P341enbr BC
P341enbr BC
P341enbr BC
Interconnection
Protection Relay
MiCOM P341
Interconnection Protection Relay
T&D
Protection & Control
MiCOM P341
Interconnection Protection Relay
Introduction
Control
Protection
Disturbance records
Monitoring
Password protection
Communications
A choice of protocols
Software support
Diagnostics
Settings editor
Power-up diagnostics
Measurements
Comprehensive measurement
values
Instantaneous
Integrated
Application
With embedded generators running
in parallel with the normal public
supply there is a risk that, due to
fault clearances on the external
system, the embedded generator
may become disconnected from the
main supply network. The machine
may continue to supply external
load and there is a significant risk
of unsynchronised reconnection due
to auto-reclosure of the remote
circuit breaker. A range of
protection functions are provided to
detect this condition.
Dual loss of mains techniques are
provided as well as the more
traditional functions encompassing
voltage, frequency and power
elements. Figure 2a shows an LV
generator application for a single
unit, where the P341 is used as the
sole protection. It provides
overcurrent and earth fault, under
and overvoltage, under and
overfrequency and power
protection for the generator. In
addition, rate of change of
frequency and voltage vector shift
protections are provided for the
interconnection.
Figure 2b shows a MiCOM P341
protecting an MV interconnection
using neutral displacement, under
and overvoltage, under and
overfrequency, power, rate of
change of frequency and voltage
vector shift.
27
59
81U
81O
df
dt
dV
51
32R
51N
64
Undervoltage
Overvoltage
Underfrequency
Overfrequency
Rate of change of frequency
27
59
df
dt
dV
51
32R
27
59
81U
81O
64
51N
27
59
81U
81O
59N
df
dt
dV
67
Undervoltage
Overvoltage
Underfrequency
Overfrequency
Residual voltage
Rate of change of frequency
df
dt
51
81U
81O
59N
dV
32
67N
Protection functions
Loss of mains
Phase overcurrent
Wattmetric
Under/overfrequency
Supervisory functions
Circuit breaker failure
protection
Two stage circuit breaker failure
protection may be used for tripping
upstream circuit breakers and/or
the local secondary trip coil.
The circuit breaker failure logic
may also be initiated externally
from other protection devices if
required.
Voltage transformer
supervision
Voltage transformer supervision
(VTS) is provided to detect loss of
one, two or three VT signals,
providing indication and inhibition
of voltage dependent protection
elements.
An optically isolated input may also
be configured to initiate the voltage
transformer supervision alarm and
blocking when used with miniature
circuit breakers (MCBs) or other
external forms of voltage
transformer supervision.
Current transformer
supervision
Current transformer supervision
(CTS) is provided to detect loss of
phase CT signals and inhibit the
operation of current dependent
protection elements.
Control
Circuit breaker control
Circuit breaker control is available
from the front panel user interface,
optically isolated inputs and
remotely via the substation
communications.
Programmable scheme logic
Programmable scheme logic allows
the user to customise the protection
and control functions. It is also used
to programme the functionality of
the optically isolated inputs, relay
outputs and LED indications.
The programmable scheme logic
comprises gate logic and general
purpose timers. The gate logic
includes OR, AND and majority
gate functions, with the ability to
invert the inputs and outputs, and
provide feedback. The system is
optimised to evaluate changes to
the scheme logic signals and thus
minimise any delays in logic
execution.
The programmable scheme logic
may be configured using the
graphical MiCOM S1 PC based
support software, as illustrated in
Figure 3.
The required logic is drawn as
shown and is then downloaded
directly into the relay. The logic
may also be uploaded from the
relay and then modified using
MiCOM S1 support software.
Independent protection
settings groups
The settings are divided into two
categories; protection settings and
control and support settings.
Four setting groups are provided
for the protection settings to allow
for different operating conditions
and adaptive relaying.
Measurements
The measurements provided, which
may be viewed in primary or
secondary values, can be accessed
by the back-lit liquid crystal display,
or the communications ports.
Phase notation is user definable
using the MiCOM S1 text editor.
Instantaneous measurements
Measurement and
recording facilities
Phase voltages
Line voltages
Van Vbn
Vab Vbc
Neutral voltage
Vn
Phase current
Ia Ib Ic
Neutral currents
In ISEF
A lithium battery provides a backup for the real time clock and all
records in the event of supply
failure. This battery is supervised
and is easily replaced from the
front of the relay.
Vcn
Vca
Wa Wb Wc
Wtotal
VAra VArb VArc
VArtotal
VAa VAb VAc
VAtotal
Integrated values
Wh
VArh
Ia Ib Ic
W VAr
Plant supervision
Trip circuit monitoring
Monitoring of the trip circuit in both
breaker open and closed states can
be realised using the
programmable scheme logic.
