Micrex-Sx SPB Leh984c

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

Integrated Controllers

Series

Programmable Logic Controller

LEH984c

Compact size

Online program edit function

Ideal for reducing control panel space.

20-points basic unit


30-points basic unit
40-points basic unit
60-points basic unit
16-points expansion unit
32-points expansion unit
60-points expansion unit

External Dimensions (mm)


Width
Height
Depth
80
90
81
110
90
81
140
90
81
180
90
81
64
90
81
90
110
81
180
90
81

Two programming languages


With one type of hardware, SPB is applicable to two programming languages:
SX mode: MICREX-SX (language compliant with IEC)
N mode: FLEX-PC N (language of ladder and instruction words)

Large-capacity memory

Type
20points basic unit
30points basic unit
40points basic unit
60points basic unit
*1

4Ksteps

International standards conformity


All SPB models conform to the UL/cUL standards as well as the CE
mark standard.

Two analog timers


Two analog timers are built in for convenient fine-tuning and
testing.

Communication & Networking


Communication adapters are available for RS-232C, RS-485,
and simplified personal computer link connections.

POD direct connection

Programming with rich memory


Memory capacity
Porogram memory
SX mode * 1 N mode
4Ksteps
2Ksteps

Allows program modification without interrupting machine operation.

The SPB can be connected to the POD via the loader port. No
special communication unit is required.
Data memory
N mode
SX mode
5Kwords
9Kwords
8.5Kwords

8Ksteps

There are Included the initiated value of the retain memory.

High-speed processing
Ideal for small-size machines requiring fast processing.
Fast 0.44 sec. per Sequence instruction and 2.19 sec(N
mode). and 1.50 sec(SX mode). for Data instructions.

Diversified functions for expanding applications


Internal high-speed counter function
Interrupting function
Pulse train output function
Pulse catch function
Constant scan setting
Pulse width modulation function

Adapted to analog control


Many types of instructions
Many types of instructions allow ease of programming.
The program size can be reduced by effectively using a combination of instruction words.
SX mode: 202 types, N mode: 211 types.

Multi-range (voltage / current) adapted. 3 types of analog unit


with detachable terminal blocks are added to the lineup.
Capable of analog control, such as temperature control by
PID instruction.

Self-lifting terminal block & Finger protection


Use of the self-lifting terminal block - the terminals automatically pop up when unscrewed, reducing the wiring works and
preventing less of screws. The finger protection structure ensures safety.

Features ................................................................. 3
SPB Lineups .......................................................... 4
System Configurations ......................................... 6
Specifications ........................................................ 9
External Connection Diagrams .......................... 14
Control Functions ............................................... 15
Programming Languages ................................... 16
Online Adapters .................................................. 20
Dimensions .......................................................... 21
Ordering Informations ........................................ 22
3

SPB Lineups

Basic Unit
20-points Basic Unit: NW0P20 -

30-points Basic Unit: NW0P30 -

Power voltage: 100-200V AC, 24V DC


Input: 12 points, Output: 8 points
Relay output, Transistor output
Stand alone unit no expansion

Power voltage: 100-200V AC, 24V DC


Input: 16 points, Output: 14 points
Relay output, Transistor output
Connectable up to five expansion units

20
120

100

120

100

80

80

60

40

20

80

60

40

40

20

20

(mm)

100

60

40-points Basic Unit: NW0P40 -

120

100

80

60

40

20

(mm)

60-points Basic Unit: NW0P60 -

Power voltage: 100-200V AC, 24V DC


Input: 24 points, Output: 16 points
Relay output, Transistor output
Connectable up to five expansion units
Calendar function (year, month, day, hour, minute, second,
day of week) (different type)

Power voltage: 100-200V AC, 24V DC


Input: 36 points, Output: 24 points
Relay output, Transistor output
Connectable up to five expansion units
Calendar function (year, month, day, hour, minute, second,
day of week) (different type)

40

60

180

30

120

160

140

120

120

100

80

60

40

20

120

100

100

80

80

60

60

40

40

20

20

(mm)

180

160

140

120

100

80

60

40

20

(mm)

Expansion Unit
Digital I/O Unit

Analog Unit

16-points I/O Expansion Unit: NW0E16 -3

Analog Input Unit: NW0AX04-MR

Input: 8 points, Output: 8 points


Relay output, Transistor output

Multi-range input: 4ch

Analog Output Unit: NW0AY04-MR

16-points Input Expansion Unit: NW0E16X


Input: 16 points

Multi-range output: 4ch

Analog I/O Unit: NW0AW03-MR

16-points Output Expansion Unit: NW0E16 -0


Relay output, Transistor output

32-points I/O Expansion Unit: NW0E32 -3


Input: 16 points, Output: 16 points
Relay output, Transistor output

Multi-range input: 2ch


Multi-range output: 1ch

Thermocouple Input Module: NW0AX04-TC


Input: 4ch

Resistance Bulb Input Module: NW0AX04-PT

60-points I/O Expansion Unit: NW0E60R-31

Input: 4ch

Power voltage: 100-200V AC


Input: 32 points, Relay output: 28 points

Communication Adapter
RS-232C Adapter: NW0LA-RS2
General-purpose communication mode: RS-232C
1ch

Option
RS-485 Adapter: NW0LA-RS4
General-purpose communication mode: RS-485
Simplified CPU link mode
1ch

Memory Card: NW8PMF-8


Flash ROM for 40/60-points basic unit

System Configurations

Expansion Digital I/O System


Basic Unit + Digital I/O Unit

I/O Points

For the SPB, the number of I/O points can be increased up to 360
by adding digital I/O units to the basic unit. Up to five digital I/O
units can be added.

Max. digital I/O points

NW0P20 -3

20 points

20 points

NW0P30 -3

30 points

330 points

NW0P40 -3

40 points

340 points

NW0P60 -3

60 points

360 points

System with 60-point digital I/O units


A maximum of five 60-point digital I/O units, or 300 digital I/O points can be added.

360

points (60 +60 +60 +60 +60 +60)

Basic unit

Maximum five units (system with 60-point digital I/O units)

System with a combination of 16- 32- and 60-point digital I/O units

Basic unit

Basic unit

60 points digital I/O unit


Maximum three units (up to 64 I/O points)

Maximum three units (up to 64 I/O points)

Maximum five units (system including 60-point digital I/O unit)

* The basic unit and 60-point digital I/O unit require a power supply. The 16-/32-point digital I/O units are supplied the power from the
basic unit and 60-point digital I/O unit as indicated with an arrow ( ). One basic unit or one 60-point digital I/O unit can supply power
to a maximum of three expansion units (64 or fewer I/O points).

System with a combination of 16- and 32-point digital I/O units


The system with no 60-point digital I/O units allows addition of a maximum of three units, or 64 digital I/O points.

Basic unit

Maximum three units (up to 64 I/O points)

Expansion Analog System


System expanded only with analog units
For the SPB, up to three analog units can be added to the basic unit.
By doing so, the number of analog I/O points can be increased up to 12.
Analog
unit

Analog
unit

Analog
unit

Basic unit

Maximum 3 units (12 analog I/O points )

System expanded with a combination of digital I/O unit and analog unit
System without 60-point digital I/O units
Also when the basic unit is used in combination with 16-/32-point digital I/O units and/or analog units, a maximum of three units can be
added.
32-points
expansion

Analog
unit

32-points
expansion

Basic unit

Maximum 3 units (64 or less digital I/O points + analog unit)

System with 60-point digital I/O units


When the basic unit is used in combination with 60-point digital I/O units and/or analog units, a maximum of five units can be added (up to
three analog units).
Analog
unit

32-points
expansion

Analog
unit

60-points
expansion

Analog
unit

Basic unit

Maximum 3 units (64 or less digital I/O points


+ analog unit)

Maximum 3 units (64 or less digital I/O points + analog unit)


Maximum 5 units

Points for system expansion


To each of the basic unit and 60-point digital I/O unit, a maximum of three units can be added (64 or fewer I/O points + analog unit). Note that
the maximum number of expansion units is 5.
Connect this unit at a position where power can be supplied from the
60-point digital I/O unit.

