Metric Performance Data
FlowBar High Throw
7/21/98
Flowbar with Continuous Slot Plenum & HighThrow Pattern Controller
FL-10
Air Flow, l/s-m
25.4 mm
36
58
79
101
122
144
165
Static Pressure, Pa
18
34
55
81
112
148
Slot
NC (Noise Criteria)
<10
16
26
33
39
44
49
1.5 - 2.5 - 4.3
2.8 - 4 - 5.5
3.8 - 4.5 - 6.5
4.3 - 5.3 - 7.3
4.5 - 5.8 - 8.3
5.3 - 6 - 8.8
5.5 - 6.8 - 9.5
Slot
Throw, m
Width
Air Flow, l/s-m
2
Static Pressure, Pa
Slots
NC (Noise Criteria)
Throw, m
24
35
47
59
71
83
94
16
28
44
63
86
112
<10
17
26
33
39
44
48
2.3 - 3.3 - 6
3.3 - 5.3 - 7.5
4.5 - 6 - 8.8
5.8 - 7 - 9.8
6 - 7.5 - 10.8
6.8 - 8.3 - 11.5
7 - 8.8 - 12.5
FL-15
Air Flow, l/s-m
1
38.1 mm
Slot
Slot
Static Pressure, Pa
NC (Noise Criteria)
Throw, m
Width
Air Flow, l/s-m
43
65
86
108
129
151
173
18
32
51
73
99
129
<10
14
24
31
37
42
48
1.8 - 3 - 5
3 - 4.3 - 5.8
4 - 5 - 6.8
4.3 - 5.5 - 7.5
5 - 5.8 - 8.3
5.3 - 6.5 - 8.8
5.5 - 6.8 - 9.8
302
86
122
158
194
230
266
Static Pressure, Pa
16
27
41
57
77
99
Slots
NC (Noise Criteria)
<10
16
24
31
36
41
45
2.8 - 4.3 - 6.8
4 - 5.8 - 8.3
5.3 - 6.5 - 9.3
5.8 - 7.3 - 10
6.5 - 8 - 11
7 - 8.5 - 12
7.3 - 8.8 - 12.8
43
72
101
129
158
187
216
14
28
46
68
95
127
Throw, m
FL-20
Air Flow, l/s-m
1
50.8 mm
Slot
Slot
Static Pressure, Pa
NC (Noise Criteria)
Throw, m
Width
Air Flow, l/s-m
2
Slots
Static Pressure, Pa
NC (Noise Criteria)
Throw, m
<10
11
22
30
36
41
46
1.5 - 2.8 - 5
2.8 - 4.3 - 6
4 - 5.3 - 7.3
5 - 5.8 - 8.3
5.3 - 6.5 - 9.3
5.8 - 7 - 10
6 - 7.5 - 10.8
86
137
187
237
288
338
388
13
24
38
56
78
103
<10
12
22
30
36
41
46
2.3 - 3.8 - 6.8
4 - 5.8 - 8.5
5.3 - 7 - 10
6.5 - 8 - 11.3
7 - 8.8 - 12.5
7.5 - 9.5 - 13.5
8.3 - 10 - 14.3
FL-25
Air Flow, l/s-m
63.5 mm
43
79
115
151
187
223
259
Static Pressure, Pa
10
22
38
58
82
110
Slot
NC (Noise Criteria)
<10
11
23
31
38
43
48
1.3 - 2.5 - 5
3 - 4.5 - 6.5
4.3 - 5.5 - 8
5.3 - 6.5 - 8.8
5.8 - 7 - 10
6.5 - 7.5 - 11
6.8 - 8.3 - 12
475
Slot
Throw, m
86
151
216
281
345
410
Static Pressure, Pa
19
32
49
69
93
Slots
NC (Noise Criteria)
<10
13
24
32
38
44
48
1.8 - 3.3 - 6.8
4 - 6 - 8.8
5.8 - 7.5 - 10.8
7 - 8.5 - 12.3
8 - 9.8 - 13.8
8.5 - 10.3 - 15
9.3 - 11.3 - 15.8
Width
Air Flow, l/s-m
Throw, m
FL-30
Air Flow, l/s-m
76.2 mm
43
86
129
173
216
259
302
Static Pressure, Pa
11
25
44
69
99
135
Slot
NC (Noise Criteria)
<10
<10
18
27
34
40
45
1 - 2.3 - 4.5
3 - 4.5 - 6.8
4.5 - 5.8 - 8.3
5.5 - 6.8 - 9.8
6 - 7.5 - 10.8
6.8 - 8.3 - 12
7.3 - 8.8 - 12.8
Slot
Throw, m
Width
86
173
259
345
432
518
604
Static Pressure, Pa
Air Flow, l/s-m
11
25
44
69
99
135
Slots
NC (Noise Criteria)
<10
<10
21
30
37
43
48
1.5 - 3 - 6.5
4.3 - 6.5 - 9.8
6.5 - 8.3 - 12
8 - 9.8 - 13.8
8.8 - 10.8 - 15.3
9.8 - 12 - 16.8
10.3 - 12.8 - 18
Throw, m
Table A, NC Correction for length
Length, mm
600
12 2 5
18 2 5
24 5 0
30 5 0
Supply
-3
+2
+3
+5
Return
+3
+5
+6
+8
Table B, Throw Correction Multiplier for length
Length, mm
600
12 2 5
24 5 0
30 5 0
36 5 0
Throw Correction
0.72
1.5
1.7
1.8
All pressures are given in Pascal
Pressure loss data assumes a duct velocity less than 4 mps in the inlet duct
Isothermal throw values are given for terminal velocities of .8, .5, and .3 mps.
Throw data are based on active sections 1225mm active section. For a 600 mm section, the throw
values are 0.72 times those shown. For a 3050 mm continuous length, the hrow values are 1.7 times those shown, 1.8 for 3650 mm units.
Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th,
with a room absorption of 10dB, re 10 - 1 2 W atts, for a 1225 mm section. (See Table A for other lengths.) For supply units used as a return, add 3 NC.
