Kohler Service Manual-TP6196

Download as pdf or txt
Download as pdf or txt
You are on page 1of 132
At a glance
Powered by AI
The document appears to provide specifications and maintenance instructions for generator sets and their components.

The main sections covered include specifications, scheduled maintenance, and an appendix with part numbers and dimensions.

Routine maintenance recommended includes checking fluid levels, changing engine oil, inspecting air filters, servicing the cooling and exhaust systems, and storage procedures.

Service

Residential/Commercial Generator Sets

Models:

8.5RES
12RES
12RESL
12RESM1
12RESNT
12TRES
Controllers:
ADC 2100
ADC-RES
DC 2200
DC-RET

TP-6196 10/09a

Table of Contents
Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
List of Related Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Service Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Section 1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Controller Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Engine Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Engine Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5 Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6 Alternator Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7 Service Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13
13
13
13
14
14
15
16

Section 2 Scheduled Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


2.1 Service Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Lubrication System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1
Low Oil Pressure Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.2
Oil Level Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.3
Engine Oil Recommendation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.4
Oil Change Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.5
Oil Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Spark Plugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4 Air Cleaner Element and Precleaner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5 Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.6 Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.7 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.7.1
Cleaning Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.7.2
Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.8 Storage Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.8.1
Lubricating System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.8.2
Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.8.3
Internal Engine Components (Gas / Gasoline-Fueled Engines) . . . . . . .
2.8.4
Exterior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.8.5
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

19
19
21
21
21
21
21
22
22
23
24
24
24
25
25
26
26
26
26
26
26

Section 3 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Initial Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Controller Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

27
27
27
27
33

Section 4 ADC 2100 and DC 2200 Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


4.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Controller Display and Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.1
Starting Sequence, Master Switch Moved to RUN . . . . . . . . . . . . . . . . .
4.3.2
Starting Sequence, Remote Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.3
Running Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.4
Stopping Sequence, Master Switch Moved to OFF/RESET . . . . . . . . . .
4.3.5
Stopping Sequence, Remote Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4.1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4.2
Shutdowns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

35
35
36
37
37
37
37
37
37
37
37
37

TP-6196 10/09

Table of Contents

Table of Contents, continued


4.5

ADC 2100 Controller Configuration and Adjustment . . . . . . . . . . . . . . . . . . . . . . . .


4.5.1
Controller Time Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.2
Controller Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.3
Voltage and Frequency Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.4
Controller Application Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Continuous Power Mode Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Master Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relay Interface Board (RIB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controller Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

40
40
40
41
41
46
48
48
49

Section 5 ADC-RES and DC-RET Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


5.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Controls and Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.1
Master Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.2
LED Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.3
Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1
Starting Sequence, Master Switch Moved to RUN . . . . . . . . . . . . . . . . .
5.3.2
Starting Sequence, Remote Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.3
Running Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.4
Stopping Sequence, Master Switch Moved to OFF/RESET . . . . . . . . . .
5.3.5
Stopping Sequence, Remote Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.6
Standby Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.7
Sleep Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.2
Shutdowns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5 Controller Configuration and Adjustment, ADC-RES . . . . . . . . . . . . . . . . . . . . . . . .
5.5.1
Controller Time Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.2
Voltage and Frequency Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.3
Controller Application Program Version Number . . . . . . . . . . . . . . . . . . .
5.5.4
System Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6 Voltage and Frequency Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6.1
Voltage Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6.2
Frequency Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.7 Controller Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.8 Optional Relay Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.8.1
Relay Board Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.8.2
Relay Board Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9 Controller Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

53
53
54
54
54
55
56
56
56
56
56
56
56
56
57
57
57
59
59
59
59
60
62
62
63
66
67
67
69
70

Section 6 Component Testing and Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


6.1 Theory of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 Separate Excitation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Stator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 Main Field (Rotor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 Slip Rings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6 Brushes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7.1
Voltage Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7.2
Voltage Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7.3
Volts per Hertz (Hz) Adjustments (Droop) . . . . . . . . . . . . . . . . . . . . . . . . .
6.7.4
Voltage Connections, Single-Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7.5
Voltage Connections, 3-Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.8 Silicon Controlled Rectifier Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

73
73
73
74
77
78
78
79
79
79
81
81
82
82

4.6
4.7
4.8
4.9

Table of Contents

TP-6196 10/09

Table of Contents, continued


6.9

6.10
6.11

6.12

6.13
6.14
6.15

Electromechanical Governor System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


6.9.1
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.9.2
Initial Checks and Operation Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.9.3
Hunting/Surging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.9.4
Governor System/Magnetic Pickup Operation Test . . . . . . . . . . . . . . . . .
6.9.5
Frequency Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical Governor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Shutdown Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.11.1 Controller Fault Shutdown Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.11.2 Fault Shutdown Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.12.1 Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.12.2 Fuel Solenoid Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.12.3 Fuel Regulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.12.4 Fuel Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.12.5 Digital Spark Advance Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.12.6 Fuel Metering Valve Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starter Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Continuity Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

84
84
84
85
85
88
89
91
91
92
93
93
93
93
94
96
96
98
98
98

Section 7 Disassembly/Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101


7.1 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
7.2 Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Section 8 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Appendix A Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Appendix B Common Hardware Application Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Appendix C General Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Appendix D Common Hardware Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Appendix E Common Hardware List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128

TP-6196 10/09

Table of Contents

Notes

TP-6196 10/09

Safety Precautions and Instructions


IMPORTANT SAFETY INSTRUCTIONS.

Electromechanical
equipment,
including generator sets, transfer
switches, switchgear, and accessories,
can cause bodily harm and pose
life-threatening
danger
when
improperly installed, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely. Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual has several types of safety
precautions and instructions: Danger,
Warning, Caution, and Notice.

Accidental Starting
WARNING

Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.

DANGER
Danger indicates the presence of a
hazard that will cause severe
personal injury, death, or substantial
property damage.

WARNING
Warning indicates the presence of a
hazard that can cause severe
personal injury, death, or substantial
property damage.

Disabling
the
generator set.
Accidental starting can cause
severe injury or death.
Before
working on the generator set or
connected equipment, disable the
generator set as follows: (1) Move the
generator set master switch to the OFF
position. (2) Disconnect the power to
the battery charger. (3) Remove the
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent starting of
the generator set by an automatic
transfer switch, remote start/stop
switch, or engine start command from a
remote computer.

CAUTION

Battery
Caution indicates the presence of a
hazard that will or can cause minor
personal injury or property damage.

WARNING

NOTICE
Notice communicates installation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publication to improve operator
recognition.
Replace missing or
damaged decals.

TP-6196 10/09

WARNING

Explosion.
Can cause severe injury or death.
Relays in the battery charger
cause arcs or sparks.
Locate the battery in a well-ventilated
area. Isolate the battery charger from
explosive fumes.
Battery electrolyte is a diluted
sulfuric acid. Battery acid can cause
severe injury or death. Battery acid
can cause blindness and burn skin.
Always wear splashproof safety
goggles, rubber gloves, and boots
when servicing the battery. Do not
open a sealed battery or mutilate the
battery case. If battery acid splashes in
the eyes or on the skin, immediately
flush the affected area for 15 minutes
with large quantities of clean water.
Seek immediate medical aid in the case
of eye contact. Never add acid to a
battery after placing the battery in
service, as this may result in hazardous
spattering of battery acid.
Battery acid cleanup. Battery acid
can cause severe injury or death.
Battery acid is electrically conductive
and corrosive. Add 500 g (1 lb.) of
bicarbonate of soda (baking soda) to a
container with 4 L (1 gal.) of water and
mix the neutralizing solution. Pour the
neutralizing solution on the spilled
battery acid and continue to add the
neutralizing solution to the spilled
battery acid until all evidence of a
chemical reaction (foaming) has
ceased. Flush the resulting liquid with
water and dry the area.

Sulfuric acid in batteries.


Can cause severe injury or death.
Wear protective goggles and
clothing. Battery acid may cause
blindness and burn skin.

Safety Precautions and Instructions

Battery gases. Explosion can cause


severe injury or death. Battery gases
can cause an explosion. Do not smoke
or permit flames or sparks to occur near
a battery at any time, particularly when
it is charging. Do not dispose of a
battery in a fire. To prevent burns and
sparks that could cause an explosion,
avoid touching the battery terminals
with tools or other metal objects.
Remove all jewelry before servicing the
equipment. Discharge static electricity
from your body before touching
batteries by first touching a grounded
metal surface away from the battery. To
avoid sparks, do not disturb the battery
charger connections while the battery
is charging. Always turn the battery
charger off before disconnecting the
battery connections. Ventilate the
compartments containing batteries to
prevent accumulation of explosive
gases.
Battery short circuits. Explosion
can cause severe injury or death.
Short circuits can cause bodily injury
and/or
equipment
damage.
Disconnect
the
battery
before
generator
set
installation
or
maintenance. Remove all jewelry
before servicing the equipment. Use
tools with insulated handles. Remove
the negative (--) lead first when
disconnecting the battery. Reconnect
the negative (--) lead last when
reconnecting the battery.
Never
connect the negative (--) battery cable
to the positive (+) connection terminal
of the starter solenoid. Do not test the
battery condition by shorting the
terminals together.

Engine Backfire/Flash
Fire

Servicing the fuel system. A flash


fire can cause severe injury or death.
Do not smoke or permit flames or
sparks near the carburetor, fuel line,
fuel filter, fuel pump, or other potential
sources of spilled fuels or fuel vapors.
Catch fuels in an approved container
when removing the fuel line or
carburetor.
Servicing the air cleaner. A sudden
backfire can cause severe injury or
death. Do not operate the generator
set with the air cleaner removed.

Exhaust System
WARNING

Carbon monoxide.
Can cause severe
fainting, or death.

nausea,

The exhaust system must be


leakproof and routinely inspected.
Generator set operation. Carbon
monoxide can cause severe nausea,
fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Avoid
breathing exhaust fumes when working
on or near the generator set. Never
operate the generator set inside a
building. Never operate the generator
set where exhaust gas could seep
inside or be drawn into a building
through windows, air intake vents, or
other openings.

Carbon
monoxide
symptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in
exhaust gases. Carbon monoxide is an
odorless,
colorless,
tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Carbon
monoxide poisoning symptoms include
but are not limited to the following:
! Light-headedness, dizziness
! Physical fatigue, weakness in
joints and muscles
! Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
! Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep. Alert others to the
possibility of carbon monoxide
poisoning. Seek medical attention if
the condition of affected persons does
not improve within minutes of breathing
fresh air.

Fuel System
WARNING

Explosive fuel vapors.


Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.

WARNING

Fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.

Safety Precautions and Instructions

TP-6196 10/09

The fuel system. Explosive fuel


vapors can cause severe injury or
death. Vaporized fuels are highly
explosive. Use extreme care when
handling and storing fuels. Store fuels
in a well-ventilated area away from
spark-producing equipment and out of
the reach of children. Never add fuel to
the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines. Use flexible
sections to avoid fuel line breakage
caused by vibration. Do not operate the
generator set in the presence of fuel
leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming
generator set operation.
Gas fuel leaks.
Explosive fuel
vapors can cause severe injury or
death. Fuel leakage can cause an
explosion. Check the LP vapor gas or
natural gas fuel system for leakage by
using a soap and water solution with
the fuel system test pressurized to
6--8 ounces
per
square
inch
(10--14 inches water column). Do not
use a soap solution containing either
ammonia or chlorine because both
prevent bubble formation. A successful
test depends on the ability of the
solution to bubble.
LP liquid withdrawal fuel leaks.
Explosive fuel vapors can cause
severe injury or death. Fuel leakage
can cause an explosion. Check the LP
liquid withdrawal gas fuel system for
leakage by using a soap and water
solution with the fuel system test
pressurized to at least 90 psi
(621 kPa). Do not use a soap solution
containing either ammonia or chlorine
because
both
prevent
bubble
formation. A successful test depends
on the ability of the solution to bubble.

TP-6196 10/09

Hazardous Noise

CAUTION

CAUTION

Hazardous noise.
Can cause hearing loss.
Never operate the generator set
without a muffler or with a faulty
exhaust system.

Hazardous Voltage/
Moving Parts
WARNING

Hazardous voltage. Moving parts.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.

WARNING

Hazardous voltage.
Backfeed to the utility system can
cause property damage, severe
injury, or death.

Welding the generator set.


Can cause severe electrical
equipment damage.
Never weld components of the
generator
set
without
first
disconnecting the battery, controller
wiring harness, and engine electronic
control module (ECM).
Grounding electrical equipment.
Hazardous voltage can cause
severe injury or death. Electrocution
is possible whenever electricity is
present. Ensure you comply with all
applicable codes and standards.
Electrically ground the generator set,
transfer switch, and related equipment
and electrical circuits. Turn off the main
circuit breakers of all power sources
before servicing the equipment. Never
contact electrical leads or appliances
when standing in water or on wet
ground because these conditions
increase the risk of electrocution.
Welding on the generator set. Can
cause severe electrical equipment
damage.
Before welding on the
generator set perform the following
steps: (1) Remove the battery cables,
negative (--) lead first. (2) Disconnect
all engine electronic control module
(ECM) connectors. (3) Disconnect all
generator set controller and voltage
regulator circuit board connectors.
(4) Disconnect the engine batterycharging
alternator
connections.
(5) Attach the weld ground connection
close to the weld location.

If the generator set is used for


standby power, install an automatic
transfer switch to prevent inadvertent
interconnection of standby and
normal sources of supply.

Safety Precautions and Instructions

High voltage test.


Hazardous
voltage can cause severe injury or
death. Follow the instructions of the
test equipment manufacturer when
performing high-voltage tests on the
rotor or stator. An improper test
procedure can damage equipment or
lead to generator set failure.
Connecting the battery and the
battery charger. Hazardous voltage
can cause severe injury or death.
Reconnect the battery correctly,
positive to positive and negative to
negative, to avoid electrical shock and
damage to the battery charger and
battery(ies).
Have a qualified
electrician install the battery(ies).
Short
circuits.
Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage. Do not contact electrical
connections with tools or jewelry while
making adjustments or repairs.
Remove all jewelry before servicing the
equipment.
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severe injury or death. Install
a transfer switch in standby power
installations to prevent the connection
of standby and other sources of power.
Electrical backfeed into a utility
electrical system can cause severe
injury or death to utility personnel
working on power lines.

WARNING

Airborne particles.
Can cause severe
blindness.

injury

Heavy Equipment
WARNING

Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.

Servicing the exhaust system. Hot


parts can cause severe injury or
death. Do not touch hot engine parts.
The engine and exhaust system
components become extremely hot
during operation.
Servicing the engine heater. Hot
parts can cause minor personal
injury or property damage. Install the
heater before connecting it to power.
Operating the heater before installation
can cause burns and component
damage. Disconnect power to the
heater and allow it to cool before
servicing the heater or nearby parts.

Notice
NOTICE

Hot Parts
WARNING

Canadian installations only. For


standby service connect the output of
the generator set to a suitably rated
transfer switch in accordance with
Canadian Electrical Code, Part 1.

NOTICE

Hot engine and exhaust system.


Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the alternator. Hot parts
can cause severe injury or death.
Avoid touching the alternator field or
exciter armature. When shorted, the
alternator field and exciter armature
become hot enough to cause severe
burns.

Electrostatic discharge damage.


Electrostatic
discharge
(ESD)
damages electronic circuit boards.
Prevent
electrostatic
discharge
damage by wearing an approved
grounding wrist strap when handling
electronic circuit boards or integrated
circuits. An approved grounding wrist
strap provides a high resistance (about
1 megohm), not a direct short, to
ground.

or

Wear protective goggles and clothing


when using power tools, hand tools,
or compressed air.

10

Safety Precautions and Instructions

TP-6196 10/09

Introduction
This manual provides troubleshooting and repair
instructions for the generator set models listed on the
front cover. This manual may also be supplied for similar
models not listed on the front cover.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow the
Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
equipment for future reference.
The equipment service requirements are very important
to safe and efficient operation. Inspect the parts often
and perform required service at the prescribed intervals.
Maintenance work must be performed by appropriately
skilled and suitably trained maintenance personnel
familiar with generator set operation and service.
For engine service procedures not covered in this
manual, refer to the Engine Service Manual, TP-2428.

List of Related Materials


Separate manuals contain operation, installation, and
parts information not provided in this manual. Separate
engine operation and service manuals are also
available. The following table lists the available manual
part numbers.

Document Description

Part
Number

Operation/Installation Manual, 8.5/12RES*

TP-6195

Installation Manual, 8.5/12RES w/ADC 2100 TP-6328


Operation Manual, 8.5/12RES w/ADC 2100

TP-6331

Installation Manual, 12RESL/RESM1


w/DC 2200

TP-6398

Operation Manual, 12RESL/RESM1


w/DC 2200

TP-6397

Installation Manual, 8.5/12RES/12TRES


w/ADC-RES

TP-6514

Operation Manual, 8.5/12RES/12TRES


w/ADC-RES

TP-6515

Installation Manual, 12RESL/RESM1


w/DC RET

TP-6516

Operation Manual, 12RESL/RESM1


w/DC RET

TP-6517

Parts Catalog, 8.5/12RES

TP-5868

Parts Catalog, 12RESL/RESM1

TP-6399

Engine Service Manual

TP-2428

* Replaced by TP--6328 and TP--6331, May, 2004.

Routine Service Parts


See the Parts Catalog for a list of common replacement
parts.

TP-6196 10/09

Introduction

11

Service Assistance
For professional advice on generator power
requirements and conscientious service, please contact
your nearest Kohler distributor or dealer.
! Consult the Yellow Pages under the heading

GeneratorsElectric.
! Visit

the Kohler Power Systems website at


KohlerPower.com.

! Look at the labels and stickers on your Kohler product

or review the appropriate literature or documents


included with the product.
! Call toll free in the US and Canada 1-800-544-2444.
! Outside the US and Canada, call the nearest regional

office.
Headquarters Europe, Middle East, Africa
(EMEA)
Kohler Power Systems
3 rue de Brennus
93200 Saint Denis
France
Phone: (33) 1 49 178300
Fax: (33) 1 49 178301
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 264-6422
Fax: (65) 264-6455

12

Service Assistance

China
North China Regional Office, Beijing
Phone: (86) 10 6518 7950
(86) 10 6518 7951
(86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai
Phone: (86) 21 6288 0500
Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax: (813) 3440-2727
Latin America
Latin America Regional Office
Lakeland, Florida, USA
Phone: (863) 619-7568
Fax: (863) 701-7131

TP-6196 10/09

Section 1 Specifications
! One-side serviceability of air cleaner, carburetor, oil

1.1 Introduction

fill, dipstick, and oil drain.

The spec sheets for each generator set provide specific


generator and engine information.
Refer to the
generator set spec sheet for data not supplied in this
manual. Consult the generator set installation manual,
engine operation manual, and engine service manual
for additional specifications.

! Electronic governor to ensure AC power output is

Check the generator set nameplate for specific


generator set ratings.

! Overspeed shutdown to prevent governed frequency

1.2 Controller Specifications


For a specific description of the controller, see
Section 2, Operation, in the operation manual.

Storage temperature
Humidity

--20" to 70"C

maintained at desired frequency.


from exceeding 70 Hz on 60 Hz models (60 Hz on
50 Hz models).
! Low oil pressure cutout to prevent failure.
! Dependable, maintenance free electronic ignition.

engine timing for natural gas or LP fuel (12 kW models


only).

--60" to 70"C
0--95% condensing

! Parts subject to the most wear and tear made from

12 or 24 VDC

! Hydraulic valve adjusters to eliminate the need for

Power requirements:
Voltage
Current

lubrication for maximum power, torque, and reliability


under all operating conditions.

! Digital Spark Advance Ignition (DSAI) optimizes

Environmental Specifications
Operating temperature

! Efficient overhead valve design and full pressure

250 mA @ 12 VDC
125 mA @ 24 VDC

precision formulated cast iron.


valve adjustments.
! Field-convertible

1.3 Engine Features


The generator sets are equipped with four-cycle, twin
cylinder, air-cooled Kohler engines. Some of the engine
features include:

TP-6196 10/09

fuel systems that allow fuel


changeover from natural gas to LP vapor (and
vice-versa) while maintaining CARB certification.

For engine service information and specifications not


covered in this manual, see the Engine Service Manual.

Section 1 Specifications

13

See the List of Related Materials in the Introduction


Section.

1.5 Torque Specifications


Torque Specifications, Nm (ft. lb.)
Alternator overbolts

1.4 Engine Specifications


Engine Specification

8.5 kW
(60 Hz)

Manufacturer
Model

12 kW
(60 Hz)
Kohler

CH20

Cycle

Number of cylinders

Compression ratio

8.5:1

9.0:1

Displacement, cc (cu. in.)

624 (38.0)

725 (44.0)

Rated power, propane fuel,


kw (HP)

11.5 (15.4)

17.6 (23.6)

Rpm
Bore x stroke, mm (in.)
Valve material
Cylinder block material
Cylinder head material
Piston rings
Crankshaft material
Main bearings: number,
type
Governor
Lubrication system
Oil capacity (w/filter), L (qt.)
Oil pressure, kPa (psi)
Fuel system
LP/natural gas minimum
supply pressure,
in. H2O (oz./in.2)
Battery voltage
Battery ground
Spark plug gap, mm (in.)
Ignition system
Starter motor
Cooling system

14

Section 1 Specifications

7 (5)

Alternator thrubolt

40 (28)

Cylinder head nuts

30 (40.7)

Generator adapter screws


Muffler flange bolts

CH740

8.5/12 kW

40 (28)
24 (17.7)

Oil filter

5.7--9.0 (4.2--6.7)

Spark plug

24.4--29.8 (18--22)

3600
77 x 67 (3.03 83 x 67 (3.27
x 2.64)
x 2.64)
Steel/Stellite#
Aluminum w/cast iron liners
Aluminum
2 compression/1 oil
Heat-treated ductile iron
2, parent material
Electronic
Full pressure
1.9 (2.0)

2 (2.1)

172--241 (25--35)
LP gas or natural gas
7--11 (4--6)
12 VDC
Negative
0.51 (0.020)

0.76 (0.030)

Capacitor
Discharge

Smart Spark
Capacitor
Discharge

Electric, solenoid shift


Air-cooled

TP-6196 10/09

1.6 Alternator Specifications


Alternator Specification
Frequency Hz
Phase
Number of leads

8.5/12 kW 1 phase

12TRES 3 phase

50/60

50

Single-Phase

Three

12

Excitation method

Static Excited

Voltage regulator type

Digital

Coupling type

Direct

Thrubolt torque, Nm ( ft. lb.)

40 (28)

Overbolt torque, Nm (in. lb.)

7 (60)

Insulation (rotor and stator)

Epoxy varnish, vacuum impregnated


Class 180 (H)

Winding material

Copper

Bearing, number and type

1, replaceable ball

Circuit protection
Controller

10 amps

Aux. winding
Generator AC output
Rotor resistance, ohms, cold

20 amps
Dependent on voltage configuration
4.0

4.2

0.07

N/A

N/A

0.18

Stator resistance, ohms,* cold


Single-Phase Leads 1-2, 3-4
Three-Phase Leads 1-4, 2-5, 3-6, 7-10, 8-11, 9-12
Leads 11-44

0.14

N/A

55-66

0.70

0.15

132 V

N/A

N/A

115 V

Stator output voltage with separately excited rotor using 12-volt


battery, minimum
Single-Phase Leads 1-2, 3-4
Three-Phase Leads 1-4, 2-5, 3-6, 7-10, 8-11, 9-12
11-44

264 V

N/A

55-66

145 V

150 V

No load

12 V / 2.0 amps

14 V / 2.8 amps

Full load

47 V / 7.4 amps

78 V /11.5 amps

Rotor field voltage/current readings at rated output voltage, hot

Brush length, new

19.05 mm (0.75 in.)

* Most ohmmeters do not give accurate readings when measuring less than 1 ohm. The stator can be considered good if a low resistance
reading (continuity) is obtained and there is no evidence of shorted windings (discoloration). Do not confuse a low resistance reading with
a reading indicating a shorted winding.

TP-6196 10/09

Section 1 Specifications

15

1.7 Service Views


1

17

See control detail

18

19

20

21
22

16

23
7

10
15
24

25

ADV-7466-

14

13

12

11
20
5
21

26
27
28

22
9
8

23

Control Detail

Fuel System Detail

29

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.

Muffler
Oil check
Oil fill
Air cleaner
Controller user interface (switch membrane)
Generator set master switch (RUN-OFF/RESET-AUTO)
Load circuit breaker (1-phase models)
Fuses
RS-232 connector (for application program updates)
Field-connection terminal block location
Spark plug locations (both sides)
Oil drain hose
Oil drain valve
Oil filter
Exhaust

Figure 1-1

16

16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.

Equipment ground
Starter relay
Battery charger
DSAI lead location
Fuel block
Gas regulator assembly
Fuel solenoid valve
Fuel inlet
Air intake
Engine starting battery location (battery purchased separately)
DSAI ground screw
Starter solenoid
Positive battery connection
Negative battery connection

Generator Set Service View, 12 kW Model with ADC-RES Controller

Section 1 Specifications

TP-6196 10/09

2
1
3

GM66010

1. Emergency stop button


2. Field-connection terminal block and circuit breakers
3. Cable inlet area

Figure 1-2

Additional Components, 3-Phase Models

TP-6196 10/09

Section 1 Specifications

17

21

22

23

24

25

26

9
10
20
11

12

19
12
ADV6823

18

17 16 15 14
27

13

24

28

25

31

26
29
30

Starter (non-service side)


1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.

Enclosure
Muffler
Oil check
Oil fill
Air cleaner
Spark plug locations (both sides)
Controller
Generator set master switch (RUN\OFF/RESET\AUTO)
Nameplate
Line circuit breaker
Battery charger
Air intake
Engine starting battery location
Oil drain hose
High engine temperature (HET) sensor
(located on non-service side)
16. Oil drain valve

Figure 1-3

18

Fuel System Detail


17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.

Oil filter
Air intake, alternator
Exhaust
Spark arrestor (not visible in this view)
Relay interface board (RIB)
SCR module
Digital spark advance module leads
(DSAM leads, ignition timing)
Multi-fuel block
Secondary fuel regulator assembly
Fuel solenoid valve
Starter solenoid
Positive battery connection
Starter relay
Negative battery connection
DSAM ground screw

Generator Set Service View, 12 kW Model with ADC 2100 Controller

Section 1 Specifications

TP-6196 10/09

Section 2 Scheduled Maintenance


WARNING

Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.

WARNING

Hot engine and exhaust system.


Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the exhaust system. Hot parts can cause
severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.

WARNING

Hazardous voltage. Moving parts.


Can cause severe injury or death.

See the Safety Precautions and Instructions at the


beginning of this manual before attempting to service,
repair, or operate the generator set. Have an authorized
distributor/dealer perform generator set service.
Alternator Service. Under normal operating conditions
the generator set alternator does not require scheduled
service. Refer to the service schedule for items that
require maintenance.
Engine Service. Perform generator set engine service
at the intervals specified by the engine service literature.
Contact an authorized Kohler! distributor/dealer to
obtain engine service literature.
All generator sets have emission-certified engines. The
carburetors on emission-certified engines are not
adjustable.
Generator Set Service. See the Safety Precautions
and Instructions at the beginning of this manual before
attempting to service, repair, or operate the generator
set. Have an authorized Kohler! distributor/dealer
perform all generator service.
Routine Maintenance. Refer to the following generator
set service schedule, the engine service schedule, and
the runtime hours displayed on the generator set
controller to determine when to schedule routine
maintenance.
Service the generator set more
frequently if it is subject to extreme weather, long
operating hours, or dusty or dirty conditions.
Service Schedule. Perform maintenance on each item
in the service schedule at the designated interval for the
life of the generator set.
Tools. Tools and instruments used to perform some
maintenance items are not generally available to the
generator set owner.
Therefore, have service
performed by an authorized distributor/dealer.

2.1 Service Schedule


Perform the items listed in the service schedule at the
designated intervals for the life of the generator set. For
example, an item serviced every 100 hours or 3 months
must also be serviced after 200 hours or 6 months,
300 hours or 9 months, etc.

Operate the generator set only when


all guards and electrical enclosures
are in place.

TP-6196 10/09

Section 2 Scheduled Maintenance

19

SystemComponent
Lubrication
Oil level
Crankcase breather hose
Change oil
Replace filter(s)*
Oil cooler*
Fuel
Flexible lines and connections $
Main tank supply level
Fuel piping
Cooling
Air ducts and louvers in enclosure *
Exhaust System
Leakage
Obstructions or combustible materials near
exhaust outlet

Action
Refer to
Section Inspect Check Change Clean Test
Interval
2.2
2.2.2
X
X
8 hr. or before use
E
E
Yearly or 500 hr.
2.2.4
R
Yearly or 100 hr.
2.2.4
R
Yearly or 200 hr.
2.2.5
X
R
X
Yearly or 100 hr.
6.12
X
R
Quarterly
X
Weekly
X
Yearly
2.5
X
X
Yearly
2.6
X
X
Weekly
X

DC Electrical System
Battery charger operation
Remove corrosion, clean and dry battery and
rack

2.7
O/M

2.7

Clean and tighten battery terminals


Inspect battery boots and replace if necessary
Tighten DC electrical connections
AC Electrical System
General inspection
Wire abrasions where subject to motion
Tighten control and power wiring connections
Wire-cable insulation breakdown
Engine and Mounting
General inspection
Air cleaner and precleaner service *
Spark plugs
Replace spark plugs
Stepper motor coupling and bushing
Generator
Compartment condition
Inspect brushes and collector ring
Measure and record resistance readings of
windings with insulation tester (Megger, with
SCR assembly or rectifier and load leads
disconnected)

2.7
2.7
2.7

X
X

Run/exercise generator set


Remote control operation
General Condition Of Equipment
Any condition of vibration, leakage, excessive
noise, high temperature, or deterioration
Interior of enclosure
R
Replace
X
Action
O/M Generator Set Operation Manual

Weekly
Monthly

Yearly

Yearly
Yearly
Yearly

R
X

X
X

Quarterly
Six Months
Yearly
3 yr. or 500 hr.

