0% found this document useful (0 votes)
216 views

D8024 Analog Fire Programming Guide

Programación de alarma de incendios
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
216 views

D8024 Analog Fire Programming Guide

Programación de alarma de incendios
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 35

D8024, D9024, D10024 Analog Fire Alarm Control Panels

Programming Guide

Radionics

D8024

SHIFT A
N

B
O

C
P

D
Q

F
S

H
U

I
V

J
W

CHANGE

K
X

ENTER

System
Re set

Trou bl e
Sil ence

Ala rm
Sile nce

Man ual
Ala rm

ENTER

NO

NO

YES

Letters
Numbers

Keyword

ALARM
TROUBLE

S yste m
Reset

Y ES

Al arm
Sil ence

Ma nua l
Al arm

EN TER

NO

Le tters
Nu mbers

Ke ywo rd

YES

K eyword

ALARM
TR OUBLE

ALAR M
TROUBLE

ALARM
TROUBLE

ARM
TROUBLE

ARM
TR OUBLE

ALARM
TROUBLE

ALARM
TR OUBLE

11/98

Tro ub le
S i len ce

Radionics
Letters
Numb ers

38789B

M
Z

D10024

D9024

Radionics

L
Y

1998 Radionics, Inc.

Table of Contents
1.0 Notice ..................................................................... 4
2.0 Warnings and Cautions ........................................ 4
3.0 FCC Notices........................................................... 4
Part 15....................................................................... 4
4.0 UL/NFPA Notices................................................... 4
5.0 Control Levels ....................................................... 5
5.1 Level Distinction .................................................. 5
5.2 Passcodes........................................................... 5
6.0 Controls and Displays .......................................... 5
6.1 Memory Lock....................................................... 7

Auto Learn Peripheral Circuit ..............................19


Peripheral Zone Configuration.............................20
Peripheral Device Configuration..........................21
Configure Peripheral Device Text....................21
Configure Peripheral Device Zone ..................21
Changing Device Information ..........................22
Calibrate Peripheral Devices ...............................22
Peripheral Circuit Addressable Notification
Appliance Circuit Controller Units (4-way
Sounders) ............................................................22
Configure Notification Appliance (Sounder) Circuits22
7.5 Configure Relays ...............................................24

7.0 Commissioning New Installations....................... 8

8.0 Day Mode..............................................................25

7.1 Front Panel Keys and Programming ................... 8

8.1 Delayed Mode....................................................25

7.2 Setup................................................................... 8
Language Settings ................................................ 9
Number of Polling Circuits..................................... 9
Calibration Time Setting........................................ 9
AC Fail Timer ...................................................... 10
Reset Inhibit ........................................................ 10
Name Settings..................................................... 10
Service Phone Number Setting........................... 10
Memory Lock Check ........................................... 11
Log Mode Settings .............................................. 11
Exiting the Setup Menu ....................................... 11
7.3 System Configuration, Polling Circuits .............. 11
Auto Learn Polling Circuit.................................... 12
Zone Configuration.............................................. 13
Exiting the Zone Configuration Option ................ 14
Device Configuration........................................... 14
Sensor Text..................................................... 15

8.2 Sensitivity Mode.................................................26


8.3 Verification Mode...............................................27
9.0 System Events .....................................................28
9.1 General Events..................................................29
9.2 Event Logic........................................................29
9.3 Define Event Outputs ........................................29
10.0 Inspect ................................................................29
11.0 Time/Date and System Options ........................30
11.1 Time/Date, System (Clear Memory), and Crystal
Settings....................................................................31
Time/Date ............................................................31
System (Clear Memory).......................................31
11.2 Crystal Setting .................................................31
11.3 Program Integrity .............................................32
11.4 Power Supplies................................................32

Device Zone .................................................... 15

11.5 Modifying the Level 2 Passcode ......................32

Alarm Thresholds ............................................ 16

11.6 Erasing Event Log ...........................................32

Device Action .................................................. 17


Device Calibration ............................................... 18
Groups/ Group Disablement ............................... 18
Group Assignment .......................................... 18

13.0 Test Outputs ......................................................33


14.0 PC Programming ...............................................33
15.0 Networking .........................................................33

Group Disablement Input ................................ 18


7.4 System Configuration, Peripherals.................... 19

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 1

38789B 11/98

Table of Figures
Figure 1: Front Panel Displays..............................................................................................................................................5
Figure 2: Status LEDs ..........................................................................................................................................................6
Figure 3: Memory Lock Switch Location ...............................................................................................................................8
Figure 4: The First Level-Two Entry Menu ............................................................................................................................8
Figure 5: The Second Level-Two Entry Menu .......................................................................................................................8
Figure 6: Main Menu .............................................................................................................................................................9
Figure 7: Path Through Commission Menus to Setup ..........................................................................................................9
Figure 8: Name Settings .....................................................................................................................................................10
Figure 9: Letters and Numbers Submenus .........................................................................................................................10
Figure 10: Path Through Commission Menu to Configure ..................................................................................................12
Figure 11: Configure Submenu ...........................................................................................................................................12
Figure 12: Configure Submenu for Polling Circuit One ......................................................................................................12
Figure 13: Auto Learn Submenu One .................................................................................................................................12
Figure 14: Typical Auto Learn Submenu Two .....................................................................................................................13
Figure 15: Configure Submenu for Polling Circuit One ......................................................................................................13
Figure 16: Zone Configuration Submenu ............................................................................................................................13
Figure 17: Zone Description Submenu ...............................................................................................................................14
Figure 18: Device Submenu One........................................................................................................................................14
Figure 19: Device Inspection Address Change Submenu ..................................................................................................14
Figure 20: Address Information Display ..............................................................................................................................14
Figure 21: Detection Device Information Change Submenu...............................................................................................15
Figure 22: Detection Device Information Change Submenu...............................................................................................15
Figure 23: The Three Keywords Displays ...........................................................................................................................15
Figure 24: Individual Device Zone Change Submenu.........................................................................................................15
Figure 25: Address Information Display ..............................................................................................................................16
Figure 26: Configure Submenu for Polling Circuit 1............................................................................................................16
Figure 27: Device Information Change Submenu ...............................................................................................................16
Figure 28: Address Information Display .............................................................................................................................16
Figure 29: Detection Device Information Change Submenu...............................................................................................17
Figure 30: Device Action Submenu One.............................................................................................................................17
Figure 31: Address Information Display ..............................................................................................................................17
Figure 32: Commission Menu One .....................................................................................................................................18
Figure 33: Memory Lock Reminder.....................................................................................................................................18
Figure 34: Memory Lock Error Message .............................................................................................................................18
Figure 35: Path to the Configure Submenu.........................................................................................................................19
Figure 36: Configure Submenu ...........................................................................................................................................19
Figure 37: Configure Peripherals Submenu........................................................................................................................19
Figure 38: Auto Learn Submenu One .................................................................................................................................19
Figure 39: Peripheral Summary Display .............................................................................................................................20
Figure 40: Configure Peripherals Submenu........................................................................................................................20
Figure 41: Peripheral Device Zone Submenu .....................................................................................................................20
Figure 42: Zone Description Change Submenu..................................................................................................................20
Figure 43: Configure Peripherals Submenu........................................................................................................................20
Figure 44: Peripheral Device Information Submenu ...........................................................................................................21
Figure 45: Peripheral Device Information Change Submenu..............................................................................................21
Figure 46: Keywords Displays.............................................................................................................................................21
Figure 47: Configure Peripherals Submenu........................................................................................................................21
Figure 48: Peripheral Device Zone Configuration Submenu...............................................................................................22
Figure 49: Device Information Menu ...................................................................................................................................22
Figure 50: Notification Appliance Circuit Controller Address ..............................................................................................22
Figure 51: Notification Appliance Configure Menu..............................................................................................................22
Figure 52: Pattern Display...................................................................................................................................................23
Figure 53: 20 Zone Panel (D8024)......................................................................................................................................23
Analog Fire Alarm Control Panels Programming Guide
1998 Radionics, Inc All rights reserved.
Page 2

