Stability Check of Foundation: 1.0 Weight For Slab

This document provides design calculations for the foundation of a new asphalt production building. It calculates the various loads that will bear on the foundation, including the weight of the building structure, equipment, and potential blast loads. It then checks that the foundation will be stable against sliding and overturning. The calculations show that the total resisting friction force is 1.2 times the maximum sliding force, and the total resisting moment is 5.7 times the maximum overturning moment, meeting the safety factor requirements.

Uploaded by

maan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
94 views3 pages

Stability Check of Foundation: 1.0 Weight For Slab

This document provides design calculations for the foundation of a new asphalt production building. It calculates the various loads that will bear on the foundation, including the weight of the building structure, equipment, and potential blast loads. It then checks that the foundation will be stable against sliding and overturning. The calculations show that the total resisting friction force is 1.2 times the maximum sliding force, and the total resisting moment is 5.7 times the maximum overturning moment, meeting the safety factor requirements.

Uploaded by

maan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Project:

Contract No:

EXPAND ASPHALT PRODUCTION FACILITIES, RTR

Description:

10-01265-0001

Calc No:

DESIGN CALCULATION FOR PIB


BUILDING FOUNDATION

RE861874

Stability check of Foundation


1.0 Weight for slab
Length of building =
Width of building =

30
15.1

m
m

Height of Building =

7.2

800Thk slab
250 thk wall

18100
mm

450 thk slab


3000

33000
FOUNDATION PLAN

mm

mm

Project:

Contract No:

EXPAND ASPHALT PRODUCTION FACILITIES, RTR

Description:

10-01265-0001

Calc No:

DESIGN CALCULATION FOR PIB


BUILDING FOUNDATION

RE861874

450

mm

800
mm

3000

3000

mm
33000

mm

mm

Thickness of slab at middle portion =


Thickness of slab at Edge portion =

450
800

mm
mm

Weight of MAT =

8695 kN

Load from walls and roof


Weight of external wall =
3897 kN
(2 x 15.1x 6 + 2 30 x6 ) x 0.25 x 24
Weight of Double Tee Roof panels +finishes =3860 kN
( 8.47 x 15.1 x 30 )
Total weight from wall and roof =
16452 kN

(Refer Load calculation)

Forces on structure
Reflect overpressure on front wall =

47.67 kN/m^2

(Refer Load calculation)

Roof overpressure =

21.44 kN/m^2

(Refer Load calculation)

Vertical load due to blast V =


( 21.4 x 15.1 x 30)
Load on Base slab
Weight of internal wall =
Weight of AHU unit =
Weight of AHU Ped =
( Ignoring all other deal load on floor)
Total load on base slab Wb =
Total Restoring load Wr
=
(16452+9711+1909)
Check for Sliding :Total sliding force in Blast load caseFs =
( 47.6 x 30 x 7.2)
Friction between concrete and soil =
Resisting force Fr( m*Wr) =
F.O.S Fr / Fs =

9711 kN

1651 kN
150 kN
108 kN

(31.44 x 30 + 3 x 31.55 x 7.5 -Refer load calc)


( Assumed 7.5MT each)
( 24 x 3 x 5 x 0.15 )

1909 kN
28071 kN

10297 kN
0.44

( Refer Doc- SK 16000072 Rev 2,Pg no 17)

12351 kN
1.20

>= 1.0Hence OK
As per SAES-M-009,7.7.2.1)

Project:

Contract No:

EXPAND ASPHALT PRODUCTION FACILITIES, RTR

Description:

10-01265-0001

Calc No:

DESIGN CALCULATION FOR PIB


BUILDING FOUNDATION

Check for Overturning :Total Overturning Moment Mo =


( 47.6 x 30 x 7.2 x 7.2 / 2)
Total Restoring Moment Mr =
( Wr + Wb + V) b/2
F.O.S Mr / Mo =

37070.135 kN m
211937.93 kN m
5.717

>

1.2 Hence OK