X
X

X
E
2.4
2.3
2.3
6.9

6.6

E
X
X
E

R
R

X
X

6.3

X
X

Weekly
Yearly or 100 hr.
Yearly
500 hr.
3 yr. or 500 hr.

Weekly
Yearly
X

3 yr.

X
X

Weekly
Monthly

Weekly

Quarterly

E
Follow procedures and frequencies indicated in the engine manufacturers
maintenance manual. If not indicated, follow this service schedule. Some items
may not apply to all generator sets.

* Service more frequently if operated in dusty areas.


! Replace fuel lines and connections as necessary.

Figure 2-1
20

Service Schedule

Section 2 Scheduled Maintenance

TP-6196 10/09

2.2 Lubrication System

2.2.3

See Section 2.1, Service Schedule, for oil change and


oil filter replacement intervals. See Figure 2-2 for the oil
drain, oil check, oil fill, and oil filter locations.

Use synthetic oil of API (American Petroleum Institute)


Service Class SG or higher. Synthetic oil causes fewer
deposits on the engine intake valves and pistons
because it oxidizes and thickens less than other oils.
See Figure 2-3 and Figure 2-4.

The engine has a positive pressure lubrication system


and low oil pressure shutdown.

Engine Oil Recommendation

Model

L (Qt.)

8.5kW

1.9 (2.0)

12kW

2.0 (2.1)

Figure 2-3

Oil Capacity with Filter

10W-30

5W-20, 5W-30

C --30 --20 --10


10 20
30
0
40
60
80
100
0
20 32 40
F --20
Temperature Range Expected Before Next Oil
Change
6
1. Dip stick location
2. Oil fill
3. Oil drain hose

Figure 2-2

ADV--7466

4. Oil drain valve


5. Oil cooler
6. Oil filter

Figure 2-4

2.2.4

Engine Oil Selection

Oil Change Procedure

Whenever possible, drain the oil while it is still warm.

Lubrication System (typical)


1. Drain the oil.

2.2.1

Low Oil Pressure Shutdown

The low oil pressure shutdown feature protects the


engine against internal damage if the oil pressure drops
below preset limits because of oil pump failure or other
malfunction. It does not protect against damage caused
by operating with the oil level below the safe rangeit is
not a low oil level shutdown.

2.2.2

Oil Level Check

Check the oil level regularly and add oil as needed to


protect against running out of oil. See Figure 2-2 for the
dipstick and oil fill locations. Do not check the oil level
when the generator set is running. Shut down the
generator set and wait several minutes before checking
the oil level.

a. Place the generator set master switch in the


OFF position.
b. Disconnect the power to the battery charger.
c. Disconnect the generator set engine starting
battery, negative (--) lead first.
d. Remove the oil drain hose from its retaining
clip. See Figure 2-2. Remove the cap from the
oil drain hose and lower the hose into an oil
collection container.
e. Open the oil drain valve on the engine.
Remove the dipstick and oil fill cap.
f. Allow time for the engine oil to drain completely.
g. Close the oil drain valve.
h. Replace the cap on the oil drain hose. Replace
the oil drain hose in its retaining clip.

TP-6196 10/09

Section 2 Scheduled Maintenance

21

2. Replace the oil filter.


a. Remove the oil filter by rotating
counterclockwise with an oil filter wrench.

it

b. Apply a light coat of clean oil to the rubber seal


of the new oil filter.
c. Install the new oil filter following the instructions
provided with the filter.
Note: Dispose of all waste materials (engine
oil, fuel, filter, etc.) in an environmentally
safe manner.
3. Fill with oil.
a. Fill with oil. See Section 2.2.3 for oil selection
and Figure 2-3 for oil capacity.

1
2
1. Oil filter
2. Oil cooler

Figure 2-5

24 590 01--A

Oil Cooler Location

b. Replace the oil fill cap and dipstick.


4. Check for leaks.
a. Check that the generator set master switch is in
the OFF position.
b. Reconnect the generator set engine starting
battery, negative (--) lead last.
c. Reconnect the power to the battery charger.
d. Start the generator set and check for leaks
around the oil filter.
e. Stop the generator set and tighten the oil filter to
stop any leaks.
f. Reinstall the housing side panel.
24 590 01--A

2.2.5

Oil Cooler

Inspect and clean the oil cooler at the intervals shown in


the Service Schedule. The oil cooler must be kept free
of debris.
See Figure 2-2 and Figure 2-5 for the oil cooler location.
Clean the outside of the oil cooler with a brush or
compressed air. If it is necessary to clean the back of the
oil cooler, remove the two screws holding the oil cooler
unit to the blower hosing. Tilt the cooler and clean with a
brush or compressed air as shown in Figure 2-6. After
cleaning, reinstall the oil cooler and secure with the
mounting screws.

22

Section 2 Scheduled Maintenance

Figure 2-6

Cleaning the Oil Cooler

2.3 Spark Plugs


Reset the spark plug gap or replace the plugs with new
plugs as necessary.
Spark Plug Maintenance Procedure
1. Clean the area around the base of the spark plug to
keep dirt and debris out of the engine.
2. Remove the spark plug and check its condition.
Replace the spark plug if it is worn or if its reuse is
questionable.

TP-6196 10/09

3. Check the spark plug gap using a wire feeler


gauge. See Figure 2-7 for the recommended gap.
Adjust the gap by carefully bending the ground
electrode. See Figure 2-8 and Figure 2-9.

Note: Operating the engine with loose or damaged air


cleaner components could allow unfiltered air
into the engine, causing premature wear and
failure.

4. Install the spark plug and tighten it according to the


torque specification in Section 1.5.

1
2

Model

Spark Plug Gap

8.5 kW

0.51 mm (0.020 in.)

12 kW

0.76 mm (0.030 in.)

Figure 2-7

Spark Plug Gap

6
7

Figure 2-8

Checking the Spark Plug Gap


586536

1.
2.
3.
4.

Cover knob
Air cleaner cover
Element cover nut
Element cover

5. Foam precleaner
6. Air cleaner element
7. Air cleaner base

Figure 2-10 Air Cleaner Components


Air Cleaner Service Procedure
1. Disable the generator set.
Figure 2-9

Adjusting the Spark Plug Gap

2.4 Air Cleaner Element and


Precleaner
The engine has a replaceable high-density paper air
cleaner element with an oiled foam precleaner. See
Figure 2-10. Refer to Section 1.7, Service View, for the
air cleaner location.
Wash and oil the precleaner and replace the paper
element at the intervals shown in the service schedule,
Figure 2-1. Service the air cleaner more often if the
generator set operates under dusty or dirty conditions.
Refer to Maintenance and Service Parts in the
Introduction section of this manual for replacement part
numbers.
Keep the area around the air cleaner housing free of dirt
and debris.

TP-6196 10/09

a. Place the generator set master switch in the


OFF/RESET position.
b. Disconnect the power to the battery charger.
c. Disconnect the generator set engine starting
battery, negative (--) lead first.
2. Remove the foam precleaner and paper element.
a. Loosen the air cleaner cover retaining knob and
remove the cover.
b. Remove the element cover nut, element cover,
and paper element with precleaner.
c. Remove the precleaner from the paper
element.
3. Wash and oil the foam precleaner.
a. Wash the precleaner in warm soapy water.

Section 2 Scheduled Maintenance

23

b. Rinse the precleaner with warm water until the


water runs clear.

Note: Do not block the generator set cooling air inlet or


mount other equipment above it. Overheating
and severe generator damage may occur.

c. Squeeze out excess water and allow the


precleaner to air dry.
Note: Do not wring (twist) the precleaner or dry
it with compressed air.

d. Saturate the precleaner with new engine oil.


Squeeze out the excess oil.
4. Replace the paper element if it is dirty, bent, or
damaged.
Note: Do not wash the paper element or clean it
with compressed air, as both will damage
the element.
5. Reinstall the air cleaner.
a. Install the precleaner over the paper element.
b. Check the air cleaner base. Make sure it is
secure and not bent or damaged. Remove any
dirt or debris from the air cleaner base. Wipe
the base carefully so that no dirt falls into the
intake throat.
c. Check the element cover for damage and fit.
Replace all damaged air cleaner components.
Check the condition of the rubber seal on the air
cleaner stud and replace the seal if necessary.
d. Install the paper element, precleaner, element
cover, element cover nut, and air cleaner cover.
Secure the cover with the cover retaining knob
(finger-tighten only).
e. Check the element cover for damage and fit.
Replace all damaged air cleaner components.
Check the condition of the rubber seals and
replace them if necessary.
6. Enable the generator set.
a. Reconnect the generator set engine starting
battery, negative (--) lead last.

3
tp6196

1. Exhaust outlet
2. Alternator air intake (both sides)
3. Engine air intake

Figure 2-11 Cooling Air Intake and Exhaust

2.6 Exhaust System


Remove combustible materials from the exhaust
location.
Combustible materials include building
materials as well as natural surroundings. Keep dry field
grass, foliage, and combustible landscaping material a
safe distance from the exhaust outlet. Check the area
periodically for accumulated debris and seasonal grass
or foliage.
Inspect exhaust system components (exhaust manifold,
exhaust line, flexible exhaust, clamps, silencer and
outlet pipe) for cracks and corrosion.
! Check for corroded or broken metal parts and replace

them as needed.
! Check that exhaust outlet is clear.

2.7 Battery
WARNING

b. Reconnect the power to the battery charger.

2.5 Cooling System


Fans in the engine and generator draw cooling air
through the louvered openings in the sides and end of
the sound enclosure. The cooling air mixes with the
engine exhaust and is discharged through the outlet
end. To prevent generator set damage caused by
overheating, keep the housing cooling inlets and outlets
clean and unobstructed at all times. See Figure 2-11.
24

Section 2 Scheduled Maintenance

Sulfuric acid in batteries.


Can cause severe injury or death.
Wear protective goggles and
clothing. Battery acid may cause
blindness and burn skin.

TP-6196 10/09

Battery electrolyte is a diluted sulfuric acid. Battery acid


can cause severe injury or death. Battery acid can cause
blindness and burn skin. Always wear splashproof safety
goggles, rubber gloves, and boots when servicing the battery.
Do not open a sealed battery or mutilate the battery case. If
battery acid splashes in the eyes or on the skin, immediately
flush the affected area for 15 minutes with large quantities of
clean water. Seek immediate medical aid in the case of eye
contact. Never add acid to a battery after placing the battery in
service, as this may result in hazardous spattering of battery
acid.
Battery acid cleanup. Battery acid can cause severe
injury or death. Battery acid is electrically conductive and
corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking
soda) to a container with 4 L (1 gal.) of water and mix the
neutralizing solution. Pour the neutralizing solution on the
spilled battery acid and continue to add the neutralizing
solution to the spilled battery acid until all evidence of a
chemical reaction (foaming) has ceased. Flush the resulting
liquid with water and dry the area.
Battery gases. Explosion can cause severe injury or
death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time,
particularly when it is charging. Do not dispose of a battery in a
fire. To prevent burns and sparks that could cause an
explosion, avoid touching the battery terminals with tools or
other metal objects. Remove all jewelry before servicing the
equipment. Discharge static electricity from your body before
touching batteries by first touching a grounded metal surface
away from the battery. To avoid sparks, do not disturb the
battery charger connections while the battery is charging.
Always turn the battery charger off before disconnecting the
battery connections. Ventilate the compartments containing
batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury
or death. Short circuits can cause bodily injury and/or
equipment damage. Disconnect the battery before generator
set installation or maintenance. Remove all jewelry before
servicing the equipment. Use tools with insulated handles.
Remove the negative (--) lead first when disconnecting the
battery.
Reconnect the negative (--) lead last when
reconnecting the battery. Never connect the negative (--)
battery cable to the positive (+) connection terminal of the
starter solenoid. Do not test the battery condition by shorting
the terminals together.

EZ-273000-J

1. To positive (+) terminal on starter solenoid.


2. To ground (--) terminal on or near starter motor.

Figure 2-12 12-Volt Engine Electrical System Single


Starter Motor, Typical Battery Connection
Clean the battery and cables and tighten battery
terminals using the service schedule recommendations.
Clean the battery by wiping it with a damp cloth. Keep
the electrical connections dry and tight.
Consult the battery manufacturers instructions for
battery care and maintenance.

2.7.1

Cleaning Battery

To prevent dirt and grime buildup, occasionally wipe the


battery with a damp cloth.
To prevent corrosion, maintain tight, dry electrical
connections at the battery terminals. To remove
corrosion from battery terminals, disconnect the cables
from the battery and scrub the terminals with a wire
brush. Clean the battery and cables with a solution of
baking soda and water. Do not allow the cleaning
solution to enter the batterys cells. After cleaning, flush
the battery and cables with clean water and wipe them
with a dry, lint-free cloth.
After reconnecting the battery cables, coat the battery
terminals with petroleum jelly, silicone grease, or other
nonconductive grease.

2.7.2

Battery Charger

Use a 12-volt battery with a minimum rating of 525 cold


cranking amps at --18"C (0"F) The generator set uses a
negative ground with a 12-volt engine electrical system.
Make sure that the battery is correctly connected and
the terminals are tight. See Figure 2-12.

Generator sets are equipped with a factory-installed


battery charger to keep the starting battery fully
charged. Observe the battery polarity when connecting
the battery charger. Check the battery charger fuse and
power supply.

Note: The generator set will not start and circuit board
damage may result if the battery is connected in
reverse.

See the generator set operation manual for information


about battery charger operation and troubleshooting.

TP-6196 10/09

Section 2 Scheduled Maintenance

25

2.8 Storage Procedure


Perform the following storage procedure before taking a
generator set out of service for three months or longer.
Follow the engine manufacturers recommendations, if
available, for fuel system and internal engine
component storage.

2.8.1

Lubricating System

Prepare the engine lubricating system for storage as


follows:
1. Run the generator set for a minimum of 30 minutes
to bring it to normal operating temperature.

2. Place the generator set master switch in the OFF/


RESET position.
If a fogging agent is not available perform the following:
1. Remove the spark plugs.
2. Pour one tablespoon of engine oil into each spark
plug hole. Install the spark plugs and ground the
spark plug leads. Do not connect the leads to the
plugs.
3. Toggle the generator set master switch to crank the
engine two or three revolutions to lubricate the
cylinders.

2. Stop the generator set.

2.8.4

3. With the engine still warm, drain the oil from the
crankcase.

Prepare the exterior for storage as follows:

4. Remove and replace the oil filter.


5. Refill the crankcase with oil suited to the climate.
6. Run the generator set for two minutes to distribute
the clean oil.

Exterior

1. Clean the exterior surface of the generator set.


2. Seal all engine openings except for the air intake
with nonabsorbent adhesive tape.
3. To prevent impurities from entering the air intake
and to allow moisture to escape from the engine,
secure a cloth over the air intake.

7. Stop the generator set.


4. Mask electrical connections.
8. Check the oil level and adjust, if needed.

2.8.2

Fuel System

Prepare the fuel system for storage as follows:


1. Start the generator set.
2. With the generator set running, shut off the gas
supply.

5. Spread a light film of oil over unpainted metallic


surfaces to inhibit rust and corrosion.

2.8.5

Battery

Perform battery storage after all other storage


procedures.
1. Place the generator set master switch in the OFF/
RESET position.

3. Run the generator set until the engine stops.


2. Disconnect the battery(ies), negative (--) lead first.
4. Place the generator set master switch in the OFF/
RESET position.

2.8.3

Internal Engine Components


(Gas/Gasoline-Fueled Engines)

If you have access to a fogging agent or SAE 10 oil,


prepare the pistons and cylinders for storage as follows:
1. While the engine is running, spray a fogging agent
or SAE 10 engine oil into the air intake for about two
minutes until the engine stops.

26

Section 2 Scheduled Maintenance

3. Clean the battery. Refer to 2.7, Battery, for the


battery cleaning procedure.
4. Place the battery in a cool, dry location.
5. Connect the battery to a float/equalize battery
charger or charge it monthly with a trickle battery
charger.
Refer to the battery charger
manufacturers recommendations.
Maintain a full charge to extend battery life.

TP-6196 10/09

Section 3 Troubleshooting
! Blown fuses. Fuses in the wiring harness protect the

3.1 Introduction
Corrective action and testing in many cases requires
knowledge of electrical systems and electronic circuits.
Have an authorized distributor/dealer or trained service
technician perform testing and service.

controller, SCR module, and relay interface board. A


battery charger fuse is located in the positive battery
lead. Always check and replace the fuses before
replacing other components.
! Incorrect controller settings.

Refer to the engine service manual for engine service


information. See List of Related Materials for the
document part number.
If the troubleshooting procedures in this section identify
a bad part, refer to the parts catalog for replacement part
numbers. See the List of Related Materials in the
Introduction for the parts catalog number.

3.2 Initial Checks


When troubleshooting, always check for simple
problems first. Check for the following common
problems before replacing parts:
! Loose connections or damaged wiring.
! Dead battery.
! Fault shutdown.

Check for a fault code on the


controller display. Section 4.4 describes the warning
and shutdown fault codes.

Always check the


controller configuration settings before replacing the
controller. Section 4.5 contains the instructions for
checking and changing the controller configuration.

! Inadequate fuel supply.

Check for damaged


primary or secondary fuel regulators, loose
connections to the fuel solenoid valve, a damaged or
closed fuel shutoff valve, an empty LP fuel tank, or
other problems with the fuel supply. Check the fuel
supply pressure to the generator set.
See
Section 6.12, Fuel Systems.

3.3 Troubleshooting Chart


Use the following table as a reference in troubleshooting
individual problems. Generator set faults are listed in
groups and include likely causes and remedies. The
simplest and most likely causes of the problem are listed
first; follow the recommendations in the order shown.
The reference column provides additional sources of
information in this and related manuals regarding the
problem and solution.

Troubleshooting Chart
Problem
Possible Cause
Weak or dead battery
Generator
set does not
crank
Battery connections
Open circuit in
engine/controller
connections

Corrective Action
Recharge or replace battery.
If battery is weak or dead, check battery charger fuse, power
supply, and operation.

Reference
Generator Set
O/M

Check for reversed or poor battery connections.


Check for loose connections.
Check the wire harness continuity.

Section 6.15
Section 8

Blown fuse F3, controller Replace fuse; if fuse blows again, check circuit and components. Section 6.13
Section 8
Blown fuse F2, relay
interface board (RIB)

TP-6196 10/09

Replace fuse.
If fuse blows again, disconnect the board leads one at a time to
identify the cause of the blown fuse:
Lead 70A at the fuel valve
Lead IGN at the ignition module
Lead 71A at the starter relay
Leads FP and FN at the rotor
Repair or replace the component causing the blown fuse.

Section 6.13
Section 8,
ADV-6835

If fuse continues to blow and the previous step did not identify
the cause, check the continuity of leads FP and FN and the
leads from the P14 connector. Replace any bad leads. Use a
pin pusher to remove leads from the connector, if necessary. If
replacing the leads does not solve the problem, replace the RIB.

Section 8,
ADV-6835
Section 4.8 or
5.7

Section 3 Troubleshooting

27

Troubleshooting Chart, continued


Problem
Generator
set does not
crank,
continued

Possible Cause
Crank relay on relay
interface board
(ADC 2100)

Crank relay K3 on
controller circuit board
(ADC-RES)

Blown fuse F2
(ADC-RES)

Generator set master


switch
Poor ground (--)
connection
Starter relay

Starter

Cranks but
does not
start

28

Corrective Action

Reference

Check connections to the RIB. Check for 12VDC to the RIB on


lead 71N.

Section 4.8 or
5.7; Section 8

Check for a good ground connection (lead 16N)


Check crank relay K2 operation (LED3). Replace the RIB if relay
does not operate.
Check connections to the controller.

Section 8
Section 4.8 or
5.7
Section 5.7
Section 8

Check for a good ground connection.


Section 8
Check LED3 to verify 12 VDC to relay K3.
Section 5.7
If LED3 is not lit, check for 12 VDC to the board.
If LED3 is lit but the relay does not operate, replace the controller
circuit board.
Replace fuse.
If fuse blows again, disconnect the leads one at a time to identify
the cause of the blown fuse:
" Lead 70C at the fuel valve.
" Lead IGN at the ignition module
" Lead 71A at the starter relay
" Leads FP and FN at the rotor
" Repair or replace the component causing the blown fuse.
If fuse continues to blow and the previous step did not identify
the cause, check the continuity of leads FP and FN and the
leads from the P14 connector. Replace any bad leads. Use a
pin pusher to remove leads from the connector, if necessary. If
replacing the leads does not solve the problem, replace the
controller circuit board.
Check connections to the master switch.
Test function of master switch.
Clean and retighten.

Section 6.13
Section 8,
ADV-7325

Check connections to the starter relay.


Check continuity of circuit.

Section 1.7
Section 6.15
Section 8

Check that the starter relay picks up when 12VDC is applied at


lead 71A connection.

Section 8

Check starter connections.

Section 1.7
Section 8

Rebuild or replace starter.

Engine Service
Manual (S/M)

Section 8,
ADV-7325
Section 4.8 or
5.7

Section 6.15
Section 6.15

Controller

Check controller connections and operation. Check for power to Section 4 or 5


the controller. Move generator set master switch to OFF/RESET Section 8
and then to RUN.

No fuel
Insufficient fuel pressure

Open (turn on) manual fuel valve. Check fuel supply tank (LP).
Check fuel pressure to the generator set. Verify adequate fuel
pressure and pipe size for the generator set plus all other gas
appliances.

Section 6.12.3

Fuel regulator/valve

Check regulator/valve operation.

Section 6.12
4

Spark plugs or spark


plug connections

Check spark plug wires and connections. Replace or clean and


regap spark plugs.

Section 2.3

Loose connection or
open circuit

Check for loose or open connection at the fuel valve (lead 70A)
and at the engine spark control module (leads IGN and 70A).
Check controller/engine wiring continuity.

Section 8

Section 3 Troubleshooting

TP-6196 10/09

Troubleshooting Chart, continued


Problem
Cranks but
does not
start,
continued

Starts hard

Starts but
shuts down
Stops
suddenly

TP-6196 10/09

Possible Cause
Air cleaner clogged
Magnetic pickup

Corrective Action
Clean or replace.
Check for 1.75 volts or higher from the magnetic pickup during
cranking. A lower signal will cause the stepper motor to open
and close during cranking.

Reference
Section 2.4
Section 6.9.4

Incorrect controller
configuration

Check for correct controller configuration settings.

Section4.5 or
5.5

Ignition system spark


control or ignition coil

Test and/or replace components.

Engine S/M

Digital spark advance


ignition (DSAI)
connections
(12kW only)

Connect for natural gas. Disconnect for LP.


Check for loose connections.

Section 6.12.5

No engine rotation
sensed (check for an
overcrank fault
shutdown)

Check mag pickup connections, mag pickup gap, and operation. Section 6.9.4
Check for locked rotor.

Section 6.4

Low battery voltage

Check battery voltage and battery charger connections, power


supply, and operation.

Generator Set
O/M

Air cleaner clogged


Fuel mixture adjustment
incorrect

Replace element.
Adjust fuel valve.

Section 2.4
Section 6.12

DSAI leads incorrectly


connected or
disconnected
(12kW only)

Connect for natural gas. Disconnect for LP.

Section 6.12.5

Spark plug(s)
Spark plug wire(s)

Replace or regap spark plug(s).


Check spark plug wires and connections. Replace spark plug
wires.

Section 2.3
Engine S/M

Ignition components
(spark control or ignition
module)

Test/replace ignition components.

Engine S/M

Insufficient fuel pressure Check fuel pressure.


Worn piston rings, valves Check compression.
Fault shutdown
Check for a fault shutdown code on the controllers LED display.
Correct the fault and then move the generator set master switch
to OFF/RESET to reset the controller.

Section 6.12.3
Engine S/M
Section 4.4 or
5.4
Section 6.11
Section 4.4 or
5.4
Section 6.11

Fault shutdown

Check for a fault shutdown code on the controllers LED display.


Correct the fault and then move the generator set master switch
to OFF/RESET to reset the controller.

No fuel
Fuel line restriction
Fuel lines too long
Air cleaner clogged
Blown fuse

Turn on fuel supply.


Inspect fuel lines.
Check fuel line length.
Replace element.
Check fuses F1, F2 and F3. Replace any blown fuses. If fuse
blows again, test generator components.

Section 6.12.1
Section 2.4
Section 6.13

Spark plug(s)
Engine overheated
(hot engine only)

Replace and regap plug(s).


Check air intake, fuel adjustment, oil level, air inlet/ outlet.

Engine S/M
Section 2.5
Section 2.2
Section 6.12

Low oil pressure (LOP)


switch

Attempt startup. If unit shuts down, remove lead from LOP switch Section 2.2.1
and reset controller. A successful restart attempt indicates a
Section 6.11.2
faulty LOP shutdown switch.
Note: Check engine oil pressure before performing test and/or
replacing LOP shutdown switch.

Section 3 Troubleshooting

29

Troubleshooting Chart, continued


Problem
Stops
suddenly,
continued

Operates
erratically

Lacks
power

Lacks
power,
continued
30

Possible Cause
Fuel valve/fuel regulator

Corrective Action
Check regulator/valve operation.

Reference
Section 2
Section 7

Engine overloaded
Loss of generator output
voltage to controller

Reduce electrical load.


Check connections at P15 plug.
Check continuity of AC sensing leads 11 and 44.

Section 8

Magnetic pickup
connections

Check for loose connections to the mag pickup.

Section 6.9

Ignition module

Test and/or replace.

Engine S/M

K3 (flash) relay on RIB.


(ADC 2100)
K3 (flash) relay on
controller board
(ADC-RES)

Check for Flash LED illumination. Check fuse F2. Replace relay Section 4.8
board.
Check for Flash LED1 illumination. Check fuse F2. If LED1 is lit Section 5.7
but relay does not operate, replace controller board.

Air cleaner clogged


Spark plug(s)
Spark plug wire(s)
DSAI leads incorrectly
connected or
disconnected
(12kW only)

Replace element.
Replace and regap plugs.
Replace spark plug wires.
Connect for natural gas. Disconnect for LP.

Section 2.4
Section 2.3
Engine S/M
Section 6.12.5

Fuel line restriction


Fuel mixture adjustment
incorrect

Check fuel lines.


Check and/or adjust.

Section 6.12.1
Section 6.12

Magnetic pickup
connections

Check for loose connections to the mag pickup.

Section 6.9

Governor adjustment
incorrect

Adjust governor stability.

Section 6.9 or
6.10

Ignition system
Inadequate cooling
(hot engine only)

Test and/or replace components.


Inspect air inlet and outlet.

Engine S/M
Section 2.5

Carbon buildup in engine Clean cylinder head.


Engine valves not
Check cylinder pressures with leakdown test. Inspect valves
seating correctly
and valve seats.

Engine S/M
Engine S/M

Air intake restriction,


inadequate cooling

Inspect air intakes and exhaust for obstructions.


Check air cleaner.

Section 2.5
Section 2.4

Generator overloaded
Spark plug(s)
Spark plug wire(s)
DSAI leads incorrectly
connected or
disconnected
(12kW only)

Reduce load.
Replace and regap plug(s).
Replace spark plug wires.
Connect for natural gas. Disconnect for LP.

Section 2.3
Engine S/M
Section 6.12.5

Insufficient fuel pressure


Fuel line restriction
Fuel regulator
Engine not running at
rated rpm

Check fuel pressure at carburetor outlet.


Check fuel pipe size.
Check function of fuel regulator.
Check controller settings for unit configuration (UC) and engine
type (EC).
Adjust governor speed.

Section 6.12
Section 6.12
Section 6.12
Section 4.5 or
Section 5.5
Section 6.9 or
6.10

Engine power loss

Refer to the engine service manual for troubleshooting and


repair instructions.

Engine S/M

Governor malfunction or
misadjustment

Test/readjust governor.

Section 6.9 or
6.10

Ignition system

Test and/or replace.

Engine S/M

Section 3 Troubleshooting

TP-6196 10/09

Troubleshooting Chart, continued


Problem
Overheats

Possible Cause
Inadequate cooling
Fuel mixture adjustment
incorrect

Corrective Action
Inspect cooling system for air intake obstructions.
Readjust fuel mixture.
Note: Adjusting the fuel mixture may void the emission
certification.

Reference
Section 2.5
Section 6.12

Low output
or
excessive
drop in
voltage

Generator overloaded
Incorrect controller
configuration

Reduce load.
Check and adjust the controller configuration parameters.

Section 4.5 or
5.5

Incorrect controller
voltage settings

Check and adjust the controller voltage settings.

Section 4.5.3 or
5.6

Alternator or control
system

Perform separate excitation procedure to isolate problem to the


alternator or the control system.

Section 6.2

SCR module

Check wiring and connections to the SCR module.


Check auxiliary winding fuse F1.
Replace SCR module and test voltage.

Section 6.13
Section 6.8

Controller

Check controller settings. Check controller fuse, wiring and


connections.
Before replacing controller, replace SCR module and test
voltage.

Section 4.5 or
5.5
Section 6.8

Rotor (open, grounded,


or shorted windings)

Test and/or replace.

Section 6.4

Stator (open, grounded,


or shorted windings)

Test and/or replace.

Section 6.3

Brush connection

Check for loose brush connections.


Check the resistance through the brushes. Resistance through
the brushes should be low, 0.1--0.2 ohms without meter lead
resistance.

Section 6.6

Low engine speed


causing voltage roll-off

Check system voltage/frequency (Uu) and engine type (Ec)


parameters.
Adjust engine governor speed.

Section 4.5 or
5.5
Section 6.9 or
6.10
Engine S/M

Troubleshoot engine.
Light flicker

Voltage stability (gain)


setting

Check and adjust the voltage stability (gain) setting using the
controller keypad.

