RSLogix Guard PLUS User Manual ENG

Download as pdf or txt
Download as pdf or txt
You are on page 1of 356

GuardPLC Controller Systems

Bulletin 1753, 1754, 1755


User Manual

Important User Information


Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell
Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences
between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that
each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING

Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.

IMPORTANT

Identifies information that is critical for successful application and understanding of the product.

ATTENTION

Identifies information about practices or circumstances that can lead to personal injury or death, property damage,
or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence

SHOCK HAZARD

Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may
be present.
BURN HAZARD

Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach
dangerous temperatures.

Allen-Bradley, Rockwell Automation, GuardPLC, GuardPLC 1200, GuardPLC 1600, GuardPLC 1800, GuardPLC 2000, RSLogix Guard PLUS!, RSNetWorx, RSNetWorx for EtherNet/IP, RSLinx, RSLogix,
RSLogix 5, RSLogix 5000, PLC-5, ControlLogix, FlexLogix, CompactLogix, SLC 500, PanelView, PanelView Plus, VersaView, FLEX I/O, POINT I/O, PanelBuilder 32, Rockwell Software, and
TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Summary of Changes
The information below summarizes the changes to this manual since
the last publication.
To help you find new and updated information in this release of the
manual, we have included change bars as shown to the right of this
paragraph.

3Publication 1753-UM001C-EN-P - March 2010

For Information About

See

Configuring Communication Between the Controller and a


PanelView PLUS Terminal

205

Updated GuardPLC 1800 specifications

286

Added service life specifications for 1753-OW8 module

294

Updated information on battery replacement

Appendix D

Various updates to style and format

throughout

Summary of Changes

Notes:

Publication 1753-UM001C-EN-P - March 2010

Table of Contents
Preface
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . 17
Purpose of This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Additional Resources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Chapter 1
Overview of Safety Controllers

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Concept . . . . . . . . . . . . . . . . . . . . . . . .
Response to Faults . . . . . . . . . . . . . . . . . . .
Safe States . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . .
GuardPLC System Hardware . . . . . . . . . . . . . .
GuardPLC 1200 System . . . . . . . . . . . . . . .
GuardPLC 1600 and GuardPLC 1800 System
GuardPLC Distributed I/O . . . . . . . . . . . . .
GuardPLC 2000 System . . . . . . . . . . . . . . .
Communication Capabilities . . . . . . . . . . . . . .
GuardPLC Ethernet Network. . . . . . . . . . . .
EtherNet/IP . . . . . . . . . . . . . . . . . . . . . . . .
ASCII. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High-speed Safety Protocol . . . . . . . . . . . .
Modbus RTU Slave. . . . . . . . . . . . . . . . . . .
PROFIBUS DP Slave. . . . . . . . . . . . . . . . . .
OPC Server . . . . . . . . . . . . . . . . . . . . . . . .

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

19
19
20
21
21
21
21
21
22
23
25
27
27
28
28
29
29
29
30

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mount the Equipment . . . . . . . . . . . . . . . . . . . . . . . . .
GuardPLC 1200 Controller . . . . . . . . . . . . . . . . . . .
GuardPLC 1600 and GuardPLC 1800 Controllers,
and Distributed I/O . . . . . . . . . . . . . . . . . . . . . . . .
GuardPLC 2000 Chassis . . . . . . . . . . . . . . . . . . . . .
GuardPLC 2000 Controller, I/O, and Power Supply .
Communication Connections . . . . . . . . . . . . . . . . . . . .
GuardPLC 1200 Controller . . . . . . . . . . . . . . . . . . .
GuardPLC 1600 and GuardPLC 1800 Controllers . . .
GuardPLC Distributed I/O Modules . . . . . . . . . . . .
GuardPLC 2000 Controller . . . . . . . . . . . . . . . . . . .
Reset Pushbutton . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

31
31
32
32

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

33
34
36
38
38
39
41
42
43

Chapter 2
Installation

5Publication 1753-UM001C-EN-P - March 2010

Table of Contents

Chapter 3
General Wiring Considerations

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Prevent Electrostatic Discharge . . . . . . . . . . . . . . . . . . .
Power Supply Considerations . . . . . . . . . . . . . . . . . . . .
Ground the Equipment . . . . . . . . . . . . . . . . . . . . . . . . .
Considerations for Grounding All Controllers . . . . . .
GuardPLC 1200 Controller . . . . . . . . . . . . . . . . . . . .
GuardPLC 1600 and GuardPLC 1800 Controllers and
Distributed I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GuardPLC 2000 Chassis . . . . . . . . . . . . . . . . . . . . . .
Terminal Connections . . . . . . . . . . . . . . . . . . . . . . . . . .
Shield-contact Plate Connections . . . . . . . . . . . . . . . . . .
Detailed Wiring Information . . . . . . . . . . . . . . . . . . . . .

.
.
.
.
.
.

.
.
.
.
.
.

.
.
.
.
.
.

45
45
45
46
46
46

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

47
47
47
48
48

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

49
49
49
50
50
51
51
52
53
53
54
54
55
56
56
58
58
58
59

Chapter 4
Wire GuardPLC 1600, GuardPLC
1800, and GuardPLC 1200
Controllers

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Supply Connections . . . . . . . . . . . . . . . . . .
GuardPLC 1600 and GuardPLC 1800 Controllers
GuardPLC 1200 Controller . . . . . . . . . . . . . . . .
Safety-related Digital Inputs . . . . . . . . . . . . . . . . . .
Safety-related Digital Outputs . . . . . . . . . . . . . . . .
Safety-related Analog Inputs . . . . . . . . . . . . . . . . .
High-speed Counters. . . . . . . . . . . . . . . . . . . . . . .
Wire the GuardPLC 1600 Controller . . . . . . . . . . . .
Safety-related Digital Input Terminals . . . . . . . .
Safety-related Digital Output Terminals . . . . . . .
Wire the GuardPLC 1800 Controller . . . . . . . . . . . .
Safety-related Digital Input Terminals . . . . . . . .
Safety-related Digital Output Terminals . . . . . . .
Safety-related Analog Input Terminals. . . . . . . .
Safety-related High-speed Counter Terminals . .
Wire the GuardPLC 1200 Controller . . . . . . . . . . . .
Lower Terminal Block . . . . . . . . . . . . . . . . . . .
Upper Terminal Block . . . . . . . . . . . . . . . . . . .

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

Chapter 5
Wire the GuardPLC 2000 Controller Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Safety-related Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 61
and I/O
Safety-related Digital Outputs . . . . . . . . . . . . . . .
Safety-Related Analog Inputs (1755-IF8) . . . . . . . .
High-speed Counter Module (1755-HSC) . . . . . . .
Safety-related Analog Output Module (1755-OF8) .
Current Draw . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wire the 1755-IB24XOB16 Digital I/O Module . . .
Wire the 1755-IF8 Analog Input Module. . . . . . . .
6

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

62
62
63
64
64
65
66

Publication 1753-UM001C-EN-P - March 2010

Table of Contents

Wire the 1755-OF8 Analog Output Module. . . . . . . . . . . . . . 66


Wire the 1755-HSC Counter Modules . . . . . . . . . . . . . . . . . . 68

Chapter 6
Wire 1753-IB16, 1753-OB16, and
1753-IB20XOB8 Modules

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety-related Digital Inputs . . . . . . . . . . . . . . .
Safety-related Digital Outputs . . . . . . . . . . . . .
Power Supply Connections . . . . . . . . . . . . . . .
Wire the 1753-IB16 Input Module . . . . . . . . . .
Safety-related Digital Inputs . . . . . . . . . . . .
Pulse Test Sources . . . . . . . . . . . . . . . . . . .
Wire the 1753-OB16 Output Module . . . . . . . .
Operating Voltage Considerations. . . . . . . .
Safety-related Digital Outputs . . . . . . . . . . .
Wire the 1753-IB20XOB8 Combination Module
Safety-related Digital Inputs . . . . . . . . . . . .
Safety-related Digital Outputs . . . . . . . . . . .

.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.

69
69
70
70
71
71
72
73
73
73
75
75
76

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

77
77
78
78
78
79
80
81

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety-related Digital Inputs . . . . . . . . . . . . . . . . . . . . . .
Terminal Connections . . . . . . . . . . . . . . . . . . . . . . .
Safety-related Digital Outputs . . . . . . . . . . . . . . . . . . . .
Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal Connections . . . . . . . . . . . . . . . . . . . . . . .
Monitor for Line Short Line Break . . . . . . . . . . . . . . . . .
Line Monitoring for Lamp and Inductive Loads . . . . .
Line Monitoring with Reduced Voltage for Resistive,
Capacitive Loads . . . . . . . . . . . . . . . . . . . . . . . . . . .
Required Signals for Line Monitoring . . . . . . . . . . . .
Pulse Test Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

83
83
85
86
86
90
91
91

Chapter 7
Wire and Configure the
1753-IB8XOB8 Module

Introduction . . . . . . . . . . . . . . . . . .
Safety-related Digital Inputs . . . . . . .
Terminal Connections . . . . . . . .
Surge on Digital Inputs . . . . . . .
Safety-related Digital Outputs . . . . .
Signals for Output Configuration
Terminal Connections . . . . . . . .
Pulse Test Sources . . . . . . . . . . . . .

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

Chapter 8
Wire and Configure the
1753-IB16XOB8 Module

Publication 1753-UM001C-EN-P - March 2010

. . . 92
. . . 93
. . . 93

Table of Contents

Chapter 9
Wire the 1753-IF8XOF4 Analog I/O Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Safety-related Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . 95
Module
Voltage Measurement.
Current Measurement .
Terminal Connections
Standard Analog Outputs.
Terminal Connections

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

95
95
96
97
98

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety-related Relay Outputs . . . . . . . . . . . . . . . .
Terminal Connections . . . . . . . . . . . . . . . . . . . . .
Example: Connecting Actuators to the Outputs
Voltage Supply Considerations. . . . . . . . . . . . . . .

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

. 99
. 99
. 99
100
100

Chapter 10
Wire the 1753-OW8 Relay Output
Module

Chapter 11
Pulse Testing

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Response to OS Configurable Faults. . . . . . . . . . . .
Wire for OS Configurable Line Control. . . . . . . . . .
GuardPLC 1600 Controller and 1753-IB20XOB8
Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1753-IB16, 1753-IB8XOB8, and 1753-IB16XOB8
Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input Configuration for Pulse Testing. . . . . . . . . . .

. . . . . . 101
. . . . . . 102
. . . . . . 103
. . . . . . 103
. . . . . . 104
. . . . . . 105

Chapter 12
High-Speed Counters

Introduction . . . . . . . . . . . . . . . . . . . . . . .
Counter/Decoder Modes . . . . . . . . . . . . . .
Counter Mode . . . . . . . . . . . . . . . . . . .
Decoder Mode. . . . . . . . . . . . . . . . . . .
Understand Counter Module Configuration
Counter Mode/Manual Direction. . . . . .
Counter Mode/Direction and Reset . . . .
Decoder Mode/Gray Codes . . . . . . . . .

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.

107
107
107
108
109
109
110
111

................
................
................
................
................
(in Stop Mode only).
................

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

113
113
116
117
120
121
122

Chapter 13
Controller Configuration and
Modes of Operation

Introduction . . . . . . . . . . . . . . . .
Controller Modes . . . . . . . . . . . .
Recover From a Failure_Stop .
Controller Configuration . . . . . . .
Routine Modes . . . . . . . . . . . . . .
Load a Configuration and Routine
Test Mode of the Routine . . . . . .

Publication 1753-UM001C-EN-P - March 2010

Table of Contents

Chapter 14
Use the Control Panel to Monitor
Status

Introduction . . . . . . . . . . . . . . . . . . . .
Resource State Tab . . . . . . . . . . . . . . .
Safety Parameters Tab . . . . . . . . . . . . .
Statistics Tab . . . . . . . . . . . . . . . . . . . .
P2P (Peer-to-Peer) State Tab . . . . . . . .
Distributed I/O Tab. . . . . . . . . . . . . . .
HH (High-level High-speed) State Tab .
Environment Data Tab . . . . . . . . . . . .
OS Tab . . . . . . . . . . . . . . . . . . . . . . . .
HSP Protocol Tab . . . . . . . . . . . . . . . .
EIP Protocol Tab. . . . . . . . . . . . . . . . .
Use the Multi Control Panel . . . . . . . . .
Control Panel Resource Menu . . . . . . .
Control Panel Extra Menu . . . . . . . . . .

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.

123
124
125
126
127
128
128
129
129
130
131
132
135
136

Chapter 15
Diagnostics

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
View Controller Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . 139
Choose Online or Offline Diagnostics . . . . . . . . . . . . . . 141
Filtering Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . 141
GuardPLC 1200 Controller Status Indicators . . . . . . . . . . . . 142
GuardPLC 1600 and GuardPLC 1800 Controllers and GuardPLC
Distributed I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
System Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . 143
Communication Status Indicators . . . . . . . . . . . . . . . . . 144
GuardPLC 2000 Controller Status Indicators . . . . . . . . . . . . 145
Controller Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Routine Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Ethernet Communication Indicators . . . . . . . . . . . . . . . 146
Serial Communication Indicators. . . . . . . . . . . . . . . . . . 147
1755-IB24XOB16 Module Status Indicators . . . . . . . . . . . . . 147
Power Supply and Module Status . . . . . . . . . . . . . . . . . 147
I/O Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
1755-IF8 Analog Input Module Status Indicators . . . . . . . . . 148
1755-OF8 Analog Output Module Status Indicators . . . . . . . 149
1755-HSC Combination High-speed Counter and Output Module
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Power Supply and Module Status . . . . . . . . . . . . . . . . . 150
I/O Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150

Chapter 16
Peer-to-peer Communication
Overview

Publication 1753-UM001C-EN-P - March 2010

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Peer-to-peer Communication Basics . . . . . . . . . . . . . . . . . . 151
Networking Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
9

Table of Contents

Network Configuration . . . . . . . . . . . . . . . . . . . .
HH Protocol Parameters . . . . . . . . . . . . . . . . . . .
Token Group ID . . . . . . . . . . . . . . . . . . . . . .
Protocol Mode . . . . . . . . . . . . . . . . . . . . . . . .
Link Mode . . . . . . . . . . . . . . . . . . . . . . . . . . .
Response Time . . . . . . . . . . . . . . . . . . . . . . .
Token Cycle Time . . . . . . . . . . . . . . . . . . . . .
Token Alive Timeout . . . . . . . . . . . . . . . . . . .
Primary Timeout . . . . . . . . . . . . . . . . . . . . . .
Secondary Interval . . . . . . . . . . . . . . . . . . . . .
Link Mode (Extern) . . . . . . . . . . . . . . . . . . . .
Response Time (Extern) . . . . . . . . . . . . . . . . .
Peer-to-peer Protocol Parameters . . . . . . . . . . . . .
Message Response Time (ReponseTime) . . . . .
Receive Timeout (ReceiveTMO) . . . . . . . . . . .
Resend Timeout (ResendTMO) . . . . . . . . . . . .
Acknowledge Timeout (AckTMO) . . . . . . . . .
Queue Length (QueueLen). . . . . . . . . . . . . . .
Production Rate (ProdRate) . . . . . . . . . . . . . .
Watchdog Time (WDZ) . . . . . . . . . . . . . . . . .
Worst-case Reaction Time (TR). . . . . . . . . . . .
HH Network Profiles . . . . . . . . . . . . . . . . . . . . . .
Profile I: Fast . . . . . . . . . . . . . . . . . . . . . . . . .
Profile II: Medium . . . . . . . . . . . . . . . . . . . . .
The None Profile . . . . . . . . . . . . . . . . . . . . .
Peer-to-Peer Network Profiles . . . . . . . . . . . . . . .
Peer-to-Peer Profile I: Fast & Cleanroom . . . . .
Peer-to-Peer Profile II: Fast & Noisy . . . . . . . .
Peer-to-Peer Profile III: Medium & Cleanroom.
Peer-to-Peer Profile IV: Medium & Noisy . . . .
Peer-to-Peer Profile V: Slow & Cleanroom. . . .
Peer-to-Peer Profile IV: Slow & Noisy . . . . . . .

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

153
153
154
154
155
155
155
156
156
156
156
156
157
157
158
159
159
159
160
160
160
161
161
164
167
168
169
170
171
172
173
174

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

175
175
176
178
178
179
179
180
180
181
182

Chapter 17
Configure Peer-to-Peer
Communication

10

Introduction . . . . . . . . . . . . . . . . . . . .
Considerations for Using Peer-to-peer .
Set Peer-to-Peer Controller Properties .
Create a Peer-to-peer Network. . . . . . .
Create Token Group(s) . . . . . . . . .
Add Controllers to Token Group(s)
Configure Token Group(s) . . . . . . .
Design the Logic . . . . . . . . . . . . . . . . .
Create Peer-to-peer Signals. . . . . . .
Use Peer-to-peer System Signals . . .
Design the Logic for all Controllers.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

Publication 1753-UM001C-EN-P - March 2010

Table of Contents

Configure Peer-to-peer Communication . . . . . . . . .


Define Controller Connections . . . . . . . . . . . . .
Assign HH-Network . . . . . . . . . . . . . . . . . . . . .
Choose a Peer-to-peer Profile . . . . . . . . . . . . . .
Define Peer-to-peer Parameters . . . . . . . . . . . .
Define The Signals to Exchange Between Each
Controller Connection . . . . . . . . . . . . . . . . . . .
Compile and Download . . . . . . . . . . . . . . . . . . . .
Compile Logic . . . . . . . . . . . . . . . . . . . . . . . . .
Start Download . . . . . . . . . . . . . . . . . . . . . . . .
Network Optimizing . . . . . . . . . . . . . . . . . . . . . . .
Check Routine Timing . . . . . . . . . . . . . . . . . . .
Reconfigure Watchdog Time . . . . . . . . . . . . . .
Check HH Status . . . . . . . . . . . . . . . . . . . . . . .
Check Peer-to-peer Status. . . . . . . . . . . . . . . . .
Reconfigure ResponseTime . . . . . . . . . . . . . . .
Reconfigure Receive Timeout . . . . . . . . . . . . . .

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

184
184
185
186
186

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

187
189
189
189
190
191
192
193
194
195
197

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EtherNet/IP Communication Overview. . . . . . . . . . . . . . . .
GuardPLC Controller as an Adapter . . . . . . . . . . . . . . .
GuardPLC Controller as a Scanner . . . . . . . . . . . . . . . .
Data Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Software Required to Configure EtherNet/IP
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Add EtherNet/IP Protocol to the Resource . . . . . . . . . . . . .
View the Controller IP Settings . . . . . . . . . . . . . . . . . . . . .
Configuring Communication Between the Controller and a
PanelView PLUS Terminal . . . . . . . . . . . . . . . . . . . . . . . . .
Set Up FactoryTalk View Studio Machine Edition
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Add Ethernet/IP Protocol to Your Project . . . . . . . . . . .
Read Integers from the Controller and Display Them
on the PanelView Plus Terminal . . . . . . . . . . . . . . . . . .
Read BOOLs from the GuardPLC Controller and Display
Them on the PanelView Plus Terminal . . . . . . . . . . . . .
Writing Integers to the GuardPLC Controller from the
PanelView Plus Terminal . . . . . . . . . . . . . . . . . . . . . . .
Writing BOOLs to the GuardPLC Controller from the
PanelView Plus Terminal . . . . . . . . . . . . . . . . . . . . . . .

199
199
199
201
202

Chapter 18
Introduction to EtherNet/IP
Communication

Publication 1753-UM001C-EN-P - March 2010

203
203
204
205
206
208
209
210
212
213

11

Table of Contents

Chapter 19
Use GuardPLC Controller as an
Adapter

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure the GuardPLC Controller as an Adapter . . . . . . .
Configure the Adapter Input Assembly . . . . . . . . . . . . .
Configure the Adapter Output Assembly . . . . . . . . . . . .
Connect Signals to the Adapter Assemblies . . . . . . . . . .
Open a Class 1 Connection from a Logix Controller to the
GuardPLC Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure the Logix Controller in RSLogix 5000
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure the Type of Connection . . . . . . . . . . . . . . . .
Download and Go Online . . . . . . . . . . . . . . . . . . . . . .
Monitor Connection Status . . . . . . . . . . . . . . . . . . . . . .
Use the Force Editor to Test the Connection . . . . . . . . .
Remove or Inhibit a Connection . . . . . . . . . . . . . . . . . .
Open a Class 3 Connection from a Logix Controller . . . . . .
Configure the GuardPLC Controller Assemblies . . . . . . .
Create a Project for the Logix Controller . . . . . . . . . . . .
Create Tags to Read and Write Assembly Data . . . . . . .
Create Ladder Logic . . . . . . . . . . . . . . . . . . . . . . . . . . .
Download and Go to Run . . . . . . . . . . . . . . . . . . . . . .
Verify the Data Exchange . . . . . . . . . . . . . . . . . . . . . . .
Use a GuardPLC Controller as an Unconnected Adapter . . .
Use Unconnected PCCC Messaging from a PLC-5 or
SLC 5/05 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure an EtherNet/IP Driver. . . . . . . . . . . . . . . . . .
Create an EtherNet/IP Project in RSLogix Programming
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Add a Message Instruction to Your Application Program
Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use Unconnected CIP Messaging from a PanelView
Standard Terminal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Create an EtherNet/IP Application . . . . . . . . . . . . . . . .
Configure the PanelView Terminal for EtherNet/IP
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure a Write Operation . . . . . . . . . . . . . . . . . . . .
Configure a Read Operation . . . . . . . . . . . . . . . . . . . . .

215
215
215
216
217
219
219
220
225
226
227
228
228
228
229
229
230
233
233
235
235
237
237
239
243
244
245
246
247

Chapter 20
Use the GuardPLC Controller as a
Scanner

12

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Prepare the GuardPLC Controller for Class 1 Scanner
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connect the Scanner Signals. . . . . . . . . . . . . . . .
Disable Scanner Function on the Controller . . . .
Configure the EtherNet/IP Driver . . . . . . . . . . . . . . .

. . . . . 249
.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

249
250
251
252

Publication 1753-UM001C-EN-P - March 2010

Table of Contents

Configure Connections in RSNetWorx for EtherNet/IP


Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Open a Connection to a Logix Controller . . . . . . . . . . . . .
Create a Producing Data Tag . . . . . . . . . . . . . . . . . . .
Configure Connections from the GuardPLC Controller
to the Logix Controller . . . . . . . . . . . . . . . . . . . . . . . .
Save the Connection Configuration in the GuardPLC
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remove the Connection Configuration . . . . . . . . . . . . . . .

. 254
. 260
. 260
. 261
. 262
. 263

Chapter 21
Communicate with ASCII Devices Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
Connect the Controller to an ASCII Device . . . . . . .
Connect to a GuardPLC 1200 Controller . . . . . .
Connect to a GuardPLC 1600 or 1800 Controller
Connect to a GuardPLC 2000 Controller . . . . . .
Configure the ASCII Serial Port . . . . . . . . . . . . . . .
Connect Signals . . . . . . . . . . . . . . . . . . . . . . . . . .
ASCII Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . .
ASCII Master - Request . . . . . . . . . . . . . . . . . . .
ASCII Slave - Controller Response. . . . . . . . . . .
Data Type Formats. . . . . . . . . . . . . . . . . . . . . .

.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.

265
265
266
267
268
269
270
270
271
273

.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.

275
275
276
276
277
279
279
280
280
282

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

283
284
286
288
288
290
292
294
296

Chapter 22
Communicate with Modbus and
Profibus Devices

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus RTU Slave Protocol . . . . . . . . . . . . . . . . .
Connect the Controller to a Modbus Device . . .
Configure the Modbus Serial Port . . . . . . . . . . .
Connect Signals . . . . . . . . . . . . . . . . . . . . . . . .
Profibus DP Slave Protocol . . . . . . . . . . . . . . . . . .
Connect the Controller to a Profibus DP Device
Configure the Profibus DP Serial Port . . . . . . . .
Connect Signals . . . . . . . . . . . . . . . . . . . . . . . .
Configure the Profibus Master . . . . . . . . . . . . .

Appendix A
Specifications

Publication 1753-UM001C-EN-P - March 2010

GuardPLC 1200 Controller . . . . . . . . . . . . . . . .


GuardPLC 1600 Controller . . . . . . . . . . . . . . . .
GuardPLC 1800 Controller . . . . . . . . . . . . . . . .
Distributed I/O . . . . . . . . . . . . . . . . . . . . . . . .
1753-IB16 Input Module. . . . . . . . . . . . . . .
1753 Combination I/O Modules . . . . . . . . .
1753-IF8XOF4 Analog Combination Module
1753-OW8 Relay Output Module . . . . . . . .
1753-OB16 Output Module. . . . . . . . . . . . .

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

13

Table of Contents

GuardPLC 2000 Controller . . . . . . . . . . . . .


GuardPLC 2000 Distributed I/O Modules . .
1755-IB24XOB16 Digital I/O Module . .
1755-IF8 Analog Input Module . . . . . . .
1755-OF8 Analog Output Module . . . . .
1755-HSC High Speed Counter Module.
GuardPLC 2000 Power Supply . . . . . . . . . .

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

297
298
298
299
300
302
303

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming Controller Data . . . . . . . . . . . . . . . . . . . . . .
I/O Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Digital I/O Module Variables (AB-DIO) for
GuardPLC 1200 and 2000 Controllers . . . . . . . . . . . . . .
Analog Input Module Variables (AB-AI) for
GuardPLC 2000 Controller . . . . . . . . . . . . . . . . . . . . . .
Analog Output Module Variables (AB-AO) for
GuardPLC 2000 Controller . . . . . . . . . . . . . . . . . . . . . .
High-Speed Counter Variables For GuardPLC 1200 and
2000 Controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Variables for GuardPLC 1600 and 1800
Controllers and Distributed I/O . . . . . . . . . . . . . . . . . .
Digital Input Module Variables for GuardPLC 1600
Controllers and Distributed I/O . . . . . . . . . . . . . . . . . .
Digital Output Module Variables for
GuardPLC 1600/1800 Controllers, 1753-IB20XOB8
Modules, and 1753-OB16 Modules . . . . . . . . . . . . . . . .
Digital Output Parameters for 1753-IB8XOB8
Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Digital Output Parameters for 1753-IB16XOB8
Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Digital Relay Output Parameters for 1753-OW8
Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Input Signals for 1753-IF8XOF4 Modules . . . . . .
Analog Output Signals for 1753-IF8XOF4 Modules . . . .
Counter Module Variables for GuardPLC 1800
Controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Digital (Analog) Input Variables for the GuardPLC 1800
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

305
305
307

Appendix B
System Signal Variables

14

307
309
311
312
315
316

318
319
320
322
323
325
326
328

Publication 1753-UM001C-EN-P - March 2010

Table of Contents

Appendix C
Wiring Examples

Introduction . . . . . . . . . . . . . . . . . . . . . . . . .
GuardPLC 1600 Controller . . . . . . . . . . . . . . .
GuardPLC 1800 Controller . . . . . . . . . . . . . . .
1753-IB16 Modules . . . . . . . . . . . . . . . . . . . .
1753-OB16 Modules . . . . . . . . . . . . . . . . . . .
1753-IB20XOB8 Module . . . . . . . . . . . . . . . .
1753-IB8XOB8 Modules . . . . . . . . . . . . . . . .
1753-IB16XOB8 Modules. . . . . . . . . . . . . . . .
1753-OW8 Modules. . . . . . . . . . . . . . . . . . . .
1753-IF8XOF4 Modules . . . . . . . . . . . . . . . . .
GuardPLC 1200 Controller . . . . . . . . . . . . . . .
1755-IB24XO16 Digital Input/Output Modules
1755-IF8 Analog Input Modules . . . . . . . . . . .
1755-OF8 Analog Output Modules . . . . . . . . .
1755-HSC High Speed Counter Module . . . . .

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

331
332
333
334
335
336
337
338
339
340
341
342
343
343
344

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

345
346
347
347

Appendix D
Replacing the Back-up Battery

Preventing Electrostatic Discharge


GuardPLC 1200 Controllers . . . . .
GuardPLC 2000 Power Supply . . .
Battery Disposal . . . . . . . . . . . . .

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

.
.
.
.

Index

Publication 1753-UM001C-EN-P - March 2010

15

Table of Contents

16

Publication 1753-UM001C-EN-P - March 2010

Preface

Who Should Use This


Manual

Use this manual if you are responsible for designing, installing,


programming, or troubleshooting control systems that use GuardPLC
controllers.
Personnel responsible for installation, programming, operation, and
troubleshooting of safety-related controllers must be familiar with
relevant safety standards for programmable electronic systems (PES).

Purpose of This Manual

The manual only briefly describes the safety concept of the GuardPLC
family of controllers. Its purpose is to provide information on
installing and operating your controller system.
For detailed information on the safety policy regarding GuardPLC
controllers, including information on the controllers central functions,
input and output channels, operating system, application program
safety and regulations for use, refer to the GuardPLC Controller
Systems Safety Reference Manual, publication 1753-RM002.
For procedural information on programming and configuring
GuardPLC Controller Systems with RSLogix Guard PLUS! programming
software, refer to Using RSLogix Guard PLUS! Software with GuardPLC
Controllers, publication 1753-PM001.

Additional Resources

The table on the following page lists documents that contain


additional information concerning Rockwell Automation GuardPLC
products.
You can view or download publications at
http://www.rockwellautomation.com/literature. To order paper copies
of technical documentation, contact your local Rockwell Automation
distributor or sales representative.

17Publication 1753-UM001C-EN-P - March 2010

17

Preface

Preface

Resource

Description

Using RSLogix Guard PLUS! Software with GuardPLC


Controllers Programming Manual, publication 1753-PM001

Provides procedural information for programming GuardPLC Controller


Systems Using RSLogix Guard PLUS! Programming Software

GuardPLC Controller Systems Safety Reference Manual,


publication 1753-RM002

Contains in-depth information on the safety concept of GuardPLC


controller systems, including the DeviceNet Safety Scanner for GuardPLC
Controller.

DeviceNet Safety Scanner for GuardPLC Controllers User


Manual, publication 1753-UM002

Provides information on installing, configuring, and operating a DeviceNet


Safety Scanner in a GuardPLC application

DeviceNet Safety I/O User Manual, publication


1791DS-UM001

Provides information on operating 1791DS DeviceNet Safety I/O Modules

GuardPLC Certified Function Blocks Safety Reference Manual, Provides information on using Certified Function Blocks in your GuardPLC
safety application
publication 1753-RM001
EtherNet/IP Performance and Application Guide, publication
ENET-AP001

Information on EtherNet/IP protocol

Industrial Automation Wiring and Grounding Guidelines,


publication 1770-4.1

In-depth information on grounding and wiring Allen-Bradley


programmable controllers

Application Considerations for Solid-State Controls,


publication SGI-1.1

A description of important differences between solid-state programmable


controller products and hard-wired electromechanical devices

National Electrical Code - Published by the National Fire


Protection Association of Boston, MA.

An article on wire sizes and types for grounding electrical equipment

18

Publication 1753-UM001C-EN-P - March 2010

Chapter

Overview of Safety Controllers

Introduction

Safety Concept

Topic

Page

Safety Concept

19

Safe States

21

GuardPLC System Hardware

21

Communication Capabilities

27

GuardPLC controllers feature a fail-safe CPU according to IEC 61508


(SIL 3) and ISO 13849-1 (PLe/Cat. 4). Faults that cause loss of safety
function are detected within the safety time you specify. Faults that
cause loss of safety function only in combination with another fault,
are detected at least within the multiple error occurrence time (24
hours).
This results in these requirements for the safety concept:
You specify the safety time and the watchdog time. The multiple
error occurrence time is preset to 24 hours.
Even upon the detection of an error, the controller continues to
react in a safety-related way.
Faulty input signals (for example, incorrectly transmitted input
values) do not affect the safe function of the controller. Faulted
input signals have a 0 value.
An error in a non-safety-related module does not affect the
safety of the controller.
The failure of the controller has no effect on the safety of other
safety-related modules.
For more information on the safety concept, refer to the GuardPLC
Controllers Safety Reference Manual, publication 1753-RM002.

19Publication 1753-UM001C-EN-P - March 2010

19

Chapter 1

Overview of Safety Controllers

Response to Faults
Type of I/O Error

Controller Behavior

Permanent

If an error occurs at an I/O point, only this I/O point is considered faulty and not the entire module.
In case of faulty input points, 0 is assumed to be the safe value. Faulty output channels are de-energized. If it
is not possible to de-energize a single point, the entire module is considered to be faulty, the entire module is
de-energized, and the corresponding error status is set. The controller reports the error to the user program. If
the entire module cannot be de-energized, the controller goes to Failure_Stop.

Transient

A transient error is an error that occurs in an I/O module and then disappears by itself. If a transient error
occurs, the module performs a self test. If the test is successful, the status of the I/O module is set to good
and the modules normal function continues.
In the process, the GuardPLC controller performs a statistical evaluation of the frequency of errors. The I/O
module is permanently set to faulty if the pre-set error frequency is exceeded. In this case, the module does
not resume its normal function after the error has disappeared. To resume normal function, you must cycle
power or change the controller to Stop and then Run.
If an error persists for a period of time exceeding that of the multiple error occurrence time (24 hours), the I/O
module is permanently set to faulty and does not continue normal function after the disappearance of the
error. The I/O module can only resume normal function after you cycle power or Stop/Start the controller.
For faulty modules, the controller uses safe values (0, LOW).

Controller

Upon the detection of an error, the controller goes to Failure_Stop and all output channels are set to the safe
state (value = 0).
In some cases in which a Failure_Stop occurs, a power cycle will not enable normal operation. A manual reset
from Stop to Run, using RSLogix Guard PLUS! software, is required. Cat. 4 faults typically require manual
resets.
An error in the user program is not considered an error of the controller.

The controller also monitors the timing and consistency of the:

20

hardware self-tests and software self-tests of the controller.


cycle of the user program.
processing of the I/O signals including I/O tests.
run cycle of the controller.
transition from Run to Stop.

Publication 1753-UM001C-EN-P - March 2010

Overview of Safety Controllers

Safe States

Chapter 1

Inputs
The safe state of an input is indicated by a 0 signal being passed to
the user program logic. When a fault occurs, the inputs are switched
off (0).

Outputs
An output is in the safe state when it is de-energized. In the event of a
fault, all outputs are switched off. This includes faults in Ethernet
communication.

GuardPLC System
Hardware

GuardPLC 1200 System


The GuardPLC 1200 controller is a compact system consisting of a
CPU, watchdog, and on-board digital I/O. The GuardPLC 1200
controller features 20 digital inputs, 8 digital outputs, and 2
high-speed counters. An RS-232 serial port supports ASCII
communication and an Ethernet port provides safety-related
communication. A user-supplied 24V DC power supply is required.
See page 45 for power supply connections.
GuardPLC 1200 Controller
Upper Terminal Block

Back-up Battery
Compartment

PLC
1200

Port for
Factory
Use Only

ASCII Serial Port

Lower Terminal Block


Ethernet Dongle
Required
Ethernet Port
(on Bottom of Controller)

RJ-45 Port

Publication 1753-UM001C-EN-P - March 2010

21

Chapter 1

Overview of Safety Controllers

GuardPLC 1600 and GuardPLC 1800 System


GuardPLC 1600 Controller
RJ-45 Ethernet Ports (on Top of Controller)

Digital Outputs

Voltage Supply
Connection

RS-485 Serial Ports


(See Page 23)

Digital Inputs

RJ-45 Ethernet Ports (on Bottom of Controller)

GuardPLC 1800 Controller


RJ-45 Ethernet Ports (on Top of Controller)
Digital Outputs
Voltage Supply
Connection

Digital Inputs

RS-485 Serial Ports

High Speed
Counter

(See Page 23)

RJ-45 Ethernet Ports (on Bottom of Controller)

Analog Inputs

The GuardPLC 1600 system features 20 digital inputs and 8 digital


outputs with the addition of optional distributed Safety I/O. The
GuardPLC 1800 system features 24 digital inputs, 8 digital outputs, 8
safety-related analog inputs, and 2 high-speed counters, as well as
optional distributed Safety I/O. The status of inputs and outputs is
indicated via status indicators. A user-supplied 24V DC power supply
is required. See page 45 for information on power supply
requirements.
Each controller features four 10/100BaseT, RJ-45 connectors to
provide safety-related communication via the GuardPLC Ethernet
network to distributed I/O and other GuardPLC controllers, OLE for
Process Control (OPC) servers(1), and with RSLogix Guard PLUS!
programming software. The four connectors and the controller are
connected via an internal Ethernet switch.

(1)

22

The OPC server is not suitable for safety-related communication.

Publication 1753-UM001C-EN-P - March 2010

Overview of Safety Controllers

Chapter 1

Three ports are located on the front of the controller, providing these
non-safety-related communication options.
Serial Port
Designation

Function

COMM1
(RS-485)

Modbus RTU Slave (1753-L28BBBM or 1753-L32BBBM-8A)


Profibus-DP-Slave (1753-L28BBBP or 1753-L32BBBP-8A) Read/Write

COMM2

not used

COMM3
(RS-485)

GuardPLC ASCII Protocol (Read-only)/High-Speed Safety Protocol (HSP)

The COMM3 (RS-485) also supports High-Speed Safety Protocol (HSP)


for high-integrity communication with the 1753-DNSI DeviceNet
Safety Scanner.
Refer to the DeviceNet Safety Scanner for GuardPLC Controllers User
Manual, publication 1753-UM002, for more information.

GuardPLC Distributed I/O


The following modules are available for use with the GuardPLC 1600
controllers, GuardPLC 1800 controllers, and series C GuardPLC 1200
controllers, and with series C GuardPLC 2000 CPUs. Module status is
indicated via status indicators.

Publication 1753-UM001C-EN-P - March 2010

Cat. No.

Description

Inputs

Outputs

1753-IB16

Input Module

16 digital (not isolated)


4 pulse test sources

NA

1753-OB16

Output Module

NA

16 digital (not isolated)

1753-IB20XOB8

Input/Output
Module

20 digital (not isolated)

8 digital (not isolated)

1753-IB8XOB8

Input/Output
Module

8 digital (not isolated)


2 pulse test sources

8 positive-switching digital
2 negative-switching digital
(not isolated)

1753-IB16XOB8

Input/Output
Module

16 digital (not isolated)


2 pulse test sources

8 two-pole digital
(not isolated)

1753-OW8

Relay Output
Module

NA

8 relay

1753-IF8XOF4

Analog
Input/Output
Module

8 analog

4 standard analog

23

Chapter 1

Overview of Safety Controllers

GuardPLC 1753 Digital I/O Modules


1753-OB16 Module

1753-IB16 Module
Digital Inputs
Voltage Supply Connection

L- L-

L+

L+

Voltage Supply
Connection

1 2 3 4 5 6

7 8 9 10 11 12

1 2 3 4 5 6

7 8 9 10 11 12

13 14 15 16 17 18

LS+ 1 2 3 4 L-

LS+ 5 6 7 8 L-

LS+ 9 10 11 12 L-

Digital
Outputs

13 14 15 16 17 18

1 2 3 4 5 6

24V DC

D1

D1

Digital
Outputs

Voltage Supply
Connection

7 8 9 10 11 12

1 2 3 4 5 6

D1

L- L-

L+

7 8 9 10 11 12

L+

L- L-

24V DC

L+

L+

24V DC

DO L- 1 2 3 4 L-

DO L- 5 6 7 8 L-

24 V DC
RUN
24 V DC

ERROR

RUN

PROG

ERROR

FORCE

PROG

FAULT

1753-IB16
16 DC Inputs
4 Pulse Test Sources

OSL
BL

FORCE
FAULT

1753-OB16
16 DC Outputs

OSL

LS+ 13 14 15 16 L-

PO PULSE TEST
L- 1 2 3 4 L-

19 20 21 22 23 24

25 26 27 28 29 30

19 20 21 22 23 24

25 26 27 28 29 30

BL

DO L- 9 10 11 12 L-

DO L- 13 14 15 16 L-

13 14 15 16 17 18

19 20 21 22 23 24

13 14 15 16 17 18

19 20 21 22 23 24

GuardPLC Ethernet

10/100 BaseT
1

()

()

GuardPLC Ethernet

10/100 BaseT
1

Digital Inputs

()

()

Pulse Test Sources


Ethernet Ports

Ethernet Ports (on Bottom of Module)

Digital Outputs

(on Bottom of Module)

1753-IB20XOB8 Module
Voltage Supply Connection

L- L-

L+

Digital Outputs
1 2 3 4 5 6

7 8 9 10 11 12

1 2 3 4 5 6

7 8 9 10 11 12

DO L- 1 2 3 4 L-

DO L- 7 8 9 10 L-

L+

24V DC

(2A)

(2A)

24 V DC
RUN
ERROR
PROG
FORCE
FAULT

1753-IB20OXB8
20 DC Inputs
8 DC Outputs

OSL
BL
D1
LS+ 1 2 3 4 L-

D1
LS+ 5 6 7 8 L-

D1
LS+ 9 10 11 12 L-

D1
LS+ 13 14 15 16 L-

D1
LS+ 17 18 19 20 L-

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

13 14 15 16 23 24

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

GuardPLC Ethernet

10/100 BaseT
1

()

()

Ethernet Ports (on Bottom of Module)


1753-IB8XOB8 Module
Voltage Supply Pulse Test Sources Digital Outputs
Connection

1753-IB16XOB8 Module
Voltage Supply
Connection
1 2 3 4 5 6

1 2 3 4 5 6

7 8 9 10 11 12

13 14 15 16 17 18

L- 1 2 3 4+ LDO
(2A)

L- 5 6 7 8+ LDO
(2A)

7 8

S+ S+ S+ S+ S- S- S- S-

L- L-

L+

24V DC

L- L-

L+
LS+ 1 2 4 8- S+
DOPO PULSE TEST

ERROR

RUN

ERROR

PROG

FORCE

FORCE

FAULT

OSL

BL

1753-IB8XOB8
8 DC Inputs
8 DC Outputs

BL

DI
LS+ 1 2 3 4 L-

DI
LS+ 5 6 7 8 L-

GuardPLC Ethernet
2

1- 1+ 2- 2+ 3- 3+ 4- 4+
DO

5- 5+ 6- 6+ 7- 7+ 8- 8+
DO
1 1 1 1 2 2 2 2

LS+ LS+ 1 2 3 4

1753-IB16 OXB8
16 DC Inputs
8 DC Outputs

L- L-

LS+ LS+ 5 6 7 8

L- L-

LS+ LS+ 9 10 11 12 L- L-

LS+ LS+ 13 14 15 16 L- L-

GuardPLC Ethernet

10/100 BaseT
()

25 26 27 28 29 30 31 32

PO PULSE TEST

PROG

OSL

19 20 21 22 23 24

25 26 27 28 29 30

10/100 BaseT
1

Ethernet Ports (on Bottom of Module)

24

L+

17 18 19 20 21 22 23 24

- DO +
1

24 V DC

FAULT

1 ()

L+

9 10 11 12 13 14 15 16

24V DC

24 V DC
RUN

Pulse Test Sources

Digital Outputs

Digital Inputs

()

()

33 34 35 36 37 38 39 40 41 42

43 44 45 46 47 48 49 50 51 52

53 54 55 56 57 58 59 60 61 62

63 64 65 66 67 68 69 70 71 72

Ethernet Ports (on Bottom of Module)

Digital Inputs

Publication 1753-UM001C-EN-P - March 2010

Overview of Safety Controllers

Chapter 1

1753 Relay Output and Analog I/O Modules


1753-OW8 Module
Relay Outputs

Voltage Supply
Connection
1

L- L-

L+

24V DC

L+

DO 1

DO 2

1753-IF8XOF4 Module
Safety Analog Inputs

Voltage Supply
Connection

DO 3

L- L-

DO 4

L+

L+

24V DC

24 V DC
1753-IF8XOF4
8 Analog Inputs
4 Analog Outputs

RUN
ERROR
PROG

1753-OW8

FORCE

8 Digital Outputs

FAULT

AI

AI

T1 I1

L- T2 I2

L-

AI

T3 I3

L- T4 I4

L-

T5 I5

AO
O1

AI
L- T6 I6

L-

T7 I7

L- T8 I8

L-

O2
+

O3
+

O4
+

OSL
BL
1

10 11 12

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32

STD ANALOG OUTPUTS


DO5

DO6

DO7

DO8

GuardPLC Ethernet
9

10

Ethernet Ports (on Bottom of Module)

11

12

13

14

Relay Outputs

15

16

10/100 BaseT
1

<>

<> 2

Ethernet Ports (on Bottom of Module)

Standard Analog Outputs

GuardPLC 2000 System


The GuardPLC 2000 controller is a modular system consisting of a
controller (1755-L1), which provides central CPU and communication
functions, and a separate power supply and I/O residing in a
GuardPLC 1755-A6 chassis. A maximum of six I/O modules may be
used in a single system.
The GuardPLC 2000 controller has one active RS-232 serial port for
non-safety related communication. It also features an Ethernet port for
configuration and safety-related communication. The lower DB9 port
supports RS-232 ASCII (read-only) communication; the upper port is
inactive.

Publication 1753-UM001C-EN-P - March 2010

25

Chapter 1

Overview of Safety Controllers

GuardPLC 2000 Controller, Power Supply, and I/O Modules


GuardPLC 2000 I/O Modules

GuardPLC 2000 Power Supply GuardPLC 2000


Controller
1755PB720

1755L1

RUN STOP
PROG

Ethernet Port

FAULT

FORCE

GuardPLC 2000

1755IB24XOB16

1755IB24XOB16

RUN ERR

RUN

RUN ERR

1755IF8

ERR

RUN

ERR

1755OF8

RUN ERR

1755HSC

1755HSC

RUN ERR

RUN ERR

LS+ 1

I1+

O1+

C-

C-

I1

I1

I-

O1-

A1

A1

I2

I2

I2+

O2+

B1

B1

I3

I3

I-

O2-

Z1

Z1

I4

I4

I3+

O3+

C1

C1

I5

I5

I-

O3-

C-

C-

I6

I6

I4+

O4+

C-

C-

I7

I7

I-

O4-

C-

C-

I8

I8

C-

C-

10

LS+ 10

10

C-

10

C-

LS+ 1

Tx COL

Back-up Battery
Compartment

10/100BaseT

3V DC
LITH-BATT.

RS-232 Serial Port


(Inactive)

24V

FAULT

3,3V

5V
RESTART

1
FB1

2
3

FAULT

LS+ 10

11

I5+/1- 10

O5+

I-

11

I9

11

O5-

11

A2

11

A2

12

I10 12

I10 12

I6+/2- 12

O6+

12

B2

12

B2

13

I11 13

I11 13

I-

13

O6-

13

Z2

13

Z2

14

I12 14

I12 14

I7+/3- 14

O7+

14

C2

14

C2

15

I13 15

I13 15

I-

15

O7-

15

C-

15

C-

16

I14 16

I14 16

I8+/4- 16

O8+

16

C-

16

C-

17

I15 17

I15 17

I-

O8-

17

C-

17

C-

18

I16 18

I16 18

18

C-

18

C-

19

LS+ 19

LS+

20

I17 20

I17

21

I18 21

I18

22

I19 22

I19

23

I20 23

I20

24

I21 24

I21

25

I22 25

I22

26

I23 26

I23

27

I24 27

I24

28

L-

28

L-

19

L- 19

L-

29

O1

29

O1

20

20

30

O2

30

O2

21

21

31

O3

31

O3

22

22

32

O4

32

O4

23

23

33

O5

33

O5

24

L- 24

L-

34

O6

34

O6

25

L- 25

L-

35

O7

35

O7

26

L- 26

L-

36

O8

36

O8

27

L- 27

L-

37

L-

37

L-

38

O9

38

O9

39

O10 39

O10

40

O11 40

O11

41

O12 41

O12

42

O13 42

O13

43

O14 43

O14

44

O15 44

O15

45

O16 45

O16

I9

11

17
18

FB2

RS-232 Serial Port


(Active)

L+
DC 24V
L-

PS

CPU

DIO

DIO

AI

AO

CO

CO

GuardPLC 2000 Power Supply


The 1755-PB720 power supply module provides two voltages
(3.3V DC and 5V DC) for the GuardPLC 2000 controller. They are
electrically isolated from the supply voltage, 24V DC.

1755-IB24XOB16 I/O Module


The 1755-IB24XOB16 digital input/output module provides 24 digital
inputs and 16 digital outputs. The status of each I/O signal is
displayed with a status indicator located on the right side of the front
plate connectors. Inputs and outputs are electrically isolated from the
supply voltage, 24V DC.

1755-IF8 Analog Input Module


The 1755-IF8 analog input module has eight inputs. These inputs can
be used as either eight single-ended inputs or four differential analog
inputs that are electrically isolated from the logic side of the GuardPLC
module. The measured input value can be either voltage or current. If
you use the input module for current, you need a shunt resistor. The
measured value is digitally transferred to the processor system as a
value between 0 and 2000.

26

Publication 1753-UM001C-EN-P - March 2010

Overview of Safety Controllers

Chapter 1

1755-OF8 Analog Output Module


The 1755-OF8 analog output module provides eight outputs,
galvanically isolated in groups of 2 (that is, 2 outputs per power
supply). They are electrically isolated from the processor system. Each
analog output can operate as a current source or a voltage source.

1755-HSC High Speed Counter Module


The 1755-HSC counter module provides two counters and four digital
outputs. They are electrically isolated from the processor system. The
status of the four output signals is displayed with status indicators
located at the right side of the front plate output connector.

Communication
Capabilities

GuardPLC Ethernet Network


The GuardPLC Ethernet network provides safe communication via
Ethernet protocol for distributed I/O and peer-to-peer communication
for all GuardPLC controllers. It also provides non-safety-related
communication with the OPC server. Programming and configuration
of controllers is accomplished via the GuardPLC Ethernet network.
Various GuardPLC systems can be networked together on the
GuardPLC Ethernet network, using star or daisy-chain configurations.
A programming device running RSLogix Guard PLUS! software can
also be connected wherever required.
IMPORTANT

Publication 1753-UM001C-EN-P - March 2010

Make sure that a network loop is not generated. Data packets


must only be able to reach a node via a single path.

27

Chapter 1

Overview of Safety Controllers

GuardPLC Ethernet Networking Example


Star Configuration

1 2 3 4 5 6

L- L-

L+

Daisy-chain (Line) Configuration

7 8 9 10 11 12

1 2 3 4 5 6

7 8 9 10 11 12

DO L- 1 2 3 4 L-

DO L- 7 8 9 10 L-

L+

24V DC

(2A)

(2A)

24 V DC

To Programming Terminal

RUN
ERROR
PROG
FORCE
FAULT

1753-IB20OXB8
20 DC Inputs
8 DC Outputs

OSL

To Programming Terminal

BL
D1
LS+ 1 2 3 4 L-

D1
LS+ 5 6 7 8 L-

13 14 15 16 17 18

D1
LS+ 9 10 11 12 L-

D1
LS+ 13 14 15 16 L-

D1
LS+ 17 18 19 20 L-

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

1 2 3 4 5 6

GuardPLC Ethernet

3 ()

10/100 BaseT
1

()

()

13 14 15 16 23 24

()

10 11 12

10 11 12

1 2 3 4 5 6

L- LL- L-

DIO

L+

COMM1

RUN

ERROR
PROG
FORCE

FAULT
BL

L+

10 11 12

10 11 12

D1
LS+- 1 2 3 4 L-

L+
DO L- 1 2 3 4 L-

DO L- 5 6 7 8 L-

(2A)

GuardPLC Ethernet

(2A)

COMM3

COMM2

COMM1

3 ()

()

D1
LS+ 9 10 11 12 L-

D1
LS+ 13 14 15 16 L-

BL

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

FAULT

1753-L28BBBM
20 DC Inputs
8 DC Outputs

OSL
BL
D1
LS+- 1 2 3 4 L-

D1
LS+ 5 6 7 8 L-

D1
LS+ 9 10 11 12 L-

D1
LS+ 13 14 15 16 L-

D1
LS+ 1 2 3 4 L-

D1
LS+ 5 6 7 8 L-

D1
LS+ 9 10 11 12 L-

D1
LS+ 13 14 15 16 L-

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

13 14 15 16 23 24

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

D1
LS+ 17 18 19 20 L-

37 38 39 40 41 42

10/100 BaseT
1

Controller

Controller

PROG
FORCE

1753-IB20OXB8
20 DC Inputs
8 DC Outputs

OSL

D1
LS+ 17 18 19 20 L-

19 20 21 22 23 24

13 14 15 16 23 24

GuardPLC Ethernet

24 V DC
RUN
ERROR

GuardPLC Ethernet

D1
LS+ 5 6 7 8 L-

13 14 15 16 17 18

10/100 BaseT

RS-485
MODBUS

FAULT

1753-L28BBBM
20 DC Inputs
8 DC Outputs

OSL
()

24V DC

(2A)

RUN

PROG

L- L-

8 9 10 11 12

24 V DC

FORCE

3 ()

8 9 10 11 12

DO L- 7 8 9 10 L-

(2A)

24 V DC
ERROR

ASCII

DO L- 1 2 3 4 L-

DO L- 5 6 7 8 L-

(2A)

MODBUS
COMM2

L+
(2A)

DO L- 1 2 3 4 L-

RS-485

COMM3

L+

24V DC

L+

24V DC

ASCII

()

()

DIO

D1
LS+ 17 18 19 20 L-

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

13 14 15 16 23 24

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

10/100 BaseT
3 ()

()

DIO
L- L1 2 3 4 5 6

7 8 9 10 11 12

1 2 3 4 5 6

7 8 9 10 11 12

DO L- 1 2 3 4 L-

DO L- 7 8 9 10 L-

1 2 3 4 5 6

L- L-

L+

24V DC

L+
(2A)

L- L-

(2A)

L+

24V DC

7 8 9 10 11 12

2 3 4 5 6

2 3 4 5 6

DIO
7

8 9 10 11 12

8 9 10 11 12

L- LDO L- 1 2 3 4 L-

(2A)

7 8 9 10 11 12

24 V DC
RUN

RUN

DO L- 7 8 9 10 L-

ERROR

ERROR

PROG

PROG

RUN

24 V DC

FORCE

FORCE

RUN

FAULT

FAULT

BL

PROG
FORCE

1753-IB20OXB8
20 DC Inputs
8 DC Outputs

OSL
BL

FAULT

1753-IB20OXB8
20 DC Inputs
8 DC Outputs

OSL
BL

D1
LS+ 1 2 3 4 L-

D1
LS+ 5 6 7 8 L-

D1
LS+ 9 10 11 12 L-

D1
LS+ 13 14 15 16 L-

D1
LS+ 17 18 19 20 L-

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

13 14 15 16 23 24

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

D1
LS+ 1 2 3 4 L-

D1
LS+ 5 6 7 8 L-

D1
LS+ 9 10 11 12 L-

D1
LS+ 13 14 15 16 L-

D1
LS+ 17 18 19 20 L-

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

GuardPLC Ethernet

10/100 BaseT
()

1753-IB20OXB8
20 DC Inputs
8 DC Outputs

OSL

ERROR

PROG

FAULT

D1
LS+ 1 2 3 4 L-

D1
LS+ 5 6 7 8 L-

D1
LS+ 9 10 11 12 L-

D1
LS+ 13 14 15 16 L-

D1
LS+ 17 18 19 20 L-

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

10/100 BaseT

()

8 9 10 11 12

8 9 10 11 12

DO L- 7 8 9 10 L(2A)

13 14 15 16 23 24

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

1753-IB20OXB8
20 DC Inputs
8 DC Outputs

BL

GuardPLC Ethernet

10/100 BaseT
()

2 3 4 5 6

OSL

GuardPLC Ethernet
1

2 3 4 5 6

DO L- 1 2 3 4 L-

24 V DC

ERROR

FORCE

L+
(2A)

1 2 3 4 5 6

(2A)

L+

24V DC

DO L- 7 8 9 10 L-

DO L- 1 2 3 4 L-

L+
(2A)

()

L+
(2A)

24 V DC

L+

24V DC

()

()

D1
LS+ 1 2 3 4 L-

D1
LS+ 5 6 7 8 L-

D1
LS+ 9 10 11 12 L-

D1
LS+ 13 14 15 16 L-

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

13 14 15 16 23 24

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

D1
LS+ 17 18 19 20 L-

37 38 39 40 41 42

GuardPLC Ethernet

10/100 BaseT
1

()

()

13 14 15 16 23 24

DIO

DIO
1 2 3 4 5 6

L- L-

L+

24V DC

7 8 9 10 11 12

1 2 3 4 5 6

7 8 9 10 11 12

DO L- 1 2 3 4 L-

DO L- 7 8 9 10 L-

L+
(2A)

(2A)

24 V DC
RUN
ERROR
PROG
FORCE
FAULT

1753-IB20OXB8
20 DC Inputs
8 DC Outputs

OSL
BL
D1
LS+ 1 2 3 4 L-

D1
LS+ 5 6 7 8 L-

D1
LS+ 9 10 11 12 L-

D1
LS+ 13 14 15 16 L-

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

13 14 15 16 23 24

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

D1
LS+ 17 18 19 20 L-

37 38 39 40 41 42

GuardPLC Ethernet

10/100 BaseT
1

()

()

DIO

EtherNet/IP
GuardPLC 1600 and GuardPLC 1800 controllers support EtherNet/IP
communication. Able to run EtherNet/IP communication at the same
time as safety-rated GuardPLC Ethernet network, the GuardPLC
controller uses the EtherNet/IP network to communicate status about
the safety control system to other standard devices such as PLCs
(ControlLogix, FlexLogix, CompactLogix, SLC 500, or PLC-5
controllers), HMIs (PanelView, PanelView Plus, and VersaView
terminals) and others. The GuardPLC controller can even control
standard I/O, like FLEX I/O and POINT I/O modules, on an
EtherNet/IP network.