Data was obtained from test conducted in accordance with ANSI / ASHRAE Standard 70-1991, " Method of Testing for Rating the Performance of Air Outlets and Inlets."
The tests were conducted with no Plenum effect for pressure or sound.
Throw values for HighThrow units are based on a 1-way discharge from the slot.
Throws listed are for the 1-way air pattern. For divide airflow, select the airflow in each direction
according to the number of slots aimed in that direction, with the total airflow apportioned between slots.
Note: All dimensions are nominal product will be built to the closest inch equivalent dimension unless specially ordered to true metric
contact factory for availability of sizes
605 Shiloh Road Plano, Texas 75074 972-212-4800
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means,
electronic or mechanical, including photocopying, or by an information storage system, without permission
in writing from Air Distribution Technologies.
D32M-S
Page 1 of 9
Metric Performance Data
1 - Sl ot ,
FlowBar High Throw
7/21/98
Hi ghThr ow wi t h TI TUS Pl e n u m
FL-10 with 150 mm inlet
Air Flow, l/s
Length
Total Pressure, Pa
600 mm
12
24
35
47
59
71
83
18
32
50
72
98
Static Pressure, Pa
16
28
44
63
86
NC (Noise Criteria)
< 10
< 10
< 10
20
28
35
40
0.3 - 0.5 - 1.8
1 - 1.8 - 3
1.8 - 2.8 - 3.8
2.5 - 3 - 4.3
2.8 - 3.3 - 5
3 - 3.8 - 5.5
3.3 - 4 - 5.8
19
38
57
76
94
113
132
Throw, m
Air Flow, l/s
25.4 mm
Length
Total Pressure, Pa
16
28
44
64
87
Slot
1225 mm
Static Pressure, Pa
10
18
28
40
55
NC (Noise Criteria)
W idth
Throw, m
Air Flow, l/s
Length
Total Pressure, Pa
1525 mm
< 10
< 10
< 10
16
24
31
37
0.3 - 0.5 - 1.8
1 - 1.8 - 4
1.8 - 3 - 5
2.8 - 4 - 5.5
3.3 - 4.3 - 6
4 - 5 - 6.8
4.3 - 5.3 - 7.3
24
47
71
94
118
142
165
19
34
53
77
104
Static Pressure, Pa
10
18
28
40
55
NC (Noise Criteria)
< 10
< 10
< 10
18
26
33
38
0.3 - 0.5 - 2.3
1 - 2.3 - 4.3
2.3 - 3.3 - 5.5
3 - 4.3 - 6
3.8 - 5 - 7
4.3 - 5.5 - 7.5
5 - 5.8 - 8.3
Throw, m
FL-15 with 150 mm inlet
Air Flow, l/s
19
33
47
61
76
90
104
13
26
45
68
96
128
57
81
109
33
40
46
3.3 - 4 - 5.5
3.3 - 4.3 - 6
3.8 - 4.5 - 6.5
151
Length
Total Pressure, Pa
600 mm
Static Pressure, Pa
11
22
38
NC (Noise Criteria)
< 10
< 10
16
25
0.5 - 1.5 - 2.8
1.5 - 2.5 - 3.8
2.5 - 3 - 4.3
2.8 - 3.8 - 5
Throw, m
38
57
76
94
113
132
38.1 mm
Length
Total Pressure, Pa
Air Flow, l/s
14
25
39
56
76
99
Slot
1225 mm
Static Pressure, Pa
14
22
32
44
57
NC (Noise Criteria)
W idth
Throw, m
Air Flow, l/s
< 10
< 10
12
20
27
33
38
1 - 1.8 - 4
1.8 - 3 - 5
2.8 - 4 - 5.5
3.3 - 4.3 - 6
4 - 5 - 6.8
4.3 - 5.3 - 7.3
4.5 - 5.5 - 8
42
66
90
113
137
160
184
15
28
44
64
88
116
Length
Total Pressure, Pa
1525 mm
Static Pressure, Pa
13
21
30
42
55
NC (Noise Criteria)
< 10
< 10
12
20
27
33
39
1 - 1.8 - 4
1.8 - 3 - 5.3
2.8 - 4.3 - 6
3.3 - 5 - 6.8
4.3 - 5.3 - 7.3
4.5 - 5.8 - 8.3
5 - 6 - 8.5
Throw, m
FL-20 with 200 mm inlet
Air Flow, l/s
24
40
57
73
90
106
123
11
22
37
56
78
104
Length
Total Pressure, Pa
600 mm
Static Pressure, Pa
10
20
34
51
71
95
NC (Noise Criteria)
< 10
< 10
12
21
28
35
40
0.5 - 1.5 - 3
1.8 - 2.8 - 4
2.5 - 3.3 - 5
3 - 4 - 5.5
3.3 - 4.3 - 6
3.8 - 4.5 - 6.8
4-5-7
42
71
99
127
156
184
212
Throw, m
Air Flow, l/s
50.8 mm
Length
Total Pressure, Pa
11
21
35
52
73
97
Slot
1225 mm
Static Pressure, Pa
16
26
38
54
71
NC (Noise Criteria)
W idth
Throw, m
Air Flow, l/s
< 10
< 10
20
29
36
42
48
1 - 1.8 - 4
2.3 - 3.3 - 5.5
3 - 4.5 - 6.5
4 - 5.3 - 7.3
4.5 - 5.5 - 8
5 - 6 - 8.5
5.5 - 6.8 - 9.5
231
47
78
109
139
170
201
Length
Total Pressure, Pa
10
19
31
46
64
85
1525 mm
Static Pressure, Pa
12
20
29
41
54
NC (Noise Criteria)
Throw, m
< 10
< 10
19
28
36
42
47
0.5 - 1.5 - 4
1.8 - 3 - 5.5
3 - 4.5 - 6.8
4 - 5.3 - 7.5
4.5 - 5.8 - 8.3
5.3 - 6.5 - 9.3
5.5 - 7 - 9.8
Note: All dimensions are nominal product will be built to the closest inch equivalent dimension unless specially ordered to true metric
contact factory for availability of sizes
605 Shiloh Road Plano, Texas 75074 972-212-4800
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means,
electronic or mechanical, including photocopying, or by an information storage system, without permission
in writing from Air Distribution Technologies.
