Design Assumptions and Calculations
Design Assumptions and Calculations
Design Assumptions and Calculations
Air stripping
Attachment C2 Ex Situ Chromium Treatment Calculation Details (for 600 gallons per
minute concept)
RDD/091890010 (NLH4093.DOC)
C-1
Attachment C1
Air Stripper and Vapor-phase Granular
Activated Carbon Treatment Calculation Details
ATTACHMENT C1
C1.1.1 Pretreatment
Based on the assumed low turbidity level of the influent, only a coarse strainer should be
necessary as pretreatment for the stripper process. The addition of a sequestration agent
and a disinfectant (bleach) has been assumed to control inorganic scales and biological
fouling, respectively. Periodic maintenance by high-rate washing with surfactant or acid
should be adequate for removing sediments and scales of iron hydroxide and calcium
carbonate, if present. Air stripper tower washing system maintenance, waste neutralization,
and disposal of the washing solution are considered outside the scope of the North
Hollywood Operable Unit (NHOU) Focused Feasibility Study (FFS).
RDD/091890010 (NLH4093.DOC)
C1-1
ATTACHMENT C1 AIR STRIPPER AND VAPOR-PHASE GRANULAR ACTIVATED CARBON TREATMENT CALCULATION DETAILS
Z = NTU x HTU x Fs
(1)
Where:
Z
Fs
= factor of safety for the column (1.0 means no safety factor, 1.25 means 25 percent
safety factor)
For the FFS, the packed-bed stripper depth was assumed to be the same as the current
stripper (19.5 feet). The air-to-water ratio was minimized to reduce capital and operation
and management costs associated with offgas treatment.
Minimum air-to-water ratio of 12:1 applies only to compounds with Henrys constants greater than 100 atm/mole fraction.
A higher minimum air-to-water ratio applies to compounds with Henrys constants less than 100 atm/mole fraction.
C1-2
RDD/091890010 (NLH4093.DOC)
ATTACHMENT C1 AIR STRIPPER AND VAPOR-PHASE GRANULAR ACTIVATED CARBON TREATMENT CALCULATION DETAILS
These removal rates are generally accepted for 1 to 2 inches of bed depth, known as the
mass transfer zone. The mass transfer zone depths are typical for superficial velocities of 0.8
to 1.5 feet per second.
For the purposes of estimating air emissions from the VGAC adsorbers, it is recommended
to assume 90 percent capture of VOCs per bed.
These are conservative estimates, and actual operation of the VGAC units is expected to
result in higher capture rates. However, a 90 percent capture rate is typical of performance
guarantees available from suppliers. The performance standards previously discussed
indicate that the actual performance should be better than the vendor guarantee; however,
only 90 percent capture should be assumed when estimating system emissions.
C1.4.3 Isotherms
The isotherm constants used and presented here were determined using isotherm graphs
provided by Calgon Carbon Corporation and American Norit Company, Inc. However,
these isotherms are only representative of virgin VGAC.
RDD/091890010 (NLH4093.DOC)
C1-3
ATTACHMENT C1 AIR STRIPPER AND VAPOR-PHASE GRANULAR ACTIVATED CARBON TREATMENT CALCULATION DETAILS
X
(
= K * Cf
M
/ n)
(2)
Where:
X/M = carbon adsorption capacity (mol(solute)/gC) for the solute at the influent
concentration Cf
K
1/n
The single solute isotherm capacity (X/M) for each compound is calculated using the
Freundlich isotherm (see Equation 2). The isotherm capacity is converted to carbon usage
rate or carbon bed life using the molecular weight, influent flows, and concentration. All
isotherm capacities are based on virgin coconut-based VGAC data. The single component
carbon usage rates for all components are summed. This assumes no coadsorption of
contaminants.
C1-4
RDD/091890010 (NLH4093.DOC)
ATTACHMENT C1 AIR STRIPPER AND VAPOR-PHASE GRANULAR ACTIVATED CARBON TREATMENT CALCULATION DETAILS
The systems developed for the FFS incorporate these guidelines where applicable.
Following are some of the considerations in developing the VGAC usage rate values:
All VGAC adsorbers are double-pass operation, and multiple adsorbers are also
arranged in parallel.
The VGAC adsorber calculations, which are based on the standards presented, are
summarized in Attachment C4.
RDD/091890010 (NLH4093.DOC)
C1-5
ATTACHMENT C1 AIR STRIPPER AND VAPOR-PHASE GRANULAR ACTIVATED CARBON TREATMENT CALCULATION DETAILS
decay of the adsorbed radon to lower levels that are believed to be acceptable for offsite
disposal or regeneration.
