Fully automated three phase Transformer Turns Ratio Meter

The TTR 2795 provides a wide ratio range, which allows the
user to determine the ratio accuracy of power-, distribution
and instrument transformers.
In addition, the selectable test voltages of 100V, 40V, 10V and
1V avoid saturation effects on current transformers.

FEATURES AND BENEFITS


Fully automated measurement of turns ratio, voltage
ratio, phase displacement and excitation current.
Highest measurement accuracy in the industry of up to
0.03% makes the 2795 the perfect tool for preventive
maintenance measurement.
Automatic winding connection identification AWCI
(patent pending) and automatic vector group detection
supports the quick and easy operation.
On-site testing of turns ratio is an important basic
measurement for power transformer diagnosis.
It helps to detect faulty transformer windings as well as
defective tap changer positions. The simple ratio of turns or
voltage and the related ratio error is not sufficient to detect all
possible failures of a power transformer winding. The
excitation current and the phase angle between primary and
secondary windings give additional information about the
winding condition. The TTR 2795 provides all these
measurements in one compact instrument.
Transformer Turns Ratio Meter TTR 2795 is the next
generation of the very successful Tettex transformer turns
ratio meter line. The result of our close collaboration with
worldwide TTR users and industry specialists in power and
distribution transformers is this advanced instrument with its
unbeaten performance. The TTR 2795 measures turns ratio
with the highest accuracy in the industry and has one of the
largest turns ratio ranges commercially available.

Safety connection control feature proofs test setup before


applying test voltage to avoid any damage of personnel, test
equipment and instrument.
Build-in printer for quick test report generation and total
prevention of data loss.
User friendly self-explaining interface with one rotarypush-button for easy access to the menu structure.
Large graphic display shows all data at a glance and
displays tap changer results in a clear graphic diagram.
Lightweight, compact and rugged design for use in harsh
environments. Closed case is IP65 waterproof, open case is
splash proof.
Remote control software to operate the unit from a laptop
PC and for easy gathering exchanging and analyzing of
measurement data.

APPLICATIONS

This advanced instrument automatically recognizes winding


connections and vector group numbers of transformer
windings. Just connect the measuring cables and press the
start button and get the test results.

Turns Ratio, Voltage Ratio, Phase Displacement and Excitation Current measurements according to ANSI, IEC and AS
standards on


Power and Distribution Transformers

For an easy and fast detection of faulty tap positions, the


measured turns ratios vs. tap changer position is displayed
graphically.

Instrument Transformers

a brand of
Haefely is a subsidiary
of Hubbell Incorporated.

Haefely has a policy of continuous product improvement. Therefore we reserve the right to change design and specification without notice.

LL_TTR2795_1208_RS.doc 1/ 4

APPLICATION SOFTWARE APSW2795


The supplied user-friendly Windows software guides the
operator through the measurements and helps to create
experts analysis and provides easy report generating. The
software can be used on any PC or laptop with a serial RS232 interface.

On the measure page, the voltage-ratio, ratio-deviation and


phase deviation are shown in a large display.
In the middle part the actual test settings (tap, test voltage
and winding under test) can be selected by pressing a
button.

Measurements can be performed in rough environments by


only using the rugged instrument and the measured data
can later be uploaded to a PC or laptop.

In the bottom part the already measured data (history) is


clearly displayed and recorded in a table format.

Measure page where the measuring values are displayed


In moderate environments the instrument can be remote
controlled by a laptop or PC, in order to make optimal use
of the advanced user interface and its many features.
Device under Test (DUT) information data can be entered in
a very convenient way. Stored data can be used and data
sets can be compared.
In order to organize data properly, the transformer data
from the boilerplate as well as the data from the operator
can be used as input for the test setup.

Setup page to select vector group and tap-changer.


Additionally tertiary windings, vector group type, phase
displacement and tap changer can be defined and edited in
the test setup.

From the measured data together with the transformer data


from the boilerplate as well as the data from the operator an
accurate report can be generated. This report contains all the
required data of the tested object to further analyze and
compare the measurements with former measurements.
In order to properly display the measured data, limits can be
set to give a clear overview of the values, with green (pass),
yellow (alert) and red (failed) areas to help the engineer in
decision making. These limits can be used according to the
IEC/IEEE standards or adjusted to own expertise.

Analysis page with limits set according to the standards

a brand of
Haefely is a subsidiary
of Hubbell Incorporated.

Haefely has a policy of continuous product improvement. Therefore we reserve the right to change design and specification without notice.

