MSLC Master Synchronizer and Load Control: Installation and Operation Manual
MSLC Master Synchronizer and Load Control: Installation and Operation Manual
MSLC Master Synchronizer and Load Control: Installation and Operation Manual
MSLC
Master Synchronizer and Load Control
9907-004 (4-Wire Wye)
9907-005 (3-Wire Delta, 120 V)
9907-006 (3-Wire Delta, 240 V)
WARNINGOUT-OF-DATE PUBLICATION
This publication may have been revised or updated since this copy was produced. To verify
that you have the latest revision, be sure to check the Woodward website:
www.woodward.com/pubs/current.pdf
The revision level is shown at the bottom of the front cover after the publication number. The
latest version of most publications is available at:
www.woodward.com/publications
If your publication is not there, please contact your customer service representative to get
the latest copy.
WARNINGOVERSPEED PROTECTION
The engine, turbine, or other type of prime mover should be equipped with an overspeed
shutdown device to protect against runaway or damage to the prime mover with possible
personal injury, loss of life, or property damage.
The overspeed shutdown device must be totally independent of the prime mover control
system. An overtemperature or overpressure shutdown device may also be needed for
safety, as appropriate.
WARNINGPROPER USE
Any unauthorized modifications to or use of this equipment outside its specified
mechanical, electrical, or other operating limits may cause personal injury and/or property
damage, including damage to the equipment. Any such unauthorized modifications: (i)
constitute "misuse" and/or "negligence" within the meaning of the product warranty
thereby excluding warranty coverage for any resulting damage, and (ii) invalidate product
certifications or listings.
CAUTIONELECTROSTATIC DISCHARGE
Electronic controls contain static-sensitive parts. Observe the following precautions to
prevent damage to these parts.
Discharge body static before handling the control (with power to the control turned off,
contact a grounded surface and maintain contact while handling the control).
Avoid all plastic, vinyl, and Styrofoam (except antistatic versions) around printed circuit
boards.
Do not touch the components or conductors on a printed circuit board with your hands
or with conductive devices.
IMPORTANT DEFINITIONS
A WARNING indicates a potentially hazardous situation which, if not avoided, could result in
A CAUTION indicates a potentially hazardous situation which, if not avoided, could result in
A NOTE provides other helpful information that does not fall under the warning or caution
Woodward Governor Company reserves the right to update any portion of this publication at any time. Information
provided by Woodward Governor Company is believed to be correct and reliable. However, no responsibility is
assumed by Woodward Governor Company unless otherwise expressly undertaken.
Woodward 1993
All Rights Reserved
Manual 02022
Contents
CHAPTER 1. GENERAL INFORMATION ........................................................... 1
Introduction.............................................................................................................1
Application ..............................................................................................................1
Synchronizer...........................................................................................................1
Load Control ...........................................................................................................2
Process Control ......................................................................................................2
VAR/PF Control ......................................................................................................3
Manual Organization ..............................................................................................3
Manual 02022
Contents
CHAPTER 6. REAL POWER CONTROL .........................................................61
Introduction ...........................................................................................................61
Power Sensor Theory of Operation......................................................................61
Load Sensor Hardware Description .....................................................................62
MSLC/DSLC Interface ......................................................................................62
Base Load Mode ..................................................................................................62
Import/Export Mode ..............................................................................................62
Process Control Mode ..........................................................................................63
Remote Control ....................................................................................................63
Automatic Power Transfer Control Functions ......................................................63
ii
Woodward
Manual 02022
Woodward
iii
iv
Manual 02022
Woodward
Manual 02022
Chapter 1.
General Information
Introduction
This manual describes the Woodward MSLC Master Synchronizer and Load
Control.
Application
The MSLC is a microprocessor-based overall plant load control designed for use
in a system with Woodward DSLC (Digital Synchronizer and Load Control)
controls on each generator to provide utility synchronizing, paralleling, loading,
and unloading of a three-phase generating system.
MSLC functions include:
Multi-function adjustable high and low limit alarms and adjustable load
switches with relay driver outputs;
Synchronizer
The MSLC uses digital signal processing techniques to derive both true RMS
voltages and relative phase angles of the fundamental frequencies of the utility
and the local bus voltage wave forms. Digital signal processing techniques offer
significantly improved measurement accuracy in the presence of wave form
distortions, particularly since the phase measurement does not depend on zero
crossings of the voltage wave forms.
Either phase matching or slip frequency synchronizing may be selected. Phase
matching provides rapid synchronizing for critical standby power applications.
Slip frequency synchronizing ensures that the initial flow of power will be either
out of the local system (export) or into the local system (import), depending on
whether a positive or negative slip is chosen. For both synchronizing methods,
the MSLC uses actual slip frequency and breaker delay values to anticipate an
adjustable minimum phase difference between the utility and the local bus.
Additional synchronizer functions include voltage matching, time delayed
automatic multi-shot reclosing, auto-resynchronizing, and a synchronizer timeout
alarm. Each of these features may be enabled or disabled during setup.
Woodward
Manual 02022
Load Control
The load control uses digital signal processing techniques to provide significantly
improved accuracy and speed of response over conventional analog
measurement techniques. Accuracy is improved because the instantaneous
measurement of the voltage and current signal wave forms allows true RMS
measurement. Measuring true RMS power allows optimal load control in parallel
applications even in the presence of power line distortions. This method provides
faster response time because it eliminates the long integration times required in
analog circuits. Measurement speed is particularly important in power control
applications where rapid response to load and speed changes is essential.
Load control begins at breaker closure when the MSLC takes control of the
system load. The system load immediately prior to breaker closure is used as the
starting base load. On command, the adjustable ramp allows smooth, timecontrolled loading into a set import/export level. A ramp pause switch is provided
to stop the ramp at any point.
The import/export control is an integrating control. It adjusts the percentage of
rated load carried by the individual generators, operating in isochronous load
sharing, in order to maintain a set import/export or base load level. The MSLC
will therefore maintain a constant base load or import/export level even with
changing utility frequencies. The MSLC provides switch inputs to allow raising or
lowering the internal digital base load or import/export reference. The control also
provides a 420 mA (15 Vdc) analog input for remote reference setting, if
desired.
The MSLC is equipped with a Utility Unload switch, which provides an adjustable
time controlled ramp to lower the base load or import/export level. When the level
is below an adjustable threshold, the MSLC issues a breaker open command to
separate the utility from the local bus. Again, the ramp pause switch can be used
to stop the utility unload at any point. The maximum load that the MSLC can tell
the individual generators to carry is their rated loads. So, in the event that the
plant load is greater than the capacity of the operating generators, the utility
unload will stop when 100% rated load is reached on each of the operating
generators. This prevents accidental overloading of the local generators when a
reduced number are on line.
The MSLC also includes two adjustable load switches which can be used for
external functions or warnings when chosen system load levels are attained. The
high and low limit switches may also be activated when 100% or 0% base load
signal to the generators is reached.
Process Control
A process controller is provided for cogeneration, fluid level maintenance,
pressure control, or other applications. An adjustable bandwidth signal input
filter, flexible PID controller adjustments, an adjustable deadband, and control
selectable for direct or indirect action, allow the process control to be used in a
wide variety of applications.
A 420 mA (15 Vdc or a 41220 mA) process transmitter provides the process
signal to the MSLC. The MSLC includes an internal digital process reference
which may be controlled by the raise and lower switch contact inputs or by an
external 420 mA (15 Vdc) remote process reference. The output of the
process control, like the import/export control, is the percentage of rated load
setpoint to the individual generators in isochronous load sharing.
2
Woodward
Manual 02022
An adjustable ramp allows smooth entry and exit from the process control mode.
When the process control mode is selected, the load reference is ramped in a
direction to reduce the error between the process input and the process
reference. When the error is minimized or the reference first reaches either the
high or low specified pull-in limits, the process controller is activated. When the
load reference output reaches either 100% or 0%, the control will maintain that
load reference until process control is established. The MSLC is not capable of
overloading or reverse powering in order to attempt to meet the process
reference. The high and low limit switches mentioned above can be used to
indicate that either too many or too few generators are on-line to maintain the
process within its limits.
VAR/PF Control
The VAR/PF function controls the power factor on all of the DSLC equipped
machines operating in isochronous load sharing. The PF control begins on
breaker closure. The MSLC has three modes of VAR/PF control (which are
selected in Menu 4):
Utility Tie Power Factor Controladjusts the power factor reference on all of
the DSLC controls in isochronous load sharing in order to maintain the
power factor across the utility tie.
Utility Tie VAR Controladjusts the power factor reference on all of the
DSLC controls in isochronous load sharing in order to maintain the level of
reactive load being imported or exported from the utility.
Manual Organization
Woodward
Manual 02022
Woodward
Manual 02022
Woodward
Manual 02022
Woodward
Manual 02022
Woodward
Manual 02022
Woodward
Manual 02022
Woodward
Manual 02022
Chapter 2.
Electrostatic Discharge Awareness
All electronic equipment is static-sensitive, some components more than others.
To protect these components from static damage, you must take special
precautions to minimize or eliminate electrostatic discharges.
Follow these precautions when working with or near the control.
1.
2.
Avoid the build-up of static electricity on your body by not wearing clothing
made of synthetic materials. Wear cotton or cotton-blend materials as much
as possible because these do not store static electric charges as much as
synthetics.
3.
4.
Do not remove the printed circuit board (PCB) from the control cabinet
unless absolutely necessary. If you must remove the PCB from the control
cabinet, follow these precautions:
When replacing a PCB, keep the new PCB in the plastic antistatic
protective bag it comes in until you are ready to install it. Immediately
after removing the old PCB from the control cabinet, place it in the
antistatic protective bag.
CAUTIONELECTROSTATIC DISCHARGE
To prevent damage to electronic components caused by improper handling,
read and observe the precautions in Woodward manual 82715, Guide for
Handling and Protection of Electronic Controls, Printed Circuit Boards, and
Modules.
10
Woodward
Manual 02022
Chapter 3.
Installation
Introduction
This chapter provides the general information for site selection, installation, and
wiring of the MSLC.
Unpacking
Before unpacking the control, refer to the inside front cover of this manual for
WARNINGS and CAUTIONS. Be careful when unpacking the control. Check for
signs of damage such as bent or dented panels, scratches, loose or broken
parts. If any damage is found, immediately notify the shipper.
Location
When selecting a location for mounting the MSLC, consider the following:
Provide adequate ventilation for cooling. Shield the unit from radiant heat
sources.
Installation
Select a mounting location for the MSLC (see considerations above). Locate and
drill six (6) holes for mounting hardware (not furnished; see Figure 1-1 for
locations). Tap the holes for machine screws or bolts. Install the unit and secure
with the mounting hardware.
Electrical Connections
This section covers typical wiring connections, as shown in Figure 1-3. For other
applications, contact Woodward Governor Company for assistance.
Connect the terminals as shown in Figure 1-3. When making the connections,
observe the following:
Make all connections using insulated terminals. Use 0.5 mm2 (20 AWG) or
larger stranded wire.
Make sure that all wires shown as shielded on the wiring diagram are
stranded, twisted-pair, shielded wire.
Do not place shielded wires in the same cable conduits with high-voltage or
high-current carrying cables.
Woodward
11
Manual 02022
Connect the cable shields to chassis ground. Shields are grounded at the
control end only for inputs and at the speed control and voltage regulator
end for outputs.
Make sure that cable shields are carried through all intermediate terminal
blocks from signal source to signal termination.
Do not subject any wiring to temperatures above 100 C (212 F).
Avoid kinks or sharp bends in the wiring. Make sure that all connections are
tight.
Shielded Wiring
All shielded cable must be twisted conductor pairs. Do not attempt to tin the
braided shield. All signal lines should be shielded to prevent picking up stray
signals from adjacent equipment. Wire exposed beyond the shield should be as
short as possible, not exceeding 50 mm (2 inches). The other end of the shields
must be left open and insulated from any other conductor. Do NOT run shielded
signal wires along with other wires carrying large currents. See Woodward
application note 50532, Interference Control in Electronic Governing Systems for
more information.
Where shielded cable is required, cut the cable to the desired length and prepare
the cable as instructed below.
1. Strip outer insulation from BOTH ENDS, exposing the braided or spiral wrapped
shield. DO NOT CUT THE SHIELD.
2. Using a sharp, pointed tool, carefully spread the strands of the shield.
3. Pull inner conductor(s) out of the shield. If the shield is the braided type, twist
it to prevent fraying.
4. Remove 6 mm (1/4 inch) of insulation from the inner conductors.
5. Connect wiring and shield as shown in plant wiring diagram.
Installations with severe electromagnetic interference (EMI) may require
additional shielding precautions, such as wire run in conduit or double shielding.
Power Supply
The MSLC requires a nominal voltage source of 20 to 40 Vdc. Power to the
control should be maintained whenever the generator set is available for service.
CAUTIONAPPLY POWER
Power must be applied to the MSLC at least 15 seconds prior to expected
use. The control must have time to do its power up diagnostics and
establish its location in the local area network to become operational.
Failure of the diagnostics will disable control function and de-energize the
alarm relay.
12
Woodward
Manual 02022
Power supply output must be of a low impedance type for proper operation of the
control. DO NOT power a control from a high voltage source containing dropping
resistors and zener diodes. If batteries are used for operating power, an
alternator or other battery charging device is necessary to maintain a stable
supply voltage.
Run power supply leads directly from the power source to the control, connecting
the negative (neutral) lead to terminal 1, and the positive lead (line) to terminal 2.