38789B 11/98

Table of Figures
Figure 54: 40 Zone Panel (D9024/D10024) ........................................................................................................................23
Figure 55: Mode OFF (D8024) ............................................................................................................................................23
Figure 56: Mode OFF (D9024/D10024) ..............................................................................................................................23
Figure 57: Off Mode Zones 1 through 12 ............................................................................................................................23
Figure 58: Double Knock Mode, Zones 1 through 12 .........................................................................................................23
Figure 59: Delay Mode........................................................................................................................................................24
Figure 60: Steady/Steady Delay Mode................................................................................................................................24
Figure 61: Path Through Commission Menus to Day Modes..............................................................................................25
Figure 62: Stage Timer Menu One......................................................................................................................................26
Figure 63: Delayed Mode Zone Assignment.......................................................................................................................26
Figure 64: Path Through Commission Menus to Sensitivity Mode......................................................................................27
Figure 65: Path Through Commission Menus to Verification Mode ....................................................................................28
Figure 66: System Events Submenu...................................................................................................................................29
Figure 67: Path Through Commission Menus to Inspect ....................................................................................................30
Figure 68: Inspect Submenu ...............................................................................................................................................30
Figure 69: Path to Commission Menu Two .........................................................................................................................30
Figure 70: Time/Date Submenu ..........................................................................................................................................31
Figure 71: Crystal Setting Submenu ...................................................................................................................................31
Figure 72: Crystal Setting Change Submenu......................................................................................................................31
Figure 73: Program Integrity Submenu ...............................................................................................................................32
Figure 74: Path to Commission Menu Three ......................................................................................................................32
Figure 75: Test Submenu....................................................................................................................................................33
Figure 76: Outputs Test Submenu ......................................................................................................................................33

Table of Tables
Table 1: Control Key Functions.............................................................................................................................................6
Table 2: Alphanumeric and Program/Interactive Key Functions ...........................................................................................6
Table 3: System Status LED Functions ................................................................................................................................7
Table 5: Address Information Data Table ...........................................................................................................................17
Table 6: Device Action Table ..............................................................................................................................................17
Table 7: Peripheral Device Type .........................................................................................................................................20
Table 8: Operating Modes...................................................................................................................................................25
Table 9: General Events .....................................................................................................................................................29
Table 10: Inspect Submenu Functions................................................................................................................................30

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 3
1998 Radionics, Inc All rights reserved.

D8024, D9024, D10024

Analog Fire Alarm Control Panels

Programming Guide
1.0

Notice

The material and instructions covered in this manual have been carefully checked for accuracy and are presumed to
be reliable. However, the manufacturer assumes no responsibility for inaccuracies and reserves the right to modify
and revise this document without notice.

These instructions are the guide to commissioning and programming the D8024, D9024 and D10024 Fire Alarm
Control Panels (FACP). See the separate Installation Instructions for information on installation and powering the
D8024 and D9024/D10024 FACPs. See the separate Operators Manual for information on the normal operation of
each system.

2.0

Warnings and Cautions


These instructions contain procedures to follow in order to avoid injury and damage equipment.

3.0

FCC Notices

Part 15
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
commercial installation. This equipment generates, uses and can radiate radio frequency energy, and, if not installed
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment on and off, the user
is encouraged to try to correct the interference by one or more of the following measures:
1.

Reorient or relocate the receiving antenna.

2.

Increase the separation between the equipment and the receiver.

3.

Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

4.

Consult the dealer or an experienced radio/TV technician for help.

4.0

UL/NFPA Notices

UL listed for NFPA 72, Local.

All references to NFPA and related requirements are based upon compliance with the 1993 edition of NFPA 72,
National Fire Alarm Code. Since installation specifications are nearly always based upon a specific edition of a
standard that has been legally adopted by the Authority Having Jurisdiction (AHJ), earlier editions of NFPA
standards will generally apply. Consult with the appropriate AHJ for confirmation.

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 4

38789B 11/98

5.0
5.1

Control Levels
Level Distinction

The D8024, D9024 and D10024 each have three available control levels. At all three levels the LED Display
indicates condition, the ZONE/AREA LEDs indicate location and detailed alarm/trouble information is displayed
alphanumerically.

Control Level One, the Display Level, inhibits the system control keys, limiting the front panel function to
annunciation.

Control Level Two, the Controller Level, allows system control for Fire Drill, Alarm Silence, Trouble Silence, and
System Reset; and allows Test and Enable/Disable operations, but does not allow access to configuration or
programming functions. At Level Two, the Alphanumeric Display becomes interactive and prompts for system
checks, log functions, and key status. Level Two is reached by entering a pass code from Level One.

Control Level Three, the programmers level, allows full system configuration information and is used to program or
modify the system program.

5.2

Passcodes

Ten passcodes are available for D8024, D9024 and D10024 Controllers. Passcodes are programmable. Level Two
passcodes are assigned or changed from Level Three and will not allow access to Level Three. See
Option 4) Passwords on Commission Menu Two for information on assigning Level Two Passcodes.
The default Level 2 passcode is 9898, which is the same passcode for Level 3. Be sure to change
the Level 2 passcode in order to provide a higher level of panel security. See Section 11.5 to
modify the Level 2 passcode.

The Level 3 passcode is 9898. In order to provide a higher level of panel security, make sure only
authorized personnel have access to the passcodes for Levels 2 and 3.

6.0

Controls and Displays

The D8024, D9024 and D10024 control panels have two rows of control keys. The Control Keys row contains the
four System Control Keys for Fire Drill, Alarm Silence, Trouble Silence and System Reset. The Zone/Area display
provides access to the alphanumeric Keys and the three Program/Interactive Keys. The Alphanumeric Keys
normally function as number keys. They can be toggled to Letter Keys by pressing the Change Key at the right end
of the Alphanumeric Key row. The Shift Key at the left end of the Alphanumeric Keys toggles between an upper and
lower row of letters. Hold the Shift Key while entering another key to enter the bottom letter.

Figure 1: Front Panel Displays

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 5
1998 Radionics, Inc All rights reserved.

System
Reset

Trouble
Silence

Alarm
Silence

Manual
Alarm

ENTER

NO

YES

Letters
Numbers

Alarm

System Trouble Point


Earth
Trouble Silenced Bypassed Fault

Sounder
Fault

Sprinkler
Supervisory

CPU
Reset

Keyword

Alarm
AC
Silenced Power

D9024/D10024

ALARM

Sprinkler Supervisory

CPU Reset

Sounder Fault

Sounders Disabled

Fire Drill
Alarm Silence

Sounders Silenced

System Trouble
Trouble Silenced

Relays Bypassed

Point Bypassed

Earth Fault

Trouble Silence
AC Power

System Reset

D8024
Figure 2: Status LEDs
Table 1: Control Key Functions
Key Label

Function

Fire Drill

Turns on ALL notification appliances.

Alarm Silence

Press to silence all notification appliances. Press again to activate all notification
appliances.

Trouble Silence

Acknowledges events and silences the internal buzzer.

System Reset

Cancels all alarm conditions and resets the panel.

Table 2: Alphanumeric and Program/Interactive Key Functions


Key Label

Function

Shift

Shows user options on Alphanumeric Display used in programming to allow letters N to Z.

0,1,2,3,4,5,6,7,8,9

Press the No Key to toggle between letters and numbers used in programming.

>,<

Scrolls through fires/faults on the Alphanumeric Display.

Change

Changes a display option.

Enter

Enters the selection.

No

To answer No or to terminate an option.

Yes

To answer Yes or step through an option.

The upper display, the Alphanumeric Display, is an illuminated two-line, 80-character, LCD display that gives
detailed information on system events and status, and displays interactive prompts. The middle display, the LED
Display, indicates the type of system event and status. The lower display, the Zone/Area LED Display, indicates
the location and type (alarm or trouble) of event. Table 3 describes the function and meaning of the status LEDs on
the D8024, D9024 and D10024 FACPs.

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 6

38789B 11/98

Table 3: System Status LED Functions


Status LED

Function

How to Clear the LED

Alarm

An input is in an alarm state, or has latched into an


alarm state, or an operator has manually sounded
the alarm (FIRE DRILL).

Correct the condition causing the alarm, and then


perform a manual reset.

System Trouble

There is a fault in the system, a wiring fault, a


power fault, a detector fault, etc.

Correct the fault condition, and then perform a


manual reset.

Trouble Silenced

The internal annunciator (indicating an alarm or


trouble) has been silenced by the operator
(TROUBLE SILENCE).

Correct the fault or alarm condition, and then


perform a manual reset. NOTE: If another fault
or alarm condition occurs, the internal
annunciator automatically resounds.

Point Bypassed

One or more inputs or outputs have been disabled


manually by the operator.

Re-enable the device(s). The system


automatically resets.

+ Sounders Disabled
and/or + Relays
Bypassed

Notification appliance circuits/output relays have


been disabled manually by the operator.

Re-enable the sounder/ relay. The system


automatically resets.

Earth Fault

The system has a short circuit wiring fault to a


foreign ground such as an SLC conductor shorted
to a heating duct.

Correct the fault condition, and then perform a


manual reset.

Sounder Fault

This indicates a wiring fault (other than an earth


fault) with a notification appliance circuit.

Correct the fault condition, and then perform a


manual reset.

Sounders Silenced

Notification circuits have been manually turned off


by the operator (ALARM SILENCE), but the system
is still in an alarm state.