If the radon levels in the NHOU treatment system influent are high, consideration of these
complications might bias the technology selection to those that do not accumulate radon,
such as air stripping with catalytic offgas treatment.
C1-6
RDD/091890010 (NLH4093.DOC)
Attachment C2
Ex Situ Chromium Treatment
Calculation Details
ATTACHMENT C2
RDD/091890010 (NLH4093.DOC)
C2-1
For the purposes of estimating anion ion exchange column adsorbers, it is assumed that two
anion ion exchange columns will operate in series to achieve the specified effluent
requirements. Higher flow systems may also use additional parallel columns for higher
flow capacity. This is a conservative assumption and may be re-evaluated pending further
demonstration-scale testing results.
Finally, there is significant concern regarding the potential ability for the weak base resin to
release partially oxidized organic material due to an oxidation reduction reaction with the
hexavalent chromium. Strong base resin does not appear to experience the same
degradation reaction. However, because the resin holding capacity is much less, it is
rationalized that if weak base resin is not cost-effective compared with ferrous iron
treatment, strong base resin treatment will be even less cost-effective.
C2.1.3 pH Adjustment
Work at the City of Glendale indicates that the loading capacity of Duolite A7 anion ion
exchange resin is pH-dependent. At the native pH of 6.8, the resin had a capacity to treat
about 2,500 bed volumes (based on 35 g/L influent). However, at a pH of 6.0, the capacity
of Duolite A7 increased to 25,000 bed volumes. Thus, the system design assumes a pH
reduction system (acid addition) to reduce the inlet pH value to approximately 6.0 and a pH
increase system (caustic addition) after ion exchange and air stripping treatment to restore
the pH to normal groundwater values or as desired for potable use.
The systems developed for the NHOU focused feasibility study incorporate these guidelines
where applicable.
C2-2
RDD/091890010 (NLH4093.DOC)
C2.3.1 Pretreatment
No pretreatment is assumed. In instances where chromium and volatile organic carbon
treatment systems are at the same facility, it is assumed that chromium treatment is
conducted first.
(1)
The rate of hexavalent chromium reduction using ferrous ions can be predicted using
Equation 2 (Fendorf and Li, 1996):
d[Cr(VI)] / dt = -kCr[Fe2+]0.6[Cr(VI)]1.0
(2)
Where:
t
k
[Fe2+]
[Cr(VI)]
=
=
=
=
time (minutes)
56.3 millimole, 0.6 minute 1 liter 0.6
iron concentration, millimole per liter (constant)
chromium (VI), millimole per liter
Dissolved oxygen competes with the hexavalent chromium for oxidizing ferrous iron to
ferric iron. The ferrous iron is oxidized by dissolved oxygen as shown in Equation 3:
4FeCl2 + O2 + 10H2O -------> 4Fe(OH)3 + 8HCl
(3)
The rate of ferrous iron oxidation by dissolved oxygen can be predicted using Equation 4
(Sung and Morgan, 1980):
d[Fe2+]/dt = -k[OH-]2pO2[Fe(II)]
RDD/091890010 (NLH4093.DOC)
(4)
C2-3
Where:
k
[Fe2+]
[Cr(VI)]
[OH-]
pO2
=
=
=
=
=
8x1013L2/(atm-min-mole2)
iron concentration, millimole/L (constant)
chromium (VI), millimole/L
[10(pH-14)]
0.21 atm at 8.3 milligrams per liter O2 (fresh water)
C2-4
RDD/091890010 (NLH4093.DOC)
Attachment C3
1,4-Dioxane Treatment Details
ATTACHMENT C3
Ozone/Peroxide
Fentons reagent
Notes:
UV =
THF =
ultraviolet
tetrahydrofuran
Advanced oxidation processes (AOP), such as ozone/peroxide and ultraviolet (UV) light/
peroxide (UV/Ox) treatment processes, are commercially viable. Biological methods have
also been evaluated at bench-scale, but results have been inconsistent, and full-scale
commercially viable biological treatment processes have not been identified.
RDD/091890010 (NLH4093.DOC)
C3-1
C3-2
RDD/091890010 (NLH4093.DOC)
Attachment C4
1,4-Dioxane Treatment Details
ATTACHMENT C4
VOC Loading
The influent VOC concentrations into the LPGAC adsorbers are estimated based on the
virtually complete removal of TCE and PCE by the upstream air strippers. CH2M HILL
assumes that the air stripper will be designed to reduce concentrations of both TCE and PCE
to less than 60 percent of the their MCLs. The LPGAC adsorbers will function strictly as a
polisher to guard against unexpected stripper failure. Therefore, for estimating purposes,
the LPGAC adsorbers are assumed to have a bed service life of 1 year.
