Kohler Service Manual-TP6196
Kohler Service Manual-TP6196
Kohler Service Manual-TP6196
Models:
8.5RES
12RES
12RESL
12RESM1
12RESNT
12TRES
Controllers:
ADC 2100
ADC-RES
DC 2200
DC-RET
TP-6196 10/09a
Table of Contents
Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
List of Related Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Service Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Section 1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Controller Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Engine Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Engine Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5 Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6 Alternator Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7 Service Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
13
13
13
14
14
15
16
19
19
21
21
21
21
21
22
22
23
24
24
24
25
25
26
26
26
26
26
26
Section 3 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Initial Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Controller Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
27
27
27
33
35
35
36
37
37
37
37
37
37
37
37
37
TP-6196 10/09
Table of Contents
40
40
40
41
41
46
48
48
49
53
53
54
54
54
55
56
56
56
56
56
56
56
56
57
57
57
59
59
59
59
60
62
62
63
66
67
67
69
70
73
73
73
74
77
78
78
79
79
79
81
81
82
82
4.6
4.7
4.8
4.9
Table of Contents
TP-6196 10/09
6.10
6.11
6.12
6.13
6.14
6.15
84
84
84
85
85
88
89
91
91
92
93
93
93
93
94
96
96
98
98
98
TP-6196 10/09
Table of Contents
Notes
TP-6196 10/09
Electromechanical
equipment,
including generator sets, transfer
switches, switchgear, and accessories,
can cause bodily harm and pose
life-threatening
danger
when
improperly installed, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely. Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual has several types of safety
precautions and instructions: Danger,
Warning, Caution, and Notice.
Accidental Starting
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
DANGER
Danger indicates the presence of a
hazard that will cause severe
personal injury, death, or substantial
property damage.
WARNING
Warning indicates the presence of a
hazard that can cause severe
personal injury, death, or substantial
property damage.
Disabling
the
generator set.
Accidental starting can cause
severe injury or death.
Before
working on the generator set or
connected equipment, disable the
generator set as follows: (1) Move the
generator set master switch to the OFF
position. (2) Disconnect the power to
the battery charger. (3) Remove the
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent starting of
the generator set by an automatic
transfer switch, remote start/stop
switch, or engine start command from a
remote computer.
CAUTION
Battery
Caution indicates the presence of a
hazard that will or can cause minor
personal injury or property damage.
WARNING
NOTICE
Notice communicates installation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publication to improve operator
recognition.
Replace missing or
damaged decals.
TP-6196 10/09
WARNING
Explosion.
Can cause severe injury or death.
Relays in the battery charger
cause arcs or sparks.
Locate the battery in a well-ventilated
area. Isolate the battery charger from
explosive fumes.
Battery electrolyte is a diluted
sulfuric acid. Battery acid can cause
severe injury or death. Battery acid
can cause blindness and burn skin.
Always wear splashproof safety
goggles, rubber gloves, and boots
when servicing the battery. Do not
open a sealed battery or mutilate the
battery case. If battery acid splashes in
the eyes or on the skin, immediately
flush the affected area for 15 minutes
with large quantities of clean water.
Seek immediate medical aid in the case
of eye contact. Never add acid to a
battery after placing the battery in
service, as this may result in hazardous
spattering of battery acid.
Battery acid cleanup. Battery acid
can cause severe injury or death.
Battery acid is electrically conductive
and corrosive. Add 500 g (1 lb.) of
bicarbonate of soda (baking soda) to a
container with 4 L (1 gal.) of water and
mix the neutralizing solution. Pour the
neutralizing solution on the spilled
battery acid and continue to add the
neutralizing solution to the spilled
battery acid until all evidence of a
chemical reaction (foaming) has
ceased. Flush the resulting liquid with
water and dry the area.
Engine Backfire/Flash
Fire
Exhaust System
WARNING
Carbon monoxide.
Can cause severe
fainting, or death.
nausea,
Carbon
monoxide
symptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in
exhaust gases. Carbon monoxide is an
odorless,
colorless,
tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Carbon
monoxide poisoning symptoms include
but are not limited to the following:
! Light-headedness, dizziness
! Physical fatigue, weakness in
joints and muscles
! Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
! Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep. Alert others to the
possibility of carbon monoxide
poisoning. Seek medical attention if
the condition of affected persons does
not improve within minutes of breathing
fresh air.
Fuel System
WARNING
WARNING
Fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
TP-6196 10/09
TP-6196 10/09
Hazardous Noise
CAUTION
CAUTION
Hazardous noise.
Can cause hearing loss.
Never operate the generator set
without a muffler or with a faulty
exhaust system.
Hazardous Voltage/
Moving Parts
WARNING
WARNING
Hazardous voltage.
Backfeed to the utility system can
cause property damage, severe
injury, or death.
WARNING
Airborne particles.
Can cause severe
blindness.
injury
Heavy Equipment
WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
Notice
NOTICE
Hot Parts
WARNING
NOTICE
or
10
TP-6196 10/09
Introduction
This manual provides troubleshooting and repair
instructions for the generator set models listed on the
front cover. This manual may also be supplied for similar
models not listed on the front cover.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow the
Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
equipment for future reference.
The equipment service requirements are very important
to safe and efficient operation. Inspect the parts often
and perform required service at the prescribed intervals.
Maintenance work must be performed by appropriately
skilled and suitably trained maintenance personnel
familiar with generator set operation and service.
For engine service procedures not covered in this
manual, refer to the Engine Service Manual, TP-2428.
Document Description
Part
Number
TP-6195
TP-6331
TP-6398
TP-6397
TP-6514
TP-6515
TP-6516
TP-6517
TP-5868
TP-6399
TP-2428
TP-6196 10/09
Introduction
11
Service Assistance
For professional advice on generator power
requirements and conscientious service, please contact
your nearest Kohler distributor or dealer.
! Consult the Yellow Pages under the heading
GeneratorsElectric.
! Visit
office.
Headquarters Europe, Middle East, Africa
(EMEA)
Kohler Power Systems
3 rue de Brennus
93200 Saint Denis
France
Phone: (33) 1 49 178300
Fax: (33) 1 49 178301
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 264-6422
Fax: (65) 264-6455
12
Service Assistance
China
North China Regional Office, Beijing
Phone: (86) 10 6518 7950
(86) 10 6518 7951
(86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai
Phone: (86) 21 6288 0500
Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax: (813) 3440-2727
Latin America
Latin America Regional Office
Lakeland, Florida, USA
Phone: (863) 619-7568
Fax: (863) 701-7131
TP-6196 10/09
Section 1 Specifications
! One-side serviceability of air cleaner, carburetor, oil
1.1 Introduction
Storage temperature
Humidity
--20" to 70"C
--60" to 70"C
0--95% condensing
12 or 24 VDC
Power requirements:
Voltage
Current
Environmental Specifications
Operating temperature
250 mA @ 12 VDC
125 mA @ 24 VDC
TP-6196 10/09
Section 1 Specifications
13
8.5 kW
(60 Hz)
Manufacturer
Model
12 kW
(60 Hz)
Kohler
CH20
Cycle
Number of cylinders
Compression ratio
8.5:1
9.0:1
624 (38.0)
725 (44.0)
11.5 (15.4)
17.6 (23.6)
Rpm
Bore x stroke, mm (in.)
Valve material
Cylinder block material
Cylinder head material
Piston rings
Crankshaft material
Main bearings: number,
type
Governor
Lubrication system
Oil capacity (w/filter), L (qt.)
Oil pressure, kPa (psi)
Fuel system
LP/natural gas minimum
supply pressure,
in. H2O (oz./in.2)
Battery voltage
Battery ground
Spark plug gap, mm (in.)
Ignition system
Starter motor
Cooling system
14
Section 1 Specifications
7 (5)
Alternator thrubolt
40 (28)
30 (40.7)
CH740
8.5/12 kW
40 (28)
24 (17.7)
Oil filter
5.7--9.0 (4.2--6.7)
Spark plug
24.4--29.8 (18--22)
3600
77 x 67 (3.03 83 x 67 (3.27
x 2.64)
x 2.64)
Steel/Stellite#
Aluminum w/cast iron liners
Aluminum
2 compression/1 oil
Heat-treated ductile iron
2, parent material
Electronic
Full pressure
1.9 (2.0)
2 (2.1)
172--241 (25--35)
LP gas or natural gas
7--11 (4--6)
12 VDC
Negative
0.51 (0.020)
0.76 (0.030)
Capacitor
Discharge
Smart Spark
Capacitor
Discharge
TP-6196 10/09
8.5/12 kW 1 phase
12TRES 3 phase
50/60
50
Single-Phase
Three
12
Excitation method
Static Excited
Digital
Coupling type
Direct
40 (28)
7 (60)
Winding material
Copper
1, replaceable ball
Circuit protection
Controller
10 amps
Aux. winding
Generator AC output
Rotor resistance, ohms, cold
20 amps
Dependent on voltage configuration
4.0
4.2
0.07
N/A
N/A
0.18
0.14
N/A
55-66
0.70
0.15
132 V
N/A
N/A
115 V
264 V
N/A
55-66
145 V
150 V
No load
12 V / 2.0 amps
14 V / 2.8 amps
Full load
47 V / 7.4 amps
78 V /11.5 amps
* Most ohmmeters do not give accurate readings when measuring less than 1 ohm. The stator can be considered good if a low resistance
reading (continuity) is obtained and there is no evidence of shorted windings (discoloration). Do not confuse a low resistance reading with
a reading indicating a shorted winding.