Circuit breaker state
monitoring
An alarm will be generated if there
is a discrepancy between the open
and closed contacts of the circuit
breaker.
Circuit breaker condition
monitoring
The circuit breaker condition
monitoring features include:
monitoring the number of
breaker trip operations
recording the sum of the broken
current quantity Ix, 1.0 x 2.0
monitoring the breaker operating
time
monitoring the fault frequency
counter
Modbus
Modbus is a master/slave protocol,
whereby the master must have
knowledge of the slaves databases
and addresses. The Modbus
implementation supported by the
MiCOM P340 series is RTU mode.
IEC 60870-5-103
The relay is compliant with the
transmission protocol defined by
the specification IEC 60870-5-103.
The standarised messages based
on the VDEW communication
protocol are supported.
DNP 3.0
The DNP 3.0 protocol is defined
and administered by the DNP User
Group.
The relay operates as a DNP 3.0
slave and supports subset level 2 of
the protocol plus some of the
features from level 3.
Local communications
The front serial communications
port has been designed for use
with MiCOM S1, which fully
supports functions within the relay
by providing the ability to
programme the settings off-line,
configure the programmable
scheme logic, extract and view
event, disturbance and fault
records, view the measurement
information dynamically and
perform control functions. PAS&T
support software can also be used
with the local communications port.
F11
Relay failed
F12
F13
Relay healthy
F14
+ F7
48V field voltage
F9
Watchdog
C1
C2
C4
C5
C7
C8
50P
50N
51P
51N
64
CTS
kA, kV, Hz
kW, kVA, kVArs
kWh, kVArh
Sequence components
+ F8
48V field voltage
F10
+ F2
Measurements
Auxiliary voltage
F1
50BF
250
Event
records
C13
IN > 1
Start ON
See note 3
00:12:00 01/01/99
Trip A B C
ON
IRIG-B
Time
synchronisation
RS232
Courier
RS485
Courier
Modbus
IEC60870-5-103
00:12:01 01/01/99
C14
See note 1
See note 2
20
Disturbance
records
C19
C20
67
67N
27
59
C21
32
C22
VTS
df
dt
81
dV
LEDs
Fault A-B-C
5
Fault
reports
User programmble
15ms
Ia = 1000 A Ib =
1000 A Ic = 1000 A
RL1
1
C23
&
59N
C24
&
RL2
RL3
RL4
Breaker
monitoring
52
No. trips
SUM I2
CB opt time
= 100
= 1000 kA
= 100 ms
RL5
RL6
L1 Setting group
L2 Setting group
L3 Block IN>3&4
User
programmble
(defaults
shown)
L4 Block I>3&4
L5 Reset
L6 Ext prot trip
L7 52a
L8 52b
RL7
D2
E1
E2
E3
E4
E5
E6
E7
E8
E9
E10
E11
E12
E13
E14
E15
E16
E17
E18
R1 IN>1 Start
R2 I>1 Start
R3 Any trip
R4 General alarm
R5 CB fail
R6 Control close
R7 Control trip
D1
D4
D3
D6
D5
D8
D7
D10
D9
D12
D11
D14
D13
D16
D15
ANSI Numbers
67/50P
67/50N
67/51P
67/51N
67N/64
50BF
CTS
27
52
59
81
32
df/dt
dV
59N
VTS
Circuit breaker
Overvoltage
Over/underfrequency
Reverse/low forward/over power
Rate of change of frequency
Voltage vector shift
Neutral displacement/residual overvoltage
Voltage transformer supervision
Note 1:
All CT connectors have integral shorting. These contacts are made before
the internal CT circuits are disconnected.
Note 2:
Note 3:
User
programmble
(defaults
shown)
Diagnostics
Automatic tests performed including
power-on diagnostics and
continuous self-monitoring ensure a
high degree of reliability. The
results of the self-test functions are
stored in non-volatile memory. Test
features available on the user
interface provide examination of
input quantities, states of the digital
inputs and relay outputs. A local
monitor port providing digital
outputs, selected from a prescribed
list of signals, including the status
of protection elements, may be
used in conjunction with test
equipment. These test signals can
also be viewed using the Courier
and Modbus communications ports.
1
6
5
4
Hardware description
The MiCOM P341 includes:
User interface
An RS485 port
A download/monitor port
A battery (supervised)
N/O and N/C watchdog contacts
Supervised +48V field voltage
Four 1A/5A dual rated CTs
(5) READ
and CLEAR
keys for viewing and
acknowledging alarms.