DO NOT POWER OTHER DEVICES WITH LEADS COMMON TO THE
CONTROL. Avoid long wire lengths.
NOTE
The MSLC receives its current and voltage input signals from standard
metering current transformers (CTs) and potential transformers (PTs). The
selection of these PTs and CTs will have an effect on synchronizer voltage
and phase matching and load sensing accuracy. Identical potential
transformers should be used for the generator and bus voltages. CTs should
provide 5 A RMS at full load for best performance of the system.
The following sections describe the potential connections for the
synchronizer and power sensor functions. The MSLC real power sensor is
available in either a four-wire, three-sensor device, which measures only
line-to-neutral voltages, or in a three-wire, three-sensor device which
measures only line-to-line voltages. The voltage sensing configuration
options are described by the WYE and Delta part number versions.
When connected to 4-wire wye systems with 120/240 Vac line-to-neutral
voltages, no potential transformers are required. Higher voltage systems
require potential transformers to reduce voltages to the 120/240 nominal
range.
Typically, 3-wire delta systems will always require potential transformers to
reduce the line-to-line voltages to the proper levels needed at the input to
the control (either 120 or 240 Vac, depending on the control part number).
Woodward
13
Manual 02022
NOTE
If the local bus PT input is not connected in the same configuration as the
utility bus PT inputs, a phase offset will have to be calibrated into the local
bus PT (see Chapter 4, Phase Matching Synchronizer).
For example, if a WYE version MSLC has the utility bus PT inputs connected
in a four-wire WYE configuration, and the local bus PT input is connected to
sense line-to-line voltage, a phase offset will need to be calibrated into the
synchroscope for proper phase angle indication, and synchronizer
operation. See Chapter 4, Phase Matching Synchronizer for more
information.
WARNINGELECTRIC SHOCK
Because of the risk of fatal electric shock, never disconnect any wire
attached to the utility current transformers (terminal 13 through 18) when the
utility feeder is energized or has the potential of becoming energized, unless
a shorting terminal block and temporary 1 A, 5 W resistors are installed as
shown in Figure 3-1.
Discrete Outputs
The discrete outputs are the relay driver output commands from the MSLC. Each
optically isolated discrete output is designed as a low-side driver capable of
sinking a maximum of 200 mA. The use of drivers allows the user to supply
relays of a contact rating appropriate for the particular application.
14
Woodward
Manual 02022
Alarm Relay
Make the alarm relay connection as shown in Figure 1-3 to terminal 28 of the
MSLC. Alarm conditions are selectable by the user (see tables in Chapter 4).
Woodward
15
Manual 02022
Discrete Inputs
The discrete inputs are the switch input commands to the MSLC. Discrete inputs
are optically isolated from the control and require 10 mA at 24 Vdc each to
activate. Discrete inputs may be powered by the same source as control power.
All contacts used in the discrete circuits should be the isolated dry contact type to
work properly with the low currents used in these circuits.
Connect the 24 Vdc supply common () to terminal 43. Route +24 Vdc through
the appropriate external contact to the discrete input.
CB Aux Contact
Connect the utility breaker auxiliary (CB Aux) contact that opens and closes
when the utility tie breaker opens and closes. Wire the breaker auxiliary contact
in series between the +24 Vdc voltage source and terminal 47 of the MSLC. In
addition, it may be desirable to put an MSLC ON/OFF switch in series with this
input.
16
Woodward
Manual 02022
Woodward
17
Manual 02022
18
Woodward
Manual 02022
Check for correct wiring in accordance with the wiring diagram, Figure 1-3.
2.
3.
Check for shield faults by measuring the resistance from control terminals to
chassis. If a resistance less than infinite is obtained, remove the
connections from each terminal one at a time until the resistance is infinite.
Check the last line removed to locate the fault.
Woodward
19
Manual 02022
Chapter 4.
Calibration and Adjustments
Introduction
Because of the variety of installations, plus system and component tolerances,
the MSLC must be tuned to each system for optimum performance.
This chapter contains information on control calibration. It includes initial prestartup and start-up settings and adjustments.
20
Not used.
Not used.
Toggles between the two displayed items (the first letter of the
active menu item will blink).
Moves backward through each menu, one step at a time.
Advances through each menu, one step at a time.
Increases the displayed set point value slowly.
Decreases the displayed set point value slowly.
Increases the displayed set point value quickly.
Decreases the displayed set point value quickly.
Not used.
Not used.
Not used.
Displays the MSLC control part number and software revision
level.
Not used.
Saves entered values (set points).
Not used.
Not used.
Not used.
Not used.
Used to retrieve current network status (see Menu 8
description)
Selects Menu 1.
Selects Menu 2.
Selects Menu 3.
Woodward
Manual 02022
4
5
6
7
8
9
0
The DSLC set points or adjustments are arranged in ten menus. You access
these menus with the 1, 2, 3, 4, 5, 6, 7, 8, 9, and 0 (zero) keys. Pressing the
appropriate key selects the first item on each menu. To step through the menu,
use the Up Arrow and Down Arrow keys. The Down Arrow key advances
through the menu and the Up Arrow key moves backward through the menu.
The menus are continuous; that is, pressing the Down Arrow key at the last
menu item takes the menu to the first item, or pressing the Up Arrow key at the
beginning of the menu takes the menu to the last item.
To adjust a set point, use the Turtle Up or the Rabbit Up keys to increase the
value, and the Turtle Down or Rabbit Down keys to decrease the value. The
Rabbit Up and Rabbit Down keys will make the rate of change faster than the
Turtle Up and Turtle Down keys. This is useful during initial setup where a
value may need to be changed significantly.
Woodward
21
Manual 02022
When a monitor set point is selected, the control will update the selected value
automatically once a second.
Finally, use the SAVE key to save entered values. After you are satisfied with
all entries and adjustments, press the SAVE key to transfer all new set point
values into EEPROM memory. The EEPROM retains all set points when power
is removed from the control.
Menu 1Synchronizer
Name
1. Sync Gain
2. Sync Stability
3. Slip Frequency Ref
4. Slip Window
5. Max Phase Window
6. Voltage Matching
7. Voltage Window
8. Breaker Delay
9. C.B. Close Hold Time
10. Close Attempts
11. Reclose Delay
12. Sync Reclose Alarm
13. Sync Timeout
14. Sync Timeout Alarm
15. Auto Re-Synchronize
22
Min Value
0.00
0
0.25 Slow
5
2
Disabled
0
0
0.1
1
1
Disabled
0
Disabled
Disabled
Max Value
100.00
20.00
0.25 Fast
1.00
20
Enabled
10.0
10.00
10.0
20
1000
Enabled
1000
Enabled
Enabled
Initial Value
0.10
1.00
0
0.05
10
Disabled
1.0
0.10
1.0
1
20
Disabled
0
Disabled
Disabled
Dimension
Sec
Hz (Slow or Fast)
Hz
Degrees
%
Sec
Sec
Sec
Sec
Woodward
Manual 02022
Min Value
0.000
0
0
0.01
0.05
0
0
30 000
import
30 000
import
30 000
import
0
0
0.01
0.01
0.01
0.01
0
Max Value
100.000
20.000
20.000
100.00
5.00
100.0
30 000
30 000
export
30 000
export
30 000
export
100.0
100.0
100.00
100.00
100.00
100.00
30 000
Initial Value
1.000
1.000
0
0
2.00
0
1000
500
Dimension
W, kW, MW
1000
W, kW, MW
0
100.0
1.00
1.00
1.00
1.00
20
0
30 000
import
30 000
import
Disabled
100.0
30 000
export
30 000
export
Enabled
5.0
1000
%
%
%/Sec
%/Sec
%/Sec
%/Sec
W, kW, MW
(Imp/Exp)
%
W, kW, MW
900
W, kW, MW
30 000
export
30 000
export
Enabled
W, kW, MW
900
W, kW, MW
30 000
import
30 000
import
Disabled
Alarm
Disabled
1000
Disabled
Disabled
Enabled
Enabled
Disabled
Enabled
Disabled
0
0
0
0
Enabled
100.0
100.0
100.0
100.0
Alarm
Disabled
Disabled
Alarm
Disabled
Alarm
Disabled
Disabled
0
10.0
100.0
90.0
%
%
%
%
9. Import/Export 4 mA
10. Import/Export 20 mA
11. Baseload 4 mA
12. Baseload 20 mA
13. Unload Ramp Rate
14. Load Ramp Rate
15. Raise Load Rate
16. Lower Load Rate
17. Utility Unload Trip
18. Gen Unload Trip
19. Util High Limit PU
20. Util High Limit DO
21. Utility High Limit
22. Utility Low Limit PU
23. Utility Low Limit DO
Sec
Sec
%
Hz
%
W, kW, MW
W, kW, MW
NOTE: The units on all power measurement displays are chosen internally
using the following scheme:
Watts
Kilowatts
Megawatts
Woodward
23
Manual 02022
Min Value
0.0001
0.0
0.0
0.0
0.0
0.1
0.0
0.01
0.01
0.0
0.0
Disabled
0.0
0.0
Disabled
Disabled
Max Value
10.0
20.0
20.0
20.0
100.0
5.0
20.0
20.0
20.0
25.0
25.0
Enabled
25.0
25.0
Enabled
Enabled
Initial Value
1.000
1.00
0
0
0
1.00
12.0
0.10
0.10
15.0
15.0
Disabled
10.0
10.0
Disabled
Disabled
Dimension
Sec
Sec
mA
%
Hz
mA
mA/Sec
mA/Sec
mA
mA
mA
mA
Min Value
VAR Control
2. VAR/PF Gain
3. VAR/PF Stability
4. Rated kVARS
5. kVAR Reference
6. PF Reference
7. Const_Gen_PF_Ref
8. PF Deadband
9. Voltage Low Limit
10. Voltage Low Alarm
11. Voltage High Limit
12. Voltage High Alarm
13. Voltage Switches
0.01
0.0
0
30 000
0.0 Lagging
0.0 Lagging
0.0
50.0
Disabled
50.0
Disabled
Disabled
Max Value
Constant
Gen PF
20.0
20.0
30 000
30 000
0.0 Leading
0.0 Leading
1.0
300xPT
Enabled
300xPT
Enabled
Enabled
Initial Value
PF Control
1.00
2.50
750
20
0.80 Lagging
0.80 Lagging
0.025
60xPT
Disabled
80xPT
Disabled
Disabled
Dimension
Sec
kVAR
kVAR
Volts, kV
Volts, kV
Menu 5Configuration
Name
1. Configuration Key
2. PT Winding Ratio
3. CT Rating
4. PT Voltage Input
5. Voltage Display *
6. System Frequency
7. Process Action
8. Network Address
9. Network Service Pin
10. Revert Status
11. Net Dropout Time
12. Utility Breaker Open Logic
Min Value
0
1:1
5:5
120
V LN
50
Direct
1
Max Value
100
1000:1
10 000:5
240
kV LN
60
Indirect
16
Initial Value
0
1.0:1
5:5
120
Volts LL
60
Direct
16
Lock In Last
0.50
Direct
Hardware
50.00
Indirect
Lock In Last
5.00
Indirect
Dimension
Amperes
Volts LN
Hz
Sec
24
Woodward
Manual 02022
Menu 6Calibration
Name
1. Calibration Key
2. Process Input
3. Remote Input
4. PT Phase A
5. PT Phase B
6. PT Phase C
7. CT Phase A
8. CT Phase B
9. CT Phase C
10. Gen Bus Voltage
11. Synchroscope
12. Command Input
Min Value
0
0
0
0
0
0
0
0
0
0
57.3
Hardware
Max Value
100
22
22
300xPT
300xPT
300xPT
7xCT
7xCT
7xCT
300xPT
57.3
Network
Initial Value
0
0
0
Dimension
mA
mA
Volts, kV
Volts, kV
Volts, kV
Amps
Amps
Amps
Volts, kV
Degrees
Hardware
Min Value
Max Value
30 000
0
30 000
Generate
0.0 Lagging
40xPT
0.0
0.0 Leading
40xPT
0.0
0.0 Leading
40xPT
0.0
0.0 Leading
0
0
40xPT
180
1.0 Slow
100
0.5 Lagging
+30 000
30 000
30 000
Absorb
0.0 Leading
300xPT
7xCT
0.0 Lagging
300xPT
7xCT
0.0 Lagging
300xPT
7xCT
0.0 Lagging
66
66
300xPT
180
5.0 Fast
+120
0.5 Leading
Initial
Value
Dimension
Watts, kW, MW
VA, kVA, MVA
VAR, kVAR (Absorb
or Generator)
Lagging, Leading
Volts, kV
Amps
Lagging, Leading
Volts, kV
Amps
Lagging, Leading
Volts, kV
Amps
Lagging, Leading
Hz
Hz
Volts, kV
Degrees
Hz (Fast or Slow)
%
Lagging, Leading
Woodward
25
Manual 02022
3. Import/Export Ref
4. Process Reference
5. Load Command Output
6. PF Command Output
7. PF Reference
8. Synchronizer Timeout
9. Sync Reclose Limit
10. Utility High Limit
11. Utility Low Limit
12. Generator High Limit
13. Generator Low Limit
14. High Process Limit
15. Low Process Limit
16. Low Voltage Limit
17. High Voltage Limit
Off
Auto-Off
Permissive
Check
Run
Sync Timer
Synchronized
Off Line
Baseload
Baseload Lower
Baseload Raise
Baseload Remote
Utility Unload
Process Ramp
Process Control
Process Lower
Process Raise
Process Remote
Import_Export Ramp
Import_Export Control
Import_Export Lower
Import_Export Raise
Import_Export Remote
Low Limit PU
High Limit PU
Low Limit PU
High Limit PU
0 to 100%
Contact Open/Closed
Contact Open/Closed
Contact Open/Closed
Contact Open/Closed
Contact Open/Closed
Contact Open/Closed
Contact Open/Closed
Contact Open/Closed
Contact Open/Closed
Contact Open/Closed
Contact Open/Closed
Contact Open/Closed
0 100
Energized/De-energized
Energized/De-energized
Woodward
Manual 02022
16. Gen Breaker Open
17. Alarm Relay
18. Low Limit Relay
19. High Limit Relay
20. Load Switch 1 Relay
21. Load Switch 2 Relay
22. Sync Enable LED
23. High Limit LED
24. Low Limit LED
25. Watchdog LED
NOTE: Items 15, 16, and 17 are normally energized relay driver outputs. All
others are normally de-energized relay driver outputs.