Section 4.5.3

High output
voltage

Incorrect controller
configuration

Check and adjust the controller configuration parameters.

Section 4.5 or
5.5

Incorrect controller
voltage settings

Check and adjust the controller voltage settings.

Section 4.5.3

Engine speed too high

Check engine speed using tachometer or frequency meter.


Adjust governor as necessary.

Section 6.9 or
6.10

Loose voltage sensing


connections

Check connections: stator leads 11 and 44 and P15 controller


connection.

Section 8

SCR module

Check wiring and connections to the SCR module.


Check auxiliary winding fuse F1 (lead 55).
Replace SCR module and recheck voltage.

Section 6.8
Section 6.13
Section 6.8

Controller

Check fuses, wiring and connections. Before replacing


controller, replace SCR module and test voltage.

Section 4.9

TP-6196 10/09

Section 3 Troubleshooting

31

Troubleshooting Chart, continued


Problem
No output
voltage

Noisy
operation

32

Possible Cause
Corrective Action
AC output circuit breaker Check for AC voltage on the generator side of circuit breaker. If
open
there is AC voltage on the generator side of the breaker, then a
problem in the load circuits is causing the line circuit breaker to
trip. Check for and correct short circuits or overloading on the
load side before resetting the circuit breaker.

Reference

Alternator or control
system

Perform separate excitation procedure to isolate the problem to


the alternator or the control system. Then troubleshoot the
alternator or control system components as follows.

Section 6.2

Aux. winding fuse F1


blown.

Check fuse F1 and replace if blown. If fuse blows again, check


stator.

Section 6.3

SCR module

Check auxiliary winding fuse F1.


Replace SCR module and test voltage.

Section 6.13
Section 6.8

Controller

Check controller settings. Check wiring and connections.


Before replacing controller, replace SCR module and check
voltage.

Section 4.5 or .
Section 6.8

Open wiring, terminal, or


pin in buildup circuit or
SCR module circuit

Check continuity.

Sections 6.13
Section 8

Brushes

Inspect brushes and replace if worn.


Check for brushes sticking in brush holder or broken brush
spring.

Section 6.6
Section 6.6

Rotor connections

Check for open circuit in rotor connection circuit (leads FN and


FP to SCR and RIB).

Section 8

Rotor slip rings dirty or


corroded

Check slip ring condition.

Section 6.4

Rotor (open, grounded,


or shorted windings)

Check voltage and continuity.

Section 6.4

Stator (open, grounded,


or shorted windings)

Check voltage and continuity.

Section 6.3

Flash relay (K3) on RIB


(ADC 2100)

Check flash LED on RIB.


Check fuse F2 and troubleshoot RIB.

Section 4.8

Flash relay (K3) on


controller board
(ADC-RES)

Check fuse F2.


Section 5.7
Check flash LED1 on controller board. If LED1 indicates power
to K3 but relay does not operate, replace controller circuit board.

Exhaust system leaks


Engine not running
smoothly

Check and replace as necessary.


See Generator set operates erratically in this table.

Section 2.6

Broken or damaged
vibromount(s)

Check and replace as necessary.

Section 7

Loose or vibrating sheet


metal/housing

Retighten screws, replace rivets.

Exhaust piping or air


inlets/outlets not
securely installed

Inspect for loose parts and secure if necessary.

Section 2.6

Excessive
engine/generator
vibration

Check, rotor, crankshaft, bearing, etc. (disassembly of engine


and/or alternator may be required).

Section 7
Engine S/M

Section 3 Troubleshooting

TP-6196 10/09

3.4 Controller Troubleshooting


Refer to the controller troubleshooting table in this
section when troubleshooting procedures in Section 3.3
indicate a possible controller problem. Always check
the ADC-RES controller configuration settings before
replacing the controller.
The installation manual
contains the instructions for checking and changing the
controller configuration.
Possible Cause
Controller

SCR module

Test
Check controller settings. *

Corrective Action
Adjust controller settings as required. *

Reference
Section 4.5 or
5.5

Check for power to the controller at


lead PF1.

Check/replace fuse F3. Check battery.

Section 8

Check controller fuse F3.

Replace controller fuse.

Section 8

Check controller wiring and


connections.

Tighten connections and/or replace


wiring.

Replace SCR module and recheck


voltage.

Replace the SCR module.

Section 6.8

Perform all tests listed under high


output voltage.

Replace the controller only if previous


steps do not solve the problem.

Section 4.9 or
5.9

Check wiring and connections to the


SCR module.

Tighten connections and/or replace


wiring to the SCR module.

Section 6.8

Test the SCR module using the


procedure in Section 6.8.

Replace the SCR module and recheck


voltage.

Section 6.8

Check auxiliary winding fuse F1


(lead 55).

Replace auxiliary winding fuse F1


(lead 55).

Section 8

* ADC-RES controller only.

TP-6196 10/09

Section 3 Troubleshooting

33

Notes

34

Section 3 Troubleshooting

TP-6196 10/09

Section 4 ADC 2100 and DC 2200 Controllers


4.1 Introduction
This section covers operation, configuration,
adjustment, and replacement of the ADC 2100 and
DC 2200 controller. See Section 3 for troubleshooting
procedures.

A silicon controlled rectifier (SCR) module works with


the controller to regulate the output voltage. See
Section 6.8.
A relay interface board (RIB) is used with the ADC
controller. Section 4.8 describes the standard and
optional RIBs.

See Figure 4-1 for the locations of the controller and


related components.
Section 4.2 describes the
controller keypad and display. Section 4.3 describes the
sequence of operation and faults are described in
Section 4.4. Controller configuration and adjustment
are covered in Section 4.5.

2
3
4

1
7

6
6

GM29253

1.
2.
3.
4.

Controller
SCR module
Ground stud
L0 stud

Figure 4-1

5.
6.
7.
8.

Relay interface board (RIB)


Line circuit breaker (load connection)
Engine harness-to-controller connection
Generator set master switch

Advanced Digital Control (ADC 2100)

TP-6196 10/09

Section 4 ADC 2100 and DC 2200 Controllers

35

4.2 Controller Display and Keypad


The ADC 2100 controller has an LED display and a
three-button keypad. See Figure 4-2. The DC 2200
controller has a display, but no keypad. See Figure 4-3.
The LED display shows runtime hours, fault codes,
application program version number, or controller
parameters during configuration and adjustment. See
Figure 4-4.

Controller Display
Item

Description

Crank
indication

Displays CC_1, CC_2, or CC_3 to


indicate the first, second or third attempt
to start the engine. The last digit
flashes during the crank cycle rest
periods.

Runtime hours

Displays total generator set runtime


hours when no other code is displayed.

Fault codes

Flashes a 2- or 3-letter fault code to


indicate various fault conditions. See
Section 4.4.

System
parameters

Displays 2-letter codes or 4-digit


alphanumeric codes during system
configuration or adjustment. See
Section 4.5.

1
3
2

Application
ADC 2100: Displays the version
program
number of the controllers application
version number program before entering the
configuration or adjustment mode. See
Section 4.5.4.
DC 2200: Application program version
number is displayed at controller
powerup.

Figure 4-4

4
1.
2.
3.
4.

GM28707A-C

LED display
Select button (use for setup and adjustment only)
Up and down arrow buttons (use for setup and adjustment only)
Generator set master switch

Figure 4-2

Controller LED Display

The ADC 2100 keypad is used to enter the controllers


configuration and adjustment menus and to change the
controller settings. A password key sequence is
required to enter the configuration and adjustment
menus. Section 4.5 contains the instructions to enter
the configuration and adjustment menus and change
the settings using the controller keypad.

ADC 2100 Controller


1

GM39579

4
1. LED display
2. Generator set master switch

Figure 4-3

36

DC 2200 Controller

Section 4 ADC 2100 and DC 2200 Controllers

TP-6196 10/09

4.3 Sequence of Operation

4.3.3

The following sections describe the controller sequence


of operation during generator start, run, stop, and fault
shutdown modes. Use this as a starting point for
controller and relay board fault identification. Refer to
the wiring diagrams in Section 8 to assist in the
troubleshooting procedure.

When the engine speed reaches 750 rpm, the crank


relay deenergizes and the crank LED (3) turns off.
When the output voltage on leads 11 and 44 reaches
about 30 VAC, the flash relay deenergizes and the flash
LED (2) turns off.

4.3.4
4.3.1

Starting Sequence, Master Switch


Moved to RUN

When the master switch is moved to the RUN position,


there is a delay of about 2 seconds before the controller
attempts to start the engine. The electronic governor
moves to its start position. The run relay energizes and
the run LED (1) turns on. The crank and flash relays
energize and the corresponding LEDs (2 and 3) turn on
0.5 seconds later. The controller display indicates the
crank cycle 1 code, CC 1.
The controller attempts to start the generator set three
times (three crank cycles, 15 seconds crank and 15
seconds off). If the generator set does not start in three
attempts, the system shuts down on an overcrank fault.
When the engine comes up to speed, the low oil
pressure switch contacts open.
Note: The controller circuit board prevents fault
shutdowns during startup until the crank
disconnect relay energizes.
The cyclic cranking cycle is programmed into the
controllers application code and is not adjustable in the
field.
The factory sets the cranking cycle for three cycles of
15 seconds on time and 15 seconds off time. If the
cranking cycle seems shorter than the factory setting,
check the engine starting battery.

4.3.2

Starting Sequence, Remote Start

Running Sequence

Stopping Sequence, Master


Switch Moved to OFF/RESET

Place the generator master switch in the OFF/RESET


position. The run relay deenergizes and the run LED (1)
turns off. The generator set stops.

4.3.5

Stopping Sequence, Remote Stop

When the remote start contacts open, the run relay


deenergizes and the run LED (1) turns off, but the
controller does not power down. The controller remains
powered and displays the engine runtime hours.
Note: Disconnecting the P7 jumper (if equipped) on the
back of the controller will allow the controller to
power down 48 hours after generator set
shutdown. See Section 4.6, Continuous Power
Mode.

4.4 Faults
4.4.1

Warnings

The fault conditions listed in Figure 4-5 will cause the


controller to display a fault code but will not shut down
the generator set.

4.4.2

Shutdowns

Under the fault conditions listed in Figure 4-6, the


controller displays a fault code and the generator set
shuts down.

When the master switch is set to the AUTO position, the


generator set starts when the remote start switch or
transfer switch engine start contacts close.

Always identify and correct the cause of a fault


shutdown before restarting the generator set. Refer to
Section 3, Troubleshooting, for instructions to identify
and correct the cause of the fault.

The start sequence proceeds as described in


Section 4.3.1, Starting Sequence, Master Switch
Moved to RUN.

Move the generator set master switch to the


OFF/RESET position to reset the controller after a fault

TP-6196 10/09

Section 4 ADC 2100 and DC 2200 Controllers

37

shutdown. Then move the switch to the AUTO or RUN


position.
Generator sets with serial numbers below 2051415
were built with controllers equipped with the continuous
power mode jumper. If the power jumper is removed

and the controller powers down after a fault shutdown,


move the master switch to OFF/RESET and then to
RUN to display the fault code. Then move the switch to
OFF/RESET again to clear the fault. See Section 4.6 for
more information on the continuous power mode
jumper.

Description
Code Fault
HB
High battery
Fault code is displayed if the engine starting battery voltage
voltage warning rises above 16 VDC for a 12 VDC system or above 30 VDC
for a 24 VDC system for more than one minute when the
engine is not running. This fault condition does not inhibit
engine starting.

Check
Check the battery rating and
condition.
Check the battery charger
operation.

The fault condition clears when the battery voltage returns to


a voltage within the limits for more than 10 seconds.
LB

Low battery
Fault code is displayed if the engine starting battery voltage
voltage warning falls below 8 VDC for a 12 VDC system or below 16 VDC for
a 24 VDC system for more than one minute when the engine
is not running. This fault condition does not inhibit engine
starting.
The fault condition clears when the battery voltage returns to
a voltage within the limits for more than 10 seconds.

Figure 4-5

38

Check the battery rating and


condition.
Check the battery charger
operation.
Charge or replace the battery.

Fault Warning Codes

Section 4 ADC 2100 and DC 2200 Controllers

TP-6196 10/09

Code Fault

Description

Check

Refer to
Section

AF

Auxiliary fault

Not used on these models.

HE

High engine
temperature

Shutdown occurs if the engine coolant


temperature exceeds the maximum
temperature for more than 5 seconds.
This protective becomes active after the
engine reaches crank disconnect speed.

Check for blocked air inlets and exhaust outlets.

1.7

LCL

Low coolant
level

Not used on air-cooled models.

LOC

Loss of coolant

Not used on air-cooled models.

LOP

Low oil
pressure

Shutdown occurs if a low oil pressure


condition exists for more than 5 seconds.
This protective becomes active
30 seconds after the engine has reached
crank disconnect speed (30 second
inhibit).

Check for leaks in the lubrication system.

2.2

Check the oil level and add oil if the level is low.

2.2

Check low oil pressure switch connections and


operation.

6.11.2

Check the oil pump and lubrication system.

Engine
S/M

Shutdown occurs after 3 unsuccessful


starting attempts. The crank cycle is set
for three starting attempts of 15 seconds
cranking and 15 seconds rest.

Check the fuel supply valves and pressure.

6.12

Check spark plug and battery.

2.3

See Troubleshooting Chart, generator set cranks


but does not start.

3.3

The generator set shuts down on an


overcrank fault if no engine rotation is
sensed. Shuts down after 3 seconds of
cranking or 1 second after the fault is
detected.

Check mag pickup connections and operation.

6.9.4

Check for a locked rotor.

6.4

Shutdown occurs when the governed


frequency exceeds 110% of the systems
frequency setpoint for more than 5
seconds. This protective becomes active
10 seconds after engine start (10 second
inhibit).

Check system frequency setting (parameter UU)


on controller.

4.5

Measure output frequency and adjust, if


necessary.

6.9.5

Note: The low oil pressure shutdown


does not protect against low oil level.
Check the oil level at the engine.
OC

OF

OS

OU *

UF

UU *

Overcrank

Overfrequency

Overspeed

Shutdown occurs if the engine speed


exceeds 115% of the normal running
speed for more than 0.3 seconds.
Overvoltage
Shutdown occurs if the voltage exceeds
120% of the system nominal voltage for
more than 2 seconds.
Underfrequency Shutdown occurs when the governed
frequency falls blow 90% of the nominal
system frequency for more than
5 seconds. This protective becomes
active 10 seconds after engine start
(10 second inhibit).
Undervoltage

Check governor system condition and operation.

6.9

Check AC voltage.

6.7

Check wiring and connections.

Reduce the load and restart the generator set.

Shutdown occurs if the voltage falls below Reduce the load and restart the generator set.
80% of the nominal system voltage for
Check wiring and connections.
more than 10 seconds.
Check controller configuration, system voltage
and frequency (parameter UU).

Replace the SCR module and test voltage again.

Software
Communication
Fault 0

6.9

Check governor settings and operation.

Check AC voltage and adjust, if necessary.

SCF0

6.11

Indicates a software or communication


problem within the ADC 2100

8
4.5
6.7
6.8

Separately excite unit.

6.2

Check stator continuity.

6.3

Replace the controller.

4.9

* Not applicable on DC 2200 controllers with software versions below 1.26. DC 2200 software version number is displayed on controller
powerup.

Figure 4-6

Fault Shutdown Codes

TP-6196 10/09

Section 4 ADC 2100 and DC 2200 Controllers

39

4.5 ADC 2100 Controller


Configuration and Adjustment
Note: The settings described in this section are not
adjustable on the DC 2200 cotnroller.
The first step in troubleshooting the controller is to verify
that the controller is correctly configured for the
generator set. The controllers configuration modes
allow setting of the engine type, generator set
configuration (marine, mobile, or standby), data input
types, and other parameters.
The controller configuration for each generator model is
set at the factory.
Changes in the controller
configuration may be required after controller
replacement or other service. Use the instructions in the
following section to check the controller settings and
change them, if necessary.

4.5.1

Controller Time Out

The controller will automatically exit the configuration


mode without saving any changes after about 1 minute
if no buttons are pressed. Start the configuration
procedure again from the beginning if the controller exits
the configuration mode before the settings have been
saved.

changed during generator set service or controller


replacement.
The controllers configuration mode allows adjustment
of the system parameters listed in this section. The
system voltage and frequency and unit configuration
and engine type are factory-set for each type of
generator set and engine and should not require
changes unless the controller is replaced.
The controllers advanced configuration mode allows
the user to set the data input type for engine senders,
toggle the battery voltage between 12 and 24 volts, and
change the controller communications setting for
optional meters (not offered for standby models). Check
these settings after controller replacement and change
them, if necessary, to match the settings shown in
Figure 4-7.
Follow the instructions in Figure 4-8 to enter the
configuration mode while the engine is not running and
then step through the following parameters. Use the up
() and down ) arrow buttons to select the appropriate
setting for the application.
Note: Be sure to save your settings before exiting the
configuration mode. The controller reverts to the
last saved settings when the master switch is
moved to the OFF/RESET position.

Changes in voltage and speed adjustments are also lost


if they are not saved before the generator set shuts
down. The generator set continues to run with the new
settings until it shuts down but then reverts to the
previous settings at the next startup. Be sure to save
your changes immediately after making adjustments.

Voltage/frequency setting (Uu). Select the system


voltage and frequency from the table in Figure 4-7.

4.5.2

Unit configuration (Uc). This parameter sets the


generator set type: marine, standby, or mobile.

Controller Configuration

The controller configuration is factory-set and should


not normally require changes in the field. However, the
controller configuration may need to be checked or
Parameter

Setting

Units system voltage


and frequency.

Note: This parameter sets the nominal system voltage


and frequency. To adjust the output (measured)
voltage and frequency, see Section 4.5.3,
Figure 4-11 and Figure 4-12.

Engine configuration (Ec). The engine configuration


must match the generator set engine type.

Definition

Uu00

Single phase, 60 Hz, 120 VAC

Uu01 *

Single phase, 60 Hz, 120/240 VAC

Uu05

Single phase, 50 Hz, 115 VAC

Uu06 *

Single phase, 50 Hz, 115/230 VAC

Unit configuration

Uc01 *

Standby

Engine type

Ec00 *

8.5/12RES

Engine data input types

Ed05 *

Digital low coolant level, digital pressure, analog temp, with mag. pickup

Bt12 *

Battery voltage 12 VDC

Cn00 *

No CAN communications

Communications

* Factory settings. Choose 50 or 60 hz setting for Uu as required for generator set frequency .

Figure 4-7
40

ADC 2100 Controller Configuration Parameters

Section 4 ADC 2100 and DC 2200 Controllers

TP-6196 10/09

Advanced configuration mode (Adnc). The data


input types, battery voltage, and communications
setting can be changed in the advanced configuration
mode. Press the up arrow button when Adnc is
displayed to enter the advanced configuration mode.
Engine data input types (Ed). This setting defines the
type of senders used on the generator set engine.
Battery voltage (Bt). This setting toggles between 12
and 24 VDC for the engine starting battery voltage.
Communications setting (Cn). This setting allows the
user to set the controller for communication with
optional meters, which are available for marine and
mobile units only.

4.5.3

Voltage and Frequency


Adjustments

The flowchart in Figure 4-12 outlines the procedures for


using the ADC controller to adjust the output voltage and
engine speed (frequency). Voltage and/or frequency
adjustments may be required after controller
replacement or other service procedures.

TP-6196 10/09

The generator set must be running during these


adjustments.
Use a multimeter to measure the
generator set output voltage and frequency during
adjustments.
Refer to Sections 6.7.2, Voltage
Adjustment, and 6.9.5, Frequency Adjustment, for
instructions to measure the output voltage and
frequency.
Note: Be sure to save your settings before exiting the
configuration mode. The controller reverts to the
last saved settings when the master switch is
moved to the OFF/RESET position.

4.5.4

Controller Application Program

The ADC 2100 application program version number is


displayed on the LED screen during the key sequence to
enter the configuration mode. Hold the Select button
and move the generator set master switch to the RUN
position. After about 5 seconds, the application
program version number will be displayed on the
controller display. For example, 01.04 will be displayed
for program version 1.04.
The DC 2200 controller application program version
number is displayed at controller powerup.

Section 4 ADC 2100 and DC 2200 Controllers

41

Controller Configuration Mode:


Hold the Select button:

Display: *
Move the generator set master switch to the RUN
position. (The generator set engine will not start.)

Wait about 5 seconds until the display shows the


program version number. (The number may be
different than the one shown here.)

1 0 4

Press the down arrow key and then the up arrow


key 3 times to enter the configuration mode.
(This is the controller password.)

Uu 0 1

Now release the Select button.


Press:
or

To set the system voltage and frequency. See


Figure 4-7 for settings.

Uu 0 1

To step to the next parameter, unit configuration


Uc.
or

To set the unit configuration setting to Uc01, if


necessary.

Uc 0 1

To step to the next parameter, engine type Ec.

or

To set the engine type to Ec00, if necessary.

E c 0 0

To step to the next parameter, advanced


configuration mode or save mode selection.

Ad n c

Now either save your settings or enter the Advanced Configuration Mode to
set the engine data inputs, battery voltage, and communications.
Press:
To enter advanced configuration mode.
Go to Figure 4-9.

E d 0 5

To proceed to the save mode without


entering the advanced configuration mode.
Go to Figure 4-10.

S AV E

or
or

Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to
the last saved settings when the master switch is moved to the OFF/RESET position.
* Shaded boxes show which number in the controller display changes when the up or down arrow key is pressed.

Figure 4-8
42

Configuration Mode (system voltage/frequency, unit configuration, and engine type parameters)

Section 4 ADC 2100 and DC 2200 Controllers

TP-6196 10/09

Pressing the up arrow key at the Adnc display (See Figure 4-8) puts you into
the Advanced Configuration Mode.
Press:
or

To set the engine data input type to Ed05.

E d 0 5

To enter battery voltage selection mode.

or

To toggle between 12 and 24 VDC. Set this


parameter to 12 VDC.

B t 1 2

To enter communications selection mode.

or

To set the communications parameter to


Cn00.

C n 0 0

To enter SAVE mode. Go to Figure 4-10.

S AV E

Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to
the last saved settings when the master switch is moved to the OFF/RESET position.
Figure 4-9

Advanced Configuration Mode (engine data input types, battery voltage, and engine
communications)

There are 3 options when the display says SAVE:


Press:

S AV E

To return to the first parameter, system voltage/frequency


Uu, to check or change settings before saving. See
Figure 4-8.

Uu 0 1

or
To save changes.

Y E S

To discard changes without saving.

n o

Yes or no flashes when the up or down arrow is pressed


and then the controller exits the configuration mode. The
display returns to the runtime hours. *

x x x x

or

Now move the master switch to OFF/RESET.


* X in the runtime hours display above denotes any number from 0 to 9.
Figure 4-10 Save Mode (after configuring generator set parameters)

TP-6196 10/09

Section 4 ADC 2100 and DC 2200 Controllers

43

Output Voltage and Frequency Adjustment Mode:

Display :*

Move the generator set master switch to the RUN position. The generator set
engine starts and the controller display shows the engine runtime hours.

x x x x

Hold:

Wait about 5 seconds until the display changes from runtime hours
to the program version number.

x. x x

Press the down arrow key and then the up arrow key 3 times to enter the
adjustment mode. (This is the controller password.)

1 P x x

The controller is now in the voltage coarse adjustment mode.


Press:
or

To raise or lower the voltage in large increments


(approximately 5--7 volts per step).

1 P x x

To enter fine voltage adjustment mode.

1 P x x
or

To raise or lower the voltage in smaller increments


(approximately 0.5--0.7 volts per step).

To enter coarse voltage stability (gain) adjustment mode.

2 P x x
or

To raise or lower the voltage stability (gain) in large


increments.

To enter fine voltage stability (gain) adjustment mode.

2 P x x
or

To raise or lower the voltage stability (gain) in smaller


increments.

To enter volts/Hz adjustment mode.

3 P 0 x
or

To raise or lower the volts/Hz: 00=low; 09= high

Continued on Figure 4-12.


* Shaded boxes show which character in the controller display changes for each adjustment. X in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model.

TP6196

Figure 4-11 Output Voltage and Frequency Adjustments


44

Section 4 ADC 2100 and DC 2200 Controllers

TP-6196 10/09

Display : *

Continued from Figure 4-11:


Press:
To enter engine governor speed coarse adjustment
mode.
or

To raise or lower the engine speed in large


increments.

To enter engine governor speed fine


adjustment mode.
or

4 P x x

To raise or lower the engine speed in smaller


increments.

To enter engine governor stability (gain) coarse


adjustment mode.
or

5 P x x

To raise or lower the engine governor stability (gain)


in large increments.

To enter engine governor stability (gain) fine


adjustment mode.

or

4 P x x

5 P x x

To raise or lower the engine governor stability (gain)


in smaller increments.

To enter SAVE mode. Go to Figure 4-13.

S AV E

Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to
the last saved settings when the master switch is moved to the OFF/RESET position.
* Shaded boxes show which character in the controller display changes for each adjustment. X in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model.
Figure 4-12 Output Voltage and Frequency Adjustments, Continued

TP-6196 10/09

Section 4 ADC 2100 and DC 2200 Controllers

45

There are 3 options when the display says SAVE:


Press:

S AV E

To return to the first parameter, coarse voltage adjustment, to check


or change settings before saving. See Figure 4-8.

1 P x x

To save changes.

Y E S

To discard changes without saving.

n o

or

or

Yesor no flashes when the up or down arrow is pressed and


then the controller exits the configuration mode. The display
returns to the runtime hours.

x x x x

Now move the master switch to OFF/RESET.


Figure 4-13 Save Mode (after generator set and engine adjustments)

4.6 Continuous Power Mode


Jumper
Generator sets with serial numbers below 2051415
were built with controllers equipped with the continuous
power mode jumper.
See TT-1364, ADC 2100
Controller Replacement, for additional information.

WARNING

Disabling the generator set. Accidental starting can


cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.

Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.

46

Section 4 ADC 2100 and DC 2200 Controllers

TP-6196 10/09

A jumper across controller pins P7-1 and P7-2 maintains


power to the controller at all times. Controllers are
shipped with the jumper connected for continuous
power. See Figure 4-14.
Note: The controller is powered by the generator set
engine starting battery. The 8.5 and 12 RES
generator sets are equipped with factoryinstalled battery chargers to prevent battery
discharge.
The P7 connector has either 2 or 3 pins. Disconnecting
the jumper or moving the jumper to pins P7-2 and P7-3
allows the controller to power down automatically
48 hours after the generator set shuts down if the
generator set master switch is in the AUTO position. A
remote start signal (from a transfer switch or a remote
start/stop switch connected to controller leads 3 and 4)
or moving the generator set master switch to the RUN
position turns the controller back on.
Use the following procedure to disconnect the jumper, if
desired.

Procedure to disconnect the continuous power


mode jumper (optional).
Note: For most applications, it is not necessary to
disconnect the continuous power mode jumper.
1. Prevent the generator set from starting.
a. Move the generator set master switch to the
OFF/RESET position.
b. Disconnect power to the battery charger.
c. Disconnect the generator set engine starting
battery, negative (--) lead first.
2. Remove the controller from the generator set
housing.
a. Disconnect the engine wiring harness
connector P1 plug (35-pin) from the controller.
Disconnect the J15 and J16 connectors. See
Figure 4-14.
b. Remove the controller from the generator set
housing in order to access the back of the
controller.

2
1

3. Remove the controllers back cover to access the


jumper.
a. Note the labels on the three leads connected to
the generator set master switch for
reconnection later. Disconnect the leads at the
pink connectors. See Figure 4-14.
b. Remove the cover screws and remove the
controllers back cover. See Figure 4-14.
4. Locate the P7 connector near the top of the
controller. See Figure 4-14. Remove the jumper
from pins 1 and 2 of the P7 connector. If the P7
connector has three pins, connect the jumper
across pins 2 and 3 for storage.
5. Replace the controllers back cover and secure the
cover screws.

tp6196

8
1.
2.
3.
4.
5.
6.
7.
8.

Engine wiring harness connector plug (P1)


Continuous power mode jumper location (P7)
J15 connector
J16 connector
Generator set master switch
AUTO
VBAT
RUN

Figure 4-14 ADC 2100 (back cover removed)


TP-6196 10/09

6. Reconnect the three pink connectors to the


generator set master switch as shown in
Figure 4-14.
7. Reconnect the J15 and J16 connectors.
8. Reconnect the generator set engine starting
battery, negative (--) lead last.
9. Reconnect power to the battery charger.
10. Place the generator set master switch in the AUTO
position.
Section 4 ADC 2100 and DC 2200 Controllers

47

4.7 Master Switch


The generator set master switch is a three-position
(RUN\OFF/RESET\AUTO) rocker switch. The leads
connecting to the master switch are labeled RUN, VBAT,
and AUTO. Check that the three pink connectors are
connected to the terminals on the back of the switch as
shown in Figure 4-14. Be careful not to reverse the RUN
and AUTO leads.

The generator set may be equipped with an optional


RIB, which contains the K4 auxiliary run relay and K1
common fault relay in addition to the standard relays.
The optional relay board kit includes a wiring harness for
connection of customer equipment to the K1 and K4
relays. See Figure 4-16 for optional relay connections.
7
1

4
3

COMMON
K1 FAULT

4.8 Relay Interface Board (RIB)


D1

P13

D2

Refer to the schematic diagram in Section 8 for the


standard relay board connections.

K5

RUN

D7

K2
CRANK P14

D6

The standard relay interface board (RIB) contains the


K2 crank, K3 flash, and K5 run relays. Three LEDs
indicate relay operation. See Figure 4-15.