16-points
expansion

16-points
expansion

16-points
expansion

Analog
unit

60-points
expansion

Basic unit

Up to three expansion units (64 or less digital I/O points + analog unit)

Basic unit and maximum number of expansion units

Max. number of connectable expansion units Connection of

The 20-point basic unit does not allow connecting expansion


units.
The maximum number of expansion units varies depend
ing on the basic unit and digital I/O unit versions.
Note that some basic unit versions do not allow connect
ing analog units. See the table given on the right for details.

Digital I/O unit

Digital I/O unit

analog unit

Older than version 10 Version 10 or later


Versions Older than version 10.07
of basic 10.07 to 20.10
unit
Version 20.11 or later

2 units

2 units

Impossible

2 units

3 units

Possible

2 units

5 units

Possible

System Configurations

Communication Systems
System based on RS-232C Adapter: NW0LA-RS2
RS-232C Adapter

Personal computer
Printer
Barcode reader
Other devices for
RS-232C

Item

Specification

Electrical specifications

RS-232C

Communication specifications Half-duplex transmission

Basic unit

Connection form

1:1

Transmission rate

38.4kbps max.

Transmission distance

15m max.

User interface

Nonsequenced transmission/
command set type
transmission

System based on RS-485 Adapter: NW0LA-RS4


1) RS-485 mode
RS-485 Adapter

Personal computer
Barcode reader
Other devices for
RS-485

Item

Specification

Electrical specifications

RS-485

Communication specifications Half-duplex transmission

Basic unit

Connection form

1:31 (max.)

Transmission rate

38.4kbps max.

Transmission distance

1km max.

User interface

Nonsequenced transmission/
command set type
transmission

2) Simplified CPU link mode


RS-485 Adapter

Item

Specification

Electrical specifications

RS-485

Communication specifications NP link micro

Basic unit

Basic unit

Basic unit

Connection form

Bus

Transmission rate

125kbps max.

Transmission distance

500m max.

Number of units connected

16 units max.

Data amount

32 words/station max.

* When connecting with the NB series, the transmission rate is limited


to 19.2 kbps and the data amount to 8 words/station.

POD Connections
1) Loader port connection

The programmable operation display (POD) can directly be connected to the loader port.

UG30 series
Dedicated cable
Type: UG200C-N0

Basic unit

2) General-purpose communication connection


Connection through the RS-232C/RS-485 adapter is possible.

UG30 series

Program Loader
Basic unit
Personal
computer

Communication adapter
8

Handy Loader

Specifications

Basic Unit / Expansion Unit Specifications


General Specifications
Item
Physical
Operating ambient
environment temperature
Storage (transport)
temperature
Relative humidity
Pollution level
Corrosive gas
Altitude/Atm.
Mechanical Vibration
operating
resistance
condition
Impact resistance
Electrical
operating
condition

Electrostatic discharge
resistance
Radiation resistance
Noise immunity
Grounding method
Structure
Installation method

Cooling method

Performance Specifications (SX mode)

Specification
0 to +55 C

Item
Calculation control

25 to +70 C

I/O control method

20 to 95% RH no condensation
Level 2 (IEC61131-2)
Free from corrosive gases, not stained with organic solvents
2000m or less above sea level
(Transport condition : 70kPa or more)
Half amplitude 0.15mm, Constant acceleration
19.6m/s2, 2 hours in each direction, 6 hours in total
Peak acceleration 147m/s2 (IEC conformance), 3 times
in each direction
6 kV: contact discharge, 8 kV: aerial discharge
(class 3)
10V/m (80 to 1,000MHz)
Noise simulator method, rising 1ns, Pulse width 1s, 1.5kV
Type D grounding (ground resistance 100)
Panel-mounted type IP30
Installation direction: Vertical
Fixing method: Direct installation (M4 screws) or
installation with JIS/IEC (35mm wide) support rail
Ambient air-cooled

Program language
(Based on IEC 61131-3)
Program capacity
No. of instructions
Instruction
processing
speed
(dimensions in s)
No. of tasks
No. of POUs
Data types *1

Basic unit
Data memory capacity
I/O memory (IQ) <Fixed>
System memory (SM) <Fixed>
Standard memory (M) <Variable>

Performance Specifications (N mode)


Item
Calculation control
I/O control method
Program language
Program capacity
No. of
Sequence instruction
instructions Applied instruction
Instruction processing speed
I/O relay
X,Y
Internal relay
M
Expanded internal relay M
Latch relay
L
Expanded latch relay
L
Special relay
M
Timer
(10 ms base) T
(1 ms base) T
Counter (increment)
C
Register Data register D
Special register D
File register R
Pointer
For branching P
For interrupt
I
Input filter time
High-speed counter
Pulse output
Self-diagnostic function
Memory backup

Calendar

Specification
Stored program repeated calculation method
Batch refresh method/Direct method
Ladder, mnemonic
Basic unit 20/30 points : 4K steps (flash memory built in)
Basic unit 40/60 points : 8K steps (flash memory built in)
45 types
166 types
Basic instruction 0.44s or more
Applied instruction 2.19s or more
1024 points
1024 points
3072 points
1024 points
3072 points
512 points
384 points (T000 to T17F)
128 points (T180 to T1FF)
256 points
8192 words
256 points
Uses the program area depending upon the setting
256 points
10 points
Variable (No filter, 3ms/3ms (default), 10ms/10ms)
Single-phase, 100kHz, 2points (unsigned 16-bit)
or Two-phase, 50kHz, 1point (signed 32-bit)
1 to 100kHz, 2points (transistor output type basic unit only)
Memory check, watchdog timer, etc.
Program (including file registers), parameters
Built-in RAM + capacitor and built-in flash (20/30-points unit)
Built-in RAM + battery and built-in flash (40/60-points unit)
Data memory (power failure retaining area)
Built-in RAM + capacitor (20/30-points unit)
Built-in RAM + battery (40/60-points unit)
Backup time of the memory
Built-in RAM + capacitor backup time: About 2 weeks (at 25C)
Built-in RAM + battery backup time: About 5 years (at 25C)
Number of updates of built-in flash: About 100,000 times
Accuracy 27 seconds/month (at 25C)
(Calendar function adapted type only)

Retain memory (RM) <Variable>


User FB memory (FM) <Variable>
System FB memory (SFM) <Variable>
Timer <Variable>
Counter <Variable>
Edge detection <Variable>
Others <Variable>
FM characteristic
initiated value <Variable>
Temporary memory capacity
Input filter time
High-speed counter
Pulse output
Self-diagnostic function
Memory backup

Calendar

Specification
Stored program, Cyclic scanning system (default
task), periodic task, event task
Whole: Scanning and batch refresh method
Digital I/O: Synchronous refresh with task method
IL, ST, LD, FBD, SFC
4K steps
2K steps
202 types
Sequence instructions: Contact: 0.44~, Coil: 0.50~
Addition and subtraction instructions: 2.56~
Multiplications and division instructions: 3.88~
Timer instructions: 18.44~
Counter instructions: 13.88~
Default task: 1
Periodic task, event task: total 4
Program: 8
User FB: 16
User FCT: 16
BOOL, WORD, DWORD, INT, DINT, UINT,
UDINT, TIME, DT, Array data types (The array
number are possible to the variable setting),
Structured data types.
60-points basic unit 40-points basic unit 30-points basic unit 20-points basic unit
8.5K words
5K words
512 words (The direct connected digital I/O are
possible to synchronous refresh with task)
512 words
2.5K words
1.5K words
(High-speed memory: 512 words fixed) (High-speed memory: 512 words fixed)
1K words
512 words
0K words (Max. 1.5K words) 0K words (Max. 1.5K words)
4K words
2K words
256 points
128 points
128 points
64 points
512 points
256 points
512 words
256 words
0K words
0K words
(Max. 192+1.5K words)
(Max. 384+3K words)
1K words (Average: 42 words/POU)
Variable (No filter, 3ms/3ms, 10ms/10ms)
Default (3ms/3ms)
Single-phase, 100kHz, 2points (unsigned 16-bit)
or Two-phase, 50kHz, 1point (signed 32-bit)
1 to 100kHz, 2points (transistor output type basic unit only)
Memory check, watchdog timer, etc.
Program (including file registers), parameters
Built-in RAM + capacitor and built-in flash (20/30-points unit)
Built-in RAM + battery and built-in flash (40/60-points unit)
Data memory (power failure retaining area)
Built-in RAM + capacitor (20/30-points unit)
Built-in RAM + battery (40/60-points unit)
Backup time of the memory
Built-in RAM + capacitor backup time: About 2 weeks (at 25C)
Built-in RAM + battery backup time: About 5 years (at 25C)
Number of updates of built-in flash: About 100,000 times
Accuracy 27 seconds/month (at 25C)
(Calendar function adapted type only)

*1 Data types: REAL type, DATE type, TOD type, STRING type are unsupported.