ASCII
This read-only, non-safety-related protocol can be used to extract
diagnostic and status information from the GuardPLC controllers.
ASCII protocol is available over the RS-232 port on the GuardPLC 1200
and GuardPLC 2000 controllers and via the RS-485 Comm 3 port on
GuardPLC 1600 and GuardPLC 1800 controllers.
See Chapter 21 for details on communication with ASCII devices.
28

Publication 1753-UM001C-EN-P - March 2010

Overview of Safety Controllers

Chapter 1

High-speed Safety Protocol


GuardPLC 1600 and 1800 controllers support High-speed Safety
Protocol (HSP), which allows them to connect to the DeviceNet safety
network via the 1753-DNSI DeviceNet Safety Scanner.
Refer to the DeviceNet Safety Scanner for GuardPLC Controllers User
Manual, publication 1753-UM002, for more information.

Modbus RTU Slave


Modbus is a standard industrial non-safety-related serial protocol in
which the Modbus master can communicate with a maximum of 255
slave devices. The Modbus master initiates and controls all
communication on the network.
Modbus RTU Slave protocol is available via the RS-485 Comm 1 port
on GuardPLC 1600 and GuardPLC 1800 controllers with catalog
numbers ending in M.
Modbus RTU Slave protocol allows both the reading and writing of
data.
For more information on the Modbus RTU Slave protocol, see the
Modbus Protocol Specifications, available from
www.modbus.org/specs.

PROFIBUS DP Slave
PROFIBUS DP protocol is a non-safety-related serial protocol,
designed for high-speed data transmission between automation
systems and distributed peripherals.
PROFIBUS DP slave protocol is available via the RS-485 Comm 1 port
on GuardPLC 1600 and GuardPLC 1800 controllers with catalog
numbers ending in P.
PROFIBUS DP Slave protocol allows both the reading and writing of
data.

Publication 1753-UM001C-EN-P - March 2010

29

Chapter 1

Overview of Safety Controllers

OPC Server
The GuardPLC 1600, GuardPLC 1800, series C GuardPLC 1200, and
series C GuardPLC 2000 controllers are OPC clients. An OPC server,
catalog number 1753-OPC, is available from Rockwell Automation and
lets personal computer applications read and write data to and from
the GuardPLC controller (non-safety-related communication only).

30

Publication 1753-UM001C-EN-P - March 2010

Chapter

Installation

Introduction

General Safety

Topic

Page

General Safety

31

Mount the Equipment

32

Communication Connections

38

Reset Pushbutton

43

Open style devices must be provided with environmental and safety


protection by proper mounting in enclosures designed for specific
application conditions. See NEMA Standards 250 and IEC 60529, as
applicable, for explanations of the degrees of protection provided by
different types of enclosure.

ATTENTION

Consider the following before installing your GuardPLC


1200/1600/1800 controller or distributed I/O.
These products are grounded through the DIN rail. Use
zinc-plated yellow-chromate steel DIN rails to assure proper
grounding. The use of other DIN rail materials (for example,
aluminum and plastic) that can corrode, oxidize, or are poor
conductors, can result in improper or intermittent grounding.

31Publication 1753-UM001C-EN-P - March 2010

31

Chapter 2

Installation

Mount the Equipment

GuardPLC 1200 Controller


The GuardPLC 1200 controller can be either snapped onto a DIN rail
or mounted to a back panel by using bolts. DIN rail mounting is the
easiest way to attach the controller and should be used wherever
possible.

IMPORTANT

For cooling reasons:


the GuardPLC 1200 controller must be mounted horizontally
with the Ethernet socket facing down.
a location where air flows freely or use an additional cooling
fan.
the minimum clearance around the
GuardPLC 1200 controller must be at least 100 mm (3.94 in.).
do not mount the GuardPLC 1200 controller over a heating
device.

DIN Rail
1. Hook the two top latches, on the back of the GuardPLC 1200
controller, over the top of the DIN rail.
2. If the lower latches are extended (see figure below), push them
up until they lock into place. If the lower latches are not
extended, press the GuardPLC 1200 controller into the DIN rail
until they lock into place.

PLC
1200

Lower Latch (Extended)

TIP

32

Lower Latch (Not Extended)

If you need to remove the controller from the DIN rail, use a
screwdriver to pull down the lower latches, then lift the
controller toward you.

Publication 1753-UM001C-EN-P - March 2010

Installation

Chapter 2

Back Panel
ATTENTION

Do not bend the controller. Bending the controller will damage


it.

Use the four brackets on the GuardPLC 1200 controller to mount it


onto a back panel.
Top Brackets

Use the following to mount the


controller.
PLC
1200

Top Brackets

Bottom Brackets

M4 screws (2)

M5 screws (2)

lock washer

lock washer

washers

washers

nut

nut

Bottom Brackets

If the mounting brackets are not flat before the nuts are tightened, use
additional washers as shims, so the controller does not bend when
you tighten the nuts.

GuardPLC 1600 and GuardPLC 1800 Controllers,


and Distributed I/O
IMPORTANT

For effective cooling:


mount the device horizontally.
provide a gap of at least 100 mm (3.94 in.) above and below the device and at
least 20 mm (0.79 in.) horizontally between devices.
the wire duct can run in the 100 mm (3.94 in.) of free space above and below
the controller if it is no deeper than 40 mm (1.58 in.). If the depth is greater
than 40 mm (1.58 in.), the devices must be placed on stand-offs that match the
depth of the duct. If stand-offs are not used, you must provide a gap of at least
80 mm (3.15 in.) between the device and the duct.
select a location where air flows freely or use an additional fan.
do not mount the controller or I/O module over a heating device.
do not block the ventilation slots on the side of the device.

Publication 1753-UM001C-EN-P - March 2010

33

Chapter 2

Installation

GuardPLC 1600 and GaurdPLC 1800 controllers and I/O cannot be


panel-mounted. Mount these controllers and distributed I/O to a DIN
rail by following the steps below.
1. Hook the top slot over the DIN
rail.
2. Insert a flathead screwdriver into
the gap between the housing and
the latch and pull the latch
downward.

(1) Top Slot


(3)

DIN Rail

(2)

Latch

3. Hold the latch down as you push


the housing back onto the DIN rail.
4. Release the latch to lock the device onto the rail.

TIP

To remove the device from the DIN rail, insert a flathead


screwdriver into the gap between the housing and the latch
and pull the latch downward as you lift the device off of the
rail.

GuardPLC 2000 Chassis


The GuardPLC 2000 chassis provides two flanges with eyelets. Refer to
the illustration below. Use bolts to mount the system to a back panel.
To mount the chassis flanges, you will need four M8-size bolts with
lock washer, washer, and nut with 13 mm (0.51 in.) max head
diameter. The bolts must be long enough to accept the chassis at its
mounting place.

ATTENTION

34

Do not bend the chassis. Bending will damage the chassis


and/or the backplane inside the GuardPLC 2000 controller.
If the rear side of the chassis does not lie flat before the nuts
are tightened, use additional washers as shims so that the
chassis does not bend when you tighten the nuts.

Publication 1753-UM001C-EN-P - March 2010

Installation

Chapter 2

IMPORTANT The chassis must be installed without any modules inserted.

Disconnect the supply voltage before mounting the chassis.


The chassis must be vertically mounted with the cooling fans on
the lower side.
Do not obstruct ventilation openings.
Provide a gap of at least 100 mm (3.94 in.) above and below the
device and at least 20 mm (0.79 in.) horizontally between
devices.

Modules are shown for illustration only. The chassis must be installed without any modules inserted.
255 mm (10 in.) Including Flanges
236 mm (9.3 in.) Width Eyelet to Eyelet
15.9 mm (0.63 in.)
Eyelet

Flanges
177.8 mm
(7.0 in.)
285 mm
(11.2 in.)

Depth:
218 mm
(8.6 in.)

Eyelet

Includes
Termination
Plug

Publication 1753-UM001C-EN-P - March 2010

35

Chapter 2

Installation

GuardPLC 2000 Controller, I/O, and Power Supply


Mount the GuardPLC 2000 chassis prior to installing the controller,
I/O, and power supply.

IMPORTANT

Disconnect the power supply, 1755-PB720, from the 24V DC


supply voltage before you insert any I/O modules.

1. Before you insert the device, you must detach the grounding
grill. To do this, remove the grounding grill screws.

grounding grill screws

2. Remove the lower panel of the chassis and disconnect the fans.
3. Power Supply: Insert the power supply into the leftmost slot of
the chassis.
Controller: Insert the controller into the slot directly to the right
of the power supply module (slot 0).
I/O Module: Insert the module into any unused slot from 16
(see the figure below). Keep the module in line with the guides
so the module runs smoothly in the track.
4. Begin pushing the device into the chassis.
a. If there is resistance when you push the device into the
backplane, do not force the device because the pins will
bend.
b. Remove the device and start again at step 3.
5. Continue pushing the device into the chassis until the front of
the device is flush with the other modules in the chassis.

36

Publication 1753-UM001C-EN-P - March 2010

Installation

Chapter 2

6. Secure the device with the screws on the top and bottom of the
device (see the figure below).
Power Supply Screws

Controller Screw
Slot 0

A-B
QUALITY

I/O Module Screw

Allen-Br
adley
GuardPLC

2000
1755IF8
RUN

A-B
QUALITY

1
2
3
4
5
6
7
8
9

Allen-Br
adley
GuardPLC

2000

10
11
12
13
14
15
16
17
18

ERR
I1+
I-

Slot 2
Slot 1

Slot 4
Slot 3

Slot 6
Slot 5

I2+
II3+
II4+
I-

I5+/1II6+/2II7+/3II8+/4I-

Guides

Power Supply Screws

I/O Module Screw

TIP

If you are installing other GuardPLC 2000 modules, follow their


installation instructions up to this point before you complete the
next 3 steps.

7. Reconnect the fans.


8. Replace the lower panel of the chassis, sliding it over the tabs on
the sides of the chassis and under the tabs on the back of the
chassis.
9. Use the grounding grill screws to attach the grounding grill.

Publication 1753-UM001C-EN-P - March 2010

37

Chapter 2

Installation

Communication
Connections

Connections for safety and non-safety related communication for


GuardPLC controllers and distributed I/O modules are described in
the following sections.

GuardPLC 1200 Controller


The GuardPLC 1200 controller has an ASCII serial port for
non-safety-related communication and an Ethernet port for
safety-related communication.
Connect the ASCII port to any RS-232 device that has the capability to
send ASCII command strings to the controller. The controller replies
with a data variable string. See Chapter 21 for more information on
ASCII communication
Use this illustration to connect the ASCII and Ethernet ports.

PLC
1200

Port for
Factory
Use
Only

ASCII
Serial Port
(Use 1761-CBL-PM02
Series C Cable)

Ethernet Dongle

Ethernet Port
(On Bottom of Controller)

The pin assignment of the ASCII Serial port is shown below.


2

4
3

5
6

8
7

38

Pin

Function

24V DC

ground (GND)

request to send (RTS)

received data (RxD)

received line signal detector (DCD)

clear to send (CTS)

transmitted data (TxD)

ground (GND)

not applicable

Publication 1753-UM001C-EN-P - March 2010

Installation

Chapter 2

GuardPLC 1600 and GuardPLC 1800 Controllers


Connections for safety- and non-safety-related communication are
described in the following sections.

Connections for Safety-Related Communication


The controller has four 10/100BaseT, RJ-45 connectors to provide
communication via the GuardPLC Ethernet network to other
GuardPLC controllers, distributed I/O, and RSLogix Guard PLUS!
software. These connectors also provide communication via an
EtherNet/IP network to other Ethernet devices. Connectors 1 and 2
are located on the bottom side on the left. Connectors 3 and 4 are
located on the top side on the left.
Ethernet Ports 3 and 4
3 ()

()

L- L-

L+

L+

24V DC
RS-485
ASCII/HSP
COMM3

MODBUS
COMM2

COMM1

GuardPLC Ethernet

10/100 BaseT
1 ()

()

Ethernet Ports 1 and 2

All four connectors and the GuardPLC controller are connected


together by an internal Ethernet switch. In contrast to a hub, a switch
is able to store data packets for a short period of time to establish a
temporary connection between two communication partners for the
transfer of data. In this way, collisions (typical of a hub) can be
avoided and the load on the network is reduced.
The switch automatically switches between transfer rates of 10 and
100 Mbps and between full- and half-duplex connections. This makes
the full bandwidth available (full-duplex operation) in both directions.
A switch enables several connections to be established at the same
time and can address up to 1000 absolute MAC addresses.
Auto-crossing recognizes that cables with crossed wires have been
connected and the switch adjusts accordingly. Therefore, either
cross-over or straight-through Ethernet cabling can be used.
Star or line configurations are available. Make sure that a network
loop is not generated. Data packets must only be able to reach a node
via a single path.
Publication 1753-UM001C-EN-P - March 2010

39

Chapter 2

Installation

See Chapter 16 for information on peer-to-peer communication or


Chapter 18 for information on EtherNet/IP communication.

Connections for Non-Safety-Related communication


Three 9-pin Min-D connectors are located on the front of the
controller, providing these communication options.
Designation

Function

COMM1 (RS-485)

Modbus RTU Slave (1753-L28BBBM or 1753-L32BBBM-8A)


Profibus-DP-Slave 1753-L28BBBP or 1753-L32BBBP-8A)

COMM2

not used

COMM3

GuardPLC ASCII Protocol/HSP

3 ()

()

L- L-

L+

L+

24V DC
RS-485
ASCII/HSP
COMM3

MODBUS
COMM2

COMM1

Modbus or Profibus Port


(COMM 1)

ASCII/HSP Port (COMM 3)

GuardPLC Ethernet

10/100 BaseT
3 ()

IMPORTANT

()

The three Min-D connectors are RS-485. You must use an


electrical interface device to connect the controller to an
RS-232 device.
To use COMM3 for HSP, you must use a 1753-CBLDN cable,
which ships with the 1753-DNSI DeviceNet Safety Scanner for
GuardPLC Controllers.

40

Publication 1753-UM001C-EN-P - March 2010

Installation

Chapter 2

The pin assignment of the Min-D connectors is shown in the table


below.
Connection

Signal

Function

RP

5V, decoupled with diodes

RxD/TxD-A

Receive/Transmit data A

CNTR-A

DGND

VP

5V, positive pole of supply voltage

RxD/TxD-B

CNTR-B

Control Signal A
Data reference potential

Receive/Transmit data B
Control Signal B

GuardPLC Distributed I/O Modules


Each module has two 10/100BaseT, RJ-45 connectors to provide
safety-related communication via the GuardPLC Ethernet network.
These two connectors and the GuardPLC distributed I/O module are
connected together by an internal Ethernet switch.

L- L-

L+

L+

24V DC

24 V DC
RUN
ERROR
PROG
FORCE
FAULT
OSL
BL

GuardPLC Ethernet

10/100 BaseT
1

()

()

Ethernet Ports 1 and 2

Publication 1753-UM001C-EN-P - March 2010

41

Chapter 2

Installation

GuardPLC 2000 Controller


Connections for safety- and non-safety-related communication are
described in the following sections.

Connections for Safety-Related Communication


To configure/program the GuardPLC system, the controller must be
connected on an Ethernet network to the RSLogix Guard PLUS!
programming terminal. The GuardPLC Ethernet network also provides
for peer-to-peer communication to distributed I/O and to other
controllers.
Tx COL

Ethernet Port
10/100 Base T

Connections for Non-Safety-Related Communication


Connect the ASCII port (FB2) to any RS-232 device that has the
capability to send ASCII command strings to the controller. The
controller replies with a data variable string. See Chapter 21 for more
information on ASCII communication.
pin

FB1

function

none

send data

receive data

none

ground

none

RTS

CTS

none

FB2

ASCII Port

7
8
9

42

1
2
3
4
5

Publication 1753-UM001C-EN-P - March 2010

Installation

Reset Pushbutton

Chapter 2

GuardPLC 1600 and 1800 controllers and distributed I/O are equipped
with a reset pushbutton. Reset via the pushbutton is necessary if you:
forget the password to go online via the programming software.
are unable to determine the IP address and SRS of the controller.
The pushbutton is accessible through a small round hole at the top of
the housing, approximately 45 cm (1.62.0 in.) from the left rim
and recessed approximately 9.5 mm (0.375 in.).
IMPORTANT

Activate the reset pushbutton by using an insulated pin to


prevent short-circuits.

To reset, press and hold the pushbutton while restarting the controller
by cycling power. Hold the reset pushbutton until the PROG status
indicator stops flashing. Pressing the Reset pushbutton during
operation has no affect.
After a reset, the IP address, SRS, and login accounts are temporarily
reset to their default settings.

IP = 192.168.0.99
SRS = 60000.1
Login Username = Administrator
Login Password = [none]

At the next power cycle, these settings will be reset to the last values
stored into Flash. This means that either:
the settings prior to the reset will be restored.
if any settings were changed after the reset, these new settings
will still be in effect.

Publication 1753-UM001C-EN-P - March 2010

43

Chapter 2

Installation

Notes:

44

Publication 1753-UM001C-EN-P - March 2010

Chapter

General Wiring Considerations

Introduction

Prevent Electrostatic
Discharge

Topic

Page

Prevent Electrostatic Discharge

45

Power Supply Considerations

45

Ground the Equipment

46

Terminal Connections

47

Shield-contact Plate Connections

48

Detailed Wiring Information

48

ATTENTION

Electrostatic discharge can damage integrated circuits or


semiconductors. Follow these guidelines when you handle the
module.

Power Supply
Considerations

45Publication 1753-UM001C-EN-P - March 2010

Touch a grounded object to discharge static potential.


Wear an approved wrist-strap grounding device.
Do not touch conductors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Keep the equipment in appropriate static-safe packaging
when not in use.

The power supply must provide a voltage between 20.4 and


28.8V DC. You must supply enough power to drive the controller,
inputs, and outputs because all GuardPLC controllers and distributed
I/O modules source the current for the input channels and drive the
output devices connected to them. No additional power supply is
required to drive outputs. To operate, GuardPLC controllers typically
draw less than 1 A at 24V DC. They require additional power to
operate the inputs and outputs connected to the controller. Consider
the power draw of the I/O when specifying the size of the power
supply and required fusing.

45

Chapter 3

General Wiring Considerations

The 24V DC voltage supply must feature galvanic isolation because


inputs and outputs are not electrically isolated from the internal
processor.(1) To comply with CE Low Voltage Directives (LVD), you
must use either an NEC Class 2, a Safety Extra Low Voltage (SELV) or a
Protective Extra Low Voltage (PELV) power supply to power the
GuardPLC controller or I/O module. A SELV supply cannot exceed
30V rms, 42.4V peak or 60V DC under normal conditions and under
single fault conditions. A PELV supply has the same rating and is
connected to protective earth.
IMPORTANT

Ground the Equipment

Protect the controller with a slow-blow fuse.

You must provide an acceptable grounding path for each device in


your application. For more information on proper grounding
guidelines, refer to the Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1.

Considerations for Grounding All Controllers


To improve EMC conditions, ground the controller.
Run the ground connection from the ground screw of the
controller to a good earth ground. Use a minimum of 2.5 mm2
(14 AWG) wire.
Keep the connection to earth ground as short as possible to
minimize resistance.
Grounding is required even if the control system does not have
shielded cables.
If you use shielded cables to connect the controller to the
external 24V DC source, connect the shield to the grounding
contact of the power supply.
No protective grounding (against hazardous shock) is required.

GuardPLC 1200 Controller


Ground the GuardPLC 1200 controller by connecting the PA terminal,
marked
, to earth ground. See page 58 for GuardPLC 1200 terminal
connections.

(1) The I/O and CPU are only isolated from one another on the GuardPLC 2000 controller.

46

Publication 1753-UM001C-EN-P - March 2010

General Wiring Considerations

Chapter 3

GuardPLC 1600 and GuardPLC 1800 Controllers and Distributed I/O


The I/O module is functionally grounded through its DIN rail
connection. A protective earth ground connection is required and is
provided by a separate grounding screw, located on the upper left of
the housing and marked with the grounding symbol
.

ATTENTION

This product is grounded through the DIN rail to chassis ground.


Use zinc plated yellow-chromate steel DIN rail to assure proper
grounding. The use of other DIN rail materials (for example,
aluminum and plastic) that can corrode, oxidize, or are poor
conductors, can result in improper or intermittent grounding.

GuardPLC 2000 Chassis


Ground the GuardPLC 2000 chassis and cables by using the grounding
screw located on the left side of the grounding grill. Ground the
chassis via the grounding grill.
PS

CPU

DIO

DIO

AI

AO

CO

CO

Grounding Grill
Grounding Screw

Terminal Connections

Publication 1753-UM001C-EN-P - March 2010

Terminals accommodate wire sizes up to 1.5 mm2 (16 AWG) for


input/output wiring and up to 2.5 mm2 (14 AWG) for voltage supply
connections.

47

Chapter 3

General Wiring Considerations

Shield-contact Plate
Connections

Shielded cabling is fed in from below so that the shielding can be


connected to the shield-contact plate by using a clip. Remove about 2
cm (0.79 in.) of the outer cable insulation so that the mesh is exposed
at the point where the cable is clipped to the plate. Position the clip
over the uninsulated cable shielding and push it into the slots of the
shield contact plate until it fits firmly in place, as shown below.
63 64

65 66 67 68 69 70

71 72

Mesh

net

T
4

Cable Clip

Shield-contact Plate

IMPORTANT

Detailed Wiring
Information

Make sure that the mesh comes in direct contact with the
shield-contact plate. If the mesh does not touch the plate, the
cable is not grounded.

For detailed wiring information by product, see the table below.


For

See

GuardPLC 1600, GuardPLC 1800 and


GuardPLC 1200 Controllers

Chapter 4

GuardPLC 2000 Controller

Chapter 5

1753-IB16, 1753-OB16, 1753-IB20XOB8


Modules

Chapter 6

1753-IB8XOB8

Chapter 7

1753-IB16XOB8

Chapter 8

1753-IF8XOF4

Chapter 9

1753-OW8

Chapter 10

Wiring Examples

Appendix C

To be sure that GuardPLC controllers and I/O modules are used in a


safety-related manner (SIL3 in accordance to IEC 61508), the whole
system, including connected sensors and encoders, must satisfy the
safety requirements described in the GuardPLC Controllers Safety
Reference Manual, publication 1753-RM002.

48

Publication 1753-UM001C-EN-P - March 2010

Chapter

Wire GuardPLC 1600, GuardPLC 1800, and


GuardPLC 1200 Controllers

Introduction

Power Supply Connections

Topic

Page

Power Supply Connections

49

Safety-related Digital Inputs

50

Safety-related Digital Outputs

51

Safety-related Analog Inputs

51

High-speed Counters

52

Wire the GuardPLC 1600 Controller

53

Wire the GuardPLC 1800 Controller

54

Wire the GuardPLC 1200 Controller

58

Power supply connections for GuardPLC 1600, GuardPLC 1800, and


GuardPLC 1200 controllers are described in the following sections.

GuardPLC 1600 and GuardPLC 1800 Controllers


ATTENTION

Before connecting the power supply, check for correct polarity,


value, and ripple.
Do not reverse the L+ and L- terminals or damage to the
controller will result. There is no reverse polarity protection.

The supply voltage is connected via a 4-pin connector that


accommodates wire sizes up to 2.5 mm2 (14 AWG). You only need to
connect one wire to L+ and one wire to L-. Both L+ and L- terminals
are internally connected. The other terminal can be used to
daisy-chain 24V DC to additional devices. The power supply
connector is rated to 10 A.

49Publication 1753-UM001C-EN-P - March 2010

49

Chapter 4

Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

GuardPLC 1200 Controller


Both L+ and L- terminals must be used in parallel to allow the
maximum current of 8 A. (Each terminal maximum is 4 A so both are
required for 8 A.)
If the power supply has only one (+) lead, a short bridge jumper must
be installed between L+(1) and L+(2).
TIP

Safety-related Digital
Inputs

The GuardPLC 1200 controller requires approximately 0.5 A to


operate. The remaining 7.5 A is used to source power for inputs
and outputs.

The status of digital inputs is indicated via status indicators when the
controller or module is in Run mode.
Follow the closed-circuit principle for external wiring when
connecting sensors. To create a safe state in the event of a fault, the
input signals revert to the de-energized state (0). The external line is
not monitored, but a wire break is interpreted as a safe (0) signal.
The GuardPLC 1600 and GuardPLC 1800 controllers provide power to
input devices through their LS+ terminals. However, input devices
with their own dedicated power supply can also be connected instead
of contacts. The reference pole (L-) of the power supply must then be
connected to the reference pole (L-) of the appropriate GuardPLC
input group. See the wiring diagrams in Appendix C for examples.
In general, the LS+ terminals, not L+ on the power supply connection,
should be used to supply voltage for safety inputs. Each LS+ features
individual short-circuit and EMC protection. Due to current limitations,
use LS+ for only the safety inputs on the same terminal plug.
An EN 61000-4.5 surge impulse can be read as a short-duration HI
signal in some modules. To avoid an error, either:
install shielded input lines to prevent effects of surges in the
system.
implement software filtering in the user program. A signal must
be present for at least two cycles before it is evaluated.

50

Publication 1753-UM001C-EN-P - March 2010

Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

Safety-related Digital
Outputs

Chapter 4

The status of digital outputs is indicated via status indicators when the
controller or module is in Run mode.
GuardPLC outputs are rated to either 0.5 A or 1.0 A at an ambient
temperature of 60 C (140 F). At an ambient temperature of 50 C
(122 F), outputs rated at 1.0 A increase to 2.0 A.
If an overload occurs, the affected outputs are turned off. When the
overload is eliminated, the outputs are under the control of the
controller and are energized based on the user program code.
An output is in the safe state when it is de-energized. Therefore,
outputs are switched off when a fault that affects the safe control of
those outputs occurs.
For connection of a load, the reference pole L- of the corresponding
channel group must be used. Although L- poles are connected
internally to L- on the power supply input, it is strictly recommended
to connect the L- reference poles only to their corresponding output
group. EMC testing was performed in this manner.
TIP

Safety-related Analog
Inputs

Inductive loads can be connected without a protection diode on


the load, because there is a protection diode located within the
GuardPLC device. However, Rockwell Automation strongly
recommends that a protection diode be fitted directly to the
load to suppress any interference voltage. A 1N4004 diode is
recommended.

GuardPLC 1800 controller analog inputs provide for the unipolar


measurement of voltages from 010V, referenced to L-. A 10 K
shunt is used for single-ended voltage signals. With a 500 shunt
resistor, currents from 020 mA can also be measured.
Analog cabling should be no more than 300 m (984 ft) in length. Use
shielded, twisted-pair cables, with the shields connected at one end,
for each measurement input. See the instructions for connecting
shielded cabling to the shield-contact plate on page 48.
Unused analog inputs must be short-circuited. Place wire jumpers to
ground on any inputs that are not used.
AI
T1 I1 L- T2 I2 L-

41 42 43 44 45 46
Wire Jumper

Publication 1753-UM001C-EN-P - March 2010

Wire Jumper

51

Chapter 4

Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

High-speed Counters

The GuardPLC 1200 and 1800 controllers feature inputs for high-speed
counting up to a maximum of 100 kHz. These counters are 24-bit, and
are configurable for either 5V or 24V DC. The counters can be used as
a counter or as a decoder for 3-bit Gray Code inputs. As a counter,
input A is the counter input, input B is the counter direction input,
and input Z is used for a reset.
The counter inputs must be connected by using shielded, twisted-pair
cables for each measurement input. The shields must be connected at
both ends. The input lines should be no more than 500 m (1640 ft) in
length. All reference (L-, C-, or I- depending on the controller)
connections are interconnected on the module in the form of common
reference pole.
Cables are clipped to the shield contact plate when connecting
counter inputs. See the instructions for connecting shielded cabling to
the shield contact plate on page 48.
IMPORTANT

Do not terminate unused high-speed counter inputs.

52

Publication 1753-UM001C-EN-P - March 2010

Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

Wire the GuardPLC 1600


Controller

Chapter 4

Input and output terminal connections for the GuardPLC 1600


controller are described below.

Safety-related Digital Input Terminals


DI
LS+ 1 2 3 4 L-

DI
LS+ 5 6 7 8 L-

DI
LS+ 9 10 11 12 L-

DI
LS+ 13 14 15 16 L-

DI
LS+ 17 18 19 20 L-

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

Digital inputs are connected to these terminals.

Publication 1753-UM001C-EN-P - March 2010

Terminal Number

Designation

Function

13

LS+

Sensor supply for inputs 14

14

Digital input 1

15

Digital input 2

16

Digital input 3

17

Digital input 4

18

L-

Reference pole

19

LS+

Sensor supply for inputs 58

20

Digital input 5

21

Digital input 6

22

Digital input 7

23

Digital input 8

24

L-

Reference pole

25

LS+

Sensor supply for inputs 912

26

Digital input 9

27

10

Digital input 10

28

11

Digital input 11

29

12

Digital input 12

30

L-

Reference pole

31

LS+

Sensor supply for inputs 13 16

32

13

Digital input13

33

14

Digital input 14

34

15

Digital input 15

35

16

Digital input 16

36

L-

Reference pole

37

LS+

Sensor supply for inputs 1720

38

17

Digital input 17

39

18

Digital input 18

40

19

Digital input 19

41

20

Digital input 20

42

L-

Reference pole
53

Chapter 4

Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

Safety-related Digital Output Terminals


1 2 3 4 5 6

7 8 9 10 11 12

1 2 3 4 5 6

7 8 9 10 11 12

DO L- 1 2 3 4 L(2 A)

DO L- 5 6 7 8 L(2 A)

Digital outputs are connected to these terminals.

Wire the GuardPLC 1800


Controller

Terminal Number

Designation

Function

Current

L-

Reference pole

Digital output 1

0.5 A

Digital output 2

0.5 A

Digital output 3

0.5 A

Digital output 4 (for increased load)

2.0 A

L-

Reference pole

L-

Reference pole

Digital output 5

0.5 A

Digital output 6

0.5 A

10

Digital output 7

0.5 A

11

Digital output 8 (for increased load)

2.0 A

12

L-

Reference pole

The controller has 24 digital inputs whose status is indicated via status
indicators when in Run mode. The digital inputs are actually analog
inputs that provide the program with UINT values of 030V
(03000), which are used to create limit values to calculate signals for
the digital inputs. Default settings are:
<7V = 0 signal.
>13V = 1 signal.
The limit values are set by using system variables. See page 328 for
more information on configuring these inputs.
TIP

Because digital inputs are actually analog values, the .USED


variable must be set HI in the output signal connections dialog
box to activate the digital input.

The 24 digital inputs of the GuardPLC 18000 controller can be used as


analog inputs by reading the DI[xx].Value Analog input signal.
However, because these inputs are intended to be used as digital
inputs, the accuracy of their analog values is not guaranteed to the be
same as the published accuracy of the 8 actual analog inputs in the
GuardPLC 1800 controller.

54

Publication 1753-UM001C-EN-P - March 2010

Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

Chapter 4

Safety-related Digital Input Terminals


11 12 13 14 15 16 17 18 19 20

21 22 23 24 25 26 27 28 29 30

31 32 33 34 35 36 37 38 39 40

11 12 13 14 15 16 17 18 19 20

21 22 23 24 25 26 27 28 29 30

31 32 33 34 35 36 37 38 39 40

DI LS+ 1 2 3 4 5 6 7 8 L-

DI LS+ 9 10 11 12 13 14 15 16 L-

DI LS+ 17 18 19 20 21 22 23 24 L-

Digital inputs are connected to these terminals.

Publication 1753-UM001C-EN-P - March 2010

Terminal Number

Designation

Function

11

LS+

Sensor supply for inputs 18

12

Digital input 1

13

Digital input 2

14

Digital input 3

15

Digital input 4

16

Digital input 5

17

Digital input 6

18

Digital input 7

19

Digital input 8

20

L-

reference pole

21

LS+

Sensor supply for inputs 916

22

Digital input 9

23

10

Digital input 10

24

11

Digital input 11

25

12

Digital input 12

26

13

Digital input 13

27

14

Digital input 14

28

15

Digital input 15

29

16

Digital input 16

30

L-

Reference pole

31

LS+

Sensor supply for inputs 1724

32

17

Digital input 17

33

18

Digital input 18

34

19

Digital input 19

35

20

Digital input 20

36

21

Digital input 21

37

22

Digital input 22

38

23

Digital input 23

39

24

Digital input 24

40

L-

Reference pole

55

Chapter 4

Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

Safety-related Digital Output Terminals

DO

10

10

L-

4 5
(2 A)

8 L(2 A)

Digital outputs are connected to these terminals.


Terminal Designation
Number

Function

Current

L-

Reference pole

Digital output 1

0.5 A

Digital output 2

0.5 A

Digital output 3

0.5 A

Digital output 4 (for increased load)

2.0 A

Digital output 5

0.5 A

Digital output 6

0.5 A

Digital output 7

0.5 A

Digital output 8 (for increased load)

2.0 A

10

L-

Reference pole

Safety-related Analog Input Terminals


The GuardPLC 1800 controller features 8 single-ended analog inputs.
Differential analog inputs cannot be used on the GuardPLC 1800
controller. Two- or four-wire transmitters can be used. These devices
can be powered from the transmitter supply terminal of the GuardPLC
1800 controller or from an external power supply. See Appendix C for
example wiring diagrams.
IMPORTANT

Unused analog inputs must be short-circuited. See page 51.

T1 I1 L- T2 I2 L-

AI
T3 I3 L- T4 I4 L-

AI
T5 I4 L- T6 I6 L-

AI
T7 I7 L- T8 I8 L-

41 42 43 44 45 46

47 48 49 50 51 52

53 54 55 56 57 58

59 60 61 62 63 64

AI

56

Publication 1753-UM001C-EN-P - March 2010

Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

Chapter 4

The analog inputs are connected to these terminals.

Publication 1753-UM001C-EN-P - March 2010

Terminal Number

Designation

Function

41

T1

Transmitter supply 1

42

I1

Analog input 1

43

L-

Reference pole

44

T2

Transmitter supply 2

45

I2

Analog input 2

46

L-

Reference pole

47

T3

Transmitter supply 3

48

I3

Analog input 3

49

L-

Reference pole

50

T4

Transmitter supply 4

51

I4

Analog input 4

52

L-

Reference pole

53

T5

Transmitter supply 5

54

I5

Analog input 5

55

L-

Reference pole

56

T6

Transmitter supply 6

57

I6

Analog input 6

58

L-

Reference pole

59

T7

Transmitter supply 7

60

I7

Analog input 7

61

L-

Reference pole

62

T8

Transmitter supply 8

63

I8

Analog input 8

64

L-

Reference pole

57

Chapter 4

Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

Safety-related High-speed Counter Terminals


HSC
A1 B1 Z1 L-

A2 B2 Z2

65

69

66

67 68

70

L-

71 72

Counters are connected to these terminals.

Wire the GuardPLC 1200


Controller

Terminal Number

Designation

Counter Function

Gray Code Function

65

A1

Input A1

bit 0 (LSB)

66

B1

Input B1

bit 1

67

Z1

Input Z1

bit 2 (MSB)

68

L-

Common reference pole

69

A2

Input A2

bit 0 (LSB)

70

B2

Input B2

bit 1

71

Z2

Input Z2

bit 2 (MSB)

72

L-

Common reference pole

The GuardPLC 1200 controller has no LS+ terminal for a safety input
voltage source. Use the L+ supply terminal as the source for safety
input voltage. The four reference terminals, labeled I-, should be used
for the safety input voltage reference. This is a common reference for
all 20 inputs.

Lower Terminal Block


Not
Used I2
1

I6

I1

58

I4
7

I3

I5

I8 I10 I12 I14 I16 I18 I20


11

10

I7

I9

13

12

15

14

17

16

19

18

21

20

I23

22

I11 I13 I15 I17 I19 I-

I25

24

I-

Publication 1753-UM001C-EN-P - March 2010

Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

Terminal Number

Designation

Function

Not Used

None

I1

Digital input 1

I2

Digital input 2

I3

Digital input 3

I4

Digital input 4

I5

Digital input 5

I6

Digital input 6

I7

Digital input 7

I8

Digital input 8

10

I9

Digital input 9

11

I10

Digital input 10

12

I11

Digital input 11

13

I12

Digital input 12

14

I13

Digital input 13

15

I14

Digital input 14

16

I15

Digital input 15

17

I16

Digital input 16

18

I17

Digital input 17

19

I18

Digital input 18

20

I19

Digital input 19

21

I20

Digital input 20

22

I-

Reference pole

23

I-

Reference pole

24

I-

Reference pole

25

I-

Reference pole

Chapter 4

Upper Terminal Block


All eight of the digital output zero-voltage reference terminals are
common. Unlike the GuardPLC 1600 and GuardPLC 1800 controllers
or distributed I/O, which have an earth ground screw, the
GuardPLC 1200 controllers earth ground should be wired to the PA
terminal, marked
.

Publication 1753-UM001C-EN-P - March 2010

59

Chapter 4

Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers

L+(1) L+(2) O1+ O2+ O3+ O4+ O5+ O6+ O7+ O8+ A1 B1 Z1
2

10

12

11

14

13

16

15

18

17

20

19

22

21

24

23

26

25

L-(1) L-(2) PA O1- O2- O3- O4- O5- O6- O7- O8- A2 B2

60

Terminal Number

Designation

Function

L-

24V DC return path

L+

24V DC power input

L-

24V DC return path

L+

24V DC power input

PA

Functional ground

I28

27

Z2

29

I-

O1+

Digital output 1

O1-

Voltage reference for digital output 1

O2+

Digital output 2

O2-

Voltage reference for digital output 2

10

O3+

Digital output 3

11

O3-

Voltage reference for digital output 3

12

O4+

Digital output 4

13

O4-

Voltage reference for digital output 4

14

O5+

Digital output 5

15

O5-

Voltage reference for digital output 5

16

O6+

Digital output 6

17

O6-

Voltage reference for digital output 6

18

O7+

Digital output 7

19

O7-

Voltage reference for digital output 7

20

O8+

Digital output 8

21

O8-

Voltage reference for digital output 8

22

A1

Universal signal input for counter 1

23

A2

Universal signal input for counter 2

24

B1

Signal input for counting direction for


counter 1

25

B2

Signal input for counting direction for


counter 2

26

Z1

Reset for counter 1

27

Z2

Reset for counter 2

28

I-

Signal ground for counters 1 and 2

29

I-

Signal ground for counters 1 and 2

Publication 1753-UM001C-EN-P - March 2010

Chapter

Wire the GuardPLC 2000 Controller and I/O

Introduction

Safety-related Digital
Inputs

Topic

Page

Safety-related Digital Inputs

61

Safety-related Digital Outputs

62

Safety-Related Analog Inputs (1755-IF8)

62

High-speed Counter Module (1755-HSC)

63

Safety-related Analog Output Module (1755-OF8)

64

Current Draw

64

Wire the 1755-IB24XOB16 Digital I/O Module

65

Wire the 1755-IF8 Analog Input Module

66

Wire the 1755-OF8 Analog Output Module

66

Wire the 1755-HSC Counter Modules

68

The status of digital inputs is indicated via status indicators when the
controller or module is in Run mode.
Follow the closed-circuit principle for external wiring when
connecting sensors. To create a safe state in the event of a fault, the
input signals revert to the de-energized state (0). The external line is
not monitored, but a wire break is interpreted as a safe (0) signal.
Input devices with their own dedicated power supply can also be
connected instead of contacts. The reference pole (L-) of the power
supply must then be connected to the reference pole of the input (L-).
See the wiring diagrams in Appendix C for examples.
In general, the LS+ terminals, not L+ on the power supply connection,
should be used to supply voltage for safety inputs. Each LS+ features
individual short-circuit and EMC protection. Due to current limitations,
use LS+ for only the safety inputs on the same terminal plug.
An EN 61000-4.5 surge impulse can be read as a short-duration HI
signal in some modules. To avoid an error, either:
install shielded input lines to prevent effects of surges in the
system.
implement software filtering in the user program. A signal must
be present for at least two cycles before it is evaluated.

61Publication 1753-UM001C-EN-P - March 2010

61

Chapter 5

Wire the GuardPLC 2000 Controller and I/O

Safety-related Digital
Outputs

The status of digital outputs is indicated via status indicators when the
controller or module is in Run mode.
GuardPLC 2000 controller outputs are rated at 2 A per point, but the
total load of all 16 outputs on a single module must not exceed 8 A.
If an overload occurs, the affected outputs are turned off. When the
overload is eliminated, the outputs are under the control of the
controller and are energized based on the user program code.
An output is in the safe state when it is de-energized. Therefore,
outputs are switched off when a fault that affects the safe control of
those outputs occurs.
For connection of a load, the reference pole L- of the corresponding
channel group must be used. Although L- poles are connected
internally to L- on the power supply input, it is strictly recommended
to connect the L- reference poles only to their corresponding output
group. EMC testing was performed in this manner.
TIP

Safety-Related Analog
Inputs (1755-IF8)

Inductive loads can be connected without a protection diode on


the load, because there is a protection diode located within the
GuardPLC device. However, Rockwell Automation strongly
recommends that a protection diode be fitted directly to the
load to suppress any interference voltage. A 1N4004 diode is
recommended.

GuardPLC analog inputs provide for the unipolar measurement of


voltages from 010V, referenced to L-. A 10 k shunt is used for
single-ended voltage signals. With a 500 shunt resistor, currents
from 020 mA can also be measured.
The feeder lines should be no more than 300 m (984 ft.) in length. Use
shielded, twisted-pair cables, with the shields connected at one end,
for each measurement input. See the instructions for connecting
shielded cabling to the shield contact plate on page 48.

62

Publication 1753-UM001C-EN-P - March 2010

Wire the GuardPLC 2000 Controller and I/O

Chapter 5

Unused analog inputs must be short-circuited. Place wire jumpers to


ground on any inputs that are not used.
10
11
12
13
14
15
16
17
18

I5+/1II6+/2II7+/3II8+/4I-

Wire
Jumper

1755-IF8

High-speed Counter
Module (1755-HSC)

The 1755-HSC module features inputs for high-speed counting up to 1


MHz. These counters are 24-bit, and are configurable for either 5V or
24V DC. The counters can be used as a counter or as a decoder for
3-bit Gray Code inputs. As a counter, input A is the counter input,
input B is the counter direction input, and input Z is used for a reset.
The counter inputs must be connected by using shielded, twisted-pair
cables for each measurement input. The shields must be connected at
both ends. The input lines should be no more than 500 m (1640 ft) in
length. All reference (L-, C-, or I- depending on the controller)
connections are interconnected on the module in the form of common
reference pole.
Cables are clipped to the shield-contact plate when connecting
counter inputs. See the instructions for connecting shielded cabling to
the shield contact plate on page 48
IMPORTANT

Do not terminate unused high-speed counter inputs.

To be sure that counters are used in a safety-related manner (SIL3 in


accordance to IEC 61508), the whole system, including connected
sensors and encoders, must satisfy these safety requirements. Refer to
the GuardPLC Controllers Safety Reference Manual, publication
1753-RM002, for more detailed information.

Publication 1753-UM001C-EN-P - March 2010

63

Chapter 5

Wire the GuardPLC 2000 Controller and I/O

Safety-related Analog
Output Module (1755-OF8)

Current Draw

The 1755-OF8 module uses analog outputs to transfer analog values


from the user program into outputs ranging from 10V DC and
020 mA. The relationship between the value in the user program
and the output value is linear and is displayed in this table.
Logic Value

Output Voltage

Output Current

0.00V

0.0 mA

1000

10.00V

20.0 mA

-1000

-10.00V

na

The GuardPLC 2000 controller features several different modules.


These modules and their backplane current draw specifications are
listed in this table.
Cat. No.

Current Draw at 3.3V DC

Current Draw at 24V DC

1755-IB24XO16

0.3 A

0.5 A

1755-IF8

0.15 A

0.4 A

1755-OF8

0.15 A

0.4 A

1755-HSC

0.8 A

0.1 A

1755-L1

1.5 A

1.0 A

TIP

The GuardPLC 2000 controller can draw up to 30 A. The majority


of this 30 A is used to source inputs and outputs. Only 1 A is
required to operate the CPU module.

Connect the power supply, 1755-PB720, to the 24V DC supply


voltage. Refer to the GuardPLC 2000 Power Supply Installation
Instructions, publication 1755-IN007, for detailed instructions.

64

Publication 1753-UM001C-EN-P - March 2010

Wire the GuardPLC 2000 Controller and I/O

Wire the 1755-IB24XOB16


Digital I/O Module

Chapter 5

This module is a combination I/O module featuring 24 safety-related


digital inputs and 16 safety-related digital outputs.
Inputs: The sockets with pins 29, 1118, and 2027 provide
the 24 digital inputs I1I24. Pins 1, 10, and 19 are the common
positive poles (LS+). Each group of 8 inputs has current limits of
100 mA.
Outputs: The sockets with pins 2936 and 3845 provide the
16 digital outputs O1O16. Pins 28 and 37 are the common
negative poles (L-) for the output loads.
Each output channel can be loaded with 2 A, but the total load
of all 16 outputs must not exceed 8 A.

Terminal
Number
1755IB24XOB16

Designation

Function

LS+

Digital input supply


for inputs 18

Designation

Function

24

I21

Digital input 21

I1

I2

Digital input 1

25

I22

Digital input 22

Digital input 2

26

I23

Digital input 23

I3

Digital input 3

27

I24

Digital input 24

I4

Digital input 4

28

L-

Reference pole for


outputs 18

I5

Digital input 5

29

O1

Digital output 1

I6

Digital input 6

30

O2

Digital output 2

I7

Digital input 7

31

O3

Digital output 3

RUN ERR
1
2
3
4
5
6
7
8
9

LS+
I1
I2
I3
I4
I5
I6
I7
I8

10
11
12
13
14
15
16
17
18

LS+
I9
I10
I11
I12
I13
I14
I15
I16

19
20
21
22
23
24
25
26
27

LS+
I17
I18
I19
I20
I21
I22
I23
I24

28
29
30
31
32
33
34
35
36

L-

37
38
39
40
41
42
43
44
45

LO9
O10
O11
O12
O13
O14
O15
O16

O1
O2
O3
O4
O5
O6
O7
O8

Terminal
Number

I8

Digital input 8

32

O4

Digital output 4

10

LS+

Digital input supply


for inputs 916

33

O5

Digital output 5

11

I9

Digital input 9

34

O6

Digital output 6

12

I10

Digital input 10

35

O7

Digital output 7

13

I11

Digital input 11

36

O8

Digital output 8

14

I12

Digital input 12

37

L-

Reference pole for


outputs 9 16

15

I13

Digital input 13

38

O9

Digital output 9

16

I14

Digital input 14

39

O10

Digital output 10

17

I15

Digital input 15

40

O11

Digital output 11

18

I16

Digital input 16

41

O12

Digital output 12

19

LS+

Digital input supply


for inputs 1724

42

O13

Digital output 13

20

I17

Digital input 17

43

O14

Digital output 14

21

I18

Digital input 18

44

O15

Digital output 15

45

O16

Digital output 16

22

I19

Digital input 19

23

I20

Digital input 20

Publication 1753-UM001C-EN-P - March 2010

65

Chapter 5

Wire the GuardPLC 2000 Controller and I/O

Wire the 1755-IF8 Analog


Input Module

This module features 8 single-ended analog inputs or 4 differential


analog inputs. Two-wire or four-wire transmitters can be used. The
devices cannot be powered from the GuardPLC module. An external
power supply is required for all analog transmitters. Single-ended
transmitters connect between the Ix+ and I- terminals. For example:
pins 1 and 2, 3 and 4, 5 and 6. Differential transmitters connect
between Ix+ and x- terminals. For example, pins 1 and 10, 3 and 12, 5
and 14.
IMPORTANT

Unused channels must be short-circuited. See page 63.

All reference poles (I-) are internally connected.

1755IF8

RUN ERR
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

I1+
II2+
II3+
II4+
I-

I5+/1II6+/2II7+/3II8+/4I-

Wire the 1755-OF8 Analog


Output Module

66

Terminal Number

Designation

Function

I1+

Analog input 1

I-

Reference pole for input 1

I2+

Analog input 2

I-

Reference pole for input 2

I3+

Analog input 3

I-

Reference pole for input 3

I4+

Analog input 4

I-

Reference pole for input 4

shield connection

signal ground

10

I5+/1-

Analog input 5

11

I-

Reference pole for input 5

12

I6/2-

Analog input 6

13

I-

Reference pole for input 6

14

I7+/3-

Analog input 7

15

I-

Reference pole for input 7

16

I8+/4-

Analog input 8

17

I-

Reference pole for input 8

18

shield connection

signal ground

This module features 8 analog outputs. Devices cannot be powered


from the 1755-OF8 module. An external power supply is required for
all analog output devices.

Publication 1753-UM001C-EN-P - March 2010

Wire the GuardPLC 2000 Controller and I/O

Chapter 5

There are 4 reference poles for the 8 outputs. A pair of outputs share
a reference pole as shown below.
These outputs

Share these Reference Poles

1 and 2

O1- and O2-

3 and 4

O3- and O4-

5 and 6

O5- and O6-

7 and 8

O7- and O8-

Each group of 2 outputs is electrically isolated from the others.


IMPORTANT

IMPORTANT

1755OF8

RUN ERR
1
2
3
4
5
6
7
8
9

O1+
O1O2+
O2O3+
O3O4+
O4-

10
11
12
13
14
15
16
17
18

O5+
O5O6+
O6O7+
O7O8+
O8-

Publication 1753-UM001C-EN-P - March 2010

If an unused channel is defined as a current output (software


configuration set to current output), the output channel has to
be short-circuited. Place jumpers into these outputs and tighten
the screws.

If an unused channel is defined as a voltage output (software


configuration set to voltage output), the unused outputs must be
left open. Short-circuiting a unused voltage output may cause
damage to the output.

Terminal Number

Designation

Function

O1+

Analog output 1

O1-

Group 1 reference pole

O2+

Analog output 2

O2-

Group 1 reference pole

O3+

Analog output 3

O3-

Group 2 reference pole

O4+

Analog output 4

O4-

Group 2 reference pole

shield connection

signal ground

10

O5+

Analog output 5

11

O5-

Group 3 reference pole

12

O6+

Analog output 6

13

O6-

Group 3 reference pole

14

O7+

Analog output 7

15

O7-

Group 4 reference pole

16

O8+

Analog output 8

17

O8-

Group 4 reference pole

18

shield connection

signal ground

67

Chapter 5

Wire the GuardPLC 2000 Controller and I/O

Wire the 1755-HSC Counter


Modules

This module contains 2 high-speed counters and 4 digital outputs.


Although the 4 digital outputs are located on the 1755-HSC module,
they cannot be driven by counter presets. The 4 digital outputs are
driven by software, just as on the 1755-IB24XOB16 module.
The nominal current per output is limited to 0.5 A. Currents > 0.5 A
are regarded as overload. The overload is limited to 11 A per
output, or 2 A if all four outputs are overloaded at the same time.
With an overload of 2 A, the output voltage drops to 18V.
All counter common reference poles, C-, share the same path. All
digital output common reference poles, L-, share the same path, but
are electrically isolated from the C- pins.

1755HSC

RUN ERR
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

19
20
21
22
23
24
25
26
27

68

CA1
B1
Z1
C1
CCCCCA2
B2
Z2
C2
CCCC-

L1
2
3
4
LLLL-

Terminal Number

Designation

Function

C-

Common reference pole

A1

Signal input for counter 1

B1

Counting direction input for counter 1

Z1

Reset input for counter 1

C1

no function

C-

Common reference pole

C-

Common reference pole

C-

Common reference pole

C-

Common reference pole

10

C-

Common reference pole

11

A2

Signal input for counter 2

12

B2

Counting direction input for counter 2

13

Z2

Reset input for counter 2

14

C2

no function

15

C-

Common reference pole

16

C-

Common reference pole

17

C-

Common reference pole

18

C-

Common reference pole

19

L-

Reference pole for digital outputs

20

Digital output 1

21

Digital output 2

22

Digital output 3

23

Digital output 4

24

L-

Reference pole for digital outputs

25

L-

Reference pole for digital outputs

26

L-

Reference pole for digital outputs

27

L-

Reference pole for digital outputs

Publication 1753-UM001C-EN-P - March 2010

Chapter

Wire 1753-IB16, 1753-OB16, and


1753-IB20XOB8 Modules

Introduction

Safety-related Digital
Inputs

Topic

Page

Safety-related Digital Inputs

69

Safety-related Digital Outputs

70

Power Supply Connections

70

Wire the 1753-IB16 Input Module

71

Wire the 1753-OB16 Output Module

73

Wire the 1753-IB20XOB8 Combination Module

75

The status of digital inputs is indicated via status indicators when the
module is in Run mode.
Follow the closed-circuit principle for external wiring when
connecting sensors. To create a safe state in the event of a fault, the
input signals revert to the de-energized state (0). The external line is
not monitored, but a wire break is interpreted as a safe (0) signal.
The GuardPLC 1600 and GuardPLC 1800 controllers provide power to
input devices through their LS+ terminals. However, input devices
with their own dedicated power supply can also be connected instead
of contacts. The reference pole (L-) of the power supply must then be
connected to the reference pole (L-) of the appropriate GuardPLC
input group. See the wiring diagrams in Appendix C for examples.
In general, the LS+ terminals, not L+ on the power supply connection,
should be used to supply voltage for safety inputs. Each LS+ features
individual short-circuit and EMC protection. Due to current limitations,
use LS+ for only the safety inputs on the same terminal plug.
An EN 61000-4.5 surge impulse can be read as a short-duration HI
signal in some modules. To avoid an error, either:
install shielded input lines to prevent effects of surges in the
system.
implement software filtering in the user program. A signal must
be present for at least two cycles before it is evaluated.

