Zapi 80v
Zapi 80v
Zapi 80v
1
2
Introduction ....................................................................................................
Specification ..................................................................................................
2.1 AC-3 Technical specifications ................................................................
2.2 AC-4 Technical Specifications ...............................................................
2.3 Block Diagram .......................................................................................
2.4 Control unit .............................................................................................
2.4.a Microswitches ...............................................................................
2.4.b Accelerator unit .............................................................................
2.4.c Other analog control unit ................................................................
2.4.d Speed feedback ............................................................................
3
3
3
3
4
4
4
4
5
5
2.5
Protection features
2.6
2.7
2.8
2.9
.......................................................................... 6
. .............................................. 8
.................................. 9
Installation .................................................................................................... 11
4.1 Connection cables ............................................................................... 11
4.2 Contactors ........................................................................................... 11
4.3 Fuses ................................................................................................... 11
4.4 Description of connectors - Traction configuration ............................... 12
4.4.a Amp Saab connector ................................................................... 12
4.4.b Molex Minifit connectors .............................................................. 14
4.5 Description of connectors - Pump configuration .................................... 16
4.5.a Amp Saab connector ................................................................... 16
4.5.b Molex Minifit connectors .............................................................. 18
4.6 Encoder installation .............................................................................. 20
4.7 Description of power connections......................................................... 21
4.8 AC3 Mechanical drawing ..................................................................... 22
4.9 AC4 Mechanical Drawing ..................................................................... 23
4.10 Connection drawing - Traction configuration ......................................... 24
4.10.a Amp Saab connector ................................................................ 24
4.10.b Molex Minifit connectors ........................................................... 25
4.11 Connection drawing - Pump configuration ............................................ 26
4.11.a Amp Saab connector ................................................................ 26
4.11.b Molex Minifit connectors ........................................................... 27
4.12 Connection drawing - Combi configuration ........................................... 28
4.12.a Amp Saab connector ................................................................ 28
4.12.b Molex Minifit connectors ........................................................... 29
Page 1
The informations included into the marked paragraphs by this symbol are
essential for the safety.
SIGNATURES TABLE
COMPANY DEPT. SERVICES
ENGINEERING SECTION EXECUTIVE
EXPORT MANAGER
Publications N: ADWZP0AD
Edition: January 2003
Page 2
MANAGEMENT EXECUTIVE
1 INTRODUCTION
Within the ZAPIMOS family, the AC3 inverter is the model suitable for control of 712 KW
motors; the AC4 inverter is the model suitable for control of 12kW to 20kW motors. They
have been expressly designed for battery electric traction.
They are fit for electric truck, electric cars, tractors and buses.
2 SPECIFICATION
2.1 AC-3 TECHNICAL SPECIFICATIONS
Inverter for AC asynchronous 3-phase motors
Regenerative braking functions
Can-bus interface
Digital control based upon a microcontroller
Voltage: ......................................................................................... 36 - 48 - 72 - 80V
Maximum current (36V,48V): ......................................................... 600A (RMS) for 3'
Maximum current (72V,80V): ......................................................... 450A (RMS) for 3'
Booster (all version) .............................. 10% of maximum current for some seconds;
Operating frequency: ..........................................................................................8kHz
External temperature range: ................................................................. -30C 40C
Maximum inverter temperature (at full power): .................................................... 75C
2.2 AC-4 TECHNICAL SPECIFICATIONS
Inverter for AC asynchronous 3-phase motors
Regenerative braking functions
Can-bus interface
Digital control based upon a microcontroller
Voltage: ................................................................................................ 48 - 72 - 80V
Maximum current (48V): ................................................................ 700A (RMS) for 3'
Maximum current (72V,80V): ......................................................... 550A (RMS) for 3'
Booster (all version) .............................. 10% of maximum current for some seconds;
Operating frequency: ..........................................................................................8kHz
External temperature range: ................................................................. -30C 40C
Maximum inverter temperature (at full power): .................................................... 75C
Page 3
Page 4
The Procedure for automatic potentiometer signal acquisition is carried out using the
Console. This enables adjustment of the minimum and maximum useful signal level
(PROGRAM VACC function), in either direction. This function is unique when it is necessary to compensate for asymmetry with the mechanical elements associated with the
potentiometer, especially relating to the minimum level.
The sequence of procedure is described in the programming console manual.
The two graphs show the output voltage from a non-calibrated potentiometer with
respect to the mechanical zero of the control lever. MI and MA indicate the point where
the direction switches close. 0 represents the mechanical zero of the rotation.
The Left Hand graph shows the relationship of the motor voltage without signal acquisition
being made. The Right Hand Graph shows the same relationship after signal acquisition
of the potentiometer.
2.4.c Other analog control unit
1) Input A13 (Saab connector version), A8 (Molex Minifit version) is an analog input,
whose typical application is for proportional braking. It should be in a 3 wire configuration. Potentiometer value should be in the 0.5-10Kohm range. Generally, the load
should be in the 1.5mA to 30 mA range.
The CPOTB (A13, A8) signal range is from 0 to 10V.
2) Connections A3 (Saab), B6 (Minifit) (PTHERM) and A4 (Saab), B12 (minifit)
(NTHERM) are used for a motor thermal sensor. It can be digital (on/off sensor, normally closed) or analog. See also chapter 4.4 for more explanation.
2.4.d Speed feedback
The motor control is based upon the motor speed feedback. The speed transducer is an
incremental encoder, with two phases shifted at 90. The encoder can be of different types
:
- power supply:
+5V or +12V
-
electric output:
For more details about encoder installation see also chapter 3.6.
Page 5
Page 6
Page 7
2.7 DIAGNOSIS
The microprocessor continually monitors the inverter and carries out a diagnostic procedure on the main functions. The diagnosis is made in 4 points
1) Diagnosis on key switch closing that checks: watchdog circuit, current sensor, capacitor charging, phase's voltages, contactor drives, can-bus interface, if the switch sequence for operation is correct and if the output of accelerator unit is correct.
2) Standby diagnosis at rest that checks: watchdog circuit, phase's voltages, contactor
driver, current sensor, can-bus interface.
3) Diagnosis during operation that checks: watchdog circuits, contactor driver, current
sensors, can-bus interface.
4) Continuos diagnosis that check: temperature of the inverter, motor temperature.
Diagnosis is provided in two ways. The digital console can be used, which gives a detailed
information about the failure; the failure code is also sent on the Can-Bus.
2.8 THERMAL CONSIDERATION
- The heat generated by the power block must be dissipated. For this to be possible,
the compartment must be ventilated and the heat sink materials ample.
- The heat sink material and system should be sized on the performance requirement of
the machine. Abnormal ambient air temperatures should be considered. In situations
where either ventilation is poor, or heat exchange is difficult, forced air ventilation should
be used.
- The thermal energy dissipated by the power block module varies and is dependent on
the current drawn and the duty cycle.
2.9 GENERAL INSTRUCTIONS AND PRECAUTIONS
- Never connect SCR low frequency chopper with ASYNCHRONOUS INVERTER because the ASYNCHRONOUS filter capacitors alter the SCR choppers' work. If it is
necessary to use two or more control units (traction + lift. for ex.), they must belong to the
ZAPIMOS family.
- Do not connect the inverter to a battery with a nominal value different from the value
indicated on the chopper plate. If the battery value is greater, the MOS may fail; if it is
lower, the control unit does not "power up".
- During battery charge, disconnect ASYNCHRONOUS from the battery.
- Supply the ASYNCHRONOUS only with battery for traction; do not use a power supply.
- When the chopper is installed, make tests with the wheels raised from the ground, in
order to avoid dangerous situations due to connection errors.
- After the chopper is switched off (key off), the filter capacitor remains charged for some
minutes; if you need to work on the inverter, discharge them using a
10W 100W resistance connected from the +Batt to the -Batt.
Page 8
- An intrinsic protection is present inside the logic when the voltage on the battery power
connection overtakes 40% more than the battery nominal voltage or if the key is
switched off before the battery power line is disconnected.
Page 9
Page 10
4 INSTALLATION
Install the chopper with the base-plate on a flat metallic surface that is clean and unpainted.
Apply a light layer of thermo-conductive grease between the two surfaces to permit better
heat dissipation.
Ensure that the wiring of the cable terminals and connectors is carried out correctly.
Fit transient suppression devices to the horn, solenoid valves, and contactors not connected to the chopper such as those for activating the pump motor or steering motor.
4.1 CONNECTION CABLES
For the auxiliary circuits, use cables of 0.5mm section.
For power connections to the motor and to the battery, use cables having section in the
3550 mm range (as a minimum).
For the optimum inverter performance, the cables to the battery should be run side by side
and be as short as possible.
4.2 CONTACTORS
The main contactor must be installed. Depending on the position of a jumper installed in
the logic board:
- the output which drives the main contactor coil is on/off (the coil is driven with the full
battery voltage).
-
the output which drives the main contactor coil is switched at high frequency (1 KHz)
with a duty cicle of 70%; this feature is useful to decrease the power dissipation of the
contactor coil.
4.3 FUSES
Page 11
A1
PPOT
A2
NPOTB
-Batt.
A3
PTHERM
A4
NTHERM
-Batt.
A5
-BATT
Battery negative.
A6
NLC
A7
NBRAKE
A8
PLC
A9
CM
A10 KEY
A11 CPOT
A12 NPOT
A13 CPOTB
A14 CAN-H
A15 CAN-L
A16 FORW
A17 BW
Backward direction request input. Must be connected to the backward direction microswitch, active high.
Page 12
A18 BACK. FORW Inching function, forward direction input. Must be connected to the
inching forward switch. Active high.
A19 BACK. BACK Inching function, backward direction input. Must be connected to the
inching backward switch. Active high.
A20 ENCODER
A21 ENCODER
A22 ENCODER
A23 ENCODER
A24 MODE
This input allows the customer to select the software for traction or
lifting application.
Configuration:
MODE: Open (not connected)
Traction inverter
MODE: Close (connected with A5)
Pump inverter
A25 SAFETY
A26 PB
A28 SR/HB
A29 SEAT
Page 13
A1
CPOT
A2
PPOT
A3
NPOT
A4
CM
A5
FORW
A6
BW
Backward direction request input. Must be connected to the backward direction microswitch, active high.
A7
PB
A8
CPOTB
A9
PPOTB
A10 NPOTB
-Batt.
A11 -BATT
-Batt.
A12 BACK. FORW Inching function, forward direction input. Must be connected to the
inching forward switch. Active high.
A13 BACK. BACK Inching function, backward direction input. Must be connected to the
inching backward switch. Active high.
A14 EX. HYDRO
B1
KEY
B2
PLC
B3
PBRAKE
B4
SEAT
Page 14
B5
SAFETY
B6
PTHERM
B7
CM
B8
NLC
B9
NBRAKE
B10 SR/HB
B11 GND
-Batt.
B12 NTHERM
-Batt.
C1
CAN-L
C2
CAN-L-OUT
C3
CAN-H
C4
CAN-H-OUT
D1
-BATT
-Batt.
D2
MODE
This input allows the customer to select the software for traction or
lifting application.
Configuration:
MODE: Open (not connected)
Traction inverter
MODE: Close (connected with A5)
Pump inverter
E1E6
F1
PCLRXD
F2
NCLRXD
F3
PCLTXD
F4
NCLTXD
F5
GND
F6
+12
F7
FLASH
F8
FLASH
Page 15
A1
PPOT
A2
NPOTB
-Batt.
A3
PTHERM
A4
NTHERM
-Batt.
A5
-BATT
Battery negative.
A6
NAUX
This output can be used for drive the main contactor coil (single
pump configuration) or to drive an auxiliary load (combi configuration)
A7
NBRAKE
Output for driving an hydraulic steering contactor coil; drives the load
to -Batt maximum current : 3A.
