Sices ATS control panel is designed for mains/genset transfer switch applications that

involve a genset usually equipped with an automatic control panel. The ATS control panel
comprises all circuits, devices and controls, which enable the switch between the mains
and the genset, in order to supply the load in case of mains failure.
The ATS control panel is made with a steel sheet subjected to a painting treatment using
high resistance epoxy powder. The power circuit is safety split from the control area in
accordance to the main operation rules.

Multiple voltage
230/380/400/440V

The grade protection is IP20 with opened door. With closed door, it is IP40 for the BASIC
version and IP54 for the LOGICA version. IP55 is also available on demand.

Double frequency 50/60Hz


BASIC and LOGICA version
From 45A up to 4000A
Attractive price
Used by the greatest
genset companies

According to the power of the genset, the power circuit is composed by a couple of
interlocked contactors (up to 125A included) or by a motorized changeover switch, in both
cases 4 poles.
In addition, there is a version of ATS with power circuit composed by two automatic,
interlocked and motorized circuit breakers.
Starting from 160A, SICES ATS Control panels have MULTIPLE VOLTAGE and
MULTIPLE FREQUENCY.

Perfect for Dual Gensets


operations

Made in Italy
IS0 9001 certified

The voltages available are: 230/380/400/440V


Frequency: 50/60Hz

BASIC
VERSION

LOGICA
VERSION

Power Terminal board Mains/


Genset/Load

YES

YES

Selector switch
Mains Automatic 0 Genset

YES

NO

Keyboard with push buttons for


the mode/control selection

NO

YES

Optical signal with lamp/led to


advise the load is supplied by
the Mains

YES

YES

Optical signal with lamp/led to


advise the load is supplied by
the Genset

YES

YES

Fuses for protections

YES

YES

Adjustable three-voltage relay


Mains and Genset voltage

NO

YES

Microprocessor controller

NO

YES

Voltmeter for Mains voltage:


Phases L1-L2/L2-L3/L1-L3

NO

YES

Mains and Genset frequency


meter

NO

YES

Battery voltage meter

NO

YES

Working hour meter

NO

YES

Current transformers for the activation of currents, power and


cosfi measurement

NO

OPTION (*)

Automatic battery charger

NO

OPTION

Features:

BASIC VERSION: Its a manual ATS Control panel without


microprocessor-based controller, equipped with a 4 positions
switch selector with AUTOMATIC 0 MAINS GENSET and
lamps for optical signalling Load supplied by the Mains and
Load supplied by the Genset. Fuses, protections and terminal
boards are available as well. This type of ATS panel is usually
combined to a local genset control panel.
LOGICA VERSION: Its an automatic ATS Control panel
equipped with microprocessor-based controller with graphic
display that allows to show voltages, frequency, working hours
and the battery voltage of the genset. This type of ATS panel is
particularly suggested in combination to gensets with semiautomatic controllers that require an external contact to start
(e.g. Caterpillar, FG Wilson, Cummins, etc. gensets).
The LOGICA ATS panel supports a microprocessor-based
controller, available in two versions: ATS115 and ATS115

Plus

As option, its possible to add 3 CTs in order to enable the


current and power measure and the cosfi.

(*) Request to SICES SRL ([email protected])


ATS Control panel

Genset control panel

START Engine start push-button


STOP Engine stop push-button
ACK Acoustic alarm silencing push-button
UP/DOWN push-buttons for the display selection
MCB push-button
GCB push-button
N.4 ARROW keys for LCD display selection mode, window
selection, parameter change and other
EXIT and ENTER keys
SHIFT key
Operation panel and LEDs for the signalisation and selection
of the operation modes: off/reset/program, manual,
automatic, alarms/warnings, aux., mains live, genset live, etc.