69Publication 1753-UM001C-EN-P - March 2010

69

Chapter 6

Wire 1753-IB16, 1753-OB16, and 1753-IB20XOB8 Modules

Safety-related Digital
Outputs

The status of digital outputs is indicated via status indicators when the
module is in RUN mode.
GuardPLC outputs are rated to either 0.5 A or 1.0 A at an ambient
temperature of 60 C (140 F). At an ambient temperature of 50 C
(122 F), outputs rated at 1.0 A increase to 2.0 A.
If an overload occurs, the affected outputs are turned off. When the
overload is eliminated, the outputs are under the control of the
controller and are energized based on the user program code.
An output is in the safe state when it is de-energized. Therefore,
outputs are switched off when a fault that affects the safe control of
those outputs occurs.
For connection of a load, the reference pole L- of the corresponding
channel group must be used. Although L- poles are connected
internally to L- on the power supply input, it is strictly recommended
to connect the L- reference poles only to their corresponding output
group. EMC testing was performed in this manner.
TIP

Inductive loads can be connected without a protection diode on


the load, because there is a protection diode located within the
GuardPLC device. However, Rockwell Automation strongly
recommends that a protection diode be fitted directly to the
load to suppress any interference voltage. A 1N4004 diode is
recommended.

Power Supply Connections


ATTENTION

Before connecting the power supply, check for correct polarity,


value and ripple.
Do not reverse the L+ and L- terminals or damage to the
controller will result. There is no reverse polarity protection.

The supply voltage is connected via a 4-pin connector that


accommodates wire sizes up to 2.5 mm2 (14 AWG). You only need to
connect one wire to L+ and one wire to L-. Both L+ and L- terminals
are internally connected. The other terminal can be used to
daisy-chain 24V DC to additional devices. The power supply
connector is rated to 10 A.

70

Publication 1753-UM001C-EN-P - March 2010

Wire 1753-IB16, 1753-OB16, and 1753-IB20XOB8 Modules

Wire the 1753-IB16 Input


Module

Chapter 6

The 1753-IB16 input module features 16 digital inputs and 4 pulse test
sources.

Safety-related Digital Inputs


DI
LS+ 1 2 3 4 L-

DI
LS+ 5 6 7 8 L-

DI
LS+ 9 10 11 12 L-

DI
LS+ 13 14 15 16 L-

1 2 3 4 5 6

7 8 9 10 11 12

13 14 15 16 17 18

19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12

13 14 15 16 17 18

19 20 21 22 23 24

Digital inputs are connected to these terminals.

Publication 1753-UM001C-EN-P - March 2010

Terminal Number

Designation

Function

LS+

Sensor supply for inputs 14

Digital input 1

Digital input 2

Digital input 3

Digital input 4

L-

Reference pole

LS+

Sensor supply for inputs 58

Digital input 5

Digital input 6

10

Digital input 7

11

Digital input 8

12

L-

Reference pole

13

LS+

Sensor supply for inputs 912

14

Digital input 9

15

10

Digital input 10

16

11

Digital input 11

17

12

Digital input 12

18

L-

Reference pole

19

LS+

Sensor supply for inputs 13 16

20

13

Digital input 13

21

14

Digital input 14

22

15

Digital input 15

23

16

Digital input 16

24

L-

Reference pole

71

Chapter 6

Wire 1753-IB16, 1753-OB16, and 1753-IB20XOB8 Modules

Pulse Test Sources


The 1753-IB16 input module is equipped with four pulse test sources
that can be software-configured for pulse testing of safety inputs, if
required. Due to minimal current capacity, these pulse test sources
cannot be used as outputs if they are not configured as pulse test
sources.

ATTENTION

Pulse test sources must not be used as safety-related outputs.

For information on configuring pulse test sources for line control, see
Chapter 11. See Appendix C for example wiring diagrams.
Pulse test sources are connected to these terminals.
PO PULSE TEST
L- 1 2 3 4 L25 26 27 28 29 30

25 26 27 28 29 30

72

Terminal Number

Designation

Function

25

L-

Reference pole

26

Pulse test source 1

27

Pulse test source 2

28

Pulse test source 3

29

Pulse test source 4

30

L-

Reference pole

Publication 1753-UM001C-EN-P - March 2010

Wire 1753-IB16, 1753-OB16, and 1753-IB20XOB8 Modules

Chapter 6

Wire the 1753-OB16 Output Operating Voltage Considerations


Module
The 1753-OB16 output module has a total current capacity (16 A)
higher than the terminal block current limitation (10 A). Therefore, it
features two separate operating voltage supply connections if more
than 10 A is used by the module. The two output groups are shown
below. Each group has a current capacity of 8 A.
Group 1

Group 2
1 2 3 4 5 6

7 8 9 10 11 12

1 2 3 4 5 6

L- L- L+ L+
24V DC

7 8 9 10 11 12

L- L- L+ L+
DO1 L- 1 2 3 4 L-

24V DC

DO2 L- 5 6 7 8 L-

24 V DC
RUN
ERROR
PROG
FORCE
FAULT

1753-OB16
16 DC Outputs

OSL
BL

GuardPLC Ethernet

DO1 L- 9 10 11 12 L-

DO2 L- 13 14 15 16 L-

13 14 15 16 17 18

19 20 21 22 23 24

13 14 15 16 17 18

19 20 21 22 23 24

10/100 BaseT
1 ()

Group

()

Outputs

1, 2, 3, 4, and 9, 10, 11,12

5, 6, 7, 8 and 13, 14, 15, 16

Safety-related Digital Outputs


The module has 16 digital outputs (DO1 to DO16) whose status is
indicated via status indicators.
DO1
LS+ 1 2 3 4 L-

DO2
LS+ 5 6 7 8 L-

1 2 3 4 5 6

7 8 9 10 11 12

1 2 3 4 5 6

7 8 9 10 11 12

DO1
LS+ 9 10 11 12 L-

DO2
LS+ 13 14 15 16 L-

13 14 15 16 17 18

19 20 21 22 23 24

13 14 15 16 17 18

19 20 21 22 23 24

Each output is rated for up to 1 A at 60 C (140 F) or 2 A at


40 C (104 F). However, each group of 8 outputs may not exceed 8 A
total. For heat dissipation, intersperse high-current and low-current
outputs so that all the high-current outputs are not next to each other.

Publication 1753-UM001C-EN-P - March 2010

73

Chapter 6

Wire 1753-IB16, 1753-OB16, and 1753-IB20XOB8 Modules

The digital outputs are connected to these terminals.

74

Terminal Number

Designation

Function

L-

Reference pole

Digital output 1

Digital output 2

Digital output 3

Digital output 4

L-

Reference pole

L-

Reference pole

Digital output 5

Digital output 6

10

Digital output 7

11

Digital output 8

12

L-

Reference pole

13

L-

Reference pole

14

Digital output 9

15

10

Digital output 10

16

11

Digital output 11

17

12

Digital output 12

18

L-

Reference pole

19

L-

Reference pole

20

13

Digital output 13

21

14

Digital output 14

22

15

Digital output 15

23

16

Digital output 16

24

L-

Reference pole

Publication 1753-UM001C-EN-P - March 2010

Wire 1753-IB16, 1753-OB16, and 1753-IB20XOB8 Modules

Wire the 1753-IB20XOB8


Combination Module

Chapter 6

The remote I/O module features 20 digital inputs and 8 digital outputs
whose status is indicate via status indicators.

Safety-related Digital Inputs


DI
LS+ 1 2 3 4 L-

DI
LS+ 5 6 7 8 L-

DI
LS+ 9 10 11 12 L-

DI
LS+ 13 14 15 16 L-

DI
LS+ 17 18 19 20 L-

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

The digital inputs are connected to these terminals.

Publication 1753-UM001C-EN-P - March 2010

Terminal Number

Designation

Function

13

LS+

Sensor supply for inputs 14

14

Digital input 1

15

Digital input 2

16

Digital input 3

17

Digital input 4

18

L-

Reference pole

19

LS+

Sensor supply for inputs 58

20

Digital input 5

21

Digital input 6

22

Digital input 7

23

Digital input 8

24

L-

Reference pole

25

LS+

Sensor supply for inputs 912

26

Digital input 9

27

10

Digital input 10

28

11

Digital input 11

29

12

Digital input 12

30

L-

Reference pole

31

LS+

Sensor supply for inputs 1316

32

13

Digital input 13

33

14

Digital input 14

34

15

Digital input 15

35

16

Digital input 16

36

L-

Reference pole

37

LS+

Sensor supply for inputs 1720

38

17

Digital input 17

39

18

Digital input 18

40

19

Digital input 19

41

20

Digital input 20

42

L-

Reference pole

75

Chapter 6

Wire 1753-IB16, 1753-OB16, and 1753-IB20XOB8 Modules

Safety-related Digital Outputs


1 2 3 4 5 6

7 8 9 10 11 12

1 2 3 4 5 6

7 8 9 10 11 12

DO L- 1 2 3 4 L(2A)

DO L- 5 6 7 8 L(2A)

The digital outputs are connected to these terminals.

76

Terminal
Number

Designation

Function

Current

L-

Reference pole

Digital output 1

0.5 A

Digital output 2

0.5 A

Digital output 3

0.5 A
2.0 A

Digital output 4 (for increased load)

L-

Reference pole

L-

Reference pole

Digital output 5

0.5 A

Digital output 6

0.5 A

10

Digital output 7

0.5 A

11

Digital output 8 (for increased load)

2.0 A

12

L-

Reference pole

Publication 1753-UM001C-EN-P - March 2010

Chapter

Wire and Configure the 1753-IB8XOB8 Module

Introduction
Topic

Page

Safety-related Digital Inputs

77

Safety-related Digital Outputs

78

Pulse Test Sources

81

The module features 8 digital inputs, 8 positive-switching digital


outputs, 2 negative-switching digital outputs, and 2 pulsed outputs.

Safety-related Digital
Inputs

The status of the modules 8 digital inputs is indicated via status


indicators when the controller or module is in Run mode.
LS+ is a voltage source that provides 24V DC for a group of four
inputs. There are two groups on the module. If devices require
24V DC to operate and use the same power source as the GuardPLC
module, wire the outputs of the device directly to inputs on the
GuardPLC module. Devices with their own dedicated power supply
can also be connected instead of contacts. Connect the reference pole
of the signal source to the L- reference pole of the input. See the
wiring diagrams in Appendix C for examples.
Follow the closed-circuit principle for external wiring when
connecting sensors. To create a safety state in the event of a fault, the
input signals revert to the de-energized state (0). The external line is
not monitored, but a wire break is interpreted as a safe (0) signal.

77Publication 1753-UM001C-EN-P - March 2010

77

Chapter 7

Wire and Configure the 1753-IB8XOB8 Module

Terminal Connections
LS+ 1 2 3 4 LDI

LS+ 5 6 7 8 LDI

19 20 21 22 23 24

25 26 27 28 29 30

19 20 21 22 23 24

25 26 27 28 29 30

See the wire size and terminal torques specifications on page 290.
Digital inputs are connected to these terminals.
Terminal Number

Designation

Function

19

LS+

Sensor supply for inputs 1 4

20

Digital input 1

21

Digital input 2

22

Digital input 3

23

Digital input 4

24

L-

Reference pole

25

LS+

Sensor supply for inputs 5 8

26

Digital input 5

27

Digital input 6

28

Digital input 7

29

Digital input 8

30

L-

Reference pole

Surge on Digital Inputs


An EN 61000-4.5 surge impulse can be read as a short-duration HI
signal in some modules. To avoid an error, either:
install shielded input lines to prevent effects of surges in the
system.
implement software filtering in the user program. A signal must
be present for at least two cycles before it is evaluated.

Safety-related Digital
Outputs

The module has 8 positive-switching digital outputs that switch


+24V DC and two negative-switching digital outputs that switch
24V COM. Their status is indicated via status indicators.
The positive and negative-switching digital outputs can be connected
in a one-pole or two-pole manner.
If configured for one-pole operation, use the reference pole L- for the
positive-switching outputs and reference pole S+ for the

78

Publication 1753-UM001C-EN-P - March 2010

Wire and Configure the 1753-IB8XOB8 Module

Chapter 7

negative-switching outputs. The total output current of the module is


limited to 8 A and is generated from the 24V of the system.
If configured for two-pole operation, the positive-switching output
DO4 operates with the negative-switching output DO4- and the
positive-switching output DO8 operates with the negative-switching
output DO8-. Line control is carried out for detection of an external
short-circuit between positive and negative-switching outputs. A
switch-on delay is necessary for inductive or capacitive load or lamp
load because the inrush of these loads may be mistakenly detected as
a short-circuit. This delay is set in the RSLogix Guard PLUS! Hardware
Management via the Switch-on delay signal at the negative-switching
output variables. The delay can be set from 030 ms, in 1 ms
increments. An external line break will not be detected.
An output is in a safety state when it is de-energized. When a fault
occurs, all outputs are switched off.
Outputs 13 and 57 can have a load of 0.5 A. Outputs 4 and 8 can
each have a load of 1 A at the maximum ambient temperature 60 C
(140 F), 2 A at an ambient temperature of 40 C (104 F).
The negative-switching outputs DO4- and DO8- can supply up to 1 A
at the maximum ambient temperature of 60 C (140 F), 2 A at an
ambient temperature of 40 C (104 F).
With an overload, one or all of the outputs are turned off. When the
overload is eliminated, the outputs are activated again.

Signals for Output Configuration


Set up these signals for 1753-IB8XOB8 modules by using the Outputs
tab of the digital outputs Signal Connections dialog box in RSLogix
Guard PLUS! software.
L+ Switching

L-Switching

Description

Notes

DO1[xx].Value DO2[xx].Value
Output value for digital output channels
(outputs 1 to 8) (outputs 4- and 8-)

1 = output is set
0 = output is not set; no current

DO2[xx].2-pole

Configures the channel for 2-pole


operation

1 = channel DO2[01] (4-) is used for 2-pole operation


with channel DO1[04] or channel DO2[02] (8-)is used
for 2-pole operation with channel DO1[08]
0 = channel DO2[xx] is not used for 2-pole operation.

Switch-on delay

Sets switch-on delay for 2-pole tests, due


to lamp load, inductive and capacitive load

See Appendix B for a complete list of 1753-IB8XOB8 variables.

Publication 1753-UM001C-EN-P - March 2010

79

Chapter 7

Wire and Configure the 1753-IB8XOB8 Module

Terminal Connections
1

2 3 4 5 6

2 3 4 5 6

DO
PO
L- 1 2 4- 8- S+

13 14 15 16 17 18

8 9 10 11 12

8 9 10 11 12

13 14 15 16 17 18

DO
L- 1 2 3 4 L-

DO
L- 5 6 7 8 L-

See the wire size and terminal torques specifications on page 290.
Digital outputs are connected to these terminals.
Terminal
Number

Designation

Function

4-

Negative switching digital output 4 (for increased load or


bi-polar output)

8-

Negative switching digital output 8 (for increased load or


bi-polar output)

S+

Reference pole for negative switching outputs


(short-circuit protection)

L-

Reference pole for positive-switching outputs

Digital output 1

Digital output 2

10

Digital output 3

11

Digital output 4 (for increased load or bi-polar output)

12

L-

Reference pole for positive-switching outputs

13

L-

Reference pole for positive-switching outputs

14

Digital output 5

15

Digital output 6

16

Digital output 7

17

Digital output 8 (for increased load or bi-polar output)

18

L-

Reference pole for positive-switching outputs

For connection of a load, the reference pole L- of the channel group


must be used. Although L- at terminals 7 and 12 and at terminals 13
and 18 are connected internally to L- on the power supply input, it is
strictly recommended to use 7 and 12 for outputs 14 only and 13
and 18 for outputs 58 only. EMC testing was performed in this
manner.

80

Publication 1753-UM001C-EN-P - March 2010

Wire and Configure the 1753-IB8XOB8 Module

Chapter 7

S+

DO 8-

DO 4-

L-

DO 4

DO 3

DO 2

DO 1

L-

1-pole Connection Examples

Inductive loads can be connected without a protection diode on


the load. However, Rockwell Automation strongly recommends
that a protection diode be fitted directly to the load to suppress
any interference voltage.

TIP

Pulse Test Sources

DO8

DO4

DO8-

DO4-

2-pole Connection Example

There are two digital pulse test sources (PO) used for line control
monitoring of digital inputs. For information on configuring pulse test
sources for line control, see Chapter 11.
Pulse test sources are connected to these terminals.
1

2 3 4 5 6

2 3 4 5 6

DO
PO
L- 1 2 4- 8- S+

Terminal Number

Designation

Function

L-

Reference pole

Pulsed output 1

Pulsed output 2

ATTENTION

Publication 1753-UM001C-EN-P - March 2010

Pulse test sources must not be used as safety-related outputs.

81

Chapter 7

Wire and Configure the 1753-IB8XOB8 Module

Notes:

82

Publication 1753-UM001C-EN-P - March 2010

Chapter

Wire and Configure the 1753-IB16XOB8


Module

Introduction
Topic

Page

Safety-related Digital Inputs

83

Safety-related Digital Outputs

86

Monitor for Line Short Line Break

91

Pulse Test Sources

93

The module features 16 digital inputs, 8 two-pole (8


positive-switching and 8 negative-switching) digital outputs, and 2
pulsed outputs.

Safety-related Digital
Inputs

The status of digital inputs is indicated via status indicators when the
module is in Run mode.
LS+ is a voltage source that provides 24V DC for a group of four
inputs. There are four groups on the module. If devices require
24V DC to operate and use the same power source as the GuardPLC
module, wire the outputs of the device directly to inputs on the
GuardPLC module. Devices with their own dedicated power supply
can also be connected instead of contacts. Connect the reference pole
of the signal source to the L- reference pole of the input. See the
wiring diagrams in Appendix C for examples.
The safety state of an input is indicated by a 0 signal being passed to
the user program logic. If the test routines detect a fault in the digital
inputs, a 0-signal is processed in the user program for the defective
channel. When a fault occurs, the inputs are switched off (0) and the
fault status indicator is activated.
The sensor supplies, LS+, supply a default current of 40 mA that is
buffered for 20 ms in case of a power failure. If a higher current is
needed, two unbuffered supplies of 1 A can be switched on by using
the DI Supply [xx] system signal in the application program. This
supply feeds the neighboring input channel group. The status of this

83Publication 1753-UM001C-EN-P - March 2010

83

Chapter 8

Wire and Configure the 1753-IB16XOB8 Module

supply is read and the supply is switched off if an overcurrent


condition occurs. This supply is protected by a current limiting device.

L+ Not Buffered

Current
Limiting
40 mA

LS+
33

Current
Limiting
1A

LS+
34

L+ Not Buffered

L+ Buffered

Current
Limiting
40 mA

LS+
43

LS+
44

Current
Limiting
40 mA

Terminal Number

LS+
53

Current
Limiting
1A

LS+
54

L+ Buffered

Current
Limiting
40 mA

LS+
63

LS+
64

Follow the closed-circuit principle for external wiring when


connecting sensors. To create a safe state in the event of a fault, the
input signals revert to the de-energized state (0). Although the
external line is not monitored, a wire break is interpreted as a safe
0-signal. Unused inputs must not be terminated.
An EN 61000-4.5 surge impulse can be read as a short-duration HI
signal in some modules. To avoid an error, either:
install shielded input lines to prevent effects of surges in the
system.
implement software filtering in the user program. A signal must
be present for at least two cycles before it is evaluated.

84

Publication 1753-UM001C-EN-P - March 2010

Wire and Configure the 1753-IB16XOB8 Module

Chapter 8

Terminal Connections
LS+ LS+ 1 2 3 4

L- L-

33 34 35 36 37 38 39 40 41 42

LS+ LS+ 5 6 7 8

L- L-

43 44 45 46 47 48 49 50 51 52

LS+ LS+ 9 10 11 12 L- L-

53 54 55 56 57 58 59 60 61 62

LS+ LS+ 13 14 15 16 L- L-

63 64 65 66 67 68 69 70 71 72

See the wire size and terminal torques specifications on page 290.
Digital inputs are connected to these terminals.

Publication 1753-UM001C-EN-P - March 2010

Terminal Number

Designation

Function

33

LS+

Sensor supply for inputs 1 4


40 mA buffered/1 A unbuffered

34

LS+

Sensor supply for inputs 14


40 mA buffered/1 A unbuffered

35

Digital input 1

36

Digital input 2

37

Digital input 3

38

Digital input 4

39

L-

Reference pole

40

L-

Reference pole

41

Ground

Shield

42

Ground

Shield

43

LS+

Sensor supply for inputs 58


40 mA buffered/1 A unbuffered

44

LS+

Sensor supply for inputs 58


40 mA buffered/1 A unbuffered

45

Digital input 5

46

Digital input 6

47

Digital input 7

48

Digital input 8

49

L-

Reference pole

50

L-

Reference pole

51

Ground

Shield

52

Ground

Shield

53

LS+

Sensor supply for inputs 912


40 mA buffered/1 A unbuffered

54

LS+

Sensor supply for inputs 912


40 mA buffered/1 A unbuffered

55

Digital input 9

56

10

Digital input 10

57

11

Digital input 11

58

12

Digital input 12

59

L-

Reference pole

60

L-

Reference pole

61

Ground

Shield

62

Ground

Shield
85

Chapter 8

Wire and Configure the 1753-IB16XOB8 Module

Safety-related Digital
Outputs

Terminal Number

Designation

Function

63

LS+

Sensor supply for inputs 1316


40 mA buffered/1 A unbuffered

64

LS+

Sensor supply for inputs 1316


40 mA buffered/1 A unbuffered

65

13

Digital input 13

66

14

Digital input 14

67

15

Digital input 15

68

16

Digital input 16

69

L-

Reference pole

70

L-

Reference pole

71

Ground

Shield

72

Ground

Shield

The module has 8 digital output pairs, each with a positive- and
negative-switching output. The digital outputs are not electrically
isolated.
An output is in the safe state when it is de-energized. Therefore,
outputs are switched off when a fault that affects the safety control of
those outputs occurs.
If an overload occurs, the affected output is switched off. If the total
current exceeds 9 A, all eight outputs are switched off. When the
overload is eliminated, the outputs are activated again according to
their current software-driven state.

Configuration
The digital outputs can be configured three ways.
1-pole switch (no line monitoring)
2-pole switch (with or without line monitoring)
3-pole switch (2-pole with common reference)

86

Publication 1753-UM001C-EN-P - March 2010

Wire and Configure the 1753-IB16XOB8 Module

Chapter 8

1-Pole Connection
For 1-pole applications, all 8 positive-switching and all 8
negative-switching outputs are available, for a total of 16 outputs. If
you are using a positive-switching output, connect the other side of
the output to S-. If you are using a negative-switching output, connect
the other side of the output to S+.
Line monitoring with a 1-pole connection is not possible.
You must not connect the positive-switching output directly to
an external L- load or connect the negative-switching output
directly to an external L+ load. You must use the S+ and Sterminals.

ATTENTION

For 1-pole connections, inductive loads can be connected without a


protection diode on the load, because there is a protection diode
located within the GuardPLC module. However, Rockwell Automation
strongly recommends that a protection diode be fitted directly to the
load to suppress any interference voltage. A 1N4004 diode is
recommended.
1-pole Configuration
S+

Actuator

1753-IB16XOB8
1+
1-

S-

2+

2-

Publication 1753-UM001C-EN-P - March 2010

87

Chapter 8

Wire and Configure the 1753-IB16XOB8 Module

2-Pole Connection
If the outputs are configured for 2-pole operation, 8 outputs are
available. Each of the 8 outputs switch both L+ and L-. 2-pole outputs
(without line monitoring) are wired to both the positive-switch and
negative-switch of a single channel, 2+ and 2- for example.
2+

2-

IMPORTANT

ATTENTION

ATTENTION

The corresponding channels for 2-pole connections must be


configured for 2-pole operation by using the system variable
DO[xx].2-pole. See Appendix B for more information on system
variables.

The positive-switching output must be wired to an output along


with the corresponding negative-switching output of the same
channel. Negative- or positive-switching outputs must not span
different channels unless they are connected in pairs (see
3-pole Connection With Line Monitoring on page 89).

Inductive loads must be connected with a protection diode on


the load in 2-pole operation.

2-pole Configuration
1753-IB16XOB8

88

Actuator

Publication 1753-UM001C-EN-P - March 2010

Wire and Configure the 1753-IB16XOB8 Module

Chapter 8

3-pole Connection With Line Monitoring


Two 2-pole channels can support dual-channel devices with only a
single reference connection. If line monitoring is required, the
channels must be configured in pairs, using the system parameter
DO[xx][xx].in pairs. There are four pairs allowed: channels 1 and 2,
channels 3 and 4, channels 5 and 6, and channels 7 and 8.
Line monitoring is accomplished by switching off one channel while
the second channel is tested for wiring faults.
A detected line fault is reported by the modules error codes. See
Appendix B for error code information.
3-pole Configuration
1753-IB16XOB8

Load

(drive, valve)

IMPORTANT

Publication 1753-UM001C-EN-P - March 2010

Inductive loads must be connected with a protection diode on


the load for 3-pole connections.

89

Chapter 8

Wire and Configure the 1753-IB16XOB8 Module

Terminal Connections
See the wire size and terminal torques specifications on page 290.
Digital outputs are connected to these terminals.
1

2 3 4 5 6

7 8

S+ S+ S+ S+ S- S- S- S-

90

9 10 11 12 13 14 15 16

17 18 19 20 21 22 23 24

1- 1+ 2- 2+ 3- 3+ 4- 4+
DO

5- 5+ 6- 6+ 7- 7+ 8- 8+
DO

Terminal Designation
Number

Function

S+

Reference pole for negative-switching digital outputs

S+

Reference pole for negative-switching digital outputs

S+

Reference pole for negative-switching digital outputs

S+

Reference pole for negative-switching digital outputs

S-

Reference pole for positive-switching digital outputs

S-

Reference pole for positive-switching digital outputs

S-

Reference pole for positive-switching digital outputs

S-

Reference pole for positive-switching digital outputs

1-

Digital output 1, negative-switching

10

1+

Digital output 1, positive-switching

11

2-

Digital output 2, negative-switching

12

2+

Digital output 2, positive-switching

13

3-

Digital output 3, negative-switching

14

3+

Digital output 3, positive-switching

15

4-

Digital output 4, negative-switching

16

4+

Digital output 4, positive-switching

17

5-

Digital output 5, negative-switching

18

5+

Digital output 5, positive-switching

19

6-

Digital output 6, negative-switching

20

6+

Digital output 6, positive-switching

21

7-

Digital output 7, negative-switching

22

7+

Digital output 7, positive-switching

23

8-

Digital output 8, negative-switching

24

8+

Digital output 8, positive-switching

Publication 1753-UM001C-EN-P - March 2010

Wire and Configure the 1753-IB16XOB8 Module

Monitor for Line Short Line


Break

Chapter 8

The Line Short Line Break (LSLB) monitoring measures the impedance
of a load and allows the modules to detect the following faults, when
LSLB monitoring is configured by using the system variable
DO[xx].LSLB:

Short-circuit between DO+ and DOShort-circuit DO+ and external L+


Short-circuit between DO+ and external LShort-circuit between DO- and external L+
Short-circuit between DO- and external LLine break between DO+ and DO-

Line monitoring of the digital outputs is possible only when outputs


are configured for 2-pole operation and both poles DO[xx]- and
DO[xx]+ are wired to a load. A detected line fault is reported in the
system signal DO[xx].+Error Code or DO[xx].-Error Code. See
Appendix B for information on system signals.
There are two kinds of line monitoring.
Line monitoring for lamp loads and inductive loads
Line monitoring for resistive, capacitive loads
For both types, you must configure a period and time for line
monitoring by using the system signal variables described on page 93.

Line Monitoring for Lamp and Inductive Loads


For short-circuit detection, a 24V impulse with a duration of 500 s is
switched in the output circuit. Afterwards, a 10V signal is set for the
duration of the monitoring time to detect a line break.
To configure this type of line monitoring:

set a DO.LSLB period and DO.LSLB time.


set the output DO[xx].2-pole signal to 1 (TRUE).
set the output DO[xx].LSLB monitoring signal to 1 (TRUE).
set the output DO[xx].LS monitoring with reduced voltage signal
to 0 (FALSE).

See Required Signals for Line Monitoring on page 93.

Publication 1753-UM001C-EN-P - March 2010

91

Chapter 8

Wire and Configure the 1753-IB16XOB8 Module

Line Monitoring with Reduced Voltage for Resistive, Capacitive


Loads
For line monitoring, a 10V signal is switched on in the output circuit
for the duration of the monitoring time. This kind of line monitoring is
designed for resistive or resistive-capacitive loads. There is no
short-circuit detection for these types of loads.
To configure this type of line monitoring:

set a DO.LSLB period and DO.LSLB time.


set the output DO[xx].2-pole signal to 1 (TRUE).
set the output DO[xx].LSLB monitoring signal to 1 (TRUE).
set the output DO[xx].LS monitoring with reduced voltage signal
to 1 (TRUE).

See Required Signals for Line Monitoring on page 93.

ATTENTION

During the 10V test to detect a line break, DO+ is at 24V and
DO- is at 14V. If DO- is shorted to 0V DC, then there is 24V at
the output for the duration of the monitoring time, which could
turn on the actuator.
During line monitoring time, a 10V signal is impressed at the
load (relay, actuator). This reduced voltage level (10V) of line
monitoring, is normally not enough to switch the load.

Period and Monitoring Times


You must set a period and monitoring time for line control. These
configured times affect all channels that are set for line monitoring.
During monitoring time, readbacks occur at intervals of 1 ms. If no
errors occur, the output is set per the application program.

ATTENTION

TIP

92

The duration of monitoring time adds to the cycle time.

There are 4 tests during the LSLB test period (DO.LSLBperiod).


In principle, this means that there will be a test every 1/4 of the
period. So if the period is 1 second, there will be a test every
250 ms. If the LSLB time duration (DO.LSLB time) is 20 ms, there
will be 230 ms between 20 ms tests.
Publication 1753-UM001C-EN-P - March 2010

Wire and Configure the 1753-IB16XOB8 Module

Chapter 8

Required Signals for Line Monitoring


Line monitoring must be configured by using these system signals for
1753-IB16XOB8 modules on the Outputs tab of the digital outputs
Signal Connections dialog box in RSLogix Guard PLUS! software.
Name

Description

Setting

DO.LSLB period

The time between steps in Line Short Line


Break (LSLB) monitoring

Values in one second increments from


1100.

DO.LSLB time

The duration of LSLB monitoring

Values in one millisecond increments from


050 ms. The default is 0 ms.

DO[xx].2-pole

Configures the module for 2-pole operation

1 = 2-pole operation.
0 = 1-pole operation.

DO[xx].+Value

Output value for DO channels (DO+)

1-pole (Value: 0 or 1).


2-pole, identical to DO- (Value: 0 or 1).

DO[xx].-Value

Output value for DO channels (DO-)

1-pole (Value: 0 or 1).


2-pole, identical to DO+ (Value: 0 or 1).

DO[xx].LSLB monitoring

Configures line control

1 = set for LSLB (line control)


0 = no LSLB (line control)

DO[xx].LS monitoring with reduced


voltage

Configures line control with reduced voltage

1 = reduced signal voltage level


0 = normal signal voltage level

DO[xx][xx].in pairs

Configures line control with channel pairs

Pair 1 = channel 1 [01] and channel 2 [02]


Pair 2 = channel 3 [03] and channel 4 [04]
Pair 3 = channel 5 [05] and channel 6 [06]
Pair 4 = channel 7 [07] and channel 8 [08]

See Appendix B for a complete list of 1753-IB16XOB8 module


variables.

Pulse Test Sources

The two digital pulse test sources (PO) can be used for short-circuit or
line break monitoring of digital inputs. For information on configuring
pulse test sources for line control, see Chapter 11.

ATTENTION

Pulse test sources must not be used as safety-related outputs.

Each output has four terminals for wiring connections.


25 26 27 28 29 30 31 32

1 1 1 1 2 2 2 2

Publication 1753-UM001C-EN-P - March 2010

93

Chapter 8

Wire and Configure the 1753-IB16XOB8 Module

Pulse test sources are connected to these terminals.


Terminal Number

Designation

Function

25

Pulse test source 1

26

Pulse test source 1

27

Pulse test source 1

28

Pulse test source 1

29

Pulse test source 2

30

Pulse test source 2

31

Pulse test source 2

32

Pulse test source 2

All PO1 terminals are internally connected and all PO2 terminals are
internally connected. Therefore, all PO1 and all PO2 terminals pulse
together.

94

Publication 1753-UM001C-EN-P - March 2010

Chapter

Wire the 1753-IF8XOF4 Analog I/O Module

Introduction
Topic

Page

Safety-related Analog Inputs

95

Standard Analog Outputs

97

The 1753-IF8XOF4 module features 8 safety analog inputs and 4


standard analog outputs.

Safety-related Analog
Inputs

These input values are available.


Input Channels

Polarity

Current or Voltage

Range

Safety
Accuracy

unipolar

0+10V

02000

2%

020 mA / 420
mA

01000(1)
02000(2)

(1) With external 250 shunt.


(2) With external 500 shunt.

Voltage Measurement
If an open-circuit fault occurs during voltage measurement,
unpredictable input signals are received on the high resistance inputs.
Values resulting from this fluctuating input voltage are not reliable.
Because the module does not feature circuit monitoring, you must
terminate input channels with a 10 k resistor when measuring
voltage. Consider the internal resistance of the source as well.

Current Measurement
To measure current, connect a 500 external shunt in parallel to the
input. Accuracy of the shunt must be included in accuracy calculations
of the input signal. Terminating resistors are not required for current
measurement with the external shunt connected in parallel.

95Publication 1753-UM001C-EN-P - March 2010

95

Chapter 9

Wire the 1753-IF8XOF4 Analog I/O Module

Terminal Connections
Analog cabling should be no more than 300 m (984 ft) in length and
must be shielded, twisted-pair cables for each measurement input.
The shields must be connected at one end.

IMPORTANT

Short-circuit unused input channels to the reference pole by


connecting wire jumpers.
AI
T1 I1 L- T2 I2 L-

41 42 43 44 45 46
Wire Jumpers

Wire Jumpers

AI
T1 I1 L- T2 I2 L-

AI
T3 I3 L- T4 I4 L-

AI
T5 I5 L- T6 I6 L-

AI
T7 I7 L- T8 I8 L-

1 2 3 4 5 6

7 8 9 10 11 12

13 14 15 16 17 18

19 20 21 22 23 24

See the wire size and terminal torques specifications on page 292.
Analog inputs (AI) are connected to these terminals.
Terminal Number

96

Designation

Function

T1

Sensor supply 1

I1

Analog input 1

L-

Reference pole input 1

T2

Sensor supply 2

I2

Analog input 2

L-

Reference pole input 2

T3

Sensor supply 3

I3

Analog input 3

L-

Reference pole input 3

10

T4

Sensor supply 4

11

I4

Analog input 4

12

L-

Reference pole input 4

13

T5

Sensor supply 5

14

I5

Analog input 5

15

L-

Reference pole input 5

16

T6

Sensor supply 6

17

I6

Analog input 6

18

L-

Reference pole input 6


Publication 1753-UM001C-EN-P - March 2010

Wire the 1753-IF8XOF4 Analog I/O Module

Standard Analog Outputs

Chapter 9

Terminal Number

Designation

Function

19

T7

Sensor supply 7

20

I7

Analog input 7

21

L-

Reference pole input 7

22

T8

Sensor supply 8

23

I8

Analog input 8

24

L-

Reference pole input 8

The module has 4 analog outputs, which are not safety-rated outputs.
However, in the event of an internal error, they can be shut down
safely through configuration via the user program.

ATTENTION

To achieve SIL 3, the output values must be read back via safety
analog inputs and evaluated in the RSLogix Guard PLUS! user
program. Appropriate reactions to incorrect output values must
be applied. Otherwise, they may not be used as safety outputs.

When you are not using the analog outputs, use RSLogix Guard PLUS!
programming software to set the 4 analog output (USED) system
signals to FALSE. When set to FALSE, no output signals are transmitted
when the safety switches are opened. Alternatively, you can set the
analog outputs to zero by using the Emergency Off system variable.
These are the analog output resolution options.

Publication 1753-UM001C-EN-P - March 2010

Value Range in the Application

Output Current

0 mA

2000

20 mA

97

Chapter 9

Wire the 1753-IF8XOF4 Analog I/O Module

Terminal Connections

AO
01
+ -

02
03
04
+ - + - + -

25 26 27 28 29 30 31 32

See the wire size and terminal torques specifications on page 292.
Analog outputs (AO) are connected to these terminals.
Terminal Number
25
26
27
28
29
30
31
32

98

Designation
O1
O2
O3
O4

Function

Analog output 1

Reference pole output 1

Analog output 2

Reference pole output 2

Analog output 3

Reference pole output 3

Analog output 4

Reference pole output 4

Publication 1753-UM001C-EN-P - March 2010

Chapter

10

Wire the 1753-OW8 Relay Output Module

Introduction

Safety-related Relay
Outputs

Topic

Page

Safety-related Relay Outputs

99

Terminal Connections

99

Voltage Supply Considerations

100

The module has 8 isolated relay outputs whose status is indicated via
status indicators.
An output is in a safety state when it is de-energized. When a fault
occurs, all outputs are switched off. Errors in one or more channels
are indicated by the FAULT status indicator. In addition, the system
status can be evaluated in the user program.
If the 1753-OW8 module faults, all 8 outputs are switched off. This is
indicated by the FAULT status indicator.
Each output has 2 safety relays with positively guided contacts and
one MSR type relay. Internal, non-replaceable fuses are used to limit
the switching current of the output contacts to 60% (3.15 A) of the
maximum admissible AC switching current. For DC switching, the
relay contact circuits must be additionally equipped with an external
fuse rated no higher than the maximum admissible DC switching
capacity.

Terminal Connections

See the wire size and terminal torques specifications on page 294.
Relay outputs are connected to these terminals.
Terminal Number

Designation

Relay Output

DO1

Contact 1, terminal A

2
3

Contact 1, terminal B
DO2

4
5
6

99Publication 1753-UM001C-EN-P - March 2010

Contact 2, terminal A
Contact 2, terminal B

DO3

Contact 3, terminal A
Contact 3, terminal B

99

Chapter 10

Wire the 1753-OW8 Relay Output Module

Terminal Number

Designation

Relay Output

DO4

Contact 4, terminal A

8
9

Contact 4, terminal B
DO5

Contact 5, terminal A

10
11

Contact 5, terminal B
DO6

Contact 6, terminal A

12
13

Contact 6, terminal B
DO7

Contact 7, terminal A

14
15

Contact 7, terminal B
DO8

Contact 8, terminal A

16

Contact 8, terminal B

The output contacts are connected in pairs via terminal connectors


(numbered terminals). The terminal pins on the front plate of the
module have the same numbering sequence to help prevent
miswiring.

Voltage Supply
Considerations

100

DO 2

DO 1

Example: Connecting Actuators to the Outputs

For the connection of higher voltages (110/220V AC) besides SELV


and PELV (24V DC), suitable cables must be used with double or
reinforced insulation.

Publication 1753-UM001C-EN-P - March 2010

Chapter

11

Pulse Testing

Introduction
Topic

Page

Response to OS Configurable Faults

102

Wire for OS Configurable Line Control

103

Input Configuration for Pulse Testing

105

Pulse testing is a high-frequency diagnostic test that can detect wiring


faults on input devices before demand is placed on the safety system.
There are two ways to generate a pulse test in the GuardPLC family of
products.
By using Redundant Pulse Test Output (RPTO) and Single Pulse
Test Output (SPTO) certified function blocks in the application
program
By using the services built into the GuardPLC 1600 and
GuardPLC 2000 controllers operating systems
This table lists the pulse test methods available for your product.
Controller

RPTO/SPTO Function Blocks

OS Configurable

GuardPLC 1200

yes

no

GuardPLC 1600

yes

yes

GuardPLC 1800

yes

no

GuardPLC 2000

yes

yes

Pulse testing cannot be configured on the GuardPLC 1200 and


GuardPLC 1800 controllers, or on the 1753-OB16 output-only module.
The GuardPLC 1800 controller is excluded because it features digital
inputs that are actually analog inputs with 1-bit resolution.
You can choose between the two methods for pulse testing the
GuardPLC 1600 controller and distributed I/O modules (catalog
numbers 1753-IB16, 1753-IB8XOB8, 1753-IB16XOB8, and
1753-IB20XOB8) controlled by the GuardPLC 1600 controller. You
also have the choice of methods for the GuardPLC 2000 controller and
1755-IB24XOB16 module.

101Publication 1753-UM001C-EN-P - March 2010

101

Chapter 11

Pulse Testing

Consider the following when choosing a method of pulse testing:


The certified function block lets the pulse test source (output)
and safety input to be on different physical nodes. The OS
configured pulse test assumes that the source and input are local
to the same physical controller or I/O module.
The certified function block has a pulse test fault output that can
be used for status inside the user program. The OS configured
pulse test has an error code that can be monitored for pulse test
status.
The OS configured pulse test occurs each cycle. The pulse test
certified function blocks allow you to configure the pulse test
interval.
The duration of the pulse test is configurable when using the
certified function blocks.
The pulse test can be disabled if necessary when using the
certified function blocks.
The response to RPTO/SPTO pulse test faults is user
configurable.
See the Certified Function Block Safety Reference Manual, publication
1753-RM001, for more information on the Single Pulse Test Output
(SPTO) and Redundant Pulse Test Output (RPTO) certified function
blocks.

Response to OS
Configurable Faults

When the following occurs, the faulted inputs are set to 0, a fault code
is generated, and the FAULT status indicator is on:
Short-circuit occurs between two parallel connections.
Two connections are reversed.
Earth fault occurs on one of the lines (only with earthed
reference pole).
Line break or opening of the contacts (for example, when one
of the E-stop off switches is pressed in the example above), the
FAULT status indicator is on and the fault code is generated.
TIP

102

If multiple errors exist at the same time, the error code is the
sum of the individual error codes. See Appendix B for error code
information.

Publication 1753-UM001C-EN-P - March 2010

Pulse Testing

Wire for OS Configurable


Line Control

Chapter 11

GuardPLC 1600 Controller and 1753-IB20XOB8 Module


Up to 8 digital outputs (DO1 to DO8) can be configured as pulsed
outputs. The example below shows 2 outputs, configured as pulse test
outputs, connected to the digital inputs (DI) of the same system. As a
result, the connections to the digital inputs (DI) are monitored.
The pulse outputs must begin at DO[01] and must be sequential. For
example, if two pulse outputs are required, they must be DO[01] and
DO[02].
DO 1

Emergency OFF 1

Emergency OFF 2

DI5

DI 7

DO1
Configurable 5 2000 s

DO2
Configurable 52000 s

The digital outputs DO1 and DO2 are pulsed (briefly set to low) so
that the connections to the digital inputs are monitored. The duration
of the test can be configured in the range of 52000 s with a default
value of 400 s.

Publication 1753-UM001C-EN-P - March 2010

103

Chapter 11

Pulse Testing

1753-IB16, 1753-IB8XOB8, and 1753-IB16XOB8 Modules


The 1753-IB16 module has four digital pulse test sources (PO). The
1753-IB8XOB8 and 1753-IB16XOB8 modules have two digital pulse
test sources.
The example below shows 2 pulse test sources connected to the
digital inputs (DI) of the same system. As a result, the connections to
the digital inputs (DI) are monitored..
PO 1

Emergency OFF 2

Emergency OFF 1
DI 1

ATTENTION

104

DI 3

Do not use pulsed outputs as safety-related outputs for control


of safety-related actuators.

Publication 1753-UM001C-EN-P - March 2010

Pulse Testing

Input Configuration for


Pulse Testing

Chapter 11

Set up these signals by using the Outputs tab of the digital inputs
Signal Connections dialogbox in RSLogix Guard PLUS! software.

Name

Description

Type

Number of Pulse Channels

Number of pulse outputs being used

USINT 1 to 8

14 for 1753-IB16
18 for GuardPLC 1600/2000 controllers
18 for 1753-IB20XOB8
12 for 1753-IB8XOB8 and 1753-IB16XOB8

Pulse Slot

Slot occupied by the module with the


pulsed outputs

UDINT

2 for GuardPLC 1600 controllers


2 for 1753-IB20XOB8
1 for 1753-IB16
3 for 1753-IB8XOB8
3 for 1753-IB16XOB8
16 for GuardPLC 2000 controllers
(wherever 1755-IB24XOB16 is located)

Pulse Delay

Pulse delay is both the low pulse


width and pulse test duration.

UINT

Error Code

Error code for each switch

BYTE

Value

Value for each switch

BOOL

DI[xx].PulseChannel

Indicates which pulse output is


sourcing the input channel

USINT 1 to 8

14 for 1753-IB16
18 for GuardPLC 1600/2000 controllers
18 for 1753-IB20XOB8
12 for 1753-IB8XOB8 and 1753-IB16XOB8

DO[xx].Value

Initialization value for the pulse


outputs

BOOL

Each pulse output must be activated.

Publication 1753-UM001C-EN-P - March 2010

Initial
Value

Notes

400
Values in s from 52000.
(default)
N/A

TRUE

See Appendix B for error code descriptions.

105

Chapter 11

Pulse Testing

Notes:

106

Publication 1753-UM001C-EN-P - March 2010

Chapter

12

High-Speed Counters

Introduction

This chapter covers using counters in these systems:


GuardPLC 1200 controllers
GuardPLC 1800 controllers
GuardPLC 2000 controllers using a 1755-HSC module

Counter/Decoder Modes

Topic

Page

Counter/Decoder Modes

107

Understand Counter Module Configuration

109

The counters can be used in these operating modes:


Counter mode
Decoder mode
The two counters can be used in different modes at the same time.

Counter Mode
Counter mode is used for counting pulses at speeds up to 1 MHz on
the GuardPLC 2000 controllers and 100 kHz on the GuardPLC 1200
and 1800 controllers.
Follow these guidelines when using counters in a GuardPLC system:
The 5V signal must be between 4.5V and 5.5V, while the 24V
signal must be between 13V and 26.4V.
The steepness of the falling edge must be at least 1V per s.
The low and high signal times must be at least 5 s for the
GuardPLC 1200 controller (duty cycle 50% at 100 kHz) and
0.5 s for the GuardPLC 2000 controller (duty cycle 50% at
1 MHz).
Shield the cable against noise.

107Publication 1753-UM001C-EN-P - March 2010

107

Chapter 12

High-Speed Counters

Counter Mode Inputs


Pins

Functions

A1, A2

counting input for pulses (high-signals) with falling edge of the pulses

B1, B2

counting direction input, incrementing the counter with low-signal,


decrementing the counter with high-signal

Z1, Z2

resets inputs
Resets can be made with a short high-signal. A continuous high-signal
blocks the counter. Resets can also be made by the controller program.

C1, C2

has no function (GuardPLC 2000 controller - 1755-HSC only)

C-

GuardPLC 2000 controller common reference pole, all pins have electrical
continuity

L-

GuardPLC 1800 controller common reference pole, all pins have electrical
continuity

I-

GuardPLC 1200 controller common reference pole, all pins have electrical
continuity

Decoder Mode
Decoder mode is used for safety supervising the inputs by Gray code,
but in the application, the bit structure is handled as a normal binary
code value. To use this value, it must be converted in the application.
The counter inputs can be connected to an incremental encoder with
4-bit binary code to recognize rotation and the direction of rotation.
Decoder Mode Inputs

108

Pins

Functions

A1, A2

bit 1 (LSB)

B1, B2

bit 2

Z1, Z2

bit 3

C1, C2

bit 4 (GuardPLC 2000 controllers only)

Publication 1753-UM001C-EN-P - March 2010

High-Speed Counters

Understand Counter
Module Configuration

Chapter 12

The high-speed counters can be configured for three counting modes:


Counter mode with manual direction, Counter mode with direction
and reset, and Decoder mode (Gray codes).

Counter Mode/Manual Direction


The simplest mode of operation is pulse counting with manual
direction. It can be used, for example, in connection with a light
barrier where counting events are to be recorded. The direction of
counting is determined by the routine.
The count begins at 0 and is incremented or decremented by 1 at each
negative transition of the counting pulse. The resolution of the
counter is 24 bits. This results in a value range from 016,777,215.
The counting pulse must be bounce free and must not exceed the
maximum frequency of 1 MHz for a GuardPLC 2000 controller or
100 kHz for a GuardPLC 1200 or 1800 controller. The counter input
can be set to a voltage of 5V or 24V via the software.
To be sure that the counter functions correctly, configure these
parameters.

Publication 1753-UM001C-EN-P - March 2010

Parameter

Setting

Cnt[0x].5/24V Mode

true for 24V


or
false for 5V
You must configure this parameter with a constant.

Cnt[0x].Auto Advance Sense

(optional according to routine)


false to count only up or only down based upon the
direction bit

Cnt[0x].Direction

(optional according to routine)


true to decrement (counts from 16,777,215 downward)
or
false to increment

Cnt[0x].Gray Code

(optional according to routine)


false

Cnt[0x].Reset

(optional according to routine)


true
If this parameter is set to false, the counter value is
reset to 0.

109

Chapter 12

High-Speed Counters

Counter Mode/Direction and Reset


In pulse counting with direction and reset, the state of input B is
evaluated in addition to counter input A.
When the B input has a low signal while the counter recognizes a
negative pulse edge at its A input, the value of the counter is
incremented by 1. When there is a high signal at the B input, the
counter is decremented by 1.
The counter is released or reset via the Z input. The counter is
released when there is a constant LOW signal at the Z input. A
constant HIGH signal halts the counter and a short-time HIGH signal
resets the counter value to 0.
To enable the counter to function correctly, configure these
parameters in the routine.

110

Parameter

Setting

Cnt[0x].5/24V Mode

true for 24V


or
false for 5V
The adjusted level also applies to inputs B and Z.
You must configure this parameter with a constant.

Cnt[0x].Auto Advance Sense

true to count up and down simultaneously

Cnt[0x].Direction

true to decrement (counts from 16,777,215 downward)


or
false to increment (standard setting)

Cnt[0x].Gray Code

false

Cnt[0x].Reset

true
If this parameter is set to false, the counter value is
reset to 0.

Publication 1753-UM001C-EN-P - March 2010

High-Speed Counters

Chapter 12

Decoder Mode/Gray Codes


The Gray code is a binary code where the code differs by only one bit
with two neighboring numbers. Gray codes are useful in mechanical
encoders, because a slight change in location affects only one bit. The
controller uses a Gray code (4 bits for a GuardPLC 2000 controller or
3 bits for GuardPLC 1200 and 1800 controllers) that has this structure.
Step

Gray Code
(GuardPLC 2000)

Gray Code
(GuardPLC 1200,
1600, and 1800)

Cnt[0x].Value

0000

000

0001

001

0011

011

0010

010

0110

110

0111

111

0101

101

0100

100

1100

12

1101

13

10

1111

15

11

1110

14

12

1010

10

13

1011

11

14

1001

15

1000

Each counter input is fed to three internal counters. When a count is


accomplished, the values of the three internal counters are compared,
and if the three values differ by more than one bit, the measuring
result is rejected and Cnt[0x].State indicates an error.
If the measuring result is valid, the system variable Cnt[0x].Value
contains the associated value (see the above table).

Publication 1753-UM001C-EN-P - March 2010

111

Chapter 12

High-Speed Counters

To enable the Gray code decoder to work correctly, configure these


parameters in the routine.

112

Parameter

Setting

Cnt[0x].5/24V Mode

true for 24V


or
false for 5V
The adjusted level also applies to inputs B and Z.
You must configure this parameter with a constant.

Cnt[0x].Auto Advance Sense

this setting has no function on the gray code


(set to false)

Cnt[0x].Direction

this setting has no function on the gray code


(set to false)

Cnt[0x].Gray Code

true

Cnt[0x].Reset

this setting has no function on the gray code


(set to true)

Publication 1753-UM001C-EN-P - March 2010

Chapter

13

Controller Configuration and Modes of


Operation

Introduction
Topic

Page

Controller Modes

113

Controller Configuration

117

Routine Modes

120

Load a Configuration and Routine (in Stop Mode only)

121

Test Mode of the Routine

122

The GuardPLC operating system is stored permanently in the memory


of the controller. The operating system is designed to make sure that
all tasks of the controller are performed in a safety-related way.
You have access to the controller via the RSLogix Guard PLUS!
software so that you can define the functionality of the controller.

Controller Modes

The controller can operate in various modes. These modes depend on


the results of the tests of the hardware, software, and the system
configuration.
After you apply power to the controller or restart the controller, the
controller first performs a system test of the data and address lines and
the flash and RAM memories. Then the controller checks the operating
system in the flash memory. During this time, the controller is in the
Init mode.
If all these initialization checks are OK, the operating system is started
and the controller changes to the Stop mode.
If any hardware or software errors are detected, the controller goes to
the Failure_Stop mode. If the check of the operating system detected
errors, the emergency loader starts. The emergency loader loads an
operating system from the programming terminal.
If the controller has a valid configuration and a routine downloaded to
the controller, the controller goes to the Stop mode.

113Publication 1753-UM001C-EN-P - March 2010

113

Chapter 13

Controller Configuration and Modes of Operation

To put the controller in Run mode:


set the Autostart switch of the both controller and the routine.
manually choose Run mode from the programming software.
If you stop the controller, it transitions from Run to Stop and
interrupts the execution of the routine. The outputs of the routine and
the I/O modules are reset to safe values.
You can use the Emergency Stop system variable to put the controller
in Stop mode by programming this variable in your logic or forcing it
when necessary.
The following table and flowchart summarize the controller modes.
Mode

Description

INIT

Safe state of the controller during initialization and the hardware tests after booting.
The controller is performing hardware and software tests.

STOP

Safe state of the controller without execution of a routine.


A loaded routine is in the Stop mode.
The outputs of the controller have been reset (LOW).
The controller is performing hardware and software tests.

RUN

The CPU is active.


The routine is being executed.
I/O signals are being processed.
The controller performs non-safety-related communication.
The controller performs software tests, hardware tests, and I/O module tests.

FAILURE_STOP

Safe state of the controller after a system fault.


A loaded routine is in Stop or Failure_Stop mode.
The outputs of the controller are being reset (LOW).
The controller is not performing software or hardware tests.
The controller is being held in the safe state.
The hardware watchdog is not triggered.
To recover from Failure_Stop, a restart of the controller is necessary. A restart can be
initiated only via RSLogix Guard PLUS! software. See Recover From a Failure_Stop on
page 116.

114

Publication 1753-UM001C-EN-P - March 2010

Controller Configuration and Modes of Operation

Chapter 13

Controller Modes

BOOT

Yes

INIT

INIT OK?
Yes

No
Hardware/Software
Errors

Restart?

No

FAILURE_STOP

STOP

Hardware/Software
Errors?