A8
PAUX
A9
CM
A10 KEY
A11 CPOT
A12 NPOT
A14 CAN-H
A15 CAN-L
A16 LIFT ENABLE Input for potentiometer lifting enable input; it is active HIGH.
A17 1st SPEED
A19 SR
Page 16
A20 ENCODER
A21 ENCODER
A22 ENCODER
A23 ENCODER
A24 MODE
This input allows the customer to select the software for traction or
lifting application.
Configuration:
MODE: Open (not connected)
Traction inverter
MODE: Close (connected with A5)
Pump inverter
A25 SAFETY
Page 17
A1
CPOT
A2
PPOT
A3
NPOT
A4
CM
A5
LIFT ENABLE Input for potentiometer lifting enable input; it is active HIGH.
A6
1st SPEED
A7
3rd SPEED
A8
AN. IN.
A9
PPOT
A10 -BATT
-Batt.
A11 -BATT
-Batt.
A13 SR
B1
KEY
B2
PAUX
B3
PHYDRO
B4
4th SPEED
B5
SAFETY
B6
PTHERM
B7
CM
Page 18
B8
NAUX
This output can be used for drive the main contactor coil (single
pump configuration) or to drive an auxiliary load (combi configuration)
B9
NHYDRO
Output for driving an hydraulic steering contactor; drives the load to Batt. Maximum current: 3A.
B11 GND
-Batt.
B12 NTHERM
-Batt.
C1
CAN-L
C2
CAN-L-OUT
C3
CAN-H
C4
CAN-H-OUT
D1
-BATT
-Batt.
D2
MODE
This input allows the customer to select the software for traction or
lifting application.
Configuration:
MODE: Open (not connected)
Traction inverter
MODE: Close (connected with A5)
Pump inverter
E1E6
F1
PCLRXD
F2
NCLRXD
F3
PCLTXD
F4
NCLTXD
F5
GND
F6
+12
F7
FLASH
F8
FLASH
Page 19
E2
A23 GND
E3
A21 A
phase A of encoder.
E4
E5
A22 B
phase B of encoder.
E6
A
B
2) Connection of encoder with differential outputs; +5V power supply (Minifit connectors).
3) Connection of encoder with open collector output; +5V power supply (Minifit connectors)..
4) Connection of encoder with open collector output: +12V power supply (Minifit connectors).
VERY IMPORTANT
It is necessary to specify in the order the type of encoder used, in terms of power
supply, electronic output and n of pulses for revolution, because the logic unit
must be set in the correct way by Zapi.
Page 20
-BATT
Negative of the battery.
+BATT
Positive of the battery.
U; V; W Connection bars of the three motor phases; follow this sequence and the indication on the motor.
Page 21
Page 22
Page 23
Page 24
Page 25
Page 26
Page 27
Page 28
Page 29
Digital consoles used to communicate with AC inverter controllers must be fitted with
EPROM CK ULTRA, minimum "Release Number 3.02".
Page 30
Page 31
Page 32
2 BATTERY CHECK
- ON:
the battery discharge level check is carried out; when the battery level reaches 10%, an alarm is signalled and the maximum current is reduced to
the half of the programmed value.
- OFF:
signalled.
3 CUTBACK MODE
- PRESENT:
speed input.
- ABSENT:
brake input.
4 HYDRO KEY ON
- ON / OFF:
if this option is programmed ON the traction inverter manages
an hydraulic steering function when the "key" is switched ON (only if the "aux output
#1" option is programmed as "hydro contactor" or as "exclusive hydro").
5 STOP ON RAMP
- ON:
the stop on ramp feature (truck electrically hold on a ramp) is
managed for a time established by "auxiliary time" parameter. After this time, the
behavior depends on the "aux output #1" option programmation (see also the following table).
- OFF:
6 AUX OUTPUT #1
- BRAKE:
output B9 (Minifit), A7 (Amp Saab) drives an electromagnetic
brake coil (see also the table below).
- HYDRO CONT.: the inverter manages an hydraulic steering function when the direction input or brake pedal input are active or a movement of the truck is detected.
- EX. HYDRO:
the inverter manages an hydraulic steering function when the
exclusive hydro input is active.
7 PEDAL BRAKING
- ANALOG:
the mechanical brake pedal has a switch and a potentiometer
installed. When the accelerator is released and the pedal brake is pushed the inverter performs an electrical braking whose intensity is proportional to the brake
Page 33
SUBMENU "ADJUSTEMENT"
1 SET POT BRK MIN:
records the minimum value of braking pedal potentiometer
when the braking pedal switch is closed; the procedure is similar to the "Program
Vacc" function (see chapter 5.4). This procedure must be carried out only if the
"Pedal braking" option is programmed as "Analog".
2 SET POT BRK MAX: records the maximum value of braking pedal potentiometer
when the braking pedal is fully pressed; the procedure is similar to the "Program
Vacc" function (see chapter 5.4). This procedure must be carried out only if the
"Pedal braking" option is programmed as "Analog".
3 SET BATTERY TYPE:
4 ADJUST BATTERY:
ler.
5 ADJUSTMENT #04:
this parameter determines the motor temperature level at which
the Motor temperature alarm is signalled. The range is from 70C to 160C with
10C steps. This parameter must be adjusted only if the Set temperature (menu
Set option) parameter is programmed Analog.
6 THROTTLE 0 ZONE:
also curve below).
7 THROTTLE X POINT:
input curve.
8 THROTTLE Y POINT:
input curve.
Page 34
VACC MIN and VACC MAX are values programmable by the "Program Vacc" function.
9 ADJUSTMENT #01:
10ADJUSTMENT #02:
11 LOAD HM FROM MDI: for an explanation of this point see the MDI instrument handbook
12 CHECK UP DONE:
book
13 CHECK UP TYPE:
book
Page 35
AUX
OUTPUT
BRAKE
BRAKE
HYDRO
CONT.
HYDRO
CONT.
EXCL.
HYDRO
EXCL.
HYDRO
Page 36
STOP
ON
RAMP
A7 (Saab), B9 (Minifit)
OUTPUT
BEHAVIUR ON A SLOPE
ON
OFF
ON
OFF
ON
OFF
5.4.b Pump
Using the config menu of the programming console, the user can configure the following functions.
SUBMENU "SET OPTIONS"
1 HOUR COUNTER
- RUNNING:
- KEY ON:
2 BATTERY CHECK
- ON:
the battery discharge level check is carried out; when the battery level reaches 10%, an alarm is signalled and the maximum current is reduced to
the half of the programmed value.
- OFF:
signalled.
Very important:
In the combi system (pump + traction), the battery discharge calculation for the complete
system is carried out by the traction inverter; the information about the pump inverter consumption is sent on the can-bus line from the pump inverter to the traction inverter. So the
correct programmation for the "Battery check" option is :
traction inverter:
ON
pump inverter:
OFF
3 SET TEMPERATURE
- DIGITAL:
a digital (ON/OFF) motor thermal sensor is connected to B6
(Minifit), A3 (Amp Saab) input.
- ANALOG:
an analog motor thermal sensor is connected to B6 (Minifit), A3
(Amp Saab) (the curve can be customized on a customer request).
- NONE:
SUBMENU "ADJUSTEMENT"
1 SET BATTERY TYPE:
2 ADJUST BATTERY:
ler.
3 ADJUSTMENT #04:
this parameter determines the motor temperature level at which
the Motor temperature alarm is signalled. The range is from 70C to 160C with
10C steps. This parameter must be adjusted only if the Set temperature (menu
Set option) parameter is programmed Analog.
4 THROTTLE 0 ZONE:
also curve below).
5 THROTTLE X POINT:
input curve.
6 THROTTLE Y POINT:
input curve.
VACC MIN and VACC MAX are values programmable by the "Program Vacc" function.
7 ADJUSTMENT #01:
8 ADJUSTMENT #02:
Page 38
Page 39
Page 40
Flow chart showing how to use the SET BATTERY TYPE adjustment
1) Opening Zapi Menu
2) Press Top Left & Right Buttons to enter
CONFIG Menu.
3) The Display will show: SET MODEL
4) Press ROLL UP button until
ADJUSTMENTS. menu appears.
5) ADJUSTMENTS appears on the display.
6) Press ENTER to go into the ADJUSTMENTS
Menu.
7) The display will show: SET BATTERY TYPE.
8) Press SET UP to choose nominal value of
the battery.
9) New battery value appears.
10) Press OUT.
11) Confirmation request appears.
12) Press ENTER to accept the changes, or press
OUT if you do not accept the changes.
13) Press OUT. Display now shows the Opening
Zapi Menu.
Page 41
Flow chart showing how to carry out ADJUSTMENT BATTERY operation by console.
1) Opening Zapi Menu
2) Press Top Left & Right Buttons to enter
CONFIG Menu.
3) The Display will show: SET MODEL
4) Press ROLL UP button until
ADJUSTMENT Menu appears.
5) ADJUSTMENTS appears on the
display.
6) Press ENTER to go into the
ADJUSTMENTS Menu.
7) The display will show the first
OPTION.
8) Press ROLL UP or ROLL DOWN button
until desired OPTION appears
9) ADJUST BATTERY appears.
10) Press SET UP or SET DOWN button
in order to increase or decrease
respectively. Set the value read
by an external meter.
11) Battery value appears on the display.
12) Press OUT to exit the Menu.
13) Confirmation request appears.
14) Press ENTER to accept the changes,
or press OUT if you do not accept the
changes.
15) ADJUSTMENTS Menu appears.
16) Press OUT. Display now show the Opening Zapi Menu.
Page 42
ACC DELAY:
RELEASE BRAKING:
INVERSION BRAKING:
PEDAL BRAKING:
BRAKE CUTBACK:
CUTBACK SPEED:
10 FREQUENCY CREEP:
11 MAXIMUM CURRENT:
12 BACKING SPEED:
13 BACKING TIME:
14 AUXILIARY TIME:
Page 43
The following table shows the different values at which the parameters can be set.
PARAMETER
PROGRAMMED LEVEL
UNIT
Sec.
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
Sec.
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
Sec.
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
Sec.
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
Sec.
8.9
8.3
7.7
7.1
6.6
6.0
5.5
4.9
4.4
3.8
Sec.
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
MAX SPEED FW
Hz
65
80
95
110
125
140
155
170
185
200
MAX SPEED BW
Hz
65
80
95
110
125
140
155
170
185
200
CUTBACK SPEED
%Max Sp
10
20
30
40
50
60
70
80
90
100
Hz
0.3
0.6
0.9
1.2
1.5
1.8
2.1
2.4
2.7
3.0
% IMAX
47
53
58
64
70
76
82
88
94
100
BACKING SPEED
Hz
10
12
14
16
18
BACKING TIME
Sec.
0.2
0.5
1.0
1.4
1.8
2.3
2.7
3.1
3.6
4.0
AUXILIARY TIME
Sec.
1.5
2.0
2.5
3.0
3.5
4.0
4.5
FREQUENCY CREEP
MAXIMUM CURRENT
After changing a parameter, press ENTER to confirm data when requested by the message on the console. Parameters modified and optimized on one unit can be stored by the
console (SAVE) and then released (RESTORE) on another chopper, thus allowing fast and
standardized settings (see console manual for details).
(*) The acceleration time shown is the time from 0 Hz to 100 Hz. This is the ideal ramp
calculated by the software; the real ramp could change as a function of motor control
parameter setting and, obviously, as a function of the load.
(**) The braking feature is based upon deceleration ramps. The value shown in the table
is the time to decrease the speed from 100 Hz to 0 Hz. This is the ideal ramps calculated by the software; the real ramp could change as a function of motor control parameter setting and, obviously, as a function of the load.
Page 44
deceleration ramp.