K4

AUX
RUN

3
D3

Repair or replace the component causing the blown


fuse.
If fuse continues to blow and disconnecting components
did not identify the cause, remove the leads from the
P14 connector using a pin pusher, part #241918 (large)
or 241919 (small). If replacing the leads does not solve
the problem, replace the RIB.
The individual relays are not replaceable. If one or more
relays are faulty, replace the entire RIB.
To replace the RIB:

FLASH

FP

T2

LED3
CRANK

LED1
RUN

R3

! Leads FP and FN at the rotor

K3

R2

! Lead 71A at the starter relay

LED2
FLASH
D5

! Lead IGN at the ignition module

T1
FN
VBAT
D4

! Lead 70A at the fuel valve

R1

The RIB is protected by a 10 amp fuse (F2) located in the


wiring harness. If the fuse blows repeatedly, disconnect
the board loads one at a time to identify the cause of the
blown fuse:

R
R

GM29779-A

6
1.
2.
3.
4.
5.
6.
7.

K1 common fault relay (optional)


K2 crank relay (standard)
K3 flash relay (standard)
K4 auxiliary run relay (optional)
K5 run relay (standard)
P14, engine harness connection (standard)
P13, connection to optional relay harness (optional)

Figure 4-15 Relay Board


Harness
Lead
Number
88
89
90
91
92
93

Connector
Pin Number Connection
6
Common fault normally open
2
Common fault common
3
Common fault normally closed
4
Run relay normally open
1
Run relay common
5
Run relay normally closed

1. Disconnect P14 and the brush leads FP and FN.


2. Pull the board straight off the mounting stand-offs.
3. Snap the new board onto the stand-offs and
reconnect P14 and the brush leads.

48

Section 4 ADC 2100 and DC 2200 Controllers

Figure 4-16 Optional Common Fault and Run Relay


Board Harness Connections

TP-6196 10/09

4.9 Controller Replacement

ADC 2100 Controller Replacement Procedure

If the troubleshooting procedures in Section 3 identify a


bad controller, use the procedure in this section for
controller replacement. Always check the controller
configuration, fuse, wiring, and connections before
replacing the controller. For output voltage problems,
replace the SCR module and check the operation again
before replacing the controller.

1. Remove the enclosure service-side door.


Figure 4-17.

After replacing the controller, verify that the new


controllers configuration settings match the generator
set system voltage and frequency, unit configuration,
engine type, engine data input types, battery voltage,
and communications settings. Refer to Section 4.5 for
instructions to check the controller configuration and to
change the settings, if necessary.

4. Disconnect power to the battery charger.

See

2. Place the generator set master switch in the OFF


position.
3. Remove 4 roof screws. Lift the roof up and off. See
Figure 4-17.

5. Disconnect the generator set engine starting


battery, negative (--) lead first.
1

After the controller configuration has been checked and


set to match the generator set, use a voltmeter to check
the generator set output voltage and frequency. If the
output voltage or frequency needs adjustment, use the
Voltage and Frequency Adjustment Procedure in
Section 6.7.2 and the controller voltage and speed
adjustment instructions in Section 4.5.3. Also see the
Frequency Adjustment Procedure in Section 6.9.5.

4
5

tp6196

1.
2.
3.
4.
5.

Roof
Roof locating pin
Roof screws (4 ea.)
Service-side door
Front panel

Figure 4-17 Enclosure Roof and Door

TP-6196 10/09

Section 4 ADC 2100 and DC 2200 Controllers

49

Note: Some versions of the controller mount from


inside the controller compartment. Others are
front-mounted.

1
3

6. For inside-mounted controllers:


a. Remove 5 screws to remove the front panel on
the air intake end of the enclosure. Remove the
plastic caps to access the 2 side screws. See
Figure 4-17.
b. Remove two screws to remove the cover from
the controller compartment. See Figure 4-18.
c. Disconnect wiring harness plugs P1, P15, and
P16 from the ADC controller. See Figure 4-19.
d. Loosen and remove four controller mounting
screws at the front of the controller. See
Figure 4-20. Remove the controller from the
compartment.
e. Place the new controller into position and install
the four mounting screws.
f. Attach connectors P1, P15, and P16 to the new
controller.
g. Replace the
compartment.

cover

on

the

tp6196

1. P1 35-pin connector
2. P15 3-pin connector
3. P16 6-pin connector

Figure 4-19 Controller Connections

controller

h. Replace the front panel on the air intake end of


the enclosure.
1

tp6196

1. Controller mounting screws (4 ea.)

Figure 4-20 Controller Mounting Screws


(inside-mounted controller shown)

tp6196

1. Cover screws

Figure 4-18 Controller Compartment Cover

50

Section 4 ADC 2100 and DC 2200 Controllers

TP-6196 10/09

7. For front-mounted controllers:


a. Remove four mounting screws from the front of
the controller.
b. Carefully pull the controller forward, angling it
so that the P1 connector on the right side clears
the opening in the mounting plate.
c. Disconnect plugs P1, P15, and P16 from the
ADC controller. See Figure 4-19.
d. Attach plugs P1, P15, and P16 to the new
controller.
e. Place the new controller into position and install
the four mounting screws.
8. Verify that the generator set master switch is in the
OFF position.
9. Reconnect the engine starting battery, negative (--)
lead last.
10. Reconnect power to the battery charger.

12. Follow the instructions in Section 4.5.2 to change


the new controllers configuration settings to match
the generator set system voltage and frequency,
unit configuration, engine type, engine data input
types, battery voltage, and communications
settings.
13. Use a voltmeter to check the output voltage. Follow
the instructions in Sections 4.5.3, Voltage and
Frequency Adjustments, and 6.7.2, Voltage
Adjustment, to adjust the output voltage and
stability.
14. Check the output frequency.
Follow the
instructions in Sections 4.5.3, Voltage and
Frequency Adjustments, and 6.9.5, Frequency
Adjustment, to adjust the output frequency and
stability.
15. Place the generator set master switch in the AUTO
position if an ATS or remote start/stop switch is
used.
16. Replace the enclosure door.

11. Replace the roof and tighten the four roof screws.

TP-6196 10/09

Section 4 ADC 2100 and DC 2200 Controllers

51

Notes

52

Section 4 ADC 2100 and DC 2200 Controllers

TP-6196 10/09

Section 5 ADC-RES and DC-RET Controller


See Figure 5-1 for the controller location.

5.1 Introduction
This section covers operation, configuration,
adjustment, and replacement of the ADC-RES and
DC-RET controllers. See Section 3 for troubleshooting
procedures.

11

8
9

10
12
1
7
2

6
5
5

Front View

1.
2.
3.
4.
5.
6.

GM57149

Controller display
Keypad (ADC-RES only; see Figure 5-2)
Generator set master switch (RUN-OFF/RESET-AUTO)
Line circuit breaker (load connection)
Fuses F1, F2, and F3
Serial port for communication connection (remove plug to access)

Figure 5-1

7.
8.
9.
10.
11.
12.

Logic board
Optional relay board location
L0 stud
Ground stud
Start relay
SCR module

Controller Components

TP-6196 10/09

Section 5 ADC-RES and DC-RET Controller

53

5.2 Controls and Display

The ADC-RES controller has an LED display and a


three-button keypad. See Figure 5-2. The DC-RET
controller has an LED display. See Figure 5-3.
A three-position generator set master switch is mounted
on the controller junction box.
1

GM57149

1. LED display
2. Generator set master switch (RUN--OFF/RESET-AUTO)

Figure 5-3
4

DC-RET Controller

The LED display is activated by a start or RUN


command as follows:
! Move the master switch to RUN.

GM57149

1.
2.
3.
4.

LED display
Select button (use for setup and adjustment only)
Up and down arrow buttons (use for setup and adjustment only)
Generator set master switch (RUN--OFF/RESET-AUTO)

Figure 5-2

5.2.1

ADC-RES Controller

Master Switch

The generator set master switch is a three-position


(RUN\OFF/RESET\AUTO) rocker switch.
See
Figure 5-2 or Figure 5-3 for the master switch location.
See Section 6.15 for master switch connections.

5.2.2

! With the master switch in AUTO, send a remote start

command (close the remote start contact across


leads 3 and 4).
The LED display indicates generator set status as
shown in Figure 5-5. When the generator set is running,
engine runtime hours are shown.
When the generator set is running, the arrow keys on the
ADC-RES can be used to step through the other
displays as described in Section 5.2.3.
When the master switch is in AUTO, the display turns off
48 hours after generator set shutdown.

LED Display

The LED display shows runtime hours, fault codes,


application program version number, or controller
parameters during configuration and adjustment. See
Figure 5-4.

54

Section 5 ADC-RES and DC-RET Controller

TP-6196 10/09

Control or Indicator

Item

Description

LED display

Runtime hours

Displays total generator set runtime hours while the generator set is running
and when no other codes are displayed.

Metering display
(ADC-RES only)

Displays AC voltage (output), frequency, and battery voltage. Press the up or


down arrow when runtime hours are displayed to step through these displays.

Crank indication

Displays CC_1, CC_2, or CC_3 to indicate the first, second, or third attempt to
start the engine. The last digit flashes during the crank cycle rest periods.

Software version
number

ADC-RES: The software version number (v#.##) is displayed when entering


configuration mode. See the installation manual.
DC-RET: The software version number (v#.##) is displayed during the first
2 seconds of the crank cycle.

Fault codes

Flashes a 2- or 3-letter fault code to indicate various fault conditions.


See Section 4.4.

Keypad
(ADC-RES only)

Select and arrow


buttons

Use the arrow buttons to step through the data displays. See Section 5.2.3.
The keypad is also used for controller setup and adjustment. The setup and
adjustment functions are password-protected. Have setup and adjustments
performed only by an authorized distributor/dealer.

Generator set master


switch

Three-position
switch

Switch functions as the generator set operation and controller reset switch.

Figure 5-4

5.2.3

Controls and Indicators

Keypad

Engine Runtime
XXX.X hours

The three-button keypad is a feature of the ADC-RES


controller. The keypad is used to check system status,
change controller settings, and adjust the generator set
output voltage and frequency.

Output Voltage
VAC

When the generator set is running, press the up and


down arrow buttons to step through system status
displays as shown in Figure 5-5. After 10 seconds, the
display returns to engine runtime hours.

Output Frequency
Hz

Use the configuration and adjustment menus to change


controller settings and adjust the generator set output. A
password key sequence is required to enter the
configuration and adjustment menus. Section 4.5
contains the instructions to enter the configuration and
adjustment menus and change the settings using the
controller keypad.
The DC-RET controller is not equipped with a keypad.
DC-RET controllers are factory-set and not adjustable.

Battery Voltage
VDC
tp6515

Notes:
Generator set master switch in AUTO.
Step through using up or down arrow buttons.
After 10 seconds, display returns to runtime hours.

Figure 5-5

TP-6196 10/09

Generator Set Status Displays


(ADC-RES only)

Section 5 ADC-RES and DC-RET Controller

55

5.3 Sequence of Operation

5.3.3

The following sections describe the controller sequence


of operation during generator start, run, stop, and fault
shutdown modes. Use this as a starting point for
controller and relay board fault identification. Refer to
the wiring diagrams in Section 8 to assist in the
troubleshooting procedure.

When the engine speed reaches 750 rpm, the crank


relay deenergizes and the crank LED turns off. When
the output voltage on leads 11 and 44 reaches about
30 VAC, the flash relay deenergizes and the flash LED
turns off.

5.3.4
5.3.1

Starting Sequence, Master Switch


Moved to RUN

When the master switch is moved to the RUN position,


there is a delay of about 2 seconds before the controller
attempts to start the engine. The electronic governor
moves to its start position. The fuel (run) relay energizes
and the corresponding LED on the control board turns
on. (See Section 4.8 for relay information.) Then the
crank and flash relays energize and the corresponding
LEDs turn on. The controller display indicates the crank
cycle 1 code, CC 1.
The controller attempts to start the generator set three
times (three crank cycles, 15 seconds crank and 15
seconds off). If the generator set does not start in three
attempts, the system shuts down on an overcrank fault.
When the engine comes up to speed, the low oil
pressure switch contacts open.
Note: The controller circuit board prevents fault
shutdowns during startup until the crank
disconnect relay energizes.
The cyclic cranking cycle is programmed into the
controllers application code and is not adjustable in the
field.
The factory sets the cranking cycle for three cycles of
15 seconds on time and 15 seconds off time. If the
cranking cycle seems shorter than the factory setting,
check the engine starting battery.

5.3.2

Starting Sequence, Remote Start

The generator set master switch must be in the AUTO


position for remote start/stop by a remote switch or
automatic transfer switch.

Running Sequence

Stopping Sequence, Master


Switch Moved to OFF/RESET

Place the generator master switch in the OFF/RESET


position. The run relay deenergizes and the run LED (1)
turns off. The generator set stops.

5.3.5

Stopping Sequence, Remote Stop

The generator set master switch must be in the AUTO


position for remote start/stop by a remote switch or
automatic transfer switch.
When the remote start contact across leads 3 and 4
opens, the run relay deenergizes and the run LED (1)
turns off. The generator set stops.

5.3.6

Standby Mode

When the generator set master switch is in the AUTO


position, the controller is in standby mode. Engine
runtime hours are shown on the display. A remote start
signal (contact closure) will start and run the generator
set.
If there is no start signal for 48 hours, the controller goes
into sleep mode.

5.3.7

Sleep Mode

When the generator set master switch is in the AUTO


position, the controller powers down automatically if
there is no start signal for 48 hours after shutdown. The
controller display is dark and battery draw is minimized.
A remote start signal (from a transfer switch or a remote
start/stop switch connected to controller leads 3 and 4)
reactivates the controller. Moving the generator set
master switch to the RUN position also activates the
controller.

The remote start contact closes across engine start


leads 3 and 4 to start the generator set. The start
sequence proceeds as described in Section 4.3.1,
Starting Sequence, Master Switch Moved to RUN.

56

Section 5 ADC-RES and DC-RET Controller

TP-6196 10/09

5.4 Faults
5.4.1

Warnings

The fault conditions listed in Figure 5-6 will cause the


controller to display a fault code but will not shut down
the generator set.

5.4.2

Always identify and correct the cause of a fault


shutdown before restarting the generator set. Refer to
Section 3, Troubleshooting, for instructions to identify
and correct the cause of the fault.
Move the generator set master switch to the OFF/
RESET position to reset the controller after a fault
shutdown. Then move the switch to the AUTO or RUN
position.

Shutdowns

Under the fault conditions listed in Figure 5-7, the


controller displays a fault code and the generator set
shuts down.
Code Fault
Description
HB * High battery
Fault code is displayed if the engine starting battery voltage rises
voltage warning above 16 VDC for a 12 VDC system or above 30 VDC for a 24 VDC
system for more than one minute when the engine is not running. This
fault condition does not inhibit engine starting.
The fault condition clears when the battery voltage returns to a voltage
within the limits for more than 10 seconds.

Check
Check the battery rating
and condition.
Check the battery charger
operation.

LB

Check the battery rating


and condition.
Check the battery charger
operation.
Charge or replace the
battery.

Low battery
Fault code is displayed if the engine starting battery voltage falls below
voltage warning 8 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system
for more than one minute when the engine is not running. This fault
condition does not inhibit engine starting.
The fault condition clears when the battery voltage returns to a voltage
within the limits for more than 10 seconds.

* ADC-RES only

Figure 5-6

Fault Codes, Warnings

TP-6196 10/09

Section 5 ADC-RES and DC-RET Controller

57

Code Fault
AF
Auxiliary fault

Description
Indicates a shutdown initiated by the emergency stop
switch or a tripped circuit breaker.
(TRES models only)
Shutdown occurs if the engine coolant temperature
exceeds the maximum temperature for more than
5 seconds. This protective becomes active after the
engine reaches the crank disconnect speed.

Check
Check the position of the
emergency stop button.
(TRES models only)
Check for blocked air inlets and
exhaust outlets.

Shutdown occurs if a low oil pressure condition


exists for more than 5 seconds. This protective
becomes active 30 seconds after the engine has
reached crank disconnect speed (30 second inhibit).
Note: The low oil pressure shutdown does not
protect against low oil level. Check the oil level at
the engine.

Check for leaks in the lubrication


system.
Check the oil level and add oil if
the level is low.
Check low oil pressure switch
connections and operation.
Check the oil pump and
lubrication system.

2.2

Overcrank

Shutdown occurs after 3 unsuccessful starting


attempts. The crank cycle is set for three starting
attempts of 15 seconds cranking and 15 seconds
rest.

6.12
O/M
3.3

Locked rotor

The generator set shuts down on an overcrank fault


if no engine rotation is sensed. Shuts down 3
seconds after the fault is detected.

Check the fuel supply valves and


pressure.
Check spark plug and battery.
See Troubleshooting Chart,
generator set cranks but does not
start.
Check mag pickup connections
and operation.
Check for a locked rotor.

Overfrequency Shutdown occurs when the governed frequency


exceeds 110% of the systems frequency setpoint for
more than 5 seconds. This protective becomes
active 10 seconds after engine start (10 second
inhibit).

Check system frequency setting


(parameter UU) on controller.

4.5

Measure output frequency and


adjust, if necessary.

6.9.5

Check governor system condition


and operation.

6.9

Overspeed

Check governor settings and


operation.

6.9.5
6.9

Check AC voltage.
Check wiring and connections.
Reduce the load and restart the
generator set.

6.7
8W/D

Reduce the load and restart the


generator set.

Check wiring and connections.


Check controller configuration,
system voltage and frequency
(parameter UU).

8W/D
4.5

Check AC voltage and adjust, if


necessary.

6.7

HE

High engine
temperature

LOP

Low oil
pressure

OC

OF

OS

Refer to
Section

OU * Overvoltage

Shutdown occurs if the engine speed exceeds 110%


of the normal running speed for more than
0.3 seconds.
Shutdown occurs if the voltage exceeds 120% of the
system nominal voltage for more than 2 seconds.

UF

Underfrequency Shutdown occurs when the governed frequency falls


below 54 Hz for more than 5 seconds. This
protective becomes active 10 seconds after engine
start. (10 second inhibit).

UU

Undervoltage

Shutdown occurs if the voltage falls below 80% of


the nominal system voltage for more than 10
seconds.

O/M

1.7

6.11
Engine
S/M

6.9.4

Check the SCR module. Replace 6.8


if necessary and test voltage
again.

SCF0 Software
Indicates a software or communication problem
Communication within the ADC-RES.
Fault 0

Separately excite unit.


Check stator continuity.
Replace the controller.

6.2
6.3
4.9

Engine S/M = Engine Service Manual; O/M = Generator Set Operation Manual
* ADC-RES only

Figure 5-7
58

Fault Codes, Shutdowns

Section 5 ADC-RES and DC-RET Controller

TP-6196 10/09

5.5 Controller Configuration and


Adjustment, ADC-RES
Note: The settings described in this section are not
adjustable on the DC-RET cotnroller.
The first step in troubleshooting the controller is to verify
that the controller is correctly configured for the
generator set. The ADC-RES controllers configuration
modes allow setting of the engine type, generator set
configuration (marine, mobile, or standby), data input
types, and other parameters.
The controller configuration for each generator model is
set at the factory.
Changes in the controller
configuration may be required after controller
replacement or other service. Use the instructions in
Section 5.5.4 to check the controller settings and
change them, if necessary.

5.5.1

Controller Time Out

The controller will automatically exit the configuration


mode without saving any changes after about 1 minute
if no buttons are pressed. Start the configuration
procedure again from the beginning if the controller exits
the configuration mode before the settings have been
saved.

down. The generator set continues to run with the new


settings until it shuts down but then reverts to the
previous settings at the next startup. Be sure to save
your changes immediately after making adjustments.

5.5.2

Voltage and Frequency


Adjustments

Voltage and/or frequency adjustments may be required


after controller replacement or other service
procedures. See the instructions in Section 5.6 to adjust
the generator set output voltage and frequency using
the ADC-RES.

5.5.3

Controller Application Program


Version Number

The ADC-RES application program version number is


displayed on the LED screen during the key sequence to
enter the configuration mode. Hold the Select button
and move the generator set master switch to the RUN
position. After about 5 seconds, the application
program version number will be displayed on the
controller display. For example, 01.10 will be displayed
for program version 1.10.
The DC-RET application program version number is
displayed during the first 2 seconds of the crank cycle.

Changes in voltage and speed adjustments are also lost


if they are not saved before the generator set shuts

TP-6196 10/09

Section 5 ADC-RES and DC-RET Controller

59

5.5.4

System Parameters

The controller configuration for each generator model is


set at the factory and should not normally require
changes. The controllers configuration mode allows
adjustment of the system parameters listed in this
section. Use the instructions in this section to check the
configuration after installation and change them to
match the settings shown in Figure 5-8, if necessary.
Parameter
Units system
voltage and
frequency

Engine type
Communication
setting *

Setting
Uu01

Definition
Single phase, 60 Hz,
120/240 VAC

Uu03

Three-phase, 50 Hz,
230/400 VAC (TRES)

Uu06

Single phase, 50 Hz,


115/230 VAC

Ec00
Cn00

8.5/12 kW
No J1939 communication.
Sleep mode enabled
(48-hour power down in
AUTO).

Cn01 !

J1939 communication
enabled. Sleep mode
disabled (no power down in
AUTO).

* Controller application code version 1.13 or higher.


! Default setting for application code version 1.13 or higher.

Figure 5-8

Controller Configuration Parameters

Follow the instructions in Figure 5-10 to enter the


configuration mode while the engine is not running and
then step through the following parameters. Use the up
() and down () arrow buttons to select the appropriate
setting for the application. See Figure 5-9.
The controller will automatically exit the configuration
mode without saving any changes after about 1 minute
if no buttons are pressed. Start the configuration
procedure over again from the beginning if the controller
exits the configuration mode before the settings have
been saved.
Note: Be sure to save your settings before exiting the
configuration mode. The controller reverts to the
last saved settings when the master switch is
moved to the OFF/RESET position.

60

Section 5 ADC-RES and DC-RET Controller

Voltage/frequency setting (Uu). Select the system


voltage and frequency from the table in Figure 5-8.
Note: The Uu parameter sets the systems rated
voltage and frequency. To adjust the output
(measured) voltage and frequency, see Section
5.6, Voltage and Frequency Adjustments.
Engine configuration (Ec). The engine configuration
must match the generator set engine type.
Communication/Sleep Mode Setting (Cn). (Available
on controllers with application code version 1.13 or
higher.) The communication setting enables or disables
J1939 communication, and also disables or enables the
sleep mode. When J1939 communication is enabled,
the sleep mode is turned off to allow uninterrupted
communication with a personal computer running
remote monitoring software. If remote monitoring is not
used, the communication can be turned off, enabling the
sleep mode which causes the controller to power down
after 48 hours of inactivity. The generator set master
switch must be in AUTO for the sleep mode to function.
The default setting for controllers with application code
version 1.13 or higher is Cn01, communication on/sleep
mode off. Controllers with earlier application code
versions have communication disabled and the sleep
mode enabled. The Cn setting is not adjustable on
these earlier versions.

tp6514

1. Select button

Figure 5-9

2. Arrow buttons

ADC-RES Control

TP-6196 10/09

Controller Configuration Mode:


Hold the Select button:

Display:
Move the generator set master switch to the RUN
position. (The generator set engine will not start.)
Wait about 5 seconds until the display shows the
program version number. (The number may be
different than the one shown here.)
Press the down arrow key and then the up arrow
key 3 times to enter the configuration mode.
(This is the controller password.)

v 1 1 3

Uu 0 1

Now release the Select button.


Press:
or

Uu 0 x

To change the voltage/frequency setting,


if necessary. See Figure 4-7.
To enter setting and step to the next parameter, engine type Ec.

or

To change the engine type,


if necessary.

8.5/12 kW

E c 0 0

To enter setting and step to the next parameter, communication


setting Cn.
or

Cn 0 x

To change the communication setting, if


necessary. See Figure 4-7.

S AV E

To enter setting and step to SAVE.


Press:
To SAVE CHANGES.

Y E S

To DISCARD CHANGES without saving.

n o

OR

Yes or no flashes when the up or down arrow is pressed and


then the controller exits the configuration mode. The display
returns to the runtime hours.

x x x x

Now move the master switch to OFF/RESET.


Note: Shaded boxes show which number in the controller display changes when the up or down arrow
key is pressed. X in the runtime hours display above denotes any number from 0 to 9.
Figure 5-10 Configuration Mode (system voltage/frequency, engine type, and communication parameters)
TP-6196 10/09

Section 5 ADC-RES and DC-RET Controller

61

5.6 Voltage and Frequency


Adjustments

5.6.1

Voltage Adjustment

Note: Refer to the flowcharts in Figure 5-13 through


Figure 5-15 during the following procedure.

WARNING
Voltage Adjustment Procedure

Hazardous voltage. Moving parts.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.

1. With the generator set off, connect a digital


multimeter to the output leads or an electrical outlet
on the load side of the generator set. Set the meter
to measure AC voltage.
2. Start the generator set by moving the generator set
master switch to the RUN position.
3. Use the ADC controller to adjust the voltage
(parameter 1P) until the output voltage reaches the
desired value.
Refer to the flowcharts in
Figure 5-13 through Figure 5-15 for instructions to
adjust the output voltage. See Figure 5-11 for the
approximate change in voltage per step.

Note: The settings described in this section are not


adjustable on the DC-RET cotnroller.
The controllers adjustment mode allows adjustment of
the output voltage and frequency, if necessary. Have
adjustments performed by an authorized distributor/
dealer or service technician. A digital multimeter that
measures voltage and frequency is required for these
adjustments.
The generator set must be running during voltage and
frequency adjustments. Use a digital multimeter to
check the output voltage and frequency. Refer to
Sections 6.7.2, Voltage Adjustment, and 6.9.5,
Frequency Adjustment, for instructions to measure the
output voltage and frequency. Use the ADC controller to
adjust the output voltage and engine speed (frequency),
if necessary, while the generator set is running. See
Figure 5-9. The flowcharts in Figure 5-13 through
Figure 5-15 outline the adjustment procedures.
Note: Be sure to save your changes as instructed in
Figure 5-15 before exiting configuration mode.
Changes in voltage and frequency are lost if not saved
before the generator set shuts down. The generator set
continues to run with the new settings until it shuts down
but then reverts to the previous settings at the next
startup if the changes have not been saved.

Voltage Change per


Step, VAC

Measured
Voltage, VAC

ADC
Display

Coarse

Fine

85--132

1P00--99

0.5

180--251

1P00--99

0.7

Figure 5-11 Voltage Adjustment (approximate)


4. Adjust the voltage stability (gain, parameter 2P) to
minimize light flicker.
5. Readjust the voltage, if necessary.
6. Set the multimeter to measure frequency.
7. Adjust the engine speed to the cut-in frequency
shown in Figure 5-12 by adjusting the engine
governor speed (parameter 4P).
Frequency

Cut-In Frequency

60 Hz

57.5 Hz

50 Hz

47.5 Hz

Figure 5-12 Cut-In Frequencies


8. Adjust the volts/Hz (parameter 3P) until the voltage
level measured by the multimeter begins to drop.
When the volts/Hz is set correctly, the generator
(as load is applied) attempts to maintain normal
output until the engine speed drops below the
cut-in frequency set in step 7.
Note: See Section 6.7.3 for more information
about the volts/Hz (droop) adjustment.

62

Section 5 ADC-RES and DC-RET Controller

TP-6196 10/09

9. Reset the engine speed to the operating frequency


(50 or 60 Hz) by adjusting engine the governor
speed (parameter 4P).

1. Attach a frequency meter to the AC output leads or


an electrical outlet on the load side of the generator
set.

10. Readjust the voltage stability (gain, parameter 2P),


if necessary.

2. Start and run the generator set until it reaches


normal operating temperature (at least 10 minutes).

11. Readjust the voltage (parameter 1P), if necessary.

3. Adjust electronic governor speed (parameter 4P)


to obtain a frequency reading of 60 Hz (or 50 Hz if
appropriate). Each step changes the engine speed
about 3.6 rpm, which changes the output
frequency about 0.06 Hz.

12. Save settings. See Figure 5-15.


13. Stop the generator set.

5.6.2

Frequency Adjustment

The engine speed determines the generator output


frequency; 60 Hz units operate at 3600 rpm and 50 Hz
units run at 3000 rpm. Adjust the engine governor
speed and gain to set the output frequency and stability
using the following procedure.
Note: Refer to the flowcharts in Figure 5-13 through
Figure 5-15 during the following procedure.
Frequency Adjustment Procedure

4. Check stability with the generator set running and


with no load applied. If the generator set speed is
unstable, hunts, or surges, adjust the governor
stability (gain, parameter 5P) until the generator
set becomes stable with no hunting or surging.
(Increasing the gain slows the governor response.)
5. Check the frequency reading. Repeat steps 3 and
4 if necessary to obtain the rated frequency and
stable operation.
6. Save settings. See Figure 5-15.

Note: Refer to the flowcharts in Figure 5-13 through


Figure 5-15 during the following procedure.

TP-6196 10/09

Section 5 ADC-RES and DC-RET Controller

63

Output Voltage and Frequency Adjustment Mode:

Display :*

Move the generator set master switch to the RUN position. The generator set
engine starts and the controller display shows the engine runtime hours.

x x x x

Hold:

Wait about 5 seconds until the display changes from runtime hours
to the program version number.

x. x x

Press the down arrow key and then the up arrow key 3 times to enter the
adjustment mode. (This is the controller password.)

1 P x x

The controller is now in the voltage coarse adjustment mode.


Press:
or

To raise or lower the voltage in large increments


(approximately 5--7 volts per step). (Parameter 1P)

1 P x x

To enter fine voltage adjustment mode.

or

To raise or lower the voltage in smaller increments


(approximately 0.5--0.7 volts per step). (Parameter 1P)

1 P x x

To enter coarse voltage stability (gain) adjustment mode.

2 P x x
or

To raise or lower the voltage stability (gain) in large


increments. (Parameter 2P)

To enter fine voltage stability (gain) adjustment mode.