Specifications

Basic Unit / Expansion Unit Specifications

Input Specifications
Input circuit characteristics Input signal

Item
Rated voltage
Voltage tolerance difference
(min. to max.)
Allowable ripple ratio
Input method
Rated current
Input impedance
Standard ON voltage range
operating range OFF voltage range
Input type
Input delay Hardware
time
Software

Isolation method
Dielectric strength
Insulation resistance

Specification
Fast DC Input
Normal DC Input
24V DC
24V DC
24V DC 10%
24V DC 10%
(including ripple)
(including ripple)
5%
5%
Both sink and source (bi-directional) Both sink and source (bi-directional)
Approx. 5mA (at 24V) Approx. 5mA (at 24V)
Approx. 4.7k
Approx. 4.7k
15 to 26.4V
15 to 26.4V
0 to 5V
0 to 5V
Conforms to Type 1
Conforms to Type 1
400s
25 s or less
Can be set to No filter, 3ms/3ms, or 10ms/10ms by parameter
(Default is 3 ms/3 ms)
Photocoupler isolation
1500V AC for 1 min. (between entire input terminals and FG)
10M or more with a 500 V DC megger (between entire input terminals and FG)

Note: Terminal Nos. 0 to 3 of the basic unit are for high-speed DC input; other terminal
numbers are generally for DC input.

10

Relay Output
Specification
240V AC, 110V DC
264V AC, 140V DC
Relay
240 V AC/30 V DC: 2 A/point, 8 A/common
110 V DC: 0.2 A/point, 1.6 A/common
Output delay time
10ms or less
Min. load voltage/current 5V DC, 1mA
Max. switching frequency 1800 times/hour
Built-in fuse
None
Output type
Relay
Surge suppress circuit None
Other output protection None
Isolation method
Relay insulation
Dielectric strength
2300V AC for 1 min. (between entire output terminals and FG)
Insulation resistance
10M or more with a 500 V DC megger (between entire output terminals and FG)

Output
power
condition

Item

Output protection
method

Output circuit
characteristic

Rated voltage
Max. allowable voltage
Output method
Rated current

Transistor output (sink output, source output)


Item

Specification

Output power
condition

Specification
AC Power Type
DC Power Type
Rated voltage
100 to 240V AC
24V DC
Voltage tolerance 85 to 264V AC
19 to 30V DC
Rated frequency
50/60Hz

Frequency tolerance range 47 to 63Hz

Allowable instantaneous
1 cycle or less
5 ms or less
Waveform distortion rate 5% or less

Waveform ripple ratio


3-phase full-wave rectified waveform: 5% or less
Rated output voltage
24V DC10% (21.6 to 26.4V DC)
(Output voltage variation)
24V DC externally Basic unit 20 points: 200mA

supplied current
Basic unit 30/40 points: 250mA
Basic unit 60 points: 300mA
Expansion unit 60 points: 300mA
Power consumption Basic unit 20 points: 35VA or less
Basic unit 20 points: 10W or less
Basic unit 30/40 points: 60VA or less Basic unit 30/40 points: 25W or less
Basic unit 60 points: 75VA or less
Basic unit 60 points: 3W or less
Expansion unit 60 points: 75VA or less
Leak current
0.25mA or less
0.25mA or less
Rush current
40 Ao-p or less, 10ms or less
150 Ao-p or less, 10ms or less
Dielectric strength 2830 Vrms AC for 1 min. entire 510 Vrms AC for 1 min. entire
external terminals and ground external terminals and ground
Isolation method
Transducer isolation
Insulation resistance 10M or more with a 500 V DC megger

24V DC
5 to 24V DC
19 to 30V DC (including ripple)
4.5 to 26.4V DC
0.5A/1 point
0.8A/4 points common
1.6A/8 points common
0.1A/1 point
1.5V or less (0.5A)
1.5V or less (0.1A)
1ms or less
5s or less
0.1mA or less
2A max. (10ms)
1800 times/hour (inductive load)
None
Zener diode
None
Terminal board M3 fastened by screws
Photocoupler isolation
1500V AC for 1 min. (between entire output terminals and FG)
10M or more with a 500V DC megger
(between entire output terminals and FG)

Output circuit characteristics

Item

Output Specifications

Rated voltage Normal output


High-speed output * 1
Voltage tolerance Normal output
difference
High-speed output * 1
Rated current Normal output

High-speed output * 1
Output voltage Normal output
drop
High-speed output * 1
Output delay Normal output
time* 2
High-speed output * 1
Leakage current at off
Surge current resistance
Max. switching frequency
Built-in fuse
Surge suppress circuit
Other output protection
External connection
Isolation method
Dielectric strength
Insulation resistance

Output
protection
method

Power Source Specifications

* 1 Bits 0 and 1 are enabled for high-speed output.


* 2 ON time/OFF time changes when output frequency is high. For details, refer to Pulse
Commands/Function Commands (FEH406) User's Manual.

Analog Unit Specifications

Digital value *1
Max. resolution
Overall accuracy
(full scale)
Sampling time
Input filtering time
Input delay time *2
External connection
Connection
Applicable wire size
Isolation method
Dielectric strength
Insulation resistance
External current
consumption (24V DC)
Rush current
Treatment of unused channel
Number of occupied words
Mass

Specification
NW0AX04-MR
4 channels
1M
250
Voltage input: 15 V
Current input: 30mA
0 to 5V
10 to 10V
20 to 20mA 0 to 20mA
1 to 5V
4 to 20mA
0 to 10V
0 to 16000 (DEC)
Voltage: 1.25mV
Current: 5A
0.1% or less (23C5C)
0.3% or less (0 to 55C), 1-5V range 0.4% or less (0 to 55C)
0.2% or less (0 to 55C), other ranges
0.27ms x (Number of conversion enabled channels + 1)
Approx. 200s (hard filter: time constant of primary delay)
Max. 1.5ms/4 points + scan time (ms)
Detachable terminal block: M3 screw, 20 poles
AWG#22-18 (Use shielded twisted pair cable.)
Photocoupler isolation (no isolation between channels)
500V AC for 1min. (between entire analog input terminals and FG (short-circuit current: 5mA)
10M or more with a 500V DC megger (between entire analog input terminals and FG)
24V DC (+10%, 15%), full-wave rectification
unavailable 100mA or less
5A or less
Basically short-circuited (between V+ and COM)
8 words (input: 6 words, output: 2 words)
Approx. 250g

*1 When the "10 to 10V" or "20 to 20mA" input range is used, the digital output range can
be expanded to "8,000 to 8,000" with the scaling function.
*2 For step response, input filtering time needs to be considered.
Note 1: The maximum deviation of noise is 1% of full scale.
Note 2: At shipment the range is set to "0 to 10V".