MAX SPEED UP
MIN SPEED UP
10 MAXIMUM CURRENT:
11 AUXILIARY TIME:
The following table shows the different values at which the parameters can be set.
PARAMETER
PROGRAMMED LEVEL
UNIT
Sec.
0.5
0.7
1.0
1.4
1.9
2.5
3.2
4.0
4.8
5.5
Sec.
0.5
0.7
1.0
1.4
1.9
2.5
3.2
4.0
4.8
5.5
MAX SPEED UP
Hz
65
80
95
110
125
140
155
170
185
200
MIN SPEED UP
Hz
Hz
% IMAX
47
53
58
64
70
76
82
88
94
100
Sec
0.2
0.4
0.8
1.0
1.5
2.0
3.0
4.0
5.0
MAX CURRENT
AUXILIARY TIME
(*)
The acceleration time shown is the time from 0 Hz to 100 Hz (maximum selectable
speed). This is the ideal ramp calculated by the software; the real ramp could change
as a function of motor control parameter setting and, obviously, as a function of the
load.
(**)
The deceleration time shown in the table is the time from 100 Hz to 0 Hz. This is the
ideal ramp calculated by the software; the real ramp could change as a function of
motor control parameter setting and, obviously, as a function of the load.
Page 45
After changing a parameter, press ENTER to confirm data when requested by the message on the console. Parameters modified and optimized on one unit can be stored by the
console (SAVE) and then released (RESTORE) on another chopper, thus allowing fast and
standardized settings (see console manual for details).
Flow Chart showing how to make Program changes using Digital Console fitted with
Eprom CK ULTRA.
1) Opening Zapi Display.
2) Press ENTER to go into the General
Menu.
3) The Display will show :
4) Press ENTER to go into the
Parameter Change facility.
5) The Display will show the first
parameter.
6) Press either ROLL UP and ROLL DOWN
to display the next parameter.
7) The names of the Parameters appear
on the Display.
8) When the desired Parameter appears, the
Display will show a Level Number that will
be between 0 and 9. Press either PARAM
(Top Right) or SET (Bottom Right)buttons
to change the Level value.
9) The Display will show the New Level.
10) When you are satisfied with the results of
the changes you have made, Press OUT.
11) The Display asks ARE YOU SURE"?
12) Press ENTER to accept the changes, or
press OUT if you do not wish to accept the
changes and wish to make further
modifications to the parameters.
13) The Display will show :
Page 46
PUMP
motor voltage (%)
frequency (Hz)
encoder (Hz)
slip value (Hz)
current rms (A)
temperature (C)
motor temperature (C)
accelerator (V)
lifting switch (ON/OFF)
1st speed switch (ON/OFF)
2nd speed switch (ON/OFF)
3rd speed switch (ON/OFF)
4th speed switch (ON/OFF)
hydro speed req. (ON/OFF)
voltage booster (V)
battery voltage (V)
cos fi
battery current (A)
battery charge (%)
Page 47
Page 48
Page 49
15) SEAT SWITCH: the level of the Seat Microswitch digital entry.
ON / +VB = active entry of closed seat switch.
OFF / GND = non active entry of open seat switch.
16) EXCLUSIVE HYDRO: status of the exclusive hydro switch.
ON / +VB = active entry of closed switch.
OFF / GND = non active entry of open switch.
17) HAND BRAKE: the level of the Handbrake Microswitch.
ON / GND = active entry of Handbrake Switch (open switch).
OFF/ +VB = non active entry of microswitch (closed switch).
18) VOLTAGE BOOSTER: this is the booster of the voltage supplied to the motor in load
condition; it is expressed in a percentage of the full voltage.
19) BATTERY VOLTAGE: level of battery voltage measured at the input to the key switch.
20) COS FI: this is the cos j (real time calculated) of the motor.
21) BATTERY CURRENT: this is the battery current (not measured but calculated).
22) BATTERY CHARGE: the percentage Charge level of the battery.
Page 50
Page 51
15) VOLTAGE BOOSTER: this is the booster of the voltage supplied to the motor in load
condition; it is expressed in a percentage of the full voltage.
16) BATTERY VOLTAGE: level of battery voltage measured at the input to the key switch.
17) COS FI: this is the cos j (real time calculated) of the motor.
18) BATTERY CURRENT: this is the battery current (not measured but calculated).
19) BATTERY CHARGE: the percentage Charge level of the battery.
Flow Chart showing how to use the TESTER function of the Digital Console.
1) Opening Zapi Display.
2) Press ENTER to go into the General menu.
3) The Display will show :
4) Press ROLL UP or ROLL DOWN button until
TESTER MENU appear on the display.
5) The Display shows :
6) Press ENTER to go into the TESTER function.
7) The first variable to be tested is shown on the Display.
8) Press either ROLL UP or ROLL DOWN buttons until your
desired variable for measurement appears on the Display.
Remember it is not possible to make any changes using TESTER. All you can do is
measure as if you were using a pre-connected multimeter.
Page 52
6 OTHER FUNCTIONS
6.1 DESCRIPTION OF THE CONSOLE SAVE FUNCTION
The SAVE function allows the operator to transmit the Parameter values and Configuration data of the chopper into the Console memory. It is possible to load 64 different programmes.
The information saved in the Console memory can then be reloaded into another chopper
using the RESTORE function.
The data that is available via the SAVE function is as follows:
- All Parameter Values (PARAMETER CHANGE).
- Options (SET. OPTIONS).
- The Level of the Battery (ADJUST BATTERY).
Flow Chart showing how to use the SAVE function of the Digital Console.
1) Opening Zapi Display.
2) Press ENTER to go into the General menu.
3) The Display will show :
4) Press ROLL UP or ROLL DOWN button until
SAVE PARAM. appears on the display
5) The Display will show :
6) Press ENTER to go into the SAVE function.
7) If this facility has been used before the type
of chopper data stored appears on the top Main with
a 2 digit reference.
8) Keep pressing either ROLL UP or ROLL DOWN keys until
the second Main indicates a FREE storage facility.
11) You can see the items that are being stored in
the chopper memory whilst the RESTORE
routine is happening.
12) When finished the Console displays :
13) Press OUT to return to the Opening Zapi Display .
Page 54
Page 55
Page 56
5 blinks:
failure of current sensor
("STBY I HIGH").
6 blinks:
failure of contactor driver
("COIL SHORTED", "DRIVER SHORTED", "CONTACTOR DRIVER", "AUX OUTPUT
KO", "CONTACTOR OPEN").
7 blinks:
excessive temperature ("HIGH TEMPERATURE", "MOTOR TEMPERATURE", "THERMIC SENSOR KO").
8 blinks:
Page 57
When the key is switched ON, the inverter tries to charge the capacitor through a power
resistance, and check if the capacitor are charged within a timeout. If this is not true: an
alarm is signalled; the main contactor is not closed.
Possible reasons:
a) the charging resistance is opened; if it is opened.
b) The charging circuit has a failure.
c) There is a problem on the power modules.
Page 58
Page 59
Page 60
3 blinks:
phase voltage or capacitor charge failure
("CAPACITOR CHARGE", "VMN LOW", "VMN HIGH").
4 blinks:
5 blinks:
failure of current sensor
("STBY I HIGH").
6 blinks:
failure of contactor driver
("COIL SHORTED", "DRIVER SHORTED", "CONTACTOR DRIVER", "CONTACTOR
OPEN").
7 blinks:
excessive temperature ("HIGH TEMPERATURE", "MOTOR TEMPERATURE", "THERMIC SENSOR KO").
8 blinks:
Page 61
5. LOGIC FAILURE #3
Fault in the hardware section of the logic board which manages the hardware current
protection. Replace the logic board.
6. INCORRECT START
This alarm signals an incorrect starting sequence. Possible causes:
a. running microswitch failure;
b. error in sequence made by the operator;
c. incorrect wiring;
d. if the default persists, replace the logic.
7. CAPACITOR CHARGE
Follows the charging capacitor system:
When the key is switched ON, the inverter tries to charge the capacitors through a
power resistance and check if the capacitors are charged within a timeout. If this is not
true: an alarm is signalled; the main contactor is not closed.
Possible reasons:
a) check if the charging resistance is opened.
b) The charging circuit has a failure.
c) There is a problem on the power modules.
8. VMN LOW, VMN HIGH
The test is carried out during initial diagnosis and in standby.
Possible causes:
a. problem with the motor connections or the motor power circuit; check if the 3 phases
are correctly connected; check if there's a dispersion of the motor towards ground;
b. chopper failure, replace it.
9. PEDAL WIRE KO
This alarm is signalled if a fault is detected in the accelerator wiring (NPOT or PPOT
cable is interrupted).
10. VACC NOT OK
The test is made in standby. This alarm indicates that the accelerator voltage is 1V
greater than the minimum value programmed by the PROGRAM VACC function.
Possible causes:
a. the potentiometer is not correctly calibrated;
b. the potentiometer is defective.
Page 62
Page 63
Page 64
Part Number
Description
C16507
C16505
C16520
C29509
SW 200 80V
Single Pole Contactor
C29532
SW 200 48V
Single Pole Contactor
Page 65
AC3/AC4 INVERTER
OPERATING HANDBOOK
AND FUNCTION DESCRIPTION
Index
1
2
3
Page
Features ......................................................................................................... 2
1.1 Specification .......................................................................................... 2
1.2 Functional Description ............................................................................ 3
1.2.a LED function .................................................................................. 3
1.2.b DISPLAY function .......................................................................... 3
Installation ...................................................................................................... 5
2.1 Connection Drawing ............................................................................... 5
2.2 Dimensions ............................................................................................ 6
Programmation and adjustments ................................................................. 7
3.1 Battery Discharge algorithm ................................................................... 7
3.2 Maintenance / Service .......................................................................... 10
3.3 Hour-meter Memory service ................................................................. 11
Alarms ........................................................................................................... 12
4.1 Decoding of the Alarms displayed ........................................................ 12
SIGNED IN APPROVAL
COMPANY DEPT. SERVICES
MANAGEMENT EXECUTIVE
1 FEATURES
1.1 SPECIFICATIONS
- ZAPI MDI is an indicator suitable for every type of battery powered vehicle equipped
with a high frequency traction controller from Zapimos family.
- This Unit is supplied directly from the chopper and not by the battery. In this way the
same device can be used on systems with different battery voltages.
- The battery's state of charge is obtained with an advanced algorithm made by the microprocessor. This algoritm considers the condition of braking or large acceleration
current demands from the drive motor.
- Using the Zapi PROGRAMMING CONSOLE, it is possible to make a selection from
100 different types of discharge curves.
- ZAPI MDI is a microprocessor- based system that allows high precision, reliability and
adaptability in the measurement of the battery's state of charge, and the calculation of
the hours worked.
- The ZAPI MDI indicator has three internal functions.
- Indication of the battery's state of charge
- Operating hour meter
- Indication of the system Alarms.
- As this unit is not connected directly to the battery, the ZAPI MDI does not require the
complex auxiliary wiring associated with traditional indicators.The wiring is "point-topoint"(from the indicator directly to the chopper). In this way, the wiring of the machine is
simpler, with reduced costs and installation time.
Page 2
Page 3
Other information
Three symbols inform the operator as follows:
Turtle Symbol
Shows activation of the soft mode of the truck, Maximum speed and acceleration are
reduced.