D32M-S
Page 2 of 9
Metric Performance Data
FlowBar High Throw
7/21/98
1-Slot, HighThrow with TITUS Plenum
FL-10 with 200 mm inlet
Length
600 mm
Air Flow, l/s
24
35
47
59
71
83
94
Total Pressure, Pa
16
29
46
66
90
117
112
Static Pressure, Pa
16
28
44
63
86
NC (Noise Criteria)
< 10
< 10
19
27
34
40
44
1 - 1.8 - 3
1.8 - 2.8 - 3.8
2.5 - 3 - 4.3
2.8 - 3.3 - 5
3 - 3.8 - 5.5
3.3 - 4 - 5.8
3.8 - 4.3 - 6
Throw, m
Air Flow, l/s
33
52
71
90
109
127
146
25.4 mm
Length
Total Pressure, Pa
10
19
30
44
60
80
Slot
1225 mm
Static Pressure, Pa
16
25
37
51
67
NC (Noise Criteria)
< 10
< 10
13
22
29
35
40
Width
Throw, m
0.5 - 1.5 - 3.3
1.8 - 2.8 - 4.5
2.5 - 3.8 - 5.5
3 - 4.3 - 6
3.8 - 4.5 - 6.8
4.3 - 5.3 - 7.3
4.5 - 5.5 - 7.5
Air Flow, l/s
38
61
85
109
132
156
179
Length
Total Pressure, Pa
10
19
30
45
63
83
1525 mm
Static Pressure, Pa
15
24
35
49
65
NC (Noise Criteria)
Throw, m
< 10
< 10
13
22
29
35
40
0.5 - 1.5 - 3.8
1.8 - 2.8 - 5
2.8 - 4 - 5.8
3.3 - 4.5 - 6.8
4.3 - 5.3 - 7.3
4.5 - 5.5 - 8
5 - 6 - 8.5
FL-15 with 200 mm inlet
Length
600 mm
Air Flow, l/s
19
33
47
61
76
90
104
Total Pressure, Pa
12
24
40
61
86
115
109
Static Pressure, Pa
11
22
38
57
81
NC (Noise Criteria)
< 10
< 10
14
24
32
38
45
0.5 - 1.5 - 2.8
1.5 - 2.5 - 3.8
2.5 - 3 - 4.3
2.8 - 3.8 - 5
3.3 - 4 - 5.5
3.3 - 4.3 - 6
3.8 - 4.5 - 6.5
Throw, m
Air Flow, l/s
38
61
85
109
132
156
179
38.1 mm
Length
Total Pressure, Pa
12
22
36
54
75
99
Slot
1225 mm
Static Pressure, Pa
18
30
44
61
81
NC (Noise Criteria)
< 10
< 10
15
24
32
38
43
Width
Throw, m
1 - 1.8 - 4
2.3 - 3 - 5
3 - 4.3 - 5.8
3.8 - 4.5 - 6.8
4.3 - 5.3 - 7.3
4.5 - 5.5 - 8
5 - 6 - 8.5
Air Flow, l/s
42
71
99
127
156
184
212
Length
Total Pressure, Pa
11
21
35
53
74
99
1525 mm
Static Pressure, Pa
16
26
39
55
73
NC (Noise Criteria)
Throw, m
< 10
< 10
14
24
31
37
43
1 - 1.8 - 4
2.3 - 3.3 - 5.5
3 - 4.5 - 6.5
4 - 5.3 - 7.3
4.5 - 5.5 - 8
5 - 6 - 8.5
5.5 - 6.8 - 9.5
FL-20 with 300 mm inlet
Length
600 mm
Air Flow, l/s
24
42
61
80
99
118
137
Total Pressure, Pa
12
24
41
63
90
121
119
Static Pressure, Pa
11
24
41
62
88
NC (Noise Criteria)
< 10
< 10
< 10
13
20
27
32
0.5 - 1.5 - 3
1.8 - 2.8 - 4.3
2.8 - 3.8 - 5
3.3 - 4 - 5.8
3.8 - 4.5 - 6.5
4-5-7
4.3 - 5.3 - 7.3
Throw, m
Air Flow, l/s
42
78
113
149
184
219
255
50.8 mm
Length
Total Pressure, Pa
10
22
37
57
82
110
Slot
1225 mm
Static Pressure, Pa
10
20
35
54
76
103
NC (Noise Criteria)
< 10
< 10
13
23
31
37
43
1 - 1.8 - 4
2.5 - 3.8 - 5.5
3.3 - 5 - 6.8
4.5 - 5.5 - 8
5 - 6 - 8.5
5.5 - 6.8 - 9.5
5.8 - 7.3 - 10
Width
Throw, m
Air Flow, l/s
47
90
132
175
217
260
302
Length
Total Pressure, Pa
20
34
53
76
103
1525 mm
Static Pressure, Pa
18
31
48
68
92
NC (Noise Criteria)
< 10
< 10
15
25
33
39
45
0.5 - 1.5 - 4
2.5 - 3.8 - 6
3.8 - 5.3 - 7.3
5 - 6 - 8.5
5.5 - 6.8 - 9.5
5.8 - 7.3 - 10.3
6.5 - 8 - 11
Throw, m
Note: All dimensions are nominal product will be built to the closest inch equivalent dimension unless specially ordered to true metric
contact factory for availability of sizes
605 Shiloh Road Plano, Texas 75074 972-212-4800
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means,
electronic or mechanical, including photocopying, or by an information storage system, without permission
in writing from Air Distribution Technologies.