TP-6196 10/09
Section 1 Specifications
15
17
18
19
20
21
22
16
23
7
10
15
24
25
ADV-7466-
14
13
12
11
20
5
21
26
27
28
22
9
8
23
Control Detail
29
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
Muffler
Oil check
Oil fill
Air cleaner
Controller user interface (switch membrane)
Generator set master switch (RUN-OFF/RESET-AUTO)
Load circuit breaker (1-phase models)
Fuses
RS-232 connector (for application program updates)
Field-connection terminal block location
Spark plug locations (both sides)
Oil drain hose
Oil drain valve
Oil filter
Exhaust
Figure 1-1
16
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
Equipment ground
Starter relay
Battery charger
DSAI lead location
Fuel block
Gas regulator assembly
Fuel solenoid valve
Fuel inlet
Air intake
Engine starting battery location (battery purchased separately)
DSAI ground screw
Starter solenoid
Positive battery connection
Negative battery connection
Section 1 Specifications
TP-6196 10/09
2
1
3
GM66010
Figure 1-2
TP-6196 10/09
Section 1 Specifications
17
21
22
23
24
25
26
9
10
20
11
12
19
12
ADV6823
18
17 16 15 14
27
13
24
28
25
31
26
29
30
Enclosure
Muffler
Oil check
Oil fill
Air cleaner
Spark plug locations (both sides)
Controller
Generator set master switch (RUN\OFF/RESET\AUTO)
Nameplate
Line circuit breaker
Battery charger
Air intake
Engine starting battery location
Oil drain hose
High engine temperature (HET) sensor
(located on non-service side)
16. Oil drain valve
Figure 1-3
18
Oil filter
Air intake, alternator
Exhaust
Spark arrestor (not visible in this view)
Relay interface board (RIB)
SCR module
Digital spark advance module leads
(DSAM leads, ignition timing)
Multi-fuel block
Secondary fuel regulator assembly
Fuel solenoid valve
Starter solenoid
Positive battery connection
Starter relay
Negative battery connection
DSAM ground screw
Section 1 Specifications
TP-6196 10/09
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
WARNING
WARNING
TP-6196 10/09
19
SystemComponent
Lubrication
Oil level
Crankcase breather hose
Change oil
Replace filter(s)*
Oil cooler*
Fuel
Flexible lines and connections $
Main tank supply level
Fuel piping
Cooling
Air ducts and louvers in enclosure *
Exhaust System
Leakage
Obstructions or combustible materials near
exhaust outlet
Action
Refer to
Section Inspect Check Change Clean Test
Interval
2.2
2.2.2
X
X
8 hr. or before use
E
E
Yearly or 500 hr.
2.2.4
R
Yearly or 100 hr.
2.2.4
R
Yearly or 200 hr.
2.2.5
X
R
X
Yearly or 100 hr.
6.12
X
R
Quarterly
X
Weekly
X
Yearly
2.5
X
X
Yearly
2.6
X
X
Weekly
X
DC Electrical System
Battery charger operation
Remove corrosion, clean and dry battery and
rack
2.7
O/M
2.7
2.7
2.7
2.7
X
X
Weekly
Monthly
Yearly
Yearly
Yearly
Yearly
R
X
X
X
Quarterly
Six Months
Yearly
3 yr. or 500 hr.
X
X
X
E
2.4
2.3
2.3
6.9
6.6
E
X
X
E
R
R
X
X
6.3
X
X
Weekly
Yearly or 100 hr.
Yearly
500 hr.
3 yr. or 500 hr.
Weekly
Yearly
X
3 yr.
X
X
Weekly
Monthly
Weekly
Quarterly
E
Follow procedures and frequencies indicated in the engine manufacturers
maintenance manual. If not indicated, follow this service schedule. Some items
may not apply to all generator sets.
Figure 2-1
20
Service Schedule
TP-6196 10/09
2.2.3
Model
L (Qt.)
8.5kW
1.9 (2.0)
12kW
2.0 (2.1)
Figure 2-3
10W-30
5W-20, 5W-30
Figure 2-2
ADV--7466
Figure 2-4
2.2.4
2.2.1
2.2.2
TP-6196 10/09
21
it
1
2
1. Oil filter
2. Oil cooler
Figure 2-5
24 590 01--A
2.2.5
Oil Cooler
22
Figure 2-6
TP-6196 10/09
1
2
Model
8.5 kW
12 kW
Figure 2-7
6
7
Figure 2-8
1.
2.
3.
4.
Cover knob
Air cleaner cover
Element cover nut
Element cover
5. Foam precleaner
6. Air cleaner element
7. Air cleaner base
TP-6196 10/09
23
3
tp6196
1. Exhaust outlet
2. Alternator air intake (both sides)
3. Engine air intake
them as needed.
! Check that exhaust outlet is clear.
2.7 Battery
WARNING
TP-6196 10/09
EZ-273000-J
2.7.1
Cleaning Battery
2.7.2
Battery Charger
Note: The generator set will not start and circuit board
damage may result if the battery is connected in
reverse.
TP-6196 10/09
25
2.8.1
Lubricating System
2.8.4
3. With the engine still warm, drain the oil from the
crankcase.
Exterior
2.8.2
Fuel System
2.8.5
Battery
2.8.3
26
TP-6196 10/09
Section 3 Troubleshooting
! Blown fuses. Fuses in the wiring harness protect the
3.1 Introduction
Corrective action and testing in many cases requires
knowledge of electrical systems and electronic circuits.
Have an authorized distributor/dealer or trained service
technician perform testing and service.
Troubleshooting Chart
Problem
Possible Cause
Weak or dead battery
Generator
set does not
crank
Battery connections
Open circuit in
engine/controller
connections
Corrective Action
Recharge or replace battery.
If battery is weak or dead, check battery charger fuse, power
supply, and operation.
Reference
Generator Set
O/M
Section 6.15
Section 8
Blown fuse F3, controller Replace fuse; if fuse blows again, check circuit and components. Section 6.13
Section 8
Blown fuse F2, relay
interface board (RIB)
TP-6196 10/09
Replace fuse.
If fuse blows again, disconnect the board leads one at a time to
identify the cause of the blown fuse:
Lead 70A at the fuel valve
Lead IGN at the ignition module
Lead 71A at the starter relay
Leads FP and FN at the rotor
Repair or replace the component causing the blown fuse.
Section 6.13
Section 8,
ADV-6835
If fuse continues to blow and the previous step did not identify
the cause, check the continuity of leads FP and FN and the
leads from the P14 connector. Replace any bad leads. Use a
pin pusher to remove leads from the connector, if necessary. If
replacing the leads does not solve the problem, replace the RIB.
Section 8,
ADV-6835
Section 4.8 or
5.7
Section 3 Troubleshooting
27
Possible Cause
Crank relay on relay
interface board
(ADC 2100)
Crank relay K3 on
controller circuit board
(ADC-RES)
Blown fuse F2
(ADC-RES)
Starter
Cranks but
does not
start
28
Corrective Action
Reference
Section 4.8 or
5.7; Section 8
Section 8
Section 4.8 or
5.7
Section 5.7
Section 8
Section 6.13
Section 8,
ADV-7325
Section 1.7
Section 6.15
Section 8
Section 8
Section 1.7
Section 8
Engine Service
Manual (S/M)
Section 8,
ADV-7325
Section 4.8 or
5.7
Section 6.15
Section 6.15
Controller
No fuel
Insufficient fuel pressure
Open (turn on) manual fuel valve. Check fuel supply tank (LP).
Check fuel pressure to the generator set. Verify adequate fuel
pressure and pipe size for the generator set plus all other gas
appliances.
Section 6.12.3
Fuel regulator/valve
Section 6.12
4
Section 2.3
Loose connection or
open circuit
Check for loose or open connection at the fuel valve (lead 70A)
and at the engine spark control module (leads IGN and 70A).
Check controller/engine wiring continuity.
Section 8
Section 3 Troubleshooting
TP-6196 10/09
Starts hard
Starts but
shuts down
Stops
suddenly
TP-6196 10/09
Possible Cause
Air cleaner clogged
Magnetic pickup
Corrective Action
Clean or replace.
Check for 1.75 volts or higher from the magnetic pickup during
cranking. A lower signal will cause the stepper motor to open
and close during cranking.
Reference
Section 2.4
Section 6.9.4
Incorrect controller
configuration
Section4.5 or
5.5
Engine S/M
Section 6.12.5
No engine rotation
sensed (check for an
overcrank fault
shutdown)
Check mag pickup connections, mag pickup gap, and operation. Section 6.9.4
Check for locked rotor.
Section 6.4
Generator Set
O/M
Replace element.
Adjust fuel valve.
Section 2.4
Section 6.12
Section 6.12.5
Spark plug(s)
Spark plug wire(s)
Section 2.3
Engine S/M
Ignition components
(spark control or ignition
module)
Engine S/M
Section 6.12.3
Engine S/M
Section 4.4 or
5.4
Section 6.11
Section 4.4 or
5.4
Section 6.11
Fault shutdown
No fuel
Fuel line restriction
Fuel lines too long
Air cleaner clogged
Blown fuse
Section 6.12.1
Section 2.4
Section 6.13
Spark plug(s)
Engine overheated
(hot engine only)
Engine S/M
Section 2.5
Section 2.2
Section 6.12
Attempt startup. If unit shuts down, remove lead from LOP switch Section 2.2.1
and reset controller. A successful restart attempt indicates a
Section 6.11.2
faulty LOP shutdown switch.
Note: Check engine oil pressure before performing test and/or
replacing LOP shutdown switch.
Section 3 Troubleshooting
29
Operates
erratically
Lacks
power
Lacks
power,
continued
30
Possible Cause
Fuel valve/fuel regulator
Corrective Action
Check regulator/valve operation.
Reference
Section 2
Section 7
Engine overloaded
Loss of generator output
voltage to controller
Section 8
Magnetic pickup
connections
Section 6.9
Ignition module
Engine S/M
Check for Flash LED illumination. Check fuse F2. Replace relay Section 4.8
board.
Check for Flash LED1 illumination. Check fuse F2. If LED1 is lit Section 5.7
but relay does not operate, replace controller board.
Replace element.
Replace and regap plugs.
Replace spark plug wires.
Connect for natural gas. Disconnect for LP.
Section 2.4
Section 2.3
Engine S/M
Section 6.12.5
Section 6.12.1
Section 6.12
Magnetic pickup
connections
Section 6.9
Governor adjustment
incorrect
Section 6.9 or
6.10
Ignition system
Inadequate cooling
(hot engine only)
Engine S/M
Section 2.5
Engine S/M
Engine S/M
Section 2.5
Section 2.4
Generator overloaded
Spark plug(s)
Spark plug wire(s)
DSAI leads incorrectly
connected or
disconnected
(12kW only)
Reduce load.
