AC 140 HangerSupport
AC 140 HangerSupport
AC 140 HangerSupport
1.0
GENERAL
1.1
DESCRIPTION
.1
1.2
1.3
WORK INCLUDED
.1
Hangers.
.2
Structure Attachments,
SUBMITTALS
.1
.2
Shop Drawings: Submit details of pipe hangers, anchors and supports for
each pipe size and pipe service. Submit details of support methods and
point loadings, and anchor reactions.
2.0
PRODUCT
2.1
.2
All pipes supports shall be steel, adjustable for height and prime coated
with rust preventive paint and finish coated black, in the types shown in
the following table. This table does not apply for buried pipes.
Services
Pipe Size
Type of Support
Chilled Water
All Sizes
Hot Water
12mm to 150mm
-do-
Hot Water
Roller or Spring
Steam
12mm to 50mm
Clamp
Steam
Roller or Spring
Drain
6mm-up
Clamp
Compressed Air
6mm-up
Clamp
Water (Drinking
or Condensing)
Saddle or clamp or
otherwise as approved
.3
.4
Vertical risers when passing through each floor slab shall be supported to
the floor by means of clamps, collars or pipe guides attached to the pipe
which in turn shall be attached to angles as per the following schedule:
Service
Support
Chilled Water
Hot Water
Spring
Steam
Spring
Cradles
Drain Pipes
Compressed Air
Spring or as approved
Medical Gases
Pipes Size
Type of Support
Under 20
Up - 4
Hanger at Elbow
Under 20
6- 8
Under 20
10- up
Foot elbow
Over 20
Up to 1
Hanger at elbow
Over 20
1 6
Support or concrete
Over 20
7 and up
Foot elbow
.5
.6
.7
.8
All piping shall generally be graded to eliminate air pockets or gas locks
depending on the service.
.9
The piping installation shall incorporate provisions for the venting of high
points and drawings of low points.
KENCANA SQUARE
HANGER, ANCHORS AND SUPPORTS
SECTION AC-140
Page 3
3.0
EXECUTION
3.1
INSTALLATION
.1
Maximum Hanger
Spacing
Minimum Rod
Size
1800mm
10mm
32mm to 50mm
2700mm
10mm
65mm to 80mm
3000mm
15mm
100mm to 125mm
3600mm
15mm
150mm
3600mm
20mm
200mm to 300mm
3600mm
25mm
350mm to 400mm
3600mm
25mm
450mm
3600mm
30mm
500mm
3600mm
35mm
600mm
3600mm
40mm
750mm
3600mm
40mm
1000mm
3600mm
50mm
1200mm
3600mm
50mm
.2
Provide hangers at each change in direction and both sides of each valve.
.3
.4
.5
Provide approved roller support, floor stands, wall brackets, etc., for all
lines running near the floor or near walls, which can be properly
supported or suspended by the floors or walls. Pipelines near walls may
also be hung by hangers carried from approved wall brackets at a level
higher than the pipe.
.6
.7
Wherever hangers using pipe rolls are used provide approved steel pipe
covering protection saddles, spot welded to the piping at each hanger
location.
.8
.9
Support all lines for copper tubing individually by approved type hangers
not more than 2m apart, or as shown on the drawings. Use hangers
especially designed for copper tubing and of exact outside diameter of
tubing. On hangers for covered tubing, use broad straps fitting outside of
covering.
.10
Hangers used for cold piping will support the pipe without piercing the
insulation. Use insulation shields to protect the insulation on cold pipes.
Weld insulation protection saddles to insulated hot pipes, or any piping
subject to axial movement, at roller supports. Space between pipe and
saddle to be filled with insulation.
.11
For piping 100mm and larger, support the elbows of the piping adjacent to
the pumps with steel base elbow supports from the inertia base which
pump is on to prevent loading heavy weights of piping on pump casing.
Where inertia base is not provided, base elbows to be supported on floor
with 25mm neoprene pad.
.12
prevent undue
separate from
and to include
of supporting.