Metering Pumps - The Lowdown On Turndown
Metering Pumps - The Lowdown On Turndown
Metering Pumps - The Lowdown On Turndown
Graph 1 shows the results of a more useful accuracy rating that is based on a deviation from the
pumps current capacity setting, or set point. When the accuracy rating is based on set point, the
accuracy expected has much more meaning. It doesnt matter what capacity the process requires
over the pumps turndown ratio the pump output will be at the expected flow within a reasonable
deviation. In this example the accuracy percentage has been increased from 1% to 5% so the
variance can be seen. If the graph were drawn for the industry standard of 1% accuracy, the lines
would be on top of each other. This graph shows percent deviation, which is a constant 5%.
Graph 2 shows how this relates to the pumps actual flow rate. In this example the accuracy has
been moved back to the industry standard value of 1%, so the lines are very close to each other.
This graph is more representative of the expected performance of a true metering pump. Its hard to
see on the graph, so here are the important flow and performance characteristics:
At maximum capacity setting (100%) where 1000 GPH is expected:
- Maximum allowable actual flow: 1010 GPH
- Minimum allowable actual flow: 990 GPH
At minimum capacity setting (1%) where 1 GPH is expected:
- Maximum allowable actual Flow: 1.01 GPH
- Minimum allowable actual Flow: 0.99 GPH
Graphs 1 and 2 represent steady state accuracy, which more accurately corresponds to the
performance of a true metering pump. Steady state accuracy can be defined as a pumps flow rate
variation expressed as a percentage of mean delivered flow under fixed system conditions applied
over the full turndown ratio of the pump.
Flow repeatability is also a form of accuracy. Also stated as percentage of rated capacity, it
describes how much the pump output is allowed to deviate when its capacity setting is changed,
and then returned to the original setting. So if the pump is providing 50 GPH at 40% capacity setting
and the pump is changed to 80%, when the setting is returned to 40% the pump will still provide a
flow near 50 GPH within the flow repeatability accuracy. Typically, metering pumps are rated at
3% flow repeatability. Many process engineers order 10 point curves with the pump to show this
variation. The 10 point curve shows output at 5 points descending, then the same 5 points
ascending, and compares the two.
Metering Pump
Manufacturers of many different types of pumps try to attach a variable speed drive to their units
and call the resulting product a metering pump. While its true that the result will be a pump that
varies capacity, the performance and characteristics will not match the industry expectations of a
metering pump. Depending on the type of pump attempting this crossover, repeatable performance
and resulting flow rate can vary based on a number of factors including:
- Fatigue of elastomers, or hoses, or tubes
- Suction pressure or tank fluid height
- Minor discharge pressure fluctuations
- Hydraulic inefficiencies
Any one of these issues will impact the performance of pump that fails to meet the design criteria of
a true metering pump.
Metering pumps, also referred to as dosing, proportioning, or chemical injection pumps, are defined
as controlled volume positive displacement pumps with the ability to precisely control process fluid
volume by varying effective stroke length. In the past several decades, reciprocating pumps with
constant stroke length and variable stroke frequency have also been recognized as metering
pumps. In general, the attributes that define a metering pump include:
- Positive displacement - a general category of pumps that differ from centrifugal pumps in that
they will displace any process fluid from within the pump head
- Integrated mechanism that enables pump capacity adjustment
variations or errors in dosage calculations. Theres nothing wrong with recognizing this possiblity,
but installing an oversized pump that will always be operating below 1% of its maximum capacity is
like using an 18 wheeler to deliver a few music CDs bought on-line. Efficiency is lost at a number of
levels.
What does High Turndown really mean?
When we look at what high turndown really means to the flow of the pump, its easy to see the true
benefit.
Start with a pump rated for 100 GPH. At 10 to1 turndown ratio, the pump gives excellent
performance between 10 GPH and 100 GPH. The benefit is clear in that 90% of the pumps
maximum capacity is within its usable range.
If the same pump provides 100 to1 turndown, the range is extended to 99% of its usable range:
100 GPH to 1 GPH. 10 to 1 verses 100 to 1 sounds like 10 times more, but it only increases the
usable range by 9% of full capacity.
Now increase this pumps turndown to 1,000 to 1 and the real increase in turndown is miniscule.