RDD/091890010 (NLH4093.DOC)
C4-1
The oxygen demand of organic loading to the LPGAC BAR is well below the inlet
dissolved oxygen concentration
Works Cited
Bouwer, E.J., Goel, S., Hozalski, R.M. Removal of Natural Organic Matter in Biofilters,
AWWA Research Foundation, Denver CO, 1995
Carlson, K.H., Amy, G.L., Blais, G., MacMillan, S., 1996. The Formation of Filter Removable
BOM During Ozonation, Proceedings of the 1996 Fourth International BOM Conference,
Waterloo, ON
Price, M.L., Ozone and Biological Treatment for DBP Control and Biological Stability,
AWWA Research Foundation, Denver CO, 1994
C4-2
RDD/091890010 (NLH4093.DOC)
Attachment C5
Hand Calculations and Computer Modeling
Results
ATTACHMENT C5
gal
min
day cf
365
2000
1440
min
day
yr 7.48 gal
Resin Use
cfH 2 O 35 ppb
80,000
= 6,700cf Re sin/ yr
Q = 600 gpm
Usage = 80,000 B.V.
600 gpm
cf Resin
6,700
2000 gpm
yr
Resin Use
= 2,010 cf Resin/yr
RDD/091890010 (NLH4093.DOC)
C5-1
Therefore,
At time = 2 minutes,
[Cr]t = 200 g/L * exp (-56.3 millimole-0.6 minute-1 L0.6 * 0.18 millimol/L)0.6 * 2 minutes)
[Cr]t < 1 g/L at time = 2 minutes
VReduct Tank =
C5-2
RDD/091890010 (NLH4093.DOC)
0.18 atm
In backmix reactors, the reaction rate equation takes the form of,
C1 = C0/(1 + k1V/Q)
where,
C1 = Concentration of Fe2+ discharged from the backmix reactor
C0 = Concentration of Fe2+ influent to the backmix reactor
k1 = k[OH-]2pO2
V = reactor volume, gallons
Q = flow rate through the reactor, gallons/minute
At pH = 7.5, pO2 = 0.21
k1 = k[OH-]2pO2
= 1.68 min-1
RDD/091890010 (NLH4093.DOC)
C5-3
10 ppm
VOx Tank =
NOTE: Actual minimum tank volume will depend heavily on pH during oxidation step.
C5-4
RDD/091890010 (NLH4093.DOC)
10
= 0.75
1.8
O = 6 .1
UV Dose = EE
Ci
log10
O
Cf
10
= 6.1 log 10
1 .8
= 4.5 kWh 1000 gal
@ 300 gpm
4.5 kWh
gal min
300
P =
60
min
hr
1,000 gal
= 81 kW
on equal performance.
Power for North Hollywood Operable Unit Focused Feasibility Study based on Calgons
method 650 kW
RDD/091890010 (NLH4093.DOC)
C5-5
2872kW
= 9.4 kW
Add 50 percent Safety Factor
P = 1.5 (75kW )
= 14 kW
C5-6
Use 15 kW
RDD/091890010 (NLH4093.DOC)
System Data:
~~~~~~~~~~~~
Enter the total flow for all wells.........................
900
gpm
900
4,000
--
gpm
acfm @
62
RDD/091890012 (NLH2360.xls)
1 of 5
1/Cap.
(#C/#VOC)
~~~~~~~
1.3E+01
1.2E+01
2.9E+01
N/A
1.4E+02
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1.1E+02
N/A
N/A
N/A
N/A
N/A
N/A
Usage
(#C/day)
~~~~~~~
1.6E+00
9.3E+00
3.2E-01
0.0E+00
1.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
2.5E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
0.0E+00
~~~~~~~
1.5E+01
SENSITIVITY
SENSITIVITY
ANALYSIS
ANALYSIS
CHECK
I
(NOTE 3)
I
{~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~}
~~~~~~~~~~~~~~~} {~~~~~~~~~~~~~~~~~~~}
~~~~~~~~~}
Max Liq. Ratio:
Ratio:
Calculation:
Ph. Conc. Max Liq. Max Liq.
Max VaporMax Vapor
Allowed Ph. Conc Conc.
Conc
Conc.
before
Allowed at one well for
using
Lead
Controling --------if others
Isotherm Existing
Contaminant Design
Actual
remain
Data
A/W Ratio
I.D.