Replace and regap plug(s).
Replace spark plug wires.
Connect for natural gas. Disconnect for LP.
Section 2.3
Engine S/M
Section 6.12.5
Section 6.12
Section 6.12
Section 6.12
Section 4.5 or
Section 5.5
Section 6.9 or
6.10
Engine S/M
Governor malfunction or
misadjustment
Test/readjust governor.
Section 6.9 or
6.10
Ignition system
Engine S/M
Section 3 Troubleshooting
TP-6196 10/09
Possible Cause
Inadequate cooling
Fuel mixture adjustment
incorrect
Corrective Action
Inspect cooling system for air intake obstructions.
Readjust fuel mixture.
Note: Adjusting the fuel mixture may void the emission
certification.
Reference
Section 2.5
Section 6.12
Low output
or
excessive
drop in
voltage
Generator overloaded
Incorrect controller
configuration
Reduce load.
Check and adjust the controller configuration parameters.
Section 4.5 or
5.5
Incorrect controller
voltage settings
Section 4.5.3 or
5.6
Alternator or control
system
Section 6.2
SCR module
Section 6.13
Section 6.8
Controller
Section 4.5 or
5.5
Section 6.8
Section 6.4
Section 6.3
Brush connection
Section 6.6
Section 4.5 or
5.5
Section 6.9 or
6.10
Engine S/M
Troubleshoot engine.
Light flicker
Check and adjust the voltage stability (gain) setting using the
controller keypad.
Section 4.5.3
High output
voltage
Incorrect controller
configuration
Section 4.5 or
5.5
Incorrect controller
voltage settings
Section 4.5.3
Section 6.9 or
6.10
Section 8
SCR module
Section 6.8
Section 6.13
Section 6.8
Controller
Section 4.9
TP-6196 10/09
Section 3 Troubleshooting
31
Noisy
operation
32
Possible Cause
Corrective Action
AC output circuit breaker Check for AC voltage on the generator side of circuit breaker. If
open
there is AC voltage on the generator side of the breaker, then a
problem in the load circuits is causing the line circuit breaker to
trip. Check for and correct short circuits or overloading on the
load side before resetting the circuit breaker.
Reference
Alternator or control
system
Section 6.2
Section 6.3
SCR module
Section 6.13
Section 6.8
Controller
Section 4.5 or .
Section 6.8
Check continuity.
Sections 6.13
Section 8
Brushes
Section 6.6
Section 6.6
Rotor connections
Section 8
Section 6.4
Section 6.4
Section 6.3
Section 4.8
Section 2.6
Broken or damaged
vibromount(s)
Section 7
Section 2.6
Excessive
engine/generator
vibration
Section 7
Engine S/M
Section 3 Troubleshooting
TP-6196 10/09
SCR module
Test
Check controller settings. *
Corrective Action
Adjust controller settings as required. *
Reference
Section 4.5 or
5.5
Section 8
Section 8
Section 6.8
Section 4.9 or
5.9
Section 6.8
Section 6.8
Section 8
TP-6196 10/09
Section 3 Troubleshooting
33
Notes
34
Section 3 Troubleshooting
TP-6196 10/09
2
3
4
1
7
6
6
GM29253
1.
2.
3.
4.
Controller
SCR module
Ground stud
L0 stud
Figure 4-1
5.
6.
7.
8.
TP-6196 10/09
35
Controller Display
Item
Description
Crank
indication
Runtime hours
Fault codes
System
parameters
1
3
2
Application
ADC 2100: Displays the version
program
number of the controllers application
version number program before entering the
configuration or adjustment mode. See
Section 4.5.4.
DC 2200: Application program version
number is displayed at controller
powerup.
Figure 4-4
4
1.
2.
3.
4.
GM28707A-C
LED display
Select button (use for setup and adjustment only)
Up and down arrow buttons (use for setup and adjustment only)
Generator set master switch
Figure 4-2
GM39579
4
1. LED display
2. Generator set master switch
Figure 4-3
36
DC 2200 Controller
TP-6196 10/09
4.3.3
4.3.4
4.3.1
4.3.2
Running Sequence
4.3.5
4.4 Faults
4.4.1
Warnings
4.4.2
Shutdowns
TP-6196 10/09
37
Description
Code Fault
HB
High battery
Fault code is displayed if the engine starting battery voltage
voltage warning rises above 16 VDC for a 12 VDC system or above 30 VDC
for a 24 VDC system for more than one minute when the
engine is not running. This fault condition does not inhibit
engine starting.
Check
Check the battery rating and
condition.
Check the battery charger
operation.
Low battery
Fault code is displayed if the engine starting battery voltage
voltage warning falls below 8 VDC for a 12 VDC system or below 16 VDC for
a 24 VDC system for more than one minute when the engine
is not running. This fault condition does not inhibit engine
starting.
The fault condition clears when the battery voltage returns to
a voltage within the limits for more than 10 seconds.
Figure 4-5
38
TP-6196 10/09
Code Fault
Description
Check
Refer to
Section
AF
Auxiliary fault
HE
High engine
temperature
1.7
LCL
Low coolant
level
LOC
Loss of coolant
LOP
Low oil
pressure
2.2
Check the oil level and add oil if the level is low.
2.2
6.11.2
Engine
S/M
6.12
2.3
3.3
6.9.4
6.4
4.5
6.9.5
OF
OS
OU *
UF
UU *
Overcrank
Overfrequency
Overspeed
6.9
Check AC voltage.
6.7
Shutdown occurs if the voltage falls below Reduce the load and restart the generator set.
80% of the nominal system voltage for
Check wiring and connections.
more than 10 seconds.
Check controller configuration, system voltage
and frequency (parameter UU).
Software
Communication
Fault 0
6.9
SCF0
6.11
8
4.5
6.7
6.8
6.2
6.3
4.9
* Not applicable on DC 2200 controllers with software versions below 1.26. DC 2200 software version number is displayed on controller
powerup.
Figure 4-6
TP-6196 10/09
39
4.5.1
4.5.2
Controller Configuration
Setting
Definition
Uu00
Uu01 *
Uu05
Uu06 *
Unit configuration
Uc01 *
Standby
Engine type
Ec00 *
8.5/12RES
Ed05 *
Digital low coolant level, digital pressure, analog temp, with mag. pickup
Bt12 *
Cn00 *
No CAN communications
Communications
* Factory settings. Choose 50 or 60 hz setting for Uu as required for generator set frequency .
Figure 4-7
40
TP-6196 10/09
4.5.3
TP-6196 10/09
4.5.4
41
Display: *
Move the generator set master switch to the RUN
position. (The generator set engine will not start.)
1 0 4
Uu 0 1
Uu 0 1
Uc 0 1
or
E c 0 0
Ad n c
Now either save your settings or enter the Advanced Configuration Mode to
set the engine data inputs, battery voltage, and communications.
Press:
To enter advanced configuration mode.
Go to Figure 4-9.
E d 0 5
S AV E
or
or
Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to
the last saved settings when the master switch is moved to the OFF/RESET position.
* Shaded boxes show which number in the controller display changes when the up or down arrow key is pressed.
Figure 4-8
42
Configuration Mode (system voltage/frequency, unit configuration, and engine type parameters)
TP-6196 10/09
Pressing the up arrow key at the Adnc display (See Figure 4-8) puts you into
the Advanced Configuration Mode.
Press:
or
E d 0 5
or
B t 1 2
or
C n 0 0
S AV E
Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to
the last saved settings when the master switch is moved to the OFF/RESET position.
Figure 4-9
Advanced Configuration Mode (engine data input types, battery voltage, and engine
communications)
S AV E
Uu 0 1
or
To save changes.
Y E S
n o
x x x x
or
TP-6196 10/09
43
Display :*
Move the generator set master switch to the RUN position. The generator set
engine starts and the controller display shows the engine runtime hours.
x x x x
Hold:
Wait about 5 seconds until the display changes from runtime hours
to the program version number.
x. x x
Press the down arrow key and then the up arrow key 3 times to enter the
adjustment mode. (This is the controller password.)
1 P x x
1 P x x
1 P x x
or
2 P x x
or
2 P x x
or
3 P 0 x
or
TP6196
TP-6196 10/09
Display : *
4 P x x
5 P x x
or
4 P x x
5 P x x
S AV E
Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to
the last saved settings when the master switch is moved to the OFF/RESET position.
* Shaded boxes show which character in the controller display changes for each adjustment. X in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model.
Figure 4-12 Output Voltage and Frequency Adjustments, Continued
TP-6196 10/09
45
S AV E
1 P x x
To save changes.
Y E S
n o
or
or
x x x x
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
46
TP-6196 10/09
2
1
tp6196
8
1.
2.
3.
4.
5.
6.
7.
8.
47
4
3
COMMON
K1 FAULT
P13
D2
K5
RUN
D7
K2
CRANK P14
D6
K4
AUX
RUN
3
D3
FLASH
FP
T2
LED3
CRANK
LED1
RUN
R3
K3
R2
LED2
FLASH
D5
T1
FN
VBAT
D4
R1
R
R
GM29779-A
6
1.
2.
3.
4.
5.
6.
7.
Connector
Pin Number Connection
6
Common fault normally open
2
Common fault common
3
Common fault normally closed
4
Run relay normally open
1
Run relay common
5
Run relay normally closed
48
TP-6196 10/09
See
4
5
tp6196
1.
2.
3.
4.
5.
Roof
Roof locating pin
Roof screws (4 ea.)
Service-side door
Front panel
TP-6196 10/09
49
1
3
cover
on
the
tp6196
1. P1 35-pin connector
2. P15 3-pin connector
3. P16 6-pin connector
controller
tp6196
tp6196
1. Cover screws
50
TP-6196 10/09
11. Replace the roof and tighten the four roof screws.
TP-6196 10/09
51
Notes
52
TP-6196 10/09
5.1 Introduction
This section covers operation, configuration,
adjustment, and replacement of the ADC-RES and
DC-RET controllers. See Section 3 for troubleshooting
procedures.