Analog Output Unit: NW0AY04-MR


Item
Type
Number of output channels
Output range
External load impedance
Digital value *1
Maximum resolution
Overall accuracy
(full scale)
Sampling time
Output delay time
Load short-circuit protection
External connection
Connection
Applicable wire size
Isolation method
Dielectric strength
Insulation resistance
External current
consumption (24V DC)
Rush current
Treatment of unused channel
Number of occupied words
Mass

Specification
NW0AY04-MR
4 channels
0 to 5V
0 to 10V 10 to 10V 0 to 20mA 4 to 20mA
1 to 5V
1k or more 2k or more 2k or more 500 or less
0 to 16000 (DEC)
Voltage: 1.25mV
Current: 5A
0.1% or less (23C5C)
0.3% or less (0 to 55C), 1-5V range 0.4% or less (0 to 55C)
0.2% or less (0 to 55C), other ranges
1.0ms or less/4 points
1.0ms or less/4 points + scan time (ms)
Provided

Detachable terminal block: M3 screw, 20 poles


AWG#22-18 (Use shielded twisted pair cable.)
Photocoupler isolation (no isolation between channels)
500V AC for 1 min. (between entire analog input terminals and FG (short-circuit current: 5mA)
10M or more with a 500V DC megger (between entire analog input terminals and FG)
200mA or less
240mA or less
24V DC (+10%, 15%), full-wave rectification unavailable
5A or less
Basically open
8 words (input: 2 words, output: 6 words)
Approx. 250g

Item
Type
Number of channels
Input impedance
Input tolerance
Input range

Input

Item
Type
Number of input channels
Input impedance
Input tolerance
Input range

Analog I/O Unit: NW0AW03-MR

Overall accuracy
(full scale)
Conversion rate *1
Input filtering time
Number of channels
Output range

Specification
NW0AW03-MR
2 channels
100k
Voltage input: 15 V
0 to 5V
1 to 5V
0 to 10V
1% or less (0 to 55C)

250
Current input: 30mA
0 to 20mA
4 to 20mA

8ms/2 channels
Approx. 2.2ms (hard filter: time constant of primary delay)
1
0 to 5V
0 to 20mA
1 to 5V
4 to 20mA
0 to 10V
External load impedance 2k or more
500 or more
Conversion rate *2 8ms/channel
Load short-circuit protection Provided

Overall accuracy 1% or less (0 to 55C)


(full scale)
Digital value
0 to 1000 (DEC)
Maximum resolution Voltage: 4mV
Current: 16A
External connection Detachable terminal block: M3 screw, 20 poles
Connection
Applicable wire size AWG#22-18 (Use shielded twisted pair cable.)
Isolation method
Photocoupler isolation (no isolation between channels)
Dielectric strength
500V AC for 1min. (between entire analog input terminals and FG (short-circuit current: 5mA)
Insulation resistance 10M or more with a 500V DC megger (between entire analog input terminals and FG)
External current
200mA or less
consumption (24V DC) 24V DC (+10%, 15%), full-wave rectification unavailable
Rush current
5A or less
Treatment of unused channel Input channel shall basically be short-circuited (between V+ and COM); output channel shall basically be open.
Number of occupied words 8 words (input: 4 words, output: 4 words)
Mass
Approx. 250g

Output

Analog Input Unit: NW0AX04-MR

*1 For step response, input filtering time needs to be considered.


*2 Can respond by 0 to 90%
Note 1: The maximum deviation of noise is 1% of full scale.
Note 2: At shipment the range is set as follows:
Analog input: 0 to 10V
Analog output: 0 to 10V

*1 When the "10 to 10V" output range is used, the digital input range can be expanded to
"8,000 to 8,000" with the scaling function.
Note 1: The maximum deviation of noise is 1% of full scale.
Note 2: At shipment the range is set to "0 to 10V".

11

Specifications

Thermocouple Input Module Specifications


NWOAX04-TC Specifications
Item
Types
Number of input channels
Accuracy
Cold contact compensation accuracy
Noise
Effects of external resistance
Resolution
Input filter
Sampling interval
Response time
Occupied words
Isolation method
Dielectric strength

External power supply


External current consumption
Inrush current
Used to the cable
Mass
External connections

Resistance Bulb Input Module Specifications


NWOAX04-PT Specifications

Specification
NW0AX04-TC
4 channels
0.3% or less (23C 5C)
0.7% or less (0 to 55C) *1
1C
0.7% or less (when the shielding compensation cable used)
Approx. 0.35V/
K, T: 0.2C, E, J, U, L: 0.1C
B, R, S, N, PL ll, W5Re, W26Re: 1C
Hardware filter (primary delay time constant): 50ms or less
Approx. 100ms or less / 4 channels
Approx. 100ms or less / 4 channels + Scanning interval (ms)
8 words (Input: 6 words, output: 2 words)
Between analog input terminals and FG: Isolated
Between analog input terminals and channels: Isolated
500V AC 1 minute
Between thermocouple input module terminals and FG
Between thermocouple input module terminals and channels
24V DC (+10 to -15%)
(Full wave rectification power supply cannot be used.)
24V DC: 150mA or less
24V DC: 5A or less
Shielding compensation cable
Approx. 250g
Detachable screw terminal bock (M3) 20 poles

* 1 Precision not assured for B0-399C.

Noise
Allowable resistance of
input wire (per wire)
Resolution
Input filter
Sampling interval
Response time
Occupied words
Isolation method

External power supply


External current consumption
Inrush current
Used to the cable
Mass
External connections

Types and Ranges of the Resistance Bulb Input Module


Types of
thermocouple
input

Celsius (C)
Setting Measuring
Resolution
No.
temperature range data

Fahrenheit (F)
Setting Measuring
Resolution
No.
temperature range data

PT

00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19

20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39

Celsius (C)
Fahrenheit (F)
Setting Measuring
Resolution Setting Measuring
Resolution
temperature range data
temperature range data
No.
No.

00
01
02
03
04
B
05
R
06
S
07
E
08
09
10
J
11
12
13
14
T
15
16
N
17
U
18
19
20
L
21
22
23
24
PL II
25
W5Re, 26
W26Re

12

0-1300
0-500
0-800
0.0-500.0
0.0-800.0
0-1800
0-1700
0-1700
0-400
0-700
0.0-700.0
0-500
0-800
0.0-500.0
0.0-800.0
-50-400
-50.0-400.0
0-1300
0-400
0-600
0.0-600.0
0-400
0-900
0.0-400.0
0.0-900.0
0-1200
0-2300

0.1
1
1
1
1
0.1
1
0.1
1
0.1
1
1
0.1
1
0.1
1
1

27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53

32-2372
32-932
32-1472
32.0-932.0
32.0-1472.0
32-3272
32-3092
32-3092
32-752
32-1292
32.0-1292.0
32-932
32-1472
32.0-932.0
32.0-1472.0
-58-752
-58.0-752.0
32-2372
32-752
32-1112
32.0-1112.0
32-752
32-1652
32.0-752.0
32.0-1652.0
32-2192
32-4172

0.1
JPT

1
1
1
1
0.1
1
0.1
1
0.1
1
1
0.1
1

0.1C
Hardware filter (primary delay time constant): Approx. 200ms or less
500ms/ 4 channels
500ms or less / 4 channels + Scanning interval (ms)
8 words (Input: 6 words, output: 2 words)
Between analog input terminals and FG: Isolated
Between analog input terminals and channels: Unisolated
500V AC 1 minute
Between thermocouple input module terminals and FG
24V DC (+10 to -15%)
(Full wave rectification power supply cannot be used.)
24V DC: 150mA or less
24V DC: 5A or less
Shielding compensation cable
Approx. 250g
Detachable screw terminal bock (M3) 20 poles

Dielectric strength

Types and Ranges of the Thermocouple Input Module


Types of
thermocouple
input
K

Specification
NW0AX04-PT
4 channels
0.3% or less (23C 5C)
0.7% or less (0 to 55C)
0.7% or less (when the shielding compensation cable used)
10 or less

Item
Types
Number of input channels
Accuracy

0-200
-50-150
0-400
-200-200
-200-600
0.0-200.0
-50.0-150.0
0.0-400.0
-200.0-200.0
-200.0-600.0
0-200
-50-150
0-400
-200-200
-200-500
0.0-200.0
-50.0-150.0
0.0-400.0
-200.0-200.0
-200.0-500.0