Correct the alarm condition, and then perform a


manual reset. NOTE: Resound the alarms by
pressing ALARM SILENCE again. The alarms
will resound if another alarm condition occurs.

Sprinkler Supervisory

This indicates a closed sprinkler supervisory valve,


pressure switch, or a sprinkler system trouble
condition (generated by Event 100).

Correct the supervisory condition, and then


perform a manual reset.

CPU Reset

The system detected an improper operation of the


CPU or in the integrity of memorized data, and has
restarted automatically.

Correct the problem, if appropriate, and then


perform a manual reset.

Alarm Silenced

Notification circuits have been manually turned off


by an operator, but the system is still in an alarm
state.

Reset the system.

AC Power

STEADY: Indicates that an acceptable AC power


supply is present. FLASHING: Indicates that AC
power is not present, or there is a power supply
fault.

N/A

The D8024 can support up to 252 addresses, the D9024 can support up to 378 addresses and the
D10024 can support up to 630 addresses.

6.1

Memory Lock

To make any changes that affect the configuration of the system, such as adding sensors, the programmer must
unlock the system memory using the Memory Lock switch (see Figure 3). Open the panel and move the memory
lock switch to the lower position.

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 7
1998 Radionics, Inc All rights reserved.

Figure 3: Memory Lock Switch Location


Make sure to unlock the system memory before commissioning the FACP. The system memory
must then be locked upon completion of panel commissioning.

7.0

Use the keys on the front panel or a PC to program the Fire Alarm Control Panel (FACP). See Section 13.0 for
complete instructions on PC programming.

7.1

Commissioning New Installations

Front Panel Keys and Programming

If the keypad is unused for over a minute, the display automatically reverts to the normal display that shows
time/date, or a display of faults on the system. Press the > key to restore the interactive display. When the system
requires information, it will display a message followed by a question mark. Press YES, NO, or key in letters or
numbers and press ENTER. To see the next item (sensor, menu page, etc.) press the YES key. To terminate an
option, press the NO key (certain commissioning procedures do not allow premature termination).

7.2

Setup

This procedure is necessary to complete the basic setup for panel operation. there are 8 Setup functions:
Language Settings, Number of Polling Circuits, Calibration of Time Setting, AC Fail Timer, Reset Inhibit,
Name Settings, Service Phone Number Setting, Memory Lock Check and Log Mode Settings.

Selecting Setup results in a series of prompts answered in sequence. Press the > key to repeat the sequence as
necessary to change an answer. To reach Setup, press the Shift key to display the first Level Two Entry Menu.

Figure 4: The First Level-Two Entry Menu

Press Yes. The panel displays the second Level Two Entry Menu.

Figure 5: The Second Level-Two Entry Menu

Enter the Level Three Pass Code.

The panel displays the Main Menu.

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 8

38789B 11/98

Figure 6: Main Menu

Select Option 1) Commission, by pressing the 1 key. The display prompts, Please enter your password. Enter the
Level Three Pass Code (9898).

Figure 7: Path Through Commission Menus to Setup


The display shows the first of the three Commission Menus. Press YES twice to page to Commission Menu
Three. Press 2 to enter Setup options. The display prompts: Memory is locked! Unlock the memory using the
Memory Lock Switch (see Figure 3). If no input is entered for over a minute while the memory is unlocked, the
panel buzzer will sound and the alphanumeric display will read: Panel left in commission mode. Press the >
key to silence the buzzer. Press 2 to enter the first Setup function.

Language Settings

The panel display prompts, ENGLISH? Press YES. The display prompts ENGLISH USA? For installations in the
USA, press YES. The display prompts, Quantity of Loop drivers = (1 or 2) OK?

Number of Polling Circuits

This number is set to one. Verify that it is correct and change the number if necessary. Press YES to accept. To
change, press NO, change the quantity to equal the number of D9067 Polling Circuit Modules present in the FACP,
and press ENTER as prompted. The display prompts Detectors [Hochiki ESP] OK? Press YES.
Radionics detectors require that the detector protocol be set to Hochiki ESP. Failure to do so will
result in faulty operation of the FACP.

Calibration Time Setting

The FACP will automatically check device calibration at the time set in this option. If the time is set to the default
0:00, automatic calibration is disabled. The display prompts Device calibration/time check = 0:00 ? Press YES to
confirm that automatic calibration is disabled. To set a calibration time, press NO. The display prompts for the time.
Enter the desired calibration time in terms of a 24-hour clock (9:00 PM = 2100). Press YES to confirm the new time.

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 9
1998 Radionics, Inc All rights reserved.

The panel recognizes time based on a 24-hour clock (for example, 4:00PM = 1600).

AC Fail Timer

The time taken for the main power source failure to be latched and permanently displayed as a fault can be set from
the display. If the main power source is restored before the timer has expired, then the panel will automatically
cancel the audible and visual indications. A corresponding System Event can also be generated (see Section 9.1,
General Events). The display will prompt, AC Fail Timer = 1 minutes? To accept the prompt, press YES. To
change the time, press NO and enter the desired value.
In order to comply with NFPA regulations, the time set for the AC Fail Timer should not exceed 3
minutes.

Reset Inhibit

The Reset Inhibit time prevents the user from hitting the reset button immediately after a fire has been detected. The
display will prompt, Reset Inhibit time =
0 seconds? Press NO and enter the desired value. Press YES to
accept the prompt.

Name Settings

The Normal Display shows the date and time on the upper level and the name that is entered during this setup step
on the lower level. The name display alternates with the message, All devices are inside working limits.

Figure 8: Name Settings

To enter or alter the Name Setting, press the > key. The display will show the Letters Submenu. In this submenu,
the NO key becomes the Letters/Numbers key. Use this key to toggle between the Letters Submenu and the
Numbers/erase Submenu. The YES key becomes the KeyWord key. Use this key to toggle through the three
KeyWord submenus.

Figure 9: Letters and Numbers Submenus

To move the cursor, toggle to the Numbers Submenu and use the < and > keys. Use the shift key with the letter
key to type the letters N through Z (the lower row). To leave this submenu press the ENTER key. If an error is made
when setting the name, press the NO hey and use the < key to erase any mistake. Press YES again to enter the
desired name. Press YES to confirm the changes and move to the next setup option, Service Phone Number
Setting.

Service Phone Number Setting

The message, For service phone . . . followed by the service phone number is displayed when a fault occurs in the
system. To enter or alter this message, press the > key and use the same procedures used in Section 7.2, Name
Settings. Press YES to confirm and move to the next Setup option.

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 10

38789B 11/98

Memory Lock Check


The display prompts Memory Lock Check [Yes] OK? Press YES to confirm. In normal operation, the
panel buzzer will sound if the memory is left unlocked. This may be inconvenient during some
programming operations. Changing the Memory Lock Check to [No] allows the operator to exit the system
configuration and resume normal operation with the memory unlocked without the buzzer sounding. See
Figure 3 for the location of the memory lock switch on the D8024, D9024 and D10024. Press YES to
confirm and move to the final Setup option.

Log Mode Settings

Whenever the system is powered up, the Event Log is automatically set to normal. During setup, it can be set to
either the diagnostic mode or the normal mode. The panel will not initiate a Trouble or Alarm until a device fails
three successive polls. This reduces the chance that line interference or a faulty detector will lead to an alarm. The
panel logs system events in the normal mode.

The panel reads every event in the diagnostic mode, including single response failures from devices. The panel also
performs a circuit integrity test every minute while in the diagnostic mode. This test checks to see if the panel can
read every device from either end of the circuit. If the panel finds a break in a circuit, it logs it in the Event Log (see
Section 8.4, System Operation, of the D8024 Operators Guide or Section 8.4, Operators Menu, of the
D9024/D10024 Operators Guide). A break in a circuit will result in two entries identified as Break Test 1 and
Break Test 2, which will identify the device(s) that have not replied to the panels poll.

From the Log Settings submenu, use the NO key to toggle between normal and diagnostic prompts, and the YES
key to accept the prompt.

Exiting the Setup Menu

Pressing the YES key at the Log Settings submenu returns the display to Commission Menu Three. Press NO to
return to Commission Menu One. Lock the memory by moving the Memory Lock Switch to the up position. Select
Option 3) NORMAL OPERATION. The display will return to normal.

7.3

System Configuration, Polling Circuits


The D8024 has a capacity of 2 polling circuits, the D9024 has a capacity of 3 polling circuits and
the D10024 may have a capacity of 5 polling circuits. A D9067 Polling Circuit Module must be
installed for each polling circuit.

Once the system setup is complete, configure the polling circuits. Specific instructions for Zone Configuration and
Device Configuration follow the Auto Learn Polling Circuit section. Use Auto Learn to save time in Setup or
when changing sensor configuration. Press the Shift key to display the first Level Two Entry Menu.