Menu 0Diagnostics
1. CPU Diagnostics
2. ROM Checksum
3. Active M/DSLCs
4. Retrieve LON Status
5. Transmit Errors
6. Transaction Timeouts
7. Rcv Transaction Full
8. Lost Messages
9. Missed Messages
10. Last Reset Cause
Woodward
1 16
Press . Key/Status Retrieved
0 65535
0 65535
0 65535
0 65535
0 65535
Power Up Reset
External Reset
Watchdog Reset
Software Reset
Cleared
Unknown
NoAppl, Unconfigured
Appl, Unconfigured
Configured, Off-line
Soft Off-line
Bypass Off-line
Configured, On-line
Unknown
No Error
Bad Event
NV Length Mismatch
NV Msg Too Short
EEPROM Write Fail
Bad Address Type
Preemption Timeout
Already Preempted
Sync NV Update Lost
Invalid Resp Alloc
Invalid Domain
Read Past EndOfMsg
Write Past EndOfMsg
Addr Table Index
Incomplete Msg
Update On Output NV
No Msg Avail
Illegal Send
Unknown PDU
Invalid NV Index
Divide by Zero
Invalid Appl Error
27
Manual 02022
2.
3.
Slip Frequency Ref specifies the positive or negative (fast or slow) slip
frequency reference used for slip frequency synchronizing. Setting the slip
frequency reference to 0 selects phase matching synchronizing.
4.
Slip Window is the maximum allowed deviation in slip (+ or +) from the slip
frequency reference when initiating breaker closure.
5.
6.
7.
Voltage Window is the maximum allowable percent the local bus voltage
may differ from the utility voltage for the synchronizer to issue a breaker
closure command, if voltage matching is enabled. If the slip frequency
reference is positive (fast) the local bus voltage may not be less than the
utility voltage. If the slip frequency reference is negative (slow) the local bus
voltage may not be greater than the utility voltage. This ensures that the
initial reactive power flow is in the same direction as the initial real power
flow.
28
Woodward
Manual 02022
8.
Breaker Delay specifies the time required for the circuit breaker blades to
engage after receiving a closure command. Set to 0 when doing phase
matching.
9.
CB Close Hold Time specifies the maximum elapsed time the synchronizer
will maintain the breaker closure relay driver output low. Failure to receive
the CB Aux contact signal during this interval results in a failed close
attempt. The breaker closure relay driver returns high when the CB Aux
contact signal is received or the specified time expires.
10. Close Attempts is the number of attempts the synchronizer will make to
close the circuit breaker. The sync fail alarm (if enabled) will be activated
and the synchronizer will enter the OFF mode if the breaker fails to close in
the specified number of tries. The synchronizer discrete inputs must be set
to OFF to clear the current close attempts and alarm.
11. Reclose Delay is the number of seconds between attempts to close the
circuit breaker if a failed attempt occurs. If the CB Aux contact remains
closed for one reclose delay interval, synchronization is assumed to have
occurred.
12. Sync Reclose Alarm enables or disables the alarm generated when
reaching the maximum close attempts.
13. Sync Timeout is the interval over which the synchronizer will attempt to get
synchronization. A value of 0 seconds disables the Sync Timeout function.
The interval begins when generator voltage is detected and either the run or
permissive mode select input is activated. Failure to get a CB Aux contact
closure within the specified time will result in a synch timeout alarm. The
synchronizer must be set to off mode to clear the interval timer and alarm.
14. Sync Timeout Alarm enables or disables the alarm generated by
exceeding the synch timeout interval without getting synchronization.
15. Auto Re-Synchronize enables or disables the synchronizer function after
achieving synchronization. Synchronization is assumed to have been
achieved if one Reclose Delay time interval passes with the CB Aux contact
closed. If this set point is set to disabled, the synchronizer is set to auto-off
mode after synchronizing. The synchronizer must be set to the off mode and
then back to the desired operating mode to resume operation. If this set
point is set to Enabled, the synchronizer will automatically restart in the
selected operating mode when synchronization is lost, as indicated when
the CB Aux contact opens. On restart, the synch timeout timer and close
attempts count are reset to their specified values.
Imp/Exp Gain (proportional term) determines how fast the load control
responds to an import/export load error. Gain is set to provide stable control.
2.
Imp/Exp Stability (integral term) compensates for lags in the load control
loop. It prevents slow hunting and controls damping (overshoot or
undershoot) after a load disturbance.
3.
Imp/Exp Derivative adjusts the rate of change in the load command during
a load transient.
Woodward
29
Manual 02022
4.
Imp/Exp Deadband selects the maximum error band within which the
import/export control does not respond. A wider deadband prevents
response to noise, but allows larger steady state errors to exist without
action.
5.
Load Input Filter adjusts the bandwidth of the digital low pass filter on the
load controller input. Higher frequency settings result in a faster control
response.
6.
7.
Rated Load is the 100% maximum load setting of the entire plant. It is equal
to the sum of 100% load on all generators, or the maximum allowable
import/export level.
8.
9.
30
Woodward
Manual 02022
17. Utility Unload Trip is the import/export load level that the MSLC must be
below before issuing the utility breaker open command during a utility
unload.
18. Gen Unload Trip is the percentage system load level that the MSLC must
be below before issuing the Local/Gen Bus breaker open command during a
Local/Gen Bus unload.
19. Util High Load PU is the import/export load level where (if enabled) the
high limit discrete output is energized and the high limit alarm is activated. It
is also limits the maximum import/export reference setting.
20. Util High Load DO is the import/export load level where (if enabled) the
high limit discrete output is de-energized and the high limit alarm is
deactivated.
21. Utility High Limit specifies if the high load limit will activate (de-energize)
the alarm relay.
22. Utility Low Limit PU is the import/export load level where (if enabled) the
low limit discrete output is energized and the low limit alarm is activated. It is
also limits the minimum import/export reference setting.
23. Utility Low Limit DO is the import/export load level where (if enabled) the
low limit discrete output is de-energized and the low limit alarm is
deactivated.
24. Utility Low Limit specifies if the low load Limit will activate the (deenergize) the alarm relay.
25. Util Limit Switches specifies if the high and low load limit discrete outputs
will activate on high or low load.
26. Generator Load High specifies if the generator high limit alarm will activate
the alarm relay. The generator high limit alarm is activated when the MSLC
is required to output a system load of 100% to the DSLC controls in order to
meet its reference.
27. Generator Load Low specifies if the generator low limit alarm will activate
the alarm relay. The generator low limit alarm is caused when the MSLC is
required to output a system load of 0% to the DSLC controls in order to
meet its reference.
28. Gen Limit Switches specifies if the high and low limit discrete outputs will
activate when the system load set point reaches 100% or 0% respectively.
29. Gen Load Switch 1 PU sets the percentage system load level at which load
switch #1 discrete output is activated.
30. Gen Load Switch 1 DO sets the percentage system load level at which
load switch #1 discrete output is de-activated.
31. Gen Load Switch 2 PU sets the percentage system load level at which load
switch #2 discrete output is activated.
32. Gen Load Switch 2 DO sets the percentage system load level at which
load switch #2 discrete output is de-activated.
Woodward
31
Manual 02022
Process Control Gain (proportional term) determines how fast the process
control responds to an error between the process variable and reference.
The gain is set to provide stable control of the process.
2.
3.
4.
Process Deadband is the error window within which the process control
integrator is not updated. This is used for control of high noise processes.
Set to 0.0 mA for normal, non-deadband control.
5.
6.
Process Filter adjusts the bandwidth of the filter on the process input.
Higher frequency settings result in faster control response, but also more
response to process noise.
7.
8.
Raise Reference Rate is the rate at which the internal process reference is
increased when the setpoint raise command is initiated in the process
control mode.
9.
Lower Reference Rate is the rate at which the internal process reference is
decreased when the setpoint lower command is initiated in the process
control mode.
10. High Limit PU is the process input level where (if enabled) the high limit
discrete output is energized and the high limit alarm is activated. It also
limits the maximum internal process reference set point.
11. High Limit DO is the process input level where (if enabled) the high limit
discrete output is de-energized and the high limit alarm is de-activated.
12. High Limit Alarm specifies if the process high limit alarm will activated (deenergize) the alarm relay.
13. Low Limit PU is the process input level where (if enabled) the low limit
discrete output is energized and the low limit alarm is activated. It also limits
the minimum internal process reference set point.
14. Low Limit DO is the process input level where (if enabled) the low limit
discrete output is de-energized and the low limit alarm is de-activated.
15. Low Limit Alarm specifies if the process low limit alarm will activated (deenergize) the alarm relay.
16. Process Switches specifies if the process high and low limits will activate
the high and low limit discrete outputs.
32
Woodward
Manual 02022
2.
VAR/PF Gain (proportional term) determines how fast the control responds
to a VAR/PF error, and is set to obtain stable control.
3.
VAR/PF Stability (integral term) compensates for lag in the control loop. It
prevents slow hunting and controls damping (overshoot and undershoot)
after a load disturbance.
4.
Rated kVARS is the rated kVAR loading of the utility. Normally in systems
rated for 0.8 PF, this will be 0.75 of the rated kW loading and 0.6 of the kVA
rating.
5.
kVAR Reference is the internal set point which the control maintains when
in VAR control mode.
NOTE
6.
A kVAR reference showing Absorb will absorb VARs from the utility
into the generators/load (typically a Leading generator PF).
A kVAR reference showing Generate will generate VARs from the
generators/load into the utility (typically a Lagging generator PF).
PF Reference is the internal set point which the control maintains when in
PF control mode.
NOTE
7.
A PF reference showing Leading will absorb VARs from the utility into
the generators/load (typically a Leading generator PF).
A PF reference showing Lagging will generate VARs from the
generators/load into the utility (typically a Lagging generator PF)
Const_Gen_PF_Ref is the constant reference the MSLC sends to the
DSLC controls (the reference level at which to maintain each DSLC control's
generator) when in constant generator power factor control mode. In this
mode the DSLC control will maintain a constant generator PF level
regardless of the amount of VARs being absorbed/generated across the
utility tie.
NOTE
It is recommended that the Constant Generator Power Factor control mode
be used in applications where the total generator kVAR capacity is less than
the kVAR load of the system.
Woodward
33
Manual 02022
8.
PF Deadband is the error window within which the VAR/PF control does not
react.
9.
Voltage Low Limit specifies the voltage low limit alarm set point. It is also
the lower limit for the synchronizing voltage matching function (below
which it will not allow a breaker closure command) and the minimum
manual voltage set point.
10. Voltage Low Alarm specifies if the voltage low limit alarm will activate (deenergize) the alarm relay.
11. Voltage High Limit specifies the voltage high limit alarm set point. It is also
the higher limit for the synchronizing voltage matching function (above
which it will not allow a breaker closure command) and the maximum
manual voltage set point.
12. Voltage High Alarm specifies if the voltage high limit alarm will activate (deenergize) the alarm relay.
13. Voltage Switches specifies if the voltage high and low limits will activate
the high and low limit relay drivers.
Menu 5Configuration
1.
2.
3.
4.
PT Voltage Input specifies whether the 120 or 240 voltage inputs are used.
NOTE
The 120 and 240 volt inputs are rated to handle up to 150 and 300 volts
respectively. A line-to-neutral voltage from a 480 volt line-to-line system can
be used on the 240 volt input as it would provide a 277 Vac signal at the
designated PT input.
5.
Voltage Display specifies whether the voltages displayed on the Hand Held
Programmer for menus 4 and 7 are line-to-line or line-to-neutral. Use only
kV when primary voltage is greater than 33 kV.
6.
7.
34
Woodward
Manual 02022
8.
NOTE
In systems where the MSLC is installed with Echelon equipped devices
other than its associated DSLC controls (see Chapter 9) using a network
management tool, the network management tool automatically assigns the
MSLC a unique address. In this case, the network address cannot be
changed using the Hand Held Programmer. It will revert to its previous value
after the SAVE key is pressed.
9.
10. Revert Status is used only in applications which use 723 speed controls
that communicate over the LON network to the DSLC. This is a dont care
setpoint for all other applications. Revert status sets the failure mode the
DSLC will assume if it has been receiving network commands, and these
commands fail. The revert status setpoint can be set for either hardware or
network.
If set to hardware, the DSLC/MSLC will revert immediately and without
consideration to transient changes to the hardware inputs upon a network
failure. Once the network is recovered, the DSLC will immediately revert
back to the network command inputs without consideration to transient
changes.