0.1

0.1

32-392
-58-302
32-752
-328-392
-328-1112
32.0-392.0
-58.0-302.0
32.0-752.0
-328.0-392.0
-328.0-1112.0
32-392
-58-302
32-752
-328-392
-328-932
32.0-392.0
-58.0-302.0
32.0-752.0
-328.0-392.0
-328.0-932.0

0.1

0.1

Characteristic Diagrams (Example)


(Thermocouple)

(Resistance Bulb)

Conversion value (INT type)

Conversion value (INT type)

8400
8000

4200
4000
Temperature input
practical range

0.1
-400

1
1

-400
K, J : 0.0-800.0C

8000 8400

Temperature
input value (C)

Temperature input
practical range
-200.0
-2000

Temperature
400.0 420.0 input value (C)

PT, JPT : 0.0-400.0C

Communication Adapter Specifications

Transmission specifications

External interface

Item
Transmission standard
Port
Transmission mode
Synchronization mode
Transmission rate
Transmission distance
Number of units connected
Connection method
Cable
Transmission procedure

Specification
RS-485
1 channel
Half-duplex transmission
Start-stop transmission
1,200/2,400/4,800/9,600/19,200/38,400 bps
1km or less (with a transmission rate of 19,200 bps or less)
1:31 (max.)
European type removable terminal board (5 pins)
Twisted pair cable with shield
Nonsequenced transmission / command set type
transmission
Transmission control code Binary (without code conversion) or ASCII (with code
conversion), EBCDIC (with code conversion)
Error control Hardware Vertical parity (parity bit), framing, overrun error
Software Horizontal parity (BCC)
Bit send-out order
Sent from LSB to MSB
Data length that can be sent/received Max. 512 bytes (depends on mode)
at a time (seen from SPB)
Start code
None, data with a length of 1 to 5 bytes
End code
Data with a length of 1 to 5 bytes
Character configuration Start bit: 1 bit
Data bit : 7 or 8 bits
Parity bit: None, odd, even
Stop bit: 1 or 2 bits

Item
Transmission standard
Port
Transmission mode
Synchronization mode
Transmission rate
Transmission distance
Number of units connected
Connection method
Transmission procedure

External interface

<General-purpose communication, basic specifications>

RS-232C Adapter: NW0LA-RS2

Transmission specifications

RS-485 Adapter: NW0LA-RS4

Specification
RS-232C
1 channel
Half-duplex transmission
Start-stop transmission
1,200/2,400/4,800/9,600/19,200/38,400 bps *1
15m or less
1: 1
D-Sub 9 pins, male
Nonsequenced transmission / command set type
transmission
Transmission control code Binary (without code conversion) or ASCII (with code
conversion), EBCDIC (with code conversion)
Error control Hardware Vertical parity (parity bit), framing, overrun error
output type Software Horizontal parity (BCC)
Bit send-out order
Sent from LSB to MSB
Data length that can be sent/received Max. 512 bytes (depends on mode)
at a time (seen from SPB)
Start code
None, data with a length of 1 to 5 bytes
End code
Data with a length of 1 to 5 bytes
Character configuration Start bit: 1 bit
Data bit: 7 or 8 bits
Parity bit: None, odd, even
Stop bit: 1 or 2 bits

*1 When using transmission rate 38400 bps, mount a ferrite core to the communication
cable. For details, refer to RS-232C/RS-485 Communication Adapter (FEH405) Users
Manual.

<Simplified CPU link, basic specifications>


Item

Link area
Communication form
Refresh time

Communication between link

Communication specifications

Number of units connected


Link capacity
(1 station)

Others

System specifications

Connection target

Communication access mode


Transmission level
Transmission mode
Synchronization mode
Transmission rate
Transmission distance
Connection method
Cable
Master station
Configuration
registration
Self diagnosis
Insertion and removal
of active wire

Specification
SPB series basic unit
FLEX-PC NB series NP link micro,
only with data link function
16 units max.
N mode: Variable: selected to 2, 4, 8, 16, or 32 words
(through parameter setting)
SX mode: Fixed to 8 words
(when operating mode 21H is selected)
Data register (D) area is used. (D1E00 to D1FFF)
Bus
130ms or less/16 stations, 32 words for each station
(When the SX mode is selected, with a scan time of 5ms or less),
excluding the case when the loader network function is used
Polling/selecting mode
Conforms to EIA standard, RS-485.
Half-duplex transmission
Start-stop transmission
115,200 bps (when the SX mode is selected)
19,200 bps (when the NB compatible mode is selected)
500m or less
European type removable terminal board (5 pins)
Twisted pair cable with shield
Fixed to station 0 (station number set by parameters)
Whether configuration is registered or not can be selected.
(Registered to station 0 only when the SX mode is selected)
Communication monitoring (omitted data bits,addition)
Insertion and removal of link active wire are possible.

13

External Connection Diagrams

External Connection Diagrams


20-points Basic Unit

Internal
power
circuit

+
24V COM

A
B

AC
-N

Ry

Ry

Ry

Ry

*1
L

*1

*1

4
5

8
7

L
L

85 to 264V AC
*4

AC
-N

AC
-L

Ry

FG COM

*1

*1

Ry

Ry

Ry

COM
2

*1

L
L

*1

6
COM

85 to 264V AC
*4

Ry

Ry

Ry

10

14

12

AC
-N

AC
-L

L
L

Ry

Ry

*1

L
L

*1
L

*1
L

*1

17

E
D

COM

*1

L
L

Ry

NC

*1

COM

Ry

Ry

NC

*1

Ry

FG COM COM COM COM COM

85 to 264V AC
*4

*1 Power source

16

13 15

11

*3
Ry

L
L

2
1

Internal
power
circuit

L
L

0V COM

Ry

60-points Basic Unit

*1 Power source

16-points Output Expansion Unit

16-points Input Expansion Unit


+

24V DC
OUTPUT

Ry

5
4

L
L

*1 Power source

+
24V COM

C
B

*3

Ry

FG COM COM COM COM COM

*1

2
1

Internal
power
circuit

*3
Ry

0V COM

2
1

0V COM

*2

+
24V COM

AC
-L

24V DC
OUTPUT

*2

*2

40-points Basic Unit

24V DC
OUTPUT

24V DC
OUTPUT

30-points Basic Unit

*1

*2

+
24V COM

0V COM

2
1

6
5

8
7

A
9

E
D

10
F

12
11

14

18

16

13 15

1C 1E

1A
19

17

1B 1D

20

22

1F

21

COM
0

23

COM

COM
7

L
L

*1

2 COM

Ry

Ry

Ry

Ry

Ry

Ry

*3

Internal
power
circuit

*3

AC
-N

AC
-L

Ry

Ry

Ry

Ry

*1
L

*1
L

L
L

L
L

NC
7

COM

*1

NC

L
L

*1

Ry

L
L

11

*1

L
L

L
L

14

L
L

85 to 264V AC
*4

17

L
L

L
L

32-points I/O Expansion Unit

COM COM
7

COM COM

2
1

6
5

8
7

E
D

Ry

COM
F

L
L

Ry

*1

Ry

Ry

*1
L

4
COM

Ry

Ry

A COM

L
L

*1

AC
-L

*1

L
L

Ry

Ry

AC
-N

*1

2
1

6
5

Ry

*1

Ry

Ry

6 COM

*1

L
L

COM
3

L
L

Note: 1 The figure above indicates external connection of the AC power supply/Ry output type.
*2 The DC power supply is not applicable
*3 The transistor type connection is shown below.
to service power supply.

FG COM

*1 Power source

Tr sink

0V COM COM COM

Ry

L
L

Ry

Ry

E
D

10
F

14

12

18

16

13 15

11

1C

1A
19

17

L
L

COM D

A
9

L
L

Ry

10 12

*1

L
L

L
L

Ry

1E
1D

1B

1F

15

*1

85 to 264V AC

1B

L
L

L
L

*1 Power source

FG
24V+

+
L

COM

L
L

*1

*4 The terminal arrangement of the DC power supply is shown below.