Select Option 1) Commission, by pressing the 1 key. The display prompts, Please enter password. Enter the
Level Three Pass Code (9898). Press 1)Commission.
If the memory is locked, the display prompts, Memory is locked! Unlock the memory using the
Memory Lock Switch (see Figure 3).

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 11
1998 Radionics, Inc All rights reserved.

Figure 10: Path Through Commission Menu to Configure

The number of polling circuits in the system is entered during the setup procedure (see Section 7.2, Number of
Polling Circuits). To configure these circuits, select Option 1) Configure from Commission Menu One. The display
shows the Configure Submenu.

Figure 11: Configure Submenu


The D8024 has a capacity of 2 polling circuits, the D9024 has a capacity of 3 polling circuits and
the D10024 may have a capacity of 5 polling circuits.

The menu will prompt for as many polling circuits as were entered in Setup. Options one through five are reserved
for these circuits. Select Option 1) to display the Configure Submenu for Polling Circuit One.

Figure 12: Configure Submenu for Polling Circuit One

Auto Learn Polling Circuit

The system uses Auto Learn to find what devices have been installed on a particular circuit. Repeat the Auto Learn
sequence for each polling circuit. It can be used as many times as required and does not affect the text used to
describe the location of each sensor. Select Option 3) Auto Learn. The FACP displays Auto Learn Submenu One.

Figure 13: Auto Learn Submenu One

Pressing NO will cause the panel to simply calibrate all the devices on the circuit and display the number and types
of devices (see Figure 13). Press any key to return to the Configure Submenu (see Figure 15).

To proceed with Auto Learn, press the YES key. The display confirms by displaying program running. The FACP
may take up to 30 seconds to learn a circuit. Each possible detector address is checked to see if it is occupied and
by what type of detector. If more than one detector is located at a single address or the detector type code is invalid,
a warning message will appear on the display.

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 12

38789B 11/98

Do not press any key until the display changes to Auto Learn Submenu Two.

When the panel has learned what devices are on the polling circuit it calibrates devices and displays a Calibrating
Devices message. After calibration, the panel displays Auto Learn Submenu Two, a summary of what it found on
the circuit. Compare this display with the installation sheets to ensure that the system has found the correct number
of devices.

Figure 14: Typical Auto Learn Submenu Two


Table 4: Device Type Table
Device Type

Description

Model Number

Ion

Ionization Detector

D324A

Opto

Photoelectric Detector

D323A

Temp

Heat Detector

D322A

Sounder

Indicating Circuit Module

D327A

MPS

Manual Pull station

D325A

Press ENTER to continue. The panel display returns to the Configure Submenu for this circuit.

Figure 15: Configure Submenu for Polling Circuit One

After the panel has used Auto Learn to configure and calibrate the devices on this polling circuit, press NO to return
to the Configure Submenu (see Figure 15). Option 1) Zones allows the programmer to assign sensors to specific
zones. Options 2) Devices (section 7.4 Peripheral Device Configuration) and 4) Calibrate (section 7.4 Calibrate
Peripheral Devices) allow detailed configuration and calibration of specific devices.

Zone Configuration
The D8024 can be divided up into 20 zones, the D9024 can be divided up into 40 zones and the
D10024 can be divided up into as many as 80 zones with the D9054 LED Extension Card. Without
the D9054 LED Extension Card, the D10024 FACP can only be divided up into 40 zones.

Use the Configure Zones option to assign alarm initiating devices to the appropriate zone. The default condition is
that all devices are in zone one. The display flashes the item that can be changed.

Figure 16: Zone Configuration Submenu

To change a value move the cursor to the desired location using the > and < keys, enter the desired number(s),
and press Yes or Enter to move to the next field. The configuration shown on the display becomes effective
immediately after pressing the Enter or Yes key. Pressing the No key at any time during the zone configuration
terminates zone configuration and returns the display to the configure submenu for this particular polling circuit. If
the to address value is less than 126, the Yes or Enter key automatically advances to the next zone to be defined.
When all of the devices for the circuit being configured are assigned to zones, the program will advance to the zone
description entry menu.

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 13
1998 Radionics, Inc All rights reserved.

Figure 17: Zone Description Submenu

Each zone can have a 20-character description assigned to it to identify the area covered by the zone. This
description will appear on the Alphanumeric Display if a fault or fire is detected by any sensor in the zone. Change
the description by highlighting the text (using the > and < keys ) pressing Change and entering either letters,
numbers or Keywords. This procedure is the same as described in sections 7.2 Name Settings and 7.3 Sensor
Text. Pressing the Yes or Enter keys saves the change.
Devices assigned to zones 99 and 100 will activate the Sprinkler Supervisory LED in the LED
Display. See Table 3 for Sprinkler LED details.

Exiting the Zone Configuration Option

Press No to exit the Zone Configuration option. The display will return to the Configure Submenu for this particular
polling circuit. Press the No key to return to the main Configure Submenu.

Device Configuration

Option 2) Devices provides information on individual devices on the circuit by device address. It allows the
programmer to insert or change device descriptions, alarm thresholds and system reaction to device input. The
Device Configuration section will describe how to set Sensor Text, Device Zone, Alarm Thresholds and Device
Action information for each device on the polling circuit. Press 2) Devices from the Configure Submenu for the
polling circuit to display Device Submenu One.

Figure 18: Device Submenu One

Press Yes to accept. The display changes to the Address Information Display (see Figure 20). To change the
address to be inspected, press the Change key. The display shows the Device Inspection Address Change
Submenu.

Figure 19: Device Inspection Address Change Submenu

Key in the address and press Enter. The Address Information Display shows detailed information about the device
at the chosen address.

Figure 20: Address Information Display

Use the > and < keys to move up and down the addresses on this circuit. Press Change to change device
information. The display will change to the Device Information Change Submenu (If only the text can be changed,
the Device Text Submenu is displayed when Change is entered). The panel allows changes to the alphanumeric
text display and the assigned zone. Option 3) Event allows the connection of individual devices to system events. If
the device is a smoke or heat detection device, alarm thresholds may be changed from this menu (see Figure 21).

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 14

38789B 11/98

Figure 21: Detection Device Information Change Submenu

Devices other than Smoke and Heat detectors may be programmed to display actions other than an alarm. Instead
of 4) Alarm Thresholds, these devices will offer Option 6) Action on the Device Information Change Submenu (see
Figure 21). Device Action programming is covered in section 7.3 Device Configuration..
Assign sprinkler monitoring devices to Event 100.

Select Option 3) Event for each sprinkler monitoring device and assign it to Event 100. Select 6) Action and assign
the sprinkler monitoring device to Sprinkler Supervisory. When the sprinkler monitoring devices activates the
Sprinkler Supervisory LED will light, the LCD display will show the location and the internal buzzer will sound.

Figure 22: Detection Device Information Change Submenu

Sensor Text

Select Option 1) Sensor Text to display the Device Text Submenu. There are five displays to this menu: a Letters
display, a Numbers display, and three Keywords displays. The display being used is shown in brackets at the top
left of the display. Use the No key to toggle between letters and numbers/erase and the Yes key to toggle through
the Keywords displays.

Figure 23: The Three Keywords Displays

To enter or change a number, use the No key to toggle to the numbers display. [Numbers] will appear at the upper
right of the display. A cursor _ will indicate the current position in the display. To enter or change a letter, use the
No key to toggle to the letters display. [Letters] will appear at the upper right of the display. Use the Shift key to
select letters N to Z. To move the cursor position or erase a letter, use the No key to select the Letters Display and
use the > and < keys. To enter or change Keywords, use the Yes key to toggle to the Keywords display. Enter
the number preceding the Keyword to insert that Keyword into the device text. Press Enter to complete the text
change. Press No to return to the Configure Submenu for this circuit.

Device Zone

During Device Configuration, the programmer has the option of changing the zone assigned to the device being
inspected. Press the Change key while viewing the Address Information Display (Figure 20) to reach The Detection
Device Information Change Submenus (Figures 21 and 22). Option 2) Zone on these submenus displays the
Individual Device Zone Change Submenu.

Figure 24: Individual Device Zone Change Submenu

Enter the desired zone for this device. If the programmer keys in the number three and presses Enter, the display
responds with the Address Information Display showing the current zone assignment for this device (see Figure 25).

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 15
1998 Radionics, Inc All rights reserved.

Figure 25: Address Information Display

Use the > and < keys to move to other address or the No key to return to the configure menu for this circuit.

Alarm Thresholds
Default devices are within UL range. Radionics does not recommend altering factory alarm
thresholds. Detection devices return to factory settings when the FACP loses power and is
initialized.

Select Option 2) Devices from the Configure Submenu for the desired polling circuit.

