAL1 307
output

Heater break alarm-2


output

HAL2 308

Common

COM 309

Heater current detection input


310
CT1
CT2
COM

311
312

Transistor contact rating: 24 V DC, 50 mA

E1-Terminal Area
24 V DC loop power supply

RS-485 communication RS485


SDB(+) 301

VALV

(Suffix code: Type1=-1)

Current (mA)
310
input

112

RS-485

207

Can be used for retransmission output or 15 V DC loop power suppy when


current/voltage pulse output is not used for control output.
Current output range can be changed.
In Position proportional type, can be used for retransmission output or 15 V DC
loop power supply.

210

Contact rating: 240 V AC, 3A Resistance: 100 to 2.5 k


30 V DC, 3 A
(resistance load)

111

(Suffix code:
Type 2=1)

24 V DC loop power supply

21.6-28.0 V DC
(Max. 30 mA DC)

SDA(-) 302

305

LPS24

(Suffix code: Type 2=0 and


optional suffix code /LP)

306

303

SG

RDB(+) 304
RDA(-) 305

DI/DO (Suffix code: Type 2=2)

External contact input

RS-485

No-voltage
contact

UT Transistor
contact

RSB(+) 407

Common

301 COM

301

RSA(-) 408

Factory default: No function

302 DI11

302

409

Factory default: No function

303 DI12

303

SG

COM
DI11
DI12

UT
+5V
+5V

Function can be
assigned to the
terminals with no
function.

Factory default: No function DO11 305

COM 306

Common

Transistor contact rating: 24 V DC, 50 mA

RS-485 communication/24 V DC loop power supply


RS-485

24 V DC loop power supply

RSA(-) 302

RS-485

UT

Factory default: No function DO12 304

RSB(+) 301

Unlit
Normal

307

OUT (Suffix code: Type1=-0, -1 or -2)

Contact rating: 12 V DC, 10 mA or more

DeviceNet communication (with Modbus master)

(Suffix code: Type 3=3)

107

Relay contact output

External contact output

206

Position proportional control output

109

Contact input / Contact output

Shield ground
Lit

Normal
RDY Communicating
(green) successfully

CC-Link communication (with Modbus master)

205

Control output

(negative data recive/transmit)

LED

ERR
(red)

305
306

206

Current/voltage pulse output Retransmission output 15 V DC loop power supply

108

301-306

PROFIBUS-DP communication (with Modbus master)

ETHR

105
106

(Suffix code: Type 1=-2)

External contact input

Allowable range:
100-240 V AC (10%)
(free voltage)
50/60 Hz shared

Ethernet communication (with gateway function)

0-20 mA DC,
4-20 mA DC,
Voltage pulse (12 V)

RET/OUT2

Can not be used for retransmission output or 15 V


DC loop power suppy when current/voltage pulse
output is used for control output.
Can be used for retransmission output or 15 V DC
loop power suppy when control output is not used.
Current output range can be changed.

205

STOP when DI2=ON


RUN when DI2=OFF

112

10BASE-T/100BASE-TX
RJ45 connector

Cooling-side control output

107

E3-Terminal Area

206

Current/voltage pulse output

Contact input

24 V AC/DC power supply (24 V AC/DC power supply:

100-240 V AC power supply

14.5-18.0 V DC
(Max. 21 mA DC)

206

Load resistance 600 or less


Default: 4-20 mA DC

106

Power supply

(Suffix code:
Type 3=1)

B 203

201
-212

Wiring direction

Relay contact rating: 240 V AC, 1 A


30 V DC, 1 A (resistance load)

RS-485

4-20 mA DC or
0-20 mA DC

301
-312

LPS24

Transistor contact rating: 24 V DC, 50 mA

RS-485 communication RS485

b 202

101
-112

24 V DC loop power supply

Alarm-1 output
(PV high limit)

401-412

A 201

E1-terminal area

Heating/cooling relay contact output (Suffix code: Type 1=-2)

OUT2

RET (Equipped as standard)

Current (mA) input Voltage (mV, V) input

Heating/cooling control output


Cooling NO
-side

Retransmission output

Retransmission output 15 V DC loop power supply Can be used for 15 V DC loop


power supply when not used for
retransmission output.
205
205

Default:
PV retransmission

203

Factory default: No function DO11 305


Common

RTD input

204

Function can be
assigned to the
terminals with no
function.

UT

PV (Equipped
as standard)

TC input

Factory default: No function DO43 503

Contact rating: 12 V DC, 10 mA or more

Factory default: No function DO12 304

103

Terminal wiring differs in Heating/cooling


control and Position proportional control.
Refer to the terminals of Position
proportional control output and
Heating/cooling control output below.
Factory default: Control output is relay.

PV input

202

DI/DO (Suffix code: Type 2=1)

External contact output

COM

Factory default:
PV input type is
undefined.

203

Transistor contact rating: 24 V DC, 50 mA

UT Transistor contact
UT
COM
301 COM
301
+5V
DI11
302
302 DI11
+5V
DI12
303
303 DI12

Factory default: No function

101
102

Factory default: No function DO41 505

+5V

No-voltage
contact

Factory default: No function

NC
NO

OUT

(Suffix code: Type1=-0)

Factory default: No function DO44 502

External contact input


Common

Control output
Relay contact output

Factory default: No function DO42 504

+5V

Function can be assigned to the


terminals with no function.

Contact input / Contact output

E3-terminal area

DO (Suffix code: Type 2=2)

External contact output

External contact input

503

105

E4-Terminal Area

Contact output

103

106

501-506

SG

21.6-28.0 V DC
(Max. 30 mA DC)

305

RS485/LPS24

(Suffix code: Type 2=1 and


optional suffix code /LP)

306

303

RSB(+) 407
No electricity

RSA(-) 408
SG

409

IM 05P01D31-11EN page /12

Operation
Guide

3. Quick Setting Function (Setting of Input and Output)

UT35A/UT32A
Digital Indicating Controllers
Operation Guide

Initial Settings

(6)

This operation guide describes basic settings and operations of the UT35A/UT32A.
For details of each function, see the electronic manual.
The scrolling guide is displayed on PV display in the Parameter Setting Display.
This guide can be turned on/off with the Fn key.

(1)
(2)

(4)
(5)

1. Names and Functions of Display Parts


2. Setup Procedure
3. Quick Setting Function (Setting of Input and Output)
4. Adjusting Valve Position Automatically (for a Position Proportional Type Controller Only)
5. Setting Alarm Type
6. Setting Alarm Setpoint

(1)

(2)

Name

(4)
(3)

(9)

(5)

(10)

(2)
(3)
(11)
(4)

(9)

(5)

UT35A: DISPLAY key


UT32A: DISP key

UT35A:
PARAMETER key
UT32A: PARA key

Hold down the key for 3 seconds to move to the Operation


Parameter Setting Display.
Hold down the key and the Left arrow key simultaneously for 3
seconds to move to the Setup Parameter Setting Display.
Press the key in the Parameter Setting Display to return to the
Menu Display. Press the key once to cancel the parameter setting (setpoint is blinking).

SET/ENTER key
Up/Down/Left/Right
arrow keys

SET/ENTER key
Press the key in the Menu Display to move to the Parameter
Setting Display of the Menu. Press the key in the Parameter
Setting Display to transfer to the parameter setting mode
(setpoint is blinking), and the parameter can be changed.
Press the key during parameter setting mode to register the
setpoint.
Up/Down/Left/Right arrow keys
Press the Left/Right arrow keys in the Menu Display to switch
the Displays.
Press the Up/Down/Left/Right arrow keys in the Parameter
Setting Display to switch the Displays.
Press the Up/Down arrow keys during parameter setting mode
(setpoint is blinking) to change a setpoint.
Press the Left/Right arrow keys during parameter setting mode
(setpoint is blinking) to move between digits according to the parameter.

(10)
(7)
(4)

(8)
(2) + (3) + (4) : Setpoint display
No. in figure

Name

(5)

PV display
(white or red)

(2)

Group display (green)

Displays a group number (1 to 4 or R) and terminal area (E1 to E4).


1 to 4 represent SP numbers in the Operation Display.
R and E1 to E4 are displayed in the Parameter Setting Display.

(3)

Symbol display (orange) Displays a parameter symbol.

(4)

Data display (orange)

Displays a parameter setpoint and menu symbol.

(5)

Bar-graph display
(orange)

Displays control output value (OUT) and measured input value (PV).
The data to be displayed can be set by the parameter.
Initial value: Deviation, Heating-side control output (in Heating/
cooling control)

(6)

Event indicator
(orange)

(7)

Key navigation indicator (green)

Lit when the alarms 1 to 4 occur.


Event displays other than alarms can be set by the parameter.

A/M key

Used to switch between AUTO and MAN modes.


The setting is switched between AUTO and MAN each time the
key is pressed.

User function keys

(6)

The UT35A has F1, F2, and Fn keys.


The UT32A has only the Fn key. The user can assign a function
to the key. The function is set by the parameter.

Note: The communication connector (maintenance port) for LL50A Parameter Setting Software is
on the top of the unit.

Parameter display level

Parameter display level


Easy setting mode
indicator (green)

EASY

PRO

Lit

Unlit

Standard setting mode

Unlit

Unlit

Professional setting mode

Unlit

Lit

(9)

Status indicator
(green and red)

REM

Description
Lit when in remote mode (REM).

STOP

Lit when in stop mode (STOP).

MAN

Lit when in manual mode (MAN).


Blinks during auto-tuning.

(10)

Security indicator (red) Lit if a password is set. The setup parameter settings are locked.

(11)

Ladder operation
indicator (green)

Lit while the ladder operation is executed.

Operation in Initial Display


Press the SET/ENTER key while YES is displayed to start the Quick setting function.
If you change YES to NO and press the SET/ENTER key, Operation Display will
appear without starting the Quick setting function.

Operation for Setting

The following flowchart shows the setup procedure for UT35A/UT32A.


Installation
and wiring

Example: Setting to PID control, thermocouple type K (range of 0.0 to


500.00C), and current control output
For the detailed procedure and switching of displays, see "Flow of Quick Setting
Function" below. For the parameters to set, see the next page.
(1) Press the SET/ENTER key while YES for QSM (Quick setting mode) is displayed.
(2) Set the control type parameter (CNT) to PID (PID control).
(3) Set the PV input type parameter (IN) to K1 (-270.0 to 1370.0 0C).
(4) Set the PV input unit parameter (UNIT) to C (Degree Celsius).
(5) Set the maximum value of PV input range parameter (RH) to 500.0.
(6) Set the minimum value of PV input range parameter (RL) to 0.0.
(7) Set the output type selection parameter (OT) to OUT terminals (current=00.02).
(8) Finally, EXIT is displayed. Change NO to YES and press the SET/ENTER key to
complete the setup. Operation Display appears.

To select the parameter setting displayed as the initial value, press the Down arrow
key to move to the next parameter.

Flow of Quick Setting Function


In Quick setting mode, the parameter guide appears on PV display.
This guide can be turned on/off with the Fn key.

7.

Power-on

Quick setting starts

8.
[NO]
[YES]

9.

First, the control type


parameter (CNT)
is displayed.
Initial value: PID (PID control)

Install and wire a controller.

3.