(6) An upper cover identifying the
product name. The cover may
be raised to provide access to
the product model number,
serial number and ratings.
(7) A lower cover concealing the
front RS232 port, down
load/monitor port and battery
compartment. The front of the
cover can display the name of
8
Password protection
Password protection may be
independently applied to the
front user interface, front
communications port and rear
communications port. Two
levels of password protection
are available providing access
to the controls and settings
respectively.
Phase fault
IEEE/US curves
TMS = 1
TD = 7
100
1000
100
10
Operating
time (s)
IEC/UK curves
Operating
time (s)
10
UK LTI
IEC SI
1
IEEE MI
IEEE VI
IEC VI
10
100
100
t = TMS x
10
TD 0.5 to 15
0.14
0.02
( ) -1
I
Wattmetric characteristic
US CO8
IEEE EI
0.1
0.1
US CO2
IEC EI
Is
TD
x
7
0.0515
0.02
( ) -1
I
+ 0.114
Is
t = TMS x
13.5
( ) -1
I
Is
TD
x
7
19.61
2
( ) -1
I
+ 0.491
Is
t = TMS x
80
2
( )-1
I
Is
TD
x
7
28.2
2
( ) -1
I
+ 0.1217
Is
t = TMS x
120
US CO8 Inverse
( )-1
I
t=
Is
TD
x
7
5.95
2
( ) -1
I
+ 0.18
Is
t=
TD
x
7
0.02394
0.02
( ) -1
I
+ 0.01694
Is
Undervoltage
Voltage settings, Vs
10 to 120V
(100 120V)
40 to 480V
(380 480V)
Time settings
DT
IDMT
Time settings
DT
IDMT
k
0 to 100s
t = k/(1 V/Vs)
0.5 to 100
Overvoltage
0 to 100s
t = k/(V/Vs 1)
k 0.5 to 100
Frequency settings
45 to 65Hz
Time settings
0 to 100s
Voltage settings, Vs
60 to 185V
(100 120V)
240 to 740V
(380 480V)
Time settings
DT
IDMT
k
56W to 160W
(In = 1A, Vn = 380 480V)
0 to 100s
t = k/(V/Vs 1)
0.5 to 100
Residual overvoltage
Voltage settings, Vs
1 to 50V
(100 120V)
4 to 200V
(380 480V)
14W to 40W
(In = 1A, Vn = 100 120V)
70W to 200W
(In = 5A, Vn = 100 120V)
280W to 800W
(In = 5A, Vn = 380 480V)
Time settings
Definite time
DO timer
0 to 100s
0 to 10s
9
280W to 6000W
(In = 5A, Vn = 380 480V)
Time setting
Definite time
DO timer
0 to 100s
0 to 10s
Outputs:
Field voltage supply
48V dc (current limit: >100mA)
Burdens
Nominal voltage circuit
Sensitve overpower
0.3W to 100W
(In = 1A, Vn = 100/120V)
1.2W to 400W
(In - 1A, Vn = 380/480V)
1.5W to 500W
(In = 5A, Vn = 100/120V)
6W to 2000W
(In = 5A, Vn = 380/480V)
Rate of change of frequency
Df/dt
0.1 to 10Hz/s
Definite time
0 to 100s
<0.15VA
<0.2VA
Auxiliary voltage
Size 8 (40TE)
minimum 11W
or 24VA
Operating voltage
>30V dc
60V dc
AC immunity
50V rms
Contacts
Contact ratings:
Make:
Carry:
5A continuous
Break:
dc 50W resistive
25W inductive
(L/R = 40ms)
ac 1250VA resistive
AC current inputs
ac 1250VA inductive
(P.F. = 0.7)
Subject to maxima of 5A and
300V
Watchdog contact ratings
dc 30W resistive
4.0In continuous
dc 15W inductive
(L/R = 40ms)
Technical data
100In for 1s
Ratings
ac 375VA inductive
(P.F. = 0.7)
AC voltage inputs
Inputs:
AC current (In)
1A/5A dual rated ac rms
AC voltage (Vn)
100 120V or 380 480V rms
nominal phase-phase
Rated frequency 50 to 60Hz
Operative range 40 to 70Hz
Auxiliary voltage (Vx)
dc
Nominal
(V)
Digital inputs
ac
24 54 19 65
Durability:
2 Vn continuous
Loaded contact
2.6 Vn for10s
Current transformer
requirements
The following CT requirements are
based on a maximum prospective
fault current of 50In and the relay
having a maximum high set setting
of 25In. The CT requirements are
designed to provide operation of:
Phase and standard earth fault
elements
1A rated currrent circuits
2.5VA 10P 20
Limiting lead resistance 0.11
5A rated current circuits
7.5VA 10P 20
10
1000m max
Connector
Screw terminals
Signal levels
RS485
Isolation
SELV
Remote access
Protocols supported
Courier
Modbus
IEC 60870-5-103
DNP 3.0
Note:
An interface to an optical
fibre, type 850nm, BFOC
2.5 connector is available
for IEC 60870-5-103.