Figure 26: Configure Submenu for Polling Circuit 1

Press Yes to accept the device inspections and use the > and < keys to move up and down the addresses on
this circuit. Press Change to change device information. The display will change to the Device Information Change
Submenu.

Figure 27: Device Information Change Submenu

Select Option 4) Alarm Thresholds. The display will show the current alarm setting and display the default setting in
brackets. Press Yes to accept the current setting. Press No and follow the prompt to change the setting. The
display will show the current pre-alarm setting and display the default setting in brackets. Press Yes to accept the
current setting. Press No and follow the prompt to change the setting. Press Enter to complete changes. Press
No to return to the Configure Submenu for this circuit. Use the > and < keys to move up and down the
addresses on this circuit. A typical heat detector display is shown in Figure 28. This display indicates that on Circuit
(Loop) One, Zone One, at Address 002, a D322A Heat detector is reporting a temperature of 73.4F (23C).
Temperatures are reported in degrees Fahrenheit.

To convert F to C: nF - 32 1.8 = nC. For example: 50F - 32 = 18. 18 1.8 = 10C.

Figure 28: Address Information Display

Table 5 gives standard values for devices on a polling circuit.

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 16

38789B 11/98

Table 5: Address Information Data Table


Device

Standard
Pre-Alarm
Threshold

Standard
Fire
Threshold

Just
Calibrated

Range

D322A Heat Detector

114F (46C)

132F (56C)

D323A Photoelectric Detector

2.5 %

3%

.1%

.5% - 4%

D324A Ion Detector

1%

1%

1%

N/A

Normal
Reading

Fault
Input

Fire

50F - 176F
(10C - 80C)

D325A Manual Station

16

64

D326A Point Contact Module

16

44

D327A NAC Output Module

16

44

D334A Point Contact Module

16

44

64

64

Device Action

The FACPs response to pre-alarm and fire level signals from smoke and heat detectors is fixed. The panels
response to closure of input contacts from most other devices may be programmed. These devices will offer Option
6) Action when the Change key is pressed from the Device Information Display

Figure 29: Detection Device Information Change Submenu

Press 6) Action to display the first of six action choices.

Figure 30: Device Action Submenu One

Press Change or No to move to the next choice (see Table 6 for an explanation of device actions). To accept the
choice press Enter. The alphanumeric display changes to the Address Information Display and shows the choice
entered in the lower right (see Figure 31).

Figure 31: Address Information Display


Table 6: Device Action Table
Option

Action

Zone Fire

Puts the programmed zone in a FIRE condition.

Bomb Alert

Displays a BOMB ALERT message on the alphanumeric display. Puts the programmed zone in an ALARM
condition (alarm outputs respond according to their programming).

Class Change

Do not program this option.

Security

Sounds the panel buzzer. Lights the System Trouble LED. Displays a security alert message on the
alphanumeric display.

Sprinkler Supervisory

Lights the Sprinkler Supervisory LED. Shows the location on the display. Sounds the internal buzzer.

Warning

Sounds the panel buzzer. Lights the System Trouble LED. Displays a warning message on the
alphanumeric display.

Group Disable

Allows an input device to disable a group of detectors remotely from the panel.

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 17
1998 Radionics, Inc All rights reserved.

Device Calibration

To calibrate all the input devices on a polling circuit, enter the Configure Menu, go the Configure Submenu for that
polling circuit and select Option 4) Calibrate. The panel will poll and calibrate all devices on that circuit, and on
completion, will return the display to the Configure Submenu. Use the calibration function that is a part of the Auto
Learn procedure to calibrate a polling circuit and list a summary of devices (see section 7.3 Auto Learn Polling
Circuit). Use No to return to the Main Menu. Press No to return Commission Menu One.

Figure 32: Commission Menu One

Select Option 3) NORMAL OPERATION. The display will prompt for memory lock.

Figure 33: Memory Lock Reminder

Move the Memory Lock Switch (see Figure 3) to the upper position and press the 3 key again. The display will return
to the Main Menu and will revert to the time/date - status display.
If the memory is locked before the Memory Lock Reminder is displayed, the trouble panel buzzer
will sound and the display will show a failure message.

Figure 34: Memory Lock Error Message

To silence the trouble buzzer and reset the Config RAM:


1. Press the > key to enter the Operators Menu, Main Level
2. Press 1) Commission
3. Key in the pass word
4. Press 1) Configure
5.
6.
7.

Press No to return Commission Menu One.


Select Option 3) NORMAL OPERATION. The display will prompt for memory lock.
Move the Memory Lock Switch (See Figure 3) to the upper position and press the
display will return to the Main Menu and will revert to the time/date - status display.

3 key again. The

Groups/ Group Disablement

The group assignment/ group disablement function allows a range of detectors and input devices to be disabled
remotely from the panel using a single input device. The initiating input device can be any loop input circuit, call point
or peripheral input circuit.

Group Assignment

Each detector or input device that is to be disabled must be assigned to a specific group using the 7) Group
command in the Change Device options. The input device that will initiate the group disablement must also be
assigned to the same group.

Group Disablement Input

The input device to be used to control the group disablement must have its Action set to Group - Disable.

Only one input device must be assigned to act as the Group Disable input for a specific group.

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 18

38789B 11/98

7.4

System Configuration, Peripherals

Peripheral Devices (controllers and annunciators) are input and output devices connected to the D9051 RS-485
Module in Port D. The panel names the RS-485 circuit Loop P. The panel supports up to 126 addresses that
peripheral devices can be assigned to. D9070 Controllers signal a manual alarm or trouble condition with Alarm or
System Trouble LED indications, panel and device buzzer, and 40-character text display at the device and at the
panel. The ALARM and TROUBLE LED in the zone/area LED display will not light. D9069 Annunciators do not
have addresses on this circuit (they repeat panel information but do not communicate with the panel). A D9069
Annunciator in a fault condition will signal its condition at the device but not at the panel. A D9073 High Integrity RS485 Bus Module functions as an RS-485 signal regenerator and booster. When multiple D9073 modules are
connected together, a high integrity RS-485 circuit is created. A D9078 is used to provide an LED logic driver for
graphic displays.
When using the D9070 Fire System Controller on the D9024 or D10024 systems operating on
software revisions earlier than 6.10-UO, Peer-to-Peer must be set to True. If this prompt is set to
False, then the system control keys will not function after being disabled. This prompt can also
be found in the Analog Panels Networking Guide (P/N: 34377).

To configure peripheral devices, unlock the memory, select Option 1) Commission from the Operators Menu, Main
Level, and enter the pass code.

Figure 35: Path to the Configure Submenu

The Display will change to the Configure Submenu.

Figure 36: Configure Submenu

Select Option 6) Peripherals. The display will change to the Configure Peripherals Submenu

Figure 37: Configure Peripherals Submenu

Select Option 3) Auto Learn. The display changes to Auto Learn Submenu One

Auto Learn Peripheral Circuit

Auto Learn allows the system to learn what devices have been installed on the RS-485 bus. Auto Learn can be
used any number of times and does not affect the text used to describe the location of devices.

Figure 38: Auto Learn Submenu One

Press the Yes key. The display responds with a Program running display.

Do not press any key while Program running is displayed. When Auto Learn has finished learning the peripheral
units the display will respond with the Peripheral Summary Display.

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 19
1998 Radionics, Inc All rights reserved.

Figure 39: Peripheral Summary Display


Table 7: Peripheral Device Type

Device Type

Description

Model Number

4-way-SCC

Annunciator

D9069

Other

Controller

D9070

Other

4 Output Notification Appliance Module

D9072

Other

High Integrity RS-495 Bus Module

D9073

Other

LED Driver Module

D9078

Check that the system has found all devices correctly. Press Enter to return to the Configure Peripherals Submenu.

Figure 40: Configure Peripherals Submenu

Peripheral Zone Configuration


The D8024 can be divided up into as many as 20 zones, the D9024 can be divided up into 40 zones
and the D10024 can be divided up into as many as 80 zones only with the D9054 LED Extension
Card. Without the D9054 LED Extension Card, the D10024 can only be divided up into 40 zones.

From the Configure Peripherals Submenu press 1) Zones. The display changes to the Peripheral Device Zone
Submenu.

Figure 41: Peripheral Device Zone Submenu

Use > and < keys to move the to the field to be changed. A blinking cursor will indicate the character to change.
Use the number keys to change the address and press Enter to complete the change. When all the device
addresses on the peripheral circuit (Loop 6) are assigned, pressing Enter will change the display to the Zone
Description Change Submenu.

Figure 42: Zone Description Change Submenu

The Display defaults to Zone 001. Use the > < keys to move the blinking cursor through the fields. Use the
letter keys to assign or change zone descriptions. Keywords (the Yes key) do not work in this submenu. Press the
Yes key to move the display to the next zone.
The display moves through all the zones and displays all zone descriptions. Zone descriptions
assigned from polling circuit configuration will be displayed and can be changed from this
submenu.