No
No

Yes
Hardware/Software
Errors

START?

Yes
RUN

Hardware/Software
Errors?

Yes

No
No

Stop Command?

Yes

Publication 1753-UM001C-EN-P - March 2010

115

Chapter 13

Controller Configuration and Modes of Operation

Recover From a Failure_Stop


If the controller is in Failure_Stop, you must restart the controller,
following the steps below.
1. If the controller is not online, you must go online first.
a. In the Hardware Management window, from the Online
menu, choose Control Panel .

b. Type the Administrator username and password on the login


dialog box.

TIP

You can use the [Ctrl]+[A] shortcut to enter the default


username (Administrator) and password.

2. Once online, from the Control Panel Extra menu, choose Reboot
Resource as shown below.

TIP

116

A Reboot Resource can be initiated only when the controller is


in Failure_Stop mode. If you attempt a restart while the
controller is in any other mode, an error message appears.

Publication 1753-UM001C-EN-P - March 2010

Controller Configuration and Modes of Operation

Chapter 13

If a routine has already been loaded in the controller when


Failure_Stop occurs, the controller goes to Stop/Valid_Configuration
after booting. If Autostart Enable is activated, the routine starts up
automatically.
If a routine has not been loaded in the controller when Failure_Stop
occurs, the controller goes to Stop/Invalid_Configuration after
booting.

Controller Configuration

TIP

If the GuardPLC controller is in Stop/Invalid_Configuration after


booting, you need to update the SRS. From the Extra menu,
choose Change System ID (SRS). Enter the SRS and click OK.

TIP

A brand-new GuardPLC 1200 or 2000 controller, into which a


back-up battery has not yet been installed, is always in
Failure_Stop and must be restarted before you can download a
routine.

To enable the controller to perform its tasks, you have to configure


the controller. The parameters you specify are stored in the
nonvolatile RAM and in the flash file system of the communication
section of the controller.
To configure a controller, follow these steps.
1. In the Hardware Management Window, expand the
Configuration module.
2. Right-click Resource and choose Properties.

3. From the Type pull-down menu, choose your controller.

Publication 1753-UM001C-EN-P - March 2010

117

Chapter 13

Controller Configuration and Modes of Operation

4. Set the controller parameters based on the information the table


below.

IMPORTANT

The safety time you specify must meet the needs of the
controlled process. See the GuardPLC Controller Systems
Safety Reference Manual, publication 1753-RM002.

For this parameter

Specify

System ID (SRS)

the system ID of the controller.


The system ID is a component of the SRS (System, Rack, Slot), and can be in the range of
265535. The programming terminal uses the system ID to communicate with the controller. The
purpose of the SRS is to match a routine to a specific resource and guarantee that only a routine
with a matching SRS can be downloaded to a resource.
The system ID of the controller should not be set at 1 because 1 is the default system ID for the
programming terminal.
IMPORTANT: The SRS set in the configuration is compiled in the routine.EXE file and must match
the SRS of the GuardPLC controller for a routine to be correctly downloaded to the GuardPLC
controller. A different system ID results in an Invalid_Configuration error during download.
IMPORTANT: The default SRS of a new controller is 60000. You must use this to establish
communication with the controller the first time. Once you establish communication, you can
change the SRS.

Safety Time (ms)

the safety time (in milliseconds) for the controller.


The safety time is the time:
the controller must react to an input signal with an output signal.
within which the controller must react to an error.
The default safety time is 2 times the default watchdog time. You can specify any time from
2050000 ms.

Watchdog Time (ms)

the maximum amount of time (in milliseconds) that the controller can take to execute one cycle.
The watchdog time must be:
10 ms.
0.5 x Safety Time (Worst case, two cycles must occur within the Safety Time. Therefore,
Safety Time 2 is the maximum watchdog time.).
no more than 5000 ms.
The default watchdog time is:
500 ms for GuardPLC 1200 and GuardPLC 2000 controllers.
50 ms for GuardPLC 1600 and GuardPLC 1800 controllers.
10 ms for 1753-IB16, 1753-IB20XOB8, 1753-OB16 modules.
If the controller exceeds the watchdog time, the controller goes into Failure_Stop.

118

Publication 1753-UM001C-EN-P - March 2010

Controller Configuration and Modes of Operation

Chapter 13

You can set these switches.


This switch

Specifies

Default

Main Enable

whether CPU switches can be changed while the controller is executing.

On/Enabled

If Main Enable is disabled, you cannot change the settings of the other 7 switches
(described below) while the controller is in operation (routine in Run).
Autostart

whether the controller automatically starts up after restarting the controller or applying
power to the controller.

Off/Disabled

If Autostart Enable is enabled, the routine automatically starts up after a restart or


applying power to the controller.
Start/Restart allowed

whether you can start a routine manually.

On/Enabled

If Start/Restart allowed is enabled, you can start a routine manually via the Routine menu
of the Control Panel. Choose either Coldstart or Warmstart. Coldstart is the recommended
setting.
If Start/Restart allowed is disabled, you cannot start a routine manually. You can only start
a routine by restarting the controller or applying power to the controller.
Loading allowed

whether you can load new configuration information to the controller.

On/Enabled

If Loading allowed is disabled, no (new) configuration can be loaded into the controller.
This prevents a user from overwriting the current routine.
Test Mode allowed

whether you can freeze the routine.

Off/Disabled

If Test Mode allowed is enabled, the routine currently running on the controller can be
frozen. This allows the Test Mode with Single Cycle function. You are not allowed to
freeze a routine in standard operation (this would be non-safe operation).
Online Test allowed

whether you can monitor the Function Block code online.

Off/Disabled

Forcing allowed

whether you can force signals.

Off/Disabled

If Forcing allowed is enabled, you can force the signals in the controller.
If Forcing allowed is disabled, you can still display the force editor, but the forcing
functions are locked.
Stop on Force Timeout

whether to stop forcing when the force time expires.

On/Enabled

If Stop on Force Timeout is enabled, the controller terminates execution of the routine
after the user-set force time expires. All outputs go to LOW.
If Stop on Force Timeout is disabled, the controller continues executing the routine with
the process values when the force time expires.
Max Communication
Time Slice

the time in milliseconds reserved for a controller to carry out and complete all
communication tasks in one CPU cycle. This setting is required for Peer-to-Peer
networking.

Publication 1753-UM001C-EN-P - March 2010

10 ms

119

Chapter 13

Controller Configuration and Modes of Operation

Routine Modes

The controller runs only one routine. The following table and
flowchart summarize the routine modes.

Mode

Description

Run_Run

The controller is in the Run mode.


The routine is executed cyclically by the controller.
Input data are processed in the routine.
Output data of the routine are operated.

Run_Freeze

The controller is in the Run mode.


The routine is not executed.
No input data are processed.
No output data of the routine are operated.

Stop

The controller is in the Stop mode.


The routine is no longer being executed.
All outputs have been reset.

Failure_Stop

The controller is in the Stop mode.


The routine was stopped due an error.
All outputs are reset.
The hardware watchdog is not triggered.
To recover from Failure_Stop, a restart of the controller is necessary. A restart can be
initiated only via RSLogix Guard PLUS! software. See Recover From a Failure_Stop on
page 116.

Test Mode (single step)

The controller is in Run mode.


The routine is triggered manually.
I/O data are processed.
IMPORTANT: Test Mode is not permitted for safe operation.

120

Publication 1753-UM001C-EN-P - March 2010

Controller Configuration and Modes of Operation

Chapter 13

Routine Modes
Load
Routine

Yes

STOP

Error in
Routine?

Yes

Restart
Routine?

No

FAILURE_STOP

No
No

Routine
start?
Yes

Freeze
enabled?

Yes

RUN_FREEZE

No

RUN_RUN

Error in
Routine?

Yes

No
No

Routine
stop?
Yes

Load a Configuration and


Routine (in Stop Mode only)

You can load a controller configuration and routine when:


the controller is in Stop mode.
the controller Loading Allowed switch is set.
The controller Stop mode is subdivided into these categories.

Publication 1753-UM001C-EN-P - March 2010

STOP Mode Category

Description

Stop_Valid_Config

The configuration is correctly loaded. The controller can be


set to Run via a command from the programming software.
This initiates a loaded user routine.

Stop_Invalid_Config

No configuration loaded or the loaded configuration is


faulty. The controller cannot go to Run mode.

Stop_Load_Config

loading configuration in process

121

Chapter 13

Controller Configuration and Modes of Operation

The configuration and the routine are loaded together into the
controller. Loading a new configuration and a new routine
automatically deletes all previously loaded objects, even if the new
objects are faulty.
IMPORTANT

Configuration changes take effect only if you re-generate code


before downloading to the controller.

If the controller is in Stop mode, the controller configuration and


routine can also be deleted by using the programming softwares
Clear resource configuration command. The controller goes into the
Stop_Invalid Configuration mode.

Test Mode of the Routine

To execute a single-step operation (cycle step), the controller must be


in Run mode. The Test Mode Allowed switch must be set to ON.
To enter Test Mode, choose the Test Mode menu from the control
panel. Then choose from Hot Start, Warm Start, or Cold Start.

The controller state changes to Freeze, and you can now single cycle
the routine by using the Single Cycle option on the Test Mode menu.
To return to normal operation, choose Continue with Run.
For more information on Test mode options, refer to the Using
RSLogix Guard PLUS! Software with GuardPLC Controllers
Programming Manual, publication 1753-PM001.

122

Publication 1753-UM001C-EN-P - March 2010

Chapter

14

Use the Control Panel to Monitor Status

Introduction

123Publication 1753-UM001C-EN-P - March 2010

The Control Panel is your window into the online functionality of the
controller. Use the tabs to modify or monitor controller status.

Topic

Page

Resource State Tab

124

Safety Parameters Tab

125

Statistics Tab

126

P2P (Peer-to-Peer) State Tab

127

Distributed I/O Tab

128

HH (High-level High-speed) State Tab

128

Environment Data Tab

129

OS Tab

129

HSP Protocol Tab

130

EIP Protocol Tab

131

Use the Multi Control Panel

132

Control Panel Resource Menu

135

Control Panel Extra Menu

136

123

Chapter 14

Use the Control Panel to Monitor Status

Resource State Tab

This field

Displays

CPU State

The current state of the controller.


Possible states are Init, Run, Stop/Valid_Configuration, Stop/Invalid_Configuration, and
Failure_Stop. See Controller Modes on page 113.

COM State

State of the communication portion of the controller.


Possible states are Run, Stop, and OS_Loading.

Program Name

The routine name.


The name assigned by the user to the routine. The default name is Routine.

Program State

The current state of the routine.


Possible states are Run, Stop, Freeze, and Failure_Stop. SeeRoutine Modes on page 120.

Faulty I/O Modules

The number of faulty I/O modules, when the controller is in Run.

Force State

The force status.


0 forcing is disabled
1 ready for forcing (the controller is in stop but is set for forcing)
2 forcing is active

Remaining Force Time [s]

124

The remaining force time in seconds.

Publication 1753-UM001C-EN-P - March 2010

Use the Control Panel to Monitor Status

Chapter 14

Safety Parameters Tab

This field

Displays

CPU configuration CRC

Cyclic redundancy check (CRC) option for the configuration in the CPU (in hexadecimal
notation).
This identifies the configuration loaded in the controller.

System ID

The system ID.

Safety Time [ms]

The safety time in milliseconds.

Watchdog Time [ms]

The watchdog time in milliseconds.

Main Enable

Whether controller switches can be changed while the controller is executing.

Autostart

Whether the controller automatically starts up after restarting the controller or applying
power to the controller.

Start/Restart allowed

Whether you can start a controller manually.

Loading allowed

Whether you can load new configuration information to the controller.

Test Mode allowed

Whether you can freeze the routine.

Forcing allowed

Whether you can force tags.

Stop on Force Timeout

Whether to stop executing the routine when the force time expires.

Publication 1753-UM001C-EN-P - March 2010

125

Chapter 14

Use the Control Panel to Monitor Status

Statistics Tab

This field

Displays

Cycle Time [ms] average

The average cycle time (in milliseconds) of the last 50 cycles.

Cycle Time [ms] last

The cycle time (in milliseconds) of the last cycle.

Cycle Time [ms] min

The fastest cycle time (in milliseconds).

Cycle Time [ms] max

The slowest cycle time (in milliseconds).


If this value exceeds the Watchdog Time, the controller goes to Failure_Stop.

Com. Time Slice [ms]

The time required to process all Peer-to-Peer communication tasks within a CPU cycle.

Number of Time Slices

The number of time slices required to process all communication tasks.


This value should always be 1 to avoid having multiple CPU cycles to complete all
communication tasks.

Date/Time

126

The date and time in the controller.

Publication 1753-UM001C-EN-P - March 2010

Use the Control Panel to Monitor Status

Chapter 14

P2P (Peer-to-Peer) State


Tab

This field

Displays

Resource

The name of the controller.

System ID

The network ID of the controller.

State

The status of the communication.

RspT (last, avg, The Measured ResponseTime for a message from PES1 PES2 PES1, based on the network hardware, CPU cycle
min, max)
time, and Peer-to-Peer profile. This parameter will be optimized later.
MsgNr

The Counter (32-bit resolution) for all messages sent to a controller.

AckMsgNr

The number of the received message that the controller has to acknowledge.

DataSeq

The Counter (16-bit resolution) for sent messages, which contain process data.

Opens

The number of successful connects to a controller.


A figure higher than 1 indicates that a controller dropped out and has been reconnected.

Resends

The Counter (32-bit resolution) for messages that have been resent due to an elapsed ResendTMO.

BadMsgs

The Counter (32-bit resolution) for received messages that are corrupted, or are not expected at that instant.
A corrupt message, for example, is a message with a wrong sender or with a faulty CRC.
An unexpected message, for example, is an Open command, when the controllers are already connected.

EarlyMsgs

The Counter (32-bit resolution) for received messages that are not in the correct sequence. If a message drops out and is
lost at the addressee, there is a gap in the received messages, and the next message comes early.

Receive Tmo

Receive Timeout as entered by the user.

ResendTMO

Resend Timeout as set by the profile.

AckTmo

Acknowledge Timeout as set by the profile.

CurKeVer

CRC for the Peer-to-Peer configuration.


Identical to the Peer-to-Peer system signal.

NewKeVer

Reserved for future use.

Publication 1753-UM001C-EN-P - March 2010

127

Chapter 14

Use the Control Panel to Monitor Status

Distributed I/O Tab

This field

Displays

Resource

The name of the module.

System.Rack

The System.Rack ID of the module.

State

The status of the I/O module:


Run
Stop/Valid_Configuration

Error_Stop
not connected

Stop/Invalid_Configuration

HH (High-level High-speed)
State Tab

128

This field

Displays

Bus Cycle Time

The time in milliseconds for a Token cycle. The value is 0, if Token Passing is off (any Cleanroom profile).

Resource

The name of the controller.

LinkID

The controller network ID.

State

The status of communication.

RspT

If Link Mode is TCS direct (Token Passing OFF), RspT is the ResponseTime of the HH profile for a message
from PES1 PES2 PES1, based on the network hardware and topology. This parameter cannot be
changed by the user.
If Link Mode is TCS TOKCYC (Token Passing ON), RspT is part of the Bus Cycle Time.

Link Mode

TCS direct when Token Passing is OFF.


TCS TOKCYC when Token Passing is ON.

Token Group ID

The ID of the Token Group.

Publication 1753-UM001C-EN-P - March 2010

Use the Control Panel to Monitor Status

Chapter 14

Environment Data Tab

This tab displays status messages in hexadecimal form for


Temperature State, Power Supply State, Fan State, and Relay State.
See Programming Controller Data on page 305 for an explanation of
the error bits.

OS Tab

This field

Displays

Serial Number

The serial number of the communication module of the controller.

CPU OS

The version of the operating system and the cyclic redundancy check of the operating
system (in hexadecimal).
(Version 2.4 or later is required for Peer-to-Peer communication.)

CPU Loader

The version of the operating system loader and the cyclic redundancy check of the
operating system loader (in hexadecimal).

CPU BootLoader

The version of the boot loader and the cyclic redundancy check of the boot loader (in
hexadecimal).

COM OS

The version of the communication operating system and the cyclic redundancy check of the
communication operating system (in hexadecimal).
(Version 2.4 or later is required for Peer-to-Peer communication.)

COM OS Loader

The version of the communication operating system loader and the cyclic redundancy
check of the communication operating system loader (in hexadecimal).

COM BootLoader

The version of the communication boot loader and the cyclic redundancy check of the
communication boot loader (in hexadecimal).

Publication 1753-UM001C-EN-P - March 2010

129

Chapter 14

Use the Control Panel to Monitor Status

HSP Protocol Tab

This field

Displays

Name

The Name of the controller

Controller Id

The SRS of the controller

Controller Receive Timeout

The time limit, within which a message from the scanner must be answered

Controller Resend Timeout

The length of time the controller waits for an acknowledgement of a message before it resend the
message

Scanner Id
HSP Signature

A unique number that ensures that the controllers configuration data matches the scanners configuration
data

Scanner Receive Timeout

The time limit, within which the scanner must receive a message from the controller

Connection State

The state of the connection.


0 = closed.
1 = try open. The active endpoint is attempting to open the connection.
2 = connected. The connection is established. Normal data transfer, time monitoring, and other
functions are occurring.

Frame No.

The number of the last frame sent

Reconnections

The number of connections since the last statistics reset

Bad Messages

The number of discarded messages since the last statistics reset

Resends

The number of repeated messages since the last statistics reset

Last Scanner Response Time The last scanner response time


Average Scanner Response
Time

The average scanner response time since the last statistics reset

Minimum Scanner Response The smallest scanner response time since the last statistics reset
Time
Maximum Scanner
Response Time

The greatest scanner response time since the last statistics reset

Click Reset Statistics to reset the statistics counters.

130

Publication 1753-UM001C-EN-P - March 2010

Use the Control Panel to Monitor Status

Chapter 14

EIP Protocol Tab

This Field

Displays

Peer IP

IP address of communication partner

Peer Status

Status of Peers, either Run or Idle.


If peer does not provide run idle information, nothing can be displayed!

Connection Type

Displays the Connection Type, Originator or Target, that the controller acts as in this connection.

Connection State

The status of connection.


1 = Connecting Configuring In the process of opening a new connection.
2 = Spare
3 = ConnectionEstablished Connection is active.
4 = ConnectionTimedOut Connection has timed out; will stay in this state at least for some time if
WatchdogTimeoutAction is set to TimeoutManualReset or TimeoutDelayAutoReset.
5 = ConnectionDeferredDelete Connection is about to be deleted and waiting for child connections to be
closed first.
6 = ConnectionClosing In the process of closing the connection.

Input

Associated input assembly Id with the connection or 0 if none. For scanner connections of the controller these field
shows the assembly id data is read from.

Output

Associated output assembly id with the connection or 0 if none. For scanner connections of the controller these
field shows the assembly id data is written to.

Sent

Number of sent packets on this connection.


Counter wraps with 232 packets.

Received

Number of received packets on this connection.


Counter wraps with 232 packets.

Bad Messages

Number of received or dropped messages for that connection. You can reset this value by pressing Counter Reset.

PRPI

Produced Requested Packet Interval (s).

CRPI

Consumed Requested Packet Interval (s).

MinPITime

Minimum Packet Interval Time (s).

MaxPITime

Maximum Packet Interval Time (s).

LastPITime

Last Packet Interval Time (s).

AvrPITime

Average Packet Interval Time (s).

Publication 1753-UM001C-EN-P - March 2010

131

Chapter 14

Use the Control Panel to Monitor Status

Use the Multi Control Panel

The Multi Control Panel lets you connect the programming terminal to
more than one controller in the project in one window and to perform
actions such as downloads, controller starts, invoking the force editor,
and so forth simultaneously.
1. Open the Multi Control Panel by choosing Online>Multi Control
Panel.
When the Multi Control Panel is opened for the first time, it does
not contain any controllers.
2. Add a controller to the Multi Control Panel by dragging and
dropping the Resource from the project tree into the Multi
Control Panel.

After a controller has been dropped in the Multi Control Panel,


the Login dialog box opens.
3. Type the correct Username and Password to connect the
controller to the programming terminal.
You must have Read/Write or Administrator rights (Access type)
to download a routine into the controller.
4. Add as many controllers to the Multi Control Panel as you need.
5. Sort the list of controllers in the Multi Control Panel by clicking
on the column headlines.

132

Publication 1753-UM001C-EN-P - March 2010

Use the Control Panel to Monitor Status

Chapter 14

The Multi Control Panel displays this controller information.

This field

Displays

Name

the controller name

System.Rack

the controller ID

CPU State

the status of the controller CPU, such as Run, Stop, Stop/Valid


Configuration, Stop/Invalid Configuration, and so forth.

CPU Configuration
CRC

the checksum (cyclic redundancy check) of the CPU configuration,


displayed in hexadecimal.

Avg. Cycle Time

the average CPU cycle time in milliseconds. This figure depends


on the complexity of the logic and, because of the Schedule Time
Slice, on the network load.

Rem. Force Time

the remaining force time in seconds (time until forcing is


deactivated). Value is 0 when forcing is not active or disabled.

Faulty I/O Modules

the number of faulty IO modules. A fault can result from a


hardware malfunction or from incorrect configuration.

Action

the display of a Multi Control Panel command and command


status (for example, Start, Start:OK). The field is cleared after five
seconds.

You can perform a Multi Control Panel command on one or more


controllers. To select a single controller, follow these steps.
1. Click the line number left of the controller name.
The boundaries of this line become thicker.
2. Select more controllers by using one of the following methods:
Hold down the CTRL key and click another line number to
add that controller to your selection.
Use the SHIFT key to select controllers from line x to line y.
To select all the controllers, click Select All
bar.

Publication 1753-UM001C-EN-P - March 2010

on the tool

133

Chapter 14

Use the Control Panel to Monitor Status

These commands can be carried out by using the Multi Control Panel
buttons in the button bar.
Multi Control Panel Buttons
Button

Command
Connect
Connects the programming software to the selected controller(s) after loss of communication or manual
disconnect.
After manual disconnect, a new login with password is required.
Disconnect
Disconnects the programming software from the selected controller(s).
Coldstart
Performs a coldstart on the selected controller(s).
Stop
Stops the selected controller(s).
Download
Loads the routine(s) into the selected controller(s). Prior to download, the code generator must have successfully
generated program code and the selected controller(s) must be in Stop mode.
Important: You cannot download a routine into a controller other than the one for which the logic was created.
Control Panel
Starts the control panel for the selected controller(s). This command can be carried out for a single controller by
choosing Online>Control Panel.
Diagnostics
Starts the diagnostics display for the selected controller(s). This command can be carried out for a single
controller by choosing Online>Diagnostics.
Force Editor
Starts the force editor for the selected controller(s). This command can be carried out for a single controller by
choosing Online>Force Editor.
Select All
Selects all controllers in the list.
Deselect
Deselects marked controllers.
Remove Controller
Removes the selected controller(s) from the list. Removing a controller from the Multi Control Panel also
disconnects the communication.

134

Publication 1753-UM001C-EN-P - March 2010

Use the Control Panel to Monitor Status

Control Panel Resource


Menu

Chapter 14

To modify the safety settings of the controller, choose Safety from the
control panels Resource menu .

IMPORTANT

Any settings you change via the Resource menu are directly
updated in the controller and are saved in the project.

Menu Item

Description

Check Consistency

Compares the program running in the controller with the program you are editing in
RSLogix Guard PLUS! software. If they match, your offline project has previously been
downloaded to the GuardPLC controller.

Set Main Enable

Lets safety parameters be changed. You can only choose Set Main Enable when the
controller is in Stop mode.
For more information, see page 119.

Reset Main Enable

Prevents safety parameters from being changed.


For more information, see page 119.

Change Safety Parameters

Changes the safety parameters, if Set Main Enable is activated.


You must have Read/Write or Administrator access to be able to change safety
parameters.
For more information about these parameters, see page 119.

TIP

Publication 1753-UM001C-EN-P - March 2010

Refer to the Using RSLogix Guard PLUS! Software with


GuardPLC Controllers Programming Manual, publication
1753-PM001, for more information on the Warmstart, Coldstart,
Stop, and Download menu items.

135

Chapter 14

Use the Control Panel to Monitor Status

Control Panel Extra Menu

Use the Extra menu of the Control Panel to modify communication


settings and change controller operation. You must have
Administrator access to use most of these menu options as indicated
in the table below.

Menu Item

Description

Set Date/Time

Sets the controller clock, if Set Main Enable is activated.


Enter the date as mm/dd/yy and the time as hh:mm.

Change System ID (SRS)

Changes the system ID (SRS) of the controller.


You must have Administrator access to be able to change the system ID (SRS).

Device Settings

Changes the Ethernet network parameters.


You must have Administrator access and the controller must be in STOP mode.

Update OS

Lets you download new COM OS and CPU OS.

Reboot Resource

Reboots the controller.


See Recover From a Failure_Stop on page 116.

Load Resource Configuration from


Flash

Loads a copy of the last executable configuration to the controller

Clear Resource Configuration

Deletes the program memory of the controller and resets the configuration of the CPU and COM
modules.
GuardPLC 1200 and 2000 controllers only: Deletes the program memory of the controller and
resets the configuration of the CPU and COM modules.
This does not affect the battery-buffered memory for long term diagnostics, short term
diagnostics, date and time settings, system ID (SRS), or IP address.
To reset a controller to default settings, clear the controller and remove the back-up battery for at
least 20 seconds. Removing the back-up battery:

deletes date and time.


deletes long term and short term diagnosis.
deletes the configuration saved in the battery-buffered memory.
deletes all user accounts.
does not delete the program memory.
does not reset the configuration of the CPU and COM modules.

Use Online>Communication Settings and write the SRS back to the battery-buffered memory. This
validates the configuration so you can restart the routine.

136

Publication 1753-UM001C-EN-P - March 2010

Use the Control Panel to Monitor Status

Menu Item

Description

Set Backplane Type

Restores backplane information.

Chapter 14

The individual modules (CPU, COM, I/O) are linked to each other over the backplane. The controller
requires this information to be able to conduct hardware tests. If the EEPROM that stores the
backplane information loses its contents, use this menu option to write the backplane type back
into the EEPROM.
You must have Administrator access to be able to set the backplane type.
To set the backplane type, follow these steps.
1. Load a project that is consistent with the connected controller type.
ATTENTION: If you try to write the backplane type of a controller (such as a GuardPLC 1200
controller) with the backplane type of another controller (such as a GuardPLC 2000
controller), the overwritten controller can no longer be used and must be repaired by the
manufacturer.
2. Choose Set Backplane Type.
The backplane type is automatically entered into the dialog box.
3. Change the Backplane Version to 0.
4. Click OK to confirm the change.

Publication 1753-UM001C-EN-P - March 2010

137

Chapter 14

Use the Control Panel to Monitor Status

Notes:

138

Publication 1753-UM001C-EN-P - March 2010

Chapter

15

Diagnostics

Introduction

View Controller
Diagnostics

Topic

Page

View Controller Diagnostics

139

GuardPLC 1200 Controller Status Indicators

142

GuardPLC 1600 and GuardPLC 1800 Controllers and GuardPLC


Distributed I/O

143

GuardPLC 2000 Controller Status Indicators

145

1755-IB24XOB16 Module Status Indicators

147

1755-IF8 Analog Input Module Status Indicators

148

1755-OF8 Analog Output Module Status Indicators

149

1755-HSC Combination High-speed Counter and Output Module Status


Indicators

149

The controller stores short term and long term diagnostics data. The
number of entries the controller can save depends on the controller,
as shown below.
Type of Data

GuardPLC 1200

GuardPLC 1600 and 1800

GuardPLC 2000

CPU

COM

CPU

COM

CPU

COM

number of short
term entries

300

700

300

700

300

700

number of long
term entries

1000

200

1000

200

1000

200

If the memory for short term entries is full and the controller needs to
log another entry, the controller deletes the oldest entry.
If the memory for the long term entries is full and the controller needs
to add a new entry, the controller deletes the oldest entry only if that
entry is more than 7 days old. Otherwise, the new entry is rejected
and a message is displayed in the diagnostics window.

139Publication 1753-UM001C-EN-P - March 2010

139

Chapter 15

Diagnostics

To display the diagnostics window, follow these steps.


1. Select the Resource and, from the Online menu, choose
Diagnostics.
If the Control Panel is already open, you do not have to login.
Otherwise, the software asks you to log in.

2. After you successfully log in, the software displays the controller
diagnostics.

This field

Displays

Level

whether the entry is Info, Warning, or Error.

Date

the date and time the entry was recorded.

Text

a description of the cause leading to the entry.

Origin

whether the cause of entry originated from the CPU or COM.

Type

whether the entry is short term (ST) or long term (LT).

Parameter

information direct from the CPU or COM. This data is only for error analysis by Rockwell
Automation representatives.

TIP

140

You can export diagnostic data to a text file for storage by


choosing Export from the Diagnostic menu.
Publication 1753-UM001C-EN-P - March 2010

Diagnostics

Chapter 15

Choose Online or Offline Diagnostics


When you start the diagnostics window, Diag. Online is automatically
activated. This signals that you want all diagnostics data transferred
from the controller to the diagnostics buffer in RSLogix Guard PLUS!
software. As long as Diag. Online is active, new diagnostic data is
transferred to this buffer as it becomes available and if the filter you
selected applies.
Diag. Offline disconnects communication with the controller. This
ends the transmission of diagnostic data from the controller to the
diagnostics buffer in RSLogix Guard PLUS! software.

Filtering Diagnostic Data


Choose from these filters to determine what diagnostic data to display.
Filter

Description

Start At Oldest Entry

Displays all the data from the RSLogix Guard PLUS! software buffer starting with the
oldest entry.
The number of lines shown in the table depends on the Entries Per Diag. Enable Sorting
defaults to disabled so that the data appears in chronological order from oldest to newest.

Start At Newest Entry

Displays all the data from the RSLogix Guard PLUS! software buffer starting with the
newest entry.
The number of lines shown in the table depends on the Entries Per Diag. Enable Sorting
defaults to disabled so that the data appears in chronological order from oldest to newest.

Start At Date

Displays entries in chronological order starting at this date and time.


The number of lines shown in the table depends on the Entries Per Diag.
Enter the date as mm/dd/yy and the time as hh:mm.

Stop At Date

Displays entries in chronological order ending at this date and time.


The number of lines shown in the table depends on the Entries Per Diag.
Enter the date as mm/dd/yy and the time as hh:mm.

Entries Per Diag.

Determines the maximum number of entries to load into the buffer for the CPU and COM
diagnostics.
For example, if you enable short term and long term diagnostics for CPU and COM and you
set Entries Per Diag. = 10, the diagnostic window contains a maximum of 40 entries
(10 entries per diagnostic type).
RSLogix Guard PLUS! software can buffer as many as 5000 entries per type of diagnostic.

Sort

If Sort is disabled, the diagnostic window displays entries in the order they were saved in
the controller.
If Sort is enabled, the diagnostic window automatically displays entries according to date.

CPU Short Term Diagnostic


CPU Long Term Diagnostic

Enables or disables whether to display the diagnostic data for each type.

COM Short Term Diagnostic


COM Long Term Diagnostic

Publication 1753-UM001C-EN-P - March 2010

141

Chapter 15

Diagnostics

GuardPLC 1200 Controller


Status Indicators

The GuardPLC 1200 controller has these status indicators.


PLC
1200

Indicator

State

Description

INput

On

Digital input channels are high (10 30V DC).

Off

Digital input channels are off.

On

Digital output channels are high.

Off

Digital output channels are off.

On

This is the normal status of the controller.

OUTput
RUN

A routine, which has been loaded into the controller, is executed. The controller processes input
and output signals, carries out communication, and performs hardware and software tests.
Flashing

The controller is in Stop mode and is not executing a routine.


All system outputs are reset.
Stop mode can be triggered by setting the system variable AB-CPU/Emergency Stop to TRUE in
the routine, or by direct command from the programming terminal.

Off
ERROR

On

The controller is in Failure_Stop (see ERROR).


A hardware error has been detected by the controller. In this case the controller goes to
Failure_Stop and the execution of the routine is halted. Hardware errors are errors in the
controller, in one or more of the digital input and output modules, or in the counters.
A software error in the operating system has been detected by the controller.
The watchdog has reported an error because of exceeded cycle time.
All system outputs will be reset and the controller ceases all hardware and software tests. The
controller can only be restarted by a command from the programming terminal.

PROGress

FORCE

142

Flashing

If all the status indicators are on and ERROR blinks, the boot loader detected a corrupted
operating system and is waiting for an operating system download.

Off

No errors are detected.

On

The upload of a new controller configuration is in progress.

Flashing

The upload of a new operating system into the Flash ROM is in progress.

Off

No upload of controller configuration or operating system is in progress.

On

The controller is executing a routine (Run) and Force mode is activated by the user.

Flashing

The controller is in Stop mode, but forcing has been saved and will be activated when the
controller is started.

Off

Forcing is off.

Publication 1753-UM001C-EN-P - March 2010

Diagnostics

Indicator

State

Description

FAULT

On

The routine logic has caused an error.

Chapter 15

The controller configuration is faulty.


The upload of a new operating system was not successful and the operating system is corrupted.
Flashing

An error has occurred during a Flash ROM write cycle.


One or more I/O errors have occurred.

COMMunication

Off

None of the above errors have been detected.

On

The programming terminal, with Administrator or Read/Write access, is communicating with the
controller via an Ethernet link.

Off

No communication or read-only communication on an Ethernet link.

GuardPLC 1600 and


GuardPLC 1800 Controllers
and GuardPLC Distributed
I/O

System Status Indicators


24V DC
RUN
ERROR
PROG
FORCE
FAULT
OSL
BL

Indicator

State

Description

24V DC

On

24V DC operating voltage present.

Off

No operating voltage.

On

This is the normal status of the controller.


A routine, which has been loaded into the controller, is executed.
The controller processes input and output signals, carries out communication and performs hardware
and software tests.

Flashing

The controller is in Stop mode and is not executing a routine.


All system outputs are reset.
Stop mode can be triggered by setting the Emergency stop system variable to TRUE in the routine, or
by direct command from the programming software.

Off

The controller is in Failure_Stop (see ERROR).

On

A hardware error has been detected by the controller. The controller goes to Failure_Stop and the
execution of the routine is halted. Hardware errors are errors in the controller, errors in one or more of
the digital input and output modules, or errors in the counters.

RUN

ERROR

A software error in the operating system has been detected by the controller.
The watchdog has reported an error due to exceeded cycle time.
All system outputs will be reset and the controller ceases all hardware and software tests. The
controller can only be restarted by a command from the programming software.
Off

No errors are detected.

Publication 1753-UM001C-EN-P - March 2010

143

Chapter 15

Diagnostics

Indicator

State

Description

PROGress

On

The upload of a new controller configuration is in progress.

Flashing

The upload of a new operating system into the Flash ROM is in progress.

FORCE

FAULT

Off

No upload of controller configuration or operating system in progress.

On

The controller is executing a routine (Run) and Force mode is activated by the user.

Flashing

The controller is in Stop, but Forcing has been initiated and will be activated when the controller is
started.

Off

Forcing is OFF.

On

The routine (logic) has caused an error.


The controller configuration is faulty.
The upload of a new operating system was not successful and the operating system is corrupted.

Flashing

An error has occurred during a Flash ROM write cycle.


One or more I/O errors have occurred.

Off

None of the above errors has occurred.

OSL

Flashing

Emergency Operating System Loader is active.

BL

Flashing

Boot Loader unable to load operating system or unable to start COMM operating system loader.

Communication Status Indicators


Status indicators on the controllers and I/O modules display
communication status information.

Safety-related GuardPLC Ethernet Communication


Communication via the GuardPLC Ethernet network is indicated via
two small status indicators integrated into each RJ-45 connector
socket.
Indicator

State

Description

Green

On

Full duplex operation

Flashing

Collision

Off

Half duplex operation, no collision

On

Connection established

Flashing

Interface activity

Yellow

Non-safety-related Communication
Active communication via the serial ports, COMM1 and COMM3, is
indicated by a status indicator located above the port.

144

Publication 1753-UM001C-EN-P - March 2010

Diagnostics

GuardPLC 2000 Controller


Status Indicators

Chapter 15

The GuardPLC 2000 controller has status indicators for:

module, both the program and the communication.


controller and the system hardware.
routine.
Ethernet communication to the programming terminal.

Controller Indicators

1755L1

Indicator Status

Description

RUN

This is the normal status of the controller (Run or Stop mode).


The controller carries out communication and performs software
tests.

RUN ERR

RUN STOP
PROG FAULT

On

ERR

Flashing

Downloading an Operating System

Off

The controller is in Failure_Stop (see ERR below), or there is no


power supply.

On

The controller is in the Failure_Stop state and the execution of


the routine is halted. All system outputs will be reset and the
controller ceases all hardware and software tests.

FORCE

The operating system loader has found a flash error (FAULT is


blinking).
Tx COL

Flashing

The boot loader has found an error in the operating system in the
flash (if all other indicators are ON); the download of a new
operating system is awaited.

Off

No errors are detected.

10/100BaseT

Publication 1753-UM001C-EN-P - March 2010

145

Chapter 15

Diagnostics

Routine Indicators

1755L1
RUN ERR

RUN STOP

Indicator

Status

Description

RUN

On

The routine is in Run or Freeze.

Off

The routine is in Failure_Stop.

STOP

On

The routine is in Stop or Failure_Stop.

PROG

On

The download of a new controller configuration is in progress.

Flashing

The download of a new operating system into the flash ROM is in


progress.

Off

No download of controller configuration or operating system is in


progress.

On

The routine (user program) has caused an error.

PROG FAULT
FORCE

FAULT

The controller configuration is faulty.

Tx COL

The download of a new operating system was not successful and


the operating system is corrupted.
Flashing
10/100BaseT

An error has occurred during a flash ROM write cycle of the


operating system.
At least one I/O module error is present.

FORCE

Off

No errors have been detected.

On

The controller is executing a routine (RUN) and one or more


inputs and/or outputs may be forced by the user.

Flashing

The controller is in Stop mode, but one or more inputs and/or


outputs have been prepared for forcing and will be activated as
soon as the controller is started.

Off

No inputs and/or outputs are forced or are prepared to be forced.

Ethernet Communication Indicators


Tx COL

Indicator

Status

Description

Tx

On

Data is transmitting via the Ethernet network by the


communication processor.

COL

On

A collision on the Ethernet network is detected.

10/100 Base T

146

Publication 1753-UM001C-EN-P - March 2010

Diagnostics

Chapter 15

Serial Communication Indicators


Indicator Status

Description

FB1

On

Field bus no. 1 is active

FB2

On

Field bus no. 2 is active


(serial interface module)

FB1
FB2

IMPORTANT

1755-IB24XOB16 Module
Status Indicators

The 1755-IB24XOB16 digital combination input and output module


(AB-DIO) has status indicators for:
power supply.
module status.
I/O status.

RUN ERR

1755IB24XOB16

RUN ERR

1
2
3
4
5
6
7
8
9

Only the bottom serial port on the GuardPLC 2000 controller is


active, as indicated by the FB2 status indicator.

LS+
I1
I2
I3
I4
I5
I6
I7
I8

Power Supply and Module Status


Indicator

Status

Description

RUN

On (green)

The module has the correct operating voltage (24V DC).

Off

The module has no power.

On (red)

If the system is in Stop mode, one or more of the inputs or


outputs is faulty, or the module is faulty.

ERR

Use the RSLogix Guard PLUS! software to verify the location


of the fault. If the module is faulty, replace the module
immediately, or the safety-related operation of the
GuardPLC 2000 controller is not maintained.
Off

Publication 1753-UM001C-EN-P - March 2010

The module is operational.

147

Chapter 15

Diagnostics

I/O Status
Status

Explanation

On (yellow)

Input is high
Output is energized

Off

Input is low
Output is de-energized

While the system is in Run mode, ERR is indicated continuously for


both a module and a channel error. Depending on the type of error,
the module switches off only a faulty output channel, but the
operation of the other outputs continues, or all the output channels
are switched off. The inputs are always in operation. A faulty input
channel transmits Low-signal to the logic. If the entire module is
switched off, all input and output channels are switched off.

1755-IF8 Analog Input


Module Status Indicators

1755IF8

The 1755-IF8 analog input module (AB-AI) has status indicators for:
power supply.
module status.
Indicator

Status

Description

RUN

ON (green)

The module has the correct operating voltage (24V DC).

OFF

The module has no power.

ON (red)

If the system is in Stop mode, one or more of the inputs or


outputs is faulty, or the module is faulty.

RUN ERR

ERR

Use the RSLogix Guard PLUS! software to verify the location


of the fault. If the module is faulty, replace the module
immediately, or the safety-related operation of the
GuardPLC 2000 controller is not maintained.
OFF

The module is operational.

While the system is in Run mode, ERR is indicated continuously for


both a module and a input channel error. Depending on the type of
error, the module may switch off only one input channel (that is, a
faulty channel transmits the value 0 to the logic, but the module
continues operation with the remaining channels). If the entire
module is switched off, all input channels transmit the value 0 to the
logic.

148

Publication 1753-UM001C-EN-P - March 2010

Diagnostics

1755-OF8 Analog Output


Module Status Indicators

Chapter 15

The 1755-OF8 analog output module (AB-AO) has status indicators


for:
power supply.
module status.

1755OF8

Indicator

Status

Description

RUN

ON (green)

The module has the correct operating voltage (24V DC).

OFF

The module has no power.

ERR

ON (red)

If the system is in Stop mode, one or more of the inputs or


outputs is faulty or the module is faulty.

RUN ERR

Use the RSLogix Guard PLUS! software to verify the location


of the fault. If the module is faulty, replace the module
immediately or the safety-related operation of the
GuardPLC 2000 controller is not maintained.
OFF

The module is operational.

While the system is in RUN mode, ERR is indicated continuously for


both a module and an output channel error. Depending on the type of
error, the module may switch only one pair of output channels
(1+2, , 7+8) to the de-energized state (that is, the value 0V or 0 mA),
but the module continues operation with the remaining channels. If
the entire module is switched off, all output channels are switched to
the de-energized state.

1755-HSC Combination
High-speed Counter and
Output Module Status
Indicators

1755HSC

RUN ERR

19
20
21
22
23
24

The 1755-HSC combination high-speed counter and output module


(AB-CO) has status indicators for:
power supply.
module status.
I/O status.

L1
2
3
4
L-

Publication 1753-UM001C-EN-P - March 2010

149

Chapter 15

Diagnostics

Power Supply and Module Status


Indicator

Status

Description

RUN

On (green)

The module has the correct operating voltage (24V DC).

Off

The module has no power.

On (red)

If the system is in Stop mode, one or more of the inputs or


outputs is faulty or the module is faulty.

ERR

Use the RSLogix Guard PLUS! software to verify the location


of the fault. If the module is faulty, replace the module
immediately or the safety-related operation of the
GuardPLC 2000 controller is not maintained.
Off

The module is operational.

Indicator

Status

Description

1, 2, 3, 4

On (green)

The corresponding output is energized.

Off

The corresponding output is de-energized.

I/O Status

While the system is in Run mode, ERR is indicated continuously for


both a module and a counter channel error. Depending on the type of
error, the module may switch off only one counter channel (that is,
the counter transmits the value 0 to the logic, the output has no signal,
but the module continues operation with the remaining counter
channel). If the entire module is switched off, all counter channels are
switched off.

150

Publication 1753-UM001C-EN-P - March 2010

Chapter

16

Peer-to-peer Communication Overview

Introduction

Peer-to-peer
Communication Basics

Topic

Page

Peer-to-peer Communication Basics

151

Networking Limitations

152

Network Configuration

153

HH Protocol Parameters

153

Peer-to-peer Protocol Parameters

157

HH Network Profiles

161

Peer-to-Peer Network Profiles

168

Peer-to-peer communication is used for data exchange between two


or more controllers and distributed I/O on a GuardPLC Ethernet
network. The GuardPLC Ethernet network is certified for use in SIL 3
and Cat. 4 applications and is designed to carry safety-related data.
The controllers are usually connected via the Ethernet network, but
other means of communication, such as telephone lines or two-way
radios are also possible, using gateways from the Ethernet network to
the respective technology.
The Peer-to-peer protocol is primarily responsible for:
the communication between controller CPUs, including
automatic connection setup.
extended diagnostics.
all safety-relevant features for correct data transfer.
Each controller is equipped with one or more 10/100 Base T Ethernet
ports. The High-level High-speed (HH) protocol is implemented in the
operating system of the GuardPLC 1200/1600/1800 controllers and of
the GuardPLC 2000 communication module (COM) and interacts with
the Ethernet port. The HH protocol is based on UDP/IP and IEEE
802.3 standards and is responsible for the collision-free data exchange
via standard Ethernet networks in various network topologies.

151Publication 1753-UM001C-EN-P - March 2010

151

Chapter 16

Peer-to-peer Communication Overview

As seen in the figure below, both the HH and the peer-to-peer


protocols are vital for safe Ethernet Communication. HH protocol can
be considered the wire or transport media through which messages
are passed. Peer-to-peer (P2P) is the protocol that runs on the wire,
making sure that the messages are transmitted over the HH
connection within the watchdog time. P2P is the mechanism that
qualifies the GuardPLC Ethernet network as a safety network.

Controller 1

Controller 2

CPU

P2P

P2P

COM

HH

HH

Ethernet
TIP

Networking Limitations

The peer-to-peer protocol is designated as a safe protocol


according to DIN V 19250 (AK6), IEC61508 (SIL 3) and
ISO 13849-1 (PLe/Cat. 4) respectively.

A peer-to-peer link is defined as communication from one GuardPLC


controller to another GuardPLC controller, or from a GuardPLC
controller to a distributed I/O module. A device on an Ethernet
network must make a connection to another device on the Ethernet
network for the two of them to communicate. Connections need to be
established only between devices that wish to communicate with each
other.
A single GuardPLC controller may have up to 64 connections to other
devices on the GuardPLC Ethernet network (GuardPLC controllers,
GuardPLC distributed I/O module, OPC servers, or programming
terminals). Each connection can transfer up to 900 bytes of data in
each direction (read and write). The data size is determined by the
number of signals transferred between the devices.
In contrast, a GuardPLC distributed I/O module can have only one
connection, the connection to the controller that owns it. The amount
of data shared between a distributed I/O module and the controller is
fixed and defined by the type of I/O module.
The total number of controllers, distributed I/O module, OPC servers,
and programming terminals on a network is limited only by the
number of available IP addresses and the network bandwidth
(maximum 100 Mbps) of a segment of the network. However, large
amounts of data flowing on the network will affect the network
response time, and therefore the safety time of the system.

152

Publication 1753-UM001C-EN-P - March 2010

Peer-to-peer Communication Overview

Network Configuration

Chapter 16

Communication between GuardPLC controllers can be established via


different kinds of Ethernet topologies. Both the HH protocol and the
peer-to-peer protocol can be adapted to the network in use, to allow
smooth and efficient data transfer.
You configure the HH protocol and the peer-to-peer protocol by
setting parameters, either manually or with the help of network
profiles. Network profiles are preset combinations of parameters you
can choose to make configuration simpler.
To optimize data transfer and customize the configuration, you must
have an extensive knowledge of the network in use and the operation
of the parameters. The following sections summarize the most
important HH and peer-to-peer protocol parameters.

HH Protocol Parameters

The HH protocol parameters are displayed in the HH Network/Token


Group dialog box. They can be preset by choosing one of two
profiles.
Fast
Medium
The profiles are explained in HH Network Profiles on page 161.
TIP

Publication 1753-UM001C-EN-P - March 2010

While manual changes to the parameters are possible by


choosing the None profile, keep in mind that ill-considered
changes can disable communication completely.

153

Chapter 16

Peer-to-peer Communication Overview

Token Group ID
The Token Group ID is the numerical identifier for a token group.
Each token group must have its unique Token Group ID.

Protocol Mode
Choose either Normal or RAW protocol mode.

Normal
In Normal mode, software token passing is ON, meaning that access
to the Ethernet network is controlled via token passing. Only the
controller that holds the token is allowed to access the network.
This mode is recommended for networks with slow hubs to avoid
message collisions.

RAW
In RAW mode, software token passing is OFF. No token is created.
Ethernet access is coordinated by hardware only. The affiliated Link
Mode is TCS direct.

154

Publication 1753-UM001C-EN-P - March 2010

Peer-to-peer Communication Overview

Chapter 16

Data transfer is faster than in Normal Mode and message collisions are
prevented by the switching and full-duplex mode ports.
This mode is recommended for networks, where full-duplex
(recommended) LAN-switches are used exclusively, or the switches
integrated into the GuardPLC 1600 and 1800 controllers can be used.

Link Mode
Choose either TCS Direct or TCS TOKCYC.

TCS Direct
In TCS Direct mode, safety-related data are sent as soon as they are
prepared for transmission. Network media access is coordinated by
hardware.

TCS TOKCYC
This link mode corresponds to Normal protocol mode. Safety-related
data is sent when the controller receives the token. Network media
access is coordinated by software.

Response Time
Response Time is the controllers maximum permissible Response
Time for a network message. PES1 (Programmable Electronic System1)
sends a message to PES2 and expects the answer within the Response
Timeout.
The actual values of the ResponseTime can be read in the HH Status
of the Control Panel.

Token Cycle Time


This is the maximum permissible time for one token cycle. In other
words, the time within which a controller expects the token.

Publication 1753-UM001C-EN-P - March 2010

155

Chapter 16

Peer-to-peer Communication Overview

The Token Cycle Time depends on the number of controllers in a


token group and can be read on the HH Status tab of the Control
Panel.

Token Alive Timeout


The current holder of the token must send a token alive message to
the Primary(1) controller within this time period or the Primary
assumes the token is bad. If the token alive message is missing, a new
token is created by the Primary.

Primary Timeout
Time, within which the Primary expects a check for liveliness from the
Secondary(2) controller. If the liveliness check fails to appear, the
Primary assumes that the present Secondary is disconnected. In this
case, the Primary selects a new Secondary.

Secondary Interval
Time, after which the Secondary checks the Primary for liveliness. The
Secondary Interval is less than the Primary Timeout.

Link Mode (Extern)


Same as Link Mode above, except for the connection is to a controller
in another Token Group.

Response Time (Extern)


Same as Response Timeout above, except for the connection is to a
controller in another token group.
(1) The Primary is the controller that generates and supervises the token.
(2) The Secondary is a controller in the same token group as the Primary. The Secondary supervises the Primary.

156

Publication 1753-UM001C-EN-P - March 2010

Peer-to-peer Communication Overview

Peer-to-peer Protocol
Parameters

Chapter 16

All peer-to-peer protocol parameters are displayed in the Peer-to-Peer


Editor. With the exception of the ResponseTime and the ReceiveTMO,
which have to be configured by the user, all other peer-to-peer
protocol parameters are automatically preset with the selection of a
peer-to-peer profile. See Configure Peer-to-peer Communication on
page 184 for detailed instructions on how to configure the
peer-to-peer protocol.

Message Response Time (ReponseTime)


ResponseTime is the user-configurable time it takes to receive an
acknowledgement of a sent message from the recipient.
The ResponseTime is not a freely configurable parameter, but results
from the physical conditions of the communication path and the
configuration of the network protocol.
Because the ResponseTime influences the speed of message
exchange, a test run is recommended to investigate network timing.
Use the P2P Status tab, in the Control Panel to display the minimum,
maximum, and average ResponseTime.

Publication 1753-UM001C-EN-P - March 2010

157

Chapter 16

Peer-to-peer Communication Overview

The ResponseTime is the sum of the following variables, described in


the table below.
ResponseTime = TGR1 + T1 + TGR2 + T3+ T2
Response Time Variables
Variable

Definition

TGR1

Message delay between two PES:


CPU1 COM1 network COM2 CPU2

T1

Time on CPU2 to process all protocol stacks:


T1 = CycleTime(CPU2) x n2
where n2 is the number of cycles needed on CPU2 to process all protocol
stacks. Set the Communication Time Slice (see below) large enough to allow
all protocol stacks to be processed in one cycle.

T2

Delay of the acknowledgement on CPU2:


T2 = AckTMO + n2 x [0 CycleTime(CPU2)]
If AckTMO = 0 or ProdRate = 0, then T2 = 0

TGR2

Message delay between two PES:


CPU2 COM2 network COM1 CPU1
(usually identical with TGR1)

T3

Time on CPU1 to process all protocol stacks:


T3 = CycleTime(CPU1) x n1
where n1 is the number of cycles needed on CPU1 to process all protocol
stacks. Set Communication Time Slice (see page 176) large enough to allow
all protocol stacks to be processed in one cycle.

Receive Timeout (ReceiveTMO)


ReceiveTMO is the safety-related, user-configurable monitoring time,
within which PES1 must receive a correct response from PES2.
TIP

ReceiveTMO is also valid for the return path from PES2 to PES1.

If ReceiveTMO elapses, safety-related communication closes down


and all imported (via communication) safety-related tags reset to their
user-configurable initial values.
If the ReceiveTMO 2 x ResponseTime(minimum), the loss of at least
one message can be handled without losing the Peer-to-Peer
connection.
158

Publication 1753-UM001C-EN-P - March 2010

Peer-to-peer Communication Overview

Chapter 16

If the Receive]TMO is not 2 x ResponseTime (minimum), the


availability of the Peer-to-Peer connection is guaranteed only in a
collision- and noise-free network. However, this does not result in a
safety problem for the CPU.
TIP

The maximum permissible value for ReceiveTMO depends upon


the application and is set in the Peer-to-Peer Editor along with
the expected maximum ResponseTime and the profile.

Resend Timeout (ResendTMO)


Resend Timeout is the safety-related monitoring time of PES1. If the
receipt of a data transmission is not confirmed by PES2 within this
time period (ResendTMO), PES1 repeats the data transmission.

Acknowledge Timeout (AckTMO)


Reception of data must be confirmed by the CPU with an ACK
(acknowledge) message to the sender of the data. If the CPU is busy,
ACK is delayed. Acknowledge Timeout is the maximum delay an ACK
message may have.
The AckTMO cannot be entered manually, but is set in conjunction
with a profile in the Peer-to-Peer Editor. For fast networks, AckTMO is
zero.

Queue Length (QueueLen)


QueueLen describes the number of messages that may be transmitted
without having to wait for an acknowledgement. It corresponds to the
network bandwidth and delay.
QueueLen cannot be entered manually, but is set along with a profile
in the Peer-to-Peer Editor.

Publication 1753-UM001C-EN-P - March 2010

159

Chapter 16

Peer-to-peer Communication Overview

Production Rate (ProdRate)


ProdRate is the minimum time interval between two data messages.
The purpose of ProdRate is to limit the amount of data to a magnitude
that can be transported to the recipient without overloading a (slow)
communication channel. This results in an even load on the
communication channel and avoids the reception of outdated data.
TIP

A production rate of 0 means that a data message can be


transmitted with each cycle of the user program.

Watchdog Time (WDZ)


Watchdog Time is the maximum permissible duration of a Run cycle
on a PES. The Run cycle depends upon the complexity of the user
program and the number of peer-to-peer connections.

Worst-case Reaction Time (TR)


Worst-case Reaction Time is a safety-relevant application parameter. It
is the time between the occurrence of a physical input signal change
at PES1 and the corresponding physical output signal change at PES2.
Worst-case Reaction Time (TR) t1 + t2 + t3 + t4
Worst-case Reaction Time Variables
Variable

Definition

t1

The worst-case time for the user program on PES1 to process the input
signal and prepare the data for transmission.
2 x WDZ (PES1)

t2

The additional transmission delay on PES1.