The upper limit value of the setting range is displayed


for the parameter RH (maximum value of PV input range).
Press the SET/ENTER key.

Select NO with the Down


arrow key and press the
SET/ENTER key.

Press the SET/ENTER key while YES


is displayed to start the Quick setting.

2.

The PV input unit parameter (UNIT) is displayed.


Initial value: C (Degree Celsius)
Press the Down arrow key.

1.

Power ON

Use
Quick setting
function?

Making Settings Using Quick Setting Function

10.

Press the Down arrow key.

The last digit of the upper limit value blinks.


Change the setpoint using the Up/Down arrow keys
to increase and decrease the value and the Left/Right arrow
keys to move between digits.
The parameter RH (maximum value of PV input range)
has been changed to 500.0.
Press the SET/ENTER key.

The PV input type


parameter (IN) is
displayed.
Initial value: OFF

11.
The setpoint for the parameter RH has been registered.

Press the SET/ENTER key.

4.

NO

YES

Control type setup


Input/output setup

Input setup

5.

YES

NO

For Position proportional type


Valve position
adjustment

YES

Position
proportional
type?
NO
Output setup

Other setup

Set the other parameters as needed.

PID tuning

Adjust PID using auto-tuning or manually for PID control.

Operation

Monitoring and control of regular operations

Follow the same procedure to set RL


to 0.0 and OT to 00.02.
Set other parameters as needed.
Select NO to return to
the Operation Display.

K1 is displayed.
Position
proportional
type?

Press the Down arrow key.

OFF blinks.
Blinking allows you to
change the setting.
Press the Up arrow key.

Control type setup

Displays the operating conditions and control status.


Indicator

After turning on the controller, first decide whether or not to use the Quick setting function.

2. Setup Procedure

Lit or blinks when the Up/Down or Left/Right arrow key operation


is possible.
Displays the setting conditions of the parameter display level function.

(8)

Light-loader interface

It is the communication interface for the adapter cable used when


setting and storing parameters from a PC. The LL50A Parameter
Setting Software (sold separately) is required.

Description
Displays PV.
Displays an error code if an error occurs.
Displays the scrolling guide in the Menu Display and Parameter
Setting Display when the guide display ON/OFF is set to ON.

(1)

(3)

(6)

(6)

(11)

(2)

Description

(1)
(8)

(5)

Used to switch the Operation Displays.


Press the key in the Operation Display to switch the provided
Operation Displays.
Press the key in the Menu Display or Parameter Setting Display
to return to the Operation Display.

1. Names and Functions of Display Parts

(2)

(1)

(3)

(6)
No. in figure

Contents

(4)

The Quick setting function is a function to easily set the basic function of the controller.
Turn on the controller to start the Quick setting function.
This function allows you to easily set the control type, input, and output, and quickly
start the control action.
The items (parameters) to be set by Quick setting function are as follows.
(1) Control type (PID control, Heating/cooling control, etc.)
(2) Input function (PV input type, range, scale (at voltage input), etc.)
(3) Output function (control output type and cycle time)

To change and set the parameter setting, press the SET/ENTER key to start the
setpoint blinking. The blinking state allows you to make changes (setting mode).
Use the Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to register the setting.

Press the SET/ENTER key.

12.

Finally, EXIT is displayed.


Press the SET/ENTER key to swtich to the setting mode.
Change NO to YES and press the SET/ENTER key
to complete the setup of the basic function.
Operation Display appears.
The Quick setting function continues in the NO state.

6.
K1 has been registered.

Operation Display

Press the Down arrow key.

Displays the measured


input value (PV).
Displays the target
setpoint (SP).

IM 05P01D31-11EN page /12

OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF

displayed.

Note 1: Open/closed shows status of relay contact, and lit/unlit shows status of EV (event) lamp.

Press the SET/ENTER key.

Parameters to be set

1.

Control Type
Parameter Symbol

Name of Parameter

CNT

Control type

Setting Range
PID: PID control
ONOF: ON/OFF control (1 point of hysteresis)
ONOF2: ON/OFF control (2 points of hysteresis)
2P2L: Two-position two-level control
H/C: Heating/cooling control

MAN
is lit

Note: Some setpoints may not be displayed depending on the model and suffix codes.

Input Function
Parameter Symbol

IN

UNIT

PV input unit

RH

Maximum value of
PV input range

RL

Minimum value of
PV input range

SDP

PV input scale
decimal point
position

SH

Maximum value of
PV input scale

SL

Minimum value of
PV input scale

OFF: Disable
K1: -270.0 to 1370.0 0C / -450.0 to 2500.0 0F
K2: -270.0 to 1000.0 0C / -450.0 to 2300.0 0F
K3: -200.0 to 500.0 0C / -200.0 to 1000.0 0F
J: -200.0 to 1200.0 0C / -300.0 to 2300.0 0F
T1: -270.0 to 400.0 0C / -450.0 to 750.0 0F
T2: 0.0 to 400.0 0C / -200.0 to 750.0 0F
B: 0.0 to 1800.0 0C / 32 to 3300 0F
S: 0.0 to 1700.0 0C / 32 to 3100 0F
R: 0.0 to 1700.0 0C / 32 to 3100 0F
N: -200.0 to 1300.0 0C / -300.0 to 2400.0 0F
E: -270.0 to 1000.0 0C / -450.0 to 1800.0 0F
L: -200.0 to 900.0 0C / -300.0 to 1600.0 0F
U1: -200.0 to 400.0 0C / -300.0 to 750.0 0F
U2: 0.0 to 400.0 0C / -200.0 to 1000.0 0F
W: 0.0 to 2300.0 0C / 32 to 4200 0F
PL2: 0.0 to 1390.0 0C / 32.0 to 2500.0 0F
P2040: 0.0 to 1900.0 0C / 32 to 3400 0F
WRE: 0.0 to 2000.0 0C / 32 to 3600 0F
JPT1: -200.0 to 500.0 0C / -300.0 to 1000.0 0F
JPT2: -150.00 to 150.00 0C / -200.0 to 300.0 0F
PT1: -200.0 to 850.0 0C / -300.0 to 1560.0 0F
PT2: -200.0 to 500.0 0C / -300.0 to 1000.0 0F
PT3: -150.00 to 150.00 0C / -200.0 to 300.0 0F
0.4-2V: 0.400 to 2.000 V
1-5V: 1.000 to 5.000 V
4-20: 4.00 to 20.00 mA
0-2V: 0.000 to 2.000 V
0-10V: 0.00 to 10.00 V
0-20: 0.00 to 20.00 mA
-1020: -10.00 to 20.00 mV
0-100: 0.0 to 100.0 mV
-: No unit, C: Degree Celsius
-: No unit, - -: No unit, - - -: No unit, F: Degree Fahrenheit
Depends on the input type.
- For temperature input Set the temperature range that is actually controlled.
(RL<RH)
- For voltage / current input Set the range of a voltage / current signal that is applied.
The scale across which the voltage / current signal is
actually controlled should be set using the maximum value
of input scale (SH) and minimum value of input scale (SL).
(Input is always 0% when RL = RH.)
0: No decimal place
1: One decimal place
2: Two decimal places

OT
Upper two digits
Lower two digits

CT

CTc

Control output cycle


time
Heating-side control
output cycle time
(in Heating/cooling
control)

Setting Range
Control output or Heatingside control output (Lower
two digits)
00: OFF
01: OUT terminals
(voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay)
06: OUT2 terminals (relay)
07: RET/OUT2 terminals
(voltage pulse)
08: RET/OUT2 terminals
(current)

Cooling-side control output


(Upper two digits)
00: OFF
01: OUT terminals
(voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay)
06: OUT2 terminals (relay)
07: RET/OUT2 terminals
(voltage pulse)
08: RET/OUT2 terminals
(current)

Alarm Type (Alarm Setpoint)

PV high limit (01)


Analog input PV high limit (19)

Open
(unlit)

ON is displayed.
Blinks during the change.

PV low limit (02)


Analog input PV low limit (20)

Closed
(lit)

ON has been registered and the automatic


adjustment of the valve position starts.
V.AT blinks during the automatic adjustment.
After the adjustment is completed, press
the DISPLAY key or DISP key once to return
to the Operation Display.
When the adjustment is completed normally, the indication
automatically returns to OFF.
When VAT.E appears on PV display, it indicates an error.
Check the wiring for feedback input and perform the
automatic adjustment again. To perform a valve adjustment
manually, see Users Manual.

5. Setting Alarm Type


The following operating procedure shows an example of changing the alarm-1 type
(factory default: PV high limit alarm) to PV low limit alarm (setpoint: 02).

1.

Open
(unlit)

Alarm setpoint

Closed
(lit)

Cooling-side control
output cycle time
(in Heating/cooling
control)

4. Adjusting Valve Position Automatically



(for a Position Proportional Type Controller Only)
The following operating procedure describes how to input feedback signals from the
control valve and adjust the fully-open and fully-closed positions of the control valve
automatically. The fully-open and fully-closed positions of the valve can be adjusted
automatically by inputting feedback signals from the valve. To adjust the valve position, you need to carry out the connection and bring the controller into manual mode.
For the connection, see 6. Terminal Wiring Diagrams in "Installation and Wiring",
and for the manual mode, see 5. Switching between AUTO and MAN in "Operations."

MODE menu is displayed.

The parameter AL1 (alarm-1 type) is


displayed.
Press the SET/ENTER key.

5.

Deviation setpoint

Open
(unlit)

SP or Target SP

Closed
(lit)

PV

Closed
(lit)

Open
(lit)

Deviation
setpoint

5.

Open
(lit)

Closed
(unlit)

PV

Open
(unlit)

Open
(lit)

Closed
(unlit)

Closed
(unlit)

Press the SET/ENTER key.

PV
Deviation
setpoint
SP or Target SP

Hysteresis

Closed
(lit)

Open
(lit)

Closed
(unlit)

Alarm setpoint

Alarm setpoint

Output

Hysteresis

Blinks during the change.

Change the setpoint using the Up/Down arrow


keys to increase and decrease the value and
the Left/Right arrow keys to move between digits.

SP or Target SP

Hysteresis Hysteresis

Hysteresis

Output

Press the SET/ENTER key.

PV

Hysteresis Hysteresis

SP or Target SP

Open
(unlit)

Display the parameter and group


that need to be changed.

Closed
(unlit)

Deviation setpoint

PV

PV
Deviation
setpoint
SP or Target SP

6.

The setpoint has been registered.


After the setup is completed, press
the DISPLAY key or DISP key once
to return to the Operation Display.

Hysteresis

Control output low limit (16)


Cooling-side control output
low limit (18)

Closed
(lit)

Feedback input high limit (27)

Fault diagnosis alarm (30)


Burnout of PV input, ADC failure, RJC error.

Open
(unlit)

Open
(lit)

Alarm setpoint Output

Feedback input low limit (28)

4.

PV

Open
(lit)

Alarm setpoint

ALRM menu is displayed.


Press the SET/ENTER key.

Open
(lit)

Open
(unlit)

Hysteresis Hysteresis

Press the Right arrow key until ALRM menu appears.

3.