D32M-S
Page 3 of 9
Metric Performance Data
FlowBar High Throw
7/21/98
1- Sl ot , Hi ghThr ow wi t h TI TUS Pl enum
FL-25 with 250 mm inlet
Air Flow, l/s
47
68
90
111
132
153
175
Length
Total Pressure, Pa
19
33
50
71
96
124
600 mm
Static Pressure, Pa
18
31
47
67
90
117
NC (Noise Criteria)
< 10
< 10
17
26
33
39
44
1.8 - 3 - 4.3
2.8 - 3.8 - 5.3
3.3 - 4.3 - 6
4 - 5 - 6.8
4.3 - 5.3 - 7.3
4.5 - 5.5 - 8
5 - 6 - 8.5
Throw, m
Air Flow, l/s
66
104
142
179
217
255
293
63.5 mm
Length
Total Pressure, Pa
13
24
38
56
77
102
Slot
1225 mm
Static Pressure, Pa
10
19
31
45
62
82
NC (Noise Criteria)
< 10
< 10
20
29
37
44
49
1.5 - 2.8 - 5.3
3 - 4.5 - 6.5
4.3 - 5.5 - 7.5
5 - 6 - 8.5
5.5 - 6.8 - 9.5
5.8 - 7.3 - 10
6.5 - 7.5 - 11
Width
Throw, m
Air Flow, l/s
71
113
156
198
241
283
326
Length
Total Pressure, Pa
11
21
33
49
68
90
1525 mm
Static Pressure, Pa
15
24
35
49
65
NC (Noise Criteria)
< 10
< 10
18
28
36
43
49
1.3 - 2.8 - 5.5
3 - 4.5 - 6.8
4 - 5.5 - 8
5.3 - 6.5 - 8.8
5.8 - 7 - 9.8
6 - 7.5 - 10.8
6.8 - 8.3 - 11.5
Throw, m
FL-30 with 250 mm inlet
Air Flow, l/s
59
80
101
123
144
165
186
Length
Total Pressure, Pa
13
24
38
55
76
100
128
600 mm
Static Pressure, Pa
12
22
35
52
71
94
119
NC (Noise Criteria)
< 10
< 10
15
23
30
36
41
2.3 - 3.3 - 5
3 - 4 - 5.8
3.8 - 4.5 - 6.5
4-5-7
4.5 - 5.5 - 7.5
5 - 5.8 - 8.3
5.3 - 6 - 8.8
Throw, m
Air Flow, l/s
94
130
165
201
236
271
307
76.2 mm
Length
Total Pressure, Pa
10
18
30
44
61
81
103
Slot
1225 mm
Static Pressure, Pa
14
23
35
48
63
81
NC (Noise Criteria)
< 10
< 10
17
25
32
39
44
2.5 - 4 - 6
3.8 - 5.3 - 7.3
4.5 - 5.8 - 8.3
5.3 - 6.5 - 9.3
5.8 - 7 - 9.8
6 - 7.3 - 10.3
6.5 - 8 - 11.3
Width
Throw, m
104
146
189
231
274
316
359
Length
Air Flow, l/s
Total Pressure, Pa
17
28
42
59
78
101
1525 mm
Static Pressure, Pa
12
20
29
41
55
71
NC (Noise Criteria)
< 10
< 10
17
25
33
40
46
2.5 - 3.8 - 6.5
3.8 - 5.3 - 7.5
4.5 - 6 - 8.8
5.5 - 7 - 9.8
6 - 7.3 - 10.8
6.5 - 8 - 11.3
7 - 8.5 - 12.3
Throw, m
All pressures are given in Pascal
Isothermal throw values are given for terminal velocities of .8, .5, and .3 mps.
Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any
-12
of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10
Watts.
Data was obtained from test conducted in accordance with ANSI / ASHRAE Standard 70-1991.
" Method of Testing for Rating the Performance of Air Outlets and Inlets."
The tests were conducted with the FlowBar and plenums as a composite assembly.
Plenums not provided by TITUS may demonstrate performance variations from data published by TITUS.
TITUS cannot guarantee performance if a factory engineered plenum is not provided.
Throw values for HighThrow units are based on a 1-way discharge from the slot.
Throws listed are for the 1-way air pattern. For divide airflow, select the airflow in each direction
according to the number of slots aimed in that direction, with the total airflow apportioned between slots.
Note: All dimensions are nominal product will be built to the closest inch equivalent dimension unless specially ordered to true metric
contact factory for availability of sizes
605 Shiloh Road Plano, Texas 75074 972-212-4800
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means,
electronic or mechanical, including photocopying, or by an information storage system, without permission
in writing from Air Distribution Technologies.
D32M-S
Page 4 of 9
Metric Performance Data
FlowBar High Throw
7/21/98
1- Sl ot , Hi ghThr ow wi t h TI TUS Pl enum
FL-25 with 300 mm inlet
47
68
90
111
132
153
175
Length
Air Flow, l/s
Total Pressure, Pa
18
32
48
69
93
120
600 mm
Static Pressure, Pa
18
31
47
67
90
117
NC (Noise Criteria)
< 10
< 10
12
21
28
34
40
1.8 - 3 - 4.3
2.8 - 3.8 - 5.3
3.3 - 4.3 - 6
4 - 5 - 6.8
4.3 - 5.3 - 7.3
4.5 - 5.5 - 8
5 - 6 - 8.5
Throw, m
Air Flow, l/s
63.5 mm
Slot
66
106
146
186
227
267
307
Total Pressure, Pa
12
23
37
55
76
101
1225 mm Static Pressure, Pa
11
20
33
49
68
90
< 10
< 10
16
26
34
41
46
1.5 - 2.8 - 5.3
3 - 4.5 - 6.8
4.3 - 5.5 - 7.5
5.3 - 6 - 8.8
5.5 - 6.8 - 9.8
6 - 7.3 - 10.3
6.5 - 8 - 11.3
354
Length
Width
NC (Noise Criteria)
Throw, m
71
118
165
212
260
307
Total Pressure, Pa
Air Flow, l/s
10
20
33
49
68
91
1525 mm Static Pressure, Pa
17
28
41
58
77
Length
NC (Noise Criteria)
Throw, m
< 10
< 10
16
26
34
41
47
1.3 - 2.8 - 5.5
3 - 4.5 - 7
4.3 - 5.8 - 8.3
5.5 - 6.8 - 9.5
5.8 - 7.3 - 10.3
6.5 - 8 - 11.3
7 - 8.5 - 12
186
FL-30 with 300 mm inlet
Air Flow, l/s
59
80
101
123
144
165
Length
Total Pressure, Pa
12
23
37
53
74
97
123
600 mm
Static Pressure, Pa
12
22
35
52
71
94
119
NC (Noise Criteria)
Throw, m
Air Flow, l/s
76.2 mm
Slot
< 10
< 10
11
19
26
32
37
2.3 - 3.3 - 5
3 - 4 - 5.8
3.8 - 4.5 - 6.5
4-5-7
4.5 - 5.5 - 7.5
5 - 5.8 - 8.3
5.3 - 6 - 8.8
349
94
137
179
222
264
307
Total Pressure, Pa
18
31
48
68
92
119
1225 mm Static Pressure, Pa
16
28
42
60
81
105
Length
Width
NC (Noise Criteria)
Throw, m
Air Flow, l/s
Length
Total Pressure, Pa
1525 mm Static Pressure, Pa
NC (Noise Criteria)
Throw, m
< 10
< 10
16
26
33
40
45
2.5 - 4 - 6
3.8 - 5.3 - 7.3
5 - 6 - 8.5
5.5 - 6.8 - 9.5
6 - 7.3 - 10.3
6.5 - 8 - 11.3
7 - 8.5 - 12
104
156
208
260
311
363
415
16
29
45
64
88
114
13
24
37
53
73
95
< 10
< 10
17
26
34
41
47
2.5 - 3.8 - 6.5
3.8 - 5.5 - 8
5 - 6.5 - 9.3
5.8 - 7.3 - 10.3
6.5 - 8 - 11.3
7 - 8.5 - 12.3
7.5 - 9.3 - 13
All pressures are given in Pascal
Isothermal throw values are given for terminal velocities of .8, .5, and .3 mps.
Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any
-12
of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10
Watts.
Data was obtained from test conducted in accordance with ANSI / ASHRAE Standard 70-1991.
" M ethod of Testing for Rating the Performance of Air Outlets and Inlets."
The tests were conducted with the FlowBar and plenums as a composite assembly.
Plenums not provided by TITUS may demonstrate performance variations from data published by TITUS.
TITUS cannot guarantee performance if a factory engineered plenum is not provided.
Throw values for HighThrow units are based on a 1-way discharge from the slot.
Throws listed are for the 1-way air pattern. For divide airflow, select the airflow in each direction
according to the number of slots aimed in that direction, with the total airflow apportioned between slots.
Note: All dimensions are nominal product will be built to the closest inch equivalent dimension unless specially ordered to true metric
contact factory for availability of sizes
605 Shiloh Road Plano, Texas 75074 972-212-4800
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means,
electronic or mechanical, including photocopying, or by an information storage system, without permission
in writing from Air Distribution Technologies.
D32M-S
Page 5 of 9
Metric Performance Data
2 - Sl ot ,
FlowBar High Throw
7/21/98
151
Hi ghThr ow wi t h TI TUS Pl enum
FL-10 with 200 mm inlet
38
57
76
94
113
132
L ength
Total Pressure, Pa
Air Flow, l/s
12
21
33
48
65
85
600 mm
Static Pressure, Pa
10
18
28
40
55
72
NC (Noise Criteria)
Throw, m
Air Flow, l/s
< 10
< 10
15
24
30
36
41
1 - 1.8 - 4
1.8 - 3 - 5
2.8 - 4 - 5.5
3.3 - 4.3 - 6
4 - 5 - 6.8
4.3 - 5.3 - 7.3
4.5 - 5.5 - 8
76
109
142
175
208
241
274
16
27
41
59
79
102
25.4 mm
L ength
Total Pressure, Pa
Slot
1225 mm
Static Pressure, Pa
16
24
34
46
59
NC (Noise Criteria)
< 10
< 10
18
25
32
37
42
6 - 7.3 - 10.8
W idth
Throw, m
L ength
1525 mm
1.3 - 2.8 - 5.5
2.8 - 4 - 6.8
3.3 - 5.3 - 7.5
4.3 - 6 - 8.5
5.3 - 6.5 - 9.3
5.8 - 7 - 9.8
Air Flow, l/s
94
132
170
208
245
283
321
Total Pressure, Pa
10
19
31
46
65
86
111
Static Pressure, Pa
15
22
30
40
52
NC (Noise Criteria)
< 10
< 10
18
25
31
36
41
1.5 - 3 - 6
2.8 - 4.3 - 7.3
3.8 - 5.5 - 8.3
4.5 - 6.5 - 9.3
5.5 - 7 - 10
6 - 7.5 - 10.8
6.8 - 8.3 - 11.5
170
Throw, m
FL-15 with 200 mm inlet
Air Flow, l/s
57
76
94
113
132
151
L ength
Total Pressure, Pa
10
18
28
40
54
71
89
600 mm
Static Pressure, Pa
14
22
32
44
57
73
NC (Noise Criteria)
Throw, m
< 10
11
19
26
32
37
41
1.8 - 3 - 5
2.8 - 4 - 5.5
3.3 - 4.3 - 6
4 - 5 - 6.8
4.3 - 5.3 - 7.3
4.5 - 5.5 - 8
5 - 5.8 - 8.3
Air Flow, l/s
113
146
179
212
245
278
311
38.1 mm
L ength
Total Pressure, Pa
15
26
39
54
72
93
117
Slot
1225 mm
Static Pressure, Pa
13
20
28
38
49
61
NC (Noise Criteria)
< 10
15
22
28
34
38
43
6.5 - 8 - 11.3
W idth
Throw, m
L ength
1525 mm
2.8 - 4.3 - 6.8
3.8 - 5.5 - 7.5
4.3 - 6 - 8.5
5.3 - 6.8 - 9.5
5.8 - 7 - 10
6 - 7.5 - 10.8
Air Flow, l/s
142
175
208
241
274
307
340
Total Pressure, Pa
20
30
42
57
73
92
113
Static Pressure, Pa
12
17
23
30
38
47
NC (Noise Criteria)
< 10
14
21
26
31
35
39
3 - 4.5 - 7.5
4 - 5.8 - 8.5
4.5 - 6.5 - 9.3
5.3 - 7 - 9.8
6 - 7.3 - 10.8
6.5 - 8 - 11.3
6.8 - 8.3 - 12
184
Throw, m
FL-20 with 200 mm inlet
57
78
99
120
142
163
L ength
Air Flow, l/s
Total Pressure, Pa
13
21
31
43
57
73
600 mm
Static Pressure, Pa
10
16
23
32
42
54
NC (Noise Criteria)
Throw, m
< 10
11
20
27
33
38
42
1.5 - 2.8 - 5
2.5 - 3.8 - 5.5
3 - 4.5 - 6.5
3.8 - 5 - 7
4.3 - 5.5 - 7.5
4.5 - 5.8 - 8.3
5 - 6 - 8.5
Air Flow, l/s
113
142
170
198
227
255
283
50.8 mm
L ength
Total Pressure, Pa
12
19
28
38
50
63
78
Slot
1225 mm
Static Pressure, Pa
11
16
20
26
32
NC (Noise Criteria)
12
21
27
33
38
43
47
W idth
Throw, m
2.3 - 3.8 - 6.8
3 - 4.5 - 7.5
3.8 - 5.5 - 8.3
4.3 - 6.5 - 8.8
5 - 6.8 - 9.8
5.5 - 7.3 - 10
6 - 7.5 - 10.8
Air Flow, l/s
123
153
184
215
245
276
307
L ength
Total Pressure, Pa
12
19
28
38
50
63
78