Press No to return to the Configure Peripherals Submenu.

Figure 43: Configure Peripherals Submenu

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 20

38789B 11/98

Peripheral Device Configuration

The text description for each peripheral device, and the zone to which each device is assigned may be individually
configured. Select Option 2) Devices, from the Configure Peripherals Submenu to add or change Peripheral Device
descriptions (Sensor Text) or to change the zone location of individual devices. The display changes to the
Peripheral Device Information submenu.

Figure 44: Peripheral Device Information Submenu

This submenu opens with peripheral device address one. If this address is not assigned, the display will show
device 001 (P:001), the zone to which it is assigned (Z001), device description
, and the device type not
used. Press the > key to move to the next assigned address. Figure 44 indicates device 11 is assigned to zone
007, third floor south, is a controller (repeater), and is sending a normal analog message to the panel.

Use the > < keys to move the display to the next device address. Press the Change key to change the address
information. The display shows the Peripheral Device Information Change Submenu.

Figure 45: Peripheral Device Information Change Submenu


Option 7) Action is not used at this time.

Configure Peripheral Device Text

Select Option 1) Sensor Text, to display the Device Text Submenu. There are five displays to this menu: a Letters
display, a Numbers display and three Keywords displays. Use the Letters/Numbers key to toggle between letters
and numbers and the Yes key to toggle through the Keywords displays.

Figure 46: Keywords Displays

Enter letters and numbers as outlined in section 7.2 Name Settings. Use the Yes key to toggle through the three
displays. Enter the number preceding the Keyword to insert that Keyword into the device text.

Press Enter to complete the text change. Press No to return to the Configure Submenu for this circuit.

Configure Peripheral Device Zone

To assign an individual peripheral device to a specific zone enter the Configure Peripherals Submenu and select
Option 2) Devices.

Use the > < keys to move the display to the device address to be assigned or changed. Press the Change key.
The display shows the Peripheral Device Information Change Submenu (see Figure 45). Select Option
8)
Zone. The display shows the Peripheral Device Zone Configuration Submenu.

Figure 47: Configure Peripherals Submenu

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 21
1998 Radionics, Inc All rights reserved.

Figure 48: Peripheral Device Zone Configuration Submenu

Key in the desired zone and press Enter. The display returns to the Peripheral Device Information Submenu (see
Figure 45). Press No to return to the Configure Peripherals Submenu. Press No to return to the main configure
submenu.

Changing Device Information

Changes are first made by pressing the Change key. If only the device text can be changed, the display will jump
straight to the location text (see Configure Peripheral Device Text, page 21). However, if the device can have other
attributes changed, these options will be presented in menu form. See Figure 49.
1) Sensor Text
6) Action

2) Zone
7) Group

3) Event
9) Mode

Figure 49: Device Information Menu

Calibrate Peripheral Devices

From the Configure Peripherals Submenu, select Option 4) Calibrate. The display indicates Calibrating Devices.
After calibration the display returns to the Configure Peripherals Submenu. Enter No to exit to the main menu.

Peripheral Circuit Addressable Notification Appliance Circuit Controller Units (4-way


Sounders)

Up to 15 peripheral sounder devices can be added to the system via the RS-485 Bus. These sounders are
programmed in the same way as the other sounders.

The letter P appears in front of the address on the display to indicate that the output is on the RS-485 bus. A letter
is added after the address to indicate relay A, B, C or D.

When RS-485 bus modules are used, their zonal programming selection is shown by using the same configure
Sounder option as the on-board and loop-driven outputs. For example, an addressable notification appliance circuit
controller module wired onto the RS-485 bus with an address of 11 is shown in Figure 50.
SCC
P : 011: B

Pattern
004

Figure 50: Notification Appliance Circuit Controller Address

Configure Notification Appliance (Sounder) Circuits

The D8024, D9024 and D10024 support two different methods for connecting notification appliances:

Direct connection to output terminals on the D8024.

Connection to addressable notification appliance circuit modules on any of the detection device (polling)
circuits.

All notification appliances are programmed from the Main Configure Menu. Select Option 7) Sounders to open the
Notification Appliance Configure Menu.

Figure 51: Notification Appliance Configure Menu

Use the > < keys to move the blinking cursor between the zone and mode prompts.

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 22

38789B 11/98

To comply with NFPA three-pulse temporal pattern evacuation requirements, set the mode to ON
(steady on). Synchronize notification appliances using the D411 or D412 Synchronization Modules.

Figure 52: Pattern Display

Any single installations that require multiple pulsed circuits should be connected to the D8024, the D9024 or the
D10024 notification appliance (sounder) outputs. Immediately after a system reformat of polling circuit devices
followed by Auto Learn, the system will default to all notification appliances activated immediately for any fire in any
zone. The notification appliance Configure Menu on a 20 or 40 zone panel would display:

Figure 53: 20 Zone Panel (D8024)

Figure 54: 40 Zone Panel (D9024/D10024)

Press Enter or Yes to accept a prompt. The display will prompt for the next zone. When all zones in a circuit are
configured, pressing Yes or Enter prompts for the next circuit. To avoid ambiguity as to what can be modified, the
display flashes the item that can be changed. If this item is a number, enter new value to change it. If the item is not
numeric, use the Change key. For example, beginning with the condition in Figure 53, use the > key to select the
On display under Mode. Press the Change key. The display changes to the next Mode option, Mode Off.

Figure 55: Mode OFF (D8024)

Figure 56: Mode OFF (D9024/D10024)

In this configuration, if an alarm condition is detected in zones one through 20, the panel will not activate notification
appliance Circuit A. Press the > key to return the blinking display to the to zone number (20). Key in 12." The
display shows the new zone range.

Figure 57: Off Mode Zones 1 through 12

In this configuration, if an alarm condition is detected in specified zones (one through 12), the panel will not activate
notification appliance Circuit A. Use the > key to move the blinking display to the Mode position and press Enter
or Yes to accept, Change to move to the next option, the Double Knock Mode.

Figure 58: Double Knock Mode, Zones 1 through 12

In this configuration the panel will activate notification appliance Circuit A, only if an alarm condition is detected in
two or more devices in a particular zone in the specified zone range (zones one through 12). Press Enter or Yes to
accept this option, Change to move to the next option, Delay Mode.

Move the blinking display to DOUBLE KNOCK and press Change to move to the next option, Delay Mode.

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 23
1998 Radionics, Inc All rights reserved.

Figure 59: Delay Mode

In this configuration the panel will activate notification appliance Circuit A in a steady alarm after the number of
seconds displayed , if any detector in the zone range is in alarm condition The delay may be between one and 990
seconds.

Press Change to move to the next option, the Steady/Steady Delay Mode.

Figure 60: Steady/Steady Delay Mode

In this configuration the panel will activate notification appliance Circuit A in a steady alarm if two or more detectors
in a zone are in an alarm condition. If only one detector is an alarm condition in any zone in the specified zone
range, the panel will activate Circuit A after the number of seconds indicated in the display.

Press Change to move to the next option. This option, the Pulse Delay Mode, is not in use at this time.
Do not attempt to program the Pulse Delay Mode. At this time, this option exceeds the
requirements for power-limited devices.

Press Change to move to the next option. This option, the Pulse/Steady Delay Mode, is not in use at this time.
Do not attempt to program the Pulse/ Steady Delay Mode. At this time, this option exceeds the
requirements for power-limited devices.

Press Change to advance to the next option. This option, the Steady/Pulse Delay Mode, is not in use at this time.
Do not attempt to program the Steady/Pulse Delay Mode. At this time, this option exceeds the
requirements for power-limited devices.

Press Change to return the mode selection to ON (steady on). The configuration shown on the display becomes
effective immediately after the Enter or Yes key is pressed. Pressing the Yes key also automatically advances to
the next zone(s) to be defined.

7.5

Configure Relays

The procedure for configuring relays is identical to the procedure for configuring notification appliances (section 7.4
Configure Notification Appliance (Sounder) Circuits) with the following exceptions.
The panel does not monitor any relay outputs and will not detect any faults on external relay
circuits.

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 24

38789B 11/98

8.0

Day Mode
Use Day Mode where permitted by the Authority Having Jurisdiction. See specifications for
Positive Alarm Sequence in NFPA 72, 1993, Section 3-8.3..

The D8024, D9024 and D10024 panels can be commissioned to automatically invoke different operating modes
according to the time of day. Each mode has adjustable start and finishing times. The operating modes available
are summarized in Table 8:
Table 8: Operating Modes
Operating Mode

Delayed Mode

During the day/night, the alarm signal from detectors is immediately recognized and identified on the
panel display, but no outputs turn on until stage 1/ stage 2 timers have expired. Manual pull stations
override this mode.