Closed
(unlit)

SP or Target SP

Control output high limit (15)


Cooling-side control output
high limit (17)

Each parameter and group can be changed


in the Parameter Setting Displays of alarms
using arrow keys.
Up/Down arrow keys: parameters
Left/Right arrow keys: groups

Hysteresis

Hysteresis Hysteresis

Open
(unlit)

SP or
Target SP

SP or Target SP

Deviation setpoint

Deviation within high and low


limits (08)
Target SP deviation within high
and low limits (14)

Group

Hysteresis

Closed
(lit)

Deviation setpoint

Deviation
setpoint

The parameter A1 is displayed.


A1 to A4 represent the alarm-1 to -4 setpoints.

Closed
(unlit)

Hysteresis

Hold down the key for 3 seconds.


0.5 to 1000.0 s

Alarm setpoint

Alarm setpoint

SP or
Target SP

Closed
(lit)

Press the Down arrow key until A1 appears.

4.

Hysteresis

SP or Target SP

Deviation high and low


limits (07)
Target SP deviation high and
low limits (13)

Press the SET/ENTER key.


Open
(lit)

Open
(lit)

Hysteresis

Deviation low limit (06)


Target SP deviation low limit (12)

SP menu is displayed.

PV

SP or
Target SP

Open
(unlit)

PV

3.

Closed
(unlit)

Closed
(unlit)

Alarm setpoint

Open
(unlit)

Display MODE menu with the same procedure as described in


Setting Alarm Type.

Hysteresis

Closed
(lit)

Closed
(lit)

Deviation high limit (05)


Target SP deviation high
limit (11)

Show the Operation Display.

2.

Open
(lit)

Hysteresis
SP low limit (04)
Target SP low limit (10)

2.

Alarm setpoint

Alarm setpoint

PV

SP or
Target SP

Show the Operation Display.

Hysteresis

Hysteresis
SP high limit (03)
Target SP high limit (09)

Open
(lit)

PV

Open
(unlit)

Alarm setpoint

1.

Press the Right arrow key.

Hysteresis

Hysteresis

Press the SET/ENTER key.

7.

The following operating procedure shows an example of setting the alarm-1 setpoint
of group 1 to 180.0.
Before setting the alarm setpoint, check the alarm type.
To change the alarm type, see 5. Setting Alarm Type.

Closed
(unlit)

Closed
(lit)

Alarm setpoint

PV

Press the Up arrow key.

Time

Power-on

Hysteresis

OFF blinks.

Latch action (0/1/2/3/4)


See Users Manual.

Alarm Action (De-energized)

No alarm (00)

The alarm output does not turn on


in this region even if the PV valule
is below PV low limit alarm setpoint.

6. Setting Alarm Setpoint

Alarm Action (Energized)

5.

-19999 to 30000, (SL<SH), | SH - SL | 30000

Name of Parameter

Stand-by action
Energized/De-energized
Latch action

The parameter V.AT (automatic valve


position adjustment) is displayed.
Press the SET/ENTER key.

6.

Without (0) or With (1)


Stand-by action

To change the alarm type, change the last 2 digits of the


5-digit value.
Stand-by action and excitation are turned on or off by
selecting 1 or 0. (See Setting Display of Alarm Type. )
For the latch action, see User s Manual.

Press the SET/ENTER key.

Abnormal
The alarm output
turns on.
PV low limit
alarm setpoint

Energized (0) / De-energized (1)

The alarm-1 type setpoint 02 (PV low limit)


is registered.
After the setup is completed, press the DISPLAY key
or DISP key once to return to the Operation Display.
Symbol

OUT menu is displayed.

3: Three decimal places


4: Four decimal places

Output Function

Output type selection

6.

Normal

Treated
as normal

Alarm type

Press the SET/ENTER key.

Hold down the keys for 3 seconds.

Stand-by Action
C

Change the setpoint using the Up/Down arrow keys


to increase and decrease the value and
the Left/Right arrow keys to move between digits.

3.

4.

Negative setpoint

The last digit of the setpoint blinks.

Press the Right arrow key until OUT menu appears.

Setting Range

Note 1: SDP, SH, and SL are displayed only for voltage/current input.
Note 2: W: W-5%Re/W-26%Re (Hoskins Mfg.Co.), ASTM E988

Parameter Symbol

Show the Operation Display.

* When a password is set, PASS is displayed.


If the correct password is not entered, setup
parameters cannot be changed.

Positive setpoint,

Setting Display of Alarm Type

CTL menu is displayed.

Name of Parameter

PV input type

5.

2.

Note 2:

Closed
(unlit)

Output

FAIL (31)
For the factory default, the contact output is turned ON in normal operation,
OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF

PV velocity (29)

Note 1: Open/closed shows status of relay contact, and lit/unlit shows status of EV (event) lamp.
Note 2:

Positive setpoint,

Negative setpoint

Setting Display of Alarm Type

IM 05P01D31-11EN page /12

Stand-by Action
C

Treated

Normal

Abnormal

Operation
Guide

UT35A/UT32A
Digital Indicating Controllers
Operation Guide

2. Setting Target Setpoint (SP)

OFF blinks.
Press the Up/Down arrow keys to display the required setpoint.

Operations

6.
This operation guide describes key entries for operating the UT35A/UT32A.
Although the display of UT35A is used in this guide, UT32A can be operated similarly.
For operations using external contact inputs, see DI of 6. Terminal Wiring Diagrams
in Installation and Wiring.
If you cannot remember how to carry out an operation during setting, press the
DISPLAY key or DISP key once. This brings you to the display (Operation Display) that
appears at power-on.
The scrolling guide is displayed on PV display in the Parameter Setting Display.
This guide can be turned on/off with the Fn key.

1.
2.

Press the SET/ENTER key to start the


last digit of the setpoint blinking.
Blinking allows you to change the value.

3.

To set the setpoint, use the


Left/Right arrow keys to move
between digits and the Up/Down
arrow keys to increase and
decrease the value.

1.

Monitoring-purpose Operation Displays Available during Operation


Setting Target Setpoint (SP)
Performing/Canceling Auto-tuning
Selecting Target Setpoint Numbers (SPNO.)
Switching between AUTO and MAN
Switching between RUN and STOP
Switching between REM (Remote) and LCL (Local)
Manipulating Control Output in Manual Mode
Troubleshooting

4.

When the required value is displayed,


press the SET/ENTER key to register
the setpoint.

Blinks during the change.

The setting range is 1 to 4 (represent group numbers) or R.


To perform auto-tuning for the PID of group 1, set the parameter AT to 1.
To quit the auto-tuning, set the parameter to OFF.

Show the SP Display (Operation Display).


(This is an example of setting the target
setpoint to 150.0).

Contents
1.
2.
3.
4.
5.
6.
7.
8.
9.

5. Switching between AUTO and MAN

5.

Press the SET/ENTER key.

7.

8.
The MAN lamp goes off, which means that
the auto-tuning completed normally.

3. Performing/Canceling Auto-tuning
Auto-tuning should be performed after setting a target setpoint.
Make sure that the controller is in automatic mode (AUTO) and in run mode (RUN)
before auto-tuning. For setting to AUTO, see 5. Switching between AUTO and
MAN, and for setting to RUN, see 6. Switching between RUN and STOP.
If the setpoint is known in advance or auto-tuning does not find any appropriate PID
constants, set the PID manually. For setting the PID manually, see Users Manual.

4. Selecting Target Setpoint Numbers (SPNO.)


The following operating procedure shows an example of changing the target setpoint
number (SPNO.) from 1 to 2. Each SP has its PID group. The PID group set for the
parameter PIDN (PID number selection) is used.

1.

Show the Operation Display.

SP Display
(SP can be changed.)

OUT Display
(OUT can be changed.)

1.

When AUTO is switched into MAN, the control output value in AUTO mode is held.
The controller can be operated manually from the hold value.
If the manual preset output is set (MPON parameter OFF), the controller can be
operated manually from the arbitrary output value (MPO1 to MPO5 parameters).

RUN and STOP switching can be performed using any of the following: (1) Contact
input, (2) Parameter, (3) Communication, and (4) User function key.
The following shows an example of switching using the contact input.
(The switching function is assigned to DI2 contact for the factory default.)
For details of other switching methods and the display appearing when the operation
is started, see Users Manual.
When the controller is stopped, input and outputs are as follows:
PV input

Displays the PV value.

Control output

Displays the preset output value.


The preset output value is set for each PID group.

Alarm output

Turns the output on in case of an alarm.

Display in STOP mode

Display in STOP mode


Hold down the PARAMETER key or PARA key for
3 seconds to display MODE menu.

210
DI2

OFF: Operation RUN


212

210

3.

Show the Operation Display.

ON: Operation STOP

DI2

Press the SET/ENTER key.

Operation Display Switching Diagram for Heating/Cooling Type


SP Display
Displays the measured input value on PV display.
Displays the target setpoint (SP) on Setpoint display (SP can be changed).
OUT Display
Displays the measured input value on PV display.
Displays the control output values (C.H.) of heating and cooling sides on Setpoint
display (C.H. can be changed in manual mode).

key,

AUTO and MAN is switched alternately.

STOP is displayed on Symbol display and "preset output value" is displayed on


Data display.

2.
Do not perform auto-tuning for the following processes.
Tune PID manually.
Processes with fast response such as flow rate control and presCAUTION
sure control.
Processes which do not allow the output to be turned on and off
even temporarily.
Processes which prohibit severe output changes at control
valves (or other actuators).
Processes in which product quality can be adversely affected if
PV values fluctuate beyond their allowable ranges.

Each time you press the

6. Switching between RUN and STOP

Operation Display Switching Diagram for Standard and Position Proportional Types
SP Display
Displays the measured input value on PV display.
Displays the target setpoint (SP) on Setpoint display (SP can be changed).
OUT Display
Displays the measured input value on PV display.
Displays the control output value (OUT) on Setpoint display (OUT can be changed
in manual mode).
Displays the valves feedback input value (at 0 to 100% valve opening) in Position
proportional control.

MAN lamp is lit in MAN mode.

The setpoint has been registered.


This starts auto-tuning.
The limiter can be set to the output during auto-tuning.
For details, see Users Manual.
During auto-tuning,
The MAN lamp blinks.
The OUT symbol appears.
The output values at 100.0% and
0% appear alternately.

Monitoring-purpose Operation Displays Available during Operation

AUTO and MAN switching can be performed using any of the following: (1) A/M key,
(2) Contact input, (3) Communication, and (4) User function key.
The figure below shows a direct operation using the A/M key.
When AUTO and MAN switching function is assigned to the contact input, and the
contact input is ON, the switching by key operation cannot be performed.
For details, see Users Manual.

212

In cases where the communication is


specified, the parameter R.L
(REMOTE/LOCAL switch) is displayed.

Preset output (PO)


Valve opening (0-100%) for
Position proportional type

Press the Down arrow key until the parameter SPNO.


appears.

STOP lamp is lit.

4.

2.

The parameter SPNO. (SP number selection)


is displayed.

Hold down the PARAMETER key or PARA key for


3 seconds to display MODE menu.

Press the SET/ENTER key.

5.
Press the SET/ENTER key.

Display in STOP mode in Heating/cooling control


Cooling-side preset output value is displayed on the left side of the ST symbol,
and Heating-side preset output value is on the right side.

Display in STOP mode


Change the setpoint using
the Up/Down arrow keys.

