EE3741 L6 Switchgear and Protection
EE3741 L6 Switchgear and Protection
y
protection
p
and circuit
breaker
Subject lecturer: Dr. XU Zhao
Department of Electrical Engineering
Hong Kong Polytechnic University
Email: [email protected]
Room: CF632
Tel: 27666160
Switching
S it hi
d
devices
i
and
d mechanism
h i
and
d selection
l ti
Arc extinction and recovery voltage
AC/DC
AC/DC currentt interruption
i t
ti
chopping
h
i
Protection system
Protection zones and
d coordination
d
h
hand
d selection
l
of protection
Over
O
currentt relay
l
and
d differential
diff
ti l and
d distance
di t
protection
Fault
F lt currentt tto size
i the
th circuit
i
it breaker
b
k
Customer sizing CB, normally short circuit
MVA is g
given by
y system
y
operator
p
in MVA
at the point of connection, equivalent to
specify
p
y
- SC current
- Reciprocal of Thevenin impedance of the
system at the point of connection
If Base kV = nominal kV
CB sizing
The current is the key
The maximum instantaneous current the break must carry:
For AC circuit fault maximum fault current should include both
DC +AC
AC components (DC+
(DC subtransient
b
i
+transient
i
+steady
d
state)
Total current the breaker contact part to interrupt the circuit
CB sizing
CB breaking process
CB has different speeds and also
classified into rated interrupting times:
time from energizing of trip circuit to the
arc extinction
Tripping delay usually cycle : between
fault occurrence and energizing of
tripping circuit
Often unsymmetrical fault current
remains at point of interruption
But the CB is normally rated according
to only symmetric current
(subtraseint/transient)
6
CB rating
Voltage class
Rated continuous current
Rated maximum voltage:
highest RMS voltage which
the CB is designed for
Voltage range factor K: the
ratio of rated max voltage
over th
the llower li
limit
it off
range of operating voltage
Rated SC current at rated
maximum kv
Maximum symmetric
interrupting
capability=k*rated SC
current
Classification of Relays
Based on apparatus
System protection
12
Line protection
Transformer protection
p
Generator protection
Others equipments, such as capacity
b k etc
banks,
t
Out-of-Step protection
Under/Over frequency relays
System islanding
df/dt relay
l
S
Some
Definitions
fi i i
Pickup level
Reset level
14
Reset time
Operating time
The value
Th
l
off actuating
t ti
quantities
titi
on the
th threshold
th
h ld above
b
which the relay operates.
15
16
Basic relay
y operating
p
g
pricinples
Electromagnetic-induction type
Use the principle of the induction motor whereby
torque is developed by induction in a rotor.
rotor
Only actuated by AC quantities due to the principle
Single-quantity or directional types
17
Electromagnetic--attraction type
Electromagnetic
For single quantity relay, electromangetic force exerted on the moving
element is proportional to the square of the flux in the air gap. The net
actuating force is
K1 = Force-conversion constant
I = The RMS magnitude of the current in the actuating coil
K2 = The restraining force (including friction)
(2)
K1 = Force-conversion constant
IP = The magnitude of the current in the polarizing coil
Ia = The magnitude of the current in the armature coil
K2 = The restraining force (including friction)
18
Shaded pole
structure
t
t
19
Watthour-meter structure
Induction-cup
structure
EE3741 Ass. Prof Zhao Xu
Electromagnetic--Induction Type
Electromagnetic
From Fig. 4, The quantities in Fig. 5 can be expressed, where is the phase angle by
which
leads
,
Assuming the paths rotor currents flow have negligible self inductance, hence the rotor
currents are in phase with the voltage,
20
Current-current relays
Voltage-voltage relays
Fig. 6 Vector diagram for maximum torque
in a current-voltage
u
o ag directional
d
o a relay.
ay
21
22
23
Primary relay
Back-up relay
Overcurrent Relays
Indicator solely on the magnitude of current
When the current in a system exceeds a predetermined value, it
indicates the presence of a fault.
Fixed time delay is provided for the operation. It can be used as the
backup relay for instantaneous relay.