11
8
9
10
12
1
7
2
6
5
5
Front View
1.
2.
3.
4.
5.
6.
GM57149
Controller display
Keypad (ADC-RES only; see Figure 5-2)
Generator set master switch (RUN-OFF/RESET-AUTO)
Line circuit breaker (load connection)
Fuses F1, F2, and F3
Serial port for communication connection (remove plug to access)
Figure 5-1
7.
8.
9.
10.
11.
12.
Logic board
Optional relay board location
L0 stud
Ground stud
Start relay
SCR module
Controller Components
TP-6196 10/09
53
GM57149
1. LED display
2. Generator set master switch (RUN--OFF/RESET-AUTO)
Figure 5-3
4
DC-RET Controller
GM57149
1.
2.
3.
4.
LED display
Select button (use for setup and adjustment only)
Up and down arrow buttons (use for setup and adjustment only)
Generator set master switch (RUN--OFF/RESET-AUTO)
Figure 5-2
5.2.1
ADC-RES Controller
Master Switch
5.2.2
LED Display
54
TP-6196 10/09
Control or Indicator
Item
Description
LED display
Runtime hours
Displays total generator set runtime hours while the generator set is running
and when no other codes are displayed.
Metering display
(ADC-RES only)
Crank indication
Displays CC_1, CC_2, or CC_3 to indicate the first, second, or third attempt to
start the engine. The last digit flashes during the crank cycle rest periods.
Software version
number
Fault codes
Keypad
(ADC-RES only)
Use the arrow buttons to step through the data displays. See Section 5.2.3.
The keypad is also used for controller setup and adjustment. The setup and
adjustment functions are password-protected. Have setup and adjustments
performed only by an authorized distributor/dealer.
Three-position
switch
Switch functions as the generator set operation and controller reset switch.
Figure 5-4
5.2.3
Keypad
Engine Runtime
XXX.X hours
Output Voltage
VAC
Output Frequency
Hz
Battery Voltage
VDC
tp6515
Notes:
Generator set master switch in AUTO.
Step through using up or down arrow buttons.
After 10 seconds, display returns to runtime hours.
Figure 5-5
TP-6196 10/09
55
5.3.3
5.3.4
5.3.1
5.3.2
Running Sequence
5.3.5
5.3.6
Standby Mode
5.3.7
Sleep Mode
56
TP-6196 10/09
5.4 Faults
5.4.1
Warnings
5.4.2
Shutdowns
Check
Check the battery rating
and condition.
Check the battery charger
operation.
LB
Low battery
Fault code is displayed if the engine starting battery voltage falls below
voltage warning 8 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system
for more than one minute when the engine is not running. This fault
condition does not inhibit engine starting.
The fault condition clears when the battery voltage returns to a voltage
within the limits for more than 10 seconds.
* ADC-RES only
Figure 5-6
TP-6196 10/09
57
Code Fault
AF
Auxiliary fault
Description
Indicates a shutdown initiated by the emergency stop
switch or a tripped circuit breaker.
(TRES models only)
Shutdown occurs if the engine coolant temperature
exceeds the maximum temperature for more than
5 seconds. This protective becomes active after the
engine reaches the crank disconnect speed.
Check
Check the position of the
emergency stop button.
(TRES models only)
Check for blocked air inlets and
exhaust outlets.
2.2
Overcrank
6.12
O/M
3.3
Locked rotor
4.5
6.9.5
6.9
Overspeed
6.9.5
6.9
Check AC voltage.
Check wiring and connections.
Reduce the load and restart the
generator set.
6.7
8W/D
8W/D
4.5
6.7
HE
High engine
temperature
LOP
Low oil
pressure
OC
OF
OS
Refer to
Section
OU * Overvoltage
UF
UU
Undervoltage
O/M
1.7
6.11
Engine
S/M
6.9.4
SCF0 Software
Indicates a software or communication problem
Communication within the ADC-RES.
Fault 0
6.2
6.3
4.9
Engine S/M = Engine Service Manual; O/M = Generator Set Operation Manual
* ADC-RES only
Figure 5-7
58
TP-6196 10/09
5.5.1
5.5.2
5.5.3
TP-6196 10/09
59
5.5.4
System Parameters
Engine type
Communication
setting *
Setting
Uu01
Definition
Single phase, 60 Hz,
120/240 VAC
Uu03
Three-phase, 50 Hz,
230/400 VAC (TRES)
Uu06
Ec00
Cn00
8.5/12 kW
No J1939 communication.
Sleep mode enabled
(48-hour power down in
AUTO).
Cn01 !
J1939 communication
enabled. Sleep mode
disabled (no power down in
AUTO).
Figure 5-8
60
tp6514
1. Select button
Figure 5-9
2. Arrow buttons
ADC-RES Control
TP-6196 10/09
Display:
Move the generator set master switch to the RUN
position. (The generator set engine will not start.)
Wait about 5 seconds until the display shows the
program version number. (The number may be
different than the one shown here.)
Press the down arrow key and then the up arrow
key 3 times to enter the configuration mode.
(This is the controller password.)
v 1 1 3
Uu 0 1
Uu 0 x
or
8.5/12 kW
E c 0 0
Cn 0 x
S AV E
Y E S
n o
OR
x x x x
61
5.6.1
Voltage Adjustment
WARNING
Voltage Adjustment Procedure
Measured
Voltage, VAC
ADC
Display
Coarse
Fine
85--132
1P00--99
0.5
180--251
1P00--99
0.7
Cut-In Frequency
60 Hz
57.5 Hz
50 Hz
47.5 Hz
62
TP-6196 10/09
5.6.2
Frequency Adjustment
TP-6196 10/09
63
Display :*
Move the generator set master switch to the RUN position. The generator set
engine starts and the controller display shows the engine runtime hours.
x x x x
Hold:
Wait about 5 seconds until the display changes from runtime hours
to the program version number.
x. x x
Press the down arrow key and then the up arrow key 3 times to enter the
adjustment mode. (This is the controller password.)
1 P x x
1 P x x
or
1 P x x
2 P x x
or
2 P x x
or
3 P x x
TP6196
TP-6196 10/09
Display : *
4 P x x
5 P x x
or
4 P x x
5 P x x
S AV E
Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to
the last saved settings when the master switch is moved to the OFF/RESET position.
* Shaded boxes show which character in the controller display changes for each adjustment. X in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model.
Figure 5-14 Output Voltage and Frequency Adjustments, Continued
TP-6196 10/09
65
S AV E
1 P x x
To save changes.
Y E S
n o
or
or
Yesor no flashes when the up or down arrow is pressed and then the
controller exits the configuration mode. The display returns to the
runtime hours.
x x x x
4
3
5
6
66
GM49103
4. LED4 Fault
5. LED5 SP2
6. LED6 SP1
TP-6196 10/09
GM53102
1. Relay board
2. Controller circuit board location
GM51403
5.8.1
from GM52541
TP-6196 10/09
67
TO ENGINE HARNESS
GM52639
Description
Contact Ratings
COMMON FAULT NC
10 A @ 120 VAC
10 A @ 28 VDC
440 VA/75 W
COMMON FAULT NO
AUX RUN NC
AUX RUN NO
68
TP-6196 10/09
5.8.2
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
TP-6196 10/09
69
ADV-7466C
1. Service-side door
2. Front panel
DANGER
1
2
Hazardous voltage.
Will cause severe injury or death.
70
fGM52541
6
1.
2.
3.
4.
5.
6.
TP-6196 10/09
TP-6196 10/09
71
Notes
72
TP-6196 10/09
No Generator Output
Separate Excitation
Output within
Specifications
Erratic or No Output
Check Rotor
Check Stator
1
55
66
ADC
Controller
55
66
AC1
AC2
G1
G2
(+)
G
F+
SCR
Figure 6-2
(--)
FP
TP563273
FN
FP
11
FN
4
44
1 11
55 66
44
7
4
5
TP6196
1.
2.
3.
4.
Fuse
Power lead (55)
Excitation to rotor
Brushes
Figure 6-1
5.
6.
7.
8.
Slip rings
Main field (rotor)
Stator windings
Sensing leads (11--44)
TP-6196 10/09
Generator Troubleshooting
73
2 3
FN
1.
2.
3.
4.
5.
6.
7.
8.
9.
SCR module
FN lead disconnected from SCR
FP lead disconnected from SCR
10-amp fuse
DC ammeter
12V battery
Brushes
Slip rings
Main field (rotor)
Figure 6-3
Example:
12 volts (battery voltage)
4 ohms (rotor resistance)
3 amps
(rotor current)
6.3 Stator
FP
- +
TP563274
WARNING
74
TP-6196 10/09
44
3
66
55
Figure 6-5
11
6196
tp6198
R14807-14
Figure 6-4
TP-6196 10/09
Figure 6-6
75
Continuity
1 and 2
1 and 11
2 and 11
3 and 4
Yes
3 and 44
4 and 44
55 and 66
2 and 3, 4, 44, 55, or 66
No
Figure 6-7
Leads
1 and 4
2 and 5
3 and 6
7 and 10
8 and 11
9 and 12
55 and 66
1 and 2, 3, 7, 8, or 9
1 and 55
Any stator lead and ground
Figure 6-8
76
Continuity
Yes
No
TP-6196 10/09
WARNING
TP-6196 10/09
2-221
R13929-7
Figure 6-9
77
1
2
3
2
GM29253B-P
Side View
3
New 1.9 cm (0.75 in.)
6.6 Brushes
The brushes transfer current from the SCR module to
the slip rings. The brushes should last the life of the
generator. Abrasive dust on the slip rings, however,
shortens the life of the brushes. Excessive arcing at the
brushes could damage the SCR module and the
controller. Weak springs, damaged slip rings, sticking
brushes, a loose brush holder, or poor brush contact
causes arcing.
3
TP5867
1.
2.
3.
4.
Brush holder
Slip ring
Brush(es)
Retainer wire
5.
6.
7.
8.