2 P x x
or

To raise or lower the voltage stability (gain) in smaller


increments. (Parameter 2P)

To enter volts/Hz adjustment mode.


(Parameter 3P)
or

3 P x x

To raise or lower the volts/Hz: 00=low; 09= high

Continued on Figure 5-14.


* Shaded boxes show which character in the controller display changes for each adjustment. X in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model.

TP6196

Figure 5-13 Output Voltage and Frequency Adjustments


64

Section 5 ADC-RES and DC-RET Controller

TP-6196 10/09

Display : *

Continued from Figure 5-13:


Press:
To enter engine governor speed coarse adjustment
mode. (Parameter 4P)
or

To raise or lower the engine speed in large


increments.

To enter engine governor speed fine


adjustment mode. (Parameter 4P)
or

4 P x x

To raise or lower the engine speed in smaller


increments.

To enter engine governor stability (gain) coarse


adjustment mode. (Parameter 5P)
or

5 P x x

To raise or lower the engine governor stability (gain)


in large increments.

To enter engine governor stability (gain) fine


adjustment mode. (Parameter 5P)

or

4 P x x

5 P x x

To raise or lower the engine governor stability (gain)


in smaller increments.

To enter SAVE mode. Go to Figure 5-15.

S AV E

Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to
the last saved settings when the master switch is moved to the OFF/RESET position.
* Shaded boxes show which character in the controller display changes for each adjustment. X in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model.
Figure 5-14 Output Voltage and Frequency Adjustments, Continued

TP-6196 10/09

Section 5 ADC-RES and DC-RET Controller

65

There are 3 options when the display says SAVE:


Press:

S AV E

To return to the first parameter, coarse voltage adjustment, to check


or change settings before saving. See Figure 5-13.

1 P x x

To save changes.

Y E S

To discard changes without saving.

n o

or

or

Yesor no flashes when the up or down arrow is pressed and then the
controller exits the configuration mode. The display returns to the
runtime hours.

x x x x

Now move the master switch to OFF/RESET.


Figure 5-15 Save Mode

5.7 Controller Relays


The K1 flash, K2 fuel (run), and K3 crank relays are
located on the controllers logic board. An LED is
associated with each relay. See Figure 5-16.
The LED indicates power to the corresponding relay. If
the LED is illuminated but the relay is not activated, the
relay is faulty.
The individual relays are not replaceable. If one or more
relays are faulty, replace the logic board. LED 4 lights to
indicate a fault condition. See Section 4.4, Faults.
The controller board is protected by a 10-amp fuse (F2)
located on the controller. If the fuse blows repeatedly,
disconnect the board loads one at a time to identify the
cause of the blown fuse:
! Lead 70C at the fuel valve
! Lead IGN at the ignition module
! Lead 71A at the starter relay
! Leads FP and FN at the rotor

4
3
5
6

Repair or replace the component causing the blown


fuse.
If fuse continues to blow and disconnecting components
did not identify the cause, remove the leads from the
P14 connector using a pin pusher. If replacing the leads
does not solve the problem, replace the controller logic
board.

66

Section 5 ADC-RES and DC-RET Controller

GM49103

1. LED1 Flash (K1)


2. LED2 Fuel (K2)
3. LED3 Crank (K3)

4. LED4 Fault
5. LED5 SP2
6. LED6 SP1

Figure 5-16 Relays and LEDs on Controller Logic


Board

TP-6196 10/09

5.8 Optional Relay Board


2

The generator set may be equipped with an optional


relay board, which contains the K1 common fault relay
and K4 auxiliary run relay. See Figure 5-17 for the relay
board location inside the controller junction box.

GM53102

1. Relay board
2. Controller circuit board location

GM51403

1. K1 common fault (CF) relay


2. LED1 (for K1 CF relay)
3. Connect P14 from RIB harness GM52639 to P14 on the
relay board
4. LED2 (for K2 aux. run relay)
5. K2 auxiliary run relay
6. Connect customer equipment to TB1, 14 AWG max.

Figure 5-18 Optional Relay Board

Figure 5-17 Relay Board Location


(inside controller junction box)

5.8.1

Relay Board Troubleshooting

First check for loose connections. Check the relay


board harness connections to the relay board, control
board, and engine harness.
See Figure 5-18,
Figure 5-19, and Figure 5-20.

Check for loose customer connections to terminal strip


TB1 on the relay board.
See Figure 5-18 and
Figure 5-21.
Check the harness and wiring for open circuits or shorts.
Replace the harness or customer wiring as necessary.
Check that the ratings of the customers connected
equipment do not exceed the relay contact
specifications shown in Figure 5-22.

from GM52541

1. P11, Relay board harness connection to the controller board.

Figure 5-19 Relay Board Harness Connection to


Controller Circuit Board

An LED is associated with each relay. See Figure 5-18.


The LED indicates power to the corresponding relay. If
the LED is illuminated but the relay is not activated, the
relay is faulty. The individual relays are not replaceable.
If one or more relays are faulty, replace the entire RIB.
See Section 5.8.2, Relay Board Replacement
Procedure.

TP-6196 10/09

Section 5 ADC-RES and DC-RET Controller

67

TO RELAY BOARD P14

TO ENGINE HARNESS

TO CONTROL BOARD P11

GM52639

Figure 5-20 Relay Board Connection Harness GM52639

TB1 Terminal Label

Description

Contact Ratings

COMMON FAULT NC

Common fault relay normally


closed contact.
Opens on a fault.

10 A @ 120 VAC
10 A @ 28 VDC

Maximum Operating Voltage

250 VAC/60 VDC

Maximum Switching Capacity

440 VA/75 W

COMMON FAULT COM

Common fault relay common

COMMON FAULT NO

Common fault relay normally


open contact.
Closes on a fault.

AUX RUN NC

Auxiliary run relay normally


closed contact.
Open when generator set is
running.

AUX RUN COM

Auxiliary run relay common

AUX RUN NO

Auxiliary run relay normally


open contact.
Closed when generator set is
running.

Figure 5-22 Relay Contact Ratings

Note: Use maximum 14 AWG wire for TB1 connections.

Figure 5-21 TB1 Customer Connections

68

Section 5 ADC-RES and DC-RET Controller

TP-6196 10/09

5.8.2

Relay Board Replacement


Procedure
WARNING

1. Access the controller junction box to locate the


relay board. See Figure 5-17.
2. Disconnect relay board harness connector P3 from
connector P14 on the relay board.
3. Pull the faulty relay board off the four mounting
standoffs inside the junction box.
4. Press the new relay board onto the four standoffs.

Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.

TP-6196 10/09

5. Connect three-pin connector of the relay board


harness GM52639 to P14 on relay board
GM51403. See Figure 5-18 and Figure 5-20.
6. Verify that the relay board harness is securely
connected to P11 on the control board. See
Figure 5-19 and Figure 5-20.
7. Verify that the relay board harness is securely
connected to the engine harness. See Figure 5-20.

Section 5 ADC-RES and DC-RET Controller

69

5.9 Controller Replacement

If the troubleshooting procedures in Section 3 identify a


bad controller, use the procedure in this section for
controller replacement. Always check the controller
configuration, fuse, wiring, and connections before
replacing the controller. For output voltage problems,
replace the SCR module and check the operation again
before replacing the controller.
After replacing the controller, verify that the new
controllers configuration settings match the generator
set system voltage/frequency and unit configuration.
Refer to Section 4.5 for instructions to check the
controller configuration and to change the settings, if
necessary.
After the controller configuration has been checked and
set to match the generator set, use a voltmeter to check
the generator set output voltage and frequency. If the
output voltage or frequency needs adjustment, use the
voltage and frequency adjustment procedure in
Section 6.7.2 and the controller voltage and speed
adjustment instructions in Section 5.6. Also see the
frequency adjustment procedure in Section 6.9.5.

ADV-7466C

1. Service-side door

2. Front panel

Figure 5-23 Enclosure Roof and Door


Logic Board Replacement
5. Note the connections on the logic board, and then
disconnect. See Figure 5-24.
6. Pull the old board straight off the mounting
standoffs.

DANGER
1
2

Hazardous voltage.
Will cause severe injury or death.

Disconnect all power sources before


opening the enclosure.
4

Controller Replacement Procedure


1. Remove the service door and the front panel to
access the controller junction box.
See
Figure 5-23.
2. Place the generator set master switch in the OFF
position.
3. Disconnect power to the battery charger.
4. Disconnect the generator set engine starting
battery, negative (--) lead first.

70

Section 5 ADC-RES and DC-RET Controller

fGM52541

6
1.
2.
3.
4.
5.
6.

P8 switch membrane connection


P9
P11 to engine harness and optional relay board, if equipped
P12 not used at this time
P1
P10

Figure 5-24 Controller Logic Board Connections

TP-6196 10/09

7. Check that the replacement board is positioned so


that the display shows through the opening in the
cover plate and then press the board onto the
standoffs. Check that all corners are securely
mounted. See Figure 5-25.
8. Reconnect all cables and harnesses to the board.
See the wiring diagram in Section 8 for
connections.
Note: Connector P12 on the logic board is not
used at this time.

User Interface Membrane Replacement


9. Disconnect the membrane ribbon cable from
connector P8 on the logic board.
10. Carefully remove the membrane from the junction
box cover.
11. Remove the protective backing to expose the
adhesive on the new membrane.
12. Thread the new membranes ribbon cable through
the small rectangular opening in the cover. Line up
the membrane window with the larger rectangular
opening.
13. Press the membrane firmly into place.
14. Connect the ribbon cable to the P8 connector on
the logic board.

15. Verify that the generator set master switch is in the


OFF position.
16. Reconnect the engine starting battery, negative (--)
lead last.
17. Reconnect power to the battery charger.
18. Replace the front panel.
19. Check settings and adjustments for the ADC-RES
controller only:
2

a. Follow the instructions in Section 5.5.4 to


change the new controllers configuration
settings to match the generator set system
voltage/frequency and unit configuration.
b. Use a voltmeter to check the output voltage.
Follow the instructions in Sections 4.5.3,
Voltage and Frequency Adjustments, and
6.7.2, Voltage Adjustment, to adjust the output
voltage and stability.
GM57149

1. User interface membrane


2. Controller logic board location

Figure 5-25 Controller

c. Check the output frequency. Follow the


instructions in Sections 4.5.3, Voltage and
Frequency Adjustments, and 6.9.5, Frequency
Adjustment, to adjust the output frequency and
stability.
20. Place the generator set master switch in the AUTO
position if an ATS or remote start/stop switch is
used.
21. Replace the service door.

TP-6196 10/09

Section 5 ADC-RES and DC-RET Controller

71

Notes

72

Section 5 ADC-RES and DC-RET Controller

TP-6196 10/09

Section 6 Component Testing and Adjustment


6.1 Theory of Operation

6.2 Separate Excitation

These generator sets utilize a rotating-field alternator to


produce AC voltage. Upon activation of the generator
master switch, DC current from the battery magnetizes
the rotor (field). When the magnetized rotor rotates
within the stator windings, an electrical voltage develops
within the stator. As engine speed and generator output
increase, the SCR module feeds rectified stator output
current to the rotor through the brushes/slip rings to
increase the strength of the rotor field. As the rotor field
increases in strength, generator output also increases.
The ADC controller monitors the generator output
voltage through leads 11 and 44 (single-phase) or leads
V7, V8, and V9 (three-phase) and adjusts the DC
current from the SCR module to the rotor to meet load
requirements. See Figure 6-1.

To determine the cause of no or low AC output, refer to


the troubleshooting flow chart in Figure 6-2. Before
beginning the test procedures, read all safety
precautions at the beginning of this manual. Many of the
test procedures include additional safety precautions.

No Generator Output

Separate Excitation

Output within
Specifications

Erratic or No Output

Check Wiring, Fuses,


SCR Module and
Controller

Check Rotor

Check Stator

1
55
66
ADC
Controller

55
66

AC1
AC2
G1
G2
(+)

G
F+

SCR

Figure 6-2

(--)

FP

TP563273

Check the condition of the alternator fuse before


performing the separate excitation procedure. The
inline fuse is located in lead 55 of the wiring harness or
on the junction box panel near the cotnroller. See
Figure 6-1. If the fuse is not blown, use the following
procedure to separately excite the generator using an
external voltage source (a 12-volt automotive battery).

FN

FP
11

FN
4

44

1 11
55 66

44

7
4
5

TP6196

1.
2.
3.
4.

Fuse
Power lead (55)
Excitation to rotor
Brushes

Figure 6-1

5.
6.
7.
8.

Slip rings
Main field (rotor)
Stator windings
Sensing leads (11--44)

Single-Phase Generator Schematic

TP-6196 10/09

Generator Troubleshooting

Separately exciting the generator can identify faulty


voltage regulation by the ADC controller or reveal a
running fault in the rotor and/or stator. An external
power source duplicates the role of the voltage regulator
and excites the generator field (rotor). A generator
component that appears to be in good condition while
stationary may exhibit a running open or short circuit
while moving. Centrifugal forces acting on the windings
during rotation cause a broken circuit to open, or
increasing temperatures cause the insulation to break
down, resulting in a running fault. If this test shows that
the rotor and stator are in good condition, test the
voltage regulation using the tests in Section 6.13.

Section 6 Component Testing and Adjustment

73

Grounding electrical equipment. Hazardous voltage can


cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.

Separate Excitation Procedure


Perform the following procedure to use an external
voltage source to excite the main field (rotor).
1. Disconnect the black FN and FP leads from the
alternator at the SCR module (+) and (--) terminals.
2. Connect a DC ammeter, 20-amp fuse, and a
12-volt automotive battery to the positive (FP) and
negative (FN) brush leads as shown in Figure 6-3.
Note and record the ammeter reading.

2 3

FN

1.
2.
3.
4.
5.
6.
7.
8.
9.

SCR module
FN lead disconnected from SCR
FP lead disconnected from SCR
10-amp fuse
DC ammeter
12V battery
Brushes
Slip rings
Main field (rotor)

Figure 6-3

Separate Excitation Connections

Example:
12 volts (battery voltage)
4 ohms (rotor resistance)

3 amps
(rotor current)

3. Start the engine and check that the ammeter


reading remains stable. An increasing meter
reading indicates a shorted rotor. A meter reading
decreasing to zero or an unstable reading
suggests a running open. Refer to Section 6.5,
Main Field (Rotor), to test the rotor. If the ammeter
reading is stable, proceed to step 4.
4. Check for AC output across the stator leads; see
Section 6.3, Stator. Compare the readings to the
AC output values shown in Section 1,
Specifications. If the readings vary considerably, a
faulty stator is likely. Refer to Section 6.3, Stator,
for further information.
5. If this test shows that the rotor and stator are in
good condition, check the wiring and fuses. Check
SCR module.
See Section NO TAG, Silicon
Controlled Rectifier Module. Check the controller
settings and connections.
See Section 4,
Controller Configuration and Adjustment.

6.3 Stator

FP
- +

Note: The approximate ammeter reading should


be the battery voltage divided by the
specified rotor resistance. See Section 1,
Specifications, for specified rotor resistance
values.

TP563274

The stator contains a series of coils of wire laid in a


laminated steel frame. The stator leads supply AC
voltage to the load and voltage regulator. Before testing
the stator, inspect it for heat discoloration and visible
damage to housing lead wires, exposed coil windings,
and exposed areas of frame laminations. Be sure the
stator is securely fastened to the stator housing.
Note: Disconnect all stator leads before performing all
stator tests.

WARNING

Hazardous voltage. Moving parts.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.

74

Section 6 Component Testing and Adjustment

TP-6196 10/09

High voltage test. Hazardous voltage can cause severe


injury or death. Follow the instructions of the test equipment
manufacturer when performing high-voltage tests on the rotor
or stator. An improper test procedure can damage equipment
or lead to generator set failure.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.

Note: For three-phase models, leads 1--12 are the


generator output leads. Leads V7, V8, V9, 55,
and 66 are the controller and SCR module
sensing and supply leads. Refer to the schematic
in Figure 6-6 when performing the following
steps.
6. Contact the ohmmeter leads and readjust the
ohmmeter to read zero ohms.

Stator Continuity and Resistance Tests

1. Place the generator set master switch in the OFF


position.

44

3
66

2. Disconnect power to the battery charger.

55

3. Disconnect the generator set engine starting


battery, negative (--) lead first.

4. Disconnect all stator leads before performing all


stator tests.
5. To check for stator continuity, set the ohmmeter on
R x 1 scale. First set the ohmmeter zero by holding
the red and black meter leads together and setting
the ohmmeter reading to zero. Then check the
stator continuity by connecting the meter leads to
the stator leads as shown in Figure 6-4.

Figure 6-5

11

6196

Single-Phase Alternator Stator Leads

tp6198

R14807-14

Figure 6-4

Testing Stator Windings

Note: For single-phase models. leads 1, 2, 3, and


4 are the generator output leads. Leads 11,
44, 55, and 66 are the controller and SCR
module sensing and supply leads. Refer to
the schematic in Figure 6-5 when
performing the following steps.

TP-6196 10/09

Figure 6-6

Three-Phase Alternator Stator Leads

7. Check the cold resistance of the stator windings by


connecting the meter leads to stator leads 1-2, 3-4,
and 55-66.
See Section 1.6, Alternator
Specifications, for stator winding resistances.
Most ohmmeters do not provide accurate readings
below 1 ohm. Low resistance readings (continuity)
and no evidence of shorted windings (heat

Section 6 Component Testing and Adjustment

75

discoloration) indicate a stator in good condition.


See Figure 6-7.
Leads

Continuity

1 and 2
1 and 11
2 and 11
3 and 4

Yes

3 and 44
4 and 44
55 and 66
2 and 3, 4, 44, 55, or 66
No

4 and 1, 2, 11, 55, or 66


Any stator lead and ground on stator
housing or frame laminations

Figure 6-7

Continuity Test Results on a Good Stator


(single-phase)

Leads
1 and 4
2 and 5
3 and 6
7 and 10
8 and 11
9 and 12
55 and 66
1 and 2, 3, 7, 8, or 9
1 and 55
Any stator lead and ground

Figure 6-8

76

Note: Because ohmmeter accuracy varies,


resistance readings are approximate
readings. Take readings of the rotor and
stator at room temperature.
Note: Make sure that all stator leads are
disconnected
before
running
the
megohmmeter test.
9. Use a megohmmeter to determine whether the
stator is shorted to ground.

1 and 3, 4, 44, 55, or 66


3 and 1, 2, 11, 55, or 66

8. If the resistance test proves inconclusive, use a


megohmmeter to test the stator as described in the
next step.

Continuity

Yes

a. Apply 500 volts DC to any stator lead and the


stator frame. Perform the megohmmeter test
following the instructions of the megohmmeter
manufacturer.
b. Repeat the test on the other stator leads until
each coil is tested.
Note: A reading of approximately 500 kOhms
(1/2 megohm) and higher indicates a
good stator.
c. Repair or replace the stator if any reading is
less than approximately 500 kOhms. A reading
of less than 500 kOhms indicates deterioration
of the winding insulation and possible current
flow to ground.

No

Continuity Test Results on a Good Stator


(3-phase)

Section 6 Component Testing and Adjustment

TP-6196 10/09

6.4 Main Field (Rotor)


The two-pole rotor creates the magnetic field needed to
produce alternating current in the stator windings.
Before testing, inspect the rotor for visible damage to
pole shoes, insulation, exposed coil windings, and slip
ring surfaces. Rotate the bearing to check for wear, heat
discoloration, or noise.
Rotor Continuity and Resistance Tests

WARNING

4. Remove the brush cover from the alternator end


bracket.
5. Check the rotor for continuity and resistance.
Raise the brushes from the slip rings while
performing ohmmeter tests. Measure the rotor
resistance (ohms) between the two slip rings; see
Figure 6-9.
See Section 1.6, Alternator
Specifications, for rotor resistance readings. If the
resistance readings are low, perform a
megohmmeter test on rotor as described in the
next step.
Note: Because ohmmeter accuracy varies,
resistance readings are approximate. Take
readings at room temperature.

Hazardous voltage. Moving parts.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
High voltage test. Hazardous voltage can cause severe
injury or death. Follow the instructions of the test equipment
manufacturer when performing high-voltage tests on the rotor
or stator. An improper test procedure can damage equipment
or lead to generator set failure.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.

Rotor Test Procedure


1. Place the generator set master switch in the OFF
position.
2. Disconnect power to the battery charger.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.

TP-6196 10/09

2-221
R13929-7

Figure 6-9

Rotor Resistance Check

6. Perform a megohmmeter test to determine


whether the rotor is shorted to ground.
a. Raise and secure the brushes away from the
slip rings by inserting a retaining wire in the
brush holder hole.
b. Using a megohmmeter, apply 500 volts DC to
one rotor slip ring and the rotor poles or shaft.
Follow the instructions of the megohmmeter
manufacturer when performing this test.
Note: A reading of approximately 500 kOhms
(1/2 megohm) or higher indicates a
good rotor.

Section 6 Component Testing and Adjustment

77

c. Repair or replace the rotor if the reading is less


than approximately 500 kOhms. A reading of
less than 500 kOhms indicates deterioration of
the winding insulation and possible current flow
to ground.

Check the resistance through the brushes. Resistance


through the brushes should be low, 0.1--0.2 ohms
without meter lead resistance.

d. Following the test, remove the retainer wire


from the brush holder and check the brush
positions on the slip rings. See Section 6.6,
Brushes.

1
2

e. Reinstall the brush cover on the end bracket.

3
2

6.5 Slip Rings


Front View

Slip rings acquire a glossy brown finish in normal


operation. Do not attempt to maintain a bright,
newly-machined appearance on the slip rings. Cleaning
with a dry, lint-free cloth is usually sufficient. Use very
fine sandpaper (#00) and apply light pressure to remove
roughness. Do not use emery or carborundum paper or
cloth. Clean all carbon dust from the generator after
sanding the slip rings. If the rings are black or pitted,
remove the rotor and use a lathe to remove some of the
slip ring surface material.

GM29253B-P

Side View

3
New 1.9 cm (0.75 in.)

6.6 Brushes
The brushes transfer current from the SCR module to
the slip rings. The brushes should last the life of the
generator. Abrasive dust on the slip rings, however,
shortens the life of the brushes. Excessive arcing at the
brushes could damage the SCR module and the
controller. Weak springs, damaged slip rings, sticking
brushes, a loose brush holder, or poor brush contact
causes arcing.

3
TP5867

1.
2.
3.
4.

Brush holder
Slip ring
Brush(es)
Retainer wire

5.
6.
7.
8.

Shim
Spring
Correctly positioned brush
Incorrectly positioned brush

Figure 6-10 Brush Assembly

The brushes must be free to move within the holder and


be held in contact with the slip rings by the springs.
When correctly positioned, spring pressure on the brush
surface causes the brush to wear evenly. The entire
brush must ride on the ring or arcing occurs and causes
burned rings or voltage regulator failure. Figure 6-10
shows the correct positioning of the brushes. Add or
remove shims as necessary to center the brushes on the
slip rings. Replace the brushes if they show uneven
wear or are worn to one half their original length.

78

Section 6 Component Testing and Adjustment

TP-6196 10/09

6.7 Voltage
6.7.1

WARNING

Voltage Regulation

Voltage regulation is performed by the Advanced Digital


Control (ADC) and the SCR module. The ADC monitors
generator output voltage and adjusts the excitation
current to the rotor through the SCR module.

6.7.2

Voltage Adjustment

The factory sets the voltage for correct generator


operation under a variety of load conditions. Usually, the
voltage needs no further adjustment. Adjust the voltage
when necessary according to the following procedure.
The adjustment procedure requires a meter that can
measure voltage and frequency.
Use the ADC controller to adjust the voltage, gain, and
volts/Hz. Refer to Section4.5 for instructions to adjust
each setting and save the changes using the controller
keypad.
Note: Be sure to save your settings as instructed. The
ADC controller will time out and exit the
adjustment mode after approximately 1 minute if
no buttons are pressed. Any unsaved changes
are discarded if the controller times out before the
settings are saved.
Voltage Adjustment.
voltage.

Adjusts generator output

Gain (Stability) Adjustment.


circuitry to reduce light flicker.

Fine tunes regulator

Hazardous voltage. Moving parts.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.

Voltage Adjustment Procedure


1. Connect a digital voltmeter from one side of the
circuit breaker to the L0 terminal inside the
controller assembly.
See Figure 6-12.
For
3-phase models. connect the voltmeter from L0 to
L1, L2, or L3 on the circuit breaker. See
Figure 6-14. Set the meter to measure voltage.
2. Start the generator set.

Volts/Hz Adjustment. Determines frequency (Hz) at


which generator output voltage begins to drop. The
controller maintains generator output at the specified
voltage under load until the generator engine speed
drops to a preset level (factory setting 57.5 Hz on 60 Hz
models and 47.5 Hz on 50 Hz models). Then the
controller allows the generator voltage and current to
drop. The voltage/current drop enables the engine to
pick up the load. When the generator speed returns to
normal (60 Hz or 50 Hz) as load is accepted, the
generator output also returns to normal. See Section for
more information about the volts/Hz (droop) adjustment.

3. Follow the controller instructions in Section 4.5 to


enter the adjustment mode and increase voltage or
decrease voltage (parameter 1P) until the output
reaches the desired voltage. See Figure 6-11.

Models
1 phase, 60 Hz
1 phase, 50 Hz
3 phase, 50 Hz

Voltage
Measurement

Approximate
Voltage, VAC

L -- L0
L-L
L -- L0
L-L
L -- L0
L-L

120
240
115
230
230
400

Figure 6-11 Voltage Measurement

TP-6196 10/09

Section 6 Component Testing and Adjustment

79

1
1
L0 L1 L2 L3
2

See
Detail

GM66010

1. Measure voltage across circuit breaker terminals L0 and L1,


L2, or L3

Figure 6-14 Voltage Measurement, Three-Phase


Models
7. Set the voltmeter to measure voltage. Adjust the
volts/Hz (parameter 3P) until the voltage level
measured by the voltmeter begins to drop. When
set, the generator (as load is applied) attempts to
maintain normal output until the engine speed
drops below the cut-in frequency set in step 6.

Note: See Section 6.7.3 for more information on


the volts/Hz (droop) adjustment.
3
Controller Box Detail
GM57149

1. Controller box location


2. Line circuit breaker
3. Load connection terminal L0

Figure 6-12 Circuit Breaker and L0 Terminal Location


4. Follow the controller instructions to step to the
voltage gain adjustment menu. Adjust the voltage
gain (parameter 2P) until the light flicker minimizes.
Save the settings.
5. Check and readjust the voltage if necessary.
6. Set the voltmeter to measure frequency. Adjust the
engine speed to the cut-in frequency shown in
Figure 6-13 by adjusting the engine governor
speed (parameter 4P) through the ADC controller.
See Section 4.5.
Frequency

Cut-In Frequency

60 Hz

57.5 Hz

50 Hz

47.5 Hz

8. Set the voltmeter to measure frequency. Adjust the


engine speed to the operating frequency (50 or
60 Hz) by adjusting the engine governor speed
(parameter 4P) through the ADC controller.
9. Readjust the voltage gain (parameter 2P) until the
light flicker minimizes, if necessary.
10. Check the voltage.
Readjust the voltage
(parameter 1P), if necessary.
11. Save the settings as instructed in Section 4.5.
Note: The controller will revert to the previous
settings at the next startup if the changes are
not saved.
12. Stop the generator set.

Figure 6-13 Cut-In Frequencies

80

Section 6 Component Testing and Adjustment

TP-6196 10/09

6.7.3

Volts per Hertz (Hz) Adjustments


(Droop)

When the frequency falls below the cut-in frequency


(see Figure 6-13), output voltage is reduced to relieve
the engine. The magnitude of the voltage reduction is
set by the 3P parameter. Monitor engine speed and
output voltage as loads are applied.

6.7.4

Voltage Connections,
Single-Phase

Single-phase generator sets are available from the


factory connected for 110/220 volt 50 Hz or 120/240 volt
60 Hz. See Figure 6-16 for the factory connections.
These generator sets are not reconnectable.
LO (Neutral)

! If there is excessive droop in engine speed and little

droop in voltage, increase the 3P value.

Ground

! If there is little engine speed droop but excessive

voltage droop, decrease the 3P value.

Load
Side

! Readjust the voltage stability (2P) and voltage (1P)

parameters after adjusting the 3P setting, if


necessary. See the instructions in Section NO TAG.

3P

Voltage Droop, % of System Voltage per


1 Hz Cycle Below Cut--In Frequency

0.5%

1.0%

1.5%

2.0%

2.5%

3.0%

3.5%

4.0%

4.5%

L2
L1
Factory two-pole
circuit breaker

Line
Side

! Remember to save your settings.

Each step of 3P changes the amount of voltage droop


approximately 0.5% of system voltage for each cycle
(Hz) below the cut-in frequency. See Figure 6-15.

LO
GRD

3
2
1
Stator Leads
L0-L1
L0-L2
L1-L2

60 Hz
120 volt
120 volt
240 volt

50 Hz
110 volt
110 volt
220 volt
TP-5867

Figure 6-16 110/220 and 120/240 Volt, 3-Wire


Configurations

Figure 6-15 Voltage Droop Adjustments

TP-6196 10/09

Section 6 Component Testing and Adjustment

81

6.7.5

Voltage Connections, 3-Phase

Three-phase generator sets are connected for


230/400 Volts, 50 Hz. See Figure 6-17 for the factory
connections. The generator sets are not reconnectable.

6.8 Silicon Controlled Rectifier


Module
The silicon controlled rectifier (SCR) module works with
the ADC-RES to regulate the output voltage. The
ADC-RES monitors generator output voltage and
adjusts the excitation current to the rotor through the
SCR module. The SCR module location is shown in
Figure 4-1.
The SCR module is powered through stator leads 55
and 66 connected to SCR terminals AC1 and AC2.
Leads G connected to terminals G1 and G2 provide the
controller signal. Leads FP and FN connected to the
positive (+) and negative (--) SCR terminals provide
excitation current to the rotor. See Figure 6-18 and the
wiring diagrams in Section 8.
The SCR module is protected by a 20-amp fuse (F1) in
lead 55 on the controller. Check the fuse and replace it,
if blown.
In the case of output voltage problems, check the
controller configuration and settings. Then test the SCR
module using the following procedure.