1525 mm
Static Pressure, Pa
12
15
19
24
NC (Noise Criteria)
Throw, m
11
20
26
32
37
42
46
1.8 - 3.8 - 7
2.8 - 4.5 - 8
3.8 - 5.5 - 8.5
4.3 - 6 - 9.5
5 - 7 - 10
5.5 - 7.5 - 10.8
5.8 - 8 - 11.3
Note: All dimensions are nominal product will be built to the closest inch equivalent dimension unless specially ordered to true metric
contact factory for availability of sizes
605 Shiloh Road Plano, Texas 75074 972-212-4800
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means,
electronic or mechanical, including photocopying, or by an information storage system, without permission
in writing from Air Distribution Technologies.
D32M-S
Page 6 of 9
Metric Performance Data
2 - Sl ot ,
FlowBar High Throw
7/21/98
Hi ghThr ow wi t h TI TUS Pl enum
FL-10 with 250 mm inlet
38
61
85
109
132
156
179
L ength
Air Flow, l/s
Total Pressure, Pa
13
24
40
59
82
109
600 mm
Static Pressure, Pa
12
23
37
55
76
101
NC (Noise Criteria)
< 10
< 10
19
28
35
41
47
1 - 1.8 - 4
2.3 - 3.3 - 5
3 - 4.3 - 5.8
3.8 - 4.5 - 6.8
4.3 - 5.3 - 7.3
4.5 - 5.5 - 8
5 - 6 - 8.5
Throw, m
76
113
151
189
227
264
302
25.4 mm
L ength
Total Pressure, Pa
Air Flow, l/s
13
23
36
52
71
93
Slot
1225 mm
Static Pressure, Pa
10
18
28
40
55
72
NC (Noise Criteria)
< 10
< 10
19
27
34
40
45
1.3 - 2.8 - 5.5
2.8 - 4.3 - 6.8
3.8 - 5.5 - 8
4.5 - 6 - 8.8
5.5 - 6.8 - 9.8
6 - 7.3 - 10.3
6.5 - 8 - 11
94
139
184
229
274
319
363
97
W idth
Throw, m
Air Flow, l/s
L ength
Total Pressure, Pa
14
25
39
55
75
1525 mm
Static Pressure, Pa
10
17
26
38
51
66
NC (Noise Criteria)
< 10
< 10
20
28
34
40
45
1.5 - 3 - 6
3 - 4.5 - 7.5
4 - 6 - 8.5
5.3 - 6.8 - 9.8
6 - 7.3 - 10.8
6.8 - 8 - 11.3
7 - 8.5 - 12.3
Throw, m
FL-15 with 300 mm inlet
57
80
104
127
151
175
198
L ength
Air Flow, l/s
Total Pressure, Pa
17
28
43
60
80
103
600 mm
Static Pressure, Pa
16
27
41
57
77
99
NC (Noise Criteria)
< 10
11
21
29
35
40
45
Throw, m
1.8 - 3 - 5
2.8 - 4 - 5.8
3.8 - 4.5 - 6.5
4.3 - 5.3 - 7.3
4.5 - 5.5 - 8
5 - 6 - 8.5
5.3 - 6.5 - 8.8
Air Flow, l/s
113
151
189
227
264
302
340
86
38.1 mm
L ength
Total Pressure, Pa
10
17
26
38
52
68
Slot
1225 mm
Static Pressure, Pa
14
22
32
44
57
73
NC (Noise Criteria)
< 10
14
22
29
35
40
44
W idth
Throw, m
2.8 - 4.3 - 6.8
3.8 - 5.5 - 8
4.5 - 6 - 8.8
5.5 - 6.8 - 9.8
6 - 7.3 - 10.3
6.5 - 8 - 11
6.8 - 8.3 - 12
Air Flow, l/s
142
189
236
283
330
378
425
L ength
Total Pressure, Pa
10
18
29
41
56
74
93
1525 mm
Static Pressure, Pa
14
22
32
44
57
73
NC (Noise Criteria)
< 10
15
24
31
36
41
46
3 - 4.5 - 7.5
4.3 - 6 - 8.8
5.3 - 7 - 9.8
6 - 7.5 - 10.8
6.8 - 8.3 - 11.5
7 - 8.8 - 12.5
7.5 - 9.5 - 13
Throw, m
FL-20 with 300 mm inlet
57
92
127
163
198
234
269
L ength
Air Flow, l/s
Total Pressure, Pa
14
28
45
67
93
123
600 mm
Static Pressure, Pa
13
26
42
62
86
115
NC (Noise Criteria)
< 10
< 10
17
26
33
39
45
1.5 - 2.8 - 5
2.8 - 4.3 - 6
4 - 5.3 - 7.3
4.5 - 5.8 - 8.3
5.3 - 6.5 - 8.8
5.5 - 7 - 9.8
6 - 7.3 - 10.3
Throw, m
113
156
198
241
283
326
368
50.8 mm
L ength
Total Pressure, Pa
Air Flow, l/s
12
20
29
41
54
69
Slot
1225 mm
Static Pressure, Pa
10
16
23
32
42
54
NC (Noise Criteria)
< 10
12
21
28
34
39
44
2.3 - 3.8 - 6.8
3.3 - 5.3 - 8
4.3 - 6.5 - 8.8
5.3 - 7 - 9.8
6 - 7.5 - 10.8
6.8 - 8.3 - 11.5
7 - 8.5 - 12.3
132
179
227
274
321
368
415
63
W idth
Throw, m
Air Flow, l/s
L ength
Total Pressure, Pa
12
19
27
38
50
1525 mm
Static Pressure, Pa
13
19
26
34
44
NC (Noise Criteria)
< 10
14
22
29
35
40
45
1.8 - 4 - 7.3
3.3 - 5.3 - 8.5
4.3 - 6.8 - 9.8
5.3 - 7.3 - 10.8
6 - 8.3 - 11.5
7 - 8.5 - 12.3
7.5 - 9.3 - 13
Throw, m
Note: All dimensions are nominal product will be built to the closest inch equivalent dimension unless specially ordered to true metric
contact factory for availability of sizes
605 Shiloh Road Plano, Texas 75074 972-212-4800
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means,
electronic or mechanical, including photocopying, or by an information storage system, without permission
in writing from Air Distribution Technologies.