Shim
Spring
Correctly positioned brush
Incorrectly positioned brush
78
TP-6196 10/09
6.7 Voltage
6.7.1
WARNING
Voltage Regulation
6.7.2
Voltage Adjustment
Models
1 phase, 60 Hz
1 phase, 50 Hz
3 phase, 50 Hz
Voltage
Measurement
Approximate
Voltage, VAC
L -- L0
L-L
L -- L0
L-L
L -- L0
L-L
120
240
115
230
230
400
TP-6196 10/09
79
1
1
L0 L1 L2 L3
2
See
Detail
GM66010
Cut-In Frequency
60 Hz
57.5 Hz
50 Hz
47.5 Hz
80
TP-6196 10/09
6.7.3
6.7.4
Voltage Connections,
Single-Phase
Ground
Load
Side
3P
0.5%
1.0%
1.5%
2.0%
2.5%
3.0%
3.5%
4.0%
4.5%
L2
L1
Factory two-pole
circuit breaker
Line
Side
LO
GRD
3
2
1
Stator Leads
L0-L1
L0-L2
L1-L2
60 Hz
120 volt
120 volt
240 volt
50 Hz
110 volt
110 volt
220 volt
TP-5867
TP-6196 10/09
81
6.7.5
PHASE ROTATION
ADV--5875
AC2
G1
--
G2
+
GM28483
82
TP-6196 10/09
1
2
(+)
(--)
G1
AC1
AC2
(+)
4. Connect the ohmmeter from AC1 to (--) on the SCR
module. You should read high resistance in one
direction and low resistance in the other.
5. Repeat steps 3 and 4 for AC2.
6. Connect the ohmmeter from G1 to (+) on the SCR
module. You should read low resistance in both
directions.
(--)
G2
1. 12 VDC power source
2. 12 VDC test lamp
3. SCR module
tp6196
4. Jumper
5. 100--500 ohm resister
11. Repeat steps 9 and 10, with the positive (+) lead
and lamp connected to terminal AC2 on the SCR
module, and connecting the jumper with resister to
terminal G2.
12. If any of the above checks indicates a bad SCR
module, replace the module. Be sure to apply the
thermal compound supplied with the module
replacement kit to the back of the new module.
TP-6196 10/09
83
6.9.1
Operation
84
6.9.2
tight.
! Check the magnetic pickup connections. Poor
TP-6196 10/09
6.9.3
Hunting/Surging
Often hunting/surging
by the governor are
carburetor problems.
using the following
governor.
6.9.4
Governor System/Magnetic
Pickup Operation Test
1
2
3
TP5632721
Yes
No
Figure 6-21 Governor System Operation Test Procedure Summary (Section 6.9.4)
TP-6196 10/09
85
6196
5
4
3
2
1.
2.
3.
4.
5.
Ignition module
Air gap, 0.5 mm (0.020 in.)
Top of flywheel ring gear tooth
Lock nut
Magnetic pickup
A-358000B-C
86
TP-6196 10/09
PIN 3, BLK
PIN 2, YEL
PIN 5, GRN
(not used)
PIN 4,
RED
PIN 1,
WHT
PIN 6, BLUE
(not used)
SB555
TP-6196 10/09
87
6.9.5
Frequency Adjustment
88
TP-6196 10/09
photo4991
1.
2.
3.
4.
Hex nut
Cross shaft
Governor lever
Throttle linkage (passes under air cleaner)
photo5005
TP-6196 10/09
89
photo5005
1
#
photo5005
1. Governor lever
2. Cross shaft
Engine Speed
3780 RPM (63 Hz)
3600 RPM (60 Hz)
90
TP-6196 10/09
WARNING
Overspeed Shutdown
The overspeed setting is programmed into the ADC
controller and is not adjustable. Verify that the following
controller configuration parameters are set correctly for
your unit. See Section 4.5 and Figure 4-7 for the
settings.
WARNING
TP-6196 10/09
91
Overcrank Shutdown
Disconnect the starter motor lead at the starter solenoid
(K20) terminal. Move the controller master switch to the
RUN position. Observe that the generator set simulates
cranking for 15 seconds and then rests for 15 seconds.
Check that the generator set shuts down after the third
crank/rest cycle.
Resistance, Ohms
2100--2500
180--200
WARNING
1
92
tp6196
TP-6196 10/09
Figure 6-33 lists the maximum gas flow rates for each
model.
8.5RES
WARNING
Pipe Length,
m (ft.)
12RES
Natural
Gas
LP
Natural
Gas
LP
(25)
3/4
1/2
3/4
3/4
15
(50)
3/4
3/4
30
(100)
46
(150)
1 1/4
61
(200)
1 1/4
1 1/4
TP-6196 10/09
Natural Gas
LP
8.5kW
132000
180000
12kW
202000
270000
93
Supply Pressure
kPa (in. water column)
Fuel Type
Natural Gas
1.2--2.7 (5--11)
LP
1.7--2.7 (7--11)
2
1
4
8
5
7
1.
2.
3.
4.
Hose fitting
Plug
Fuel metering valve (factory-sealed, do not adjust)
Secondary regulator
TP-6196
5.
6.
7.
8.
Figure 6-35 Fuel Regulator, Fuel Metering Valve, and Fuel Solenoid Valve
94
TP-6196 10/09
WARNING
Accidental starting.
Can cause severe injury or death.
GM29253
TP-6196 10/09
tp6195
95
WARNING
Note: Adjusting the fuel metering valves on emissionscertified generator sets may void the emission
certification.
Use a universal exhaust gas oxygen (UEGO) sensor to
check the fuel mixture after replacing the fuel regulator,
carburetor, or silencer. Use the following procedure to
check the fuel mixture after the engine has reached
normal operating temperature.
The fuel metering valves are sealed to prevent field
adjustments. If the fuel metering valve requires
adjustment, do not break the seals on the fuel metering
valve. Obtain a new fuel metering valve from the
manufacturer and replace the sealed valve with the new
part. See Figure 6-36 for the fuel metering valve
location. Refer to the generator set Parts Catalog for the
fuel metering valve part number.
96
GM29253
TP-6196 10/09
12. Remove the load and allow the generator set to run
unloaded to cool for at least 510 minutes.
Natural Gas
2.400.05
LP
2.250.05
12kW
2.600.05
2.600.05
GM-28981-
4
1.
2.
3.
4.
97
6.13 Fuses
Three fuses are located on the junction box next to the
controller display/keypad. (Early models may have the
fuses located in the wiring harness.) See Figure 6-41.
Another 10-amp fuse protects the battery charger.
Fuse
Label
Part Number
F1
292937
F2
223316
Controller, 10 amps
F3
223316
223316
Relay Terminal
Lead
30
14P
85
N7
86
71
87
14S
87A
NC
259391
98
TP-6196 10/09
AUTO
RUN
VBAT
Master Switch in
RUN Position
AUTO
VBAT
RUN
Master Switch in
AUTO Position
Component
Ohmmeter
Connections
Ohmmeter
Scale
Generator set
master switch
R x 100
Generator Set
Master Switch Ohmmeter Readings for
Operative Components*
Position
RUN
OFF/RESET
R x 100
AUTO
OFF/RESET
Rx1
OFF/RESET
Rx1
OFF/RESET
Rx1
OFF/RESET
R x 100
OFF/RESET
OFF/RESET
R x 100
OFF/RESET
Temperature
sensor (CTS) *
R x 1000
OFF/RESET
P1 wiring
harness
Controller fuse
and wiring
TP-6196 10/09
99
Notes
TP-6196 10/09
Section 7 Disassembly/Reassembly
This section provides instructions for the disassembly
and reassembly of the generator set alternator. Before
beginning the generator disassembly or reassembly
procedure, carefully read all safety precautions at the
beginning of this manual.
7.1 Disassembly
The disassembly procedure provides important
information to minimize disassembly time and indicates
where special configurations exist, which may require
taking notes.
1
2
tp6196
1. Screws (2 ea.)
2. Plastic caps (2 ea.) (remove to access screws)
3. Screw (1 ea.) (access from inside the enclosure)
Figure 7-2
4
5
tp6196
1. Roof
2. Roof locating pin
3. Roof screws (4 ea.)
Figure 7-1
4. Service-side door
5. Front panel (air intake end)
6. Rear panel (exhaust end)
TP-6196 10/09
2
1
tp6196
1
2
1. Screws (5 ea.)
Figure 7-3
GM29253A-F
Figure 7-4
TP-6196 10/09
3
Top View
GM29253
Figure 7-7
1.
2.
3.
4.
5.
Figure 7-5
5
1
GM29253A-F
Figure 7-6
Figure 7-8
4. Flange connection
5. Heat shield bolts
TP-6196 10/09
1
2
3
2
Front View
4
GM29253A
GM29253B-P
Figure 7-9
Side View
3
New 1.9 cm (0.75 in.)
2
3
TP5867
1.
2.
3.
4.
Brush holder
Slip ring
Brush(es)
Retainer wire
5.
6.
7.
8.
Shim
Spring
Correctly positioned brush
Incorrectly positioned brush
2
6
GM29253B-P
1.
2.
3.
4.
5.
6.
TP-6196 10/09
7.2 Reassembly
GM29253A
GM29253A
1. End bracket
2. Alternator frame vibromount
3
A-358000A-B
1. Generator adapter
2. Generator fan guard
TP-6196 10/09
tp6196
1. Brush holder
2. Brushes
3. Slip rings
TP-6196 10/09
3
GM29253C-U
3. Exhaust shield
1
1
3
5
4
ADV-7466
1.
2.
3.
4.
5.
1. Roof
2. Service-side door
3. Front panel (air intake end)
tp6196
4. Mounting pad
5. Rear panel (alternator end)
TP-6196 10/09
Page
ADV-6835A
110
ADV-6835B
111
ADV-7592
115
ADV-6835A
110
ADV-6835B
111
ADV-7592
115
ADV-7296A
112
ADV-7296B
113
DC-RET
ADV-7351
114
ADC-RES
ADV-7623:
Sheet 3
Sheet 4
116
117
Model No.