If set to lock in last, the DSLC/MSLC will lock the last valid network
command input in its memory. This input will remain in place unless:
A) The network recovers, and the network command of the recovered
network matches that of the last valid network command input received prior
to network failure. This is referred to as the Network Loop (displayed as
Loop 3 in menu 0 of the DSLC hand held programmer).
B) The hardware discrete inputs match those of the last valid network
command. If the hardware discrete inputs match, the control will use the
hardware inputs from that point on, until the network recovers. Once the
network recovers, the new network command input on the recovered
network must match the hardware input before the transition back to the
network command inputs becomes active. This is referred to as the
Hardware Loop (displayed as Loop 4 in menu 0 of the DSLC hand held
programmer).
Woodward
35
Manual 02022
NOTE
The command inputs can be forced at any time to Hardware by setting the
Command Input setpoint in menu 6 to Hardware. This action will cause an
immediate transition to all hardware inputs (analog and discrete) of the
DSLC/MSLC.
The specific command groups (USE_DS, USE_CBAUX, USE_RR, and
USE_PS) can be forced to hardware at any time by changing the 723
setpoint for these tunable values from TRUE (network) to FALSE (hardware).
The USE_PS and USE_RR inputs will always revert to the hardware inputs
on a network failure, and automatically reset back to the network inputs
when the network recovers, regardless of the Revert Status setting in the
DSLC/MSLC.
11. Net Dropout Time is used only in applications which use 723 speed
controls that communicate over the LON network to the DSLC. This is a
dont care setpoint for all other applications.
The network dropout time is a counter, which can be incremented in 0.5
second steps between 0.5 and 50 seconds. This timer sets the maximum
allowable time which will elapse, and within which at least three valid
messages must be received by the DSLC/MSLC. If less than three valid
messages are received in this time, the network is considered to have
failed.
The network time is also used to establish the parameters for a recovered
network. The DSLC must receive three valid messages within three times
(3x) the network dropout time for the network to be considered OK. This is a
fixed multiplier, and a failed network will always take at least three times the
Network Dropout Time to recover.
NOTE
The Network Dropout Time is updated only on power up of the DSLC/MSLC.
This value may be changed and stored in memory using the hand held
programmer, but changes to this setting will not affect operation until power
is cycled to the DSLC/MSLC.
12. Util Breaker Open Logic selects the logic used for the MSLC Utility
Breaker Open output on terminal 22.
NOTE
Any changes to the Utility Breaker Open Logic setpoint must be saved using
the hand held programmer, and power must be cycled to the MSLC before
the new setting will be active. This is to protect the system against
accidental changes made to this setpoint causing an accidental opening of
the utility tie breaker.
INDIRECT
If set for Indirect, the Breaker Open Command Output will be normally
energized, and will de-energize to issue a utility breaker open command.
The Utility Breaker Open command is issued during normal operation in
Utility Unload mode.
36
Woodward
Manual 02022
NOTE
An indirect setting will cause the utility breaker open command to deenergize (open the utility breaker) on loss of power to the MSLC, or on MSLC
CPU failure (CPU OK LED ON COVER OF MSLC IS OFF).
DIRECT
If set for direct, the Breaker Open Command Output will be normally deenergized, and will energize to issue a utility breaker open command. The
Utility Breaker Open Command is issued during normal operation in the
Utility Unload Mode.
NOTE
A direct setting will cause the utility breaker open command to remain deenergized (no action to open the utility tie breaker) on loss of power to the
MSLC, or on MSLC CPU failure (CPU OK LED ON COVER OF MSLC IS OFF).
Menu 6Calibration
1.
2.
Process Input displays the current value on the 420 mA process variable
input. Raise or lower the displayed value to correspond to the actual input
value during calibration.
3.
Remote Input displays the current value on the 420 mA remote input.
Raise or lower the displayed value to correspond to the actual mA input
value during calibration.
4.
PT Phase A displays the sensed utility bus phase A voltage at the DSLC
terminal strip. When potential is applied to the control, adjust the displayed
value such that the voltage in Menu 7 corresponds to the actual utility phase
A voltage. NOTE: This must be calibrated as part of the installation on the
actual switchboard.
5.
PT Phase B displays the sensed utility bus phase B voltage at the DSLC
terminal strip. When potential is applied to the control, adjust the displayed
value such that the voltage in Menu 7 corresponds to the actual utility phase
B voltage. NOTE: This must be calibrated as part of the installation on the
actual switchboard.
6.
PT Phase C displays the sensed utility bus phase C voltage at the DSLC
terminal strip. When potential is applied to the control, adjust the displayed
value such that the voltage in Menu 7 corresponds to the actual utility phase
C voltage. NOTE: This must be calibrated as part of the installation on the
actual switchboard.
7.
Woodward
37
Manual 02022
8.
9.
10. Gen Bus Voltage displays the sensed local/gen bus phase A voltage at the
DSLC terminal strip. When potential is applied to the control, adjust the
displayed value such that the voltage in Menu 7 corresponds to the actual
local/gen phase A voltage. NOTE: This must be calibrated as part of the
installation on the actual switchboard.
11. Synchroscope compensates for phase shift between the utility and
local/gen bus potential transformers. If the synchroscope does not remain at
0.00 (in the Check Mode) during phase matching synchronizing (see
adjustment later in this chapter), adjust this set point until the synchroscope
remains at 0.00. After the breaker is closed, do a final adjustment for 0.00.
NOTE: If line-to-line voltage is used for the single phase local/gen bus input,
a 300 phase error will initially exist. This must be adjusted as mentioned
above before automatic operation is initiated. THE SAVE KEY MUST BE
PRESSED TO STORE THE PROPER PHASE OFFSET AFTER IT HAS
BEEN CALIBRATED!
12. Command Input is used only in applications which use 723 speed controls
that communicate over the LON network to the DSLC. This is a dont care
setpoint for all other applications.
The command input setpoint can be set for either hardware, or network.
If set to hardware, the DSLC will only recognize the hardware discrete and
analog (420 mA) inputs it is receiving, regardless of the presence of
messages on the LON network. If set to network, the DSLC will monitor the
network for active command input messages and only recognize these
messages, regardless of the hardware input status, unless there is a
network failure. If there is a network failure, the DSLC will operate on
command inputs according to the Revert Status setpoint.
The status of the network and of the network and hardware loops can be
monitored in menu 0 of the DSLC/MSLC hand held programmer.
NOTE
A cycling between network and hardware may be seen in the DI COMMANDS
menu item if the control is set for command inputs from hardware, but a
valid message is being seen on the network.
The DI Commands monitor shows only the status of the USE_DS command
inputs. The USE_CBAUX and USE_PS, USE_RR status is not indicated by
this display.
38
Woodward
Manual 02022
Active Power (P) is the real power (kW) flowing across the utility tie.
Negative values indicate power imported and positive values indicate power
exported. In more recent software versions, the terms import and export
replace the indications.
2.
Apparent Power (S) is the apparent power (kVA) flowing across the utility
tie. Apparent Power is displayed as an absolute value.
3.
Reactive Power (Q) is the reactive power (kVAR) flowing across the utility
tie.
NOTE
4.
NOTE
5.
Phase A is the voltage on phase A of the utility bus. This voltage is used for
voltage matching and is compared to the high and low limits in menu 4.
6.
7.
8.
9.
Woodward
39
Manual 02022
2.
Load Control Mode is the current operating mode of the load control
function.
3.
4.
5.
Load Command Output is the current output from the MSLC telling the
associated DSLC controls what level to set their system load percentage.
6.
7.
8.
9.
Sync Reclose Limit is the status of the alarm for exceeding the
synchronizer close attempts limit.
40
Woodward
Manual 02022
10. Utility High Limit is the status of the alarm for exceeding the high
import/export load limit set point.
11. Utility Low Limit is the status of the alarm for exceeding the low
import/export load limit set point.
12. Generator High Limit is the status of the alarm when the MSLC load
command output reaches 100%.
13. Generator Low Limit is the status of the alarm when the MSLC load
command output reaches 0%.
14. High Process Limit is the status of the alarm for exceeding the process
control input high limit set point.
15. Low Process Limit is the status of the alarm for exceeding the process
control input low limit set point.
16. Low Voltage Limit is the status of the alarm for exceeding the low voltage
limit set point.
17. High Voltage Limit is the status of the alarm for exceeding the high voltage
limit set point.
Synch Check Switch is the status of the synchronizer Check Mode switch
input.
2.
3.
Synch Run Mode is the status of the synchronizer Run Mode switch input.
4.
5.
6.
7.
8.
9.
Setpoint Raise is the status of the set point raise contact input.
10. Setpoint Lower is the status of the set point lower contact input.
11. Raise Voltage is the status of the voltage raise contact input.
12. Lower Voltage is the status of the voltage lower contact input.
13. Test Key must be set to 49 to allow closing of discrete outputs for test
purposes. In addition, all discrete inputs must be open to allow testing of
discrete outputs.
Woodward
41
Manual 02022
14. Breaker Close Relay is the status of the circuit breaker closure command
relay.
15. Utility Breaker Open is the status of the utility breaker open command
relay.
16. Gen Breaker Open is the status of the local/gen bus breaker open
command relay.
17. Alarm Relay is the status of the alarm Relay.
18. Low Limit Relay is the status of the Low Limit relay.
19. High Limit Relay is the status of the High Limit relay.
20. Load Switch 1 Relay is the status of the load switch #1 relay.
21. Load Switch 2 Relay is the status of the load switch #2 relay.
22. Sync Enable LED is the status of the SYNC ENABLE LED.
23. High Limit LED is the status of the HIGH LIMIT LED.
24. Low Limit LED is the status of the LOW LIMIT LED.
25. Watchdog LED is the status of the CPU OK LED.
Menu 0Diagnostics
1.
2.
3.
4.
5.
42
Woodward
Manual 02022
6.
7.
Rcv Transaction Full is the number of times than an incoming packet was
discarded because there was no room in the transaction database. These
may be due to excessively long receive timers, or inadequate size of the
transaction database.
8.
9.
10. Last Reset Cause is the cause of the last reset of the network processor.
11. Node State indicates the current state of the network processor. The
normal node state is Configured, On-line. Other states can occur during
installation of the control using network management tools.
12. LON Error Log is the last run-timer error logged.
13. LON Interface Errors is the number of errors detected by the MSLC
processor software during communicating with the network processor.
Errors can occur during custom installation of the control with network
management tools. Occasional errors will not effect control operation.
Frequent errors indicate a defective control.
14. A/D Errors is the number of errors detected by the MSLC software during
communication with the A/D (analog-to-digital) converter. Occasional errors
will not effect control operation. Frequent errors may be caused by
excessive electrical noise or extreme voltage transients on the wiring, or by
a defective control.
15. Network Loop is a TRUE/FALSE indication which, when true, indicates a
network command input failure has occurred, causing the MSLC control to
lock into the last valid network operating command. See Chapter 4, Menu 5
Configuration section, for more details on network command operations.
16. Hardware Loop is a TRUE/FALSE indication which, when true, indicates a
network command input failure has occurred, causing the MSLC control to
lock into the current hardware input operating commands. See Chapter 4,
Menu 5 Configuration section, for more details on network command
operations.
Woodward
43
Manual 02022
Configuration Menu
Select Menu 5 and adjust the Configuration Key to 49. Set the following set
points to their appropriate value as described above.
1.
2.
3.
4.
5.
6.
7.
Press the SAVE key, and verify in Menu 0 that the MSLC sees the proper
number of DSLC controls in the system. If not, see Chapter 10 for corrective
action.
44
Woodward
Manual 02022
MSLC Adjustments
When the prestart setup procedures above have been completed, the MSLC
may be installed into the system, and the following adjustment procedures must
be followed.
After the unit has been installed and before applying power to the PT and CT
inputs, verify the following:
1.
2.
3.
The MSLC sees the proper number of DSLC controls on the network (see
Menu 0).
The MSLC recognizes the synchronizer switch inputs (see Menu 9).
The synchronizer is in the OFF mode.
Calibration Check
Temporarily disconnect the network interconnection wires at terminals 40 & 41
on the MSLC (this will prevent the MSLC from giving commands to the
associated DSLC controls). Load the system up to a typical import/export level.
Check Menu 7 to ensure that the MSLC is sensing the proper voltages, currents,
power levels, and power factor.
NOTE
These are calibrated at the factory, but they must be checked for accuracy in
order for the MSLC to accurately track to the proper load levels. The MSLC
can only be verified against calibrated, true RMS meters. If not in calibration
see chapter 10 troubleshooting.
All DSLC controls must be appropriately calibrated according to the DSLC
manual prior to further MSLC adjustment.
Synchronizer Adjustment
This section is for adjusting the synchronizer functions, including procedures for
phase matching and slip frequency synchronizing. Note that dynamic
adjustments for gain and stability will be different for each method.
To assist in setup and adjustments, you can monitor synchronizer mode of
operation on Menu 8 and Synchronizer Mode and Slip Frequency and
Synchroscope values on Menu 7.
Woodward
45
Manual 02022
2.
Select Menu 1 and verify that the Sync Gain and Sync Stability set points
are at their default values.
3.
Set the Max Phase Window and Max Slip Window set points to desired
values or use the default values if unknown.
4.
5.
Set CB Close Hold Time to the time desired for the MSLC to hold the
breaker closure signal. This time should at least exceed the Breaker Delay
time.
6.
7.
8.
Set the Slip Frequency Ref set point to 0.0 Hz to select phase matching.
2.
3.
With utility and bus active, adjust the synchronizer Gain set point for stable
control of the utility frequency as indicated by the synchroscope's holding
steady at zero phase.
