VENTILATION
Page 2 of 3
MALE TOILET
4.5 x 3.0 x 2.7 m = 36.45 m3
36.45 m3
291.6 m3/h.
Divide by 3600
= 0.081 m3/s.
8 AC/h
0.081 / 4 =
0.02025 m2.
( 0.02025 )0.5
0.142 m x 0.142 m
The flexible ductwork may be sized using the same technique as above.
Volume flow rate through each flexible
=
0.081 m3/s / 2
=
0.041 m3/s.
A simple method of duct sizing would be: Duct area = volume flow rate / air velocity.
An appropriate air velocity for a flexible in this situation is 4 m/s
Therefore duct area
Cross sectional area
=
=
0.041 / 4 =
. d2 / 4
0.01025 m2.
d
=
( 4 . CSA / )0.5
http://www.arca53.dsl.pipex.com/index_files/vent8.htm
06-09-2016
VENTILATION
Page 3 of 3
( 4 x 0.01025 / )0.5
0.114 m
114 mm diameter.
Branch
Side Of Duct
The Female Toilet may be sized using the same method but since the physical dimensions are so close to the Male Toilet then the
same duct sizes can be used, this also standardizes the complete ventilation system so that the two fans are also identical.
Fans
To choose suitable fans for this example the duct pressure drop and fittings pressure drop would be calculated.
If the total pressure drop is assumed to be 200 Pa and the flow rate is 0.081 m3/s (81 litres/s) then a suitable catalogue can be used
to pick the fan.
See http://www.flaktwoods.com. Go to Other Fans section.
A tube fan or boxed fan can be used for this project.