Controller
8.5RES
ADC 2100
8.5RES
ADC-RES
12RES
ADC 2100
12RES
ADC-RES
12RESL
12RESM1
DC 2200
12RESL
12RESM1
12RESNT
12TRES
(3-phase 50 Hz)
Figure 8-1
Page
GM29358
118
GM66285
121
GM29358
118
GM66285
121
GM49761
119
GM52471
120
GM63546
(sheet 3)
122
TP-6196 10/09
Figure 8-2
TP-6196 10/09
Figure 8-3
TP-6196 10/09
Figure 8-4
TP-6196 10/09
Figure 8-5
TP-6196 10/09
Figure 8-6
TP-6196 10/09
Figure 8-7
TP-6196 10/09
Figure 8-8
TP-6196 10/09
Figure 8-9
TP-6196 10/09
Figure 8-10 Point-to-Point Wiring Diagram, Single-Phase, 8.5/12RES w/ADC 2100 Controller, GM29358-E
TP-6196 10/09
Figure 8-11 Point-to-Point Wiring Diagram, Single-Phase, 12RESL/RESM1 w/DC 2200 Controller, GM49761-A
TP-6196 10/09
TP-6196 10/09
Figure 8-13 Point-to-Point Wiring Diagram, Single-Phase, 8.5/12RES w/ADC-RES Controller, GM66285TP-6196 10/09
Figure 8-14 Point-to-Point Wiring Diagram, Three-Phase, 12TRES w/ADC-RES Controller, GM63546, Sheet 3
TP-6196 10/09
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, amp
ABDC
AC
A/D
ADC
adj.
ADV
Ah
AHWT
AISI
ALOP
alt.
Al
ANSI
AO
APDC
API
approx.
AQMD
AR
AS
ASE
ASME
assy.
ASTM
ATDC
ATS
auto.
aux.
avg.
AVR
AWG
AWM
bat.
BBDC
BC
BCA
BCI
BDC
BHP
blk.
blk. htr.
BMEP
bps
br.
BTDC
Btu
Btu/min.
C
cal.
CAN
CARB
CB
cc
CCA
ccw.
CEC
cert.
cfh
ampere
after bottom dead center
alternating current
analog to digital
advanced digital control;
analog to digital converter
adjust, adjustment
advertising dimensional
drawing
amp-hour
anticipatory high water
temperature
American Iron and Steel
Institute
anticipatory low oil pressure
alternator
aluminum
American National Standards
Institute (formerly American
Standards Association, ASA)
anticipatory only
Air Pollution Control District
American Petroleum Institute
approximate, approximately
Air Quality Management District
as required, as requested
as supplied, as stated, as
suggested
American Society of Engineers
American Society of
Mechanical Engineers
assembly
American Society for Testing
Materials
after top dead center
automatic transfer switch
automatic
auxiliary
average
automatic voltage regulator
American Wire Gauge
appliance wiring material
battery
before bottom dead center
battery charger, battery
charging
battery charging alternator
Battery Council International
before dead center
brake horsepower
black (paint color), block
(engine)
block heater
brake mean effective pressure
bits per second
brass
before top dead center
British thermal unit
British thermal units per minute
Celsius, centigrade
calorie
controller area network
California Air Resources Board
circuit breaker
cubic centimeter
cold cranking amps
counterclockwise
Canadian Electrical Code
certificate, certification, certified
cubic feet per hour
TP-6196 10/09
cfm
CG
CID
CL
cm
CMOS
est.
E-Stop
etc.
exh.
ext.
F
fglass.
FHM
fl. oz.
flex.
freq.
FS
ft.
ft. lb.
ft./min.
ftp
g
ga.
gal.
gen.
genset
GFI
estimated
emergency stop
et cetera (and so forth)
exhaust
external
Fahrenheit, female
fiberglass
flat head machine (screw)
fluid ounce
flexible
frequency
full scale
foot, feet
foot pounds (torque)
feet per minute
file transfer protocol
gram
gauge (meters, wire size)
gallon
generator
generator set
ground fault interrupter
GND,
gov.
gph
gpm
gr.
GRD
gr. wt.
HxWxD
HC
HCHT
HD
HET
ground
governor
gallons per hour
gallons per minute
grade, gross
equipment ground
gross weight
height by width by depth
hex cap
high cylinder head temperature
heavy duty
high exhaust temp., high
engine temp.
hexagon
mercury (element)
hex head
hex head cap
horsepower
hour
heat shrink
housing
heating, ventilation, and air
conditioning
high water temperature
hertz (cycles per second)
integrated circuit
inside diameter, identification
International Electrotechnical
Commission
Institute of Electrical and
Electronics Engineers
improved motor starting
inch
inches of water
inches of mercury
inch pounds
incorporated
industrial
internal
internal/external
input/output
iron pipe
International Organization for
Standardization
joule
Japanese Industry Standard
hex
Hg
HH
HHC
HP
hr.
HS
hsg.
HVAC
HWT
Hz
IC
ID
IEC
IEEE
IMS
in.
in. H2O
in. Hg
in. lb.
Inc.
ind.
int.
int./ext.
I/O
IP
ISO
J
JIS
Appendix 123
k
K
kA
KB
KBus
kg
kg/cm2
kilo (1000)
kelvin
kiloampere
kilobyte (210 bytes)
Kohler communication protocol
kilogram
kilograms per square
centimeter
kgm
kilogram-meter
kg/m3
kilograms per cubic meter
kHz
kilohertz
kJ
kilojoule
km
kilometer
kOhm, k kilo-ohm
kPa
kilopascal
kph
kilometers per hour
kV
kilovolt
kVA
kilovolt ampere
kVAR
kilovolt ampere reactive
kW
kilowatt
kWh
kilowatt-hour
kWm
kilowatt mechanical
kWth
kilowatt-thermal
L
liter
LAN
local area network
L x W x H length by width by height
lb.
pound, pounds
lbm/ft3
pounds mass per cubic feet
LCB
line circuit breaker
LCD
liquid crystal display
ld. shd.
load shed
LED
light emitting diode
Lph
liters per hour
Lpm
liters per minute
LOP
low oil pressure
LP
liquefied petroleum
LPG
liquefied petroleum gas
LS
left side
Lwa
sound power level, A weighted
LWL
low water level
LWT
low water temperature
m
meter, milli (1/1000)
M
mega (106 when used with SI
units), male
m3
cubic meter
m3/hr.
cubic meters per hour
cubic meters per minute
m3/min.
mA
milliampere
man.
manual
max.
maximum
MB
megabyte (220 bytes)
MCCB
molded-case circuit breaker
MCM
one thousand circular mils
meggar
megohmmeter
MHz
megahertz
mi.
mile
mil
one one-thousandth of an inch
min.
minimum, minute
misc.
miscellaneous
MJ
megajoule
mJ
millijoule
mm
millimeter
mOhm, mmilliohm
MOhm, Mmegohm
MOV
metal oxide varistor
MPa
megapascal
mpg
miles per gallon
mph
miles per hour
MS
military standard
ms
millisecond
m/sec.
meters per second
MTBF
mean time between failure
124 Appendix
MTBO
mtg.
MTU
MW
mW
F
N, norm.
NA
nat. gas
NBS
NC
NEC
NEMA
rms
rnd.
ROM
rot.
rpm
RS
RTU
RTV
RW
SAE
scfm
SCR
s, sec.
SI
SI/EO
sil.
SN
SNMP
SPDT
SPST
spec
specs
sq.
sq. cm
sq. in.
SS
std.
stl.
tach.
TD
TDC
TDEC
TDEN
TDES
TDNE
TDOE
TDON
temp.
term.
THD
TIF
TIR
tol.
turbo.
typ.
UF
UHF
UL
UNC
UNF
univ.
US
UV
V
VAC
VAR
VDC
VFD
VGA
VHF
W
WCR
w/
w/o
wt.
xfmr
TP-6196 10/09
3
G-585
Figure 1
G-585
1.
2.
3.
4.
5.
6.
Cap screw
Entry hole types
Standard nut and SAE washer
Whiz nut or spiralock: up to 1/2 in. dia. hardware
Weld nuts: above 1/2 in. dia. hardware
Exit hole types
Figure 2
TP-6196 10/09
Appendix 125
Size
Assembled into
Aluminum
Grade 2 or 5
Torque
Measurement
Grade 2
Grade 5
Grade 8
8-32
Nm (in. lb.)
1.8
(16)
2.3
(20)
10-24
Nm (in. lb.)
2.9
(26)
3.6
(32)
10-32
Nm (in. lb.)
2.9
(26)
3.6
(32)
1/4-20
Nm (in. lb.)
6.8
(60)
10.8
(96)
14.9
(132)
1/4-28
Nm (in. lb.)
8.1
(72)
12.2
(108)
16.3
(144)
5/16-18
Nm (in. lb.)
13.6
(120)
21.7
(192)
29.8
(264)
5/16-24
Nm (in. lb.)
14.9
(132)
23.1
(204)
32.5
(288)
3/8-16
Nm (ft. lb.)
24.0
(18)
38.0
(28)
53.0
(39)
3/8-24
Nm (ft. lb.)
27.0
(20)
42.0
(31)
60.0
(44)
7/16-14
Nm (ft. lb.)
39.0
(29)
60.0
(44)
85.0
(63)
7/16-20
Nm (ft. lb.)
43.0
(32)
68.0
(50)
95.0
(70)
1/2-13
Nm (ft. lb.)
60.0
(44)
92.0
(68)
130.0
(96)
1/2-20
Nm (ft. lb.)
66.0
(49)
103.0
(76)
146.0
(108)
9/16-12
Nm (ft. lb.)
81.0
(60)
133.0
(98)
187.0
(138)
9/16-18
Nm (ft. lb.)
91.0
(67)
148.0
(109)
209.0
(154)
5/8-11
Nm (ft. lb.)
113.0
(83)
183.0
(135)
259.0
(191)
5/8-18
Nm (ft. lb.)
128.0
(94)
208.0
(153)
293.0
(216)
3/4-10
Nm (ft. lb.)
199.0
(147)
325.0
(240)
458.0
(338)
3/4-16
Nm (ft. lb.)
222.0
(164)
363.0
(268)
513.0
(378)
1-8
Nm (ft. lb.)