PHASE ROTATION
ADV--5875

Note: If it is necessary to replace the SCR module, be


sure to apply thermal compound to the back of the
module to prevent overheating.
Thermal
compound is provided with the SCR module
replacement kit.

Figure 6-17 3-Phase Configuration


AC1

AC2

G1

--

G2

+
GM28483

Figure 6-18 Silicon Controlled Rectifier (SCR)


Module

82

Section 6 Component Testing and Adjustment

TP-6196 10/09

SCR Module Test Procedure


Required equipment:
! Ohmmeter
! 12-volt test lamp (or voltmeter)

1
2

(+)

(--)

! 12-volt DC power source


! 100--500 ohm resistor
! Jumper

1. Set the ohmmeter to the R x 1 scale.


5

2. Connect the ohmmeter from (+) to (--) on the SCR


module. You should read high resistance in one
direction and low resistance in the other (reverse
the leads).

G1

3. Connect the ohmmeter from AC1 to (+) on the SCR


module. You should read high resistance in both
directions.

AC1
AC2

(+)
4. Connect the ohmmeter from AC1 to (--) on the SCR
module. You should read high resistance in one
direction and low resistance in the other.
5. Repeat steps 3 and 4 for AC2.
6. Connect the ohmmeter from G1 to (+) on the SCR
module. You should read low resistance in both
directions.

(--)

G2
1. 12 VDC power source
2. 12 VDC test lamp
3. SCR module

tp6196

4. Jumper
5. 100--500 ohm resister

Figure 6-19 SCR Test

7. Repeat step 6 for G2. You should read low


resistance in both directions.

9. Connect the positive (+) lead from the DC power


source, with the lamp in series, to terminal AC1 on
the SCR module. The lamp should not glow.

8. See Figure 6-19. Connect the negative (--) lead


from the DC power source to the positive (+)
terminal on the SCR module.

10. Connect the jumper, with the resistor in series, from


the positive lead of the DC power source to terminal
G1 on the SCR module. The lamp should glow.

Note: The SCR module may be damaged if the


power supply is connected incorrectly. Be
sure to connect the negative lead from the
battery to the positive terminal on the SCR
module.

11. Repeat steps 9 and 10, with the positive (+) lead
and lamp connected to terminal AC2 on the SCR
module, and connecting the jumper with resister to
terminal G2.
12. If any of the above checks indicates a bad SCR
module, replace the module. Be sure to apply the
thermal compound supplied with the module
replacement kit to the back of the new module.

TP-6196 10/09

Section 6 Component Testing and Adjustment

83

6.9 Electromechanical Governor


System
Electromechanical governor systems are used on
models 8.5/12RES and 12TRES.
The governor system consists an electromechanical
stepper motor (actuator) and a magnetic pickup. The
ADC controller controls the governor system operation.
See Section 8, Wiring Diagrams, for governor
connections.

6.9.1

Operation

The frequency of the alternator output is determined by


the speed of the engine. A two-pole alternator must be
driven at 3600 rpm to provide 60 Hertz. (A 50 Hz model
must be driven at 3000 rpm.) Engine speed is
maintained by an electronic governor system that
consists of a magnetic pickup and electric actuator
(stepper motor). The ADC controller controls the
governor system.
The magnetic pick-up, which monitors the speed of the
flywheel ring gear, provides the speed reference signal
to the ADC controller. The controller provides regulated
power to the bidirectional stepper motor actuator, which
is linked to the carburetor throttle arm.
At cranking speed a properly adjusted pick-up should
produce a minimum of 1.75 VAC. The magnetic pick-up
air gap is factory-set to 0.5 mm (0.020 in.). Failure or
loss of the input speed signal from the magnetic pick-up
will result in erratic speed.
A setting on the ADC controller allows adjustment of the
engine speed within the 50/60Hz range.
See
Section 6.9.3.
A gain adjustment may be required if an unstable
(hunting/surging) condition occurs. Adjusting the gain
may require readjustment of the engine speed. See
Section 6.9.3.

84

Section 6 Component Testing and Adjustment

6.9.2

Initial Checks and Operation Test

The factory sets the electronic governor. Under normal


circumstances the electronic governor requires no
further adjustment. Verify that the governor stepper
motor moves smoothly and steadily during operation. If
the engine operates erratically check the following
connections and conditions before adjusting the
governor.
! Verify that the electrical connections are clean and

tight.
! Check the magnetic pickup connections. Poor

connections may cause an erratic signal or an


overspeed condition. An erratic signal causes the
generator set to govern poorly but not shut down.
! Verify that the battery connections are clean and tight.
! Check for dirt buildup on the magnetic pickup. Metal

filings or caked-on dirt or grease decreases the output


signal of the magnetic pickup.
! Check for a loose or worn stepper motor/throttle shaft

coupling. Replace the shaft and bushing every 500


hours of engine operation.
! Check

the carburetor for dirt, grime, or


misadjustment. Check for a loose mixer assembly.

! Check the idle-adjustment screw. The screw should

not prevent the throttle plate from closing completely.


! Check the throttle linkage for any binding, dirt,

damage, or other visible problems.


! Check for electronic governor faults. The fuel shutoff

solenoid deenergizes and the generator set shuts


down under the following conditions:
! Closed throttle
! Engine overspeed
! Broken fuel shutoff solenoid lead
! Broken stepper motor leads (erratic performance)
! Failed actuator linkage (erratic performance)

TP-6196 10/09

6.9.3

Hunting/Surging

Often hunting/surging
by the governor are
carburetor problems.
using the following
governor.

problems thought to be caused


actually caused by engine or
Check engine speed stability
procedure before testing the

1. Open the generator set line circuit breaker.


2. Start the generator set.
3. Hold the throttle linkage steady while the engine is
running. See Figure 6-20. If the engine runs at a
steady speed with no hunting or surging when the
throttle is held steady, then the hunting/surging
problems during operation are probably caused by
the governor. Proceed to Section 6.9.4.

4. If the engine speed hunts or surges while the


throttle is held steady, check the carburetor
position and engine operation.
a. Check carburetor position. Slotted mounting
holes in the base of the carburetor determine
the carburetor position, which affects the
throttle operation. Verify that the carburetor is
mounted as close to the governor actuator
(stepper motor) as the mounting holes allow.
b. Refer to the engine service manual for other
engine diagnostic and service information.

6.9.4

Governor System/Magnetic
Pickup Operation Test

If the engine continues to operate erratically after the


previous checks, test the governor system operation
using the following procedure. The procedure is
summarized in the flowchart in Figure 6-21.

1
2
3

1. Electronic governor stepper motor


2. Carburetor throttle linkage
3. Carburetor mounting holes

TP5632721

Figure 6-20 Stepper Motor and Carburetor


Check that the carburetor throttle linkage
is connected to the stepper motor as
shown in Figure 6-20.
Check for broken or loose wiring or
connections and other items in step 2.

Yes

Check stepper motor operation at startup.


Does it move to fully open and then move
to and stay in the fully closed position?
See step 3.

Check the magnetic pickup. See steps 4--6.

Check the magnetic pickup connections to the controller:


P1-17, P1-18, and P1-29.

No

Disconnect the magnetic pickup and check the stepper


motor operation again. See steps 7--9.
Check the stepper motor connections to the controller.
See step 10.

Check the stepper motor coils. See step 11.

Troubleshoot the controller. See step 12.


tp5867

Figure 6-21 Governor System Operation Test Procedure Summary (Section 6.9.4)
TP-6196 10/09

Section 6 Component Testing and Adjustment

85

Governor System Operation Test Procedure


1. Verify that the carburetor throttle linkage is
connected to the stepper motor as shown in
Figure 6-20.
2. Look for broken or loose wiring or plug connections
if the stepper motor moves erratically. Check the
condition of the throttle linkage, and verify that the
throttle plate closes completely.

5. If the voltmeter displays less than 1.75 volts AC,


check the air gap as described in the following
steps before replacing the sensor. Verify that the
magnetic pickup air gap is 0.5 mm (0.020 in.).
Measure the air gap at 3 or 4 places to get an
accurate reading. See Figure 6-23.
a. Stop the generator set. Remove housing
panels as required to gain access to the front of
the engine.

3. Check the operation of the stepper motor at


startup.

b. Remove the engine blower housing.


c. Use a feeler gauge to check the gap. The gap
should be 0.5 mm (0.020 in.).

a. If the throttle moves to the fully open throttle


position and then steps to and remains in the
fully closed position, the engine speed input is
probably missing. The engine starts and then
shuts down on an overspeed fault. Proceed to
step 4 to check the magnetic pickup.

d. Adjust the air gap, if necessary, by loosening


the locknut and turning the pickup. See
Figure 6-23.
e. Hold the pickup in position and retighten the
locknut.

b. If the throttle linkage moves erratically or not at


all at startup, proceed to step 7 to check the
stepper motor.

f. Verify the magnetic pickup air gap after


tightening the locknut.

4. Verify the operation of the magnetic pickup by


connecting a voltmeter to the magnetic pickup
leads. See Figure 6-22. If the air gap is correct, the
voltage should be 1.75 volts AC minimum during
engine cranking.

g. Reinstall the engine blower housing.


h. Reinstall the junction box and housing panels
removed to gain access to the front of the
engine.
6. After adjusting the air gap, check the voltage again
as described in step 4. If the voltage does not
measure 1.75 VAC minimum, replace the magnetic
pickup.

6196

Figure 6-22 Magnetic Pickup Leads

5
4
3
2
1.
2.
3.
4.
5.

Ignition module
Air gap, 0.5 mm (0.020 in.)
Top of flywheel ring gear tooth
Lock nut
Magnetic pickup

A-358000B-C

Figure 6-23 Magnetic Pickup Air Gap

86

Section 6 Component Testing and Adjustment

TP-6196 10/09

7. To test the controllers governing function,


disconnect the magnetic pickup leads and open
the generator set circuit breaker.
8. Manually move the throttle shaft/governor stepper
motor fully counterclockwise (closed throttle).
9. Start the generator set. The stepper motor should
step clockwise to the wide open throttle position.
The stepper motor should remain in the clockwise
(throttle fully open) position. If the stepper motor
does not operate as described here, proceed to the
next steps to check the governor and stepper
motor.
10. Place the generator set master switch in the STOP
position. Check the stepper motor connections to
the controller: Leads 1A, 1B, 2A, and 2B to pins
P1-4, P1-5, P1-6 and P1-7. Check the pins and
connections at plugs J6 and P6. See the wiring
diagrams in Section 8.

PIN 3, BLK

PIN 2, YEL

PIN 5, GRN
(not used)

PIN 4,
RED

PIN 1,
WHT

PIN 6, BLUE
(not used)

SB555

Figure 6-24 Actuator Coil Group


12. If there is power and a good ground connection to
the ADC controller and the stepper motor coil
resistances are good, but the stepper motor does
not operate as described in step 9, the problem is
with the ADC controller.
Check controller
connections, fuses, wiring, and settings. Refer to
the troubleshooting procedures in Section 3.

11. Check the stepper motor coil resistance across


pins 2 and 3 and across pins 1 and 4. Only two
stepper motor leads of each coil group are used
(BLK-YEL and RED-WHT). See Figure 6-24. The
resistance per half coil is 38.5 ohms. If one of the
coils has a significantly higher resistance or is
shorted, replace the stepper motor.

TP-6196 10/09

Section 6 Component Testing and Adjustment

87

6.9.5

Frequency Adjustment

The engine speed determines the generator output


frequency; 60 Hz units operate at 3600 rpm and 50 Hz
units run at 3000 rpm. Adjust the engine governor to
change the output frequency using the following
procedure.
Note: Engine governor speed (frequency) and gain
adjustments are made using the ADC controller.
See Section 4.5.3 for instructions.
Frequency Adjustment Procedure
1. Open the generator set line circuit breaker.
2. Attach a frequency meter to the AC output leads.
3. Start and run the generator set until it reaches
normal operating temperature (at least 10 minutes).
4. Use the ADC controller to adjust the electronic
governor speed (parameter 4P) to obtain a
frequency reading of 60 Hz (or 50 Hz on 50 Hz
models). See Section NO TAG.
Note: Often hunting/surging problems thought to
be caused by the governor are actually
caused by engine or carburetor problems. If
the generator set speed is unstable, hunts,
or surges, check for the cause using the
procedure
in
Section 6.9.3
before
proceeding.
5. Check stability with the generator set running and
with no load applied. If the generator set speed is
unstable, hunts, or surges, use the ADC controller
to decrease the gain (parameter 5P) until the
generator set becomes stable with no hunting or
surging. Observe the frequency reading.

88

Section 6 Component Testing and Adjustment

6. Repeat steps 4 and 5 to obtain the rated frequency


and stable operation.
7. Save the settings as instructed in Section 4.5.
Note: The controller will revert to the previous
settings at the next startup if the changes are
not saved within one minute after the last
change.
8. Apply rated load to the generator set and observe
the frequency reading. The no load and full load
frequencies should be within 0.4 Hz of the rated
generator frequency; if not, check that the
carburetor throttle plate opens completely without
sticking and check the carburetor adjustment. If
these procedures do not correct the problem,
replace the controller.
9. Check for hunting and surging at full load. Use the
controller to increase the gain (parameter 5P) until
the engine hunts and surges. Then decrease the
gain in small steps using the governor gain fine
adjust parameter until the engine operation
stabilizes. Save the controller changes.
10. Remove the load and observe the frequency. The
frequency should return to the value stated in
step 4. Gain adjustment may affect the generator
set speed/frequency.
If the frequency has
changed, repeat step 4.
Note: Speed adjustments have no effect on gain
adjustments. It is not necessary to repeat
the gain adjustments after adjusting the
engine speed.
Check the overspeed shutdown operation when
investigating a shutdown problem. See Section 6.11.1
for the overspeed shutdown test procedure.

TP-6196 10/09

6.10 Mechanical Governor

Mechanical Governor Arm Adjustment Procedure

Mechanical governors are used on model 12RESL,


12RESM1, and 12RESNT generator sets.
See
Figure 6-25. This section includes governor adjustment
procedures. See the engine service manual for a
description of mechanical governor design and
operation, if desired.

Make this adjustment whenever the governor arm is


loosened or removed from the cross shaft. See
Figure 6-26 and adjust as follows:
1. Make sure the throttle linkage is connected to the
governor arm and the throttle lever on the
carburetor.
2. Loosen the hex nut holding the governor lever to
the cross shaft.
3. Move the governor lever toward the carburetor as
far as it will move (wide open throttle) and hold in
this position.
4. Insert a nail into the hole in the cross shaft and
rotate the shaft counterclockwise as far as it will
turn. Tighten the hex nut securely and then remove
the nail.
1

1. Mechanical governor assembly

photo4991

Figure 6-25 Mechanical Governor Assembly Location

1.
2.
3.
4.

Hex nut
Cross shaft
Governor lever
Throttle linkage (passes under air cleaner)

photo5005

Figure 6-26 Governor Arm Adjustment

TP-6196 10/09

Section 6 Component Testing and Adjustment

89

Mechanical Governor Sensitivity Adjustment


Note: Often hunting/surging problems thought to be
caused by the governor are actually caused by
engine or carburetor problems. If the generator
set speed is unstable, hunts, or surges, check for
the cause using the procedure in Section 6.9.3
before proceeding.

Engine Speed (Frequency) Adjustment,


Mechanical Governor
Use the adjusting nut shown in Figure 6-28 to adjust the
engine speed, if necessary. Recommended engine
speeds with no load and full load are shown in
Figure 6-29.
1. With the engine running, loosen the lock nut.

Governor sensitivity is adjusted by repositioning the


governor spring in the holes of the governor lever. If
speed surging occurs with a change in engine load,
decrease the governor sensitivity. If a drop in speed
occurs when normal load is applied, increase the
governor sensitivity. See Figure 6-27 and adjust as
follows:
1. To increase the sensitivity, move the spring closer
to the governor cross shaft.

2. If the engine is running too slow (frequency is low),


turn the adjusting nut clockwise to increase the
speed.
3. If the engine is running too fast, turn the adjusting
nut counterclockwise, backing the nut out and
decreasing the speed.
4. Verify that the engine speed is correct and tighten
the locknut.

2. To decrease the sensitivity, move the spring away


from the governor cross shaft.

photo5005

1
#
photo5005

1. Speed adjusting nut and lock nut

1. Governor lever
2. Cross shaft

Figure 6-27 Governor Sensitivity Adjustment

Figure 6-28 Engine Speed Adjustment


Generator Set Load
No Load
Full Load

Engine Speed
3780 RPM (63 Hz)
3600 RPM (60 Hz)

Figure 6-29 Recommended Engine Speed

90

Section 6 Component Testing and Adjustment

TP-6196 10/09

6.11 Fault Shutdown Tests


Verify the operation of the generator set overspeed,
overcrank, and low oil pressure shutdowns by
performing the following tests. If these tests are
inconclusive, test individual shutdown circuit
components (wiring harness, switch, etc.) as described
elsewhere in this section.

WARNING

Hazardous voltage. Moving parts.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Servicing the generator set when it is operating. Exposed
moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts
and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.

6.11.1 Controller Fault Shutdown


Functions
Check the operation of the fault functions programmed
in the ADC controller by performing the following tests. If
the ADC controller does not operate as described,
check the controller configuration settings; see
Section 4.5.2. Also check the controller wiring and
connections.

Overspeed Shutdown
The overspeed setting is programmed into the ADC
controller and is not adjustable. Verify that the following
controller configuration parameters are set correctly for
your unit. See Section 4.5 and Figure 4-7 for the
settings.

WARNING

Hot engine and exhaust system.


Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the exhaust system. Hot parts can cause
severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.

Open the generator set output circuit breaker before


beginning the test. (See Figure 4-1 for the circuit
breaker location.)
Connect a DVM to measure the output frequency. Start
the generator set and manually adjust the engine speed
by moving the throttle linkage.
Note: Be careful not to touch the hot silencer when
reaching in to adjust the throttle linkage.
Increase the engine speed (parameter 4P) to at least
115% of the rated engine speed, 69 Hz on 60 Hz models
or 58 Hz on 50 Hz models. Verify that the generator set
shuts down on an overspeed fault (OS). If the
overspeed shutdown does not operate, the generator
set should shut down on an overfrequency fault (OF)
after approximately 5 seconds.
If the controller does not indicate an overspeed fault
(OS), check the wiring to the magnetic pickup (red and
black leads, P1-17 and P1-29). Check the magnetic
pickup air gap and voltage output; see Section 6.9.4.

Low Oil Pressure (LOP) Shutdown


Connect a jumper wire from the LOP switch (lead 13) to
the generator set ground. Start the generator set. Verify
that the generator set shuts down after approximately
25--35 seconds of operation. Remove the jumper wire
from the LOP switch and ground. Start the generator set
and run it for at least 25--35 seconds to verify that the
generator set does not shut down.

! System voltage/frequency parameter (UU)


! Unit configuration parameter (UC)
! Engine type parameter (EC)
! Engine data input type parameter (ED)

TP-6196 10/09

Section 6 Component Testing and Adjustment

91

Overcrank Shutdown
Disconnect the starter motor lead at the starter solenoid
(K20) terminal. Move the controller master switch to the
RUN position. Observe that the generator set simulates
cranking for 15 seconds and then rests for 15 seconds.
Check that the generator set shuts down after the third
crank/rest cycle.

High Engine Temperature Shutdown


Connect a jumper wire across coolant temperature
sensor (CTS) connections P1-8 and P1-9. Start the
generator set. Verify that the generator set shuts down
approximately 5 seconds after the generator set comes
up to speed. Remove the jumper wire. Start the
generator set and run it for at least 30 seconds to verify
that the generator set does not shut down.

6.11.2 Fault Shutdown Switches


Check the low oil pressure and high engine temperature
shutdown switches on the engine by performing the
following tests. If the sensor does not function as
described, replace it.

Service View, for the coolant temperature sensor


location. Set the generator set master switch to the OFF
position and allow the generator set to cool. Disconnect
the CTS and use an ohmmeter to measure the
resistance across the sensor. The sensor resistance
varies with temperature and should be within the values
shown in Figure 6-30. If the resistance is very low
(indicated a short circuit) or very high (indicating an open
circuit) replace the CTS.
Note: The HET switch is located in the engine oil pan.
Drain the engine oil before removing the switch.
Temperature, !C (!F)
30 (86)
100 (212)

Resistance, Ohms
2100--2500
180--200

Figure 6-30 Coolant Temperature Sensor Resistance


Readings

Low Oil Pressure (LOP) Switch


The low oil pressure (LOP) switch is located under the
engine air cleaner. See Figure 6-31.

WARNING
1

Hazardous voltage. Moving parts.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Servicing the generator set when it is operating. Exposed
moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts
and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.

Temperature Sensor (CTS)


The coolant temperature sensor (CTS) is used to
monitor engine temperature for the high engine
temperature fault shutdown (HE). See Section 1.7,

92

Section 6 Component Testing and Adjustment

tp6196

1. Oil pressure switch

Figure 6-31 Oil Pressure Switch Location (under air


cleaner)
Remove the LOP switch and install an oil pressure
gauge to verify that the engine oil pressure is within the
range specified in Section 1, Specifications, before
testing or replacing the LOP switch. To test the LOP
switch, reinstall the switch and start the generator set. If
the unit shuts down, disconnect lead 13 from the LOP
switch and reset the controller. Restart the generator set
and verify that it does not shut down. A successful
restart indicates a bad LOP switch. Replace the switch.

TP-6196 10/09

6.12 Fuel Systems

Figure 6-33 lists the maximum gas flow rates for each
model.
8.5RES

WARNING
Pipe Length,
m (ft.)

12RES

Natural
Gas

LP

Natural
Gas

LP

(25)

3/4

1/2

3/4

3/4

15

(50)

3/4

3/4

Explosive fuel vapors.


Can cause severe injury or death.

30

(100)

46

(150)

1 1/4

Use extreme care when handling,


storing, and using fuels.

61

(200)

1 1/4

1 1/4

Figure 6-32 Maximum Gas Pipe Length


The fuel supplier provides and maintains manual
shut-off valves and the primary regulator. Verify that the
fuel system capacity is adequate to supply the generator
set plus all other gas appliances.
A factory-installed secondary regulator and 12 VDC
solenoid valve are located in the front inlet air
compartment. The controller energizes the fuel
solenoid valve to open at startup and deenergizes the
valve to close at shutdown. The secondary fuel
regulator reduces fuel pressure for delivery to the fuel
metering valve. The fuel flows from the fuel metering
valve to the carburetor in a gaseous state. The
carburetor mixes the fuel with intake air for consumption
by the engine.
Use a universal exhaust gas oxygen (UEGO) sensor to
check the fuel mixture after replacing the fuel regulator,
fuel mixer, or silencer. The engine should be warm when
the fuel mixture is checked. See Section 6.12.6 for
instructions to check the fuel mixture.
Refer to the troubleshooting instructions in
Section 3,Troubleshooting, to identify generator set
operation problems that may be caused by an
inadequate fuel supply, incorrect adjustments, or
damaged fuel system components. Then use the
instructions in this section to check fuel system
components.

6.12.1 Gas Piping


Verify that the gas pipe size meets the size
specifications in Figure 6-32. Measure the pipe length
from the gas utility pressure regulator to the end of the
pipe where it connects to the fuel inlet of the generator
set. Add 2.4 m (8 ft.) for each bend in the pipe.
Compare the total length with the chart in Figure 6-32. If
the piping is longer than the maximum length shown in
the chart, replace it with a larger pipe size. Bleed the air
from the gas lines after installation.

TP-6196 10/09

Gas Flow Rate, Btu/hr.


Generator Set Model

Natural Gas

LP

8.5kW

132000

180000

12kW

202000

270000

Figure 6-33 Maximum Natural Gas Flow Rate

6.12.2 Fuel Solenoid Valve


A solenoid valve upstream of the regulator and the
flexible fuel connector provides automatic fuel on/off
control. The engine starting battery powers the solenoid
valve and the engine starting controls open the valve
when the engine cranks or runs.
Gas Valve Operation Test Procedure
1. Disconnect the positive (+) battery lead from the
gas valve terminal.
2. Apply 12 VDC to the gas valve terminal and listen
for an audible click, indicating that the valve
actuates.
3. Replace the gas valve if it does not actuate in
step 2.

6.12.3 Fuel Regulators


The typical gaseous fuel system uses two regulators.
The primary regulator reduces the line pressure to an
allowable inlet pressure for the secondary regulator.
The fuel supplier provides and maintains the primary
regulator. The secondary regulator is factory-installed
on the generator set and is designed for a maximum inlet
pressure of 2.7 kPa (6 oz./in.2) or 280 mm (11 in.) water
column.
Note: Do not attempt to adjust the fuel mixture or engine
speed by adjusting the regulators.

Section 6 Component Testing and Adjustment

93

The fuel lock-off prevents fuel flow when the engine is


not operating. See Figure 6-35. Do not try to adjust the
fuel pressure, fuel mixture, or engine speed using the
fuel lock-off.
Checking the Fuel Pressure
Use a gauge or manometer to check the fuel pressure at
the secondary regulator inlet.
See Figure 6-35.
Measure the fuel pressure with the generator set
running at rated load. Verify that the fuel pressure is
within the range shown in Figure 6-34. Contact the fuel
supplier if the inlet pressure is not within the specified
range.

6.12.4 Fuel Conversion


The multi-fuel system allows conversion from natural
gas to LP vapor (or vice-versa) in the field while
maintaining emissions-standard compliance. A trained
technician or authorized distributor/dealer can convert
the fuel system.
Two fuel connections on the fuel metering valve allow
field conversion between natural gas and LP vapor. The
fuel metering valves are factory-set and sealed to
comply with applicable emission standards and to
provide the best possible hot and cold starting.

Supply Pressure
kPa (in. water column)

Fuel Type
Natural Gas

1.2--2.7 (5--11)

LP

1.7--2.7 (7--11)

Figure 6-34 Fuel Supply Pressure

2
1

4
8
5

Regulator, Side View

7
1.
2.
3.
4.

Hose fitting
Plug
Fuel metering valve (factory-sealed, do not adjust)
Secondary regulator

TP-6196

5.
6.
7.
8.

Fuel solenoid valve


Fuel inlet, 1/2 in. NPT
Fuel lockoff (do not adjust)
Inlet pressure check location

Figure 6-35 Fuel Regulator, Fuel Metering Valve, and Fuel Solenoid Valve

94

Section 6 Component Testing and Adjustment

TP-6196 10/09

1. Place the generator set master switch in the OFF


position.

Fuel Conversion Procedure


Use the following procedure to convert from natural gas
to LP vapor. See Figure 6-36 for the fuel system
component locations.

2. Disconnect the power to the battery charger.


3. Disconnect the generator set engine starting
battery, negative (--) lead first.

WARNING

4. Turn off the fuel supply.


5. Remove the hose clamp and fuel hose from the
hose fitting in the fuel metering valve. See
Figure 6-35.

Accidental starting.
Can cause severe injury or death.

6. Remove the hose fitting from the natural gas outlet


port in the fuel metering valve. See Figure 6-35.

Disconnect the battery cables before


working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.

7. Remove the plug from the LP port in the fuel


metering valve. See Figure 6-35. Clean the plug
with a dry cloth or brush, apply fresh pipe sealant,
and install the plug into the natural gas outlet port.

Disabling the generator set. Accidental starting can


cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.

8. Clean the hose fitting with a dry cloth or brush,


apply fresh pipe sealant to the threads, and install
the fitting into the LP port.
Note: Do not adjust the fuel metering valves.
9. Slide the hose onto the hose fitting and secure it
with the clamp.
10. For 12 kW models only: Connect the digital
spark-advance ignition (DSAI) leads together for
natural gas. (Disconnect the leads for LP.) See
Figure 6-37.

1. DSAI connector location


2. Fuel metering valve
3. Fuel inlet, 1/2 in. NPT female

GM29253

Figure 6-36 Generator Set Fuel System Location, Air


Inlet Side

TP-6196 10/09

tp6195

1. DSAI leads: connect for natural gas, disconnect for LP.

Figure 6-37 Digital Spark Advance Ignition Leads


(12kW only) (located in generator set air
intake area)

Section 6 Component Testing and Adjustment

95

11. Connect and turn on the new fuel supply.


12. Check that the generator set master switch is in the
OFF position.
13. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
14. Reconnect power to the battery charger.
15. Start the generator set by moving the generator set
master switch to the RUN position.

Only trained, authorized service technicians may adjust


the new fuel metering valve. The adjustment procedure
requires a digital volt meter (DVM), UEGO oxygen
sensor service kit GM29385, and a load bank capable of
the rated kW for the fuel being used. Always use an
oxygen sensor when adjusting the fuel metering valves.
Observe the following safety precautions while
performing the procedure.

WARNING

16. Check for leaks using a gas leak detector.


17. Move the generator set master switch to the AUTO
position.
To convert from LP vapor to natural gas, follow the same
fuel conversion procedure, moving the hose fitting to the
natural gas port and plugging the LP port. For the
12kWmodel, disconnect the DSAI leads for LP vapor.
See Figure 6-37.

6.12.5 Digital Spark Advance Ignition


The digital spark advance ignition (DSAI) on the Model
12kWoptimizes the engine timing for the selected fuel,
natural gas or LP. The location of the DSAI leads is
shown in Figure 6-36. Connect the DSAI leads in the air
intake compartment together for natural gas fuel.
Disconnect the leads if LP is used. See Figure 6-37.
See the engine service manual for DSAI service
information.