Page 4
2 INSTALLATION
2.1 CONNECTION SCHEME
Page 5
2.2 DIMENSIONS
Page 6
% IN THE
CO N SO LE TESTER
N UMBER O F
LEDs O N MDI
100%
4 LED GREEN
V BATT 99.54% V N O M
90%
3 LED GREEN
V BATT 98.62% V N O M
80%
3 LED GREEN
V BATT 97.25% V N O M
70%
3 LED GREEN
V BATT 96.33% V N O M
60%
2 LED GREEN
V BATT 95.41% V N O M
50%
2 LED GREEN
V BATT 94.50% V N O M
40%
2 LED GREEN
V BATT 93.57% V N O M
30%
1 LED GREEN
V BATT 92.20% V N O M
20%
1 LED GREEN
V BATT 91.28% V N O M
10%
1 LED RED
Page 7
It has to be considered that:Once the controller is turned on, the charge can decrease
- It is possible to reach the 100% charge only at turning on after a re-charge, except in the
case in which the preceding turn off, the charge was over 70%. When this happens, the
displayed percentage (ex. 80%) is reteined longer than normal.This is because the true
voltage is higher than the dispalyed value. It becomes necessary to wait until the true
voltage decreases until it reaches the limit of the displayed percentage
- It is advised to charge batteries when low charge percentages are reached (example
10%, 20%, 30%).This will extend the life of the battery. .
Using the ZAPI Console, it is possible to modify the limits of the algorithm for battery discharge, as follows:
Page 8
Follow the procedure from point 5 to point 12 to make other adjustments (ex adjustment
#2).
IMPORTANT:
Before making tests on a discharged battery, it is reccomended to check (with a calibrated digital multimeter), that the value Battery Voltage dispalyed in the Tester" Menu of
the Zapi Console, is the same as the same as the true battery voltage.
If the two voltages are not the same, it is necessary to make a calibration. This can be
made using the "Adjust Battery" facility located in the "Adjustement" Menu. For further
information, see the Manual applicable to the controller to wich the MDI is connected.
Page 9
STATE OF THE
OPTION CHECK
UP TYPE
DISPLAYED
ALARM 340
HOURS
NONE
NO
NO
NO
OPTION 1
YES
NO
NO
OPTION 2
YES
YES
NO
OPTION 3
YES
YES
YES
Note:
- the state of the option CHECK UP TYPE on default is NONE. Therefore in this configuration the Alarm is not shown and does not cause any speed reduction or disabling of
the traction motor.
- To cancel the Alarm it is necessary to set option " CHECK UP DONE" to ON.This can
be found in the HARDWARE SETTING Menu (Zapi Protected Menu) of the
Console.When this change has been made, esxit all Menus so that Zapi Opening
Dispaly is seen. The Key switch should be turned off and after 10 seconds turned on
again.
- If it is required to activate the maintenance function, after the machine has done some
hours of work, it is necessary to set option "CHECK UP DONE" to ON. This permits a
reset of the maintenance hour-meter. As above, when this change has been made, exit
all Menus so that the Zapi Opening Display is seen. The key switch should be turned off
and after 10 seconds turned on again.
- In case you wish to activate the maintenance function also after the machine has done
some hours of work, you have to set ON the option CHECK UP DONE which permits
to reset the maintenance hour-meter. Turning off and on again the key, the function will
self-reset to OFF.
Page 10
Page 11
4 ALARMS
The ZAPI MDI gives indication of the Alarm of the controller to which it is connected, with a
corresponding code..
When an Alarm is generated, the Red LED flashes to attract the attention of the operator.
The symbol of Shifting Spanner also appears.
Page 12
AL 00
NONE
AL 01
CHOPPER RUNNING
AL 02
NO COMUNICATION
AL 03
UNKNOWN CHOPPER
AL 04
CONSOLE EEPROM
AL 05
SERIAL ERROR 2
AL 06
SERIAL ERROR 1
AL 07
AL 08
WATCHDOG
AL 09
FIELD FF FAILURE
AL 10
EEPROM DATA KO
AL 11
EEPROM PAR KO
AL 12
EEPROM CONF KO
AL 13
EEPROM KO
AL 14
EEPROM OFFLINE
AL 15
LOGIC FAILURE 5
AL 16
LOGIC FAILURE 4
AL 17
LOGIC FAILURE 3
AL 18
LOGIC FAILURE 2
AL 19
LOGIC FAILURE 1
AL 20
AL 21
AL 22
AL 23
AL 24
AL 25
AL 26
AL 27
AL 28
AL 29
AL 30
VMN LOW
AL 31
VMN HIGH
AL 32
VMN NOT OK
AL 33
NO FULL COND
AL 34
AL 35
AL 36
PU NO FULL COND
AL 37
CONTACTOR CLOSED
AL 38
CONTACTOR OPEN
AL 39
AL 40
Page 14
AL 41
AL 42
AL 43
AL 44
AL 45
AL 46
AL 47
AL 48
AL 49
I=0 EVER
AL 50
AL 51
AL 52
AL 53
STBY I HIGH
AL 54
AL 55
AL 56
AL 57
AL 58
NO FIELD CURR
AL 59
HIGH BRAKING I
AL 60
CAPACITOR CHARGE
AL 61
HIGH TEMPERATURE
AL 62
TH PROTECTION
AL 63
THERMIC LEVEL 2
AL 64
PUMP TEMPERATURE
AL 65
MOTOR TEMPERATURE
AL 66
BATTERY LOW
AL 67
BATTERY LEVEL 2
AL 68
BATTERY LEVEL 1
AL 69
CURRENT SENS KO
AL 70
POWER FAILURE 4
AL 71
POWER FAILURE 3
AL 72
POWER FAILURE 2
AL 73
POWER FAILURE 1
AL 74
DRIVER SHORTED
AL 75
CONTACTOR DRIVER
AL 76
COIL SHORTED
AL 77
COIL INTERRUPTED
AL 78
VACC NOT OK
AL 79
INCORRECT START
AL 80
FORW + BACK
AL 81
AL 82
ENCODER ERROR
AL 83
AL 84
STEER SENS KO
AL 85
STEER HAZARD
AL 86
PEDAL WIRE KO
AL 87
PEDAL FAILURE
AL 88
TRACTION BRUSHES
AL 89
PUMP BRUSHES
AL 90
DRIVER 1 KO
AL 91
DRIVER 2 KO
AL 92
DRIVER 1 SIC KO
AL 93
DRIVER 2 SIC KO
AL 94
INPUT ERROR 6
AL 95
INPUT ERROR 5
AL 96
INVERSION
AL 97
POSITION HANDLE
AL 98
INPUT ERROR 2
AL 99
INPUT ERROR 1
Page 15
Important:
The alarms reported in the previous tables are refered to Zapi standard coding.
Customized software or special products can have same changements in the alarms
indications.
Following you can find same example:
COD. MDI
ALARM
CHOPPER
AL 15
V FIELD NOT OK
SEM-0 / SEM-1C
AL 15
R VMN NOT OK
DUAL-SEM
AL 16
SYSTEM CHECK KO
AL 16
L VMN NOT OK
DUAL-SEM
AL 17
AL 17
R V FIELD NOT OK
DUAL-SEM
AL 18
BRAKE DRIVER KO
AL 18
L V FIELD NOT OK
DUAL-SEM
AL 70
AL 70
R FIELD I LOW
DUAL-SEM
AL 71
HANDBRAKE
AL 71
L FIELD I LOW
DUAL-SEM
AL 72
R FIELD I HIGH
DUAL-SEM
AL 73
L FIELD I HIGH
DUAL-SEM
AL 94
MICRO CHECK KO
DUAL-SEM
AL 95
OPERATOR ABSENT
DUAL-SEM
AL 96
BRAKE DRIVER KO
DUAL-SEM
AL 97
HANDBRAKE
DUAL-SEM
AL 98
CLEARING MDI HM
DUAL-SEM
AL 99
CHECK UP NEEDED
SEM-0 / SEM-1C
Page 16
INSTALLATION AND
USER MANUAL
MDI
( Multifunction Digital Indicator )
CONSOLE MANU
AL
MANUAL
Page 1
Page 2
INDEX
Page
Legend
Keyboard
Hour meter
Alarm display
Parameter programming
Tester
Save
Restore
Data motor
Operators manual
Menu A description
11
Menu B description
12
12
Description menu B
12
13
13
14
14
18
19
20
21
23
24
25
Page 3
LEGEND
VMN = Mosfet drain voltage
I / O = Input, Output connection ( pin configuration see pag. 11 )
Page 4
KEYBOARD
Description of key functions:
Key 1
Key 2
Key 3
Key 4
Key 5
Key 6
Page 5
Page 6
DATA MOTOR
This function allows the engineer to record the motor's electrical parameters in the chopper
memory the characteristics memorized varies between motors and are used during
reversal, allowing more efficient control of the motor current.
This procedure requires an input of answers to questions displayed on the console,
automatically leaving " motor data " routine upon completion.
Page 7
OPERATOR'S MANUAL
When switched on, the console tries to become connected with the chopper and displays
the following messages:
At this stage you should check whether connections have been correctly performed as per
the attached drawings.
Page 8
H1 3 CABLES
2-
H1 4 CABLES S
3-
H1 4 CABLES T
4-
H1 SPECIAL
5-
NO CONFIG.
6-
NO CONFIG.
7-
NO CONFIG.
8-
NO CONFIG.
9-
NO CONFIG.
10 - NO CONFIG.
By means of the ROLL UP (key No. 1) and ROLL DOWN (key No. 2) keys you can scroll
the possible configurations of selectable choppers while the ENTER key (No. 3) confirms
the selection made.
The NO CONFIG. item shows that the selected model number has not yet been set.
Page 9
When a menu item is confirmed via the ENTER key (No. 3) the display shows:
At this stage if you confirm by pressing ENTER (key No. 3) the chopper configuration is as
per the selected model.
By pressing OUT (key No. 4) you can have access to the previous menu (SELECT MODEL).
After setting the model configuration the console enters the I/O CONFIGURATION MENU.
The display shows the number of pins requiring configuration and the meaning that a pin
may acquire.
Example:
By pressing SET-UP (key No. 5) and SET-DOWN (key No. 6) you scroll the different
possible states of a pin.
Any time you confirm by pressing ENTER (key No. 3) the display shows:
Confirming again with the ENTER key (No. 3) the state of the pin is stored in the chopper
while the OUT key (No. 4) allows you to repeat pin programming.
Once pin programming is completed the display shows:
At this point chopper configuration is complete. To move to the B menu simply switch off
and on again.
Page 10
Selectable states:
Pin 4E
Selectable states:
Pin 2D
Selectable states:
Pin 1E
Selectable states:
SEAT (seat)
HANDLE (handle)
FREE (free pin)
Pin 3E
Selectable states:
WEAK (weakening)
BY-PASS (by-pass)
Page 11
where:
ZAPI
V.1.0
H1 SP
35
MENU B DESCRIPTION
By pressing the ENTER key you enter the main menu which consists of the following
functions:
1 - Program
2 - Tester
3 - Save
4 - Restore
5 - Alarms
6 - Accelerator setting
7 - Motor data
By means of the ROLL UP (No. 1) and ROLL DOWN (No. 2) keys you can scroll the
functions while with the ENTER key (No. 3) you can confirm the selected function.
By selecting OUT (key No. 4) you return to the menu B.
Page 12
By means of the ROLL UP (No. 1) and ROLL DOWN (No. 2) keys you can scroll the
parameters while with the SET-UP (No. 5) and SET-DOWN (No. 6) keys you can change
the levels.
The UP key allows you to increase the level while by pressing the DOWN key you decrease
the level.
LIST OF MENU ITEMS FOR MENU 1 - PROGRAM:
1.1 ACCEL. DELAY
1.2 BRAKING
: Acceleration time
: Current braking threshold
: Speed 1 reduction
: Speed 2 reduction
1.5 COMPENSATION
1.7 I MAX.
: Max. current
By pressing the OUT key (No. 4) you return to the main menu.
Page 13
The displayed message shows the voltage level available at the chopper output terminals
with reference to VMN forward and VMN reverse.