Equals 0 ms, if the ProdRate is 0.
Otherwise: equals ReceiveTMO + WDZ (PES1)

t3

ReceiveTMO
The maximum age of a message when received at PES2.

t4

160

The maximum time for the received data message to be processed by the
user program on PES2 and the output signal to be set.

Publication 1753-UM001C-EN-P - March 2010

Peer-to-peer Communication Overview

Chapter 16

The Worst-case ReactionTime TR is process-dependent and has to be


coordinated with the approving board. In the Peer-to-Peer Editor, the
Worst-case ReactionTime can be read in the Worst Case column.

HH Network Profiles

Two HH network profiles are used to configure the appropriate set of


parameters for the network in use. The profiles, described below, can
be chosen in the properties of the HH Network token group.
Profile I: Fast
Profile II: Medium
A third profile option, None, lets you set parameters manually. See
The None Profile on page 167 for more information.

Profile I: Fast
This is the recommended profile. It provides the fastest data
throughput, and covers approximately 95% of all application cases.
Use Fast for:
applications that require fast data update rates within a token
group(1).
fast communication between two or more token groups(1),
where the other token groups must run Fast as well.
applications that require the shortest feasible Worst-case
Reaction Time.
TIP

Because Token Passing is switched off in the Fast profile, it is


possible to generate a token group with only one controller. No
second controller is needed to exchange the token. The single
controller can communicate with other token groups containing
more controllers.

(1) A token group consists of at least two controllers, which share the same token. Each controller must be a
member of exactly one token group. A token group can work stand-alone or can exchange data with other token
groups.

Publication 1753-UM001C-EN-P - March 2010

161

Chapter 16

Peer-to-peer Communication Overview

The minimum network requirements are outlined this table.


Minimum Ethernet Network Requirements for Profile I
Requirement

Definition

Fast

100 Mbps technology (100-Base TX)

Switched

Fast Ethernet (full-duplex recommended) LAN switches or integrated


switches (GuardPLC 1600/1800 controller) required.

Cleanroom

No loss of data due to traffic overload, harsh environmental


conditions, or network defects.

TIP

162

The network can be shared with other applications, if sufficient


bandwidth is provided.

Publication 1753-UM001C-EN-P - March 2010

Peer-to-peer Communication Overview

Chapter 16

Example of HH Network Profile I Topology

Token Group 1
GuardPLC 2000

GuardPLC 2000

GuardPLC
2000
Controllers

GuardPLC 1200
Controller

GuardPLC 1200
Controller

GuardPLC 1200
Controller

GuardPLC 2000
Controller
GuardPLC 2000

Token Group 2
GuardPLC 1600 Controllers with
Integrated Ethernet Switch

Controllers
GuardPLC 1200
Controller

100 Mbps
LAN Switch

GuardPLC 1800 Controller with


Integrated Ethernet Switch

Fiber Optic Cable

Programming Terminal

Twisted Pair Cable, max 100 m

Buffer Amp

Token Group 3
GuardPLC 2000

GuardPLC 1800 Controller with


Integrated Ethernet Switch
GuardPLC 1200
controller

GuardPLC 2000 Controller


GuardPLC 1200
Controller

Buffer Amp
Backbone
GuardPLC 1600 Controller with
Integrated Ethernet Switch
100 Mbps LAN Switch

Publication 1753-UM001C-EN-P - March 2010

163

Chapter 16

Peer-to-peer Communication Overview

Profile II: Medium


This profile provides medium-speed data throughput and covers
approximately 4% of all application cases. It is appropriate for
applications where timing is not a critical factor. With the Medium
profile, network media access within a token group and
communication with external token groups is controlled by token
passing. These external token groups must also run Medium profiles.

IMPORTANT

In the Medium profile, a token group must be comprised of at


least two controllers to carry out token passing, otherwise the
controller configuration is erroneous. (Stop/Invalid
Configuration).

Minimum Ethernet Network Requirements for Medium & Cleanroom


Requirement

Definition

Medium

10 Mbps technology (10-Base T)


Hubs are used within the token groups and LAN switches connect one
token group to another.

Clean

IMPORTANT

No loss of data due to traffic overload, harsh environmental


conditions, or network defects.

The network must not be shared with other applications. Do not


use more than one programming terminal (recommended).
programming terminals increase network traffic, but do not
participate in token passing.

Using LAN Switches and Hubs


When using a hub instead of a LAN switch to interconnect two or
more controllers of the same token group, network access within the
token group is no longer conducted by the hardware, but must be
managed by token passing.

164

Publication 1753-UM001C-EN-P - March 2010

Peer-to-peer Communication Overview

Chapter 16

Each token group handles its token passing individually, depending


on user settings, CPU cycle times, network topology, and so forth.
This means that for two (or more) token groups, which are
exchanging data, Token passing is not synchronized, resulting in a
loss of messages between the Token Groups.
IMPORTANT

To minimize loss of messages, only one controller in a token


group is allowed to exchange data with exactly one controller
in a second token group. Furthermore, the overall number of
links between token groups is limited to eight.

Token Group 1
GuardPLC 2000

Token Group 2
GuardPLC 2000

GuardPLC 2000

GuardPLC
2000
Controllers

GuardPLC 1200
Controller

GuardPLC 1200
Controller

GuardPLC 1600 Controllers with


Integrated Ethernet Switch

GuardPLC 2000
Controller

GuardPLC 1200
Controller

GuardPLC 1200
Controller

GuardPLC 1800 Controller with


Integrated Ethernet Switch
Programming Terminal
10 Mbps Hub

10 Mbps Switch

The illustration above shows an application, consisting of two token


groups. The token groups equipped with hubs require token passing
to coordinate network access within the token groups. The token
groups are interconnected via a LAN switch.

Publication 1753-UM001C-EN-P - March 2010

165

Chapter 16

Peer-to-peer Communication Overview

In this network topology, only one controller in Token Group 1 is


allowed to exchange data with one controller in Token Group 2. If
Token Group 2 needs data from different controllers in Token Group
1, the talking controller in Token Group 1 must collect the data.
In the HH Network Profile II Configuration Topology example on
page 167, only these links between Token Groups are allowed:
A1 A2
B1 B2
C1 C2
To configure this scenario, the controllers are placed in their
respective token groups.
Token Group 1

Token Group 2

Token Group 3

Controller 1

Controller 5

Controller 9

Controller 2

Controller 6

Controller 10

Controller 3

Controller 7

Controller 11

Controller 4

Controller 8

Controller 12

In the Peer-to-Peer Editor, you create connections between


controllers. For example, all controllers in Token Group 1 can
communicate to each other, but Controller 1 can also communicate to
Controller 5 in Token Group 2.
Token Group 1 Connections

166

Controller 1

Controller 2

Controller 3

Controller 4

Controller 2

Controller 1

Controller 1

Controller 1

Controller 3

Controller 3

Controller 2

Controller 2

Controller 4

Controller 4

Controller 4

Controller 3

Controller 5

Publication 1753-UM001C-EN-P - March 2010

Peer-to-peer Communication Overview

Chapter 16

HH Network Profile II Configuration Topology

Token Group 1
GuardPLC 2000

Token Group 2
GuardPLC
2000
controllers

GuardPLC 2000

GuardPLC 1200
controller

GuardPLC 2000

Token Group 3
GuardPLC
9
2000
controllers

GuardPLC 2000

GuardPLC 2000

GuardPLC 2000

11

GuardPLC 1200
controller

4
8
10 Mbit
Hub

Buffer Amp

10 Mbit
Hub
Programming
Terminal

12

10

10 Mbit
Hub

Twisted Pair Cable, max 100 m

Buffer Amp
10 Mbit Switch
Fiber Optic Cable

The None Profile


The None profile is different from the profiles described previously
because it has no pre-defined parameters. You must set all the
parameters manually.
To set the parameters, choose either Fast or Medium from the HH
Network/Token Group dialog box, and click Apply. This presets the
parameters according to the profile.
To enable manual changes and activate the entry fields, choose None
and click Apply again. The former parameter settings will be
overridden and can then be changed.
Because the profiles Fast and Medium cover nearly all conceivable
network topologies, None is recommended for evaluation purposes
only. An extensive knowledge of the functions of the parameters, their
value ranges, and their impact on the availability of the network is
required for proper manual parameterization.
IMPORTANT

Publication 1753-UM001C-EN-P - March 2010

The None profile should not be used in regular applications.

167

Chapter 16

Peer-to-peer Communication Overview

Peer-to-Peer Network
Profiles

Due to the variety of parameters, manual network configuration is


very complex and requires extensive knowledge of the parameters
and how they influence one another.
To simplify the setup, RSLogix Guard PLUS! software provides six
Peer-to-Peer profiles, which can be selected by the user, depending
upon application requirements and the capabilities of the network.
Profiles are combinations of matched parameters that are
automatically set when the user chooses a certain profile. The
intention of all profiles is to optimize the data throughput on the
network, which minimizes the ReceiveTMO and results in a low Worst
Case ReactionTime.
For the definitions of the Peer-to-Peer network parameters, see page
157.
The six profiles, listed below, are described in the following sections:

168

Fast & Cleanroom,


Fast & Noisy,
Medium & Cleanroom,
Medium & Noisy,
Slow & Cleanroom, and
Slow & Noisy

Publication 1753-UM001C-EN-P - March 2010

Peer-to-peer Communication Overview

Chapter 16

Peer-to-Peer Profile I: Fast & Cleanroom


This profile provides the fastest data throughput for applications that
require fast data update rates. It is also best for applications that
require the shortest feasible Worst-Case ReactionTime.

Fast & Cleanrooom Characteristics

Minimum Ethernet
network
requirements(1)

Characteristics of the
communication path

Variables

Suitable HH network
profile

Peer-to-Peer
parameter presets

Fast

100 Mbit technology (100 Base TX)

Switched

Fast Ethernet (full-duplex recommended) LAN


switches or integrated switches
(GuardPLC 1600/1800 controller) required.

Cleanroom

No loss of data due to traffic overload, harsh


environmental conditions or network defects.

Minimum delays
ResponseTime ReceiveTMO 2 (otherwise ERROR)
ResponseTime

manually set in the Peer-to-Peer Editor

ReceiveTMO

manually set in the Peer-to-Peer Editor

WDZ
(Watchdog
Time)

manually set in the controller properties

Fast
QueueLen = 2
Communication Time Slice large enough to process and send
all data defined for transmission in one CPU cycle.
ResendTMO
if ReceiveTMO 2 x WDZ, then
ResendTMO = ReceiveTMO 2, or
ResendTMO = ResponseTime, whichever is greater
if ReceiveTMO < 2 x WDZ, then
ResendTMO = ReceiveTMO
AckTMO = 0
ProdRate = 0

(1) The network can be shared with other applications, if sufficient bandwidth is provided.

Publication 1753-UM001C-EN-P - March 2010

169

Chapter 16

Peer-to-peer Communication Overview

Peer-to-Peer Profile II: Fast & Noisy


This profile provides fast data throughput for applications that require
fast data update rates. It is good for applications that require the
shortest feasible Worst-Case Reaction Time where minor loss of
messages can be corrected.

Fast & Noisy Characteristics

Minimum Ethernet
network
requirements

Characteristics of the
communication path
Variables
Suitable HH network
profile

Peer-to-Peer
parameter presets

170

Fast

100 Mbit technology (100 Base TX), if HH


network profile Fast & Cleanroom is selected.
10 Mbit technology (10 Base T), if HH network
profile Medium & Cleanroom is selected.

Switched

Fast Ethernet (full duplex recommended) LAN


switches, if HH network profile Fast &
Cleanroom is selected.
10 MBit hubs, if HH network profile Medium &
Cleanroom is selected.
Or use switches integrated into the
GuardPLC 1600/1800 controllers.

Noisy

Low probability for loss of messages.


Time for 1 repetitions.

Minimum delays
ResponseTime ReceiveTMO 2 (otherwise ERROR)
ResponseTime

manually set in the Peer-to-Peer Editor

ReceiveTMO

manually set in the Peer-to-Peer Editor

WDZ

manually set in the controller properties

Fast
Medium ( 10 controllers in a Token Group)
QueueLen = 2
Communication Time Slice large enough to process and send
all data defined for transmission in one CPU cycle.
ResendTMO
if ReceiveTMO 2 x WDZ, then
ResendTMO = ResponseTime ( 1 Resend possible)
if ReceiveTMO < 2 x WDZ, then ERROR
AckTMO = 0
ProdRate = 0

Publication 1753-UM001C-EN-P - March 2010

Peer-to-peer Communication Overview

Chapter 16

Peer-to-Peer Profile III: Medium & Cleanroom


This profile provides medium data throughput for applications where
only a moderate data update rate is required and where the Worst
Case Reaction Time is not a critical factor. It is well-suited for virtual
private networks (VPN), where data exchange is slow due to safety
devices (firewalls, encoding/decoding), but error-free.
TIP

Normally use the profile Medium & Noisy


(see page 172).

Medium & Cleanroom Characteristics

Minimum Ethernet
network requirements

10 MBit (10 Base T) or 100 Mbit technology


(100 Base TX) or network with both 10 MBit
Medium or Fast
and 100 MBit components.
LAN switches required.
Clean

Characteristics of the
communication path
Variables
Suitable HH network
profile

Peer-to-Peer
parameter presets

Publication 1753-UM001C-EN-P - March 2010

No loss of data due to traffic overload, harsh


environmental conditions or network defects.
Time for 0 repetitions.

Moderate delays
ResponseTime ReceiveTMO (otherwise ERROR)
ResponseTime

manually set in the Peer-to-Peer Editor

ReceiveTMO

manually set in the Peer-to-Peer Editor

WDZ

manually set in the controller properties

Fast
Medium ( 10 controllers in a Token Group)
QueueLen = 3
Communication Time Slice large enough to process and send
all data defined for transmission in one CPU cycle.
ResentTMO
if ReceiveTMO 2 x WDZ, then
ResendTMO = ResponseTime ( 0 Resends possible)
if ReceiveTMO < 2 x WDZ, then
ResendTMO = ReceiveTMO
AckTMO = ReceiveTMO or AckTMO = AckTMOMax,
whichever is smaller
ProdRate = ResponseTime 4

171

Chapter 16

Peer-to-peer Communication Overview

Peer-to-Peer Profile IV: Medium & Noisy


The Medium and Noisy profile provides medium data throughput for
applications where only a moderate data update rate is required. It is
good for applications where the Worst Case ReactionTime is not a
critical factor. Minor loss of messages can be corrected.

Medium & Noisy Characteristics


10 MBit (10 Base T) or 100 Mbit technology (100
Base TX) or network with both 10 MBit and 100
Medium or Fast
MBit components.
Minimum Ethernet
Usage of hubs possible.
network requirements
Low probability for loss of messages.
Noisy
Time for 1 repetitions.
Characteristics of the
communication path
Variables
Suitable HH network
profile

Peer-to-Peer
parameter presets

172

Moderate delays
ResponseTime ReceiveTMO 2
ResponseTime

manually set in the Peer-to-Peer Editor

ReceiveTMO

manually set in the Peer-to-Peer Editor

WDZ

manually set in the controller properties

Medium or Fast
QueueLen = 3
Communication Time Slice large enough to process and send
all data defined for transmission in one CPU cycle.
ResendTMO
if ReceiveTMO 2 x WDZ, then
ResendTMO = ResponseTime ( 1 Resend possible)
if ReceiveTMO < 2 x WDZ, then ERROR
AckTMO = ReceiveTMO or AckTMO = AckTMOMax, whichever
is smaller
ProdRate = ResponseTime 4

Publication 1753-UM001C-EN-P - March 2010

Peer-to-peer Communication Overview

Chapter 16

Peer-to-Peer Profile V: Slow & Cleanroom


This profile provides low data throughput for applications where only
a low data update rate is required from remote controllers, via
communication paths, whose conditions cannot be predicted by the
user.
TIP

Normally use the profile Slow & Noisy


(see page 174).

Slow & Cleanroom Characteristics


Minimum Ethernet
network
requirements

Slow

Primarily for data exchange via ISDN, leased


line or slow line-of-sight radio link.

Clean

No loss of data due to traffic overload, harsh


environmental conditions or network defects.
Time for 0 repetitions.

Characteristics of the Moderate to long delays


communication path ResponseTime ReceiveTMO, otherwise ERROR

Variables

Suitable HH network
profile

Peer-to-Peer
parameter presets

Publication 1753-UM001C-EN-P - March 2010

ResponseTime

manually set in the Peer-to-Peer Editor

ReceiveTMO

manually set in the Peer-to-Peer Editor

WDZ

manually set in the controller properties

number of link partners a controller can talk to


defined in the Peer-to-Peer Editor

Medium or
Fast
QueueLen = 4
Communication Time Slice large enough to process and send
all data defined for transmission in one CPU cycle.
ResendTMO
if ReceiveTMO 2 x WDZ, then
ResendTMO = ResponseTime ( 0 Resends possible)
if ReceiveTMO < 2 x WDZ, then
ResendTMO = ReceiveTMO
AckTMO = ReceiveTMO or AckTMO = AckTMOMax, whichever
is smaller
ProdRate = ResponseTime 4

173

Chapter 16

Peer-to-peer Communication Overview

Peer-to-Peer Profile IV: Slow & Noisy


This profile provides low data throughput for applications where only
low data update rates are required. It is primarily for data exchange
via poor quality telephone lines or distorted radio links.

Slow & Noisy Characteristics

Minimum Ethernet
network requirements

Characteristics of the
communication path
Variables
Suitable HH network
profile

Peer-to-Peer
parameter presets

174

Slow

Data transfer via telephone, satellite link, radio,


and so forth.

Noisy

Low loss of data due to distortions on the


communication path or network defects.
Time for 1 repetitions.

Moderate to long delays


ResponseTime ReceiveTMO 2, otherwise ERROR
ResponseTime

manually set in the Peer-to-Peer Editor

ReceiveTMO

manually set in the Peer-to-Peer Editor

Medium or Fast
QueueLen = 4
Communication Time Slice large enough to process and send
all data defined for transmission in one CPU cycle.
ResendTMO
if ReceiveTMO 2 x WDZ, then
ResendTMO = ResponseTime ( 1 Resend possible)
if ReceiveTMO < 2 x WDZ, then ERROR
AckTMO = ReceiveTMO or AckTMO = AckTMOMax, whichever
is smaller
ProdRate = ResponseTime 4

Publication 1753-UM001C-EN-P - March 2010

Chapter

17

Configure Peer-to-Peer Communication


Introduction
Topic

Page

Considerations for Using Peer-to-peer

175

Set Peer-to-Peer Controller Properties

176

Create a Peer-to-peer Network

178

Design the Logic

180

Configure Peer-to-peer Communication

184

Compile and Download

189

Network Optimizing

190

Using peer-to-peer communication, you can exchange signals


between controllers by dragging signals onto pages that create
controller-to-controller connections. For example, controller 1 could
send three signals (out1, out2, and out3) to controller 2. Controller 2
can then use these signals as inputs within its function block code.

Considerations for Using


Peer-to-peer

Before you start a project that exchanges data between several


controllers, you should become familiar with the requirements of your
application. Questions about the network design, which should be
answered prior to developing the project, include the following:
Is timing a critical factor of the application? This is the most
important question!
How many controllers will be involved?
Is it necessary to establish an Ethernet network exclusively for
the application, or can an existing network be shared?
How far away from each other are the controllers?
Are transportation media, other than the Ethernet network,
needed (such as telephone lines, radios, fiber optics, and so
forth)?
Is it necessary for each controller to communicate with all other
controllers?
Can some functions of the application be grouped and executed
separately by an isolated group of controllers (token group)?

175Publication 1753-UM001C-EN-P - March 2010

175

Chapter 17

Configure Peer-to-Peer Communication

Set Peer-to-Peer Controller


Properties

Right-click Resource and choose Properties to set the timing


parameters and switches according to the requirements of your
application.

The Communication Time Slice and Code Generation Version settings


are needed for peer-to-peer network parameterization.

Communication Time Slice


The Communication Time Slice is the time in milliseconds reserved for
a controller to carry out and complete all communication tasks in one
CPU cycle.
The minimum Communication Time Slice depends on the number of
communication connections (n) a controller has.
The minimum Communication Time Slice (CTSmin) is calculated as
follows.
For n 13:

CTSmin (n 13) = n x 1 ms + 4 ms

For n > 13:

CTSmin (n > 13) = n x 1.3 ms

IMPORTANT

176

Do not set the Communication Time Slice below the calculated


value. If the Communication Time Slice is too small, it takes
more than one CPU cycle to carry out the pending
communication tasks. Therefore, more time is needed to
complete the communication tasks, which degrades
performance and could result in a communication shutdown
due to a communication timeout (ReceiveTMO).

Publication 1753-UM001C-EN-P - March 2010

Configure Peer-to-Peer Communication

Chapter 17

The time actually needed for communication adds to the CPU cycle
time. A short Communication Time Slice limits the communication
time to a low value. This prevents the CPU cycle time from being
noticeably influenced by network occurrences. Although a
Communication Time Slice well above the minimum value may result
in cycle time on the local machine slowing down a bit if network
traffic is heavy, it is not necessarily negative.
If you are transferring safety I/O over the network, you need a
Communication Time Slice high enough to guarantee that the
communication are completed every cycle. If it takes more than one
cycle to read/write safety I/O, your safety time will need to increase to
compensate.
If you are only transferring status data over the network, then a lower
Communication Time Slice is permissible, because it leaves more time
in the cycle for your program to run. Its likely to be acceptable even
if it takes more than one cycle to read the status.
Check the CPU short-term diagnostics for any Time Slice expired
entries and increase the Communication Time Slice if necessary,
before the application goes into regular operation. In the Statistics of
the Control Panel, Number of Time Slices higher than 1 also indicate a
Communication Time Slice that is too short. Number of Time Slices
indicates the number of cycles it took for communication to complete.
The maximum Communication Time Slice depends on the application
and is calculated as follows.
WDZ Communication Time Slice (max) + Application
Execution Time
In other words, the Communication Time Slice plus Application
Execution Time must not exceed the Watchdog Time.

EXAMPLE

If the controller on page 176 has 10 connections, the


minimum Communication Time Slice is:
CTSmin = 10 x 1 ms + 4 ms = 14 ms.
CTSmin is increased by 6 milliseconds to provide a
safety margin.
CTSmin = 20 ms
With a Watchdog Time of 500 ms, this leaves 480 ms
for the application to be executed.

Publication 1753-UM001C-EN-P - March 2010

177

Chapter 17

Configure Peer-to-Peer Communication

Code Generator Version


To compile the logic correctly for your type of controller, set Code
Generator Version to three (3) for RSLogix Guard PLUS! software. Set
to version two (2) for RSLogix Guard software.

Create a Peer-to-peer
Network

To create a peer-to-peer network, right-click the project in the


Hardware Management window and choose New>HH-Network.

You can right-click HH-Network and Rename the entry, if desired.

Create Token Group(s)


A single token group is automatically created with the HH network. If
you need more, create token groups by right-clicking HH-Network
and choosing New>Token Group.

Expand the HH-Network, right-click Token Group(s) and rename the


Token Group(s), if desired.

178

Publication 1753-UM001C-EN-P - March 2010

Configure Peer-to-Peer Communication

Chapter 17

Add Controllers to Token Group(s)


A controller must be a member of only one token group. To add a
controller to a token group, follow these steps.
1. Expand the HH-Network, right-click a token group, and choose
Node Editor.
The Node Editor is empty when you open it for the first time.
2. Click a controller in the tree view and drag and drop it in the
Node Editor.

Configure Token Group(s)


1. Right-click the token group and choose Properties.
2. In the HH-Network/Token Group dialog box, choose a profile.
For a description of the HH-Network profiles, see page 161. In
general, Fast works with most network topologies.
3. Enter a Token Group ID.
The Token Group ID must be greater than 0. If you create more
than one token group, each token group must have a unique ID.
4. Do not make changes to the other settings in this dialog box.
See page 153 for the description of the HH protocol parameters.

Publication 1753-UM001C-EN-P - March 2010

179

Chapter 17

Configure Peer-to-Peer Communication

IMPORTANT

Design the Logic

You must choose identical profiles for token groups that you
want to interconnect. If Link Mode (External) does not match,
communication between token groups is impossible.

Create Peer-to-peer Signals


Signals are transferred among controllers over the peer-to-peer
network. Consider the following when creating signals:
You can create as many signals as you need in the logic for all
controllers.
You can add signals anytime.
Signals with the same name can be used on more than one
controller without influencing each other (LOCAL variable), as
long as they are not exchanged via network.
Signals that are intended for network exchange, must have the
same name on the participating controllers. Whether a signal is
written to or read from the network is defined in the
Peer-to-Peer Editor as explained in Configure Peer-to-peer
Communication on page 184.

180

Publication 1753-UM001C-EN-P - March 2010

Configure Peer-to-Peer Communication

Chapter 17

Use Peer-to-peer System Signals


The status of the peer-to-peer communication as well as some timing
parameters can be evaluated in the user program by means of system
signals. Furthermore, the user program can control how a
peer-to-peer connection is setup.

Input System Signals

These system signals can be used as inputs for the application:


Connection State. Using the Connection State system signal of
the Peer-to-Peer Editor, the user program can evaluate the status
of the communication between two controllers. This table shows
the possible values for the Connection State system signal and
the corresponding status.
Value

Status

Description

CLOSED

Communication path is closed. No attempt to connect.

TRY_OPEN

Communication path is closed. Attempt to connect.

CONNECTED

Communication path is open. No attempt to connect.

Receive Timeout, in milliseconds, is set by the user.


For more information see Receive Timeout (ReceiveTMO) on
page 158 and Define Peer-to-peer Parameters on page 186.
Response Time, in milliseconds, is the actual value of the last
answer message and is identical to RspT last in the P2P status of
the Control Panel.
For more information, see Reconfigure ResponseTime on page
195.
Version indicates the CRC for the peer-to-peer configuration
between two controllers. The CRC must be identical to establish
communication.

Publication 1753-UM001C-EN-P - March 2010

181

Chapter 17

Configure Peer-to-Peer Communication

Output System Signal


Using the output system Connection Control signal, the user program
can control how the peer-to-peer connection is setup.

Connection Control Values


Value

Setting

Description

0x0000

Autoconnect

After loss of peer-to-peer communication, the controller


tries to re-establish communication in the next CPU cycle.
This is the standard mode of operation.

0x0100

Toggle_Mode 0

0x0101

Toggle_Mode 1

These modes allow automatic connect with Disable after


loss of communication.
If Toggle_Mode is 0 and communication is lost
(Connection State = CLOSED), a connect is performed
only after Toggle_Mode is set to 1 by the user program.
If Toggle_Mode is 1 and communication is lost, a connect
is performed only after Toggle_Mode is set to 0 by the
user program.

0x8000

Disabled

IMPORTANT

Peer-to-peer communication is disabled.


No attempt to connect.

If the P2PControl signal, in the illustration above, is set to


32768, peer-to-peer communication is disabled. If Connection
Control is not set by the application, the default is 0 and
Autoconnect is enabled.

Design the Logic for all Controllers


Design the logic for the controllers, considering the variables intended
for network exchange.
The following examples show part of the routines for controllers
Robot A and Robot B, respectively. To evaluate the state of the
OutRange signal in Robot B, use the same signal name (OutRange) as
an input for the logic of Robot B. OutRange is sent over the Ethernet

182

Publication 1753-UM001C-EN-P - March 2010

Configure Peer-to-Peer Communication

Chapter 17

network, via Peer-to-Peer, from Robot A to Robot B, which uses it as


an input.

Design Logic for Robot A

Design Logic for Robot B

Publication 1753-UM001C-EN-P - March 2010

183

Chapter 17

Configure Peer-to-Peer Communication

Configure Peer-to-peer
Communication

As discussed in the following sections, you configure peer-to-peer


communication by:

defining controller connections.


assigning the HH-Network.
choosing a peer-to-peer profile.
defining peer-to-peer parameters.
defining process signals for exchange.

Define Controller Connections


To define all of the controllers each controller can communicate with,
follow these steps.
1. Right-click the resource you want to define controller
connections for and choose Peer-to-Peer Editor.
The title bar of the Peer-to-Peer Editor shows the name of the
selected controller. When the Peer-to-Peer Editor is opened for
the first time, it does not contain any entries.
2. In the project tree, click a resource and drag and drop it in the
Peer-to-Peer Editor.
3. Repeat step 2 to add more controller connections.
In the example below, RobotA (title bar) has a connection to
RobotB and RobotC. Because the return path is automatically
added, you do not need to drag RobotA onto the Peer-to-Peer
editors of RobotB or RobotC.

184

Publication 1753-UM001C-EN-P - March 2010

Configure Peer-to-Peer Communication

Chapter 17

This example shows how the three Peer-to-Peer Editors would appear
if connections existed between all three controllers.

Assign HH-Network
Peer-to-peer communication requires the HH-Network, which must be
entered in the Peer-to-Peer Editor.
To assign the HH-Network, click the HH-Network in the tree view and
drag and drop it in the Network column of the Peer-to-Peer Editor.
The return path is automatically updated with the HH-Network.

Publication 1753-UM001C-EN-P - March 2010

185

Chapter 17

Configure Peer-to-Peer Communication

Choose a Peer-to-peer Profile


1. Click in the Profile column and choose one of the profiles.
Make sure that the profile is suitable for your network topology
and matches the HH profile.
See page 161 for a detailed description of all the profiles.

2. Click outside the table or press the Return key to activate the
selection.
The profile of the return path is automatically updated with the
new profile.

Define Peer-to-peer Parameters


The most important timing parameter of a safety related installation is
the Safety Time. Safety Time is the time a process can run with
incorrect controller outputs without affecting the safety of the process.
See the GuardPLC Controller Systems Safety Reference Manual,
publication 1753-RM002 for more details on the Safety Time.
The Worst Case Reaction Time (TR) is the time within which two
linked controllers must detect the occurrence of a physical input
signal at PES1 and put out the resulting physical output signal at PES2.
To guarantee the integrity of the application, the requirement below
must always be fulfilled.
TR < Safety Time
When you choose a peer-to-peer profile, most parameters are
automatically preset. Because ReceiveTMO (safety-relevant) is part of
the Worst Case ReactionTime TR (see Peer-to-peer Protocol Parameters

186

Publication 1753-UM001C-EN-P - March 2010

Configure Peer-to-Peer Communication

Chapter 17

on page 157), ReceiveTMO must be calculated and set manually by


overwriting the default value in the Peer-to-Peer Editor.
For profiles where ProdRate = 0 (Fast & Cleanroom, Fast & Noisy),
ReceiveTMO is:
ReceiveTMO = TR 2 x WDZ(PES1) 2 x WDZ(PES2)
For profiles where ProdRate 0, ReceiveTMO is:
ReceiveTMO = [TR 3 x WDZ(PES1) 2 x WDZ(PES2)] 2
Calculate the ReceiveTMO with the suitable formula and overwrite the
default value in the Peer-to-Peer Editor.

In first approximation, the ResponseTime can be calculated as:


ResponseTime = ReceiveTMO 2
Overwrite the default value of the ResponseTime with the calculated
value.
TIP

Setting the ResponseTime this way allows the controller to


resend a message, in case of unexpected message loss. For
best network performance, the ReceiveTMO and the
ResponseTime are optimized after the project has been
compiled, loaded and started on the controllers. At that time,
the actual ResponseTimes and the actual cycle times can be
read in the Control Panel.

Define The Signals to Exchange Between Each Controller


Connection
1. Right-click a resource in the project tree and choose
Peer-to-Peer Editor.
The Peer-to-Peer Editor opens.
2. Click a line number (leftmost column) in the Peer-to-Peer Editor
table.
This selects a controller with which the controller, named in the
headline of the Peer-to-Peer Editor, exchanges data.

Publication 1753-UM001C-EN-P - March 2010

187

Chapter 17

Configure Peer-to-Peer Communication

3. Open the Signal Editor by choosing Editor from the Signals


menu.
4. Click Connect Process Signals in the Peer-to-Peer Editor.
5. Arrange the Signal Editor and the Peer-to-Peer (P2P) Process
Signals dialog boxes side by side.
When you open it for the first time, the P2P Process Signals
dialog box is empty.
6. Using the tabs below the button bar of the P2P Process Signals,
choose the direction of data exchange.
In the example below, the direction of data exchange is from
RobotA to RobotB.
7. In the Signal Editor, click a signal name and drag & drop it in
the P2P Process Signals.
You can also add signals by using the New Connected Signals
button. This creates a new line in the list, in which you must
enter the case-sensitive signal name exactly as defined in the
Signal Editor.

TIP

188

Sending a signal from one controller to another (PES1


PES2) makes the value of this signal available in PES2. To
process this value in the logic of PES2, identical signal
names must be used in the logic of both PES1 and PES2.

Publication 1753-UM001C-EN-P - March 2010

Configure Peer-to-Peer Communication

Chapter 17

8. Change the direction of data exchange with the tab and define
the return signals.
The illustration below shows the signals that RobotB sends to
RobotA.

Compile and Download

Compile Logic
If changes, such as adding or deleting a tag, are made to a connection
between two controllers, the code must be recompiled for both
controllers.
To compile logic, right-click the resource (controller) in the RSLogix
Guard PLUS! Project Management window, and choose Code
Generation.

If code generation is not successful, carefully check the Error-state


viewer in the Hardware Management window for error messages and
correct the errors.

Start Download
1. Using the Multi-Control Panel, click Select all
controllers.
2. Click Stop
mode.
Publication 1753-UM001C-EN-P - March 2010

to select all

to make sure that all controllers are in Stop

189

Chapter 17

Configure Peer-to-Peer Communication

3. Click Download to start the simultaneous download for all


selected controllers.
The Action column shows the command that is currently
executed or a short status message. In the example below, the
downloads have completed successfully.

4. After successful download, the CPU Status is Stop/Valid


Configuration.
5. Select all controllers again if necessary, and click Coldstart to
start the application.

Network Optimizing

With the initial network settings made in the HH protocol and


Peer-to-Peer protocol, communication is likely to work, but the
settings can be optimized for homogenous network load and faster
message exchange.

IMPORTANT

If there is no real need to reduce Worst Case ReactionTime, do


not make changes to the WDZ and the ReceiveTMO!
Only optimize the ResponseTime.
A high WDZ or ReceiveTMO does not degrade performance, but
an optimized ResponseTime increases availability.

Before starting the optimization steps, let the project run for several
hours. Test as many operating conditions as possible to address timing
factors that may prevent a project from running after optimization.

190

Publication 1753-UM001C-EN-P - March 2010

Configure Peer-to-Peer Communication

Chapter 17

Check Routine Timing


1. In the Multi Control Panel, select all controllers and click Control
Panel.
2. In the Control Panels of each controller, click the Statistics tab.

3. Write down the maximum Cycle Time for each controller.


4. Write down the maximum Com. Time Slice for each controller.

IMPORTANT

Before you continue to optimize settings, make sure that


Number of Time Slices (see above) is not greater than 1. If
Number of Time Slices max is greater than 1, more than one
CPU cycle is needed to carry out all communication tasks.
In this case, you need to determine if it is permissible for
communication to take multiple cycles to complete. This
depends on how many cycles can be completed within the
safety time.
If you need to increase the Com. Time Slice, start the code
generator again, and download and start the new routine on
the controller.

Publication 1753-UM001C-EN-P - March 2010

191

Chapter 17

Configure Peer-to-Peer Communication

Reconfigure Watchdog Time


To optimize the Watchdog Time to the lowest possible value, you
must know the maximum CPU cycle time. Cycle Time max., as
displayed on the Statistics tab of the Control Panel, is the value that
occurred so far, but is not necessarily the maximum value that can
occur depending on network and process conditions.
If the maximum Cycle Time cannot be estimated, run the project for
several hours and under as many conditions as possible.
Follow these steps to reconfigure the Watchdog Time.
1. In the project tree, right-click the first resource and choose
Properties.
2. Calculate a Margin of Safety, MoS:
MoS = 0.1 x (Cycle Time max.)
MoS should be at least 6 ms. If MoS < 6 ms, then
MoS = 6 ms
3. Readjust the Watchdog Time:
Watchdog Time = (Cycle Time max.) + (MoS)
In the example on the following page, the new Watchdog Time
is: 8 ms + 6 ms = 14 ms.

192

Publication 1753-UM001C-EN-P - March 2010

Configure Peer-to-Peer Communication

Chapter 17

4. For all controllers in your project, re-adjust the Watchdog Times


to their individual optimum values.
After these modifications, you must re-compile the
TIP
project with the Code Generator and download the
routines in the controllers again.
5. Start the project and let it run for a while.
6. If you encounter controller errors due to a Watchdog Time that
is too short, increase the Watchdog Time. Otherwise, continue
with the network optimization.

Check HH Status
In the Control Panel, click the HH Status tab.

The HH Status displays the following information.


Parameter

Explanation

Bus Cycle Time Time in milliseconds for a Token cycle. The value is 0, if Token Passing is
off (any Cleanroom profile).
Resource

Name of the controller

LinkId

Controller network ID

State

Status of the communication

RspT

If Link Mode is TCS direct (Token Passing OFF), RspT is the


ResponseTime of the HH profile for a message from PES1 PES2
PES1, based on the network hardware and topology. This parameter
cannot be changed by the user.
If Link Mode is TCS TOKCYC (Token Passing ON), RspT is part of the Bus
Cycle Time.

Link Mode

TCS direct when Token Passing is OFF.


TCS TOKCYC when Token Passing is ON.

Token Group ID ID of the Token Group

Read the RspT min parameter. This is the minimum time needed for
the communication modules (COM) of two controllers to talk to each
other. Refresh RspT values with Communication>Update HH State, if
Token Passing is OFF.

Publication 1753-UM001C-EN-P - March 2010

193

Chapter 17

Configure Peer-to-Peer Communication

Check Peer-to-peer Status


In the Control Panel, click the P2P Status tab.

The P2P Status displays the following information.


Parameter

Description

Resource

Name of the controller

System.Rack

Network ID of the controller

State

Status of the communication

RspT (last, avg, Measured ResponseTime for a message from PES1 PES2 PES1, based on the network hardware, CPU cycle time,
min, max)
and Peer-to-Peer profile. This parameter will be optimized later.
MsgNr

Counter (32-bit resolution) for all messages sent to a controller. In the illustration above, Robot A has sent message no.
54980 to Robot B.

AckMsgNr

The number of the received message that the controller has to acknowledge. In the illustration above, Robot A has
acknowledged message no. 54979 from Robot B.

DataSeq

Counter (16-bit resolution) for sent messages, which contain process data. In the illustration above, Robot A has sent
data message no. 54980 to Robot B.

Opens

Number of successful connects to a controller.


A figure higher than 1 indicates that a controller dropped out and has been reconnected.

Resends

Counter (32-bit resolution) for messages that have been resent due to an elapsed ResendTMO.

BadMsgs

Counter (32-bit resolution) for received messages that are corrupted, or are not expected at that instant.
A corrupt message, for example, is a message with a wrong sender or with a faulty CRC.
An unexpected message, for example, is an Open command, when the controllers are already connected.

EarlyMsgs

Counter (32-bit resolution) for received messages that are not in the correct sequence. If a message drops out and is lost
at the addressee, there is a gap in the received messages, and the next message comes early.

Receive Tmo

Receive Timeout as entered by the user (see Define Peer-to-peer Parameters on page 186).

ResendTMO

Resend Timeout as set by the profile.

AckTmo

Acknowledge Timeout as set by the profile.

CurKeVer

CRC for the peer-to-peer configuration. Identical to the Peer-to-Peer system signal version (see page 181).

NewKeVer

Reserved for future use.

194

Publication 1753-UM001C-EN-P - March 2010

Configure Peer-to-Peer Communication

Chapter 17

Reconfigure ResponseTime
The ResponseTime initially configured in Define Peer-to-peer
Parameters on page 186 was derived from theoretical considerations
and was chosen conservatively, to start the network running. The
ResponseTime actually needed is usually much smaller than the
theoretical value and can be optimized to improve network
performance.
To optimize the ResponseTime, follow these steps.
1. Open the Control Panels for all controllers in the project and
choose P2P State.
2. Position the horizontal slider so that you can read the
ResponseTime.

3. Compare the RspT avg of two linked controllers for the forward
and return path.
Values for RspT avg may jump a bit.
4. Watch both readings for a couple of seconds and pick the
largest value.
Your reading need not be accurate to the millisecond.

Publication 1753-UM001C-EN-P - March 2010

195

Chapter 17

Configure Peer-to-Peer Communication

5. Note the larger of the two values.


The example on page 195 shows RespT avg for
Robot A Robot B (11 ms) and Robot B Robot A (10 ms).
6. Compare the RspT max of two linked controllers for the forward
and return paths.
Note down the larger of the two values.
The example on page 195 shows RspT max for
Robot A Robot B (19 ms) and Robot B Robot A (20 ms).
7. In the P2P State tab, check the entries for Resends and
EarlyMsgs.
a. If the entries for both Resends and EarlyMsgs are 0, no
messages have been repeated. In this case, delete the noted
RspT avg.
b. If one or more entries for Resends or EarlyMsgs is not 0,
messages have been repeated. In this case, delete the noted
RspT max.

8. Enter the remaining noted value for RspT, either avg or max, in
the ResponseTime of the Peer-to-Peer Editor.

196

Publication 1753-UM001C-EN-P - March 2010

Configure Peer-to-Peer Communication

Chapter 17

Reconfigure Receive Timeout


1. Set the new ReceiveTMO to: 2 x ResponseTime.
2. The Worst Case Reaction Time is optimized and displayed in the
Peer-to-Peer Editor (see above).
3. Compile the project.
4. Download the routines in the controllers again.
5. Start and test your application.

Publication 1753-UM001C-EN-P - March 2010

197

Chapter 17

Configure Peer-to-Peer Communication

Notes:

198

Publication 1753-UM001C-EN-P - March 2010

Chapter

18

Introduction to EtherNet/IP Communication


Introduction

EtherNet/IP Communication
Overview

Topic

Page

EtherNet/IP Communication Overview

199

Add EtherNet/IP Protocol to the Resource

203

View the Controller IP Settings

204

Configuring Communication Between the Controller and a


PanelView PLUS Terminal

205

EtherNet Industrial Protocol (EtherNet/IP) is an open networking


standard communication protocol. GuardPLC 1600 and
GuardPLC 1800 controllers can connect to other EtherNet/IP devices,
such as other controllers, HMIs or distributed I/O blocks.
To use the EtherNet/IP network, the GuardPLC 1600 or GuardPLC
1800 must meet these requirements.
Operating System

Version

CPU

6.28

COM

10.36

A GuardPLC controller can be configured as an EtherNet/IP scanner


(originator) and/or adapter (target). Signals are exchanged between
the scanner and the adapter in packets within the user-defined time
(Requested Packet Interval).

GuardPLC Controller as an Adapter


To configure a GuardPLC controller as an adapter, configure the input
and output assemblies in the GuardPLC controller by using RSLogix
Guard PLUS! software and then connect signals to the I/O assemblies.
RSLogix Guard PLUS! software is used to create EtherNet/IP
assemblies for the GuardPLC controller. An adapter input assembly
(IN_120) and output assembly (OUT_121) are created automatically
when EtherNet/IP protocol is added to the controller. You can use
these standard assemblies or create your own by using RSLogix Guard
PLUS! software.

199Publication 1753-UM001C-EN-P - March 2010

199

Chapter 18

Introduction to EtherNet/IP Communication

The GuardPLC controller can be used as a Class 1 adapter, a Class 3


adapter, or as an unconnected adapter to communicate to Logix
controllers, PLC-5 or SLC 5/05 controllers, or PanelView Standard
terminals. See Chapter 19 for information on using the GuardPLC
controller as an adapter.

Class 1 Connections
GuardPLC assemblies may have various sizes and have signals of
different types associated with them. An EtherNet/IP scanner can
establish Class 1 connections to the GuardPLC controller to read from
the input assemblies and write to the output assemblies. When
establishing a Class 1 connection, the data is addressed by using the
unique instance number of the assembly object. This is similar to
establishing a Class 1 connection to an I/O module but different than
establishing a Class 1 connection to Logix controllers where data is
addressed by a name.

Class 3 Connections
An EtherNet/IP scanner may be used to establish Class 3 connections
to the GuardPLC controller. The Class 3 connection can be used to
send explicit requests to any of the implemented objects, including
Identity, Assembly, PCCC, Connection Configuration, Port, TCP/IP and
Ethernet Link. Connected explicit requests may be used to read
assembly data from an input adapter assembly and write data to the
output assembly.

Unconnected Adapter
Using the GuardPLC controller as an unconnected adapter is similar to
using it as a Class 3 adapter. In both cases, an explicit message is sent
from the client to the GuardPLC controller, addressing one of the
built-in objects, including Identity, Assembly, PCCC, Connection
Configuration, Port, TCP/IP and Ethernet Link. In the case of an
unconnected adapter, the message is not sent over a connection, but
is sent as a single, independent request.

200

Publication 1753-UM001C-EN-P - March 2010

Introduction to EtherNet/IP Communication

Chapter 18

GuardPLC Controller as a Scanner


The scanner data memory is divided into input and output buffers of
assemblies. The input area is used for signals received from the target
(consumed data). The output area is used for signals transmitted to
the target (produced signals). Each I/O assembly must have a
corresponding signal connection. Signal connections are configured
by using RSLogix Guard PLUS! software. The scanner data memory is
configured via a scanlist by using RSNetWorx for EtherNet/IP software.
To enable the GuardPLC controller to scan I/O, set up the controller
as a scanner. See Chapter 20 for information on using the GuardPLC
controller as a scanner.
FLEX I/O, POINT I/O,
ControlLogix or
CompactLogix Controllers
Produced Signals

Consumed Signals

100
Outputs

101
Inputs

Input Assemblies
(IN_120)

Output Assemblies
(OUT_121)

Scanner Assemblies
Adapter (Target)
Assemblies

Read/Write
Read

Produced Signals

Consumed Signals

PLC-5
SLC 5/05
PanelView Standard
(Via Explicit Messages)

ControlLogix Scanner
CompactLogix Scanner
Generic Device

Publication 1753-UM001C-EN-P - March 2010

201

Chapter 18

Introduction to EtherNet/IP Communication

Data Limits
IMPORTANT

In addition to the Ethernet/IP protocol, other protocols (for


example, PROFIBUS-DP, TCP S/R, and others) can also be
executed on a GuardPLC controller at the same time.
A total of 16284 bytes of data can be transmitted and received
per GuardPLC controller. These 16284 bytes can be arbitrarily
divided between the protocols. However, the system signals for
the configured assemblies must be subtracted from the
maximum of send and receive data.

GuardPLC Controller as an Adapter


Up to 64 assemblies of any type (input or output) can be configured
in one GuardPLC controller acting as a target, as long as the maximum
transmit or receive data is not exceeded. However, because there are
always 2 scanner assemblies, the true maximum for adapter
assemblies is 62. These assemblies must have instance numbers in the
range of 120183. All input adapter assemblies and the input scanner
assembly together should not exceed 16K in size. Likewise, all output
adapter assemblies and the output scanner assembly together should
not exceed 16K in size.
If an adapter assembly is used for Class 1 PCCC access, its size is
limited only by the total buffer size for all of the assemblies listed
above. However, if the adapter assembly is used for Class 1 implicit
access, the size of the assembly should not exceed 502 bytes. This is a
limitation that EtherNet/IP protocol puts on any EtherNet/IP adapter.
These 502 bytes include a Run/Idle status header, if the output
assembly is configured to use the header. When the Run/Idle header
is used, the actual maximum size for the data is 498, because the
header uses 4 bytes. A similar limitation applies for explicit CIP access.
If the adapter assembly is used only for PCCC access, its size can
exceed the 502 byte limit. Any one PCCC command cannot address
more than 244 bytes. However, an offset can be specified to allow
access to any assembly portion up to a maximum of 16K.

GuardPLC Controller as a Scanner


The Scanner (GuardPLC controller) can connect up to 32 connections,
which can be configured in different targets.

202

Publication 1753-UM001C-EN-P - March 2010

Introduction to EtherNet/IP Communication

Chapter 18

Signal Connections
It is your responsibility to allocate assemblies to be of the desired
connection size. You do this by assigning signals, created in the Signal
Editor, to the scanner buffers or adapter assemblies.
For more information on creating signals by using the Signal Editor,
refer to the Using RSLogix Guard PLUS! Software with GuardPLC
Controllers Programming Manual, publication 1756-PM001.

Software Required to Configure EtherNet/IP Communication


This table lists the software required to make EtherNet/IP connections.
Function

Software

communication

RSLinx

EtherNet/IP Configuration

RSNetWorx for EtherNet/IP

Programming Application Logic

Add EtherNet/IP Protocol to


the Resource

Publication 1753-UM001C-EN-P - March 2010

RSLogix Guard PLUS!, Program Management,


version 4.1 or later
RSLogix Guard PLUS!, Hardware Management,
version 7.56.10 or later

1. Expand the Resource folder in the project tree.


2. Right-click the Protocols folder under your Resource and choose
New>EtherNet/IP.

203

Chapter 18

Introduction to EtherNet/IP Communication

RSLogix Guard PLUS! software creates an EtherNet/IP branch under


the Protocols folder where it adds the scanner and the adapter
assemblies.

Scanner defines the GuardPLC controllers scanner I/O space, which


consists of two buffers: one to store input data and one to store
output data.
The controllers adapter input assembly, [120]IN_120, contains data
that is produced by the GuardPLC controller. The controllers adapter
output assembly, [121]OUT_121, contains the data that is consumed
by the GuardPLC controller.

View the Controller IP


Settings

You need to know the IP settings for the GuardPLC controller when
you configure a device to communicate with it over the EtherNet/IP
network.
To view and configure the IP settings for the GuardPLC controller,
follow these steps.
1. Expand the controller in the project tree.
2. Right-click COM and choose Properties.

204

Publication 1753-UM001C-EN-P - March 2010

Introduction to EtherNet/IP Communication

Chapter 18

Parameter

Description

IP address

The IP address uniquely identifies the module. The IP address is in the form
xxx.xxx.xxx.xxx where each xxx is a number between 0255. These are reserved values
you cannot use:
127.0.0.1
0.0.0.0
255.255.255.255

subnet mask

Subnet addressing is an extension of the IP address scheme that allows a site to use a
single network ID for multiple physical networks. Routing outside of the site continues by
dividing the IP address into a net ID and a host ID via the class. Inside a site, the subnet
mask is used to redivide the IP address into a custom network ID portion and host ID
portion. This field is set to 0.0.0.0 by default.
If you change the subnet mask of an already-configured module, you must cycle power to
the module for the change to take effect.

gateway

A gateway connects individual physical networks into a system of networks. When a node
needs to communicate with a node on another network, a gateway transfers the data
between the two networks. This field is set to 0.0.0.0 by default.

For more information on the EtherNet/IP network, refer to these


publications from Rockwell Automation:
EtherNet/IP Performance Application Solution, publication
ENET-AP001
EtherNet/IP Modules in Logix 5000 Control Systems User
Manual, publication ENET-UM001

Configuring Communication
Between the Controller
and a PanelView PLUS
Terminal

To enable communication between a GuardPLC 1600 or


GuardPLC 1800 controller and PanelView PLUS terminal, you need the
following software
RSLinx Enterprise, version 5.0 (CPR9)
FactoryTalk View Studio Machine Edition, version 5.00.00
(CPR9)
RSLogix Guard PLUS, version 4.1 (Build 6111)
This section guides you through:
setting up FactoryTalkView Studio Machine Edition software
adding Ethernet/IP protocol to your RSLogix Guard PLUS project
creating a graphic display that can read and write INT and
BOOL data to and from the GuardPLC controller

Publication 1753-UM001C-EN-P - March 2010

205

Chapter 18

Introduction to EtherNet/IP Communication

Set Up FactoryTalk View Studio Machine Edition Software


Follow these steps to setup FactoryTalk View Studio Machine Edition
software.
1. Open FactoryTalk View Studio software.
2. Add the RSLinx Enterprise server to your application.

3. On the Communications tab, verify that RSLinx Enterprise


software can browse and locate the GuardPLC controller.

206

Publication 1753-UM001C-EN-P - March 2010

Introduction to EtherNet/IP Communication

Chapter 18

4. To add a shortcut for the GuardPLC controller to your


application, double-click Communication Setup under the
RSLinx Enterprise Server.

5. On the Design (Local) tab, select the GuardPLC controller.


6. On the Device Shortcuts pane, click Add and type a name for
the shortcut.
When you choose a name for the shortcut, note that because
there is no tag browsing for GuardPLC controllers, you will have
to type this shortcut name for each object in your graphic
displays.

Publication 1753-UM001C-EN-P - March 2010

207

Chapter 18

Introduction to EtherNet/IP Communication

Add Ethernet/IP Protocol to Your Project


Next, you need to add the Ethernet/IP protocol to your project in
RSLogix Guard PLUS software. Follow these steps.
1. In the Hardware Management window of RSLogix Guard PLUS
software, right-click Protocols and choose Add Ethernet/IP.

By default, the software creates one input assembly (120) and


one output assembly (121). Input and output are referenced to
the scanner. Thus, an input assembly is used to send data from
the GuardPLC controller to the PanelView Plus terminal. An
output assembly is used to send data from the PanelView Plus
terminal out to the GuardPLC controller.
For simplicity, use separate assemblies for each of the four types
of data transfer, as shown above.

Reading integers from the GuardPLC controller


Reading BOOLs from the GuardPLC controller
Writing integers to the GuardPLC controller
Writing integers to the GuardPLC controller

2. To add an assembly, right-click Ethernet/IP, choose New and


then either input or output assembly.

208

Publication 1753-UM001C-EN-P - March 2010

Introduction to EtherNet/IP Communication

Chapter 18

Read Integers from the Controller and Display Them on the


PanelView Plus Terminal
This example uses input assembly 120 and shows how two integers
can be read by the PanelView Plus terminal. Two INT tags,
fromGuard_INT1 and fromGuard_INT2, were used in the controller as
shown.
The names, tag01 and tag02, in the input assembly window could be
any names unique to the GuardPLC controller. The offsets must be
renumbered by using the New Offsets tab. The order of this offset
determines the order in which these tags appear in the buffer.

The numeric display objects shown below read the two integers from
the GuardPLC controller. Tags N120:0 and N120:1 were used to match
the input assembly used in the GuardPLC controller. The GuardPLC
controller does not use the N; it is required for FactoryTalk View
software.

Publication 1753-UM001C-EN-P - March 2010

209

Chapter 18

Introduction to EtherNet/IP Communication

N120:0 corresponds to the first INT tag in the GuardPLC assembly 120.
N120:1 corresponds to the second INT tag in the GuardPLC assembly
120.

Read BOOLs from the GuardPLC Controller and Display Them on


the PanelView Plus Terminal
This example uses input assembly 122. Two BOOL tags,
fromGuard_BOOL1 and fromGuard_BOOL2, were used in the
controller as shown.

210

Publication 1753-UM001C-EN-P - March 2010

Introduction to EtherNet/IP Communication

Chapter 18

The multistate indicator objects shown below read the two BOOLs
from the GuardPLC controller. Tags B122:0 and B122:1 were used to
match the input assembly used in the GuardPLC controller. The
GuardPLC controller does not use the B; it is required for FactoryTalk
View software.