210

OFF: Operation RUN

DI2
212

Blinks during the change.

3.
SP Display
(SP can be changed.)

Heating/cooling OUT Display


(OUT can be changed.)

After showing the OUT Display, press the DISPLAY key or DISP key to show the following displays conditionally.
For details, see Users Manual.

Standard, Position Proportional, and Heating/Cooling Types


SELECT Displays 1 to 5 (which appear when registered)
Analog Input Display (display only) (factory default: non-display)
Position Proportional Computation Output Display (display only) (factory default:
non-display)
PID Number Display (display only) (factory default: non-display)
Heater Break Alarm-1 Current Display (display only) (for heater break alarm option only)
Heater Break Alarm-2 Current Display (display only) (for heater break alarm option
only)

In cases where the communication is


specified, the parameter R.L
(REMOTE/LOCAL switch) is displayed.

Press the SET/ENTER key.

6.

Press the Down arrow key until the parameter AT appears.

210

ON: Operation STOP

DI2

The setpoint has been registered.


Press the DISPLAY key or DISP key once
to return to the Operation Display.

4.

212

Heating-side preset output (PO)


The parameter AT (auto-tuning switch) is displayed.
Press the SET/ENTER key.

Cooling-side preset output (POc)

7.

STOP lamp is lit .


SPNO. has been changed to 2.

IM 05P01D31-11EN page /12

7.

Switching between REM (Remote) and LCL (Local)

8. Manipulating Control Output in Manual Mode

Remote and local switching can be performed using any of the following:
(1) Contact input, (2) Parameter, (3) Communication, and (4) User function key.

NOTE

LCL (Local)

In manual mode, control output is manipulated by operating the keys (the value is
changed using the Up/Down arrow keys, then outputted as it is).
Even if the SET/ENTER key is not pressed, the control output value changes according to the displayed value.
In stop mode (when the STOP lamp is lit), control output cannot be manipulated.

Control is performed using the target setpoint set on the controller.

REM (Remote)
Control is performed using a setpoint via communication for the target setpoint. The
following shows an example of switching from local to remote using the parameter.
(Only in cases where the communication is specified.)
For details of other switching methods, see Users Manual.
The PID group for the local SP number is used as PID in remote mode.

Up arrow key: increases control output.


Down arrow key: decreases control output.

n Errors at Power On

The errors shown below may occur in the fault diagnosis when the power is turned on. (For details of Setpoint display and input/output action when each error occurs, see Users Manual.
PV display
(Operation
Display)

Status indicator
(Operation Display)

Parameter that displays error


details

Faulty MCU RAM / MCU ROM

MCU RAM / MCU ROM are failed.

Faulty.
Contact us for repair.

System data error

System data is corrupted.

Faulty.
Contact us for repair.

User (parameter) default value


error

User parameter is corrupted.


Initialized to factory default value.

Setup parameter error

Setup parameter data is corrupted.


Initialized to user default value.

Operation parameter error

Operation parameter data is corrupted.


Initialized to user default value.

Nonresponding hardware of
extended function (E1 to E4terminal areas)

Inconsistence of system data and


hardware of extended function.
Nonresponding communication between
hardware of extended function (E1 to E4terminal areas).

Indication off Indication off

SYS - - - - PAR 0004

(for user default value error


only)

PAR 0010

ERR

NOTE

Setup parameter (PA.ER)

(for setup parameter error


only)

PAR 0020

(for operation parameter error only)

SLOT 0015

When the contact input is ON, operation cannot be performed using the parameter,
communication, or key. When the contact input is OFF and the setting is switched
using the parameter, communication, or key, the last switching operation is performed.

1.

Setpoint display
(Operation Display)

(0015: Error occurs to all


hardware of E1 to E4-terminal
areas.)

MAN lamp is lit.


In Position proportional control:
Up arrow key; opens the valve.
Down arrow key; closes the valve.
Output; only while pressing a key.
OUT; valve opening (0-100%)

Show the Operation Display.

2.

Output manipulation in Position proportional control


is not restricted from output limiters (OH, OL).

Hold down the PARAMETER key or PARA key


for 3 seconds to display MODE menu.

Manual operation in Heating/cooling control

Normal
indication

Normal indication

Normal
indication

Normal indication

Normal
indication

Setup parameter (OP.ER)

Rightmost decimal point


on PV display blinks.
Rightmost decimal point
on Symbol display blinks.
LADDER lamp blinks

0.000 00000

(Decimal point on the left of


the Symbol display blinks)

Error description

Calibration value error


Setup parameter (PA.ER)
Faulty FRAM

Cause and diagnosis

Remedy

Check and reconfigure the initialized


setting parameters. Error indication is
erased when the power is turned on
again.

Faulty.
Contact us for repair.

Initialized to calibrated default value because


of corrupted factory default value.
Faulty.
Contact us for repair.
Data writing (storing) to FRAM is impossible.

Setup parameter (LA.ER)

Corrupted ladder program

Ladder program is corrupted.


Operates without ladder program.

Download the ladder program again.

Setup parameter (OP.ER)

User profile error

User profile is corrupted.

Download the user profile again.

n Errors during Operation

The errors shown below may occur during operation. (For input/output action when each error occurs, see Users Manual.

Heating-side control output

3.

Cooling-side control output

Up arrow key: concurrently decreases cooling-side control output and increases


heating-side control output.
Down arrow key: concurrently increases cooling-side control output and decreases
heating-side control output.
(Either none of the heating-side and cooling-side outputs are presented, or both of
them are presented according to the dead band setting.)

Change the operation mode using


the Up/Down arrow keys.
Blinks during the change.

Actual output (%)


100

Press the SET/ENTER key.

5.

Actual output (%)


100

Heating-side
manipulated output

Cooling-side
manipulated output

Heating-side
manipulated output

Cooling-side
manipulated output

The REM lamp is lit.


-12.4

12.4

Control computation output


DB=24.8

Parameter that displays


error details

-12.4

Error description
Analog input terminal ADC error
PV input

(Displays RJC. Normal indication (Note)


E and PV
alternately.)

Setup parameter (AD1.E)

Universal input terminal RJC error


Universal input terminal RJC error
PV input

Faulty.
Contact us for repair.
Set the parameter RJC to OFF to erase
error indication.

Setup parameter (AD1.E)

Analog input terminal burnout error


Analog input terminal sensor burnout
PV input

Check wiring and sensor.


Error indication is erased in normal
operation.

Setup parameter (PV1.E)

PV input burnout error

Burnout of analog input connected to PV

Check wiring and sensor of connected


analog input terminals.
Error indication is erased in normal
operation.

B.OUT

Normal indication (Note)

Normal indication

Setup parameter (PV1.E)

PV input over-scale
PV input under-scale
(PV values out of -5 to 105%)

PV input is out of -5 to 105%. Also occurs


when the data out of range which is the
ladder calculation result is input.

Check analog input value or ladder


program.

Normal
indication

OUT - - - - -

Setup parameter (AD2.E)

Feedback input resistor/current


burnout

Feedback input burnout

Check wiring of feedback input resistor/


current. Error indication is erased in
normal operation.

Ladder calculation overflow

Floating point computation for ladder


calculation is infinite.

Check the ladder program.

Load factor over 100%

Computation does not end within the


control period (load factor is 100% or
more).

Change the control period or reduce


the number of steps for the ladder
program.

Load factor over 200%


(Forced end)

Computation does not end within the control


period (load factor is 200% or more).

Change the control period or reduce the


number of steps for the ladder program.

Ladder program is corrupted.

Download the ladder program again. If


the error indication is still not erased,
there is a fault. Contact us for repair.

Normal indication

LADDER lamp blinks

Setup parameter (LA.ER)

Normal
indication

9. Troubleshooting

0.000 00000

If the Operation Display does not appear after turning on the controllers power, check the procedures in the following flowchart.
If a problem appears to be complicated, contact our sales representatives.
Is the controller
defective?
Yes
Key
operation
failure?

No

Completely
inactive?
Yes

Yes

Check wiring of the


power terminals.

Check the key lock


setting.

Display
failure?
*
Yes
Turn off power, and
then turn it on again.

No

No

I/O signal
failure?

Yes

Check the I/O specifications


of the controller.

No
No

Yes

Correct the error(s).

No

Contact us for repair.

Is the
key locked?
Yes

* The LCD (a liquid crystal display) is used for


a display portion of this product.
The LCD has a characteristic that the display action
Yes
Cancel the setting. becomes late at the low temperature.
Additionally, the luminance and contrast degradation
are caused due to aged deterioration.
However, the control function is not affected.
Problem solved.

Correct?

Communication
failure?

Yes

Check the
specifications and polarity
of connected devices .

Check the
supply voltage.

Normal?

No

No communication
capability

Check the specifications


of the controller.
No

With
communication?
Yes

Check the communicationrelated parameters.

Instantaneous power failure within 20 ms.


A power failure is not detected. Normal
operation continues.
Power failure for less than about 5 seconds,
or for about 5 seconds or more.
Affects the "settings" and "operation status."
For details, see User's Manual.

NOTE
Write down the settings of parameters for a
repair request.

Faulty.
Contact us for repair.

OVER
-OVER

DB= -24.8

Remedies if Power Failure Occurs


during Operations

Analog input terminal AD value error

Ladder program error

Troubleshooting Flow

Remedy

Setup parameter (AD1.E)

12.4

Manipulated output change


when a dead band is negative (-)

Cause and diagnosis

Control computation output

Dead band: Operation parameter DB

Manipulated output change


when a dead band is positive (+)

Status indicator
(Operation Display)

RJC.E

Target setpoint (SP) number

Press the SET/ENTER key.

Setpoint display
(Operation Display)
Normal indication (Note)

AD.ERR

Symbol of cooling side

The parameter R.L (REMOTE/LOCAL switch)


is displayed.

4.

PV display
(Operation
Display)

Symbol of heating side

Press the SET/ENTER key.

Check that the target devices are


connected correctly.
Recovery at normal receipt.

(Decimal point on the left of


the Symbol display blinks)

Setup parameter (OP.ER)

Peer-to-peer communication error Peer-to-peer communication error

AT.E

Normal indication

Setup parameter (PV1.E)

Auto-tuning time-out

Auto-tuning does not end even when 24


Check the process. Hold down any key to
hours have elapsed after the start of tuning. erase the error indication

VAT.E

Normal indication

Setup parameter (AD2.E)

Valve position automatic


adjustment error

Fully-closed valve position is equal to or larger


Check wiring and valve. Hold down any
than the fully-open valve position after automatic
key to erase the error indication.
valve position adjustment is performed.

Setup parameter (OP.ER)

Communication error
(RS-485 communication)

Framing parity error


Buffer overflow
Inter-character time-out
Checksum error (PC link communication with
checksum)
CRC check error (Modbus/RTU)
LRC check error (Modbus/ASCII)

Setup parameter (OP.ER)

Communication error
(coordinated operation)

Inconsistence of loop between coordinated Check the communication parameters.


Recovery at normal receipt. Change from remote
master and slaves
to local mode to stop blinking.
When the mode is changed from remote to
Communication from coordinated master is local, SP tracking does not work even if it is
interrupted for 2 seconds.
set to ON.

Setup parameter (OP.ER)

User profile error

User profile is corrupted.