Where:
< 30%
Indicates that on output connector there is a voltage less than 30% of battery
voltage
> 30%
Indicates that on output connector there is a voltage greater than 30% of battery
voltage
By means of the ROLL UP (No. 1) and ROLL-DOWN (No. 2) keys you can scroll all the
signals available on the chopper connectors.
By pressing the OUT key you can return to the main menu.
LIST OF MEASUREMENTS TAKEN BY THE TESTER:
1)
where:
< 80%
Indicates that on output connector there is a voltage less than 80% of battery
voltage
> 80%
Indicates that on output connector there is a voltage greater than 80% of battery
voltage
Page 14
2)
where:
3)
VB
4)
where:
5)
VB
Page 15
where:
6)
VB
where:
7)
VB
where:
5000 is the accelerator mVolt value
100% is the percent accelerator value
8)
where:
50 is motor current in Ampere.
Page 16
9)
where:
30 is the power block temperature value in degrees centigrade.
10) Reads battery voltage.
Example:
where:
23.5 Volt is battery voltage read during the tester phase
24 Volt is the type of battery used by the chopper.
11) Reads motor voltage
Example:
where:
22 Volt is voltage applied to the motor.
Page 17
The ROLL UP (No. 1) and ROLL DOWN (No. 2) keys allow you to select the number of the
program while the parameters should be saved while by pressing ENTER (No. 3) you can
confirm the selection made.
You can select up to 10 programs.
When confirming by pressing ENTER (key No. 3) the display shows:
By pressing the OUT key you return to the menu B. If you confirm by pressing ENTER (key
No. 3) the display shows:
The chopper parameters are now transferred to the console in the showed point..
Once this transfer has occurred the program returns to the menu B.
Page 18
The ROLL UP (No. 1) and ROLL DOWN (No. 2) keys make it possible to select the number
of the program to be stored into the chopper while by pressing the ENTER key (No. 3) you
confirm the selection made.
When confirming by pressing ENTER (key No. 3) if the selected program has not been
generated by a SAVE the display shows:
By pressing the OUT key you return to the menu B. If you confirm by pressing ENTER (key
No. 3) the display shows:
The parameters of the console program are now transferred to the chopper. Once transfer
has occurred the program return to the menu B.
Page 19
where:
23 is the time at which the alarm was sent
2 is the number of times that the alarm was sent
25 is the temperature in degrees centigrade at the time of the alarm
If the display shows
Page 20
Chopper no conf.
2-
VMN 1/3 at rest or VMN 1/3 when operating with PWM 80%
(forward).
3-
VMN 1/3 at rest or VMN 1/3 when operating with PWM 80%
(reverse).
4-
No full cond.
5-
6-
I=0 ever
7-
I hight at stand
8-
Watch - dog
Watch-dog.
9-
Forw back
10 - Incorrect start
12 - Contactor driver
Shorted driver.
13 - EEprom data ko
14 - EEprom par. ko
15 - EEprom conf. ko
16 - EEprom ko
Page 21
17 - Err. by-pass
18 - Protection
19 - Battery
Battery dis-charged.
Page 22
By confirming with the ENTER key (No. 3) you enter the programming phase and the display
shows:
If you confirm by pressing ENTER again (key No. 3) the values are stored in the chopper
and the program returns to the menu B.
Page 23
The console display requires that the operator stops the motor from rotating.
If ENTER (No. 3) is pressed the display shows:
The console display requires that the operator selects the forward direction.
If you press ENTER (key No. 3) the display shows:
If all console instructions have been accurately followed the motor parameters are
calculated and stored into the chopper memory.
At the end of processing the program returns to the menu B.
The above procedure can be interrupted at any time returning to the menu B by simply
pressing the OUT key.
Page 24
By means of the ROLL UP (No. 1) and ROLL DOWN (No. 2) keys you can scroll all menu
functions while by pressing the ENTER key (No. 3) you can confirm the selected function.
Menu items are as follows:
1 - SEL. MODEL
2 - CONFIG. I/O
The operations to do are the some of menu' A (see instructions of menu' A).
Page 25
INDEX
1
2
Introduction ............................................................................................................. 4
Specification ........................................................................................................... 5
2.1 Technical specifications - "Dualac2"................................................................ 5
2.2 Technical specifications - "Dualac2&hp" ......................................................... 6
2.3 Technical specifications - "Dualac2 Power" ..................................................... 7
2.4 Technical specifications - "Dualac2&hp Power" .............................................. 8
2.5 Control unit ...................................................................................................... 8
2.5.1 Microswitches ........................................................................................ 8
2.5.2 Accelerator unit ...................................................................................... 8
2.5.3 Other analog control unit ......................................................................... 9
2.5.4 Speed feedback ................................................................................... 10
2.5.5 Steering angle transducer ..................................................................... 10
2.6
Protection features
................................................................................. 12
2.7
2.8
2.9
...................................................... 14
......................................... 15
Installation ............................................................................................................. 17
4.1 Connection cables ........................................................................................ 17
4.2 Contactors .................................................................................................... 17
4.3 Fuses ............................................................................................................ 17
4.4 Description of connectors - "Dualac2" and "Dualac2 Power" ........................ 18
4.5 Description of connectors - "Dualac2&hp" and "Dualac2&hp Power" ............ 20
4.6 Encoder installation ....................................................................................... 23
4.7 CANBUS connector description .................................................................... 24
4.7.1 "Dualac2" Controller in stand-alone configuration .................................. 24
4.7.2 "Dualac2" Controller is a termination module in the canbus net ............. 24
4.7.3 "Dualac2" Controller is a repetition module in the canbus net ................ 25
4.8 Description of power connections.................................................................. 26
4.8.1 "Dualac2" ............................................................................................. 26
4.8.2 "Dualac2 Power" .................................................................................. 27
4.8.3 "Dualac2&hp" ....................................................................................... 28
4.8.4 "Dualac2&hp Power" ............................................................................ 30
4.9 Mechanical drawing ...................................................................................... 32
4.10 Connection drawing - "Dualac2" and "Dualac2 Power" standalone ................ 36
4.11 Connection drawing - "Dualac2&hp" and "Dualac2&hp Power" standalone ... 37
Page 1
Page 2
8
9
The informations included into the marked paragraphs by this symbol are
essential for the safety.
SIGNATURES TABLE
COMPANY DEPT. SERVICES
MANAGEMENT EXECUTIVE
1 INTRODUCTION
Within the ZAPIMOS family, the DUALAC2 inverter is the model suitable for control of pairs
of 3.0kW to 7.0kW motors. The DUALAC2&HP can also control a DC-Series pump motor,
up to 15kW. These controllers have been expressly designed for battery powered applications, traction and hydraulic functions. They are fit for electric trucks, utility cars, tractors.
Page 4
2 SPECIFICATION
2.1 TECHNICAL SPECIFICATIONS - "DUALAC2"
Inverter for pairs of AC asynchronous 3-phase motors
Regenerative braking functions
Can-bus interface
Digital control based upon a microcontroller (one per each motor)
Voltage: .................................................................................. 24 - 36 - 48 - 72 - 80V
Maximum current (24V): ........................................ 350A (RMS) for 3' per each motor
Maximum current (36/48V): ................................... 275A (RMS) for 3' per each motor
Maximum current (72/80V): ................................... 200A (RMS) for 2' per each motor
Operating frequency: ..........................................................................................8kHz
External temperature range: ................................................................. -30C 40C
Maximum inverter temperature (at full power): .................................................... 75C
BLOCK DIAGRAM
Page 5
Page 6
Page 7
Page 8
PPOT is the accelerator unit positive supply. It can be either a 5V output or a 10V output.
The selection of the output voltage is made in the logic card by moving a jumper (factory
set).
NPOT is the accelerator unit negative supply. This output is feedback to the C A/D converter to test the continuity of the accelerator unit circuit (test of poti wire disconnection).
The Procedure for automatic potentiometer signal acquisition is carried out using the
Console. This enables adjustment of the minimum and maximum useful signal level
(PROGRAM VACC function), in either direction. This function is unique when it is necessary to compensate for asymmetry with the mechanical elements associated with the
potentiometer, especially relating to the minimum level.
The sequence of procedure is described in the programming console manual.
The two graphs show the output voltage from a non-calibrated potentiometer with
respect to the mechanical zero of the control lever. MI and MA indicate the point where
the direction switches close. 0 represents the mechanical zero of the rotation.
The Left Hand graph shows the relationship of the motor voltage without signal acquisition
being made. The Right Hand Graph shows the same relationship after signal acquisition
of the potentiometer.
2.5.3 Other analog control unit
1) Input C18 is an analog input, whose typical application is for proportional braking. It
should be in a 3 wire configuration. Potentiometer value should be in the 0.5-10 Kohm
range. Generally, the load should be in the 1.5mA to 30 mA range.
The CPOTB (C18) signal range is from 0 to 5V or from 0V to 10V.
2) Connections C25 (PTHERMR) and C24 (NTHERMR) are used for the right motor
thermal sensor. Connections C35 (PTHERML) and C34 (NTHERML) are used for the
left motor thermal sensor. Sensors can be digital (on/off sensor, normally closed) or
analog. See also chapter 5.4 for more explanation.
3) In the versions with integrated pump chopper (DUALAC2&HP and DUALAC2&HP
POWER), it is possible to input to the controller an analog signal for proportional lifting.
This input will be the output of a potentiometer (3 wires, resistance in the 1 to 10kohm
range) or of a Hall Effect device; the load must be below 10mA. CPOTLIFT (D9) signal
has to be within the 0 to 10V range.
Page 9
electric output:
For more details about encoder installation see also chapter 4.6.
2.5.5 Steering angle transducer
Angular position of steered wheels is transduced to an electric information (voltage) by
means of a potentiometer, with following characteristics:
- resistance in the 2kohm to 20kohm range;
- suggested rotation electric angle: at least 300;
- positive supply: 5V or 10V;
- potentiometer has to be installed in a way that in the "zero" position (straight wheels),
poti output voltage is in the middle of the electric range corresponding to a full left-toright transition of the steered wheels;
- install the potentiometer in a way that, when truck turns right, poti output voltage increases;
- use "SET STEER MIN" and "SET STEER MAX" functions to record the extremes (minimum and maximum) of the potentiometer range; see chapter 5.4.
- use "SET STEER 0-POS" function to record the poti output when the steered wheels
are straight; see chapter 5.4.
Page 10
Potentiometer connections
Steering table
The relationship between the two motors speed changes as a function of the steering
angle and of the axle/wheeltrack ratio.
While the steering angle is an information coming from the trasducer (potentiometer), the
axle/wheeltrack ratio is a constant characteristic of the truck that depends on his dimensions. Actually two steering tables are provided:
Option #1 = tables for 3 wheels trucks with driving wheels counter-rotation (the internal
wheel inverts the direction).
Option #2 = tables for 4 wheels trucks without driving wheels counter-rotation (the
internal wheel does not inverts the direction).
The truck data have to be communicated to Zapi, so that it is possible to put in the software
the correct steering table.
The correct table selection is done in the SET OPTION menu, see chapter 5.4.
The relationship between the two motors speed is equal to the relationship between the
two radius described during the curve.
Page 11
Page 12
Page 13
2.8 DIAGNOSIS
The microprocessors continually monitor the inverter and carry out a diagnostic procedure
on the main functions. The diagnosis is made in 4 points
1) Diagnosis on key switch closing that checks: watchdog circuit, current sensor, capacitor charging, phase's voltages, contactor drivers, can-bus interface, if the switch sequence for operation is correct and if the output of accelerator unit is correct, correct
synchronization of the two CS, integrity of safety related inputs hardware.
2) Standby diagnosis at rest that checks: watchdog circuit, phase's voltages, contactor
driver, current sensor, can-bus interface.
3) Diagnosis during operation that checks: watchdog circuits, contactor driver, current
sensors, can-bus interface.