25
Operating Characteristics
27
Distance Relay
Indicator based on the measured impedance
Most interesting and versatile family of relays
Can be used in various voltage levels
Not impacted by the network configurations
Basic types
Impedance relays
Reactance relyas
mho relays
28
Reactance Relay
y Princples
p
The reactance relay only response to the reactance component of the
impedance. The operating torque is obtained by current (positive)
and the restraining torque due to a current/voltage directional
element (either positive or negative).
The directional element is arranged to develop maximum negative
torque when current lags voltage by 90 degree
degree. The torque equation
is
is defined as positive when I lags V
At the
h balance
b l
point, T = 0, h
hence
From this we can derive
so
Neglecting control spring effect,
Fig. 10 Operating characteristic of
an reactance relay
30
Therefore
Fig. 11 Mho characteristics
It is seen from Fig. 11 that
Mho relay is inherently directional.
directional
The impedance angle of the protected line is normally a 60 to 70
degrees.
31
32
Relay applications
Feeder protection
Generator protection
Transformer protection
33
Feeder protection
3-zone p
protection coordination are widely
y applied
pp
for
overcurrent and distance relays
One primary protection, two backup protections
A certain time delay is applied to backup protections . The
setting of time delay has to consider the relays operation
time, the safety time, etc.
Differential Relays
The differential relay is one that operates when the vector difference
of two or more similar electrical quantities exceeds a pre-determined
value.
It takes two or more similar electrical quantities
These quantities should have phase displacement (normally approx. 180
degree)
Generator Protections
Other than line protection, generator protection concerns against
more possible abnormal operating conditions since it is not
necessarily required to remove the service of a machine from short
circuits that might be left to the control of an attendant.
The automatic protective equipment is necessary to protect the
generator from damage as well as maintain the service when its
removal would be embarrassing, but it might operate incorrectly with
high amount of equipments.
The quality of the generator protection is not necessarily determined
by the size of the generator, but the effect on the rest of the system
of a prolonged fault in the generator.
36
Overcurrent relay
Used when installation of differential relays cannot be justified
37
C -Stator
CTCT
S
Differential
iff
i l Relay
l
Arrangement
The elements of relay include
CT
Circuit breaker
Relay
Types of connection
Wye-connected
Delta-connected
Oth Stator
Other
St t
P t ti
Protections
Overcurrent protection
If current transformers are not connected in the neutral ends of Yconnected generator windings, relay can be actuated only by the shortcircuit current supplied by the system.
Cannot provide as good protection as differential relay
Overheating protection
May caused by overloading or by failure of the cooling system. The
practice is to embed resistance temperature-detector coils in the stator
winding
i di
slots
l t tto obtain
bt i the
th temperature
t
t
conditions
diti
th
throughout
h t the
th stator.
t t
Alarm devices are usually involved.
39
R t
Rotor
P t ti
Protections
Overheating protection
Unbalanced 3-phase stator currents cause double-system-frequency
currents induced in the rotor iron. These currents will quickly cause rotor
o e heating if the gene
overheating
generator
ato is permitted
pe mitted to continue
contin e operating
ope ating with
ith such
s ch
an unbalance.
Recommended type of relay is an inverse-time overcurrent relay
operating from the output of a negative
negative-phase-sequence-current
phase sequence current filter
that is energized from the generator CT.
Loss-of-excitation protection
Synchronous generator will operates as an induction generator.
generator Instability
problem may be developed quickly since it may draw large amount of
reactive power from the system, unless other generators can
automatically pick up the additional reactive load immediately.
Field protection
Overexcitation protection, vibration protection, etc.
40
Transformer Protections
Abnormal circumstances
41
42
43
B hh l Relay
Buchholz
R l
Buchholz relay is a combination gas-accumulator and pressure relay
named after the inventor. This relay is applicable to the transformer
in which the tank is filled with oil, and a pipe connects to an auxiliary
tank, or conservator, which acts as an expansion chamber.
Whenever
Wh
a fault
f l takes
k place
l
in a transformer, the oil of the
tank gets overheated and
gases are formed.
f
d The
Th generation
ti
of the gases may be slow or
violent depending on whether the
fault is a minor or incipient one
or heavy short circuit. The
generation of gas is used as a
means of fault detection.
detection