46
Woodward
Manual 02022
NOTE
If the system (not the MSLC) synchroscope does not lock close to zero
phase, but at some other value(such as 30, 60, 180, 210, etc. degrees), verify
bus and utility potential wiring to either the synchroscope or MSLC. DO NOT
PROCEED WITH ANY ACTION RESULTING IN BREAKER CLOSURE UNTIL
THE PROBLEM IS DETERMINED AND CORRECTED.
If you have a WYE version MSLC (part number 9907-004), and if line-to-line
voltage is used on the Bus PT input, the synchroscope adjustment in Menu 6
must be changed in order to indicate proper phase (compensate for the 30
degree phase shift between the wye and delta inputs). Manually parallel the
two power sources in question using a proven device (a panel
synchroscope, or phase indication lamps). When the utility breaker is
closed, adjust the synchroscope in Menu 6 of the MSLC hand held until the
synchroscope reading in menu 6 is 0.0 degrees (1 degree).
If you have a DELTA version MSLC (part numbers 9907-005 or 9907-006), and
if line-to-neutral voltage is used on the Bus PT input, the synchroscope
adjustment in Menu 6 must be changed in order to indicate proper phase
(compensate for the 30 degree phase shift between the delta and wye
inputs). Manually parallel the two power sources in question using a proven
device (a panel synchroscope, or phase indication lamps). When the utility
breaker is closed, adjust the synchroscope in Menu 6 of the MSLC hand held
until the synchroscope reading in menu 6 is 0.0 degrees (1 degree).
4.
Turn the synchronizer mode to Off. Allow the phase to drift until the
synchroscope indicates approximately 150 degrees fast. It may be
necessary to adjust the engine speed setting slightly fast to achieve the
desired phase drift.
5.
Turn the synchronizer mode to Check. The synchronizer should pull the
generator smoothly into phase lock.
If the synchronizer action is too slow, increase Sync Gain by a factor of two.
If increasing Sync Gain results in unstable operation, reduce the value by at
least one-half and proceed to step 6. Otherwise, repeat steps 4 and 5.
6.
Do step 4 and then turn the synchronizer mode to Check. The synchronizer
should pull the generator smoothly into phase lock. If the synchronizer is too
slow, or over-damped, decrease Sync Stability by a factor of two to
decrease damping, and increase Sync Gain by a factor of two. If the
synchronizer is too fast, or under-damped as indicated by excessive overshoot of zero phase when pulling in, decrease Sync Gain by a factor of two,
and increase Sync Stability by a factor of two to increase damping.
7.
8.
Turn the synchronizer mode to Off. Allow the phase to drift until the
synchroscope indicates approximately 150 degrees slow. It may be
necessary to adjust the engine speed setting slightly slow to achieve the
phase drift. Repeat steps 5 and 6 if necessary to get the desired
performance.
9.
Woodward
47
Manual 02022
Set the Slip Frequency Ref set point initially to 0.0 Hz to select phase
matching.
2.
3.
With utility and bus active, adjust the synchronizer Gain set point for stable
control of the utility frequency as indicated by the synchroscope's holding
steady at zero phase.
NOTE
If the system (not the MSLC) synchroscope does not lock close to zero
phase, but at some other value(such as 30, 60, 180, 210, etc. degrees), verify
bus and utility potential wiring to either the synchroscope or MSLC. DO NOT
PROCEED WITH ANY ACTION RESULTING IN BREAKER CLOSURE UNTIL
THE PROBLEM IS DETERMINED AND CORRECTED.
If you have a WYE version MSLC (part number 9907-004), and if line-to-line
voltage is used on the Bus PT input, the synchroscope adjustment in Menu 6
must be changed in order to indicate proper phase (compensate for the 30
degree phase shift between the wye and delta inputs). Manually parallel the
two power sources in question using a proven device (a panel
synchroscope, or phase indication lamps). When the utility breaker is
closed, adjust the synchroscope in Menu 6 of the MSLC hand held until the
synchroscope reading in menu 6 is 0.0 degrees (1 degree).
If you have a DELTA version MSLC (part number 9907-005 or 9907-006), and
if line-to-neutral voltage is used on the Bus PT input, the synchroscope
adjustment in Menu 6 must be changed in order to indicate proper phase
(compensate for the 30 degree phase shift between the delta and wye
inputs). Manually parallel the two power sources in question using a proven
device (a panel synchroscope, or phase indication lamps). When the utility
breaker is closed, adjust the synchroscope in Menu 6 of the MSLC hand held
until the synchroscope reading in menu 6 is 0.0 degrees (1 degree).
4.
Turn the synchronizer mode to Off. Allow the phase to drift until the
synchroscope indicates approximately 150 degrees fast. It may be
necessary to adjust the engine speed setting slightly fast to achieve the
desired phase drift.
5.
Turn the synchronizer mode to Check. The synchronizer should pull the
generator smoothly into phase lock.
If the synchronizer action is too slow, increase Sync Gain by a factor of two.
If increasing Sync Gain results in unstable operation, reduce the value by at
least one-half and proceed to step 6. Otherwise, repeat steps 4 and 5.
48
Woodward
Manual 02022
6.
Turn the synchronizer mode to Off. Set the Slip Frequency Ref set point to
the desired slip rate. Set engine speed slightly slow.
7.
8.
9.
With the circuit breaker closed, select the Calibration Menu 6 and adjust the
Calibration Key to 49. Select the Synchroscope set point and adjust for 0.0
0.3 degrees.
2.
Open the breaker to disconnect the local generator bus from the utility bus.
3.
Set Close Attempts to the desired number of times the synchronizer should
attempt to close the circuit breaker. Set to 1 if only one close attempt should
be made.
4.
Set Reclose Delay to the desired interval between close attempts. This
should be greater than the time required to recharge the circuit breaker
arming mechanism.
5.
6.
Set the Sync Timeout to the maximum number of seconds the synchronizer
should attempt to achieve synchronization. Set to 0 for no timeout.
7.
If an alarm is desired when the Sync Timeout interval expires, set the Sync
Timeout Alarm set point to Enabled.
Woodward
49
Manual 02022
8.
9.
10. Record all Menu 1 set point values in the spaces provided in Appendix A.
This completes the MSLC synchronizer setup.
NOTE
Individual DSLC controls must be setup for proper voltage regulator control
prior to adjusting the MSLC control (See the DSLC manual).
With the utility tie breaker closed, calibrate the bus voltage and the phase A
voltage to read the same voltage.
2.
Select Menu 1 and set the Voltage Matching set point to Enabled.
3.
Select Menu 3 and set the Voltage High Limit 5% higher than the maximum
expected value. Set the Voltage Low Limit 5% lower than the final minimum
expected value.
Final Setup
1.
Select Menu 7 and display both Phase A and local generator bus voltages.
2.
With the synchronizer OFF, manually raise the local bus voltage until it is
approximately 5% higher than the utility voltage.
Set the synchronizer mode to CHECK. The MSLC should adjust the local
bus voltage until it is within the voltage window selected in Menu 1.
4.
If the voltage cycles through the window without settling into it, the voltage
adjusting potentiometer on the DSLC controls may need to be adjusted. See
the DSLC manual.
5.
Set the synchronizer to OFF, manually lower the local bus voltage until it is
approximately 5% lower than the utility voltage.
50
Woodward
Manual 02022
6.
Set the synchronizer mode to CHECK. The MSLC should adjust the local
bus voltage until it is within the voltage window selected in Menu 1.
NOTE
If the slip frequency reference is set to zero, the voltage window is the set
point chosen in Menu 1. If the slip frequency reference is set to a negative or
slow slip, the voltage window is such that the local bus voltage must be less
than the utility voltage. Conversely, if the slip frequency reference is set to a
positive or fast slip, the voltage window is such that the local bus voltage
must be greater than the utility voltage. This ensures that the initial flow of
reactive power is in the same direction as the initial flow of real power.
2.
3.
When the voltage matching function is satisfactory, press SAVE key on the
Hand Held Programmer.
2.
Break the parallel between the local bus and the utility. Place at least one
generator in isochronous load sharing.
3.
Set the Hand Held Programmer to display Load Command (Menu 8) and
the system load (Menu 7). Re-synchronize and parallel the local bus to the
utility. Verify that, when the utility tie breaker shuts, the load command
assumes the value of system load immediately prior to paralleling.
4.
Temporarily issue a lower set point command, and then a raise set point
command. Verify that the load command changes appropriately and that the
engines in isochronous load sharing respond appropriately.
Woodward
51
Manual 02022
Set the 4 mA and 20 mA Base Load set points (Menu 2). Either set point
may be higher or lower than the other. The MSLC will linearly interpolate
between those two set points.
2.
Synchronize and parallel the local bus to the utility in the base load mode.
Adjust the 420 mA input to a level different from the present base load
level.
3.
Close both the raise and lower set point contacts to select the Remote
Mode. The Load Control Mode in Menu 8 should indicate baseload remote,
and the load command should ramp to the specified level.
4.
Raise and Lower the 420 mA signal. The load will ramp at the rates
chosen in Menu 2 Load and Unload Ramp Rates. These rates may be
adjusted to achieve satisfactory performance.
5.
Open the Raise and Lower Set Point contacts. The Load Control Mode
should indicate Base Load, and the control should lock at the last base load
level chosen by the 420 mA input.
2.
3.
Ensure that the import/export gain, stability, and derivative are at their
default values.
4.
Place the control in import/export control while monitoring load control mode
(Menu 8). The control will ramp the Load Command Output until the
import/export level is within 5% of its target. Then the MSLC will enter
dynamic import/export control.
5.
If you see instability, adjust the gain, stability, and derivative. If the chosen
import/export level is not obtainable within the 0100% load command
range, the control will stop at 0% or 100%.
6.
Temporarily issue a lower set point command, and then a raise set point
command. Verify that the load command changes appropriately and that the
engines in isochronous load sharing respond appropriately.
52
Woodward
Manual 02022
Set the 4 mA and 20 mA import/export load set points (Menu 2). Either set
point may be higher or lower than the other. The MSLC will linearly
interpolate between those two set points.
2.
Synchronize and parallel the local bus to the utility in the base load mode.
Place the control in import/export mode at some desirable import/export
level. Adjust the 420 mA input to a level different from the present
import/export level.
3.
Close both the raise and lower set point contacts to select the Remote
Mode. The Load Control Mode in Menu 8 should indicate import/export
remote, and the load command should ramp to the specified level.
4.
Raise and Lower the 420 mA signal. The load will ramp at the rates
chosen in Menu 2 Load and Unload Ramp Rates. These rates may be
adjusted to achieve satisfactory performance.
Open the Raise and Lower Set Point contacts. The Load Control Mode
should indicate Base Load, and the control should lock at the last
import/export level chosen by the 420 mA input. Toggling the import/export
contact will cause the control to return to its internally chosen import/export
level.
Set the Load and Unload Rates to their desired values (Menu 2).
2.
Set the Load and Unload Ramp Rates to their desired values (Menu 2).
3.
Set the Utility and Generator Unload Trip levels to their desired values
(Menu 2).
4.
Set the High Limit PU (pick up) and DO (drop out) set points to their final
values. The High Limit PU set point should be set to limit the load reference
even if the alarm and high limit switch will not be used.
5.
Set the Low Limit PU and DO set points to their final values. The Low Limit
PU set point should be set to limit the load reference even if the alarm and
low limit switch will not be used.
6.
If it is desired that the Alarm output will also de-energize the alarm relay
when load reaches the High Limit PU, set the High Limit Alarm set point to
Enabled. The alarm will be automatically cleared when load drops below the
High Limit DO switch point.
7.
If it is desired that the Alarm output will also de-energize the alarm relay
when load reaches the Low Limit PU, set the Low Limit Alarm set point to
Enabled. The alarm will be automatically cleared when load increases to
above the Low Limit DO switch point.
Woodward
53
Manual 02022
8.
If it is desired that the high and low limit switches also activate the High Limit
and Low Limit relay driver outputs, set the Load Limit Switches set point to
Enabled.
9.
Set the Load Switch PU and Load Switch DO set points to their desired
operating levels.
10. When all load control setup is completed, press the SAVE key on the
Hand Held Programmer to store modified set points.
11. Record all Menu 2 and Menu 3 set points in their respective locations in
Appendix A.
Set Menu 4 set points for Process Control Gain, Process Stability, Process
Derivative, Process Deadband, Process Droop, and Process Filter to their
default values.
2.
Set Menu 5 Configuration Key to 49. Set Menu 5 Process Control Action to
Direct or Indirect as required for the process. If increasing load also
increases the process input signal level, use Direct. If increasing load
decreases the process input signal level, use Indirect.
3.
Set the Process Reference set point to a value requiring approximately 50%
load to maintain the process signal level. If the required process reference is
not known at start-up, operate the MSLC in base load mode. Use the Raise
and Lower Set Point inputs to adjust the load until the desired process level
is obtained. Observe the process input in Menu 6 to determine the required
process reference value.
4.
Close the Process switch. Select RUN on the MSLC to parallel the local
bus with the utility. The MSLC will ramp into process control.
5.
6.
7.
8.
Set the Process High Limit PU and DO set points to the desired values. The
Process High Limit PU set point must be set to limit the range of the process
reference even if the alarm will not be used.
54
Woodward
Manual 02022
9.
Set the Process Low Limit PU and DO set points to the desired values. The
Process Low Limit PU set point must be set to limit the range of the process
reference even if the alarm will not be used.