Faulty FRAM

Writing (storing) data to FRAM is impossible. Faulty. Contact us for repair.

Faulty MCU / DCU


(ROM / RAM error, corrupted)

MCU / DCU is corrupted.

Normal
indication

Normal
indication

Normal
indication
Normal
indication
Undefined

0.000 00000

(Decimal point on the left of


the Symbol display blinks)

0.000 00000

(Decimal point on the left of


the Symbol display blinks)

0.000 00000

(Decimal point on the left of


the Symbol display blinks)
Normal indication
Undefined

Rightmost decimal point on


Setup parameter (PA.ER)
Symbol display blinks.

Check the communication parameters.


Recovery at normal receipt.
Hold down any key to stop blinking.

Download the user profile again.

Faulty. Contact us for repair.

Note: When an error occurs in input shown in Analog input display (Operation display), Setpoint display shows the same symbol as the PV display.

Check the
communication wiring.

Check the specifications


of communication
devices.

IM 05P01D31-11EN page /12

Operation
Guide

UT35A/UT32A
Digital Indicating Controllers
Operation Guide

n SP and Alarm Setpoint Setting Parameter

n Alarm Function Setting Parameter

Menu symbol:

Menu symbol:

Parameter
symbol

Parameters

(SP)

Yokogawa Electric Corporation

(SUB)

This operation guide describes the functions of parameters briefly. The parameter
symbols listed are in the order shown on the display in each group of menu symbols.
In addition, each parameter table has a User Setting column, where you can record
your setpoints when setting them in the controller. The scrolling guide is displayed on
PV display in the Parameter Setting Display. This guide can be turned on/off with
the Fn key.

Operation Parameters

Operation Dsipaly

DISPLAY key
or DISP key

Hold down PARAMETER key or PARA key


for 3 sec.
Menu

key

Menu

Parameter

Parameter

key

key
Parameter
END

END

Parameter

Parameter
END

Parameter
END
,

STOP/RUN switch

Initial
value

Setting Range
STOP: Stop mode
RUN: Run mode
Preset output (PO) is generated in
STOP mode.
Default: Not displayed. STOP/RUN
switch is assigned to contact input.

LCL: Local mode


REM: Remote mode
REMOTE/LOCAL switch
(Displayed only in cases where the
communication is specified.)

User Display
setting level

Set a display value of setpoint of PV


alarm, SP alarm, deviation alarm,
output alarm, or velocity alarm.
-19999 to 30000 (Set a value within the
input range.)
Decimal point position depends on the
input type

n=2

n=3

Initial
value

User Display
setting level

Table
below

EASY

to
(AL1 to AL4)

n=4

SP number selection

1 to 4 (Depends on the setup parameter SPGR. setting.)

PID number

The PID group number being selected


is displayed.
1 to 4, R: PID group for reference
deviation

Setting Range

Initial
value

Proportional band
Heating-side proportional band (in Heating/cooling control)

0.0 to 999.9%
When 0.0% is set, it operates as
0.1%.
Heating-side ON/OFF control applies
when 0.0% in Heating/cooling control

5.0%

(I)

Integral time
Heating-side integral time
(in Heating/cooling control)

OFF: Disable
1 to 6000 s

240 s

(D)

Derivative time
Heating-side derivative time
(in Heating/cooling control)

OFF: Disable
1 to 6000 s

60 s

Control output high limit


Heating-side control
output high limit (in
Heating/cooling control)

-4.9 to 105.0%, (OL<OH)


In Heating/cooling control: 0.1 to
105.0% (OL<OH)

Control output low limit


Heating-side control
output low limit (in Heating/cooling control)

-5.0 to 104.9%, (OL<OH), SD: Tight


shut
In Heating/cooling control: 0.0 to
104.9% (OL<OH)

0.0%

Manual reset

Enabled when integral time is OFF.


The manual reset value equals the
output value when PV = SP.
-5.0 to 105.0%

50.0%

(P)

AL1,
AL3:
PV high
limit (01)
Alarm type: 2 digits
Without
00: Disable
Stand01: PV high limit
by
02: PV low limit
action
03: SP high limit
(0)
04: SP low limit
Ener05: Deviation high limit
gized
06: Deviation low limit
Alarm-1 to 4 type
(0)
07: Deviation high and low limits
Example: Alarm-1
08: Deviation within high and low limits Latch
action
09: Target SP high limit
(0)
10: Target SP low limit
Alarm
11: Target SP deviation high limit
Latch action
type
AL2,
12: Target SP deviation low limit
Energized/
AL4:
13: Target SP deviation high and low limits
De-energize
PV low
14: Target SP deviation within high
limit (02)
Stand-by
and low limits
action
Without
15: OUT high limit
Stand16: OUT low limit
by
17: Cooling-side OUT high limit
action
18: Cooling-side OUT low limit
(0)
19: Analog input PV high limit
Table
Ener20: Analog input PV low limit
below
gized
27: Feedback input high limit
(0)
28: Feedback input low limit
Latch
29: PV velocity
action
30: Fault diagnosis
(0)
31: FAIL

n SP-related Setting Parameter


Menu symbol:
Parameter
symbol
(RT)

(RBS)

(DNR)

(PVT)

to

(SPS)
Name of Parameter
Remote input ratio

Remote input bias

SP ramp-up rate

SP ramp-down rate

SP ramp-rate time unit

SP tracking selection

PV tracking selection

Setting Range

Initial
value

SP = Remote input x RT + Remote


input bias
0.001 to 9.999

1.000

-100.0 to 100.0% of PV input range


span (EUS)

0.0 %
of PV
input
range
span

Used to prevent SP from changing


suddenly.
Set a ramp-up rate or ramp-down rate
per hour or minute. Set a time unit
using the parameter TMU.
OFF, 0.0 + 1 digit to 100.0% of PV
input range span (EUS)
HOUR: Ramp-up rate or ramp-down
rate per hour
MIN: Ramp-up rate or ramp-down
rate per minute
Tracking is performed when the mode
changes from Remote to Local. (The
local setpoint keeps track of the
remote setpoint.)
OFF, ON
Causes the setpoint to keep track of
the PV so the setpoint automatically
reverts to its original value at a preset
rate of change. The UPR, DNR, and
TMU are used in combination. Operating conditions: 1) MAN AUTO, 2)
STOP AUTO, 3) Power-on, 4) SP
number change, 5) SP change
OFF, ON

User Display
setting level

(VT1 to VT4)

to
STD

to
(DYN1 to DYN4)
EASY

0.01 to 99.59 (minute.second)

Alarm-1 to -4 hysteresis

Set a display value of setpoint of


hysteresis.
-19999 to 30000 (Set a value within
the input range.)
Decimal point position depends on
the input type.
When the decimal point position for
the input type is set to "1", the initial
value of the hysteresis is "1.0".

(HY1 to HY4)

OFF

OFF

PV velocity alarm time


setpoint 1 to 4

(AMD)

Alarm-1 to -4 On-delay
timer

An alarm output is ON when the delay


timer expires after the alarm setpoint
is reached.
0.00 to 99.59 (minute.second)

Alarm mode

0: Always active
1: Not active in STOP mode
2: Not active in STOP or MAN mode

(OH)

(OL)

(MR)

EASY

Parameter

n=1

n=2

n=3

10

(SU.HY)

Sub-hysteresis (in
Two-position two-level
control)

(HY.UP)

Upper-side hysteresis
(in ON/OFF control)

OFF

(HY.LO)

Lower-side hysteresis
(in ON/OFF control)

(DR)

Direct/reverse action
switch

n=4
(SU.DR)

VTn

n: alarm number

n PV-related Setting Parameter


Parameter
symbol

(BS)

PV input bias

Setting Range

-100.0 to 100.0% of PV input range


span (EUS)

0.0 %
of PV
input
range
span

OFF, 1 to 120 s

OFF

1
(FL)

PV input filter

Initial
value

User Display
setting level

EASY

Registered
parameter
symbol

SELECT parameter 10
to 19
n=10

n=11

n=12

Initial
value

Setting range of a registered parameter.


For details, see User's Manual.
n=13

n=14

n=15

n=16

CSn

For the registration of SELECT parameters, see User's Manual.

n=17

User Display
setting level
Table
below

EASY

n=18

n=19

0.0 to 100.0% of PV input range


span (EUS)

0.5 %
of PV
input
range
span
0.5 %
of PV
input
range
span
RVS

RVS: Reverse action


DIR: Direct action

STD
DIR

(Ic)

Cooling-side integral
time

OFF: Disable
1 to 6000 s

240 s

(Dc)

Cooling-side derivative
time

OFF: Disable
1 to 6000 s

60 s

(OHc)

Cooling-side control
output high limit

0.1 to 105.0%, (OLc<OHc)

100.0%

(OLc)

Cooling-side control
output low limit

0.0 to 104.9%, (OLc<OHc)

0.0%

Cooling-side ON/OFF
control hysteresis

0.0 to 100.0%

0.5%

Output dead band (in


Heating/cooling control
or Position proportional
control)

In Heating/cooling control: -100.0 to


50.0%
In Position proportional control: 1.0
to 10.0%

3.0%

Preset output
Heating-side preset
output (in Heating/cooling control)

In STOP mode, fixed control output


can be generated. In Position proportional control, Valve opening can be
set; -5.0 to 105.0%

0.0%

Sub-preset output (in


Two-position two-level
control)

In STOP mode, fixed sub-control


output can be generated.
0%, 100%

0%

Cooling-side preset
output

In STOP mode, cooling-side fixed


control output can be generated.
-5.0 to 105.0%

0.0%

(DB)

Setting Range

0.5 %
of PV
input
range
span

5.0%

(HYSc)

(PO)

(SU.PO)

(POc)

EASY

In Heating/
cooling
control
or
Position
proportional
control:
0.5 %

(Pc)

(CS)
Name of Parameter

In
ON/OFF
control
or
Twoposition
two-level
control:
0.5 % of
PV input
range
span

0.0 to 999.9%
(Cooling-side ON/OFF control
applies when 0.0% in Heating/cooling control)

(PVS)
Name of Parameter

Sub-direct/reverse
action switch (in Twoposition two-level
control)

User Display
setting level

100.0%

Cooling-side proportional band

DYNn

Menu symbol:

In Heating/cooling control or Position


proportional control: 0.0 to 100.0%

STD

HYn
STD

In ON/OFF control or Two-position


two-level control: 0.0 to 100.0% of
PV input range span (EUS)

0.00

ALn

ON

Hysteresis (in ON/OFF


control, Position
proportional control, or
Two-position two-level
control)
Heating-side ON/OFF
control hysteresis (in
Heating/cooling control)

1.00

For the alarm function setting parameter, 4 alarms are displayed for the factory default.
The number of alarms can be changed by the setup parameter ALNO. (number of
alarms). To change the number of alarms, see User's Manual.

HOUR

(PID)
Name of Parameter

(HYS)

LCL

OFF

Parameter
symbol

n: group number

(TMU)

RUN

OFF: Disable
1 to 4: Perform auto-tuning. Tuning
result is stored in the specified numbered PID.
R: Tuning result is stored in the PID
for reference deviation.