Mains Voltage
L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1
True measure calibrated to RMS.
Lx-N max. voltage < 300Vac cat. IV
High voltage pulse = 6kV 1.2/50 us
Max. measurable voltage = 25.000V (by external TV).
Generator Voltages
L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1
True RMS measure.
Lx-N max. voltage < 300Vac cat. IV
High voltage pulse = 6kV 1.2/50 us
Max. measurable voltage = 25.000V (by external TV).
Generator Currents (Op t i o n al i n c as e ad d i t i o n al
current transformers)
L1, L2, L3, N
True RMS measure.
Nominal max. current: 5Aac
Overload measurable current : 4 x 5Aac (sinusoidal).
Internal current transformer.
Max. nominal current = 6000A (by external TA).
Generator and Mains Frequency meter
Resolution = 0.1 Hz.
Accuracy = 50ppm, 35ppm/C (typical)
Battery Voltmeter
Resolution = 0.1V

A set of high efficiency LEDs are used to inform on the


current status of the Mains and of the Genset and for the
visualization of any alarm. Secondary alarms are
represented by their corresponding display code.
Status and signalling
Source A live (Mains or Genset)
Source B live (Mains or Genset)
Source A circuit breaker closed
Source B circuit breaker closed
Start/Stop Source A or B
Remote start
Battery fault (Max/Min voltage)

Max. controller temperature


Emergency stop
Clock not configured
Protections
Genset X not stopped
Genset X out limit
Source A or B operating mode not reached
Phase sequence failure on Source A or B
Source A or B failure
Source A or B circuit breaker stopped
Source A or B circuit breaker open
Additional indications are available to display measures
and cumulative alarms.

N.1 USB Port for the configuration of parameters


As option:

Use of the ATS115Plus controller equipped with:


N.1 RS232 Serial port Modbus RTU
N.1 RS485 Serial port Modbus RTU
N.1 RJ45 Ethernet Serial port Modbus TCP/IP
Direct management of a PSTN and GSM modem
GSM/GPRS/GPS Modem
Optional circuits available:
Addition of a battery charger 5A 12/24Vdc
Addition of 3 CTs on the output
Dual Genset operation for the automatic switch of the two
gensets

Engine diagnostic codes


Periodic test
Clock and History log
Remote start and stop
Alarm horn
Different levels of password for the correct configuration of
the parameters
Graphic display 70x38 mm - 128x64 pixel
LCD display with LEDs
Multilanguage display: IT, EN, FR, RU, ES, PT/BR

Current

Dimensions
HxLxD mm

Weight

45A

600x400x200

25Kg

70A

600x400x200

25Kg

100A

600x400x200

25Kg

125A

600x400x200

25Kg

160A

1000x600x250

30Kg

250A

1000x600x250

56Kg

400A

1000x600x300

60Kg

630A

1000x600x400

90Kg

800A

1000x600x400

100Kg

1000A

1900x800x600

245Kg

1250A

1900x800x600

245Kg

1600A

1900x800x600

275Kg

2000A

1900x1000x800

335Kg

2500A

1900x1000x800

390Kg

3150A

1900x1000x1000

500Kg

4000A

1900x1000x1000

600Kg

Supply voltage: 230 400 Vac (others to be specified)


Available also multiple voltage version: 220/380/400/440V
Auxiliary voltage: 12 Vdc or 24 Vdc
Frequency: 50 Hz or 60 Hz
The electric diagrams are available in double language,
choosing among: EN, FR, IT, PT, ES.
Insulation: > 50 Mohm
Dielectric strength AC: 2500V/1'
Dielectric strength DC: 1000 V/1'
Level of protection: IP40 (BASIC version) or IP54
(LOGICA version)
Colour: RAL 7035
Ambient temperature: - 20 to + 70 C
Compliance to CEI IEC EN rules:
2006/95/CE LOW VOLTAGE DIRECTIVE
2004/108/CE EMC DIRECTIVE
93/68/CEE CE STAMP REGULATION
The ATS panel is designed and manufactured in
compliance with the ISO9001 certification