Experiment 2 Level Control System: 1.0 Objective
Experiment 2 Level Control System: 1.0 Objective
Laboratory Module
EXPERIMENT 2
LEVEL CONTROL SYSTEM
1.0 OBJECTIVE
To study the response of level control process in open tank using the PID controller.
2.0 INTRODUCTION TO THE APPARATUS (MODEL WLF922).
a) The process consists of a level tank T31 and a collection tank T32 connected with the appropriate
pumps and piping system.
b) T31 as an Open or Closed Tank
To operate T31 as an Open tank, the top vent (V) and overflow drain (D) manual valves are opened, so
that the top space of T31 is at atmospheric pressure.
CONTROL SYSTEM AND INSTRUMENTATION
Field-Mount Instruments: Transmitters, Control Valve, Gauges, etc
LT31
FE31
FT31
LCV31
PP
LCY31
: Current-to-Air Converter
Converts 4-20 mA to 3-15 psig proportionally for PP/LCV31
LS32
Laboratory Module
PG31, PG32
: Pressure Gauges
SV31
: One unit panel Controller configured for: LIC31-Loop 1, PID1, Level PID Controller
FIC31-Loop 2, PID2, Flow PID Controller
In Cascade mode, LIC31 is the primary, FIC31 is the
secondary.
Three control strategies can be operated as described earlier
LIC31, Level Single Loop, PID1, Loop 1 :
LT31-LIC31-LCY31/PP/LCV31
Selector switch in Position 1: LIC31.
LIC31 in Auto (A) or Manual (M) mode.
FIC31, Flow Single Loop, PID2, Loop 2 :
FE31/FT31-FIC31-LCY31/PP/LCV31
Selector switch in Position 2: CASCADE LIC31-FIC31.
FIC31 in Auto (A) or Manual (M) mode.
LFR31
: Tank level at T31 measured by LT31 exceeds the preset High level
alarm limit. The High alarm limit is set at PH1 at the PID1 page
FAL31
LAH32
: Tank level at T32 exceeds the High level limit (shortest probe) of
the Level Switch LS32.
Laboratory Module
All pumps (P31, P32, P33) suction, discharge and by-pass valves are fully opened.
Operate T31 as an Open tank with the top vent (V) and overflow drain valves fully opened. The
pressurizing air inlet to T31 is isolated at its inlet manual valve (with the valve handle at 90 to
the air supply inlet tubing), located next to the preset Air Regulator AR31 near the top of tank
T31.
Operate T31 as a Self Regulating process. Open only the manual GATE valve at the gravity
discharge pipe at the tank bottom. The second manual globe valve at the second gravity
discharge pipe must remain shut, thus operating only one gravity discharge pipeline at the
bottom of tank T31.
Shut the two manual discharge valves of pump P31, one of which is at the strainer inlet.
For a Self Regulating process, pump P31 must be OFF.
The manual by-pass valve around the control valve LCV31 should be always shut but its two
adjacent manual valves should be always opened.
4. Compressed air is required to operate the control valve system LCY31/PP/LCV31 and to pressurize
tank T31. Check that the pressure is in accordance to the pressure indicated at the air pressure
regulator (IAS. Do not pressurize T31 yet. Shut the pressurizing air inlet manual isolation valve.
5. Note the following switches and pushbuttons but do not switch ON any pump yet.
Laboratory Module
Pump P32
Pump P31
Pump P33
6. Check the Positioner (PP) manual By-pass switch at LCV31/PP. Make sure the Positioner (PP) is
connected to LCV31 i.e. do not by-pass it, but use the Positioner (PP).
Set the 1-2 Selector switch to Position 1 to operate LIC31 and display LIC31, Loop 1
accordingly.
With LIC31 in Manual (M) mode, adjust MV = 25%. Check that LCV31 is about 25%
OPENED (see the indicator scale at the valve stem). Also note that the control valve LCV31 is
Air-to-Open (ATO).
7. Start the recorder, LFR31 by pressing the RCD button ON, with the front swing cover opened.
Check the recorder chart speed (500mm/Hr) which is regularly printed out on the chart. The recorder
chart drive should be stopped (press RCD) when its chart recording is not required.
8. With the controller Selector switch in Position 1, display LIC31 faceplate at the controller. Note that
Position 1, PV1, SV1 and MV1 are displayed as PV, SV and MV in the main display page
(faceplate).
Set the setpoint (SV1) of LIC31 to 400 mm. Note that SV1 should be operated from 200 (25%)
to 640mm (80%) only.
Set the first (I) trial PID values at the PID1 page or panel as follows:LIC31 (PID1, Loop1): PB1 = 30%, TI1 = 25secs, TD1 = 0
9. When the level is near to the setpoint SV1, switch LIC31 to Auto (A) mode .Quickly change to the
FIC31(PID2) page and make sure the Cascade(C) mode indicator for FIC31 is lit up. Else press
C once. Switch back to LIC31(PID1) page.
Throughout the following test and observation, LIC31 is to remain in Auto (A) mode and the control
valve Positioner (PP) must be used and connected unless instructed otherwise.
10. The recorder LFR31 chart drive should be at fast speed (500 mm/Hr) with RCD ON. Check the
chart speed which is regularly printed out on the chart. Observe the level response at the red pen
until the response is almost steady to with 1.0 mm or it displays oscillatory response even after 3
cycles. Write down the setpoint (SV2) and PID values on the recorder chart paper beside its
response. These chart recordings constitute the results of your experiment and should be kept for
your reports.
Updated for Academic Session 2012/2013
4
Laboratory Module
11. Repeat the flow (green pen) observation by using the following TEST DISTURBANCE, one test at
a time. Start and end each test when the flow response is reasonably steady or remains oscillating
even after 3 cycles.
(i) Switch LIC31 to Manual (M) mode and quickly step change MV (inflow) by about 10%
to 20% . Then quickly switch LIC31 back to Auto (A) mode. This simulates a load step
test at the inflow. Observe the level (red pen) response similarly.
(ii) Open 1-turn, hold for 15 seconds and shut fully the pump by-pass manual valve B32.
This simulates a load pulse disturbance test at the inflow. Observe similarly.
Repeat the test with any of the above disturbances such as above, using the second (II) trial
PID values as follows:-
Double the PB1 to say 20% and observe the damping at both the inflow (Green
pen) and level (Red pen) response and at the control valve LCV31. When the
level is almost steady at its setpoint again, apply test disturbance.
STOP ALL THE PUMPS. MAKE SURE BOTH THE MANUAL DISCHARGE
VALVES OF PUMP P31 ARE FULLY SHUT.
4.0 RESULTS/DISCUSSION
The recorder LFR31 records the results of the experiments. Relevant portions of the recorder chart
responses should be submitted as results of the experiment, with the following pertinent data marked on
the corresponding chart recording:-
Laboratory Module
The Recorder chart speed is occasionally printed on the chart, for example at
500 mm or 0.139 mm or 7.2 secs
Hr
sec
mm
a) Study and compare the level responses at different PID. Use the following terms to explain
the dynamics of process i.e. Rise time, Settling time, Overshoot and Period of oscillation.
b) Note that from the recorder chart response that even though the inflow (green pen) is
fluctuating, the level is held almost steady. Explain why.
c) Discuss the response of P-control only.
d) Discuss the response when adding derivative (D) control mode.Observe the fluctuation of the
flow(green pen) and level(red pen). Is derivative control suitable?Eplain why.