AUTO-tuning switch

1 to 4

Setting Range

A4

(UPR)

Name of Parameter

Parameter
symbol

Parameter

n=1

(MODE)

n SELECT Parameter
Menu symbol:

Alarm-1 to -4 setpoint

Set a PID group number to use.


1 to 4 (Depends on the setup parameter PIDG. setting.)

Menu symbol:

Name of Parameter

A3

EASY

(PID)

PID number selection

0.0 %
of PV
input
range
span

A2

keys.

(SPT)

(SPNO.)

Set the offset from SP.


-100.0 to 100.0% of PV input range
span (EUS)

A1

n Operation Mode

(AT)

Sub-target setpoint (in


Two-position two-level
control)

n PID Setting Parameter

(ALRM)

Set a 5-digit value in the following


order.
[Alarm type: 2 digits (see below)] +
[Without (0) or With (1) Stand-by action] + [Energized (0) or De-energized
(1)] + [Latch action (0/1/2/3/4)]
For latch action, see User's Manual.

SUB

To select the parameter setting displayed as the initial value, press the Down arrow
key to move to the next parameter.
To change and set the parameter setting, press the SET/ENTER key to start the setpoint blinking. The blinking state allows you to make changes (setting mode). Use the
Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to
register the setting.
Note that there are some parameters which are not displayed depending on the model
and suffix codes, control type (CNT), etc. The parameters for professional setting mode
(LEVL: PRO) are not described in this manual. See Users Manual.

(R.L)

SPL

PIDN

Operation for Setting

(S.R)

0.0 to 100.0% of PV input range (EU)


(Setting range: SPL to SPH)

Parameter
symbol

SP

Menu Display and


Parameter Setting
Display are changed
in a circular pattern.

Move to the Setup Parameter Setting Display:


Hold down the PARAMETER key or PARA key and the Left arrow key simultaneously
for 3 sec.

Parameter
symbol

Target setpoint

User Display
setting level

For the parameter SP (target setpoint), 4 groups are displayed for the factory default.
The number of groups can be changed by the setup parameter SPGR. (number of
SP groups). For the alarm setpoint parameter, alarm-1 to -4 are displayed for the factory default. The number of alarms can be changed using the setup parameter ALNO.
(number of alarms). To change the number of SP groups or alarms, see User's Manual.
Parameter

key

The parameter groups can be switched using

Menu symbol:

Initial
value

Use the following table to record SP and alarm setpoints.

key

PARAMETER key
or PARA key

SET/ENTER key

to

Setting Range

Name of Parameter

(A1 to A4)

Hold down the PARAMETER key or PARA key for 3 seconds to move from the Operation Display to the Operation Parameter Setting Display. Press the DISPLAY key or
DISP key once to return to the Operation Display.

Menu

(PIDN)

(SP)

EASY

For the PID setting parameter, 4 groups are displayed for the factory default.
The number of groups can be changed by the setup parameter PIDG. (number of PID
groups). To change the number of PID groups, see User's Manual.
IM 05P01D31-11EN page /12

If you are using two or more groups of PID parameters, use the following table to record their setting values.
Parameter

n=2

n=3

n=4

Menu symbol:

Parameter
symbol

D
OH

to

OL
MR

(ZONE)
Name of Parameter

Reference point 1 to 3

Zone PID switching


hysteresis

Hysteresis can be set for switching at


a reference point.
0.0 to 10.0% of PV input range span
(EUS)

Reference deviation

Set a deviation from SP. The PID for


reference deviation is used if there
is a larger deviation than the preset
reference deviation.
OFF: Disable
0.0 + 1 digit to 100.0% of PV input
range span (EUS)

SU.HY
HY.UP
HY.LO

(RHY)

DR
SU.DR
Pc
Ic

(RDV)

Dc
OHc
OLc

Initial
value

Setting Range

Set reference points at which switching is carried out between groups of


100.0%
PID constants according to the given
of PV
temperature zone.
input
0.0 to 100.0% of PV input range (EU) range
(RP1 RP2 RP3)

(RP1 to RP3)

HYS

Setup Parameters

n Zone Control Parameter


User Display
level
setting

Hold down the PARAMETER key or PARA key and Left arrow key simultaneously for 3
seconds to move from the Operation Display or Operation Parameter Setting Display to
the Setup Parameter Setting Display.
Press the DISPLAY key or DISP key once to return to the Operation Display.
Hold down PARAMETER key or PARA key and
Left arrow key simultaneously for 3 sec.
Menu

STD

SET/ENTER key

DB

Parameter
symbol

(PV)
Name of Parameter

Menu

Parameter
key

Parameter
END

DISPLAY key
or DISP key
END

key

PARAMETER key
or PARA key

key

OFF

Menu

key

Parameter

For Zone control, set the setup parameter ZON (zone PID selection) to Zone PID selection.

HYSc

Menu symbol:

Operation Dsipaly

Table
below

0.5 %
of PV
input
range
span

n PV Input Setting Parameter

Parameter
key

Parameter
END

Parameter
END

Menu Display and


Parameter Setting
Display are changed
in a circular pattern.
(IN)

PV input type

Move to the Operation Parameter Setting Display:


Hold down the PARAMETER key or PARA key for 3 sec.

Use the following table to record the reference point setting value.

PO

Parameter

SU.PO

RPn

n=1

n=2

n=3

Operation for Setting

POc

n P Parameter (for Ladder Program)

n: group number

n Tuning Parameter
Menu symbol:
Parameter
symbol

(TUNE)
Name of Parameter

Super function

(SC)

(AT.TY)
(AR)
(OPR)

(MPON)

to
(MPO1 to MPO5)

Menu symbol:

Auto-tuning type

Initial
value

Setting Range
OFF: Disable
1: Overshoot suppressing function
(normal mode)
2: Hunting suppressing function
(stable mode)
Enables to answer the wider
characteristic changes compared
with response mode.
3: Hunting suppressing function
(response mode)
Enables quick follow-up and short
converging time of PV for the
changed SP.
4: Overshoot suppressing function
(strong suppressing mode)
Note: Setpoints 2 and 3 must be
used in PID control or PI control.
Disabled in the following controls:
1) ON/OFF control, 2) PD control,
3) P control, 4) Heating/cooling
control.
Do not use the function for the
control processes with response
such as flow or pressure control.

User Display
setting level

Parameter
symbol

to

(PPAR)
Name of Parameter

P01 to P10 parameter

(P01 to P10)
Parameter
Pn

n=01

n=02

n=03

Initial
value

Setting Range
-19999 to 30000 (Set a decimal point
position using LL50A Parameter Setting Software.)
n=04

n=05

n=06

n=07

n=08

User Display
level
setting
Table
below
n=09

STD

n=10

To select the parameter setting displayed as the initial value, press the Down arrow
key to move to the next parameter.
To change and set the parameter setting, press the SET/ENTER key to start the setpoint blinking. The blinking state allows you to make changes (setting mode). Use the
Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to
register the setting.
Note that there are some parameters which are not displayed depending on the Model
and Suffix codes, control type (CNT), etc. The parameters for professional setting
mode (LEVL: PRO) are not described in this manual. See Users Manual.

n Control Function Setting Parameter


Menu symbol:
Parameter
symbol

OFF

EASY
(CNT)

(SPGR.)

0: Normal
1: Stability

0
(ZON)

Anti-reset windup
(excess integration
prevention)

AUTO, 50.0 to 200.0%

Output velocity limiter

OFF: Disable
0.1 to 100.0%/s

Manual preset output


number selection

Select the output used in MAN mode


when switched from AUTO to MAN
mode.
OFF: Hold the control output in AUTO
mode (bumpless)
1: Use manual preset output 1 (output
bump)
2: Use manual preset output 2 (output
bump)
3: Use manual preset output 3 (output
bump)
4: Use manual preset output 4 (output
bump)
5: Use manual preset output 5 (output
bump)

OFF

Manual preset output 1


to 5

-5.0 to 105.0%
However, output is limited to the
output high limit and low limit.

0.0%

PV input unit

(RH)

Maximum value of PV
input range

(RL)

Minimum value of PV
input range

(CTL)
Name of Parameter

Control type

Number of SP groups

Zone PID selection

AUTO
OFF

(PIDG.)

(UNIT)

Number of PID groups

Setting Range
PID: PID control
ONOF: ON/OFF control (1 point of
hysteresis)
ONOF2: ON/OFF control (2 points of
hysteresis)
2P2L: Two-position two-level control
H/C: Heating/cooling control
Set a number of SP groups to use.
1 to 4

Initial
value
PID
or
H/C
(for
Heating/
Cooling
type)

User Display
setting
level

EASY
(SDP)

PV input scale decimal


point position

(SH)

Maximum value of PV
input scale

(SL)

Minimum value of PV
input scale

If set to SP group number selection,


allows PID constants to be selected
for each SP group.
If set to Zone PID selection,
automatically selects PID constants
according to the range set in the
Reference point.
0: SP group number selection 1
1: Zone PID selection (selection by PV)
2: Zone PID selection (selection by
target SP)
3: SP group number selection 2
4: Zone PID selection (selection by SP)

Set a number of PID groups to use.


1 to 4

STD

(BSL)

(A.BS)

(A.FL)

Setting Range

Initial
value

OFF: Disable
K1: -270.0 to 1370.0 0C / -450.0 to 2500.0 0F
K2: -270.0 to 1000.0 0C / -450.0 to 2300.0 0F
K3: -200.0 to 500.0 0C / -200.0 to 1000.0 0F
J: -200.0 to 1200.0 0C / -300.0 to 2300.0 0F
T1: -270.0 to 400.0 0C / -450.0 to 750.0 0F
T2: 0.0 to 400.0 0C / -200.0 to 750.0 0F
B: 0.0 to 1800.0 0C / 32 to 3300 0F
S: 0.0 to 1700.0 0C / 32 to 3100 0F
R: 0.0 to 1700.0 0C / 32 to 3100 0F
N: -200.0 to 1300.0 0C / -300.0 to 2400.0 0F
E: -270.0 to 1000.0 0C / -450.0 to 1800.0 0F
L: -200.0 to 900.0 0C / -300.0 to 1600.0 0F
U1: -200.0 to 400.0 0C / -300.0 to 750.0 0F
U2: 0.0 to 400.0 0C / -200.0 to 1000.0 0F
W: 0.0 to 2300.0 0C / 32 to 4200 0F
PL2: 0.0 to 1390.0 0C / 32.0 to 2500.0 0F
P2040: 0.0 to 1900.0 0C / 32 to 3400 0F
WRE: 0.0 to 2000.0 0C / 32 to 3600 0F
JPT1: -200.0 to 500.0 0C / -300.0 to 1000.0 0F
JPT2: -150.0 to 150.0 0C / -200.0 to 300.0 0F
PT1: -200.0 to 850.0 0C / -300.0 to 1560.0 0F
PT2: -200.0 to 500.0 0C / -300.0 to 1000.0 0F
PT3: -150.00 to 150.00 0C / -200.0 to 300.0 0F
0.4-2V: 0.400 to 2.000 V
1-5V: 1.000 to 5.000 V
4-20: 4.00 to 20.00 mA
0-2V: 0.000 to 2.000 V
0-10V: 0.00 to 10.00 V
0-20 : 0.00 to 20.00 mA
-1020: -10.00 to 20.00 mV
0-100: 0.0 to 100.0 mV