4) Continuos diagnosis that check: temperature of the inverter, motor temperature.
Diagnosis is provided in two ways. The digital console can be used, which gives a detailed
information about the failure; the failure code is also sent on the Can-Bus.
2.9 THERMAL CONSIDERATION
- The heat generated by the power block must be dissipated. For this to be possible,
the compartment must be ventilated and the heat sink materials ample.
- The heat sink material and system should be sized on the performance requirement of
the machine. Abnormal ambient air temperatures should be considered. In situations
where either ventilation is poor, or heat exchange is difficult, forced air ventilation should
be used.
- The thermal energy dissipated by the power block module varies and is dependent on
the current drawn and the duty cycle.
2.10 GENERAL INSTRUCTIONS AND PRECAUTIONS
- Never connect SCR low frequency chopper with ASYNCHRONOUS INVERTER because the ASYNCHRONOUS filter capacitors alter the SCR choppers' work. If it is
necessary to use two or more control units (traction + lift. for ex.), they must belong to the
ZAPIMOS family.
- Do not connect the inverter to a battery with a nominal value different from the value
indicated on the chopper plate. If the battery value is greater, the MOS may fail; if it is
lower, the control unit does not "power up".
- During battery charge, disconnect ASYNCHRONOUS from the battery.
- Supply the ASYNCHRONOUS only with battery for traction; do not use a power supply.
- When the chopper is installed, make tests with the wheels raised from the ground, in
order to avoid dangerous situations due to connection errors.
- After the chopper is switched off (key off), the filter capacitor remains charged for about
1 minute; if you need to work on the inverter, discharge them using a
10W 100W resistance connected from the +Batt to the -Batt.
Page 14
- An intrinsic protection is present inside the logic when the voltage on the battery power
connection overtakes 40% more than the battery nominal voltage or if the key is
switched off before the battery power line is disconnected.
Page 15
Page 16
4 INSTALLATION
Install the controller with the base-plate on a flat metallic surface that is clean and
unpainted. Apply a light layer of thermo-conductive grease between the two surfaces to
permit better heat dissipation.
Ensure that the wiring of the cable terminals and connectors is carried out correctly.
Fit transient suppression devices to the horn, solenoid valves, and contactors not connected to the chopper such as those for activating the pump motor or steering motor.
4.1 CONNECTION CABLES
For the auxiliary circuits, use cables of 0.5mm section.
For power connections to the motor and to the battery, use cables having section
of 35 mm (as a minimum).
For the optimum inverter performance, the cables to the battery should be run side by side
and be as short as possible.
4.2 CONTACTORS
The main contactor must be installed. The LC coil driver is voltage controlled by means of
a 1 khz PWM. The voltage applied to the coil can be adjusted by "Main Cont Voltage"
parameter in Config/Adjustment menu. It has to be adjusted to the LC coil nominal voltage.
4.3 FUSES
- Use a 6.3A Fuse for protection of the auxiliary circuits.
- For protection of the power unit, refer to diagrams.. The Fuse value shown is the maximum allowable. For special applications or requirements these values can be reduced.
- For Safety reasons, we recommend the use of protected fuses in order to prevent the
spread of fused particles should the fuse blow.
Page 17
A1
CAN_H
A2
CANT_H
A3
CAN_POS
A4
CAN_L_OUT
A5
CANT_L
A6
CAN_L
A7
CAN_H_OUT
A8
CAN_NEG
B1
PCLRXD
B2
NCLRXD
B3
PCLTXD
B4
NCLTXD
B5
GND
B6
+12
B7
FLASH
B8
FLASH
Page 18
C1
PENC_R
C2
NENC_R
C3
KEY
C4
CM
C5
SEAT
C6
FORWARD
C7
REVERSE
C8
ENABLE
C9
PB
C10 SR/HB
C11 PENC_L
C12 NENC_L
C13 PHA_R
C14 PHB_R
C15 NPOTST
C16 PPOTST
C17 CPOTST
C18 CPOTB
C19 NPOTB
-BATT.
C20 NPOT
C21 CPOT
C22 PHA_L
C23 PHB_L
C24 NTHERM_R
C25 PTHERM_R
C26 NLC
C27 PLC
C28 NBRAKE
C29 PBRAKE
C30 PAUX
C31 NAUX
C32 -BATT
C33 PPOT
C34 NTHERM_L
C35 PTHERM_L
A1
CAN_H
A2
CANT_H
A3
CAN_POS
A4
CAN_L_OUT
A5
CANT_L
A6
CAN_L
A7
CAN_H_OUT
A8
CAN_NEG
B1
PCLRXD
B2
NCLRXD
B3
PCLTXD
B4
NCLTXD
B5
GND
B6
+12
B7
FLASH
B8
FLASH
Page 20
C1
PENC_R
C2
NENC_R
C3
KEY
C4
CM
C5
SEAT
C6
FORWARD
C7
REVERSE
C8
ENABLE
C9
PB
C10 SR/HB
C11 PENC_L
C12 NENC_L
C13 PHA_R
C14 PHB_R
C15 NPOTST
C16 PPOTST
C17 CPOTST
C18 CPOTB
C19 NPOTB
-BATT.
C20 NPOT
C21 CPOT
C22 PHA_L
C23 PHB_L
C24 NTHERM_R
C25 PTHERM_R
C26 NLC
C27 PLC
C28 NBRAKE
C29 PBRAKE
C30 PAUX
C31 NAUX
C32 -BATT
C33 PPOT
C34 NTHERM_L
C35 PTHERM_L
D1
-BATT
Negative output.
D2
2ND
D3
1ST
D4
ENABLE
D5
CMM
D6
5TH
D7
4TH
D8
3RD
D9
CPOTLIFT
D10 -BATT
D11 -BATT
D12 -BATT
D13 NPOTLIFT
D14 PPOTLIFT
Page 22
+5V/+12V:
C12/C2:
GND:
C22/C13:
A:
phase A of encoder.
C23/C14:
B:
phase B of encoder.
The encoder power supply voltage and output electronic has to be communicated to ZAPI
in order to correctly set the selection jumpers in the logic card.
Page 23
Bridge 2-4 and 5-7 connect both built-in120 ohm can termination resistances.
4.7.2 "Dualac2" Controller is a termination module in the canbus net
Bridge 2-4 connects one built-in 120 ohm can termination resistance, the second will be
connected in another module of the canbus net.
Page 24
Page 25
-B
+BT
Positive of the battery; if the power fuse is not present, the positive
cable coming from LC contact must be connected to this power
connection.
+BTF
Um; Vm; Wm
Connection bars of the three right motors phases; follow this sequence and the indication on the motor.
Us; Vs; Ws
Connection bars of the three left motors phases; follow this sequence and the indication on the motor.
Page 26
-B
+BT
Positive of the battery; if the power fuse is not present, the positive
cable coming from LC contact must be connected to this power
connection.
+BTF
Um; Vm; Wm
Connection bars of the three right motors phases; follow this sequence and the indication on the motor.
Us; Vs; Ws
Connection bars of the three left motors phases; follow this sequence and the indication on the motor.
Page 27
4.8.3 "Dualac2&hp"
View of the power bars:
-B
+BT
Positive of the battery; if the power fuse is not present, the positive
cable coming from LC contact must be connected to this power
connection.
Page 28
+BTF
Um; Vm; Wm
Connection bars of the three right motors phases; follow this sequence and the indication on the motor.
Us; Vs; Ws
Connection bars of the three left motors phases; follow this sequence and the indication on the motor.
-P
+P
Pump chopper positive, if the power fuse is not present, the positive
cable coming from LC contact must be connected to this power
connection; also the pump motor positive cable must be connected
to this power connection.
+BPF
Page 29
-B
+BT
Positive of the battery; if the power fuse is not present, the positive
cable coming from LC contact must be connected to this power
connection.
Page 30
+BTF
Um; Vm; Wm
Connection bars of the three right motors phases; follow this sequence and the indication on the motor.
Us; Vs; Ws
Connection bars of the three left motors phases; follow this sequence and the indication on the motor.
-P
+P
Pump chopper positive, if the power fuse is not present, the positive
cable coming from LC contact must be connected to this power
connection; also the pump motor positive cable must be connected
to this power connection.
+BPF
Page 31
Page 32
Page 33
Dimensions of "Dualac2&hp":
Page 34
Page 35
Page 36
Page 37
Digital consoles used to communicate with AC inverter controllers must be fitted with
EPROM CK ULTRA, minimum "Release Number 3.02".
Page 38
Page 39
5.3.1.b Slave
Page 40
Page 41
5.3.2.b Slave
Page 42
- KEY ON:
2 BATTERY CHECK
- ON:
the battery discharge level check is carried out; when the battery level reaches 10%, an alarm is signalled and the maximum
current is reduced to the half of the programmed value.
- OFF:
3 HYDRO KEY ON
- ON / OFF:
4 STOP ON RAMP
- ON:
- OFF:
5 AUX INPUT #1
- EXCLUSIVE HYDRO:
input C10 activates hydraulic steering function, output
A31 is activated.
- OPTION #1:
- CUTBACK SPEED: input C10 is the input for a speed reduction device, active low
(open switch).
Page 43
6 PEDAL BRAKING
- ANALOG:
- DIGITAL:
The truck does not have a potentiometer installed on the mechanical brake pedal, but only a microswitch; when the accelerator pedal is released and the brake pedal is pushed (brake
switch closed), the inverter performs an electrical braking
following "Pedal braking" parameter.
7 SET TEMPERATURE
- DIGITAL:
- ANALOG:
- NONE:
8 STEER TABLE
SUBMENU "ADJUSTEMENT"
1 SET POT BRK MIN:
4 ADJUST BATTERY:
Page 44
10
11
12
THROTTLE Y POINT: these parameter change the characteristic of the acceleratorinput curve.
VACC MIN and VACC MAX are values programmable by the "Program Vacc" function.
13
ADJUSTMENT #01: adjust the upper level of the battery discharge table.
Page 45
14
ADJUSTMENT #02: adjust the lower level of the battery discharge table.
15
MAIN CONT VOLTAGE: this parameters adjusts the Line contactor coil voltage
(PWM output C26)
16
AUX OUTPUT VOLTAGE: this parameters adjusts the Electric brake coil voltage
(PWM output C28).
2 ADJUST BATTERY:
Page 46
2 ADJUST BATTERY:
4 SET ACCELER MAX: This parameter is used to adjust maximum value of the lift
potentiometer. Press ENTER, pull the lever to the maximum,
then record the value (OUT --> ENTER).
5 THROTTLE 0 ZONE:
6 THROTTLE X POINT:
these parameter change the characteristic of the lifting accelerator input curve.
7 THROTTLE Y POINT:
these parameter change the characteristic of the lifting accelerator input curve.
Page 47
Page 48
Page 49
Flow chart showing how to use the SET BATTERY TYPE adjustment
1) Opening Zapi Menu
2) Press Top Left & Right Buttons to enter
CONFIG Menu.
3) The Display will show: SET MODEL
4) Press ROLL UP button until
ADJUSTMENTS. menu appears.
5) ADJUSTMENTS appears on the display.
6) Press ENTER to go into the ADJUSTMENTS
Menu and use ROLL UP/DOWN buttons to final
the SET BATTERY TYPE parameter.
7) The display will show: SET BATTERY TYPE.
8) Press SET UP to choose nominal value of
the battery.
9) New battery value appears.
10) Press OUT.
11) Confirmation request appears.
12) Press ENTER to accept the changes, or press
OUT if you do not accept the changes.
13) Press OUT. Display now shows the Opening
Zapi Menu.
Page 50
Flow chart showing how to carry out ADJUSTMENT BATTERY operation by console.
1) Opening Zapi Menu
2) Press Top Left & Right Buttons to enter
CONFIG Menu.