259.0
(191)
721.0
(532)
1109.0
(818)
1-12
Nm (ft. lb.)
283.0
(209)
789.0
(582)
1214.0
(895)
See Note 3
x 1.00
6.2
(4.6)
9.5
(7)
13.6
(10)
M8
x 1.25
15.0
(11)
23.0
(17)
33.0
(24)
M8
x 1.00
16.0
(11)
24.0
(18)
34.0
(25)
M10 x 1.50
30.0
(22)
45.0
(34)
65.0
(48)
M10 x 1.25
31.0
(23)
47.0
(35)
68.0
(50)
M12 x 1.75
53.0
(39)
80.0
(59)
115.0
(85)
M12 x 1.50
56.0
(41)
85.0
(63)
122.0
(90)
M14 x 2.00
83.0
(61)
126.0
(93)
180.0
(133)
M14 x 1.50
87.0
(64)
133.0
(98)
190.0
(140)
M16 x 2.00
127.0
(94)
194.0
(143)
278.0
(205)
M16 x 1.50
132.0
(97)
201.0
(148)
287.0
(212)
M18 x 2.50
179.0
(132)
273.0
(201)
390.0
(288)
M18 x 1.50
189.0
(140)
289.0
(213)
413.0
(305)
See Note 3
Notes:
1. The torque values above are general guidelines. Always use the torque values specified in the service manuals and/or assembly
drawings when they differ from the above torque values.
2. The torque values above are based on new plated threads. Increase torque values by 15% if non-plated threads are used.
3. Hardware threaded into aluminum must have either two diameters of thread engagement or a 30% or more reduction in the torque to
prevent stripped threads.
4. Torque values are calculated as equivalent stress loading on American hardware with an approximate preload of 90% of the yield strength
and a friction coefficient of 0.125.
126 Appendix
TP-6196 10/09
Nuts
Hardness Grades
Head Styles
Nut Styles
American Standard
Hex Head
Grade 2
Lock or Elastic
Grade 5
Square
Grade 8
Cap or Acorn
Pan Head
Wing
Metric
Washers
5.8
Washer Styles
Plain
Stud
Spring or Wave
Drive Styles
Number stamped on
hardware; 5.8 shown
Hex
Internal Tooth Lock
Hex and Slotted
Internal-External Tooth Lock
Phillips#
Slotted
Hex Socket
Allen$ head screw is a trademark of Holo-Krome Co.
Phillips# screw is a registered trademark of Phillips Screw Company.
Sample Dimensions
American Standard (Screws, Bolts, Studs, and Nuts)
1/4-20 x 1
Length In Inches (Screws and Bolts)
Plain Washers
9/32 x 5/8 x 1/16
Thickness
External Dimension
Internal Dimension
Lock Washers
5/8
Internal Dimension
TP-6196 10/09
Appendix 127
American Standard
Part No.
Dimensions
Hex Head Bolts (Grade 5)
Part No.
Dimensions
Hex Head Bolts, cont.
Part No.
X-465-17
X-465-6
X-465-2
X-465-16
X-465-18
X-465-7
X-465-8
X-465-9
X-465-10
X-465-11
X-465-12
X-465-14
X-465-21
X-465-25
X-465-20
1/4-20 x .38
1/4-20 x .50
1/4-20 x .62
1/4-20 x .75
1/4-20 x .88
1/4-20 x 1.00
1/4-20 x 1.25
1/4-20 x 1.50
1/4-20 x 1.75
1/4-20 x 2.00
1/4-20 x 2.25
1/4-20 x 2.75
1/4-20 x 5.00
1/4-28 x .38
1/4-28 x 1.00
X-6238-14
X-6238-16
X-6238-21
X-6238-22
3/8-24 x .75
3/8-24 x 1.25
3/8-24 x 4.00
3/8-24 x 4.50
X-6009-1
1-8
Standard
X-6024-5
X-6024-2
X-6024-8
X-6024-3
X-6024-4
X-6024-11
X-6024-12
7/16-14 x .75
7/16-14 x 1.00
7/16-14 x 1.25
7/16-14 x 1.50
7/16-14 x 2.00
7/16-14 x 2.75
7/16-14 x 6.50
X-6210-3
X-6210-4
X-6210-5
X-6210-1
6-32
8-32
10-24
10-32
Whiz
Whiz
Whiz
Whiz
X-125-33
X-125-23
X-125-3
X-125-31
X-125-5
X-125-24
X-125-34
X-125-25
X-125-26
230578
X-125-29
X-125-27
X-125-28
X-125-22
X-125-32
X-125-35
X-125-36
X-125-40
5/16-18 x .50
5/16-18 x .62
5/16-18 x .75
5/16-18 x .88
5/16-18 x 1.00
5/16-18 x 1.25
5/16-18 x 1.50
5/16-18 x 1.75
5/16-18 x 2.00
5/16-18 x 2.25
5/16-18 x 2.50
5/16-18 x 2.75
5/16-18 x 3.00
5/16-18 x 4.50
5/16-18 x 5.00
5/16-18 x 5.50
5/16-18 x 6.00
5/16-18 x 6.50
X-129-15
X-129-17
X-129-18
X-129-19
X-129-20
X-129-21
X-129-22
X-129-23
X-129-24
X-129-25
X-129-27
X-129-29
X-129-30
X-463-9
X-129-44
1/2-13 x .75
1/2-13 x 1.00
1/2-13 x 1.25
1/2-13 x 1.50
1/2-13 x 1.75
1/2-13 x 2.00
1/2-13 x 2.25
1/2-13 x 2.50
1/2-13 x 2.75
1/2-13 x 3.00
1/2-13 x 3.50
1/2-13 x 4.00
1/2-13 x 4.50
1/2-13 x 5.50
1/2-13 x 6.00
X-6210-2
X-6210-6
X-6210-7
X-6210-8
X-6210-9
X-6210-10
X-6210-11
X-6210-12
X-6210-15
X-6210-14
1/4-20
1/4-28
5/16-18
5/16-24
3/8-16
3/8-24
7/16-14
1/2-13
7/16-20
1/2-20
Spiralock
Spiralock
Spiralock
Spiralock
Spiralock
Spiralock
Spiralock
Spiralock
Spiralock
Spiralock
X-85-3
X-88-12
X-89-2
5/8-11
3/4-10
1/2-20
Standard
Standard
Standard
X-129-51
X-129-45
X-129-52
1/2-20 x .75
1/2-20 x 1.25
1/2-20 x 1.50
X-125-43
X-125-44
X-125-30
X-125-39
X-125-38
5/16-24 x 1.75
5/16-24 x 2.50
5/16-24 x .75
5/16-24 x 2.00
5/16-24 x 2.75
X-6238-2
X-6238-10
X-6238-3
X-6238-11
X-6238-4
X-6238-5
X-6238-1
X-6238-6
X-6238-17
X-6238-7
X-6238-8
X-6238-9
X-6238-19
X-6238-12
X-6238-20
X-6238-13
X-6238-18
X-6238-25
3/8-16 x .62
3/8-16 x .75
3/8-16 x .88
3/8-16 x 1.00
3/8-16 x 1.25
3/8-16 x 1.50
3/8-16 x 1.75
3/8-16 x 2.00
3/8-16 x 2.25
3/8-16 x 2.50
3/8-16 x 2.75
3/8-16 x 3.00
3/8-16 x 3.25
3/8-16 x 3.50
3/8-16 x 3.75
3/8-16 x 4.50
3/8-16 x 5.50
3/8-16 x 6.50
X-6021-3
X-6021-4
X-6021-2
X-6021-1
273049
X-6021-5
X-6021-6
X-6021-7
X-6021-12
X-6021-11
X-6021-10
5/8-11 x 1.00
5/8-11 x 1.25
5/8-11 x 1.50
5/8-11 x 1.75
5/8-11 x 2.00
5/8-11 x 2.25
5/8-11 x 2.50
5/8-11 x 2.75
5/8-11 x 3.75
5/8-11 x 4.50
5/8-11 x 6.00
X-6021-9
5/8-18 x 2.50
X-6239-1
X-6239-8
X-6239-2
X-6239-3
X-6239-4
X-6239-5
X-6239-6
3/4-10 x 1.00
3/4-10 x 1.25
3/4-10 x 1.50
3/4-10 x 2.00
3/4-10 x 2.50
3/4-10 x 3.00
3/4-10 x 3.50
X-792-1
X-792-5
X-792-8
1-8 x 2.25
1-8 x 3.00
1-8 x 5.00
128 Appendix
Dimensions
Type
Hex Nuts
Washers
Part No.
ID
X-25-46
.125
X-25-9
.156
X-25-48
.188
X-25-36
.219
X-25-40
.281
X-25-85
.344
X-25-37
.406
X-25-34
.469
X-25-26
.531
X-25-15
.656
X-25-29
.812
X-25-127 1.062
OD
.250
.375
.438
.500
.625
.687
.812
.922
1.062
1.312
1.469
2.000
Bolt/
Thick. Screw
.022
.049
.049
.049
.065
.065
.065
.065
.095
.095
.134
.134
#4
#6
#8
#10
1/4
5/16
3/8
7/16
1/2
5/8
3/4
1
TP-6196 10/09
Metric
Hex head bolts are hardness grade 8.8 unless noted.
Part No.