6.12.6 Fuel Metering Valve Adjustment

Hot engine and exhaust system.


Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the exhaust system. Hot parts can cause
severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.

Fuel Mixture Check/Fuel Metering Valve


Adjustment Procedure
1. Place the generator set master switch in the OFF
position.
2. Disconnect power to the battery charger.
3. Remove the oxygen sensor plug from the exhaust
manifold and install the oxygen sensor. See
Figure 6-38 for location.

The fuel system is factory-adjusted to comply with


applicable emission standards and to provide the best
possible hot and cold starting.

Note: Adjusting the fuel metering valves on emissionscertified generator sets may void the emission
certification.
Use a universal exhaust gas oxygen (UEGO) sensor to
check the fuel mixture after replacing the fuel regulator,
carburetor, or silencer. Use the following procedure to
check the fuel mixture after the engine has reached
normal operating temperature.
The fuel metering valves are sealed to prevent field
adjustments. If the fuel metering valve requires
adjustment, do not break the seals on the fuel metering
valve. Obtain a new fuel metering valve from the
manufacturer and replace the sealed valve with the new
part. See Figure 6-36 for the fuel metering valve
location. Refer to the generator set Parts Catalog for the
fuel metering valve part number.
96

Section 6 Component Testing and Adjustment

GM29253

1. Oxygen sensor mounting location

Figure 6-38 Oxygen Sensor Mounting Location

TP-6196 10/09

4. Connect the oxygen sensor to the engine starting


battery, control module, and voltmeter as shown in
Figure 6-40.

11. When the fuel mixture is correct, use thread sealant


to seal the metering valve adjustment screws.

5. Reconnect power to the battery charger.

12. Remove the load and allow the generator set to run
unloaded to cool for at least 510 minutes.

6. Place the controller master switch in the RUN


position to start the generator set.

13. Place the generator set master switch in the OFF


position.

7. Allow the generator set to run until the engine


reaches normal operating temperature.

14. Disconnect the generator set engine starting


battery, negative (--) lead first.

8. With the generator set at normal operating


temperature, apply rated load.

15. Allow the generator set exhaust system to cool.

9. Connect one of the DVM leads to the oxygen


sensor lead. Connect the other DVM lead to
ground and measure the output voltage of the
oxygen sensor (potential to ground).
10. Adjust the fuel metering valve as required to obtain
the output from the oxygen sensor specified in
Figure 6-39. The output of the oxygen sensor
reads high when the mixture is fuel-rich and close
to zero volts when the mixture is lean.
Oxygen Sensor Reading,
VDC
Model
8.5kW

Natural Gas
2.400.05

LP
2.250.05

12kW

2.600.05

2.600.05

16. Disconnect the DVM leads from the oxygen


sensor.
17. Remove the oxygen sensor from exhaust manifold.
18. Apply a small amount of antiseize compound to
exhaust plug and reinstall the plug into the exhaust
manifold.
19. Check that the generator set master switch is in the
OFF position.
20. Reconnect the generator set engine starting
battery, negative (--) lead last.
21. Reconnect power to the battery charger.

Figure 6-39 Acceptable Oxygen Sensor Readings

GM-28981-

4
1.
2.
3.
4.

Battery power supply connection


Digital voltmeter (DVM) connection
Air/fuel control module connection
Oxygen sensor connection

Figure 6-40 UEGO Sensor Interface Harness GM28981 Electrical Connections


TP-6196 10/09

Section 6 Component Testing and Adjustment

97

6.13 Fuses
Three fuses are located on the junction box next to the
controller display/keypad. (Early models may have the
fuses located in the wiring harness.) See Figure 6-41.
Another 10-amp fuse protects the battery charger.
Fuse

Label

Part Number

Auxiliary Winding, 20 amps

F1

292937

Relay Interface Board, 10 amps

F2

223316

Controller, 10 amps

F3

223316

Battery Charger, 10 amps

223316

Relay Terminal

Lead

30

14P

85

N7

86

71

87

14S

87A

NC

Figure 6-43 Starter Relay Connections

6.15 Continuity Checks


WARNING

Figure 6-41 Fuses


Always identify and correct the cause of a blown fuse
before restarting the generator set. Refer to Section 3,
Troubleshooting, for conditions that may indicate a
blown fuse. Replace blown fuses with identical
replacement parts.

Hazardous voltage. Moving parts.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.

6.14 Starter Relay


The starter relay contains an internal diode across the
relay coil. See Figure 6-42. Continuity checks across
the coil terminals will show continuity (low resistance) in
one direction and an open circuit in the other.
Figure 6-43 shows the starter relay connections.

Short circuits. Hazardous voltage/current can cause


severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.

259391

Figure 6-42 Starter Relay

98

Section 6 Component Testing and Adjustment

TP-6196 10/09

To further check generator set components, disconnect


the battery and remove wiring harness plugs from the
controller circuit board. Use an ohmmeter to check the
continuity of the components listed in Figure 6-45. Also
see Section 8, Wiring Diagrams.

AUTO

RUN

VBAT

Master Switch in
RUN Position

Zero ohms (continuity) across


COM and AUTO terminals

AUTO

VBAT

RUN

Master Switch in
AUTO Position

Note: Disconnect the generator set battery before


performing continuity checks to prevent damage
to the ohmmeter.

Figure 6-45 gives resistance readings for functional


components. A zero reading on the ohmmeter indicates
continuity. No ohmmeter reading indicates very high
resistance or an open circuit. A measurement that
varies significantly from the value shown in the table
indicates a faulty component; replace faulty
components.

Zero ohms (continuity) across


RUN and COM terminals

Figure 6-44 Generator Set Master Switch Continuity


Checks

Component

Ohmmeter
Connections

Ohmmeter
Scale

Generator set
master switch

RUN and VBAT (see


Figure 6-44)

R x 100

Generator Set
Master Switch Ohmmeter Readings for
Operative Components*
Position
RUN
OFF/RESET

AUTO and VBAT


(see Figure 6-44)

R x 100

AUTO

Zero ohms (continuity). Any other reading


indicates a bad switch.
No reading (open circuit). Any other reading
indicates a bad switch.
Zero ohms (continuity). Any other reading
indicates a bad switch.

OFF/RESET

No reading (open circuit). Any other reading


indicates a bad switch.

P1-27 and ground

Rx1

OFF/RESET

Zero ohms (continuity). Any other reading


indicates a poor ground connection.

P15-1 and P15-3


(stator leads 11 and 44)

Rx1

OFF/RESET

Zero ohms (continuity). If no continuity,


check wiring.

P16-3 and P16-6 (stator


leads 55 and 66)

Rx1

OFF/RESET

Zero ohms (continuity). If no continuity,


check fuse F1 and wiring.

P1-24 and battery


positive (+)

R x 100

OFF/RESET

Zero ohms (continuity). If no continuity is


found, check fuse F3 and wiring.

Auxiliary winding P16-3 and stator lead 55 R x 100


fuse 20 amp fuse

OFF/RESET

Zero ohms (continuity). If no continuity is


found, check for an open circuit and/or a
blown fuse.

Low oil pressure


(LOP) switch *

Lead 13 and ground


(engine block)

R x 100

OFF/RESET

Zero ohms (continuity). No continuity


indicates a bad switch and/or wiring.

Temperature
sensor (CTS) *

P1-8 and P1-9

R x 1000

OFF/RESET

180--2500 ohms, depending on engine


temperature. Zero ohms or an open circuit
indicates bad wiring or a bad switch.

P1 wiring
harness

Controller fuse
and wiring

* See Section 6.11.2, Fault Shutdown Switches

Figure 6-45 Continuity Checks

TP-6196 10/09

Section 6 Component Testing and Adjustment

99

Notes

100 Section 6 Component Testing and Adjustment

TP-6196 10/09

Section 7 Disassembly/Reassembly
This section provides instructions for the disassembly
and reassembly of the generator set alternator. Before
beginning the generator disassembly or reassembly
procedure, carefully read all safety precautions at the
beginning of this manual.

b. Place the generator set master switch in the


OFF position.
c. Remove 4 roof screws. Lift the roof up and off.
See Figure 7-1.
d. Remove 5 screws to remove the front panel.
Remove the plastic caps to access the 2 side
screws. See Figure 7-2.

7.1 Disassembly
The disassembly procedure provides important
information to minimize disassembly time and indicates
where special configurations exist, which may require
taking notes.

1
2

The engine and generator set may use both American


Standard and metric hardware. Use the correct size
tools to prevent rounding of the bolt heads and nuts.
1. Remove the generator set from service and
remove the generator set enclosure.
a. Remove the enclosure service-side door. See
Figure 7-1.
1

tp6196

1. Screws (2 ea.)
2. Plastic caps (2 ea.) (remove to access screws)
3. Screw (1 ea.) (access from inside the enclosure)

Figure 7-2

Front Panel Mounting Screw Locations

e. Disconnect power to the battery charger.


1

f. Disconnect the generator set engine starting


battery, negative (--) lead first.

4
5

g. Turn off the fuel supply to the generator set.

tp6196

1. Roof
2. Roof locating pin
3. Roof screws (4 ea.)

Figure 7-1

4. Service-side door
5. Front panel (air intake end)
6. Rear panel (exhaust end)

Generator Set Weather Housing

TP-6196 10/09

Section 7 Disassembly/Reassembly 101

h. From the inside of the enclosure, remove 5


screws to remove the rear (exhaust end) panel.
See Figure 7-3.

2
1

tp6196

1
2
1. Screws (5 ea.)

Figure 7-3

Rear Panel Mounting Screw Locations


(viewed from inside the enclosure)

i. From the inside of the enclosure, remove the


remaining screws to remove the non-service
side housing panel.
4

2. Note the alternator connections inside the


controller box for reconnection later. Disconnect
the alternator leads inside the controller box. See
Figure 7-4 or Figure 7-5 and the wiring diagrams in
Section 8.
3. Remove the engine exhaust muffler and alternator
heat shield. See Figure 7-6.
a. Disconnect the muffler from the engine exhaust
pipe at the two flange connections.

Controller Box Top View


1.
2.
3.
4.

GM29253A-F

Controller box location


Line circuit breaker
SCR module
Neutral connection terminal L0

Figure 7-4

Alternator Connections inside Controller


Box, ADC 2100

b. Remove the bolts holding the muffler to the


alternator heat shield and remove the muffler.
c. Remove the bolts securing the heat shield to
the alternator and remove the heat shield.

102 Section 7 Disassembly/Reassembly

TP-6196 10/09

Junction Box Detail


1
1
4
L0

3
Top View

GM29253

1. Exhaust shield screws


2. Alternator air inlet duct screws

Figure 7-7

Shield and Alternator Air Inlet Duct,


Top View

a. Remove two bolts securing the exhaust shield


at the exhaust end and remove the shield.
b. Remove three bolts securing the alternator air
inlet duct to the base and remove the duct.
GM57149

1.
2.
3.
4.
5.

Line circuit breaker


Neutral (L0)
Ground terminal
SCR module
Fuses

Figure 7-5

5. Remove the alternator end bracket.


a. Remove the nuts securing the alternator end
vibromount mounting plate to the skid. See
Figure 7-8.

Alternator Connections inside Controller


Box, ADC-RES
1

5
1

GM29253A-F

1. Alternator end vibromount


ADV-7466

1. Engine exhaust muffler


2. Muffler bolts
3. Heat shield

Figure 7-6

Figure 7-8

Generator Set, Right Side (typical)

4. Flange connection
5. Heat shield bolts

Muffler and Heat Shield

4. Remove the exhaust shield and alternator air inlet


duct. See Figure 7-7.

TP-6196 10/09

Section 7 Disassembly/Reassembly 103

b. Raise the alternator end of the generator set


enough to place a thin block of wood beneath
the rear of the engine. See Figure 7-9.

retainer wire hole.


Figure 7-11.

See Figure 7-10 and

1
2
3
2
Front View
4

GM29253A
GM29253B-P

1. Engine support block

Figure 7-9

Generator Set, Right Side

Side View

c. Remove 4 screws securing the brush cover to


the alternator end bracket. See Figure 7-10.

3
New 1.9 cm (0.75 in.)

2
3

TP5867

1.
2.
3.
4.

Brush holder
Slip ring
Brush(es)
Retainer wire

5.
6.
7.
8.

Shim
Spring
Correctly positioned brush
Incorrectly positioned brush

Figure 7-11 Brush Details


e. Remove the alternator overbolts and centering
washers. See Figure 7-10.

f. Using a soft-faced hammer, strike the side of


the end bracket with medium-force blows to
remove the end bracket from the stator or
remove the end bracket from the stator using a
puller.

2
6

GM29253B-P

1.
2.
3.
4.
5.
6.

Brush cover screws


Overbolt and centering washer
Alternator end bracket
Brush holder
Brush retainer wire hole
Thrubolt

Figure 7-10 Alternator End Bracket


d. Raise the brushes in the brush holder and
insert a small piece of wire into the brush holder
104 Section 7 Disassembly/Reassembly

g. Remove the leads connected to the end


bracket from the convoluted conduit leading to
controller. Set the end bracket assembly aside.
6. Check the brushes.
a. Remove the brush holder from the end bracket.
See Figure 7-10.
b. Inspect the brushes. Replace brushes when
they are worn to half of their original size. See
Figure 7-11 and Section 6.6, Brushes.

TP-6196 10/09

7. Remove the stator and rotor.

7.2 Reassembly

a. Remove the stator from the rotor.

1. Reinstall the generator adapter onto the engine.

b. Loosen and remove the thrubolt. Use a strap


wrench on the rotor to keep the rotor from
turning during loosening, if necessary. See
Figure 7-12.

a. Attach the generator adapter and alternator


adapter guard to the engine using four
7/16-14 x 1.0 hex cap bolts and washers. See
Figure 7-13.

c. Remove the rotor assembly by striking the side


of the rotor repeatedly with a soft-faced
hammer to loosen it from the tapered
crankshaft fitting. See Figure 7-12. Rotate the
rotor and strike it on alternate sides. Set the
rotor assembly aside.

b. Torque the bolts to 40 Nm (28 ft. lb.).


2. Install the rotor. See Figure 7-12.
a. Clean the crankshaft stub and mating surface
on the fan hub. Do not use antisieze compound
when reassembling the rotor.
b. Install the rotor onto the engine crankshaft.

c. Thread the thrubolt through the actuator and


rotor into the crankshaft. Do not tighten the
thrubolt.

3. Install the stator and end bracket.


a. Align the stator so that the alternator frame
vibromount points down toward the generator
base. See Figure 7-14. Install the stator
assembly around the rotor.

GM29253A

1. Thrubolt and magnetic actuator


2. Rotor strike surface
3. Generator adaptor

Figure 7-12 Rotor and Thrubolt


8. Remove the four engine adapter mounting bolts.
See Figure 7-13. Remove the generator adapter.
2
1

GM29253A

1. End bracket
2. Alternator frame vibromount

Figure 7-14 Generator Set, Right Side (typical)


4

b. Align the alignment mark on the top of the stator


with the slot in the generator adaptor.

3
A-358000A-B

1. Generator adapter
2. Generator fan guard

3. Engine adapter mounting holes


4. Alternator adapter guard

Figure 7-13 Generator Adapter

TP-6196 10/09

c. Route the leads connected to the alternator end


bracket through the opening in the base of the
alternator frame.
d. Place the end bracket onto the stator assembly,
lining up the alignment marks on the top of the
stator and end bracket.
Section 7 Disassembly/Reassembly 105

e. Thread the four overbolts with locating washers


through the end bracket and into the generator
adapter. Position the locating tab of each
washer to the outer edge of the oblong
(OBROUND) hole on the end bracket. See
Figure 7-15. The overbolts should be parallel
to the outside of the alternator. If the overbolts
are slanted, rotate the locating washer 1/2 turn.
Do not final tighten the overbolts.
1

tp6196

1. Alternator assembly overbolts


2. Rotor thrubolt
3. Vibromount plate

Figure 7-16 Generator Set, Right Side (typical)


6. Reinstall the end bracket components.
a. Install the brush holder onto the end bracket.
Verify that the brushes are not sticking in the
holder.
GM29253B-P

1. OBROUND holes for overbolts (4)

Figure 7-15 End Bracket


4. Secure the generator set to the skid.
a. Raise the alternator end of the generator set
and remove the block of wood from beneath the
rear of the engine.
b. Lower the end of the generator set and reinstall
the screws and washers that secure the
vibromount mounting plate to the generator set
skid. See Figure 7-16.

b. Verify that the brushes are centered on the slip


rings. If required, insert spacers between the
mounting surface and brush holder to center
the brushes on the slip rings. See Figure 7-17.
See Section 6.6, Brushes, for more
information.
c. Reinstall the brush cover onto the alternator
end bracket. Verify that the brush leads are not
pinched between the brush cover and end
bracket.
1
2

5. Tighten the hardware to the following torques. See


Figure 7-16.

a. Tighten the rotor thrubolt to 40 Nm (28 ft. lb.). It


may be necessary to keep the engine flywheel
from turning while torquing the rotor thrubolt.
5632716

b. Tighten the four alternator assembly overbolts


to 7 Nm (60 in. lb.).

1. Brush holder
2. Brushes
3. Slip rings

Figure 7-17 Brush Positioning

106 Section 7 Disassembly/Reassembly

TP-6196 10/09

7. Reinstall the alternator air inlet duct. Orient the


duct as shown in Figure 7-18.

8. Install the exhaust shield. See Figure 7-18.

3
GM29253C-U

1. Alternator air inlet duct

2. Mounting screws (3 ea.)

3. Exhaust shield

Figure 7-18 Alternator Air Inlet Duct


9. Install the exhaust system. See Figure 7-19.
a. Install the heat shield onto the alternator
exhaust support using M8 hardware.
b. Using new gaskets, connect the engine
exhaust muffler to the engine at the flanges. Do
not final tighten the mounting hardware.

10. Reconnect the alternator leads inside the controller


box. See the wiring diagrams in Section 8 for
connections.
11. Reinstall the enclosure panels in reverse order of
removal. See Figure 7-20 and refer to Step 1 of the
disassembly instructions.
a. Install the non-service side housing panel.

c. Secure the muffler mounting tab to the heat


shield with M8 hardware.

b. Install the alternator end housing panel.


c. Install the generator set housing roof.

d. Torque the nuts securing the engine muffler


flange to the engine to 24 Nm (216 in. lb.).

1
1

3
5

4
ADV-7466

1.
2.
3.
4.
5.

Engine exhaust muffler


Muffler bolts
Heat shield
Flange connection
Heat shield bolts

1. Roof
2. Service-side door
3. Front panel (air intake end)

tp6196

4. Mounting pad
5. Rear panel (alternator end)

Figure 7-20 Generator Set Enclosure


Figure 7-19 Exhaust System
TP-6196 10/09

Section 7 Disassembly/Reassembly 107

12. Return the generator set to operation.


a. Check that the generator set master switch is in
the OFF position.
b. Reconnect the generator set engine starting
battery, negative (--) lead last.
c. Reconnect power to the battery charger, if
equipped.

108 Section 7 Disassembly/Reassembly

13. Turn on the fuel supply. Move the generator set


master switch to the RUN position and check for
leaks with the engine running.
14. Move the generator set master switch to the
OFF/RESET position. Move the switch to the
AUTO position if an automatic transfer switch or
remote start/stop switch is used.
15. Reinstall the generator set housing service side
door.

TP-6196 10/09

Section 8 Wiring Diagrams


At the time of print, this manual applied to the models with controllers shown in Figure 8-1. The schematics and wiring
diagram drawing numbers and page numbers are listed in the table below. The drawings are arranged in numerical
order on the following pages.
Schematic
Drawing Number

Page

ADV-6835A

110

ADV-6835B

111

ADV-7592

115

ADV-6835A

110

ADV-6835B

111

ADV-7592

115

ADV-7296A

112

ADV-7296B

113

DC-RET

ADV-7351

114

ADC-RES

ADV-7623:
Sheet 3
Sheet 4

116
117

Model No.

Controller

8.5RES

ADC 2100

8.5RES

ADC-RES

12RES

ADC 2100

12RES

ADC-RES

12RESL
12RESM1

DC 2200

12RESL
12RESM1
12RESNT
12TRES
(3-phase 50 Hz)

Figure 8-1

Point-to-Point Wiring Diagram


Drawing Number

Page

GM29358

118

GM66285

121

GM29358

118

GM66285

121

GM49761

119

GM52471

120

GM63546
(sheet 3)

122

Wiring Diagrams and Schematics

TP-6196 10/09

Section 8 Wiring Diagrams 109

Figure 8-2

Schematic Diagram, Single-Phase, 8.5/12RES w/ADC 2100 Controller, ADV-6835A-E

110 Section 8 Wiring Diagrams

TP-6196 10/09

Figure 8-3

Schematic Diagram, Single-Phase, 8.5/12RES w/ADC 2100 Controller, ADV-6835B-E

TP-6196 10/09

Section 8 Wiring Diagrams 111

Figure 8-4

Schematic Diagram, Single-Phase, 12RESL/RESM1 w/DC 2200 Controller, ADV-7296A-

112 Section 8 Wiring Diagrams

TP-6196 10/09

Figure 8-5

Schematic Diagram, Single-Phase, 12RESL/RESM1 w/DC 2200 Controller, ADV-7296B-

TP-6196 10/09

Section 8 Wiring Diagrams 113

Figure 8-6

Schematic Diagram, Single-Phase, 12RESL/RESM1/RESNT w/DC-RET Controller, ADV-7351-D

114 Section 8 Wiring Diagrams

TP-6196 10/09

Figure 8-7

Schematic Diagram, Single-Phase, 8.5/12RES w/ADC-RES Controller, ADV-7592-

TP-6196 10/09

Section 8 Wiring Diagrams 115

Figure 8-8

Schematic Diagram, Three-Phase, 12TRES w/ADC-RES Controller, ADV-7623 Sheet 3

116 Section 8 Wiring Diagrams

TP-6196 10/09

Figure 8-9

Schematic Diagram, Three-Phase, 12TRES w/ADC-RES Controller, ADV-7623 Sheet 4

TP-6196 10/09

Section 8 Wiring Diagrams 117

Figure 8-10 Point-to-Point Wiring Diagram, Single-Phase, 8.5/12RES w/ADC 2100 Controller, GM29358-E

118 Section 8 Wiring Diagrams

TP-6196 10/09

Figure 8-11 Point-to-Point Wiring Diagram, Single-Phase, 12RESL/RESM1 w/DC 2200 Controller, GM49761-A

TP-6196 10/09

Section 8 Wiring Diagrams 119

Figure 8-12 Point-to-Point Wiring Diagram, Single-Phase, 12RESL/RESM1/RESNT w/DC-RET Controller,


GM52471-C
120 Section 8 Wiring Diagrams

TP-6196 10/09

Figure 8-13 Point-to-Point Wiring Diagram, Single-Phase, 8.5/12RES w/ADC-RES Controller, GM66285TP-6196 10/09

Section 8 Wiring Diagrams 121

Figure 8-14 Point-to-Point Wiring Diagram, Three-Phase, 12TRES w/ADC-RES Controller, GM63546, Sheet 3

122 Section 8 Wiring Diagrams

TP-6196 10/09

Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, amp
ABDC
AC
A/D
ADC
adj.
ADV
Ah
AHWT
AISI
ALOP
alt.
Al
ANSI
AO
APDC
API
approx.
AQMD
AR
AS
ASE
ASME
assy.
ASTM
ATDC
ATS
auto.
aux.
avg.
AVR
AWG
AWM
bat.
BBDC
BC
BCA
BCI
BDC
BHP
blk.
blk. htr.
BMEP
bps
br.
BTDC
Btu
Btu/min.
C
cal.
CAN
CARB
CB
cc
CCA
ccw.
CEC
cert.
cfh

ampere
after bottom dead center
alternating current
analog to digital
advanced digital control;
analog to digital converter
adjust, adjustment
advertising dimensional
drawing
amp-hour
anticipatory high water
temperature
American Iron and Steel
Institute
anticipatory low oil pressure
alternator
aluminum
American National Standards
Institute (formerly American
Standards Association, ASA)
anticipatory only
Air Pollution Control District
American Petroleum Institute
approximate, approximately
Air Quality Management District
as required, as requested
as supplied, as stated, as
suggested
American Society of Engineers
American Society of
Mechanical Engineers
assembly
American Society for Testing
Materials
after top dead center
automatic transfer switch
automatic
auxiliary
average
automatic voltage regulator
American Wire Gauge
appliance wiring material
battery
before bottom dead center
battery charger, battery
charging
battery charging alternator
Battery Council International
before dead center
brake horsepower
black (paint color), block
(engine)
block heater
brake mean effective pressure
bits per second
brass
before top dead center
British thermal unit
British thermal units per minute
Celsius, centigrade
calorie
controller area network
California Air Resources Board
circuit breaker
cubic centimeter
cold cranking amps
counterclockwise
Canadian Electrical Code
certificate, certification, certified
cubic feet per hour

TP-6196 10/09

cfm
CG
CID
CL
cm
CMOS

cubic feet per minute


center of gravity
cubic inch displacement
centerline
centimeter
complementary metal oxide
substrate (semiconductor)
cogen.
cogeneration
com
communications (port)
coml
commercial
Coml/Rec Commercial/Recreational
conn.
connection
cont.
continued
CPVC
chlorinated polyvinyl chloride
crit.
critical
CRT
cathode ray tube
CSA
Canadian Standards
Association
CT
current transformer
Cu
copper
cUL
Canadian Underwriters
Laboratories
CUL
Canadian Underwriters
Laboratories
cu. in.
cubic inch
cw.
clockwise
CWC
city water-cooled
cyl.
cylinder
D/A
digital to analog
DAC
digital to analog converter
dB
decibel
dB(A)
decibel (A weighted)
DC
direct current
DCR
direct current resistance
deg.,
degree
dept.
department
DFMEA Design Failure Mode and
Effects Analysis
dia.
diameter
DI/EO
dual inlet/end outlet
DIN
Deutsches Institut fur Normung
e. V. (also Deutsche Industrie
Normenausschuss)
DIP
dual inline package
DPDT
double-pole, double-throw
DPST
double-pole, single-throw
DS
disconnect switch
DVR
digital voltage regulator
E, emer. emergency (power source)
ECM
electronic control module,
engine control module
EDI
electronic data interchange
EFR
emergency frequency relay
e.g.
for example (exempli gratia)
EG
electronic governor
EGSA
Electrical Generating Systems
Association
EIA
Electronic Industries
Association
EI/EO
end inlet/end outlet
EMI
electromagnetic interference
emiss.
emission
eng.
engine
EPA
Environmental Protection
Agency
EPS
emergency power system
ER
emergency relay
ES
engineering special,
engineered special
ESD
electrostatic discharge

est.
E-Stop
etc.
exh.
ext.
F
fglass.
FHM
fl. oz.
flex.
freq.
FS
ft.
ft. lb.
ft./min.
ftp
g
ga.
gal.
gen.
genset
GFI

estimated
emergency stop
et cetera (and so forth)
exhaust
external
Fahrenheit, female
fiberglass
flat head machine (screw)
fluid ounce
flexible
frequency
full scale
foot, feet
foot pounds (torque)
feet per minute
file transfer protocol
gram
gauge (meters, wire size)
gallon
generator
generator set
ground fault interrupter

GND,
gov.
gph
gpm
gr.
GRD
gr. wt.
HxWxD
HC
HCHT
HD
HET

ground
governor
gallons per hour
gallons per minute
grade, gross
equipment ground
gross weight
height by width by depth
hex cap
high cylinder head temperature
heavy duty
high exhaust temp., high
engine temp.
hexagon
mercury (element)
hex head
hex head cap
horsepower
hour
heat shrink
housing
heating, ventilation, and air
conditioning
high water temperature
hertz (cycles per second)
integrated circuit
inside diameter, identification
International Electrotechnical
Commission
Institute of Electrical and
Electronics Engineers
improved motor starting
inch
inches of water
inches of mercury
inch pounds
incorporated
industrial
internal
internal/external
input/output
iron pipe
International Organization for
Standardization
joule
Japanese Industry Standard

hex
Hg
HH
HHC
HP
hr.
HS
hsg.
HVAC
HWT
Hz
IC
ID
IEC
IEEE
IMS
in.
in. H2O
in. Hg
in. lb.
Inc.
ind.
int.
int./ext.
I/O
IP
ISO
J
JIS

Appendix 123

k
K
kA
KB
KBus
kg
kg/cm2

kilo (1000)
kelvin
kiloampere
kilobyte (210 bytes)
Kohler communication protocol
kilogram
kilograms per square
centimeter
kgm
kilogram-meter
kg/m3
kilograms per cubic meter
kHz
kilohertz
kJ
kilojoule
km
kilometer
kOhm, k kilo-ohm
kPa
kilopascal
kph
kilometers per hour
kV
kilovolt
kVA
kilovolt ampere
kVAR
kilovolt ampere reactive
kW
kilowatt
kWh
kilowatt-hour
kWm
kilowatt mechanical
kWth
kilowatt-thermal
L
liter
LAN
local area network
L x W x H length by width by height
lb.
pound, pounds
lbm/ft3
pounds mass per cubic feet
LCB
line circuit breaker
LCD
liquid crystal display
ld. shd.
load shed
LED
light emitting diode
Lph
liters per hour
Lpm
liters per minute
LOP
low oil pressure
LP
liquefied petroleum
LPG
liquefied petroleum gas
LS
left side
Lwa
sound power level, A weighted
LWL
low water level
LWT
low water temperature
m
meter, milli (1/1000)
M
mega (106 when used with SI
units), male
m3
cubic meter
m3/hr.
cubic meters per hour
cubic meters per minute
m3/min.
mA
milliampere
man.
manual
max.
maximum
MB
megabyte (220 bytes)
MCCB
molded-case circuit breaker
MCM
one thousand circular mils
meggar
megohmmeter
MHz
megahertz
mi.
mile
mil
one one-thousandth of an inch
min.
minimum, minute
misc.
miscellaneous
MJ
megajoule
mJ
millijoule
mm
millimeter
mOhm, mmilliohm
MOhm, Mmegohm
MOV
metal oxide varistor
MPa
megapascal
mpg
miles per gallon
mph
miles per hour
MS
military standard
ms
millisecond
m/sec.
meters per second
MTBF
mean time between failure

124 Appendix

MTBO
mtg.
MTU
MW
mW
F
N, norm.
NA
nat. gas
NBS
NC
NEC
NEMA

mean time between overhauls


mounting
Motoren-und Turbinen-Union
megawatt
milliwatt
microfarad
normal (power source)
not available, not applicable
natural gas
National Bureau of Standards
normally closed
National Electrical Code
National Electrical
Manufacturers Association
NFPA
National Fire Protection
Association
Nm
newton meter
NO
normally open
no., nos. number, numbers
NPS
National Pipe, Straight
NPSC
National Pipe, Straight-coupling
NPT
National Standard taper pipe
thread per general use
NPTF
National Pipe, Taper-Fine
NR
not required, normal relay
ns
nanosecond
OC
overcrank
OD
outside diameter
OEM
original equipment
manufacturer
OF
overfrequency
opt.
option, optional
OS
oversize, overspeed
OSHA
Occupational Safety and Health
Administration
OV
overvoltage
oz.
ounce
p., pp.
page, pages
PC
personal computer
PCB
printed circuit board
pF
picofarad
PF
power factor
ph.,
phase
PHC
Phillips# head Crimptite#
(screw)
PHH
Phillips# hex head (screw)
PHM
pan head machine (screw)
PLC
programmable logic control
PMG
permanent magnet generator
pot
potentiometer, potential
ppm
parts per million
PROM
programmable read-only
memory
psi
pounds per square inch
psig
pounds per square inch gauge
pt.
pint
PTC
positive temperature coefficient
PTO
power takeoff
PVC
polyvinyl chloride
qt.
quart, quarts
qty.
quantity
R
replacement (emergency)
power source
rad.
radiator, radius
RAM
random access memory
RDO
relay driver output
ref.
reference
rem.
remote
Res/Coml Residential/Commercial
RFI
radio frequency interference
RH
round head
RHM
round head machine (screw)
rly.
relay

rms
rnd.
ROM
rot.
rpm
RS
RTU
RTV
RW
SAE
scfm
SCR
s, sec.
SI
SI/EO
sil.
SN
SNMP
SPDT
SPST
spec
specs
sq.
sq. cm
sq. in.
SS
std.
stl.
tach.
TD
TDC
TDEC
TDEN
TDES
TDNE
TDOE
TDON
temp.
term.
THD
TIF
TIR
tol.
turbo.
typ.
UF
UHF
UL
UNC
UNF
univ.
US
UV
V
VAC
VAR
VDC
VFD
VGA
VHF
W
WCR
w/
w/o
wt.
xfmr

root mean square


round
read only memory
rotate, rotating
revolutions per minute
right side
remote terminal unit
room temperature vulcanization
read/write
Society of Automotive
Engineers
standard cubic feet per minute
silicon controlled rectifier
second
Systeme international dunites,
International System of Units
side in/end out
silencer
serial number
simple network management
protocol
single-pole, double-throw
single-pole, single-throw
specification
specification(s)
square
square centimeter
square inch
stainless steel
standard
steel
tachometer
time delay
top dead center
time delay engine cooldown
time delay emergency to
normal
time delay engine start
time delay normal to
emergency
time delay off to emergency
time delay off to normal
temperature
terminal
total harmonic distortion
telephone influence factor
total indicator reading
tolerance
turbocharger
typical (same in multiple
locations)
underfrequency
ultrahigh frequency
Underwriters Laboratories, Inc.
unified coarse thread (was NC)
unified fine thread (was NF)
universal
undersize, underspeed
ultraviolet, undervoltage
volt
volts alternating current
voltampere reactive
volts direct current
vacuum fluorescent display
video graphics adapter
very high frequency
watt
withstand and closing rating
with
without
weight
transformer

TP-6196 10/09

Appendix B Common Hardware Application Guidelines


Use the information below and on the following pages to
identify proper fastening techniques when no specific
reference for reassembly is made.
Bolt/Screw Length: When bolt/screw length is not given,
use Figure 1 as a guide. As a general rule, a minimum
length of one thread beyond the nut and a maximum
length of 1/2 the bolt/screw diameter beyond the nut is
the preferred method.