10. If it is desired that the Alarm output will also de-energize the alarm relay
when the process input reaches the Process High Limit PU, set the Process
High Limit Alarm set point to Enabled. The alarm will be automatically
cleared when the process input level drops below the Process High Limit
DO switch point.
11. If it is desired that the Alarm output will also de-energize the alarm relay
when the process input reaches the Process Low Limit PU, set the Process
Low Limit Alarm set point to Enabled. The alarm will be automatically
cleared when the process input increases to a level above the Process Low
Limit DO switch point.
12. If it is desired that the high and low limit switches also activate the High Limit
and Low Limit relay driver outputs, set the Process Switches set point to
Enabled.
13. Verify dynamic performance is satisfactory under all expected operating
conditions, then press the SAVE key on the Hand Held Programmer to
save the dynamic and other modified settings.
14. Record all set points in Menu 4 in their respective locations in Appendix A.
This completes setup of the MSLC Process Control function.
Woodward
55
Manual 02022
Chapter 5.
Synchronizer Description
Introduction
Synchronization as applied to the generation of electricity, is the matching of the
output voltage wave form of one synchronous alternating current electrical
generator with the voltage wave form of another alternating current electrical
system. For the two systems to be synchronized and connected in parallel, five
conditions must be considered:
Functional Description
This section describes how generator and bus matching occurs and how all
conditions are verified by the synchronizer functions. Figure 5-1 shows the
functional block diagram of the synchronizer for reference during the following
descriptions.
Operating Modes
The operation of the synchronizer is determined by the mode switch as shown in
Figure 5-2. The four modes are Off, Run, Check, and Permissive. When the
switch is off, the synchronizer is out of operation.
Run mode allows normal synchronizer operation and breaker closure signals.
The speed bias signal (explained below) is maintained throughout the breaker
closure signal. When the specified closure signal time has elapsed or the CB
(circuit breaker) aux contact closure signal is received at terminal 47, the
synchronizer is disabled. The synchronizer may optionally be reset automatically
when the generator is disconnected from the bus.
Check mode allows normal synchronizing and voltage matching, but does not
issue a breaker closure signal.
Permissive mode enables the synch-check function for proper synchronization,
but synchronizer operation does not affect the engine's speed or generator
voltage. If phase, frequency, and voltage are within proper limits, the
synchronizer issues the breaker closure command.
56
Woodward
Manual 02022
Woodward
57
Manual 02022
58
Woodward
Manual 02022
Voltage Matching
The voltages of two systems in parallel must be matched within a small
percentage to minimize the unnecessary reactive power flow in the system. If a
local plant is paralleled to the main grid with unequal voltages, the local plant will,
in most cases, follow the utility voltage. The difference in voltage will cause
reactive power either to be absorbed or generated.
If the system is initially at a lower voltage than the utility, reactive power will be
absorbed by the system. If the system voltage was initially higher, the local plant
will provide extra reactive power to the utility. In either case the breaker across
which the parallel is made will experience unnecessary wear and tear created by
the arcing across different voltages.
Figure 5-3 shows the voltage matching circuits of the synchronizer function in the
MSLC. The voltages proportional to the local generator bus phase A and the
utility phase A are input to the sample-and-hold circuits of the A/D (analog-todigital) converter, where they are held until actually read by the A/D converter.
This process is repeated for the desired number of samples and cycles of the ac
input wave forms.
The microprocessor then computes the RMS values of the voltages. The
processor issues appropriate raise or lower commands, or voltage bias
adjustment to all of the DSLC controls over the digital network. The MSLC will
continue this process until the difference between local bus and utility voltage is
within a specified window. The automatic voltage matching function may be
enabled or disabled with a configuration set point. When enabled, voltage
matching will occur in both the Check and Run modes, and is verified to be within
the window in the Permissive mode.
Woodward
59
Manual 02022
Sync-check
The sync-check function determines when all conditions for proper
synchronization are met and energizes the breaker closure relay driver. The
voltages of the two sources to be paralleled are verified to be within the chosen
window if the voltage matching function is enabled.
To minimize voltage transients and limit wear and tear on the breakers, the
parallel must be made when the phase difference between the utility and the
local bus is near zero. Due to delays inherent in the breaker closure relays and
breaker mechanisms, the synchronizer must issue the breaker closure command
ahead of the zero phase difference point. The control compares the slip
frequency to the breaker closure delay in order to anticipate the breaker actually
closing at the zero phase difference. The phase and slip frequency windows
provide maximum and minimum conditions for this calculation. When all
conditions of voltage and phase are achieved, the breaker closure command is
issued.
Synchronizer Timers
The synchronizer function is equipped with two adjustable timers. The first is the
circuit breaker close hold time. This timer has two functions. First, it determines
the amount of time the control maintains the utility breaker close relay driver
energized. Second, it sets the period the breaker must remain closed for the
control to assume that a proper synchronization and parallel has been achieved.
The other timer is the sync timeout. The sync timeout chooses how long the
control is allowed to attempt to achieve synchronization. If synchronization is not
attained in this period of time from the issuing of the RUN command, the
synchronizer goes to the OFF mode, requiring the synchronizer mode selector
switch to be toggled to OFF and then back to RUN before the control will
again attempt synchronization. An alarm is provided which if enabled will
energize the alarm relay driver, terminal 24, if the a sync timeout occurs. The
sync timeout function is disabled by setting it to zero.
60
Woodward
Manual 02022
Chapter 6.
Real Power Control
Introduction
The MSLC provides several modes of system load control. These are:
Base Loading
1
n
V I
i i
i=1
where Vi and Ii are simultaneous samples of voltage and current equally spaced
in time. The average power in the three phase system is the sum of the power in
each phase.
While the power measurement is of the greatest interest, other functions may
also be derived from the raw data. These are
1
r
1 n 2 2
rms Volts V = V i
n i=1
1
r
1 n 2 2
rms Amps I = I i
n i=1
rr
Volt - Amps S = VI
Reactive Power Q = ( S 2 - P2 )2
P
Power Factor pf =
S
Q
Phase Angle = tan-1
P
Frequency f =
1
T
where T is the sampling period. The sampling period is derived from the zero
crossings of the A phase voltage signal.
Woodward
61
Manual 02022
MSLC/DSLC Interface
The MSLC controls only those DSLC controls which are set up for isochronous
load sharing, in the parallel mode of load control. In the parallel mode, DSLC
controls normally average the percentage of rated load seen by all machines on
the network. This average is called the system load. Without an MSLC present,
the DSLC controls use the calculated system load as their load reference. The
MSLC takes control of this system load to vary the load on the individual DSLC
controls.
Import/Export Mode
In this mode of system load control, the MSLC measures the real power flow to
or from the main power grid. It then controls all individual DSLC controls which
are in the isochronous load sharing mode, by setting their system load. The
individual DSLC controls will control to this percentage of their rated loads, and
the MSLC will adjust this system load up or down to achieve the proper
import/export level. For safety, the MSLC is limited to controlling generators
between 0% and 100%.
62
Woodward
Manual 02022
NOTE
Any DSLC set for base loading will maintain its individually set base load,
regardless of the MSLC signal. Therefore, a sufficient number of generators
must be in isochronous load sharing in order to handle plant load swings
and still maintain the import/export level.
Remote Control
In any of the above modes, the reference can be determined by a 4-20 mA (1-5
Vdc) input at terminals 35 & 36. The remote mode is selected by activating both
the set point raise and lower at the same time. The 4 mA and 20 mA targets are
set in Menu 2, and the control linearly interpolates for intermediate values.
Utility Unload
When the utility unload command is issued, the MSLC will adjust the
import/export level until a specified level about the zero power transfer point is
obtained. It will then issue a utility breaker open command. If the local plant is
initially operating at some export level, supplying power to the utility, the MSLC
will lower the system load set point to obtain a zero power transfer condition. If
the local plant is initially operating at some import level, absorbing power from
the utility, the MSLC will raise the system load set point to obtain a zero power
transfer condition. If the MSLC cannot bring the import/export level within the
chosen band prior to reaching a system load set point of 0% or 100%, the unload
will stop and if enabled the appropriate high/low limit alarms will activate.
Local Unload
When the MSLC is in base load mode and the set point lower command is
continuously activated, the control will lower on the system load reference until it
is below a chosen percentage. It will then issue a local generator bus breaker
open command. This will transfer the plant load back to the utility power grid.
Woodward
63
Manual 02022
NO CONTROL
BASE LOAD
RAISE BASE LOAD
LOWER BASE LOAD
REMOTE BASE LOAD1
UTILITY UNLOAD2
LOCAL UNLOAD3
RAMP PAUSE4
I/E MODE
I/E RAISE
I/E LOWER
I/E REMOTE1
PROCESS CONTROL
PROCESS RAISE
PROCESS LOWER
PROCESS REMOTE1
CB
AUX
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
UTLTY
UNLD
X
0
0
0
0
1
0
X
0
0
0
0
0
0
0
0
I/E
X
0
0
0
0
X
0
X
1
1
1
1
X
X
X
X
PROC
CTRL
X
0
0
0
0
X
0
X
0
0
0
0
1
1
1
1
RAMP
PAUSE
X
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
STPT
RAISE
X
0
1
0
1
X
0
X
0
1
0
1
0
1
0
1
STPT
LOWER
X
0
0
1
1
X
1
X
0
0
1
1
0
0
1
1
NOTES:
1.
Remote reference is activated by closing both set point raise and set point lower switches at the
same time.
2.
The MSLC can only load the associated generators to 100%. If this is not enough capacity to
unload the utility, the unload ramps stops at 100% rated load on the associated generators. The
generator high limit alarm, if enabled, will activate at this time.
3.
The local plant unload is accomplished by switching to base load mode and supplying a
continuous set point lower command.
4.
64
The ramp pause command will pause all ramps in any mode.
Woodward
Manual 02022
Chapter 7.
VAR/PF Control
When a local plant is paralleled with the main utility power grid, the synchronizer
voltage matching function adjusts the individual generator voltages to match the
local bus to the main grid. Voltage fluctuations may occur in the utility system
after paralleling. This results in corresponding fluctuations in the reactive load on
the local plant. The MSLC has three modes of controlling reactive load:
Constant Generator Power Factor. The MSLC sets the power factor
reference of the generators according to the value chosen by the hand held
programmer. This reference remains constant, and will not change with
changing reactive load across the utility tie.
Power Factor Control. The MSLC adjusts the power factor references of
the generators in order to maintain a chosen power factor level across the
utility tie.
VAR Control. The MSLC adjusts the power factor reference of the
generators in order to maintain a chosen VAR level across the utility tie.
Manual VAR/PF control can be attained by using the raise and lower voltage
inputs in the Constant Generator Power Factor mode. The raise voltage
command will make the power factor reference more lagging and the lower
voltage command will make the power factor reference more leading.
The MSLC implements power factor control over the LON, setting the power
factor reference on all DSLC controls in isochronous load sharing. The DSLC
controls then either adjust their analog outputs to their associated voltage
regulators or adjust their associated voltage trim motor operated potentiometers,
depending on the individual installation.
When a utility unload command is issued, the control automatically shifts from
VAR control to power factor control in order to ensure a minimum amount of
current flow across the utility tie when it is opened.
It is important to note that, as with the real load functions, the VAR/PF control in
the MSLC controls only those DSLC controls which are in isochronous load
sharing. Any DSLC controls which are in base load mode will control the reactive
power on their associated generators in accordance with their own internal
reference and chosen mode of VAR/PF control.
Woodward
65
Manual 02022
Chapter 8.
Process Control
Introduction
The process control function of the MSLC controls any process where the
controlled parameter is determined by the load on the local generators. The
controlled parameter can be monitored as a 4-20 mA or 1-5 Vdc signal.
The control compares the input signal to the process reference set point, or the
remote reference if used, and adjusts the local generator loading to maintain the
desired set point.
Description
Figure 8-1 shows a block diagram of the process control function. The process
control mode is selected when the process input switch contact is closed. The
process input signal is compared with the process reference, which may be
either the internal fixed reference or the 4-20 mA remote input. In process control
mode, the raise/lower set point discrete inputs operate on the process control
reference rather than on the load reference. The 4-20 mA remote reference input
becomes the process reference and is selected when both the raise and lower
set point contact inputs are closed.
When the process function is initially selected, the reference is set equal to the
internal or remote process reference. If the process input and process reference
are not equal, the control ramps the load reference in the appropriate direction to
reduce the difference error. When the process error reaches zero or the
percentage system load command reaches the maximum (100%) or minimum
(0%) values, the process control is enabled.
When the process control is enabled, the error signal between the process
reference and process signal is the input to a PID (proportional/integral/derivative)
controller operating in cascade with the load control. The output of the controller is
the system load percentage to all associated DSLC controls operating in the
parallel mode. The individual DSLC controls then control their associated speed
controls to maintain the commanded percentage of their individual rated loads
(thereby maintaining the process level at the desired set point).
Additional features of the process control are an adjustable process input signal
filter and adjustable deadband on the integrator. The adjustable filter allows
reducing bandwidth when controlling a noisy process. The deadband is useful in
both noisy applications as well as for very slow processes.
The process control function is configurable for direct and inverse action. Direct
process control is where the sensed input signal increases as the load increases.
An inverse action control is where the sensed input signal decreases as the load
increases.
NOTE
The MSLC system load command is obeyed only by the associated DSLC
controls which are in isochronous load sharing. Base load or process
control mode will ignore the MSLC load command signal and maintain its
set base load reference.
66
Woodward
Manual 02022
Woodward
67
Manual 02022
Chapter 9.