OFF

-: No unit, C: Degree Celsius


-: No unit, - -: No unit, - - -: No unit,
F: Degree Fahrenheit
Depends on the input type.
- For temperature input Set the temperature range that is
actually controlled. (RL<RH)
- For voltage / current input Set the range of a voltage / current
signal that is applied.
The scale across which the voltage/
current signal is actually controlled
should be set using the maximum
value of input scale (SH) and minimum value of input scale (SL).
(Input is always 0% when RL = RH.)
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places

User Display
level
setting

EASY

Depends
on the
input type

Depends
on the
input type

Depends
on the
input type

-19999 to 30000, (SL<SH),


| SH - SL | 30000

Depends
on the
input type
Depends
on the
input type

PV input burnout action

OFF: Disable
UP: Upscale
DOWN: Downscale

Depends
on the
input type

PV analog input bias

-100.0 to 100.0% of each input range


span (EUS)

0.0 % of
PV input
range
span

PV analog input filter

OFF, 1 to 120 s

STD

OFF

W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988, WRE: W97Re3-W75Re25

STD

Table
below

Use the following table to record the manual preset output setting value.
Parameter

n=1

n=2

n=3

n=4

n=5

MPOn

IM 05P01D31-11EN page 10/12

n Input Range, SP Limiter Setting Parameter


Menu symbol:
Parameter
symbol

(P.UNI)

(P.DP)

(P.RH)

(MPV)
Name of Parameter

Control PV input unit

Setting Range
-: No unit
C: Degree Celsius
-: No unit
- -: No unit
- - -: No unit
F: Degree Fahrenheit

0: No decimal place
1: One decimal place
Control PV input decimal
2: Two decimal places
point position
3: Three decimal places
4: Four decimal places

Initial
value

(SPH)

STD

Minimum value of control


PV input range

Depends
on the
input type

SP high limit

100.0 %
of PV
input
range

SP low limit

Parameter
symbol

(CT)

Name of Parameter

Upper two
digits
Lower two
digits

Control output cycle time


Heating-side control
output cycle time (in
Heating/cooling control)

Setting Range

Initial
value

(O1RH)

Maximum value of
retransmission output
scale of OUT current
output

Minimum value of
retransmission output
scale of OUT current
output

(OU.A)

OUT current output


range

(RET.A)

RET current output


range

When O1RS = PV1, SP1, TSP1, PV,


O1RL + 1 digit to 30000
-19999 to O1RH - 1 digit
Decimal point position:
When O1RS=PV1, SP1, or TSP1,
decimal point position is same as
that of PV input.
When O1RS =PV, decimal point position is same as that of PV input
scale.

100 %
of PV
input
range

Menu symbol:
Parameter
symbol

EASY

0.5 to 1000.0 s

(V.AT)
(V.RS)

Valve position setting


reset

Setting V.RS to ON resets the valve


adjustment settings and causes the
indication V.RS to blink.

Fully-closed valve position setting

Pressing the SET/ENTER key with


valve position set to the fully-closed
position by Down arrow key causes
the adjusted value to be stored. When
V.L adjustment is complete, V.L stops
blinking.

Fully-opened valve position setting

Pressing the SET/ENTER key with


valve position set to the fully-opened
position by Up arrow key causes the
adjusted value to be stored. When V.H
adjustment is complete, V.H stops
blinking

Valve traveling time

5 to 300 s

Valve adjusting mode

0: Valve position feedback type


1: Valve position feedback type
(moves to the estimating type if a
feedback input error or break occurs.)
2: Valve position estimating type

4-20: 4 to 20 mA
0-20: 0 to 20 mA
20-4: 20 to 4 mA
20-0: 20 to 0 mA

Parameter
symbol

(HB1.S)

Heater break alarm-1


function selection

(HB2.S)

Heater break alarm-2


function selection

(HB1)

Heater break alarm-1


current setpoint

(HB2)

Heater break alarm-2


current setpoint

30.0 s

OFF

(CT1.T)

CT1
coil winding number ratio

(CT2.T)

CT2
coil winding number ratio

Setting Range
0: Heater current measurement
1: Heater break alarm (Heating-side)
2: Cooling-side heater break alarm

Name of Parameter

Protocol selection

STD

(BPS)

(PRI)

4-20

(DLN)

4-20

(ADR)

19200

Parity

NONE: None
EVEN: Even
ODD: Odd

EVEN

Initial
value

User Display
level
setting

Parameter
symbol

1: 1 bit, 2: 2 bits

Data length

7: 7 bits, 8: 8 bits

Address

1 to 99

EASY
OFF

Name of Parameter

800
1 to 3300

Parameter
symbol
EASY

800

(FILE)

Initial
value

Setting Range

User Display
level
setting

9600: 9600 bps


19200: 19.2k bps
38400: 38.4k bps

Parity

NONE: None
EVEN: Even
ODD: Odd

IP address 1 to 4

0 to 255
Initial value:
(IP1).(IP2).(IP3).(IP4) =
(192).(168).(1).(1)

See left

Subnet mask 1 to 4

0 to 255
Initial value:
(SM1).(SM2).(SM3).(SM4) =
(255).(255).(255).(0)

See left

Table
below

Default gateway 1 to 4

0 to 255
Initial value:
(DG1).(DG2).(DG3).(DG4) =
(0).(0).(0).(0)

See left

Table
below

Port number

502, 1024 to 65535

502

IP access restriction

OFF: Disable, ON: Enable

OFF

Permitted IP address 1-1


to 1-4
Permitted IP address 2-1
to 2-4

0 to 255
Initial value:
(1.IP1).(1.IP2).(1.IP3).(1.IP4) =
(255).(255).(255).(255)
(2.IP1).(2.IP2).(2.IP3).(2.IP4) =
(255).(255).(255).(255)

Ethernet setting switch

Setting this parameter to ON


enables the Ethernet communication
parameter settings.
OFF, ON

(PRT)

to
,
to
(1.IP1 to 1.IP4,
2.IP1 to 2.IP4)

(ESW)

Name of Parameter

Baud rate

1
38400

Menu symbol:
Parameter
symbol

(BR)

(ADR)

EVEN
(BPS)
Table
below
(FILE)

See left

Setting Range
9.6K: 9.6k bps
19.2K: 19.2k bps
93.75K: 93.75k bps
187.5K: 187.5k bps
0.5M: 0.5M bps
1.5M: 1.5M bps
3M: 3M bps
6M: 6M bps
12M: 12M bps
AUTO
45.45K: 45.45k bps

Address

0 to 125

Baud rate

9600: 9600 bps


19200: 19.2k bps
38400: 38.4k bps

Profile number

0 to 3

Initial
value

User
setting

Display
level

AUTO

EASY
3

38400

(DNET)
Name of Parameter

Setting Range

Baud rate

125K: 125k bps


250K: 250k bps
500K: 500k bps

Address

0 to 63

Baud rate

9600: 9600 bps


19200: 19.2k bps
38400: 38.4k bps

Profile number

0 to 3

Initial
value

User Display
level
setting

125K

63
EASY
38400

n CC-Link Communication Setting Parameter (E3-terminal Area)

Baud rate

to

(BR)

(BPS)

(BPS)

(IP1 to IP4)

(ADR)

Menu symbol:

(HSR)

to

(PROF)

n DeviceNet Communication Setting Parameter (E3-terminal Area)

OFF, 1 to 8

(PRI)

(BR)

(FILE)

(ETHR)

OFF
OFF, 0.1 to 300.0 Arms

Parameter
symbol

(BPS)

High-speed response
mode

Menu symbol:

(ADR)

Stop bit

Menu symbol:

(IPAR)

PCL: PC link communication


PCLSM: PC link communication (with
checksum)
LADR: Ladder communication
CO-M: Coordinated master station
CO-S: Coordinated slave station
MBRTU
MBASC: Modbus (ASCII)
MBRTU: Modbus (RTU)
CO-S1: Coordinated slave station
(Loop-1 mode)
CO-S2: Coordinated slave station
(Loop-2 mode)
P-P: Peer-to-peer communication

Baud rate

(DG1 to DG4)

STD

User Display
level
setting

Ethernet Communication Setting Parameter (E3-terminal Area)

to

60 s

Initial
value

Setting Range

600: 600 bps


1200: 1200 bps
2400: 2400 bps
4800: 4800 bps
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps

(SM1 to SM4)

OFF

0.00

(R485)

OFF

(HBA)
Name of Parameter

STD

In cases where the current transformers manufactured by U.R.D. Co., Ltd are used, set
the following value for the coil winding number ratio.
CTL-6-S-H: 800
CTL-12L-30: 3000

Menu symbol:

0%
of PV
input
range

n PROFIBUS-DP Communication Setting Parameter (E3-terminal Area)

0.00
0.00 to 99.59 (m.s)

n RS-485 Communication Setting Parameter (UT35A: E3-terminal


Area, UT32A: E1-terminal Area)

n Heater Break Alarm Setting Parameter

30.0 s

OFF: Stop automatic adjustment


ON: Start automatic adjustment

(V.MOD)

Same as RTS

(HDN2)

Heater break alarm-2


On-delay timer

(STP)

User Display
level
setting

Control output or Heating-side control


output (Lower two digits)
00: OFF
01: OUT terminals (voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay)
Standard
06: OUT2 terminals (relay)
type:
07: RET/OUT2 terminals (voltage
00.03
pulse)

08: RET/OUT2 terminals (current)
Cooling-side control output (Upper Heating/
two digits)
cooling
type:
00: OFF
06.03
01: OUT terminals (voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay)
06: OUT2 terminals (relay)
07: RET/OUT2 terminals (voltage
pulse)
08: RET/OUT2 terminals (current)

Automatic valve position


adjustment

(TR.T)

Retransmission output
type of OUT current
output

(O1RL)

(CTc)

(V.H)

(O1RS)

0.0 %
of PV
input
range

Cooling-side control
output cycle time

(V.L)

(RTL)

Minimum value of
retransmission output
scale of RET

EASY

Heater break alarm-1


On-delay timer

(OUT)

Output type selection

(OT)

(RTH)

When RTS = PV1, SP1, TSP1, PV


RTL + 1 digit to 30000
-19999 to RTH - 1 digit
Decimal point position:
When RTS=PV1, SP1, or TSP1,
decimal point position is same as
that of PV input.
When RTS=PV, decimal point position
is same as that of PV input scale.