B122:0.0 corresponds to the first BOOL tag in the GuardPLC assembly


122. B122:0.8 corresponds to the second BOOL tag in the GuardPLC
assembly 122.

TIP

Publication 1753-UM001C-EN-P - March 2010

GuardPLC is a BYTE machine. BOOL tags take up a complete


BYTE in the buffer. That is why .0 and .8 are used in the VIEW
tags to read the first bit from the GuardPLC byte. If a third BOOL
tag was read, the address in the VIEW tag would be B122:1.0.

211

Chapter 18

Introduction to EtherNet/IP Communication

Writing Integers to the GuardPLC Controller from the PanelView


Plus Terminal
This example uses output assembly 121 and shows how two integers
can be written by the PanelView Plus terminal. Two INT tags,
toGuard_INT1 and toGuard_INT2, were used in the controller as
shown.

The numeric input objects write the two integers to the GuardPLC
controller. Tags N121:0 and N121:1 were used to match the output
assembly used in the GuardPLC controller. The GuardPLC controller
does not use the N; it is required for FactoryTalk View software.

212

Publication 1753-UM001C-EN-P - March 2010

Introduction to EtherNet/IP Communication

Chapter 18

N121:0 corresponds to the first INT tag in the GuardPLC assembly 121.
N121:1 corresponds to the second INT tag in the GuardPLC assembly
121.

Writing BOOLs to the GuardPLC Controller from the PanelView


Plus Terminal
This example uses output assembly 123. Two BOOLs are written by
the PanelView Plus terminal to the controller. Four BOOL tags,
toGuard_BOOL1 and toGuard_BOOL2 and two dummy tags, were
used in the controller as shown on the following page.
TIP

Publication 1753-UM001C-EN-P - March 2010

The dummy tags are required because BOOL extensions cannot


be used on the write tags within the PanelView Plus terminal.
INT tags must be used on the terminal side. Because an integer
is 2 bytes, a dummy is needed to fill this space in the
controllers buffer. A BOOL tag takes up a complete byte in the
GuardPLC controllers buffer.

213

Chapter 18

Introduction to EtherNet/IP Communication

These momentary pushbutton objects write the two integers to the


GuardPLC controller. Tags N123:0 and N123:1 were used to match the
output assembly used in the GuardPLC controller. The GuardPLC
controller does not use the N; it is required for FactoryTalk View
software.

N123:0 corresponds to the first two BOOL tags in the GuardPLC


assembly 123. The first tag changes between 0 and 1; the second is
the dummy tag. N123:1 corresponds to the next two BOOL tags in the
GuardPLC assembly 123.

214

Publication 1753-UM001C-EN-P - March 2010

Chapter

19

Use GuardPLC Controller as an Adapter


Introduction
Topic

Page

Configure the GuardPLC Controller as an Adapter

215

Open a Class 1 Connection from a Logix Controller to the GuardPLC


Controller

219

Open a Class 3 Connection from a Logix Controller

228

Use a GuardPLC Controller as an Unconnected Adapter

235

Use Unconnected PCCC Messaging from a PLC-5 or SLC 5/05 Controller 235
Use Unconnected CIP Messaging from a PanelView Standard Terminal

Configure the GuardPLC


Controller as an Adapter

243

Make sure the GuardPLC controller resource has the EtherNet/IP


protocol added under the Protocols folder in the RSLogix Guard PLUS!
Hardware Management project tree. If it does not, see page 203 for
instructions on adding EtherNet/IP protocol.

Configure the Adapter Input Assembly


Input assemblies contain data that is produced by the GuardPLC
controller and consumed by a scanner.
1. You can use the default input assembly IN_120 or create a new
input assembly by right-clicking EtherNet/IP in the project tree
and choosing New > Input Assembly.
2. Modify the input assembly properties, if desired, by
right-clicking the input assembly and choosing Properties.

215Publication 1753-UM001C-EN-P - March 2010

215

Chapter 19

Use GuardPLC Controller as an Adapter

3. Type the name for the input assembly in the Name field.
The Assembly ID can be any number from 120183. All
Assembly IDs under the same EtherNet/IP folder must be
unique.
If the Run/Idle header box is checked, the assembly uses a
Run/Idle header. This four-byte header contains Run/Idle
information about the GuardPLC controller that can be used in
the scanners application logic. The GuardPLC controller sends
this Run/Idle header along with the data in the assembly when it
is read.
Usually this box should be unchecked. Normally, the Run/Idle
header will always be used for output assemblies and sometimes
used for input assemblies. However, this may not hold true for
connections to non-Rockwell Automation scanners.
If the Run/Idle header is checked, the input data size specified
by the scanner should be four bytes larger than the actual
GuardPLC controller input assembly size. This is necessary
because the input Run/Idle header, unlike the output one, is not
stored in the GuardPLC assembly, it is automatically added by
the GuardPLC controller when it sends the packet. So, if both
input and output assembly Run/Idle flags are checked, the input
size specified by the scanner should be four bytes larger than
the target assembly size and the output size specified by the
scanner should be four bytes smaller than the target assembly
size.

Configure the Adapter Output Assembly


1. You can use the default output assembly OUT_121 or create a
new output assembly by right-clicking EtherNet/IP in the project
tree and choosing New > Output Assembly.

216

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

2. Modify the default output assembly properties, if desired, by


right-clicking the output assembly and choosing Properties.

3. Type the name for the output assembly in the Name field.
The Assembly ID can be any number from 120183. All
Assembly IDs under the same EtherNet/IP folder must be
unique.
If the Run/Idle header box is checked, the assembly uses a
Run/Idle header. The default is checked. Typically, output
assemblies always use the Run/Idle header. Checking the
Run/Idle header box indicates that the first 4 bytes of the data
received by the GuardPLC controller contains the Run/Idle
header produced by the scanner. These 4 bytes are stored in the
beginning of the assembly buffer and you can use the associated
signal in the GuardPLC controllers application logic that
depends on the scanners Run/Idle state.
If the Data initialization box is checked, the controller uses the
consumed initial values if the corresponding I/O connection
disconnects. If it is not checked, the controller does not use
initial values and the data stays in its last state. The default is
checked.

Connect Signals to the Adapter Assemblies


The Signal Connections dialog box is used to assign signals created in
the Signal Editor to the appropriate tab, either input or output.
1. To open the Signal Connections dialog box, right-click an
Assembly and choose Connect Signals.

Publication 1753-UM001C-EN-P - March 2010

217

Chapter 19

Use GuardPLC Controller as an Adapter

The example below shows the Signal Connections dialog box


for an input assembly. Signals created in the Signal Editor are
assigned to connections to the Output tab for the input
assembly.

2. Drag the signals from the Signal Editor to the Signal Connections
tab.
3. After assigning the signals, either assign the offsets manually or
click New Offsets and choose Renumber at the Renumber
Offsets prompt.
The offsets are byte offsets.
When assigning offsets manually, make sure there are no holes
in the assembly buffer and that the next signal starts where the
previous signal ended.
If the scanner is a Logix controller, be sure that:
the Run/Idle header is checked for output assemblies.
the Run/Idle header is unchecked for input assemblies.
output assemblies have 4 extra bytes in the beginning to hold
the Run/Idle header. These can be 1 DWORD or 2 WORD or
4 byte signals.

218

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Open a Class 1 Connection


from a Logix Controller to
the GuardPLC Controller

Chapter 19

The following example demonstrates making a connection to a Logix


controller, specifically a ControlLogix controller, with a 1756-ENBT or
1756-ENET module to a GuardPLC controller. You can also open
connections to CompactLogix controllers. In a Class 1 connection,
data is cyclically exchanged based on a time interval (RPI).

Configure the Logix Controller in RSLogix 5000 Software


1. In RSLogix 5000 software, create a new project for the Logix
controller.
2. Add the Ethernet adapter module to the I/O Configuration
a. Right-click I/O Configuration and choose New Module.
b. In the Select Module Type dialog box, click the 1756-ENBT or
1756-ENET module type.
c. Click OK.
d. In the Module Properties dialog box, type the IP address and
the slot number of the 1756-ENBT module.

e. Click Finish.
RSLogix 5000 software displays the new 1756-ENBT module
under the I/O Configuration.
3. Right-click the new 1756-ENBT icon and choose New Module.

Publication 1753-UM001C-EN-P - March 2010

219

Chapter 19

Use GuardPLC Controller as an Adapter

4. Choose Generic Ethernet Module from the list and click OK.

5. Type the connection name in the Name field.


6. Type the IP address of the GuardPLC controller in the IP
Address field.
7. Enter the Configuration Assembly Instance as 1 and its size as 0
because the configuration data instance will not be used by the
GuardPLC controller.

Configure the Type of Connection


GuardPLC controllers support these types of Class 1 connections:
Exclusive Owner both sides are cyclically producing data for
one another.
Input Only more than one scanner can listen to the same data
produced by a single GuardPLC controller.
Listen Only the first scanner to establish a connection to the
GuardPLC controller becomes the owner of the connection.
When that scanner closes the owner connection, all subsequent
Listen Only connections are also closed.
These connection types are explained in more detail in the following
sections.

220

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

Exclusive Owner

To establish an exclusive owner connection, follow these steps.


1. Choose Data SINT in the Comm Format Field.
2. Type the GuardPLC controllers Input Assembly instance number
in the Input Assembly Instance field.
3. Type the size of the Input Assembly in the Input Size field.
IMPORTANT

This entry must exactly match the size of the input


assembly, or the GuardPLC adapter controller will return
an error.
The size of the input assembly is determined during the
signal connection process.

4. Type the GuardPLC controllers Output Assembly instance


number in the Output Assembly Instance field.
5. Type the size of the Output Assembly minus 4 bytes in the
Output Size field.
The data size in RSLogix 5000 software does not include the
4 bytes of the Run/Idle header, but these 4 bytes must be part of
the GuardPLC controllers output assembly, because the
ControlLogix controller sends the 4-byte Run/Idle header to the
GuardPLC controller.
For example, if you created an output assembly of 6 bytes (6
BYTE signals assigned in RSLogix Guard PLUS! software), you
must enter an Output Size of 2 in RSLogix 5000 software,
because only the last 2 bytes contain the actual data.

Publication 1753-UM001C-EN-P - March 2010

221

Chapter 19

Use GuardPLC Controller as an Adapter

6. Click Next and type the desired packet rate for this connection
in milliseconds.
7. Click Finish.

Input Only Connections


When you use input only connections, you can create more than one
Class 1 scanner connection to the GuardPLC controller, specifying the
same input assembly instance. The GuardPLC controller specifies the
same multicast address for input data to all scanners asking for the
same input assembly instance. The GuardPLC controller only
produces the data once and all scanners receive the same input data.
No output data will go from the scanners to the GuardPLC controller.
All input only connections are independent from each other. When
one of them times out, the others remain active.

222

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

To open an input only connection, follow these steps.


1. Choose Input Data SINT in the Comm Format field.
2. Type the GuardPLC controllers Input Assembly instance number
in the Input Assembly Instance field.
3. Type the size of the input assembly in bytes in the Input Size
field.
IMPORTANT

This entry must exactly match the size of the input


assembly, or the GuardPLC adapter controller will return
an error.
The size of the input assembly is determined during the
signal connection process.

4. Type the Output Assembly instance number as 199.


This is the heartbeat instance number, a virtual number that is
not associated with any real assembly. It indicates to the
GuardPLC controller that there will be no data coming from the
scanner.
5. Click Next and type the desired packet rate for this connection
in milliseconds.
6. Click Finish.

Listen Only Connections


Listen only connections are similar to input only connections, but all
subsequent input only connections are dependent upon the first input
only connection, which is the owner connection. When an owner
connection is closed, all subsequent listen only connections are also
closed.

Publication 1753-UM001C-EN-P - March 2010

223

Chapter 19

Use GuardPLC Controller as an Adapter

To establish a listen only connection, follow these steps.


1. Choose Input Data SINT in the Comm Format field.
2. Type the input assembly instance number in the Input Assembly
Instance field.
3. Type the size of the input assembly in bytes in the Input Size
field.
IMPORTANT

This entry must exactly match the size of the input


assembly, or the GuardPLC adapter controller will return
an error.
The size of the input assembly is determined during the
signal connection process.

4. Type 199 for the first Output Assembly Instance number and 198
for all subsequent listen only connections.
Number 198 is the Listen Only instance number, a virtual
number that is not associate with any real assembly.
5. Click Next and type the desired packet rate for this connection
in milliseconds.

6. Click OK.

224

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

Download and Go Online


Download new changes to the Logix controller and go online.
Double-click the new connection icon under I/O Configuration. If the
connection is established successfully, RSLogix 5000 software displays
the status as Running in the Module Properties dialog box. If an error
occurred, it is displayed in the Module Fault field of the Connection
tab of the Module Properties dialog box.

Publication 1753-UM001C-EN-P - March 2010

225

Chapter 19

Use GuardPLC Controller as an Adapter

Monitor Connection Status


To monitor the status of your connections, follow these steps.
1. Go online with the GuardPLC controller by using RSLogix Guard
PLUS! software.
2. Switch to the EIP tab of the Control Panel and click the
Connection Status tab.

You can view the connections EtherNet/IP statistics, described in the


table below.
Statistic

Description

Peer IP

Reports the IP address of the scanner, in this case the


1756-ENBT

Peer Status

Indicates whether the scanner, in this case the Logix


controller, is in Run or Idle mode. This is displayed only
for exclusive owner connections, because input only
connections ignore any data coming from the scanner,
including the Run/Idle header.

Type

Displays the connection type

State

Displays the status of the connection

Input

Reports the assembly instance numbers that this


connection services

Output
Sent
Rcvd

226

Displays the total number of sent or received packets


over this connection

PRPI

Displays the producing packet rate requested when


scheduling this connection

CRPI

Displays the consuming packet rate requested when


scheduling this connection

MinPRPI, MaxPRPI, LastPRPI,


and AvrPRPI

Corresponds to the actual minimum, maximum, last, and


average producing packet rates observed over this
connection

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

Use the Force Editor to Test the Connection


You can use the Force Editor in the RSLogix Guard PLUS! software
and the I/O controller tags in RSLogix 5000 software to test the
connection between the GuardPLC controller and the Logix controller.
Under normal operating conditions, the GuardPLC application
program will change and update the data being read and update the
data being read by the Logix controller. By using the Force Editor, you
can force changes to the input assembly and see this change reflected
in the Logix tag. In the example below, the Force Editor is configured
to display Signal_120_xxxx and Signal_121_xxxx. Signal_120_xxxx is
set in RSLogix Guard PLUS! software and the data is received in the
GPLC_Exclusive_Owner:I.Data tag in RSLogix 5000 software. Likewise,
after GPLC_Exclusive_Owner:O.Data is modified in RSLogix 5000
software, the changes are visible in the Signal_121_xxxx signals in
RSLogix Guard PLUS! software.
Note that the first four bytes in the GuardPLC controllers output
assembly, Signal_121_0001 to Signal_121_0004, are the Run/Idle
header received by the Logix controller.

For more information on forcing, refer to the Using RSLogix Guard


PLUS! Software with GuardPLC Controllers Programming Manual,
publication 1753-PM001.

Publication 1753-UM001C-EN-P - March 2010

227

Chapter 19

Use GuardPLC Controller as an Adapter

Remove or Inhibit a Connection


You can remove a connection in RSLogix 5000 software by going
offline, right-clicking the connection icon, and choosing Delete.
Download to apply the changes.
You can also Inhibit a connection in Run mode, by double-clicking
the connection icon and checking the Inhibit box on the Connection
tab.

Open a Class 3 Connection


from a Logix Controller

In a Class 3 connection, data is exchanged by using an explicit


message instruction (MSG). Every time the MSG is executed in the
Logix controller, data is exchanged with the GuardPLC controller.

Configure the GuardPLC Controller Assemblies


In RSLogix Guard PLUS! software, set up the appropriate assemblies
and connect the signals. In this example, we connected signals to the
input and output assemblies as shown below.
Make sure the Run/Idle header box is unchecked as Class 3
connections do not use a Run/Idle header.

228

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

Create a Project for the Logix Controller


1. In RSLogix 5000 software, create a new project for the Logix
controller.
2. Add the Ethernet adapter module to the I/O Configuration.
a. Right-click I/O Configuration and choose New Module.
b. In the Select Module Type dialog box, choose the 1756-ENBT
or 1756-ENET module type and click OK.
c. In the Module Properties dialog box, enter the IP address and
the slot number of the module.

d. Click Finish.
RSLogix 5000 software displays the new 1756-ENBT module
under the I/O Configuration.

Create Tags to Read and Write Assembly Data


1. Double-click Controller Tags and choose the Edit Tags tab.
2. Add an Enable BOOL tag, which will start the connected
messaging example.
3. Add a TIMER_CONN timer tag to set the packet rate for the Class
3 connection.
4. Create MSG_READ and MSG_WRITE message tags, which are
used for read and write messages.

Publication 1753-UM001C-EN-P - March 2010

229

Chapter 19

Use GuardPLC Controller as an Adapter

5. Add a ReadBuffer tag with type DINT[3] and a WriteBuffer tag


with type SINT[4].
These types correspond directly to the signal types of the
GuardPLC adapter assemblies. When explicit CIP messaging is
used to read and write assemblies, the tag being written to or
read from must be of the same or larger size than the assembly
size in the GuardPLC controller. The tag types should match the
signal types associated with the target assembly in RSLogix
Guard PLUS! software.
For more information on programming Logix controllers, refer to
the Logix5000 Controllers Common Procedures Programming
Manual, publication 1756-PM001

Create Ladder Logic


1. Switch to the Main Routine window in RSLogix 5000 software.
2. Build the first rung containing the following instructions:
Examine On Enable tag to start the connected messaging.
Examine Off TIMER_CONN.DN.
A timer instruction with the control tag TIMER_CONN and a
preset of 100. This is the rate at which Class 3 messages are
sent by the Logix controller.

3. Build the second run containing the following instructions:


Examine On Enable tag.
Examine On TIMER_CONN.DN.
Message instruction with the control tag MSG_READ.

230

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

4. Configure the message parameters as follows.

a. Set Service Type to Get Attribute Single.


b. Set Class to 4 (assembly)
c. Set Instance to 120. This is the assembly instance number that
will be read from.
d. Set Attribute to 3 (assembly data).
e. Set Destination to ReadBuffer.
5. Switch to the Communication tab and enter this text in the Path
field: ENBT,2,<GuardPLC IP address>.
Here, 2 is the EtherNet/IP port of the 1756-ENBT module.

Publication 1753-UM001C-EN-P - March 2010

231

Chapter 19

Use GuardPLC Controller as an Adapter

6. Check the Connected and then the Cache Connections boxes.


The Connected option ensures that messages are sent over a
Class 3 connection, not as unconnected ones.
Cache Connections is the default option. If it is checked, the
connection is opened the first time the controller is in Run mode
and the rung condition is true. In this example, the rung
condition is true when Enable value is true and the timer has
expired (DN flag is set). This connection remains open until the
controller goes to Program mode.
If Cache Connections is unchecked, a connection is opened
every time the controller is in Run mode and the rung condition
becomes true. The Logix controller opens the connection, sends
an explicit message over the new connection and then closes
the connection immediately. The next time the rung condition is
true, the whole sequence is repeated: open connection, send
message, close connection.
7. Build the third rung containing these instructions:
Examine on Enable tag
Examine on TIMER_CONN.DN
Message instruction with the control tag MSG_WRITE

8. Configure the message parameters as follows:


a. Set Service Type to Set Attribute Single.
b. Set Class to 4 (assembly).
c. Set Instance to 121.
This is the assembly instance number that will be written to.
d. Set Attribute to 3 (assembly data).
e. Set Source Element to WriteBuffer.
f. Set Source Length to 4 bytes.
The Source tag can be larger in size than the target GuardPLC
assembly. However, the Source Length should exactly match
the size of the assembly, otherwise an error occurs.

232

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

This Class 3 example uses the Cache Connections option. A


connection with this flag is opened when the controller switches to
Run mode and the rung condition is true. In our example, the rung
condition is true when Enable value is true and the timer has expired
(DN flag is set). When the rung condition is False, the connection
remains open.
If the Enable tag is changed to false, the connection still remains
open. To maintain the open connection, the Logix controller
periodically sends the last message with the same data sequence
number. This same data sequence number indicates to the GuardPLC
controller that this is just a keep alive message and that the data has
not changed. If this is a write message, the GuardPLC controller still
responds to it, but ignores the data that came with it because it knows
the data has not changed. This periodic frequency is set by default to
7.5 seconds, meaning that every 7.5 seconds a keep alive message
will be sent to keep the connection open.
Once Enable is set back to true, the messages are sent with every
transition of the rung condition from false to true. In this example, a
message is sent when the timer times out at 100 ms, and every time it
has a new data sequence count. So, if the write data changes, this
change is communicated to the GuardPLC controller no later than 100
ms past the data change tick.
The connection is closed when the controller transitions to Program
mode.

Download and Go to Run


1. Download to the Logix controller and switch the controller to
Run.
2. Set Enable to true.
Both messages should show the Done flag set. If an Error flag is set,
double-click the message instruction to see the error description.

Verify the Data Exchange


Follow these steps to verify the data exchange.
1. In RSLogix 5000 software, switch to the Controller Tags tab.

Publication 1753-UM001C-EN-P - March 2010

233

Chapter 19

Use GuardPLC Controller as an Adapter

2. Set the WriteBuffer display type to Hex. Enter 16#12, 16#34,


16#ab, 16#cd in the WriteBuffer.
3. Set the ReadBuffer type to Decimal.
The ReadBuffer is set to Decimal because RSLogix Guard PLUS!
software displays DINT types in decimal format only.
4. Configure the Force Editor menu in RSLogix Guard PLUS!
software to display all signals for assemblies IN_120 and
OUT_121.
5. Set signals for the IN_120 assembly to values 12345678,
13572468, 98765432.
6. Start forcing to send the new signal values.
7. Verify that RSLogix 5000 software displays the same values in
the ReadBuffer.
8. Verify that the OUT_121 signals show 16#12, 16#34, 16#ab,
16#cd.

234

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Use a GuardPLC Controller


as an Unconnected Adapter

Chapter 19

Using the GuardPLC controller as an unconnected adapter is similar to


using it as a Class 3 adapter. In both cases, an explicit message is sent
from the client to the GuardPLC controller, addressing one of the
built-in objects, including Identity, Assembly, PCCC, Connection
Configuration, Port, TCP/IP and Ethernet Link. In the case of an
unconnected adapter, the message is not sent over a connection, but
is sent as a single independent request.
The table below illustrates the differences between unconnected and
Class 3 connection requests.
Unconnected Request

Class 3 Connection Request

The request can be sent immediately over


an established TCP session.

The request requires a connection to be


established before it can be sent.

When the adapter goes offline, the client is


unaware until the next time a request is
sent.

The client is notified by the connection


timeout logic that the adapter is no longer
responding.

The adapter processes every request


independently from the previous ones.

The request is sent over an established


transport and, therefore, requires less
adapter processing.

In the case of a Logix controller, a client


request is sent every time the controller is
in the Run state and the rung condition is
true.

In the case of a Logix controller, a client


request is not only sent every time the
controller is in the Run state and the rung
condition is true, but is also sent
periodically to keep the connection open

TIP

In general, use a Class 3 connection when data should be


exchanged on a regular basis. Use unconnected requests when
data should be sent occasionally and the connection does not
need to be maintained.

To use the GuardPLC controller as an unconnected adapter with a


Logix controller, follow the steps in Open a Class 3 Connection from a
Logix Controller on page 228. However, when configuring the
message instruction, do not check the Connected box on the
Communication tab, as described on page 232.

Use Unconnected PCCC


Messaging from a PLC-5 or
SLC 5/05 Controller

The GuardPLC controller and PLC-5 or SLC 5/05 controllers exchange


data via PCCC read/write unconnected messages from the PLC-5 or
SLC 5/05 controller to the GuardPLC controller.
The PLC-5 or SLC 5/05 controllers and GuardPLC controllers must be
connected to the EtherNet/IP network. Channel 2 on the PLC-5
controller or Channel 1 on the SLC 5/05 controller must be configured
for EtherNet/IP communication.

Publication 1753-UM001C-EN-P - March 2010

235

Chapter 19

Use GuardPLC Controller as an Adapter

Refer to the Enhanced and Ethernet PLC-5 Programmable Controllers


User Manual, publication 1785-UM012, or to the SLC 500 Modular
Hardware Style User Manual, publication 1747-UM011, for more
information on configuring these controllers for Ethernet
communication.
You will also need RSLogix 5 programming software to configure the
PLC-5 controller or RSLogix 500 programming software to configure
the SLC 5/05 controller.
Follow these steps to enable communication between the GuardPLC
controller, acting as an adapter (target), and a PLC-5 or SLC 5/05
controller.
1. Create a GuardPLC adapter Assembly Instance (input or output),
including the data type, assembly size, and assembly name. See
pages 215 and 216.
TIP

Make sure the Run/Idle header box is unchecked as


PCCC messages do not use a Run/Idle header.

2. Configure an EtherNet/IP driver for the PLC-5 or SLC 5/05


controller by using RSLinx software.
3. Add a MSG instruction to the PLC-5 or SLC 5/05 application
program logic.
4. Save and download your application.
These steps are described in more detail beginning on page 237.
For detailed information on the MSG Instruction, refer to these
publications:
PLC-5 Programmable Controllers Instruction Set Reference
Manual, publication 1785-6.1.
SLC 500 Instruction Set Reference Manual, publication
1747-RM001.

236

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

Configure an EtherNet/IP Driver


If you are going to program the PLC-5 or SLC 5/05 controller via the
EtherNet/IP network, you must configure an EtherNet/IP driver in
RSLinx software to allow your PC to communicate with the PLC-5 or
SLC 5/05 controller.
1. Start RSLinx software.
2. Click the Configure Drivers button.
3. From the Available Driver Types pull-down menu, choose the
Ethernet/IP Driver.
4. Click Add New.
5. Enter a name for the new driver and click OK.

Create an EtherNet/IP Project in RSLogix Programming Software


Use RSLogix 5 programming software for PLC-5 controllers and
RSLogix 500 programming software for SLC 5/05 controllers. Follow
these steps to create an EtherNet/IP project in RSLogix software.
1. Open the appropriate programming software.
2. From the File menu, choose New.

Publication 1753-UM001C-EN-P - March 2010

237

Chapter 19

Use GuardPLC Controller as an Adapter

3. Enter a name for the processor and choose the EtherNet/IP


driver as shown below.

PLC-5 Controller

SLC 5/05 Controller

4. If your controller is a PLC-5 controller, configure the controller.


a. Expand the Project in the project tree, right-click Controller,
and choose Properties.

238

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

b. On the Controller Communications tab, choose the


EtherNet/IP communication driver you configured in RSLinx
software and click OK.

Add a Message Instruction to Your Application Program Logic


1. To allocate a MSG instruction control block, right-click Data Files
and choose New > Message.
PLC-5 Controller

SLC 5/05 Controller

For the SLC 5/05 controller, the number of elements must be at


least 93.

Publication 1753-UM001C-EN-P - March 2010

239

Chapter 19

Use GuardPLC Controller as an Adapter

The MSG control block appears in the project tree under Data
Files.

PLC-5 Message Control Block

2. Insert a MSG instruction rung and assign it to a MSG instruction


control block.
SLC 5/05 Controller

PLC-5 Controller

3. For an SLC 5/05 controller, edit the instruction parameters in the


as described below.
Parameter

Setting

Read/Write

Choose either Read or Write.

Target Device

PLC-5

Local/Remote

Local

Control Block

Enter an integer file with at least 93


elements.

Control Block Length

93 (This is automatically entered by


the programming software.)

4. Double-click Setup Screen in the MSG instruction to configure


the MSG instruction.

240

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

5. Configure the This Controller parameters.


SLC 5/05 Controller

PLC-5 Controller

Parameter

PLC-5 Controller Settings

Communication Command

Choose PLC-5 Typed Read or PLC-5 Typed Write Choose either PLC5 Read or PLC5 Write.

Data Table Address

Enter the source file address for a write or the


destination file address for a read.

Enter the source file address for a write or the


destination file address for a read.

Size in Elements

The number of items to read or write (11000).


The actual number of bytes transmitted is
based on the data type of the file specified in
the Data Table Address.

The number of items to read or write (11000).


The actual number of bytes transmitted is
based on the data type of the file specified in
the Data Table Address.

Port Number (for PLC-5 controllers)

Enter the Ethernet port number.

Enter 1 for the EtherNet/IP port.

Channel (for SLC 5/05 controllers)

SLC 5/05 Controller Settings

The onboard PLC-5E port number is 2.


The EtherNet/IP sidecar Ethernet port
number 3 A.

TIP

You cannot send a write message to an input assembly, for


example IN_120.
Input versus output assemblies are from the perspective of the
PLC-5 or SLC 5/05 controller, which sends the request to the
GuardPLC controller.

TIP

Publication 1753-UM001C-EN-P - March 2010

The GuardPLC controller supports only PLC-5 Typed Read and


Typed Write commands. No other PCCC commands work with
the GuardPLC controller on the EtherNet/IP network.

241

Chapter 19

Use GuardPLC Controller as an Adapter

6. Configure the Target Device (the GuardPLC controller)


parameters.
Parameter

PLC-5 Controller Settings

SLC 5/05 Controller Settings

Data Table Address

This is the GuardPLC assembly object. Enter the


text name of the GuardPLC assembly proceeded
by a $ and enclosed in double quotes. For
example, "$BLK_120:8:W".

This is the GuardPLC assembly object. Enter the


text name of the GuardPLC assembly proceeded
by a $ and enclosed in double quotes. For
example, "$BLK_121:6:W".

MultiHop

Choose Yes to configure MultiHop operation. The


Local/Remote parameter disappears and the
MultiHop tab becomes available.

Choose Yes to configure MultiHop operation. The


EtherNet/IP Address field disappears and the
MultiHop tab becomes available.

SLC 5/05 Controller

PLC-5 Controller

In the example above, the PLC-5 controller is configured to send a read


instruction to the GuardPLC controller. Four 16-bit words of data will be read
from a GuardPLC assembly named BLK_120 at an offset of eight 16-bit words.
The data will be placed into the PLC-5 controllers integer file number 7 at
offset 22.

In the example above, the SLC 5/05 controller is configured to send


a read instruction to the GuardPLC controller. Four 16-bit words of
data will be read from a GuardPLC assembly named BLK_121 at an
offset of six 16-bit words. The data will be placed into the SLC 5/05
controllers integer file number 7 at offset 0.

7. Click the MultiHop tab.


8. Press the Insert key to add the GuardPLC controller hop.

242

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

9. Enter the IP address of the GuardPLC controller.


SLC 5/05 Controller

PLC-5 Controller

Use Unconnected CIP


Messaging from a
PanelView Standard
Terminal

Use the Generic CIP message profile to configure the PanelView


Standard terminal to exchange data with the GuardPLC controller.
Both devices must be connected to the EtherNet/IP network. You will
need PanelBuilder32 software, version 3.82.xx or later, to configure
the PanelView Standard terminal.
Follow these steps to enable the PanelView Standard terminal to
message to the GuardPLC controller, acting as an adapter (target).
1. Create a GuardPLC Assembly Instance (input or output),
including the data type, assembly size, and assembly name. See
pages 215 and 216.
TIP

Make sure the Run/Idle header box is unchecked as


unconnected CIP messages do not use a Run/Idle
header.

2. Create a new EtherNet/IP application in PanelBuilder32


software.
3. Configure the PanelView terminal for EtherNet/IP
communication.
4. To perform read and write operations to the GuardPLC
controllers target assemblies, add objects to the PanelView
Standard terminals application. Configure those objects for read
or write operation, using tags.

Publication 1753-UM001C-EN-P - March 2010

243

Chapter 19

Use GuardPLC Controller as an Adapter

5. Save and download your application.


These steps are described in more detail beginning on page 244.
For more information on PanelView Standard terminals and using
PanelBuilder32 software, refer to the following:
PanelView Standard Operator Terminals User Manual,
publication 2711-UM014.
PanelBuilder32 Application Development Software for
PanelView Standard Terminals Quick Start, publication
2711-QS003.

Create an EtherNet/IP Application


Follow these steps to create a new EtherNet/IP application in
PanelBuilder32 software.
1. Select Create New Application from the PanelBuilder32 start-up
screen and click OK.

2. Enter a name for your application.


3. Select your PanelView terminal and EtherNet protocol.
4. Click OK.

244

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

Configure the PanelView Terminal for EtherNet/IP


Communication
Follow these steps to configure the PanelView terminal.
1. Double-click the Comms. Setup button on the Application
Settings dialog box.
2. When the Communications Setup - Ethernet dialog box opens,
press the Insert key.

3. Choose Generic CIP from the Node Type list.

Publication 1753-UM001C-EN-P - March 2010

245

Chapter 19

Use GuardPLC Controller as an Adapter

4. Enter the GuardPLC controllers Node Name and its EtherNet/IP


address.

5. Leave the Path field blank.


6. Click OK.

Configure a Write Operation


The example below configures the PanelView Standard terminal to
perform a write operation to set the preset value of a tag located in
the GuardPLC controllers target output assembly (OUT_120).
1. From the Objects menu, choose Numeric Entry > Cursor Point.
2. Position the pointer (+) on the application screen, hold down
the left mouse button and drag to draw the object on the screen.
The object is created with six ####### characters as a
placeholder for the numeric value. Each # character is a single
digit.
3. Double-click the object to open the Properties dialog box.
4. Check the Touch Cell checkbox.
5. Enter a name for the Write Tag.
6. Click the Edit Tag button to open the Tag Form dialog box.

246

Publication 1753-UM001C-EN-P - March 2010

Use GuardPLC Controller as an Adapter

Chapter 19

7. Configure the tag as shown below.

Parameter

Setting

Messaging Type

CIP

Node Name

Enter the name of the GuardPLC controller that will receive the command.

Service Code

Choose Set Attribute Single to indicate that this is a write operation.

Class Code

Enter 4, for an assembly object.

Instance Number

Enter 120 to indicate the GuardPLC target output assembly that was created for the
PanelView Standard terminal to write to.

Attribute

Enter 3 to provide access to the assembly object instance data.

Byte Offset

Index into the GuardPLC input assembly x number of bytes, then write the data.

Configure a Read Operation


This example configures the PanelView Standard terminal to perform
a read operation on the accumulated value of a tag located in the
GuardPLC controllers target input assembly (IN_121) at offset 4 bytes.
1. From the Objects menu, choose Numeric Display Data.
2. Position the pointer (+) on the application screen, hold down
the left mouse button and drag to draw the object on the screen.
The object is created with six ####### characters as a
placeholder for the numeric value. Each # character is a single
digit.
Publication 1753-UM001C-EN-P - March 2010

247

Chapter 19

Use GuardPLC Controller as an Adapter

3. Double-click the object to open the Properties dialog box.


4. Enter the desired Field Width and Decimal Point display
information.
5. Enter a name for the Read Tag.
6. Click the Edit Tag button to open the Tag Form dialog box.
7. Configure the tag as shown below.

248

Parameter

Setting

Messaging Type

CIP

Node Name

Enter the name of the GuardPLC controller that will receive the command.

Service Code

Choose Get Attribute Single to indicate that this is a read operation.

Class Code

Enter 4, for an assembly object.

Instance Number

Enter 121 to indicate the GuardPLC target input assembly that was created for the
PanelView Standard terminal to read from.

Attribute

Enter 3 to provide access to the assembly object instance data.

Byte Offset

Index into the GuardPLC output assembly x number of bytes, then read the data.

Publication 1753-UM001C-EN-P - March 2010

Chapter

20

Use the GuardPLC Controller as a Scanner


Introduction

Prepare the GuardPLC


Controller for Class 1
Scanner Connections

Topic

Page

Prepare the GuardPLC Controller for Class 1 Scanner Connections

249

Configure the EtherNet/IP Driver

252

Configure Connections in RSNetWorx for EtherNet/IP Software

254

Open a Connection to a Logix Controller

260

Save the Connection Configuration in the GuardPLC Controller

262

Remove the Connection Configuration

263

Make sure the GuardPLC controller resource has the EtherNet/IP


protocol added under the Protocols folder in the RSLogix Guard PLUS!
Hardware Management project tree. If it does not, see page 203 for
instructions on adding EtherNet/IP protocol to the project.

The GuardPLC controllers scanner I/O assembly consists of two


buffers: one to store input data and the other to store output data.
When a new connection is opened from the GuardPLC controller to
an I/O module, the scanner input buffer receives data from the I/O
module and the scanner output buffer stores data that is sent to the
I/O module.
You must allocate enough space in both of these buffers to store the
corresponding data. You do this by creating signals in the Signal
Editor and assigning them to the scanner assembly. For detailed
information on defining signals by using the Signal Editor, refer to the
Using RSLogix Guard PLUS! Software with GuardPLC Controllers
Programming Manual, publication 1753-PM001.

249Publication 1753-UM001C-EN-P - March 2010

249

Chapter 20

Use the GuardPLC Controller as a Scanner

Connect the Scanner Signals


1. Right-click Scanner and choose Connect Signals from the context
menu to open the Signal Connections dialog box.

2. Assign signals created in the Signal Editor by dragging them to


either the Input or Output tab on the Connect Signals dialog
box.
The Input tab contains all signals to be received from the target.
The Output tab contains all signals to be transmitted to the
target.

3. After the signals are assigned in the desired order, click New
Offsets and RSLogix Guard PLUS! software fills in the offsets
based on the type of signals you created.
You must make sure that the Scanner assembly is big enough to
establish the scanner connections. For example, when you establish a
connection from a GuardPLC controller to the 1794-OB16 FLEX I/O
module, up to 3 words of status may come from the FLEX I/O
module. One word of output data is sent to the digital output module.
This means that the input assembly should be at least 6 bytes in size
and the output assembly should be at least 2 bytes.
250

Publication 1753-UM001C-EN-P - March 2010

Use the GuardPLC Controller as a Scanner

Chapter 20

Also make sure that the data to be written or read does not cross data
type boundaries or try to use only a portion of the signal. In the
example above, you must assign 1 WORD or 1 INT signal, or 2 BYTE
signals to the output assembly and 6 BYTES, or 3 WORDs, or 3 INT
signals to the input tab. If any I/O module uses an odd number of
bytes, then you must use only BYTE data type signals. For example,
the 1734-IB4 module requires 2.5 WORDs or 5 BYTEs for the input
assembly. If you use anything other than BYTE signals, the GuardPLC
returns an error to RSNetWorx for EtherNet/IP software when you try
to save the scanlist.
TIP

The GuardPLC controller uses four input bytes for status. To


prevent this data from automatically being the first four data
signals, add four BYTE signals to the first 4 rows of the Inputs
tab. In RSNetWorx for EtherNet/IP software, offset 0 will be
TAG_000, as shown below.

Disable Scanner Function on the Controller


The controller is able to function as a scanner by default. Follow these
steps if you need to disable scanner function.
1. Right-click EtherNet/IP in the project tree under the desired
Resource and choose Connect Signals to open the Signal
Connections dialog box.
2. To open the Signal Editor, from the Signals menu, choose Editor.
3. Create a new signal of type BOOL and an initial value of 1.

Publication 1753-UM001C-EN-P - March 2010

251

Chapter 20

Use the GuardPLC Controller as a Scanner

4. Assign the signal to the Disable scanner signal in the signal


connections dialog box by dragging and dropping it in the
Signal field.

If this signal is TRUE, scanner functionality on the controller is


disabled. If this signal is FALSE, scanner functionality is enabled.

Configure the EtherNet/IP


Driver

1. Start RSLinx software.


2. Click the Configure Driver button.
3. From the list of Available Driver Types pull-down menu, choose
the Ethernet/IP Driver and click Add New.
4. Enter a name for the new driver and click OK.

252

Publication 1753-UM001C-EN-P - March 2010

Use the GuardPLC Controller as a Scanner

Chapter 20

5. In the Configure Drivers dialog box, leave Browse Local Subnet


checked and click OK.

TIP

The controllers will be recognized automatically if


they are in the same subnet. If the controller type or
name is unidentified, you must install the correct EDS
file.
EDS files are available on the RSLogix Guard PLUS!
software CD or at
http://support.rockwellautomation.com.

Publication 1753-UM001C-EN-P - March 2010

253

Chapter 20

Use the GuardPLC Controller as a Scanner

Configure Connections in
RSNetWorx for EtherNet/IP
Software

Before starting RSNetWorx for EtherNet/IP software and configuring


the GuardPLC controllers scanlist, make sure the GuardPLC controller
is in the STOP/VALID CONFIGURATION state, or RSNetWorx for
EtherNet/IP software will generate an error.
1. Start RSNetWorx for EtherNet/IP software.
2. To create a new configuration, from the File menu, choose New.

3. To go online, click the online button or, from the Network


menu, choose Online.
Your EtherNet/IP devices appear in the graphic view.

TIP

254

You may see icons overlaying the devices when you first
go online. This is normal and only indicates the status of
the offline versus the online configuration. Once you
complete the configuration, the symbols disappear.

Publication 1753-UM001C-EN-P - March 2010

Use the GuardPLC Controller as a Scanner

Chapter 20

4. Right-click the GuardPLC controller icon in the graphic view and


choose Scanlist Configuration to open the Scanlist Configuration
dialog box.

The GuardPLC controller is highlighted in the Scanlist


Configuration dialog box to show that it is the scanner in this
configuration.

Publication 1753-UM001C-EN-P - March 2010

255

Chapter 20

Use the GuardPLC Controller as a Scanner

5. Right-click the target I/O module in the Scanlist Configuration


dialog box and choose Insert Connection.

TIP

256

If the controller is in the RUN mode, a warning message


appears, instructing you to put the scanner into the
STOP/VALID CONFIGURATION mode before you attempt
to add connections.

Publication 1753-UM001C-EN-P - March 2010

Use the GuardPLC Controller as a Scanner

Chapter 20

6. Configure the Connection Properties for the I/O module, using


the Connection tab on the Connection Properties dialog box.

In a produce/consume system, modules multicast data, meaning


that multiple modules can receive the same data at the same
time from a single module. When you choose Connection
Name, in this dialog box, you must choose whether to establish
an owner or listen-only relationship with the module. An owner
connection is any connection that does not include Listen Only
in its Connection Name.
Property

Description
Some modules do not support all of the possible EtherNet/IP connection types: Exclusive Owner, Input Only, and Listen
Only. The Connection Name pulldown menu contains only the connection types supported by the selected module.

Connection
Name

Exclusive
Owner

When the exclusive owner type is used, output assemblies can be written. Only one exclusive owner
connection is allowed to connect to a single output assembly. Multiple Exclusive Owner connections can
be made to input only modules. Any module that contains output assemblies can have only one Exclusive
Owner.

Input Only

An input only connection lets input assemblies be exported to one or more consumers. Another connection
request to the same input connection can be made if the same data size and requested packet rate are
specified. All Input Only connections are independent of one another. When one of the connections is
closed, the others remain open.

Listen Only

With listen only connections, input assemblies are sent to one or more consumers. For a listen-only
connection to be established, an exclusive owner or input only connection with multicast must already
exist. All the subsequent Listen Only connections depend upon the owner connection. When an owner
connection is closed, all subsequent Listen Only connections are also closed.

Enter the Requested Packet Interval (RPI) in ms. The RPI specifies the period at which data updates over a connection.
Requested
Packet Interval The RPI is entered in 1 ms increments. The RPI specified for the GuardPLC controller can be as little as 1 ms. However,
the GuardPLC controller will not produce or consume data with a rate less than 2 ms, because this is the tick of the
(RPI)
GuardPLC communication module. This limits the minimum RPI to 2 ms.

Publication 1753-UM001C-EN-P - March 2010

257

Chapter 20

Use the GuardPLC Controller as a Scanner

Property

Description

Input Size

Input size is the length of the data sent from the I/O module (target) to the GuardPLC controller (scanner). The value in
this field is predetermined by the module type and cannot be changed.

Output Size

Output size is the length of the data sent from the GuardPLC controller (scanner) to the I/O module (target). The value in
this field is predetermined by the module type and cannot be changed.

Configuration
Size

Configuration Size is the size of the configuration data sent with the connection establishment request.

Input Address

The Input Address is the offset in words of the GuardPLC input scanner assembly where the GuardPLC controller will
store the input data from the target device. Enter the Input Address.

Output
Address

The Output Address is the offset in words of the GuardPLC controllers scanner output assembly buffer where the
GuardPLC controller will store its data before sending it to the target device, in this case the FLEX I/O module.

7. Once you have set these properties, click the OK button to


apply the changes.
RSNetWorx for EtherNet/IP software displays these changes in
blue under the I/O module entry.

8. Repeat steps 57 for all target I/O modules and press the Save
button to download the connection configuration to the
GuardPLC controller.
If you get a Type error and the save procedure is
TIP
aborted, it is most likely a data type error with the
signals in the RSLogix Guard PLUS! software scanner
configuration. Make sure that you have not tried to cross
a data type boundary or that you have not used a module
with an odd number of bytes with INT or WORD data
types.

258

Publication 1753-UM001C-EN-P - March 2010

Use the GuardPLC Controller as a Scanner

Chapter 20

9. In RSLogix Guard PLUS! software, put the GuardPLC controller


into RUN mode.
The configuration is now complete and the I/O modules should
be working under the control of the GuardPLC controller.

10. To view the status of the connection in RSNetWorx for


EtherNet/IP software, click the Connection Status tab.
Every connection in the GuardPLC controller is listed on this
screen. Any non-working connections are also listed.

11. You can also verify the connection status in RSLogix Guard
PLUS! software.
a. Open the Control Panel by choosing Control Panel from the
Online menu.
b. Click the EIP tab.
c. Click the Connections Status tab.

For more information on the Control Panel, see Chapter 14.

Publication 1753-UM001C-EN-P - March 2010

259

Chapter 20

Use the GuardPLC Controller as a Scanner

Open a Connection to a
Logix Controller

The GuardPLC controller can establish a connection to a ControlLogix


or CompactLogix controller and read the data over this connection.
The data must be stored in the producing data tag in the Logix
controller. The data exchange is one-sided, from the Logix controller
to the GuardPLC controller. For exchanging data in both directions,
see Open a Class 1 Connection from a Logix Controller to the
GuardPLC Controller on page 219.

Create a Producing Data Tag


1. Open your RSLogix 5000 project.
2. Click the Edit Tags tab.
3. Right-click an empty line and choose Edit Tag Properties.

4. Enter the tag name.


5. Set the tag type as Produced.
The Number of Consumers parameter dictates how many
scanners should be able to read from this tag at the same time.
6. Enter the Data Type.
7. Click OK to save the changes.

260

Publication 1753-UM001C-EN-P - March 2010

Use the GuardPLC Controller as a Scanner

Chapter 20

For more information on configuring Logix controllers, refer to


Logix5000 Controllers Quick Start, publication 1756-QS001.

Configure Connections from the GuardPLC Controller to the Logix


Controller
1. In RSNetWorx for EtherNet/IP software, right-click the GuardPLC
scanner controller in the graphic view and choose Scanlist
Configuration.
2. Right-click the target Logix controller in the Scanlist
Configuration dialog box and choose Insert Connection.
3. In this example, the Connection Name is Receive Data From.

4. Enter the name of the producing tag in the Communication


Parameters Value field.
5. Make sure that the Input Size value matches the size of the
producing tag.
6. Once you have set these properties, click the OK button to
apply the changes.
RSNetWorx for EtherNet/IP software displays these changes in
blue under the I/O module entry.
7. Click Save in RSNetWorx for EtherNet/IP software to download
the configuration to the GuardPLC controller.
Publication 1753-UM001C-EN-P - March 2010

261

Chapter 20

Use the GuardPLC Controller as a Scanner

Save the Connection


Configuration in the
GuardPLC Controller

Up to this point, only the configuration has been downloaded to the


GuardPLC controller. The offline project currently contains only the
assigned signal connections.
Once the connection configuration is saved with the RSLogix Guard
PLUS! project, you can switch to other projects, reprogram the
GuardPLC controller, and be sure that when the configuration is
loaded back to the GuardPLC controller, it will use this RSNetWorx
configuration to reestablish connections.
Follow these steps to upload the online configuration to your offline
project.
1. Open the Control Panel in RSLogix Guard PLUS! Hardware
Management by choosing Control Panel from the Online menu.
2. Click the EIP tab.
3. Press the FS Upload button to upload the connection
configuration and add it to the project configuration.
An RSNetWorx Configuration sub-branch will be added to the
project tree under the EtherNet/IP Scanner branch.

4. Right-click the controller Resource in the project tree and choose


Code Generation to compile the configuration code.

262

Publication 1753-UM001C-EN-P - March 2010

Use the GuardPLC Controller as a Scanner

Remove the Connection


Configuration

Chapter 20

You can also remove a connection configuration from a project.


1. Click the RSNetWorx Configuration under the EtherNet/IP
Scanner branch and press the Delete key.
RSLogix Guard PLUS! software removes the RSNetWorx
Configuration branch.
2. Right-click the controller Resource and choose Code Generation
to save the change to the project.

Publication 1753-UM001C-EN-P - March 2010

263

Chapter 20

Use the GuardPLC Controller as a Scanner

Notes:

264

Publication 1753-UM001C-EN-P - March 2010

Chapter

21

Communicate with ASCII Devices


Introduction

Connect the Controller to an


ASCII Device

Topic

Page

Connect the Controller to an ASCII Device

265

Configure the ASCII Serial Port

268

Connect Signals

269

ASCII Protocol

270

For the sole purpose of sending the status of the signals from the
GuardPLC controller to an external device, you can connect an
intelligent ASCII device to the GuardPLC controllers serial port. This
ASCII connection is one-way from the GuardPLC controller (slave) to
the master device. You cannot program the GuardPLC controller or
change the values in the GuardPLC controller by using this port.
To use the ASCII function, signals that you wish to send out the serial
port must be connected to placeholders in the ASCII-protocol Connect
Signals dialog box. These signals are then capable of being sent out
the serial port if a command string is properly received from the
master. The command string includes a starting address and number
of signals to be sent. The GuardPLC controller replies to this
command string by sending the values of these signals out the serial
port in an ASCII string.

Connect to a GuardPLC 1200 Controller

PLC
1200

RS-232
ASCII
serial port

Use a 1761-CBL-PM02 series C cable to connect to the serial port. The


mini-DIN connector attaches to the controller. The other end is a 9-pin

265Publication 1753-UM001C-EN-P - March 2010

265

Chapter 21

Communicate with ASCII Devices

D-shell connector. This mini-DIN connector is not commercially


available, so you cannot make this cable.
The pin assignment of the ASCII Serial port is shown below.
2

4
3

5
6

8
7

Pin

Function

24V DC

ground (GND)

request to send (RTS)

received data (RxD)

received line signal detector (DCD)

clear to send (CTS)

transmitted data (TxD)

ground (GND)

not applicable

Connect to a GuardPLC 1600 or 1800 Controller


The ASCII COMM3 port location and connector pin assignment are
shown below.

3 ()

()

L-

L+

L+

24V DC
RS-485
ASCII
COMM3

COMM2

10/100 BaseT

266

Signal

Function

---

---

RP

5V, decoupled with diodes

RxD/TxD-A

Receive/Transmit data A

CNTR-A

DGND

VP

5V, positive pole of supply voltage

---

---

RxD/TxD-B

CNTR-B

Control Signal A

PROFIBUS

GuardPLC Ethernet
3 ()

Connection

()

COMM1

IMPORTANT

Data reference potential

Receive/Transmit data B
Control Signal B

The ASCII port is RS-485. You must use an electrical interface


device to connect the controller to an RS-232 device.

Publication 1753-UM001C-EN-P - March 2010

Communicate with ASCII Devices

Chapter 21

Connect to a GuardPLC 2000 Controller

1755PB720

1755L1

RUN STOP
PROG

FAULT

FORCE

GuardPLC 2000

1755IB24XOB16

1755IB24XOB16

RUN ERR

RUN

RUN ERR

1755IF8

ERR

RUN

ERR

1755OF8

RUN ERR

1755HSC

1755HSC

RUN ERR

RUN ERR

LS+ 1

I1+

O1+

C-

C-

I1

I1

I-

O1-

A1

A1

I2

I2

I2+

O2+

B1

B1

I3

I3

I-

O2-

Z1

Z1

I4

I4

I3+

O3+

C1

C1

I5

I5

I-

O3-

C-

C-

I6

I6

I4+

O4+

C-

C-

I7

I7

I-

O4-

C-

C-

I8

I8

C-

C-

10

LS+ 10

10

C-

10

C-

LS+ 1

Tx COL

10/100BaseT

3V DC
LITH-BATT.

24V

FAULT

3,3V

5V
RESTART

1
FB1

2
3

FAULT

LS+ 10

11

I5+/1- 10

O5+

I-

11

I9

11

O5-

11

A2

11

A2

12

I10 12

I10 12

I6+/2- 12

O6+

12

B2

12

B2

13

I11 13

I11 13

I-

13

O6-

13

Z2

13

Z2

14

I12 14

I12 14

I7+/3- 14

O7+

14

C2

14

C2

15

I13 15

I13 15

I-

15

O7-

15

C-

15

C-

16

I14 16

I14 16

I8+/4- 16

O8+

16

C-

16

C-

17

I15 17

I15 17

I-

O8-

17

C-

17

C-

18

I16 18

I16 18

18

C-

18

C-

19

LS+ 19

LS+

20

I17 20

I17

21

I18 21

I18

22

I19 22

I19

23

I20 23

I20

24

I21 24

I21

25

I22 25

I22

26

I23 26

I23

27

I24 27

I24

28

L-

28

L-

19

L- 19

L-

29

O1

29

O1

20

20

30

O2

30

O2

21

21

31

O3

31

O3

22

22

32

O4

32

O4

23

23

33

O5

33

O5

24

L- 24

L-

34

O6

34

O6

25

L- 25

L-

35

O7

35

O7

26

L- 26

L-

36

O8

36

O8

27

L- 27

L-

37

L-

37

L-

38

O9

38

O9

39

O10 39

O10

40

O11 40

O11

41

O12 41

O12

42

O13 42

O13

43

O14 43

O14

44

O15 44

O15

45

O16 45

O16

I9

11

17
18

FB2

RS-232 ASCII serial port


(only the bottom serial port is active)

L+
DC 24V
L-

PS

CPU

DIO

DIO

AI

AO

CO

CO

The serial port requires a 9-pin D-shell connector.


Pin

Publication 1753-UM001C-EN-P - March 2010

Function
1

none

send data

receive data

none

ground

none

RTS

CTS

none

267

Chapter 21

Communicate with ASCII Devices

Configure the ASCII Serial


Port

You must either create a new project or open an existing project


before you can configure ASCII communication. Once the software
opens a project, it automatically displays the Hardware Management
window, from which you configure the ASCII port.
1. Right-click Protocols and choose New>ASCII.

2. Right-click the ASCII icon and choose Properties.

For this field

Specify

Slave Address

the slave address (165535) of the controller. The ASCII protocol of the controller supports only a
direct point-to-point connection between the master and slave.
The controller is always configured as slave. It only transfers process values via the serial interface
to the master when it receives the corresponding request from the master.

Refresh Rate

the refresh rate in milliseconds for non-safe communication between the COM and CPU.
The default is 0, the fastest refresh rate.

Interface

the field bus interface to be used by the ASCII protocol (comm1, comm2, comm3).
Choose comm3 for GuardPLC 1600 or 1800 controllers.

Baud Rate(1)

the data transfer speed in bits/s. Choose from a pull-down menu of predefined values between 300
and 115,200 bps. The default baud rate is 9600 bps.

Parity

the parity for the recognition of transfer errors. Choose No, Odd, or Even. The default is No parity.

