Ner P122

The document describes the testing and inspection of an overcurrent and earth fault relay. It provides details of the relay specifications, settings, and results of testing various components including current measurements, binary inputs and outputs, LED indications, and timing characteristics.

Uploaded by

sathiyaseelan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
98 views3 pages

Ner P122

The document describes the testing and inspection of an overcurrent and earth fault relay. It provides details of the relay specifications, settings, and results of testing various components including current measurements, binary inputs and outputs, LED indications, and timing characteristics.

Uploaded by

sathiyaseelan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 3

SITE INSPECTION AND TEST RECORD

Description:

End Client:

Date:

Over Current & Earth Fault Relay


(MICOM P122)
ALGIHAZ CO. LTD
Site:

25/02/2013

SEC-WOA
Panel Ref:

Sheet:

+R06.2- 13.8/11 kV Transformer T1 Protn. Panel 2

1 of 3

Device ID:

project no.:

13.8/11kV Tabuk Air Base S/S

51NER

30/31

FINAL SETTING TEST:


1. RELAY DETAILS:
Type No :

P122

Designation

51NER

Model No :

MiCOM P122B00Z112CD0

Nominal Current : In

1/5 A, 50/60Hz

Serial Number

360418

Aux. Volts

24-250 V DC, 48-240 V AC

Make

ALSTOM

: Vx

2. VISUAL INSPECTION:
Sl. No

Description

Inspect For Physical Damage / Defects

Verify Connections As Per Approved Drawing

Check Tightness Of All Connections

Check relay version and switching elements on printed circuit board

Checked

3. GENERAL CHECK:
Description

Sl. No
1

Auxiliary voltage value on terminals 33 ( + ) and 34 ( - )

Watchdog contact when relay OFF

Watchdog contact when relay ON

Check if the frequency is set on required value

Checked

Terminals 35- 36

Close

Terminals 37- 36

Open

Terminals 35- 36

Open

Terminals 37- 36

Close

4. BINARY INPUT OPERATION CHECK:


Test equipment used
FREJA 300

SL.NO. of Test equipment


1202561

Multimeter -Fluke 289

20130020

Calibration valid up to
17/09/2013
23/10/2013

Tested by:

Witnessed by: SEC Consultant Engineer

Name: Engr. Ganesan Selvam


Signature & Date :

Name: Engr. Sajid Rafique


Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

End Client:

Over Current & Earth Fault Relay


(MICOM P122)

Date:

25/02/2013

SEC-WOA
Panel Ref:

ALGIHAZ CO. LTD

Sheet:

+R06.2- 13.8/11 kV Transformer T1 Protn. Panel 2

Site:

Device ID:

project no.:

13.8/11kV Tabuk Air Base S/S

51NER

Terminal No.

Input No.

30/31

Active

Function Assigned

24

High

Future use

26

28

High

Future use

17

19

High

Not Used

(+)

(-)

OPTO 1

22

OPTO 2
OPTO 3

2 of 3

Result

5. BINARY OUTPUT CONTACT CHECK:


Commission Test Test Mode Contacts Blocked. Check Test Pattern Each BO.
Output No.

Terminal No.

Type

Function Assigned

42

NC

Spare

62

NO

Trip Stage-2

10 8

NC

Spare

12 8

NO

Trip Stage-1

RL 3

14 16

NO

Trip Stage-2

RL 4

18 20

NO

Trip Stage-2

RL 5

13

NO

Trip Stage-2

RL 6

57

NO

Spare

RL 1
RL 2

6.1.

6.2.

Result

FIXED LED INDICATIONS TEST:


LED No.

LED Label

Color

LED HI

Trip

Red

LED H2

Alarm

Yellow

LED H3

Warning

Yellow

LED H4

Healthy

Green

Result

LED INDICATIONS TEST: (RIGHT SIDE LED)


LED No.

LED Label

Test equipment used


FREJA 300

SL.NO. of Test equipment


1202561

Multimeter -Fluke 289

20130020

Color
Calibration valid up to
17/09/2013
23/10/2013

Tested by:

Witnessed by: SEC Consultant Engineer

Name: Engr. Ganesan Selvam


Signature & Date :

Name: Engr. Sajid Rafique


Signature & Date :

Result

SITE INSPECTION AND TEST RECORD


Description:

End Client:

Date:

Over Current & Earth Fault Relay


(MICOM P122)

25/02/2013

SEC-WOA
Panel Ref:

ALGIHAZ CO. LTD

Sheet:

+R06.2- 13.8/11 kV Transformer T1 Protn. Panel 2

Site:

Device ID:

project no.:

13.8/11kV Tabuk Air Base S/S

51NER

30/31

LED H5

NER Pickup

Red

LED H6

Stage 1 Trip

Red

LED H7

Stage 2 Trip

Red

LED H8

Spare

Red

7.

3 of 3

MEASUREMENT VALUE TEST:


CT Ratio: 300/1

Inj. Current
(A)

Calculated
Current
( A)

0.25

75.0

0.50

150.0

Relay Reading ( A )
R
Prim.

1.00
300.0
Deviation: Typical 0.5% at In ,
8.
8.1

Y
%Error

Prim.

B
%Error

Prim.

%Error

Manual : Schneider Technical Guide P12x/EN AD/Eb6

STAGE 1 (Ie>) EARTH FAULT :


PICK UP TEST:
Measured Current IN ( A )

Set Current
( A)

Pick up

Drop off

0.20
Deviation: Pickup: DT =Ies 2%, IDMT =1.1Ies2%
Drop off: DT =0.95Ies 2%, IDMT =1.05Ies2%
8.2

TIMING TEST:

Stage

Set Current ( A )

Set Time ( S )

Injected Current ( A )

Stage 1

0.20

1.20

0.40

Stage 2
0.20
1.40
Deviation : DT = 2%<50ms, IDMT =5%<50ms

0.40

Test equipment used


FREJA 300

SL.NO. of Test equipment


1202561

Multimeter -Fluke 289

20130020

Measured Time IN ( S )

Calibration valid up to
17/09/2013
23/10/2013

Tested by:

Witnessed by: SEC Consultant Engineer

Name: Engr. Ganesan Selvam


Signature & Date :

Name: Engr. Sajid Rafique


Signature & Date :