Sensitivity Mode

Allows smoke and temperature detectors to use different pre-alarm and fire alarm thresholds during
the day/night.

Verification Mode (available


on software version 563)

Allows smoke detectors to tolerate transient alarms according to the programmed verification delay
time during either day or night.

To return to the Main Menu after configuring the relays, press No to return to the Configure Submenu. Press No
again to return to Commission Menu 2. Then press 3) Normal Operations to return to the Main Menu.

8.1

Description

Delayed Mode

To reach the Delayed Mode feature, select Option 1) Day Mode from Commission Menu 3. Then press 1) Delayed
Mode.

Figure 61: Path Through Commission Menus to Day Modes


The panel recognizes time based on a 24-hour clock (for example, 4:00 PM = 1600)

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 25
1998 Radionics, Inc All rights reserved.

The Delayed Mode inserts a two-stage delay between the time the panel recognizes an alarm condition and the time
it activates notification appliances. After entering 1) Delayed Mode, the display prompts, Allow mode ? Press
Yes. The display then prompts, Start at 0:00 ? By pressing Yes, the panel will then ask what time the Delayed
Mode should start and end. If either prompts are incorrect, press No, then enter the correct times.

After setting the start and end times for the Delayed Mode, the display will then prompt, Stage 1 time = 60 seconds
OK? If the Stage 1 timer is as shown in Figure 62, the panel will go into a full fire condition within 60 seconds of the
sensor exceeding the preset threshold level. The panel buzzer sounds during this period, and the sensor location is
shown on the alphanumeric display with a warning that the panel has entered Stage 1 of a delayed alarm.
Stage 1: Full alarm. Stage 2: Delay time before bells.

Figure 62: Stage Timer Menu One

Stage 1 is acknowledged at the panel by pressing the Trouble Silence key. This starts Stage 2. Press Yes to
accept the Stage 1 timer prompt. To change the Stage 1 time, press No and enter a value between 1 and 600
seconds. Press Yes.
Radionics recommends that Stage 1 not exceed 15 seconds or Stage 2 not exceed 180 seconds.
The display prompts for time in seconds for Stages 1 and 2.

The display will then prompt for the Stage 2 time. The Stage 1 timer and the Stage 2 timer both start counting as
soon as the panel recognizes an alarm condition. Setting the Stage 2 timer for a longer period than the Stage 1
timer allows for time to investigate the cause of the alarm and take appropriate action before the panel activates an
alarm. The panel activates a full alarm condition if the panel is not reset by the time the Stage 2 timer has expired.
Press Yes to accept the Stage 2 timer prompt. To change the Stage 2 time, press No and enter a value between 1
and 600 seconds. Then press the Yes key. The display prompts for zones to be used in the Delay Mode.

Figure 63: Delayed Mode Zone Assignment

Figure 63 shows that zones 1 through 12 will not use the Day Mode. The panel will activate indicator devices
immediately on determining an alarm condition exists. Change the items in the brackets by using the < and >
keys to select the item and typing over with the desired number. Use the Change key to toggle between [FALSE]
and [TRUE]. At the end of the Delayed Mode settings, the display returns to Commission Menu 3.

8.2

Sensitivity Mode
Assign alternate thresholds to individual detector devices in the polling circuit configuration
procedure before setting Day Mode sensitivity.

The sensitivity of both heat and smoke detectors can be adjusted by adjusting the threshold at which pre-alarm and
fire alarm signals are generated. These alternative thresholds are programmed to operate only at certain times of
the day. The thresholds will return to normal levels at all other times.
The Sensitivity Mode should only be used in certain specialized applications and with great care.
The default mode is for all detectors to default to the manufacturers recommended alarm level.

Select Day Mode from Commission Menu 3, then Sensitivity Mode.

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 26

38789B 11/98

Figure 64: Path Through Commission Menus to Sensitivity Mode

The display will prompt, Allow mode? Press Yes. The display will then ask for start and end times. There is no
restriction on the range of times entered. Any special pre/fire alarm entered for devices will then be used within the
specified time period. By pressing No, the Sensitivity Mode will be inhibited, and the display will return to
Commission Menu 3.

8.3

Verification Mode

Alarm verification can be used to reduce false alarms by placing a delay on a transient alarm signal received by a
smoke detector. This delay can be set when commissioning the panel. When an alarm is first received from a
smoke detector, the panel will start an internal timer and attempt to reset the detector. If the detector is still in
alarm after the verification timer has expired, the control panel will go into alarm. If the detector is not in alarm at this
point, the panel will enter a 60 second confirmation period. Any alarm received during the confirmation period will
be understood as a genuine fire alarm.

Select Day Mode from Commission Menu 3, then press 3) Verification Mode.

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 27
1998 Radionics, Inc All rights reserved.

Figure 65: Path Through Commission Menus to Verification Mode

After pressing 3) Verification Mode, the display will prompt, Allow mode ? Press Yes and set the desired start
and end times. By pressing No, the display returns to Commission Menu 3.
According to NFPA guidelines, the alarm verification feature should not be used as a substitute for
proper detector location/applications or regular system maintenance. Alarm verification features
are intended to reduce the frequency of false alarms caused by transient conditions. They are not
intended to compensate for design errors or lack of maintenance. Keep the verification delay to a
minimum (60 seconds absolute maximum).

The display will prompt, Verification delay = 0s? Enter the desired delay (see above NFPA guidelines for
maximum times). At the end of the Verification Mode settings, the display returns to Commission Menu 3. Lock the
memory and press No to return the panel to normal operation.

9.0

System Events
All System Events apart from the General events are normally programmed from a PC. Consult
the D9060 PC Programming Guide (P/N: 38647) for details.

System Events provide a flexible way of performing more complex cause-and-effect programming than that available
from the standard zone programming. Most systems do not require system events. Individual detectors can be
made to generate system events. Entry by way of a PC is strongly recommended if many detectors are to generate
events. If there are only a small number to enter, then this can be done directly from the Device change option on
any of the loops.

Event numbers can be any number from 1 to 200. Event number 0 is used to denote an unused event input or
output. The events can be shared over a network of panels if required by setting the Network, System Events to be
[Global]. For example, the operation of a manual pull station on Panel 1, Loop 2, Address 3 in one building is
required to energize a smoke control fan connected to Relay 2 on Panel 6. The steps to achieve this would be as
follows:

A.

At Panel 1, add an arbitrary system event number (for example, 20) to the manual call station.

B.

At Panel 6, allocate the smoke control fan output to System Event 20.

Check that both panels have Network option set for System Events to be global.

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 28

38789B 11/98

Most system events are latched and held until the panel is reset. Transient system events will automatically be
removed once the device that caused the event is restored to its normal condition. Input devices with action set to
non-latched create transient events. A transient event is held local to the panel of origin - it is not transmitted over
the network.

The Event Menu gives the following options:

Figure 66: System Events Submenu

9.1

General Events

This option allows special system event operation on several general functions as shown below. Any item set to
Event 0 means that this item is not in use.
Table 9: General Events
General System Event Name

When the Event is Generated

Fault Event

Detection of a fault.

Pre-Alarm Event

Any detector entering a pre-alarm condition.

Delayed Day Mode Event

Detection of a fire in a delayed-day mode (for example, when a panel enters Stage 1).

Local Fire Event

Any detector connected to the panel entering a fire condition.

Common Fire Event

Any panel connected to the panel entering a fire condition.

Silence Event (1)

When the external alarms are silenced.

AC Fail Event

When the AC timer has expired (see section 7.2 Calibration Time Setting).

Reset Event

Generated when the panel is reset.

Simple Coincidence Event

When any 2 devices enter a fire condition (this is independent of device type).

The Silence Event is automatically created as non-latching. The event is removed when silence is
canceled (for example, by resounding the alarms or resetting the panel). A Reset Event is
transient. It is removed 15 seconds after the panel has reset.

9.2

Event Logic
A PC is essential for programming Event Logic. Consult the D9060 PC Programming Guide (P/N:
38647) for details.

The System Event Logic allows complex logic sequences to be programmed into the fire panel. The logic modes
support both AND (coincidence) and OR functions on events, together with timers adjustable in 1 second steps
up to 999 seconds. The logic display allows any event sequence uploaded form the PC to be inspected on the
panel.

9.3

Define Event Outputs


Using a PC is strongly recommended when defining events. Consult the D9060 PC Programming
Guide (P/N: 38647) for details.

All output devices can have 2 system events directly assigned to them. A relay style device will turn on if either of
the assigned events occur. A sounder style device will turn on if the primary event occurs (shown as Event-A) or
will pulse if only the secondary event occurs (shown as Event-B). The Define Outputs display option allows the
events assignments to be inspected and changed if required. Press the No key to terminate this display option.