3) The Display will show: SET MODEL
4) Press ROLL UP button until
ADJUSTMENT Menu appears.
5) ADJUSTMENTS appears on the
display.
6) Press ENTER to go into the
ADJUSTMENTS Menu.
7) The display will show the first
OPTION.
8) Press ROLL UP or ROLL DOWN button
until desired OPTION appears
9) ADJUST BATTERY appears.
10) Press SET UP or SET DOWN button
in order to increase or decrease
respectively. Set the value read
by an external voltmeter.
11) Battery value appears on the display.
12) Press OUT to exit the Menu.
13) Confirmation request appears.
14) Press ENTER to accept the changes,
or press OUT if you do not accept the
changes.
15) ADJUSTMENTS Menu appears.
16) Press OUT. Display now show the Opening Zapi Menu.
Page 51
ACC DELAY:
RELEASE BRAKING:
INVERSION BRAKING:
PEDAL BRAKING:
BRAKE CUTBACK:
7
8
9
10 CUTBACK SPEED:
11 FREQUENCY CREEP:
12 MAXIMUM CURRENT:
13 AUXILIARY TIME:
Page 52
The following table shows the different values at which the parameters can be set.
PARAMETER
PROGRAMMED LEVEL
UNIT
Sec.
1.5
2.5
3.5
4.5
5.5
Sec.
5.5
4.5
3.5
2.5
1.5
Sec.
5.5
4.5
3.5
2.5
1.5
Sec.
5.5
4.5
3.5
2.5
1.5
Sec.
8.9
8.3
7.7
7.1
6.6
6.0
5.5
4.9
4.4
3.8
Sec.
5.5
4.5
3.5
2.5
1.5
MAX SPEED FW
Hz
65
80
95
110
125
140
155
170
185
200
MAX SPEED BW
Hz
65
80
95
110
125
140
155
170
185
200
CURVE CUTBACK
10
15
20
25
38
50
63
75
87
100
CUTBACK SPEED
10
15
20
25
38
50
63
75
87
100
FREQUENCY CREEP
Hz
0.3
0.6
0.9
1.2
1.5
1.8
2.1
2.4
2.7
% IMAX
43
50
56
62
68
75
81
87
94
100
Sec.
0.2
0.4
0.8
1.5
MAXIMUM CURRENT
AUXILIARY TIME
(*)
The acceleration time shown is the time from 0 Hz to 100 Hz. This is the ideal ramp
calculated by the software; the real ramp could change as a function of motor control
parameter setting and, obviously, as a function of the load.
(**)
The braking feature is based upon deceleration ramps. The value shown in the table
is the time to decrease the speed from 100 Hz to 0 Hz. This is the ideal ramps calculated by the software; the real ramp could change as a function of motor control parameter setting and, obviously, as a function of the load.
Page 53
ACC DELAY:
RELEASE BRAKING:
INVERSION BRAKING:
PEDAL BRAKING:
BRAKE CUTBACK:
7
8
9
10 CUTBACK SPEED:
11 FREQUENCY CREEP:
12 MAXIMUM CURRENT:
13 AUXILIARY TIME:
Page 54
The following table shows the different values at which the parameters can be set.
PARAMETER
PROGRAMMED LEVEL
UNIT
Sec.
1.5
2.5
3.5
4.5
5.5
Sec.
5.5
4.5
3.5
2.5
1.5
Sec.
5.5
4.5
3.5
2.5
1.5
Sec.
5.5
4.5
3.5
2.5
1.5
Sec.
8.9
8.3
7.7
7.1
6.6
6.0
5.5
4.9
4.4
3.8
Sec.
5.5
4.5
3.5
2.5
1.5
MAX SPEED FW
Hz
65
80
95
110
125
140
155
170
185
200
MAX SPEED BW
Hz
65
80
95
110
125
140
155
170
185
200
CURVE CUTBACK
10
15
20
25
38
50
63
75
87
100
CUTBACK SPEED
10
15
20
25
38
50
63
75
87
100
FREQUENCY CREEP
Hz
0.3
0.6
0.9
1.2
1.5
1.8
2.1
2.4
2.7
% IMAX
43
50
56
62
68
75
81
87
94
100
Sec.
0.2
0.4
0.8
1.5
MAXIMUM CURRENT
AUXILIARY TIME
(*)
The acceleration time shown is the time from 0 Hz to 100 Hz. This is the ideal ramp
calculated by the software; the real ramp could change as a function of motor control
parameter setting and, obviously, as a function of the load.
(**)
The braking feature is based upon deceleration ramps. The value shown in the table
is the time to decrease the speed from 100 Hz to 0 Hz. This is the ideal ramps calculated by the software; the real ramp could change as a function of motor control parameter setting and, obviously, as a function of the load.
CREEP SPEED:
Page 55
COMPENSATION:
Page 56
18 HYDRO TIME:
19 PUMP IMAX:
Page 57
PARAMETER
PROGRAMMED LEVEL
UNIT
Sec.
0.2
0.4
0.6
0.8
1.5
2.5
3.5
Sec.
0.2
0.4
0.6
0.8
1.5
2.5
3.5
83
88
94
100
SPEED LIMIT
0 - 100
CREEP SPEED
0 - 100
COMPENSATION
0 - 100
0 - 100
0 - 100
0 - 100
0 - 100
0 - 100
0 - 100
0 - 100
0 - 100
0 - 100
0 - 100
0 - 100
0 - 100
Sec.
0 - 25.5
HYDRO TIME
PUMP IMAX
(*)
%IMAX
50
55
61
66
72
77
The acceleration time shown is the theoretical time to change from 0V to full voltage
applied to the motor. This is an ideal ramp, the real ramp can change as a function of
the load.
(**) The deceleration feature is based upon deceleration ramps. The value shown in the
table is the time to decrease the voltage applied to the motor from 100% down to
0%.
Page 58
After changing a parameter, press ENTER to confirm data when requested by the message on the console. Parameters modified and optimized on one unit can be stored by the
Zapi Pc-console (SAVE) and then downloaded (RESTORE) to another controller, thus
allowing fast and standardized settings (see Pc-console manual for details).
Flow Chart showing how to make Parameter changes using Digital Console fitted with
Eprom CK ULTRA.
1) Opening Zapi Display.
2) Press ENTER to go into the General
Menu.
3) The Display will show :
4) Press ENTER to go into the
Parameter Change facility.
5) The Display will show the first
parameter.
6) Press either ROLL UP and ROLL DOWN
to display the next parameter.
7) The names of the Parameters appear
on the Display.
8) When the desired Parameter appears, the
Display will show a Level Number that will
be between 0 and 9. Press either PARAM
(Top Right) or SET (Bottom Right)buttons
to change the Level value.
9) The Display will show the New Level.
10) When you are satisfied with the results of
the changes you have made, Press OUT.
11) The Display asks ARE YOU SURE"?
12) Press ENTER to accept the changes, or
press OUT if you do not wish to accept the
changes and wish to make further
modifications to the parameters.
13) The Display will show :
Page 59
Page 60
SLAVE
motor voltage (%)
frequency (Hz)
encoder (Hz)
slip value (Hz)
current rms (A)
temperature (C)
seat switch (ON/OFF)
forw. switch (ON/OFF)
back. switch (ON/OFF)
enable switch (ON/OFF)
voltage booster (%)
battery voltage (V)
5.6.4 "Dualac2&hp" and "Dualac2&hp Power" Tester: user can verify the state of
the following parameters:
MASTER
motor voltage (%)
frequency (Hz)
encoder (Hz)
slip value (Hz)
current rms (A)
temperature (C)
temperature #1 (C)
temperature #2 (C)
accelerator (V)
steer angle ()
brake pedal poti (%)
int wheel cutback (%)
seat switch (ON/OFF)
forw. switch (ON/OFF)
back. switch (ON/OFF)
enable switch (ON/OFF)
brake switch (ON/OFF)
cutback switch (ON/OFF)
exclusive hydro (ON/OFF)
hand brake (ON/OFF)
voltage booster (%)
battery voltage (V)
battery charge (%)
SLAVE
motor voltage (%)
frequency (Hz)
encoder (Hz)
slip value (Hz)
current rms (A)
temperature (C)
seat switch (ON/OFF)
forw. switch (ON/OFF)
back. switch (ON/OFF)
enable switch (ON/OFF)
lift control (V)
lifting switch (ON/OFF)
1st speed switch (ON/OFF)
2nd speed switch (ON/OFF)
3rd speed switch (ON/OFF)
4th speed switch (ON/OFF)
5th speed switch (ON/OFF)
pump current (A)
pump vmn (V)
pump temperature (C)
battery voltage (V)
voltage booster (%)
5.6.5 Save function (for storing data) --> only with Pc-console
5.6.6 Restore function (for downloading parameters to another controller) --> only
with Pc-console
5.6.7 Display of the last 5 alarms including hour-meter value and temperature at
the moment of the alarm.
5.6.8 Accelerator range programming
Records the minimum and maximum useful accelerator stroke values for both
direction of running.
5.6.9 See the console manual for a detailed description of function and parameters.
Page 61
15) BACKWARD SWITCH: the level of the Reverse direction digital input BW.
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch open.
16) ENABLE SWITCH: the level of the Enable digital input:
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch open.
17) BRAKE SWITCH: the level of the Pedal Brake Microswitch.
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch open.
18) CUTBACK SWITCH: the level of the Speed Reduction Microswitch.
ON / GND = input active, switch opened.
OFF / +VB = input non active, switch closed.
19) EXCLUSIVE HYDRO: status of the exclusive hydro switch.
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch open.
20) HAND BRAKE: the level of the Handbrake Microswitch.
ON / GND = input active, switch opened.
OFF / +VB = input non active, switch closed.
21) VOLTAGE BOOSTER: this is the booster of the voltage supplied to the motor in load
condition; it is expressed in a percentage of the full voltage.
22) BATTERY VOLTAGE: level of battery voltage measured at the input of the key switch.
23) BATTERY CHARGE: the percentage Charge level of the battery.
5.8.2 "Dualac2" and "Dualac2 Power" - Slave
1) MOTOR VOLTAGE: this is the voltage supplied to the motor by the inverter; it is expressed as a percentage of the full voltage (which depends of the battery voltage).
2) FREQUENCY: this is the frequency of the voltage and current supplied to the motor.
3) ENCODER: this is the speed of the motor, expressed in the same unit of the frequency; this information comes from the speed sensor.
4) SLIP VALUE: this is the difference of speed between the rotating field and the shaft
of the motor, expressed in the same unit of the frequency.
5) CURRENT RMS: Root Mean Square value of the motor current.
6) TEMPERATURE: the temperature measured on the aluminum heat sink holding the
MOSFET devices.
7) SEAT SWITCH: the level of the Seat Microswitch digital input.
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch opened.
Page 64
8) FORWARD SWITCH: the level of the Forward direction digital input FW.
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch opened.
9) BACKWARD SWITCH: the level of the Reverse direction digital input BW.
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch opened.
10) ENABLE SWITCH: the level of the Enable digital input:
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch open.
11) VOLTAGE BOOSTER: this is the booster of the voltage supplied to the motor in load
condition; it is expressed in a percentage of the full voltage.
12) BATTERY VOLTAGE: level of battery voltage measured at the input of the key switch.
5.8.3 "Dualac2&hp" and "Dualac2&hp Power" - Master
1) MOTOR VOLTAGE: this is the voltage supplied to the motor by the inverter; it is expressed as a percentage of the full voltage (which depends of the battery voltage).
2) FREQUENCY: this is the frequency of the voltage and current supplied to the motor.
3) ENCODER: this is the speed of the motor, expressed in the same unit of the frequency; this information comes from the speed sensor.