D32M-S
Page 7 of 9
Metric Performance Data
2 - Sl ot ,
FlowBar High Throw
7/21/98
Hi ghThr ow wi t h TI TUS Pl e n u m
FL-25 with 250 mm inlet
38
76
113
151
189
227
L ength
Total Pressure, Pa
Air Flow, l/ s
15
27
42
61
83
600 mm
Static Pressure, Pa
12
22
34
49
67
NC (Noise Criteria)
Throw, m
264
< 10
< 10
11
22
31
39
45
0.5 - 1.3 - 3.3
2.3 - 3.3 - 5.5
3.3 - 5 - 6.8
4.3 - 5.5 - 8
5.3 - 6 - 8.8
5.5 - 6.8 - 9.8
6 - 7.3 - 10.3
415
76
132
189
245
302
359
63.5 mm
L ength
Total Pressure, Pa
Air Flow, l/ s
17
29
43
61
82
Slot
1225 mm
Static Pressure, Pa
14
22
31
41
NC (Noise Criteria)
W idth
Throw, m
< 10
< 10
15
26
35
42
48
1 - 1.8 - 4.5
2.5 - 4 - 7.3
4 - 5.8 - 8.8
5.3 - 7 - 10
6 - 8 - 11
7 - 8.5 - 12.3
7.5 - 9.3 - 13
477
94
158
222
286
349
413
L ength
Air Flow, l/ s
Total Pressure, Pa
10
19
32
47
66
88
1525 mm
Static Pressure, Pa
12
19
26
35
NC (Noise Criteria)
Throw, m
< 10
< 10
17
27
35
42
48
1 - 1.8 - 5.3
2.5 - 4.3 - 8
4 - 6 - 9.5
5.3 - 7.5 - 10.8
6.5 - 8.5 - 12
7.5 - 9.3 - 13
8 - 9.8 - 14
38
85
132
179
227
274
321
19
35
56
82
113
FL-30 with 250 mm inlet
Air Flow, l/ s
L ength
Total Pressure, Pa
600 mm
Static Pressure, Pa
15
28
44
64
89
NC (Noise Criteria)
< 10
< 10
< 10
20
31
39
46
0.3 - 1 - 3
2.3 - 3.3 - 5.8
3.8 - 5.3 - 7.3
5 - 6 - 8.5
5.5 - 6.8 - 9.8
6 - 7.3 - 10.8
6.8 - 8.3 - 11.5
71
142
212
283
354
425
496
20
36
56
81
110
Throw, m
Air Flow, l/ s
76.2 mm
L ength
Total Pressure, Pa
Slot
1225 mm
Static Pressure, Pa
10
17
27
39
53
NC (Noise Criteria)
< 10
< 10
< 10
22
32
41
48
0.5 - 1.3 - 4
2.3 - 4 - 7.5
4 - 6 - 9.5
5.5 - 7.5 - 10.8
6.8 - 8.5 - 12
7.5 - 9.5 - 13
8.3 - 10 - 14.3
85
165
245
326
406
486
566
10
22
39
61
88
119
W idth
Throw, m
Air Flow, l/ s
L ength
Total Pressure, Pa
1525 mm
Static Pressure, Pa
15
23
32
44
NC (Noise Criteria)
< 10
< 10
10
23
33
41
48
0.5 - 1.3 - 4.3
2.3 - 4.3 - 8.3
4.3 - 6.5 - 10
5.5 - 8.3 - 11.5
7 - 9.3 - 12.8
8.3 - 10 - 14
8.8 - 10.8 - 15.3
Throw, m
Al l
I s o t h e r ma l t h r o w v a l u e s a r e g i v e n f o r t e r mi n a l v e l o c i t i e s o f
E a c h NC v a l u e r e p r e s e n t s t h e n o i s e c r i t e r i a c u r v e wh i c h wi l l
pr e s s u r es ar e gi ven i n Pascal
of
t he oct ave bands,
2nd t hr ough 7t h,
. 8,
not
. 5 , a n d . 3 mp s .
be exceeded by t he sound pr
wi t h a r o o m a b s o r p t i o n o f
-12
Wa t t s .
Da t a wa s o b t a i n e d f r o m t e s t
T h e t e s t s we r e c o n d u c t e d wi t h t h e F l o wBa r a n d p l e n u ms a s a c o mp o s i t e a s s e mb l y .