Stop Bit

either 1 or 2 stop bits for the serial data transfer. The default is 1 stop bit.

(1) Even if the baud rate is changed from 9600, the power-up string is always sent out at 9600 baud.

268

Publication 1753-UM001C-EN-P - March 2010

Communicate with ASCII Devices

Connect Signals

Chapter 21

Only ASCII output signals are sent from the controller. You connect
signals to the ASCII outputs to determine which signal values you
want to send from the controller to the connected ASCII device.
1. Expand Protocols, right-click the ASCII icon and choose Connect
Signals.

If you want to

Choose this tab

create a new signal

New Connected Signal

renumber offsets sequentially for all signals

New Offsets

delete the selected signal

Delete Connected Signal

2. Edit the output signals you want to send to the ASCII device.
Use the Outputs tab to define output values to send to the
ASCII device.
Associate each output with a signal from the signal editor by
dragging the signal from the Signal Editor to the Signal field
on the Outputs tab in the ASCII Signal Connections dialog
box.
Refer to the Using RSLogix Guard PLUS! Software With
GuardPLC Controllers Programming Manual, publication
1753-PM001, for more information on defining signals.

The signal name is used


only in printouts.

Publication 1753-UM001C-EN-P - March 2010

269

Chapter 21

Communicate with ASCII Devices

The offset in the ASCII output section is numbered based on bytes. In the example, the first signal uses
bytes 0, 1, 2, and 3. The second signal uses bytes 4 and 5. However, when you request these signals in
the command string (see ASCII Master - Request below), the first signal is always 0, the second signal
is always 1, the third signal is always 2, and so forth.

TIP

The output section automatically sorts the name field based on alphanumerical order. This does not
automatically change the offsets, but if you renumber after sorting, the offsets will change and there is
no undo feature. This changes the order in which the signals are sent out the serial port.
Because names are used only in printouts, you may want to enter these names in alphanumeric order
to begin with. (For example signal 101, signal 102, signal 103, signal 104, and so forth.)

ASCII Protocol

The controller is a slave ASCII device and expects this protocol from
the master device.

ASCII Master - Request


If the ASCII master sends a request, the slave can send a response.
The master request has this format (each character is one byte).
Start Sign

Destination

Source

Function Code

Start Address

Number of
Variables

End Sign

1 char

2 char

2 char

1 char

5 char

3 char

1 char

270

Component

Description

Start Sign

identifies the start of a message


^ character

Destination

unique slave address (GuardPLC controller)


0199

Source

unique master address (requester)


0199

Function Code

read data
R character

Start Address

data start address for characters to read (offset)


0000065535

Number of Variables

number of variables to read and send back to master


000999

End Sign

identifies the end of a message


& character

Publication 1753-UM001C-EN-P - March 2010

Communicate with ASCII Devices

Chapter 21

For example, this string requests the first two variables from the slave.
Start Sign

Destination

Source

Function Code

Start Address

Number of
Variables

End Sign

15

01

00000

002

&

ASCII Slave - Controller Response


If the controller receives a request from an ASCII master, it responds
in this format (each character is one byte).
Start Sign

Destination

Source

Function
Code

Start
Address

Number of
Variables

Number of Data
Characters

End Sign

1 char

2 char

2 char

1 char

5 char

3 char

4 char

1 char

Publication 1753-UM001C-EN-P - March 2010

maximum
10000 char

Component

Description

Start Sign

identifies the start of a message


^ character

Destination

unique master address (requester)


0199

Source

unique slave address (GuardPLC controller)


0199

Function Code

r character identifies data sent by slave


E identifies error with master request

Start Address

data start address for characters to read (offset)


0000065535

Number of Variables

number of variables to read and send back to master


000999

Number of Characters

number of characters in the data string (This includes


the / delimiter but not the & termination character.)
00009999

Data

data characters

End Sign

needed to recognize the end of a message


& character

271

Chapter 21

Communicate with ASCII Devices

For example, this string replies to the master request for the first two
variables from the slave.
Start Sign

Destination

Source

Function
Code

Start
Address

Number of
Variables

Number of Data
Characters

End Sign

01

15

00000

002

0005

&

4/123

Every data field in the message is separated with a slash ( / ). The


slash also counts as a character when counting the total number of
characters in the data string.
The reply string will have a variable number of characters if
non-BOOL are used. For example, 99 is 2 characters, 100 is 3
characters. There is no leading zero.

TIP

If the master request was not received properly at the GuardPLC


controller, the slave response is the following.
Start Sign

Destination

Source

Function
Code

Start
Address

Number of
Variables

Number of End Sign


Characters

01

15

00000

000

0000

&

This error response is typically sent when more signals are requested
than exist in the ASCII protocol output tab. For example, 10 signals
were dragged to the ASCII output section, but 20 signals were
requested in the command string.

272

Publication 1753-UM001C-EN-P - March 2010

Communicate with ASCII Devices

Chapter 21

Data Type Formats


Follow these formats for sending different data types.
Data Type

Format

BOOL

Description:
Size:
Range:

boolean
1 character
1 = true; 0 = false

0
1

SINT

Description:
Size:
Range:

short integer
14 characters
-128127

-101
5
127
-128

INT

Description:
Size:
Range:

integer
16 characters
-3276832767

-25724
232
-6
248

DINT

Description:
Size:
Range:

double integer
111 characters
-21474836482147483647

-1357679042
257
6200471

USINT

Description:
Size:
Range:

unsigned short integer


13 characters
0 255

123
35
6
255

UINT

Description:
Size:
Range:

unsigned integer
15 characters
0 65535

65535
7
333
597

UDINT

Description:
Size:
Range:

unsigned double integer


110 characters
04294967295

4294967295
256
334510

Publication 1753-UM001C-EN-P - March 2010

Example

273

Chapter 21

Communicate with ASCII Devices

Notes:

274

Publication 1753-UM001C-EN-P - March 2010

Chapter

22

Communicate with Modbus and Profibus


Devices

Introduction

Modbus RTU Slave


Protocol

Topic

Page

Modbus RTU Slave Protocol

275

Connect the Controller to a Modbus Device

276

Configure the Modbus Serial Port

276

Connect Signals

277

Profibus DP Slave Protocol

279

Connect the Controller to a Profibus DP Device

279

Configure the Profibus DP Serial Port

280

Connect Signals

280

Configure the Profibus Master

282

Modbus is available only on GuardPLC 1600 or 1800 controllers. You


can connect a Modbus master to the controllers COMM1 port. This
Modbus connection is two-way non-safety-related communication
between the controller (slave) and the master device. You cannot
program the controller by using this port.
The controller is a Modbus RTU slave device and responds only to
reads and writes from the master.
To use the Modbus function, signals that you wish to send out/receive
into the COMM1 port must be connected to placeholders in the
Modbus-protocol Connect Signals dialog box.

275Publication 1753-UM001C-EN-P - March 2010

275

Chapter 22

Communicate with Modbus and Profibus Devices

Connect the Controller to a Modbus Device

()

()

L-

L+

Signal

Function

---

---

RP

5V, decoupled with diodes

RxD/TxD-A

Receive/Transmit data A

CNTR-A

Control Signal A

DGND

Data reference potential

VP

5V, positive pole of supply voltage

---

---

RxD/TxD-B

Receive/Transmit data B

CNTR-B

Control Signal B

L+

24V DC
RS-485
ASCII

MODBUS

COMM3

COMM2

COMM1

RS-485

GuardPLC Ethernet

10/100 BaseT
3

Connection

()

()

IMPORTANT

The Modbus port is RS-485. You must use an electrical


interface device to connect the controller to an RS-232 device.

Configure the Modbus Serial Port


You must either create a new project or open an existing project
before you can configure Modbus communication. Once the software
opens a project, it automatically displays the Hardware Management
window, from which you configure the Modbus port.
1. Right-click Protocols and choose New>Modbus Slave.

276

Publication 1753-UM001C-EN-P - March 2010

Communicate with Modbus and Profibus Devices

Chapter 22

2. Expand Protocols, right-click the Modbus Slave icon, and choose


Properties.

For this field

Specify

Slave Address

the slave address (1247) of the controller. The Modbus protocol of the controller supports only a
direct point-to-point connection between the master and slave.
The controller is always configured as slave. It transfers process values via the serial interface to
the master only when it receives the corresponding request from the master.

Interface

the field bus interface to be used by the Modbus Slave protocol (comm1, comm2, comm3).
Choose comm1 for GuardPLC 1600 or 1800 controllers.

Refresh Rate

Refresh rate in ms for non-safe communication. The default is 0, the fastest refresh rate.

Baud Rate

the data transfer speed in bits/s. Choose from a pull-down menu of predefined values between
300 and 115,200 bps. The default baud rate is 9600 bps.

Parity

the parity for the recognition of transfer errors. Choose No, Odd, or Even. The default is No parity.

Stop Bit

either 1 or 2 stop bits for the serial data transfer. The default is 1 stop bit.

Connect Signals
The Modbus RTU Slave protocol lets you read data from the
GuardPLC controller and write data to the GuardPLC controller, but
none of this data can be used for safety functions.
Inputs are signals sent from the Modbus master to the controller
(slave). Outputs are signals sent from the controller (slave) to the
master.

Publication 1753-UM001C-EN-P - March 2010

277

Chapter 22

Communicate with Modbus and Profibus Devices

Follow these steps to connect signals.


1. Expand Protocols, right-click the Modbus Slave icon, and choose
Connect Signals.

If you want to

Click this tab

create a new signal

New Connected Signal

renumber offsets sequentially for all signals

New Offsets

delete the selected signal

Delete Connected Signal

2. Edit the signals you want to receive or send.


Use the Inputs tab to determine which values to read into the
controller.
Use the Outputs tab to define output values to send to the
Modbus master. Signals in the output tab must match the
order of signal types requested by the Modbus master.
Associate each input or output with a signal from the signal
editor. You can drag and drop signals from the signal editor
to the signal connections dialog box.
The Modbus function calls must match the order in which the signal
offsets appear. For example, if you want to read 3 Boolean signals
followed by 4 Registers, the first 3 signals must be BOOL and the next
4 must be INT signals.

TIP

The output section automatically sorts the name field based on alphanumerical order. This does not
automatically change the offsets, but if you renumber after sorting, the offsets will change and there is
no undo feature. This changes the order in which the signals are sent out the serial port.
Because names are used only in printouts, you may want to enter these names in alphanumeric order
to begin with. (For example signal 101, signal 102, signal 103, signal 104, and so forth.)

278

Publication 1753-UM001C-EN-P - March 2010

Communicate with Modbus and Profibus Devices

Profibus DP Slave Protocol

Chapter 22

Profibus DP Slave protocol is available only via the GuardPLC 1600


and 1800 controllers COMM1 port. This connection is two-way
non-safety-related communication from the controller (slave) to the
master device. You cannot program the controller by using this port.
To use the Profibus DP function, signals that you wish to send out the
COMM1 port must be connected to placeholders in the Profibus
DP-protocol Connect Signals dialog box.

Connect the Controller to a Profibus DP Device


3 ()

()

L-

L+

L+

24V DC

Connection

Signal

Function

---

---

RP

5V, decoupled with diodes

RxD/TxD-A

Receive/Transmit data A

CNTR-A

Control Signal A

DGND

Data reference potential

VP

5V, positive pole of supply voltage

---

---

RxD/TxD-B

Receive/Transmit data B

CNTR-B

Control Signal B

RS-485
ASCII
COMM3

PROFIBUS
COMM2

COMM1

RS-485

GuardPLC Ethernet

10/100 BaseT
3 ()

()

IMPORTANT

Publication 1753-UM001C-EN-P - March 2010

The Profibus port is RS-485. You must use an electrical


interface device to connect the controller to an RS-232 device.

279

Chapter 22

Communicate with Modbus and Profibus Devices

Configure the Profibus DP Serial Port


You must either create a new project or open an existing project
before you can configure Profibus DP communication. Once the
software opens a project, it automatically displays the Hardware
Management window, from which you configure the Profibus port.
1. Right-click Protocols and choose New>Profibus dp Slave.

2. Expand Protocols, right-click the Profibus dp Slave icon, and


choose Properties.

For this field

Specify

Station Address

the address that uniquely identifies the Profibus dp slave on the network.
The station address must be less than or equal to 126.

Refresh Rate

Refresh rate in ms for non-safe communication. The default is 0, the fastest refresh rate.

Interface

the field bus interface to be used by the Profibus dp Slave protocol (comm1, comm2, comm3).
Choose comm1 for GuardPLC 1600 or 1800 controllers.

Baud Rate

the data transfer speed in bits/s. Choose from a pull-down menu of predefined values between
300 and 115,200 bps. The default baud rate is 9600 bps.

Connect Signals
The Profibus DP Slave protocol lets you read data from the GuardPLC
controller and write data to the GuardPLC controller, but none of this
data can be used for safety functions.

280

Publication 1753-UM001C-EN-P - March 2010

Communicate with Modbus and Profibus Devices

Chapter 22

Inputs are signals sent from the Profibus master to the controller
(slave). Outputs are signals sent from the controller (slave) to the
master.
1. Expand Protocols, right-click the Profibus-dp Slave icon, and
choose Connect Signals.

If you want to

Click this tab

create a new signal

New Connected Signal

renumber offsets sequentially for all signals

New Offsets

delete the selected signal

Delete Connected Signal

2. Edit the signals you want to receive or send:


Use the Inputs tab to determine which values to read into the
controller. The Inputs tab contains pre-defined system
variables that can be interrogated via the assignment of
signals.
Use the Outputs tab to define output values to send to the
Profibus master.
Associate each input or output with a signal from the signal
editor. You can drag and drop signals from the signal editor
to the signal connections dialog box.

Publication 1753-UM001C-EN-P - March 2010

281

Chapter 22

Communicate with Modbus and Profibus Devices

3. Click New Offsets to automatically calculate the offsets for the


new signals.

IMPORTANT

Due to the offsets of the system variables, the offset of the first
input signal must begin with 12. The offset for the first output
signal begins with 0.
The Profibus ID for the first input signal is 0.

Configure the Profibus Master


For both the Profibus output and input signals, the Profibus ID of the
first signal to communicate, the number of signals, and the number of
bytes must be configured in the Profibus Master.
Configuration is accomplished via parameter data read from a GSD
file. The parameter data consists of 32 bytes in hexadecimal format,
which may be displayed in different ways depending upon the
Profibus DP master software.
The GSD file for GuardPLC 1600 and GuardPLC 1800 controllers is
available on the RSLogix Guard PLUS! software CD.
For more information on using Profibus protocol, consult the online
Help.

282

Publication 1753-UM001C-EN-P - March 2010

Appendix

Specifications

GuardPLC 1200 Controller

Attribute

1754-L28BBB

Controller
User Memory

500 KB application code memory


500 KB application data memory

Digital Inputs
Number of inputs

20 (not electrically isolated from each other, isolated from


the backplane)

Nominal input voltage

24V DC

On-state voltage

10V DC30V DC

On-state current

2 mA @ 10V DC, 13 mA @ 30V DC

Off-state voltage, max

5V DC (max)

Off-state current, max

1.5 mA max (1 mA @ 5V)

Digital Outputs
Number of outputs

8 (not electrically isolated from each other, isolated from


the backplane)

Output voltage range

18.4V26.8V

Output current

0.5 A per channel (channel 16)


2 A per channel (channel 7, 8)

Surge current per channel

1 A for 10 ms @ 1 Hz (channel 16)


4 A for 10 ms @ 1 Hz (channel 7, 8)

Minimum current load

2.5 mA per channel

On-state voltage drop, max

2.0V DC @ 500 mA

Off-state leakage current,


max

1 mA per channel

Temporary overload

Output switches off until overload is eliminated

Counters

Publication 1753-UM001C-EN-P - March 2010

Number of counters

Inputs per counter

3 (Input A, Input B, Z/Gate/Reset)

Counter resolution

24 bit

Input frequency, max

100 kHz in counter modes (input A)

Trigger

Negative edge

Edge steepness

1 V/s

Duty cycle

50% @ 100 kHz

Input voltages

4.5V5.5V for 5V input


13V26.4V for 24V input

Input current

Typ. 15 mA, 3 mA

283

Appendix A

Specifications

Attribute

1754-L28BBB

Power Supply
Supply Voltage (L+)

24V DC

Supply voltage range

20.4V DC28.8V DC (10 ms buffer), ripple 15%

Power rating, max

8 A (1 A to run the controller, 7 A for inputs and outputs)

Environmental Conditions
Temperature, operating

0 60 C (32140F)

Temperature, storage

-4085 C (-40185F) without back-up battery

Mechanical Dimensions
Width x height x depth

160 mm x 112 mm x 90 mm (6.3 in. x 4.41 in. x 3.54 in.)

Weight

680 g (1.5 lb)

Certifications (when product is marked)


c-UL-us

UL Listed Industrial Control Equipment, certified for US


and Canada

CE

European Union 89/336/EEC EMC Directive, compliant


with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
EN61131-2; Programmable Controllers (Clause 8, Zone
A, B, & C)

GuardPLC 1600 Controller

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

Functional Safety

Certified by TV

Attribute

1753-L28BBBM and 1753-L28BBBP

Controller

284

User memory, max

250 KB user program memory


250 KB application data memory

Watchdog time, min

10 ms

Safety time, min

20 ms

Current consumption

8 A max (with max load)


0.5 A idle current (just running the controller)

Operating voltage

24V DC, -15%+20%, wss 15% (from a power supply with


protective separation conforming to IEC 61131-2 requirements)

GuardPLC Ethernet
interfaces

4 x RJ-45, 10/100BaseT (with 100 Mbps) with integrated switch

Protection

IP20

Publication 1753-UM001C-EN-P - March 2010

Specifications

Attribute

Appendix A

1753-L28BBBM and 1753-L28BBBP

Digital Inputs
Number of inputs

20 (not electrically isolated)

Voltage, on-state

15V 30V DC

Current consumption,
on-state

2 mA @ 15V
7.5 mA @ 30V

Voltage, off-state,
max

5V DC

Current consumption,
off-state, max

1.5 mA (1 mA @ 5V)

Switching point,
typical

7.5V

Supply

5 x 20V / 100 mA @ 24V short-circuit proof

Digital Outputs
Number of Outputs

8 (not electrically isolated)

Output voltage range

18.4V 26.8V

Output current

Channels 13 and 57: 0.5 A @ 60 C (140 F)


Channels 4 and 8: 1 A @ 60 C (140 F); 2A @ 50 C (122 C)

Surge current per


channel

1 A for 10ms @ 1 Hz (Channels 13 and 57)


4 A for 10ms @ 1 Hz (Channels 4 and 8)

Current load, min

2 mA per channel

On-state voltage drop, 2.0V DC @ 2 A


max
Off-state leakage
current, max

1 mA @ 2V

Environmental Conditions
Temperature,
operating

060 C (32140 F)

Temperature, storage

-4085 C (-40185 F)

Mechanical Dimensions
Width

Publication 1753-UM001C-EN-P - March 2010

257 mm (10.1 in.) including housing screws

Height

114 mm (4.49 in.) including latch

Depth

66 mm (2.60 in.) including grounding bolt

Weight

1.2 kg (2.64 lb)

285

Appendix A

Specifications

Attribute

1753-L28BBBM and 1753-L28BBBP

Certifications (when product is marked)


c-UL-us

UL Listed Industrial Control Equipment, certified for US and


Canada

CE

European Union 89/336/EEC EMC Directive, compliant with:


EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN61131-2; Programmable Controllers (Clause 8, Zone A, B, &
C)

GuardPLC 1800 Controller

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS


CISPR 11; Industrial Emissions

Functional Safety

Certified by TV

Attribute

1753-L32BBBM-8A and 1753-L32BBBP-8A

Controller
User memory, max

250 KB user program memory


250 KB application data memory

Watchdog time, min

10 ms

Safety time, min

20 ms

Current consumption

9 A max (with max load)


0.75 A idle current (just running the controller)

Operating voltage

24V DC, -15%20%, wss 15% (from a power supply with


protective separation conforming to IEC 61131-2 requirements)

Protection

IP 20

Digital Inputs

286

Number of inputs

24 (not electrically isolated)

Voltage, on-state

15V30V DC

Current consumption,
on-state, approx.

3.5 mA @ 24V DC
4.5 mA @ 30V DC

Voltage, off-state, max

5V DC

Current consumption,
off-state, max

1.5 mA (1 mA @ 5V DC)

Input resistance

< 7 k

Overvoltage protection

-10V, +35V

Line length, max

300 m (984 ft.)

Supply

20V / 100 mA, short-circuit proof

Publication 1753-UM001C-EN-P - March 2010

Specifications

Attribute

Appendix A

1753-L32BBBM-8A and 1753-L32BBBP-8A

Digital Outputs
Number of outputs

8 (not electrically isolated)

Output voltage range

L+ minus 2V

Output current

Channels 13 and 57: 0.5 A @ 60 C (140 F)


Channels 4 and 8: 1 A @ 60 C (140 F); 2 A @ 50 C (122 C)

Surge current per


channel

1 A for 10 ms @ 1 Hz (Channels 13 and 57)


4 A for 10 ms @ 1 Hz (Channels 4 and 8)

Current load, min

2 mA per channel

Internal voltage drop,


max

2.0V DC @ 2 A

Off-state leakage
current, max

1 mA @ 2V

Total output current,


max

7A

Counters
Number of counters

2 (not electrically isolated)

Inputs

3 per counter (A, B, Z)

Input voltages

5V and 24V DC
High signal (5V DC): 4V6V
High signal (24V DC): 13V33V
Low signal (5V DC): 0V0.5V
Low signal (24V DC): -3V5V

Input currents

1.4 mA @ 5V DC
6.5 mA @ 24V DC

Input impedance

3.7 k

Counter resolution

24-bit

Input frequency, max

100 kHz

Triggered

on negative edge

Edge steepness

1 V/s

Pulse duty factor

1:1

Analog Inputs

Publication 1753-UM001C-EN-P - March 2010

Number of inputs

8 (unipolar, not electrically isolated)

External shunt
(for current
measurement)

500 for 020 mA

Input values related to


L-

Nominal Value: 010V DC or 0 20 mA with 500 shunt


Service Value: -0.111.5V DC or -0.423 mA with 500
shunt

Input impedance

1 M

Internal resistance of
the signal source

500

Overvoltage protection

+15V, -4V

Resolution (A/D
converter)

12-bit

Accuracy

0.1% @ 25 C (77 F)
0.5% @ 60 C (140 F)
287

Appendix A

Specifications

Attribute

1753-L32BBBM-8A and 1753-L32BBBP-8A

Transmitter supplies

25.37 28.24V / 46 mA, short-circuit proof

Safety accuracy

2%

Environmental Conditions
Temperature, operating

060 C (32 140 F)

Temperature, storage

-4085 C (-40185 F)

Mechanical Dimensions
Width

257 mm (10.1 in.) including housing screws

Height

114 mm (4.49 in.) including latch

Depth

66 mm (2.60 in.) including grounding screw


80 mm (3.15 in.) including shield plate

Weight

1.2 kg (2.64 lb)

Certifications (when product is marked)


c-UL-us

UL Listed Industrial Control Equipment, certified for US and


Canada

CE

European Union 89/336/EEC EMC Directive, compliant with:


EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN61131-2; Programmable Controllers (Clause 8, Zone A, B,
& C)

Distributed I/O

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS


CISPR 11; Industrial Emissions

Functional Safety

Certified by TV

1753-IB16 Input Module

Attribute

1753-IB16

General

288

GuardPLC Ethernet
interfaces

2 x RJ-45, 10/100BaseT (with 100 Mbps) with integrated


switch

Operating voltage

24V DC, -15% +20%, wss 15% from a power supply with
protective separation, conforming to IEC 61131-2
requirements

Response time

10 ms

Current consumption

0.8 A max (with max load)


(0.4 A idle current)

Publication 1753-UM001C-EN-P - March 2010

Specifications

Attribute

Appendix A

1753-IB16

Digital Inputs
Number of inputs

16 (not electrically isolated)

1 Signal

Voltage: 15V 30V DC, Current consumption: 2 mA @ 15V

0 Signal

Voltage, max: 5V DC
Current consumption, max: 1.5 mA (1 mA @ 5V)

Switching point

typically 7.5V

Switching time

typically 250 s

Sensor supply

4 x 19.2V / 40 mA @ 24V short-circuit proof

Pulse Test Sources


Number of pulse test
sources

4 (not electrically isolated)

Output voltage range

approximately 24V

Output current

60 mA

Current load, min

none

Response to overload

4 x 19.2V, short circuit current 60 mA @ 24V

Environmental Conditions
Temperature, operating 060 C (32140 F)
Temperature, storage

-4085 C (-40185 F)

Mechanical Dimensions
Width

152 mm (5.99 in.) including housing screws

Height

114 mm (4.49 in.) including latch

Depth

66 mm (2.60 in.) including grounding bolt

Weight

0.7 kg (1.54 lb)

Certifications (when product is marked)


c-UL-us

UL Listed Industrial Control Equipment, certified for US and


Canada

CE

European Union 89/336/EEC EMC Directive, compliant with:


EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN61131-2; Programmable Controllers (Clause 8, Zone A,
B, & C)

Publication 1753-UM001C-EN-P - March 2010

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

Functional Safety

Certified by TV

289

Appendix A

Specifications

1753 Combination I/O Modules


Attribute

1753-IB8XOB8

1753-IB16XOB8

1753-IB20XOB8

General
GuardPLC Ethernet
interfaces

2 x RJ-45, 10/100BaseT (with 100 Mbps) with integrated switch

Operating voltage

24V DC, -15% +20%, wss 15% from a power supply with protective separation, conforming to IEC 61131-2
requirements

Response time

10 ms

Battery backup

none

Current consumption

8 A max (with max load), idle


current 0.4 A @24V

Wiring category

category 2 on communication ports, signal ports, and power ports

Wire size

I/O 1.5 mm2 (16 AWG) 0.14 mm2 (26 AWG) solid or stranded copper wire rated at 75 C (167 F) or greater
with 3/64 inch (1.2 mm) insulation max

10 A max (with max load),idle


current 0.4 A @24V

8 A max (with max load), idle


current 0.4 A @24V

Power 2.5 mm2 (14 AWG) 0.34 mm2 (22 AWG) solid or stranded copper wire rated at 75 C (167 F) or
greater with 3/64 inch (1.2 mm) insulation max
Terminal block torque

0.51 Nm (4.5 in-lb)

Digital Inputs
Number of inputs

8 (not electrically isolated)

16 (not electrically isolated)

1 Signal

Voltage: 15V30V DC, Current consumption: 2 mA @ 15V

20 (not electrically isolated)

0 Signal

Voltage, max: 5V DC; Current consumption, max: 1.5 mA (1.0 mA @ 5V)

Switching point

typically 7.5V

Sensor supply

2 x 20V / 100 mA @ 24V


short-circuit proof

4 x 24V DC/ 40 mA short-circuit


proof, buffered for 20 ms
2 x 24V DC/1 A short-circuit-proof,
not buffered

5 x 20V / 100 mA @ 24V


short-circuit proof

Number of outputs

8 positive-switching
2 negative-switching
(not electrically isolated)

8 positive-switching
8 negative-switching
(not electrically isolated)

8 (not electrically isolated)

Output voltage range

L+ minus 2V

L+ minus 2V

L+ minus 2V

Output current

channels 13 and 57:


0.5 A @ 60 C (140 F)

channels 2, 4, 5 and 7:
0.5 A @ 60 C (140 F)

channels 13 and 57:


0.5 A @ 60 C (140 F)

channels 4 and 8:
1 A @ 60 C (140 F),
2 A @ 40 C (104 F)

channels 1 and 8:
1 A @ 60 C (140 F);
2 A @ 40 C (104 F)

channels 4 and 8:
1 A @60 C (140 F),
2 A @ 50 C (122 F)

Digital Outputs

channels 3 and 6:
1 A @ 60 C (140 F)
Surge current per
channel

Current load, min

2 mA per channel

290

1 A for 10 ms @ 1 Hz
(Channels 1 3 and 5 7)
4 A for 10 ms @ 1 Hz
(Channels 4 and 8)

Publication 1753-UM001C-EN-P - March 2010

Specifications

Attribute

1753-IB8XOB8

Internal voltage drop,


max

2V @ 2 A

1753-IB16XOB8

1753-IB20XOB8

8A

7A

Appendix A

Leakage current (with 0 maximum 1 mA @ 2V


signal)
Total output current,
max

7A

Response to overload

shut down of the concerned output with cyclic reconnecting

Pulse Test Sources


Number of pulse test
sources

2 (not electrically isolated)

2 (not electrically isolated)

Not applicable

Output voltage range

L+ minus 4V

Not applicable

Output current

60 mA

Not applicable

Current load, min

none

Not applicable

Switching time

100 s

Response to overload

4 x 19.2V, short circuit current


60 mA @ 24V

2 x 19.2V, short circuit current


60 mA @ 24V

Not applicable

205 mm (in.) including housing


screws

207 mm (8.16 in.) including housing


screws

Environmental Conditions
Temperature, operating 060 C (32140 F)
Temperature, storage

-4085 C (-40 185 F)

Mechanical Dimensions
Width

15mm (in.) including housing


screws

Height

114 mm (4.49 in.) including latch

Depth

66 mm (2.60 in.) including


grounding bolt

88 mm ( in.) including grounding


bolt

66 mm (2.60 in.) including


grounding bolt

Weight

1.0 kg (2.2 lb)

1.3 kg (2.9 lb)

1.0 kg (2.2 lb)

Certifications (when product is marked)


c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada

CE

European Union 89/336/EEC EMC Directive, compliant with:


EN 61000-6-4; Industrial Emissions

C-Tick

Australian Radiocommunication Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Functional Safety

Certified by TV

EN 61000-6-2; Industrial Immunity

Publication 1753-UM001C-EN-P - March 2010

291

Appendix A

Specifications

1753-IF8XOF4 Analog Combination Module


Attribute
GuardPLC Ethernet
interfaces
Operating voltage

Response time
Battery backup
Current consumption
Wiring category
Wire size

Terminal block torque


Analog Inputs
Number of inputs
Input signal range, nom
Input signal range, service
Shunt resistor, external
Impedance, analog input
Analog input signal, source
impedance
Input resolution
Effective resolution
Sensor supply
Accuracy
Safety accuracy
Calibration error zero point
Calibration error terminal
point
Channel error
Temperature error zero
point
Temperature error terminal
point
Linearity error
Long-term drift

292

1753-IF8XOF4
2 x RJ-45, 10/100BaseT (with 100 Mbps) with integrated
switch
24V DC, -15% +20%, wss 15% from a power supply with
protective separation, conforming to IEC 61131-2
requirements
20 ms
none
0.8 A max (with max load), idle current 0.4 A @24V
category 2 on communication ports, signal ports, and power
ports
I/O 1.5 mm2 (16 AWG)0.14 mm2 (26 AWG) solid or
stranded copper wire rated at 75 C (167 F) or greater with
3/64 inch (1.2 mm) insulation max
Power 2.5 mm2 (14 AWG)0.34 mm2 (22 AWG) solid or
stranded copper wire rated at 75 C (167 F) or greater with
3/64 inch (1.2 mm) insulation max
0.51 Nm (4.5 in-lb)
8 (not electrically isolated)
Voltage: 010V DC
Current: 020 mA(1)
Voltage: -0.111V DC
Current: -0.423 mA(1)
500 (for current input)
>2 M
500
12 bits
9 bits @ 10V
selectable 26V/8.2V
200 mA, short-circuit-proof
0.5%
2%
1%
0.4%
0.5%
0.5%/10 K
0.5%/10 K
0.5%
0.5%

Publication 1753-UM001C-EN-P - March 2010

Specifications

Analog Outputs
Number of outputs
Output signal range

Appendix A

4 (not electrically isolated)


non-safety with common safety switch off
420 mA nominal
020 mA full range
12 bits
600 max
1%
1%

resolution of software
Impedance, current output
Calibration error zero point
Calibration error terminal
point
Channel error
1%
Temperature error zero
1%/10 K
point
Temperature error terminal 1%/10 K
point
Linearity error
1%
Environmental Conditions
Temperature, operating
060 C (32140 F)
Temperature, storage
-4085 C (-40185 F) without back-up battery
Mechanical Dimensions
Width
207 mm (8.16 in.) including housing screws
Height
114 mm (4.49 in.) including latch
Depth
97 mm (3.82 in.) including grounding bolt
Weight
0.95 kg (2.09 lb)
Certifications (when product is marked)
c-UL-us
UL Listed Industrial Control Equipment, certified for US and
Canada
CE
European Union 89/336/EEC EMC Directive, compliant with:
EN 61000-6-4; Industrial Emissions
C-Tick
Functional Safety

EN 61000-6-2; Industrial Immunity


Australian Radiocommunication Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Certified by TV

(1) with external shunt resistor

Publication 1753-UM001C-EN-P - March 2010

293

Appendix A

Specifications

1753-OW8 Relay Output Module

Attribute

1753-OW8

Response Time

10 ms

GuardPLC Ethernet
Interfaces

2 x RJ-45, 10/100BaseT (with 100 Mbps) with integrated switch

Operating voltage

24V DC, -15%20%, wss 15% from a power supply with


protective separation conforming to IEC 61131-2 requirements

Current consumption

0.6 A max (with max load)

Isolation voltage

No isolation between circuits

Wiring category(1)

category 2 on communication ports, signal ports, and power


ports

Wire size

I/O 1.5 mm2 (16 AWG)0.14 mm2 (26 AWG) solid or stranded
copper wire rated at 75 C (167 F) or greater with 3/64 inch
(1.2 mm) insulation max
Power 2.5 mm2 (14 AWG) 0.34 mm2 (22 AWG) solid or
stranded copper wire rated at 75 C (167 F) or greater with
3/64 inch (1.2 mm) insulation max

Terminal block torque 0.51 Nm (4.5 in-lb)


Fuse (external)

10 A (slow blow)

Battery backup

none

Relay Outputs
Number of outputs

8 normally open contacts

Switching voltage

5V, 250V AC/250V DC

Switching current

UL: 24V DC @ 1 A resistive load, 250V AC @ 6 A general


purpose
TV:
up to 240VA (for V AC)
up to 30V DC @ 90 W
up to 70V DC @ 35 W
up to 127V DC @ 30 W

Turn-on time

approx. 30 ms

Turn-off time

approx. 10 ms

Bounce time

approx. 15 ms

Service life,
mechanical

106 switching cycles

Service life, electrical 2.5 x 105 switching cycles with resisitive full load and I 0.1
e
switching cycles per second
Environmental Conditions
Temperature,
operating

0...60 C (32...140 F)

Temperature, storage -40...85 C (-40...185 F)


Vibration

294

1 g @ 10150 Hz

Publication 1753-UM001C-EN-P - March 2010

Specifications

Shock, operating

15 g

Relative humidity

10 95% noncondensing

Emissions

Group 1, Class A

ESD immunity

6 kV contact discharges
8 kV air discharges

Appendix A

Radiated RF immunity 10V/m with 1kHz sine-wave 80% AM from 80 MHz2000 MHz
EFT/B immunity

2 kV @ 5 kHz on power ports


1 kV @ 5 kHz on signal ports
1 kV @ 5 kHz on communication ports

Surge transient
immunity

500V line-line (DM) and 500V line-earth (CM) on DC power


ports
1 kV line-earth (CM) on signal ports
1 kV line-earth (CM) on communication ports

Conducted RF
immunity

10Vrms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

Enclosure type rating

meets IP20

Mechanical Dimensions
Width

207 mm (8.14 in.) including housing screws

Height

114 mm (4.49 in.) including latch

Depth

86 mm (3.38 in.) including grounding bolt

Weight

1.3 kg (3.47 lb)

Certifications
(when product is marked)
c-UL-us

UL Listed Industrial Control Equipment, certified for US and


Canada

CE

European Union 89/336/EEC EMC Directive, compliant with:


EN 61000-6.2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
European Union 73/23/EEC LVDDirective, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunication Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

Functional Safety
(1)

Publication 1753-UM001C-EN-P - March 2010

Certified by TV

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1.

295

Appendix A

Specifications

1753-OB16 Output Module

Attribute

1753-OB16

General
GuardPLC Ethernet
interfaces

2 x RJ-45, 10/100Base T (with 100 Mbps) with integrated


switch

Operating voltage

24V DC, -15% +20%, wss 15% from a power supply with
protective separation, conforming to IEC 61131-2
requirements

Response time

10 ms

Battery backup

none

Current consumption

approximately 0.2 A per group (idle current)

Digital Outputs
Number of outputs

16 (not electrically isolated)

Output Voltage Range

L+ minus 2V

Output current

maximum 1 A @ 60 C (140 F),


maximum 2 A @40 C (104 F)

Surge current per


channel

4 A for 10 ms @ 1 Hz

Current load, min

2 mA per channel

Current per group


(admissible total
current)

max 8 A per group (max 16 A per module)

Lamp load, max

10 W (for output 1 A),


25 W (for output 2 A)

Inductive load, max

500 mH

Internal voltage drop,


max

2V @ 2 A

Leakage current, max


(with 0 signal)

1 mA @ 2V

Response to overload

shut down of concerned output with cyclic reconnecting

Environmental Conditions
Temperature, operating 060 C (32140 F)
Temperature, storage

-4085 C (-40185 F)

Mechanical Dimensions

296

Width

207 mm (8.16 in.) including housing screws

Height

114 mm (4.49 in.) including latch

Depth

66 mm (2.60 in.) including grounding bolt

Weight

0.85 kg (1.87 lb)

Publication 1753-UM001C-EN-P - March 2010

Specifications

Attribute

Appendix A

1753-OB16

Certifications (when product is marked)


c-UL-us

UL Listed Industrial Control Equipment, certified for US and


Canada

CE

European Union 89/336/EEC EMC Directive, compliant with:


EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN61131-2; Programmable Controllers (Clause 8, Zone A,
B, & C)

C-Tick

Australian Radiocommunication Act, compliant with: AS/NZS


CISPR 11; Industrial Emissions

Functional Safety

Certified by TV

GuardPLC 2000 Controller

Publication 1753-UM001C-EN-P - March 2010

Attribute

1755-L1

User memory

500 KB application code memory


500 KB application data memory

Operating voltages

3.3V DC
5V DC

Current consumptions

3.3V / 1.5 A
5V / 0.1 A
24V DC / 1.0 A

Front connectors

1 Ethernet connector for RSLogix Guard PLUS! software


2 ASCII connectors (RS-232)

Temperature, operating

060 C (32140 F)

Temperature, storage

-4085 C (-40 185 F)

Weight

280 g (0.62 lb)

297

Appendix A

Specifications

Attribute

1755-L1

Certifications (when product is marked)


UL

UL Listed Industrial Control Equipment

CE

European Union 89/336/EEC EMC Directive, compliant with:


EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN61131-2; Programmable Controllers (Clause 8, Zone A,
B, & C)

GuardPLC 2000 Distributed


I/O Modules

C-Tick

Australian Radiocommunication Act, compliant with: AS/NZS


CISPR 11; Industrial Emissions

Functional Safety

Certified by TV

1755-IB24XOB16 Digital I/O Module

Attribute

1755-IB24XOB16

Digital Inputs
Quantity of inputs

24

Nominal input voltage (1


signal)

24V DC (1030V)

Off-state input voltage,


max (0 signal)

5V DC

On-state current

2 mA @ 10V, 13 mA @ 30V (3 groups of 8, each group limited


to 100 mA)

Off-state current

1.5 mA @ 5V

Digital Outputs

298

Quantity of outputs

16

Output voltage range

operating voltage minus 2V (depending on load)

Output current (30 C)

2 A per channel, overload protected, 8 A max per module

Publication 1753-UM001C-EN-P - March 2010

Specifications

Attribute

Appendix A

1755-IB24XOB16

General Specifications
Current consumption

0.3 A / 3.3V DC
0.5 A / 24V DC (Idle current to run module)

Operating voltage

24V DC, -15 +20%, ripple 15%

Temperature, operating

060 C (32140 F)

Temperature, storage

-4085 C (-40185 F)

Weight

260 g (0.57 lb)

Certifications (when product is marked)


UL

UL Listed Industrial Control Equipment

CE

European Union 89/336/EEC EMC Directive, compliant with:


EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN61131-2; Programmable Controllers (Clause 8, Zone A,
B, & C)

C-Tick

Australian Radiocommunication Act, compliant with: AS/NZS


CISPR 11; Industrial Emissions

Functional Safety

Certified by TV

1755-IF8 Analog Input Module

Publication 1753-UM001C-EN-P - March 2010

Attribute

1755-IF8

Number of inputs

8 single-ended or 4 differential

Input values

rated values: 010V DC or 020 mA (with shunt)


user values: 010.25V DC or 020.5 mA (with shunt)

External shunt
(for current input)

500

Overvoltage protection

30V (15V DC)

Resolution

12 bit

Input impedance

1 M (DC)

Input signal / source


impedance

500

Accuracy

0.1% @ 25 C (77 F)
0.5% @ 60 C (140 F)

Operating voltage

24V DC
-1520%
ripple 15%

299

Appendix A

Specifications

Attribute

1755-IF8

Maximum common mode


voltage to I-

13V DC

Current consumption

150 mA / 3.3V DC
400 mA / 24V DC

Temperature, operating

060 C (32140 F)

Temperature, storage

-4085 C (-40185 F)

Weight

240 g (0.53 lb)

Certifications (when product is marked)


UL

UL Listed Industrial Control Equipment

CE

European Union 89/336/EEC EMC Directive, compliant with:


EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN61131-2; Programmable Controllers (Clause 8, Zone A, B,
& C)

C-Tick

Australian Radiocommunication Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

Functional Safety

Certified by TV

1755-OF8 Analog Output Module

300

Attribute

1755-OF8

Quantity of outputs

Output values, max

010V or 020 mA

Overvoltage protection

24V

Source value

UINT

Load impedance

load 600 (current)


limit resistance > 5 k (voltage)

Accuracy

0.3% @ 25 C (77 F)
0.5% @ 60 C (140 F)

Safety relevant accuracy

1%

Operating voltage

24V DC
-1520%
ripple 15%

Current consumption

150 mA / 3.3V DC
400 mA / 24V DC

Temperature, operating

060 C (32140 F)

Temperature, storage

-4085 C (-40185 F)

Publication 1753-UM001C-EN-P - March 2010

Specifications

Attribute

1755-OF8

Weight

280 g (0.53 lb)

Appendix A

Certifications (when product is marked)


UL

UL Listed Industrial Control Equipment

CE

European Union 89/336/EEC EMC Directive, compliant with:


EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN61131-2; Programmable Controllers (Clause 8, Zone A, B,
& C)

Publication 1753-UM001C-EN-P - March 2010

C-Tick

Australian Radiocommunication Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

Functional Safety

Certified by TV

301

Appendix A

Specifications

1755-HSC High Speed Counter Module

Attribute

1755-HSC

Number of counters

Input voltage

5V or 24V

Input current

3 mA

Input signal frequency

01 MHz

Trigger

with falling edge

Edge steepness

1V/s

Input cables

500 m @ 100 kHz, shielded, twisted

Input resistance

3.7 k

Resolution

24 bit (value range 0 6,777,215)

Accuracy of time basis

0.2%

Quantity of outputs

4 digital

Output load

0.5A, voltage drop: 3V

Output load in summary

2 A
18V

Operating Voltage

24V DC, -1520%, ripple 15%

Current consumption

0.1 A / 24V DC without load


0.8 A (3.3V DC), 0.1 A (5V DC)

Temperature, operating

060 C (32140 F)

Temperature, storage

-4085 C (-4085 F)

Weight

260 g (0.57 lb)

Certifications (when product is marked)


UL

UL Listed Industrial Control Equipment

CE

European Union 89/336/EEC EMC Directive, compliant with:


EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN61131-2; Programmable Controllers
(Clause 8, Zone A, B, & C)

302

C-Tick

Australian Radiocommunication Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

Functional Safety

Certified by TV

Publication 1753-UM001C-EN-P - March 2010

Specifications

GuardPLC 2000 Power


Supply

Appendix A

Attribute

1755-PB720

Supply voltage

24V DC

Supply voltage range

20.4V DC28.8V DC (10 ms buffer), ripple 15%

External fusing

30 A(1) / IEC (This module has no overcurrent protection.)

Outputs

3.3V DC/10 A, 5V DC/2 A

Temperature, operating

060 C (32140 F)

Temperature, storage

-4060 C (-40140 F) with battery


-4085 C (-40185 F) without battery

Weight

820 g (1.80 lb)

Certifications (when product is marked)


UL

UL Listed Industrial Control Equipment

CE

European Union 89/336/EEC EMC Directive, compliant with:


EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN61131-2; Programmable Controllers (Clause 8, Zone A, B, &
C)

C-Tick

Australian Radiocommunication Act, compliant with: AS/NZS


CISPR 11; Industrial Emissions

Functional Safety

Certified by TV

(1) The power supply can supply up to 30 A for I/O modules. Use an appropriate fuse for your systems power
requirements.

Publication 1753-UM001C-EN-P - March 2010

303

Appendix A

Specifications

Notes:

304

Publication 1753-UM001C-EN-P - March 2010

Appendix

System Signal Variables

Introduction

Programming Controller
Data

Topic

Page

Programming Controller Data

305

I/O Variables

307

The controller supports system variables that you can configure.


The system variables are defined as:
SAFE: the controller can use this information in safety-related
functions.
NON-SAFE: additional information that safety functions must not
rely on.
These are the system variables.

System Variable

Unit/Value

Read/Write

Description(1)

Contact Assembly 1
Contact Assembly 2
Contact Assembly 3
Contact Assembly 4

true
false

Write

On true, the contact closes; on false the contact does not close.
Only available for a GuardPLC 2000 controller.
[BOOL]
NON-SAFE

Cooling Fan State

0, 1, 2

Read

0 = normal
1 = fans OK
2 = fan error
Only available for a GuardPLC 2000 controller.
[BYTE]
NON-SAFE

Cycle Time

milliseconds Read

Duration of the last cycle


[UDINT]
SAFE

Date Time Seconds


Date Time
Milliseconds

seconds
Read
milliseconds

Time passed since 1970. An automatic switchover from summer to winter time is
not supported.
[UDINT]
NON-SAFE

Emergency Stop 1
Emergency Stop 2
Emergency Stop 3
Emergency Stop 4

true
false

True triggers Emergency Off


[BOOL]
SAFE
Use these signals to force all inputs and outputs to the zero/OFF state from within
the user program.

Write

Publication 1753-UM001C-EN-P - March 2010

305

Appendix B

System Signal Variables

Read/Write

Description(1)

System Variable

Unit/Value

Force Time

milliseconds Read

Remaining running time during forcing; 0 if Force is inactive.


[DINT]
NON-SAFE

Power Supply

0-255

GuardPLC 1200 and GuardPLC 2000


Controllers
0 = normal
1 = error of input power supply 24 VDC
2 = error of battery
4 = module error of power supply 5 V
8 = module error of power supply 3.3 V
16 = 5 V undervoltage
32 = 5 V overvoltage
64 = 3.3 V undervoltage
128 = 3.3 V overvoltage
255 = status does not exist
[BYTE]
NON-SAFE

System Tick High


System Tick Low

milliseconds Read

Ring counter with 64 bits, incremented in millisecond steps. [UDINT]


SAFE

Temperature State

0, 1, 2, 3,
255

0 = normal
1 = high
2 = faulty
3 = very high
255 = status does not exist
[BYTE]
NON-SAFE (but for additional switch-off)

Read

Read

GuardPLC 1600 and GuardPLC 1800


Controllers
0 = normal
1 = 24 VDC undervoltage
4 = 5 V undervoltage
8 = 3.3 V undervoltage
16 = 3.3 V overvoltage
[BYTE]
NON-SAFE

(1) Binary values are ORed.

306

Publication 1753-UM001C-EN-P - March 2010

System Signal Variables

I/O Variables

Appendix B

Depending upon the type of controller, the various GuardPLC


controllers support variables for digital and analog I/O parameters that
you can configure or monitor.

Digital I/O Module Variables (AB-DIO) for GuardPLC 1200 and


2000 Controllers
The GuardPLC 1200 and 2000 controllers support these digital I/O
parameters.
I/O Data

Read/Write

Description

Board.SRS

Read

System.Rack.Slot

Board.Type

Read

Module type

Board.State

(1)

Read

Publication 1753-UM001C-EN-P - March 2010

0x00E1

digital I/O module for GuardPLC 1200 controllers

0xFE01

digital I/O module for GuardPLC 2000 controllers

0xFFFF

missing module in GuardPLC 2000 chassis

Error mask for the module


0x000

I/O processing may be running with errors

0x001

No I/O processing (CPU not in RUN)

0x002

No I/O processing during start-up tests

0x004

Manufacturing interface running

0x010

No I/O processing due to faulty parameterization

0x020

No I/O processing due to exceeded fault rate

0x040

No I/O processing because configured module is not plugged in

307

Appendix B

System Signal Variables

I/O Data
DO.State

(1)

DO[0x].State(1)(2)

DO[0x].Value(1)

DI.State

DI[xy].State(3)

DI[xy].Value(2)

Read/Write

Description

Read

Error mask for all digital outputs

Read

Write

Write

Read

Read

0x0000

No errors detected

0x0001

Error of the DO section of the module

0x0002

Within the multiple error occurrence time: safety switch 1 faulty

0x0004

Within the multiple error occurrence time: safety switch 2 faulty

0x0008

Within the multiple error occurrence time: test sample tests faulty

0x0010

Within the multiple error occurrence time: readback channels faulty

0x0020

Within the multiple error occurrence time: active switch-off faulty

0x0100

Within the safety time: CS signals faulty

0x0200

All outputs switched off; total current too high

0x0400

Within the safety time: temperature limit 1 exceeded

0x0800

Within the safety: temperature limit 2 exceeded

0x01000

Within the safety time: auxiliary voltage monitoring: undervoltage

0x02000

Within the multiple error occurrence time: status of the


safety switches

Error mask for digital output channels


0x00

No error detected; outputs driven as expected

0x01

Error in digital output module; outputs not driven

0x02

Output switched off due to overcurrent; outputs not driven

0x04

Error during readback of the digital output; outputs not driven

Output value of digital output channels


0

Output de-energized

Output activated

Error mask for all digital inputs


0x0000

No error detected

0x0001

Error of the DI section of the module

0x0002

Within the safety time: test sample test faulty

Error mask of digital input channels


0x00

No error detected

0x01

Error in the digital input module; input value set to 0

Input values of digital input channels


0

Input not activated

Input activated

(1) Values are ORed.


(2) 0x = output channel 0116 for GuardPLC 2000 controller and 0108 for GuardPLC 1200, 1600, and 1800 controllers.
(3) xy = input channel 0124 for GuardPLC 2000 and GuardPLC 1800 controllers and 01 20 for GuardPLC 1200 and 1600 controllers.

308

Publication 1753-UM001C-EN-P - March 2010

System Signal Variables

Appendix B

Analog Input Module Variables (AB-AI) for GuardPLC 2000


Controller
The GuardPLC 2000 controller supports these analog input
parameters.
I/O Data

Read/Write

Description

AI.Mode

Write

Mode for all channels of the analog input module

AI.State

Read

Publication 1753-UM001C-EN-P - March 2010

unipolar (single-ended)

differential

Error mask for all analog inputs


0x0000

No errors detected

0x0001

Error of the module

0x0008

Within the safety time: data bus walking bit error

0x0010

Within the safety time: coefficient table check error

0x0020

Within the safety time: supply voltages error

0x0040

Error on A/D conversion (DRDY_HIGH)

0x0080

Within the multiple error occurrence time: error in multiplexer


crosslink

0x0100

Within the multiple error occurrence time: data bus walking


bit error

0x0200

Within the multiple error occurrence time: multiplexer address error

0x0400

Within the multiple error occurrence time: supply voltages error

0x0800

Within the multiple error occurrence time: error in characteristic


curve (Unipolar mode)

0x1000

Within the multiple error occurrence time: limit values/zero point


error (Unipolar mode)

0x2000

Within the multiple error occurrence time: error in characteristic


curve (Differential mode)

0x4000

Within the multiple error occurrence time: limit values/zero point


error (Differential mode)

0x8000

Error in A/D conversion (DRDY_LOW)

309

Appendix B

System Signal Variables

I/O Data
AI[0x].State

(1)

AI[0x].Used

Read/Write

Description

Read

Error mask for analog input channels

Write

0x00

No error detected

0x01

Error in analog input channel

0x02

Invalid measurement values

0x04

A/D converters faulty

0x08

Measurement values are not within the safety accuracy

0x10

Measurement value overflow

0x20

Channel not in use

0x40

Addressing error of the two A/D converters

Configuration of analog input channel


0

not used

used

AI[0x].Value

Read

Analog value of input channel (WORD)


-10V10V = -10001000

Board.SRS

Read

System.Rack.Slot

Board.Type

Read

Module type

(1)

Board.State

Read

0xFD02

analog input module for GuardPLC 2000 controller

0xFFFF

missing module in GuardPLC 2000 chassis

Error mask for the module


0x000

I/O processing may be running with errors

0x001

No I/O processing (CPU not in RUN)

0x002

No I/O processing during start-up tests

0x004

Manufacturing interface running

0x010

No I/O processing due to faulty parameterization

0x020

No I/O processing due to exceeded fault rate

0x040

No I/O processing because configured module is not plugged in

(1) 0x = input channel 0108.

310

Publication 1753-UM001C-EN-P - March 2010

System Signal Variables

Appendix B

Analog Output Module Variables (AB-AO) for GuardPLC 2000


Controller
The GuardPLC 2000 controller supports these analog output
parameters
I/O Data

Read/Write

Description

AO.State

Read

Error mask for all analog outputs

AO[0x].Mode

(1)

AO[0x].State

AO[0x].Used

Write

Read

Write

Publication 1753-UM001C-EN-P - March 2010

0x0000

No errors detected

0x0001

Error of the module

0x0002

Within the safety time: co-efficient table check error

0x0004

No communication with the module due to controller error

Mode of analog output channel


0

voltage

current

Error mask for analog output channels


0x0000 0001

CPU detected error on AB-AO module

0x0000 0002

CPU detected faulty monotony counter

0x0000 0004

CPU detected error in safe addressing

0x0000 0008

CPU detected faulty CRC

0x0000 0010

CPU detected error in watchdog time of the AB-AO onboard


microprocessor

0x0000 0020

CPU cannot communicate with the AB-AO onboard microprocessor

0x0000 0040

CPU detected that the present operating mode (current/voltage) is


different from the initialized operating mode

0x0001 0000

AB-AO onboard microprocessor detected read back error

0x0004 0000

AB-AO onboard microprocessor detected wrong supply voltage

0x0008 0000

Within the multiple error occurrence time: AB-AO onboard


microprocessor detected faulty safety switch

0x0080 0000

AB-AO onboard microprocessor detected both safety switches


as faulty

0x0200 0000

AB-AO onboard microprocessor INITIALIZE

0x1000 0000

AB-AO onboard microprocessor detected error because of module


over temperature

0x2000 0000

AB-AO onboard microprocessor detected module over temperature

0x8000 0000

CPU detected error on redundant AB-AO onboard microprocessor


channel

Configuration of analog output channel


0

not used

used

311

Appendix B

System Signal Variables

I/O Data

Read/Write

Description

Write

Output value of analog output channels


Voltage mode: -10V10V = -10001000
Current mode: 0 mA20 mA = 01000
for values between -1000 0, the output current is 0 mA

Board.SRS

Read

System.Rack.Slot

Board.Type

Read

Module type

AO[0x].Value

(1)

Board.State

Read

0xFB04

analog output module for GuardPLC 2000 controller

0xFFFF

missing module in GuardPLC 2000 chassis

Error mask for the module


0x000

I/O processing may be running with errors

0x001

No I/O processing (CPU not in RUN)

0x002

No I/O processing during start-up tests

0x004

Manufacturing interface running

0x010

No I/O processing due to faulty parameterization

0x020

No I/O processing due to exceeded fault rate

0x040

No I/O processing because configured module is not plugged in

(1) 0x = output channels 0108.

