Client: Phed, Rajasthan Contractor: NCC Limited Project: Sheet of

The document is a test report for an over current/earth fault relay used in the Chambal Bhilwara Water Supply Project Phase 1 Package 1. The relay was tested at the Intermediate Pumping Station Tilswa. Test results showed the relay specifications matched the nameplate details and it was found fit for commissioning. Testing equipment used included a digital mini clamp meter and relay test kit, both of which are due for calibration in 2017. Commissioning checks of primary/secondary current injection and insulation resistance were performed and found to be okay.

Uploaded by

Jacob B Chacko
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
78 views1 page

Client: Phed, Rajasthan Contractor: NCC Limited Project: Sheet of

The document is a test report for an over current/earth fault relay used in the Chambal Bhilwara Water Supply Project Phase 1 Package 1. The relay was tested at the Intermediate Pumping Station Tilswa. Test results showed the relay specifications matched the nameplate details and it was found fit for commissioning. Testing equipment used included a digital mini clamp meter and relay test kit, both of which are due for calibration in 2017. Commissioning checks of primary/secondary current injection and insulation resistance were performed and found to be okay.

Uploaded by

Jacob B Chacko
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

CLIENT: PHED, RAJASTHAN

CONTRACTOR: NCC LIMITED

PROJECT: CHAMBAL BHILWARA WATER SUPPLY PROJECT


PHASE1 PACKAGE1

SHEET

OF

TEST REPORT FOR OVER CURRENT / EARTH FAULT RELAY


1. Designation : 6.6KV INCOMER1 (OVER CURRENT / EARTH FAULT RELAY )
Location

: INTERMEDIATE PUMPING STATION TILSWA

2. Name Plate Details :

MAKE
SR.NO.
I>>
I>
Ie>>
Ie>

ALSTOM
15CP1540072
PLUG SET
4
0.8
2.0
0.2

TYPE

P154

TMS
0.2
0.25
0.15
0.20

3. Remarks: Fit For Commissioning


4. Equipment used for testing:
Equipments

Make

S.no

Calibration Due

Digital Mini Clamp meter

Motwane

Z10687L11

12-06-2017

Relay test kit

Sudharsan

05/14

28-08-2017

Commissioning Checks
S.No. Details
1.
Primary or secondary current injection
testing of relays for their operation such as
indication/alarm/ control etc.
2.
Insulation resistance

TESTED BY

WITNESSED BY

Status

Checked &
Found Ok
Checked &
Found Ok

Refrence

As per approved documents


As per electrical standards

APPROVED BY