This document summarizes the air system sizing for AHU-1 in Colombo, Sri Lanka. It was prepared on 07/14/2016 for a 1-zone air handling unit serving a 30.3 square meter floor area. Key specifications include a central cooling coil load of 6.8 kW requiring 427 L/s of air at peak conditions in February. The outdoor air ventilation rate was designed for 17 L/s. Fan power was calculated at 0 kW given the 472 L/s maximum airflow requirement.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
21 views1 page
Air System Sizing Summary For AHU-1
This document summarizes the air system sizing for AHU-1 in Colombo, Sri Lanka. It was prepared on 07/14/2016 for a 1-zone air handling unit serving a 30.3 square meter floor area. Key specifications include a central cooling coil load of 6.8 kW requiring 427 L/s of air at peak conditions in February. The outdoor air ventilation rate was designed for 17 L/s. Fan power was calculated at 0 kW given the 472 L/s maximum airflow requirement.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1
Air System Sizing Summary for AHU-1
Project Name: cecb project 1
07/14/2016 Prepared by: sanjeev 03:58PM
Air System Information
Air System Name ............................................... AHU-1 Equipment Class ......................................... SPLT AHU Air System Type ............................................ 1FDDVAV
Number of zones ............................................................. 1
Floor Area ................................................................... 30.3 m Location ........................................... Colombo, Sri Lanka
Sizing Calculation Information
Zone and Space Sizing Method: Zone L/s ............................... Peak zone sensible load Space L/s ...................... Individual peak space loads
Calculation Months ......................................... Jan to Dec
Sizing Data ...................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ............................................................ 6.8 Sensible coil load ..................................................... 6.3 Coil L/s at Feb 1600 ................................................ 427 Max block L/s at Feb 1600 ...................................... 472 Sum of peak zone L/s ............................................. 472 Sensible heat ratio ............................................... 0.919 m/kW ....................................................................... 4.4 W/m ..................................................................... 225.9 Water flow @ 5.6 K rise ......................................... N/A
kW kW L/s L/s L/s
Load occurs at ................................................... Feb 1600
OA DB / WB ...................................................... 34.8 / 26.6 Entering DB / WB ............................................. 25.0 / 17.1 Leaving DB / WB .............................................. 12.8 / 12.0 Coil ADP ..................................................................... 11.4 Bypass Factor .......................................................... 0.100 Resulting RH ................................................................. 44 Design supply temp. ................................................... 12.8 Zone T-stat Check .................................................... 1 of 1 Max zone temperature deviation .................................. 0.0
C C C C % C OK K
Central Heating Coil Sizing Data
Max coil load ............................................................ 0.2 kW Coil L/s at Des Htg ...................................................... 6 L/s Max coil L/s ................................................................. 6 L/s Water flow @ 11.1 K drop ...................................... N/A
Load occurs at ..................................................... Des Htg
W/m ............................................................................. 5.4 Ent. DB / Lvg DB .............................................. 21.3 / 43.3 C
Preheat Coil Sizing Data
No heating coil loads occurred during this calculation.
Supply Fan Sizing Data
Actual max L/s at Feb 1600 .................................... 472 L/s Standard L/s ............................................................ 472 L/s Actual max L/(s-m) .............................................. 15.59 L/(s-m)
Fan motor BHP ........................................................... 0.00 BHP
Fan motor kW ............................................................. 0.00 kW Fan static ......................................................................... 0 Pa L/s/person ................................................................... 5.53 ............................................................................L/s/person