Cascade Control Signal Distribution Block
Cascade Control Signal Distribution Block
IN
TIC301
OUT
PID
%Z011106
SET
FOUT301
FOUT
J01
J02
SET
IN
TIC302
SET
OUT
IN
PID
%Z011111
TIC303
OUT
PID
%Z011112
%Z011113
%Z011114
54
The setpoint value (SV) of the Cascade Signal Distributor Block (FOUT) can be used for
data reference but not for data setting.
55
The cascade set signal is adjusted to the range of each destination to which it is distributed.
In the example, assume that FOUT block has an SV range of 0 to 100% and the downstream
controller blocks have PV ranges of 0 to 8000 NM3/H and 0 to 10.00 KG/H. When the
upstream controller blocks control output is 50%, the outputs of FOUT block is 4000M3/H
and 5.00 KG/H.
The upstream function blocks, which can be connected to the FOUT block, are to satisfy the
following conditions:
Regulatory control blocks that enable cascade connection and provide a control
output(MV).
Analog computation blocks that enable cascade connection.
If the FOUT blocks are connected in cascade, up to 6 FOUT blocks can be connected in
series between the most upstream block and the most downstream block.
The selector switch blocks (SW-33, SW-91) provided between the blocks are excluded.
If more than 6 FOUT blocks are connected, the control out (MV) status of the most upstream
block turns to output fail (PTPF).
56
2. Create control window on [CG0001]. Assign four function blocks on the control window.
3. Operation confirmation by test function.
4. Confirmation procedure.
Set the block mode of the control blocks [TIC302] and [TIC303] to CAS.
Set MV of TIC301 to 50%.
Confirm that the SV of [TIC302] becomes 100.0 DEGC and the SV of [TIC303]
becomes 200.0 DEGC.
57