Point to point
Cable type
Multi-core
Cable length
15m max
Connector
RS232 DTE
9 pin D-type female
Protocol
Isolation
Courier
Local access
Carrier signal
Amplitude modulated
SELV
Internal battery
Battery type:
1/ AA,
2
3.6V
Download/monitor port
This is a 25 pin D-type female
connector located on the front user
interface and is specifically
designed for test purposes and
software download.
Isolation
Local access
ELV
Cable type
50 coaxial cable
Isolation
ANSI/IEEE C37.90-1989
(r1994)
IRIG-B Port
BNC
ELV
Connection
Electrical environment
DC supply interruption
IEC 60255-11: 1979
The unit will withstand a 20ms
interruption in the auxiliary
supply, in its quiescent state,
without de-energising.
AC ripple on dc supply
11
Surge immunity
IEC 61000-4-5: 1995 Level 4
Atmospheric environment
Additional information
Temperature
Technical Guide
TG8614
IEC 60255-6:1988
Operation Guide
OG8614
Courier Communications
R4113
R8610
R7012
Cold
PAS&T
R8514
EMC compliance
89/336/EEC
Compliance to the European
Commission Directive on EMC is
claimed via the Technical
Construction File route.
Generic Standards were used to
establish conformity:
EN50081-2: 1994
EN50082-2: 1995
Product safety
73/23/EEC
Compliance with European
Commission Low Voltage
Directive.
Compliance is demonstrated by
reference to generic safety
standards:
EN61010-1: 1993/A2: 1995
EN60950: 1992/A11: 1997
Case
Dry heat
Humidity
IEC 60068-2-3: 1969
56 days at 93% RH and +40C
Enclosure protection
IEC 60529: 1989
IP52 Protection (front panel)
against dust and dripping water
at 15 to the vertical.
Mechanical environment
Vibration
IEC 60255-21-1: 1996
Response Class 2
Endurance Class 2
Shock and bump
IEC 60255-21-2: 1995
Shock response Class 2
Shock withstand Class 1
Bump Class 1
Seismic
IEC 60255-21-3: 1995 Class 2
Case
P341 MiCOM 40TE
Weight
P341
7kg
12
23.30
155.40
A B
BA
159.00
AB
10.35
Sealing strip
177.0
(4U)
168.00
BA
181.30
202.00
A = Clearance holes
B = Mounting holes
200.00
Front view
177.00
206.00
MiCOM P341
specification
An integrated interconnection
protection scheme shall provide
rate of change of frequency,
voltage vector shift, neutral
displacement/residual overvoltage,
under and overvoltage, under and
overfrequency and directional
power protections, as well as
directional overcurrent and
directional earth fault protection.
Four stages of directional phase
overcurrent and earth fault
protection shall be provided, with a
selection of nine IDMT
characteristics for two of the stages.
An additional CT shall be provided
for sensitive or restricted earth fault
protection. It shall be possible to
use frequency to supervise the rate
of change of frequency function. It
shall be possible to set the power
element for any potential power
157.5 max
30.00
Side view
13
MiCOM
P 3 4
Vx aux rating
1
2
3
24 48V dc
48 125V dc (30 100V ac)
110 250V dc (100 240V ac)
Vn rating
1
2
100 120V ac
380 480V ac
Hardware options
1
2
3
4
Standard version
IRIG-B input
Fibre optic converter (IEC 60870-5-103)
IRIG-B input & fibre optic converter (IEC 60870-5-103)
Protocol options
1
2
3
4
K-Bus
Modbus
IEC 60870-5-103 (VDEW)
DNP 3.0
Accessories
FX0021 001
GN2044 001
P341
Blanking plates:
Size
Size
Size
Size
Size 40TE
10TE
20TE
30TE
40TE
ZB9124 900
ZB9124 901
GN0037 001
GJ2028
GJ2028
GJ2028
GJ2028
14
102
104
106
108
Notes
Your contact
15
T R A N S M I S S I O N & D I S T R I B U T I O N Protection & Control, Le Sextant, 3 avenue Andr Malraux, 92300 Levallois-Perret. France
Tel: +33 (0) 141 49 20 00 Fax: +33 (0) 1 41 49 24 85 Email: [email protected] Internet: www.tde.alstom.com
Contact Centre on line 24 hours a day : +44 (0) 1785 27 24 51