The performance of the pump will now be usable between 100 GPH and 0.1 GPH. The pump now
provides an additional accurate flow rating of 0.9 GPH, 0.9 % of full capacity. Again, it sounds like
10 times more than 100 to1, or 100 times more than 10 to 1, but the real result is quite small.
Table 1 provides a way to look at the increase in accurate flow that is achieved by increasing
turndown. Observe the amount of extra capacity that is realized by increasing the turndown 10
times that of the row above. Rating a 100 GPH pump with a turndown ratio of 10,000 to 1 only
provides 0.09 GPH more range than a 1,000 to 1 rating.
Clearly, wide turndowns do not really increase what the pump can do by all that much. Once the
claim of turndown goes beyond 100 to 1, theres little benefit. In fact, beyond 100 to 1 it raises the
question of pump efficiency. The motor and drive is sized to provide 100 gallons per hour. If the
pump operates at 0.2 % of its design, efficiency has to suffer. But the other question this raises is
just as important.
How do you measure wide turndown ratios?
Flow meters have a useable turndown too, and 1000 to 1 is well beyond the capability of most. Loss
in weight measurement of the fluid being pumped (usually a digital scale under the supply tank) is a
possiblility, but its a rare process that has this hardware installed. Calibration columns require
visual observation of the amount of chemical pumped, which introduces human error that causes
inaccuracies. At wide turndown ratios, the difference between 10 to 1 and 1000 to 1 may be less
than a drop of fluid and there is no chance anyone can see the change in a calibration column, flow
meters cannot handle the range, and other potential methods are impractical or too expensive to
justify.
So the answer is simple wild claims of wide turndown ratios cannot be effectively measured or
confirmed in the installation. Up to 100 to 1 is easily measured and verified within the steady state
accuracy of the pump. 1000 to 1 is more difficult, but can be measured in a controlled setting at the
manufacturers testing facility. When turndown claims reach 10,000 to 1 or higher, the claim cannot
be substantiated. If the rating cant be measured or proven, that makes it safe to boast exaggerated
claims of large turndown ratios. To make a claim that a pump can provide 1,000,000 to 1 turndown,
especially without an accuracy rating, is nothing more than marketing fluff without any basis in
reality. Companies that make these kinds of claims usually do not manufacture real metering
pumps, and resort to meaningless exagerations to project an image of accuracy that isnt really
there.
Can there be an efficent metering pump with 1,000,000 to 1 turndown and a steady state accuracy
of 2% or better? Let those making the claim prove it, because I seriously doubt it!
Summary
Exaggerated claims that cannot be verified are not only misleading, but in the actual installation
provide very little benefit to the process. A professional metering pump company rates the turndown
of its products based on solid design and verifyable testing methods. In those tests, every pump
manufactured can be tested at the turndown ratings while maintaining repeatability and steady state
accuracy.
The basic questions that need to be asked related to turndown are:
What turndown does the process really require?
If it exceeds 100 to 1, what is the best and most efficient way to address it?
Will the pump selected provide the turndown needed with the accuracy expected from a true
metering pump regardless of pressure fluctuations and the age of the equipment?
If a pump is purchased based on exaggerated turndown that isnt required by the process, the buyer
may not realize some other important issues:
- Most pumps offered with exaggerated claims are primarily plastic housings with significant
electronic componentry that, by nature, usually last about 5 years at best. True metering pumps are
robust pieces of equipment with 30 year design life.
- Pump designs that try to be metering pumps usually require much more frequent maintenance.
For example, peristaltic pumps boast that they can go up to 6 months before needing maintenance.
Actual experiences have seen many examples of hose replacement every few weeks. True
metering pumps can run for years without maintenance and, in fact, have diaphragms with design
life ratings as high as 96,000 hours (almost 11 years running 24/7).
- True metering pumps usually cost less to buy and cost less to maintain. As a taxpayer that is the
performance Id expect at my local municipal treatment plant. Process managers and operators
recognize the impact in reducing capital costs and controlling operating expenses.
- Steady state accuracy and repeatability assure accurate dosage and that ties directly to reduced
chemical usage while maintaining chemical treatment performance in the process. In potable water,
for example, this assures compliant water in the distribution system. Only a true controlled volume
metering pump provides the performance required for this level of process integrity.