Echelon Lonworks Network
Introduction
The communications network used by the MSLC is Echelon Corporation's
LonWorks technology. An Echelon Neuron chip operates as a slave
processor to the MSLC main processor. As described in previous chapters,
LonWorks provides the interconnection between the MSLC and all of its
associated DSLC controls over which the MSLC will control the loading of
generators, generator power factor, and local bus/utility synchronization.
The MSLC contains diagnostics software to assist in verifying proper operation of
the network and to aid in troubleshooting in case of problems. Diagnostic and
other network test information is contained in Chapter 10 (Troubleshooting).
The MSLC also provides optional remote metering, control status, alarm
monitoring, and full remote control capability over the network when connected to
the appropriate LonWorks-compatible devices through a custom installation. This
chapter provides information on network specifications and the optional
capabilities of the MSLC. Contact the Woodward Governor Company for full
information on optional devices to take advantage of these features.
68
Woodward
Manual 02022
Remote Metering
The following listing shows the actual values as applied to the MSLC. The values
are not necessarily the same as the values displayed on the Hand Held
Programmer. The Hand Held Programmer displays values which are, in some
cases, multiplied by the PT or CT ratios (voltages may also be displayed as lineto-line). All described values are available as SNVT_count (Standard Network
Variable Type, count is 16-bits). Values area also in standard 2's complement
integer form stored such that the most significant byte is at the lowest address.
Metering values are updated at a 1.0 second rate and are intended for
monitoring purposes only.
The following signals are available through the LonWorks network:
V_a, V_b, V_c are the actual three-phase, line-to-neutral RMS voltages on the
PT inputs to the MSLC. The voltage has a times-10 scaling (that is, 1146 would
represent 114.6 volts RMS).
I_a, I_b, I_c are the actual three-phase RMS current inputs on the CT inputs to
the MSLC. The currents have a times-100 scaling (485 would represent 4.85 A
RMS). Negative currents represent current flowing into the local plant (import
current).
P is the actual three-phase RMS real power in watts. Negative watts indicates
power import. The value is not multiplied by the CT and PT ratios, so does not
reflect actual real power across the utility tie, but instead a proportional value to
the actual power flow.
S is the apparent power in volt-amperes (VA). The value is not multiplied by the
CT and PT ratios, so does not reflect actual apparent power across the utility tie,
but instead a proportional value to the actual power flow. Displayed as an
absolute value.
Q is the actual three-phase RMS reactive power in volt-amperes-reactive
(VARs). Negative VARs indicates power absorbed. The value is not multiplied by
the CT and PT ratios, so does not reflect actual reactive power across the utility
tie, but instead a proportional value to the actual power flow.
V_gen is the actual line-to-neutral RMS voltage on the local bus PT input to the
MSLC. The voltage has a times-10 scaling (that is, 1146 would represent 114.6
volts RMS).
Gen_frequency is the local generator bus frequency. The frequency has a
times-100 scaling (that is, 6002 would represent 60.02 Hz).
Util_frequency is the utility bus frequency. The frequency has a times-100
scaling (that is, 6002 would represent 60.02 Hz).
pf is the average of the A, B, and C phase power factors. Power factor has a
times-20000 scaling (that is, 20000 would represent a 1.0 and +20000 would
represent +1.0). Power factor is further encoded such that 1.0 represents 0.0
lagging power factor, +1.0 represents 0.0 leading power factor, and 0.0
represents a power factor of 1.0. (Note: power factor across the utility tie is
available at a 200 ms rate.)
Woodward
69
Manual 02022
Control Status
All described values are available as SNVT_count (Standard Network Variable
Type, count is 16-bits). Discrete inputs, outputs, and alarm values are in
unsigned integer form stored such that the most significant byte is at the lowest
address, with each bit representing a discrete value. Integer values are signed
2's complement, and are updated once per second.
discrete_in is a 16-bit word containing the status of the discrete inputs of the
MSLC and the watchdog function. A bit value of 0 indicates the specified input
is not active (does not have 20-40 Vdc applied). A bit value of 1 indicates that
the specified input is active. The bit representation is:
0Synchronizer Check Mode
1Synchronizer Permissive Mode
2Synchronizer Run Mode
3Circuit Breaker Auxiliary Contact
4Utility Unload
5Import/Export Control
6Process Control
7Ramp Pause
8Set Point Raise
9Set Point Lower
10Voltage Raise
70
Woodward
Manual 02022
11Voltage Lower
120
130
140
15Watchdog Status
discrete_out is a 16-bit word containing the status of the discrete outputs of the
MSLC. A bit value of 0 indicates the specified relay driver output is not active
(has not gone low). A bit value of 1 indicates that the specified output is active.
The bit representation is:
0Low Limit Relay Driver
1High Limit Relay Driver
2Load Switch #1
3Load Switch #2
4Alarm Relay Driver
5Generator Breaker Open
6Utility Breaker Open
7Utility Breaker Close
Bits 915 are not used.
alarm_status is a 16-bit word containing the status of the alarms within the
MSLC. A bit value of 0 indicates the specified alarm is not active. A bit value of
1 indicates that the specified alarm is active. The bit representation is:
0Synchronizer Timeout
1Synchronizer Reclose Attempt Limit
2Utility High Load Limit
3Utility Low Load Limit
4Process Input High Limit
5Process Input Low Limit
6Voltage High Limit
7Voltage Low Limit
load_control_state is a 16-bit word containing the state of the load control
function within the MSLC. The state is encoded as an unsigned value which
represents the present load control state. The load control state is updated once
per second. The value representation is:
0Offline
1Baseload
2Baseload Lower
3Baseload Raise
4Baseload Remote
5Utility Unload
6Process Ramp
7Process Control
8Process Lower
9Process Raise
10Process Remote
11Import/Export Ramp
12Import/Export Control
13Import/Export Lower
14Import/Export Raise
15Import/Export Remote
Woodward
71
Manual 02022
72
Woodward
Manual 02022
Specifications
Data Rate:
Network Isolation:
Common Mode Range:
Electrostatic Discharge:
Maximum Nodes per Bus:
Woodward
73
Manual 02022
Chapter 10.
Troubleshooting
General
The following troubleshooting guide is an aid in isolating trouble to the control
box, actuator, plant wiring, or elsewhere. Troubleshooting beyond this level is
recommended ONLY when a complete facility for control testing is available.
CAUTIONCORRECT VOLTAGE
The control can be damaged with the wrong voltage. When replacing a
control, check the power supply, battery, etc., for the correct voltage.
Bench Tests
The following tests provide a complete test procedure for the MSLC. Do each
test in the order described, as results of tests depend on the results of prior tests.
Failure of any of these tests indicates a failure of the control. See Chapter 11 for
instructions for returning a control for repair.
Accuracy of tests requiring an external meter will be dependent on instrument
accuracy. For best results, use only properly calibrated instruments providing
precision exceeding the calibration tolerance.
Unless otherwise specified, all inputs to the control should be disconnected or
deactivated during bench tests. Several of the tests cannot be done when the
MSLC is in operation. The internal test software verifies that bus and generator
potentials are dead prior to executing the test or calibration procedure.
After doing a calibration step as described in the following sections, save the
calibration value by pressing the SAVE key on the Hand Held Programmer.
Removal of power prior to saving will result in loss of calibration data.
General
Do the following checks on the MSLC. Then verify the functioning of set points
and adjustments.
1.
Connect the Hand Held Programmer to the control in accordance with the
instructions in Chapter 4. Verify that correct voltage and polarity are applied
to the control. Verify that the programmer does its power-up test. Failure to
do the power up test indicates that either the control or Hand Held
Programmer has failed. Replace the MSLC or Hand Held Programmer.
2.
Press the ID key. The message MSLC P/N 54XX-XXX should appear.
Failure to display this message indicates either the control or Hand Held
Programmer has failed. Replace the MSLC or Hand Held Programmer.
3.
Select the Diagnostics menu by pressing 0. The Self Test Result should
display a value of 49. If any other value is displayed, replace the control.
74
Woodward
Manual 02022
4.
Select each of the menus described in Chapter 4 and verify that all set
points are as recorded during installation. If any differences are found,
change the set point(s) to the correct value. Press the SAVE key. The
message Set Points Saved should be displayed. Remove power from the
control for at least 10 seconds. Restore power and verify that correct values
were retained during power down. Failure to save values indicates the
control has failed and should be replaced.
Power Supply
To verify that the MSLC power supply functions over its full operating range, set
the power supply voltage to the minimum specified (18 Vdc). Apply power to the
control and verify that the Self Test Result in Menu 0 is 49. If any other value is
displayed, replace the control. Set supply voltage to the maximum specified for
the model being tested and repeat the diagnostic check.
Discrete Inputs
These tests verify the correct function of each of the switch inputs.
Connect a jumper between terminals 1 and 43 of the MSLC to connect the
discrete input common. Connect a wire to terminal 2 which will provide the
voltage source to test each of the discrete inputs.
With all discrete inputs disconnected, select Menu 9. Step through the menu and
verify that all switch inputs indicate Open.
Connect the wire from terminal 2 to terminal 44, the Synchronizer Check Mode
switch input. Verify that the Check Switch indication on Menu 9 indicates Closed.
Repeat the above step for each of the remaining discrete inputs, terminals 45
through 55, and verify that the corresponding switch input indicates Closed.
An optional minimum voltage test with an external dc power source may be done
on the discrete inputs. Connect the dc source to terminal 43 (+) and repeat the
previous tests with the voltage source set to 12 Vdc.
Process Input
This test verifies the operation and calibration of the Process Variable Input.
Connect a jumper between terminals 37 and 38 for testing with a milliamp
source. If a voltage source is to be used, do not install the jumper. Calibrate the
control with the type of source to be used in service. There is a slight difference
in calibration between milliamp and voltage input. Select the Process Input on
Menu 6. The value displayed should be 0.0 0.1 mA. Connect an adjustable mA
(dc voltage) source to terminals 38 (+) and 39 (+). Set the source for 4.0 mA (1.0
Vdc). The Process Input on Menu 6 should indicate 4.0 0.1 mA. Set the source
for 20.0 mA (5.0 Vdc). The Process Input should indicate 20.0 0.1 mA.
To calibrate the Process Input, select Calibration Menu 6. Set the Calibration Key
to 49. Select the Process Input set point. Set the mA source to 20.0 mA (5.0
Vdc). Adjust the Process Cal set point for 20.0 0.1 mA. Be sure to save the
calibration information by pressing the SAVE key on the Hand Held
Programmer. Repeat the above process input tests to verify correct calibration
over the input range.
Woodward
75
Manual 02022
76
Woodward
Manual 02022
Select Menu 5 and set Configuration Key to 49. Then set the PT Winding Ratio
to 1:1. Verify the System Frequency set point is 50 or 60 Hertz as appropriate.
Set the PT Voltage Input set point to 240 Vac or 120 Vac (nominal) as supplied
for this test. Connect the line potential to the Utility A phase terminal 6 for 240
Vac or terminal 7 for 120 Vac. The actual potential is not important, but should be
within 20% of the nominal of 120 or 240 Vac. Connect neutral to terminal 12.
Connect an AC voltmeter in parallel with the potential. Select Menu 6 and set the
Calibration Key to 49. Select PT Phase A set point, also on Menu 6. Adjust the
set point to read the same as the calibration meter 0.1%.
Repeat the above procedure for the PT Phase B and PT Phase C utility potential
inputs.
Restore the PT Winding Ratio, System Frequency, and PT Voltage Input set
points to their previous values.
LonWorks Network
Menu 0 (Diagnostics Menu), beginning with item 3, contains information to aid in
verifying operation and troubleshooting of network operation.
Woodward
77
Manual 02022
Active DSLCs
Active DSLCs is the number of MSLC/DSLC controls currently in
communication. For example, if six units are installed and powered, the value
displayed by this set point should be 6. If a value less than the number of
MSLC/DSLC controls you have installed is shown, check Menu 5, Network
Address, on all MSLC/DSLC controls to verify that each unit has a unique
address assigned. Press the SAVE key on each unit to be sure the address has
been made effective. After the Set Points Saved message is displayed, refresh
the screen by pressing the Up/Down Arrow key twice and verify that the Menu 5
Network Address set point remains at the desired value. While checking each
MSLC/DSLC control's address assignment, also note the Menu 0 Active DSLCs
set point on each off these units to further aid in troubleshooting.
If Active DSLCs still indicates the wrong value after all addresses are verified,
refer to the Active DSLCs information noted when checking each of the units.
The following are the most probable causes:
1.
If one unit indicates one active MSLC/DSLC and the other units indicate the
number is one less than the actual number of units installed, verify the
wiring to the MSLC/DSLC reporting one active unit. Replace that
MSLC/DSLC if necessary to correct the problem.
2.
If one or more units indicate some number less than the correct value,
power down one MSLC/DSLC at a time (or carefully disconnect the network
wires from each MSLC/DSLC, one at a time) to observe its effect on the
other units' Active DSLCs values. If MSLC/DSLC controls on far ends of the
network are determined not to be in communication with each other, do the
tests described below under Installation Verification below.
If Active DSLCs still indicates the wrong value after doing the above steps,
continue with the tests described below under Neuron Status.
Neuron Status
Neuron Status is a set of data that may be retrieved at any time by pressing the
. key on the Hand Held Programmer. This action causes the Echelon Neuron
network communications processor to read its status registers and pass this
information to the main processor so that it may be observed on the Hand Held
Programmer.