18 1A

17 COM 19

L
L

Ry

Ry

16 NC

14

NC

13 COM

E COM 11

*1

Ry

Ry

0V
Y
COM

Tr source

Internal
power
circuit

*1 Power source

14

*1

60-points I/O Expansion Unit

+
24V COM COM COM

Ry

COM

C
COM

Ry

*1

Ry

*1

A
9

*3

COM

6
5

Ry

*1

*2

*3

COM
7

COM

Ry

COM

6
5

24V DC
OUTPUT

+
4

3
2

Ry

*1 Power source

+
1
0

3
2 COM

Ry

*1 Power source

16-points I/O Expansion Unit

COM

COM

16

13 COM 15

*1

Ry

Ry

Ry

12 NC

10

NC

F COM

B COM

L
L

Ry

Ry

*1

Ry

Ry

*1

FG COM COM COM COM COM

*1

Ry

Ry

Ry

Note: 2 The output terminal


can be used as a pulse output terminal in the case of transistor output.
Note: 3 For external connection of communication adapters, refer to RS-232C/RS-485 Communication Adapter (FEH405) Users Manual.
Note: 4 For external connection of analog unit, refer to Analog Unit (FEH407) User's Manual.

+
24V DC

Control Functions
Enabling various controls with standard functions
Pulse Train Output Function

High-speed Counter Function

With basic units of the Tr output type, the terminal for output bits 0
and 1 can be used not only as a usual external output but as pulse
output with up to 100kHz.
The pulse output can be operated with dedicated instructions, allowing easy control based on pulse train output and pulse width
modulation.

Pulse Train Output

Positioning control with servo motors and stepping motors is possible without specialized units, based on the pulse train output instruction, return-to-origin instruction, relative positioning instruction,
absolute positioning instruction, and other positioning instructions.

Pulse train

ON/OFF

The SPB has a built-in high-speed counter which can count pulses
at a maximum rate of 100kHz for a single phase or 50kHz for two
phases.

Specification
Item

Specification
1-phase
2-phasee
Method
Preset increment counter Preset increment/decrement counter
Count input signal 1-phase increment signal x 2 ch 90-deg.phase difference 2phase signal x 1 ch Counting pulse + Direction input x 1ch
Control input Reset
Counting speed Max. 100kHz
Max. 50kHz
Counting range Unsigned binary 16 bits Signed binary 32 bits
Multiplication
x1, x2
x2, x4
x1
Reset
Soft reset by control input and command register
Preset
Soft reset by control command register

<Sample Application for Packing Machine>


Encoder

The encoder output pulse can be


input to the high-speed counter to
control such a high-speed
operation.

<Operation Patterns>
Return to origin

Relative positioning
Absolute positioning

Frequency

Melting
signal

Print
signal

Frequency

Start

Origin signal ON Origin signal OFF

Cutting
signal

Current position

Target position

Number of output pulses


Rotational direction
ON: Forward OFF: Reverse
signal

Constant Scan Function


For the control of a machine which outputs at constant intervals,
constant scan can be set to suppress the irregular I/O operating
times. Constant scan can be set in the range from 1 to 255 in units
of 1 msec.

Pulse Width Modulation


The pulse width modulation instruction allows pulse output with
variable pulse ON width and pulse interval with the following specifications, enabling light control.

Program execution
Set time

Wait time
Set time

Time is extended for the excess.


Set time

Set time

ON
OFF

Pulse ON width
Pulse interval

Interrupt Input Function


The SPB has an interrupt input function for interrupting normal
program operation to initiate an interrupt program. It executes the
interrupt program at the rise of the input from X0 to X3.

Pulse Catch Function


Regardless of the input filter time setting, the pulse catch function
allows the SPB to detect a pulse (min. 50sec.) shorter than the
scan time and output it at the following scan. It can be used for
detecting an object which moves at high speed.

I/O

Program execution
Scan

Scan

Scan

Analog Timer Function


The SPB has two analog timers
as standard. Each timer value is
converted to a digital value of 0
to 255 in the SPB and stored in
the internal memories.

External signal
Internal relay

Analog Timer

15

Programming Languages
One type of hardware applicable to two languages
SX mode: Applicable to MICREX-SX (IEC61131-3 compatible language)
N mode: Applicable to FLEX-PC N (IEC61131-3 incompatible language)

Programming support tool D300win


SX mode programming support tool NP4H-SEDBV3
IEC61131-3 compatible programming enabled

Compatible with the IEC 61131-3 international


standard
The use of a programming language system in compliance with
international standards allows the user to produce programs that
are understandable worldwide.
The MICREX-SX Series SPB is a programmable controller compliant with the above standards.

Replacing system software


The SPB system software is in N mode when shipping from the
factory.
To use it in SX mode, download the SX mode system software
using the system software utility for D300win V3.1 or up.

N mode programming

N Series
PC loader
Handy loader

[Shipped in N mode]

System software
update

Use of program components


Reuse of components improves the programming efficiency.
Programming with labels (variables)
Use of components through function blocks (FBs)

Language set
Five programming languages specified in IEC standards are all
supported.
Optimum program expressions for the control contents can be
used in combination.
IL language: Reducing application size
ST language: High-level language (IF, THEN, ELSE, etc.)
LD language: Replacing relay boxes
FBD language: Data processing system
SFC element: Application structure description

Ample instruction words


Sufficient instruction words, as many as 202 types, enable to
write any kind of programs at will.

16

D300win V3.1 or up
SPB System Software Utility

[N mode SX mode]

SX mode programming

D300win V3.1 or up
[Used in SX mode]

Notes:
1. The SPB handy loader is disabled in SX mode. It is enabled only in N mode.
2. SX mode is enabled for SPB main unit version of V 10 or up.

**

Simulation function

Use of FBs for user-original circuits

Use of the simulation-dedicated software PLC function built in


D300win enables logical testing of the program without using the
actual unit.
Simulation is carried out for the program written in the programming
language compliant with IEC61131-3. Because it enables monitoring
or forced ON/OFF of an arbitrary signal, it can be expected to raise
the programming and/or debugging efficiency for the SX Series.

Formalized programs or circuits used frequently can be easily reused by creating FBs. For creating user FBs, the language applicable to IEC61131-3 supported by D300win is available and no special languages are necessary. The function placed in a library form
can be used alone efficiently without considering about debugging.
In addition, creating an FB for individual control blocks facilitates
circuit standardization and structuring.

Operation environment
Item
Hardware
CPU
Hard disk

Specification
IBM-PC/AT compatible
Intel Pentium 233MHz or higher (when WindowsXP used, 350MHz or higher recommended.)
Free space of 220M bytes or more
For D300win system software: 100M bytes or more
For standard expansion FB package: 120M bytes or more
CD-ROM unit
1 unit (x 4 speed or faster), media: ISO 9660 format
Memory capacity
64M bytes or more (128M bytes or more recommended)
Keyboard
101 keyboard (when japaneas OS used, 106 keyboard)
Mouse
USB mouse, bus mouse, or PS2 mouse
Indicator
800 x 600-dots resolution or higher (1024 x 768-dots resolution or higher recommended)
Communication interface RS-232C 9,600bps to 57,600k bps (default setting according to the resource model selection)
OS
WindowsNT4.0(SP6 or higher), 2000, XP
Portability
Depends on a commercial mobile personal computer.
Environmental durability
Depends on environmental condition of a commercial personal computer.

System Configuration

Personal computer
SPB
RS-232C

Support tool connection cable: NW0H-CA3


+
RS-232C/RS-422 signal converter: NW0H-CNV
D300win

17

Programming Languages

Loader Software for Personal Computer


N mode programming support tool SX-Programmer Standard: NP4H-SWN
Enables same programming as FLEX-PC N Series

Free-form circuit layout


Ladder diagram ruled lines and instruction symbols can be
optionally arranged by a simple operation.
Ruled line write/delete
Ruled lines can be written by Ctrl+Arrow keys or deleted by
Ctrl+Alt+Arrow keys.
Instruction symbol write
An instruction symbol can be optionally arranged by clicking on
the corresponding icon or function key.