PV1

(HDN1)

(PSL)

n Output Setting Parameter


Menu symbol:

Retransmission output
type of RET

Maximum value of
retransmission output
scale of RET

Depends
on the
input type

Maximum value of
control PV input range

0.0 to 100.0% of PV input range (EU),


(SPL<SPH)
(SPL)

(RTS)

Same
as PV
input
unit

-19999 to 30000, (P.RL<P.RH),


| P.RH - P.RL | 30000
(P.RL)

User Display
level
setting

OFF: Disable
PV1: PV
SP1: SP
OUT1: OUT (Valve opening: 0 to 100
% in Position proportional control)
LPS: 15 V DC loop power supply
TSP1: Target SP
HOUT1: Heating-side OUT
COUT1: Cooling-side OUT
MV1: Position proportional output
(internal computed value)
PV: PV terminals analog input

Table
below

OFF

(CC-L)
Name of Parameter

Setting Range

Baud rate

156K: 156k bps


625K: 625k bps
2.5K: 2.5k bps
5M: 5M bps
10M: 10M bps

Address

1 to 64

Initial
value

User Display
level
setting

10M

1
EASY

Baud rate

Profile number

9600: 9600 bps


19200: 19.2k bps
38400: 38.4k bps

38400

0 to 3

Key Action Setting Parameter


Menu symbol:
EASY

Parameter
symbol

(KEY)
Name of Parameter

(F1)

User function key-1


action setting

(F2)

User function key-2


action setting

(Fn)

User function key-n


action setting

Setting Range
OFF: Disable
A/M: AUTO/MAN switch
R/L1: REM/LCL switch
S/R: STOP/RUN switch
AUTO: Switch to AUTO
MAN: Switch to MAN
REM1: Switch to REM
LCL1: Switch to LCL
STOP: Switch to STOP
RUN: Switch to RUN
AT: Auto-tuning
LTUP: LCD brightness UP
LTDN: LCD brightness DOWN
BRI: Adjust LCD brightness
LCD: LCD backlight ON/OFF switch
LAT: Latch release
PID: PID tuning switch

Initial
value

User
setting

Display
level

OFF

OFF

EASY

PID

Use the following table to record Ethernet communication setting value.


Parameter

n=1

n=2

n=3

n=4

IPn
SMn
DGn
1.IPn
2.IPn

IM 05P01D31-11EN page 11/12

Display Function Setting Parameter

DI Function Registration Parameter

DO Setting Parameter (E1/E4-terminal Area)

Menu symbol:

Menu symbol:

Menu symbol:

Parameter
symbol

(PCMD)

(PCH)
(PCL)

(DISP)
Name of Parameter

Active color PV display


switch

Initial
value

Setting Range
0: Fixed in white
1: Fixed in red
2: Link to alarm 1 (Alarm OFF: white,
Alarm ON: red)
3: Link to alarm 1 (Alarm OFF: red,
Alarm ON: white)
4: Link to alarm 1 or 2 (Alarm OFF:
white, Alarm ON: red)
5: Link to alarm 1 or 2 (Alarm OFF:
red, Alarm ON: white)
6: PV limit (Within range: white, Out
of range: red)
7: PV limit (Within range: red, Out of
range: white)
8: SP deviation (Within deviation:
white, Out of deviation: red)
9: SP deviation (Within deviation: red,
Out of deviation: white)
10: Link to DI (ON: red, OFF: white)

User Display
level
setting

Parameter
symbol
(A/M)
(R/L)

(BAR1)

EASY

(AUTO)
(MAN)
(REM)

(LCL)

(AT)

(LCD)
5
(Heating
/cooling
type: 1)

(PVRW)

(BDV)

(GUID)

(ECO)

(BRI)
(MLSD)

Guide display ON/OFF

Economy mode

Brightness
Least significant digital
mask of PV display

Menu symbol:

0.0 to 100.0% of PV input range span


(EUS)

10.0 %
of PV
input
range
span

OFF: Nondisplay, ON: Display

Parameter
symbol

to
(CS1 to CS5)

(SP.B1)

ON

(SP.B2)

OFF: Disable
1: Economy mode ON (All indications
except PV display OFF)
2: Economy mode ON (All indications
OFF)
3: Brightness 10 % (whole indication)

OFF

(PN.B0)
(PN.B1)

(Dark) 1 to 5 (Bright)

EASY
(PN.B2)

OFF: With least significant digit


ON: Without least significant digit

OFF

STD
(MP.B0)

Name of Parameter

Setting Range

SELECT Display-1 to -5
registration

Register the operation parameter


(except the Operation Mode) that is
frequently modified to display it in the
Operation Display.
OFF, 2301 to 5000
For the setting range, see User's
Manual.

n=1

n=2

n=3

AUTO/MAN switch

5025

REMOTE/LOCAL switch

OFF

Switch to AUTO
Switch to MAN
Switch to REMOTE
Switch to LOCAL
Auto-tuning START/STOP
switch

Initial
value

User Display
level
setting

OFF

STD

OFF

LCD backlight ON/OFF


switch

OFF

PV red/white switch

OFF

(COM.W)
(DATA)

Front panel parameter


data (,) key lock

(A/M)

Front panel A/M key lock

OFF: Enable, ON: Disable

(DO2.S)

DO12/DO42 function
selection

OFF

n=4

OFF

Bit-1 of SP number

OFF

Bit-2 of SP number

OFF

Parameter

Initial
value

Parameter
symbol

OFF
OFF: Unlock, ON: Lock

DO45 function selection

OFF

E1-terminal Area

(R.TM)

(EPO)

(FREQ)

OFF

(QSM)

(LANG)

(PASS)
0

(PV1.E)
(LA.ER)

E4-terminal Area

(ECU1)
(ECU3)
Setting Range

Initial
value

Set how the controller should recover


from a power failure of 5 seconds or
more.
CONT: Continue action set before
power failure.
MAN: Start from MAN.
AUTO: Start from AUTO.

CONT

Restart timer

Set time between power on and the


instant where controller starts computation.
0 to 10 s

Input error preset output

Set preset output value when the


input burnout or ADC error occurs.
Manual output is prioritized when the
input burnout occurs in MAN.
0: Preset output
1: 0% output
2: 100% output

Restart mode

Power frequency

AUTO, 60: 60 Hz, 50: 50 Hz

Quick setting mode

OFF: Disable
ON: Enable

Guide display language

ENG: English
FRA: French
GER: German
SPA: Spanish

STD

0: Status switch 1
1: Status switch 2

(AD2.E)

(SYS)
Name of Parameter

OFF

Bit changing method of SP


number

(AD1.E)

(DCU)

EASY

OFF

(SP.BC)

STD

(MCU)

User Display
level
setting

Standard terminals
DI1: 5025, DI2: 5026

Password setting

0 (No password) to 65535

User Display
setting
level

(ECU4)
(PARA)
(H.VER)
(SER1)

STD
(SER2)
(MAC1)

0
(MAC2)
(MAC3)

AUTO

Name of Parameter

Display
level

Status record

Parameter error status


Option error status
A/D converter error status 1
A/D converter error status 2
PV input error status
Ladder error status
MCU version
DCU version
ECU-1 version (E1-terminal area)
EASY
ECU-3 version (E3-terminal area)
ECU-4 version (E4-terminal area)
Parameter version
Product version
Serial number 1
Serial number 2
MAC address 1 (E3-terminal area)
MAC address 2 (E3-terminal area)
MAC address 3 (E3-terminal area)

Parameter Display Level Parameter

ON
Depends
on the
model
and
suffix
codes

(VER)

Menu symbol:
EASY

Parameter
symbol
(LEVL)

(LVL)
Name of Parameter
Parameter display level

Setting Range
EASY: Easy setting mode
STD: Standard setting mode
PRO: Professional setting mode

Initial
value
STD

User
setting

Display
level
EASY

* For Professional setting mode, see Users Manual.

STD

AL1-AL3 Function Registration Parameter


(ALM)
Name of Parameter

AL1 function selection

AL2 function selection

Setting Range
Set an I relay number. For the items
other than below, see User's Manual.
Ex.) Set the number 4353 for AL1.S
to use the alarm 1.
Set OFF to disable the function.

AL3 function selection

No function: OFF
Alarm 1: 4353
Alarm 2: 4354
Alarm 3: 4355
Alarm 4: 4357

(OR.S)

OUT relay function


selection

AUTO (ON ) / MAN (OFF) status: 4193


REM (ON) / LCL (OFF) status: 4194
STOP (ON) / RUN (OFF) status: 4195
FAIL (Normally ON) output: 4256

(OR2.S)

OUT2 relay function


selection

User Display
level
setting
(AL3.S)

OFF

OFF

Table
below

System Setting Parameter

Bit-1 of PID number

Bit-0 of manual preset


output number

DO44 function selection

(OP.ER)

DO5.S

OFF

Bit-2 of PID number

OFF

(PA.ER)

DO4.S

Bit-0 of PID number

E1-terminal area
DI11: 5041, DI12: 5042, DI13: 5043,
DI14: 5044, DI15: 5045

Same as AL1.S
Set OFF to disable the function

Parameter
symbol

DO3.S

Set an I relay number of contact input.


Set OFF to disable the function.

OFF

Parameter
symbol

n=5

Bit-0 of SP number

DO43 function selection

User Display
setting
level

Use the following table to record DO setting value.

(R.MD)
Initial
value

Bit-2 of manual preset


output number

(AL2.S)
Setting Range

OFF

Menu symbol:

Setting Range

Initial
value

DO2.S

(DI.NU)
Name of Parameter

Setting Range

DO1.S

OFF

(MP.B2)

Menu symbol:

(KLOC)
Name of Parameter

STD

OFF

Latch release

Key Lock Setting Parameter

Communication write
enable/disable

E1-terminal area
DI11: 5041, DI12: 5042, DI13: 5043,
DI14: 5044, DI15: 5045

OFF

Menu symbol:

Name of Parameter
DO11/DO41 function
selection

(DO5.S)

Error and Version Confirmation Parameter (for display only)

(DO)

(DO1.S)

(DO4.S)

OFF

OFF

(AL1.S)

Parameter
symbol

Standard terminals
DI1: 5025, DI2: 5026

Parameter
symbol

(DO3.S)

OFF
Set an I relay number of contact
input.
Set OFF to disable the function.

Bit-1 of manual preset


output number

CSn

Menu symbol:

User Display
level
setting

5026

(MP.B1)

(CSEL)

Use the following table to record SELECT Display setting value.


Parameter

Parameter
symbol
(SP.B0)

SELECT Display Setting Parameter


Menu symbol:

Initial
value

DI Function Numbering Parameter


STD

Bar-graph deviation
display band

Setting Range

STOP/RUN switch

(LAT)

Bar-graph display registration

Name of Parameter

(S/R)

Set a display value when in PV limit


PV color change high
or SP deviation.
limit
-19999 to 30000 (Set a value within
the input range.)
PV color change low limit Decimal point position depends on
the input type.

0: Disable
1: OUT, Heating-side OUT, Internal value
in Position proportional control
2: Cooling-side OUT
3: PV
4: SP
5: Deviation
6 to 16: Disable
17: Feedback input (valve opening)
18: PV terminals analog input

(DI.SL)

STD

Initial
value

User Display
setting
level

4353

4354

4355

STD

OFF

OFF
OFF

Trademarks
Our product names or brand names mentioned in this manual are
the trademarks or registered trademarks of Yokogawa Electric Corporation.
Adobe, Acrobat, and Postscript are either registered trademarks or trademarks
of Adobe Systems Incorporated.
Ethernet is a registered trademark of XEROX Corporation in the United States.
Modbus is a registered trademark of Schneider Electric.
PROFIBUS-DP is a registered trademark of PROFIBUS User Organization.
DeviceNet is a registered trademark of Open DeviceNet Vendor Association.
CC-Link is a registered trademark of CC-Link Partner Association.
We do not use the TM or mark to indicate these trademarks or
registered trademarks in this manual.
All other product names mentioned in this manual are trademarks
or registered trademarks of their respective companies.
IM 05P01D31-11EN page 12/12

You might also like