Water Curtain (20.04.16)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

GW

WATER CURTAIN NOZZLE


Bore
A (mm)

K - Factor

8.0
11.0
13.0
16.3
Materials:

32 A/F
HEX.

5
Connection: NPT male

(option: BSPT)

23
39
53
78

Weight (Brass)
215 g
206 g
185 g
165 g

Brass *)
Ni. Al. Bronze
St.Steel: AISI 316
St.Steel: 254 SMO
Titanium

*) Nozzles in brass
material can also be
supplied in an ENP
(electroless nickel
plating) coated
version for improved
corrosion resistance.

Description
The GW Water Curtain nozzle is developed to provide a flat fan spray when water is distributed in a 240 X 15
circular fan from the machined orifice slot located perpendicular to the nozzle axis.
Application:
The GW Water Curtain nozzle is designed for horizontal installation. It is typically installed as part of a deluge system
to protect a surface or area from heat radiation. With the orifice slot pointing upwards or downwards, the nozzle is
installed between the protected surface and the heat source. The water spray will both reflect and absorb the heat
radiation thus reducing the resultant level of heat reaching the protected surface.
Selection:
Nozzles should be selected to provide the required application rate for the hazard/application. Whilst the cooling /
protective effect of the water curtain is difficult to quantify a thumb rule is that small orifices operated at high
pressure will generate small droplets (water mist) with little mass and velocity and limited spray robustness (is easily
diverted by wind). The most robust spray is achieved by using nozzles with relatively large orifices, operated at low to
medium pressure (recommended working pressure: 2 to 5 barg). It is recommended to consult NFPA 15 chapter 6 and
7 for more guidance on nozzle selection and installation.
Installation:
The GW Water Curtain nozzles should be installed in such a way that a robust uninterrupted water curtain is
generated in front of the full surface of the protected structure/facility. The nozzle spacing should ideally provide a
50-75% spray overlap with the neighbour nozzle.
In order to avoid adjacent sprays from colliding, it is recommended to offset neighbour nozzles axially by ca. 200 mm.
to allow for a double layer parallel (overlapped) spray to be formed.

GW SPRINKLER A/S
Kastanievej 15, DK-5620 Glamsbjerg, Denmark
Tel: +45 64 72 20 55 Fax: +45 64 72 22 55
E-mail: [email protected]
Data sheet no.:

GW WS030 1001 D

The right is reserved to vary or modify any specifications without prior notice.

Data sheet:

GW Water Curtain Nozzle

Page

1 of 3

Date:

20 April 2016

GW
WATER CURTAIN NOZZLE

Water Curtain nozzle spray - schematic

120
120

Approx. 4 metre

GW SPRINKLER A/S
Kastanievej 15, DK-5620 Glamsbjerg, Denmark
Tel: +45 64 72 20 55 Fax: +45 64 72 22 55
E-mail: [email protected]
Data sheet no.:

GW WS030 1001 D

The right is reserved to vary or modify any specifications without prior notice.

Data sheet:

GW Water Curtain Nozzle

Page

2 of 3

Date:

20 April 2016

GW
WATER CURTAIN NOZZLE

Extract from NFPA 15:


Effective exposure protection is accomplished by application of water spray
directly to the exposed structures or equipment to remove or reduce the
heat transferred to them from the exposing fire. Water spray curtains are
less effective than direct application but can, under favourable conditions,
provide some protection against fire exposure through subdivision of fire
areas. Unfavorable conditions can include such factors as windage, thermal
updrafts, and inadequate drainage.

GW SPRINKLER A/S
Kastanievej 15, DK-5620 Glamsbjerg, Denmark
Tel: +45 64 72 20 55 Fax: +45 64 72 22 55
E-mail: [email protected]
Data sheet no.:

GW WS030 1001 D

The right is reserved to vary or modify any specifications without prior notice.

Data sheet:

GW Water Curtain Nozzle

Page

3 of 3

Date:

20 April 2016

You might also like