4) SLIP VALUE: this is the difference of speed between the rotating field and the shaft
of the motor, expressed in the same unit of the frequency.
5) CURRENT RMS: Root Mean Square value of the motor current.
6) TEMPERATURE: the temperature measured on the aluminum heat sink holding the
MOSFET devices.
7) TEMPERATURE #1: this is the temperature of the right motor; if the option is programmed "None" (see chapter 5.4.a) it shows 0.
8) TEMPERATURE #2: this is the temperature of the left motor; if the option is programmed "None" (see chapter 5.4.a) it shows 0.
9) ACCELERATOR: the voltage of the accelerator potentiometer's wiper (CPOT). The
voltage level is shown on the Left Hand Side of the Console Display and the value in
percentage is shown on the Right Hand Side.
10) STEER ANGLE: this is the indication of the angular position of the steered wheel.
11) BRAKE PEDAL POTI: voltage of the brake potentiometer's wiper (CPOTB). The
parameter is active only if the PEDAL BRAKING parameter is set ANALOG (see
chapter 5.4.).
12) INTERNAL WHEEL CUTBACK: this is the indication of the speed reduction applied
to the internal wheel; in other words, it shows the ratio of the two speeds.
13) SEAT SWITCH: the level of the Seat Microswitch digital input.
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch open.
Page 65
14) FORWARD SWITCH: the level of the Forward direction digital input FW.
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch open.
15) BACKWARD SWITCH: the level of the Reverse direction digital input BW.
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch open.
16) ENABLE SWITCH: the level of the Enable digital input:
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch open.
17) BRAKE SWITCH: the level of the Pedal Brake Microswitch.
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch open.
18) CUTBACK SWITCH: the level of the Speed Reduction Microswitch.
ON / GND = input active, switch opened.
OFF / +VB = input non active, switch closed.
19) EXCLUSIVE HYDRO: status of the exclusive hydro switch.
ON / +VB = input active, switch closed.
OFF / GND = input non active, switch opened.
20) HAND BRAKE: the level of the Handbrake Microswitch.
ON / GND = input active, switch opened.
OFF / +VB = input non active, switch closed.
21) VOLTAGE BOOSTER: this is the booster of the voltage supplied to the motor in load
condition; it is expressed in a percentage of the full voltage.
22) BATTERY VOLTAGE: level of battery voltage measured at the input of the key switch.
23) BATTERY CHARGE: the percentage Charge level of the battery.
5.8.4 "Dualac2&hp" and "Dualac2&hp Power" - Slave
1) MOTOR VOLTAGE: this is the voltage supplied to the motor by the inverter; it is expressed as a percentage of the full voltage (which depends of the battery voltage).
2) FREQUENCY: this is the frequency of the voltage and current supplied to the motor.
3) ENCODER: this is the speed of the motor, expressed in the same unit of the frequency; this information comes from the speed sensor.
4) SLIP VALUE: this is the difference of speed between the rotating field and the shaft
of the motor, expressed in the same unit of the frequency.
5) CURRENT RMS: Root Mean Square value of the motor current.
6) TEMPERATURE: the temperature measured on the aluminum heat sink holding the
MOSFET devices.
Page 66
22) VOLTAGE BOOSTER: this is the booster of the voltage supplied to the motor in load
condition; it is expressed in a percentage of the full voltage.
23) BATTERY VOLTAGE: level of battery voltage measured at the input of the key switch.
Flow Chart showing how to use the TESTER function of the Digital Console.
1) Opening Zapi Display.
2) Press ENTER to go into the General menu.
3) The Display will show :
4) Press ROLL UP or ROLL DOWN button until
TESTER MENU appear on the display.
5) The Display shows :
6) Press ENTER to go into the TESTER function.
7) The first variable to be tested is shown on the Display.
8) Press either ROLL UP or ROLL DOWN buttons until your
desired variable for measurement appears on the Display.
Remember it is not possible to make any changes using TESTER. All you can do is
measure as if you were using a pre-connected multimeter.
Page 68
6 OTHER FUNCTIONS
6.1 SAVE AND RESTORE FUNCTION
SAVE function allows to transfer controller parameters to the Pc console memory. With this
function, a copy of the controller set of parameters can be retained in a Pc and
downloaded to another controller (see RESTORE).
RESTORE function allows to download controller parameters from the Pc console memory
to the controller Eeprom. Thus a copy of the parameters stored in a Pc can be downloaded
in a controller avoiding the parameter setting operation.
For more details, please refer to Pc console manual.
Page 69
Page 70
Page 71
ALARM
STRING
Mast- Slave
CONTROLLER
er
DESCRIPTION
STATUS
Init
Stby Motor
running
"WATCHDOG"
17
"LOGIC
FAILURE#3"
protection hw circuit
+ activation of traction
request
18
"LOGIC
FAILURE#2"
+ activation of traction
request
19
"LOGIC
FAILURE#1"
Alarm: an overvoltage or
30
"VMN LOW"
alarm condition
motor
is necessary to remove
alarm condition and to
activate a traction request
31
"VMN HIGH"
alarm condition
motor
is necessary to remove
alarm condition and to
activate a traction request
Page 72
Co
de
ALARM
STRING
Mast- Slave
CONTROLLER
er
DESCRIPTION
STATUS
Init
Stby
Motor
running
53
"STBY I HIGH"
feedback circuit
alarm condition
-If the alarm has occurred
in stby or running mode, it
is necessary to remove
alarm condition and to
activate a traction request
60
"CAP
CHARGE"
74
"DRIVER
SHORTED"
75
"CONTACTOR
DRIVER"
request
correct voltage)
76
"COIL
SHORTED"
Alarm:
on LC coil or EB coil
is necessary to remove
alarm cause and to activate
traction request
37
"CONTACTOR
CLOSED"
Page 73
Co
de
ALARM
STRING
Mast- Slave
CONTROLLER
er
DESCRIPTION
STATUS
status
running
38
"CONTACTOR
OPEN"
pull-in
timeout is elapsed, it is
necessary to re-cycle the
key
82
"ENCODER
ERROR"
84
"STEER
SENSOR KO"
86
"PEDAL WIRE
KO"
BATTERY"
programmation
246
"SLAVE KO"
malfunctioning or a
mismatch between inputs
status and Master
commands (via Canbus)
250
"INPUT
detects a mismatch
MISMATCH"
shorted or open
Page 74
Co
de
ALARM
STRING
Mas- Slater
CONTROLLER
ve
DESCRIPTION
STATUS
status
running
13
"EEPROM KO"
"HIGH
or both temperature
TEMPERA-
TURE"
65
"MOTOR
"VACC NOT
LOW"
78
high
TURE"
"BATTERY
TEMPERA66
Warning: accelerator
OK"
79
"INCORRECT
START"
80
"FORWARD +
request sequence
X
BACKWARD"
active
249
"THERMIC
SENSOR KO"
of range
251
"WAITING
FOR NODE#4"
Warning: Master C
251
"WAITING
"NO CAN
FOR NODE#3"
241
Warning: Slave C
MESSAGE #4"
247
"NO CAN
MESSAGE #3"
Page 75
When the key is switched ON, the inverter tries to charge the capacitor through a power
resistance, and check if the capacitor are charged within a timeout. If they do not
charge, an alarm is signalled; the main contactor is not closed.
Page 76
Possible reasons:
a) the charging resistance is opened.
b) The charging circuit has a failure.
c) There is a problem in the power section.
8. MAIN CONTACTOR ALARMS
COIL SHORTED:
When the key is switched ON the Controller checks the LC coil driver shortcircuit
protection hardware. If it does not react in a correct way to the C stimulus, the alarm is
signalled. Replace the logic board. When the fault occurs while the LC is closed, the
alarm signals a shortcircuit across LC coil.
Check if there are external shortcircuit and if the ohmic value of the MC coil is correct;
otherwise replace the logic.
DRIVER SHORTED:
When the key is switched ON, the C checks that the LC coil driver is not shorted; if it
is, this alarm is signalled. Preliminary, check if there is an external short or low impedance pull-down between NLC (C26) and -BATT. If no external causes can be found out,
replace the controller.
CONTACTOR DRIVER:
When the initial diagnosis is finished, the traction logic closes the LC and checks the
voltage on the Drain of the driver. If this is not low , the driver is not able to close an
alarm is signalled. Replace the logic.
CONTACTOR OPEN:
The main contactor coil has been driven by the logic board, but the contactor does not
close. Two possible reasons:
a) the wires to the coil are interrupted or not well connected.
b) the contact of the contactor is not properly working (does not pull-in).
CONTACTOR CLOSED:
Before driving the LC coil, the controller checks if the LC contact is stuck. The controller
drives the bridge for a while, trying to discharge the capacitor bank. If they don't discharge, the fault condition is entered. It is suggested to check the contactor contact, if it
is mechanically stuck.
9. ENCODER ERROR
This alarm is signalled in following condition: the frequency supplied to the motor is
higher than 20 Hz, and the signal feedback from the encoder has a jump higher than 20
Hz in few tens millisecond. This condition clearly shows a malfunctioning of the encoder
signal. It is suggested to preliminary check the encoder wiring; if no fault is found in the
wiring it is necessary to replace the encoder.
Page 77
Page 78
17. EEPROM KO
Fault in the area of memory in which the adjustment parameters are stored; this alarm
does not inhibits truck operation, but the controller will use default parameters. If the
defect persists when the key is switched OFF and ON again, replace the logic. If the
alarm disappears, remember that the parameters stored previously have been cancelled and replaced by the default values.
18. HIGH TEMPERATURE
Master or Slave or both temperatures are greater than 75C. The maximum current is
reduced proportionally to the temperature increase. At 100C the max current of both
inverter is reduced to zero.
If the alarm is signalled when the controller is cold:
a) thermal sensor failure;
b) failure in the logic card.
19. MOTOR TEMPERATURE
This warning is signalled if right or left or both motors temperature switches open
(digital sensor) or if the analog signals overtakes the cut off level. If it happens when the
motor is cold, check the wiring. If all is ok, replace the logic board.
20. BATTERY LOW
If the "battery check" option is ON, a battery discharge algorithm is carried out. When
the charge level is 20% , this alarm is signalled and the current is reduced to the half of
the programmed level.
21. VACC NOT OK
The test is made in standby. This alarm indicates that the accelerator voltage is 1V
greater than the minimum value programmed by the PROGRAM VACC function.
Possible causes:
a. the potentiometer is not correctly calibrated;
b. the potentiometer is defective.
22. INCORRECT START
This alarm signals an incorrect starting sequence. Possible causes:
a. Fw or Rev or Enable microswitch failure;
b. error in sequence made by the operator;
c. incorrect wiring;
d. if the default persists after checking the harness, replace the logic.
23. FORW + BACK
The test is carried out continuously. An alarm is signalled when a double running request is made simultaneously. Possible causes:
a. defective wiring;
b. running microswitch failure;
c. incorrect operation;
d. if the defect persists, replace the logic.
Page 79
Page 80
Co
de
ALARM
STRING
Mas- Slater
CONTROLLER
ve
DESCRIPTION
STATUS
Init
Stby
Motor
running
28
"PUMP VMN
LOW"
applied PWM
56 "PUMP STBY I
HIGH"
cause
window
242
"PUMP
Sla-
TEMPERAT."
chopper temperature is
ve
242
"PUMP"
Ma-
ster
243
"PUMP INC.
START"
244 "PUMP VACC
MOTOR"
start sequence
X
Page 81
Page 82
Part Number
Description
C16507
C16505
C16520
C29523
SW 180 80V
Single Pole Contactor
C29522
SW 180 48V
Single Pole Contactor
C29508
SW 180 24V
Single Pole Contactor
Page 83
Page 84
DUALAC2 INVERTER
OPERATING HANDBOOK
AND FUNCTION DESCRIPTION