Pl e n u ms n o t p r o v i d e d b y T I TUS ma y d e mo n s t r a t e p e r f o r ma n c e v a r i a t i o n s f r o m d a t a p u b l i s h e d b y T
TI TUS c a n n o t g u a r a n t e e p e r f o r ma n c e i f a f a c t o r y e n g i n e e r e d p l e n u m i s n o t p r o v i d e d .
T h r o w v a l u e s f o r Hi g h T h r o w u n i t s a r e b a s e d o n a 1 - wa y d i s c h a r g e f r o m t h e s l o t .
Me t h o d o f
Test i ng f or
Ra t i n g t h e P e r f o r ma n c e o f
T h r o ws l i s t e d a r e f o r t h e 1 - wa y a i r p a t t e r n .
For
a c c o r d i n g t o t h e n u mb e r o f s l o t s a i me d i n t h a t
Ai r
r e 10
"
c o n d u c t e d i n a c c o r d a n c e wi t h ANSI
10dB,
ASHRAE St a n d a r d 7 0 - 1 9 9 1 .
Ou t l e t s a n d I n l e t s . "
d i v i d e a i r f l o w, s e l e c t t h e a i r f l o w i n e a c h d
d i r e c t i o n , wi t h t h e t o t a l a i r f l o w a p p o r t i o n e d b e
Note: All dimensions are nominal product will be built to the closest inch equivalent dimension unless specially ordered to true metric
contact factory for availability of sizes
605 Shiloh Road Plano, Texas 75074 972-212-4800
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means,
electronic or mechanical, including photocopying, or by an information storage system, without permission
in writing from Air Distribution Technologies.
D32M-S
Page 8 of 9
Metric Performance Data
FlowBar High Throw
7/21/98
2-Slot, HighThrow with TI T U S Plenum
FL-25 with 300 mm inlet
38
80
123
165
208
250
L engt h
Air Flow, l/s
T o t al Pressure, Pa
16
29
46
67
92
600 mm
Static Pressure, Pa
14
26
41
60
82
NC (Noise Criteria)
Throw, m
Air Flow, l/s
293
<10
<10
<10
21
31
38
45
0.5 - 1.3 - 3.3
2.5 - 3.3 - 5.8
3.8 - 5 - 7
5 - 5.8 - 8.3
5.3 - 6.5 - 9.3
5.8 - 7 - 10
6.5 - 7.5 - 11
458
76
139
203
267
330
394
63.5 mm
L engt h
T o t al Pressure, Pa
15
25
38
55
74
Slot
1225 mm
Static Pressure, Pa
10
17
26
37
50
NC (Noise Criteria)
W i dth
Throw, m
Air Flow, l/s
<10
<10
13
25
33
41
47
1 - 1.8 - 4.5
2.8 - 4.3 - 7.5
4.3 - 6.5 - 9.3
5.5 - 7.3 - 10.3
6.8 - 8.3 - 11.5
7.3 - 8.8 - 12.8
8 - 9.8 - 13.8
94
165
236
307
378
448
519
L engt h
T o t al Pressure, Pa
15
25
38
54
72
1525 mm
Static Pressure, Pa
14
22
31
41
NC (Noise Criteria)
<10
<10
14
25
34
41
47
1 - 1.8 - 5.3
2.8 - 4.5 - 8.3
4.3 - 6.5 - 9.8
5.8 - 8 - 11.3
7 - 8.8 - 12.5
8 - 9.5 - 13.5
8.5 - 10.3 - 14.8
Throw, m
FL-30 with 300 mm inlet
38
85
132
179
227
274
321
L engt h
Air Flow, l/s
T o t al Pressure, Pa
17
31
50
73
100
600 mm
Static Pressure, Pa
15
28
44
64
89
NC (Noise Criteria)
<10
<10
<10
16
26
35
42
0.3 - 1 - 3
2.3 - 3.3 - 5.8
3.8 - 5.3 - 7.3
5 - 6 - 8.5
5.5 - 6.8 - 9.8
6 - 7.3 - 10.8
6.8 - 8.3 - 11.5
524
Throw, m
71
146
222
297
373
448
76.2 mm
L engt h
Air Flow, l/s
T o t al Pressure, Pa
16
29
46
66
90
Slot
1225 mm
Static Pressure, Pa
11
19
30
43
59
NC (Noise Criteria)
W i dth
Throw, m
Air Flow, l/s
<10
<10
<10
19
30
38
45
0.5 - 1.3 - 4
2.5 - 4.3 - 7.5
4.3 - 6.5 - 9.5
5.8 - 8 - 11
7 - 8.8 - 12.3
8 - 9.5 - 13.5
8.5 - 10.3 - 14.8
85
170
255
340
425
510
595
L engt h
T o t al Pressure, Pa
16
29
45
65
89
1525 mm
Static Pressure, Pa
16
25
36
49
NC (Noise Criteria)
<10
<10
<10
20
30
38
45
0.5 - 1.3 - 4.3
2.3 - 4.3 - 8.3
4.3 - 6.5 - 10
5.8 - 8.3 - 12
7.3 - 9.5 - 13
8.3 - 10 - 14.3
8.8 - 11 - 15.5
Throw, m
All pressures are given in Pascal
Isothermal throw values are given for terminal velocities of .8, .5, and .3 mps.
Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any
-12
of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10 W atts.
Data was obtained from test conducted in accordance with A N SI / ASHRAE Standard 70-1991.
" Method of Testing for Rating the Performance of A ir Outlets and Inlets."
The tests were conducted with the FlowBar and plenums as a composite assembly.
Plenums not provided by TITUS may demonstrate performance variations from data published by TITUS.
TITUS cannot guarantee performance if a factory engineered plenum is not provided.
Throw values for HighThrow units are based on a 1-way discharge from the slot.
Throws listed are for the 1-way air pattern. For divide airflow, select the airflow in each direction
according to the number of slots aimed in that direction, with the total airflow apportioned between slots.
Note: All dimensions are nominal product will be built to the closest inch equivalent dimension unless specially ordered to true metric
contact factory for availability of sizes
605 Shiloh Road Plano, Texas 75074 972-212-4800
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means,
electronic or mechanical, including photocopying, or by an information storage system, without permission
in writing from Air Distribution Technologies.
D32M-S
Page 9 of 9