NOTE
When the Retrieve Net Status setpoint in Menu 0 is toggled from False
to True, all status registers are cleared and the current network status is
retrieved. The transaction and message information displayed has been
accumulated since the control was powered up or status was last retrieved.
The following information can be used to determine if the MSLC is operating
correctly.
Menu 0 Transmit Errors is a communications accuracy test. Errors result from
message collisions and weak or noisy signals. The number of errors from
message collisions is a function of the number of messages presented to the
network. More than five or ten errors per second indicates the network function
should be checked.
78
Woodward
Manual 02022
1.
If the network being used by the MSLCs for load sharing is heavily loaded
with other non-load sharing devices, separate the network used by the
MSLCs and their associated devices from the other devices. Routers may
be used if necessary to communicate between the separated networks.
2.
Transaction Timeouts is the number of timeouts that occurred while the unit
was waiting for a response from a message. The MSLC expects responses only
by the deadbus closing functions. If timeout errors occur during deadbus closing,
verify that network wiring installation is to specifications. Otherwise, transaction
timeout errors should not normally occur with MSLCs unless a non-standard
custom installation has been done and another device to which the MSLC has
been connected is not responding.
Rcv (Receive) Transactions Full is the number of times an incoming message
was lost because no more transaction buffers were available. Frequent errors
indicate an overloaded network.
Lost Messages is the number of times the application processor received more
messages at one time than it could process. It is possible in large systems that
enough MSLCs may send out their load sharing information at nearly the same
time that lost messages may occur. Occasional errors will not affect operation. If
frequent errors occur in systems where a custom network installation has been
done, contact the installer. If no custom installation has been done and sufficient
errors are occurring to cause load sharing problems, contact Woodward
Governor Company.
Missed Messages is the number of times the network processor received more
messages at one time than it could process. It is possible that enough MSLCs
may send out their load sharing information at nearly the same time that Rcv
Transaction Full errors may occur. Frequent errors indicate an overloaded
network.
NOTE
Missed and lost message errors will occur during power up when connected
to an active network. This is normal as messages are not processed during
power up diagnostics.
Last Reset Cause is the method by which the Echelon Neuron network chip was
reset. After power-up, Watchdog Reset should initially be the indicated reset
cause. This will switch to Cleared on subsequent retrievals of the diagnostic
data. External Reset indicates the main MSLC processor reset the Neuron chip
after losing communication with it. The number of times this occurs is logged in
Net(work) Interface Errors described below.
Network State should always be Configured, On-line. Any other state indicates
either a defective MSLC or an improper custom installation using a network
management tool.
Network Error Log should always display No Error. Any logged error should
be reported to Woodward Governor Company.
Woodward
79
Manual 02022
Net(work) Interface Errors is the number of times the main MSLC processor
had to reset the Neuron chip due to loss of communications. Errors may occur
during a custom installation and will cease when installation is complete.
Interface errors should not normally occur in operation, but occasional errors that
may be caused by extreme transient interference are possible and will not affect
control function. Frequent errors indicate extreme interference or a defective
MSLC.
Installation Verification
Verify that the overall network wiring has been done according to specification in
Chapters 3 and 9:
1.
2.
3.
4.
5.
6.
7.
8.
9.
NOTE
See Chapter 9 for a complete list of network specifications.
If problems still exist, you may disconnect or replace a MSLC or other device
attached to the network to investigate its effect on the network. If a custom
installation has been done, it will be necessary to use the installation network
management tool to properly install a replacement device on the network.
80
Woodward
Manual 02022
PROBLEM
Unit does not power
up
PROBABLE CAUSE
No input power supply
ACTION
Check +24 V power supply.
*NOTE 1: Installing PROMs backwards will result in the destruction of the chips. PROMs that have
been powered up while installed backwards will need to be replaced.
Woodward
81
Manual 02022
Chapter 11.
Service Options
Product Service Options
The following factory options are available for servicing Woodward equipment,
based on the standard Woodward Product and Service Warranty (5-01-1205)
that is in effect at the time the product is purchased from Woodward or the
service is performed:
Replacement/Exchange
Replacement/Exchange is a premium program designed for the user who is in
need of immediate service. It allows you to request and receive a like-new
replacement unit in minimum time (usually within 24 hours of the request),
providing a suitable unit is available at the time of the request, thereby
minimizing costly downtime. This is also a flat rate structured program and
includes the full standard Woodward product warranty (Woodward Product and
Service Warranty 5-01-1205).
This option allows you to call in the event of an unexpected outage, or in
advance of a scheduled outage, to request a replacement control unit. If the unit
is available at the time of the call, it can usually be shipped out within 24 hours.
You replace your field control unit with the like-new replacement and return the
field unit to the Woodward facility as explained below (see Returning Equipment
for Repair later in this chapter).
Charges for the Replacement/Exchange service are based on a flat rate plus
shipping expenses. You are invoiced the flat rate replacement/exchange charge
plus a core charge at the time the replacement unit is shipped. If the core (field
unit) is returned to Woodward within 60 days, Woodward will issue a credit for
the core charge. [The core charge is the average difference between the flat rate
replacement/exchange charge and the current list price of a new unit.]
Return Shipment Authorization Label. To ensure prompt receipt of the core,
and avoid additional charges, the package must be properly marked. A return
authorization label is included with every Replacement/Exchange unit that leaves
Woodward. The core should be repackaged and the return authorization label
affixed to the outside of the package. Without the authorization label, receipt of
the returned core could be delayed and cause additional charges to be applied.
82
Woodward
Manual 02022
CAUTIONELECTROSTATIC DISCHARGE
To prevent damage to electronic components caused by improper handling,
read and observe the precautions in Woodward manual 82715, Guide for
Handling and Protection of Electronic Controls, Printed Circuit Boards, and
Modules.
Packing a Control
Use the following materials when returning a complete control:
packing materials that will not damage the surface of the unit;
a strong tape around the outside of the carton for increased strength.
Woodward
83
Manual 02022
NOTE
We highly recommend that you make arrangement in advance for return
shipments. Contact a Woodward customer service representative at
1 (800) 523-2831 in North America or +1 (970) 482-5811 for instructions and
for a Return Authorization Number.
Replacement Parts
When ordering replacement parts for controls, include the following information:
Phone Number
+55 (19) 3708 4800
+91 (129) 230 7111
+81 (476) 93-4661
+31 (23) 5661111
You can also contact the Woodward Customer Service Department or consult
our worldwide directory on Woodwards website (www.woodward.com) for the
name of your nearest Woodward distributor or service facility.
84
Woodward
Manual 02022
Engineering Services
Woodward Industrial Controls Engineering Services offers the following aftersales support for Woodward products. For these services, you can contact us by
telephone, by email, or through the Woodward website.
Technical Support
Product Training
Field Service
Contact information:
Telephone+1 (970) 482-5811
Toll-free Phone (in North America)1 (800) 523-2831
Emailicinfo@woodward.com
Websitewww.woodward.com
Technical Support is available through our many worldwide locations or our
authorized distributors, depending upon the product. This service can assist you
with technical questions or problem solving during normal business hours.
Emergency assistance is also available during non-business hours by phoning
our toll-free number and stating the urgency of your problem. For technical
support, please contact us via telephone, email us, or use our website and
reference Customer Services and then Technical Support.
Product Training is available at many of our worldwide locations (standard
classes). We also offer customized classes, which can be tailored to your needs
and can be held at one of our locations or at your site. This training, conducted
by experienced personnel, will assure that you will be able to maintain system
reliability and availability. For information concerning training, please contact us
via telephone, email us, or use our website and reference Customer Services
and then Product Training.
Field Service engineering on-site support is available, depending on the product
and location, from one of our many worldwide locations or from one of our
authorized distributors. The field engineers are experienced both on Woodward
products as well as on much of the non-Woodward equipment with which our
products interface. For field service engineering assistance, please contact us
via telephone, email us, or use our website and reference Customer Services
and then Technical Support.
Woodward
85
Manual 02022
Technical Assistance
If you need to telephone for technical assistance, you will need to provide the following information.
Please write it down here before phoning:
General
Your Name
Site Location
Phone Number
Fax Number
Control/Governor Information
Please list all Woodward governors, actuators, and electronic controls in your system:
86
Woodward
Manual 02022
Appendix A.
MSLC Setup Work Sheet
Synchronizer Menu 1
Sync Gain
__________
Sync Stability
__________Seconds
__________Hertz
Slip Window
__________Hertz
__________Degrees
Voltage Matching
Enabled | Disabled
Voltage Window
__________%
Breaker Delay
__________Seconds
__________Seconds
Close Attempts
__________
Reclose Delay
__________Seconds
Enabled | Disabled
Sync Timeout
__________Seconds
Enabled | Disabled
Auto Re-Synchronize
Enabled | Disabled
__________
Imp/Exp Stability
__________Seconds
Imp/Exp Derivative
__________Seconds
Imp/Exp Deadband
__________%
__________Hertz
Import/Export Droop
__________%
Rated Load
__________kW
Import/Export Level
__________kW
Import/Export 4 mA
__________kW
Woodward
87
__________kW
Baseload 4 mA
__________%
Baseload 20 mA
__________%
__________%/second
__________%/second
__________%/second
__________%/second
__________kW
__________%
__________kW
__________kW
Enabled | Disabled
__________kW
__________kW
Enabled | Disabled
Enabled | Disabled
Enabled | Disabled
Enabled | Disabled
Enabled | Disabled
__________%
__________%
__________%
__________%
Manual 02022
__________
Process Stability
__________Seconds
Process Derivative
__________Seconds
Process Deadband
__________mA
Process Droop
__________%
88
Woodward
Manual 02022
Process Filter
__________Hertz
Process Reference
__________mA
__________mA/Second
__________mA/Second
High Limit PU
__________mA
High Limit DO
__________mA
Enabled | Disabled
Low Limit PU
__________mA
Low Limit DO
__________mA
Enabled | Disabled
Process Switches
Enabled | Disabled
__________
VAR/PF Gain
__________
VAR/PF Stability
__________Seconds
Rated kVARS
__________kVAR
kVAR Reference
__________kVAR
PF Reference
Const-Gen-PF-Ref
__________
PF Deadband
__________
__________V, kV
Enabled | Disabled
__________V, kV
Enabled | Disabled
Voltage Switches
Enabled | Disabled
Woodward
89
Manual 02022
Configuration Menu 5
PT Winding Ratio
:1
CT Rating
:5
Voltage Input
120
240 Vac
Voltage Display
System Frequency
50 Hz | 60 Hz
Process Action
Direct | Indirect
Network Address
__________
__________
Revert Status
Hardware|Lock In Last
_________seconds
Direct | Indirect
90
Woodward
Manual 02022
Appendix B.
MSLC Specifications
Part Numbers
9907-004
9907-005
9907-006
9907-205
Electrical Specifications
Control Power Supply Input
Operating
Maximum
Reverse
Burden
12 to 40 Vdc continuous
7 to 77 Vdc for up to 5 minutes
+56 Vdc continuous
18 W
Synchronizer Input
Voltage
Phases
Frequency
Burden
Accuracy
Current Inputs
Current
Frequency
Burden
Accuracy
0 to 5 A RMS
45 to 66 Hz
less than 0.1 VA per phase
0.1% of full scale
Discrete Inputs
Voltage
Burden
12 to 40 Vdc
10 mA nominal
12 to 40 Vdc
200 mA sink (max)
Analog Inputs
Current
Voltage
Resistance
Woodward
4 to 20 mA
1 to 5 Vdc
243 current mode
10 k voltage mode
91
Manual 02022
Environmental Specifications
Exceeds:
Temperature
Operating
Storage
40 to +70 C
55 to +105 C
Humidity
Operating
95% at 38 C
Mechanical Vibration
Level
Frequency
2.5 G
24 to 2000 Hz
Mechanical Shock
Test Methods
Electromagnetic Susceptibility
Test Method
ANSI/IEEE C37.90.2
Electrostatic Discharge
6000 Volts
Electrical Transients
Test Method
ANSI C37.90.1-1989
92
Woodward
4VAR/PF Control
1.
VAR/PF Control Mode
2.
VAR/PF Gain
3.
VAR/PF Stability
4.
Rated kVARS
5.
kVAR Reference
6.
PF Reference
7.
Const_Gen_PF_Ref
8.
PF Deadband
9.
Voltage Low Limit
10. Voltage Low Alarm
11. Voltage High Limit
12. Voltage High Alarm
13. Voltage Switches
5Configuration
1.
Configuration Key
2.
PT Winding Ratio
3.
CT Rating
4.
PT Voltage Input
5.
Voltage Display
6.
System Frequency
7.
Process Action
8.
Network Address
9.
Network Service Pin
10. Revert Status
11. Net Dropout Time
6Calibration
1.
Calibration Key
2.
Process Input
3.
Remote Input
4.
PT Phase A
5.
PT Phase B
6.
PT Phase C
7.
CT Phase A
8.
CT Phase B
9.
CT Phase C
10. Gen Bus Voltage
11. Synchroscope
12. Command Input
7Electrical Parameters
1.
Active Power (P)
2.
Apparent Power (S)
3.
Reactive Power (Q)
4.
Power Factor (PF)
5.
Phase A
6.
Phase A
7.
Phase A PF
8.
Phase B
9.
Phase B
10. Phase B PF
11. Phase C
12. Phase C
13. Phase C PF
14. Utility Frequency
15. Gen Bus Frequency
16. Gen Bus Voltage
17. Synchroscope
18. Slip Frequency
19. System Load
20. System PF
06/5/F