Improved program edit and debugging workability


Information required for program edit/debugging can be displayed
in a single window with the divided display feature showing a
program and a datasheet or the filter function* for indicating only
the circuit which uses a specific address or instruction.
<2-divided display>

<Filter function>

Filter display of a circuit


containing the specified
address.

Support of the full-keyboard facilitates expeditious program editing and debugging in the field.

Display/edit in 2 languages of ladder language and instruction words (mnemonic)


A circuit or the entire program can be displayed/edited in mnemonic (instruction words).
<Partial display/edit window>

18

<Overall display/edit window>

Operation environments
Item

System Configurations

Specification

Hardware

IBM-PC/AT compatible

CPU

Intel Pentium 100MHz or higher

Hard disk

Free space of 10M bytes or more (100M bytes or more recommended.)

CD-ROM unit

1 unit (x 4 speed or faster), media: ISO 9660 format

Memory capacity

32M bytes or more

Keyboard

101 keyboard (when Japanese OS used, 106 keyboard)

Mouse

USB mouse, series mouse, bus mouse, or PS2 mouse

Indicator

800 x 600-dots resolution or higher

Support tool connection cable:


NW0H-CA3
+
RS-232C/RS-422 signal converter:
NW0H-CNV
RS-232C

(1024 x 768-dots resolution or higher recommended)


Communication RS-232C 9,600bps to 57,600k bps
interface
(Transmission speed is set automatically by the model for resource.)
OS

Windows95,98,Me,NT4.0(SP6 or higher), 2000, XP


Depends on a commercial mobile personal computer.

Portability

SPB
Personal computer

Depends on environmental condition of a commercial

NP4H-SWN

personal computer.

Handy Loader
A "palm-top" handy loader with maintenance function: NW0H-NE (English), NW0H-N (Japanese)

Palm size convenient for portable use


Program edit and data monitor can be performed in the compact
unit 90(W)x148(H)x38(D).

Flash memory built in for user program storage


Two user programs with up to 32K steps can be stored in the internal memory of the handy loader. Stored programs can be copied to
multiple basic units. The program in a basic unit can be compared
with the program in the handy loader, allowing easy secure copy
operation.
* Note that user data is not stored.
The SPB handy loader is disabled in SX mode. It is enabled only in N mode.

1 Store

Basic Specifications
2 Copy
Flash
Memory

Item

Specification

Display section

LCD 16 characters x 2 lines with backlight

Keyboard section

40 embossed sheet keys with buzzer

User program memory

Built-in flash memory

Processor connection

RS-422

Handy Loader

3 Verification

19

Online Adapter
Facilitating configuration of remote maintenance system
Online Adapter: FOA-ALFA2
Features

Specifications

This module allows easy remote maintenance system


configuration simply by connecting the online adapter to the
loader port without changing any program on the PLC
(MICREX-SX SPH/SPB) side. The SPB is based on SX mode.
 Bi-directional communication between the master station
(personal computer) and slave station (SPH)
 Diverse functions
Failure monitor function Data accumulation function
Integrated time monitor function
Communication functions of the each PLCs
 Calendar functions (year, month, day, hour, minute, second),
and data backup functions (data memory, calendar IC
memory) are provided too.

General specifications
Item
Physical
environment

Mechanical
operating
condition
Electrical
operating
condition

Operating ambient
temperature
Storage temperature
Relative humidity
Contamination
Corrosion resistance
Operating altitude/air
pressure
Resistance to
vibration
Resistance to shock
Resistance to noise
Resistance to
electrostatic
discharge
Resistance to
radiation
electromagnetic field

Cooling system
Insulation
Insulation resistance
characteristic
Power supply method
Current consumption
Mass
Calendar accuracy
Battery type/operating life

Specification
0 to 55C (without condensation)
-20 to 70C (without condensation)
20 to -90%RH (without condensation)
Contamination level 2
No corrosive gas is present, no organic solvent adhesion
Altitude of 2000m or less (air pressure of 70kPa or higher
during transportation)
One amplitude: 0.15mm, constant acceleration: 9.8m/s2, 2
hours for each direction, 6 hours total
Peak acceleration: 294m/s2, 3 times for each direction
Noise simulator method, rise time of 1ns, pulse width of 1s,
1kV
Contact discharge method: 6kV, air discharge method: 8kV

10V/m (80 to 1000MHz)

Natural cooling
10M or more (between connectors and ground) with a 500V DC
megger
Supplies 24V DC from PC or 12V DC from AC adapter.
24V: 60mA or less
12V: 120mA or less
Approx. 320g
90 seconds/month (25C, conduction)
Lithium primary battery 3.6V
NP8P-BT (Fuji Electric FA Components & Systems Co., Ltd.)/
5 years (ambient temperature of 25C)

Note: For operating environment, take into consideration the specifications of the
communication devices used.
* Use the AC adapter only at the time of initial setup data transmission. Do not use it for
connection with SPH/SPB (SX mode).

Functional specifications
Mode
Online adapter mode
Loader mode
Remote mode

Online Adapter

Initial setup mode


Memory clear mode

Contents
Execution mode of various monitor functions
Monitors SPH/SPB (SX mode) programming monitor locally.
Monitors SPH/SPB (SX mode) programming monitor from a
remote site.
Writes setup data necessary for various monitor functions
using the initial setup loader.
Backup memory initialization (clear) mode

System Configurations
Communication
network

Online adapter
FOA-ALFA2
Specialized connection
cable (option)
NW0H-CA3

Communication
device

Performs various monitor functions and


communication setup using the initial
setup loader (FOA-LOADER2-CD).

Initial setup loader (Model: FOA-LOADER2-CD)


<Japanese version>
Creates initial setup data (each function setup).
Sets the failure monitor, data accumulation, integrated time
monitor functions and registers AT commands for
communication.
Writes the initial setup data to the online adapter.
Reads the initial setup data from the online adapter.

Master Station Monitoring Software


(Model: FOA-CENTER2-CD)
<Japanese version>
Slave station monitor function (reception of notification from slave
station)
Failure monitor function Data accumulation function
Integrated time monitor function

20

Communication
device

Performs remote monitor, e-mail


sending, and data monitoring using
the master station monitoring software
(FOA-CENTER2-CD).

Access from the master monitor software (personal computer)


to slave station.
Reads data accumulated in the online adapter.
Automatically collects data by time specification (with circuit
connection each time).
Updates the initial setup data from a remote site. (Remote
update function)
Uses the personal computer loader software from a remote
site.
Other functions
Saves receive data as CSV files.
Monitors accumulated data in bar graph form.
Upon reception of failure information, automatically transfers
the failure information to E-mail-based mobile tool through
the internet using the online adapter.

Dimensions

[mm]

Basic Unit / Expansion Unit

Communication Adapter
RS-232C Adapter: NW0LA-RS2

81

2-4.5 (for M4 screw)


SND
RCV

80

90

90

*1

Approx. 50

40

RS-232C

*1

(51.5)

30
40
48

W1
W2

67

RS-485 Adapter: NW0LA-RS4


2-4.5 (for M4 screw)

20-point basic unit

80

70

30-point basic unit

110

100

40-point basic unit

140

130

60-point basic unit

180

170

16-point expansion unit

64

54

32-point expansion unit

110

100

60-point expansion unit

180

170

RUN

SDA
SDB

80

W1

90

W2

RDA
RDB
SG

Approx. 50

RS-485

(17.5)

30
40
48

Note: The mounting hole of a basic unit of 60 point type is on four corners.
Other units has not the mounting hole on *1 part.

Analog Unit

8
67

Handy Loader

Analog Input Unit:


NW0AX04-MR
Analog Output Unit:
NW0AY04-MR
Analog I/O Unit:
NW0AW03-MR
Thermocouple Input Module: NWOAX04-TC
Resistance Bulb Input Module: NWOAX04-PT

English:

NW0H-NE

Japanese: NW0H-N
8

38

90

-MR

28
48

INS

WR

87

Note: When analog unit and basic unit are installed and connected together, the
distance between them must be approx. 10 to 20 mm.