(ppm)
Influent
Constant
(ug/l)
(ug/l)
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
not lead
0.1001
8.7
24
500
2.8993
not lead
0.07
1
1
400
2.0275
not lead
0.0752
75.2
224
470
2.1781
not lead
0
0
0
400
#DIV/0!
LEAD
0.0159
22.7
66
300
0.4605
not lead
0
0
0
200
0
not lead
0
0
0
40
0
not lead
0
0
0
300
#DIV/0!
not lead
0
0
0
510
#DIV/0!
not lead
0
0
0
180
#DIV/0!
not lead
0
0
0
70
#DIV/0!
not lead
0
0
0
70
#DIV/0!
not lead
0
0
0
260
#DIV/0!
not lead
0
0
0
50
#DIV/0!
not lead
0
0
0
320
#DIV/0!
not lead
0
0
0
190
#DIV/0!
not lead
0
0
0
220
#DIV/0!
not lead
0
0
0
770
#DIV/0!
not lead
0
0
0
35
#DIV/0!
not lead
0.0151
7.2
20
35
0.4374
not lead
0
0
0
360
#DIV/0!
not lead
0
0
0
N/A
#DIV/0!
not lead
0
0
0
450
#DIV/0!
not lead
0
0
0
340
#DIV/0!
not lead
0
0
0
410
#DIV/0!
not lead
0
0
0
40
#DIV/0!
NOTE 1: The data for the isotherms are based primarily on Calgon's BPL and American Norit RB. Graphic
isotherms were provided. The equations for each were derived. The resulting carbon use rates for Calgon BPL
and Norit RB at concentrations typical of air stripper off-gas were compared. The more conservative value was used.
NOTE 2: All isotherm values are based on a temperature of 84 F and 0% humidity. Adsorption capacity tends to
increase as temperature decreases and decreases with increasing relative humidity. The calculations below
provide a crude estimate to compensate for your actual temperature and relative humidity.
WARNING:
The temperature and humidity correction factors provided herein are crude and subject to error.
NOTE 3: A Sensivity Analysis of the carbon usage calculation is provided. Two sections are provided. The Carbon Usage Sensitivity Analysis
and the Check of the Maximum Concentration that the existing data is valid for.
RDD/091890012 (NLH2360.xls)
2 of 5
1.058
0.69
RDD/091890012 (NLH2360.xls)
22
lbs C/day/stripper
22
lbs/day
8.0E+03
lbs/yr
3 of 5
Mechanical Design:
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
COMMENT:
The following section is used to develop mechanical design features for a carbon adsorber system.
Typically, carbon adsorbers are NOT custom designed. In most cases, carbon adsorbers are
off-the-shelf units. Most off-the-shelf units are based on the poundage of carbon which they hold.
Typical poundages for drum size units are 150 lbs each, medium tank size units holding 300 lbs each, and
for vessel size units poundages of 1,500 lbs, 2,000 lbs, 5,000 lbs, 10,000 lbs, and 13,600 lbs are
representative of available systems (based on Systems by Carbonair).
Typical Design Parameters
~~~~~~~~~~~~~~~~~~~
Design Values:
Minimum Flux Rate
0.8 ft/sec
Typical Flux Rate
1.0 ft/sec
Maximum Flux Rate
1.4 ft/sec
Activated Carbon bed depth should be at least equal to 1/3 the diameter of the bed or 2.0 ft (except drums
size units)., whichever is more.
Unit(s).
The table below will summarize designs for off-the-shelf adsorbers sizes treating
Type of Unit
Drum
Tank
Vessel
Vessel
Vessel
Vessel
Vessel
Pounds
of C
(lbs)
150
300
1,500
2,000
5,000
10,000
13,600
Surface
Area
(sq.ft.)
2.7
4
12
20
48
70
120
Surfacial
Velocity
(ft/sec)
Unit Too Small
Unit Too Small
Unit Too Small
Unit Too Small
1.4
1
Unit Too Large
RDD/091890012 (NLH2360.xls)
Bed
Depth
(inches)
22
30
50
40
42
57
45
4000 cfm.
Bed Life
before
Breakthrough
(days)
6.8
13.6
68.2
90.9
227.3
454.5
618.2
4 of 5
Custom Designs
~~~~~~~~~~~~~
Enter Design Gas Velocity.............
1
Note: Typical VGAC Velocities are .8 to 1.4 ft/sec
ft/sec
66.7
--
66.7
9.2
10
sq.ft.
ft
ft
78.5
0.85
4
sq.ft.
ft/sec
ft
314
30
RDD/091890012 (NLH2360.xls)
5 of 5