High-Speed Counter Variables For GuardPLC 1200 and 2000


Controllers
The GuardPLC 1200 and GuardPLC 2000 controllers support these
variables for counter I/O parameters.
I/O Data

Read/Write

Description

Board.SRS

Read

System.Rack.Slot

Board.Type

Read

Module type

312

0x0003

counter module for GuardPLC 1200 controller

0xFC03

counter module for GuardPLC 2000 controller

0xFFFF

missing module in GuardPLC 2000 chassis

Publication 1753-UM001C-EN-P - March 2010

System Signal Variables

I/O Data

Read/Write

Description

Board.State

Read

Error mask for the module

Cnt.State

Read

0x000

I/O processing may be running with errors

0x001

No I/O processing (CPU not in RUN)

0x002

No I/O processing during start-up tests

0x004

Manufacturing interface running

0x010

No I/O processing due to faulty parameterization

0x020

No I/O processing due to exceeded fault rate

0x040

No I/O processing because configured module is not plugged in

Error mask of both counters


0x0000

No errors detected

0x0001

Error of the counter section of the module

0x0002

Error while comparing the time base

0x0004

Addressing error while reading the time base

0x0008

Parameterization of the time base corrupted

0x0010

Addressing error while reading the counts

0x0020

Parameterization of counter corrupted

0x0040

Addressing error while reading the Gray codes

0x0080

Within the multiple error occurrence time: test sample test faulty

0x0100

Error of the module

Cnt[0x].Value(1)

Read

Counts of counter 1 or 2 (cyclic 24-bit)


24 bits for pulse counter
4 bits for Gray code for GuardPLC 2000 controllers;
3 bits for Gray code for GuardPLC 1200 controllers

Cnt[0x].5/24V Mode(1)

Read/Write

5V or 24V mode of counter 1 or 2


The write values must have initial values or constants.

Cnt[0x].Auto Advance
Sense(1)

Cnt[0x].Direction(1)

Read/Write

Read/Write

5V

24V

Automatic recognition of direction of counting for counter 1 or 2


0

Manual setting of direction of counting

Automatic recognition of direction of counting

Direction of counting for counter 1 or 2


(only when Automatic Counter Advance Sense = false)
0

Up

Down

Cnt[0x].Dummy1

Read/Write

reserved memory space for future use

Cnt[0x].Dummy2

Read/Write

reserved memory space for future use

Publication 1753-UM001C-EN-P - March 2010

Appendix B

313

Appendix B

System Signal Variables

I/O Data
Cnt[0x].GrayCode

(1)

Read/Write

Description

Read/Write

Gray code mode of counter 1 or 2


0

Pulse

Gray

Cnt[0x].Halt(1)

Read/Write

currently not used

Cnt[0x].Reset(1)

Read/Write

Reset for counter 1 or 2

Cnt[0x].State(1)

Cnt[0x].Time Overflow(1)

Read

Read

Resetting of counter

No resetting of counter

Error mask of counter 1 or 2


0x01

Error in counter unit

0x02

Error while comparing the counts

0x04

Error while comparing the time stamps

0x08

Error resetting counter

Overflow indicator of time stamp of counter 1 or 2


true

24 bits overflow since last cycle

false

No 24 bits overflow since last cycle

Cnt[0x].Time Stamp(1)

Read

Time stamp for Cnt[0x].Value (cyclic 24-bit)


24 bits, time resolution 1s

Cnt[0x].Value Overflow(1)

Read

Overflow indicator of counter 1 or 2

DO.State

314

Read

true

24 bits overflow since last cycle (only when Automatic Counter


Advance Sense = false)

false

No 24 bits overflow since last cycle

Error mask for all counter outputs


0x0001

Error of the DO section of the module

0x0002

Within the multiple error occurrence time: safety switch 1 faulty

0x0004

Within the multiple error occurrence time: safety switch 2 faulty

0x0008

Within the multiple error occurrence time: test sample tests faulty

0x0010

Within the multiple error occurrence time: readback channels faulty

0x0020

Within the multiple error occurrence time:


active switch-off faulty

0x0100

Within the safety time: CS signals faulty

0x0200

All outputs switched off; total current too high

0x0400

Within the safety time: temperature limit 1 exceeded

0x0800

Within the safety time: temperature limit 2 exceeded

0x01000

Within the safety time: auxiliary voltage monitoring: undervoltage

0x02000

Within the multiple error occurrence time: status of the safety switches

Publication 1753-UM001C-EN-P - March 2010

System Signal Variables

I/O Data
(2)

DO[0y].State

DO[0x].Value(2)

Read/Write

Description

Read

Error mask for counter outputs 14

Write

0x01

Error in output channel

0x02

Output channel switched off due to overcurrent

0x04

Error during readback of the output channel

0x08

Faulty initialization after counter reset

Appendix B

Output value of counter outputs 14 (These 4 outputs cannot be driven by counter presets.
They are driven by user software only.)
0

Output de-energized

Output activated

(1) Ox = counter 01 or 02.


(2) 0y = outputs 01, 02, 03, or 04

Module Variables for GuardPLC 1600 and 1800 Controllers and


Distributed I/O
The GuardPLC 1600 and 1800 controllers and distributed I/O support
these module parameters.
I/O Data

Read/Write

Description

Module.SRS

Read

Slot number (System.Rack.Slot)

Module.Type

Read

Module type
Digital input module (DI20) for GuardPLC 1600 controllers
0x00A5

Digital input module (DI20) for 1753-IB20XOB8


Digital input module (DI8) for 1753-IB8XOB8

Publication 1753-UM001C-EN-P - March 2010

0x00E2

Digital input module (DI16) for 1753-IB16XOB8

0x002D

Digital input module (DI16) for 1753-IB16

0x005A

Digital output module (DO16) for 1753-OB16

0x003C

Digital relay output module (DO8) 1753-OW8

0x00B4

Digital output module (DO8) for GuardPLC 1600/1800 controllers, and


1753-IB20XOB8

0x005B

Digital output module (DO8) for 1753-IB8XOB8

0x00C4

Digital output module (DO8) for 1753-IB16XOB8

315

Appendix B

System Signal Variables

I/O Data

Read/Write

Description

Module.Error.Code

Read

Error mask for the module


0x0000

I/O processing may be running with errors

0x0001

No I/O processing (CPU not in RUN)

0x0002

No I/O processing during start-up tests

0x0004

Manufacturing interface running

0x0010

No I/O processing due to incorrect configuration

0x0020

No I/O processing due to exceeded fault rate

0x0040/80

No I/O processing because configured module is not plugged in

Digital Input Module Variables for GuardPLC 1600 Controllers and


Distributed I/O
The GuardPLC 1600 controllers and distributed I/O support these
digital input parameters.
I/O Data

Read/Write

Description

DI.Error Code Supply


(1753-IB16XOB8 only)

Read

0x0001

DI[xx].Error Code Supply


(1753-IB16XOB8 only)

Read

Error mask of all digital inputs

DI.Error Code

DI[xx].Error Code(1)

DI[xx].Value(1)

316

Read

Read

Write

Error in the total module DI supply.

0x01

Error in DI supply of the module.

0x02

Supply is switched off due to overcurrent.

0x04

Error in reading back the supply.

Error mask for all digital inputs


0x0001

Error in digital input range

0x0002

FTZ test of test pattern failed

Error mask of all digital input channels


0x01

Error in digital input module

0x10

Short-circuit of the channel

0x80

Line interrupt between pulse output (DO) and pulse input (DI)

Input value of digital input channels


0

Input not set

Input set

Publication 1753-UM001C-EN-P - March 2010

System Signal Variables

I/O Data

Read/Write

Description

DI.Number of Pulse
Channel

Write

Number of pulse outputs (feed outputs)

DI Supply[xx]
1753-IB16XOB8 only)

Write

No output channel provided for line monitoring

Output channel 1 provided for line monitoring

Output channels 1 and 2 provided for line monitoring

Output channels 1, 2, and 3 provided for line monitoring

Output channels 14 provided for line monitoring

Output channels 15 provided for line monitoring

Output channels 16 provided for line monitoring

Output channels 17 provided for line monitoring

Output channels 18 provided for line monitoring

Activation of the single DI supply


0

Transmitter supply (1 A) is switched off (default: supply current 40 mA)

Transmitter supply (1 A) is switched on

DI.Pulse Slot

Write

Pulse module slot (LC)

DI.Pulse Channel

Write

Source channel of pulse feed

DI.LC Delay
(GuardPLC 1600 and 1800
Controllers and 1753-IB16
and 1753-IB20XOB8
modules)

Write

Appendix B

Input channel

Pulse from first DO channel

Pulse from second DO channel

Pulse from third DO channel

Pulse from fourth DO channel

Pulse from fifth DO channel

Pulse from sixth DO channel

Pulse from seventh DO channel

Pulse from eighth DO channel

Waiting time for pulse output (short-circuit-proof)

DI Pulse Delay
(1753-IB8XOB8 and
1753-IB16XOB8)
(1) xx = the affected input channel of the controller or module.

Publication 1753-UM001C-EN-P - March 2010

317

Appendix B

System Signal Variables

Digital Output Module Variables for GuardPLC 1600/1800


Controllers, 1753-IB20XOB8 Modules, and 1753-OB16 Modules
The GuardPLC 1600 and GuardPLC 1800 controllers, 1753-IB20XOB8
modules, and 1753-OB16 modules support these digital output
parameters.
I/O Data

Read/Write

Description

DO.Error Code

Read

Error mask for all digital outputs

DO[xx].Error Code(1)

Read

0x0001

Error in digital output range

0x0002

MEZ test of test pattern failed

0x0004

MEZ test, auxiliary supply failed

0x0010

FTZ test of test pattern failed

0x0020

FTZ test of test pattern of the output switch failed.

0x0040

FTZ test of the test pattern of the output switch (disconnection test
of outputs) failed.

Error mask of all digital output channels


0x01

Error in digital output module

0x02

Output switched off due to overload

0x04

Error when reading back the activation of the digital outputs

0x08

Error when reading back the status of the digital outputs

(1) xx = affected output channel of the controller or module.

318

Publication 1753-UM001C-EN-P - March 2010

System Signal Variables

Appendix B

Digital Output Parameters for 1753-IB8XOB8 Modules


In addition to the output parameters in the table on page 318, the
GuardPLC 1753-IB8XOB8 module features these digital output
parameters.
I/O Data

Read/ Description
Write

L+ Switching Outputs

L- Switching Outputs

DO1.Error Code

DO2.Error Code

Read

Error mask for all digital outputs


0x0001 Error in digital output range
0x0002 MEZ test of safety shutdown failed
0x0004 MEZ test, auxiliary supply failed
0x0008 FTZ test of test pattern failed
0x0010 MEZ test of test pattern of the output switch failed
0x0020 MEZ test of test pattern of the output switch (disconnection test
of outputs) failed
0x0040 MEZ test, active disconnection via watchdog failed
0x0200 All outputs switched off, total current exceeded
0x0400 FTZ test: 1. Temperature threshold exceeded
0x0800 FTZ test: 2. Temperature threshold exceeded
0x1000 FTZ test: Monitoring of auxiliary supply 1: Undervoltage

DO1[xx].Error Code(1)

DO1[xx].Value

DO2[xx].Error Code(1)

DO2[xx].Value

Publication 1753-UM001C-EN-P - March 2010

Read

Write

Error mask of all digital output channels


0x01

Error in digital output module

0x02

Output switched off due to overload

0x04

Error when reading back the activation of the digital outputs

0x08

Error when reading back the status of the digital outputs

0x40

external short-circuit or short-circuit of EMC protection yield to


an error

0x80

channel is switched off due to an error in the corresponding DO


channel

Output value of the digital output channels


0

The output is not set, no current

The output is set

319

Appendix B

System Signal Variables

I/O Data
L+ Switching Outputs

L- Switching Outputs

DO2[xx].2 Pole used

Switch-on delay

Read/
Write

Description

Write

Configures the channel for 2 pole operation.

Write

channel DO2[xx] is not used for 2-pole operation.

channel DO2[01] is used for 2-pole operation with channel


DO1[04], or
channel DO2[02] is used for 2-pole operation with channel
DO1[08]

Sets switch-on delay for 2-pole tests, due to lamp load, inductive and
capacitive load

(1) xx = affected output channel of the controller or module.

Digital Output Parameters for 1753-IB16XOB8 Modules


In addition to the output parameters in the table on page 318, the
GuardPLC 1753-IB16XOB8 module features these digital output
parameters.
I/O Data

Read/Write

Description

DO.Error Code

Read

Error mask for all digital outputs

320

0x0001

Error in digital output range

0x0002

MEZ test of safety shutdown failed

0x0004

MEZ test, auxiliary supply failed

0x0008

FTZ test of test pattern failed

0x0010

MEZ test of test pattern of the output switch failed

0x0020

MEZ test of test pattern of the output switch (disconnection test of


outputs) failed

0x0040

MEZ test, active disconnection via watchdog failed

0x0080

FTZ test of the period monitoring causes an error.

0x0100

FTZ read back of the period monitoring causes an error

0x0200

All outputs switched off, total current exceeded

0x0400

FTZ test: 1. Temperature threshold exceeded

0x0800

FTZ test: 2. Temperature threshold exceeded

0x1000

FTZ test: Monitoring of auxiliary supply 1: Undervoltage

0x2000

FTZ test: Monitoring of auxiliary supply 2: Undervoltage

0x4000

Flip-flop of the supply monitoring (18V) causes undervoltage

0x8000

MEZ test of the period monitoring causes an error

Publication 1753-UM001C-EN-P - March 2010

System Signal Variables

I/O Data

Read/Write

Description

DO[xx].+Error Code(1)
DO[xx].-Error Code

Read

Error code of digital outputs DO+


Error code of digital outputs DO0x0001

Error in the digital output module

0x0002

Output switched off due to overload

0x0004

Error reading back the activation of digital outputs

0x0008

Error reading back status of the digital outputs

0x0010

Short-circuit

0x0020

Channel is switched off due to an error in the corresponding DO


channel

0x0040

Zener diode at the output is not alloyed

0x0080

Line break

0x0100

MEZ test of the output switches in the DO+ line caused an error

0x0200

MEZ test of the output switches in the DO- line caused an error

0x0400

MEZ test of the L- test switch caused an error

0x0800

External L+ supply at DO+

DO.LSLB period(2)

Write

Period during which line monitoring is carried out.


Values in one second increments from 1100 s.

DO.LSLB time

Write

Time for Line Short Line Break (LSLB) monitoring.


Values in one millisecond increments from 0 50 ms. The default is 0 ms.

DO[xx].2-pole

Write

Configures the module for 2-pole operation


0

1-pole operation

2-pole operation

DO[xx].+Value

Write

Output value for DO channels (DO+)


1-pole (Value:0 or 1)
2-pole, identical to DO- (Value: 0 or 1)

DO[xx].-Value

Write

Output value for DO channels (DO-)


1-pole (Value:0 or 1)
2-pole, identical to DO+ (Value: 0 or 1

DO[xx].LSLB monitoring

Write

Configures line control

DO[xx]LS monitoring with


reduced voltage

DO[xx][xx].in pairs

Write

Write

Appendix B

no LSLB (line control)

set for LSLB (line control)

Configures line control with reduced voltage


0

normal signal voltage level

reduced signal voltage level

Configures line control with channel pairs


Pair 1

channel 1 [01] and channel 2 [02

Pair 2

channel 3 [03] and channel 4 [04

Pair 3

channel 5 [05] and channel 6 [06

Pair 4

channel 7 [07] and channel 8 [08]

(1) xx = affected output channel of the controller or module.


(2) LSLB = Line Short Line Break

Publication 1753-UM001C-EN-P - March 2010

321

Appendix B

System Signal Variables

Digital Relay Output Parameters for 1753-OW8 Modules


The 1753-OW8 module supports these digital output parameters.
I/O Data

Read/Write

Description

DO.Error Code

Read

Error mask for all digital outputs

DO[xx].Error Code(1)

Read

0x0001

Module error

0x0002

MEZ test, safety switch 1 failed

0x0004

MEZ test, safety switch 2 failed

0x0008

FTZ test of test pattern failed

0x0010

MEZ test of test of readback channels failed

0x0020

MEZ test, active disconnection failed

0x0040

Error with initialization: relays

0x0080

FTZ test: error of relay voltage

0x0100

FTZ test of chip select (cs) signals failed

0x0400

FTZ test: 1. Temperature threshold exceeded

0x0800

FTZ test: 2. Temperature threshold exceeded

0x1000

MEZ test: status of safety switch 1

0x2000

MEZ test: status of safety switches

0x4000

MEZ test: active disconnection by watchdog failed

Error code of digital output channels


0x01

Error in the digital output module

0x04

Error reading back the digital outputs

0x10

Error reading back relay [x].1 (The channel is permanently


deactivated.)

0x20

Error reading back relay [x].2 (The channel is permanently


deactivated.)

0x80

Channel cannot be activated after deactivation by:


user program
forcing
channel/module failure

DO[xx].Value

Write

Output value for DO channels


0

Output not powered.

Output activated.

(1) xx = affected output channel of the controller or module.

322

Publication 1753-UM001C-EN-P - March 2010

System Signal Variables

Appendix B

Analog Input Signals for 1753-IF8XOF4 Modules


The 1753-IF8XOF4 module supports these analog input signals.
I/O Data

Read/Write

Description

Module.SRS

Read

Slot number (System.Rack.Slot)

Module.Type

Read

Module type: 0x001E

Module.Error.Code

Read

Error mask for the module

AI.Error Code

Read

Publication 1753-UM001C-EN-P - March 2010

0x0000

I/O processing may be running with errors

0x0001

No I/O processing (CPU not in RUN)

0x0002

No I/O processing during start-up tests

0x0004

Manufacturing interface running

0x0010

No I/O processing due to incorrect configuration

0x0020

No I/O processing due to exceeded fault rate

0x0040/80

No I/O processing because configured module is not plugged in

Error mask for all analog inputs


0x0001

Module error

0x0004

MEZ test, time monitoring of conversion

0x0008

FTZ test: walking bit of data bus faulty

0x0010

FTZ test: Operating voltages faulty

0x0020

MEZ test, active disconnection failed

0x0040

A/D conversion faulty

0x0080

MEZ test: cross links of MUX faulty

0x0100

MEZ test: walking bit of data bus faulty

0x0200

MEZ test: multiplexer addresses faulty

0x0400

MEZ test: operating voltages faulty

0x0800

MEZ test: measuring system (characteristic) faulty (unipolar)

0x1000

MEZ test: measuring system (final values, zero point) faulty


(unipolar)

0x8000

A/D conversion faulty (DRDY_HIGH)

323

Appendix B

System Signal Variables

I/O Data
AI[xx].Error Code

(1)

Read/Write

Description

Read

Error code of analog input channels


0x01

Error in the analog input module

0x02

Limit value underflow/overflow

0x04

A/D converter faulty; measuring values not valid

0x08

Measured value not within safety accuracy

0x10

Measured value overflow

0x20

Channel not in operation

0x40

Address error of both A/D converters

AI[xx].Value

Read

Analog value of each channel [INT] from 02000 (0V10V). The validity depends on
the AI[xx].Error Code.

AI[xx].Used

Write

Configures the channel for operation

AI[xx].Transmitter Used

Transmitter Voltage[01]

Transmitter.Error Code

Transmitter[01].Error Code

Write

Write

Read

Read

Channel is not in operation.

Channel is operating.

Configures the channel for transmitter supply


0

Transmitter supply is not used.

Transmitter supply is used.

Configures switchover of the transmitter supply per group


1

8.2V

26.0V

Error codes of the transmitter unit


0x0001

Error in the transmitter supply

0x0400

FTZ test 1: temperature threshold exceeded

0x0800

FTZ test 2: temperature threshold exceeded

Error codes of each transmitter group


0x01

Module error of transmitter supply

0x02

Overcurrent of transmitter supply

0x04

Undervoltage of transmitter supply

0x08

Overvoltage of transmitter supply

AI[xx].Underflow

Read

Underflow AI[xx].Value according to AI[xx].Limit LOW.


The validity depends upon the AI[xx].Error Code.

AI[xx].Overflow

Read

Overflow AI[xx].Value according to AI[xx].Limit HIGH.


The validity depends upon the AI[xx].Error Code.

AI[xx].Limit LOW

Write

Upper limit of voltage range 0-signal AI[xx].Underflow

AI[xx].Limit HIGH

Write

Lower limit of voltage range 0-signal AI[xx].Overflow

(1) xx = affected output channel of the controller or module.

324

Publication 1753-UM001C-EN-P - March 2010

System Signal Variables

Appendix B

Analog Output Signals for 1753-IF8XOF4 Modules


The 1753-IF8XOF4 module supports these analog output signals.
I/O Data

Read/Write

Description

Module.SRS

Read

Slot number (System.Rack.Slot)

Module.Type

Read

Module type: 0x

Module.Error.Code0069

Read

Error mask for the module

AO.Error Code

AO[xx].Error Code(1)

AO[xx].Value

Read

Read

Write

0x0000

I/O processing may be running with errors

0x0001

No I/O processing (CPU not in RUN)

0x0002

No I/O processing during start-up tests

0x0004

Manufacturing interface running

0x0010

No I/O processing due to incorrect configuration

0x0020

No I/O processing due to exceeded fault rate

0x0040/80

No I/O processing because configured module is not plugged in

Error mask for all analog inputs


0x0001

Module error

0x0002

MEZ test: safety switch 1 failed

0x0004

MEZ test: safety switch 2 failed

0x0008

FTZ test: of test pattern failed

0x0010

FTZ test: error checking coefficients

0x0400

FTZ test: 1. Temperature threshold exceeded.

0x0800

FTZ test: 2. Temperature threshold exceeded.

0x2000

MEZ test: status of safety switches

0x4000

MEZ test: active disconnection by watchdog failed

Error code of analog input channels


0x01

Error in the analog output unit

0x80

AO[xx].Value not in the specified range.

Output value of AO channels:


Current characteristic: 02000 (0 mA20 mA)
Current characteristic: -20000 (0 mA)
Values are tested for plausibility before standardization.
Current characteristic:
Values < 0: standardization with 0
Values < sampling point LOW: standardization with sampling point LOW
Values > sampling point HIGH: standardization with sampling point HIGH
IMPORTANT: Outputs must not be used as safety-related outputs!

AO[xx].Used

Write

Configures the channel for operation


0

Channel is not in operation.

Channel is operating.

(1) xx = affected output channel of the controller or module.

Publication 1753-UM001C-EN-P - March 2010

325

Appendix B

System Signal Variables

Counter Module Variables for GuardPLC 1800 Controllers


The GuardPLC 1800 controllers support these counter parameters.
I/O Data

Read/Write

Description

Module.SRS

Read

Slot number (System.Rack.Slot)

Module.Type

Read

Module type
0x0003

Module.Error.Code

Cnt.Error Code

Cnt[0x].Error Code(1)

Read

Read

Read

high speed counter module for GuardPLC 1800 controllers

Error mask for the module


0x0000

I/O processing may be running with errors

0x0001

No I/O processing (CPU not in RUN)

0x0002

No I/O processing during start-up tests

0x0004

Manufacturing interface running

0x0010

No I/O processing due to incorrect configuration

0x0020

No I/O processing due to exceeded fault rate

0x0040

No I/O processing because configured module is not plugged in

Error mask of counter module


0x0001

Error in module

0x0002

Error comparing the time base

0x0004

Address error reading the time base

0x0008

Parameters for the time base are faulty

0x0010

Address error reading the counter content

0x0020

Configuration of counter damaged

0x0040

Address error reading the Gray Code

0x0080

FTZ test of the test pattern failed

0x0100

FTZ test, error checking the coefficients

Error mask of counter channels 1 and 2


0x01

Error in counter module

0x02

Error comparing contents of counters

0x04

Error comparing the timestamps of the counters

0x08

Error setting the parameters (reset)

Cnt[0x].Value(1)

Read

Content of counters: 24-bit for pulse counter, 3-bit for Gray Code

Cnt[0x].Timestamp(1)

Read

Time stamp for Cnt[0x].Value 24-bit, time resolution 1s

Cnt[0x].Value Overflow(1)

Read

Counter overflow indication

326

True

24-bit overflow since last measurement


(only if Cnt[0x].Auto Advance Sense = False)

False

No overflow since last cycle

Publication 1753-UM001C-EN-P - March 2010

System Signal Variables

I/O Data
Cnt[0x].Time Overflow

Cnt[0x].Direction(1)

Cnt[0x].Auto Advance
Sense(1)

Cnt[0x].Reset(1)

Cnt[0x].5/24V Mode(1)

Cnt[0x].Gray Code(1)

(1)

Read/Write

Description

Read

Overflow indication for the time stamp of the counters

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

True

24-bit overflow since last measurement

False

No 24-bit overflow since last measurement

Appendix B

Counting direction of the counter


(only if Cnt[0x].Auto Advance Sense = False)
True

upward (increment)

False

downward (decrement)

Automatic counter direction recognition


True

Automatic recognition on

False

Manual setting of counter direction

Reset counter
True

No reset

False

Reset

Counter input 5V or 24V


True

24V

False

5V

Decoder or pulse operation


True

Gray Code decoder

False

Pulse operation

(1) Ox = counter 01 or 02.

Publication 1753-UM001C-EN-P - March 2010

327

Appendix B

System Signal Variables

Digital (Analog) Input Variables for the GuardPLC 1800 Controller


The digital inputs on the GuardPLC 1800 controller are actually analog
inputs with these configurable parameters.
I/O Data

Read/Write

Description

Module.SRS

Read

Slot number (System.Rack.Slot)

Module.Type

Read

Module type

Module.Error.Code

AI.Error Code

328

Read

Read

0x00D2

Digital input module (MI24/8 FS:1000) for GuardPLC 1800


controllers

0x0096

Digital input module (MI24/8 FS:2000) for GuardPLC 1800


controllers

Error mask for the module


0x0000

I/O processing may be running with errors

0x0001

No I/O processing (CPU not in RUN)

0x0002

No I/O processing during start-up tests

0x0004

Manufacturing interface running

0x0010

No I/O processing due to incorrect configuration

0x0020

No I/O processing due to exceeded fault rate

0x0040

No I/O processing because configured module is not plugged in

Error mask for all digital (analog) inputs


0x0001

Error in input range

0x0008

FTZ test: walking bit of data bus faulty

0x0010

FTZ test: error checking coefficients

0x0020

FTZ test: operating voltages faulty

0x0040

A/D conversion faulty (DRDY_LOW)

0x0080

MEZ test: cross links of MUX faulty

0x0100

MEZ test: walking bit of data bus faulty

0x0200

MEZ test: multiplexer addresses faulty

0x0400

MEZ test: operating voltages faulty

0x0800

MEZ test: measuring system (characteristic) faulty (unipolar)

0x1000

MEZ test: measuring system (final values, zero point) faulty


(unipolar)

0x8000

A/D conversion faulty (DRDY_HIGH)

Publication 1753-UM001C-EN-P - March 2010

System Signal Variables

I/O Data

Read/Write

Description

AI[xx].Error Code
DI[xx].Error Code

Read
Read

Error mask for analog input channels (18)


Error mask for digital input channels (932)
0x01

Error in input module

0x02

Measured values invalid

0x04

A/D converter faulty

0x08

Measured value not within the safety accuracy

0x10

Measured value overflow

0x20

Channel not in operation

0x40

Address error of both A/D converters

0x80

Configuration of hysteresis faulty

AI[xx].Value Analog

Read

Analog value of AI channels (18) [WORD] from 01000


The validity is dependent on the error mask.

DI[xx].Value Analog

Read

Analog value of the DI channels (932) [WORD] from 03000


The validity is dependent on the error mask.

DI[xx].Value Bool

Read

Digital value of DI channels (932) [BOOL] according to hysteresis


The validity is dependent on the error mask.

AI[xx].Hysteresis LOW

Write

Upper limit of the 0-signal voltage range DI[xx].Value Bool

AI[xx].Hysteresis HIGH

Write

Lower limit of the 1-signal voltage range DI[xx].Value Bool

AI[xx].Used
DI[xx].Used

Write
Write

Configuration for indicating utilization of channels 18


Configuration for indicating utilization of channels 932

Publication 1753-UM001C-EN-P - March 2010

Appendix B

329

Appendix B

System Signal Variables

Notes:

330

Publication 1753-UM001C-EN-P - March 2010

Appendix

Wiring Examples

Introduction
Topic

Page

GuardPLC 1600 Controller

332

GuardPLC 1800 Controller

333

1753-IB16 Modules

334

1753-OB16 Modules

335

1753-IB20XOB8 Module

336

1753-IB8XOB8 Modules

337

1753-IB16XOB8 Modules

338

1753-OW8 Modules

339

1753-IF8XOF4 Modules

340

GuardPLC 1200 Controller

341

1755-IB24XO16 Digital Input/Output Modules

342

1755-IF8 Analog Input Modules

343

1755-OF8 Analog Output Modules

343

1755-HSC High Speed Counter Module

344

IMPORTANT

The wiring diagrams in this appendix detail only the wiring


necessary to sense/control the I/O devices.
They do not show all of the wiring necessary to achieve Cat. 3
or Cat. 4 safety circuits.
For example, monitoring feedback signals is not illustrated.

Publication 1753-UM001C-EN-P - March 2010

331

Appendix C

Wiring Examples

GuardPLC 1600 Controller

24V DC
Power
Supply

24V DC
Power
Supply

+
COM

COM
A1

A2

CH1

CH2

Safety Relay

()

()

PE
L- L-

L+

A1

A2

CH1

CH2

Safety Relay

10 11 12

10 11 12

Pulse-Tested
Safety Input

L+
DO L- 1 2 3 4 L-

24V DC

DO L- 5 6 7 8 L-

(2A)

(2A)

RS-485
MODBUS

ASCII/HSP
COMM3

COMM2

COMM1

24 V DC
RUN

Dry
Contact

ERROR
PROG
FORCE
FAULT

1753-L28BBBM
20 DC Inputs
8 DC Outputs

OSL
BL
D1
LS+- 1 2 3 4 L-

GuardPLC Ethernet

D1
LS+ 5 6 7 8 L-

D1
LS+ 9 10 11 12 L-

D1
LS+ 13 14 15 16 L-

D1
LS+ 17 18 19 20 L-

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

13 14 15 16 23 24

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

10/100 BaseT
3

()

()

COM

COM

Dry Contact
Light Curtain/
Safety Input

332

24V DC
Power
Supply

+
COM

Light Curtain

Publication 1753-UM001C-EN-P - March 2010

Wiring Examples

Appendix C

GuardPLC 1800 Controller


Light Curtain/
Safety Input

+
COM

24V DC
Power
Supply

Light Curtain/
Safety Input
+

Dry Contact

+
COM

COM

COM

24V DC
Power
Supply

Pulse Tested
Safety Input

3 ()

PE

()

L-

L+

L+

24V DC

10

10

11 12 13 14 15 16 17 18 19 20

21 22 23 24 25 26 27 28 29 30

31 32 33 34 35 36 37 38 39 40

DO L- 1 2 3 4 5 6 7 8 L-

DI LS+ 1 2 3 4 5 6 7 8 L-

DI LS+ 1 2 3 4 5 6 7 8 L-

DI LS+ 1 2 3 4 5 6 7 8 L-

(2A)

11 12 13 14 15 16 17 18 19 20

21 22 23 24 25 26 27 28 29 30

31 32 33 34 35 36 37 38 39 40

(2A)

1753-L34BBBP
24 DC Inputs
8 DC Outputs
8 Analog Inputs
2 High Speed Counters

RS-485
PROFIBUS

ASCII/HSP
COMM3

COMM2

24 V DC

COMM1

RUN
ERROR
PROG
FORCE

AI

AI
T1 I1

L- T2 I2

L-

T3 I3

AI
L- T4 I4

L-

T5 I4

AI
L- T6 I6

L-

T7 I7

HSC
L- T8 I8

L-

A1 B1 Z1 L- A2 B2 Z2 L-

FAULT
OSL

41 42 43 44 45 46

47 48 49 50 51 52

53 54 55 56 57 58

59 60 61 62 63 64

65 66 67 68 69 70

71 72

BL

GuardPLC Ethernet

10/100 BaseT
3 ()

()

AI
T5 I4

L- T6 I6

4-wire Device Using


External Power

L-

4-wire Device Using


Transmitter Supply
COM 24V DC
+

Power
Supply

+
2-wire Device Using External
Power

Publication 1753-UM001C-EN-P - March 2010

B Z

B Z

+ -

53 54 55 56 57 58

+ -

+
2-wire Device
Using
Transmitter
Supply

24V DC +
Power
Supply COM
24V DC +
Power
Supply COM

* If current: 500
If voltage: 10k

333

Appendix C

Wiring Examples

1753-IB16 Modules
24V DC
Power
Supply

COM

COM

COM

PE
L- L-

L+

L+

24V DC
Power
Supply

2 3 4 5 6

7 8 9 10 11 12

2 3 4 5 6

7 8 9 10 11 12

13 14 15 16 17 18

LS+ 1 2 3 4 L-

LS+ 5 6 7 8 L-

LS+ 9 10 11 12 L-

D1

D1

D1

13 14 15 16 17 18

24V DC

24 V DC
RUN
ERROR
PROG
FORCE
FAULT

1753-IB16
16 DC Inputs
4 Pulse Test Sources

OSL
BL

LS+ 13 14 15 16 L-

PO PULSE TEST
L- 1 2 3 4 L-

19 20 21 22 23 24

25 26 27 28 29 30

19 20 21 22 23 24

25 26 27 28 29 30

GuardPLC Ethernet

Pulse Tested
Safety Input

10/100 BaseT
1

()

()

Dry Contact

COM

Dry Contact
Light Curtain/
Safety Input

334

Publication 1753-UM001C-EN-P - March 2010

Wiring Examples

Appendix C

1753-OB16 Modules
24V DC
Power
Supply

24V DC
Power
Supply

+
COM
A1

A2

Safety Relay

COM

CH1

PE
L- L-

L+

24V DC

2 3 4 5 6

2 3 4 5 6

L+

L- L-

L+

24V DC

DO L- 1 2 3 4 L-

CH2

8 9 10 11 12

8 9 10 11 12

L+
DO L- 5 6 7 8 L-

24 V DC
RUN
ERROR
PROG
FORCE
FAULT

1753-OB16
16 DC Outputs

OSL
BL

DO L- 9 10 11 12 L-

DO L- 13 14 15 16 L-

13 14 15 16 17 18

19 20 21 22 23 24

13 14 15 16 17 18

19 20 21 22 23 24

GuardPLC Ethernet

10/100 BaseT
1

()

24V DC
Power
Supply

()

+
COM

Contactor
A1

A2

Safety Relay
CH1

CH2

Contactor
Load

Publication 1753-UM001C-EN-P - March 2010

335

Appendix C

Wiring Examples

1753-IB20XOB8 Module
24V DC
Power
Supply

24V DC
Power
Supply

+
COM

COM
A1

A2

Safety Relay
CH1

PE
L- L-

L+

CH2

2 3 4 5 6

8 9 10 11 12

2 3 4 5 6

8 9 10 11 12

A1

A2

CH1

CH2

Safety Relay

L+

24V DC

DO L- 1 2 3 4 L-

DO L- 5 6 7 8 L-

(2A)

(2A)

24 V DC
RUN
ERROR
PROG
FORCE
FAULT

1753-IB20OXB8
20 DC Inputs
8 DC Outputs

OSL
BL
D1
LS+ 1 2 3 4 L-

D1
LS+ 5 6 7 8 L-

D1
LS+ 9 10 11 12 L-

D1
LS+ 13 14 15 16 L-

Pulse-Tested
Safety Input

D1
LS+ 17 18 19 20 L-

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

13 14 15 16 23 24

19 20 21 22 23 24

25 26 27 28 29 30

31 32 33 34 35 36

37 38 39 40 41 42

Dry
Contact

GuardPLC Ethernet

10/100 BaseT
1

()

()

+
COM

+
COM

Dry Contact
Light Curtain/
Safety Input

336

24V DC
Power
Supply

+
COM

Light Curtain

Publication 1753-UM001C-EN-P - March 2010

Wiring Examples

Appendix C

1753-IB8XOB8 Modules
-

Load
-

Load

Contactor
Contactor

24V DC COM
Power
Supply

Load

1 2 3 4 5 6

7 8 9 10 11 12

13 14 15 16 17 18

L- 1 2 4- 8- S+
DO-

L- 1 2 3 4+LDO
(2A)

L- 5 6 7 8+LDO
(2A)

PE
L+ L+
L-L- L-L- L+
L+
24V DC
DC
24V

PO PULSE TEST

24 V DC
RUN
ERROR
PROG
FORCE
FAULT

1753-IB8XOB8
8 DC Inputs
8 DC Outputs

OSL
BL

D1
LS+ 1 2 3 4 L-

DI
LS+ 5 6 7 8 L-

19 20 21 22 23 24

25 26 27 28 29 30

GuardPLC Ethernet

10/100 BaseT
1(

( )

COM
+

COM 24V
+

DC
Power
Supply

Dry Contact
Light Curtain/
Safety Input

Publication 1753-UM001C-EN-P - March 2010

337

Appendix C

Wiring Examples

1753-IB16XOB8 Modules
-

Load

Load

24V DCCOM
Power +
Supply
1

PE
L- L- L+ L+
L- LL+ L+
24V DC

2 3 4 5 6

7 8

S+ S+ S+ S+ S- S- S- S-

9 10 11 12 13 14 15 16

17 18 19 20 21 22 23 24

1- 1+ 2- 2+ 3- 3+ 4- 4+
DO

5- 5+ 6- 6+ 7- 7+ 8- 8+
DO

25 26 27 28 29 30 31 32

1 1 1 1 2 2 2 2

24V DC

PO PULSE TEST

- DO +
1

24 V DC
RUN

ERROR

PROG

FORCE

FAULT

OSL

BL

LS+ LS+ 1 2 3 4

1753-IB16 OXB8
16 DC Inputs
8 DC Outputs

L- L-

LS+ LS+ 5 6 7 8

L- L-

LS+ LS+ 9 10 11 12 L- L-

LS+ LS+ 13 14 15 16 L- L-

GuardPLC Ethernet

10/100 BaseT
1

()

()

33 34 35 36 37 38 39 40 41 42

43 44 45 46 47 48 49 50 51 52

53 54 55 56 57 58 59 60 61 62

63 64 65 66 67 68 69 70 71 72

COM
+

Dry Contact

338

Light Curtain/
Safety Input

Publication 1753-UM001C-EN-P - March 2010

Wiring Examples

Appendix C

1753-OW8 Modules

Load

L2 or DC-

L1 or DC+
1

PE

L- L-

L+

24V DC

L+

DO 1

DO 2

DO 3

DO 4

1753-OW8
8 Digital Outputs

L1 or DC+

DO5

L1 or DC+

Publication 1753-UM001C-EN-P - March 2010

DO6

10

11

Load

12

DO7

13

14

DO8

15

16

L2 or DC-

339

Appendix C

Wiring Examples

1753-IF8XOF4 Modules

PE
L- L-

L+

L+

24V DC

24 V DC
1753-IF8XOF4
8 Analog Inputs
4 Analog Outputs

RUN
ERROR
PROG
FORCE
FAULT

AI

AI

T1 I1

L- T2 I2

L-

AI

T3 I3

L- T4 I4

L-

T5 I5

AO
O1

AI
L- T6 I6

L-

T7 I7

L- T8 I8

L-

O2
+

O3
+

O4
+

OSL
BL
1

10 11 12

13 14 15 16 17 18

19 20 21 22 23 24

25 26 27 28 29 30

31 32

STD ANALOG OUTPUTS

GuardPLC Ethernet

10/100 BaseT
1 <>

<> 2

*
*

4-wire device
with power
source from
GuardPLC

* 10 K for Voltage
500 for Current

340

+ + -

2-wire device
with power
source from
GuardPLC

Current
Output

+ + +

24V DC
+
Power
Supply COM

24V DC
Power
COM Supply

+
24V DC
Power
Supply COM

2-wire device with


external power source

Publication 1753-UM001C-EN-P - March 2010

Wiring Examples

Appendix C

GuardPLC 1200 Controller


A1 A2

Safety
Relay

CH1 CH2

COM

24V DC
Power
Supply

B Z

A1 A2

Safety
Relay

CH1 CH2
L+(1) L+(2) O1+ O2+ O3+ O4+ O5+ O6+ O7+ O8+ A1 B1 Z1
2

24V DC
Power
Supply

10

12

14

16

24V DC
Power
COM Supply
+

18

20

22

24

I-

26

28

+
COM
1

11

13

15

17

19

21

23

25

27

L-(1) L-(2) PA O1- O2- O3- O4- O5- O6- O7- O8- A2 B2

29

Z2

I-

Pulse-Tested
Safety Input

PE

Dry Contact

Dry Contact
Not
Used I2
+

I4

I6

I8 I10 I12 I14 I16 I18 I20


9

11

13

15

17

19

21

I23

I25

COM
+
2

Light
Curtain or
any Safety
Input

I1

I3

I5

10

I7

I9

12

14

16

18

20

22

I11 I13 I15 I17 I19 I-

24

24V DC
Power

COM Supply

I+
COM

Light
Curtain

Publication 1753-UM001C-EN-P - March 2010

341

Appendix C

Wiring Examples

1755-IB24XO16 Digital
Input/Output Modules
1755IB24XOB16

RUN ERR
1
2
3
4
5
6
7
8
9

LS+
I1
I2
I3
I4
I5
I6
I7
I8

10
11
12
13
14
15
16
17
18

LS+
I9
I10
I11
I12
I13
I14
I15
I16

19
20
21
22
23
24
25
26
27

LS+
I17
I18
I19
I20
I21
I22
I23
I24

28
29
30
31
32
33
34
35
36

L-

37
38
39
40
41
42
43
44
45

LO9
O10
O11
O12
O13
O14
O15
O16

Dry
Contact

Same power
supply used by
GuardPLC CPU

+
COM

Pulse Tested
Safety Input
O1
O2
O3
O4
O5
O6
O7
O8

A1

A2

Safety Relay
CH1

342

24V DC
Power
Supply

+
COM

CH2
+
COM
A1

24V DC Power
Supply

A2

Safety Relay
CH1 CH2

Publication 1753-UM001C-EN-P - March 2010

Wiring Examples

Appendix C

1755-IF8 Analog Input


Modules
10K (current devices)
500 (voltage devices)

1755IF8

10K

RUN ERR

external +
power
supply COM

1
2
3
4
5
6
7
8
9

2-wire transmitters

10
11
12
13
14
15
16
17
18

I1+
II2+
II3+
II4+
I-

singleended
voltage

external
power
supply

singleended
current

external
power
supply

differential
voltage

500

I5+/1II6+/2II7+/3II8+/4I-

external
power
supply

4-wire analog devices

1755-OF8 Analog Output


Modules
1755OF8

RUN ERR

Publication 1753-UM001C-EN-P - March 2010

1
2
3
4
5
6
7
8
9

O1+
O1O2+
O2O3+
O3O4+
O4-

+ voltage
output

external
+ power
supply

10
11
12
13
14
15
16
17
18

O5+
O5O6+
O6O7+
O7O8+
O8-

+ current
output

external
+
power
supply

343

Appendix C

Wiring Examples

1755-HSC High Speed


Counter Module
1755HSC

RUN ERR
1
2
3
4
5
6
7
8
9

CA1
B1
Z1
C1
CCCC-

10
11
12
13
14
15
16
17
18

CA2
B2
Z2
C2
CCCC-

19
20
21
22
23
24
25
26
27

344

A1
B1 +
Z1

+
COM

Same power
supply used
by GuardPLC
CPU

A1
B1 +
Z1

L1
2
3
4
LLLL-

+
COM

A1

24V DC
Power
Supply

24V DC
Power
Supply

A2

Safety Relay
CH1 CH2

Publication 1753-UM001C-EN-P - March 2010

Appendix

Replacing the Back-up Battery

The following procedures apply only to GuardPLC 1200 controllers


and GuardPLC 2000 power supplies. Other GuardPLC controllers and
I/O modules are not equipped with back-up batteries.

ATTENTION

A risk of fire or chemical burn exists if the battery is not


handled properly. Do not crush, puncture, disassemble, or short
external contacts, or expose the battery to temperatures higher
than 60 C (140 F).
For safety information on the handling and disposal of lithium
batteries, refer to Guidelines for Handling Lithium Batteries,
publication AG-5.4.

Preventing Electrostatic
Discharge

Only qualified personnel with knowledge of ESD protective measures


may replace the back-up battery.

ATTENTION

Electrostatic discharge can damage integrated circuits or


semiconductors. Follow these guidelines when you handle the
module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store equipment in appropriate static-safe packaging when not
in use.

Publication 1753-UM001C-EN-P - March 2010

345

Appendix D

Replacing the Back-up Battery

GuardPLC 1200 Controllers

Replace the back-up battery on your GuardPLC 1200 controller every


two years. The battery case is located on the left-hand side of the
cabinet (see drawing below). The battery must be replaced together
with the case.
Replacements are available from Rockwell Automation under part
number 1754-BAT.
Follow these steps to replace the battery.
Battery Case

Back-up Battery
and Case
(bottom view)

ATTENTION

Make sure that the GuardPLC 1200 controller is powered on.


Replacing the back-up battery while the controller is
de-energized causes a reset. All data including the clock
settings will be lost.

1. Press the left side of the battery case toward the controller and
pull the left side of the battery case toward you to remove the
battery case.
2. Insert a new battery case making sure that the case is correctly
aligned and the pins inside the GuardPLC 1200 controller are not
bent.
3. Press on the left edge of the case so that the pins seat in the
connector, then press on both sides of the case until the battery
snaps into place.

346

Publication 1753-UM001C-EN-P - March 2010

Replacing the Back-up Battery

GuardPLC 2000 Power


Supply

Appendix D

Replace the back-up battery every four years. Replacement batteries


are available from Rockwell Automation (1755-BAT).
Follow these steps to replace the battery.
ATTENTION

Make sure that the GuardPLC 2000 controller is powered on.


Replacing the back-up battery while the controller is off
causes a reset. All data including the clock settings will be
lost.

1. Remove the lid by removing the two


screws.

2. Use a flat-head screwdriver to remove the


battery from its compartment.

3. Insert a new battery, following the polarity


shown on the compartment.
IMPORTANT

Battery Disposal

Make sure that the contact pins inside the battery compartment
are not damaged.

Dispose of the used battery in accordance with local regulations.

ATTENTION

Do not incinerate or dispose of lithium batteries in


general trash collection. They may explode or rupture
violently. Follow all local regulations for disposal of
these materials. You are legally responsible for hazards
created during disposal of your battery.

GuardPLC 1200 controllers and GuardPLC 2000 power


supplies contain a sealed lithium battery which may need
to be replaced during the life of the product.
At the end of its life, the battery contained in this product
should be collected separately from any unsorted
municipal waste.
The collection and recycling of batteries helps protect the
environment and contributes to the conservation of
natural resources as valuable materials are recovered.

Publication 1753-UM001C-EN-P - March 2010

347

Appendix D

Replacing the Back-up Battery

Notes:

348

Publication 1753-UM001C-EN-P - March 2010

Index
Numerics
1753-CBLDN 40
1753-DNSI 40
1754-BAT
replacement 346
1755-BAT
replacement 347
1755-HSC status indicators 149
1755-IF8 status indicators 148
1755-OF8 status indicators 149
1-pole connection
1753-IB16XOB8 87
1753-IB8XOB8 example 81
1753-IB8XOB8 operation 78
2-pole connection
1753-IB16XOB8 88
1753-IB8XOB8 configuration 79
1753-IB8XOB8 example 81
1753-IB8XOB8 operation 79
3-pole connection
1753-IB16XOB8 89

A
acknowledge timeout 159
adapter
input assembly 215
output assembly 216
adapter assemblies
connect signals 217
analog data 309, 311
ASCII
connecting 265
data type formats 273
master request 270
overview 28
protocol 270
serial port 268
signals 269
slave response 271
assembly ID
adapter input assembly 216
adapter output assembly 217

B
battery
replacement 345-347
Bus Cycle Time 155

Publication 1753-UM001C-EN-P - March 2010

C
check consistency 135
CIP messaging
PanelView Standard terminals 243-248
code generator version 178
communication
ASCII 28, 265
control panel 123
EtherNet/IP 28
High-speed safety protocol 29
Modbus 29, 275
Peer-to-Peer 151
PROFIBUS 29
communication time slice 176
configuring
controllers 117
counters 109
EtherNet/IP driver 252
serial port 268
connecting
ASCII device 265
ASCII signals 269
Modbus device 276
Modbus signals 277
Profibus DP device 279
Profibus DP signals 280
scanner signals 250
signals to adapter assemblies 217
connection control system tag 182
connection state system tag 181
control panel 123
controllers
configuring 117
control panel 123
GuardPLC 1200 status indicators 142
GuardPLC 1600 status indicators 143
GuardPLC 1800 status indicators 143
GuardPLC 2000 status indicators 145
modes 113
serial port 268
switches 119
system variables 305
counter configuration 109
counter mode
inputs 108
counter modes 107
counters
data 312
gray code 111
with direction and reset 110
with manual direction 109

349

Index

D
data initialization 217
data types 273
decoder mode 111
inputs 108
DeviceNet Safety Scanner for GuardPLC
See 1753-DNSI.
diagnostics
1755-HSC status indicators 149
1755-IF8 status indicators 148
1755-OF8 status indicators 149
controller 139
distributed I/O 143
filtering 141
GuardPLC 1200 status indicators 142
GuardPLC 1600 status indicators 143
GuardPLC 1800 status indicators 143
GuardPLC 2000 status indicators 145
viewing 139
digital data 307
driver types 237, 252

E
EDS files 253
Ethernet
see GuardPLC Ethernet
EtherNet/IP
add to project 203
configure a driver 237
configure driver 252
overview 28, 199
related publications 205
required software 203
exclusive owner connection 221, 257

GuardPLC 1600
connecting ASCII device 266
overview 22
status indicators 143
GuardPLC 1800
connecting ASCII device 266
overview 22
status indicators 143
GuardPLC 2000
1755-HSC terminals 68
1755-IB24XO16 wiring 342
1755-IF8 wiring 343
1755-OF8 wiring 343
connecting ASCII device 267
overview 25
status indicators 145
GuardPLC Ethernet
overview 27

H
HH Network Profiles 161-167
fast 161
medium 164
None 167
HH protocol parameters 153-156
HH-Network 178-180
High Level High Speed (HH) protocol 151
High-Speed Safety Protocol 23, 29
connections 40

I
I/O data 307
input only connection 222, 257
IP addresses
definition 205

F
Faults
response 20
filtering diagnostic data 141

G
gateway 205
gray code 111
GSD file 282
GuardPLC 1200
connecting ASCII device 265
overview 21
status indicators 142

350

L
line control
1753-IB16 104
1753-IB16XOB8 104
1753-IB20XOB8 103
1753-IB8XOB8 104
GuardPLC 1600 103
response to faults 102
line monitoring
1753-IB16XOB8 89
Line Short Line Break monitoring 91
lamp and inductive loads 91
required signals 93
resistive, capacitive loads 92
Publication 1753-UM001C-EN-P - March 2010

Index

link mode 155


link mode (extern) 156
listen only connection 223, 257
Logix controllers
as scanners 218
Class 1 connections 219-228
Class 3 connections 228-234
related publications 230

M
manuals, related 18
Modbus
configuring 276
connecting 276
overview 29
protocol 279
signals 277
modes
controllers 113
routines 120
monitoring
diagnostics 139
See also line monitoring.

O
OPC Server
overview 30

P
PanelBuilder32 software
version level 243
PanelView Standard terminals
CIP messaging 243-248
related publications 244
PCCC messaging 235-243
Peer-to-Peer Network Profiles 168-174
fast & cleanroom 169
fast & noisy 170
medium & cleanroom 171
medium & noisy 172
slow & cleanroom 173
slow & noisy 174
Peer-to-Peer protocol 151
PLC-5 controllers
PCCC messaging 235-243
related publications 236
power supply connections
distributed I/O 49, 64, 70
GuardPLC 1600 49, 64, 70
GuardPLC 1800 49, 64, 70
Publication 1753-UM001C-EN-P - March 2010

primary controller 156


primary timout 156
production rate 160
Profibus DP Slave
configuring 280
connecting 279
overview 29
protocol 282
signals 280
publications, related 18
pulse test sources
1753-IB16 104
1753-IB16XOB8 104
1753-IB8XOB8 104
configuration 105

Q
queue length 159

R
receive timeout
definition 158
reconfiguring 197
setting 159
Requested Packet Interval
in scanlist configuration 257
resend timeout 159
reset pushbutton 43
response time
definition 155, 157
reconfiguring 195
variables 158
response time (extern) 156
routines
modes 120
RPTO/SPTO function blocks 101
RSLinx software 203, 237, 252
RSLogix Guard PLUS, Hardware
Management
version level 203
RSLogix Guard PLUS, Program
Management
version level 203
RSNetWorx for EtherNet/IP
version level 203
Run/Idle header 216, 217
in Class 3 connections 228
with CIP messages 243
with Logix controllers 218
with PCCC messages 236
351

Index

S
Safe States
inputs 21
outputs 21
safety concept 19
scanlist configuration 254-259
scanner
connect to Logix controller 260-261
disable function 251
input buffer 249
output buffer 249
remove connection configuration 263
save connection configuration 262
scanner signals
connect 250
secondary controller 156
secondary interval 156
serial port 268
signals
ASCII 269
counter data 312
I/O data 307
Modbus 277
Profibus DP 280
system variables 305
SLC 5/05 controllers
PCCC messaging 235-243
related publications 236
software version
PanelBuilder32 243
RSLogix Guard PLUS 203
RSNetWorx for EtherNet/IP 203

352

status indicators
See diagnostics.
subnet mask 205
switches 119
system variables 305

T
terminals
1755-HSC 68
token alive timeout 156
token cycle time 155
token group
configuring 179
creating 178
definition 161
ID 154, 179

U
Unconnected adapter 235

V
variables
system 305

W
watchdog time 160
reconfiguring 192
worst-case reaction time
definition 160
variables 160

Publication 1753-UM001C-EN-P - March 2010

Rockwell Automation Support


Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and
application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the
best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect
support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/support/.

Installation Assistance
If you experience an anomoly within the first 24 hours of installation, review the information that's contained in this manual.
You can contact Customer Support for initial help in getting your product up and running.
United States or Canada

1.440.646.3434

Outside United States or


Canada

Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html,


or contact your local Rockwell Automation representative.

New Product Satisfaction Return


Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing
facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States

Contact your distributor. You must provide a Customer Support case number (call the phone number
above to obtain one) to your distributor to complete the return process.

Outside United States

Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Publication 1753-UM001C-EN-P - March 2010 354


Supersedes Publication 1753-UM001B-EN-P - November 2005

Copyright 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

GuardPLC Controller Systems

User Manual

You might also like