Steps for common hardware application:


1. Determine entry hole type: round or slotted.
2. Determine exit hole type: fixed female thread
(weld nut), round, or slotted.

Washers and Nuts: Use split lock washers as a bolt


locking device where specified. Use SAE flat washers
with whiz nuts, spiralock nuts, or standard nuts and
preloading (torque) of the bolt in all other applications.

For round and slotted exit holes, determine if


hardware is greater than 1/2 inch in diameter, or
1/2 inch in diameter or less. Hardware that is
greater than 1/2 inch in diameter takes a standard
nut and SAE washer. Hardware 1/2 inch or less in
diameter can take a properly torqued whiz nut or
spiralock nut. See Figure 2.

See Appendix C, General Torque Specifications, and


other torque specifications in the service literature.

3. Follow these SAE washer rules after determining


exit hole type:
a. Always use a washer between hardware and a
slot.

Preferred Nut/Bolt Clearance


1

b. Always use a washer under a nut (see 2 above


for exception).
c. Use a washer under a bolt when the female
thread is fixed (weld nut).
4. Refer to Figure 2, which depicts the preceding
hardware configuration possibilities.

Unacceptable Nut/Bolt Clearance


3

3
G-585

1. 1/2 of bolt diameter


2. Min. 1 full thread beyond top of nut
3. Below top of nut

Figure 1

Acceptable Bolt Lengths


5
4

G-585

1.
2.
3.
4.
5.
6.

Cap screw
Entry hole types
Standard nut and SAE washer
Whiz nut or spiralock: up to 1/2 in. dia. hardware
Weld nuts: above 1/2 in. dia. hardware
Exit hole types

Figure 2

TP-6196 10/09

Acceptable Hardware Combinations

Appendix 125

Appendix C General Torque Specifications


American Standard Fasteners Torque Specifications

Size

Assembled into
Aluminum
Grade 2 or 5

Assembled into Cast Iron or Steel

Torque
Measurement

Grade 2

Grade 5

Grade 8

8-32

Nm (in. lb.)

1.8

(16)

2.3

(20)

10-24

Nm (in. lb.)

2.9

(26)

3.6

(32)

10-32

Nm (in. lb.)

2.9

(26)

3.6

(32)

1/4-20

Nm (in. lb.)

6.8

(60)

10.8

(96)

14.9

(132)

1/4-28

Nm (in. lb.)

8.1

(72)

12.2

(108)

16.3

(144)

5/16-18

Nm (in. lb.)

13.6

(120)

21.7

(192)

29.8

(264)

5/16-24

Nm (in. lb.)

14.9

(132)

23.1

(204)

32.5

(288)

3/8-16

Nm (ft. lb.)

24.0

(18)

38.0

(28)

53.0

(39)

3/8-24

Nm (ft. lb.)

27.0

(20)

42.0

(31)

60.0

(44)

7/16-14

Nm (ft. lb.)

39.0

(29)

60.0

(44)

85.0

(63)

7/16-20

Nm (ft. lb.)

43.0

(32)

68.0

(50)

95.0

(70)

1/2-13

Nm (ft. lb.)

60.0

(44)

92.0

(68)

130.0

(96)

1/2-20

Nm (ft. lb.)

66.0

(49)

103.0

(76)

146.0

(108)

9/16-12

Nm (ft. lb.)

81.0

(60)

133.0

(98)

187.0

(138)

9/16-18

Nm (ft. lb.)

91.0

(67)

148.0

(109)

209.0

(154)

5/8-11

Nm (ft. lb.)

113.0

(83)

183.0

(135)

259.0

(191)

5/8-18

Nm (ft. lb.)

128.0

(94)

208.0

(153)

293.0

(216)

3/4-10

Nm (ft. lb.)

199.0

(147)

325.0

(240)

458.0

(338)

3/4-16

Nm (ft. lb.)

222.0

(164)

363.0

(268)

513.0

(378)

1-8

Nm (ft. lb.)

259.0

(191)

721.0

(532)

1109.0

(818)

1-12

Nm (ft. lb.)

283.0

(209)

789.0

(582)

1214.0

(895)

See Note 3

Metric Fasteners Torque Specifications, Measured in Nm (ft. lb.)


Assembled into
Assembled into Cast Iron or Steel
Aluminum
Grade 5.8 or 8.8
Grade 5.8
Grade 8.8
Grade 10.9
Size (mm)
M6

x 1.00

6.2

(4.6)

9.5

(7)

13.6

(10)

M8

x 1.25

15.0

(11)

23.0

(17)

33.0

(24)

M8

x 1.00

16.0

(11)

24.0

(18)

34.0

(25)

M10 x 1.50

30.0

(22)

45.0

(34)

65.0

(48)

M10 x 1.25

31.0

(23)

47.0

(35)

68.0

(50)

M12 x 1.75

53.0

(39)

80.0

(59)

115.0

(85)

M12 x 1.50

56.0

(41)

85.0

(63)

122.0

(90)

M14 x 2.00

83.0

(61)

126.0

(93)

180.0

(133)

M14 x 1.50

87.0

(64)

133.0

(98)

190.0

(140)

M16 x 2.00

127.0

(94)

194.0

(143)

278.0

(205)

M16 x 1.50

132.0

(97)

201.0

(148)

287.0

(212)

M18 x 2.50

179.0

(132)

273.0

(201)

390.0

(288)

M18 x 1.50

189.0

(140)

289.0

(213)

413.0

(305)

See Note 3

Notes:
1. The torque values above are general guidelines. Always use the torque values specified in the service manuals and/or assembly
drawings when they differ from the above torque values.
2. The torque values above are based on new plated threads. Increase torque values by 15% if non-plated threads are used.
3. Hardware threaded into aluminum must have either two diameters of thread engagement or a 30% or more reduction in the torque to
prevent stripped threads.
4. Torque values are calculated as equivalent stress loading on American hardware with an approximate preload of 90% of the yield strength
and a friction coefficient of 0.125.

126 Appendix

TP-6196 10/09

Appendix D Common Hardware Identification


Screw/Bolts/Studs

Nuts

Hardness Grades

Head Styles

Nut Styles

American Standard

Hex Head or Machine Head

Hex Head

Grade 2

Hex Head or Machine Head


with Washer

Lock or Elastic

Grade 5

Flat Head (FHM)

Square

Grade 8

Round Head (RHM)

Cap or Acorn

Grade 8/9 (Hex Socket


Head)

Pan Head

Wing

Metric
Washers

Hex Socket Head Cap or


Allen$ Head Cap

5.8

Washer Styles

Hex Socket Head or Allen$


Head Shoulder Bolt

Plain

Sheet Metal Screw

Split Lock or Spring

Stud

Spring or Wave

Drive Styles

Number stamped on
hardware; 5.8 shown

External Tooth Lock

Hex
Internal Tooth Lock
Hex and Slotted
Internal-External Tooth Lock
Phillips#
Slotted
Hex Socket
Allen$ head screw is a trademark of Holo-Krome Co.
Phillips# screw is a registered trademark of Phillips Screw Company.

Sample Dimensions
American Standard (Screws, Bolts, Studs, and Nuts)
1/4-20 x 1
Length In Inches (Screws and Bolts)

Plain Washers
9/32 x 5/8 x 1/16
Thickness

Threads Per Inch

External Dimension

Major Thread Diameter In Fractional Inches Or Screw Number Size

Internal Dimension

Metric (Screws, Bolts, Studs, and Nuts)


M8-1.25 x 20
Length In Millimeters (Screws and Bolts)
Distance Between Threads In Millimeters

Lock Washers
5/8
Internal Dimension

Major Thread Diameter In Millimeters

TP-6196 10/09

Appendix 127

Appendix E Common Hardware List


The Common Hardware List lists part numbers and dimensions for common hardware items.

American Standard
Part No.
Dimensions
Hex Head Bolts (Grade 5)

Part No.
Dimensions
Hex Head Bolts, cont.

Part No.

X-465-17
X-465-6
X-465-2
X-465-16
X-465-18
X-465-7
X-465-8
X-465-9
X-465-10
X-465-11
X-465-12
X-465-14
X-465-21
X-465-25
X-465-20

1/4-20 x .38
1/4-20 x .50
1/4-20 x .62
1/4-20 x .75
1/4-20 x .88
1/4-20 x 1.00
1/4-20 x 1.25
1/4-20 x 1.50
1/4-20 x 1.75
1/4-20 x 2.00
1/4-20 x 2.25
1/4-20 x 2.75
1/4-20 x 5.00
1/4-28 x .38
1/4-28 x 1.00

X-6238-14
X-6238-16
X-6238-21
X-6238-22

3/8-24 x .75
3/8-24 x 1.25
3/8-24 x 4.00
3/8-24 x 4.50

X-6009-1

1-8

Standard

X-6024-5
X-6024-2
X-6024-8
X-6024-3
X-6024-4
X-6024-11
X-6024-12

7/16-14 x .75
7/16-14 x 1.00
7/16-14 x 1.25
7/16-14 x 1.50
7/16-14 x 2.00
7/16-14 x 2.75
7/16-14 x 6.50

X-6210-3
X-6210-4
X-6210-5
X-6210-1

6-32
8-32
10-24
10-32

Whiz
Whiz
Whiz
Whiz

X-125-33
X-125-23
X-125-3
X-125-31
X-125-5
X-125-24
X-125-34
X-125-25
X-125-26
230578
X-125-29
X-125-27
X-125-28
X-125-22
X-125-32
X-125-35
X-125-36
X-125-40

5/16-18 x .50
5/16-18 x .62
5/16-18 x .75
5/16-18 x .88
5/16-18 x 1.00
5/16-18 x 1.25
5/16-18 x 1.50
5/16-18 x 1.75
5/16-18 x 2.00
5/16-18 x 2.25
5/16-18 x 2.50
5/16-18 x 2.75
5/16-18 x 3.00
5/16-18 x 4.50
5/16-18 x 5.00
5/16-18 x 5.50
5/16-18 x 6.00
5/16-18 x 6.50

X-129-15
X-129-17
X-129-18
X-129-19
X-129-20
X-129-21
X-129-22
X-129-23
X-129-24
X-129-25
X-129-27
X-129-29
X-129-30
X-463-9
X-129-44

1/2-13 x .75
1/2-13 x 1.00
1/2-13 x 1.25
1/2-13 x 1.50
1/2-13 x 1.75
1/2-13 x 2.00
1/2-13 x 2.25
1/2-13 x 2.50
1/2-13 x 2.75
1/2-13 x 3.00
1/2-13 x 3.50
1/2-13 x 4.00
1/2-13 x 4.50
1/2-13 x 5.50
1/2-13 x 6.00

X-6210-2
X-6210-6
X-6210-7
X-6210-8
X-6210-9
X-6210-10
X-6210-11
X-6210-12
X-6210-15
X-6210-14

1/4-20
1/4-28
5/16-18
5/16-24
3/8-16
3/8-24
7/16-14
1/2-13
7/16-20
1/2-20

Spiralock
Spiralock
Spiralock
Spiralock
Spiralock
Spiralock
Spiralock
Spiralock
Spiralock
Spiralock

X-85-3
X-88-12
X-89-2

5/8-11
3/4-10
1/2-20

Standard
Standard
Standard

X-129-51
X-129-45
X-129-52

1/2-20 x .75
1/2-20 x 1.25
1/2-20 x 1.50

X-125-43
X-125-44
X-125-30
X-125-39
X-125-38

5/16-24 x 1.75
5/16-24 x 2.50
5/16-24 x .75
5/16-24 x 2.00
5/16-24 x 2.75

X-6238-2
X-6238-10
X-6238-3
X-6238-11
X-6238-4
X-6238-5
X-6238-1
X-6238-6
X-6238-17
X-6238-7
X-6238-8
X-6238-9
X-6238-19
X-6238-12
X-6238-20
X-6238-13
X-6238-18
X-6238-25

3/8-16 x .62
3/8-16 x .75
3/8-16 x .88
3/8-16 x 1.00
3/8-16 x 1.25
3/8-16 x 1.50
3/8-16 x 1.75
3/8-16 x 2.00
3/8-16 x 2.25
3/8-16 x 2.50
3/8-16 x 2.75
3/8-16 x 3.00
3/8-16 x 3.25
3/8-16 x 3.50
3/8-16 x 3.75
3/8-16 x 4.50
3/8-16 x 5.50
3/8-16 x 6.50

X-6021-3
X-6021-4
X-6021-2
X-6021-1
273049
X-6021-5
X-6021-6
X-6021-7
X-6021-12
X-6021-11
X-6021-10

5/8-11 x 1.00
5/8-11 x 1.25
5/8-11 x 1.50
5/8-11 x 1.75
5/8-11 x 2.00
5/8-11 x 2.25
5/8-11 x 2.50
5/8-11 x 2.75
5/8-11 x 3.75
5/8-11 x 4.50
5/8-11 x 6.00

X-6021-9

5/8-18 x 2.50

X-6239-1
X-6239-8
X-6239-2
X-6239-3
X-6239-4
X-6239-5
X-6239-6

3/4-10 x 1.00
3/4-10 x 1.25
3/4-10 x 1.50
3/4-10 x 2.00
3/4-10 x 2.50
3/4-10 x 3.00
3/4-10 x 3.50

X-792-1
X-792-5
X-792-8

1-8 x 2.25
1-8 x 3.00
1-8 x 5.00

128 Appendix

Dimensions

Type

Hex Nuts

Washers
Part No.

ID

X-25-46
.125
X-25-9
.156
X-25-48
.188
X-25-36
.219
X-25-40
.281
X-25-85
.344
X-25-37
.406
X-25-34
.469
X-25-26
.531
X-25-15
.656
X-25-29
.812
X-25-127 1.062

OD
.250
.375
.438
.500
.625
.687
.812
.922
1.062
1.312
1.469
2.000

Bolt/
Thick. Screw
.022
.049
.049
.049
.065
.065
.065
.065
.095
.095
.134
.134

#4
#6
#8
#10
1/4
5/16
3/8
7/16
1/2
5/8
3/4
1

TP-6196 10/09

Metric
Hex head bolts are hardness grade 8.8 unless noted.
Part No.
Dimensions
Hex Head Bolts (Partial Thread)
M931-05055-60
M931-06040-60
M931-06055-60
M931-06060-60
M931-06060-SS
M931-06070-60
M931-06070-SS
M931-06075-60
M931-06090-60
M931-06145-60
M931-06150-60

M5-0.80 x 55
M6-1.00 x 40
M6-1.00 x 55
M6-1.00 x 60
M6-1.00 x 60
M6-1.00 x 70
M6-1.00 x 70
M6-1.00 x 75
M6-1.00 x 90
M6-1.00 x 145
M6-1.00 x 150

M931-08035-60
M931-08040-60
M931-08045-60
M931-08050-60
M931-08055-60
M931-08055-82
M931-08060-60
M931-08070-60
M931-08070-82
M931-08075-60
M931-08080-60
M931-08090-60
M931-08095-60
M931-08100-60
M931-08110-60
M931-08120-60
M931-08130-60
M931-08140-60
M931-08150-60
M931-08200-60

M8-1.25 x 35
M8-1.25 x 40
M8-1.25 x 45
M8-1.25 x 50
M8-1.25 x 55
M8-1.25 x 55*
M8-1.25 x 60
M8-1.25 x 70
M8-1.25 x 70*
M8-1.25 x 75
M8-1.25 x 80
M8-1.25 x 90
M8-1.25 x 95
M8-1.25 x 100
M8-1.25 x 110
M8-1.25 x 120
M8-1.25 x 130
M8-1.25 x 140
M8-1.25 x 150
M8-1.25 x 200

M931-10040-82
M931-10040-60
M931-10045-60
M931-10050-60
M931-10050-82
M931-10055-60
M931-10060-60
M931-10065-60
M931-10070-60
M931-10080-60
M931-10080-82
M931-10090-60
M931-10090-82
M931-10100-60
M931-10110-60
M931-10120-60
M931-10130-60
M931-10140-60
M931-10180-60
M931-10235-60
M931-10260-60
M960-10330-60

M10-1.25 x 40*
M10-1.50 x 40
M10-1.50 x 45
M10-1.50 x 50
M10-1.25 x 50*
M10-1.50 x 55
M10-1.50 x 60
M10-1.50 x 65
M10-1.50 x 70
M10-1.50 x 80
M10-1.25 x 80*
M10-1.50 x 90
M10-1.50 x 90*
M10-1.50 x 100
M10-1.50 x 110
M10-1.50 x 120
M10-1.50 x 130
M10-1.50 x 140
M10-1.50 x 180
M10-1.50 x 235
M10-1.50 x 260
M10-1.25 x 330

M931-12045-60
M960-12050-60
M960-12050-82
M931-12050-60
M931-12050-82
M931-12055-60
M931-12060-60
M931-12060-82
M931-12065-60
M931-12075-60
M931-12080-60
M931-12090-60
M931-12100-60
M931-12110-60

M12-1.75 x 45
M12-1.25 x 50
M12-1.25 x 50*
M12-1.75 x 50
M12-1.75 x 50*
M12-1.75 x 55
M12-1.75 x 60
M12-1.75 x 60*
M12-1.75 x 65
M12-1.75 x 75
M12-1.75 x 80
M12-1.75 x 90
M12-1.75 x 100
M12-1.75 x 110

Part No.
Dimensions
Hex Head Bolts (Partial Thread),
continued

Part No.
Dimensions
Hex Head Bolts (Full Thread),
continued

M960-16090-60
M931-16090-60
M931-16100-60
M931-16100-82
M931-16120-60
M931-16150-60

M16-1.50 x 90
M16-2.00 x 90
M16-2.00 x 100
M16-2.00 x 100*
M16-2.00 x 120
M16-2.00 x 150

M931-20065-60
M931-20090-60
M931-20100-60
M931-20120-60
M931-20140-60
M931-20160-60

M20-2.50 x 65
M20-2.50 x 90
M20-2.50 x 100
M20-2.50 x 120
M20-2.50 x 140
M20-2.50 x 160

M933-12016-60
M933-12020-60
M961-12020-60F
M933-12025-60
M933-12025-82
M961-12030-60
M933-12030-82
M961-12030-82F
M933-12030-60
M933-12035-60
M961-12040-82
M933-12040-60
M933-12040-82

M12-1.75 x 16
M12-1.75 x 20
M12-1.50 x 20
M12-1.75 x 25
M12-1.75 x 25*
M12-1.25 x 30
M12-1.75 x 30*
M12-1.50 x 30*
M12-1.75 x 30
M12-1.75 x 35
M12-1.25 x 40*
M12-1.75 x 40
M12-1.75 x 40*

M931-22090-60
M931-22120-60
M931-22160-60

M22-2.50 x 90
M22-2.50 x 120
M22-2.50 x 160

M961-14025-60
M933-14025-60
M961-14050-82

M14-1.50 x 25
M14-2.00 x 25
M14-1.50 x 50*

M931-24090-60
M931-24120-60
M931-24160-60
M931-24200-60

M24-3.00 x 90
M24-3.00 x 120
M24-3.00 x 160
M24-3.00 x 200

M961-16025-60
M933-16025-60
M961-16030-82
M933-16030-82
M933-16035-60
M961-16040-60
M933-16040-60
M961-16045-82
M933-16045-82
M933-16050-60
M933-16050-82
M933-16060-60
M933-16070-60

M16-1.50 x 25
M16-2.00 x 25
M16-1.50 x 30*
M16-2.00 x 30*
M16-2.00 x 35
M16-1.50 x 40
M16-2.00 x 40
M16-1.50 x 45*
M16-2.00 x 45*
M16-2.00 x 50
M16-2.00 x 50*
M16-2.00 x 60
M16-2.00 x 70

M933-18035-60
M933-18050-60
M933-18060-60

M18-2.50 x 35
M18-2.50 x 50
M18-2.50 x 60

M933-20050-60
M933-20055-60

M20-2.50 x 50
M20-2.50 x 55

M933-24060-60
M933-24065-60
M933-24070-60

M24-3.00 x 60
M24-3.00 x 65
M24-3.00 x 70

Hex Head Bolts (Full Thread)


M933-04006-60

M4-0.70 x 6

M933-05030-60
M933-05035-60
M933-05050-60

M5-0.80 x 30
M5-0.80 x 35
M5-0.80 x 50

M933-06010-60
M933-06012-60
M933-06014-60
M933-06016-60
M933-06020-60
M933-06025-60
M933-06030-60
M933-06040-60
M933-06050-60

M6-1.00 x 10
M6-1.00 x 12
M6-1.00 x 14
M6-1.00 x 16
M6-1.00 x 20
M6-1.00 x 25
M6-1.00 x 30
M6-1.00 x 40
M6-1.00 x 50

M933-07025-60

M7-1.00 x 25

M933-08010-60
M933-08012-60
M933-08016-60
M933-08020-60
M933-08025-60
M933-08030-60
M933-08030-82

M8-1.25 x 10
M8-1.25 x 12
M8-1.25 x 16
M8-1.25 x 20
M8-1.25 x 25
M8-1.25 x 30
M8-1.25 x 30*

M933-10012-60
M961-10020-60
M933-10020-60
M933-10025-60
M961-10025-60
M933-10025-82
M961-10030-60
M933-10030-60
M933-10030-82
M961-10035-60
M933-10035-60
M933-10035-82
M961-10040-60

M10-1.50 x 12
M10-1.25 x 20
M10-1.50 x 20
M10-1.50 x 25
M10-1.25 x 25
M10-1.50 x 25*
M10-1.25 x 30
M10-1.50 x 30
M10-1.50 x 30*
M10-1.25 x 35
M10-1.50 x 35
M10-1.50 x 35*
M10-1.25 x 40

Pan Head Machine Screws


M7985A-03010-20 M3-0.50 x 10
M7985A-03012-20 M3-0.50 x 12
M7985A-04010-20
M7985A-04016-20
M7985A-04020-20
M7985A-04050-20
M7985A-04100-20

M4-0.70 x 10
M4-0.70 x 16
M4-0.70 x 20
M4-0.70 x 50
M4-0.70 x 100

M7985A-05010-20
M7985A-05012-20
M7985A-05016-20
M7985A-05020-20
M7985A-05025-20
M7985A-05030-20
M7985A-05080-20
M7985A-05100-20

M5-0.80 x 10
M5-0.80 x 12
M5-0.80 x 16
M5-0.80 x 20
M5-0.80 x 25
M5-0.80 x 30
M5-0.80 x 80
M5-0.80 x 100

M7985A-06100-20 M6-1.00 x 100

Flat Head Machine Screws


M965A-04012-SS

M4-0.70 x 12

M965A-05012-SS
M965A-05016-20
M965A-06012-20

M5-0.80 x 12
M5-0.80 x 16
M6-1.00 x 12

* This metric hex bolts hardness is grade 10.9.

TP-6196 10/09

Appendix 129

Metric, continued
Part No.
Hex Nuts

Dimensions

Type

M934-03-50

M3-0.50

Standard

M934-04-50
M934-04-B

M4-0.70
M4-0.70

Standard
Brass

M934-05-50

M5-0.80

Standard

M934-06-60
M934-06-64
M6923-06-80
M982-06-80

M6-1.00
M6-1.00
M6-1.00
M6-1.00

Standard
Std. (green)
Spiralock
Elastic Stop

M934-08-60
M6923-08-80
M982-08-80

M8-1.25
M8-1.25
M8-1.25

Standard
Spiralock
Elastic Stop

M934-10-60
M934-10-60F
M6923-10-80
M6923-10-62
M982-10-80

M10-1.50
M10-1.25
M10-1.50
M10-1.50
M10-1.50

Standard
Standard
Spiralock
Spiralock!
Elastic Stop

M934-12-60
M934-12-60F
M6923-12-80
M982-12-80

M12-1.75
M12-1.25
M12-1.75
M12-1.75

Standard
Standard
Spiralock
Elastic Stop

M982-14-60

M14-2.00

Elastic Stop

M6923-16-80
M982-16-80

M16-2.00
M16-2.00

Spiralock
Elastic Stop

M934-18-80
M982-18-60

M18-2.5
M18-2.50

Standard
Elastic Stop

M934-20-80
M982-20-80

M20-2.50
M20-2.50

Standard
Elastic Stop

M934-22-60

M22-2.50

Standard

M934-24-80
M982-24-60

M24-3.00
M24-3.00

Standard
Elastic Stop

M934-30-80

M30-3.50

Standard

Washers
Part No.
M125A-03-80
M125A-04-80
M125A-05-80
M125A-06-80
M125A-08-80
M125A-10-80
M125A-12-80
M125A-14-80
M125A-16-80
M125A-18-80
M125A-20-80
M125A-24-80

ID
3.2
4.3
5.3
6.4
8.4
10.5
13.0
15.0
17.0
19.0
21.0
25.0

Bolt/
OD Thick. Screw
7.0
9.0
10.0
12.0
16.0
20.0
24.0
28.0
30.0
34.0
37.0
44.0

0.5
0.8
1.0
1.6
1.6
2.0
2.5
2.5
3.0
3.0
3.0
4.0

M3
M4
M5
M6
M8
M10
M12
M14
M16
M18
M20
M24

! This metric hex nuts hardness is grade 8.

130 Appendix

TP-6196 10/09

KOHLER CO. Kohler, Wisconsin 53044


Phone 920-565-3381, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPower.com

TP-6196 10/09a
! 2004, 2008, 2009 by Kohler Co. All rights reserved.

Kohler Power Systems


Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65)6264-6422, Fax (65)6264-6455

You might also like