DEL

LD
X

AND
M

OR
L

LDI
Y

ANI
S

ORI
T

TEST

AUX

OUT ANB ORB


C
D
E

SET
8

PLS
9

INV
B

RST
4

PLF MCR RET


5
6
7

MC
A

MNT

HELP CLR

148

RD

NW0A

For ratings see instruction manual

Analog Unit

82

90

2-4.5 (for M4 screw)

FNC
P/I

SP
STEP

K/H
-

NOP MPS MRD MPP END


0
1
2
3

GO

82

21

Ordering Informations
Standards

Certificated

Under planing

---

No planing

Exceptions

Basic Unit
Products names
20-points basic unit

Types

Specifications

(= Ordering codes)

Power specifications

Input specifications

Output specifications

Standards

NW0P20R-31

100 to 240V AC

24V DC 12 points

Ry 8 points

NW0P20T-31

Ry 8 points
Tr sink 8 points

NW0P20U-34
NW0P30R-31

Tr source 8 points
100 to 240V AC

24V DC 16 points

NW0P30T-31

Tr source 14 points
24V DC

Ry 14 points

NW0P30T-34

Tr sink 14 points

NW0P30U-34
40-points basic unit

NW0P40R-31

Tr source 14 points
100 to 240V AC

24V DC 24 points

Ry 16 points

NW0P40T-31

Tr sink 16 points

NW0P40U-31

Tr source 16 points

NW0P40R-31C

Ry 16 points

NW0P40T-31C

Tr sink 16 points

NW0P40U-31C
NW0P40R-34

Tr source 16 points
24V DC

Ry 16 points

NW0P40T-34

Tr sink 16 points

NW0P40U-34

Tr source 16 points

NW0P40R-34C

Ry 16 points

NW0P40T-34C

Tr sink 16 points

NW0P40U-34C
60-points basic unit

Ry 14 points
Tr sink 14 points

NW0P30U-31
NW0P30R-34

NW0P60R-31

Tr source 16 points
100 to 240V AC

24V DC 36 points

Ry 24 points

NW0P60T-31

Tr sink 24 points

NW0P60U-31

Tr source 24 points

NW0P60R-31C

Ry 24 points

NW0P60T-31C

Tr sink 24 points

NW0P60U-31C
NW0P60R-34

LR

Tr source 8 points
24V DC

NW0P20T-34
30-points basic unit

UL/cUL

Tr sink 8 points

NW0P20U-31
NW0P20R-34

CE

Tr source 24 points
24V DC

Ry 24 points

NW0P60T-34

Tr sink 24 points

NW0P60U-34

Tr source 24 points

NW0P60R-34C

Ry 24 points

NW0P60T-34C

Tr sink 24 points

NW0P60U-34C

Tr source 24 points

Note: Pulse train output and PWM output are not available for relay output.

Expansion Unit
Digital I/O Unit
Types

Specifications

(= Ordering codes)

Power specifications

Input specifications

Output specifications

16-points

NW0E16X

No power sourc

24V DC 16 points

expansion unit *1

NW0E16R-0

Ry 16 points

Products names

Standards

Tr sink 16 points

NW0E16T-0

Tr source 16 points

NW0E16U-0
NW0E16R-3

24V DC 8 points

Tr source 8 points

NW0E16U-3
32-points

NW0E32R-3

expansion unit *1

NW0E32T-3

24V DC 16 points

NW0E60R-31

expansion unit *1
*1 50mm expansion cable is supplied as accessory.

22

Ry 16 points
Tr sink 16 points
Tr source 16 points

NW0E32U-3
60-points

Ry 8 points
Tr sink 8 points

NW0E16T-3

Prpvided power sourc

24V DC 32 points

Ry 28 points

CE

UL/cUL

LR

Analog Unit
Products names

Types

Specifications

Standards

(= Ordering codes)

CE

Analog Input Unit

NW0AX04-MR

Multi-range input: 4ch, Resolution: 14 bits (voltage / current)

Analog Output Unit

NW0AY04-MR

Multi-range output: 4ch, Resolution: 14 bits (voltage / current)

Analog I/O Unit

NW0AW03-MR

Multi-range input: 2ch, Multi-range output: 1ch, Resolution: 10 bits (voltage / current)

Thermocouple Input Module

NW0AX04-TC

Input: 4ch

Resistance Bulb Input Module

NW0AX04-PT

Input: 4ch

UL/cUL

LR

Communication Adapter
Products names

Types

Specifications

Standards

(= Ordering codes)

CE

RS-232C adapter

NW0LA-RS2

RS-232C 1 channel (general-purpose communication mode, loader interface mode)

RS-485 adapter

NW0LA-RS4

RS-485 1 channel (general-purpose communication mode, loader interface mode, simplified CPU link mode)

Types

Specifications

UL/cUL

LR

Option
Products names

Standards
CE

UL/cUL

LR

Memory card

NW8PMF-8

Flash ROM (for 40/60-points basic unit)

---

---

---

Battery

NW8P-BT

Lithium battery for backup

---

---

---

(= Ordering codes)

Programming Loader
Products names

Types

Standards

Specifications

(= Ordering codes)
SX-Programmer

NP4H-SWN

Standard
Programming support

CE

UL/cUL

LR

---

---

---

---

---

---

Windows NT4.0 Workstation (Service Pack 6 or later)/2000, XP compatible


NP4H-SEDBV3

tool D300win
Handy loader

For N mode, CD-ROM, English/Japanese edition, English/Japanese manual (PDF)


For SX mode, CD-ROM, English/Japanese edition, English/Japanese manual (PDF)
Windows NT4.0 Workstation (Service Pack 6 or later)/2000, XP compatible, Version 3

NW0H-NE

English type: 1000mm loader cable x1: supplied as accessory (Type: NB-EC0100)

NW0H-N

Japanese type: 1000mm loader cable x1: supplied as accessory (Type: NB-EC0100)

Loader Option
Products names

Types

Specifications

Standards

(= Ordering codes)
PC connection adapter

NW0H-CNV

CE

UL/cUL

LR

---

---

---

---

---

---

(combined with the optional loader cable: NW0H-CA3)

(Signal converter)
Loader cable

For personal computer loader-basic unit connection, RS-232C/RS-422 conversion,

NW0H-CA3

Connection cable for personal computer loader-basic unit: 3000 mm straight cable
(combined with the optional PC connection adapter: NW0H-CNV)

Online Adapter
Standards

Products names

Types

Ordering codes

Specifications

Online adapter

FOA-ALFA2

NP1L-FOA

Adapted to MICREX-SX SPH/SPB (SX mode ) series.

Initial setup loader software


<Japanese version>

FOA-LOADER2-CD NL4N-WNOL

CD-ROM, (Adapted to SPH versions: LV3.00.25 or higher)

---

---

---

Master station monitoring software


<Japanese version>

FOA-CENTER2-CD

CD-ROM, (Adapted to SPH versions: LV3.00.24 or higher)

---

---

---

CE

NL4N-WNOC

UL/cUL

LR

Microsoft, Windows, Windows NT are trademarks of Microsoft Corporation in the USA and other countries.
Pentium is trademarks or registered trademarks of Intel Corporation.
And other companies name, products name in this catalog, are trademarks or registered trademarks of the each companies.

23

Safety Considerations
For safe operation, before using the product read the instruction manual or user manual that comes with the
product carefully or consult the Fuji sales representative from which you purchased the product.
Some of the products listed in this catalog may have limits on their use or location or may require periodic
inspections. Call Fujis sales representative for further information.
For safe operation, wiring should be conducted only by qualified engineers who have sufficient technical
knowledge about electrical work or wiring.
Appearance and specifications are subject to change without prior notice for the purpose of product improvement.

Fuji Electric FA Components & Systems Co., Ltd.


Gate City Ohsaki, East Tower
11-2, Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032, Japan
Phone:
Fax:
URL

+81-3-5435-7135~8
+81-3-5435-7456~9
http://www.fujielectric.co.jp/fcs/eng/

Materials covered in this document are subject to revision due to the modification of the product.

2004-9 (I04c/D01) FIS