Product Data Sheet: Tesys Gv2 - Circuit Breaker - Magnetic - 2.5 A - Screw Clamp Terminals

This document provides specifications for a TeSys GV2L07 circuit breaker. It is a 3-pole, magnetic trip circuit breaker rated for 2.5 amps. Key specifications include AC voltage ratings from 230-690V, breaking capacities from 4kA to 100kA, and suitability for motor protection applications up to 1.5kW. The breaker uses screw clamp terminals and has dimensions of 89x45x97mm.

Uploaded by

Ayyappa Raj
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views2 pages

Product Data Sheet: Tesys Gv2 - Circuit Breaker - Magnetic - 2.5 A - Screw Clamp Terminals

This document provides specifications for a TeSys GV2L07 circuit breaker. It is a 3-pole, magnetic trip circuit breaker rated for 2.5 amps. Key specifications include AC voltage ratings from 230-690V, breaking capacities from 4kA to 100kA, and suitability for motor protection applications up to 1.5kW. The breaker uses screw clamp terminals and has dimensions of 89x45x97mm.

Uploaded by

Ayyappa Raj
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Product data sheet

Characteristics

GV2L07

TeSys GV2 - Circuit breaker - magnetic - 2.5 A


- screw clamp terminals

Range

TeSys

Product name

TeSys GV2

Device short name

GV2L

Product or component
type

Circuit breaker

Circuit breaker application

Motor protection

Poles description

3P

Network type

AC

Utilisation category

Category A conforming to IEC 60947-2


AC-3 conforming to IEC 60947-4-1

Network frequency

50/60 Hz conforming to IEC 60947-2

Breaking capacity

Icu = 4 kA at 690 V AC 50/60 Hz conforming to IEC


60947-2
Icu = 100 kA at 500 V AC 50/60 Hz conforming to
IEC 60947-2
Icu = 100 kA at 440 V AC 50/60 Hz conforming to
IEC 60947-2
Icu = 100 kA at 400/415 V AC 50/60 Hz conforming
to IEC 60947-2
Icu = 100 kA at 230/240 V AC 50/60 Hz conforming
to IEC 60947-2

[Ics] rated service


short-circuit breaking
capacity

100 % at 400/415 V AC 50/60 Hz conforming to IEC


60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC
60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC
60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC
60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC
60947-2

Trip unit rating

2.5 A

Trip unit technology

Magnetic

Magnetic tripping current

33.5 A

Complementary
Mounting mode

By clips
By screws

Mounting support

Plate
Rail

Mounting position

Horizontal
Vertical

Motor power kW

1.5 kW at 690 V AC 50/60 Hz


1.1 kW at 500 V AC 50/60 Hz
0.75 kW at 400/415 V AC 50/60 Hz

Control type

Rotary knob

[Ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

[Ui] rated insulation voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-2

Power dissipation per pole

1.8 W

Mechanical durability

100000 cycles

Electrical durability

100000 cycles for AC-3 at 415 V

Operating rate

40 cyc/h

Apr 14, 2014

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.

Main

Rated duty

Continuous conforming to IEC 60947-4-1

Connections - terminals

Screw clamp terminals 2 cable(s) 1...4 mm - cable stiffness : flexible - with cable
end
Screw clamp terminals 2 cable(s) 1.5...6 mm - cable stiffness : flexible - without
cable end
Screw clamp terminals 2 cable(s) 1...6 mm - cable stiffness : solid

Tightening torque

1.7 N.m - on screw clamp terminals

Mechanical robustness

Vibrations 5 Gn, 5...150 Hz conforming to IEC 60068-2-6


Shocks 30 Gn conforming to IEC 60068-2-27

Suitability for isolation

Yes conforming to IEC 60947-1

Height

89 mm

Width

45 mm

Depth

97 mm

Product weight

0.33 kg

Environment
Standards

EN 60204
IEC 60947-1
IEC 60947-2
NF C 63-120
NF C 63-650
NF C 79-130
VDE 0113
VDE 0660

Product certifications

BV
CCC
CSA
DNV
GL
RINA
LROS

Protective treatment

TH

IK degree of protection

IK04

Ambient air temperature for operation

-20...60 C

Ambient air temperature for storage

-40...80 C

Fire resistance

960 C conforming to IEC 60695-2-1

Operating altitude

2000 m

You might also like