10.0

Inspect

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 29
1998 Radionics, Inc All rights reserved.

The Inspect Mode allows the programmer to inspect system configuration without the possibility of changing
configuration.

Figure 67: Path Through Commission Menus to Inspect


Select Option 1) Commission from the Main Menu, key in the Level Three Passcode (9898) and select Option 2)
Inspect. The display changes to the Inspect Submenu. See Table 10 for a description of the nine Inspect
options.
Table 10: Inspect Submenu Functions
Inspect Options

Function

Options 1-5

Allow the programmer to inspect the polling circuits by either zone or device.

Option 6

Allows the programmer to inspect the polling circuits by either zone or device.

Option 7

Allows the inspection of the notification appliance (sounder) outputs.

Option 8

Allows the inspection of the relay circuits.

Option 9

PC - not in use at this time.

Figure 68: Inspect Submenu

Press No to return to Commission Menu One. Select Option 3) Normal Operation. The Trouble LEDs will go out
and the display will return to normal.

11.0

Time/Date and System Options

These options are available from Commission Menu Two. Press > from the standard display to open the Main
Menu. Select Option 1) Commission, enter the Level Three Passcode (9898) and press Yes at Commission Menu
One to open Commission Menu Two.

Figure 69: Path to Commission Menu Two

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 30

38789B 11/98

11.1

Time/Date, System (Clear Memory), and Crystal Settings

Select Option 1) Time/Date. The display shows the current time and date. Press Enter to accept the current values.
Press Change to enter the Time/Date Submenu.

Time/Date

The Time/Date Submenu allows the programmer to change the time and date, erase all programming and return the
panel to factory default settings, and to adjust the crystal that controls the panels internal timer.

Figure 70: Time/Date Submenu

To reset the time, press 1 and key in the time based on a 24-hour clock. Press Enter to complete the time change.
To reset the date, press 2 and enter the current date.

System (Clear Memory)


A System Wipe will erase all current programming, returning the panel to factory default settings.
All programming entries will be lost.

Option 6) System asks, Do you want to wipe the WHOLE SYSTEM ?!! Press Yes to erase all programming. Press
No to return to the Time/Date prompt. Press Change to display the Time/Date Submenu

11.2

Crystal Setting

The panels internal clock is regulated by the timer crystal operating frequency. The programmer can adjust the
internal clock by changing the timer frequency value. Select Option 7) Crystal to display the current frequency of the
timer crystal.

Figure 71: Crystal Setting Submenu

Press Change to enter the Crystal Setting Change Submenu.

Figure 72: Crystal Setting Change Submenu

The system will prompt for the last three digits in the number. In Figures 68 and 69, the system currently has a value
of 3.68667 Mhz. Changing the last three digits from 667 to 668 (increasing the last digit by one) will cause the clock
to lose two seconds per week. Changing the last three digits to 666 (decreasing the last digit by one) will cause the
clock to gain two seconds per week.

Enter No to return to Commission Menu Two

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 31
1998 Radionics, Inc All rights reserved.

11.3

Program Integrity

Select Option 2) Program Integrity, from Commission Menu Two to display the program and Config RAM status, the
software revision number and checksums.

Figure 73: Program Integrity Submenu

The top line displays the status of the program and the configuration. The bottom line displays the software version
code, the software checksum and the RAM checksum. The software information should be quoted in any
correspondence. The RAM checksum will change whenever the configuration changes. Program integrity should be
checked and the RAM checksum recorded whenever the system configuration is changed.

11.4

Press 3) Power Supplies for the status of the AC power and standby battery power.

11.5

Modifying the Level 2 Passcode

Select Option 1) Commission from the Main Menu, and press Yes to move the display to Commission Menu Two.
Select Option 4) Modify Level 2 Code. Key in the four digits of the new Level 2 passcode and press Yes. Lock the
memory by moving the Memory Lock Switch to the up position. Select Option 3) Normal Operation. The Trouble
LEDs will go out and the display will return to normal.

11.6

Power Supplies

Erasing Event Log

Each panels log stores up to 500 events. The level three programmer may completely erase the event log. Select
Option 1) Commission from the Main Menu, enter the passcode and press Yes twice to display Commission Menu 3.
Press > twice. The display reads, the memory is locked. Unlock the memory. The display will prompt for the
passcode. Enter the Level Three Passcode (9898). The display reads erasing memory, and returns to
Commission Menu 1.

Figure 74: Path to Commission Menu Three

Lock the memory and press 3) Normal Operation.

Analog Fire Alarm Control Panels Programming Guide


1998 Radionics, Inc All rights reserved.
Page 32

38789B 11/98

13.0

Test Outputs

Section 8.4 System Tests in the D8024 Operators Manual (P/N: 35394) and the D9024/D10024 Operators Manual
(P/N: 74-07661-000) covers system testing. The LED Tests and the Walk Tests are available to Level Two
Operators. Test Outputs is available only to Level Three programmers. Select Option 2) Test from Commission
Menu One to display the Test Submenu.

Figure 75: Test Submenu

Select Option 3) Outputs. The display prompts for the passcode. Enter the Level Three Passcode (9898). The
display changes to the Outputs Test Submenu.

Figure 76: Outputs Test Submenu

Outputs one and two are relay outputs one and two. Outputs three through six are notification appliance (sounder)
outputs A through D. Press Yes to scroll through the outputs. Press Change from NOT OPERATED to
OPERATED. Press No to return to the Main Menu

14.0

The D8024, D9024 and D10024 may be programmed by using a PC. See the D9060 PC Programming Guide, P/N:
38647, for complete information.

15.0

PC Programming

Networking

Each analog panel can be networked with other panels of its own kind (for example, a D8024 can be networked with
other D8024s), or each analog panel can be networked with the other analog panels (for example, a D8024 can be
networked with either a D9024 or a D10024). See the Networking Guide, P/N: 34377, for complete information.

38789B 11/98

Analog Fire Alarm Control Panels Programming Guide


Page 33
1998 Radionics, Inc All rights reserved.

Alarm Thresholds, 14, 16


Alphanumeric Display, 5, 6, 9, 14, 17, 26
Auto Learn
Peripheral Circuit, 19
Polling Circuit, 12
Calibration
Device, 18
Peripheral Devices, 22
Time Setting, 9
Commissioning New Installations, 8
Configure Peripheral Device Text
Sensor Text, 21
Configure Relays, 24
Control Levels
Control Level One, 5
Control Level Three, 5
Control Level Two, 5
Controls and Displays, 5
Detector Protocol, 9
Device Action, 17
Event Log
Erasing, 32
Front Panel Keys, 8
Groups, 18
Group Assignment, 18
Group Disablement, 18
Inspect, 30
LED Display, 5, 6
Level Distinction, 5
Main Menu, 8, 9, 18, 25, 30, 32, 33
Memory Lock, 7, 8, 9, 11, 18, 32
Modes
Day Mode, 25
Delayed Mode, 25
Diagnostic Mode, 11
Normal Mode, 11
Pulse Delay Mode, 24
Pulse/Steady Delay Mode, 24
Sensitivity Mode, 26
Steady/Pulse Delay Mode, 24
Steady/Steady Delay Mode, 24
Verification Mode, 27
Modifying the Level 2 Passcode, 32
Networking, 33

Outputs
Testing, 33
Passcodes, 5
PC Programming, 33
Peripheral Circuit Addressable Notification
Appliance Circuit Controller Units (4-way
Sounders), 22
Power Supplies, 32
Program Integrity, 32
Program/Interactive Keys, 5
Sensor Text, 15
Setup
AC Fail Timer, 10
Exiting the Setup Menu, 11
Language Settings, 9
Log Mode Settings, 11
Memory Lock Check, 11
Name Settings, 10
Number of Polling Circuits, 9
Reset Inhibit, 10
Service Phone Number Setting, 10
Software Revision Number
Instructions for Identifying, 32
System Configuration
Changing Device Information, 22
Device, 14
Exiting Zone ConfigurationOption, 14
Notification Appliance (sounder) Circuits, 22
Peripheral Device Configuration, 21
Peripheral Device Zone, 21
Peripheral Zone, 20
Polling Circuits, 11
Zone, 13
System Control Keys, 5
System Events
Define Event Outputs, 29
Event Logic, 29
General Events, 29
System Options
Crystal Setting, 31
System (Clear Memory), 31
Time/Date, 31
Zone/Area Display, 5

1998 Radionics, Inc.


All rights reserved.
The Radionics logo is a registered trademark of Radionics, Inc.
1800 Abbott Street, Salinas, CA 93901, USA
Comments? Suggestions? E-Mail: [email protected]

You might also like