Dimensions
Hex Head Bolts (Partial Thread)
M931-05055-60
M931-06040-60
M931-06055-60
M931-06060-60
M931-06060-SS
M931-06070-60
M931-06070-SS
M931-06075-60
M931-06090-60
M931-06145-60
M931-06150-60
M5-0.80 x 55
M6-1.00 x 40
M6-1.00 x 55
M6-1.00 x 60
M6-1.00 x 60
M6-1.00 x 70
M6-1.00 x 70
M6-1.00 x 75
M6-1.00 x 90
M6-1.00 x 145
M6-1.00 x 150
M931-08035-60
M931-08040-60
M931-08045-60
M931-08050-60
M931-08055-60
M931-08055-82
M931-08060-60
M931-08070-60
M931-08070-82
M931-08075-60
M931-08080-60
M931-08090-60
M931-08095-60
M931-08100-60
M931-08110-60
M931-08120-60
M931-08130-60
M931-08140-60
M931-08150-60
M931-08200-60
M8-1.25 x 35
M8-1.25 x 40
M8-1.25 x 45
M8-1.25 x 50
M8-1.25 x 55
M8-1.25 x 55*
M8-1.25 x 60
M8-1.25 x 70
M8-1.25 x 70*
M8-1.25 x 75
M8-1.25 x 80
M8-1.25 x 90
M8-1.25 x 95
M8-1.25 x 100
M8-1.25 x 110
M8-1.25 x 120
M8-1.25 x 130
M8-1.25 x 140
M8-1.25 x 150
M8-1.25 x 200
M931-10040-82
M931-10040-60
M931-10045-60
M931-10050-60
M931-10050-82
M931-10055-60
M931-10060-60
M931-10065-60
M931-10070-60
M931-10080-60
M931-10080-82
M931-10090-60
M931-10090-82
M931-10100-60
M931-10110-60
M931-10120-60
M931-10130-60
M931-10140-60
M931-10180-60
M931-10235-60
M931-10260-60
M960-10330-60
M10-1.25 x 40*
M10-1.50 x 40
M10-1.50 x 45
M10-1.50 x 50
M10-1.25 x 50*
M10-1.50 x 55
M10-1.50 x 60
M10-1.50 x 65
M10-1.50 x 70
M10-1.50 x 80
M10-1.25 x 80*
M10-1.50 x 90
M10-1.50 x 90*
M10-1.50 x 100
M10-1.50 x 110
M10-1.50 x 120
M10-1.50 x 130
M10-1.50 x 140
M10-1.50 x 180
M10-1.50 x 235
M10-1.50 x 260
M10-1.25 x 330
M931-12045-60
M960-12050-60
M960-12050-82
M931-12050-60
M931-12050-82
M931-12055-60
M931-12060-60
M931-12060-82
M931-12065-60
M931-12075-60
M931-12080-60
M931-12090-60
M931-12100-60
M931-12110-60
M12-1.75 x 45
M12-1.25 x 50
M12-1.25 x 50*
M12-1.75 x 50
M12-1.75 x 50*
M12-1.75 x 55
M12-1.75 x 60
M12-1.75 x 60*
M12-1.75 x 65
M12-1.75 x 75
M12-1.75 x 80
M12-1.75 x 90
M12-1.75 x 100
M12-1.75 x 110
Part No.
Dimensions
Hex Head Bolts (Partial Thread),
continued
Part No.
Dimensions
Hex Head Bolts (Full Thread),
continued
M960-16090-60
M931-16090-60
M931-16100-60
M931-16100-82
M931-16120-60
M931-16150-60
M16-1.50 x 90
M16-2.00 x 90
M16-2.00 x 100
M16-2.00 x 100*
M16-2.00 x 120
M16-2.00 x 150
M931-20065-60
M931-20090-60
M931-20100-60
M931-20120-60
M931-20140-60
M931-20160-60
M20-2.50 x 65
M20-2.50 x 90
M20-2.50 x 100
M20-2.50 x 120
M20-2.50 x 140
M20-2.50 x 160
M933-12016-60
M933-12020-60
M961-12020-60F
M933-12025-60
M933-12025-82
M961-12030-60
M933-12030-82
M961-12030-82F
M933-12030-60
M933-12035-60
M961-12040-82
M933-12040-60
M933-12040-82
M12-1.75 x 16
M12-1.75 x 20
M12-1.50 x 20
M12-1.75 x 25
M12-1.75 x 25*
M12-1.25 x 30
M12-1.75 x 30*
M12-1.50 x 30*
M12-1.75 x 30
M12-1.75 x 35
M12-1.25 x 40*
M12-1.75 x 40
M12-1.75 x 40*
M931-22090-60
M931-22120-60
M931-22160-60
M22-2.50 x 90
M22-2.50 x 120
M22-2.50 x 160
M961-14025-60
M933-14025-60
M961-14050-82
M14-1.50 x 25
M14-2.00 x 25
M14-1.50 x 50*
M931-24090-60
M931-24120-60
M931-24160-60
M931-24200-60
M24-3.00 x 90
M24-3.00 x 120
M24-3.00 x 160
M24-3.00 x 200
M961-16025-60
M933-16025-60
M961-16030-82
M933-16030-82
M933-16035-60
M961-16040-60
M933-16040-60
M961-16045-82
M933-16045-82
M933-16050-60
M933-16050-82
M933-16060-60
M933-16070-60
M16-1.50 x 25
M16-2.00 x 25
M16-1.50 x 30*
M16-2.00 x 30*
M16-2.00 x 35
M16-1.50 x 40
M16-2.00 x 40
M16-1.50 x 45*
M16-2.00 x 45*
M16-2.00 x 50
M16-2.00 x 50*
M16-2.00 x 60
M16-2.00 x 70
M933-18035-60
M933-18050-60
M933-18060-60
M18-2.50 x 35
M18-2.50 x 50
M18-2.50 x 60
M933-20050-60
M933-20055-60
M20-2.50 x 50
M20-2.50 x 55
M933-24060-60
M933-24065-60
M933-24070-60
M24-3.00 x 60
M24-3.00 x 65
M24-3.00 x 70
M4-0.70 x 6
M933-05030-60
M933-05035-60
M933-05050-60
M5-0.80 x 30
M5-0.80 x 35
M5-0.80 x 50
M933-06010-60
M933-06012-60
M933-06014-60
M933-06016-60
M933-06020-60
M933-06025-60
M933-06030-60
M933-06040-60
M933-06050-60
M6-1.00 x 10
M6-1.00 x 12
M6-1.00 x 14
M6-1.00 x 16
M6-1.00 x 20
M6-1.00 x 25
M6-1.00 x 30
M6-1.00 x 40
M6-1.00 x 50
M933-07025-60
M7-1.00 x 25
M933-08010-60
M933-08012-60
M933-08016-60
M933-08020-60
M933-08025-60
M933-08030-60
M933-08030-82
M8-1.25 x 10
M8-1.25 x 12
M8-1.25 x 16
M8-1.25 x 20
M8-1.25 x 25
M8-1.25 x 30
M8-1.25 x 30*
M933-10012-60
M961-10020-60
M933-10020-60
M933-10025-60
M961-10025-60
M933-10025-82
M961-10030-60
M933-10030-60
M933-10030-82
M961-10035-60
M933-10035-60
M933-10035-82
M961-10040-60
M10-1.50 x 12
M10-1.25 x 20
M10-1.50 x 20
M10-1.50 x 25
M10-1.25 x 25
M10-1.50 x 25*
M10-1.25 x 30
M10-1.50 x 30
M10-1.50 x 30*
M10-1.25 x 35
M10-1.50 x 35
M10-1.50 x 35*
M10-1.25 x 40
M4-0.70 x 10
M4-0.70 x 16
M4-0.70 x 20
M4-0.70 x 50
M4-0.70 x 100
M7985A-05010-20
M7985A-05012-20
M7985A-05016-20
M7985A-05020-20
M7985A-05025-20
M7985A-05030-20
M7985A-05080-20
M7985A-05100-20
M5-0.80 x 10
M5-0.80 x 12
M5-0.80 x 16
M5-0.80 x 20
M5-0.80 x 25
M5-0.80 x 30
M5-0.80 x 80
M5-0.80 x 100
M4-0.70 x 12
M965A-05012-SS
M965A-05016-20
M965A-06012-20
M5-0.80 x 12
M5-0.80 x 16
M6-1.00 x 12
TP-6196 10/09
Appendix 129
Metric, continued
Part No.
Hex Nuts
Dimensions
Type
M934-03-50
M3-0.50
Standard
M934-04-50
M934-04-B
M4-0.70
M4-0.70
Standard
Brass
M934-05-50
M5-0.80
Standard
M934-06-60
M934-06-64
M6923-06-80
M982-06-80
M6-1.00
M6-1.00
M6-1.00
M6-1.00
Standard
Std. (green)
Spiralock
Elastic Stop
M934-08-60
M6923-08-80
M982-08-80
M8-1.25
M8-1.25
M8-1.25
Standard
Spiralock
Elastic Stop
M934-10-60
M934-10-60F
M6923-10-80
M6923-10-62
M982-10-80
M10-1.50
M10-1.25
M10-1.50
M10-1.50
M10-1.50
Standard
Standard
Spiralock
Spiralock!
Elastic Stop
M934-12-60
M934-12-60F
M6923-12-80
M982-12-80
M12-1.75
M12-1.25
M12-1.75
M12-1.75
Standard
Standard
Spiralock
Elastic Stop
M982-14-60
M14-2.00
Elastic Stop
M6923-16-80
M982-16-80
M16-2.00
M16-2.00
Spiralock
Elastic Stop
M934-18-80
M982-18-60
M18-2.5
M18-2.50
Standard
Elastic Stop
M934-20-80
M982-20-80
M20-2.50
M20-2.50
Standard
Elastic Stop
M934-22-60
M22-2.50
Standard
M934-24-80
M982-24-60
M24-3.00
M24-3.00
Standard
Elastic Stop
M934-30-80
M30-3.50
Standard
Washers
Part No.
M125A-03-80
M125A-04-80
M125A-05-80
M125A-06-80
M125A-08-80
M125A-10-80
M125A-12-80
M125A-14-80
M125A-16-80
M125A-18-80
M125A-20-80
M125A-24-80
ID
3.2
4.3
5.3
6.4
8.4
10.5
13.0
15.0
17.0
19.0
21.0
25.0
Bolt/
OD Thick. Screw
7.0
9.0
10.0
12.0
16.0
20.0
24.0
28.0
30.0
34.0
37.0
44.0
0.5
0.8
1.0
1.6
1.6
2.0
2.5
2.5
3.0
3.0
3.0
4.0
M3
M4
M5
M6
M8
M10
M12
M14
M16
M18
M20
M24
130 Appendix
TP-6196 10/09
TP-6196 10/09a
! 2004, 2008, 2009 by Kohler Co. All rights reserved.