LL_TTR2795_1208_RS.doc 2/ 4

REPORTING
Full reports are automatically generated in XML-, HTML- and
CSV- format.
The graphs itself are also separately stored in jpg-format to
make the easy handling complete.
The XML- and HTML-files can be opened in e.g. Internet
Explorer and from there directly printed or copied into a
Microsoft Word document.
To further expand the powerful analysis functionality of the
APSW2795 the automatic generated CSV-file can be directly
opened in Microsoft EXCEL where customer specific data
processing and calculations are possible.

Example of XML-report printout

TECHNICAL SPECIFICATIONS
General
Excitation voltage
Excitation current
Display
Memory
Printer
Interfaces
Operating temperature
Storage temperature
Mains
Dimension (L x W x D)
Weight

1 V, 10 V, 40 V and 100 V; automatic or manual selectable


max. 1 A (10 mA at 1 V)
5.2 dot matrix LCD 240x128 module with backlight
Stores up to 100 complete test results/test setups
Thermal strip printer, paper width 58mm
Computer:
RS 232C, 19200 baud, 9 pole
Tap changer:
3 pole contact in/out (potential free)
- 10C* 55C * - 10C typical, - 5C guaranteed
- 20C 70C
95 .. 240 V AC, 50/60 Hz, max. 1.3 A
41 cm x 31 cm x 17 cm (16 x 12.2 x 7)
8.8 kg (19 lbs)
excl. cables

Measurement Ranges and Accuracy


Ratio
0.8 .. 100
101 .. 1000
1001 .. 1500
1501 .. 2000
2001 .. 4000
4001 .. 13000
13001 .. 20000

Accuracy (1)
@ 100 V
0.03%
0.05 %
0.05 %
0.05 %
0.05 %
0.15 %
0.20 %

Excitation Current
Range and Accuracy

Range
01A

Resolution
0.1 mA

Typical Accuracy
0.3 % 2 mA

Phase Angle
Range and Accuracy

Range
180

Resolution
0.01

Typical Accuracy
0.05

@ 40 V
0.05 %
0.05 %
0.05 %
0.05 %
0.10 %
n/a
n/a

@ 10 V
0.05 %
0.05 %
0.10 %
0.15 %
n/a
n/a
n/a

(1) At Excitation voltage, values valid after a warmup-time of 30 min

a brand of
Haefely is a subsidiary
of Hubbell Incorporated.

Haefely has a policy of continuous product improvement. Therefore we reserve the right to change design and specification without notice.

LL_TTR2795_1208_RS.doc 3/ 4

SCOPE OF SUPPLY

TTR 2795 instrument in shell case, cable bag, two 3-phase cable sets (5 m
spider and two sets of clamps), remote control/data storage/report
generation software, remote/data transfer cable, mains cable, manual &
calibration certificate.

288x TTR instrument built-into


MIDAS 288x, operated via the
touch screen display. Complete
cable set included.

ACCESSORIES & OPTIONS

 2795/V
Verification box 2795V is used to check
the correct functionality of the Ratio
Meter and its connected measuring
cables. Different ratios (1, 10, 100,
1000) can be selected. Measuring
cables have to be connected following
the description on the front
respectively the color code. The
verification measurements shall be
within an overall accuracy of 1% of
the nominal ratio. If the displayed
values exceed this limit the unit has to
be sent back to the manufacturer for
recalibration respectively repair.

 2795/TAP
External Tap Test Start Switch 2795TAP is used
for convenient tap changer testing.
After the TTR has measured a tap, it stands by
waiting for the tap changer to be moved to the
next tap position and then continue the
measurement, by pressing CONTINUE on the
unit. The tap changer operation box on power
transformers is normally not in the same place
where the TTR 2795 is placed. The external tap
switch cable allows the operator to perform the
measurement by controlling the TTR 2795 from
a remote position (normally at the tap changer
box of the transformer).

 2795/10
Additional two 3-phase
extension cables, 10 m.
Used to extend the reach of
the basic connection set by
another 10 m.
The final length results in
total 15 m (5+10) with this
additional cable set.

www.tettex.com
Europe, Asia, South &
Central America, Australia
Haefely Test AG
Birsstrasse 300
4052 Basel
Switzerland
 + 41 61 373 4111
 + 41 61 373 4912
 [email protected]

China (Sales & Service Office)


Haefely Test AG Beijing Office
8-1-602, Fortune Street
No. 67, Chaoyang Road, Chaoyang District
Beijing, 100025
P. R. China
 + 86 10 8578 8099
 + 86 10 8578 9908
 [email protected]

North America
Hipotronics Inc.
1650 Route 22
PO Box 414
Brewster, NY 10509
USA
 + 1 845 279 3644
 + 1 845 279 2467
[email protected]

a brand of
Haefely is a subsidiary
of Hubbell Incorporated.

Haefely has a policy of continuous product improvement. Therefore we reserve the right to change design and specification without notice.

LL_TTR2795_1208_RS.doc 4/ 4

You might also like